BOQ 1

Sr. No Description

1.1
1.2

2.1

Unit

Wiring for the following light points with 1.5 sq.mm PVC insulated copper conductor
1100 volts grade stranded flexible FRLS wires of approved make in concealed or surface
mounted 25 mm dia 2mm thick PVC Conduit including providing and fixing of 6 amps modular
type single pole rocker operated flush mounted switch of approved quality colour make &
design in 2 mm thick GI box and earthing of fixtures and the outlet box with 1.5 sq.mm
PVC insulated copper conductor stranded flexible "FRLS" wire.
Primary point controlled by one 6 amps switch length 8-9 Mtrs
Same as item no. 1 above but Secondary point. Length 5-6 Mtrs

No
No

Wiring for the twin control light points with 1.5 sq.mm PVC insulated copper conductor 1100
volts grade stranded flexible "FRLS" wires in concealed or surface
mounted 25 mm dia
2mm thick PVC conduit including providing and fixing 2 Nos. 6 amps 2 way modular type
rocker operated flush mounted switches of approved quality colour make & design in 2
mm thick GI box and
earthing of fixture and the outlet box with 1.5 Sq.mm PVC
insulated copper conductor stranded flexible "FRLS" wire.
Primary point controlled by 2 Nos. two way switches.

No

BOQ 2

Wiring for ceiling fan point with 1.5 sq.mm PVC insulated copper conductor 1100 volts
grade stranded flexible "FRLS" wires in concealed or surface mounted 25 mm dia 2mm thick
PVC conduits, including providing fan hook box, 6 amps switch and 300 watts electronic step
type fan regulator of approved make in GI box and earthing the fan and outlet box with 1.5
sq. mm. PVC insulated copper conductor stranded flexible FRLS wire.

No

Wiring for 250 volts single phase and neutral 16 amps 6 pin switched sockets with
safety shutter with 4 sq.mm PVC insulated copper conductor 1100 volts grade stranded
flexible FRLS wires in concealed or surface mounted 25 mm dia 2mm thick PVC conduit
including providing and fixing of 16 amps 3 pin switched sockets of approved make and
design in 2 mm thick GI box with grid plates and earthing the third pin of each socket outlet
with 2.5 Sq mm PVC insulated copper conductor stranded flexible FRLS wire (one socket
outlet shall be connected on one circuit).

No

Wiring for 250 volts single phase and neutral 6 amps switched socket outlet with safety
shutter with 2.5 sq.mm PVC insulated copper conductor 1100 volts grade stranded flexible
FRLS wires in concealed or surface mounted 25 mm dia PVC conduit including providing and
fixing of 6 amps 3 pin switch socket outlet of aprpoved make and design in 2 mm thick GI box
with grid plate and earthing of third pin of the socket with 2.5 Sq. mm PVC insulated copper
conductor stranded flexible FRLS wire

No

Wiring for 250 volts single phase and neutral 6 amps switched socket outlet on switch
board including providing and fixing of 6 amps 3 pin switch socket outlet of aprpoved make
and design in 2 mm thick GI box with grid plate and earthing of third pin of the socket with
2.5 Sq. mm PVC insulated copper conductor stranded flexible FRLS wire in concealed or
surface mounted 25mm dia & 2mm thick PVC conduit.

No

Wiring for Exhaust fan point with 1.5 sq. mm. insulated copper conductor 1100 volts grade
stranded flexible FRLS wires of approved make in concealed or surface mounted 25 mm dia 2
mm thick PVC Conduit including providing and fixing of 6 amps flush mounted switch at the
normal switch level in 2 mm thick GI box and ceiling rose near exhaust fan and earthing of
exhaust fan through the third pin of the socket outlet and GI box with 2.5 sq. mm. PVC
insulated copper conductor flexible FRLS wire.

No

Wiring for light point as in item No. A-1 above but controlled by SPMCB provided in the
DB. (Cost of MCB not to be included here).

8.1
8.2

Primary point controlled by one MCB.


Same as item no. .. above but Secondary point.

No
No

Providing and fixing of following PVC insulated copper conductor 1100 volt grade stranded
flexible FRLS wire in existing raceway including providing and fixing of PVC conduits concealed
or surface mounted making connections where ever required to complete the installation.

9.1

3 Nos. 1.5 sq.m (for phase Neutral & earthing) PVC


grade stranded flexible FRLS wires

insulated copper conductor 1100 volts

9.2

2 Nos. 4 sq.mm (For Phase + Neutral) +1 No. 2.5 (For Earthing) Sqmm PVC
conductor 1100 volts grade stranded FRLS wires

insulated copper

RM

RM

BOQ 3

10

Supply and fixing of 2 mm thick PVC Conduits of following sizes including cost of junction
boxes, bends, elbows, sockets, tees etc. laying in slab, cutting chasis and making good or
surface mounted including all fixing hardware.

10.1

20 mm dia 16 guage 2mm thick PVC

RM

10.2

25 mm dia 16 guage 2mm thick PVC

RM

10.3

32 mm dia 16 guage 2mm thick PVC

RM

11

Wiring for Push bell points with 1.5 sqmm PVC insulated copper conductor 1100 volts grade
stranded flexible FRLS wires in concealed or surfaced mounted 25mm dia 2 mm thick PVC
conduit including providing and fixing of electronic call bell (as per interior designer) with
control switch and earthing of GI box with 1.5 sqmm PVC insulated copper conductor stranded
flexible wire.

No

12

Video Door Phone Complete with suitable Cabling, Indoor unit which includes display screen,two
way communication, able to view of live video of outside situation,image and picture memory
with space of max. 32 images,and also able to unlock the electronic lock on recognizing the
visitor & Outdoor unit which includes loudspeaker which makes the users vioce audible to
visitor, camera to capture the image of visitor,infrared LED to ensure cleare vision during night
time,Call buttonto generate a bell sound inside the house and activate the camera,microphone
to capture voice of visitor.

No

13

Wiring for telephone points with 2 pair twisted pair cable in 2 mm thick PVC Conduits of
suitable sizes including cost of junction boxes, bends, elbows, sockets, tees etc. laying in slab,
cutting chasis and making good or surface mounted including all fixing hardware with RJ45
modular terminal, cover plate and metal box

No

14

Wiring for LAN points with CAT 6 cable in 2 mm thick PVC Conduits of suitable sizes including
cost of junction boxes, bends, elbows, sockets, tees etc. laying in slab, cutting chasis and
making good or surface mounted including all fixing hardware with LAN scoket modular
terminal, cover plate and metal box

No

15

Surface mounting energy saving tube light fitting of 1 x 28W similar to WIPRO WIF 20128 SG
(parking area)

No

15.1
15.2

Surface mounting energy saving tube light fitting of 1 x 28W similar to WIPRO WRF 80128 SG
(indoor)
Surface or recess mounted Fluorescent lighting fixture 2X18 W downlighter similar to Wipro GCP
23218

15.3

Surface mounted Fluorescent lighting fixture 1X11W CFL (TC-S) complete with
lamp & accessories similar to Wipro WRP21111

fluorescent

15.4

CFL Bulkhead 1x 9W CFL(TC-S) complete with lamp & all accessories similar to Wipro WKP
14109

No
No
No
No

BOQ 4

15.5

1200 mm Ceiling Fan complete with all fixing accessories.

No

15.6

400 mm Wall mounted fan complete with all fixing accessories.

No

16

Supply, Installation, Testing and commissioning of 6/12 WAY SPN Distribution Board with
MCBs
DB Compromising of Incomer as - 25 Amp DP ELMCB
Outgoing :
20A, SP, 10kA, MCB
16A, SP, 10kA, MCB
10A, SP, 10kA, MCB
6A, SP, 10kA, MCB

No