3AH
Vacuum Circuit-Breakers
Medium-Voltage
Equipment
Catalog HG 11.11
1999
3AH Vacuum
Circuit-Breakers
R-HG11-059a eps
R-HG11-058 eps
Siemens
8BJ50 medium-voltage
withdrawable switchgear
with 3AH vacuum circuit-breaker
on central truck
Airport Munich
Page
Applications,
cases of application
1/ 2
Versions,
fields of application
1/ 3
Supply program
1/ 4
Technical
specifications
1/ 4 1/ 5
Construction and
1/ 5 1/ 7
mode of operation
Power consumption
and rated currents
1/ 8
Secondary
equipment
1/ 8 1/ 11
Schematic
diagrams
1/ 12 1/ 14
Standards, tests,
insulating capacity,
ambient conditions
Quality standard
1/ 15
Under normal
ambient conditions
in accordance with
IEC 60 694 and
VDE 0670 Part 1000
Up to 10,000
operating cycles
No relubrication
No readjustment
Nominal performance
remains within
tolerance even at
very high operating
frequencies or after
long periods of idleness
Environmental compatibility
The 3AH vacuum circuitbreakers are environmentalfriendly:
As far as material selection and manufacturing
methods are concerned
Environmentally neutral
in operation and during
switching operations
Easy to dispose of at
the end of their service
life
Advantages of vacuum
technology:
Vacuum-tight for life
Soldered seal
Small number of mechanical
parts
Siemens HG 11.11 19991/1
3AH
Vacuum
Circuit-Breakers
Contents
3AH2/3AH4
Frequent-Operation Circuit-Breakers
Appendix
Medium-Voltage Equipment
Catalog HG 11.11 1999
Supersedes: Catalog HG 11.11 1997
Siemens AG 1999
Cases of application
Synchronization
The closing times (for switching
duties U and K) are so short
that, at the instant the contacts
touch, the systems being paralleled are still sufficiently in
synchronism.
Rapid load transfer
(Transfer of loads from one
source of supply to another
without interruption of service)
The vacuum circuit-breakers
(for switching duties U and K)
have the very short closing and
opening times which are required for this purpose.
Tests conforming to the relevant standards have been carried out on the vacuum circuitbreakers for switching duty U.
They included tests using the
sequence O-t- CO-t'- CO
(t, t' 3 min) with full rated
short-circuit breaking current.
Auto-reclosing
Used in overhead line systems
to eliminate transient faults or
short-circuits, such as those
caused by thunderstorms,
lightning or animals.
The vacuum circuit-breakers
for switching duty K have such
short dead times between
opening and closing, even at
full short-circuit current, that
the interruption in the supply
has no appreciable effect on
the load.
If auto-reclosing is unsuccessful, the affected circuit is completely disconnected.
According to VDE 0670 a vacuum circuit-breaker designed for
auto-reclosing must be able to
perform the test sequence
O-t-CO-t'-CO (t 0.3 s; t' 3 min);
in the case of unsuccessful
auto-reclosing, only the
sequence O-t-CO (t 0.3 s) is
required.
Abbreviations
for switching duties
and cases of application:
U
= Synchronization and
rapid load transfer
(closing time 90 ms)
= Auto-reclosing
= Opening
= Closing
3AH Vacuum
Circuit-Breakers
Auto-reclosing in contact
line systems
Multiple auto-reclosing
The vacuum circuit-breakers
are also suitable for multiple
auto-reclosing. This is employed
primarily in English-speaking
countries under the designa-
Making currents up to 10 kA
(peak value) are permissible;
higher values on request.
Switching of overhead lines
and cables
When unloaded overhead lines
and cables are being disconnected, the relatively low capacitive currents are interrupted
without restrike and, therefore,
without overvoltage.
Switching of motors
If small high-voltage motors are
disconnected during start-up,
switching overvoltages may
occur. This affects high-voltage
motors with a starting current
of up to 600 A.
The level of these overvoltages
can be reduced to safe values
by means of special surge limiters.
Overvoltage protection is not
required for motors with individual p.f. correction.
Switching of generators
If generators with a shortcircuit current 600 A are
switched, switching overvoltages may occur.
In such a case, surge limiters
or surge arresters should be
used.
Switching of filter circuits
When interrupting filter circuits
or disconnecting reactor-connected capacitor banks, loading
of the vacuum circuit-breaker
by recovery voltage is greater
than with pure capacitors.
The reason for this is that the
reactor and the capacitor are
connected in series.
This has to be taken into
account when selecting the
vacuum circuit-breaker with
respect to rated voltage.
Switching of arc furnaces
Up to 100 operating cycles per
day are required, for which the
3AH2 and 3AH4 vacuum circuit-breakers are particularly
suitable.
As a result of the characteristics of the load circuit, the currents can be asymmetrical and
distorted.
In order to prevent any resonance in the furnace transformers, an individually adapted
suppressor circuit is necessary.
3AH Vacuum
Circuit-Breakers
Versions
Standard circuit-breakers
Type 3AH1
Up to 10,000 operating cycles
Up to 24 kV
Type 3AH3
Rated short-circuit breaking currents of
up to 63 kA
Rated normal currents of up to 4000 A
Up to 10,000 operating cycles
Up to 36 kV
Fields of application
Case of
application*
Number of
operating
cycles
10,000
Transformers
Rated voltage/
rated short-circuit
breaking current
Vacuum
Catalog
circuitpage
breaker type
17.5 kV / 40 kA
24 kV / 25 kA
3AH1
2/2 2/9
2/10, 2/11
17.5 kV / > 40 kA
24 kV / 40 kA
36 kV / 40 kA
3AH3
2/2 2/9
2/10, 2/11
2/12, 2/13
12 kV / 25 kA
17.5 kV / 25 kA
24 kV / 16 kA
36 kV / 16 kA
3AH5
4/2, 4/3
4/4, 4/5
4/6, 4/7
4/8, 4/9
17.5 kV / 40 kA
24 kV / 25 kA
3AH1
2/2 2/9
2/10, 2/11
17.5 kV / 63 kA
24 kV / 40 kA
36 kV / 40 kA
3AH3
2/2 2/9
2/10, 2/11
2/12, 2/13
3AH3 83
5/2, 5/3
17.5 kV / 40 kA
24 kV / 25 kA
3AH1
2/2 2/9
2/10, 2/11
17.5 kV / 50 and 63 kA
24 kV / 40 kA
36 kV / 40 kA
3AH3
2/2 2/9
2/10, 2/11
2/12, 2/13
12 kV / 25 kA
17.5 kV / 25 kA
24 kV / 16 kA
36 kV / 16 kA
3AH5
4/2, 4/3
4/4, 4/5
4/6, 4/7
4/8, 4/9
17.5 kV / 40 kA
24 kV / 25 kA
3AH2
3/2 3/9
3/10, 3/11
3AH4
3/10, 3/11
3/12, 3/13
3AH1
2/2 2/7
Frequent-operation circuit-breakers
Type 3AH2
Up to 60,000 mechanical operating cycles
Up to 24 kV
Type 3AH4
For very high numbers of operating cycles,
up to 120,000 mechanical operating cycles
24 kV and 36 kV
Generators
10,000
17.5 kV /
Capacitors
10,000
Filter circuits
Economy circuit-breakers
Type 3AH5
For small switching capacities
Individual secondary equipment
Up to 10,000 operating cycles
12 kV to 36 kV
Filter circuits
cause an increase
in voltage at the
series-connected
switchgear.
> 10,000
High-current circuit-breakers
Type 3AH3 83
According to ANSI C37.013
Rated short-circuit breaking currents of
up to 63 kA
Rated normal currents of up to 12,000 A
Up to 10,000 operating cycles
17.5 kV
According to IEC 60 056
Rated short-circuit breaking currents of
up to 80 kA
Rated normal currents of up to 12,000 A
Up to 10,000 operating cycles
17.5 kV
24 kV
36 kV
Motors
10,000
3AH3
2/2 2/7
3AH5
4/2, 4/3
> 10,000
15 kV / 40 kA
3AH2
3/2 3/7
10,000
17.5 kV / 40 kA
24 kV / 25 kA
3AH1
2/2 2/9
2/10, 2/11
17.5 kV / 50 and 63 kA
24 kV / 40 kA
36 kV / 40 kA
3AH3
2/2 2/9
2/10, 2/11
2/12, 2/13
17.5 kV / 40 kA
24 kV / 25 kA
3AH2
3/2 3/9
3/10, 3/11
/ 40 kA
/ 40 kA
3AH4
3/10, 3/11
3/12, 3/13
17.5 kV / 40 kA
24 kV / 25 kA
3AH2
3/2 3/9
3/10, 3/11
3AH4
3/10, 3/11
3/12, 3/13
> 10,000
24 kV
36 kV
Arc furnaces
Special circuit-breakers
1-pole to 3-pole
Rated short-circuit breaking currents of
up to 80 kA
Rated normal currents of up to 4000 A
Up to 10,000 operating cycles
7.2 kV to 36 kV
15 kV / 40 kA
12 kV / 25 kA
/ 40 kA
/ 40 kA
15 kV /
Reactors
50 to 80 kA
60,000
50 and 63 kA
120,000
24 kV
36 kV
60,000
17.5 kV / 31.5 kA
3AH4 7
6/2, 6/3
10,000
17.5 kV /
3AH4 7
6/2, 6/3
Traction 50/60 Hz
60,000
27.5 kV / 31.5 kA
3AH4 7
6/4, 6/5
Special
applications
On req.
On request
On req.
7/2
Traction 16 2/3 Hz
/ 40 kA
/ 40 kA
40 and 50 kA
3AH Vacuum
Circuit-Breakers
Technical specifications for details regarding service life, please refer to catalog sections 2 to 6
Electrical data and supply program
Circuit-breaker
types
3AH1 / 3AH3
standard circuitbreakers
3AH2 / 3AH4
frequent-operation
circuit-breakers
3AH5 economy
circuit-breakers
Rated shortcircuit
breaking
current1) Isc
Rated shortcircuit
making
current Ima
Rated normal
current
24 kV
27.5 kV 36 kV
50/60 Hz 50/60 Hz 50/60 Hz
13.1 kA
32.8 kA
800 A
3AH5
16 kA
40 kA
800 to 1250 A
3AH5
3AH1
3AH5
3AH5
3AH1
3AH1
3AH1
3AH1
20 kA
25 kA
50 kA
800 to 1250 A
63 kA
3AH5
800 to 2500 A
3AH1
800 to 1250 A
3AH5
3AH5
800 to 2500 A
31.5 kA
40 kA
1250 to 2500 A 2)
80 kA
100 kA
1250 to 3150 A
2500 A
3AH1
3AH1
3AH1
3AH1
3AH1
3AH2
3AH1
3AH1
3AH1
3AH1
3AH3
3AH2
3AH2
3AH2
3AH2
3AH4
3AH1
3AH1
3AH1
3AH1
3AH2
3AH2
3AH2
3AH2
3AH3
3AH3
3AH4
3AH4
50 kA
125 kA
1250 to 3150 A
3AH3
3AH3
3AH3
3AH3
63 kA
160 kA
1250 to 4000 A
3AH3
3AH3
3AH3
3AH3
3AH3 83
high-current
circuit-breakers
50 kA
125 kA
3AH3 83
63 kA
160 kA
3AH3 83
80 kA
225 kA
3AH3 83
3AH4 7
traction circuitbreakers, 1-pole
25 kA
63 kA
31.5 kA
80 kA
1250 to 2000 A
3AH4 7
2000 A
3AH4 7
2000 A
3AH4 7
2000 to 2500 A
3AH4 7
40 kA
100 kA
2500 A
3AH4 7
50 kA
125 kA
2500 A
3AH4 7
On request
Special circuitbreakers
Operating times
Operating times
at rated voltage
of secondary circuit
Closing time
Opening time
3AH2
3AH3
3AH4
3AH5
3AH3 83 3AH4 7
ms
<75 3)
<75 3)
<80 3)
<80 3)
<75 3) 5)
<80 3)
<80 3)
ms
<65 3)
<65 3)
<65 3)
<65 3)
<65 3)
<65 3)
<65 3)
<45
ms
<50
<50
<45
<45
<50
<45
Opening time
Instantaneous release
ms
Arcing time
ms
<15
<15
<15
<15
<15
<15
Break time
15
<15 4)
ms
<80
<80
<80
<80
<80
<80
<80
ms
<65
<65
<60
<60
<65
<60
<60
Dead time
ms
CLOSE/OPEN time
ms
<80
<80
<90
<90
<75
<90
<90
ms
<65
<65
<70
<70
<60
<70
<70
Closing solenoid
ms
45
45
45
45
45
45
45
ms
40
40
40
40
40
40
40
ms
20
20
20
20
20
20
20
ms
>15
>15
>15
>15
>15
>15
>15
300
300
300
300
300
300
300
ms
>10
>10
>10
>10
>10
>10
>10
<15
<15
<15
<15
<10
<15
<15
ms
3AH Vacuum
Circuit-Breakers
Rated normal
current
A
4 000 A
4 000
3 150 A
3 000
2 500 A
2 000
1 250 A
30
40
50
Ambient temperature
A certain minimum current is needed in order to maintain the metalvapour arc discharge. The arc will be
chopped before the natural current
zero, if the current falls below this
value.
Moving
contact piece
Insulator
Fixed
contact piece
800 A
0
20
Connecting
disc
Arcing
chamber
2 000 A
1 000
As the contacts are galvanically separated, the current that is to be interrupted initiates a metal-vapour arc
discharge. Current continues flowing
through the metal-vapour plasma
until the next current zero. The arc
extinguishes at approximately current zero. The metal vapour loses its
conductivity within a few microseconds, which very quickly re-establishes the dielectric strength of the
contact gap.
HG11-2362a eps
Permissible
load current at 50 Hz
5 000
Arc-quenching system
HG11-2262a eps
Current-carrying capacity
C 60
Metal
bellows
Guide
Drive and
terminal bolt
Vacuum interrupter
example
3AH Vacuum
Circuit-Breakers
Vacuum circuit-breakers
(examples)
Mechanism
versions
Vacuum interrupters
2 interrupter supports
14
15
HG11-2259a eps
16
Section
through the pole assembly;
mechanism version 1
R-HG11-061a eps
Legend
13 Outer strut
14 Vacuum interrupter
36 kV
16 kA / 1250 A
The operating motion results from the operating
rod (16), lever (15) and
opening and contactpressure spring (9) to the
bracket (11) attached to
the drive bolt (5).
up to 17.5 kV
25 kA / 2000 A
31.5 kA / 1250 A
12
13
24 kV
20 kA / 1250 A
25 kA / 1250 A
14
15
The contact-pressure
spring (10) acts on the
drive bolt (5) through the
bracket (11) and lever (15).
6
7
8
10
11
12 Upper terminal
up to 17.5 kV
25 kA / 1250 A
1
2
12 kV with pole-centre
distance 160 mm
31.5 kA / 1250 A
24 kV
25 kA / 1250 A
5
6
7
8
9
11
12
13
1
2
3
16
HG11-2260b eps
Section
through the pole assembly;
mechanism version 2
16 Flexible connector
17 Lower interrupter support
18 Lower terminal
up to 17.5 kV
50 kA
1
2
19 Opening and
contact-pressure spring
24 kV
40 kA
R-HG11-124 eps
R-HG11-060a eps
10 Contact-pressure spring
11 Bracket
12 Upper post insulator
12
13 Inner strut
15 Lever
16 Operating rod
14
5
6
7
8
15
HG11-2261b eps
16
Section
through the pole assembly;
mechanism version 3
36 kV
31.5 kA
The operating motion results from the operating
rod (16) and lever (15) to
the drive bolt (5).
3AH Vacuum
Circuit-Breakers
6
R-HG11-062a eps
Operating mechanisms
The whole operating mechanism is contained in a single housing, including the releases, auxiliary switches, indicators and
actuating devices.
Stored-energy operating mechanism
The operating drive is usually a storedenergy mechanism. The mechanism operates the pole assemblies through rods. The
closing spring can be charged either electrically or manually. It latches in when charging is complete. The closing spring acts as
the stored-energy mechanism.
To close the breaker, the closing spring can
be unlatched either mechanically by means
of the local CLOSE pushbutton or electrically by remote control. The closing spring
charges the contact-pressure/opening
springs as the breaker closes.
indicator
3
4
5 CLOSED/OPEN
indicator
6 LV plug connector
7 CLOSE pushbutton
8 OPEN pushbutton
3AH1 vacuum circuit-breaker
12 kV / 31.5 kA / 2000 A
Front side with control and display elements
R-HG11-063a eps
13
10
12 Opening spring
(only on vacuum circuitbreakers of mechanism
versions 2 and 3, page 1/6)
1 Rating plate
13 Auxiliary switch S1
11
14
12
available in a choice
of 3 versions:
2 NO + 2 NC
6 NO + 6 NC
12 NO + 12 NC
Trip-free mechanism
The 3AH vacuum circuit-breakers are
equipped with a trip-free mechanism
according to IEC 60 056 and VDE 0670.
In the event of an opening command being
given after a closing operation has been
initiated, the moving contacts return to
the open position and remain there even
if the closing command is sustained.
This means that the contacts of vacuum
circuit-breakers are momentarily in the
closed position under these circumstances, which is permitted according to
IEC 60 056 and VDE 0670.
Abbreviations:
NO = normally-open
NC = normally-closed
Siemens HG 11.11 19991/7
Secondary equipment
DC 24
48
60
26
53
66
20
41
51
350
350
350
8
6
4
110
220
121
242
93
187
350
350
2
1.6
Releases
AC 110
230
121
244
93
187
400
400
2
1.6
Rated voltage
of operating
mechanism
Operating
voltage
max.
V
min.
V
Power con-sumption of
the motor
Smallest possible
rated current of the
m.c.b. with
C-characteristic
VA
3AH Vacuum
Circuit-Breakers
26
53
66
20
41
51
500
500
500
16
8
6
110
220
121
242
93
187
500
500
3
1.6
AC 110
230
121
244
93
187
650
650
3
1.6
Motors of operating
mechanism
The motors operate in shorttime duty and therefore the
voltage and power consumption do not have to be in conformance with the data of the
rating plate.
Protection of the motors
See table above.
The inrush current in the motor
can be neglected since it is of
very brief duration.
3AH Vacuum
Circuit-Breakers
Secondary equipment
Undervoltage release
with delay
Releases
Order No.
of
releases
Power consumption
Operating ranges
Tripping voltage/
current
(AC 50/60 Hz)
approx. W approx. VA
Closing solenoid
3AY15 10
140
140
85 to 110% U
85 to 110% U
85 to 110% U
85 to 110% U
Undervoltage release
3AY11 03
20
20
35 to
0% U
35 to
0% U
10 *
90 to 110% Ia
Current transformer-operated release (tripping pulse 0.1 Ws)
3AX11 04
3AX11 03
undervoltage release
An undervoltage release comprises a stored-energy mechanism, an unlatching mechanism and an electromagnetic
system which is permanently
energized while the circuitbreaker is closed.
If the voltage falls below a predetermined value, unlatching of
the release is enabled and the
circuit-breaker is opened via
the stored-energy mechanism.
For delayed tripping, the undervoltage release can be combined with stored-energy mechanisms:
Type AN 1901 (for AC),
settable
delay times:
1 s 1.8 s 2.5 s
Type AN 1902 (for DC),
settable
delay times:
0.5 s 0.9 s 1.5 s
These stored-energy mechanisms can either be order together with the vacuum circuitbreaker, or can be purchased
separately from Bender 1):
Current transformeroperated release
comprises
A stored-energy mechanism
An unlatching mechanism
An electromagnetic system
It is used when there is no
external source of auxiliary
power (e.g. a battery). Tripping
is effected by means of a protective relay (e.g. overcurrenttime protection) acting on the
current transformer-operated
release.
The following current transformer-operated releases are
used:
3AX11 02 current transformer-operated release with
a rated current of 0.5 A or
1 A which requires auxiliary
transformers (e.g. type
4AM5 see catalog sheet
LSA 2.2.6 Auxiliary current
transformers for differential
relays for overhead lines,
cables and transformers) in
addition to the main current
transformers.
The stored-energy mechanism is unlatched when the
tripping current is exceeded
(90 % of the rated current of
the current transformer-operated release), thus causing
Ordering addresses:
1) Dipl.-Ing.
W. Bender GmbH & Co. KG
Postfach 11 61
D-35301 Grnberg
Germany
2) Schaltanlagen Elektronik
Gerte GmbH & Co. KG
Krefelder Weg 47
D-47906 Kempen
Germany
Siemens HG 11.11 19991/9
3AH Vacuum
Circuit-Breakers
Secondary equipment
Electrical local closing
Secondary connections
(for control circuit)
Interlocking
Versions:
Mechanical interlocking
Varistor module
When inductive loads are being
disconnected in DC circuits it is
possible for switching overvoltages to be produced which
might pose a risk to solid-state
devices. This risk can be eliminated by connecting varistors
across the inductances of the
vacuum circuit-breaker (motor,
closing solenoid, releases).
A suitable varistor module for
operating voltages 60 V to
250 V DC is fitted when
ordering; it limits overvoltages
to approximately 500 V.
Rated insulation
voltage
250 V AC/DC
Insulation
Class C to
VDE 0110
Continuous current
10 A
Making current
50 A
Breaking capacity
at 220 V DC,
T = 20 ms
2A
3AH Vacuum
Circuit-Breakers
Basic equipment
Basic equipment
without wiring
-X0
wired
not wired
and
and
Auxiliary switch -S1, 6 NO+6 NC
1 NO+1 NC
internally wired
2 NO+2 NC+2 CH
1 NO+1 NC
, of which:
Basic and
additional equipment
wiring on request
Lower plug part or
terminal strip, 24-pole
Manual operation ON/OFF
Motor operation, mechanical ON
1st shunt release
Closing solenoid
-X0
wiring
on request
wired
and
and
Auxiliary switch -S1, 6 NO+6 NC
, of which:
1 NO+1 NC
internally wired
5 NO+5 NC
wiring
on request
Closing solenoid
and
wiring
on request
2nd release 2)
and
Basic and
1 NO+1 NC
additional equipment
, of which:
internally wired
-X0
wired
2 NO+2 NC+2 CH
or
3 NO+3 NC+1 CH
1 NO+1 NC
and
2nd and 3rd release 1)
wired
or
and
1 NO+1 NC
internally wired
internally wired
7 NO+4 NC+2 CH
2 NO+5 NC
, of which:
7 NO+4 NC+2 CH
2 NO+5 NC
Lower plug part or
terminal strip, 24-pole
Alternatively
-X0
wired
internally wired
available to the customer
and
2nd and 3rd release 1)
wired
and
Auxiliary switch -S1, 12 NO+12 NC
1 NO+1 NC
11 NO+11 NC
, of which:
Wiring of the equipment (auxiliary switch, motoroperated mechanism and release) possible with
Plug connector, 64-pole or
Plug connector, 24-pole or
Terminal strip, 24-pole
internally wired
available to the customer
1) In the case of more than one release, the number of auxiliary switch contacts available
to the customer and given in the schematic diagrams is binding.
NO = normally-open, NC = normally-closed,
CH = changeover contact (NO/NC)
Siemens HG 11.11 19991/11
3AH Vacuum
Circuit-Breakers
Schematic diagrams for 3AH vacuum circuit-breakers (without 3AH5) Not binding examples only
Basic equipment
Manual tripping
HE
Manual closing
K1
Contactor (anti-pumping)
M1
Motor-operated mechanism
Stored-energy mechanism
R1
Resistor
S1
Auxiliary switch
-X0
-S10 -S11
-S21
-M1 M
-S22
-S41 -S42
-S1
-S7
S6
S7
V1,
V2
Varistor modules*
X0
Y2
Y2
Instantaneous release
(for 3AH4 7 traction circuitbreakers only)
Y4
Current transformer-operated
release
(rated current of 0.5 A or 1 A)
Y6
Current transformer-operated
release
(tripping pulse 0.1 Ws)
Y7
Undervoltage release
Y9
Closing solenoid
* Option:
Varistor circuitry
for 60 V DC (on request)
21 23
31 33
41 43
51
53
61 63
12
14
22 24
32 34
42 44
52
54
62 64
-Y1
-X0
5 NO + 5 NC contacts available to the
customer (see also page 1/11)
-X0
-S14
Y1
13
Release OFF
HA
Position switch
(opens when closing spring
charged)
11
-S6
-S3
S10, Mechanical
S11 anti-pumping
S14, Electrical
S15 local closing
-Y9
HE
HG11-2393a eps
HA
14
-S14
-Y9
-S15
13
11
HE
-S1
-S21
-M1 M
-S22
-S3
-S41 -S42
-K1
P
-S7
-K1
-S6
HA
-S15
-Y1
HG11-2396a eps
-S3 22
12
21
21
13
22
14
-V1 u
31
4
32
Release OFF
14
-Y9 A1
-K1 A1
13
A2
A2
-X0
Electrical
local closing
Closing and
anti-pumping
Additional equipment, releases (for combination possibilities, refer to Secondary equipment, catalog sections 2 to 6)
Releases
-X0
-X0
-X0
-X0
43
-S1
33
-Y7 D1
-S1
Abbreviations:
NO = normally-open
NC = normally-closed
A2
A2
A2
-X0
-X0
-R1
-X0
2
HG11-2402a eps
-Y6 A1
HG11-2401a eps
-Y4 A1
HG11-2400a eps
-Y2 A1
-X0
44
U<
D2
34
HG11-2399a eps
A1
HG11-2398 eps
Legend
3AH Vacuum
Circuit-Breakers
21
23
22
22
11
-S1
-S10
21
A1
-K1
-M1 M
-V1 u
D2
21
u
2
-K1
-S11 22
-Y9
22
-S22 21
22
-S3
12
-S7
21
21
13
22
14
-S1
22
24
21
-S6
14
-S41 13
-S42 21
13
14
22
-V2 u
31
2
32
A1
-K1 A1
-Y1 A1
A2
A2
A2
Breaker tripping
signal
Closing spring
charged signal
HG11-2394a eps
-S21
1st shunt
release
Auxiliary switch -S1 (12 NO + 12 NC), instead of the auxiliary switch with 6 NO + 6 NC
-X0
-X0
21
-S21
22
1
A1
-S1
-M1 M
-V1 u
D2
13
21 23
31 33
41 43
51
53
61 63
71 73
81 83
91 93
101 103
111 113
121 123
12
14
22 24
32 34
42 44
52
54
62 64
72 74
82 84
92 94
122 124
HG11-2397a eps
21
-X0
HG11-2395 eps
22
-X0
Motor-operated
mechanism
L+
L+
Tripping
via NC
contact
Tripping
via NO
contact
Wiring in
the system
-X0
43
43
-S1
-Y7 D1
U<
D2
-S1
44
-Y7 D1
for deritry
n
ircu f the u
c
l
a
o
c
Typi ection ase
1 conn
rele
age
-R1
volt
2
U<
D2
44
Wiring in the
vacuum circuit-breaker
L-
33
-S1
34
-Y2 A1
-A1
A2
HG11-2403a eps
-R1
-X0
L+
-X0
L-
Wiring in the
system
-X0
HG11-2404a eps
-S22
11
3AH Vacuum
Circuit-Breakers
Schematic diagrams for 3AH5 vacuum circuit-breakers Not binding examples only
Basic equipment
Manual closing Manual tripping
HA
Manual tripping
without wiring
HE
Manual closing
K1
Contactor (anti-pumping)
M1
Motor-operated mechanism
Stored-energy mechanism
R1
Resistor
S1
Auxiliary switch
Position switch
(opens when closing spring
charged)
S4
Position switch
(signal charging state)
S6
S7
X0
Y1
Y6
Low-energy current
transformer-operated release
Y7
Undervoltage release
Y9
Closing solenoid
-S3
-S4
-S1
P
-S7
-S6
Release OFF
HA
11
13
21 23
12
14
22 24
-M1 M
-S22
2 NO + 2 NC contacts
available to the customer
-Y1
HG11-2405a eps
Additional equipment
-X0
-X0
-S21
-X0
-S3
21
22
21
13
22
31
14
-M1 M
-S7
-K1
-S6
32
22
-Y9 A1
-K1 A1
A2
A2
-X0
HG11-2264a eps
21
Motor-operated
mechanism *
21
22
D2
-S22
6 NO + 6 NC or 12 NO + 12 NC
(instead of 2 NO + 2 NC in the
basic equipment).
Most of these contacts are available to the customer and on
request can in some cases be
wired to a plug connector or terminal strip (see page 1/11).
22
21
-K1
A1
Auxiliary switch
-X0
13
Wiring of the
secondary equipment
14
Closing and
anti-pumping *
HG11-2269a eps
S3
-S21
HG11-2265b eps
-Y9
HE
-X0
Wiring to choice of
64-pole plug connector or
24-pole plug connector or
24-pole terminal strip
-X0
-S4
-X0
13
14
21
-X0
-X0
-Y1 A1
-Y7 D1
-Y6 A1
A2
U<
D2
A2
22
Closing spring
charged signal *
-X0
Undervoltage
release *
-X0
HG11-2268a eps
-X0
1st shunt
release *
-R1
HG11-2267a eps
-X0
HG11-2266a eps
1
HG11-2270a eps
Legend
Abbreviations:
NO = normally-open
NC = normally-closed
3AH Vacuum
Circuit-Breakers
Standards
Standards
Tests
Insulating capacity
Ambient conditions
ANSI C37.013
(only 3AH3 83 high-current
circuit-breakers up to 63 kA)
Ambient temperature
HG11-2271a eps
BS 5311
VDE 0670
0.9
Correction factor a
IEC 60 056
IEC 60 694
0.8
Highest value:
Highest value of
24-hour mean:
Lowest value:
+40 C
+35 C
5 C
0.7
Relative humidity
(average values measured):
0.6
0.1
0
1.1 a
Over 24 hours:
Over 1 month:
max. 95%
max. 90%
Definitions:
Rated lightning impulse withstand voltage or rated shorttime power frequency
voltage 1) = target value
according to VDE, IEC, etc.
referred to sea level.
Lightning impulse withstand
voltage or power frequency
withstand voltage 2)
= actual value
at the respective height.
The vacuum circuit-breakers for
15 kV rated voltage meet the
requirements of the American
standard ANSI C 37 with respect to their insulating capacity.
1) Rated
lightning impulse withstand voltage
Rated short-time
power frequency voltage
2) Lightning impulse withstand voltage
Power frequency withstand voltage
Siemens HG 11.11 19991/15
3AH Vacuum
Circuit-Breakers
7.2 to 36 kV
R-HG11-065a eps
R-HG11-062a eps
Page
Rated data
Selection and ordering data
Electrical and
mechanical service life
Dimensions and weights
Secondary equipment
For rated voltages
7.2 kV
12 kV
15 kV
17.5 kV
24 kV
36 kV
Enquiry form
2/22/3
2/42/5
2/62/7
2/82/9
2/102/11
2/122/13
A/2
3AH Vacuum
Circuit-Breakers
R-HG11-066a eps
7.2 kV
3AH1 055-4
31.5 kA / 2000 A
Isc
Ima
Polecentre
distance
kA
kA
mm
Please add
Order No.
suffix
210
3AH1 053-
25
63
210
3AH1 054-
31.5
80
210
3AH1 055-
100
210
3AH1 056-
2000 A
2500 A
3150 A
210
3AH3 057-
63 (can
160
be used up
to 72 kA)
275
3AH3 078-
rm
iry fo
Enqu e A / 2
ag
see p
4000 A
50
1250 A
40
Remarks
O - 3min - CO - 3min - CO
800 A
20
Ima up to 181 kA
Electrical service life (load char. Nos. 1 to 8 ) Mechanical breaker service life 10,000 operating cycles
50 000
20 000
10 000
5 000
2 000
1 000
500
200
140
80
100
100 000
50 000
20 000
10 000
5 000
2 000
1 000
500
145
200
20
1
10
3
20 31.5 50 kA 100
25
50 000
20 000
10 000
5 000
2 000
1 000
500
200
75
100
50
20
10
100 000
85 100
50
50
10
HG11-2236a eps
HG11-2234a eps
100 000
HG11-2235a eps
10
6
20 31.5 50 kA 100
25 40
20
10
10
20
8
50 kA 100
63
3AH Vacuum
Circuit-Breakers
Secondary equipment
522
520
105
20 kA / up to 1250 A
473
437
60
520
549
550
210
105
210
Current transformer-operated
release 0.5 A / 1 A, type 3AX11 02
40 kA / 1250 A, 2000 A,
2500 A, 3150 A
Current transformer-operated
release 0.1 Ws, type 3AX11 04
587
437
HG11-2196e eps
Undervoltage release
type 3AX11 03
109
1250/2000 A 550 mm
2500/3150 A 565 mm
a
550
210
105
561
50 kA / up to 3150 A
668
494
Anti-pumping
mechanical and electrical
Breaker tripping signal
Operating cycle counter
switches (2 pieces)
Position
for signalling
70
HG11-2212a eps
610
A current transformer-operated
release for a tripping pulse of
0.1 Ws is used in connection
with the 7SJ41 protective
system or with the protective
relay made by SEG
Auxiliary switch 6 NO + 6 NC
Dimension a in mm
210
Closing
type 3AY15 10
shunt release
Refer to table below for
1st
type 3AY15 10
release combinations
25 kA / 2000 A, 2500 A
190
604
Remarks
Additional equipment
Weight approx. 75 kg
190
HG11-2194c eps
Basic equipment
25 kA / up to 1250 A
604
Pole-centre distance
210 mm
210
210
7.2 kV
571
a
c
275
63 kA
HG11-2213a eps
211
494
105
275
Pole-centre distance
275 mm
Mechanical interlocking
Varistor circuitry
Weight at 4000 A
approx. 308 kg
Condensation protection
For 230 V AC
Silver-plated or tinned
primary current paths
Hand crank
Silicone-free design
105
d
e
In place of mechanical
local closing
Weight up to 3150 A
approx. 196 kg
Dimensions in mm
776
a
b
c
d
e
To 3150A
mm
680
668
591
601
4000 A
mm
750
733
694
Release combinations
1
2nd release
3rd release
3AH Vacuum
Circuit-Breakers
R-HG11-067a eps
12 kV
3AH3 117-7
50 kA / 3150 A
Rated voltage 12 kV
Rated lightning impulse withstand voltage 75 kV
Rated short-time power frequency
withstand voltage 28 kV*
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
* Up to 42 kV on request
Isc
Ima
Polecentre
distance
kA
kA
mm
Please add
Order No.
suffix
210
3AH1 113-
25
63
63
160
210
3AH1 104-
3AH1 114-
80
80
160
210
3AH1 105-
3AH1 115-
40
100
210
3AH1 116-
50
125
210
3AH3 117-
63
160
275
3AH3 128-
1250 A
2000 A
2500 A
3150 A
rm
iry fo
Enqu e A / 2
ag
see p
4000 A
Remarks
O - 3min - CO - 3min - CO
800 A
20
2
2
2
2
Electrical service life (load char. Nos. 1 to 8 ) Mechanical breaker service life 10,000 operating cycles
50 000
20 000
10 000
5 000
2 000
1 000
500
200
140
80
100
100 000
50 000
20 000
10 000
5 000
2 000
1 000
500
145
200
20
1
10
3
20 31.5 50 kA 100
25
50 000
20 000
10 000
5 000
2 000
1 000
500
200
75
100
50
20
10
100 000
85 100
50
50
10
HG11-2236a eps
HG11-2234a eps
100 000
HG11-2235a eps
10
6
20 31.5 50 kA 100
25 40
20
10
10
20
8
50 kA 100
63
3AH Vacuum
Circuit-Breakers
Secondary equipment
422
519
25 kA / up to 1250 A
31.5 kA / up to 1250 A
473
60
435
HG11-2214a eps
520
105
Current transformer-operated
release 0.1 Ws, type 3AX11 04
25 kA / up to 1250 A
Weight approx. 75 kg
Undervoltage release
type 3AX11 03
473
437
Current transformer-operated
release 0.5 A / 1 A, type 3AX11 02
20 kA / up to 1250 A
190
HG11-2194c eps
Pole-centre distance
210 mm
210
210
Remarks
Additional equipment
also be manually controlled
Electrical operating mechanism Can
Option: with manual control
solenoid
Closing
type 3AY15 10
shunt release
Refer to table below for
1st
type 3AY15 10
release combinations
519
522
Basic equipment
Weight approx. 62 kg
188
492
Pole-centre distance
160 mm
160
105
160
12 kV
A current transformer-operated
release for a tripping pulse of
0.1 Ws is used in connection
with the 7SJ41 protective
system or with the protective
relay made by SEG
60
Auxiliary switch 6 NO + 6 NC
604
520
549
25 kA / 2000 A, 2500 A
550
210
105
210
40 kA / 1250 A, 2000 A,
2500 A, 3150 A
190
587
437
HG11-2196e eps
109
1250/2000 A 550 mm
2500/3150 A 565 mm
a
Anti-pumping
mechanical and electrical
Breaker tripping signal
Operating cycle counter
switches (2 pieces)
Position
for signalling
550
210
561
105
210
604
50 kA / up to 3150 A
668
211
70
HG11-2212a eps
494
610
571
Pole-centre distance
275 mm
275
211
105
HG11-2213a eps
494
Weight up to 3150 A
approx. 196 kg
d
776
In place of mechanical
local closing
Mechanical interlocking
Varistor circuitry
Condensation protection
For 230 V AC
Silver-plated or tinned
primary current paths
Hand crank
Silicone-free design
63 kA
105
275
Release combinations
Weight at 4000 A
approx. 308 kg
Dimensions in mm
2nd release
To 3150A
mm
a 680
b 668
c 591
d 601
e
3rd release
4000 A
mm
750
733
694
3AH Vacuum
Circuit-Breakers
R-HG11-074a eps
15 kV
3AH1 166-6
40 kA / 2500 A
Rated voltage 15 kV
Rated lightning impulse withstand voltage 95 kV
Rated short-time power frequency
withstand voltage 36 kV*
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
* Up to 42 kV on request
Isc
Ima
Polecentre
distance
kA
kA
mm
Please add
Order No.
suffix
210
3AH1 163-
25
63
63
160
210
3AH1 154-
3AH1 164-
80
210
3AH1 165-
1
1
210
3AH1 166-
50
125
210
3AH3 167-
63
160
275
3AH3 178-
2000 A
2500 A
3150 A
rm
iry fo
Enqu e A / 2
ag
see p
4000 A
40
1250 A
1
31.5
Remarks
O - 3min - CO - 3min - CO
800 A
20
2
2
Ima up to 110 kA
Electrical service life (load char. Nos. 1 to 8 ) Mechanical breaker service life 10,000 operating cycles
50 000
20 000
10 000
5 000
2 000
1 000
500
200
140
80
100
100 000
50 000
20 000
10 000
5 000
2 000
1 000
500
145
200
20
1
10
3
20 31.5 50 kA 100
25
50 000
20 000
10 000
5 000
2 000
1 000
500
200
75
100
50
20
10
100 000
85 100
50
50
10
HG11-2236a eps
HG11-2234a eps
100 000
HG11-2235a eps
10
6
20 31.5 50 kA 100
25 40
20
10
10
20
8
50 kA 100
63
3AH Vacuum
Circuit-Breakers
Secondary equipment
160
105
25 kA / up to 1250 A
Weight approx. 67 kg
473
600
519
522
105
Current transformer-operated
release 0.1 Ws, type 3AX11 04
Weight approx. 75 kg
473
Undervoltage release
type 3AX11 03
60
520
549
550
25 kA /
2000 A, 2500 A
210
105
588
437
Weight
120 to 130 kg
Dimension a in mm
604
550
1250/2000 A 550 mm
2500/3150 A 565 mm
679
561
210
105
668
800
494
169
HG11-2216a eps
211
494
105
63 kA
192**
105*
d
f
e
In place of mechanical
local closing
Mechanical interlocking
Varistor circuitry
Condensation protection
For 230 V AC
Silver-plated or tinned
primary current paths
Hand crank
Silicone-free design
Weight up to 3150 A
approx. 198 kg
Release
Weight at 4000 A
approx. 310 kg
2nd release
3rd release
Dimensions in mm
776
Pole-centre distance
275 mm
275
571
HG11-2217a eps
Anti-pumping
mechanical and electrical
Breaker tripping signal
Operating cycle counter
switches (2 pieces)
Position
for signalling
50 kA / up to 3150 A
610
275
40 kA /
1250 to 3150 A
109
HG11-2200d eps
31.5 kA /
1250 to 2500 A
190
210
A current transformer-operated
release for a tripping pulse of
0.1 Ws is used in connection
with the 7SJ41 protective
system or with the protective
relay made by SEG
Auxiliary switch 6 NO + 6 NC
604
210
Current transformer-operated
release 0.5 A /1 A, type 3AX11 02
25 kA / up to 1250 A
437
HG11-2198d eps
20 kA / up to 1250 A
190
Remarks
Additional equipment
Pole-centre distance
210 mm
520
210
210
Basic equipment
Closing
type 3AY15 10
shunt release
Refer to table below for
1st
type 3AY15 10
release combinations
70
435
HG11-2215a eps
188
492
Pole-centre distance
160 mm
584
519
422
160
15 kV
To 3150A
mm
a 680
b 668
c 591
d 601
e
f
g
4000 A
mm
750
733
694
623
697
Release combinations
3AH Vacuum
Circuit-Breakers
R-HG11-057a eps
17.5 kV
3AH3 228-7
63 kA / 3150 A
(Partitions not
shown)
Isc
Ima
Polecentre
distance
kA
kA
mm
Please add
Order No.
suffix
210
3AH1 213-
25
63
63
160
210
3AH1 204-
3AH1 214-
80
210
3AH1 215-
1250 A
2000 A
2500 A
3150 A
2
2
7
7
8
8
100
210
3AH1 216-
50
125
210
3AH3 217-
63
160
160
275
275
3AH3 228-
3AH3 818-
rm
iry fo
Enqu e A / 2
ag
see p
4000 A
Remarks
O - 3min - CO - 3min - CO
800 A
20
Ima up to 110 kA
Electrical service life (load char. Nos. 1 to 7 ) Mechanical breaker service life 10,000 operating cycles
50 000
20 000
10 000
5 000
2 000
1 000
500
200
140
80
50 000
20 000
10 000
5 000
2 000
1 000
500
85
50
1
1
10
2
20
25
50 kA 100
10
20 000
10 000
5 000
2 000
1 000
500
200
100
50
3
20
10
50 000
200
100
50
20
10
100 000
145
100
5
HG11-2238b eps
HG11-2237b eps
100 000
HG11-2378 eps
30
20
6
10
20 31.5 50 kA 100
25 40
10
20
7
50 kA 100
63
3AH Vacuum
Circuit-Breakers
Secondary equipment
160
105
25 kA / up to 1250 A
Weight approx. 67 kg
473
600
519
522
105
Current transformer-operated
release 0.1 Ws, type 3AX11 04
Weight approx. 75 kg
473
Undervoltage release
type 3AX11 03
60
520
549
550
25 kA /
2000 A, 2500 A
210
105
588
437
Weight
120 to 135 kg
Dimension a in mm
604
550
1250/2000 A 550 mm
2500/3150 A 565 mm
679
561
210
105
Weight approx. 75 kg
668
800
494
211
169
HG11-2216a eps
105
63 kA
494
211
105*
d
f
e
In place of mechanical
local closing
Mechanical interlocking
Varistor circuitry
Condensation protection
For 230 V AC
Silver-plated or tinned
primary current paths
Hand crank
Silicone-free design
Weight up to 3150 A
approx. 198 kg
Release
Weight at 4000 A
approx. 310 kg
2nd release
3rd release
Dimensions in mm
776
Pole-centre distance
275 mm
275
192**
Anti-pumping
mechanical and electrical
Breaker tripping signal
Operating cycle counter
switches (2 pieces)
Position
for signalling
Closing spring charged
571
HG11-2217a eps
50 kA / up to 3150 A
610
275
40 kA /
1250 up to 3150 A
109
HG11-2200d eps
31.5 kA /
1250 up to 2500 A
190
210
A current transformer-operated
release for a tripping pulse of
0.1 Ws is used in connection
with the 7SJ41 protective
system or with the protective
relay made by SEG
Auxiliary switch 6 NO + 6 NC
604
210
Current transformer-operated
release 0.5 A / 1 A, type 3AX11 02
25 kA / up to 1250 A
437
HG11-2198d eps
20 kA / up to 1250 A
190
Remarks
Additional equipment
Pole-centre distance
210 mm
520
210
210
Basic equipment
Closing
type 3AY15 10
shunt release
Refer to table below for
1st
type 3AY15 10
release combinations
70
435
HG11-2215a eps
188
492
Pole-centre distance
160 mm
584
519
422
160
17.5 kV
To 3150A
mm
a 680
b 668
c 590
d 600
e
f
g
4000 A
mm
750
733
694
623
697
Release combinations
3AH Vacuum
Circuit-Breakers
R-HG11-060a eps
24 kV
3AH1 284-2
25 kA / 1250 A
Rated voltage 24 kV
Rated lightning impulse withstand voltage 125 kV
Rated short-time power frequency
withstand voltage 50 kV
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
Isc
Ima
Polecentre
distance
kA
kA
mm
Please add
Order No.
suffix
Remarks
210
275
3AH1 252-
3AH1 262-
20
50
50
210
3AH1 273-
3AH1 253-
50
50
275
3AH1 283-
3AH1 263-
63
63
210
63
63
275
100
275
1250 A
1250 A
2000 A
2
2
2
3AH1 284-
3AH1 264-
3AH1 274-
3AH1 254-
rm
iry fo
Enqu e A / 2
ag
see p
2500 A
1
1
25
O - 3min - CO - 3min - CO
16
3AH3 266-
Electrical service life (load char. Nos. 1 to 6 ) Mechanical breaker service life 10,000 operating cycles
50 000
20 000
10 000
5 000
2 000
1 000
500
80
100 000
50 000
20 000
10 000
5 000
2 000
1 000
500
100 000
50 000
20 000
10 000
5 000
2 000
1 000
500
200
200
200
100
100
100
90
50
50
50
HG11-2241a eps
HG11-2239b eps
100 000
HG11-2240a eps
35
20
20
10
1
1
10
3
20
16
25
10
50 kA 100
10
10
20
25
20
50 kA 100
10
50 kA 100
20
40
3AH Vacuum
Circuit-Breakers
Secondary equipment
532
16 kA / up to 1250 A
105
20 kA / up to 1250 A
(only for type
3AH1 27.-.)
700
437
HG11-2206c eps
190
102
565
540
690
595
210
Closing
type 3AY15 10
shunt release
Refer to table below for
1st
type 3AY15 10
release combinations
2nd shunt release
type 3AX1101
Current transformer-operated
release 0.1 Ws, type 3AX11 04
790
437
Undervoltage release
type 3AX11 03
188
662
565
Pole-centre distance
275 mm
275
275
105
16 kA / up to 1250 A
535
25 kA / up to 1250 A
(only for type
3AH1 28.-.)
60
437
HG11-2202c eps
190
20 kA / up to 1250 A
(only for type
3AH1 28.-.)
708
565
670
595
Weight
120 kg to 130 kg
20 kA
(for type 3AH1 263-.)
275
25 kA
(for type 3AH1 264-.)
105
275
Weight
120 kg to 130 kg
HG11-2205c eps
437
648
190
Dimensions a in mm
109
1250/2000 A 595 mm
2500 A
610 mm
708
680
275
773
635
275
A current transformer-operated
release for a tripping pulse of
0.1 Ws is used in connection
with the 7SJ41 protective
system or with the protective
relay made by SEG
Auxiliary switch 6 NO + 6 NC
1250/2000 A 595 mm
2500 A
610 mm
604
Current transformer-operated
release 0.5 A /1 A, type 3AX11 02
Weight
120 kg to 130 kg
Dimension a in mm
Remarks
Additional equipment
25 kA
(for type 3AH1 254-.)
190
HG11-2209b eps
Basic equipment
20 kA
(for type 3AH1 253-.)
105
210
25 kA / up to 1250 A
(only for type
3AH1 27.-.)
Weight approx. 85 kg
604
Pole-centre distance
210 mm
635
565
210
210
24 kV
Anti-pumping
mechanical and electrical
Breaker tripping signal
Operating cycle counter
switches (2 pieces)
Position
for signalling
In place of mechanical
local closing
Mechanical interlocking
Varistor circuitry
Condensation protection
For 230 V AC
Silver-plated or tinned
primary current paths
Hand crank
Silicone-free design
40 kA / 2500 A
105
Weight
approx. 168 kg
778
1030
Release
Release combinations
1
2nd release
3rd release
194
HG11-2218a eps
494
210
704
645
3AH Vacuum
Circuit-Breakers
R-HG11-126 eps
36 kV
3AH3 305-6
31.5 kA / 2500 A
(Partitions
not shown)
Isc
Ima
Polecentre
distance
kA
kA
mm
Please add
Order No.
suffix
350
3AH3 305-
100
350
3AH3 306-
Remarks
80
O - 3min - CO - 3min - CO
2000 A
rm
iry fo
Enqu e A / 2
ag
see p
2500 A
Electrical service life (load char. Nos. 1 and 2 ) Mechanical breaker service life 10,000 operating cycles
Load char. No. 2
20 000
10 000
5 000
2 000
1 000
500
100 000
50 000
20 000
10 000
5 000
2 000
500
200
100
100
50
1
20
10
1 000
200
50
HG11-2255a eps
HG11-2242a eps
50 000
100 000
Kennlinien-Nr.
Zulssige Schaltspiele
10
20
31.5
50 kA 100
20
10
10
50 kA 100
20
40
Ausschaltstrom (Effektivwert)
3AH Vacuum
Circuit-Breakers
Secondary equipment
Pole-centre
distance
350 mm
823
737
820
350
350
36 kV
Basic equipment
Remarks
HG11-2219a eps
734
1000
494
105
Additional equipment
211
234
31.5 kA /
up to 2000 A
Weight
approx. 175 kg
853
737
820
823
737
350
Closing
type 3AY15 10
shunt release
Refer to table below for
1st
type 3AY15 10
release combinations
350
Current transformer-operated
release 0.5 A/1 A, type 3AX11 02
Current transformer-operated
release 0.1 Ws, type 3AX11 04
Undervoltage release
type 3AX11 03
A current transformer-operated
release for a tripping pulse of
0.1 Ws is used in connection
with the 7SJ41 protective
system or with the protective
relay made by SEG
HG11-2220a eps
791
1000
494
105
Auxiliary switch 6 NO + 6 NC
211
31.5 kA /
2500 A
234
40 kA /
2500 A
853
Weight
approx. 180 kg
737
Anti-pumping
mechanical and electrical
Breaker tripping signal
Operating cycle counter
switches (2 pieces)
Position
for signalling
In place of mechanical
local closing
Mechanical interlocking
Varistor circuitry
Condensation protection
For 230 V AC
Silver-plated or tinned
primary current paths
Hand crank
Silicone-free design
Release combinations
1
2nd release
3rd release
3AH Vacuum
Circuit-Breakers
R-HG11-070 eps
R-HG11-127 eps
R-HG11-071b eps
7.2 to 36 kV
Page
Rated data
Selection and ordering data
Electrical and
mechanical service life
Dimensions and weights
Secondary equipment
7.2 kV
12 kV
15 kV
17.5 kV
24 kV
36 kV
Enquiry form
3 /23 /3
3 /43 /5
3 /63 /7
3 /83 /9
3 /103 /11
3 /123 /13
A/2
3AH Vacuum
Circuit-Breakers
R-HG11-073a eps
7.2 kV
3AH2 056-6
40 kA / 2500 A
Polecentre
distance
kA
kA
mm
Please add
Order No.
suffix
210
3AH2 055-
100
210
3AH2 056-
Remarks
80
O - 3min - CO - 3min - CO
2000 A
2500 A
rm
iry fo
Enqu e A / 2
ag
see p
3150 A
Electrical service life (load char. Nos. 1 and 2 ) Mechanical breaker service life 60,000 operating cycles
Load char. No. 2
30 000
20 000
10 000
5 000
2 000
1 000
500
85
100 000
50 000
30 000
20 000
10 000
5 000
2 000
500
200
100
100
50
1
20
10
1 000
200
50
HG11-2244a eps
HG11-2243a eps
50 000
100 000
Kennlinien-Nr.
Zulssige Schaltspiele
Isc
10
50 kA 100
20
31.5
20
10
10
50 kA 100
20
40
Ausschaltstrom (Effektivwert)
3AH Vacuum
Circuit-Breakers
Secondary equipment
549
Pole-centre distance
210 mm
550
210
105
210
587
HG11-2227b eps
437
190
109
31.5 kA /
1250 A, 2000 A,
2500 A
Basic equipment
40 kA /
1250 A, 2000 A,
2500 A, 3150 A
Closing
type 3AY15 10
shunt release
Refer to table below for
1st
type 3AY15 10
release combinations
7.2 kV
Dimension a in mm
1250/2000 A 550 mm
2500/3150 A 565 mm
Remarks
Additional equipment
A current transformer-operated
Current transformer-operated
release for a tripping pulse of
release 0.5 A /1 A, type 3AX11 02
0.1 Ws is used in connection
with the 7SJ41 protective
Current transformer-operated
system or with the protective
release 0.1 Ws, type 3AX11 04
relay made by SEG
Undervoltage release
type 3AX11 03
Auxiliary switch 6 NO + 6 NC
Auxiliary switch 12 NO + 12 NC*
strip 24-pole or
Terminal
plug connector
64-pole or 24-pole
Anti-pumping
mechanical and electrical
Breaker tripping signal
Operating cycle counter
switches (2 pieces)
Position
for signalling
In place of mechanical
local closing
Mechanical interlocking
Varistor circuitry
Condensation protection
For 230 V AC
Silver-plated or tinned
primary current paths
Hand crank
Silicone-free design
Release combinations
1
2nd release
3rd release
3AH Vacuum
Circuit-Breakers
R-HG11-073a eps
12 kV
3AH2 116-6
40 kA / 2500 A
Rated voltage 12 kV
Rated lightning impulse withstand voltage 75 kV
Rated short-time power frequency
withstand voltage 28 kV*
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
* Up to 42 kV on request
Polecentre
distance
kA
kA
mm
Please add
Order No.
suffix
210
3AH2 115-
100
210
3AH2 116-
Remarks
80
O - 3min - CO - 3min - CO
2000 A
2500 A
rm
iry fo
Enqu e A / 2
ag
see p
3150 A
Electrical service life (load char. Nos. 1 and 2 ) Mechanical breaker service life 60,000 operating cycles
Load char. No. 2
30 000
20 000
10 000
5 000
2 000
1 000
500
85
100 000
50 000
30 000
20 000
10 000
5 000
2 000
500
200
100
100
50
1
20
10
1 000
200
50
HG11-2244a eps
HG11-2243a eps
50 000
100 000
Kennlinien-Nr.
Zulssige Schaltspiele
Isc
10
50 kA 100
20
31.5
20
10
10
50 kA 100
20
40
Ausschaltstrom (Effektivwert)
3AH Vacuum
Circuit-Breakers
Secondary equipment
549
Pole-centre distance
210 mm
550
210
105
210
587
HG11-2227b eps
437
190
109
31.5 kA /
1250 A, 2000 A,
2500 A
Basic equipment
40 kA /
1250 A, 2000 A,
2500 A, 3150 A
Closing
type 3AY15 10
shunt release
Refer to table below for
1st
type 3AY15 10
release combinations
12 kV
Dimension a in mm
1250/2000 A 550 mm
2500/3150 A 565 mm
Remarks
Additional equipment
Current transformer-operated
release 0.5 A /1 A, type 3AX11 02
Current transformer-operated
release 0.1 Ws, type 3AX11 04
Undervoltage release
type 3AX11 03
Auxiliary switch 6 NO + 6 NC
Auxiliary switch 12 NO + 12 NC*
strip 24-pole or
Terminal
plug connector
64-pole or 24-pole
A current transformer-operated
release for a tripping pulse of
0.1 Ws is used in connection
with the 7SJ41 protective
system or with the protective
relay made by SEG
Anti-pumping
mechanical and electrical
Breaker tripping signal
Operating cycle counter
switches (2 pieces)
Position
for signalling
In place of mechanical
local closing
Mechanical interlocking
Varistor circuitry
Condensation protection
For 230 V AC
Silver-plated or tinned
primary current paths
Hand crank
Silicone-free design
Release combinations
1
2nd release
3rd release
3AH Vacuum
Circuit-Breakers
15 kV
Rated voltage 15 kV
Rated lightning impulse withstand voltage 95 kV
Rated short-time power frequency
withstand voltage 36 kV*
R-HG11-074a eps
3AH2 166-6
40 kA / 2500 A
Polecentre
distance
kA
kA
mm
Please add
Order No.
suffix
210
3AH2 165-
100
210
3AH2 166-
Remarks
80
O - 3min - CO - 3min - CO
2000 A
2500 A
rm
iry fo
Enqu e A / 2
ag
see p
3150 A
Ima up to 110 kA
Electrical service life (load char. Nos. 1 and 2 ) Mechanical breaker service life 60,000 operating cycles
Load char. No. 2
30 000
20 000
10 000
5 000
2 000
1 000
500
85
100 000
50 000
30 000
20 000
10 000
5 000
2 000
500
200
100
100
50
1
20
10
1 000
200
50
HG11-2244a eps
HG11-2243a eps
50 000
100 000
Kennlinien-Nr.
Zulssige Schaltspiele
Isc
10
50 kA 100
20
31.5
20
10
10
50 kA 100
20
40
Ausschaltstrom (Effektivwert)
3AH Vacuum
Circuit-Breakers
Secondary equipment
549
Pole-centre distance
210 mm
550
210
105
210
587
HG11-2228b eps
437
190
109
31.5 kA /
1250 A, 2000 A,
2500 A
Basic equipment
40 kA /
1250 A, 2000 A,
2500 A, 3150 A
Closing
type 3AY15 10
shunt release
Refer to table below for
1st
type 3AY15 10
release combinations
15 kV
Dimension a in mm
1250/2000 A 550 mm
2500/3150 A 565 mm
Remarks
Additional equipment
Current transformer-operated
release 0.5 A/1 A, type 3AX1102
Current transformer-operated
release 0.1 Ws, type 3AX11 04
Undervoltage release
type 3AX11 03
Auxiliary switch 6 NO + 6 NC
Auxiliary switch 12 NO + 12 NC*
strip 24-pole or
Terminal
plug connector
64-pole or 24-pole
Anti-pumping
mechanical and electrical
Breaker tripping signal
Operating cycle counter
switches (2 pieces)
Position
for signalling
In place of mechanical
local closing
Mechanical interlocking
Varistor circuitry
Condensation protection
For 230 V AC
Silver-plated or tinned
primary current paths
Hand crank
Silicone-free design
Release combinations
1
2nd release
3rd release
3AH Vacuum
Circuit-Breakers
R-HG11-074a eps
17.5 kV
3AH2 215-6
31.5 kA / 2500 A
Polecentre
distance
kA
kA
mm
Please add
Order No.
suffix
210
3AH2 215-
100
210
3AH2 216-
Remarks
80
O - 3min - CO - 3min - CO
2000 A
2500 A
rm
iry fo
Enqu e A / 2
ag
see p
3150 A
Ima up to 110 kA
Electrical service life (load char. Nos. 1 and 2 ) Mechanical breaker service life 60,000 operating cycles
Load char. No. 2
30 000
20 000
10 000
5 000
2 000
1 000
500
85
100 000
50 000
30 000
20 000
10 000
5 000
2 000
500
200
100
100
50
1
20
10
1 000
200
50
HG11-2244a eps
HG11-2243a eps
50 000
100 000
Kennlinien-Nr.
Zulssige Schaltspiele
Isc
10
50 kA 100
20
31.5
20
10
10
50 kA 100
20
40
Ausschaltstrom (Effektivwert)
3AH Vacuum
Circuit-Breakers
Secondary equipment
549
Pole-centre distance
210 mm
550
210
105
210
587
HG11-2228b eps
437
190
109
31.5 kA /
1250 A, 2000 A,
2500 A, 3150 A
Basic equipment
40 kA /
1250 A, 2000 A,
2500 A, 3150 A
Closing
type 3AY15 10
shunt release
Refer to table below for
1st
type 3AY15 10
release combinations
17.5 kV
Dimension a in mm
1250/2000 A 550 mm
2500/3150 A 565 mm
Remarks
Additional equipment
Current transformer-operated
release 0.5 A/1 A, type 3AX1102
Current transformer-operated
release 0.1 Ws, type 3AX11 04
Undervoltage release
type 3AX11 03
Auxiliary switch 6 NO + 6 NC
Auxiliary switch 12 NO + 12 NC*
strip 24-pole or
Terminal
plug connector
64-pole or 24-pole
Anti-pumping
mechanical and electrical
Breaker tripping signal
Operating cycle counter
switches (2 pieces)
Position
for signalling
In place of mechanical
local closing
Mechanical interlocking
Varistor circuitry
Condensation protection
For 230 V AC
Silver-plated or tinned
primary current paths
Hand crank
Silicone-free design
Release combinations
1
2nd release
3rd release
3AH Vacuum
Circuit-Breakers
R-HG11-124 eps
24 kV
3AH4 266-6
40 kA / 2500 A
(Partitions
not shown)
Rated voltage 24 kV
Rated lightning impulse withstand voltage 125 kV
Rated short-time power frequency
withstand voltage 50 kV
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
Isc
Ima
Polecentre
distance
kA
kA
mm
Please add
Order No.
suffix
210
275
3AH2 254-
3AH2 264-
40
100
275
3AH4 266-
Remarks
O - 3min - CO - 3min - CO
1250 A
25
2
2
2000 A
rm
iry fo
Enqu e A / 2
g
a
see p
2500 A
4
4
6
6
30 000
20 000
10 000
5 000
2 000
1 000
500
100 000
50 000
30 000
20 000
10 000
5 000
2 000
1 000
500
200
200
100
100
50
50
1
20
10
HG11-2246a eps
HG11-2245a eps
50 000
100 000
10
1
10
20
25
50 kA 100
20
1
10
50 kA 100
20
40
3AH Vacuum
Circuit-Breakers
Secondary equipment
540
690
595
210
Pole-centre distance
210 mm
25 kA /
1250 A, 2000 A,
2500 A
105
210
Weight approx.130 kg
790
HG11-2229a eps
437
190
188
Dimension a in mm
1250/2000 A 595 mm
2500 A
610 mm
604
670
595
Pole-centre distance
275 mm
275
25 kA /
1250 A, 2000 A,
2500 A
105
275
HG11-2230a eps
437
648
190
Weight approx.130 kg
Basic equipment
Closing
type 3AY15 10
shunt release
Refer to table below for
1st
type 3AY15 10
release combinations
2nd shunt release
type 3AX1101
Current transformer-operated
release 0.1 Ws, type 3AX11 04
Undervoltage release
type 3AX11 03
Auxiliary switch 6 NO + 6 NC
Auxiliary switch 12 NO + 12 NC*
109
1250/2000 A 595 mm
2500 A
610 mm
a
680
64-pole or 24-pole
773
635
275
778
1030
105
Weight
approx.168 kg
494
HG11-2231a eps
A current transformer-operated
release for a tripping pulse of
0.1 Ws is used in connection
with the 7SJ41 protective
system or with the protective
relay made by SEG
40 kA / 2500 A
210
Current transformer-operated
release 0.5 A/1 A, type 3AX1102
strip 24-pole or
Terminal
plug connector
275
Remarks
Additional equipment
Dimension a in mm
714
24 kV
Anti-pumping
mechanical and electrical
Breaker tripping signal
Operating cycle counter
switches (2 pieces)
Position
for signalling
194
704
645
In place of mechanical
local closing
Mechanical interlocking
Varistor circuitry
Condensation protection
For 230 V AC
Silver-plated or tinned
primary current paths
Hand crank
Silicone-free design
Release combinations
1
2nd release
3rd release
3AH Vacuum
Circuit-Breakers
R-HG11-126 eps
36 kV
3AH4 305-6
31.5 kA / 2500 A
(Partitions
not shown)
Rated voltage 36 kV
Rated lightning impulse withstand voltage 170 kV*
Rated short-time power frequency
withstand voltage 70 kV**
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
* Up to 185 kV on request
** Up to 85 kV on request
Polecentre
distance
kA
kA
mm
Please add
Order No.
suffix
350
3AH4 305-
100
350
3AH4 306-
Remarks
80
O - 3min - CO - 3min - CO
2000 A
rm
iry fo
Enqu e A / 2
ag
see p
2500 A
Electrical service life (load char. Nos. 1 and 2 ) Mechanical breaker service life 120,000 operating cycles
Load char. No. 2
30 000
20 000
10 000
5 000
2 000
1 000
500
100 000
50 000
30 000
20 000
10 000
5 000
2 000
500
200
100
100
50
1
20
10
1 000
200
50
HG11-2248a eps
HG11-2247a eps
50 000
100 000
Kennlinien-Nr.
Zulssige Schaltspiele
Isc
10
20
31.5
50 kA 100
20
10
10
50 kA 100
20
40
Ausschaltstrom (Effektivwert)
3AH Vacuum
Circuit-Breakers
Secondary equipment
Pole-centre
distance 350 mm
823
737
820
350
350
36 kV
Basic equipment
Remarks
734
1000
211
31.5 kA /
up to 2000 A
234
HG11-2232a eps
494
105
Additional equipment
853
737
820
823
737
350
350
Weight
approx. 175 kg
Closing
type 3AY15 10
shunt release
Refer to table below for
1st
type 3AY15 10
release combinations
2nd shunt release
type 3AX1101
Current transformer-operated
release 0.5 A/1 A, type 3AX1102
Current transformer-operated
release 0.1 Ws, type 3AX11 04
Undervoltage release
type 3AX11 03
Auxiliary switch 6 NO + 6 NC
791
1000
494
105
211
40 kA /
2500 A
234
HG11-2233a eps
31.5 kA /
2500 A
853
737
strip 24-pole or
Terminal
plug connector
64-pole or 24-pole
Weight
approx. 180 kg
A current transformer-operated
release for a tripping pulse of
0.1 Ws is used in connection
with the 7SJ41 protective
system or with the protective
relay made by SEG
Anti-pumping
mechanical and electrical
Breaker tripping signal
Operating cycle counter
switches (2 pieces)
Position
for signalling
In place of mechanical
local closing
Mechanical interlocking
Varistor circuitry
Condensation protection
For 230 V AC
Silver-plated or tinned
primary current paths
Hand crank
Silicone-free design
Release combinations
1
2nd release
3rd release
3AH Vacuum
Circuit-Breakers
R-HG11-076a eps
12 to 36 kV
4
R-HG11-075a eps
Page
Rated data
Selection and ordering data
Electrical and mechanical
service life
Dimensions and weights
Secondary equipment
For rated voltages
12 kV
17.5 kV
24 kV
36 kV
Enquiry form
4 / 44 / 3
4 / 44 / 5
4 / 64 / 7
4 / 84 / 9
A/3
3AH Vacuum
Circuit-Breakers
12 kV
Rated voltage 12 kV
Rated lightning impulse withstand voltage 75 kV
Rated short-time power frequency
withstand voltage 28 kV*
R-HG11-077a eps
3AH5 103-2
20 kA / 1250 A
Ima
Polecentre
distance
Please add
Order No.
suffix
kA
kA
mm
13.1
32.8
32.8
160
210
3AH5 101-
3AH5 111-
16
40
40
160
210
3AH5 102-
3AH5 112-
20
50
50
160
210
3AH5 103-
3AH5 113-
25
63
63
160
210
3AH5 104-
3AH5 114-
O - 3min - CO - 3min - CO
Remarks
rm
iry fo
Enqu e A / 3
ag
see p
1250 A
1
1
2
2
1
1
2
2
1
1
2
2
1)
Possible
Electrical service life (load char. Nos. 1 to 4 ) Mechanical breaker service life 10,000 operating cycles
Load char. No. 2
5 000
2 000
1 000
500
25
50 000
20 000
10 000
5 000
2 000
1 000
500
100 000
50 000
20 000
10 000
5 000
2 000
1 000
500
200
200
200
100
100
100
50
50
25
20
1
10
0,5
50
20
3
10
20
kA 50
13.1
40
25
20
HG11-2272 eps
20 000
10 000
100 000
HG11-2250a eps
HG11-2249a eps
50 000
100 000
Kennlinien-Nr.
Load
char. Nos. 73 84
Permissible
Zulssige
operating
Schaltspiele
cycles
10
0,5
10
20
kA 50
16
10
0,5
10
4
20
25
kA 50
Breaking
Ausschaltstrom
current(Effektivwert)
(r.m.s. value)
3AH Vacuum
Circuit-Breakers
Secondary equipment
390
160 160
Pole-centre distance
160 mm
491
16 kA / up to 1250 A
Weight
35 kg to 45 kg
482
171
44
435
HG11-2221c eps
90
13.1 kA / 800 A
Remarks
490
491
Manual snap-action
operating mechanism
405
160 160
491
20 kA / up to 1250 A
25 kA / up to 1250 A
Current transformer-operated
release 0.5 A/1 A, type 3AX1102
90
482
Weight
40 kg to 45 kg
44
435
HG11-2222c eps
171
490
491
490
210
13.1 kA / 800 A
16 kA / up to 1250 A
Weight
40 kg to 50 kg
482
171
592
491
505
491
Undervoltage release
type 3AX1103
Auxiliary switch 2 NO+2 NC,
unwired
Auxiliary switch 6 NO+6 NC,*
unwired
210
90
210
Current transformer-operated
release 0.1Ws, type 3AX1104
44
435
HG11-2223c eps
90
210
Pole-centre distance
210 mm
491
25 kA / up to 1250 A
592
482
491
10
HG11-2252 eps
S1
9
10
S22
S4
S3
S21
11
99981
HG11-2253a eps
12
Maximum equipment
Mechanical interlocking
1 Gearbox
2 Position switch
Condensation protection
For 230 V AC
3 Closing spring
Hand crank
Silicone-free design
5 Closing spring
charged signal
8 Auxiliary switch
9 PushbuttonCLOSED
11 2nd release
3
4
5
6
10 PushbuttonOPEN
7 Closing solenoid
14
8
Option: 12 NO + 12 NC available
only with 64-pole plug connector
6 Operating cycle
counter
Basic equipment
Varistor circuitry
4 Motor
12
Secondary equipment
View into the
mechanism housing
S1
Weight
45 kg to 50 kg
44
435
HG11-2224c eps
20 kA / up to 1250 A
171
12 kV
12 1st release
13 Mechanical
interlocking
or scanning
14 Low-voltage
plug connector
Release combinations
1 2 3 4 5 6 7
3AH Vacuum
Circuit-Breakers
R-HG11-078a eps
17.5 kV
3AH5 204-1
25 kA / 800 A
(Partitions
not shown)
Ima
Polecentre
distance
kA
kA
mm
25
63
63
160
210
Please add
Order No.
suffix
O - 3min - CO - 3min - CO
Remarks
1
1
rm
iry fo
Enqu e A / 3
ag
see p
1250 A
1
2
2
1)
Electrical service life (load char. No. 1 ) Mechanical breaker service life 10,000 operating cycles
Load char. No. 1
HG11-2256b eps
100 000
50 000
20 000
10 000
5 000
2 000
1 000
500
200
100
50
25
20
1
10
0.5
10
20
25
kA 50
Possible
3AH Vacuum
Circuit-Breakers
160
422
160
Secondary equipment
Pole-centre distance
160 mm
629
491
Weight
40 kg to 45 kg
482
630
171
86
435
HG11-2225c eps
90
25 kA / up to 1250 A
490
491
210
Pole-centre distance
210 mm
491
90
25 kA / up to 1250 A
Weight
45 kg to 50 kg
171
482
435
HG11-2226c eps
Remarks
Manual snap-action
operating mechanism
522
210
Current transformer-operated
release 0.5 A/1 A, type 3AX1102
44
Current transformer-operated
release 0.1Ws, type 3AX1104
592
Undervoltage release
type 3AX1103
491
1
S1
Secondary equipment
1 Gearbox
10
2 Position switch
3 Closing spring
4 Motor
HG11-2252 eps
12
Basic equipment
14
8
1
5 Closing spring
charged signal
9
10
S22
S4
S3
S21
11
99981
HG11-2253a eps
12
Maximum equipment
13
7 Closing solenoid
8 Auxiliary switch
Mechanical interlocking
9 PushbuttonCLOSED
10 PushbuttonOPEN
S1
6 Operating cycle
counter
11 2nd release
3
4
5
6
17.5 kV
12 1st release
13 Mechanical
interlocking
or scanning
14 Low-voltage
plug connector
Varistor circuitry
Condensation protection
For 230 V AC
Hand crank
Silicone-free design
Release combinations
1 2 3 4 5 6 7
3AH Vacuum
Circuit-Breakers
R-HG11-083a eps
24 kV
3AH5 252-1
16 kA / 800 A
(Partitions not
shown)
Rated voltage 24 kV
Rated lightning impulse withstand voltage 125 kV
Rated short-time power frequency
withstand voltage 50 kV
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
Ima
Polecentre
distance
kA
kA
mm
16
40
40
210
275
Please add
Order No.
suffix
O - 3min - CO - 3min - CO
Remarks
1
1
rm
iry fo
Enqu e A / 3
ag
see p
1250 A
1
2
2
1)
Electrical service life (load char. No. 1 ) Mechanical breaker service life 10,000 operating cycles
Load char. No. 1
HG11-2257a eps
100 000
50 000
20 000
10 000
5 000
2 000
1 000
500
200
100
50
25
20
1
10
0.5
10
20
kA 50
16
Possible
3AH Vacuum
Circuit-Breakers
Secondary equipment
516
210
700
567
210
Pole-centre
distance
210 mm
90
16 kA / up to 1250 A
Weight
55 kg to 70 kg
592
567
567
646
Pole-centre
distance
275 mm
275
16 kA / up to 1250 A
90
275
HG11-2313c eps
435
597
171
Remarks
Manual snap-action
operating mechanism
Weight
55 kg to 70 kg
Current transformer-operated
release 0.5 A/1 A, type 3AX1102
Current transformer-operated
release 0.1Ws, type 3AX1104
Undervoltage release
type 3AX1103
Auxiliary switch 2 NO+2 NC,
unwired
567
30
708
123
HG11-2312c eps
435
767
171
Secondary equipment
View into the
mechanism housing
S1
1 Gearbox
10
2 Position switch
3 Closing spring
HG11-2252 eps
12
14
8
S1
9
10
S22
S4
11
99981
12
HG11-2253a eps
3
4
5
6
S3
S21
Maximum equipment
5 Closing spring
charged signal
6 Operating cycle
counter
Mechanical interlocking
7 Closing solenoid
Basic equipment
4 Motor
24 kV
8 Auxiliary switch
Varistor circuitry
9 PushbuttonCLOSED
10 PushbuttonOPEN
11 2nd release
Condensation protection
For 230 V AC
12 1st release
Hand crank
Silicone-free design
13 Mechanical
interlocking
or scanning
14 Low-voltage
plug connector
Release combinations
1 2 3 4 5 6 7
3AH Vacuum
Circuit-Breakers
R-HG11-134 eps
36 kV
3AH5 302-2
16 kA / 1250 A
(Partitions
not shown)
Rated voltage 36 kV
Rated lightning impulse withstand voltage 170 kV
Rated short-time power frequency
withstand voltage 70 kV
Rated short-circuit duration 3 s
Rated short-circuit breaking current Isc and
rated short-circuit making current Ima
see table
Ima
Polecentre
distance
kA
kA
mm
16
40
350
Order No.
O - 3min - CO - 3min - CO
Remarks
rm
iry fo
Enqu e A / 3
ag
see p
A
Load char. No. 1
3AH5 302-2
1250
1)
Electrical service life (load char. No. 1 ) Mechanical breaker service life 10,000 operating cycles
Load char. No. 1
HG11-2257a eps
100 000
50 000
20 000
10 000
5 000
2 000
1 000
500
200
100
50
25
20
1
10
0.5
10
20
kA 50
16
Possible
3AH Vacuum
Circuit-Breakers
Secondary equipment
Pole-centre distance
350 mm
818
673
645
973
171
150
435
HG11-2258a eps
90
350
868
786
350
673
16 kA / 1250 A
Weight
85 kg to 95 kg
Basic equipment
Additional equipment
Remarks
Manual snap-action
operating mechanism
Current transformer-operated
release 0.5 A/1 A, type 3AX1102
Current transformer-operated
release 0.1Ws, type 3AX1104
1
S1
Secondary equipment
Undervoltage release
type 3AX1103
1 Gearbox
10
2 Position switch
3 Closing spring
4 Motor
HG11-2252 eps
12
S1
9
10
S22
S4
11
99981
12
HG11-2253a eps
3
4
5
6
S3
S21
Maximum equipment
7 Closing solenoid
14
8
5 Closing spring
charged signal
6 Operating cycle
counter
Basic equipment
13
36 kV
8 Auxiliary switch
9 PushbuttonCLOSED
10 PushbuttonOPEN
11 2nd release
12 1st release
Mechanical interlocking
13 Mechanical
interlocking
or scanning
14 Low-voltage
plug connector
Varistor circuitry
Condensation protection
For 230 V AC
Hand crank
Silicone-free design
Release combinations
1 2 3 4 5 6 7
3AH Vacuum
Circuit-Breakers
R-HG11-140 eps
17.5 kV
R-HG11-143 eps
Page
Rated data
Selection and ordering data
Electrical and mechanical
service life
Dimensions and weights
Secondary equipment
For rated voltage
17.5 kV
Enquiry form
5 / 25 /3
A/2
3AH Vacuum
Circuit-Breakers
17.5 kV
R-HG11-139 eps
Rated
- voltage 17.5 kV
- lightning impulse withstand
voltage 95 kV
- short-time power frequency
withstand voltage 38 kV*
- short-circuit duration 3 s
- short-circuit breaking current Isc and
- short-circuit making current Ima
see table
* Up to 42 kV on request
3AH3 838-7
63 kA / 8000 A
Ima
Polecentre
distance
kA
kA
mm
Please add
Order No.
suffix
No. of
poles
per phase
O - 3min - CO - 3min - CO
125
125
210
275
3AH3 837-
3AH3 837-
63
160
275
3AH3 838-
80
225
275
3AH3 830-
rm
iry fo
Enqu e A / 2
ag
see p
12 000 A
Remarks
3
3
8
3
5
Possible
Electrical service life (load char. Nos. 1 to 3 ) Mechanical breaker service life 10,000 operating cycles
2
3
HG11-2307a eps
Phase L1
50 000
20 000
10 000
HG11-2311a eps
5 000
2 000
1 000
Kennlinien-Nr.
Phase L2
Phase L3
100 000
Zulssige Schaltspiele
500
200
100
50
1
30
15
20
10
2
1
10
20
kA 50
100
63 80
Ausschaltstrom (Effektivwert)
3AH Vacuum
Circuit-Breakers
Secondary equipment
Pole-centre distance
210 mm
550
210
561
50 kA / 8000 A
683
211
Weight of the
3 vacuum
circuit-breakers
approx. 552 kg
83
HG11-2379 eps
494
105
210
610
571
17.5 kV
Basic equipment
Remarks
Additional equipment
also be manually controlled
Electrical operating mechanism Can
Option: with manual control
solenoid
Closing
type 3AY15 10
shunt release
Refer to table below for
1st
type 3AY15 10
release combinations
2nd shunt release
type 3AX1101
Current transformer-operated
release 0.5 A/1 A, type 3AX11 02
750
694
Pole-centre distance
275 mm
275
50 kA / 12 000 A
733
211
Weight of the
3 vacuum
circuit-breakers
approx. 930 kg
Current transformer-operated
release 0.1 Ws, type 3AX11 04
Undervoltage release
type 3AX11 03
Auxiliary switch 6 NO + 6 NC
Auxiliary switch 12 NO + 12 NC *
149
HG11-2380 eps
494
105
275
strip 24-pole or
Terminal
plug connector
694
776
64-pole or 24-pole
680
590
63 kA / 8000 A
HG11-2381 eps
Weight of the
3 vacuum
circuit-breakers
approx. 594 kg
729
494
80 kA / 8000 A
211
275
105
275
A current transformer-operated
release for a tripping pulse of
0.1 Ws is used in connection
with the 7SJ41 protective
system or with the protective
relay made by SEG
Anti-pumping
mechanical and electrical
Breaker tripping signal
Operating cycle counter
switches (2 pieces)
Position
for signalling
144
750
In place of mechanical
local closing
Mechanical interlocking
Varistor circuitry
63 kA / 12 000 A
Condensation protection
For 230 V AC
80 kA / 12 000 A
Silver-plated or tinned
primary current paths
Hand crank
Silicone-free design
694
275
733
211
Weight of the
3 vacuum
circuit-breakers
approx. 930 kg
149
HG11-2382 eps
494
105
275
776
776
694
Release combinations
1
2nd release
3rd release
3AH Vacuum
Circuit-Breakers
e. g.
1-pole traction circuit-breaker
17.5 kV, 16 2/3 Hz /
50 kA / 2500 A
R-HG11-044 eps
e. g.
1-pole traction circuit-breaker
27.5 kV, 50/60 Hz /
25 kA / 2000 A
R-HG11-138 eps
R-HG11-137 eps
Krle substation, 110 / 15 kV, 16 2/3 Hz (traction power supply) with ICE power unit
Page
Rated data
Selection and ordering data
Electrical and mechanical
service life
Dimensions and weights
Secondary equipment
For rated voltages
17.5 kV, 16 2/3 Hz 6 /26 / 3
27.5 kV, 50 / 60 Hz 6 / 46 / 5
Enquiry form
16 2/
A/4
3AH Vacuum
Circuit-Breakers
R-HG11-136 eps
3AH4 757-6
50 kA / 2500 A
Selection and ordering data for rated voltage 17.5 kV, 16 2/3 Hz
Isc
Ima
kA
kA
Please add
Order No.
suffix
O - 15s - CO
Remarks
rm
iry fo
Enqu e A / 4
g
a
see p
2500 A
63
3AH4 754-
31.5
80
3AH4 755-
40
100
3AH4 756-
50
125
3AH4 757-
Possible
10
10 000
5 000
2 000
1 000
500
80
20 000
10 000
5 000
2 000
1 000
500
200
200
100
100
50
50
100 000
HG11-2385b eps
50 000
20 000
100 000
HG11-2384a eps
HG11-2383a eps
50 000
100 000
50 000
20 000
10 000
5 000
2 000
1 000
500
200
80
100
50
30
20
20
10
1
10
1
10
50 kA 100
20
10
20 31.5 50 kA 100
25
20
3
10
4
50 kA 100
20
40
3AH Vacuum
Circuit-Breakers
Secondary
equipment
636
105
153
25 kA / 2000 A
732
Weight
approx. 90 kg
68
HG11-2389
494
31.5 kA / 2000 A
211
531
636
716
105
138
40 kA / 2500 A
50 kA / 2500 A
Weight
approx. 138 kg
Basic equipment
Remarks
Additional equipment
Instantaneous release
type 3AX60 1.
Undervoltage release
type 3AX11 03
Auxiliary switch 6 NO + 6 NC
Auxiliary switch 12 NO + 12 NC *
211
534
64-pole or 24-pole
613
HG11-2390 eps
1276
494
716
Anti-pumping
mechanical and electrical
Breaker tripping signal
Operating cycle counter
switches (2 pieces)
Position
for signalling
In place of mechanical
local closing
Mechanical interlocking
Varistor circuitry
Condensation protection
For 230 V AC
Silver-plated or tinned
primary current paths
Hand crank
Silicone-free design
Release combinations
1
3AH Vacuum
Circuit-Breakers
R-HG11-135 eps
Selection and ordering data for rated voltage 27.5 kV, 50/60 Hz
Please add
Order No.
suffix
Up
Ud
Isc
Ima
kV
kV
kA
kA
25
63
3AH4 784-
31.5
80
3AH4 785-
25
63
3AH4 794-
70
Remarks
2000 A
1
rm
iry fo
Enqu e A / 4
g
a
see p
2500 A
250
O - 0.3s - CO - 3min - CO
Possible
Electrical service life (load char. Nos. 1 and 2 ) Mechanical breaker service life 60,000 operating cycles
Load char. No. 2
20 000
10 000
5 000
2 000
1 000
500
100 000
50 000
20 000
10 000
5 000
2 000
100
100
50
50
20
10
1
10
50 kA 100
20
25
500
200
10
1 000
200
20
HG11-2387b eps
HG11-2386b eps
50 000
100 000
Kennlinien-Nr.
Zulssige Schaltspiele
2
1
10
50 kA 100
20
31.5
Ausschaltstrom (Effektivwert)
3AH Vacuum
Circuit-Breakers
Secondary
equipment
153
721
Up = 170 kV
90
25 kA / up to 2000 A
31.5 kA / 2500 A
732
211
534
721
118
Basic equipment
Remarks
Additional equipment
105
914
25 kA / up to 1250 A
Weight approx. 135 kg
Auxiliary switch 6 NO + 6 NC
Auxiliary switch 12 NO + 12 NC *
Electrical equipment
such as motor, release
wired to terminal strip or
plug connector
Option: Gold-plated plug
connector contacts
531
Anti-pumping
mechanical and electrical
Breaker tripping signal
Operating cycle counter
switches (2 pieces)
Position
for signalling
914
914
105
120
25 kA / up to 2000 A
211
1238
494
594
HG11-2392 eps
577
HG11-2407 eps
Undervoltage release
type 3AX11 03
64-pole or 24-pole
531
Max. 3 releases
can be combined
211
1203
494
150
HG11-2391 eps
494
914
In place of mechanical
local closing
Mechanical interlocking
Varistor circuitry
Condensation protection
For 230 V AC
Silver-plated or tinned
primary current paths
Hand crank
Silicone-free design
Release combinations
1
Special Circuit-Breakers
3AH Vacuum
Circuit-Breakers
On
reque
st
e. g.
special circuit-breaker, 2-pole
24 kV / 25 kA / 800 A
e. g.
explosion-protected circuit-breaker
12 kV / 23.6 kA / 630 A
R-HG11-129 eps
R-HG11-130 eps
R-HG11-131 eps
7.2 to 36 kV
Mobile selective-cut road driving machine for underground mining type WAV 300 (photo Westfalia Lnen)
Page
Rated data
Service life
Secondary equipment
Ambient influences
Standards
For
Special circuit-breakers 7 / 2
1, 2 and 3-pole
Explosion-protected circuit-breakers
Explosion-protected
circuit-breakers
7/3
Enquiry form
A/5
o
ts int
emen .
ir
u
q
e
our r us a line
p
urn y
in
We t . Just dro
orm
y
t
uiry f
reali
e
r nq e A / 5
u
o
e
ag
se
Also pendix, p
p
the A
reque
3AH Vacuum
Circuit-Breakers
st
R-HG11-132 eps
7.2 to 36 kV
2-pole special
circuit-breaker
24 kV /
25 kA / 800 A
Pole-centre distance
550 mm
Requirements
Vibration stability and seismic
withstand capability in accordance with
the guidelines of Germanischer LIoyd
and LIoyds Register of Shipping,
e. g. for
Power plants
Shipbuilding
Climatic withstand
capability
s into
ment
quire line.
e
r
r
a
ou
p us
urn y
in
We t . Just dro
y form
y
ir
t
u
li
a
q
e
n
r
e
5
r
/
u
A
o
age
see
Also pendix, p
p
the A
Selection data
Rated voltages Ur
7.2 to 36 kV
Rated frequencies fr
16 2/3 or 50 / 60 Hz
60 to 250 kV
20 to 105 kV
up to 4 s
800 to 4000 A
16 to 80 kA
50 to 225 kA
Rated
operating
sequences
possible
O - 0.3s - CO - 3min - CO
possible
O - 3min - CO - 3min - CO
Pole-centre distances of 2-pole special circuit-breakers
Basic equipment
Additional equipment
Current transformer-operated release, type 3AX11 04, for tripping pulse 0.1 Ws
Undervoltage release, type 3AX11 03
Instantaneous release, type 3AX60 1.
Auxiliary switch 6 NO + 6 NC
Auxiliary switch 12 NO + 12 NC 1)
possible
320 to 700 mm
Explosion-Protected Circuit-Breakers
3AH Vacuum
Circuit-Breakers
On
reque
st
Explosionprotected
circuit-breaker
12 kV /
23.6 kA / 630 A
Requirements
Explosion protection, e. g. for
Mining installations
Chemical plants
Firedamp protection
Firedamp protection involves special
design measures as compared with
normal industrial equipment:
Vacuum interrupters with cast-resinimpregnated glass-fibre coating and
with the same distances between
poles, degree of protection EEx d I
Auxiliary switch, fitted in the lower section of the operating mechanism box
(actuated by a linkage from the operating shaft), degree of protection EEx d I
Lift motor with degree of
protection EEx d I
Secondary release and closing solenoid,
degree of protection EEx e I
Limit switch (Sch)d, degree of
protection EEx d I
Line-up terminals with degree of
protection EEx e I
o
ts int
emen
equir a line.
r
r
u
o
p us
urn y
We t . Just dro
rm in
y
iry fo
realit
enqu A / 5
r
u
o
age
see
Also pendix, p
p
the A
R-HG11-133 eps
7.2 and 12 kV
Selection data
Rated voltages Ur
7.2 and 12 kV
Rated frequencies fr
50 / 60 Hz
75 kV
28 kV
3s
630 A
23.6 kA
75 kA
O - 3min - CO - 3min - CO
possible
Pole-centre distance
210 mm
Basic equipment
Electrical operating mechanism
Closing solenoid
1st shunt release
Undervoltage release
Auxiliary switch 4 NO + 4 NC
Terminal strip as line-up terminal 22+6-pole
Operating cycle counter
Appendix
R-HG11-141 eps
R-HG11-142 eps
3AH Vacuum
Circuit-Breakers
Page
A/2
3AH3 83 high-current
circuit-breakers
A/2
3AH5 economy
circuit-breakers
A/3
3AH4 7, 1-pole
A/4
traction circuit-breakers
Facilities:
Development
Design
Type testing
Accredited test bays
Parts manufacture
Surface treatment
Several assembly lines
Routine testing and dispatch
Training and information centre
Quality management and environmental protection management
Special circuit-breakers A / 5
Catalog index
Conditions of
sale and delivery
A / 6A / 8
A / 10
Enquiry Form
Enquiry concerning
Standard
circuit-breakers type 3AH1/3AH3
Frequent-operation
circuit-breakers type 3AH2/3AH4
High-current
circuit-breakers type 3AH3 83
3AH Vacuum
Circuit-Breakers
Technical specifications
Rated voltage
Rated lightning impulse
withstand voltage
Rated short-time power
frequency withstand voltage
Rated short-circuit
breaking current
requesting
Offer
Phone call
Visit
Your address
Pole-centre distance
Other values
7.2 kV
12 kV
24 kV
36 kV
15 kV
17.5 kV
60 kV
75 kV
95 kV
125 kV
20 kV
28 kV
36 kV
38 kV
50 kV
70 kV
16 kA
20 kA
25 kA
31.5 kA
40 kA
50 kA
63 kA
80 kA
800 A
1250 A
2000 A
2500 A
3150 A
4000 A
8000 A
12 000 A
170 kV
kV
kV
kV
kA
Secondary equipment
Refer to pages 2 / 3 to 2 / 13, 3 / 3 to 3 / 13 and 5 / 3 for combination possibilities
Motor-operated mechanism
DC
AC
V,
Hz
Closing solenoid
DC
AC
V,
Hz
DC
AC
V,
Hz
Name
DC
AC
V,
Hz
Street
0.5 A
1A
Undervoltage release
DC
AC
Auxiliary switch
6 NO + 6 NC
12 NO + 12 NC
Low-voltage connection
Plug connector or
Company
Department
Postcode/town
Tel.
V,
64-pole
FAX
24-pole
Electrical local closing
Siemens AG
Mechanical interlocking
Varistor circuitry at 60 V DC
Department
Language of operating
instructions
German
English
Name
Street
Postcode/town
FAX
,
form
y this it to your
p
o
c
e
Pleas and send
r.
in
fill it ns partne
e
m
ie
S
French
Spanish
Hz
Enquiry Form
3AH Vacuum
Circuit-Breakers
Enquiry concerning
Technical specifications
Economy
Rated voltage
Other values
12 kV
17.5 kV
24 kV
75 kV
95 kV
125 kV
28 kV
38 kV
42 kV
50 kV
70 kV
13.1 kA
16 kA
36 kV
170 kV
20 kA
25 kA
requesting
800 A
Offer
Pole-centre distance
1250 A
kV
kV
kV
kA
Phone call
Visit
Secondary equipment
Refer to pages 4 / 3 to 4 / 9 for combination possibilities
Your address
without
Wiring
with
Company
Department
Name
Street
Postcode/town
DC
AC
V,
Hz
Closing solenoid
DC
AC
V,
Hz
DC
AC
V,
Hz
DC
AC
V,
Hz
0.5 A
1A
Undervoltage release
DC
AC
Auxiliary switch
2 NO + 2 NC
6 NO + 6 NC
Low-voltage connection
Plug connector or
Tel.
FAX
V,
Hz
12 NO + 12 NC
64-pole
Siemens AG
without
Department
Name
with
24-pole
Mechanical interlocking
Varistor circuitry at 60 V DC
Language of operating
instructions
German English
French
Spanish
Street
FAX
,
form
y this it to your
p
o
c
e
Pleas and send
r.
in
fill it ns partne
e
m
ie
S
Enquiry Form
Enquiry concerning
Traction
circuit-breaker,
1-pole, type 3AH4 7
requesting
3AH Vacuum
Circuit-Breakers
Technical specifications
Other values
Rated voltage
17.5 kV,
27.5 kV
kV
125 kV
170 kV
250 kV
kV
50 kV
70 kV
105 kV
kV
Rated short-circuit
breaking current
25 kA
31.5 kA
40 kA
kA
1250 A
2000 A
2500 A
2/
Hz
50 kA
Offer
Phone call
Visit
Secondary equipment
Refer to pages 6 / 3 and 6 / 5 for combination possibilities
Your address
Motor-operated mechanism
DC
AC
V,
Hz
Closing solenoid
DC
AC
V,
Hz
DC
AC
V,
Hz
DC
AC
V,
Hz
Instantaneous release
DC
Undervoltage release
DC
AC
V,
Hz
Auxiliary switch
6 NO + 6 NC
12 NO + 12 NC
Low-voltage connection
Plug connector or
Company
Department
Name
Street
64-pole
Postcode/town
24-pole
Tel.
FAX
Varistor circuitry at 60 V DC
Language of operating
instructions
Siemens AG
German
English
Department
Street
Postcode/town
FAX
,
form
y this it to your
p
o
c
e
Pleas and send
r.
in
fill it ns partne
e
Siem
Others
Enquiry Form
3AH Vacuum
Circuit-Breakers
Enquiry concerning
Special circuit-breakers
for special applications
Technical specifications
7.2 kV
12 kV
15 kV
24 kV
27.5 kV
36 kV
60 kV
75 kV
95 kV
125 kV
170 kV
250 kV
20 kV
28 kV
36 kV
38 kV
50 kV
70 kV
105 kV
16 kA
20 kA
25 kA
31.5 kA
40 kA
50 kA
63 kA
80 kA
800 A
1250 A
1600 A
2000 A
2500 A
3150 A
4000 A
Number of poles
1-pole
2-pole
3-pole
Rated voltage
Rated lightning impulse
withstand voltage
Rated short-time power
frequency withstand voltage
Rated short-circuit
breaking current
requesting
Offer
Phone call
Visit
Your address
Other values
17.5 kV
kV
kV
kV
kA
Secondary equipment
Motor-operated mechanism
DC
AC
V,
Hz
Closing solenoid
DC
AC
V,
Hz
DC
AC
V,
Hz
DC
AC
V,
Hz
Street
0.5 A
1A
Postcode/town
Instantaneous release
DC
Undervoltage release
DC
Auxiliary switch
6 NO + 6 NC
12 NO + 12 NC
Low-voltage connection
Plug connector or
Company
Department
Name
Tel.
FAX
AC
V,
Hz
64-pole
24-pole
Siemens AG
Electrical local closing
Mechanical interlocking
Department
Varistor circuitry at 60 V DC
Name
Language of operating
instructions
German
English
French
Spanish
Street
FAX
,
form
y this it to your
p
o
c
e
Pleas and send
r.
in
fill it ns partne
e
m
ie
S
Appendix
3AH Vacuum
Circuit-Breakers
Designation
High Voltage
Title
Order No.
Medium-Voltage
Switchgear
E50001-K1511-A111-A4-7600
E50001-K1511-A151-A1-7600
E50001-K1511-A211-A1-7600
E50001-K1511-A311-A1-7600
E50001-K1511-A511-A1-7600
E50001-K1512-A101-A4-7600
E86010-K1513-A101-A1-7600
E50001-K1521-A101-A1-7600
E50001-K1521-A251-A3-7600
E50001-K1521-A271-A3-7600
E50001-K1522-A111-A1-7600
E50001-K1524-A101-A2-7600
E86010-K1525-A101-A4-7600
HA 35.41
HA 35.51
HA 39.1
HA 39.3
HA 40.1
HA 41.11
HA 45.11
HA 45.31
HA 51.1
HA 52.1
E86010-K1421-A101-A3-7600
E50001-K1425-A311-A6-7600
E50001-K1425-A411-A2-7600
E50001-K1425-A511-A1-7600
E50001-K1425-A711-A2-7600
E50001-K1425-A811-A1-7600
Siemens Den Haag,
Dept. CMS DMS
E50001-K1427-A111-A2-7600
E50001-K1535-A101-A6-7600
E50001-K1435-A401-A3-7600
E50001-K1435-A511-A1-7600
E86010-K1439-A111-A2-7600
E86010-K1439-A131-A1-7600
E50001-K1440-A111-A1-7600
E50001-K1441-A101-A2-7600
E50001-K1445-A111-A6-7600
E50001-K1445-A311-A1-7600
E50001-K1451-A111-A2-7600
E50001-K1452-A111-A1-7600
A
Protection and
Substation
Control Systems
Power Quality
SR 10.1.1
SR 10.1.2
SR 10.1.3
SR 10.2
SR 10.2.5
SR 10.2.6
SR 10.4
SR 10.5
SR 10.6
E50001-K4011-A101-A1-7600
see Intranet
E50001-K4013-A101-A1-7600
E50001-K4020-A101-A1-7600
E50001-K4025-A101-A1-7600
E50001-K4026-A101-A1-7600
E50001-K4040-A101-A1-7600
E50001-K4050-A201-A1-7600
E50001-K4060-A101-A1-7600
Appendix
3AH Vacuum
Circuit-Breakers
Designation
Protection and
Substation
Control Systems
Title
Order No.
E50001-K4501-A111-A1-7600
E50001-K4501-A121-A1-7600
E50001-K4501-A131-A1-7600
E86010-K4500-A151-A1-7600
E86010-K4500-A161-A1-7600
E86010-K4500-A131-A1-7600
E50001-K4500-A361-A2-7600
E50001-K4500-A241-A2-7600
E86010-K4500-A321-A1-7600
E86010-K4500-A141-A1-7600
E50001-K5702-A011-A1-7600
E50001-K5702-A121-A1-7600
E50001-K5702-A031-A2-7600
E50001-K5712-A251-A2-7600
E50001-K5712-A261-A1-7600
E50001-K5712-A201-A2-7600
E50001-K5712-A131-A2-7600
E50001-K5712-A141-A3-7600
E50001-K5712-A411-A1-7600
E50001-K5712-A191-A4-7600
E50001-K5742-A121-A3-7600
E50001-K5712-A271-A1-7600
E50001-K5712-A211-A2-7600
E50001-K5712-A221-A1-7600
E50001-K5712-A241-A2-7600
E50001-K5712-A181-A2-7600
E50001-K5722-A111-A2-7600
E50001-K5722-A121-A2-7600
E50001-K5722-A131-A2-7600
E50001-K4405-A121-A1-7600
E50001-K5722-A141-A2-7600
E50001-K4405-A111-A1-7600
E50001-K5722-A161-A1-7600
E50001-K5722-A171-A1-7600
E50001-K5732-A111-A2-7600
E50001-K5732-A121-A1-7600
E50001-K5732-A131-A1-7600
E50001-K5732-A141-A1-7600
E50001-K5742-A111-A1-7600
E50001-K5752-A111-A1-7600
E50001-K5752-A121-A2-7600
E50001-K5752-A131-A2-7600
E50001-K5752-A141-A2-7600
E50001-K5752-A151-A1-7600
E50001-K5752-A161-A1-7600
E50001-K5752-A171-A1-7600
E50001-K5762-A111-A2-7600
E50001-K5762-A121-A1-7600
E50001-K5772-A111-A1-7600
E50001-K5772-A121-A1-7600
E50001-K5772-A131-A1-7600
E50001-K5772-A151-A1-7600
E50001-K5772-A161-A1-7600
E50001-K5772-A191-A1-7600
E50001-K5772-A201-A1-7600
E50001-K4408-A111-A1-7600
E50001-K5782-A121-A1-7600
E50001-K4407-A111-A1-7600
Energy Automation
SICAM 2.1.1
SICAM 2.3.1
SICAM 5.1.1
SICAM 5.2.1
SICAM 5.2.2
SICAM 5.2.3
SICAM 5.3.1
SICAM 5.3.2
E50001-K5602-A111-A1-7600
E50001-K5602-A311-A1-7600
E50001-K5605-A111-A1-7600
E50001-K5605-A211-A1-7600
E50001-K5605-A221-A1-7600
E50001-K5605-A231-A1-7600
E50001-K5605-A311-A1-7600
E50001-K5605-A321-A1-7600
Siemens HG 11.11 1999A/7
Appendix
3AH Vacuum
Circuit-Breakers
Designation
Substation
Control and
Protection
Title
Order No.
E50001-K5701-A111-A4-7600
E50001-K5701-A121-A2-7600
E50001-K5701-A131-A2-7600
E50001-K5701-A141-A1-7600
E50001-K5701-A161-A1-7600
E50001-K5701-A171-A2-7600
E50001-K5701-A181-A1-7600
E50001-K5701-A211-A2-7600
E50001-K5701-A221-A1-7600
E50001-K5701-A231-A1-7600
E50001-K5701-A241-A1-7600
E50001-K5701-A251-A1-7600
E50001-K5701-A261-A1-7600
E50001-K5701-A411-A1-7600
E50001-K5701-A421-A1-7600
E50001-K5701-A431-A1-7600
E50001-K5701-A441-A1-7600
E50001-K5701-A451-A1-7600
E50001-K5701-A461-A1-7600
E50001-K5701-A471-A1-7600
E50001-K5701-A481-A1-7600
E50001-K5701-A491-A1-7600
E50001-K5701-A521-A1-7600
E50001-K5701-A531-A1-7600
E50001-K5701-A551-A1-7600
E50001-K5701-A611-A1-7600
Distribution Transformers
Transformers
GEAFOL
TV 1
TV 2
A19100-T5101-A9A-7600
E50001-K7101-A101-A2-7600
E50001-K7102-A101-A1-7600
Energy Meters
Energy Meters
Z 9.1.1
Z 9.1.2
Z 9.1.3
Z 9.1.4
Z 9.1.5
Z 9.2.2
Z 9.2.3
E50001-K8991-A101-A1-7600
E50001-K8991-A111-A3-7600
E50001-K8991-A121-A1-7600
E50001-K8991-A131-A1-7600
E50001-K8991-A141-A1-7600
E50001-K8992-A111-A1-7600
E50001-K8992-A121-A1-7600
A
Power Cables
Power Cables
SK 1.12
SK 3.30
SK 3.40
SK 4.20
E50001-K8112-A101-A1-7600
E50001-K8133-A101-A1-7600
E50001-K8134-A101-A2-7600
E50001-K8142-A101-A1-7600
3AH Vacuum
Circuit-Breakers
Notes
Appendix
3AH Vacuum
Circuit-Breakers
The technical data, dimensions
and weights are subject to
change unless otherwise stated
on the individual pages of this
catalog.
The illustrations are
for reference only.
Export Regulations
In accordance with the present
provisions of the German Export
List and the US Commercial
Control List, export licences are
not required for the products
listed in this catalog.
A En 1.91a
Trademarks
An export licence may however
be required due to countryspecific application and final
destination of the products.
Relevant are the export criteria
stated in the delivery note and
the invoice regarding a possible
export and reexport licence.
Responsible for:
Technical contents:
Hermann Bierfelder,
Siemens AG, Dept. EV MNK V,
Erlangen
General editing:
Gabriele Pollok,
Siemens AG, Dept. EV BK T,
Erlangen
Printed in Germany
KGK 08.99 12.0 80 101200 6101/ U886
Bereich
Energiebertragung und -verteilung
Geschftsgebiet Mittelspannung
Postfach 32 20
D-91050 Erlangen
http: // www.ev.siemens.de
Siemens Aktiengesellschaft
Power
to the
Order No.: E50001-K1511-A111-A4-7600