TABLE 4E4A

Ref.Method 1
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
630

2c, 1
2
27
36

892

3c/4c,3
3
23
31
42
53
73
94
124
154
187
238
289
335
386
441
520
599
673

Ref.Method 11
2c, 1
4
29
39
52
66
90
115
152
188
228
291
354
410
472
539
636
732
847

3c/4c,3
5
25
33
44
56
78
99
131
162
197
251
304
353
406
463
546
628
728

TABLE 4E4B
1c,3
6
15.5
21
28
36
50
68
89
110
134
171
207
239
262
296
346
394
467
892

1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400

TABLE 4E2A
Multicore 900C Thermosetting insulated cables, non armoured (CU)
Ref. Method 4
Ref. Method 3
Ref. Method 1
2c, 1
3c/4c,3 2c, 1
3c/4c,3 2c, 1 3c/4c,3
CSA
1
2
3
4
5
6
7
1
15
1.5
19.5
2.5
26
4
35
6
44

10
16

60
80

25
35

105
128

50

154

70
95
120
150
185

194
233
268
300
340

2c, 1
4

5
31
19
12
7.9
4.7
2.9
1.9
1.35
1
0.69
0.52
0.42
0.35
0.29
0.24
0.21
0.19

3c/4c, 3-
7
8
27
16
10
6.8
4.0
2.5
1.65
1.15
0.87
0.60
0.45
0.37
0.30
0.26
0.21
0.185
0.165

MEMDUCT 50 Hz, Copper Busbar Trunking System


VL-L Drop in mV/m at rated current & at
Rated
Current (A)
1.00
0.90
100
92.26
160
112.83
200
114.49
300
120.51
400
125.54
500
131.74
630
135.55
800
102.19
1000
93.74
1250
87.84
1400
81.93
1600
89.74
1800
83.90
2000
83.63
2500
86.57
3000
84.40
3200
80.35
3500
81.83
4000
80.97
4500
84.80
5000
78.30
6000
69.79

9
25
15
9.5
6.4
3.8
2.4
1.5
1.1
0.81
0.57
0.43
0.35
0.29
0.25
0.21
0.185
0.16

Ref. Method 11
2c, 1 3c/4c,3
8
9

TABL

Correction factors for groups of more than one circ


Reference method of
installation
Enclosed (Method 3 or
(see table 4A)
4) or bunched &
clipped
Single direct to a non
metallic
surface
Touching
layer
(Method
clipped to1)
a nonmetallic
surface
Spaced*
layer
(Method 1) Touching
clipped to
a nonmetallic
Spaced*#
surface
layer
clipped to Horizontal
a nonmetallic
Vertical
surface
Single layer multicore
touching on ladder
supports (Method 13)

Num
2
0.8
0.85

3
0.7
0.79

4
0.65
0.75

5
0.6
0.73

0.94

0.9

0.9

0.9

0.86

0.81

0.77

0.75

0.91

0.89

0.88

0.87

0.9

0.85

0.85

0.8

0.79

0.86

0.82

240
300
400

398
455
536

TABLE 4B2
Correction factors for minerals insulated cables installed on perforated trays
Tray
Arrangeme
Number
orientatio
nt of
of trays
n
cables

Number of multicore cables or circuits


2
3
4
6

TABLE 4B3
Correction factors for cables installed in enclosed trenches
Correction factor

Installation Method 18
Conductor
cross
sectional
area

Horizontal
Horizontal
Vertical
Vertical
Horizontal
Vertical

Multiconduc
Multiconduc
Multiconduc
Multiconduc
Single condu
Single condu

1
1
1
1
1
1

1
1
1
1
1
1

0.9
1
0.9
0.9
1
0.9

0.8
1
0.8
0.9
0.95
0.9

0.8
0.95
0.75
0.9

0.75
0.9
0.75
0.85

0.75
0.7
-

Installation Method 19

6 single- 6 single core


2 single4 single- core cables, cables, 4
3 single8 single core
core cables,
core cables, 4 two-core
two-core
core cables,
cables, or 4 three
or 1 threeor 2 three- cables, or 3 cables or 3
or 2 twoor four-core
or four-core
or four core
three-or
three- or
core cables
cables
cable
cables
four-core
four-core
cables
cables

Installation Method 20

12 single
12 single
core cables,
core cables,
8 two-core
8 two-core
cables, or 6
cables, or 6
three- or
three-or four
four core
core cables
cables

9
0.81

mm
4

0.93

0.9

0.87

0.82

0.86

0.83

0.76

0.92

0.89

0.86

0.81

0.86

0.82

0.75

0.8

10

0.91

0.88

0.85

0.8

0.85

0.8

0.74

0.78

16

0.91

0.87

0.84

0.78

0.83

0.78

0.71

0.76

25

0.9

0.86

0.82

0.76

0.81

0.76

0.69

0.74

++ separated by a clearance between adjacent surfaces of at least two cable diameters (2De)

35

0.89

0.85

0.81

0.75

0.8

0.74

0.68

0.72

50

0.88

0.84

0.79

0.74

0.78

0.73

0.66

0.71

70

0.87

0.82

0.78

0.72

0.77

0.72

0.64

0.7

95

0.86

0.81

0.76

0.7

0.75

0.7

0.63

0.68

120

0.85

0.8

0.75

0.69

0.73

0.68

0.61

0.66

150

0.84

0.78

0.74

0.67

0.72

0.67

0.59

0.64

185

0.83

0.77

0.73

0.65

0.7

0.65

0.58

0.63

240

0.82

0.76

0.71

0.63

0.69

0.63

0.56

0.61

300

0.81

0.74

0.69

0.62

0.68

0.62

0.54

0.59

400

0.8

0.73

0.67

0.59

0.66

0.6

0.52

0.57

500

0.78

0.72

0.66

0.58

0.64

0.58

0.51

0.56

630

0.77

0.71

0.65

0.56

0.63

0.57

0.49

0.54

70
-

75
-

80
-

85
-

90
-

95
-

0.45
0.52
0.71
0.58
-

0.32
0.43
0.61
0.5
-

0.3
0.5
0.41
-

0.35
0.29
-

space by a clearance between surfaces of at least one cable diameter (De)


correction factor not tabulated

TABLE 4C1
Correction Factors for ambient temperature where protection is against short-circuit
Type of
Operating
Insulation temperature
Rubber (flex60C
General
purpose
pvc
70C
Paper
80C
Rubber
85C
Heat resisti 90C
Thermosetti90C
70C sheath
Mineral

25
1.04

30
1

35
0.91

40
0.82

45
0.71

50
0.58

Ambient temperature (C)


55
60
65
0.41
-

1.03
1.02
1.02
10.3
1.02
1.03

1
1
1
1
1
1

0.94
0.95
0.95
0.97
0.96
0.93

0.87
0.89
0.9
0.94
0.91
0.85

0.79
0.84
0.85
0.91
0.87
0.77

0.71
0.77
0.8
0.87
0.82
0.67

0.61
0.71
0.74
0.84
0.76
0.57

0.5
0.63
0.67
0.8
0.71
0.45

0.35
0.55
0.6
0.76
0.65
0.31

Mineral

105C sheat

1.02

0.96

* this factor s are applicable only to ratings in column 2 to 5 of Table 4D1A

0.92

0.88

0.84

0.8

0.75

0.7

0.65

0.6

0.54

0.47

0.4

0.32

er Busbar Trunking System


op in mV/m at rated current & at various power factors
0.80
0.70
0.60
0.50
87.38
108.30
110.89
119.05
124.84
131.83
140.31
98.32
90.46
84.91
79.24
86.76
81.07
80.38
83.40
81.70
77.81
79.17
78.71
82.26
75.91
67.44

ECC
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400

1.5
2.5
4
6
10
16
16
16
25
35
50
70
95
95
120
150
240

TABLE 4B1

s for groups of more than one circuit of single-cables, or more than one multicore cable
Correction factor (Cg)
Number of circuits or multi cables
7
8
9
0.54
0.52
0.5
0.72
0.71
0.7

10
0.48
-

12
0.45
-

14
0.43
-

16
0.41
-

18
0.39
-

20
0.38
-

90

0.9

0.9

0.9

0.9

0.9

0.9

0.9

0.9

0.9

0.74

0.73

0.73

0.73

0.71

0.7

0.87

0.78

0.78

0.78

0.77

6
0.57
0.72

Installation Method 20
18 single
24 single
core cables, core cables,
12 two-core 16 two-core
cables, or 9 cables, or 12
three or
three- or
four-core
four core
cables
cables
10

11

0.74

0.69

0.73

0.68

0.72

0.66

0.7

0.64

0.67

0.62

0.66

0.6

0.64

0.59

0.62

0.57

0.6

0.55

0.58

0.53

0.57

0.51

0.55

0.49

0.53

0.48

0.52

0.46

0.5

0.44

0.48

0.43

0.47

0.41

UAE rating (A)


800
1000
values at 50 Degrees based on UAE Size conductors.
Conductor CSA (mm2)

420

Reactance (m ohm/m)

0.013

540
0.013

1250

1350

1600

2000

2500

3200

4000

5000

6300

600

750

960

960

1380

1920

1920

2760

3600

0.01

0.0088

0.0076

0.0076

0.0044

0.0038

0.03

0.0044

0.0025

Resistance (m ohm/m)

0.045

0.053

0.041

0.0355

0.03

0.03

0.016

0.015

0.011

0.016

0.009

Impedance (m ohm/m)

0.047

0.055

0.042

0.0365

0.031

0.031

0.017

0.015

0.11

0.017

0.0096

1.5

1.5

2.5

2.5

10

10

16

16

25

16

35

16

"Voltage drop, pf = 0.7 (V/m)"


"Voltage drop, pf = 0.8 (V/m)"

0.0568
0.0608

0.062
0.068

0.057
0.061

0.057
0.061

0.057
0.061

0.068
0.073

0.063
0.067

0.057
0.061

0.068
0.073

0.063
0.067

0.06
0.065

50

25

70

35

"Voltage drop, pf = 0.9 (V/m)"

0.0614

0.072

0.065

0.065

0.065

0.078

0.071

0.065

0.078

0.071

0.069

95

50

"Voltage drop, pf = 1.0 (V/m)"

0.0624

0.071

0.064

0.064

0.064

0.076

0.07

0.064

0.076

0.07

0.068

120

70

150

95

UAE rating (A)


800
1000
values at 20 Degrees based on UAE Size conductors.

1250

1350

1600

2000

2500

3200

4000

5000

6300

185

95

"Voltage drop, pf = 0.7 (V/m)"

0.0568

0.0568

0.0544

0.0544

0.0544

0.068

0.056

0.0544

0.068

0.07

0.059

240

120

"Voltage drop, pf = 0.8 (V/m)"


"Voltage drop, pf = 0.9 (V/m)"
"Voltage drop, pf = 1.0 (V/m)"

0.0608
0.064
0.0624

0.0608
0.064
0.0624

0.0584
0.0616
0.06

0.0584
0.0616
0.06

0.0584
0.0624
0.0608

0.073
0.078
0.076

0.0608
0.064
0.0632

0.0584
0.0616
0.06

0.073
0.078
0.076

0.076
0.08
0.079

0.064
0.067
0.066

300

150

630

300

10

2.5

16

20

25

Calculation

e.g.

VD @ PF
Length M
0.068
100

VOLTS
6.8

VD % @400V
1.7

Example
1000A busbar at full load over 100mtrs will have a volt drop at 0.8 p.f. of

100 x 0.068

6.8Volts or 1.7%

32

40

10

63

16

80

25

100

35

125

50

160

70

200

95

225

120

250

150

300

185

350

240

400

300

500

150

4c x 2

630

185

4c x 2

800

300

4c x 2

1000

240

4c x 3

1250

300

4c x 3

1600

630

1c x 8

2000

630

1c x 11

2500

630

1c x 11

HILTON GARDEN INN


AL BARSHA, DUBAI
UNITED ARAB EMIRATES

ELECTRICAL
VOLTAGE DROP CALCULATIONS REV 1
REVISED DETAIL DESIGN ISSUE 08-10-2014

Tameem House

T : + 971 (0) 4 450 3999

P.O Box 500137


F : + 971 (0) 4 450 3998
Tecom, Dubai
E : dubai@tjeg.com
United Arab Emirates W : www.tjeg.com

AKOYA
MDB-A1- CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

MDB-A1

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

SMDB -R15

359.60

0.80

287.68

153

800

519.05

0.77

0.87

0.67

774.82

4/c-

300

628

1256

0.185

7.35

1.84%

1/c-

300

SMDB -R16

130.20

0.80

104.16

140

300

187.93

0.77

0.87

0.67

280.54

4/c-

185

463

463

0.250

6.58

1.64%

1/c-

95

BBR - A1

1105.25

0.70

775.97

94

2250

1400.06

0.038

1.19

0.30%
1/c-

300

PFC

TOTALS

350 kVAr 8 STEP AUTO PFC

1595.05

0.73

1167.81

800

15

2500

2107.04

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 10 of 72

( mm2 )

BBR - A1 2250A TPN + E Cu BUSBAR


4/c-

300

1/c-

630

11

( mm2 )

AKOYA
BBR - A1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

BBR - A1

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

SMDB -AL3 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB -AL3 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB -AL3 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB -AL3 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB -AL3 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB -AL3 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB -AL3 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB -AL3 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB -AL3 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB -AL3 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

TOTALS

1105.25

0.70

775.97

2250

1400.06

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 11 of 72

( mm2 )

BBR - A1 2250A TPN + E Cu BUSBAR

( mm2 )

AKOYA
SMDB-AL3 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-AL3

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-A301

6.51

0.70

4.58

40

32

8.26

0.77

0.87

0.67

12.33

1/c

36

108

7.900

3.04

0.76%

1/c-

DB-A302

6.51

0.70

4.58

40

32

8.26

0.77

0.87

0.67

12.33

1/c

36

108

7.900

3.04

0.76%

1/c-

DB-A303

6.51

0.70

4.58

50

32

8.26

0.77

0.87

0.67

12.33

1/c

36

108

7.900

3.26

0.81%

1/c-

DB-A304

6.51

0.70

4.58

30

32

8.26

0.77

0.87

0.67

12.33

1/c

36

108

7.900

2.82

0.71%

1/c-

DB-A305

6.51

0.70

4.58

30

32

8.26

0.77

0.87

0.67

12.33

1/c

36

108

7.900

2.82

0.71%

1/c-

DB-A306

6.51

0.70

4.58

30

32

8.26

0.77

0.87

0.67

12.33

1/c

36

108

7.900

2.82

0.71%

1/c-

DB-A307

11.71

0.70

8.19

25

40

14.77

0.77

0.87

0.67

22.05

1/c

10

50

150

4.700

2.75

0.69%

1/c-

10

DB-A308

11.86

0.70

8.26

20

40

14.90

0.77

0.87

0.67

22.25

1/c

10

50

150

4.700

2.64

0.66%

1/c-

10

DB-A309

8.75

0.70

6.14

30

40

11.07

0.77

0.87

0.67

16.53

1/c

10

50

150

4.700

2.69

0.67%

1/c-

10

DB-A310

8.75

0.70

6.14

40

40

11.07

0.77

0.87

0.67

16.53

1/c

10

50

150

4.700

2.86

0.72%

1/c-

10

DB-A311

8.75

0.70

6.14

45

40

11.07

0.77

0.87

0.67

16.53

1/c

10

50

150

4.700

2.95

0.74%

1/c-

10

DB-A312

8.75

0.70

6.14

55

40

11.07

0.77

0.87

0.67

16.53

1/c

10

50

150

4.700

3.12

0.78%

1/c-

10

DB-A313

12.95

0.70

9.12

45

40

16.46

0.77

0.87

0.67

24.57

1/c

10

50

150

4.700

3.33

0.83%

1/c-

10

TOTALS

110.53

0.70

77.60

225.00

140.01

4/c-

120

1/c-

70

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 12 of 72

( mm2 )

( mm2 )

AKOYA
MDB-A2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

0.038

1.63

0.41%

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

DF

EMD

BBR - A2

1105.25

0.70

775.97

129

2250

1400.06

SMDB - GR1

223.23

0.80

178.58

15

500

322.21

0.77

0.87

0.67

480.99

4/c-

150

406

812

0.290

0.70

0.18%

1/c-

150

2.35

0.75

1.77

20

32

3.19

0.77

0.87

0.67

4.76

4/c-

56

56

6.400

0.41

0.10%

1/c-

SMDB - GA

104.71

0.76

79.12

20

225

142.75

0.77

0.87

0.67

213.09

4/c-

120

353

353

0.350

1.00

0.25%

1/c-

70

SMDB - R3

67.20

0.80

53.76

47

160

97.00

0.77

0.87

0.67

144.79

4/c-

70

251

251

0.570

2.60

0.65%

1/c-

35

SMDB - R8

57.60

0.80

46.08

124

125

83.14

0.77

0.87

0.67

124.11

4/c-

50

197

197

0.810

8.35

2.09%

1/c-

25

SMDB - R9

79.20

0.80

63.36

183

160

114.32

0.77

0.87

0.67

170.65

4/c-

70

251

251

0.570

11.92

2.98%

1/c-

35

4/c-

300

1/c-

300

15

2500

1/c-

630

11

PFC

TOTALS

350 kVAr 8 STEP AUTO PFC


1639.54

0.73

1198.64

800
2162.67

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
Column 9 = column 4 / column 8
Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 13 of 72

( mm2 )

BBR - A2 2250A TPN + E Cu BUSBAR

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

3
4
5
6
7

TCL

DB - SS1

MDB-A2

( mm2 )

AKOYA
BBR - A2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

BBR - A2

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

SMDB -AL13 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB -AL13 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB -AL13 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB -AL13 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB -AL13 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB -AL13 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB -AL13 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB -AL13 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB -AL13 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB -AL13 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

TOTALS

1105.25

0.70

775.97

2250

1400.06

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 14 of 72

( mm2 )

BBR - A2 2250A TPN + E Cu BUSBAR

( mm2 )

AKOYA
SMDB-AL13 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-AL13

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-A1301

6.51

0.70

4.58

40

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

3.48

0.87%

1/c-

DB-A1302

6.51

0.70

4.58

40

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

3.48

0.87%

1/c-

DB-A1303

6.51

0.70

4.58

50

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

3.70

0.93%

1/c-

DB-A1304

6.51

0.70

4.58

30

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

3.27

0.82%

1/c-

DB-A1305

6.51

0.70

4.58

30

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

3.27

0.82%

1/c-

DB-A1306

6.51

0.70

4.58

30

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

3.27

0.82%

1/c-

DB-A1307

11.71

0.70

8.19

25

40

14.77

0.77

0.87

0.67

22.05

1/c-

10

50

150

4.700

3.19

0.80%

1/c-

10

DB-A1308

11.86

0.70

8.26

20

40

14.90

0.77

0.87

0.67

22.25

1/c-

10

50

150

4.700

3.08

0.77%

1/c-

10

DB-A1309

8.75

0.70

6.14

30

40

11.07

0.77

0.87

0.67

16.53

1/c-

10

50

150

4.700

3.13

0.78%

1/c-

10

DB-A1310

8.75

0.70

6.14

40

40

11.07

0.77

0.87

0.67

16.53

1/c-

10

50

150

4.700

3.31

0.83%

1/c-

10

DB-A1311

8.75

0.70

6.14

45

40

11.07

0.77

0.87

0.67

16.53

1/c-

10

50

150

4.700

3.39

0.85%

1/c-

10

DB-A1312

8.75

0.70

6.14

55

40

11.07

0.77

0.87

0.67

16.53

1/c-

10

50

150

4.700

3.57

0.89%

1/c-

10

DB-A1313

12.95

0.70

9.12

50

40

16.46

0.77

0.87

0.67

24.57

1/c-

16

68

204

2.900

3.41

0.85%

1/c-

16

TOTALS

110.53

0.70

77.60

225.00

140.01

4/c-

120

1/c-

70

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 15 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-GR1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-GR1

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-RETAIL -R1

49.05

0.80

39.24

15

100

70.80

0.77

0.87

0.67

105.69

4/c-

35

162

162

1.100

1.87

0.47%

1/c-

16

DB-RETAIL -R2

37.80

0.80

30.24

41

80

54.56

0.77

0.87

0.67

81.45

4/c-

25

131

131

1.500

4.06

1.01%

1/c-

16

DB-RETAIL -R4

33.12

0.80

26.50

68

80

47.81

0.77

0.87

0.67

71.36

4/c-

25

152

152

1.900

6.88

1.72%

1/c-

16

DB-RETAIL -R5

29.82

0.80

23.86

77

63

43.04

0.77

0.87

0.67

64.25

4/c-

16

115

115

2.900

10.31

2.58%

1/c-

16

DB-RETAIL -R6

29.22

0.80

23.38

99

63

42.18

0.77

0.87

0.67

62.96

4/c-

16

115

115

2.900

12.81

3.20%

1/c-

16

DB-RETAIL -R7

44.22

0.80

35.38

105

100

63.83

0.77

0.87

0.67

95.28

4/c-

35

188

188

1.350

9.75

2.44%

1/c-

16

TOTALS

223.23

0.80

178.58

500

322.21

4/c-

150

1/c-

150

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 16 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-GA - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-GA

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

GARBAGE CHUTE -1

5.00

0.80

4.00

63

32

7.22

0.77

0.87

0.67

10.77

4/c-

56

56

6.400

3.91

0.98%

1/c-

GARBAGE CHUTE -2

5.00

0.80

4.00

176

32

7.22

0.77

0.87

0.67

10.77

4/c-

56

56

6.400

9.13

2.28%

1/c-

DB-FP

4.44

0.78

3.47

32

32

6.26

0.77

0.87

0.67

9.35

4/c-

66

66

7.900

2.58

0.65%

1/c-

DB - LV -1

2.46

0.75

1.85

15

32

3.33

0.77

0.87

0.67

4.97

4/c-

66

66

7.900

1.39

0.35%

1/c-

DB - GL 1

20.69

0.77

15.93

63

63

28.75

0.77

0.87

0.67

42.92

4/c-

16

115

115

2.900

6.25

1.56%

1/c-

16

DB - GL 2

15.12

0.79

11.87

176

40

21.41

0.77

0.87

0.67

31.96

4/c-

16

115

115

2.900

11.93

2.98%

1/c-

16

SUMP PUMP
STATION 1

15.00

0.80

12.00

132

63

21.65

0.77

0.87

0.67

32.32

4/c-

16

115

115

2.900

9.29

2.32%

1/c-

16

DB -EXT -01

12.00

0.75

9.00

15

40

16.24

0.77

0.87

0.67

24.24

4/c-

10

90

90

4.700

2.14

0.54%

1/c-

10

OUTDOOR CINEMA

10.00

0.80

8.00

153

32

14.43

0.77

0.87

0.67

21.55

4/c-

10

90

90

4.700

11.38

2.84%

1/c-

10

SPARE

15.00

0.60

9.00

TOTALS

104.71

0.76

79.12

4/c-

120

1/c-

70

200

142.75

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
Column 9 = column 4 / column 8
Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 17 of 72

( mm2 )

( mm2 )

40

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

3
4
5
6
7

AKOYA
MDB-A3- CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

MDB-A3

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

0.089

4.66

1.16%

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

BBR - A3

769.97

0.70

540.62

157

1600

975.43

MCC - GA

118.50

0.90

106.65

40

250

192.43

0.77

0.87

0.67

287.25

4/c-

150

406

406

0.290

2.23

0.56%

1/c-

95

MCC - ETS

290.00

0.90

261.00

222

630

470.92

0.77

0.87

0.67

702.96

4/c-

240

546

1092

0.210

10.98

2.74%

1/c-

240

SPARE

200.00

0.80

160.00

4/c-

300

1/c-

300

1/c-

630

11

PFC

TOTALS

0.77

1068.27

800
15

2500

1927.46

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
Column 9 = column 4 / column 8
Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 18 of 72

( mm2 )

40

350 kVAr 8 STEP AUTO PFC


1378.47

( mm2 )

BBR - A3 1600A TPN + E Cu BUSBAR

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

3
4
5
6
7

AKOYA
BBR - A3 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

BBR - A3

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

SMDB -AL23 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

5.64

1.41%

1/c-

70

SMDB -AL23 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

5.64

1.41%

1/c-

70

SMDB -AL23 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

5.64

1.41%

1/c-

70

SMDB -AL23 TYP

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

5.64

1.41%

1/c-

70

SMDB -AL27 TYP

91.08

0.70

63.90

20

200

115.29

0.77

0.87

0.67

172.09

4/c-

95

304

304

0.430

5.65

1.41%

1/c-

50

SMDB -AL27 TYP

91.08

0.70

63.90

20

200

115.29

0.77

0.87

0.67

172.09

4/c-

95

304

304

0.430

5.65

1.41%

1/c-

50

SMDB -AL29 TYP

72.86

0.70

51.22

20

160

92.42

0.77

0.87

0.67

137.96

4/c-

70

251

251

0.570

5.71

1.43%

1/c-

35

SMDB -AL29 TYP

72.86

0.70

51.22

20

160

92.42

0.77

0.87

0.67

137.96

4/c-

70

251

251

0.570

5.71

1.43%

1/c-

35

TOTALS

769.97

0.70

540.62

1600

975.43

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 19 of 72

( mm2 )

BBR - A3 1600A TPN + E Cu BUSBAR

( mm2 )

AKOYA
SMDB-AL23 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-AL23

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-A2301

6.51

0.70

4.58

40

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

6.51

1.63%

1/c-

DB-A2302

6.51

0.70

4.58

40

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

6.51

1.63%

1/c-

DB-A2303

6.51

0.70

4.58

50

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

6.73

1.68%

1/c-

DB-A2304

6.51

0.70

4.58

30

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

6.29

1.57%

1/c-

DB-A2305

6.51

0.70

4.58

30

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

6.29

1.57%

1/c-

DB-A2306

6.51

0.70

4.58

30

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

6.29

1.57%

1/c-

DB-A2307

11.71

0.70

8.19

25

40

14.77

0.77

0.87

0.67

22.05

1/c-

10

50

150

4.700

6.22

1.55%

1/c-

10

DB-A2308

11.86

0.70

8.26

20

40

14.90

0.77

0.87

0.67

22.25

1/c-

10

50

150

4.700

6.10

1.53%

1/c-

10

DB-A2309

8.75

0.70

6.14

30

40

11.07

0.77

0.87

0.67

16.53

1/c-

10

50

150

4.700

6.16

1.54%

1/c-

10

DB-A2310

8.75

0.70

6.14

40

40

11.07

0.77

0.87

0.67

16.53

1/c-

10

50

150

4.700

6.33

1.58%

1/c-

10

DB-A2311

8.75

0.70

6.14

45

40

11.07

0.77

0.87

0.67

16.53

1/c-

10

50

150

4.700

6.42

1.60%

1/c-

10

DB-A2312

8.75

0.70

6.14

55

40

11.07

0.77

0.87

0.67

16.53

1/c-

10

50

150

4.700

6.59

1.65%

1/c-

10

DB-A2313

12.95

0.70

9.12

50

40

16.46

0.77

0.87

0.67

24.57

1/c-

16

68

204

2.900

6.43

1.61%

1/c-

16

TOTALS

110.53

0.70

77.60

225

140.01

4/c-

120

1/c-

70

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 20 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-AL27 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-AL27

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-A2701

6.51

0.70

4.58

40

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

6.52

1.63%

1/c-

DB-A2702

6.51

0.70

4.58

40

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

6.52

1.63%

1/c-

DB-A2703

6.51

0.70

4.58

30

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

6.30

1.58%

1/c-

DB-A2704

6.51

0.70

4.58

20

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

6.08

1.52%

1/c-

DB-A2705

6.51

0.70

4.58

25

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

6.19

1.55%

1/c-

DB-A2706

11.71

0.70

8.19

40

40

14.77

0.77

0.87

0.67

22.05

1/c-

10

50

150

4.700

6.57

1.64%

1/c-

10

DB-A2707

11.86

0.70

8.26

30

40

14.90

0.77

0.87

0.67

22.25

1/c-

10

50

150

4.700

6.35

1.59%

1/c-

10

DB-A2708

8.75

0.70

6.14

50

40

11.07

0.77

0.87

0.67

16.53

1/c-

10

50

150

4.700

6.52

1.63%

1/c-

10

DB-A2709

8.75

0.70

6.14

55

40

11.07

0.77

0.87

0.67

16.53

1/c-

10

50

150

4.700

6.60

1.65%

1/c-

10

DB-A2710

8.75

0.70

6.14

50

40

11.07

0.77

0.87

0.67

16.53

1/c-

10

50

150

4.700

6.52

1.63%

1/c-

10

DB-A2711

8.75

0.70

6.14

45

40

11.07

0.77

0.87

0.67

16.53

1/c-

10

50

150

4.700

6.43

1.61%

1/c-

10

TOTALS

91.08

0.70

63.90

200

115.29

4/c-

95

1/c-

50

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 21 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-AL29 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-AL29

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-A2901

6.51

0.70

4.58

40

32

8.26

0.77

0.87

0.67

12.33

1/c

36

108

7.900

6.58

1.65%

1/c-

DB-A2902

6.51

0.70

4.58

40

32

8.26

0.77

0.87

0.67

12.33

1/c

36

108

7.900

6.58

1.65%

1/c-

DB-A2903

6.51

0.70

4.58

25

32

8.26

0.77

0.87

0.67

12.33

1/c

36

108

7.900

6.26

1.56%

1/c-

DB-A2904

6.51

0.70

4.58

30

32

8.26

0.77

0.87

0.67

12.33

1/c

36

108

7.900

6.36

1.59%

1/c-

DB-A2905

11.86

0.70

8.35

40

40

15.07

0.77

0.87

0.67

22.50

1/c

10

50

150

4.700

6.66

1.66%

1/c-

10

DB-A2906

8.75

0.70

6.14

50

40

11.07

0.77

0.87

0.67

16.53

1/c

10

50

150

4.700

6.58

1.64%

1/c-

10

DB-A2907

8.75

0.70

6.14

55

40

11.07

0.77

0.87

0.67

16.53

1/c

10

50

150

4.700

6.67

1.67%

1/c-

10

DB-A2908

8.75

0.70

6.14

50

40

11.07

0.77

0.87

0.67

16.53

1/c

10

50

150

4.700

6.58

1.64%

1/c-

10

DB-A2909

8.75

0.70

6.14

45

40

11.07

0.77

0.87

0.67

16.53

1/c

10

50

150

4.700

6.49

1.62%

1/c-

10

TOTALS

72.86

0.70

51.22

160

92.42

4/c-

70

1/c-

35

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 22 of 72

( mm2 )

( mm2 )

AKOYA
MCC-GA - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

MCC-GA

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

CWPS - 1 & 2

37.00

0.90

33.30

15

100

60.08

0.77

0.87

0.67

89.69

4/c-

35

162

162

1.100

1.28

0.32%

1/c-

16

CWPS - 3 & 4

37.00

0.90

33.30

15

100

60.08

0.77

0.87

0.67

89.69

4/c-

35

162

162

1.100

1.28

0.32%

1/c-

16

CWPS - 5 & 6

37.00

0.90

33.30

15

100

60.08

0.77

0.87

0.67

89.69

4/c-

35

162

162

1.100

1.28

0.32%

1/c-

16

CWPS - 13 & 14

7.50

0.90

6.75

15

32

12.18

0.77

0.87

0.67

18.18

4/c-

10

78

78

3.800

0.98

0.25%

1/c-

10

118.50

0.90

106.65

250

4/c-

150

1/c-

95

TOTALS
Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:

1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 23 of 72

( mm2 )

( mm2 )

AKOYA
MCC-ETS - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

2
Power (kW)

MCC-ETS

LOAD

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

Corrected Cable

10
Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

S.CHWP -01(D)

55.00

0.90

49.50

20

125

89.31

0.77

0.87

0.67

133.32

4/c-

70

251

251

0.570

12.00

3.00%

1/c-

35

S.CHWP -02 (D)

55.00

0.90

49.50

20

125

89.31

0.77

0.87

0.67

133.32

4/c-

70

251

251

0.570

12.00

3.00%

1/c-

35

S.CHWP -03 (D)

55.00

0.90

49.50

20

125

89.31

0.77

0.87

0.67

133.32

4/c-

70

251

251

0.570

12.00

3.00%

1/c-

35

S.CHWP -04 (D)

55.00

0.90

49.50

20

125

89.31

0.77

0.87

0.67

133.32

4/c-

70

251

251

0.570

12.00

3.00%

1/c-

35

S.CHWP -05 (D)

55.00

0.90

49.50

20

125

89.31

0.77

0.87

0.67

133.32

4/c-

70

251

251

0.570

12.00

3.00%

1/c-

35

S.CHWP -06 (S)

55.00

0.90

49.50

20

125

89.31

0.77

0.87

0.67

133.32

4/c-

70

251

251

0.570

12.00

3.00%

1/c-

35

PRESSURISATION UNIT

10.00

0.90

9.00

20

40

16.24

0.77

0.87

0.67

24.24

4/c-

25

131

131

1.500

11.46

2.87%

1/c-

16

DOSING EQT

5.00

0.90

4.50

20

32

8.12

0.77

0.87

0.67

12.12

4/c-

16

99

99

2.400

11.37

2.84%

1/c-

16

290.00

0.90

261.00

630

4/c-

240

1/c-

120

TOTALS
Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:

1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 24 of 72

( mm2 )

( mm2 )

AKOYA
MDB-A4 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

Power (kW)

MDB-A4

LOAD

Correction Factor (C.F.)


Table 4C1

Overall C.F.

Ampacity It

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

Grouping (Cg)

9
Corrected Cable

10

11

Cable size
required

12

13

14

Equivalent

Voltage Drop

15

16

17

Percentage

ECC Cable size


required

No. of
cables in
parallel
required

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

Voltage Drop

18
No. of ECC
cables in
parallel
required

TCL

DF

EMD

FIRE PUMP CP

150.00

0.90

135.00

40

350

243.58

0.77

0.87

0.67

363.60

4/c-

240

546

546

0.210

2.05

0.51%

1/c-

120

MCC - AP2

89.50

0.90

80.55

58

200

145.33

0.77

0.87

0.67

216.95

4/c-

95

304

304

0.430

3.62

0.91%

1/c-

50

SMDB -LIFT -A

100.00

0.90

90.00

180

250

162.38

0.77

0.87

0.67

242.40

4/c-

150

406

406

0.290

8.48

2.12%

1/c-

70

BBR - B1

906.01

0.71

640.69

212

2000

1155.97

0.062

4.38

1.10%

SPARE

100.00

0.80

80.00

200

144.34

SPARE

50.00

0.80

40.00

200

72.17
1/c-

300

PFC

TOTALS

350 kVAr 8 STEP AUTO PFC

1395.51

0.76

1066.24

800

15

2500

1923.78

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (Ib) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 25 of 72

( mm2 )

BBR - B1 2000A TPN + E Cu BUSBAR

4/c-

300

1/c-

630

11

( mm2 )

AKOYA
BBR - B1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

BBR - B1

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

SMDB -BL3

132.33

0.74

97.51

10

300

175.93

0.77

0.87

0.67

262.62

4/c-

185

463

463

0.250

4.82

1.21%

1/c-

95

SMDB -BL4 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

4.87

1.22%

1/c-

70

SMDB -BL4 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

4.87

1.22%

1/c-

70

SMDB -BL4 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

4.87

1.22%

1/c-

70

SMDB -BL4 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

4.87

1.22%

1/c-

70

SMDB -BL4 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

4.87

1.22%

1/c-

70

SMDB -BL4 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

4.87

1.22%

1/c-

70

SMDB -BL4 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

4.87

1.22%

1/c-

70

TOTALS

906.01

0.71

640.69

2000

1155.97

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (Ib) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 26 of 72

( mm2 )

BBR - B1 2000A TPN + E Cu BUSBAR

( mm2 )

AKOYA
SMDB-BL3 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-BL3

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-B301

6.51

0.70

4.58

35

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

5.58

1.40%

1/c-

DB-B302

6.51

0.70

4.58

38

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

5.65

1.41%

1/c-

DB-B303

6.51

0.70

4.58

45

32

8.26

0.77

0.87

0.67

12.33

1/c-

36

108

7.900

5.80

1.45%

1/c-

DB-B304

6.51

0.70

4.58

47

40

8.26

0.77

0.87

0.67

12.33

1/c-

10

50

150

4.700

5.43

1.36%

1/c-

10

DB-B305

6.51

0.70

4.58

45

40

8.26

0.77

0.87

0.67

12.33

1/c-

10

50

150

4.700

5.40

1.35%

1/c-

10

DB-B306

11.71

0.70

8.19

43

40

14.77

0.77

0.87

0.67

22.05

1/c-

10

50

150

4.700

5.82

1.45%

1/c-

10

DB-B307

11.86

0.70

8.26

40

40

14.90

0.77

0.87

0.67

22.25

1/c-

10

50

150

4.700

5.76

1.44%

1/c-

10

DB-B308

8.75

0.70

6.14

35

40

11.07

0.77

0.87

0.67

16.53

1/c-

10

50

150

4.700

5.43

1.36%

1/c-

10

DB-B309

8.75

0.70

6.14

30

32

11.07

0.77

0.87

0.67

16.53

1/c-

36

108

7.900

5.70

1.42%

1/c-

DB-B310

8.75

0.70

6.14

28

32

11.07

0.77

0.87

0.67

16.53

1/c-

36

108

7.900

5.64

1.41%

1/c-

DB-GYM

50.00

0.80

40.00

15

125

72.17

0.77

0.87

0.67

107.73

4/c-

50

197

197

0.810

5.70

1.42%

1/c-

25

TOTALS

132.33

0.74

97.76

300

176.38

4/c-

185

1/c-

95

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 27 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-BL4 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-BL4

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-B401

6.51

0.70

4.55

28

32

8.22

0.77

0.87

0.67

12.26

1/c-

36

108

7.900

5.48

1.37%

1/c-

DB-B402

6.51

0.70

4.55

32

32

8.22

0.77

0.87

0.67

12.26

1/c-

36

108

7.900

5.56

1.39%

1/c-

DB-B403

6.51

0.70

4.55

42

32

8.22

0.77

0.87

0.67

12.26

1/c-

36

108

7.900

5.78

1.45%

1/c-

DB-B404

11.71

0.70

8.20

45

40

14.79

0.77

0.87

0.67

22.08

1/c-

10

50

150

4.700

5.91

1.48%

1/c-

10

DB-B405

11.86

0.70

8.30

43

40

14.98

0.77

0.87

0.67

22.36

1/c-

10

50

150

4.700

5.88

1.47%

1/c-

10

DB-B406

8.75

0.70

6.13

39

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

5.55

1.39%

1/c-

10

DB-B407

8.75

0.70

6.13

35

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

5.48

1.37%

1/c-

10

DB-B408

8.75

0.70

6.13

32

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

5.43

1.36%

1/c-

10

DB-B409

6.51

0.70

4.56

20

32

8.22

0.77

0.87

0.67

12.27

1/c-

36

108

7.900

5.30

1.33%

1/c-

DB-B410

8.75

0.70

6.13

18

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

5.18

1.30%

1/c-

10

DB-B411

12.95

0.70

9.07

15

40

16.36

0.77

0.87

0.67

24.42

1/c-

10

50

150

4.700

5.26

1.31%

1/c-

10

DB-B412

6.51

0.70

4.56

21

32

8.22

0.77

0.87

0.67

12.27

1/c-

36

108

7.900

5.33

1.33%

1/c-

DB-B413

6.51

0.70

4.56

23

32

8.22

0.77

0.87

0.67

12.27

1/c-

36

108

7.900

5.37

1.34%

1/c-

TOTALS

110.57

0.70

77.40

225

139.64

4/c-

120

1/c-

70

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 28 of 72

( mm2 )

( mm2 )

AKOYA
MCC-AP2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

MCC-AP2

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

FAHU - 03 - SUPPLY

30.00

0.90

27.00

20

80

48.72

0.77

0.87

0.67

72.72

3/c-

25

131

262

1.500

4.36

1.09%

1/c-

16

FAHU - 03 -RETURN

11.00

0.90

9.90

20

40

17.86

0.77

0.87

0.67

26.66

3/c-

10

78

156

3.800

4.30

1.08%

1/c-

10

FAHU - 04 - SUPPLY

30.00

0.90

27.00

20

80

48.72

0.77

0.87

0.67

72.72

3/c-

25

131

262

1.500

4.36

1.09%

1/c-

16

FAHU - 04 - RETURN

18.50

0.90

16.65

20

63

30.04

0.77

0.87

0.67

44.84

3/c-

16

99

198

2.400

4.35

1.09%

1/c-

16

TOTALS

89.50

0.90

80.55

200

4/c-

95

1/c-

50

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 29 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-LIFT-A - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-LIFT-A

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

LIFT - PL - 1

25.00

0.90

22.50

10

63

40.60

0.77

0.87

0.67

60.60

4/c-

16

99

99

2.400

9.45

2.36%

1/c-

16

LIFT - PL - 2

25.00

0.90

22.50

10

63

40.60

0.77

0.87

0.67

60.60

4/c-

16

99

99

2.400

9.45

2.36%

1/c-

16

LIFT - PL - 3

25.00

0.90

22.50

10

63

40.60

0.77

0.87

0.67

60.60

4/c-

16

99

99

2.400

9.45

2.36%

1/c-

16

LIFT - SL

25.00

0.90

22.50

10

63

40.60

0.77

0.87

0.67

60.60

4/c-

16

99

99

2.400

9.45

2.36%

1/c-

16

TOTALS

100.00

0.90

90.00

250

162.38

4/c-

150

1/c-

70

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 30 of 72

( mm2 )

( mm2 )

AKOYA
MDB-A5 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

MDB-A5

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

0.87

0.67

183.01

TCL

DF

EMD

MCC - AR

75.50

0.90

67.95

180

200

122.60

BBR - B2

1105.25

0.70

775.97

247

2250

1400.06

SMDB -P1B

146.44

0.80

116.62

180

350

210.41

SPARE

100.00

0.80

80.00

200

144.34

SPARE

50.00

0.80

40.00

100

72.17

PFC

TOTALS

350 kVAr 8 STEP AUTO PFC


1401.69

0.72

1012.58

Grouping (Cg)

0.77

2500

0.77

1826.97

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 31 of 72

10

Corrected Cable

Cable size
required
( mm2 )

4/c-

150

11

12

13

14

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

406

406

0.290

6.40

1.60%

0.038

3.13

0.78%

0.210

7.95

1.99%

BBR - B2 2250A TPN + E Cu BUSBAR

800
15

0.87

0.67

314.08

4/c-

240

4/c-

300

1/c-

630

11

546

546

15
Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required
( mm2 )

No. of ECC
cables in
parallel
required

1/c-

70

1/c-

120

1/c-

300

AKOYA
BBR - B2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

BBR - B2

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

SMDB -BL11 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

3.62

0.90%

1/c-

70

SMDB -BL11 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

3.62

0.90%

1/c-

70

SMDB -BL11 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

3.62

0.90%

1/c-

70

SMDB -BL11 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

3.62

0.90%

1/c-

70

SMDB -BL11 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

3.62

0.90%

1/c-

70

SMDB -BL11 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

3.62

0.90%

1/c-

70

SMDB -BL11 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

3.62

0.90%

1/c-

70

SMDB -BL11 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

3.62

0.90%

1/c-

70

SMDB -BL11 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

3.62

0.90%

1/c-

70

SMDB -BL11 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

3.62

0.90%

1/c-

70

TOTALS

1105.25

0.70

775.97

2250

1400.06

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 32 of 72

( mm2 )

BBR - B2 2250A TPN + E Cu BUSBAR

( mm2 )

AKOYA
SMDB-BL11 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-BL11

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-B1101

6.51

0.70

4.55

28

32

8.22

0.77

0.87

0.67

12.26

1/c-

36

108

7.900

4.22

1.06%

1/c-

DB-B1102

6.51

0.70

4.55

32

32

8.22

0.77

0.87

0.67

12.26

1/c-

36

108

7.900

4.31

1.08%

1/c-

DB-B1103

6.51

0.70

4.55

42

32

8.22

0.77

0.87

0.67

12.26

1/c-

36

108

7.900

4.53

1.13%

1/c-

DB-B1104

11.71

0.70

8.20

45

40

14.79

0.77

0.87

0.67

22.08

1/c-

10

50

150

4.700

4.66

1.17%

1/c-

10

DB-B1105

11.86

0.70

8.30

43

40

14.98

0.77

0.87

0.67

22.36

1/c-

10

50

150

4.700

4.63

1.16%

1/c-

10

DB-B1106

8.75

0.70

6.13

39

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

4.29

1.07%

1/c-

10

DB-B1107

8.75

0.70

6.13

35

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

4.22

1.06%

1/c-

10

DB-B1108

8.75

0.70

6.13

32

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

4.17

1.04%

1/c-

10

DB-B1109

6.51

0.70

4.56

20

32

8.22

0.77

0.87

0.67

12.27

1/c-

36

108

7.900

4.05

1.01%

1/c-

DB-B1110

8.75

0.70

6.13

18

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

3.93

0.98%

1/c-

10

DB-B1111

12.95

0.70

9.07

15

40

16.36

0.77

0.87

0.67

24.42

1/c-

10

50

150

4.700

4.00

1.00%

1/c-

10

DB-B1112

6.51

0.70

4.56

21

32

8.22

0.77

0.87

0.67

12.27

1/c-

36

108

7.900

4.07

1.02%

1/c-

DB-B1113

6.51

0.70

4.56

23

32

8.22

0.77

0.87

0.67

12.27

1/c-

36

108

7.900

4.12

1.03%

1/c-

110.57

0.70

77.40

250

139.64

4/c-

120

1/c-

70

TOTALS

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 33 of 72

( mm2 )

( mm2 )

AKOYA
MCC-AR - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

MCC-AR

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

FAHU - RF- A1(S)

18.00

0.90

16.20

15

63

29.23

0.77

0.87

0.67

43.63

3/c-

16

99

198

2.400

6.93

1.73%

1/c-

16

FAHU - RF- A1(R)

11.00

0.90

9.90

15

40

17.86

0.77

0.87

0.67

26.66

3/c-

10

78

156

3.800

6.91

1.73%

1/c-

10

FAHU - RF- A2(S)

22.50

0.90

20.25

15

63

36.54

0.77

0.87

0.67

54.54

3/c-

16

99

198

2.400

7.06

1.76%

1/c-

16

FAHU - RF- A2(R)

18.50

0.90

16.65

15

63

30.04

0.77

0.87

0.67

44.84

3/c-

16

99

198

2.400

6.94

1.74%

1/c-

16

GEF - A

1.50

0.90

1.35

15

16

2.44

0.77

0.87

0.67

3.64

4/c-

56

56

6.400

6.63

1.66%

1/c-

CW BOOSTER PUMP

4.00

0.90

3.60

15

16

6.50

0.77

0.87

0.67

9.70

4/c-

44

44

9.500

7.33

1.83%

1/c-

TOTALS

75.50

0.90

67.95

200

4/c-

150

1/c-

70

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 34 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-P1B - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-P1B

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

EMD

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10
Cable size
required

11

12

13

14

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

TCL

DF

DB - P1 -2

11.91

0.80

9.15

10

40

16.50

0.77

0.87

0.67

24.63

4/c-

10

78

78

DB - P2 -2

13.45

0.80

10.35

15

40

56.25

0.77

0.87

0.67

83.96

4/c-

10

78

78

DB - BL3

10.50

0.80

8.28

22

40

44.98

0.77

0.87

0.67

67.15

4/c-

10

78

DB - BL6

10.50

0.80

8.28

33

40

44.98

0.77

0.87

0.67

67.15

4/c-

10

DB - BL9

10.50

0.80

8.40

43

40

45.63

0.77

0.87

0.67

68.12

4/c-

16

DB - BL12

10.50

0.80

8.40

53

40

45.63

0.77

0.87

0.67

68.12

4/c-

DB - BL15

10.80

0.80

8.64

64

40

46.96

0.77

0.87

0.67

70.09

DB - BL18

10.50

0.80

8.40

74

40

45.63

0.77

0.87

0.67

DB - BL21

10.50

0.80

8.40

85

40

45.63

0.77

0.87

DB - BL24

10.50

0.80

8.40

95

40

45.63

0.77

DB - BL27

11.38

0.80

9.11

106

40

49.50

0.77

DB - BR

13.73

0.80

10.98

130

40

59.69

DAMAC SIGNAGE

12.00

0.80

9.60

130

40

52.17

TOTALS

146.74

0.79

116.36

300

209.95

Percentage
Voltage Drop

17

18

ECC Cable size


required
( mm2 )

No. of ECC
cables in
parallel
required

3.800

8.58

2.15%

1/c-

10

3.800

11.16

2.79%

1/c-

10

78

3.800

11.71

2.93%

1/c-

10

78

78

3.800

13.59

3.40%

1/c-

16

99

99

2.400

12.66

3.17%

1/c-

16

16

99

99

2.400

13.76

3.44%

1/c-

16

4/c-

25

131

131

1.500

12.46

3.12%

1/c-

16

68.12

4/c-

25

131

131

1.500

13.02

3.25%

1/c-

16

0.67

68.12

4/c-

25

131

131

1.500

13.77

3.44%

1/c-

16

0.87

0.67

68.12

4/c-

35

162

162

1.100

12.72

3.18%

1/c-

16

0.87

0.67

73.89

4/c-

35

162

162

1.100

13.72

3.43%

1/c-

16

0.77

0.87

0.67

89.10

4/c-

50

197

197

0.810

14.24

3.56%

1/c-

25

0.77

0.87

0.67

77.88

4/c-

50

197

197

0.810

13.45

3.36%

1/c-

25

4/c-

240

1/c-

120

1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).

Page 35 of 72

Voltage Drop

16

(%)

Notes:

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

( mm2 )

15

(V)

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

3
4
5
6
7

AKOYA
MDB-A6 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

MDB-A6

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

0.062

5.75

1.44%

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

BBR - B3

880.50

0.70

618.22

278

2000

1115.44

SMDB -P1A

178.21

0.78

139.68

55

400

252.02

0.77

0.87

0.67

376.20

4/c-

300

628

628

0.185

2.56

0.64%

1/c-

150

EMDB - A

320.69

0.80

257.95

30

800

465.41

0.77

0.87

0.67

694.75

4/c-

300

628

1256

0.185

1.29

0.32%

1/c-

300

SPARE

100.00

0.80

80.00

4/c-

300

1/c-

300

1/c-

630

11

PFC

TOTALS

0.74

1095.85

800
15

2500

1977.21

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
Column 9 = column 4 / column 8
Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 36 of 72

( mm2 )

200

350 kVAr 8 STEP AUTO PFC


1479.39

( mm2 )

BBR - B3 2000A TPN + E Cu BUSBAR

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

3
4
5
6
7

AKOYA
BBR - B3 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

BBR - B3

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

SMDB -BL21 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

6.24

1.56%

1/c-

70

SMDB -BL21 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

6.24

1.56%

1/c-

70

SMDB -BL21 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

6.24

1.56%

1/c-

70

SMDB -BL21 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

6.24

1.56%

1/c-

70

SMDB -BL21 TYP

110.53

0.70

77.60

10

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

6.24

1.56%

1/c-

70

SMDB -BL27 TYP

91.08

0.70

63.90

10

200

115.29

0.77

0.87

0.67

172.09

4/c-

95

304

304

0.430

6.24

1.56%

1/c-

50

SMDB -BL27 TYP

91.08

0.70

63.90

10

200

115.29

0.77

0.87

0.67

172.09

4/c-

95

304

304

0.430

6.24

1.56%

1/c-

50

SMDB -BL29 TYP

72.86

0.70

51.22

10

160

92.42

0.77

0.87

0.67

137.96

4/c-

70

251

251

0.570

6.27

1.57%

1/c-

35

SMDB -BL29 TYP

72.86

0.70

51.22

10

160

92.42

0.77

0.87

0.67

137.96

4/c-

70

251

251

0.570

6.27

1.57%

1/c-

35

TOTALS

880.50

0.70

618.22

2000

1115.44

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 37 of 72

( mm2 )

BBR - B3 2000A TPN + E Cu BUSBAR

( mm2 )

AKOYA
SMDB-BL21 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-BL21

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-B2101

6.51

0.70

4.55

28

32

8.22

0.77

0.87

0.67

12.26

1/c-

36

108

7.900

6.84

1.71%

1/c-

DB-B2102

6.51

0.70

4.55

32

32

8.22

0.77

0.87

0.67

12.26

1/c-

36

108

7.900

6.93

1.73%

1/c-

DB-B2103

6.51

0.70

4.55

42

32

8.22

0.77

0.87

0.67

12.26

1/c-

36

108

7.900

7.14

1.79%

1/c-

DB-B2104

11.71

0.70

8.20

45

40

14.79

0.77

0.87

0.67

22.08

1/c-

10

50

150

4.700

7.28

1.82%

1/c-

10

DB-B2105

11.86

0.70

8.30

43

40

14.98

0.77

0.87

0.67

22.36

1/c-

10

50

150

4.700

7.24

1.81%

1/c-

10

DB-B2106

8.75

0.70

6.13

39

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

6.91

1.73%

1/c-

10

DB-B2107

8.75

0.70

6.13

35

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

6.84

1.71%

1/c-

10

DB-B2108

8.75

0.70

6.13

32

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

6.79

1.70%

1/c-

10

DB-B2109

6.51

0.70

4.56

20

32

8.22

0.77

0.87

0.67

12.27

1/c-

36

108

7.900

6.67

1.67%

1/c-

DB-B2110

8.75

0.70

6.13

18

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

6.55

1.64%

1/c-

10

DB-B2111

12.95

0.70

9.07

15

40

16.36

0.77

0.87

0.67

24.42

1/c-

10

50

150

4.700

6.62

1.65%

1/c-

10

DB-B2112

6.51

0.70

4.56

21

32

8.22

0.77

0.87

0.67

12.27

1/c-

36

108

7.900

6.69

1.67%

1/c-

DB-B2113

6.51

0.70

4.56

23

32

8.22

0.77

0.87

0.67

12.27

1/c-

36

108

7.900

6.73

1.68%

1/c-

110.57

0.70

77.40

225

139.64

4/c-

120

1/c-

70

TOTALS

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 38 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-BL27 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-BL27

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-B2701

6.51

0.70

4.55

28

32

8.22

0.77

0.87

0.67

12.26

1/c-

36

108

7.900

6.85

1.71%

1/c-

DB-B2702

6.51

0.70

4.55

32

32

8.22

0.77

0.87

0.67

12.26

1/c-

36

108

7.900

6.93

1.73%

1/c-

DB-B2703

6.51

0.70

4.55

42

32

8.22

0.77

0.87

0.67

12.26

1/c-

36

108

7.900

7.15

1.79%

1/c-

DB-B2704

11.71

0.70

8.20

45

40

14.79

0.77

0.87

0.67

22.08

1/c-

10

50

150

4.700

7.28

1.82%

1/c-

10

DB-B2705

11.86

0.70

8.30

43

40

14.98

0.77

0.87

0.67

22.36

1/c-

10

50

150

4.700

7.25

1.81%

1/c-

10

DB-B2706

8.75

0.70

6.13

39

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

6.92

1.73%

1/c-

10

DB-B2707

8.75

0.70

6.13

35

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

6.85

1.71%

1/c-

10

DB-B2708

8.75

0.70

6.13

32

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

6.80

1.70%

1/c-

10

DB-B2709

8.75

0.70

6.13

20

40

11.05

0.77

0.87

0.67

16.50

1/c-

10

50

150

4.700

6.59

1.65%

1/c-

10

DB-B2710

6.51

0.70

4.56

18

32

8.22

0.77

0.87

0.67

12.27

1/c-

36

108

7.900

6.63

1.66%

1/c-

DB-B2711

6.51

0.70

4.56

15

32

8.22

0.77

0.87

0.67

12.27

1/c-

36

108

7.900

6.57

1.64%

1/c-

TOTALS

91.11

0.70

63.77

200

115.06

4/c-

95

1/c-

50

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 39 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-BL29 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-BL29

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-B2901

6.51

0.70

4.56

28

32

8.22

0.77

0.87

0.67

12.27

1/c

36

108

7.900

6.88

1.72%

1/c-

DB-B2902

6.51

0.70

4.56

35

32

8.22

0.77

0.87

0.67

12.27

1/c

36

108

7.900

7.03

1.76%

1/c-

DB-B2903

11.86

0.70

8.30

38

40

14.98

0.77

0.87

0.67

22.36

1/c

10

50

150

4.700

7.16

1.79%

1/c-

10

DB-B2904

8.75

0.70

6.13

36

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.90

1.72%

1/c-

10

DB-B2905

8.75

0.70

6.13

35

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.88

1.72%

1/c-

10

DB-B2906

8.75

0.70

6.13

30

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.79

1.70%

1/c-

10

DB-B2907

8.75

0.70

6.13

25

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.70

1.68%

1/c-

10

DB-B2908

6.51

0.70

4.56

26

32

8.22

0.77

0.87

0.67

12.27

1/c

36

108

7.900

6.84

1.71%

1/c-

DB-B2909

6.51

0.70

4.56

29

32

8.22

0.77

0.87

0.67

12.27

1/c

36

108

7.900

6.90

1.73%

1/c-

TOTALS

72.90

0.70

51.03

160

92.07

4/c-

70

1/c-

35

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 40 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-P1A - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-P1A

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10
Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB - P1 -1

21.01

0.80

16.22

10

63

29.27

0.77

0.87

0.67

43.69

4/c-

16

99

99

2.400

3.27

0.82%

1/c-

16

DB - P2 -1

22.98

0.80

17.71

20

63

31.95

0.77

0.87

0.67

47.70

4/c-

16

99

99

2.400

4.10

1.02%

1/c-

16

DB - AL3

10.40

0.80

8.22

25

40

14.83

0.77

0.87

0.67

22.14

4/c-

10

78

78

3.800

3.97

0.99%

1/c-

10

DB - EXT-A

12.00

0.80

9.00

28

40

16.24

0.77

0.87

0.67

24.24

4/c-

10

78

78

3.800

4.29

1.07%

1/c-

10

DB - AL6

10.40

0.80

8.22

32

40

14.83

0.77

0.87

0.67

22.14

4/c-

10

78

78

3.800

4.37

1.09%

1/c-

10

DB - AL9

10.40

0.80

8.22

38

40

14.83

0.77

0.87

0.67

22.14

4/c-

10

78

78

3.800

4.71

1.18%

1/c-

10

DB - AL12

10.40

0.80

8.22

45

40

14.83

0.77

0.87

0.67

22.14

4/c-

10

78

78

3.800

5.10

1.28%

1/c-

10

DB - AL15

10.40

0.80

8.22

49

40

14.83

0.77

0.87

0.67

22.14

4/c-

10

78

78

3.800

5.33

1.33%

1/c-

10

DB - AL18

10.40

0.80

8.22

55

40

14.83

0.77

0.87

0.67

22.14

4/c-

10

78

78

3.800

5.66

1.42%

1/c-

10

DB - AL21

10.40

0.80

8.22

60

40

14.83

0.77

0.87

0.67

22.14

4/c-

10

78

78

3.800

5.95

1.49%

1/c-

10

DB - AL24

10.40

0.80

8.22

66

40

14.83

0.77

0.87

0.67

22.14

4/c-

10

78

78

3.800

6.28

1.57%

1/c-

10

DB - AL27

6.86

0.80

5.52

71

32

9.96

0.77

0.87

0.67

14.87

4/c-

56

56

6.400

7.09

1.77%

1/c-

DB - AL29

6.95

0.80

5.58

78

32

10.07

0.77

0.87

0.67

15.03

4/c-

56

56

6.400

7.59

1.90%

1/c-

DB - AR

13.83

0.80

11.15

86

40

20.12

0.77

0.87

0.67

30.03

4/c-

10

78

78

3.800

9.14

2.28%

1/c-

10

DAMAC SIGNAGE

12.00

0.80

10.80

98

40

19.49

0.77

0.87

0.67

29.09

4/c-

10

78

78

3.800

9.82

2.46%

1/c-

10

TOTALS

178.82

0.79

141.74

400

255.74

4/c-

300

1/c-

150

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 41 of 72

( mm2 )

( mm2 )

AKOYA
EMDB - A - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

EMDB - A

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

9
Corrected Cable

10
Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

ESMDB - GA

39.33

0.76

29.78

50

80

53.73

0.77

0.87

0.67

80.21

4/c-

25

131

131

1.500

5.32

1.33%

1/c-

16

EMCC-GA

25.00

0.90

22.50

60

63

40.60

0.77

0.87

0.67

60.60

4/c-

16

99

99

2.400

7.14

1.78%

1/c-

16

ESMDB - PIA

84.24

0.77

64.72

60

200

116.77

0.77

0.87

0.67

174.31

4/c-

95

304

304

0.430

4.30

1.08%

1/c-

50

ESMDB - PIB

81.31

0.77

62.48

60

200

112.73

0.77

0.87

0.67

168.28

4/c-

95

304

304

0.430

4.20

1.05%

1/c-

50

EMCC-AR

82.40

0.90

74.25

108

200

133.97

0.77

0.87

0.67

199.98

4/c-

95

304

304

0.430

7.51

1.88%

1/c-

50

TOTALS

312.28

0.81

253.73

800

457.80

1/c-

300

1/c-

300

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (Ib) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 42 of 72

( mm2 )

( mm2 )

AKOYA
EMCC-AR - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

DF

EMD

18.50

0.90

16.65

40

63

30.04

0.77

0.87

0.67

44.84

3/c-

16

99

99

2.400

10.40

2.60%

1/c-

16

SPF -A-2

18.50

0.90

16.65

20

63

30.04

0.77

0.87

0.67

44.84

3/c-

16

99

99

2.400

8.95

2.24%

1/c-

16

LPF -A-1

30.00

0.90

27.00

54

80

48.72

0.77

0.87

0.67

72.72

3/c-

25

131

131

1.500

11.46

2.86%

1/c-

16

LPF -A-2

11.00

0.90

9.90

33

40

17.86

0.77

0.87

0.67

26.66

3/c-

10

78

78

3.800

9.75

2.44%

1/c-

10

CPF - A-1

3.00

0.90

2.70

50

20

4.87

0.77

0.87

0.67

7.27

4/c-

56

56

6.400

9.07

2.27%

1/c-

SEF - A-1

1.50

0.90

1.35

50

20

2.44

0.77

0.87

0.67

3.64

4/c-

56

56

6.400

8.29

2.07%

1/c-

TOTALS

82.50

0.90

74.25

200

4/c-

95

1/c-

50

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

TCL

SPF -A-1

EMCC-AR

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 43 of 72

( mm2 )

( mm2 )

AKOYA
ESMDB-GA - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

ESMDB-GA

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10
Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

EDB - COM

4.67

0.61

2.87

10

32

5.18

0.77

0.87

0.67

7.73

4/c-

56

56

6.400

5.65

2.46%

1/c-

EDB - MDF

12.44

0.79

9.85

25

63

17.77

0.77

0.87

0.67

26.53

4/c-

16

99

99

2.400

6.39

2.78%

1/c-

16

EDB - GSM -1

14.64

0.79

11.58

22

63

20.89

0.77

0.87

0.67

31.19

4/c-

16

99

99

2.400

6.42

2.79%

1/c-

16

EDB - GL1

4.61

0.72

3.34

22

32

6.03

0.77

0.87

0.67

9.00

4/c-

56

56

6.400

6.17

2.68%

1/c-

EDB - GL2

2.97

0.72

2.14

19

32

3.86

0.77

0.87

0.67

5.76

4/c-

56

56

6.400

5.79

2.52%

1/c-

TOTALS

39.33

0.76

29.78

80

53.73

4/c-

25

1/c-

16

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 44 of 72

( mm2 )

( mm2 )

AKOYA
ESMDB-P1A - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

ESMDB-P1A

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

LIFT - A

25.00

0.80

20.00

85

63

36.09

0.77

0.87

0.67

53.87

4/c-

16

99

99

2.400

11.67

2.92%

1/c-

16

EDB - P1 -1

4.41

0.74

3.26

10

32

5.88

0.77

0.87

0.67

8.78

4/c-

56

56

6.400

4.68

1.17%

1/c-

EDB - P2 -1

4.58

0.74

3.40

25

32

6.13

0.77

0.87

0.67

9.16

4/c-

56

56

6.400

5.29

1.32%

1/c-

EDB - AL3

3.01

0.74

2.24

30

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

5.08

1.27%

1/c-

EDB - AL6

3.01

0.74

2.24

35

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

5.21

1.30%

1/c-

EDB - AL9

3.01

0.74

2.24

40

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

5.34

1.33%

1/c-

EDB - AL12

3.01

0.74

2.24

45

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

5.47

1.37%

1/c-

EDB - AL15

3.01

0.74

2.24

50

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

5.60

1.40%

1/c-

EDB - AL18

3.01

0.74

2.24

55

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

5.73

1.43%

1/c-

EDB - AL21

3.01

0.74

2.24

60

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

5.86

1.46%

1/c-

EDB - AL24

3.01

0.74

2.24

65

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

5.99

1.50%

1/c-

EDB - AL27

2.21

0.74

1.63

70

32

2.94

0.77

0.87

0.67

4.39

4/c-

56

56

6.400

5.62

1.41%

1/c-

EDB - AL29

2.21

0.74

1.63

75

32

2.94

0.77

0.87

0.67

4.39

4/c-

56

56

6.400

5.72

1.43%

1/c-

EDB - AR

7.11

0.74

5.27

80

32

9.51

0.77

0.87

0.67

14.19

4/c-

56

56

6.400

9.17

2.29%

1/c-

EDB - GSM - A

14.64

0.79

11.58

90

63

20.89

0.77

0.87

0.67

31.19

4/c-

16

99

99

2.400

8.82

2.20%

1/c-

16

TOTALS

84.24

0.77

64.69

200

116.72

4/c-

95

1/c-

50

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 45 of 72

( mm2 )

( mm2 )

AKOYA
ESMDB-P1B - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

ESMDB-P1B

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

LIFT - B

25.00

0.80

20.00

85

63

36.09

0.77

0.87

0.67

53.87

4/c-

16

99

99

2.400

11.56

2.89%

1/c-

16

EDB - P1 -2

3.84

0.73

2.81

10

32

5.07

0.77

0.87

0.67

7.57

4/c-

56

56

6.400

4.52

1.13%

1/c-

EDB - P2 -2

3.62

0.72

2.62

25

32

4.73

0.77

0.87

0.67

7.06

4/c-

56

56

6.400

4.96

1.24%

1/c-

EDB - BL3

3.01

0.74

2.24

30

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

4.98

1.24%

1/c-

EDB - BL6

3.01

0.74

2.24

35

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

5.11

1.28%

1/c-

EDB - BL9

3.01

0.74

2.24

40

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

5.23

1.31%

1/c-

EDB - BL12

3.01

0.74

2.24

45

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

5.36

1.34%

1/c-

EDB - BL15

3.01

0.74

2.24

50

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

5.49

1.37%

1/c-

EDB - BL18

3.01

0.74

2.24

55

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

5.62

1.41%

1/c-

EDB - BL21

3.01

0.74

2.24

60

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

5.75

1.44%

1/c-

EDB - BL24

3.01

0.74

2.24

65

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

5.88

1.47%

1/c-

EDB - BL27

3.01

0.74

2.24

70

32

4.04

0.77

0.87

0.67

6.03

4/c-

56

56

6.400

6.01

1.50%

1/c-

EDB - BR

( mm2 )

( mm2 )

7.11

0.74

5.27

75

32

9.51

0.77

0.87

0.67

14.19

4/c-

56

56

6.400

8.76

2.19%

1/c-

EDB - GSM - B

14.64

0.79

11.58

90

63

20.89

0.77

0.87

0.67

31.19

4/c-

16

99

99

2.400

8.71

2.18%

1/c-

16

TOTALS

81.30

0.77

62.44

200

112.66

4/c-

95

1/c-

50

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 46 of 72

AKOYA
MDB-B1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

MDB-B1

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

0.038

1.19

0.30%

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

BBR - C1

1105.25

0.70

775.97

94

2250

1400.06

SMDB -R18

355.70

0.80

284.56

175

800

513.42

0.77

0.87

0.67

766.42

4/c-

300

628

1256

0.185

8.31

2.08%

1/c-

300

MCC - CR

76.00

0.90

68.40

250

200

123.41

0.77

0.87

0.67

184.22

4/c-

120

353

353

0.350

10.80

2.70%

1/c-

70

10

800

4/c-

300

1/c-

300

15

2500

1/c-

630

11

PFC

TOTALS

350 kVAr 8 STEP AUTO PFC

1536.95

0.73

1128.93

2036.89

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
Column 9 = column 4 / column 8
Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 47 of 72

( mm2 )

BBR - C1 2250A TPN + E Cu BUSBAR

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

3
4
5
6
7

( mm2 )

AKOYA
BBR -C1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

BBR -C1

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

SMDB-CL3

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB-CL4

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB-CL5

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB-CL6

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB-CL7

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB-CL8

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB-CL9

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB-CL10

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB-CL11

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

SMDB-CL12

110.53

0.70

77.60

20

225

140.01

0.77

0.87

0.67

208.99

4/c-

120

353

353

0.350

2.17

0.54%

1/c-

70

TOTALS

1105.25

0.70

775.97

2500

1400.06

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 48 of 72

( mm2 )

BBR - C1 2250A TPN + E Cu BUSBAR

( mm2 )

AKOYA
SMDB-CL3 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-CL3

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-C301

6.50

0.70

4.55

29

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

2.80

0.70%

1/c-

DB-C302

6.50

0.70

4.55

25

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

2.71

0.68%

1/c-

DB-C303

12.95

0.70

9.07

20

40

16.36

0.77

0.87

0.67

24.42

1/c

10

50

150

4.700

2.68

0.67%

1/c-

10

DB-C304

8.75

0.70

6.13

22

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

2.55

0.64%

1/c-

10

DB-C305

6.50

0.70

4.55

24

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

2.69

0.67%

1/c-

DB-C306

8.75

0.70

6.13

25

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

2.60

0.65%

1/c-

10

DB-C307

8.75

0.70

6.13

30

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

2.69

0.67%

1/c-

10

DB-C308

8.75

0.70

6.13

35

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

2.78

0.69%

1/c-

10

DB-C309

11.86

0.70

8.30

40

40

14.98

0.77

0.87

0.67

22.36

1/c

10

50

150

4.700

3.11

0.78%

1/c-

10

DB-C310

11.71

0.70

8.20

42

40

14.79

0.77

0.87

0.67

22.08

1/c

10

50

150

4.700

3.14

0.79%

1/c-

10

DB-C311

6.50

0.70

4.55

38

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

2.99

0.75%

1/c-

DB-C312

6.50

0.70

4.55

35

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

2.93

0.73%

1/c-

DB-C313

6.50

0.70

4.55

31

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

2.84

0.71%

1/c-

TOTALS

110.52

0.70

77.36

225

139.59

4/c-

120

1/c-

70

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 49 of 72

( mm2 )

( mm2 )

AKOYA
MCC-CR - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

MCC-CR

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

FAHU - RF- C1(S)

18.50

0.90

16.65

40

63

30.04

0.77

0.87

0.67

44.84

3/c-

16

99

198

2.400

12.24

3.06%

1/c-

16

FAHU - RF- C1(R)

11.00

0.90

9.90

20

40

17.86

0.77

0.87

0.67

26.66

3/c-

10

78

156

3.800

11.48

2.87%

1/c-

10

FAHU - RF- C2(S)

22.50

0.90

20.25

54

63

36.54

0.77

0.87

0.67

54.54

3/c-

16

99

198

2.400

13.17

3.29%

1/c-

16

FAHU - RF- C2(R)

18.50

0.90

16.65

31

63

30.04

0.77

0.87

0.67

44.84

3/c-

16

99

198

2.400

11.92

2.98%

1/c-

16

GEF - C

1.50

0.90

1.35

33

16

2.44

0.77

0.87

0.67

3.64

4/c-

56

56

6.400

11.31

2.83%

1/c-

CW BOOSTER PUMP

4.00

0.90

3.60

20

16

6.50

0.77

0.87

0.67

9.70

4/c-

56

56

6.400

11.63

2.91%

1/c-

TOTALS

76.00

0.90

68.40

200

4/c-

120

1/c-

70

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 50 of 72

( mm2 )

( mm2 )

AKOYA
MDB-B2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

DF

EMD

1.56

0.73

1.14

20

32

2.06

0.77

0.87

0.67

3.07

4/c-

56

56

6.400

0.26

0.07%

1/c-

SMDB -R19

332.10

0.80

265.68

82

800

479.36

0.77

0.87

0.67

715.57

4/c-

300

628

1256

0.185

3.64

0.91%

1/c-

300

SMDB -R12

59.40

0.80

47.52

143

125

85.74

0.77

0.87

0.67

127.99

4/c-

50

197

197

0.810

9.93

2.48%

1/c-

25

SMDB -R10

52.70

0.80

42.16

148

125

76.07

0.77

0.87

0.67

113.55

4/c-

50

197

197

0.810

9.12

2.28%

1/c-

25

SMDB -R14

124.50

0.80

99.60

62

300

179.71

0.77

0.87

0.67

268.26

4/c-

185

463

463

0.250

2.79

0.70%

1/c-

95

FIRE PUMP

260.00

0.90

234.00

83

800

422.20

0.77

0.87

0.67

630.24

4/c-

300

628

1256

0.185

3.24

0.81%

1/c-

300

MCC - BP2

86.00

0.90

77.40

167

200

139.65

0.77

0.87

0.67

208.46

4/c-

95

304

304

0.430

10.03

2.51%

1/c-

50

SMDB -LIFT -C

100.00

0.90

90.00

175

225

162.38

0.77

0.87

0.67

242.40

4/c-

120

353

353

0.350

9.95

2.49%

1/c-

70

SMDB -LIFT -B

100.00

0.90

90.00

225

225

162.38

0.77

0.87

0.67

242.40

4/c-

120

353

353

0.350

12.79

3.20%

1/c-

70

MCC - BR

69.00

0.90

62.10

225

160

112.05

0.77

0.87

0.67

167.26

4/c-

120

353

353

0.350

8.82

2.21%

1/c-

70

SMDB -R17

139.10

0.80

111.28

180

300

200.78

0.77

0.87

0.67

299.72

4/c-

185

463

463

0.250

9.04

2.26%

1/c-

95

SMDB -NUR

42.50

0.80

34.00

150

100

61.35

0.77

0.87

0.67

91.57

4/c-

35

162

162

1.100

10.12

2.53%

1/c-

16

SPARE

50.00

0.70

35.00
10

800

4/c-

300

1/c-

300

15

2500

1/c-

630

11

PFC

TOTALS

350 kVAr 8 STEP AUTO PFC

1416.86

0.84

1189.88

2146.87

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

TCL

DB-RMU

MDB-B2

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 51 of 72

( mm2 )

( mm2 )

AKOYA
MCC-BR - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

MCC-BR

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

FAHU - RF - B1

15.00

0.90

13.50

40

63

24.36

0.77

0.87

0.67

36.36

3/c-

16

99

198

2.400

9.99

2.50%

1/c-

16

FAHU - RF - B1

11.00

0.90

9.90

20

63

17.86

0.77

0.87

0.67

26.66

3/c-

16

99

198

2.400

9.25

2.31%

1/c-

16

FAHU - RF - B2

22.50

0.90

20.25

54

63

36.54

0.77

0.87

0.67

54.54

3/c-

16

99

198

2.400

11.19

2.80%

1/c-

16

FAHU - RF - B2

15.00

0.90

13.50

31

63

24.36

0.77

0.87

0.67

36.36

3/c-

16

99

198

2.400

9.73

2.43%

1/c-

16

GEF

1.50

0.90

1.35

50

16

2.44

0.77

0.87

0.67

3.64

4/c-

56

56

6.400

9.60

2.40%

1/c-

CW BOOSTER PUMP

4.00

0.90

3.60

25

16

6.50

0.77

0.87

0.67

9.70

4/c-

56

56

6.400

9.86

2.47%

1/c-

TOTALS

69.00

0.90

62.10

160

4/c-

120

1/c-

70

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 52 of 72

( mm2 )

( mm2 )

AKOYA
MCC-BP2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

MCC-BP2

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

FAHU - 03

22.50

0.90

20.25

40

63

36.54

0.77

0.87

0.67

54.54

3/c-

16

99

198

2.400

11.78

2.95%

1/c-

16

FAHU - 03

15.00

0.90

13.50

20

63

24.36

0.77

0.87

0.67

36.36

3/c-

16

99

198

2.400

10.61

2.65%

1/c-

16

FAHU - 04

30.00

0.90

27.00

54

80

48.72

0.77

0.87

0.67

72.72

3/c-

25

131

262

1.500

12.00

3.00%

1/c-

16

FAHU - 04

18.50

0.90

16.65

31

63

30.04

0.77

0.87

0.67

44.84

3/c-

16

99

198

2.400

11.15

2.79%

1/c-

16

TOTALS

86.00

0.90

77.40

200

4/c-

95

1/c-

50

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 53 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-LIFT-B - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-LIFT-B

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

LIFT - PL - 1

25.00

0.90

22.50

15

80

40.60

0.77

0.87

0.67

60.60

4/c-

25

131

131

1.500

13.70

3.43%

1/c-

16

LIFT - PL - 2

25.00

0.90

22.50

48

80

40.60

0.77

0.87

0.67

60.60

4/c-

25

131

131

1.500

15.71

3.93%

1/c-

16

LIFT - PL - 3

25.00

0.90

22.50

78

80

40.60

0.77

0.87

0.67

60.60

4/c-

25

131

131

1.500

17.54

4.38%

1/c-

16

LIFT - SL

25.00

0.90

22.50

48

80

40.60

0.77

0.87

0.67

60.60

4/c-

25

131

131

1.500

15.71

3.93%

1/c-

16

TOTALS

100.00

0.90

90.00

225

162.38

4/c-

120

1/c-

70

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 54 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-LIFT-C - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-LIFT-C

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

LIFT - PL - 1

25.00

0.90

22.50

15

80

40.60

0.77

0.87

0.67

60.60

4/c-

25

131

131

1.500

10.86

2.71%

1/c-

16

LIFT - PL - 2

25.00

0.90

22.50

48

80

40.60

0.77

0.87

0.67

60.60

4/c-

25

131

131

1.500

12.87

3.22%

1/c-

16

LIFT - PL - 3

25.00

0.90

22.50

78

80

40.60

0.77

0.87

0.67

60.60

4/c-

25

131

131

1.500

14.70

3.67%

1/c-

16

LIFT - SL

25.00

0.90

22.50

48

80

40.60

0.77

0.87

0.67

60.60

4/c-

25

131

131

1.500

12.87

3.22%

1/c-

16

TOTALS

100.00

0.90

90.00

225

162.38

4/c-

120

1/c-

70

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 55 of 72

( mm2 )

( mm2 )

AKOYA
MDB-B3 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

MDB-B3

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

0.038

1.63

0.41%

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

BBR - C2

1105.25

0.70

775.97

129

2250

1400.06

SMDB -R20

178.00

0.80

142.40

82

350

256.93

0.77

0.87

0.67

383.53

4/c-

240

546

546

0.210

4.42

1.11%

1/c-

120

SMDB -R9

79.20

0.80

63.36

198

160

114.32

0.77

0.87

0.67

170.65

4/c-

95

304

304

0.430

9.73

2.43%

1/c-

50

MCC - CP2

89.50

0.90

80.55

40

200

145.33

0.77

0.87

0.67

216.95

4/c-

95

304

304

0.430

2.50

0.62%

1/c-

50

SMDB -GR2

51.80

0.80

41.44

120

125

74.77

0.77

0.87

0.67

111.61

4/c-

50

197

197

0.810

7.27

1.82%

1/c-

25

SPARE

100.00

0.80

80.00

200

144.34
4/c-

300

1/c-

300

1/c-

630

11

PFC

TOTALS

350 kVAr 8 STEP AUTO PFC

1603.75

0.74

1183.72

10

800

15

2500

2135.75

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
Column 9 = column 4 / column 8
Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 56 of 72

( mm2 )

BBR - C2 2250A TPN + E Cu BUSBAR

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

3
4
5
6
7

( mm2 )

AKOYA
BBR -C2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

BBR -C2

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

SMDB-CL13

110.50

0.70

77.60

20

225

140.01

0.77

0.87

0.67

209.00

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB-CL14

110.50

0.70

77.60

20

225

140.01

0.77

0.87

0.67

209.00

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB-CL15

110.50

0.70

77.60

20

225

140.01

0.77

0.87

0.67

209.00

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB-CL16

110.50

0.70

77.60

20

225

140.01

0.77

0.87

0.67

209.00

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB-CL17

110.50

0.70

77.60

20

225

140.01

0.77

0.87

0.67

209.00

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB-CL18

110.50

0.70

77.60

20

225

140.01

0.77

0.87

0.67

209.00

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB-CL19

110.50

0.70

77.60

20

225

140.01

0.77

0.87

0.67

209.00

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB-CL20

110.50

0.70

77.60

20

225

140.01

0.77

0.87

0.67

209.00

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB-CL21

110.50

0.70

77.60

20

225

140.01

0.77

0.87

0.67

209.00

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

SMDB-CL22

110.50

0.70

77.60

20

225

140.01

0.77

0.87

0.67

209.00

4/c-

120

353

353

0.350

2.61

0.65%

1/c-

70

TOTALS

1105.00

0.70

776.00

2250

1400.12

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 57 of 72

( mm2 )

BBR - C2 2250A TPN + E Cu BUSBAR

( mm2 )

AKOYA
SMDB-CL13 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-CL13

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-C1301

6.50

0.70

4.55

29

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

3.24

0.81%

1/c-

DB-C1302

6.50

0.70

4.55

25

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

3.15

0.79%

1/c-

DB-C1303

12.95

0.70

9.07

20

40

16.36

0.77

0.87

0.67

24.42

1/c

10

50

150

4.700

3.13

0.78%

1/c-

10

DB-C1304

8.75

0.70

6.13

22

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

2.99

0.75%

1/c-

10

DB-C1305

6.50

0.70

4.55

24

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

3.13

0.78%

1/c-

DB-C1306

8.75

0.70

6.13

25

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

3.05

0.76%

1/c-

10

DB-C1307

8.75

0.70

6.13

30

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

3.13

0.78%

1/c-

10

DB-C1308

8.75

0.70

6.13

35

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

3.22

0.81%

1/c-

10

DB-C1309

11.86

0.70

8.30

40

40

14.98

0.77

0.87

0.67

22.36

1/c

10

50

150

4.700

3.55

0.89%

1/c-

10

DB-C1310

11.71

0.70

8.20

42

40

14.79

0.77

0.87

0.67

22.08

1/c

10

50

150

4.700

3.59

0.90%

1/c-

10

DB-C1311

6.50

0.70

4.55

38

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

3.44

0.86%

1/c-

DB-C1312

6.50

0.70

4.55

35

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

3.37

0.84%

1/c-

DB-C1313

6.50

0.70

4.55

31

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

3.28

0.82%

1/c-

110.52

0.70

77.36

225

139.59

4/c-

120

1/c-

70

TOTALS

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 58 of 72

( mm2 )

( mm2 )

AKOYA
MCC-CP2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

MCC-CP2

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

FAHU - 03

22.50

0.90

20.25

40

63

36.54

0.77

0.87

0.67

54.54

3/c-

16

99

198

2.400

4.25

1.06%

1/c-

16

FAHU - 03

18.50

0.90

16.65

20

63

30.04

0.77

0.87

0.67

44.84

3/c-

16

99

198

2.400

3.22

0.81%

1/c-

16

FAHU - 04

30.00

0.90

27.00

54

80

48.72

0.77

0.87

0.67

72.72

3/c-

25

131

262

1.500

4.47

1.12%

1/c-

16

FAHU - 04

18.50

0.90

16.65

31

63

30.04

0.77

0.87

0.67

44.84

3/c-

16

99

198

2.400

3.62

0.90%

1/c-

16

TOTALS

89.50

0.90

80.55

200

4/c-

95

1/c-

50

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 59 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-GR2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-GR2

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-R11

24.10

0.59

14.30

25

63

25.80

0.77

0.87

0.67

38.51

4/c-

25

131

262

1.500

7.75

1.94%

1/c-

16

DB-R13

27.70

0.80

22.20

25

63

40.05

0.77

0.87

0.67

59.79

4/c-

25

131

262

1.500

8.02

2.00%

1/c-

16

TOTALS

51.80

0.70

36.50

125

4/c-

50

1/c-

25

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 60 of 72

( mm2 )

( mm2 )

AKOYA
MDB-B4 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

MDB-B4

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

0.089

4.66

1.16%

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

BBR - C3

769.97

0.70

540.62

157

1600

975.43

SMDB -GC

133.02

0.81

107.27

120

225

193.55

0.77

0.87

0.67

288.92

4/c-

120

353

353

0.350

8.13

2.03%

1/c-

70

SMDB -P1C

155.94

0.78

122.03

40

350

220.18

0.77

0.87

0.67

328.67

4/c-

240

546

546

0.210

1.85

0.46%

1/c-

120

2.15

0.75

1.61

20

32

2.90

0.77

0.87

0.67

4.33

4/c-

56

56

6.400

0.37

0.09%

1/c-

330.23

0.84

276.19

30

800

498.32

0.77

0.87

0.67

743.87

4/c-

300

628

1256

0.185

1.38

0.35%

1/c-

300

10

800

4/c-

300

1/c-

300

15

2500

1/c-

630

11

DB-SS2
EMDB - B
PFC

TOTALS

350 kVAr 8 STEP AUTO PFC

1391.31

0.75

1047.72

1890.38

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
Column 9 = column 4 / column 8
Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 61 of 72

( mm2 )

BBR - C3 1600A TPN + E Cu BUSBAR

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

3
4
5
6
7

( mm2 )

AKOYA
BBR - C3 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

BBR - C3

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

SMDB-CL23

110.50

0.70

77.60

20

225

140.01

0.77

0.87

0.67

209.00

4/c-

120

353

353

0.350

5.64

1.41%

1/c-

70

SMDB-CL24

110.50

0.70

77.60

20

225

140.01

0.77

0.87

0.67

209.00

4/c-

120

353

353

0.350

5.64

1.41%

1/c-

70

SMDB-CL25

110.50

0.70

77.60

20

225

140.01

0.77

0.87

0.67

209.00

4/c-

120

353

353

0.350

5.64

1.41%

1/c-

70

SMDB-CL26

110.50

0.70

77.60

20

225

140.01

0.77

0.87

0.67

209.00

4/c-

120

353

353

0.350

5.64

1.41%

1/c-

70

SMDB-CL27

91.08

0.70

63.90

20

200

115.29

0.77

0.87

0.67

172.10

4/c-

95

304

304

0.430

5.65

1.41%

1/c-

50

SMDB-CL28

91.08

0.70

63.90

20

200

115.29

0.77

0.87

0.67

172.10

4/c-

95

304

304

0.430

5.65

1.41%

1/c-

50

SMDB-CL29

72.86

0.70

51.22

20

160

92.41

0.77

0.87

0.67

137.95

4/c-

70

251

251

0.570

5.71

1.43%

1/c-

35

SMDB-CL30

72.86

0.70

51.22

20

160

92.41

0.77

0.87

0.67

137.95

4/c-

70

251

251

0.570

5.71

1.43%

1/c-

35

TOTALS

769.88

0.70

540.64

1600

975.46

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 62 of 72

( mm2 )

BBR - C3 1600A TPN + E Cu BUSBAR

( mm2 )

AKOYA
SMDB-CL23 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-CL23

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-C2301

6.50

0.70

4.55

29

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

6.26

1.57%

1/c-

DB-C2302

6.50

0.70

4.55

25

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

6.18

1.54%

1/c-

DB-C2303

12.95

0.70

9.07

20

40

16.36

0.77

0.87

0.67

24.42

1/c

10

50

150

4.700

6.15

1.54%

1/c-

10

DB-C2304

8.75

0.70

6.13

22

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.02

1.50%

1/c-

10

DB-C2305

6.50

0.70

4.55

24

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

6.16

1.54%

1/c-

DB-C2306

8.75

0.70

6.13

25

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.07

1.52%

1/c-

10

DB-C2307

8.75

0.70

6.13

30

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.16

1.54%

1/c-

10

DB-C2308

8.75

0.70

6.13

35

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.24

1.56%

1/c-

10

DB-C2309

11.86

0.70

8.30

40

40

14.98

0.77

0.87

0.67

22.36

1/c

10

50

150

4.700

6.58

1.64%

1/c-

10

DB-C2310

11.71

0.70

8.20

42

40

14.79

0.77

0.87

0.67

22.08

1/c

10

50

150

4.700

6.61

1.65%

1/c-

10

DB-C2311

6.50

0.70

4.55

38

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

6.46

1.61%

1/c-

DB-C2312

6.50

0.70

4.55

35

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

6.39

1.60%

1/c-

DB-C2313

6.50

0.70

4.55

31

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

6.31

1.58%

1/c-

110.52

0.70

77.36

225

139.59

4/c-

120

1/c-

70

TOTALS

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 63 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-CL27 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-CL27

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-C2701

6.50

0.70

4.55

28

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

6.25

1.56%

1/c-

DB-C2702

6.50

0.70

4.55

26

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

6.21

1.55%

1/c-

DB-C2703

8.75

0.70

6.13

20

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.00

1.50%

1/c-

10

DB-C2704

8.75

0.70

6.13

23

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.05

1.51%

1/c-

10

DB-C2705

8.75

0.70

6.13

26

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.10

1.52%

1/c-

10

DB-C2706

8.75

0.70

6.13

29

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.15

1.54%

1/c-

10

DB-C2707

11.86

0.70

8.30

32

40

14.98

0.77

0.87

0.67

22.36

1/c

10

50

150

4.700

6.40

1.60%

1/c-

10

DB-C2708

11.71

0.70

8.20

35

40

14.79

0.77

0.87

0.67

22.08

1/c

10

50

150

4.700

6.46

1.62%

1/c-

10

DB-C2709

6.50

0.70

4.55

33

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

6.36

1.59%

1/c-

DB-C2710

6.50

0.70

4.55

32

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

6.34

1.59%

1/c-

DB-C2711

6.50

0.70

4.55

30

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

6.30

1.57%

1/c-

TOTALS

91.07

0.70

63.75

200

115.02

4/c-

95

1/c-

50

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 64 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-CL29 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-CL29

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB-C2901

6.50

0.70

4.55

28

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

6.32

1.58%

1/c-

DB-C2902

6.50

0.70

4.55

27

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

6.29

1.57%

1/c-

DB-C2903

8.75

0.70

6.13

25

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.14

1.54%

1/c-

10

DB-C2904

8.75

0.70

6.13

28

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.20

1.55%

1/c-

10

DB-C2905

8.75

0.70

6.13

31

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.25

1.56%

1/c-

10

DB-C2906

8.75

0.70

6.13

34

40

11.05

0.77

0.87

0.67

16.50

1/c

10

50

150

4.700

6.30

1.57%

1/c-

10

DB-C2907

11.86

0.70

8.30

36

40

14.98

0.77

0.87

0.67

22.36

1/c

10

50

150

4.700

6.56

1.64%

1/c-

10

DB-C2908

6.50

0.70

4.55

29

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

6.34

1.58%

1/c-

DB-C2909

6.50

0.70

4.55

28

32

8.21

0.77

0.87

0.67

12.25

1/c

36

108

7.900

6.32

1.58%

1/c-

TOTALS

72.86

0.70

51.00

160

92.02

4/c-

70

1/c-

35

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 65 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-GC - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-GC

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB - LV -2

5.00

0.80

4.00

20

32

7.22

0.77

0.87

0.67

10.77

4/c-

56

56

6.400

9.05

2.26%

1/c-

DB - GL3

15.45

0.80

12.36

30

63

22.30

0.77

0.87

0.67

33.29

4/c-

16

99

99

2.400

9.73

2.43%

1/c-

16

DB-EXT-02

12.00

0.80

9.60

50

40

17.32

0.77

0.87

0.67

25.86

4/c-

10

78

78

3.800

11.42

2.86%

1/c-

10

GARBAGE
CHUTE-3

5.00

0.80

4.00

30

32

7.22

0.77

0.87

0.67

10.77

4/c-

56

56

6.400

9.51

2.38%

1/c-

POOL

50.00

0.80

40.00

60

125

72.17

0.77

0.87

0.67

107.73

4/c-

70

291

291

0.690

11.12

2.78%

1/c-

35

KIDS POOL

15.00

0.80

12.00

70

63

21.65

0.77

0.87

0.67

32.32

4/c-

25

152

152

1.900

11.01

2.75%

1/c-

16

KIDS POOL

15.00

0.80

12.00

80

63

21.65

0.77

0.87

0.67

32.32

4/c-

25

152

152

1.900

11.42

2.86%

1/c-

16

SUMP PUMP
STATION 2

15.00

0.80

12.00

35

63

21.65

0.77

0.87

0.67

32.32

4/c-

16

115

115

2.900

10.33

2.58%

1/c-

16

TOTALS

132.45

0.80

105.96

300

191.18

4/c-

120

1/c-

70

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 66 of 72

( mm2 )

( mm2 )

AKOYA
SMDB-P1A - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

SMDB-P1A

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10
Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

DB - P1 -3

9.74

0.78

7.60

25

40

13.71

0.77

0.87

0.67

20.46

4/c-

10

78

78

3.800

3.15

0.79%

1/c-

10

DB - P2 -3

12.39

0.78

9.66

35

40

17.44

0.77

0.87

0.67

26.03

4/c-

10

90

90

4.700

4.72

1.18%

1/c-

10

DB - CL3

9.50

0.78

7.41

40

40

13.37

0.77

0.87

0.67

19.96

4/c-

10

90

90

4.700

4.36

1.09%

1/c-

10

DB - EXT-C

12.00

0.78

9.36

50

40

16.89

0.77

0.87

0.67

25.21

4/c-

10

90

90

4.700

5.82

1.45%

1/c-

10

DB - CL6

9.50

0.78

7.41

50

40

13.37

0.77

0.87

0.67

19.96

4/c-

10

90

90

4.700

4.99

1.25%

1/c-

10

DB - CL9

9.50

0.78

7.41

60

40

13.37

0.77

0.87

0.67

19.96

4/c-

10

90

90

4.700

5.62

1.40%

1/c-

10

DB - CL12

9.50

0.78

7.41

65

40

13.37

0.77

0.87

0.67

19.96

4/c-

10

90

90

4.700

5.93

1.48%

1/c-

10

DB - CL15

9.50

0.78

7.41

70

40

13.37

0.77

0.87

0.67

19.96

4/c-

10

90

90

4.700

6.25

1.56%

1/c-

10

DB - CL18

9.50

0.78

7.41

75

40

13.37

0.77

0.87

0.67

19.96

4/c-

10

90

90

4.700

6.56

1.64%

1/c-

10

DB - CL21

9.50

0.78

7.41

80

40

13.37

0.77

0.87

0.67

19.96

4/c-

10

90

90

4.700

6.88

1.72%

1/c-

10

DB - CL24

9.50

0.78

7.41

85

40

13.37

0.77

0.87

0.67

19.96

4/c-

10

90

90

4.700

7.19

1.80%

1/c-

10

DB - CL27

6.36

0.78

4.96

90

32

8.95

0.77

0.87

0.67

13.36

4/c-

10

90

90

4.700

5.64

1.41%

1/c-

10

DB - CL29

6.45

0.78

5.03

100

32

9.08

0.77

0.87

0.67

13.55

4/c-

10

90

90

4.700

6.12

1.53%

1/c-

10

DB - CR

13.75

0.78

10.73

125

40

19.35

0.77

0.87

0.67

28.89

4/c-

16

115

115

2.900

8.86

2.22%

1/c-

16

DAMAC SIGNAGE

12.00

0.78

9.36

125

40

16.89

0.77

0.87

0.67

25.21

4/c-

16

115

115

2.900

7.97

1.99%

1/c-

16

TOTALS

148.69

0.78

115.98

300

209.26

4/c-

240

1/c-

120

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 67 of 72

( mm2 )

( mm2 )

AKOYA
EMDB - B - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

EMDB - B

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

9
Corrected Cable

10
Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

ESMDB - GC

32.95

0.74

24.53

35

80

44.26

0.77

0.87

0.67

66.07

4/c-

25

131

131

1.500

3.71

0.93%

1/c-

16

EMCC-GC

25.00

0.90

22.50

25

63

40.60

0.77

0.87

0.67

60.60

4/c-

25

131

131

1.500

2.91

0.73%

1/c-

16

ESMDB - PIC

82.28

0.77

63.16

40

200

113.96

0.77

0.87

0.67

170.11

4/c-

95

304

304

0.430

3.34

0.84%

1/c-

50

EMCC-BR

82.50

0.90

74.25

225

200

133.97

0.77

0.87

0.67

199.98

4/c-

150

406

406

0.290

10.12

2.53%

1/c-

50

EMCC - CR

82.50

0.90

74.25

225

200

133.97

0.77

0.87

0.67

199.98

4/c-

150

406

406

0.290

10.12

2.53%

1/c-

50

SPARE

25.00

0.70

17.50

TOTALS

330.23

0.84

276.19

4/c-

300

1/c-

300

800

498.32

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (Ib) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
Column 9 = column 4 / column 8
Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 68 of 72

( mm2 )

( mm2 )

63

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

3
4
5
6
7

AKOYA
EMCC-BR - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

DF

EMD

18.50

0.90

16.65

40

63

30.04

0.77

0.87

0.67

44.84

3/c-

16

99

99

2.400

13.01

3.25%

1/c-

16

SPF -B-2

18.50

0.90

16.65

20

63

30.04

0.77

0.87

0.67

44.84

3/c-

16

99

99

2.400

11.57

2.89%

1/c-

16

LPF -B-1

30.00

0.90

27.00

54

100

48.72

0.77

0.87

0.67

72.72

3/c-

25

131

131

1.500

14.07

3.52%

1/c-

16

LPF -B-2

11.00

0.90

9.90

33

40

17.86

0.77

0.87

0.67

26.66

3/c-

10

78

78

3.800

12.36

3.09%

1/c-

10

CPF - B -1

3.00

0.90

2.70

35

20

4.87

0.77

0.87

0.67

7.27

4/c-

56

56

6.400

11.22

2.80%

1/c-

SEF - B-1

1.50

0.90

1.35

40

20

2.44

0.77

0.87

0.67

3.64

4/c-

56

56

6.400

10.75

2.69%

1/c-

TOTALS

82.50

0.90

74.25

200

4/c-

150

1/c-

95

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

TCL

SPF -B-1

EMCC-BR

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 69 of 72

( mm2 )

( mm2 )

AKOYA
EMCC-CR - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

LOAD

Power (kW)

Cable

CPD

Design Current

Correction Factor (C.F.)

Length

In

Ib

Table 4C1

Overall C.F.

Ampacity It

(m)

(A)

(A)

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

10

Corrected Cable

Cable size
required

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

DF

EMD

18.50

0.90

16.65

40

63

30.04

0.77

0.87

0.67

44.84

3/c-

16

99

99

2.400

13.01

3.25%

1/c-

16

SPF -C-2

18.50

0.90

16.65

20

63

30.04

0.77

0.87

0.67

44.84

3/c-

16

99

99

2.400

11.57

2.89%

1/c-

16

LPF -C-1

30.00

0.90

27.00

54

100

48.72

0.77

0.87

0.67

72.72

3/c-

25

131

131

1.500

14.07

3.52%

1/c-

16

LPF -C-2

11.00

0.90

9.90

33

40

17.86

0.77

0.87

0.67

26.66

3/c-

10

78

78

3.800

12.36

3.09%

1/c-

10

CPF - C -1

3.00

0.90

2.70

35

20

4.87

0.77

0.87

0.67

7.27

4/c-

56

56

6.400

11.22

2.80%

1/c-

SEF - C-1

1.50

0.90

1.35

40

20

2.44

0.77

0.87

0.67

3.64

4/c-

56

56

6.400

10.75

2.69%

1/c-

TOTALS

82.50

0.90

74.25

200

4/c-

150

1/c-

95

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

TCL

SPF -C-1

EMCC-CR

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 70 of 72

( mm2 )

( mm2 )

AKOYA
ESMDB-GC - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

EDB - GSM - 2

14.60

0.74

10.80

69

63

19.49

0.77

0.87

0.67

29.10

4/c-

16

99

99

2.400

6.93

3.02%

1/c-

16

EDB - GL3

3.31

0.74

2.45

10

32

4.42

0.77

0.87

0.67

6.60

4/c-

10

78

78

3.800

3.87

1.68%

1/c-

10

SPARE

15.00

0.74

11.10

TOTALS

32.91

0.74

24.35

4/c-

25

1/c-

16

( mm2 )

( mm2 )

ESMDB-GC

40

80

43.94

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 71 of 72

AKOYA
ESMDB-P1C - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
1

ESMDB-P1C

LOAD

Power (kW)

Cable

CPD

Design Current

Length

In

Ib

(m)

(A)

(A)

10

Correction Factor (C.F.)

Corrected Cable

Table 4C1

Overall C.F.

Ampacity It

Cable size
required

Amb. Temp. (Ca)

(Ca x Cg)

(A)

Grouping (Cg)

11

12

13

14

15

No. of
cables in
parallel
required

Equivalent

Voltage Drop

Table 4E4A
Cable Ampacity
(A)

Ampacity Ita

Table 4E4B

(A)

(mV/A-m)

(V)

(%)

Voltage Drop

16
Percentage
Voltage Drop

17

18

ECC Cable size


required

No. of ECC
cables in
parallel
required

TCL

DF

EMD

LIFT - C

25.00

0.84

21.00

110

63

37.89

0.77

0.87

0.67

56.56

4/c-

35

162

162

1.100

7.93

3.45%

1/c-

16

EDB - P1 -3

3.47

0.72

2.51

10

32

4.53

0.77

0.87

0.67

6.76

4/c-

56

56

6.400

3.63

1.58%

1/c-

16

EDB - P2 -3

3.56

0.73

2.59

25

32

14.08

0.77

0.87

0.67

21.01

4/c-

66

66

7.900

6.12

2.66%

1/c-

16

EDB - CL3

3.01

0.74

2.24

36

32

12.17

0.77

0.87

0.67

18.17

4/c-

66

66

7.900

6.81

2.96%

1/c-

EDB - CL6

3.01

0.74

2.24

42

32

12.17

0.77

0.87

0.67

18.17

4/c-

66

66

7.900

7.38

3.21%

1/c-

EDB - CL9

3.01

0.74

2.24

51

32

12.17

0.77

0.87

0.67

18.17

4/c-

10

90

90

4.700

6.26

2.72%

1/c-

EDB - CL12

3.01

0.74

2.24

55

32

12.17

0.77

0.87

0.67

18.17

4/c-

10

90

90

4.700

6.49

2.82%

1/c-

10

EDB - CL15

3.01

0.74

2.24

60

32

12.17

0.77

0.87

0.67

18.17

4/c-

10

90

90

4.700

6.78

2.95%

1/c-

10

EDB - CL18

3.01

0.74

2.24

63

32

12.17

0.77

0.87

0.67

18.17

4/c-

10

90

90

4.700

6.95

3.02%

1/c-

10

EDB - CL21

3.01

0.74

2.24

68

32

12.17

0.77

0.87

0.67

18.17

4/c-

10

90

90

4.700

7.23

3.15%

1/c-

10

EDB - CL24

3.01

0.74

2.24

71

32

12.17

0.77

0.87

0.67

18.17

4/c-

10

90

90

4.700

7.41

3.22%

1/c-

16

EDB - CL27

2.21

0.74

1.63

75

32

8.86

0.77

0.87

0.67

13.22

4/c-

10

90

90

4.700

6.47

2.81%

1/c-

16

EDB - CL29

2.21

0.74

1.63

80

32

8.86

0.77

0.87

0.67

13.22

4/c-

10

90

90

4.700

6.67

2.90%

1/c-

16

EDB - CR

7.71

0.68

5.27

85

32

28.64

0.77

0.87

0.67

42.75

4/c-

35

188

188

1.350

6.63

2.88%

1/c-

16

EDB - GSM - C

14.64

0.79

11.58

88

40

62.93

0.77

0.87

0.67

93.95

4/c-

50

228

228

1.000

8.88

3.86%

1/c-

25

TOTALS

82.88

0.77

64.13

250

115.71

4/c-

150

1/c-

70

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop
Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3
4
5
6
7

Column 9 = column 4 / column 8


Column 10 selected to suit column 9
Column 16 calculated according to columns 10 and 11.
Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
Nominal system voltage is 400/230V 6%, 3 Phase, 4 Wire.

Page 72 of 72