SYSTEMS
198
198
199
206
INSTALLATION
208
General Requirements
Framing
Plasterboard Layout
Plasterboard Fixing
Exterior Cladding
208
208
209
210
211
CONSTRUCTION
DETAILS
213
INTRODUCTION
External timber framed
plasterboard walls protect
the inside from weather,
noise and, when applicable,
re. They must also comply
with local energy efciency
provisions.
framed walls.
197
NON-FIRE RATED
KTW73
EXTERNAL WALL CLADDING: 1 layer of minimum 6mm bre cement
MOISTURE BARRIER:
Breathable wall wrap
FRAME:
Minimum 70mm timber studs at maximum 600mm centres
WALL INSULATION:
As specied in table below
INTERNAL WALL LINING:
1 layer of 10mm MastaShield
[10mm MastaShield can be substituted with 10mm WaterShield or 10mm SoundShield]
Stud Size
(mm)
Width
(mm)
FRL
Stud Depth
//
70
87mm
approximate
107mm
approximate
90
Acoustics
Rw (Rw + Ctr)
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
39 (30)
39 (30)
40 (31)
40 (31)
40 (31)
Acoustic Report
Marshall Day
KTW274
EXTERNAL WALL CLADDING:
MOISTURE BARRIER:
FRAME:
WALL INSULATION:
INTERNAL WALL LINING:
Stud Size
(mm)
FRL
Stud Depth
//
70
90
198
Width
(mm)
97mm
approximate
117mm
approximate
Acoustics
Rw (Rw + Ctr)
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
44 (35)
44 (35)
44 (37)
45 (38)
44 (37)
Acoustic Report
Day Design
3094-43
FIRE RATED
FRL
30/30/30
Stud Size
(mm)
Width
(mm)
Acoustics
Rw (Rw + Ctr)
Stud Depth
rated from
the outside only
70
Fire Report
FAR 3371
90
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
94mm
+ external cladding
39 (31)
39 (31)
114mm
+ external cladding
39 (32)
40 (32)
39 (31)
Acoustic Report
Marshall Day
KTW473
FRL
60/60/60
rated from
the outside only
Fire Report
FAR 3371
Stud Size
(mm)
Width
(mm)
Acoustics
Rw (Rw + Ctr)
Stud Depth
70
90
97mm
+ external cladding
117mm
+ external cladding
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
39 (31)
39 (37)
39 (32)
40 (33)
39 (32)
Acoustic Report
Marshall Day
KTW471
EXTERNAL WALL CLADDING: Any cladding
EXTERNAL CLADDING FRAME: Timber or steel battens
MOISTURE BARRIER:
Breathable wall wrap
EXTERNAL WALL LINING:
2 layers of 13mm MultiShield
FRAME:
Minimum 70mm timber studs at maximum 600mm centres
WALL INSULATION:
As specied in table below
INTERNAL WALL LINING:
1 layer of 10mm MastaShield
[10mm MastaShield can be substituted with 10mm WaterShield or 10mm SoundShield]
[Use approved re rated penetration details in the non-re rated internal lining to maintain FRL]
FRL
90/90/90
rated from
the outside only
Fire Report
FAR 3371
Stud Size
(mm)
Width
(mm)
Acoustics
Rw (Rw + Ctr)
Stud Depth
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
70
107mm
+ external cladding
44 (36)
44 (36)
90
127mm +
external cladding
45 (37)
45 (38)
45 (37)
KTW470
Acoustic Report
Marshall Day
199
KTW472
EXTERNAL WALL CLADDING: Any cladding
EXTERNAL CLADDING FRAME: Timber or steel battens
MOISTURE BARRIER:
Breathable wall wrap
EXTERNAL WALL LINING:
3 layers of 13mm MultiShield
FRAME:
Minimum 70mm timber studs at maximum 600mm centres
WALL INSULATION:
As specied in table below
INTERNAL WALL LINING:
1 layer of 10mm MastaShield
[10mm MastaShield can be substituted with 10mm WaterShield or 10mm SoundShield]
[Use approved re rated penetration details in the non-re rated internal lining to maintain FRL]
FRL
120/120/120
Stud Size
(mm)
Width
(mm)
Stud Depth
rated from
the outside only
70
Fire Report
FAR 3371
90
Acoustics
Rw (Rw + Ctr)
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
120mm
+ external cladding
47 (38)
47 (38)
140mm
+ external cladding
48 (40)
48 (41)
48 (40)
Acoustic Report
Marshall Day
KTW491
EXTERNAL WALL CLADDING:
EXTERNAL CLADDING FRAME:
MOISTURE BARRIER:
EXTERNAL WALL LINING:
FRAME:
WALL INSULATION:
INTERNAL WALL LINING:
FRL
30/30/30
Any cladding
Timber or steel battens
Breathable wall wrap
2 layers of 13mm MultiShield
Minimum 70mm timber studs at maximum 600mm centres
Optional
Optional
Stud Size
(mm)
Width
(mm)
Stud Depth
rated from
the outside only
70
Fire Report
FAR 3348
90
Acoustics
Rw (Rw + Ctr)
No Insulation
R1.5 EarthWool
R1.5 Polyester
97mm
+ external cladding
34 (31)
34 (31)
34 (31)
117mm
+ external cladding
34 (31)
34 (31)
34 (31)
Acoustic Report
Day Design
3094-45
KTW494
EXTERNAL WALL CLADDING:
EXTERNAL CLADDING FRAME:
MOISTURE BARRIER:
EXTERNAL WALL LINING:
FRAME:
WALL INSULATION:
INTERNAL WALL LINING:
FRL
60/60/60
Stud Size
(mm)
Width
(mm)
Stud Depth
rated from
the outside only
70
Fire Report
FAR 3348
90
200
Any cladding
Timber or steel battens
Breathable wall wrap
2 layers of 16mm MultiShield
Minimum 70mm timber studs at maximum 600mm centres
Optional
Optional
Acoustics
Rw (Rw + Ctr)
No Insulation
R1.5 EarthWool
R1.5 Polyester
103mm
+ external cladding
35 (32)
35 (32)
35 (32)
123mm
+ external cladding
35 (32)
35 (32)
35 (32)
Acoustic Report
Day Design
3094-45
FRL
90/90/90
Any cladding
Timber or steel battens
Breathable wall wrap
3 layers of 13mm MultiShield
Minimum 70mm timber studs at maximum 600mm centres
Optional
Optional
Stud Size
(mm)
Width
(mm)
Acoustics
Rw (Rw + Ctr)
Stud Depth
rated from
the outside only
70
Fire Report
FAR 3348
90
No Insulation
R1.5 EarthWool
R1.5 Polyester
110mm
+ external cladding
37 (35)
37 (35)
37 (35)
130mm
+ external cladding
37 (35)
37 (35)
37 (35)
Acoustic Report
Day Design
3094-45
KTW495
FRL
120/120/120
Stud Size
(mm)
Width
(mm)
Acoustics
Rw (Rw + Ctr)
Stud Depth
rated from
the outside only
70
Fire Report
FAR 3348
90
No Insulation
R1.5 EarthWool
R1.5 Polyester
119mm
+ external cladding
38 (36)
38 (36)
38 (36)
139mm
+ external cladding
38 (36)
38 (36)
38 (36)
Acoustic Report
Day Design
3094-45
KTW476
EXTERNAL WALL CLADDING:
EXTERNAL CLADDING FRAME:
MOISTURE BARRIER:
EXTERNAL WALL LINING:
FRAME:
WALL INSULATION:
INTERNAL WALL LINING:
FRL
60/60/60
Any cladding
Timber or steel battens
Breathable wall wrap
1 layer of 16mm MultiShield
Minimum 70mm timber studs at maximum 600mm centres
As specied in table below
1 layer of 16mm FireShield or 16mm MultiShield
Stud Size
(mm)
Width
(mm)
Acoustics
Rw (Rw + Ctr)
Stud Depth
rated from
both sides
70
Fire Report
FAR 3371
90
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
103mm
+ external cladding
41 (33)
41 (33)
123mm
+ external cladding
42 (34)
42 (36)
42 (34)
KTW492
Acoustic Report
Day Design
3094-45
201
KTW477
EXTERNAL WALL CLADDING:
EXTERNAL CLADDING FRAME:
MOISTURE BARRIER:
EXTERNAL WALL LINING:
FRAME:
WALL INSULATION:
INTERNAL WALL LINING:
FRL
90/90/90
rated from the outside
60/60/60
rated from the inside
Fire Report
FAR 3371
Any cladding
Timber or steel battens
Breathable wall wrap
2 layers of 13mm MultiShield
Minimum 70mm timber studs at maximum 600mm centres
As specied in table below
1 layer of 16mm FireShield or 16mm MultiShield
Stud Size
(mm)
Width
(mm)
Stud Depth
Acoustics
Rw (Rw + Ctr)
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
70
113mm
+ external cladding
44 (37)
44 (37)
90
133mm
+ external cladding
44 (38)
45 (39)
44 (38)
Acoustic Report
Day Design
3094-45
KTW478
EXTERNAL WALL CLADDING:
EXTERNAL CLADDING FRAME:
MOISTURE BARRIER:
EXTERNAL WALL LINING:
FRAME:
WALL INSULATION:
INTERNAL WALL LINING:
FRL
90/90/90
Any cladding
Timber or steel battens
Breathable wall wrap
2 layers of 13mm MultiShield
Minimum 70mm timber studs at maximum 600mm centres
As specied in table below
2 layers of 13mm FireShield or 13m MultiShield
Stud Size
(mm)
Width
(mm)
Stud Depth
rated from
both sides
70
Fire Report
FAR 3371
90
Acoustics
Rw (Rw + Ctr)
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
123mm
+ external cladding
47 (41)
47 (41)
143mm
+ external cladding
47 (42)
48 (43)
47 (42)
Acoustic Report
Day Design
3094-45
KTW479
EXTERNAL WALL CLADDING:
EXTERNAL CLADDING FRAME:
MOISTURE BARRIER:
EXTERNAL WALL LINING:
FRAME:
WALL INSULATION:
INTERNAL WALL LINING:
FRL
120/120/120
202
Any cladding
Timber or steel battens
Breathable wall wrap
2 layers of 16mm MultiShield
Minimum 70mm timber studs at maximum 600mm centres
As specied in table below
2 layers of 16mm FireShield or 16mm MultiShield
Stud Size
(mm)
Width
(mm)
Stud Depth
rated from
both sides
70
Fire Report
FAR 3371
90
Acoustics
Rw (Rw + Ctr)
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
135mm
+ external cladding
47 (42)
47 (42)
155mm
+ external cladding
47 (43)
48 (44)
47 (43)
Acoustic Report
Day Design
3094-45
EXTERNAL WALL CLADDING: 1 layer of 7.5mm bre cement monolithic texture base sheet
MOISTURE BARRIER:
Breathable wall wrap
EXTERNAL WALL LINING:
1 layer of 13mm MultiShield
FRAME:
Minimum 70mm timber studs at maximum 600mm centres
WALL INSULATION:
As specied in table below
INTERNAL WALL LINING:
1 layer of 10mm MastaShield
[10mm MastaShield can be substituted with 10mm WaterShield or 10mm SoundShield]
[Use approved re rated penetration details in the non-re rated internal lining to maintain FRL]
FRL
30/30/30
Stud Size
(mm)
Width
(mm)
Acoustics
Rw (Rw + Ctr)
Stud Depth
rated from
the outside only
70
Fire Report
FAR 3371
90
102mm
approximate
122mm
approximate
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
45 (35)
44 (35)
45 (37)
45 (38)
45 (37)
Acoustic Report
Marshall Day
KTW483
FRL
60/60/60
Stud Size
(mm)
Width
(mm)
Acoustics
Rw (Rw + Ctr)
Stud Depth
rated from
the outside only
70
Fire Report
FAR 3371
90
EXTERNAL WALL CLADDING: 1 layer of 7.5mm bre cement monolithic texture base sheet
MOISTURE BARRIER:
Breathable wall wrap
EXTERNAL WALL LINING:
1 layer of 16mm MultiShield
FRAME:
Minimum 70mm timber studs at maximum 600mm centres
WALL INSULATION:
As specied in table below
INTERNAL WALL LINING:
1 layer of 10mm MastaShield
[10mm MastaShield can be substituted with 10mm WaterShield or 10mm SoundShield]
[Use approved re rated penetration details in the non-re rated internal lining to maintain FRL]
105mm
approximate
125mm
approximate
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
47 (38)
46 (38)
47 (39)
47 (39)
47 (39)
Acoustic Report
Day Design
3094-43
KTW481
EXTERNAL WALL CLADDING: 1 layer of 7.5mm bre cement monolithic texture base sheet
MOISTURE BARRIER:
Breathable foil
EXTERNAL WALL LINING:
2 layers of 13mm MultiShield
FRAME:
Minimum 70mm timber studs at maximum 600mm centres
WALL INSULATION:
As specied in table below
INTERNAL WALL LINING:
1 layer of 10mm MastaShield
[10mm MastaShield can be substituted with 10mm WaterShield or 10mm SoundShield]
[Use approved re rated penetration details in the non-re rated internal lining to maintain FRL]
FRL
90/90/90
Stud Size
(mm)
Width
(mm)
Acoustics
Rw (Rw + Ctr)
Stud Depth
rated from
the outside only
70
Fire Report
FAR 3371
90
115mm
approximate
135mm
approximate
KTW480
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
47 (38)
47 (38)
48 (41)
48 (41)
48 (41)
Acoustic Report
Marshall Day
203
KTW484
EXTERNAL WALL CLADDING: 1 layer of 7.5mm bre cement monolithic texture base sheet
MOISTURE BARRIER:
Breathable foil
EXTERNAL WALL LINING:
2 layers of 16mm MultiShield
FRAME:
Minimum 70mm timber studs at maximum 600mm centres
WALL INSULATION:
As specied in table below
INTERNAL WALL LINING:
1 layer of 10mm MastaShield
[10mm MastaShield can be substituted with 10mm WaterShield or 10mm SoundShield]
[Use approved re rated penetration details in the non-re rated internal lining to maintain FRL]
FRL
90/90/90
Stud Size
(mm)
Width
(mm)
Stud Depth
rated from
the outside only
70
Fire Report
FAR 3371
90
121mm
approximate
141mm
approximate
Acoustics
Rw (Rw + Ctr)
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
49 (40)
49 (40)
50 (42)
50 (42)
50 (42)
Acoustic Report
Day Design
3094-43
KTW482
EXTERNAL WALL CLADDING: 1 layer of 7.5mm bre cement monolithic texture base sheet
MOISTURE BARRIER:
Breathable wall wrap
EXTERNAL WALL LINING:
3 layers of 13mm MultiShield
FRAME:
Minimum 70mm timber studs at maximum 600mm centres
WALL INSULATION:
As specied intable below
INTERNAL WALL LINING:
1 layer of 10mm MastaShield
[10mm MastaShield can be substituted with 10mm WaterShield or 10mm SoundShield]
[Use approved re rated penetration details in the non-re rated internal lining to maintain FRL]
FRL
120/120/120
Stud Size
(mm)
Width
(mm)
Stud Depth
rated from
the outside only
70
Fire Report
FAR 3371
90
128mm
approximate
148mm
approximate
Acoustics
Rw (Rw + Ctr)
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
49 (41)
49 (41)
50 (44)
50 (44)
50 (44)
Acoustic Report
Marshall Day
KTW486
EXTERNAL WALL CLADDING:
MOISTURE BARRIER:
EXTERNAL WALL LINING:
FRAME:
WALL INSULATION:
INTERNAL WALL LINING:
FRL
60/60/60
204
Stud Size
(mm)
Width
(mm)
Stud Depth
rated from
both sides
70
Fire Report
FAR 3371
90
111mm
approximate
131mm
approximate
Acoustics
Rw (Rw + Ctr)
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
47 (40)
47 (39)
47 (41)
47 (41)
47 (41)
Acoustic Report
Day Design
3094-43
FRL
90/90/90
rated from the outside
60/60/60
rated from the inside
Fire Report
FAR 3371
Stud Size
(mm)
Width
(mm)
Acoustics
Rw (Rw + Ctr)
Stud Depth
121mm
approximate
141mm
approximate
70
90
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
47 (42)
47 (42)
48 (43)
48 (44)
48 (43)
Acoustic Report
Marshall Day
KTW488
FRL
90/90/90
Stud Size
(mm)
Width
(mm)
Acoustics
Rw (Rw + Ctr)
Stud Depth
rated from
both sides
70
Fire Report
FAR 3371
90
131mm
approximate
151mm
approximate
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
48 (45)
48 (45)
49 (46)
49 (46)
49 (46)
Acoustic Report
Marshall Day
KTW489
EXTERNAL WALL CLADDING:
MOISTURE BARRIER:
EXTERNAL WALL LINING:
FRAME:
WALL INSULATION:
INTERNAL WALL LINING:
FRL
120/120/120
Stud Size
(mm)
Width
(mm)
Acoustics
Rw (Rw + Ctr)
Stud Depth
rated from
both sides
70
Fire Report
FAR 3371
90
143mm
approximate
163mm
approximate
KTW487
R1.5 EarthWool
R2.0 EarthWool
R1.5 Polyester
50 (47)
50 (47)
50 (47)
50 (47)
50 (47)
Acoustic Report
Marshall Day
205
BRICK VENEER
KTW70
EXTERNAL MASONRY:
Minimum 90mm masonry with FRL 60/60/60 (Minimum laid weight 130 kg/m)
FRAME:
Minimum 70mm timber studs at maximum 600mm centres with a minimum 20mm air gap
WALL INSULATION:
As specied in table below
INTERNAL WALL LINING:
1 layer of 10mm MastaShield
[10mm MastaShield can be substituted with 10mm WaterShield or 10mm SoundShield]
FRL
60/60/60
rated from
the outside only
Stud Size
(mm)
Width
(mm)
Stud Depth
Fire Report
FAR 3586
70
190 mm
approximate
Acoustics
Rw (Rw + Ctr)
R1.5 EarthWool
R1.5 Polyester
54 (46)
53 (46)
Acoustic Report
Marshall Day
KTW373
EXTERNAL MASONRY:
Minimum 90mm masonry with FRL 60/60/60 (Minimum laid weight 130 kg/m)
FRAME:
Minimum 70mm timber studs at maximum 600mm centres with a minimum 20mm air gap
WALL INSULATION:
As specied in table below
INTERNAL WALL LINING:
1 layer of 16mm FireShield
[16mm FireShield can be substituted with 16mm MultiShield]
FRL
60/60/60
rated from both sides
Stud Size
(mm)
Width
(mm)
Stud Depth
Fire Report
FAR 3586
70
196 mm
approximate
Acoustics
Rw (Rw + Ctr)
R1.5 EarthWool
R1.5 Polyester
54 (49)
54 (49)
Acoustic Report
Marshall Day
KTW371
EXTERNAL MASONRY:
Minimum 90mm masonry with FRL 90/90/90 (Minimum laid weight 130 kg/m)
FRAME:
Minimum 70mm timber studs at maximum 600mm centres with a minimum 20mm air gap
WALL INSULATION:
As specied in table below
INTERNAL WALL LINING:
2 layers of 13mm FireShield
[13mm FireShield can be substituted with 13mm MultiShield or 13mm ImpactShield or 13mm QuadShield]
FRL
90/90/90
rated from both sides
Fire Report
FAR 3586
206
Stud Size
(mm)
Width
(mm)
Stud Depth
70
206 mm
approximate
Acoustics
Rw (Rw + Ctr)
R1.5 EarthWool
R1.5 Polyester
54 (51)
54 (51)
Acoustic Report
Marshall Day
KTW374
FRL
120/120/120
rated from both sides
Width
(mm)
Stud Depth
70
212 mm
approximate
Acoustics
Rw (Rw + Ctr)
R1.5 EarthWool
R1.5 Polyester
55 (51)
55 (51)
Acoustic Report
Marshall Day
Fire Report
FAR 3586
Stud Size
(mm)
EXTERNAL MASONRY:
Minimum 90mm masonry with FRL 120/120/120 (Minimum laid weight 130 kg/m)
FRAME:
Minimum 70mm timber studs at maximum 600mm centres with a minimum 20mm air gap
WALL INSULATION:
As specied in table below
INTERNAL WALL LINING:
2 layers of 16mm FireShield
[16mm FireShield can be substituted with 16mm MultiShield]
207
GENERAL REQUIREMENTS
Non-Fire
Rated
Fire
Rated
Jointing of MultiShield is not required due to the overlying breathable wall wrap
and external cladding.
Use approved re rated penetration details for systems that use the internal
non-re rated plasterboard wall lining to maintain the FRL.
Pack any gaps between the top of the wall and the underside of the roof covering
with mineral bre or other suitable re resisting material. This maintains the re
rating of the system. [Refer to mineral bre manufacturers specications for minimum
widths required]
FRAMING
Non-Fire
Rated
Fire
Rated
For load bearing walls use timber studs with minimum dimensions 70x45mm
or 90x35mm.
208
PLASTERBOARD LAYOUT
Fire
Rated
Alternate from one side of the wall to the other when xing the plasterboard sheets.
Vertical joints must be 200mm minimum from the edge of any opening such as
windows and doorways to minimise cracking at the joints.
Stagger butt joints by 600mm minimum on adjoining sheets, between layers and on
opposite sides of the wall.
Non-Fire
Rated
Horizontal Layout
Stagger butt joints by 600mm minimum on adjoining sheets, between layers and on
opposite sides of the wall.
Vertical Layout
209
PLASTERBOARD FIXING
Non-Fire
Rated
Drive fasteners to just below the sheet surface, taking care not to break the paper
linerboard.
Laminating screws can be used to x butt joints in the second and third layer.
Fire
Rated
Apply MastaGrip daubs 200mm minimum from screws and plasterboard edges.
SCREW TYPE AND MINIMUM SIZE FOR THE INSTALLATION OF PLASTERBOARD TO STEEL
Plasterboard
Thickness
1st Layer
2nd Layer
3rd Layer
10mm
25mm 6g S screw
40mm 6g S screw*
13mm
25mm 6g S screw
40mm 6g S screw*
60mm 6g S screw*
16mm
30mm 6g S screw
45mm 6g S screw*
65mm 6g S screw*
For steel up to 0.8mm BMT use Type S ne thread needle point screws.
For steel 0.8mm to 2.0mm BMT use Type S ne thread drill point screws.
*40mm 10g Laminating screws may be used as detailed in installation diagrams.
FASTENER TYPE AND MINIMUM SIZE FOR THE INSTALLATION OF PLASTERBOARD TO SOFTWOOD TIMBER
Plasterboard
Thickness
1st Layer
2nd Layer
3rd Layer
6.5mm
10mm
13mm
16mm
210
EXTERIOR CLADDING
Non-Fire
Rated
Fire
Rated
Extend the external re rated wall up to the non-combustible roof covering or noncombustible eaves lining [Refer to Construction Details].
Fixing
Sheet Layout
Perimeter
Field
10-15mm
Horizontal
Perimeter fasteners 10-15mm from sheet edges
Fix screws or double nails at 300mm max
centres. Fix nails at 200mm max centres.
Stagger
recessed
edges by
300mm min
on opposite
sides of the
wall or
back by a
nogging
Nails at
200mm
max
Butt joints
200mm min
from
openings
Double Nails
at 300mm max
10-15mm
Screws at
300mm max
200mm max
200mm
max
Openings
200mm
max
Butt Joints
Internal and
External
Corners
Openings
Fire Sealant
Jointing Face
Layer
10-15mm
211
Fix cladding or cladding battens to the timber frame through the MultiShield
Fixing
Sheet Layout
Perimeter
Field
10-15mm
200mm min
1st layer
Nails at
300mm
max
1st layer
Screws or
Double
Nails at
400mm max
1st layer
300mm max
1st layer
300mm max
1st layer
Openings
300mm
max
1st layer
Screws 300mm max
Nails 200mm max
stagger fasteners
2nd layer
Nails at
200mm
max
10-15mm
2nd layer
200mm max
Stagger
recessed
edges by
300mm min
between
layers
2nd layer
Screws or Double
Nails at 300mm max
2nd layer
200mm max
2nd layer
Screws 200mm max
Nails 150mm max
stagger fasteners
10-15mm
3rd layer
laminate at
400mm max
3rd layer
laminate at
400mm max
1st layer
Screws 300mm max
Nails 200mm max
stagger fasteners
2nd layer
Screws 200mm max
Nails 150mm max
stagger fasteners
1st layer
Screws or
Double
Nails at
400mm
max
1st layer
openings
300mm
max
1st layer
300mm max
Stagger recessed
edges by 300mm
min between layers
212
Internal and
External
Corners
Openings
Fire Sealant
Jointing Face
Layer
Fixing
Sheet Layout
Perimeter
Field
Recessed
Edges
Butt Joints
Internal and
External
Corners
Openings
Fire Sealant
Jointing Face
Layer
3rd layer
openings
400mm
max
3rd layer
400mm
Butt Joints
2nd layer
openings
200mm
max
2nd layer
Screws or Double
Nails at 300mm max
2nd layer
200mm max
Butt joints
200mm min
from
openings
2nd layer
Openings
200mm
max
10-15mm
10-15mm
Non-re rated
plasterboard. Internal
Batten or channel lining required to maintain
FRL. Use approved re
rated penetration details
in internal lining.
Breathable
wall wrap
Skirting board
Breathable
wall wrap
Skirting board
Any external
cladding
Suitable ground
clearance
Suitable ground
clearance
CONSTRUCTION DETAILS
MultiShield
Breathable
wall wrap
Floor joist
Batten or channel
Floor bearer
Floor joist
Floor bearer
(sitting on posts)
Ant Cap
Damp proof
course
Any external
cladding
Suitable ground
clearance
Suitable ground
clearance
Non-re rated
plasterboard. Internal
lining required to maintain
FRL. Use approved re
rated penetration details
in internal lining.
MultiShield
213
MultiShield
Architectural
shape
CONSTRUCTION DETAILS
Non-re rated
plasterboard. Internal lining
required to maintain FRL.
Use approved re rated
penetration details in
internal lining.
Fix 10-15mm from
sheet bottom
MultiShield
Architectural
shape
10mm min gap.
Fire sealant
required to
maintain re
and acoustic
integrity
Batten or channel
7.5mm bre
cement with texture
coating.
Any external
cladding
Boundary joist
(Rimboard)
Breathable
wall wrap
Boundary joist
(Rimboard)
Breathable
wall wrap
MultiShield
Non-re rated
plasterboard. Internal
lining required to
maintain FRL. Use
approved re rated
penetration details
in internal lining.
External
window trim
Corrosion resistant
ashing
214
FireShield or
MultiShield
MultiShield
FireShield or
MultiShield
MultiShield
Batten or channel
Breathable
wall wrap
Breathable
wall wrap
Any external
cladding
Suitable ground
clearance
Corrosion resistant
ashing
Suitable ground
clearance
Batten or channel
MultiShield
FireShield or
MultiShield
Any external
cladding
MultiShield
FireShield or
MultiShield
CONSTRUCTION DETAILS
Corrosion resistant
ashing
Boundary joist
(Rimboard)
Breathable
wall wrap
Non-openable re window
with equivalent FRL to wall
system (example -/60/-)
External
window trim
215
FIRE RATED
EXTERNAL WALL TO ROOF ELEVATION
FIGURE 15 External Wall to Non-Combustible Eave Lining
CONSTRUCTION DETAILS
Rafter
Ceiling joist
Eave lining
(non-combustible)
Rafter
Ceiling joist
No eaves lining
216
FIRE RATED
Rafter
Ceiling joist
MultiShield
CONSTRUCTION DETAILS
Eave lining
(non-combustible)
217
FIRE RATED
EXTERNAL WALL TO PARAPET ROOF ELEVATION
Parapet capping
CONSTRUCTION DETAILS
Batten or channel
Rafter
MultiShield
Ceiling joist
Align battens/channel vertically
for cavity drainage
Breathable
wall wrap
Batten or channel
Rafter
MultiShield
Fire rated ceiling with
equivalent FRL as external wall
Align battens/channel vertically
for cavity drainage
Ceiling joist
Breathable
wall wrap
Fire sealant
Timber wall top plate
218
FIRE RATED
EXTERNAL WALL JUNCTIONS PLAN VIEW
Align battens/channel vertically
for cavity drainage
Overlap plasterboard
edges at corners
Any external cladding
Overlap plasterboard
edges at corners
Corrosion resistant
ashing
Breathable
wall wrap
Corrosion resistant
ashing
Batten or channel
Align battens/channel vertically
for cavity drainage
MultiShield
Overlap plasterboard
edges at corners
Overlap plasterboard
edges at corners
CONSTRUCTION DETAILS
Corrosion resistant
ashing
Breathable
wall wrap
Corner moulding
Additional studs
may be required
to x cladding
MultiShield
Corrosion resistant
ashing
7.5mm bre cement
with texture coating
FireShield
Non-re rated
plasterboard
FireShield
Sacrical solid timber blocking to maintain
re rating. Additional to structural timber.
Use 1x45mm or 2x35mm thick for FRL 60.
Use 2x45mm or 3x35mm thick for FRL 90.
Fill any gaps with re sealant to
maintain re and acoustic integrity.
Batten or
channel
Non-re rated
plasterboard
219
FIRE RATED
EXTERNAL WALL CONTROL JOINTS PLAN VIEW
Fire sealant depth same as
plasterboard thickness to maintain
re and acoustic integrity
Bond breaker tape
15mm
Breathable
wall wrap
MultiShield
Non-re rated
plasterboard
CONSTRUCTION DETAILS
Breathable
wall wrap
MultiShield
FireShield
MultiShield
FireShield or non-re
rated plasterboard
220