Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Busbar Protection
Instruction Manual
Preface
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Documentation for equipment ordered from NR is dispatched separately from manufactured goods
and may not be received at the same time. Therefore, this guide is provided to ensure that printed
information normally present on equipment is fully understood by the recipient.
Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
Preface
DANGER!
It means that death, severe personal injury, or considerable equipment damage will occur if safety
precautions are disregarded.
WARNING!
It means that death, severe personal, or considerable equipment damage could occur if safety
precautions are disregarded.
CAUTION!
It means that light personal injury or equipment damage may occur if safety precautions are
disregarded. This particularly applies to damage to the device and to resulting damage of the
protected equipment.
WARNING!
The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.
WARNING!
During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.
In particular, the general facility and safety regulations for work with high-voltage equipment must
be observed. Noncompliance may result in death, injury, or significant equipment damage.
DANGER!
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING!
Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous
ii
Preface
Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.
CAUTION!
Earth
Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.
Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.
External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
Connection cable
Copyright
Version: R1.02
P/N: EN_YJBH5301.0086.0003
Tel: +86-25-87178185,
Fax: +86-25-87178208
Email: NR_TechSupport@nari-relays.com
We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination
to third parties is strictly forbidden except where expressly authorized.
The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.
We reserve the rights to make technical improvements without notice.
iii
Preface
Documentation Structure
The manual provides a functional and technical description of this relay and a comprehensive set
of instructions for the relays use and application.
All contents provided by this manual are summarized as below:
1 Introduction
Briefly introduce the application, functions and features about this relay.
2 Technical Data
Introduce the technical data about this relay, such as electrical specifications, mechanical
specifications, ambient temperature and humidity range, communication port parameters, type
tests, setting ranges and accuracy limits and the certifications that our products have passed.
3 Operation Theory
Introduce a comprehensive and detailed functional description of all protective elements.
4 Supervision
Introduce the automatic self-supervision function of this relay.
6 Hardware
Introduce the main function carried out by each plug-in module of this relay and providing the
definition of pins of each plug-in module.
7 Settings
List settings including protection settings, system settings, communication settings, label settings,
VEBI settings and etc., and some notes about the setting application.
9 Communication
Introduce the communication port and protocol which this relay can support, IEC60970-5-103,
IEC61850 and DNP3.0 protocols are introduced in details.
10 Installation
Introduce the recommendations on unpacking, handling, inspection and storage of this relay. A
guide to the mechanical and electrical installation of this relay is also provided, incorporating
iv
Preface
11 Commissioning
Introduce how to commission this relay, comprising checks on the calibration and functionality of
this relay.
12 Maintenance
A general maintenance policy for this relay is outlined.
Preface
vi
1 Introduction
1 Introduction
Table of Contents
1 Introduction..................................................................................... 1-a
1.1 Application....................................................................................................... 1-1
1.2 Function ........................................................................................................... 1-2
1.3 Feature ............................................................................................................. 1-2
1.4 Abbreviation .................................................................................................... 1-3
1-a
Date: 2012-08-31
1 Introduction
1-b
Date: 2012-08-31
1 Introduction
1.1 Application
PCS-915A is a numerical busbar differential protection intended to be used for protecting and
monitoring of double busbars with bus coupler arrangement, single busbar arrangement and
single busbar with single bus section arrangement of various voltage levels. It is capable to protect
up to 25 bays including bus coupler and bus section (bay 01 is connected with bus coupler (BC),
the rest bays are taken as feeder 01~24).
PCS-915A utilizes NRs innovative hardware platform supporting both conventional CT/VT and
electronic current and voltage transformer (ECVT). It is compliant to several communication
protocols, such as IEC60870-5-103, IEC61850 and DNP3.0 protocol.
PCS-915
87B
50BF
FR
VT1
BB1
*
VT2
BC
BB2
Note!
The bay label of displayed alarm signals, tripping signals, binary input signals, settings and
sampled values related with each feeder and busbar will change with the corresponding
description settings. Please refer to Section 7.8 for details.
For example, if the description setting of feeder 01 i.e. [NameDef_Bay02] is set as Fdr01,
the three-phase initiating contact of BFP for feeder 01 is [BI_BFI_Fdr01]. If
[NameDef_Bay02] is set as 0001, the three-phase initiating contact of BFP for feeder 01
is [BI_BFI_0001].
In this instruction manual, only take the default settings in Table 7.8-1 as an example to
introduce.
1-1
Date: 2012-08-31
1 Introduction
1.2 Function
PCS-915 provides the following functions
1.
Protection function
2.
Auxiliary protection
1.3 Feature
1.
1-2
Date: 2012-08-31
1 Introduction
Less than 20ms typical trip time for busbar differential protection
2.
Time synchronization
Receiving PPS (pulse per second) and PPM (pulse per minute) via external contact
3.
32 latest fault waveforms (The file format of disturbance recorder is compatible with the
international COMTRADE file)
4.
Communication
2 rear RS-485 communication ports supporting with IEC 60870-5-103 protocol, ModBus
protocol or DNP3.0 protocol
4 Ethernet ports at most (depend on the chosen CPU type) supporting with IEC 60870-5-103
protocol or IEC 61850-8-1 protocol
1.4 Abbreviation
Symbol
Description
FD
Fault detector
BBx
1-3
Date: 2012-08-31
1 Introduction
Symbol
Description
feeder xx
VCE
BBP
BFP
BFI
EFP
PD
Pole disagreement
SAS
RTU
CT
Current transformer
VT
Voltage transformer
DPFC
1-4
Date: 2012-08-31
2 Technical Data
2 Technical Data
Table of Contents
2 Technical Data................................................................................. 2-a
2.1 Electrical Specifications ................................................................................. 2-1
2.1.1 Alternating Analog Current................................................................................................... 2-1
2.1.2 Alternating Analog Voltage................................................................................................... 2-1
2.1.3 Power Supply....................................................................................................................... 2-1
2.1.4 Binary Input .......................................................................................................................... 2-1
2.1.5 Binary Output ....................................................................................................................... 2-2
2-a
Date: 2013-06-03
2 Technical Data
2-b
Date: 2013-06-03
2 Technical Data
ABC
505Hz, 605Hz
1A
Linear to
0.05In~40In
5A
Thermal withstand
-continuously
4In
-for 10s
30In
-for 1s
100In
250In
Burden
Accuracy
0.5%In
ABC
505Hz, 605Hz
100V~130V
Linear to
1V~170V
Thermal withstand
-continuously
200V
-10s
260V
-1s
300V
Burden at rated
Accuracy
0.5%Un
IEC 60255-11:2008
Rated Voltage
110Vdc/125Vdc, 220Vdc/250Vdc
Operating Range
Burden
Quiescent condition
<40W
Operating condition
<60W
24V
48V
110V
125V
220V
250V
1.2mA
2.4mA
1.1mA
1.25mA
2.2mA
2.5mA
Pickup voltage
Dropoff voltage
2-1
Date: 2013-06-03
2 Technical Data
Maximum permissible voltage
Withstand voltage
-continously
Response time for logic input
Trip output
Signal output
Output mode
8A@380Vac
5A@250Vdc
8A@250Vdc
Pickup time
<10ms
Dropoff time
<5ms
<8ms
0.65A@48Vdc
1.20A@48Vdc
0.30A@110Vdc
0.50A@110Vdc
0.15A@220Vdc
0.25A@220Vdc
Electrical Life
10000 times
10000 times
Burden
300mW
240mW
Making capacity
2000VA
3040VA
Continuous carry
380Vac
250Vdc
1000V RMS for 1min
6A@3s
10A@3S
15A@0.5s
20A@0.5S
Flush mounted
Housing color
Silver grey
Approx. 30kg
Housing material
Aluminum
Location of terminal
Device structure
Protection class
Standard
IEC 60225-1:2009
Front side
Other sides
IP30
IP20
IEC 60225-1:2009
Operating temperature
2-2
Date: 2013-06-03
2 Technical Data
C)
Transport and storage temperature
range
-40C to +70C
Permissible humidity
Pollution degree
Altitude
<3000m
Protocol
IEC 60870-5-103:1997
Maximal capacity
32
Transmission distance
<500m
Safety level
Twisted pair
RJ-45
Transmission rate
100Mbits/s
Transmission standard
100Base-TX
Transmission distance
<100m
Protocol
Safety level
Connector type
ST, SC
Fibre type
Multi mode
Transmission distance
<2km
Wave length
1310nm
Transmission power
Min. -20.0dBm
Min. -30.0dBm
Margin
Min +3.0dB
Connector type
LC
Fibre type
Multi mode
Transmission distance
<2km
2-3
Date: 2013-06-03
2 Technical Data
Wave length
1310nm
Transmission power
Min. -20.0dBm
Min. -30.0dBm
Margin
Min +3.0dB
Connector type
ST
Fibre type
Multi mode
Wave length
820nm
Min. -25.0dBm
Margin
Min +3.0dB
RS-232
Baud Rate
Printer type
Safety level
RS-485
Transmission distance
<500m
Maximal capacity
32
Timing standard
PPS, IRIG-B
Safety level
IEC60068-2-1:2007
IEC60068-2-2:2007
IEC60068-2-30:2005
IEC 60255-27:2005
Dielectric tests
Standard
IEC 60255-5:2000
2-4
Date: 2013-06-03
2 Technical Data
Overvoltage category
Insulation
resistance
measurements
Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
IEC 60255-22-4:2008
Conducted
RF
Electromagnetic
Disturbance
IEC 60255-22-6:2001
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150
kHz~80MHz
IEC 61000-4-8:2001
Immunity
IEC 61000-4-9:2001
class V, 6.4/16s, 1000A/m for 3s
IEC 61000-4-10:2001
immunity
IEC60255-11: 2008
- Voltage dips
2-5
Date: 2013-06-03
2 Technical Data
2.6 Certifications
ISO9001:2008
ISO14001:2004
OHSAS18001:2007
ISO10012:2003
CMMI L4
Range
Accuracy
Phase range
0~ 360
0.5% or 1
Frequency
fn3Hz
0.01Hz
0.05 ~ 40.00In
Voltage
0.05 ~ 1.20Un
3s/day
1ms
Recording position
1ms
Potential-free contact
Resolution of SOE
1ms
2-6
Date: 2013-06-03
2 Technical Data
0.05In~20.00In
0.05In~20.00In
0.05In~20.00In
0.000~10.000s
1%xSetting + 40ms
0~20.00In
0~20.00In
0.000~10.000s
1%xSetting + 40ms
0~20.00In
0.010~10.000s
1%xSetting + 40ms
0~20.00In
2-7
Date: 2013-06-03
2 Technical Data
Residual current setting range
0~20.00In
0~20.00In
0.000~10.000s
1%xSetting + 40ms
01.732U2n
0U2n
0U2n
2-8
Date: 2013-06-03
3 Operation Theory
3 Operation Theory
Table of Contents
3 Operation Theory ............................................................................ 3-a
3.1 Overview .......................................................................................................... 3-1
3.2 Busbar Differential Protection ....................................................................... 3-2
3.2.1 Fault detector (FD) element................................................................................................. 3-3
3.2.2 Percentage differential element ........................................................................................... 3-4
3.2.3 Voltage controlled element of busbar differential protection (VCE_BBP) ........................... 3-6
3.2.4 Faulty busbar zone discrimination ....................................................................................... 3-7
3.2.5 Backup busbar differential elements ................................................................................... 3-8
3.2.6 Detection of CT saturation ................................................................................................... 3-8
3.2.7 External Block Signal ........................................................................................................... 3-9
3.2.8 Logic scheme....................................................................................................................... 3-9
3-a
3 Operation Theory
List of Figures
Figure 3.1-1 Double-busbar arrangement................................................................................. 3-2
Figure 3.2-1 Sketch diagram of double busbars with one bus section arrangement ......... 3-2
Figure 3.2-2 Operation characteristic of steady-state percentage restraint differential
element .................................................................................................................................. 3-5
Figure 3.2-3 Waveform of CT saturation during external fault ............................................... 3-9
Figure 3.2-4 Logic scheme of busbar differential protection ............................................... 3-10
Figure 3.3-1 Logic scheme of SOTF protection ..................................................................... 3-12
Figure 3.3-2 Logic scheme of overcurrent protection........................................................... 3-13
Figure 3.3-3 The logic scheme of BFP .................................................................................... 3-14
Figure 3.3-4 The logic scheme of end zone fault protection ................................................ 3-15
Figure 3.3-5 The logic scheme of pole discrepancy protection ........................................... 3-16
Figure 3.4-1 The logic scheme of BFP (for the bay that main transformer is not connected)
.............................................................................................................................................. 3-18
Figure 3.4-2 The logic scheme of BFP (for the bay that main transformer is connected) 3-19
Figure 3.8-1 BC breaker substituting through BB2 ............................................................... 3-22
Figure 3.8-2 BC breaker substituting through BB1 ............................................................... 3-23
3-b
3 Operation Theory
3.1 Overview
PCS-915 provides busbar differential protection (BBP), bus coupler/section protection (includes
overcurrent protection, switch-onto-fault protection, pole disagreement protection, end zone fault
protection and breaker failure protection), feeder breaker failure protection, CT circuit supervision
and VT circuit supervision.
The device can support several busbar arrangements, such as double-busbar arrangement,
single-busbar arrangement and single busbar with single bus section arrangement. The switch
method of each busbar arrangement is listed as below:
System settings
En_SingleBB
En_SingleBB_with_SingleBS
Double-busbar
Single-busbar
Busbar arrangement
Please refer to Section 7.1 about detailed description of each system setting. For single busbar
with bus section arrangement, the system setting [Cfg_DS_BBx] (x=1, 2) is used to indicate which
busbar zone the feeder is connected to.
The device has 2 plug-in modules (protection DSP module and fault detector DSP module) to
perform calculation. The protection DSP module is responsible for calculation of protection
elements, and fault detector DSP module is responsible for calculation of fault detectors. Any fault
detector of fault detector DSP module picks up to provide positive supply of output relays. The
relays will trip only if the fault detector and the corresponding protection element operate
simultaneously. On the premise of 24 samples per cycle, all data measurement, calculation and
logic discrimination can be processed within one sampling period. The event recording and
protection logic calculation are completed simultaneously.
The following figure shows double busbars arrangement and application mode.
3-1
3 Operation Theory
Panel A
PCS-915
VT1
BB1
*
VT2
BC
BB2
Discriminative
zone No.1
Discriminative
zone No.2
Check zone
BB1
*
BC
BB2
Figure 3.2-1 Sketch diagram of double busbars with one bus section arrangement
3-2
3 Operation Theory
Note!
The protective device only identifies the physical position of busbar, ignoring the number of
busbar, takes the busbar arrangement in Figure 3.2-1 as an example, the protective device
will refer the busbar of which the polarity of BC CT is towards as BB1.
The primary protection of PCS-915 is phase-segregated percentage restraint differential
protection. The differential circuits include check zone differential circuit and discriminating zone
differential circuits of each busbar zone. The check zone differential element is used to distinguish
between internal and external fault of the overall busbar system, it measures the current from all
the circuits connected to the busbar system except BC and BS. The discriminating zone
differential elements are used to select faulty zone by measuring the current of all the circuits
connected to individual zones of the busbar system separated by BC and BS.
Discriminating zone No.1 is defined as discriminating differential element of BB1. Discriminating
zone No.2 is defined as discriminating differential element of BB2.
3.2.1 Fault detector (FD) element
PCS-915 provides three independent FD elements for busbar differential protection, which are
DPFC voltage FD element, DPFC current FD element and differential current FD element. If any of
these three elements picks up, the positive supply to the output relays is then available and wait
for the tripping signal from busbar differential protection. The fault detector output signal will last
for 500ms after the corresponding fault detector element drop off.
1.
When DPFC voltage of any phase of any busbar is larger than the threshold, DPFC voltage FD
element picks up, the operating criterion is:
u>UFloat+0.05Un
Equation 3.2-1
Where:
u: Instantaneous value of phase-to-phase DPFC voltage
UFloat: Float threshold value, automatically varied with the gradually voltage changing
0.05Un: Fixed threshold value, Un is the rated secondary phase-to-ground voltage.
If voltage is not sampled or VT circuit failure is detected, DPFC voltage FD element will quit
automatically.
2.
If DPFC check zone restraint current is larger than the threshold, DPFC current fault detector
element will operate, the operating criterion is:
si>SIFloat+0.5In
Equation 3.2-2
3-3
3 Operation Theory
Where:
si: Instantaneous value of DPFC check zone restraint current of any phase (scalar sum of current
change of all circuits/bays for check zone)
SIFloat: Float threshold value, automatically varied with the gradually current changing
0.5In: Fixed threshold value, In is the rated secondary current of reference CT.
3.
When any phase of the check zone differential current is larger than the setting, this element will
operate. The operating criterion is:
ID> [I_Pkp_Pcnt_BBP]
Equation 3.2-3
Where:
ID: Differential phase current of check zone
[I_Pkp_Pcnt_BBP]: Current setting of busbar differential protection
3.2.2 Percentage differential element
The percentage restraint differential element includes steady-state percentage restraint differential
element and DPFC percentage restraint differential element.
I
j1
I
j1
I D KI R
Equation 3.2-4
Where:
K: Restraint coefficient of steady-state differential element
Ij: The current of the j-th feeder (Feeder j) connected
[I_Pkp_Pcnt_BBP]: Current setting of busbar differential protection
The operation characteristic is shown as below.
3-4
3 Operation Theory
ID
ID=IR
Operation region
ID=kIR
[I_Pkp_Pcnt_BBP]
IR
To enhance the sensitivity of steady-state check zone differential element for a fault occurred in
the weak source bus zone when the BC breaker is open, dual restraint coefficients [0.5, 0.3] and
[0.6, 0.5] are adopted for steady-state check zone and discriminating zones respectively.
When one of the following conditions is fulfilled, the busbar steady-state percentage restraint
differential protection will operate.
1.
Steady-state check zone differential element with high restraint coefficient (0.5) operates and
steady-state discriminating zone differential element with low restraint coefficient (0.5)
operates.
2.
Steady-state check zone differential element with low restraint coefficient (0.3) operates and
steady-state discriminating zone differential element with high restraint coefficient (0.6)
operates.
The DPFC percentage restraint differential element is adopted to enhance the performance of
busbar protection against high impedance fault and the influence of heavy loading condition. The
busbar DPFC differential protection is formed by DPFC percentage restraint differential element
and steady-state check zone percentage restraint differential element with fixed restraint
coefficient 0.2.
m
I
j1
I
j1
3-5
3 Operation Theory
ID IDFloat I DP ickup
I D 0.2I R
ID K / IR
Equation 3.2-5
Where:
K': DPFC restraint coefficient
Ij: DPFC current of the j-th feeder (Feeder j) connected
IDFloat: Float threshold value of DPFC check zone differential current
IDPickup: Fixed threshold value of DPFC check zone differential current, which derives from the
setting of [I_Pkp_Pcnt_BBP]
Similar to steady-state percentage restraint differential element, dual restraint coefficients are also
introduced to DPFC differential element. The restraint coefficients are fixed at [0.65, 0.3] and [0.65,
0.5] for DPFC check zone and discriminating zones respectively.
When the steady-state check zone percentage restraint differential element with fixed restraint
coefficient of 0.2 operates, if one of the following conditions is fulfilled, the busbar DPFC
percentage restraint differential protection will operate.
1.
DPFC check zone percentage restraint differential element with high restraint coefficient (0.65)
operates and DPFC discriminating zone percentage restraint differential element with low
restraint coefficient (0.5) operates.
2.
DPFC check zone percentage restraint differential element with low restraint coefficient (0.3)
operates and DPFC discriminating zone percentage restraint differential element with high
restraint coefficient (0.65) operates.
Equation 3.2-6
3U0 [V_ROV_VCE_BBP]
Equation 3.2-7
U2 [V_NegOV_VCE_BBP]
Equation 3.2-8
Where:
UP: Secondary rated phase-to-ground voltage
3-6
3 Operation Theory
Equation 3.2-9
U2[V_NegOV_VCE_BBP]
Equation 3.2-10
Where:
UPP: Phase-to-phase voltage
U2: Negative sequence voltage
[V_UV_VCE_BBP]: Phase-to-phase voltage setting for blocking BBP
[V_NegOV_VCE_BBP]: Negative voltage setting for blocking BBP
3.2.4 Faulty busbar zone discrimination
The check zone differential element calculates the current from all circuits connected to the entire
busbar system except BC and BS to distinguish between internal and external fault. The
discriminating zone differential elements calculate the current of all the circuits connected to
individual zones via replica image of disconnector position to determine faulty zone.
When the operation criterion of check zone differential element (steady-state check zone
differential element is supervised by CT saturation detector 2 and DPFC check zone differential
element is supervised by CT saturation detector 1, to be described in the following section) and
any discriminating zone differential element is fulfilled, VCE_BBP of any busbar operates, the
busbar differential protection will operate to trip all bays connected to the faulty busbar.
The protection has a feature of inter-connection operation mode, the feature will be effective
automatically under the following conditions.
1. The binary input [EBI_IntLink_Mode] is energized or the virtual enable binary input
[VEBI_IntLink_Mode] is set as 1, it should be done when two bus zones are coupled together
and unable to detach for a particular system operation condition.
2. On-load transfer condition (when two busbar disconnectors of one feeder are closed at the
3-7
3 Operation Theory
same time).
Under the inter-connection operation mode, the discriminating zone differential elements measure
the current signals are the same as that of check zone differential element. The coupled busbars
will be tripped simultaneously when there is a fault.
3.2.5 Backup busbar differential elements
If only the check zone percentage restraint differential element (supervised by CT saturation
detector 2) operates, two stages of backup protection with fixed time delay are applied to trip the
corresponding circuit breakers. Stage 1 of backup protection will trip BC/BS (when VCE of any
busbar operates) and the feeders of which CT correction coefficient is not zero and does not have
disconnector position after 240ms. Stage 2 of backup protection will trip the feeders connected to
the busbar of which voltage clocking has been released and the feeders with current larger than
2*In (In: the rated secondary current of reference CT) after 480ms.
3.2.6 Detection of CT saturation
Two detectors are used to prevent unwanted tripping caused by severe CT saturation during
external close up fault. If the differential current is determined to be caused by CT saturation, the
device will block busbar differential protection to prevent mal-operation.
CT saturation detector 1
When DPFC voltage or current FD element operates, the adaptive weighted algorithm for CT
saturation detector will be activated. In case of busbar fault occurs, DPFC differential element will
operate almost at the same time with DPFC voltage FD element or DPFC current FD element,
whereas for external fault, DPFC differential element will not operate before CT saturation at the
fault incipient stage, it will only operate after DPFC voltage element and DPFC current element in
case CT is saturated. Adaptive weighted algorithm for CT saturation detector is derived from the
difference of operating time among these DPFC elements. In coordination with DPFC differential
element, it has performed excellently to distinguish between internal and external fault with CT
saturation.
CT saturation detector 2
3-8
3 Operation Theory
Above figure shows the current waveforms recorded in dynamic simulation with heavy CT
saturation during external phase-to-phase fault. Protection stability is well achieved in this extreme
case.
3.2.7 External Block Signal
PCS-915 provides a binary input [BI_Blk_BBP] to block BBP through external binary signal. If the
logic setting [En_BI_Blk_BBP] is set as 1, BBP will be blocked if the binary input [BI_Blk_BBP] is
energized. However, if the binary input [BI_Blk_BBP] is energized for longer than 1 second,
PCS-915 will issue an alarm [Alm_Blk_BBP] and the blocking for BBP is released.
3.2.8 Logic scheme
Figure 3.2-4 only takes BB1 as an example, the logic scheme of BB2 is similar to it.
3-9
3 Operation Theory
[En_BI_Blk_BBP]
&
1s
[BI_Blk_BBP]
1
CT circuit failure
DPFC DIF
CT saturation
detector 1
DPFC DIF 1
DPFC current FD element
&
&
Op_TrpBB1_DPFC_BBP
&
Op_TrpBB1_Pcnt_BBP
&
Op_TrpBC_BBP
&
SP DIF 1
&
HM REL
1
500ms
1
&
SP DIF
[En_BBP]
[VEBI_BBP]
&
[EBI_BBP]
VCE_BBP 1
VCE_BBP x
SP DIF x
&
VCE_BBP x & BBx is in service
240ms
[Op_Dly1_Pcnt_BBP]
480ms
[Op_Dly2_Pcnt_BBP]
3 Operation Theory
2.
The binary input [BI_52b_BC] is energized and BC current changes from being smaller than
0.04IN to being greater than 0.04IN.
3.
The binary input [BI_52b_BC] is energized and BB1 and BB2 are in service.
3-11
3 Operation Theory
[BI_52a_BC]
&
[BI_52b_BC]
BB1 is in service
&
&
0 300ms
BB2 is in service
&
&
Ia_BC>0.04IN
Ib_BC>0.04IN
&
Op_TrpBC_SOTF
Ic_BC>0.04IN
[En_SOTF_BC]
&
[VEBI_SOTF_BC]
[EBI_SOTF_BC]
Ia_BC>[I_OC_SOTF_BC]
Ib_BC>[I_OC_SOTF_BC]
Ic_BC>[I_OC_SOTF_BC]
3-12
3 Operation Theory
Ia_BC>[I_OC_BC]
Ib_BC>[I_OC_BC]
1
&
Ic_BC>[I_OC_BC]
[t_OC_BC]
Op_TrpBC_OC
[En_OC_BC]
&
[VEBI_OC_BC]
[EBI_OC_BC]
&
[t_OC_BC]
Op_TrpBC_ROC
3I0_BC>[I_ROC_BC]
BBP
2.
3-13
3 Operation Theory
VCE_BBP 1
Ia_BC>[I_BFP_BC]
Ib_BC>[I_BFP_BC]
Ic_BC>[I_BFP_BC]
BBP Trip BC
&
BBP Trip BB1
[t_TrpBB_BFP_BC]
Op_BFP_BB1
&
1
[BI_BFI_BC_1]
&
&
[t_TrpBB_BFP_BC]
Op_BFP_BB2
[BI_BFI_BC_2]
VCE_BBP 2
3-14
3 Operation Theory
BB No.1
BC CT
Dead zone
BC Breaker
BB No.2
The logic scheme of end zone fault protection is shown as Figure 3.3-4.
BB1 is in service
&
BB2 is in service
Ia_BC>0.04IN
0 400ms
&
Ib_BC>0.04IN
&
Ic_BC>0.04IN
[EBI_Decoupled_BC]
1
[BI_52a_BC]
&
&
[BI_52b_BC]
SP Trip BC
&
SP DIF
Ia_BC>0.1IN
&
Ib_BC>0.1IN
150ms
Ic_BC>0.1IN
3 Operation Theory
[BI_PD_BC]
3I0_BC>[I_ROC_PD_BC]
&
1
&
[t_PD_BC]
Op_BC_PD
I2_BC>[I_NegOC_PD_BC]
[EBI_PD_BC]
&
[VEBI_PD_BC]
[En_PD_BC]
52b_A
52a_A
52b_B
52a_B
52b_C
52a_C
[BI_PD_BC]
3 Operation Theory
xx=04~13, 16~25.
2.
Current criterion 1
Current criterion 2
Current criterion 3
Equation 3.4-1
3U0[V_ROV_VCE_BFP]
Equation 3.4-2
U2[V_NegOV_VCE_BFP]
Equation 3.4-3
Where:
UP: Secondary rated phase-to-ground voltage
3U0: Residual voltage
U2: Negative sequence voltage
[V_UV_VCE_BFP]: Phase voltage setting for blocking BFP
3-17
3 Operation Theory
Equation 3.4-4
U2[V_NegOV_VCE_BFP]
Equation 3.4-5
Where:
UPP: Phase-to-phase voltage
U2: Negative sequence voltage
[V_UV_VCE_BFP]: Phase-to-phase voltage setting for blocking BFP
[V_NegOV_VCE_BFP]: Negative sequence voltage setting for blocking BFP
3.4.4 Logic scheme
The logic scheme of BFP is shown as Figure 3.4-1.
[BI_BFI_Bayxx]
1
BBP operates to trip feeder xx
&
1
Ia_Bayxx>[I_OC_BFP_Bayxx]
&
[BI_A_BFI_Bayxx]
Ib_Bayxx>[I_OC_BFP_Bayxx]
&
[BI_B_BFI_Bayxx]
Ic_Bayxx>[I_OC_BFP_Bayxx]
&
[BI_C_BFI_Bayxx]
1
[En_ROC_BFP_Bayxx]
1
&
&
3I0_Bayxx>[I_ROC_BFP_Bayxx]
[En_NegOC_BFP_Bayxx]
&
&
I2_Bayxx>[I_NegOC_BFP_Bayxx]
[t_ReTrp_BFP]
[VEBI_BFP]
&
[EBI_BFP]
&
[t_TrpBC_BFP]
Op_Retrip_Bayxx
Op_TrpBC_BFP
[En_BFP]
&
[t_TrpBB_BFP]
Op_BFP_BB1
&
VCE 1
[t_ReTrp_BFP]
&
VCE 2
&
[t_TrpBC_BFP]
[t_TrpBB_BFP]
Op_Retrip_Bayxx
Op_TrpBC_BFP
Op_BFP_BB2
Figure 3.4-1 The logic scheme of BFP (for the bay that main transformer is not connected)
3-18
3 Operation Theory
Ia_Bayxx>[I_OC_BFP_Bayxx]
Ib_Bayxx>[I_OC_BFP_Bayxx]
1
Ic_Bayxx>[I_OC_BFP_Bayxx]
&
[En_ROC_BFP_Bayxx]
&
&
3I0_Bayxx>[I_ROC_BFP_Bayxx]
[En_NegOC_BFP_Bayxx]
&
&
I2_Bayxx>[I_NegOC_BFP_Bayxx]
[EBI_BFP]
&
[VEBI_BFP]
&
[En_BFP]
[t_ReTrp_BFP]
[t_TrpBC_BFP]
Op_ReTrp_Bayxx
Op_TrpBC_BFP
VCE 1
1
&
[t_TrpBB_BFP]
&
[BI_Rls_VCE_BFP_Trans]
Op_BFP_BB1
Op_IntTrp_BFP_Bayxx
&
[t_ReTrp_BFP]
Op_ReTrp_Bayxx
&
[t_TrpBC_BFP]
Op_TrpBC_BFP
Op_BFP_BB2
Op_IntTrp_BFP_Bayxx
Figure 3.4-2 The logic scheme of BFP (for the bay that main transformer is connected)
3 Operation Theory
simultaneously. If there is current flowing in a bay but the bay has no disconnector positions for
dual busbars, the protective device can remember the original disconnector position. An
abnormality of disconnector position is detected and disconnector position alarms [Alm_DS_Bayxx]
will be issued with a specific time delay in any of the following cases (xx: from 02 to 25).
1.
Disconnector position is changed. The operator should check it and confirm whether it is
correct. The alarm can be reset by energizing the binary input [BI_ConfirmDS].
2.
If both disconnectors to BB1 and BB2 of a bay are closed, an alarm signal [Alm_IntLink] will
be issued. The alarm can not be reset by energizing the binary input [BI_ConfirmDS].
3.
There is current detected in a bay but the bay has no disconnector positions for dual busbars.
The alarm can not be reset by energizing the binary input [BI_ConfirmDS]. In this case, the
protective device can remember the original disconnector position of the bay, and check its
validity based on the current distribution of system.
4.
If discriminating zone differential current is greater than 0.04IN due to the wrong disconnector
position, an alarm will be issued with a time delay and the device can identify the right
disconnector position based on the current distribution of system.
Besides, in order to prevent the feeder from missing-operation because the bay has no
disconnector position, no matter which busbar zone does the fault occur in, the bays whose CT
correction coefficient is not zero but no disconnector position can be detected will be tripped.
Note!
When disconnector position alarm is issued, the operator must check the actual condition
at first and then energize the binary input [BI_ConfirmDS] to reset the alarm if it is correct.
Usually a button on the panel is provided, pressing the button will result in energizing the
binary input [BI_ConfirmDS].
If three times busbar negative sequence voltage (3U2) is larger than 0.2UN (UN: the secondary
rated phase-to-ground voltage of VT), an alarm [Alm_VTS_BB1] or [Alm_VTS_BB2] will be
issued with a time delay of 1.25s.
2.
If any busbar is in service and the sum of the amplitude of busbar three-phase voltage
(|UA|+|UB|+|UC|) is smaller than UN, an alarm [Alm_VTS_BB1] or [Alm_VTS_BB2] will be
issued with a time delay of 1.25s.
3.
When the logic setting [Opt_UnearthedSys_Mode] is set as 1, if three times busbar negative
sequence voltage (3U2) is greater than 0.2UN or any phase-to-phase voltage is smaller than
0.7UN_PP (UN_PP: the secondary rated phase-to-phase voltage of VT), an alarm
[Alm_VTS_BB1] or [Alm_VTS_BB2] will be issued with a time delay of 1.25s.
If the fault detector element picks up due to a disturbance in the system, the VT circuit supervision
3-20
3 Operation Theory
If check zone differential current is greater than the setting [I_Alm_CTS], an alarm [Alm_CTS]
will be issued with a time delay of 5s and BBP will be blocked. The alarm can be reset only by
pressing reset button on the panel to energize binary input [BI_RstTarg] after the CT circuit
returns to normal condition.
2.
If check zone differential current is smaller than the setting i.e. [I_Alm_CTS] and both
discriminating zone currents are greater than [I_Alm_CTS], an alarm [Alm_CTS_BC] will be
issued with a time delay of 5s and BBP will not be blocked but single busbar mode will be
enabled automatically. Under this situation, if any internal fault occurs, faulty busbar will not
be identified. The alarm can be reset only by pressing reset button on the panel to energize
the binary input [BI_RstTarg] even the CT circuit returns to normal condition.
When VCE of any busbar operates, CT circuit failure will not be detected.
3.7.2 CT circuit abnormality
1.
If check zone differential current is greater than the setting i.e. [I_Alm_SensCTS], an alarm
[Alm_SensCTS] will be issued with a time delay of 5s. The alarm can be reset only by
pressing reset button on the panel to energize the binary input [BI_RstTarg] after the CT
circuit returns to normal condition.
2.
If check zone differential current is smaller than the setting [I_Alm_SensCTS] and both
discriminating zone currents are greater than [I_Alm_SensCTS], an alarm
[Alm_SensCTS_BC] will be issued with a time delay of 5s. The alarm can be reset only by
pressing reset button on the panel to energize the binary input [BI_RstTarg] after the CT
circuit returns to normal condition.
3.
3 Operation Theory
energized and negative value of BC current will be calculated in check zone differential current
and discriminating zone differential current.
If BC breaker is used temporarily to substitute one of feeder breakers, the BC current will be taken
as the current of the substituted feeder, whether the positive value or the negative value of the
substituting BC current is calculated in check zone differential current and discriminating zone
differential current depends on the status of the binary input [EBI_NegPolar_CT_BT].
If the normally open auxiliary contact of substituting disconnector of BBx [BI_52a_DSBBx_BT] is
energized, the BC breaker is substituting through BBx, and the BC current will be calculated in
discriminating zone differential current of BBx.
When BC breaker is used to substitute any of feeder breakers, some protection elements (such as
SOTF protection, EFP and BFP) of BC will quit automatically, but overcurrent protection and pole
disagreement protection are still reserved, which can be used as the protection function of the
substituted feeder. In addition, some functions for BC breaker is used as a tie breaker connecting
two busbars are also quit (such as: tripping BC breaker when busbar internal fault happens).
Note!
[EBI_NegPolar_CT_BT] should be energized prior to [EBI_BT_BC].
1.
Transfer Busbar
*
BB1
BC
BB2
The polarity mark of BC CT is on the feeder side, the binary input [EBI_NegPolar_CT_BT] should
be energized. Negative value of BC current will be calculated in check zone differential current and
discriminating zone differential current of BB2.
2.
3-22
3 Operation Theory
Transfer Busbar
*
BB2
*
BC1
BB1
The polarity mark of BC CT is on the busbar side, the binary input [EBI_NegPolar_CT_BT] should
not be energized. Positve value of BC current will be calculated in check zone differential current
and discriminating zone differential current of BB1.
3-23
3 Operation Theory
3-24
4 Supervision
4 Supervision
Table of Contents
4 Supervision ..................................................................................... 4-a
4.1 Overview .......................................................................................................... 4-1
4.2 Protective Device Supervision ....................................................................... 4-1
4.2.1 Hardware supervision .......................................................................................................... 4-1
4.2.2 Opto-coupler Power Supervision ......................................................................................... 4-1
4.2.3 Binary output supervision .................................................................................................... 4-1
4.2.4 Binary input supervision ...................................................................................................... 4-1
4.2.5 Setting supervision .............................................................................................................. 4-2
4.2.6 Test Mode Supervision ........................................................................................................ 4-2
4.2.7 Hardware Configuration Supervision................................................................................... 4-2
Table of Tables
Table 4.5-1 Self-supervision report ........................................................................................... 4-3
Table 4.5-2 Equipment self-check alarm list................................................................................ 4-7
PCS-915A Busbar Protection
4-a
Date: 2012-08-31
4 Supervision
4-b
4 Supervision
4.1 Overview
PCS-915 is a microprocessor based busbar protection which can provide successive automatic
supervision to the protected object to ensure the power system can quickly restore from any fault
to normal state. When the device is in energizing process before the LED HEALTHY is lightened,
operators need to check the device operating state to ensure the automatic supervision function
can work normally.
The device will be blocked if there is any severe problem occurs in the hardware module or
software program. Before reboot the relay, users are recommended to solve the problem or return
the feedbacks to NR.
When a failure is detected in the system, the fault message will be displayed on the LCD and the
corresponding LED will be lightened. Meanwhile, the corresponding alarm output contacts will be
energized and the failure alarm will be recorded and stored in the device. Users can either view
the fault report directly on LCD or print out the report.
The automatic supervision of PCS-915 has advantages in independent operation to the protection
functions and is capable to identify the fault location when the fault occurs in the system.
4-1
Date: 2012-08-31
4 Supervision
If any binary input for initiating feeder BFP is energized for over 10s, the alarm
[Alm_PersistFD_BFP] will be issued with BFP blocked.
4 Supervision
value of power system. The main purpose is to detect faults in the secondary circuits of CT and to
avoid influences on corresponding protection functions. Please refer to Section 3.7 for details.
No.
Alarm Message
Indicator LED
HEALTHY
MISC_ALM
VT/CT_ALM
DS_ALM
Alm_Device
GREEN
YELLOW
OFF
OFF
Fail_Device
OFF
YELLOW
OFF
OFF
Fail_SettingItem_Chgd
OFF
YELLOW
OFF
OFF
Alm_Version
GREEN
YELLOW
OFF
OFF
Alm_BO_Test
GREEN
YELLOW
OFF
OFF
Alm_Setting_Out-of-Scope
OFF
YELLOW
OFF
OFF
Alm_BoardConfig
OFF
YELLOW
OFF
OFF
4-3
Date: 2012-08-31
4 Supervision
No.
Alarm Message
Indicator LED
HEALTHY
MISC_ALM
VT/CT_ALM
DS_ALM
Alm_TimeSync
GREEN
YELLOW
OFF
OFF
Alm_VTS_BB1
GREEN
OFF
YELLOW
OFF
10
Alm_VTS_BB2
GREEN
OFF
YELLOW
OFF
11
Alm_Pkp_VCE_BB1
GREEN
YELLOW
OFF
OFF
12
Alm_Pkp_VCE_BB2
GREEN
YELLOW
OFF
OFF
13
Alm_CTS
GREEN
OFF
YELLOW
OFF
14
Alm_SensCTS
GREEN
YELLOW
OFF
OFF
15
Alm_CTS_BC
GREEN
OFF
YELLOW
OFF
16
Alm_SensCTS_BC
GREEN
YELLOW
OFF
OFF
17
Alm_52a/52b_BC
GREEN
YELLOW
OFF
OFF
18
Alm_52b_BC
GREEN
YELLOW
OFF
OFF
19
Alm_PersistFD_BFP_BC
GREEN
YELLOW
OFF
OFF
20
Alm_PersistFD_OC_BC
GREEN
YELLOW
OFF
OFF
21
Alm_PersistFD_ROC_BC
GREEN
YELLOW
OFF
OFF
22
Alm_PersistFD_SOTF_BC
GREEN
YELLOW
OFF
OFF
23
Alm_PersistFD
GREEN
YELLOW
OFF
OFF
24
Alm_PD_BC
GREEN
YELLOW
OFF
OFF
25
Alm_BI_BFI_1_BC
GREEN
YELLOW
OFF
OFF
26
Alm_BI_BFI_2_BC
GREEN
YELLOW
OFF
OFF
27
Alm_Sample_BC
OFF
YELLOW
OFF
OFF
28
Alm_Sample_Bay02
OFF
YELLOW
OFF
OFF
29
Alm_Sample_Bay03
OFF
YELLOW
OFF
OFF
30
Alm_Sample_Bay04
OFF
YELLOW
OFF
OFF
31
Alm_Sample_Bay05
OFF
YELLOW
OFF
OFF
32
Alm_Sample_Bay06
OFF
YELLOW
OFF
OFF
33
Alm_Sample_Bay07
OFF
YELLOW
OFF
OFF
34
Alm_Sample_Bay08
OFF
YELLOW
OFF
OFF
35
Alm_Sample_Bay09
OFF
YELLOW
OFF
OFF
36
Alm_Sample_Bay10
OFF
YELLOW
OFF
OFF
37
Alm_Sample_Bay11
OFF
YELLOW
OFF
OFF
38
Alm_Sample_Bay12
OFF
YELLOW
OFF
OFF
39
Alm_Sample_Bay13
OFF
YELLOW
OFF
OFF
40
Alm_Sample_Bay14
OFF
YELLOW
OFF
OFF
41
Alm_Sample_Bay15
OFF
YELLOW
OFF
OFF
42
Alm_Sample_Bay16
OFF
YELLOW
OFF
OFF
43
Alm_Sample_Bay17
OFF
YELLOW
OFF
OFF
44
Alm_Sample_Bay18
OFF
YELLOW
OFF
OFF
45
Alm_Sample_Bay19
OFF
YELLOW
OFF
OFF
46
Alm_Sample_Bay20
OFF
YELLOW
OFF
OFF
47
Alm_Sample_Bay21
OFF
YELLOW
OFF
OFF
48
Alm_Sample_Bay22
OFF
YELLOW
OFF
OFF
4-4
4 Supervision
No.
Alarm Message
Indicator LED
HEALTHY
MISC_ALM
VT/CT_ALM
DS_ALM
49
Alm_Sample_Bay23
OFF
YELLOW
OFF
OFF
50
Alm_Sample_Bay24
OFF
YELLOW
OFF
OFF
51
Alm_Sample_Bay25
OFF
YELLOW
OFF
OFF
52
Alm_VoltSample_BB1
OFF
YELLOW
OFF
OFF
53
Alm_VoltSample_BB2
OFF
YELLOW
OFF
OFF
54
Alm_PersistFD_Pcnt_BBP
GREEN
YELLOW
OFF
OFF
55
Alm_PersistFD_DPFC_BBP
GREEN
YELLOW
OFF
OFF
56
Alm_Fail_PersistFD
OFF
YELLOW
OFF
OFF
57
Alm_Blk_BBP
GREEN
YELLOW
OFF
OFF
58
Alm_IntLink
GREEN
YELLOW
OFF
OFF
59
Alm_PersistFD_BFP
GREEN
YELLOW
OFF
OFF
60
Alm_Output_B12
OFF
YELLOW
OFF
OFF
61
Alm_Output_B13
OFF
YELLOW
OFF
OFF
62
Alm_Output_B14
OFF
YELLOW
OFF
OFF
63
Alm_Output_B15
OFF
YELLOW
OFF
OFF
64
Alm_Output_B30
OFF
YELLOW
OFF
OFF
65
Alm_Output_B31
OFF
YELLOW
OFF
OFF
66
Alm_Output_B32
OFF
YELLOW
OFF
OFF
67
Alm_Pwr_BI_B04
GREEN
YELLOW
OFF
OFF
68
Alm_Pwr_BI_B05
GREEN
YELLOW
OFF
OFF
69
Alm_Pwr_BI_B06
GREEN
YELLOW
OFF
OFF
70
Alm_Pwr_BI_B07
GREEN
YELLOW
OFF
OFF
71
Alm_Pwr_BI_B08
GREEN
YELLOW
OFF
OFF
72
Alm_Pwr_BI_B09
GREEN
YELLOW
OFF
OFF
73
Alm_Pwr_BI_B10
GREEN
YELLOW
OFF
OFF
74
Alm_Pwr_BI_B11
GREEN
YELLOW
OFF
OFF
75
Alm_Setting_ProtBrd
OFF
YELLOW
OFF
OFF
76
Alm_Setting_FDBrd
OFF
YELLOW
OFF
OFF
77
Alm_Setting
OFF
YELLOW
OFF
OFF
78
Alm_DSP_ProtBrd
OFF
YELLOW
OFF
OFF
79
Alm_DSP_FDBrd
OFF
YELLOW
OFF
OFF
80
Alm_DS_Bay02
GREEN
OFF
OFF
YELLOW
81
Alm_DS_Bay03
GREEN
OFF
OFF
YELLOW
82
Alm_DS_Bay04
GREEN
OFF
OFF
YELLOW
83
Alm_DS_Bay05
GREEN
OFF
OFF
YELLOW
84
Alm_DS_Bay06
GREEN
OFF
OFF
YELLOW
85
Alm_DS_Bay07
GREEN
OFF
OFF
YELLOW
86
Alm_DS_Bay08
GREEN
OFF
OFF
YELLOW
87
Alm_DS_Bay09
GREEN
OFF
OFF
YELLOW
88
Alm_DS_Bay10
GREEN
OFF
OFF
YELLOW
89
Alm_DS_Bay11
GREEN
OFF
OFF
YELLOW
4-5
Date: 2012-08-31
4 Supervision
No.
Alarm Message
Indicator LED
HEALTHY
MISC_ALM
VT/CT_ALM
DS_ALM
90
Alm_DS_Bay12
GREEN
OFF
OFF
YELLOW
91
Alm_DS_Bay13
GREEN
OFF
OFF
YELLOW
92
Alm_DS_Bay14
GREEN
OFF
OFF
YELLOW
93
Alm_DS_Bay15
GREEN
OFF
OFF
YELLOW
94
Alm_DS_Bay16
GREEN
OFF
OFF
YELLOW
95
Alm_DS_Bay17
GREEN
OFF
OFF
YELLOW
96
Alm_DS_Bay18
GREEN
OFF
OFF
YELLOW
97
Alm_DS_Bay19
GREEN
OFF
OFF
YELLOW
98
Alm_DS_Bay20
GREEN
OFF
OFF
YELLOW
99
Alm_DS_Bay21
GREEN
OFF
OFF
YELLOW
100
Alm_DS_Bay22
GREEN
OFF
OFF
YELLOW
101
Alm_DS_Bay23
GREEN
OFF
OFF
YELLOW
102
Alm_DS_Bay24
GREEN
OFF
OFF
YELLOW
103
Alm_DS_Bay25
GREEN
OFF
OFF
YELLOW
104
Alm_BI_BFI_Bay02
GREEN
YELLOW
OFF
OFF
105
Alm_BI_BFI_Bay03
GREEN
YELLOW
OFF
OFF
106
Alm_BI_BFI_Bay04
GREEN
YELLOW
OFF
OFF
107
Alm_BI_BFI_Bay05
GREEN
YELLOW
OFF
OFF
108
Alm_BI_BFI_Bay06
GREEN
YELLOW
OFF
OFF
109
Alm_BI_BFI_Bay07
GREEN
YELLOW
OFF
OFF
110
Alm_BI_BFI_Bay08
GREEN
YELLOW
OFF
OFF
111
Alm_BI_BFI_Bay09
GREEN
YELLOW
OFF
OFF
112
Alm_BI_BFI_Bay10
GREEN
YELLOW
OFF
OFF
113
Alm_BI_BFI_Bay11
GREEN
YELLOW
OFF
OFF
114
Alm_BI_BFI_Bay12
GREEN
YELLOW
OFF
OFF
115
Alm_BI_BFI_Bay13
GREEN
YELLOW
OFF
OFF
116
Alm_BI_BFI_Bay14
GREEN
YELLOW
OFF
OFF
117
Alm_BI_BFI_Bay15
GREEN
YELLOW
OFF
OFF
118
Alm_BI_BFI_Bay16
GREEN
YELLOW
OFF
OFF
119
Alm_BI_BFI_Bay17
GREEN
YELLOW
OFF
OFF
120
Alm_BI_BFI_Bay18
GREEN
YELLOW
OFF
OFF
121
Alm_BI_BFI_Bay19
GREEN
YELLOW
OFF
OFF
122
Alm_BI_BFI_Bay20
GREEN
YELLOW
OFF
OFF
123
Alm_BI_BFI_Bay21
GREEN
YELLOW
OFF
OFF
124
Alm_BI_BFI_Bay22
GREEN
YELLOW
OFF
OFF
125
Alm_BI_BFI_Bay23
GREEN
YELLOW
OFF
OFF
126
Alm_BI_BFI_Bay24
GREEN
YELLOW
OFF
OFF
127
Alm_BI_BFI_Bay25
GREEN
YELLOW
OFF
OFF
128
Alm_BI_BFI_BT
GREEN
YELLOW
OFF
OFF
129
Alm_DS_BT
GREEN
OFF
OFF
YELLOW
130
Alm_BI_Chk_BFI_1
GREEN
YELLOW
OFF
OFF
4-6
4 Supervision
No.
Indicator LED
Alarm Message
HEALTHY
MISC_ALM
VT/CT_ALM
DS_ALM
131
Alm_BI_Chk_BFI_2
GREEN
YELLOW
OFF
OFF
132
Alm_BI_Chk_BFI_3
GREEN
YELLOW
OFF
OFF
133
Alm_BI_Chk_BFI_4
GREEN
YELLOW
OFF
OFF
134
Alm_BI_Rls_VCE_BFP_Trans
GREEN
YELLOW
OFF
OFF
Alarm Message
Meaning Description
Alm_Device
Fail_Device
Any alarm signal(s) that will lead blocking of the device is(are) issued.
Fail_SettingItem_Chgd
Alm_Version
Alm_BO_Test
Alm_Setting_Out-of-Scope
Alm_BoardConfig
Alm_TimeSync
Alm_VTS_BB1
10
Alm_VTS_BB2
11
Alm_Pkp_VCE_BB1
12
Alm_Pkp_VCE_BB2
13
Alm_CTS
14
Alm_SensCTS
CT circuit is abnormal.
15
Alm_CTS_BC
16
Alm_SensCTS_BC
BC CT circuit is abnormal.
17
Alm_52a/52b_BC
18
Alm_52b_BC
19
Alm_PersistFD_BFP_BC
20
Alm_PersistFD_OC_BC
21
Alm_PersistFD_ROC_BC
22
Alm_PersistFD_SOTF_BC
23
Alm_PersistFD
After config file is updated, settings of the file and settings saved on the
device are not matched.
Version information of system program or DSP program is not
consistent with that defined in the standard device program.
4-7
Date: 2012-08-31
4 Supervision
No.
Alarm Message
Meaning Description
The pole discrepancy binary input of BC/BS [BI_PD_BC] is energized
24
Alm_PD_BC
25
Alm_BI_BFI_1_BC
26
Alm_BI_BFI_2_BC
27
Alm_Sample_BC
28
Alm_Sample_Bay02
29
Alm_Sample_Bay03
30
Alm_Sample_Bay04
31
Alm_Sample_Bay05
32
Alm_Sample_Bay06
33
Alm_Sample_Bay07
34
Alm_Sample_Bay08
35
Alm_Sample_Bay09
36
Alm_Sample_Bay10
37
Alm_Sample_Bay11
38
Alm_Sample_Bay12
39
Alm_Sample_Bay13
40
Alm_Sample_Bay14
41
Alm_Sample_Bay15
42
Alm_Sample_Bay16
43
Alm_Sample_Bay17
44
Alm_Sample_Bay18
45
Alm_Sample_Bay19
46
Alm_Sample_Bay20
47
Alm_Sample_Bay21
48
Alm_Sample_Bay22
49
Alm_Sample_Bay23
50
Alm_Sample_Bay24
51
Alm_Sample_Bay25
52
Alm_VoltSample_BB1
53
Alm_VoltSample_BB2
54
Alm_PersistFD_Pcnt_BBP
55
Alm_PersistFD_DPFC_BBP
56
Alm_Fail_PersistFD
57
Alm_Blk_BBP
58
Alm_IntLink
59
Alm_PersistFD_BFP
Both disconnectors of any feeder for BB1 and BB2 are closed at the
same time.
Duration of pickup of BFP fault detector on protection module is in
excess of 10s.
4-8
4 Supervision
No.
Alarm Message
Meaning Description
Driving transistors of binary output module located in slot No.12 are
60
Alm_Output_B12
61
Alm_Output_B13
62
Alm_Output_B14
63
Alm_Output_B15
64
Alm_Output_B30
65
Alm_Output_B31
66
Alm_Output_B32
67
Alm_Pwr_BI_B04
68
Alm_Pwr_BI_B05
69
Alm_Pwr_BI_B06
70
Alm_Pwr_BI_B07
71
Alm_Pwr_BI_B08
72
Alm_Pwr_BI_B09
73
Alm_Pwr_BI_B10
74
Alm_Pwr_BI_B11
75
Alm_Setting_ProtBrd
76
Alm_Setting_FDBrd
77
Alm_Setting
78
Alm_DSP_ProtBrd
79
Alm_DSP_FDBrd
80
Alm_DS_Bay02
81
Alm_DS_Bay03
82
Alm_DS_Bay04
83
Alm_DS_Bay05
84
Alm_DS_Bay06
85
Alm_DS_Bay07
86
Alm_DS_Bay08
damaged.
Driving transistors of binary output module located in slot No.13 are
damaged.
Driving transistors of binary output module located in slot No.14 are
damaged.
Driving transistors of binary output module located in slot No.15 are
damaged.
Driving transistors of binary output module located in slot No.30 are
damaged.
Driving transistors of binary output module located in slot No.31 are
damaged.
Driving transistors of binary output module located in slot No.32 are
damaged.
Loss of power supply of the opto-couplers for binary input module
located in slot No.04.
Loss of power supply of the opto-couplers for binary input module
located in slot No.05.
Loss of power supply of the opto-couplers for binary input module
located in slot No.06.
Loss of power supply of the opto-couplers for binary input module
located in slot No.07.
Loss of power supply of the opto-couplers for binary input module
located in slot No.08.
Loss of power supply of the opto-couplers for binary input module
located in slot No.09.
Loss of power supply of the opto-couplers for binary input module
located in slot No.10.
Loss of power supply of the opto-couplers for binary input module
located in slot No.11.
4-9
Date: 2012-08-31
4 Supervision
No.
Alarm Message
Meaning Description
87
Alm_DS_Bay09
88
Alm_DS_Bay10
89
Alm_DS_Bay11
90
Alm_DS_Bay12
91
Alm_DS_Bay13
92
Alm_DS_Bay14
93
Alm_DS_Bay15
94
Alm_DS_Bay16
95
Alm_DS_Bay17
96
Alm_DS_Bay18
97
Alm_DS_Bay19
98
Alm_DS_Bay20
99
Alm_DS_Bay21
100
Alm_DS_Bay22
101
Alm_DS_Bay23
102
Alm_DS_Bay24
103
Alm_DS_Bay25
104
Alm_BI_BFI_Bay02
105
Alm_BI_BFI_Bay03
106
Alm_BI_BFI_Bay04
107
Alm_BI_BFI_Bay05
108
Alm_BI_BFI_Bay06
109
Alm_BI_BFI_Bay07
110
Alm_BI_BFI_Bay08
111
Alm_BI_BFI_Bay09
112
Alm_BI_BFI_Bay10
113
Alm_BI_BFI_Bay11
114
Alm_BI_BFI_Bay12
115
Alm_BI_BFI_Bay13
116
Alm_BI_BFI_Bay14
117
Alm_BI_BFI_Bay15
118
Alm_BI_BFI_Bay16
119
Alm_BI_BFI_Bay17
120
Alm_BI_BFI_Bay18
121
Alm_BI_BFI_Bay19
122
Alm_BI_BFI_Bay20
123
Alm_BI_BFI_Bay21
124
Alm_BI_BFI_Bay22
125
Alm_BI_BFI_Bay23
126
Alm_BI_BFI_Bay24
127
Alm_BI_BFI_Bay25
128
Alm_BI_BFI_BT
4-10
4 Supervision
No.
Alarm Message
Meaning Description
feeder breaker) is energized for over 10s.
129
Alm_DS_BT
130
Alm_BI_Chk_BFI_1
131
Alm_BI_Chk_BFI_2
132
Alm_BI_Chk_BFI_3
133
Alm_BI_Chk_BFI_4
134
Alm_BI_Rls_VCE_BFP_Trans
Self-supervision Report
Suggestion
Alm_Setting_Out-of-Scope
Alm_BoardConfig
Alm_Sample_BC
Alm_Sample_Bay02
Alm_Sample_Bay03
Alm_Sample_Bay04
Alm_Sample_Bay05
Alm_Sample_Bay06
Alm_Sample_Bay07
10
Alm_Sample_Bay08
11
Alm_Sample_Bay09
12
Alm_Sample_Bay10
Put the protective device out of service at once. Inform the factory or
13
Alm_Sample_Bay11
14
Alm_Sample_Bay12
15
Alm_Sample_Bay13
16
Alm_Sample_Bay14
17
Alm_Sample_Bay15
18
Alm_Sample_Bay16
19
Alm_Sample_Bay17
20
Alm_Sample_Bay18
21
Alm_Sample_Bay19
22
Alm_Sample_Bay20
23
Alm_Sample_Bay21
24
Alm_Sample_Bay22
4-11
Date: 2012-08-31
4 Supervision
No.
Self-supervision Report
25
Alm_Sample_Bay23
26
Alm_Sample_Bay24
27
Alm_Sample_Bay25
28
Alm_VoltSample_BB1
29
Alm_VoltSample_BB2
30
Alm_Output_B12
31
Alm_Output_B13
32
Alm_Output_B14
33
Alm_Output_B15
34
Alm_Output_B30
35
Alm_Output_B31
36
Alm_Output_B32
37
Alm_Setting_ProtBrd
38
Alm_Setting_FDBrd
39
Alm_Setting
40
Alm_DSP_ProtBrd
41
Alm_DSP_FDBrd
42
Alm_Version
43
Alm_Device
44
Fail_Device
Suggestion
45
Fail_SettingItem_Chgd
46
47
48
Alm_PersistFD_OC_BC
Alm_PersistFD_ROC_BC
Alm_PersistFD_SOTF_BC
49
Alm_PersistFD
50
Alm_PD_BC
synchronization source;
Alm_TimeSync
4-12
4 Supervision
No.
Self-supervision Report
Suggestion
and the equipment will restore to normal operation state.
52
Alm_52b_BC
53
Alm_52a/52b_BC
54
Alm_VTS_BB1
55
Alm_VTS_BB2
56
Alm_Pkp_VCE_BB1
57
Alm_Pkp_VCE_BB2
58
Alm_CTS
59
Alm_SensCTS
60
Alm_CTS_BC
61
Alm_SensCTS_BC
62
Alm_BI_Rls_VCE_BFP_Trans
63
Alm_BI_BFI_1_BC
64
Alm_PersistFD_BFP_BC
whether the protective element (which can initiate BC/BS BFP) drops
off.
65
Alm_BI_BFI_Bay02
66
Alm_BI_BFI_Bay03
67
Alm_BI_BFI_Bay04
68
Alm_BI_BFI_Bay05
69
Alm_BI_BFI_Bay06
70
Alm_BI_BFI_Bay07
71
Alm_BI_BFI_Bay08
72
Alm_BI_BFI_Bay09
73
Alm_BI_BFI_Bay10
74
Alm_BI_BFI_Bay11
75
Alm_BI_BFI_Bay12
76
Alm_BI_BFI_Bay13
77
Alm_BI_BFI_Bay14
78
Alm_BI_BFI_Bay15
79
Alm_BI_BFI_Bay16
80
Alm_BI_BFI_Bay17
81
Alm_BI_BFI_Bay18
82
Alm_BI_BFI_Bay19
83
Alm_BI_BFI_Bay20
84
Alm_BI_BFI_Bay21
85
Alm_BI_BFI_Bay22
86
Alm_BI_BFI_Bay23
87
Alm_BI_BFI_Bay24
88
Alm_BI_BFI_Bay25
89
Alm_BI_BFI_BT
4-13
Date: 2012-08-31
4 Supervision
No.
Self-supervision Report
Suggestion
90
Alm_PersistFD_BFP
91
Alm_Fail_PersistFD
92
Alm_BO_Test
93
Alm_BI_Chk_BFI_1
Check all the binary inputs of the BI module located in slot No.6
94
Alm_BI_Chk_BFI_2
Check all the binary inputs of the BI module located in slot No.7
95
Alm_BI_Chk_BFI_3
Check all the binary inputs of the BI module located in slot No.8
96
Alm_BI_Chk_BFI_4
97
Alm_BI_BFI_2_BC
98
Alm_Blk_BBP
99
Alm_Pwr_BI_B04
100
Alm_Pwr_BI_B05
101
Alm_Pwr_BI_B06
102
Alm_Pwr_BI_B07
103
Alm_Pwr_BI_B08
104
Alm_Pwr_BI_B09
105
Alm_Pwr_BI_B10
106
Alm_Pwr_BI_B11
107
Alm_PersistFD_Pcnt_BBP
108
Alm_PersistFD_DPFC_BBP
109
Alm_DS_Bay02
110
Alm_DS_Bay03
111
Alm_DS_Bay04
112
Alm_DS_Bay05
113
Alm_DS_Bay06
114
Alm_DS_Bay07
115
Alm_DS_Bay08
116
Alm_DS_Bay09
117
Alm_DS_Bay10
118
Alm_DS_Bay11
119
Alm_DS_Bay12
120
Alm_DS_Bay13
121
Alm_DS_Bay14
122
Alm_DS_Bay15
123
Alm_DS_Bay16
124
Alm_DS_Bay17
125
Alm_DS_Bay18
126
Alm_DS_Bay19
127
Alm_DS_Bay20
128
Alm_DS_Bay21
129
Alm_DS_Bay22
130
Alm_DS_Bay23
Please refer to the other alarm signal to confirm the blocking reason
No special treatment is needed, and only wait for the completion of
testing
Check all the binary inputs of the BI module located in slot No.9
Check the contact of blocking BBP externally
4-14
4 Supervision
No.
Self-supervision Report
131
Alm_DS_Bay24
132
Alm_DS_Bay25
133
Alm_DS_BT
134
Alm_IntLink
Suggestion
4-15
Date: 2012-08-31
4 Supervision
4-16
5-a
Date: 2013-06-03
5-b
5.2 Metering
PCS-915 can provide continuous measurements of analogue input quantities. The measurement
data shown below is displayed on the LCD of the relay front panel or by the software interface on
the local or remote PC. The analog quantities will be displayed as RMS values of the secondary
side of CT.
Equipment samples 24 points per cycle. The RMS value is calculate in each interval and the LCD
display will be updated in every 0.5 second.
Users can view the measured data on LCD by navigating the menu Measurements, or by
PCS-PC software or substation automatic system (SAS) software.
PCS-915 has two DSP module which are protection calculation module (DSP module 1) and fault
detector calculation module (DSP module 2) The sampling values of both modules can be
displayed on LCD through different access menu.
5.2.1 Analogue input quantities of DSP module 1 and DSP module 2 (Have been
converted to the referenced side)
Item
Rotation
Description
Id_CZ
A,B,C
Id_BBx
A,B,C
UP_BBx
A,B,C
IP_Bayxx
A,B,C
Access path:
MainMenuMeasurementsProt MeasurementsMeasured Values
MainMenuMeasurementsFD MeasurementsMeasured Values
5-1
Date: 2013-06-03
value, the phase A current of the bay (takes the bay whose number is minimal) will be taken as a
reference.
Item
Rotation
Description
If the phase A voltage of BB1 is taken as a reference, the displayed value
ofAngRef is 1, if phase A voltage of BB2 is taken as a reference, the
displayed value of AngRef is 2. If phase A voltage of BB1 and BB2
are all smaller than a certain value, the displayed value of AngRef is
AngRef
0.
If the phase A current of bay m is taken as a reference, the displayed
value of AngRef is m (m=01, 02, 03, ), if all the currents are
smaller than a certain value, the displayed value of AngRef is 0.
Ang(IP)_Bayxx
A,B,C
Ang(UP)_BBx
A,B,C
Access path:
MainMenuMeasurementsProt MeasurementsPhase Angle
MainMenuMeasurementsFD MeasurementsPhase Angle
Rotation
Upp_BBx
AB, BC, CA
Description
Phase-to-phase voltage of BBx (x=1 or 2)
I2_Bayxx
3I0_Bayxx
U2_BBx
3U0_BBx
Access path:
MainMenuMeasurementsProt MeasurementsCal Values
MainMenuMeasurementsFD MeasurementsCal Values
5-2
When binary input status changes, the changed information will be displayed on LCD and logged
as binary input change report at the same time.
2)
The fault detector element operates along with the operation of protective elements.
1.
The equipment can store 32 pieces of trip reports in non-volatile memory. If a new fault occurs
when the spaces are fully occupied, the oldest will be overwritten by the latest one.
A complete trip record includes the following items:
1)
Sequence number
Each operation will be recorded with a sequence number in the report and displayed on LCD
screen.
2)
The time resolution is 1 ms using the relay internal clock. Initiating date and time is when a fault
detector picks up. The relative time is the time when protection element operates to send tripping
5-3
Date: 2013-06-03
Faulty phase
The faulty phase detected by the operating element is shown in the record report.
4)
Operating time
It is the relative time when protection element operates to send tripping signal relative to fault
detector element operating, the operating time of output relay is not included.
5)
Protection element
The protection element that issues the tripping command will be shown. If no protection element
operates to trip but only fault detector element operates, the fault report will record the title of fault
detector element.
6)
Tripping element
MON module of the relay can store 32 pieces of fault waveform oscillogram in non-volatile memory.
If a new fault occurs when 32 fault waveform recorders have been stored, the oldest will be
overwritten by the latest one.
Each fault record consists of all analog and digital quantities related to protection, such as original
current and voltage, differential current, alarm elements, and binary inputs and etc.
Each time recording includes 2-cycle waveform before a fault detector pickup, and up to 250
cycles can be recorded.
5-4
6 Hardware
6 Hardware
Table of Contents
6 Hardware ......................................................................................... 6-a
6.1 General Description ........................................................................................ 6-1
6.2 Plug-in Module Terminal Definition ............................................................... 6-3
6.2.1 PWR Plug-in Module (Power Supply) ................................................................................. 6-3
6.2.2 MON Plug-in Module (Monitor) ............................................................................................ 6-5
6.2.3 DSP Plug-in Module 1 (Protection Calculation) .................................................................. 6-8
6.2.4 DSP Plug-in Module 2 (Fault Detector) ............................................................................... 6-8
6.2.5 BI Plug-in Module (Binary Input) ......................................................................................... 6-8
6.2.6 BO Plug-in Module (Binary Output) ................................................................................... 6-16
6.2.7 AI Plug-in Module (Analog Input)....................................................................................... 6-22
List of Figures
Figure 6.1-1 Front view of PCS-915 ........................................................................................... 6-2
Figure 6.1-2 Typical rear view of PCS-915 ................................................................................ 6-3
Figure 6.2-1 View of PWR plug-in module ................................................................................ 6-4
Figure 6.2-2 Output contacts of PWR plug-in module............................................................. 6-4
Figure 6.2-3 View of MON plug-in module ................................................................................ 6-6
Figure 6.2-4 Connection of communication terminal .............................................................. 6-8
Figure 6.2-5 Pin definition of binary input module NR1502D ................................................. 6-9
Figure 6.2-6 Pin definition of binary input module NR1502AS............................................. 6-11
Figure 6.2-7 Pin definition of tripping output module NR1547 ................................................. 6-17
Figure 6.2-8 Pin definition of signal output module NR1548A ................................................. 6-21
Figure 6.2-9 Pin definition of the first AC analog input module ............................................... 6-22
Table of Tables
Table 6.2-1 Terminal definition and description of PWR plug-in module .............................. 6-4
6-a
Date: 2012-08-31
6 Hardware
6-b
6 Hardware
Module description
10
MON module provides management function, completed event record, setting management,
and etc.
DSP modules can provide filtering, sampling, protection calculation and fault detector
calculation.
AI module converts AC current and voltage to low voltage signals by current transformers
and voltage transformers respectively.
6-1
Date: 2012-08-31
6 Hardware
BO signal module provides all kinds of signal output contacts, including annunciation signals,
remote signals, fault and disturbance signals, operation abnormal signals and etc.
HMI module is comprised of LCD, keypad, LED indicator and test serial ports.
PCS-915
HEALTHY
BUSBAR PROTECTION
MISC ALM
ENT
C
BBP TRIP
BFP TRIP
MISC TRIP
ES
DS ALM
GR
P
PT/CT ALM
6-2
6 Hardware
Slot No.
01
02
03
NR1102D
NR1151D
04
NR1151D
05
06
07
08
09
10
11
12
13
14
15
NR1547
NR1547
NR1547
NR1547
P1
NR1301A
5V
BJ
BJJ BSJ
1
2
BO_COM1
BO_FAIL
BO_ALM
BO_COM2
BO_FAIL
BO_ALM
OPTO+
OPTO-
NR1401
NR1401
DANGER
Slot No.
16
17
NR1401
DANGER
18
19
NR1401
DANGER
20
21
NR1401
DANGER
22
NR1401
DANGER
23
24
25
NR1401
DANGER
26
27
10
PWR+
11
PWR-
12
GND
NR1547
NR1547
NR1548A
30
31
32
DANGER
28
29
6-3
Date: 2012-08-31
6 Hardware
A 12-pin connector is fixed on PWR module. The terminal definition of the connector is described
as below.
NR1301
5V OK
ALM
BO_ALM BO_FAIL
ON
OFF
BO_COM1
BO_FAIL
BO_ALM
BO_COM2
BO_FAIL
BO_ALM
OPTO+
OPTO-
9
10 PWR+
11 PWR12 GND
01
BO_FAIL
02
BO_ALM
03
04
BO_FAIL
05
BO_ALM
06
Symbol
Description
01
BO_COM1
Common terminal 1
02
BO_FAIL
03
BO_ALM
04
BO_COM2
Common terminal 2
05
BO_FAIL
6-4
6 Hardware
Terminal No.
Symbol
Description
06
BO_ALM
07
OPTO+
08
OPTO-
09
Blank
Not used
10
PWR+
11
PWR-
12
GND
Note!
The standard rated voltage of PWR module is self-adaptive to 88~300 Vdc. If input voltage
is out of range, an alarm signal (Fail_Device) will be issued. For non-standard rated
voltage power supply module please specify when ordering, and check if the rated voltage
of power supply module is the same as the voltage of power source before the device
being put into service.
PWR module provides terminal 12 and grounding screw for device grounding. Terminal 12
shall be connected to grounding screw and then connected to the earth copper bar of
panel via dedicated grounding wire.
Effective grounding is the most important measure for a device to prevent EMI, so effective
grounding must be ensured before the device is put into service.
PCS-915, like almost all electronic relays, contains electrolytic capacitors. These
capacitors are well known to be subject to deterioration over time if voltage is not applied
periodically. Deterioration can be avoided by powering the relays up once a year.
6-5
Date: 2012-08-31
6 Hardware
NR1102A
ETHERNET
NR1102B
ETHERNET
NR1102C
ETHERNET
NR1102D
NR1102H
NR1102I
TX
TX
RX
RX
TX
TX
ETHERNET
NR1101E
ETHERNET
RX
RX
ETHERNET
ETHERNET
Memory
Interface
Terminal No.
2 RJ45 Ethernet
RS-485
NR1102A
64M DDR
To SCADA
01
SYN+
02
SYN-
To
03
SGND
synchronization
05
RTS
06
TXD
07
SGND
4 RJ45 Ethernet
RS-485
64M DDR
To printer
Cable
To SCADA
01
SYN+
02
SYN-
To
03
SGND
synchronization
05
RTS
06
TXD
07
SGND
2 RJ45 Ethernet
128M DDR
clock
clock
04
RS-232
NR1102C
Physical Layer
04
RS-232
NR1102B
Usage
RS-485
To printer
Cable
To SCADA
01
SYN+
02
SYN-
To
03
SGND
synchronization
clock
04
6-6
6 Hardware
RS-232
05
RTS
06
TXD
07
SGND
4 RJ45 Ethernet
RS-485
NR1102D
128M DDR
128M DDR
Cable
To SCADA
01
SYN+
02
SYN-
To
03
SGND
synchronization
clock
04
RS-232
NR1102H
To printer
05
RTS
06
TXD
07
SGND
To printer
Cable
2 RJ45 Ethernet
To SCADA
2 FO Ethernet
To SCADA
Optical fibre SC
RS-485
01
SYN+
02
SYN-
To
03
SGND
synchronization
clock
04
RS-232
NR1102I
128M DDR
05
RTS
06
TXD
07
SGND
To printer
Cable
2 RJ45 Ethernet
To SCADA
2 FO Ethernet
To SCADA
Optical fibre ST
RS-485
01
SYN+
02
SYN-
To
03
SGND
synchronization
clock
04
RS-232
05
RXD
06
TXD
07
SGND
2 RJ45 Ethernet
RS-485
To printer
Cable
To SCADA
01
02
03
SGND
To SCADA
04
NR1101E
128M DDR
RS-485
05
06
07
SGND
To SCADA
08
RS-485
09
SYN+
10
SYN-
To
11
SGND
synchronization
RTS
To printer
clock
12
RS-232
13
Cable
6-7
Date: 2012-08-31
6 Hardware
14
TXD
15
SGND
16
The correct connection is shown in Figure 6.2-4. Generally, the shielded cable with two pairs of
twisted pairs inside shall be applied. One pair of the twisted pairs are respectively used to connect
the + and terminals of difference signal. The other pair of twisted pairs are used to connect
the signal ground of the communication interface. The module reserves a free terminal for all the
communication ports. The free terminal has no connection with any signal of the device, and it is
used to connect the external shields of the cable when connecting multiple devices in series. The
external shield of the cable shall be grounded at one of the ends only.
Twisted pair wire
01
02
SGND
03
COM
04
01
SYN-
02
SGND
03
Clock SYN
04
Cable
05
TXD
06
SGND
07
RTS
6-8
6 Hardware
10
11
12
13
15
16
24/48V-
24/48V+
14
18
17
20
19
22
21
24
23
26
25
28
27
30
29
Symbol
Description
01
BI_Pulse_GPS
02
BI_Print
03
BI_Maintenance
04
BI_RstTarg
05
BI_ConfirmDS
06
Blank
Blank
07
EBI_BBP
08
EBI_BFP
09
EBI_SOTF_BC
10
EBI_OC_BC
11
EBI_PD_BC
12
Reserved
Reserved
6-9
Date: 2012-08-31
6 Hardware
Pin No.
Symbol
Description
13
Blank
Blank
14
Opto+
Positive pole of power supply for low voltage opto-couplers (DC 24/48V)
15
Opto-
Negative pole of power supply for low voltage opto-couplers (DC 24/48V)
16
Blank
Blank
17
Reserved
Reserved
18
Reserved
Reserved
19
Reserved
Reserved
20
Reserved
Reserved
21
Reserved
Reserved
22
EBI_IntLink_Mode
23
Reserved
Reserved
24
Reserved
Reserved
25
EBI_NegPolar_CT_BT
26
Reserved
27
EBI_BT_BC
28
Reserved
Reserved
29
Reserved
Reserved
Binary input to confirm BB1 and BB2 are under inter-connected operation
mode
6-10
6 Hardware
10
11
12
13
110/220V+
14
15
110/220V-
16
18
17
20
19
22
21
24
23
26
25
28
27
30
29
Symbol
Description
01
BI_52b_BC
02
Reserved
Reserved
03
BI_52a_BC
04
BI_PD_BC
05
Reserved
Reserved
06
Reserved
Reserved
07
Reserved
Reserved
08
Reserved
Reserved
09
Reserved
Reserved
10
Reserved
Reserved
11
Reserved
Reserved
12
Reserved
Reserved
6-11
Date: 2012-08-31
6 Hardware
Pin No.
Symbol
Description
14
Opto+
15
Opto-
17
BI_Blk_BBP
18
BI_Rls_VCE_BFP_Trans
19
Reserved
20
EBI_Decoupled_BC
21
Reserved
Reserved
22
Reserved
Reserved
23
Reserved
Reserved
24
Reserved
Reserved
25
BI_52a_DSBB1_BT
26
BI_52a_DSBB2_BT
27
Reserved
Reserved
28
Reserved
Reserved
29
Reserved
Reserved
The binary input for releasing voltage blocking element for main
transformer bays
Reserved
Binary input to confirm BB1 and BB2 are separated as two
independent busbars
Symbol
Description
01
BI_BFI_Bay02
02
BI_BFI_Bay03
03
BI_BFI_Bay14
04
BI_BFI_Bay15
05
BI_A_BFI_Bay04
06
BI_B_BFI_Bay04
07
BI_C_BFI_Bay04
08
BI_BFI_Bay04
09
BI_A_BFI_Bay05
10
BI_B_BFI_Bay05
11
BI_C_BFI_Bay05
12
BI_BFI_Bay05
14
Opto+
15
Opto-
17
BI_A_BFI_Bay06
18
BI_B_BFI_Bay06
19
BI_C_BFI_Bay06
20
BI_BFI_Bay06
21
BI_A_BFI_Bay07
22
BI_B_BFI_Bay07
23
BI_C_BFI_Bay07
6-12
6 Hardware
Pin No.
Symbol
Description
24
BI_BFI_Bay07
25
BI_A_BFI_Bay08
26
BI_B_BFI_Bay08
27
BI_C_BFI_Bay08
28
BI_BFI_Bay08
29
Reserved
Reserved
Symbol
Description
01
BI_A_BFI_Bay09
02
BI_B_BFI_Bay09
03
BI_C_BFI_Bay09
04
BI_BFI_Bay09
05
BI_A_BFI_Bay10
06
BI_B_BFI_Bay10
07
BI_C_BFI_Bay10
08
BI_BFI_Bay10
09
BI_A_BFI_Bay11
10
BI_B_BFI_Bay11
11
BI_C_BFI_Bay11
12
BI_BFI_Bay11
14
Opto+
15
Opto-
17
BI_A_BFI_Bay12
18
BI_B_BFI_Bay12
19
BI_C_BFI_Bay12
20
BI_BFI_Bay12
21
BI_A_BFI_Bay13
22
BI_B_BFI_Bay13
23
BI_C_BFI_Bay13
24
BI_BFI_Bay13
25
BI_A_BFI_Bay16
26
BI_B_BFI_Bay16
27
BI_C_BFI_Bay16
28
BI_BFI_Bay16
29
Reserved
Reserved
Symbol
Description
01
BI_A_BFI_Bay17
02
BI_B_BFI_Bay17
6-13
Date: 2012-08-31
6 Hardware
Pin No.
Symbol
Description
03
BI_C_BFI_Bay17
04
BI_BFI_Bay17
05
BI_A_BFI_Bay18
06
BI_B_BFI_Bay18
07
BI_C_BFI_Bay18
08
BI_BFI_Bay18
09
BI_A_BFI_Bay19
10
BI_B_BFI_Bay19
11
BI_C_BFI_Bay19
12
BI_BFI_Bay19
14
Opto+
15
Opto-
17
BI_A_BFI_Bay20
18
BI_B_BFI_Bay20
19
BI_C_BFI_Bay20
20
BI_BFI_Bay20
21
BI_A_BFI_Bay21
22
BI_B_BFI_Bay21
23
BI_C_BFI_Bay21
24
BI_BFI_Bay21
25
BI_A_BFI_Bay22
26
BI_B_BFI_Bay22
27
BI_C_BFI_Bay22
28
BI_BFI_Bay22
29
Reserved
Reserved
Symbol
Description
01
BI_A_BFI_Bay23
02
BI_B_BFI_Bay23
03
BI_C_BFI_Bay23
04
BI_BFI_Bay23
05
BI_A_BFI_Bay24
06
BI_B_BFI_Bay24
07
BI_C_BFI_Bay24
08
BI_BFI_Bay24
09
BI_A_BFI_Bay25
10
BI_B_BFI_Bay25
11
BI_C_BFI_Bay25
12
BI_BFI_Bay25
14
Opto+
6-14
6 Hardware
Pin No.
Symbol
Description
15
Opto-
17
BI_A_BFI_BT
18
BI_B_BFI_BT
19
BI_C_BFI_BT
20
BI_BFI_BT
21
Reserved
Reserved
22
Reserved
Reserved
23
Reserved
Reserved
24
Reserved
Reserved
25
BI_BFI_BC_1
26
Reserved
Reserved
27
Reserved
Reserved
28
Reserved
Reserved
29
Reserved
Reserved
Symbol
Description
01
BI_52a_DSBB1_Bay02
02
BI_52a_DSBB2_Bay02
03
BI_52a_DSBB1_Bay03
04
BI_52a_DSBB2_Bay03
05
BI_52a_DSBB1_Bay04
06
BI_52a_DSBB2_Bay04
07
BI_52a_DSBB1_Bay05
08
BI_52a_DSBB2_Bay05
09
BI_52a_DSBB1_Bay06
10
BI_52a_DSBB2_Bay06
11
BI_52a_DSBB1_Bay07
12
BI_52a_DSBB2_Bay07
14
Opto+
15
Opto-
17
BI_52a_DSBB1_Bay08
18
BI_52a_DSBB2_Bay08
19
BI_52a_DSBB1_Bay09
20
BI_52a_DSBB2_Bay09
21
BI_52a_DSBB1_Bay10
22
BI_52a_DSBB2_Bay10
6-15
Date: 2012-08-31
6 Hardware
Pin No.
Symbol
Description
23
BI_52a_DSBB1_Bay11
24
BI_52a_DSBB2_Bay11
25
BI_52a_DSBB1_Bay12
26
BI_52a_DSBB2_Bay12
27
BI_52a_DSBB1_Bay13
28
BI_52a_DSBB2_Bay13
29
Reserved
Reserved
Symbol
Description
01
BI_52a_DSBB1_Bay14
02
BI_52a_DSBB2_Bay14
03
BI_52a_DSBB1_Bay15
04
BI_52a_DSBB2_Bay15
05
BI_52a_DSBB1_Bay16
06
BI_52a_DSBB2_Bay16
07
BI_52a_DSBB1_Bay17
08
BI_52a_DSBB2_Bay17
09
BI_52a_DSBB1_Bay18
10
BI_52a_DSBB2_Bay18
11
BI_52a_DSBB1_Bay19
12
BI_52a_DSBB2_Bay19
14
Opto+
15
Opto-
17
BI_52a_DSBB1_Bay20
18
BI_52a_DSBB2_Bay20
19
BI_52a_DSBB1_Bay21
20
BI_52a_DSBB2_Bay21
21
BI_52a_DSBB1_Bay22
22
BI_52a_DSBB2_Bay22
23
BI_52a_DSBB1_Bay23
24
BI_52a_DSBB2_Bay23
25
BI_52a_DSBB1_Bay24
26
BI_52a_DSBB2_Bay24
27
BI_52a_DSBB1_Bay25
28
BI_52a_DSBB2_Bay25
29
Reserved
Reserved
6 Hardware
(NO) tripping output contacts and all the output contacts provided by NR1547 will be controlled by
positive power supply of fault detector.
A 30-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
NR1547
BO_Trp_1
01
BO_Trp_1
02
BO_Trp_2
03
BO_Trp_2
04
BO_Trp_3
05
BO_Trp_3
06
BO_Trp_4
07
BO_Trp_4
08
BO_Trp_5
09
BO_Trp_5
10
BO_Trp_6
11
BO_Trp_6
12
BO_Trp_7
13
BO_Trp_7
14
BO_Trp_8
15
BO_Trp_8
16
BO_Trp_9
17
BO_Trp_9
18
BO_Trp_10
19
BO_Trp_10
20
BO_Trp_11
21
BO_Trp_11
22
BO_Trp_12
23
BO_Trp_12
24
BO_Trp_13
25
BO_Trp_13
26
BO_Trp_14
27
BO_Trp_14
28
BO_Trp_15
29
BO_Trp_15
30
BO_Trp_1
BO_Trp_2
BO_Trp_3
BO_Trp_4
BO_Trp_5
BO_Trp_6
BO_Trp_7
BO_Trp_8
BO_Trp_9
BO_Trp_10
BO_Trp_11
BO_Trp_12
BO_Trp_13
BO_Trp_14
BO_Trp_15
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
Symbol
Description
01~02
BO_TrpBay01_1
03~04
BO_TrpBay01_2
05~06
BO_TrpBay02_1
07~08
BO_TrpBay02_2
09~10
BO_TrpBay03_1
11~12
BO_TrpBay03_2
6-17
Date: 2012-08-31
6 Hardware
Pin No.
Symbol
Description
13~14
BO_TrpBay04_1
15~16
BO_TrpBay04_2
17~18
BO_TrpBay05_1
19~20
BO_TrpBay05_2
21~22
BO_TrpBay06_1
23~24
BO_TrpBay06_2
25~26
BO_TrpBay07_1
27~28
BO_TrpBay07_2
29~30
BO_TrpBay08_1
Symbol
Description
01~02
BO_TrpBay08_2
03~04
BO_TrpBay09_1
05~06
BO_TrpBay09_2
07~08
BO_TrpBay10_1
09~10
BO_TrpBay10_2
11~12
BO_TrpBay11_1
13~14
BO_TrpBay11_2
15~16
BO_TrpBay12_1
17~18
BO_TrpBay12_2
19~20
BO_TrpBay13_1
21~22
BO_TrpBay13_2
23~24
BO_TrpBay14_1
25~26
BO_TrpBay14_2
27~28
BO_TrpBay15_1
29~30
BO_TrpBay15_2
Symbol
Description
01~02
BO_TrpBay16_1
03~04
BO_TrpBay16_2
05~06
BO_TrpBay17_1
07~08
BO_TrpBay17_2
09~10
BO_TrpBay18_1
11~12
BO_TrpBay18_2
13~14
BO_TrpBay19_1
15~16
BO_TrpBay19_2
17~18
BO_TrpBay20_1
6-18
6 Hardware
Pin No.
Symbol
Description
19~20
BO_TrpBay20_2
21~22
BO_TrpBay21_1
23~24
BO_TrpBay21_2
25~26
BO_TrpBay22_1
27~28
BO_TrpBay22_2
29~30
BO_TrpBay23_1
Symbol
Description
01~02
BO_TrpBay23_2
03~04
BO_TrpBay24_1
05~06
BO_TrpBay24_2
07~08
BO_TrpBay25_1
09~10
BO_TrpBay25_2
11~12
BO_IntTrp_BFP_Bay02
13~14
BO_IntTrp_BFP_Bay03
15~16
BO_IntTrp_BFP_Bay14
17~18
BO_IntTrp_BFP_Bay15
19~20
BO_BBP_TrpBay02
21~22
BO_BBP_TrpBay03
23~24
BO_BBP_TrpBay14
25~26
BO_BBP_TrpBay15
27~28
Reserved
Reserved
29~30
Reserved
Reserved
Symbol
Description
01~02
BO_TrpBB1_1
03~04
BO_TrpBB1_2
05~06
BO_TrpBB2_1
07~08
BO_TrpBB2_2
09~10
Reserved
Reserved
11~12
Reserved
Reserved
13~14
Reserved
Reserved
15~16
Reserved
Reserved
17~18
Reserved
Reserved
6-19
Date: 2012-08-31
6 Hardware
Pin No.
Symbol
Description
19~20
Reserved
Reserved
21~22
Reserved
Reserved
23~24
Reserved
Reserved
25~26
Reserved
Reserved
27~28
Reserved
Reserved
29~30
Reserved
Reserved
Symbol
Description
Busbar differential protection operates to trip busbar No.1
01~02
BO_TrpBB1_BBP_1
03~04
BO_TrpBB1_BBP_2
05~06
BO_TrpBB2_BBP_1
07~08
BO_TrpBB2_BBP_2
09~10
Reserved
Reserved
11~12
Reserved
Reserved
13~14
BO_TrpBB1_BFP_1
15~16
BO_TrpBB1_BFP_2
17~18
BO_TrpBB2_BFP_1
19~20
BO_TrpBB2_BFP_2
21~22
Reserved
Reserved
23~24
Reserved
Reserved
25~26
BO_TrpBC/BS_1
27~28
BO_TrpBC/BS_2
29~30
Reserved
(first)
Busbar differential protection operates to trip busbar No.1
(second)
Busbar differential protection operates to trip busbar No.2
(first)
Busbar differential protection operates to trip busbar No.2
(second)
6 Hardware
01
BO_Signal_1
02
BO_Signal_2
03
BO_Signal_2
04
BO_Signal_3
05
BO_Signal_3
06
BO_Signal_4
07
BO_Signal_4
08
BO_Signal_5
09
BO_Signal_5
10
BO_Signal_6
11
BO_Signal_6
12
BO_Signal_7
13
BO_Signal_7
14
BO_Signal_8
15
BO_Signal_8
16
BO_Signal_9
17
BO_Signal_9
18
BO_Signal_10
19
BO_Signal_10
20
BO_Signal_11
21
BO_Signal_11
22
BO_Signal_12
23
BO_Signal_12
24
BO_Signal_13
25
BO_Signal_13
26
BO_Signal_14
27
BO_Signal_14
28
BO_Signal_15
29
BO_Signal_15
30
BO_Signal_1
BO_Signal_2
BO_Signal_3
BO_Signal_4
BO_Signal_5
BO_Signal_6
BO_Signal_7
BO_Signal_8
BO_Signal_9
BO_Signal_10
BO_Signal_11
BO_Signal_12
BO_Signal_13
BO_Signal_14
BO_Signal_15
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
Symbol
Description
01~02
BO_VT/CT_Alm_1
03~04
BO_VT/CT_Alm_2
05~06
BO_DS_Alm_1
07~08
BO_DS_Alm_2
09~10
BO_IntLink_Alm_1
11~12
BO_IntLink_Alm_2
13~14
Reserved
6-21
Date: 2012-08-31
6 Hardware
Pin No.
Symbol
15~16
Reserved
17~18
BO_TrpBB1_BBP
19~20
BO_TrpBB2_BBP
21~22
Reserved
23~24
BO_TrpBB1_BFP
25~26
BO_TrpBB2_BFP
27~28
Reserved
29~30
BO_TrpBC/BS
Description
Reserved
Busbar differential protection operates to trip busbar No.1
(magnetic latched contact)
Busbar differential protection operates to trip busbar No.2
(magnetic latched contact)
Reserved
Breaker failure protection operates to trip busbar No.1 (magnetic
latched contact)
Breaker failure protection operates to trip busbar No.2 (magnetic
latched contact)
Reserved
BC/BS protection operates or other protective element operates
to trip BC/BS (magnetic latched contact)
Ia_Bay01
01
Ib_Bay01
03
Ibn_Bay01
04
Ic_Bay01
05
Icn_Bay01
06
Ia_Bay02
07
Ian_Bay02
08
Ib_Bay02
09
Ibn_Bay02
10
Ic_Bay02
11
Icn_Bay02
12
Ia_Bay03
13
Ian_Bay03
14
Ib_Bay03
15
Ibn_Bay03
16
Ic_Bay03
17
Icn_Bay03
18
Ia_Bay04
19
Ian_Bay04
20
Ib_Bay04
21
Ibn_Bay04
22
Ic_Bay04
23
Icn_Bay04
24
Ian_Bay01
02
6-22
6 Hardware
Table 6.2-17 Pin definition of the first analog input module (slot 16,17)
Pin No.
Symbol
Description
01
Ia_Bay01
02
Ian_Bay01
03
Ib_Bay01
04
Ibn_Bay01
05
Ic_Bay01
06
Icn_Bay01
07
Ia_Bay02
08
Ian_Bay02
09
Ib_Bay02
10
Ibn_Bay02
11
Ic_Bay02
12
Icn_Bay02
13
Ia_Bay03
14
Ian_Bay03
15
Ib_Bay03
16
Ibn_Bay03
17
Ic_Bay03
18
Icn_Bay03
19
Ia_Bay04
20
Ian_Bay04
21
Ib_Bay04
22
Ibn_Bay04
23
Ic_Bay04
24
Icn_Bay04
Table 6.2-18 Pin definition of the second analog input module (slot 18,19)
Pin No.
Symbol
Description
01
Ia_Bay05
02
Ian_Bay05
03
Ib_Bay05
04
Ibn_Bay05
05
Ic_Bay05
06
Icn_Bay05
07
Ia_Bay06
08
Ian_Bay06
09
Ib_Bay06
10
Ibn_Bay06
11
Ic_Bay06
12
Icn_Bay06
13
Ia_Bay07
6-23
Date: 2012-08-31
6 Hardware
Pin No.
Symbol
Description
14
Ian_Bay07
15
Ib_Bay07
16
Ibn_Bay07
17
Ic_Bay07
18
Icn_Bay07
19
Ia_Bay08
20
Ian_Bay08
21
Ib_Bay08
22
Ibn_Bay08
23
Ic_Bay08
24
Icn_Bay08
Table 6.2-19 Pin definition of the third analog input module (slot 20,21)
Pin No.
Symbol
Description
01
Ia_Bay09
02
Ian_Bay09
03
Ib_Bay09
04
Ibn_Bay09
05
Ic_Bay09
06
Icn_Bay09
07
Ia_Bay10
08
Ian_Bay10
09
Ib_Bay10
10
Ibn_Bay10
11
Ic_Bay10
12
Icn_Bay10
13
Ia_Bay11
14
Ian_Bay11
15
Ib_Bay11
16
Ibn_Bay11
17
Ic_Bay11
18
Icn_Bay11
19
Ia_Bay12
20
Ian_Bay12
21
Ib_Bay12
22
Ibn_Bay12
23
Ic_Bay12
24
Icn_Bay12
Table 6.2-20 Pin definition of the fourth analog input module (slot 22,23)
Pin No.
01
Symbol
Ia_Bay13
Description
Phase A current from CT of bay 13 (polarity mark)
6-24
6 Hardware
Pin No.
Symbol
Description
02
Ian_Bay13
03
Ib_Bay13
04
Ibn_Bay13
05
Ic_Bay13
06
Icn_Bay13
07
Ia_Bay14
08
Ian_Bay14
09
Ib_Bay14
10
Ibn_Bay14
11
Ic_Bay14
12
Icn_Bay14
13
Ia_Bay15
14
Ian_Bay15
15
Ib_Bay15
16
Ibn_Bay15
17
Ic_Bay15
18
Icn_Bay15
19
Ia_Bay16
20
Ian_Bay16
21
Ib_Bay16
22
Ibn_Bay16
23
Ic_Bay16
24
Icn_Bay16
Table 6.2-21 Pin definition of the fifth analog input module (slot 24,25)
Pin No.
Symbol
Description
01
Ia_Bay17
02
Ian_Bay17
03
Ib_Bay17
04
Ibn_Bay17
05
Ic_Bay17
06
Icn_Bay17
07
Ia_Bay18
08
Ian_Bay18
09
Ib_Bay18
10
Ibn_Bay18
11
Ic_Bay18
12
Icn_Bay18
13
Ia_Bay19
14
Ian_Bay19
15
Ib_Bay19
16
Ibn_Bay19
6-25
Date: 2012-08-31
6 Hardware
Pin No.
Symbol
Description
17
Ic_Bay19
18
Icn_Bay19
19
Ia_Bay20
20
Ian_Bay20
21
Ib_Bay20
22
Ibn_Bay20
23
Ic_Bay20
24
Icn_Bay20
Table 6.2-22 Pin definition of the sixth analog input module (slot 26,27)
Pin No.
Symbol
Description
01
Ia_Bay21
02
Ian_Bay21
03
Ib_Bay21
04
Ibn_Bay21
05
Ic_Bay21
06
Icn_Bay21
07
Ia_Bay22
08
Ian_Bay22
09
Ib_Bay22
10
Ibn_Bay22
11
Ic_Bay22
12
Icn_Bay22
13
Ia_Bay23
14
Ian_Bay23
15
Ib_Bay23
16
Ibn_Bay23
17
Ic_Bay23
18
Icn_Bay23
19
Ia_Bay24
20
Ian_Bay24
21
Ib_Bay24
22
Ibn_Bay24
23
Ic_Bay24
24
Icn_Bay24
Table 6.2-23 Pin definition of the seventh analog input module (slot 28,29)
Pin No.
Symbol
Description
01
Ia_Bay25
02
Ian_Bay25
03
Ib_Bay25
04
Ibn_Bay25
6-26
6 Hardware
Pin No.
Symbol
Description
05
Ic_Bay25
06
Icn_Bay25
07
Ua_BB1
08
Uan_BB1
09
Ub_BB1
10
Ubn_BB1
11
Uc_BB1
12
Ucn_BB1
13
Ua_BB2
14
Uan_BB2
15
Ub_BB2
16
Ubn_BB2
17
Uc_BB2
18
Ucn_BB2
19
Reserved
Reserved
20
Reserved
Reserved
21
Reserved
Reserved
22
Reserved
Reserved
23
Reserved
Reserved
24
Reserved
Reserved
6-27
Date: 2012-08-31
6 Hardware
6-28
7 Settings
7 Settings
Table of Contents
7 Settings ........................................................................................... 7-a
7.1 System Settings .............................................................................................. 7-1
7.2 Device Settings ............................................................................................... 7-4
7.3 Busbar Protection Settings ............................................................................ 7-5
7.4 Breaker Failure Protection Settings .............................................................. 7-7
7.5 Logic Settings ................................................................................................. 7-9
7.6 Virtual Binary Input Settings ........................................................................ 7-10
7.7 Communication Settings ............................................................................... 7-11
7.8 Label Settings ............................................................................................... 7-15
7-a
Date: 2012-08-31
7 Settings
Settings are classified to two kinds, protection settings and common settings. Each protection
element has its independent setting menu. Common settings consist of device settings,
communication settings, label settings, system settings and VEBI settings.
PCS-915 has ten protection setting groups to coordinate with the different modes of power system
operation. One of these setting groups is assigned to be active. However, common settings are
shared by all protection setting groups.
All current settings in this chapter are secondary current converted from primary current by
reference CT ratio.
Setting list
No.
Item
Setting Range
Default Setting
Active_Grp
1~10
PrimaryEquip_ID
6 characters maximum
PCS915
U1n
1.0~1200kV
220.00kV
U2n
1~100V
57.70V
I1n_Bay01
0~9999A
1200A
I1n_Bay02
0~9999A
1200A
I1n_Bay03
0~9999A
1200A
I1n_Bay04
0~9999A
1200A
I1n_Bay05
0~9999A
1200A
10
I1n_Bay06
0~9999A
1200A
11
I1n_Bay07
0~9999A
1200A
12
I1n_Bay08
0~9999A
1200A
13
I1n_Bay09
0~9999A
1200A
14
I1n_Bay10
0~9999A
1200A
15
I1n_Bay11
0~9999A
1200A
16
I1n_Bay12
0~9999A
1200A
17
I1n_Bay13
0~9999A
1200A
18
I1n_Bay14
0~9999A
1200A
19
I1n_Bay15
0~9999A
1200A
20
I1n_Bay16
0~9999A
1200A
21
I1n_Bay17
0~9999A
1200A
22
I1n_Bay18
0~9999A
1200A
23
I1n_Bay19
0~9999A
1200A
24
I1n_Bay20
0~9999A
1200A
25
I1n_Bay21
0~9999A
1200A
26
I1n_Bay22
0~9999A
1200A
27
I1n_Bay23
0~9999A
1200A
28
I1n_Bay24
0~9999A
1200A
7-1
Date: 2012-08-31
7 Settings
No.
Item
Setting Range
Default Setting
29
I1n_Bay25
0~9999A
1200A
30
I1n_CT_Base
0~9999A
1200A
31
I2n_CT_Base
1A or 5A
1A
32
Opt_UnearthedSys_Mode
0, 1
1: unearthed; 0: earthed
33
En_SingleBB
0, 1
34
En_SingleBB_with_SingleBS
0, 1
35
Cfg_DS_BB1
00000000~01FFFFFE
36
Cfg_DS_BB2
00000000~01FFFFFE
Setting description
1.
[Active_Grp]
position
position
Number of active setting group; ten setting groups can be configured for busbar differential
protection and breaker failure protection, and only one is active at a time.
2.
[PrimaryEquip_ID]
[U1n]
[U2n]
Primary rated current of the CT of bay xx. It should be set as 0 if the corresponding bay is not
used.
6.
[I1n_CT_Base]
[I2n_CT_Base]
7-2
7 Settings
The rated secondary current of reference CT. This setting is used in case that the rated secondary
current of each feeder connected to busbar are different. Among these CTs, the CT with the most
applied ratio is taken as the reference CT.
8.
[Opt_UnearthedSys_Mode]
[En_SingleBB]
When PCS-915 is applied to single busbar arrangement, it should be set as 1. The feeder of
which the primary rated current is not zero will be regarded as connecting to the busbar.
10. [En_SingleBB_with_SingleBS]
When PCS-915 is applied to single busbar with single bus section arrangement, it should be set as
1, then the system setting [Cfg_DS_BBx] (x=1, 2) is used to indicate which busbar zone the
feeder is connected to.
If [En_SingleBB] and [En_SingleBB_with_SingleBS] are all set as 0, double busbars
arrangement will be taken as the actual busbar arrangement by the device.
11. Cfg_DS_BBx (x=1 or 2)
Disconnector position configuration setting of BBx. In the case of single busbar with bus section
arrangement, the setting is used to indicate which busbar zone the feeder is connected to. The
setting is consisted of 32 binary digits but 8 hexadecimal digits can be viewed through device LCD
screen. The definition of the system setting is as follows.
Bay 09
Bay 08
Bay 07
Bay 06
Bay 05
Bay 04
Bay 03
Bay 02
Bay 01
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
Bay 24
Bay 23
Bay 22
Bay 21
Bay 20
Bay 19
Bay 18
Bay 17
Bay 25
Bay 10
Bay 11
Bay 12
Bay 13
Bay 14
10
11
Bay 5
12
13
Bay 16
14
15
When the system setting [En_SingleBB_with_SingleBS] is set as 1, it is not needed that using
auxiliary contact of disconnector to identify the position of feeder. The feeder bay is connected to
BBx if corresponding binary digit of [Cfg_DS_BBx] is set as 1.
Generally, Bay 01 is connected with BC, so bit 0 of [Cfg_DS_BBx] is not used. For double-CT BC,
bay 01 and bay 02 will be occupied, so bit 0 and bit 1 of [Cfg_DS_BBx] are not used.
7-3
Date: 2012-08-31
7 Settings
Note!
The maximum short circuit current of various CT shall not exceed 30In. In order to ensure
accuracy, difference of various CT ratios shall not be too high. Maximum summation of
corrected secondary currents of various CT during short circuit condition shall not exceed
80In. All displayed current values include both the corrected secondary currents and
original currents.
Access path:
MainMenuSettingsSystem Settings
Setting list
No.
Item
Description
Setting Range
HDR_EncodedMode
GB18030, UTF-8
UTF-8.
2
Un_BinaryInput_Bx
Setting description
1.
0:24V, 1:48V
2:110V, 3:220V
[HDR_EncodeMode]
Default value of [HDR_EncodeMode] is 1((i.e. UTF-8 code) and please set it to 0 (i.e. GB18030)
according to the special requirement.
2.
[Un_BinaryInput_Bx]
The setting is used to set the voltage level of corresponding binary input module. For
high-voltage BI modules, 110V or 220V can be set according to the actual requirement. For
low-voltage BI modules, 24V or 48V can be set according to the actual requirement.
0: 24V
1: 48V
2: 110V
3: 220V
Access path:
7-4
7 Settings
Setting list
No.
Item
Description
Setting Range
I_Pkp_Pcnt_BBP
0.05In ~20In
I_OC_SOTF_BC
0.05In ~20In
I_OC_BC
0.05In ~20In
I_ROC_BC
0.05In ~20In
t_OC_BC
0~10.000s
I_ROC_PD_BC
0~20In
I_NegOC_PD_BC
0~20In
t_PD_BC
0~10.000s
I_Alm_SensCTS
0.05In ~20In
10
I_Alm_CTS
0.05In ~20In
11
V_UV_VCE_BBP
0~1.732U2n
12
V_ROV_VCE_BBP
0~U2n
13
V_NegOV_VCE_BBP
0~U2n
14
I_BFP_BC
0~20In
15
t_TrpBB_BFP_BC
0.01~10.00s
1.
Setting description
[I_Pkp_Pcnt_BBP]
It should ensure sensitive enough in minimum operation mode and should be greater than
maximum load current of its outlets.
2.
[I_OC_SOTF_BC]
It should make BC SOTF protection sensitive enough to operate when energizing busbar in
minimum operation mode.
3.
[I_OC_BC]
[I_ROC_BC]
It should make BC OC protection sensitive enough to operate when there is an earth fault
occurring in the end of feeder energized.
7-5
Date: 2012-08-31
7 Settings
5.
[t_OC_BC]
[I_ROC_PD_BC]
It should be greater than maximum unbalance residual current in maximum operation mode.
7.
[I_NegOC_PD_BC]
It should be greater than maximum unbalance negative sequence current in maximum operation
mode.
8.
[t_PD_BC]
It should be greater than maximum inconsistent time of three phase interrupters when bus coupler
breaker is in the process of being closed.
9.
[I_Alm_SensCTS]
It is used to better response the abnormality of CT circuit in light load feeder and shunt of CT
circuit, etc. It should be more sensitive than [I_Alm_CTS] and can be set as 1.5~2 times of
differential current displayed in maximum operation mode.
10.
[I_Alm_CTS]
[V_UV_VCE_BBP]
It should make BBP sensitive enough when there is a symmetric fault occurring in the busbar zone.
The recommended value is 35~40V. When the system setting [Opt_UnearthedSys_Mode] is set
as 1, the setting should be set as phase-to-phase voltage.
12.
[V_ROV_VCE_BBP]
It should make BBP sensitive enough when there is an unsymmetrical fault occurring in the busbar
zone and it should be larger than maximum unbalance residual voltage in normal operation mode.
The recommended value is 6~10V. When the system setting [Opt_UnearthedSys_Mode] is set as
1, the setting is invalid.
13.
[V_NegOV_VCE_BBP]
It should make BBP sensitive enough when there is an unsymmetrical fault occurring in the busbar
zone and it should be larger than the negative sequence component of maximum unbalance
voltage in normal operation mode. The recommended value is 4~8V.
14.
[I_BFP_BC]
It should be set as minimum fault current flowing through BC/BS breaker. The influence of power
system topology change on fault current after BBP operating shall be considered.
15.
[t_TrpBB_BFP_BC]
7 Settings
Access path
Setting list
Common BFP Settings
No.
Item
Description
Setting
Range
t_ReTrp_BFP
0~10s
t_TrpBC_BFP
0~10s
t_TrpBB_BFP
0~10s
V_UV_VCE_BFP
0~1.732U2n
V_ROV_VCE_BFP
0~U2n
V_NegOV_VCE_BFP
0~U2n
Item
Description
Settings
Range
I_OC_BFP_BT
0~20IN
I_ROC_BFP_BT
0~20IN
I_NegOC_BFP_BT
En_ROC_BFP_BT
En_NegOC_BFP_BT
Disable_VCE_BFP_BT
0~20IN
0 or 1
0 or 1
0 or 1
I_OC_BFP_Bayxx
0~20IN
I_ROC_BFP_Bayxx
0~20IN
I_NegOC_BFP_Bayxx
0~20IN
10
En_ROC_BFP_Bayxx
0 or 1
11
En_NegOC_BFP_Bayxx
0 or 1
12
Disable_VCE_BFP_Bayxx
1.
0 or 1
Settings description
[t_ReTrp_BFP]
It should be set as greater than 100ms and smaller than the setting i.e. [t_TrpBC_BFP]. The
recommended value is 0.15. The function of retripping target breaker can be disabled if it is set as
same as [t_TrpBC_BFP].
7-7
Date: 2012-08-31
7 Settings
2.
[t_TrpBC_BFP]
It should be greater than the summation of operating time of breaker and reset time of protective
device with certain margin. The recommended value is 250ms~350ms.
3.
[t_TrpBB_BFP]
Based on the premise of BC breaker tripped, it should be greater than the summation of operating
time of BC breaker and reset time of protective device with certain margin. It should be as short as
possible on the premise of losing selectivity. The recommended value is 500ms~600ms.
4.
[V_UV_VCE_BFP]
It should make BFP sensitive enough to operate when there is a symmetrical fault occurring in the
end of the longest feeder and not to operate in the lowest operation voltage. After the fault is
cleared, the protective device can reset reliably. When the logic setting i.e.
[Opt_UnearthedSys_Mode] is set as 1, it will be changed to phase-to-phase voltage. Please
refer to Section 3.4.3.
5.
[V_ROV_VCE_BFP]
It should make BFP sensitive enough to operate when there is an unsymmetrical fault occurring in
the end of the longest line and be greater than residual voltage in normal operation mode. When
the logic setting i.e. [Opt_UnearthedSys_Mode] is set as 1, it is invalid.
6.
[V_NegOV_VCE_BFP]
It should make BFP sensitive enough to operate when there is an unsymmetrical fault occurring in
the end of the longest line and be greater than negative sequence component of maximum
unbalance voltage in normal operation mode.
7.
It should make BFP sensitive enough to operate when there is a fault occurring in end of feeder or
in LV side of transformer if this feeder is transformer bay. It should be greater than maximum load
in normal operation mode.
8.
It should make BFP sensitive enough to operate when there is a single-phase earth fault occurring
in end of line or in LV side of transformer if this feeder is transformer bay. It should be greater than
the maximum unbalance residual current in normal operation mode.
9.
It should make BFP sensitive enough to operate when there is a phase-to-phase fault occurring in
end of line or in LV side of transformer if this feeder is transformer bay. It should be greater than
the maximum negative sequence unbalance current in normal operation mode.
10.
If phase current setting of BFP can not avoid the influence of load current, it should be set as 1.
7-8
7 Settings
11.
If phase current setting of BFP can not avoid the influence of load current and residual current
setting of BFP is not sensitive enough to meet the project requirement, it should be set as 1.
12.
If a fault occurs at LV side of transformer and the circuit breaker of HV side may fails to trip, feeder
BFP is needed to be initiated. In this case, HV side VCE may not pick up to release feeder BFP,
and therefore users can select feeder BFP not being controlled by VCE, i.e. connect the tripping
contact of HV side of transformer to the binary input [BI_Rls_VCE_BFP_Trans] to initate feeder
BFP and set the logic setting to 1.
Access path:
Item
Remark
En_BBP
En_BFP
En_SOTF_BC
En_OC_BC
En_PD_BC
En_BI_Blk_BBP
Setting Description
1.
[En_BI_Blk_BBP]
If it is set as 1, BBP will be blocked when the binary input [BI_Blk_BBP] from external protective
device is energized.
PCS-915A Busbar Protection
7-9
Date: 2012-08-31
7 Settings
Access Path:
Setting list
No.
Symbol
Range
Remark
Enable remote setting modification. Set it as 0 if only local
VEBI_RmtModifySettings
0, 1
VEBI_RmtChgSettingGrp
0, 1
VEBI_RmtCtrl
0, 1
VEBI_BBP
0, 1
VEBI_BFP
0, 1
VEBI_SOTF_BC
0, 1
VEBI_OC_BC
0, 1
7-10
7 Settings
the corresponding enable isolator link [EBI_OC_BC] and the
corresponding logic setting [En_OC_BC].
Virtual binary input to enable BC PD protection, the relation is
VEBI_PD_BC
0, 1
VEBI_Decoupled_BC
0, 1
10
VEBI_IntLink_Mode
0, 1
Access Path:
MainMenuSettingsVEBI Settings
Setting list
Table 7.7-1 Communication settings
No.
Settings item
Range
Description
000.000.000.000~
IP_LAN1
Mask_LAN1
IP_LAN2
Mask_LAN2
En_LAN2
0: disable, 1: enable
IP_LAN3
0: disable, 1: enable
Mask_LAN3
En_LAN3
0: disable, 1: enable
IP_LAN4
0: disable, 1: enable
10
Mask_LAN4
11
En_LAN4
255.255.255.255
000.000.000.000~
255.255.255.255
000.000.000.000~
255.255.255.255
000.000.000.000~
255.255.255.255
000.000.000.000~
255.255.255.255
000.000.000.000~
255.255.255.255
0: disable, 1: enable
7-11
Date: 2012-08-31
7 Settings
No.
Settings item
Range
Description
000.000.000.000~
12
Gateway
13
En_Broadcast
0: disable, 1: enable
14
Fmt_Net_103
0, 1
15
Addr_RS485A
0255
255.255.255.255
Gateway of router
Enable/disable sending message in broadcast
mode via network. (IEC103).
Time scale format of IEC 60870-5-103 protocol (for
Ethernet port).
Communication address between the protective
device with the SCADA or RTU via RS-485 serial
port 1.
16
Baud_RS485A
17
Protocol_RS485A
4800,9600,19200,
38400,57600,115200 bps
09
1.
Spontaneous events are sent in the format of FUN
18
Inf_RS485A_103
0, 1
19
Fmt_RS485A_103
0, 1
20
Addr_RS485B
0255
21
Baud_RS485B
22
Protocol_RS485B
4800,9600,19200,
38400,57600,115200 bps
02
23
Inf_RS485B_103
0, 1
24
Fmt_RS485B_103
0, 1
25
Threshold_Measmt
0~100%
26
Period_Measmt
0~65535s
27
Format_Measmt
0, 1
7-12
7 Settings
No.
Settings item
Range
Description
4800,9600,
28
Baud_Printer
19200,38400, 51600,
115200 bps
29
0: disable
En_AutoPrint
1: enable
Conventional
30
SAS
Opt_TimeSync
Advanced
equipment.
NoTImeSyn
31
IP_Server_SNTP
32
Opt_DisplayValue
Setting description
1.
000.000.000.000~
255.255.255.255
The
address
of
the
external
SNTP
clock
Primary value/
Second value
or secondary value
[En_LANx] (x= 2, 3, 4)
[En_Broadcast]
This setting is only used only for IEC 103 protocol. If NR network IEC103 protocol is used, the
setting must be set as 1.
0: the device does not send UDP messages through network;
1: the device sends UDP messages through network.
3.
Fmt_Net_103
If the setting is set as0, GDD data type of spontaneous events based on IEC 60870-5-103
protocol is 18 (automatic supervision report, binary input change report), 19 (tripping report), i.e.
4-byte time scale format.
If the setting is set as1, GDD data type of spontaneous events based on IEC 60870-5-103
protocol is 203 (automatic supervision report, binary input change report), 204 (tripping report), i.e.
7-byte time scale format.
4.
[Protocol_RS485x] (x=A, B)
7-13
Date: 2012-08-31
7 Settings
The setting is used to select the communication protocol of rear RS-485 serial port X.
0: IEC 60870-5-103 protocol
1: Reserved
2: Modbus protocol
5.
Inf_RS485A_103, Inf_RS485B_103
When spontaneous events are sent via generic services based on IEC 60870-5-103 protocol, this
setting should be setting as 0. When spontaneous events are sent in the format of FUN and INF
based on IEC 60870-5-103 protocol, this setting should be set as 1.
6.
Fmt_RS485A_103/Fmt_RS485B_103
[Format_Measmt]
The setting is used to select the format of measurement data sent to SCADA through IEC103
protocol.
0: GDD data type through IEC103 protocol is 12;
1: GDD data type through IEC103 protocol is 7, i.e. 754 shorth real number of IEEE standard.
8.
[En_AutoPrint]
If automatic print is required for disturbance report after protection operating, the setting should be
set as 1.
9.
[Opt_TimeSyn]
There are four selectons for clock synchronization of device, each selection includs different time
clock synchronization signals shown in following table.
Item
Description
PPS(RS-485): Pulse per second (PPS) via RS-485 differential level.
Conventional
SAS
7-14
7 Settings
Item
Description
IEEE1588: Clock message via IEEE1588.
Advanced
NoTimeSync
this option and the alarm message [Alm_TimeSync] will not be issued anymore.
Conventional mode and SAS mode are always be supported by device, but Advanced mdoe
is only supported when NET-DSP module is equipped. The alarm signal [Alm_TimeSyn] may be
issued to remind user loss of time synchronization signals.
1)
When SAS is selected, if there is no conventional clock synchronization signal, the device
will not send the alarm signal [Alm_TimeSyn]. When Conventionalmode is slected, if there is
no conventional clock synchronization signal, SASmode will be enabled automatically with
the alarm signal [Alm_TimeSyn] being issued simultaneously.
2)
3)
When NoTimeSyn mode is selected, the device will not send alarm signals without
NOTE! The clock message via IEC103 protocol is invalid when the device receives the
IRIG-B signal through RC-485 port.
10.
[IP_Server_SNTP]
It is the address of the SNTP time synchronization server which sends SNTP timing messages to
the relay or BCU.
Access Path:
MainMenuSettingsCommunication Settings
Setting list
Table 7.8-1 Setting list of lab settings
No.
Symbol
Default Setting
NameDef_Bus1
BB1
NameDef_Bus2
BB2
NameDef_Bay01
Bay01
NameDef_Bay02
Bay02
NameDef_Bay03
Bay03
NameDef_Bay04
Bay04
NameDef_Bay05
Bay05
Remark
They can be set by 6 characters at most.
The description parameter of each
feeder and busbar will influence the
display of all reports and meterings.
Taking default setting as an example to
introduce in this instruction manual.
7-15
Date: 2012-08-31
7 Settings
8
NameDef_Bay06
Bay06
NameDef_Bay07
Bay07
10
NameDef_Bay08
Bay08
11
NameDef_Bay09
Bay09
12
NameDef_Bay10
Bay10
13
NameDef_Bay11
Bay11
14
NameDef_Bay12
Bay12
15
NameDef_Bay13
Bay13
16
NameDef_Bay14
Bay14
17
NameDef_Bay15
Bay15
18
NameDef_Bay16
Bay16
19
NameDef_Bay17
Bay17
20
NameDef_Bay18
Bay18
21
NameDef_Bay19
Bay19
22
NameDef_Bay20
Bay20
23
NameDef_Bay21
Bay21
24
NameDef_Bay22
Bay22
25
NameDef_Bay23
Bay23
26
NameDef_Bay24
Bay24
27
NameDef_Bay25
Bay25
These setting are used to definite the description of the feeder and bus coupler.
Access Path:
MainMenuSettingsLabel Settings
7-16
8-a
Date: 2012-08-30
List of Figures
Figure 8.1-1 Front panel of 8U chassis ..................................................................................... 8-5
Figure 8.1-2 Keypad mounted on the front panel .................................................................... 8-6
Figure 8.1-3 the figure shows the LED indications ..................................................................... 8-7
Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel .................................. 8-8
Figure 8.1-5 Rear view and terminal definition of NR1102C ................................................... 8-9
Figure 8.2-1 Menu tree of PCS-915 .......................................................................................... 8-11
Figure 8.3-1 LCD display of single line diagram .................................................................... 8-19
Figure 8.3-2 LCD display 1 of trip report ................................................................................ 8-20
Figure 8.3-3 LCD display 2 of trip report and alarm report................................................... 8-21
Figure 8.3-4 LCD display of alarm report................................................................................ 8-22
Figure 8.3-5 Display of binary input change report ............................................................... 8-23
Figure 8.3-6 Display of control report ..................................................................................... 8-23
8-b
List of Tables
Table 8.1-1 Definition of the 8-core cable ................................................................................. 8-8
Table 8.3-1 User Operating event list ...................................................................................... 8-24
8-c
Date: 2012-08-30
8-d
A 320240 backlight LCD visible in dim lighting conditions for monitoring status, fault
diagnostics and setting, etc.
LED indicators on the front panel for denoting the status of this protection operation.
A 9-key keypad on the front panel of the device for full access to the device.
5
PCS-915
HEALTHY
BUSBAR PROTECTION
MISC ALM
GR
P
PT/CT ALM
DS ALM
BBP TRIP
BFP TRIP
MISC TRIP
ES
ENT
Description
20 LED indicators
A 9-key keypad
8.1.1 Functionality
The HMI module helps to view activated LED or a report display on the LCD after an
8-5
Date: 2012-08-30
incident occurred.
GR
P
ESC
The keypad contains nine keys with different function. Following figure shows the keypad and
keys.
ENT
+
-
Symbol
,
and
, arrow buttons
Description
+, -
ENT
GRP
ESC
Note!
8-6
MISC_ALM
VT/CT_ ALM
DS_ ALM
BBP_ TRIP
BFP_ TRIP
MISC_ TRIP
Display
Off
HEALTHY
Description
When the device is out of service or any hardware error is detected
during self-check.
Green
Off
Yellow
Off
Yellow
Off
Yellow
Off
Red
Off
Red
Off
MISC_ALM
VT/CT_ALM
DS_ALM
BBP_TRIP
BFP_TRIP
MISC_TRIP
Red
Note!
The HEALTHY LED can only be turned on by energizing the device again to restart the
relay.
The xx_TRIP LED is turned and latched once any protection element operates. The
8-7
Date: 2012-08-30
xx_TRIP LED can be turned off by energizing the resetting binary input [BI_RstTarg].
Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel
Core color
Function
Device side
Computer side
(Left)
(Right)
Orange
P1-1
P2-1
P1-2
P2-2
P1-3
P2-3
Blue
P1-4
P3-2
P1-5
P3-3
Green
P1-6
P2-6
P1-7
P3-5
the IP address and subnet mask of network A. (using network A to connect with PC)
PC: IP address is set as 198.87.96.102, subnet mask is set as 255.255.255.0
The IP address and subnet mask of protection device should be [IP_LAN1]= 198.87.96.XXX,
[Mask_LAN1]=255.255.255.0, [En_LAN1]=1. (XXX can be any value from 0 to 255 except 102)
If the logic setting [En_LAN1] is non-available, it means that network A is always enabled.
NR1102C
ETHERNET
Network A
Network B
SYN+
SYNSGND
GND
RXD
TXD
SGND
GND
Note!
If using other Ethernet port, for example, Ethernet B, the logic setting [En_LAN2] must be
set as 1.
8-9
Date: 2012-08-30
menus. Press to enter the main menu with the interface as shown in the following diagram:
Quick Menu
Language
Main Menu
For the first powered protective device, there is no recorded shortcut menu. Press to enter the
main menu with the interface as shown in the following diagram:
E
Measurements
Status
Records
Settings
Print
Local Cmd
Information
Test
Clock
Language
8-10
Information
Device Info
Version Info
Board Info
Settings
Measured Values
Phase Angle
Cal Values
System Settings
Prot Settings
BBP Settings
BFP Settings
FD Measurements
Measured Values
Phase Angle
Cal Values
Test
Device Test
Logic Settings
Prot Elements
All Test
Select Test
VEBI Settings
Product Setup
Superv Events
Device Settings
Communication Settings
Status
All Test
Select Test
Label Settings
Inputs
All Settings
Prot Inputs
Bay Inputs
Function Inputs
FD Inputs
Bay Inputs
Function Inputs
Contact Inputs
Superv State
IO Events
All Test
Select Test
Disturb Records
Superv Events
Internal Signal
IO Events
Zone Cal BI
Device Logs
Bay Info
Device Status
bay25
Waveforms
Diff Wave
bay02
Oscillogram1
Prot Superv
Oscillogram2
FD Superv
Oscillogram3
bay01
bus2
bus1
Oscillogram4
Oscillogram5
Records
Oscillogram6
Disturb Records
Superv Events
IEC103 Info
Cancel Print
Clock
IO Events
Device Logs
Local Cmd
Settings
Language
Reset Target
Trig Oscillograph
System Settings
Confirm DS
Prot Settings
Download
BBP Settings
BFP Settings
Logic Settings
VEBI Settings
Product Setup
Device Settings
Communication Settings
Label Settings
Copy Settings
Under the main interface, press to enter the main menu, and select submenu by pressing ,
and ENT. The command menu adopts a tree shaped content structure. The above diagram
provides the integral structure and all the submenus under menu tree of the protection device.
8.2.2 Measurements
This menu is used to display real time AC voltage and AC current sampled values of the protective
device. These data can help users to acquaint the operation condition of the protective device.
This menu comprises following submenus. Please refer to Section 5.2 about the details of
PCS-915A Busbar Protection
8-11
Date: 2012-08-30
sampled values.
No.
Item
Description
Prot Measurements
FD Measurements
Item
Description
Display measured analog values on protection DSP module (have been
Measured Values
Phase Angle
Cal Values
8.2.2.2 FD Measurements
The submenu FD Measurements has following lower submenus.
No.
Item
Description
Display measured analog values on fault detector DSP module (have been
Measured Values
Phase Angle
Cal Values
8.2.3 Status
This menu is used to display real time binary inputs and alarm signals of the protective device.
These data can help users to acquaint the operation condition of the protective device. This menu
comprises following submenus. Please refer to Section 6.2.5 about the details of binary inputs and
Section 4.5 about the details of alarm signals.
No.
Item
Description
Inputs
Superv State
8.2.3.1 Inputs
The submenu Inputs has following submenus.
No.
Item
Prot Inputs
FD Inputs
Description
Display the status of binary inputs that used for calculation of protection DSP
module
Display the status of binary inputs that used for calculation of fault detector
DSP module
8-12
Item
Contact Inputs
Description
Display the status of contact inputs
(1) The submenu Prot Inputs includes the following command menus.
No.
Item
Bay Inputs
Function Inputs
Description
Display the status of binary inputs about each bay on protection DSP module.
Display the status of function enabling binary inputs on protection DSP
module.
Item
Bay Inputs
Function Inputs
Description
Display the status of binary inputs about each bay on fault detector DSP
module.
Display the status of function enabling binary inputs on fault detector DSP
module.
Item
Description
Prot Superv
FD Superv
8.2.4 Records
This menu displays protection tripping report, self-supervision report, binary input change report
and control report. The protective device can store 1024 pieces of recorders for each kind of report
in non-volatile memory.
No.
Item
Description
Disturb Records
Superv Events
IO Events
Device Logs
8.2.5 Settings
This submenu is used to browse, modify and set all settings including device settings,
communication parameters, label settings, VEBI settings, system settings and protection settings.
The submenu Settings includes the following command menus.
8-13
Date: 2012-08-30
Item
Function description
System Settings
Prot Settings
VEBI Settings
Product Setup
Copy Settings
Item
Function description
Device Settings
Communication Settings
Label Settings
Item
Function description
BBP Settings
BFP Settings
Logic Settings
8.2.6 Print
This menu is used to print the self-supervision report, binary input change report, waveform and
the information related with settings, fault report and 103 protocol, and so on.
This menu includes the command menus and submenus as follows:
No.
1
Item
Device Info
Description
Print the description information of protective device.
Print settings, includes device settings, communication parameters, label
Settings
settings, VEBI settings, system settings, and protection settings. It can print
by different classifications as well as printing all settings of the device.
Besides, it can also print out the latest modified setting item.
Disturb Records
Superv Events
IO Events
Device Status
Waveforms
8-14
IEC103 Info
Cancel Print
8.2.6.1 Settings
The submenu Settings includes the following command menus.
No.
Item
Function description
System Settings
Prot Settings
VEBI Settings
Product Setup
All Settings
Latest Modified
Print the content of all settings including product setups, system settings,
protection settings and VEBI settings.
Print the content of the latest modified setting
(1) The submenu Product Setup includes the following command menus.
No.
Item
Function description
Device Settings
Communication Settings
Label Settings
(2) The submenu Prot Settings includes the following command menus.
No.
Item
Function description
BBP Settings
BFP Settings
Logic Settings
8.2.6.2 Waveforms
The submenu Waveforms has following submenus.
No.
Item
Description
Diff Wave
Oscillogram1
Oscillogram2
Oscillogram3
Oscillogram4
Oscillogram5
Oscillogram6
8-15
Date: 2012-08-30
Item
Function description
Reset Target
Reset the local signal, the signal indicator lamp and the LCD display.
Trig Oscillograph
Confirm DS
Download
8.2.8 Information
In this menu the LCD displays current working state of each intelligent module and software
information of DSP module, MON module and HMI module.
This menu includes the following command menus.
No.
Item
Function description
Display software information of DSP module, MON module and HMI module,
Version Info
Board Info
8.2.9 Test
This menu is used for developers to debug the program and for engineers to maintain the device.
It can be used to check module information and item fault message, and fulfill the communication
test function. Its also used to generate all kinds of report or event to transmit to the SAS without
any external input, so as to debug the communication on site.
This menu includes the following command menus.
No.
Item
Function description
Automatically generate all kinds of message to transmit to the backstage,
Device Test
Internal Signal
Display the calculated virtual binary input of bay n for differential circuit and
relevant information about each protected bay
Check the fault report one by one.
Item
Prot Elements
Superv Events
IO Events
Description
View the relevant information about tripping report (only used for debugging
persons)
View the relevant information about alarm report (only used for debugging
persons)
View the relevant information about binary input change report (only used
for debugging persons)
Item
Description
All Test
Select Test
Item
Description
All Test
Select Test
Item
Description
All Test
Select Test
Item
Zone Cal BI
Description
Display the calculated virtual binary input of bay n for differential circuit
Display the relevant information about each protected bay. Please refer to
Bay Info
Section 5.2 about the details of sampled values, Section 6.2.5 about the
details of binary inputs and Section 4.5 about the details of alarm signals.
The submenu Zone Cal BI will display the calculated virtual binary input of each bay for
differential circuit. It can help users to know the current composition of differential current. If the
value of the calculated virtual binary input of a bay for differential circuit is 1, it means that the
current of the bay is included in differential current.
Item
VBI_DSCZ_Bayxx
VBI_DZBBx_Bayxx
Description
Calculated binary input of bay xx for check zone differential circuit
Calculated binary input of bay xx for discriminating zone differential circuit of
BBx
8-17
Date: 2012-08-30
x=1 or 2
xx=01~25
The submenu Bay Info has following submenus.
No.
Item
Description
bus1
bus2
bay01
bay25
8.2.10 Clock
The time of internal clock can be viewed in Clock option. The time is displayed in the form
YY-MM-DD and hh:mm:ss. All values are presented with digits and can be modified.
8.2.11 Language
This menu is mainly used for set LCD display language.
8-18
Communication address
Description of BB No.1
Description of BC
Phase-A current of BC
2010-4-28 10:10:00
Comm_Addr:098
Fdr02
BC
0.01A
Fdr04
0.01A
Fdr06
0.00A
Grp:01
Fdr08
0.00A
0.01A
Disconnector (Closed)
BB1
Bus Coupler
means BC is open
BB2
Disconnector (Open)
means BC is closed
0.01A
Fdr03
Description of BB No.2
0.01A
Fdr05
0.00A
Fdr07
BB1 Volt:
57.70V
57.70V
57.70V
BB2 Volt:
57.70V
57.70V
57.70V
DI:
0.00A
0.00A
0.01A
Fdr09
0.01A
Middle part displays single line diagram of the busbar and the bays whose CT correction
coefficient is not zero. The description of each bay (at most 6 digits or characters, please refer to
Section 7.8) and feeder current is shown by the side of the corresponding feeder. Three-phase
voltage of BBx (BBx Volt and x=1 or 2), check zone differential current (DI), discriminating zone
differential current of BBx (BBx_DI and x=1 or 2) are shown under the single line diagram.
If the protective device receives the signal of IRIG-B for time synchronization and can correctly
decode it, S will be displayed on the top left corner of LCD
If all feeders can not displayed in one page, the single line diagram will move automatically and
circularly from right to left if no key is pressed, and will move to left quickly by pressing key
continuously, move to right quickly by pressing key continuously.
The displayed content of the interface contains: the current date and time of the protection device
(with a format of yy-mm-dd hh:mm:ss:), the currently valid setting group number, the three-phase
current and voltage sampling values of each side, differential current etc.
8-19
Date: 2012-08-30
Op_FD
A
Op_Trp_BB1_DPFC_BBP
0006ms
Id_max
1.05A
NO.005 2010-04-28 07:10:00:200 Disturb Records: shows the SOE number, the time when fault
detector picks up (the format is yearmonth-date and hour:minute:second:millisecond) and title
of the report.
0000ms Op_FD
0006ms A Op_Trp_BB1_DPFC_BBP
Bay01 Bay02 Bay03 Bay06
Bay12 Bay13 Bay15
0006ms Op_TrpBC_BBP
Id_max 1.05A
For the situation that the fault report and the self-check alarm report occur simultaneously in the
following figure, the upper half part is fault report, and the lower half part is self-check report. As to
the upper half part, it displays separately the record number of fault report, fault name, generating
time of fault report (with a format of yy-mm-dd hh:mm:ss:), protection element and tripping element.
If there is protection element, there is relative time on the basis of fault detector element and fault
phase. At the same time, if the protection element and tripping element are too much and can not
displayed in the upper half part, it will move automatically and circularly from top to bottom if no
key is pressed.
The displayed content of the lower half part is the alarm element. If the alarm element is more than
one, all the alarm elements will displayed circularly one by one.
8-20
Op_FD
A
Op_Trp_BB1_DPFC_BBP
0006ms
Id_max
1.05A
Superv Events
Alm_52a&52b_BC
Operation elements
No.
Item
Description
Op_TrpBB1_DPFC_BBP
Op_TrpBB2_DPFC_BBP
Op_TrpBB1_Pcnt_BBP
Op_TrpBB2_Pcnt_BBP
Op_TrpBC_BBP
Op_TrpBB_BFP_BC
Op_BFP_BB1
Op_BFP_BB2
Op_TrpBC_BFP
10
Op_Dly1_Pcnt_BBP
11
Op_Dly2_Pcnt_BBP
12
Op_IntTrp_BFP_Bayxx
13
Op_Retrip_Bayxx_BFP
14
Op_Retrip_BT_BFP
15
Op_TrpBC_PD
16
Op_TrpBC_OC
17
Op_TrpBC_ROC
18
Op_EFP_BC
19
Op_TrpBC_SOTF
8-21
Date: 2012-08-30
Item
Description
20
Op_FD
21
Op_ManTrigOscillog
2.
Trip elements
No.
1
Item
Trp_Bayxx
Description
Trip bay xx (xx=01, 02, , 25)
Superv Events
Alm_52b_BC
Superv Events
Alm_52b_BC
If view the corresponding alarm report from the submenu Superv Events under the menu of
Records, the SOE number and the real time of the report will be contained with the alarm report.
All the alarm elements have been listed in Chapter Automatic Supervision.
8-22
IO Events NO.26
2010-04-29 09:18:47:500
shows date and time when the report occurred, the format is
yearmonth-date and hour:minute:second:millisecond
EBI_BBP 0->1
shows the state change of binary input, including binary input name,
original state and final state
Binary inputs have been listed in input signal table in Chapter Hardware Description and virtual
binary inputs list in Chapter Setting and please refer to each protection element for details.
8-23
Date: 2012-08-30
2010-04-29 10:18:47:569
shows date and time when the report occurred, the format is
yearmonth-date and hour:minute:second:millisecond
Settings_Chgd
Message
Description
Reboot
Reset_Target
Settings_Chgd
ActiveGrp_Chgd
Report_Cleared
All reports have been deleted. (User operating event can not be deleted)
Waveform_Cleared
SubProcess_Exit
2.
Press the key or to move the cursor to the Measurements menu, and then
press the ENT or to enter the menu.
3.
Press the key or to move the cursor to any command menu item, and then press
ENT to enter submenu.
4.
Press the key or to page up/down (if all information cannot be displayed in one
display screen, one screen can display 14 lines of information at most).
5.
6.
Press the key ENT or ESC to exit this menu (returning to the Measurements menu).
2.
Press the key or to move the cursor to the Status menu, and then press the
ENT or to enter the menu.
3.
Press the key or to move the cursor to any command menu item, and then press
ENT to enter submenu.
4.
Press the key or to page up/down (if all information cannot be displayed in one
8-24
6.
Press the key ENT or ESC to exit this menu (returning to the Status menu).
2.
Press the key or to move the cursor to the Records menu, and then press the
key ENT or to enter the menu.
3.
Press the key or to move the cursor to any command menu, and then press the
key ENT to enter the submenu.
4.
5.
6.
7.
Press the key ENT or ESC to exit this menu (returning to the Records menu).
For the fault report, view the single item fault report by the command menu Disturb Record
Items, and the item fault report produces with change of any item of fault report. The item fault
report can save up to 1024 events.
The operation is as follows:
1.
2.
Press the key or to move the cursor to the Test menu, and then press the key
ENT or to enter the menu.
3.
Press the key or to move the cursor to the command menu Disturb Record
Items, and then press the ENT to enter the menu.
4.
5.
Press the key ESC to exit this menu (returning to the Test menu).
2.
Press the key or to move the cursor to the Settings menu, and then press
ENT or to enter the menu.
3.
Press the key or to move the cursor to any command menu, and then press
ENT to enter the menu.
8-25
Date: 2012-08-30
4.
5.
6.
7.
Press the key ESC to exit this menu (returning to the menu Settings).
Note!
If the displayed information exceeds 14 lines, the scroll bar will appear on the right side of
the LCD to indicate the quantity of all displayed information of the command menu and the
relative location of information where the current cursor points at.
2.
Press the key or to move the cursor to the Settings menu, and then press
ENT or to enter the menu.
3.
Press the key or to move the cursor to any command menu, and then press
ENT to enter the menu.
4.
5.
6.
7.
Press the key ESC to exit this menu (returning to the menu Settings ).
8.
1.
2.
Press the key or to move the cursor to the Settings menu, and then press
ENT or to enter the menu.
3.
Press the key or to move the cursor to the command menu System
Settings, and then press ENT to enter the menu.
4.
Move the cursor to the setting item to be modified, and then press the key ENT.
5.
Press the key or to modify the value (if the modified value is multi-bit, press
the key or to move the cursor to the digit bit, and then press the or to
modify the value), press the key ESC to cancel the modification and return to the
8-26
displayed interface of the command menu System Settings. Press the key ENT to
automatically exit this menu (returning to the displayed interface of the command
menu System Settings).
6.
Move the cursor to continue modifying other setting items. After all setting values are
modified, press the key , or ESC, and the LCD will display Save or Not?.
Directly press the ESC or press the key or to move the cursor. Select the
Cancel, and then press the key ENT to automatically exit this menu (returning to
the displayed interface of the command menu System Settings).
7.
Press the key or to move the cursor. Select No and press the key ENT, all
modified setting item will restore to its original value, exit this menu (returning to the
menu Settings).
8.
Press the key or to move the cursor to select Yes, and then press the key
ENT, the LCD will display password input interface.
Password:
9.
Note!
The above modification instructions are available for all setting items.
Note!
8-27
Date: 2012-08-30
After modifying the settings in menu System Settings or Prot Settings, the
HEALTHY indicator of the protection device will go out, and the protection device will
automatically restart and re-check the settings. The device will be blocked until the check
process is finished. If selecting the command menu of protection element such as BBP
Settings, the LCD will display the following interface:
2. BBP Settings
Please Select Group for Config
Active Group:
01
Selected Group:
01
Then move the cursor to the modified value and press ENT to enter. For example, if the setting
[I_Pkp_Pcnt_BBP] need to be modified, press the ENT to enter and the LCD will display the
interface as below. Press the or to modify the value and then press the ENT to enter.
I_Pkp_Pcnt_BBP
Current Value
5.00
Modified Value
005.00
Min Value
0.05
Max Value
20.00
10. If selecting the other menus, move the cursor to the setting to be modified, and then
8-28
2.
Press the key or to move the cursor to the Settings menu, and then press the
key ENT or to enter the menu;
3.
Press the key or to move the cursor to the command menu Copy Settings,
and then press the key ENT to enter the menu. The following display will be shown on
LCD.
Copy Settings
Active Group:
01
Copy To Group:
02
Press the key or to modify the value. Press the key ESC, and return to the
menu Settings. Press the ENT, the LCD will display the interface for password input,
if the password is incorrect, continue inputting it, press the key ESC to exit the
password input interface and return to the menu Settings. If the password is correct,
the LCD will display Copy Settings Success!, and exit this menu (returning to the menu
Settings).
2.
Press the key or to move the cursor to the Print menu, and then press the
ENT or to enter the menu.
3.
Press the key or to move the cursor to any command menu, and then press the
ENT to enter the menu.
8-29
Date: 2012-08-30
Selecting the command menu Superv Events or IO Events, and then press the
key or to move the cursor. Press the or to select the starting and
ending numbers of printing message. After pressing the key ENT, the LCD will
display Start Printing, and then automatically exit this menu (returning to the
menu Print). Press the key ESC to exit this menu (returning to the menu Print).
4.
If selecting the command menu IEC103 Info, Device Status or Device Info, press
the key ENT, the LCD will display Start printing.., and then automatically exit this menu
(returning to the menu Print).
5.
6.
After entering the submenu Settings, press the key or to move the cursor, and
then press the key ENT to print the corresponding default value. To select items to print:
Press the key or to select the setting group to print. After pressing the key ENT,
the LCD will display Start Printing, and then automatically exit this menu (returning to
the menu Settings). Press the key ESC to exit this menu (returning to the menu
Settings).
7.
After entering the submenu Waveforms, press the or to select the printed
waveform and press ENT to enter. With waveform data existing:
Press the key or to select pervious or next record. After pressing the key ENT,
the LCD will display Start Printing, and then automatically exit this menu (returning to
the menu Waveforms). If the printer does not complete its current print task and
re-start it for printing, and the LCD will display Printer Busy. Press the key ESC to
exit this menu (returning to the menu Waveforms). If there is no any waveform data,
the LCD will display No Waveform Data!.
2.
8-30
Active Group:
01
Change To Group:
02
Press the or to modify the value, and then press the key ESC to exit this menu
(returning to the main menu). After pressing the key ENT, the LCD will display the password
input interface. If the password is incorrect, continue inputting it, and then press the key ESC to
exit the password input interface and return to its original state. If the password is correct, the
HEALTHY indicator of the protection device will go out, and the protection device will re-check
the protection setting. If the check doesnt pass, the protection device will be blocked. If the check
is successful, the LCD will return to its original state.
2.
Press the , , , and key ENT; Press the key ESC to exit this menu
(returning to the original state). Press the key ENT to carry out the deletion.
8-31
Date: 2012-08-30
Note!
The operation of deleting report will delete all messages except for user operation reports
(i.e. control reports), including tripping reports, alarm reports and binary input change
reports. The deleted reports are irrecoverable, so the function shall be used with great
cautious.
2.
Press the key or to move the cursor to the Clock menu, and then press the key
ENT to enter clock display.
8-32
Clock
Year:
2010
Month:
04
Day:
28
Hour:
20
Minute:
59
Second:
14
3.
Press the key or to move the cursor to the date or time to be modified.
4.
Press the key or , to modify value, and then press the key ENT to save the
modification and return to the main menu.
5.
Press the key ESC to cancel the modification and return to the main menu.
2.
Press the key or to move the cursor to the Information menu, and then press
the key ENT or to enter the menu.
3.
Press the key or to move the cursor to the command menu Board Info, and
then press the ENT to enter the menu.
4.
5.
Press the key ENT or ESC to exit this menu (returning to the Information menu).
2.
Press the key or to move the cursor to the Information menu, and then press
the key ENT or to enter the menu.
3.
Press the key or to move the cursor to the command menu Version Info, and
then press the ENT to enter the menu.
8-33
Date: 2012-08-30
4.
5.
Press the key ENT or ESC to exit this menu (returning to the Information menu).
2.
Press the key or to move the cursor to the Test menu, and then press the key
ENT or to enter the menu.
3.
Select the command menu Prot Elements, Superv Events or IO Events, users
need to enter the submenu Device Test firstly.
4.
Select any command menu (takes Prot Elements as an example), press the key ENT,
two options All Test and Select Test are provided.
5.
If Select Test is selected, press the key ENT. Press the or to page up/down,
and then press the key or to move the scroll bar. Move the cursor to select the
corresponding protection element. Press the key ENT to execute the communication
test of this protection element, the substation automatic system (SAS) will receive the
corresponding fault report, and view the fault report produced by communication test in
the command menu Disturb Record Items.
6.
If All Test is selected, press the key ENT to execute the communication test of all
protection element one by one, the substation automatic system (SAS) will receive all the
fault report.
Note!
If selecting the Superv Events or IO Events, the substation automatic system can
receive the corresponding self-check report or binary signals, and the self-check report or
binary signals produced by communication test can also be viewed by the two command
menus of Superv Events and IO Events in the menu Records.
2.
Press the key or to move the cursor to the Language menu, then press ENT
to enter the menu and the following display will be shown on LCD.
8-34
English
3.
Press the key or to move the cursor to the preferred language and press the key
ENT to execute language switching. After language switching is finished, LCD will
return to the main menu, and the display language is changed. Otherwise, press ESC to
cancel language switching and return to the main menu.
Note!
The LCD interfaces provided in this chapter are only for references and available for
explaining specific definition of LCD. The actual displayed interfaces maybe different from
these.
8-35
Date: 2012-08-30
8-36
9 Communications
9 Communications
Table of Contents
9 Communications ............................................................................ 9-a
9.1 General Description ........................................................................................ 9-1
9.2 Rear Communication Port Information ......................................................... 9-1
9.2.1 RS-485 Interface.................................................................................................................. 9-1
9.2.2 Ethernet Interface ................................................................................................................ 9-3
9.2.3 IEC60870-5-103 Communication ........................................................................................ 9-4
9-a
Date: 2013-06-03
9 Communications
List of Figures
Figure 9.2-1 EIA RS-485 bus connection arrangements ......................................................... 9-2
Figure 9.2-2 Ethernet communication cable ............................................................................ 9-3
Figure 9.2-3 Ethernet communication structure ...................................................................... 9-4
9-b
9 Communications
9-1
Date: 2013-06-03
Master
EIA RS-485
9 Communications
120 Ohm
120 Ohm
Slave
Slave
Slave
9-2
9 Communications
It is extremely important that the 120 termination resistors are fitted. Failure to do so
will result in an excessive bias voltage that may damage the devices connected to the
bus.
As the field voltage is much higher than that required, NR cannot assume
responsibility for any damage that may occur to a device connected to the network as
a result of incorrect application of this voltage.
Ensure that the field voltage is not being used for other purposes (i.e. powering logic
inputs) as this may cause noise to be passed to the communication network.
9-3
Date: 2013-06-03
9 Communications
SCADA
Exchanger A
Exchanger B
Equipment
Equipment
Equipment
Initialization (reset)
Time synchronization
General interrogation
General commands
9-4
9 Communications
Disturbance records
9.3.2 Initialization
When the protective device is powered up, or the communication parameters are changed, a reset
command is required to initialize the communications. The protective device will respond to either
of the two reset commands (Reset CU or Reset FCB), the difference is that the Reset CU will clear
any unsent messages in the transmit buffer.
The protective device will respond to the reset command with an identification message ASDU 5,
the COT (Cause Of Transmission) of this response will be either Reset CU or Reset FCB
depending on the nature of the reset command.
9-5
Date: 2013-06-03
9 Communications
9-6
9 Communications
IEC 61850-5: Communications and requirements for functions and device models
IEC 61850-7-1: Basic communication structure for substation and feeder device - Principles
and models
IEC 61850-7-2: Basic communication structure for substation and feeder device - Abstract
communication service interface (ACSI)
IEC 61850-7-3: Basic communication structure for substation and feeder device Common
data classes
IEC 61850-7-4: Basic communication structure for substation and feeder device Compatible
logical node classes and data classes
IEC 61850-8-1: Specific Communication Service Mapping (SCSM) Mappings to MMS (ISO
9506-1 and ISO 9506-2) and to ISO/IEC 8802-3
IEC 61850-9-1: Specific Communication Service Mapping (SCSM) Sampled values over
serial unidirectional multidrop point to point link
IEC 61850-9-2: Specific Communication Service Mapping (SCSM) Sampled values over
ISO/IEC 8802-3
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC 61850 implementation obtain this document set.
MMS protocol
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. Actual IEC 61850-7-2 abstract services and objects are mapped to MMS protocol
services in IEC61850-8-1.
2.
Client/server
This is a connection-oriented type of communication. The connection is initiated by the client, and
communication activity is controlled by the client. IEC61850 clients are often substation computers
running HMI programs or SOE logging software. Servers are usually substation device such as
protection relays, meters, RTUs, transformer, tap changers, or bay controllers.
3.
Peer-to-peer
9-7
Date: 2013-06-03
9 Communications
A substation configuration language is a number of files used to describe IED and communication
system realized according to IEC 61850-5 and IEC 61850-7. Each configured device has an IEC
Capability Description (ICD) file and a Configured IED Description (CID) file. The substation single
line information is stored in a System Specification Description (SSD) file. The entire substation
configuration is stored in a Substation Configuration Description (SCD) file. The SCD file is the
combination of the individual ICD files and the SSD file, moreover, add communication system
parameters (MMS, GOOSE, control block, SV control block) and the connection relationship of
GOOSE and SV to SCD file.
MMXU.MX.Hz: frequency
9-8
9 Communications
RBRF:Breaker failure
The protection elements listed above contain start (pickup) and operate flags, instead of any
element has its own start (pickup) flag separately, all the elements share a common start (pickup)
flags PTRC.ST.Str.general. The operate flag for PDIF1 is PDIF1.ST.Op.general. For PCS-915
series relay protection elements, these flags take their values from related module for the
corresponding element. Similar to digital status values, the protection trip information is reported
via BRCB, and it also locates in LLN0.
9.5.3.4 LLN0 and Other Logical Nodes
Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address
common issues for Logical Devices. Most of the public services, the common settings, control
values and some device oriented data objects are available here. The public services may be
BRCB, URCB and GSE control blocks and similar global defined for the whole device; the
common settings include all the setting items of communication settings. System settings and
some of the protection setting items, which can be configured to two or more protection elements
(logical nodes). In LLN0, the item Loc is a device control object, this item indicates the local
operation for complete logical device, when it is true, all the remote control commands to the IED
will be blocked until Loc is changed to false. In PCS-915 series relays, besides the logical nodes
described above, there are some other logical nodes in the IEDs:
LPHD: Physical device information, the logical node to model common issues for physical
device.
9-9
Date: 2013-06-03
9 Communications
PTRC: Protection trip conditioning, it is used to connect the operate outputs of one or more
protection functions to a common trip to be transmitted to XCBR. In addition or alternatively, any
combination of operate outputs of protection functions may be combined to a new operate of
PTRC.
RDRE: Disturbance recorder function. It triggers fault wave recorder and its output refers to
the IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System (IEC
60255-24). All enabled channels are included in the recording and is independent of the trigger
mode.
9-10
9 Communications
Complete names are in the form of xxxxxxPTOC1, where the xxxxxx character string is
configurable. Details regarding the logical node naming rules are given in IEC61850 parts 6 and
7-2. It is recommended that a consistent naming convention be used for an entire substation
project.
Client
Server
PCS-915
B11
C1
B12
C1
Client-Server Roles
SCSMS Supported
B21
B22
B23
B24
SCSM: other
Publisher side
B32
Subscriber side
Publisher side
B42
Subscriber side
Where:
PCS-915A Busbar Protection
9-11
Date: 2013-06-03
9 Communications
C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
M: Mandatory
Y:
Client
Server
PCS-915
M1
Logical device
C2
C2
M2
Logical node
C3
C3
M3
Data
C4
C4
M4
Data set
C5
C5
M5
Substitution
M6
M7-1
sequence-number
M7-2
report-time-stamp
M7-3
reason-for-inclusion
M7-4
data-set-name
M7-5
data-reference
M7-6
buffer-overflow
M7-7
entryID
M7-8
BufTm
M7-9
IntgPd
M7-10
GI
M8-1
sequence-number
M8-2
report-time-stamp
M8-3
reason-for-inclusion
M8-4
data-set-name
M8-5
data-reference
M8-6
BufTm
M8-7
IntgPd
Log control
Reporting
M7
M8
Logging
M9
9-12
9 Communications
Services
Client
Server
PCS-915
M9-1
IntgPd
M10
Log
M12
GOOSE
M13
GSSE
M14
Multicast SVC
M15
Unicast SVC
M16
Time
M17
File transfer
GSE
Where:
C2: Shall be "M" if support for LOGICAL-NODE model has been declared
C3: Shall be "M" if support for DATA model has been declared
C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has
been declared
C5: Shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory
Y:
Server/Publisher
PCS-900 Series
Server
S1
ServerDirectory
Application association
S2
Associate
S3
Abort
S4
Release
LogicalDeviceDirectory
S6
LogicalNodeDirectory
S7
GetAllDataValues
GetDataValues
Logical device
S5
Logical node
Data
S8
9-13
Date: 2013-06-03
9 Communications
Service
Server/Publisher
PCS-900 Series
S9
SetDataValues
S10
GetDataDirectory
S11
GetDataDefinition
S12
GetDataSetValues
S13
SetDataSetValues
S14
CreateDataSet
S15
DeleteDataSet
S16
GetDataSetDirectory
SetDataValues
Data set
Substitution
S17
SelectActiveSG
M/O
S19
SelectEditSG
M/O
S20
SetSGValuess
M/O
S21
ConfirmEditSGValues
M/O
S22
GetSGValues
M/O
S23
GetSGCBValues
M/O
Reporting
Buffered report control block
S24
Report
S24-1
data-change
S24-2
qchg-change
S24-3
data-update
S25
GetBRCBValues
S26
SetBRCBValues
Report
S27-1
data-change
S27-2
qchg-change
S27-3
data-update
S28
GetURCBValues
S29
SetURCBValues
Logging
Log control block
9-14
9 Communications
Service
Server/Publisher
PCS-900 Series
S30
GetLCBValues
S31
SetLCBValues
S32
QueryLogByTime
S33
QueryLogAfter
S34
GetLogStatusValues
Log
SendGOOSEMessage
S36
GetGoReference
S37
GetGOOSEElementNumber
S38
GetGoCBValues
S39
SetGoCBValuess
S51
Select
S52
SelectWithValue
S53
Cancel
S54
Operate
S55
Command-Termination
S56
TimeActivated-Operate
Control
File transfer
S57
GetFile
M/O
S58
SetFile
S59
DeleteFile
S60
GetFileAttributeValues
M/O
Time
SNTP
PCS-915
YES
9-15
Date: 2013-06-03
9 Communications
Nodes
PCS-915
YES
YES
PDIS: Distance
YES
PTOF: Overfrequency
PTOV: Overvoltage
YES
PTUC: Undercurrent
PTUV: Undervoltage
PTUF: Underfrequency
YES
9-16
9 Communications
Nodes
PCS-915
YES
RREC: Autoreclosing
CILO: Interlocking
YES
YES
MMTR: Metering
MMXU: Measurement
YES
9-17
Date: 2013-06-03
9 Communications
Nodes
PCS-915
YES
YES
ZBAT: Battery
ZBSH: Bushing
ZCON: Converter
ZGEN: Generator
ZMOT: Motor
ZREA: Reactor
9-18
9 Communications
implementation. This manual only specifies which objects, variations and qualifiers are supported
in this relay, and also specifies what data is available from this relay via DNP3.0.
The relay operates as a DNP3.0 slave and supports subset level 2 of the protocol, plus some of
the features from level 3. The DNP3.0 communication uses the EIA RS-485 at the rear of this relay.
The data format is 1 start bit, 8 data bits, no parity bit and 1 stop bit.
2.
3.
Function Code
Object
Variation
Qualifier
Master
0x17
Slave
0x81
0x34
0x02
0x07
Master/Slave
Function Code
Object
Variation
Qualifier
Master
0x01
0x34
0x00, 0x01
0x04-
Slave
0x81
0x34
0x02
0x07
Function Code
Object
Variation
Qualifier
Master
0x02
0x32
0x01
Slave
0x81
2.
Function Code
Object
Variation
Qualifier
Master
0x02
0x50
0x01
0x00, 0x01
Slave
0x81
Supported qualifiers
Master Variation
0x00
0x01
0x06
0x07
0x08
9-19
Date: 2013-06-03
9 Communications
Slave Variation
2.
0x00
0x01
0x01
0x07
0x08
0x00
0x01
0x02
Slave Variation
0x02
0x01
0x02
The protection operation signals, alarm signals and binary input state change signals are
transported respectively according to the variation sequence in above table.
Object 2, SOE
Master Qualifier
0x00
0x01
0x02
0x03
Slave Qualifier
0x00
0x01
0x02
0x03
If the master qualifier is 0x07, the slave responsive qualifier is 0x27; and if the master
qualifier is 0x01, 0x06 or 0x08, the slave responsive qualifier is 0x28.
0x00
0x01
0x02
0x03
0x04
Slave Qualifier
0x01
0x01
0x02
0x03
0x04
The metering values are transported firstly, and then the protection measurement values are
transported.
0x00
0x01
0x02
Slave Variation
0x01
0x01
0x02
3.
4.
5.
9-20
9 Communications
The master adopts the Object 60 for the multiple object request and the variation is 0x01,
0x02, 0x03 and 0x04.
The slave responds with the above mentioned Object 1, Object 2, Object 30 and Object
40 (see Supported objects and variations in Section 9.6.4.3).
9.6.4.4 Remote Control Functions
The function code 0x03 and 0x04 are supported in this relay. The function code 0x03 is for the
remote control with selection; and the function code 0x04 is for the remote control with execution.
The selection operation must be executed before the execution operation, and the single point
control object can be supported to this relay.
Master Qualifier
0x17
0x27
0x18
0x28
Slave Qualifier
0x17
0x27
0x18
0x28
0x01
Slave Variation
0x01
Control Code
0x01: closing
0x10: tripping
9-21
Date: 2013-06-03
9 Communications
9-22
11 Commissioning
11 Commissioning
Table of Contents
11 Commissioning ........................................................................... 11-a
11.1 General .......................................................................................................... 11-1
11.2 Safety Instructions ....................................................................................... 11-1
11.3 Commission Tools ....................................................................................... 11-2
11.4 Setting Familiarization ................................................................................. 11-2
11.5 Product Checks ............................................................................................ 11-3
11.5.1 With the Relay De-energized ............................................................................................11-3
11.5.2 With the Relay Energized .................................................................................................11-5
11.5.3 Protection Function Checks ..............................................................................................11-7
11.5.4 Print Fault Report ............................................................................................................11-21
11.5.5 On-load Checks ..............................................................................................................11-21
11.5.6 Final Checks ...................................................................................................................11-22
11-a
Date: 2012-08-30
11 Commissioning
11-b
11 Commissioning
11.1 General
This relay is fully numerical in their design, implementing all protection and non-protection
functions in software. The relay employs a high degree of self-checking and in the unlikely event of
a failure, will give an alarm. As a result of this, the commissioning test does not need to be as
extensive as with non-numeric electronic or electro-mechanical relays.
To commission numerical relays, it is only necessary to verify that the hardware is functioning
correctly and the application-specific software settings have been applied to the relay.
Blank commissioning test and setting records are provided at the end of this manual for
completion as required.
Before carrying out any work on the equipment, the user should be familiar with the contents of the
safety and technical data sections and the ratings on the equipments rating label.
The earthing screw of the device must be connected solidly to the protective earth conductor
before any other electrical connection is made.
Hazardous voltages can be present on all circuits and components connected to the supply
voltage or to the measuring and test quantities.
Hazardous voltages can be present in the device even after disconnection of the supply
voltage (storage capacitors!)
The limit values stated in the Chapter Technical Data must not be exceeded at all, not even
during testing and commissioning.
When testing the device with secondary test equipment, make sure that no other
measurement quantities are connected. Take also into consideration that the trip circuits and
maybe also close commands to the circuit breakers and other primary switches are
disconnected from the device unless expressly stated.
11-1
Date: 2012-08-30
11 Commissioning
DANGER! Current transformer secondary circuits must have been short-circuited before
the current leads to the device are disconnected.
WARNING! Primary test may only be carried out by qualified personnel, who are familiar
with the commissioning of protection system, the operation of the plant and safety rules
and regulations (switching, earthing, etc.).
Multifunctional dynamic current and voltage injection test set with interval timer.
Multimeter with suitable AC current range and AC/DC voltage ranges of 0~440V and 0~250V
respectively.
Optional equipment:
An electronic or brushless insulation tester with a DC output not exceeding 500V (for
insulation resistance test when required).
A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).
EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested).
11-2
11 Commissioning
Hardware tests
These tests are performed for the following hardware to ensure that there is no hardware
defect. Defects of hardware circuits other than the following can be detected by
self-monitoring when the DC power is supplied.
Function tests
These tests are performed for the following functions that are fully software-based. Tests of
the protection schemes and fault locator require a dynamic test set.
Timers test
Conjunctive tests
The tests are performed after the relay is connected with the primary equipment and other
11-3
Date: 2012-08-30
11 Commissioning
external equipment.
On load test.
Protection panel
Carefully examine the protection panel, protection equipment inside and other parts inside to
see that no physical damage has occurred since installation.
The rated information of other auxiliary protections should be checked to ensure it is correct
for the particular installation.
Panel wiring
Check the conducting wire which is used in the panel to assure that their cross section
meeting the requirement.
Carefully examine the wiring to see that they are no connection failure exists.
Label
Check all the isolator binary inputs, terminal blocks, indicators, switches and push buttons to
make sure that their labels meet the requirements of this project.
Earthing cable
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
11-4
11 Commissioning
DC power supply
Output contacts
Communication ports
11-5
Date: 2012-08-30
11 Commissioning
11-6
11 Commissioning
must be made for the accuracy of the test equipment being used.
NOTE! The closing circuit should remain isolated during these checks to prevent
accidental operation of the associated circuit breaker.
11.5.2.7 Testing the AC Voltage Inputs
This test verified that the accuracy of voltage measurement is within the acceptable tolerances.
Apply rated voltage to each voltage transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the relays menu.
The measurement accuracy of the relay is 2.5% or 0.1V. However an additional allowance must be
made for the accuracy of the test equipment being used.
NOTE! The closing circuit should remain isolated during these checks to prevent
accidental operation of the associated circuit breaker.
11.5.2.8 Testing the Binary Inputs
This test checks that all the binary inputs on the equipment are functioning correctly.
The binary inputs should be energized one at a time, see external connection diagrams for
terminal numbers.
Ensure that the voltage applied on the binary input must be within the operating range.
The status of each binary input can be viewed using relay menu. Sign 1 denotes an energized
input and sign 0 denotes a de-energized input.
Test method:
To unplug all the terminals sockets of this protective device, and do the insulation resistance test
for each circuit above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected
to the protection.
11-7
Date: 2012-08-30
11 Commissioning
[U2n]=110V
[I2n_CT_Base]=1A
[I1n_Bayxx]=1200 (xx=01~25)
Setting BBP Settings
[I_Pkp_Pcnt_BBP] =1.8A
[En_BBP]=1
Change the following settings to avoid effects on steady state differential protection element.
[I_BFP_BC]=5A
[I_Alm_CTS]=5A
[I_Alm_SensCTS]=5A
Setting VEBI Settings:
[VEBI_BBP]=1
Energize the binary input [EBI_BBP]
Please pay attention that the polarity of CT of bus coupler is same to CT of feeder connected to
bus 1, but opposite to that connected to bus 2.
External fault test
1.
Set bay 02 connecting to BB1 through energizing binary input [BI_52a_DSBB1_Bay02] and
set bay 03 connecting to BB2 through energizing binary input [BI_52a_DSBB2_Bay03].
2.
Connect CT of bay 02 and BC CT with the reverse polarity in series and then connect CT of
bay 03 with reverse polarity in series (Refer to Figure 11.5-1). Inject a current (For example
ITEST1 100 ) to make steady-state percentage differential element operate.
3.
VCE for BBP will operate. Steady-state percentage differential element does not operate.
11-8
11 Commissioning
ITEST1
A
1601
Test source
1603
BUS COUPLER
1605
1602
1604
1606
1607
1609
1612
CURRENT CIRCUIT
1610
PCS-915
1608
Bay 02
1611
1613
1615
1617
Bay03
1614
1616
1618
Because check zone differential current is equal to zero, the protective judges that it is an external
fault.
Internal fault test (BB1)
1.
Set bay 02 connecting to BB1 though energizing binary input [BI_52a_DSBB1_Bay02] and
set bay 03 connecting to BB2 though energizing binary input [BI_52a_DSBB2_Bay03]
2.
Connect CT of bay 02, BC CT, and CT of bay 03 with the same polarity in series (Refer to
Figure 11.5-2).
3.
Only inject a current to make steady-state percentage differential element operate (For
example ITEST1 10 0 A).
4.
VCE for BBP will operate. Steady-state percentage differential element operates with
BBP_TRIP LED and MISC_TRIP LED turned on simultaneously.
11-9
Date: 2012-08-30
11 Commissioning
ITEST1
1601
Test source
1603
BUS COUPLER
1605
1602
1604
1606
1607
1610
PCS-915
1608
Bay 02
1611
1612
CURRENT CIRCUIT
1609
1613
1615
Bay 03
1617
1614
1616
1618
1.
Set both bay 02 and bay 03 connecting to BB1 through energizing binary input
[BI_52a_DSBB1_Bay02] and [BI_52a_DSBB1_Bay03].
2.
Connect CT of bay 02 and CT of bay 03 with the same polarity in series (Refer to Figure
11.5-3)
3.
Inject a current (For example ITEST1 [I_Pkp_Pcnt_BBP] 1.05/2 0.94500 A), the
steady-state percentage differential element will operate to trip BB1
11-10
11 Commissioning
4.
Inject a current ( ITEST1 [I_Pkp_Pcnt_BBP] 0.95/2 0.85500 A), the steady state
percentage differential element will not operate.
ITEST1
1607
Test Source
1609
1611
Bay 02
1608
1610
PCS-915
1613
1615
Bay 03
1617
CURRENT CIRCUIT
1612
1614
1616
1618
Binary input
[BI_Blk_BBP]
PCS-915
0514
0517
Set both bay 02 and bay 03 connecting to BB1 through energizing binary input
[BI_52a_DSBB1_Bay02] and [BI_52a_DSBB1_Bay03].
2.
Connect CT of bay 02 and CT of bay 03 with the same polarity in series and connect the
binary input [BI_Blk_BBP] (Refer to Figure 11.5-3).
3.
4.
Inject a current (For example ITEST1 10 0 A), BBP protection will not operate.
Set bay 02 connecting to BB1 through energizing the binary input [BI_52a_DSBB1_Bay02]
and set bay 03 connecting to BB2 through energizing binary input [BI_DSBB2_Bay03].
2.
Connect CT of bay 02 and BC CT the opposite polarity in series, and then connect CT of bay
03 with reverse polarity in series. Then connect binary output contact of tripping BB2 and
11-11
Date: 2012-08-30
11 Commissioning
binary input [BI_52b_BC] to test source. Connect binary output contact of tripping BB1 and
binary output contact of tripping bay 03 to time meter. (Refer to Figure 11.5-4)
I TEST1
1601
1603
BUS COUPLER
1605
1602
1604
1606
1607
Bay 02
1608
Test source
PCS-915
1611
Current Circuit
1609
1610
1612
1613
1615
Bay 03
1617
1614
1616
1618
0514
0501
Binary output
tripping bay 03
1210
1205
Binary output
tripping bay 02
1206
Start
Time
meter
PCS-915
1209
Binary input
[BI_52b_BC ]
Stop
Figure 11.5-4 BC end zone fault protection test (BC breaker is closed)
3.
Please set two stages of test source and change from stage 1 to stage 2 to simulate to trip BC
breaker and to make end zone fault protection operate. (For example STAGE 1:
Use binary output contact of tripping BB2 (bay 03 will be tripped) as a triggering signal to
change the state from STAGE 1 to STAGE 2.
5.
Start test from STAGE 1. BBP should operate to trip BC breaker and BB2. The binary output
contact of tripping BB2 (bay 03 will be tripped) will close and control the test source to change
11-12
11 Commissioning
the state from STAGE 1 to STAGE 2, and then BBP will trip BB1 with a time delay for end
zone fault protection operates to make BC current be excluded from discriminative zone
differential current. BBP_TRIP LED and MISC_TRIP LED will be turned on.
BC breaker is open
1.
2.
3.
Connect CT of bay 02 and BC CT with the opposite polarity in series, and connect VTs of BB1
and BB2. (Refer to Figure 11.5-5)
ITEST1
1601
1603
BUS COUPLER
1605
1602
1604
1606
1609
1610
PCS-915
1608
Bay 02
1611
1612
V
2807
2809
2811
BUS 1 VOLTAGE
UTEST1
1607
Test source
2808
2815
2817
BUS 2 VOLTAGE
2813
2814
Figure 11.5-5 BC end zone fault protection test (BC breaker is open)
4.
Please set two stages of test source and change from stage 1 to stage 2 to make end zone
fault protection operate. (For example STAGE 1: ITEST1 000 A , UTEST1 4000 V ;
STAGE 2: ITEST1 200 A , UTEST1 000 V ).
5.
Start test from STAGE 1 to STAGE 2. BBP should operate to only trip BC breaker and BB1
11-13
Date: 2012-08-30
11 Commissioning
Connect the BC CT, connect VT of BB1 and connect binary input [BI_52b_BC]. (Refer to
Figure 11.5-6)
ITEST1
A
1601
1603
1602
1604
PCS-915
1606
1607
Test source
1609
CURRENT CIRCUIT
BUS COUPLER
1605
Bay 02
1611
1608
1610
1612
0501
Binary input
[BI_52b_BC]
PCS-915
0514
2.
Injecting a current ITEST1 0.950 0 A and make the binary input [BI_52b_BC] change from
being energized to being de-energized, BC SOTF protection should not operate.
3.
Injecting a current ITEST1 1.050 0 A and make the binary input [BI_52b_BC] change from
being energized to being de-energized, BC SOTF protection should operate to trip BC
breaker with MISC_TRIP LED turned on.
11-14
11 Commissioning
Must inject the current while the binary input [BI_52b_BC] changes from being energized to being
de-energized, because the BC SOTF protection is only enabled for 300ms when the binary input
[BI_52b_BC] changes from being energized to being de-energized.
11.5.3.4 Bus coupler overcurrent protection
Change BBP_Settings
[I_OC_BC] =1A
[I_ROC_BC] =1A
[t_OC_BC] =0.5S
[En_OC_BC]=1
Setting VEBI_Settings:
[VEBI_OC_BC]=1
Energize binary input [EBI_OC_BC].
Connect the BC CT and binary output contact of tripping BC to time meter. (For example Figure
11.5-7)
I1
Test source
1601
1604
BUS COUPLER
1602
PCS-915
1605
CURRENT CIRCUIT
1603
1606
Start
Time meter
PCS-915
Stop
2.
Inject a current ITEST1 1.050 0 A and BC OC protection should operate to trip BC breaker
with MISC_TRIP LED turned on.
11-15
Date: 2012-08-30
11 Commissioning
3.
After finishing the test, change the setting i.e. [I_ROC_BC] =1A
2.
Inject a current ITEST1 1.050 0 A and BC OC protection should operate to trip BC breaker
with MISC_TRIP LED turned on.
3.
After finishing the test, change the setting i.e. [I_OC_BC] =1A
2.
Inject a current ITEST1 20 0 A and the persisting time is longer than the setting i.e.
[t_TrpBB_BFP_BC].
3.
BBP protection should operate to trip BB1 and BC breaker. BBP_TRIP LED and
MISC_TRIP LED will be turned on first. Then after a delay [t_TrpBB_BFP_BC], BC BFP will
operate to trip BB1 and BB2, and BFP_TRIP LED will be turned on.
4.
After finishing the test, change the setting i.e. [En_BBP]=0 and de-energize the binary input
[EBI_BBP].
11-16
11 Commissioning
1.
Connect BC CT and binary input [BI_BFI_BC] to test source (Refer to Figure 11.5-8)
I1
1601
1604
Test source
PCS-915
1602
BUS COUPLER
1605
CURRENT CIRCUIT
1603
1606
0925
Binary input
[BI_BFI_BC]
PCS-915
0914
2.
Please set two stages to make the BC BFP operate. (For example STAGE 1:
Start test from STAGE 1 to STAGE 2. BC BFP will operate to trip BB1 and BB2 with a time
delay [t_TrpBB_BFP_BC]. BFP_TRIP LED and MISC_TRIP LED should be turned on.
11-17
Date: 2012-08-30
11 Commissioning
ITEST1
A
1601
1603
BUS COUPLER
1602
PCS-915
1605
1604
CURRENT CIRCUIT
Test source
1606
Start
Time meter
1202
Bus coupler
protection operate
to trip BC
PCS-915
1201
Stop
2.
Inject a current ITEST1 0.950 0 A with persisting time longer than the time delay
[t_PD_BC]. BC PD protection does not operate.
3.
Inject a current ITEST1 1.050 0 A with persisting time longer than the time delay
[t_PD_BC].
4.
BC PD protection should operate to trip BC breaker with a time delay [t_PD_BC], and
MISC_TRIP LED should be turned on.
5.
After finishing the test, please change the setting i.e. [I_NegOC_PD_BC]=1A.
2.
Inject a current ITEST1 2.850 0 A with persisting time longer than the time delay
[t_PD_BC]. BC PD protection does not operate.
3.
Inject a current ITEST1 3.150 0 A and persisting time is longer than the time delay
[t_PD_BC].
4.
BC PD protection should operate to trip BC breaker with a time delay [t_PD_BC], and
MISC_TRIP LED should be turned on.
5.
After finishing the test, please change the setting i.e. [I_ROC_PD_BC]=1A.
6.
After finishing all test of BC PD protection, de-energize the two binary inputs [EBI_PD_BC]
11-18
11 Commissioning
and [BI_52b_BC].
11.5.3.7 Feeder breaker failure protection
Chang BFP Settings
[t_TrpBC_BFP]=0.25S
[t_TrpBB_BFP]=0.35S
[V_UV_VCE_BFP]=30V
[V_ROV_VCE_BFP]=8V
[V_NegOV_VCE_BFP]=3V
[I_OC_BFP_Bay02]=2A
[I_ROC_BFP_Bay02]=1A
[I_NegOC_BFP_Bay02]=1A
[En_ROC_BFP_Bay02]=0
[En_NegOC_BFP_Bay02]=0
[En_BFP]=1
[VEBI_BFP]=1
Energize the binary input [EBI_BFP]
Set bay 02 connecting to BB1 through energizing binary input [BI_52a_DSBB1_Bay02].
Connect the VT of BB1, CT of bay 02 and binary inputs [BI_Rls_VCE_BFP_Trans] and
[BI_BFI_Bay02] to test source (Refer to Figure 11.5-10).
11-19
Date: 2012-08-30
11 Commissioning
UTEST1
UTEST2
V
2807
2809
2811
2808
2810
2812
1607
1609
Test source
PCS-915
ITEST1
BUS 1 voltage
UTEST3
Bay 02
1611
1608
1610
1612
0518
0614
0601
Binary input
[BI_Rls_VCE_
BFP_Trans]
Binary input
[BI_BFI_Bay02]
PCS-915
0514
Check BFP
1.
ITEST1 00 0 A
3.
Start test from STAGE 1 to STAGE 2. BFP should operate to re-trip bay 02, and then trip BC
breaker and finally trip BB1 with different time delays. BFP_TRIP LED and MISC_TRIP
should be turned on.
2.
Set
three
stages:
STAGE1:
UTEST1 63.50 0 V
ITESY1 2.50 0 A
and
STAGE3: UTEST1 00 0 V ,
binary
input
[BI_BFI_Bay02]
11-20
is
energized;
UTEST3 63.5120 0 V ,
PCS-915A Busbar Protection
Date: 2012-08-30
11 Commissioning
The persisting time of STAGE 1, STAGE 2 and STAGE 3 are set as 1s.
4.
Start test from STAGE 1 to STAGE 2. BFP should not operate. Sequentially test from STAGE
2 to STAGE 3. BFP should operate.
Set
two
stages:
STAGE1:
UTEST1 63.50 0 V
3.
4.
Energize the binary input [BI_Rls_VCE_BFP_Trans] and repeat the above test, BFP will
operate.
Confirm the external wiring to the current and voltage inputs is correct.
11-21
Date: 2012-08-30
11 Commissioning
However, these checks can only be carried out if there are no restrictions preventing the
tenderization of the plant being protected.
Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has
been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the protection in order to
perform any of the foregoing tests, it should be ensured that all connections are replaced in
accordance with the relevant external connection or scheme diagram. Confirm current and voltage
transformer wiring.
11-22
12 Maintenance
12 Maintenance
Table of Contents
12 Maintenance ................................................................................ 12-a
12.1 Appearance Check ...................................................................................... 12-1
12.2 Failure Tracing And Repair ......................................................................... 12-1
12.3 Replace Failed Modules ............................................................................. 12-1
12.4 Cleaning ....................................................................................................... 12-3
12.5 Storage ......................................................................................................... 12-3
12-a
Date: 2012-08-30
12 Maintenance
12-b
12 Maintenance
NR numerical relay PCS-915 is designed to require no special maintenance. All measurement and
signal processing circuit are fully solid state. All input modules are also fully solid state. The output
relays are hermetically sealed.
Since the device is almost completely self-monitored, from the measuring inputs to the output
relays, hardware and software defects are automatically detected and reported. The
self-monitoring ensures the high availability of the device and generally allows for a corrective
rather than preventive maintenance strategy. Therefore, maintenance checks in short intervals are
not required.
Operation of the device is automatically blocked when a hardware failure is detected. If a problem
is detected in the external measuring circuits, the device normally only provides alarm messages.
12-1
Date: 2012-08-30
12 Maintenance
Replacing a module
Short circuit all AC current inputs and disconnect all AC voltage inputs
2)
Unplug the ribbon cable on the front panel by pushing the catch outside.
3)
12-2
12 Maintenance
After replacing the CPU module, input the application-specific setting values again.
Warning!
Units and modules may only be replaced while the supply is switched off and only by
appropriately trained and qualified personnel. Strictly observe the basic precautions to
guard against electrostatic discharge.
Warning!
When handling a module, take anti-static measures such as wearing an earthed wrist band
and placing modules on an earthed conductive mat. Otherwise, many of the electronic
components could suffer damage. After replacing the CPU module, check the settings.
Danger!
After replacing modules, be sure to check that the same configuration is set as before the
replacement. If this is not the case, there is a danger of the unintended operation of
switchgear taking place or of protections not functioning correctly. Persons may also be
put in danger.
12.4 Cleaning
Before cleaning the relay, ensure that all AC/DC supplies, current transformer connections are
isolated to prevent any chance of an electric shock whilst cleaning. Use a smooth cloth to clean
the front panel. Do not use abrasive material or detergent chemicals.
12.5 Storage
The spare relay or module should be stored in a dry and clean room. Based on IEC standard
60255-1 the storage temperature should be from -40oC to +70oC, but the temperature of from 0oC
to +40oC is recommended for long-term storage.
12-3
Date: 2012-08-30
12 Maintenance
12-4
13-a
Date: 2012-08-30
13-b
13.1 Decommissioning
1.
Switching off
To switch off the PCS-915, switch off the external miniature circuit breaker of the power supply.
2.
Disconnecting Cables
Disconnect the cables in accordance with the rules and recommendations made by relational
department.
Danger!
Before disconnecting the power supply cables that connected with the DC module of the
PCS-915, make sure that the external miniature circuit breaker of the power supply is
switched off.
Danger!
Before disconnecting the cables that are used to connect analog input module with the
primary CTs and VTs, make sure that the circuit breaker for the primary CTs and VTs is
switched off.
3.
Dismantling
The PCS-915 rack may now be removed from the system cubicle, after which the cubicles may
also be removed.
Danger!
When the station is in operation, make sure that there is an adequate safety distance to
live parts, especially as dismantling is often performed by unskilled personnel.
13.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste.
Note!
Strictly observe all local and national regulations when disposing of the device.
13-1
Date: 2012-08-30
13-2
Software
Date
Description of change
New
Version
R1.00
R1.00
2011-08-16
R1.00
R1.01
R1.00
2012-08-31
R1.01
R1.02
R1.00
2013-06-03
Source
14-1
Date: 2013-06-03
14-2