DESIGN OF SKEW BRIDGE

Name of the work:-Construction of High Level Bridge on the R/F


Yaganamilli to Komatilanka

Design Philosophy:-

The design of 5V-- 6.37m right span skew bridge with skew angle of 23 0 is carried as
per the procedure out lined below:Step1:The design discharge was fixed after arriving discharge based on the following methods:a.The Catchment area is plotted from the Topo sheet.Ryve's formula is used to arrive
at the discharge duly taking the coefficient as 8.5.
b.By Area-Velocity method using Manning's equation for arriving at the flow velocity
and area by considering actual cross-section of the stream.
Step2:a.Hydraulic particulars like HFL,OFL are fixed as per the local enquiry.
b.Bottom of deck level was fixed based on HFL and road formation levels on both sides.
The vertical clearence and afflux are also verified.
c.Ventway calculations are done for fixation of ventway.
d.Normal scour depth with reference to HFL was calculated using Lacey's equations
e.After arriving at the Maximum scour depth,bottom level of the foundation was fixed
below the maximum scour depth
Step3:After arriving at bottom of deck level,bottom of foundation level and required
ventway,the dimensions of the bridge are finalised.
The structural components are desined in the following manner:a.As per the recommendations of IRC 6:2010,two lanes of IRC class A live load or
one lane of IRC Class AA tracked or wheel loads,whichever produces severe effect
is considered.
b.Other loads and Load combinations are selected as per IRC 6:2010
c.Based on the soil test reports,type of foundation was selected.
d.The structural components like Abutments,piers,RCC Wing walls,raft foundation are
designed as per the guide lines given in relevent IRC codes.
e.The deck slab is proposed as per the MOST drawing Nos.BD 12-74&BD 13-74

f.The dirt wall is proposed as per the drawings given in Plate No.7.25 of
IRC:SP20-2002(Rural roads manual)
g.The pier cap is proposed as per the drawings given in Plate No.7.25 of
IRC:SP20-2002(Rural roads manual)

Design of Abutments for skew bridge


I)Design Parameters:Clear Right Span

6.00m

Deck slab length

7.322m

Width of the carriage way

7.50m

Length of abutment

8.15m

Thickness of deck slab as per MOST Dg.BD 12-74

0.540m

Thickness of wearing coat

0.075m

Height of hand rail(Vertical)

0.845m

Sectional area of hand rail (vertical)

0.220sqm

No.of hand rails per span(Verticals)

10Nos

Length of hand rail(Horizontal)

1.354m

Sectional area of hand rail (Horizontal)

0.020sqm

No.of hand rails per span(Horizontal)

16Nos

Thickness of dirt wall

0.30m

Sectional area of dirt wall

0.370sqm

Sectional area of kerb

0.130sqm

Thickness of raft

0.60m

Height of abutments

3.202m

Top width of abutments

0.700m

Bottom width of abutments

2.40m

Sectional area of abutment section

4.963sqm

Bank side batter of abutment

0.000m

Stream side batter of abutment

1.700m

Width of 1st footing

3.00m

Thickness of 1st footing

0.50m

Canal side offset of 1st footing wrt abutment

0.30m

Bank side offset of 1st footing wrt abutment

0.30m

Width of 2nd footing

3.30m

Thickness of 2nd footing

0.50m

Canal side offset of 2nd footing wrt abutment

0.60m

Bank side offset of 2nd footing wrt abutment

0.30m

Width of 3rd footing

3.60m

Thickness of 3rd footing

0.50m

Canal side offset of 3rd footing wrt abutment

0.90m

Bank side offset of 3rd footing wrt abutment

0.30m

(As per hydralic calculations)

Thickness of VRCC raft footing

0.60m

Offset of top footing along width

0.00m

Offset of 2nd footing along width

0.00m

Offset of 3rd footing along width

0.00m

Type of bearings

Unit weight of RCC (yrc)

25KN/cum

Unit weight of PCC (ypc)

24KN/cum

Density of back fill soil behind abutments (y)

18KN/Cum

Unit weight of water (yw)

10KN/Cum

Angle of shearing resistance of back fill material(Q)

30

Angle of face of wall supporting earth with horizontal(In


degrees)(in clock wise direction)(a)

90

Slope of back fill (b)

Angle of wall friction (q)

15

Height of surcharge considered (h3)

1.20m

Road crest level (RTL)

9.280m

Low bed level (LBL)

5.62m

High flood Level (HFL)


Bottom of foundation level (BFL)
Safe Bearing Capacity of the soil (SBC)

=
=
=

7.950m
3.30m
15.00t/sqm

Compressive strength of concrete for RCC Strip footing


(fck)

25.00N/sqmm

Yield strength of steel (fy)

415.00N/sqmm

Cover to reinforcement

50.00mm

No bearings proposed

II)General loading pattern:As per IRC:6---2010,the following loadings are to be considered on the bridge or slab
culvert:1.Dead load
2.Live load
3.Impact load
4.Wind load
5.Water current
6.Tractive,braking effort of vehicles&frictional resistance of bearings
7.Buoyancy
8.Earth pressure
9.Seismic force
10.Water pressure force

As per clause 202.3,the increase in permissible stresses is not permissible for the
above loading combination.

III)Loading on the slab culvert for design of abutments:1.Dead Load:-

i)Self wieght of the deck slab =

402.80KN

ii)Self wieght of dirtwall over abutment =

75.39KN

iii)Self weight of wearing coat =

55.95KN

iv)Self weight of kerb =

23.80KN

v)Self weight of hand rails(verticals) =

23.24KN

vi)Self weight of hand rails(horizontals) =

5.42KN

586.59KN
There is no need to consider snow load as per the climatic conditions
Self wieght of the abutments upto bottom most footing based on the preliminary
section assumed:iv)Self wieght of the abutment section =

970.76KN

v)Self wieght of top footing =

293.40KN

vi)Self wieght of 2nd footing =

322.74KN

vii)Self wieght of 3rd footing =

352.08KN

viii)Self wieght of 4th footing =

0.00KN

1938.98KN

ix)Calculation of eccentricity of self weight of abutment w.r.t base of abutment


S.No

Description Load in KN

Distance of centroid of load from toe of


abutment

Moment

Back
batter(W1)

2.4

Centre
portion(W2)

438.41784

2.05

898.76

Front
batter(W3)

532.36452

1.133

603.17

970.78236

1501.93

Location of resultant from toe of abutment =

1.55m

Eccentricity wrt centre of base of abutment =

0.350m

x)Calculation of eccentricity of self weight of abutment&1st footing w.r.t bottom of 1st footing
S.No

Description Load in KN

Back batter

Distance of centroid of load from toe of 1st


footing

Moment

2.7

Centre portion

438.41784

2.35

1030.28

Front batter

532.36452

1.433

762.88

1st footing

293.4

1.5

440.1

1264.18236

2233.26

Location of resultant from toe of abutment =

1.77m

Eccentricity wrt centre of 1st footing=

0.270m

xi)Calculation of eccentricity of self weight of abutment,1st&2nd footings w.r.t bottom of 2nd footing

S.No

Description Load in KN

Back batter

Distance of centroid of load from toe of 2nd


footing

Moment

Centre portion

438.41784

2.65

1161.81

Front batter

532.36452

1.733

922.59

1st footing

293.4

1.80

528.12

2nd footing

322.74

1.65

532.52

1586.92236

3145.04

Location of resultant from toe of abutment =

1.98m

Eccentricity =

0.330m

xii)Calculation of eccentricity of self weight of abutment,1st,2nd & 3rd footings w.r.t bottom of 3rd footing
S.No

1
2
3
4
5
6

Description Load in KN

Back batter
Centre portion
Front batter
1st footing
2nd footing
3rd footing

Distance of centroid of load from toe of 3rd


footing

0
438.41784
532.36452
293.4
322.74
352.08
1939.00236

Moment

3
2.65
1.733
1.80
1.65
1.80

0
1161.81
922.59
528.12
532.52
633.74
3778.78

Location of resultant from toe of abutment =

1.95m

Eccentricity =

0.150m

2.Live Load:As per clause 204.3 of IRC:6--2010,the bridges of carriage way width 7.5m shall be designed for IRC
loadings of one lane of 70R or two lanes of Class A.
GENERAL IRC Class-AA tracked vehicle loading Pattern

35t

35t
1200

35t

850

3600

GENERAL IRC Class-AA wheeled vehicle loading Pattern

300
300

3.75t

300

6.25t

300

700

6.25t
3.75t
1050
1200

3.75t
1050
1200

GENERAL IRC Class-A loading Pattern

6.8t

6.8t

3.00

3.00

6.8t

11.4t

3.00

6.8t

4.30

1.20

11.4t

3.20

2.7t

1.80

2.7t

1.10

The IRC Class AA Tracked loading as per the drawing is considered

Y
9071

7322
850

35t

35t

3600

1200

1200

23

Resultant live load:Eccentricity of live load w.r.t y-direction(Along the direction of travel of vehicles)
Taking moments of all the forces w.r.t y-axis
S.No

Wheel
Load/UDL in
KN

Distance from Y-axis

350

1.63m

568.75KNm

350

3.68m

1286.25KNm

700.000

Moment

1855.00KNm

Distance of centroid of forces from y-axis

= 2.650m

Eccentricity of live load w.r.t x-direction(At right angle to the travel of vehicles)
Taking moments of all the forces w.r.t x-axis
S.No

Load in KN

Distance from X-axis

Moment

350

3.54m

1239.00KNm

350

3.54m

1239.00KNm

700

2478.00KN

Distance of centroid of forces from x-axis

= 3.540m

Location of Resultant is as shown in the figure:-

Y
9071

7322

2650

3540

23

Reaction on the abutment =

x
469.44KN

The IRC Class AA wheeled loading as per the drawing is considered

Y
9071

7322

Y
9071

3.75t

6.25t

6.25t

3.75t

7322

300

1050 1200

6.25t

6.25t

3.75t

3.75t

700

300

23

Resultant live load:Eccentricity of live load w.r.t y-direction(Along the direction of travel of vehicles)
Taking moments of all the forces w.r.t y-axis
S.No

Wheel
Load/UDL in
KN

Distance from Y-axis

37.5

1.20m

45.00KNm

37.5

1.20m

45.00KNm

62.5

1.95m

121.88KNm

62.5

1.95m

121.88KNm

62.5

2.95m

184.38KNm

62.5

2.95m

184.38KNm

37.5

3.55m

133.13KNm

37.5

3.55m

133.13KNm

400.000
Distance of centroid of forces from y-axis

= 2.422m

Moment

968.75KNm

Eccentricity of live load w.r.t x-direction(At right angle to the travel of vehicles)
Taking moments of all the forces w.r.t x-axis
S.No

Load in KN

Distance from X-axis

Moment

37.5

2.921m

109.54KNm

62.5

2.921m

182.56KNm

62.5

2.921m

182.56KNm

37.5

2.921m

109.54KNm

37.5

1.721m

64.54KNm

62.5

1.721m

107.56KNm

62.5

1.721m

107.56KNm

37.5

1.721m

64.54KNm

400

928.40KN

Distance of centroid of forces from x-axis

= 2.321m

Location of Resultant is as shown in the figure:-

Y
9071

7322

2422

23

2321

2422

23

Reaction on the abutment =

2321

x
329.38KN

The details of wheel loads for IRC Class A live load ,each axle wise are as
given below:Axle load
(Tonnes)

Ground Contact Area


B(mm)

11.4
6.8
2.7

W(mm)

250
200
150

500
380
200

Placement of two lanes of IRC Class A loading as shown below:-

Y
9071

11.4t
1200

7322

11.4t

1200
4300

6.8t
23

Resultant live load:Eccentricity of live load w.r.t y-direction(Along the direction of travel of vehicles)
Taking moments of all the forces w.r.t y-axis

S.No

Wheel
Load/UDL in
KN

Distance from Y-axis

57

0.835m

47.60KNm

57

0.835m

47.60KNm

34

0.835m

28.39KNm

57

2.625m

149.63KNm

57

2.625m

149.63KNm

34

2.625m

89.25KNm

57

4.325m

246.53KNm

57

4.325m

246.53KNm

57

6.125m

349.13KNm

10

57

6.125m

349.13KNm

524.000

Moment

1703.38KNm

Distance of centroid of forces from y-axis

= 3.251m

Eccentricity of live load w.r.t x-direction(At right angle to the travel of vehicles)
Taking moments of all the forces w.r.t x-axis
S.No

Load in KN

Distance from X-axis

Moment

57

6.947m

395.98KNm

57

6.947m

395.98KNm

57

6.947m

395.98KNm

57

6.947m

395.98KNm

57

5.747m

327.58KNm

57

5.747m

327.58KNm

57

5.747m

327.58KNm

57

5.747m

327.58KNm

34

1.447m

49.20KNm

10

34

1.447m

49.20KNm

524

2992.63KN

Distance of centroid of forces from x-axis

= 5.711m

Location of Resultant is as shown in the figure:-

Y
9071

7322
3251

5711

23

Calculation of reactions on abutments:As per PCI bridge design code,apply correction factor for skew angle of bridge,as given below:The reaction at the obtuse corner of skew slab is to be multiplied with correction
factor

1.0+{[Ld/12]0.5 +(Tan/6S)}

Where L =
d=

Effective span
Depth of slab

for 600

S=

Width of slab

Hence correction factor =

1.585112003

Reaction due to loads Ra =

310.20KN

Reaction due to loads = Rb =

213.80KN

The critical reaction from the above loading patterns is

Hence,the critical reaction is Ra =

469.4KN

The corrected reaction at obtuse corner =

744.11KN

469.44KN

Assuming that the live load reaction acts at the centre of the contact area on the abutment,

215

185

515

1885

The eccentricty of the line of action of live load on top of 1st footing =
-----do------ on top of 2nd footing =
-----do------ on top of 3rd footing =
-----do------ on top of raft =

0.685m
0.835m
0.985m
0.985m

The eccentricity in the other direction need not be considered due to high section modulus in transverse
direction.

3.Impact of vehicles:As per Clause 208.3(a) of IRC:6--2010,impact allowance for the spans designed for class AA tracked vehicles,
is increment of live load by a percent of
Hence,the factor is

5+2.5*(25-10)/4 =

14.375%

0.14375

Further as per clause 208.7(a),(b)&(c) of IRC:6--2010,the above impact factor shall be only
50% for calculation of pressure on piers and abutments just below the level of bed block.There
is no need to increase the live load below 3m depth.
As such,the impact allowance for the top 3m of abutments will be

0.071875

For the remaining portion,impact need not be considered.


4.Wind load:Data:Bredth of the Bridge cross section 'b' =
Depth of the Bridge cross section 'd' =
b/d ratio =
Gust Factor 'G' =
Length of the bridge =
Height of the bridge in elevation =
Basic wind speed =
(From basic wind speed map of India)

8.15m
0.54m
15.0925926
2
6.74m
3.66m
50.00m/s

1)CALCULATION OF WIND FORCES ON SUPER STRUCTURE:A)Transverse Wind force:The drag coefficient for the deck slab bridges with b/d 10 is

=1.10

Hence,drag Coefficient for the bridge 'CD' =

=1.10

Area exposed to the wind A1 = Length of the bridgex(Ht.including ralings-Perforations)


Area of perforations =
Net exposed area 'A1' =
Hourly mean wind pressure ' Pz' for height upto 10m =
(Table 4 of IRC 6:2010)
The transverse wind force FT = PzXA1XGXCD =

3.22sqm
21.45sqm
1064.5N/sqm

50.23KN

B)Longitudinal Wind force:As per the clause 209.3.4. of IRC 6:2010,the longitudinal wind force FL shall be taken as 25% of the
transverse wind force,hence

FL =

12.56KN

C)Upward/Downward Wind force:The upward or downward windforce FV = PzxA3XGXCL


A3 is plan area of the bridge =

56.95sqm

CL is lift coefficient =
Hence FV =

0.75
90.94KN

2)CALCULATION OF WIND FORCES ON LIVE LOAD OVER THE ROAD SURFACE:As per the clause 209.3.2 of IRC 6:2010,the shall not be considered to be carrying
any live load when the wind speed at deck level exceeds 36m/s.
Hence,it is not necessary to consider the effect of wind on live load.

3)CALCULATION OF WIND FORCES ON SUBSTRUCTURE:The ratio of l/b =


The ratio of h/b =
Exposed area =

3.395833333
1.334166667
4.963sqm

The drag coefficient for abutment CD from the

0.8

table 5 of IRC 6:2010 =


The transverse wind force acting on the abutment only =

8.45KN

The location of this force from top of raft =

3.63m

Tranverse wind force transmitted to abutment from super structure =

50.23KN

The location of this force from top of raft =

6.24m

Taking moments of the above forces about top of raft,the location


of resultant from the top of raft =

5.86m

Hence,the final transverse wind force FT =

58.68KN

The location of the wind force from the top of RCC raft footing =

5.86m

5.Water current force:Water pressure considered on square ended abutments as per clause 210.2 of
IRC:6---2010 is
P = 52KV2 =

3.51 Kg/m2.

(where the value of 'K' is 1.5 for square ended abutments)

Hence,the water current force =

0.11KN

Point of action of water current force from the top of RCC raft footing =

2.70m

6.Tractive,braking effort of vehicles&frictional resistance of bearings:The breaking effect of vehicles shall be 20% of live load acting in longitudinal
direction at 1.2m above road surface as per the clause 211.2 of IRC:6--2010.

As no bearings are assumed in the present case,50% of the above longitudinal


force can be assumed to be transmitted to the supports of simply supported spans resting on
stiff foundation with no bearings as per clause 211.5.1.2 of IRC:6---2010

Hence,the longitudinal force due to braking,tractive or frictional resistance of


bearings transferred to abutments is
74.41KN

The location of the tractive force from the top of RCC raft footing =

6.82m

7.Buoyancy :As per clause 213.4 of IRC:6---2010,for abutments or piers of shallow depth,the
dead weight of the abutment shall be reduced by wieght of equal volume of water upto HFL.
The above reduction in self wieght will be considered assuming that the back fill
behind the abutment is scoured.
For the preliminary section assumed,the volume of abutment section is
i)Volume of abutment section =

40.45Cum

ii)Volume of top footing =

12.23Cum

iii)Volume of 2nd footing =

13.45Cum

iv)Volume of 3rd footing =

14.67Cum

v)Volume of 4th footing =

0.00Cum
80.79Cum

Reduction in self wieght =

8.Earth pressure :As per clause 214.1 of IRC:6---2010,the abutments are to be designed for a
surcharge equivalent to a back fill of hieght 1.20m behind the abutment.

807.91KN

The coefficient of active earth pressure exerted by the cohesion less back fill on
the abutment as per the Coulomb's theory is given by
'2
Ka =

Sin(a+Q)
sina

sin(a-q)

sin(Q+q)sin(Q-b)
sin(a+b)

Sin(a+Q) =
Sin(a-q) =
Sina =
Sin(Q+q) =
Sin(Q-b) =
Sin(a+b) =

SIN[3.14*(76.06+30)/180] =
SIN[3.14*(76.06-15)/180] =
SIN[3.14*(76.06)/180] =
SIN[3.14*(30+15)/180] =
SIN[3.14*(30-0)/180] =
SIN[3.14*(76.06+0)/180] =

0.961
0.875
0.97
0.707
0.5
0.97

From the above expression,


Ka =

0.3

The hieght of abutment above GL,as per the preliminary section assumed =
Hence,maximum pressure at the base of the wall

3.202m
Pa =

17.29KN/sqm

The pressure distribution along the height of the wall is as given below:Surcharge load =

6.48 KN/sqm

6.48

3.202

17.29

6.48

Area of the rectangular portion =


Area of the triangular portion =

20.75
27.68
48.43

Taking moments of the areas about the toe of the wall


S.No
1
2

Description

Area

Lever arm Moment

Rectangular
Triangular

20.75
27.68

1.601
33.22075
1.06733333 29.543786667

48.43

62.764536667

Height from the bottom of the wall =

1.30m

The active Earth pressure acts on the abutment as shown below:-

0.70

15
3.202m
1.30m
90

2.40
0
Total earth pressure acting on the abutment P =

394.71KN

Horizontal component of the earth pressure Ph =

381.27KN

Vertical component of the earth pressure Pv =

102.11KN

Eccentricity of vertical component of earth pressure =

1.20m

9.Siesmic force :As per clause 219.1.1(a) of IRC:6---2010 in all siesmic zones,the bridges and culverts of spans upto 10m need
not be designed for siesmic forces.As the span of the bridge is only 6.37m,it need not be designed for siesmic forces.

10.Water pressure force:The water pressure distribution on the abutment is as given below:-

HFL 7.95m

4.65

BFL 3.30m

46.50kn/sqm

Total horizontal water pressure force =

881.12KN

The above pressure acts at height of H/3 =

1.55m

IV)Check for stresses for abutments&footings:-

a)Load Envelope-I:-(The Canal is dry,back fill scoured with live load on span)
i)On top of RCC raft footing
The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical forces acting on the abutment (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about x- Eccentricty about yaxis(m)


axis(m)

Reaction due to dead load from super structure

586.59KN

0.00

0.00

Self wieght of abutment&footings

1939.00KN

0.150

0.000

Reaction due to live load with impact factor---(Wheel


loads)

851.08KN

-0.985

0.000

Upward wind load

-90.94

0.00

0.00

3285.73
Horizontal forces acting/transferred on the abutment (H) composes of the following components
S.No

Type of load

Intensity in KN Direction x or y

Location(Ht.from the
section considered).
(m)

Wind load

58.68KN

x-Direction

5.86

Tractive,Braking&Frictional resistance of bearings

74.41KN

y-Direction

6.82

Check for stresses:About x-axis:Breadth of 3rd footing b =

8.15m

Depth of 3rd footing d =

3.60m

Area of the footing = A =

29.34 m2

Section modulus of bottom footing


about x-axis --Zx =

(1/6)bd2 =

17.60 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2
i.e, 4000KN/sqm

For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
5

Type of load

Intensity in KN Eccentricity/Lever
(P)
arm

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Tractive,Braking&Frictional resistance of bearings

586.59KN
1939.00KN
851.08KN
-90.94KN
74.41KN

Stress at heel
P/A(1+6e/d)

0.00
0.15
-0.985
0.00

19.99
82.61
-18.61
-3.10

6.82

-28.83
52.06

S.No

1
2
3
4
5

Type of load

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Tractive,Braking&Frictional resistance of bearings

Stress at toe
P/A(1+6e/d)

586.59KN
1939.00KN
851.08KN
-90.94KN

0.00
-0.15
0.985
0.00

19.99
58.79
50.04
-3.1

74.41KN

6.82

28.83
154.55

Stress at heel =

P/A(1+6e/d)+M/Z =

52.06 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at toe =

P/A(1+6e/d)+M/Z =

154.55 KN/Sqm<4000KN/sqm

Hence safe.

TOE
U/S

3600

D/S

HEEL
8150

About y-axis:-

Breadth of 3rd footing b =

3.60m

Depth of 3rd footing d =

8.15m

Area of the footing = A =

29.34 m2

Section modulus of bottom footing about =


y-axis--Zy =

(1/6)bd2 =

39.85 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
5

Type of load

Intensity in KN Eccentricity/Lever
(P)
arm

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Wind load

Stress at upstream
edge
P/A(1+6e/d)

586.59KN
1939.00KN
851.08KN
-90.94KN

0.00
0.00
0.000
0.00

19.99
66.09
29.01
-3.1

58.68KN

5.86

-8.63
103.36

S.No

1
2
3
4
5

Type of load

Intensity in KN Eccentricity/Lever
(P)
arm

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Wind load

Stress at up stream side


edge =

P/A(1+6e/d)+M/Z =

Stress at D/S edge


P/A(1+6e/d)

586.59KN
1939.00KN
851.08KN
-90.94KN

0.00
0.00
0.000
0.00

19.99
66.09
29.01
-3.1

58.68KN

5.86

8.63
120.62

103.36 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at down stream side
edge =

P/A(1+6e/d)+M/Z =
Hence safe.

ii)On top of 3rd footing


The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles

120.62 KN/Sqm<4000KN/sqm

b)y-Direction-----In the direction of movement of vehicles


Vertical load acting on the abutment (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about x- Eccentricty about yaxis(m)


axis(m)

Reaction due to dead load from super structure

586.59KN

0.00

0.00

Self wieght of abutment&footings

1586.92KN

0.330

0.000

Reaction due to live load with impact factor

851.08KN

-0.985

0.000

Upward wind load

-90.94

0.00

0.00

Horizontal load acting/transferred on the abutment (H) composes of the following components
S.No

Type of load

Intensity in KN Direction x or y

Location(Ht.from the
section considered).
(m)

Wind load

58.68KN

x-Direction

5.36

Tractive,Braking&Frictional resistance of bearings

74.41KN

y-Direction

6.32

Check for stresses:About x-axis:Breadth of 2nd footing b =


Depth of 2nd footing d =
Area of the footing = A =
Section modulus of Ist footing about
x-axis--Zx =

8.15m
3.30m
26.895 m2
(1/6)bd2 =

14.79 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
5

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Tractive,Braking&Frictional resistance of bearings

Intensity in KN Eccentricity/Lever
(P)
arm

586.59KN
1586.92KN
851.08KN
-90.94KN
74.41KN

Stress at heel
P/A(1+6e/d)

0.00
0.33
-0.985
0.00

21.81
94.41
-25.03
-3.38

6.32

-31.79
56.02

S.No

1
2
3
4
5

Type of load

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Tractive,Braking&Frictional resistance of bearings

Stress at toe
P/A(1+6e/b)

586.59KN
1586.92KN
851.08KN
-90.94KN

0.00
-0.33
0.985
0.00

21.81
23.6
88.32
-3.38

74.41KN

6.32

31.79
162.14

Stress at heel =

P/A(1+6e/d)+M/Z =

56.02 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at toe =

P/A(1+6e/d)+M/Z =

162.14 KN/Sqm<4000KN/sqm

Hence safe.

TOE

U/S

3300

D/S

HEEL
8150

About y-axis:Breadth of 1st footing b =


Depth of 1st footing d =
Area of the footing = A =
Section modulus of Ist footing about
y-axis--Zy =

3.30m
8.15m
26.895 m2
(1/6)bd2 =

36.53 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

Type of load

Intensity in KN Eccentricity/Lever
(P)
arm

Stress at upstream
edge
P/A(1+6e/d)

1
2
3
4
5

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Wind load

586.59KN
1586.92KN
851.08KN
-90.94KN

0.00
0.00
0.000
0.00

21.81
59
31.64
-3.38

58.68KN

5.36

-8.61
100.46

S.No

1
2
3
4
5

Type of load

Intensity in KN Eccentricity/Lever
(P)
arm

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Wind load

Stress at up stream side


edge =

P/A(1+6e/d)+M/Z =

Stress at D/S edge


P/A(1+6e/d)

586.59KN
1586.92KN
851.08KN
-90.94KN

0.00
0.00
0.000
0.00

21.81
59
31.64
-3.38

58.68KN

5.36

8.61
117.68

100.46 KN/Sqm>-2000KN/sqm.

Hence safe.

Stress at down stream side


edge =

P/A(1+6e/d)+M/Z =

117.68 KN/Sqm<4000KN/sqm

Hence safe.

i)On top of 2nd footing


The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the abutment (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about x- Eccentricty about yaxis(m)


axis(m)

Reaction due to dead load from super structure

586.59KN

0.00

0.00

Self wieght of abutment&cut waters

1264.18KN

0.270

0.000

Reaction due to live load with impact factor

851.08KN

-0.985

0.000

Upward wind load

-90.94

0.00

0.00

Horizontal load acting/transferred on the abutment (H) composes of the following components

S.No

Type of load

Intensity in KN Direction x or y

Location(Ht.from the
section considered).
(m)

Wind load

58.68KN

x-Direction

4.86

Tractive,Braking&Frictional resistance of bearings

74.41KN

y-Direction

5.82

Check for stresses:About x-axis:Breadth of 1st footing b =


Depth of 1st footing d =
Area of the footing = A =

8.15m
3.00m
24.45 m2

Section modulus of base of abutment


about x-axis--Zx =

(1/6)bd2 =

12.23 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
5

Type of load

Intensity in KN Eccentricity/Lever
(P)
arm

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Tractive,Braking&Frictional resistance of bearings

586.59KN
1264.18KN
851.08KN
-90.94KN
74.41KN

Stress at heel
P/A(1+6e/d)

0.00
0.27
-0.835
0.00

23.99
79.63
-23.32
-3.72

5.82

-35.43
41.15

S.No

1
2
3
4
5

Type of load

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Tractive,Braking&Frictional resistance of bearings

Stress at toe
P/A(1+6e/d)

586.59KN
1264.18KN
851.08KN
-90.94KN

0.00
-0.27
0.985
0.00

23.99
23.78
103.38
-3.72

74.41KN

5.82

35.43
182.86

Stress at heel =

P/A(1+6e/d)+M/Z =

Hence safe.

41.15 KN/Sqm>-2000KN/sqm.

Stress at toe =

P/A(1+6e/d)+M/Z =

182.86 KN/Sqm<4000KN/sqm

Hence safe.

TOE

U/S

3000

D/S

HEEL
8150

About y-axis:Breadth of 1st footing b =


Depth of 1st footing d =
Area of the footing = A =
Section modulus of base of abutment
about y-axis--Zy =

3.00m
8.15m
24.45 m2
(1/6)bd2 =

33.21 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2

i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
5

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Wind load

Intensity in KN Eccentricity/Lever
(P)
arm

Stress at upstream
edge
P/A(1+6e/d)

586.59KN
1264.18KN
851.08KN
-90.94KN

0.00
0.00
0.000
0.00

23.99
51.7
34.81
-3.72

58.68KN

4.86

-8.59
98.19

S.No

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)

Intensity in KN Eccentricity/Lever
(P)
arm

Stress at D/S edge


P/A(1+6e/d)

1
2
3
4
5

Reaction due to dead load from super structure


Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Wind load

Stress at up stream side


edge =

P/A(1+6e/d)+M/Z =

586.59KN
1264.18KN
851.08KN
-90.94KN

0.00
0.00
0.000
0.00

23.99
51.7
34.81
-3.72

58.68KN

4.86

8.59
115.37

98.19 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at down stream side
edge =

P/A(1+6e/d)+M/Z =

115.37 KN/Sqm<4000KN/sqm

Hence safe.
i)On top of 1st footing
The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the abutment (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about x- Eccentricty about yaxis(m)


axis(m)

1
2
3

Reaction due to dead load from super structure


Self wieght of abutment&footings
Reaction due to live load with impact factor

Upward wind load

586.59KN
970.78KN
851.08KN

0.00
0.350
-0.685

0.00
0.000
0.000

-90.94

0.00

0.00

Horizontal load acting/transferred on the abutment (H) composes of the following components
S.No

1
2

Type of load

Intensity in KN Direction x or y

Wind load
Tractive,Braking&Frictional resistance of bearings

58.68KN
74.41KN

x-Direction
y-Direction

Check for stresses:About x-axis:Breadth of abutment b =


Depth of abutment d =
Area of the footing = A =
Section modulus of base of abutment
about x-axis--Zx =

8.15m
2.40m
19.56 m2
(1/6)bd2 =

7.82 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2

Location(Ht.from the
section considered).
(m)
4.36
5.32

i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
5

Type of load

Intensity in KN Eccentricity/Lever
(P)
arm

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Tractive,Braking&Frictional resistance of bearings

Stress at heel
P/A(1+6e/d)

586.59KN
970.78KN
851.08KN
-90.94KN

0.00
0.350
-0.685
0.00

29.99
93.06
-31
-4.65

74.41KN

5.32

-50.6
36.80

S.No

1
2
3
4
5

Type of load

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Tractive,Braking&Frictional resistance of bearings

Stress at toe
P/A(1+6e/d)

586.59KN
970.78KN
851.08KN
-90.94KN

0.00
-0.35
0.685
0.00

29.99
6.2
118.02
-4.65

74.41KN

5.32

50.6
200.16

Stress at heel =

P/A(1+6e/d)+M/Z =

36.8 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at toe =

P/A(1+6e/d)+M/Z =

200.16 KN/Sqm<4000KN/sqm

Hence safe.

U/S

TOE

2400

D/S

HEEL

8150

HEEL

8150

About y-axis:Breadth of abutment b =


Depth of abutment d =
Area of the footing = A =

2.40m
8.15m
19.56 m2

Section modulus of base of abutment


about y-axis--Zy =

(1/6)bd2 =

26.57 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2

i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
5

Type of load

Intensity in KN Eccentricity/Lever
(P)
arm

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Wind load

Stress at upstream
edge
P/A(1+6e/d)

586.59KN
970.78KN
851.08KN
-90.94KN

0.00
0.00
0.000
0.00

29.99
49.63
43.51
-4.65

58.68KN

4.36

-9.63
108.85

S.No

1
2
3
4
5

Type of load

Intensity in KN Eccentricity/Lever
(P)
arm

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of abutment&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Wind load

Stress at up stream side


edge =

P/A(1+6e/d)+M/Z =

Stress at D/S edge


P/A(1+6e/d)

586.59KN
970.78KN
851.08KN
-90.94KN

0.00
0.00
0.000
0.00

29.99
49.63
43.51
-4.65

58.68KN

4.36

9.63
128.11

108.85 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at down stream side
edge =

P/A(1+6e/d)+M/Z =

128.11 KN/Sqm<4000KN/sqm

Hence safe.
b)Load Envelope-II:-(The Canal is full,back fill intact with no live load on span)

i)On top of RCC raft footing


The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the abutment (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about x- Eccentricty about yaxis(m)


axis(m)

Reaction due to dead load from super structure

586.59KN

0.00

0.00

Self wieght of abutment&cut waters

1939.00KN

Reduction in self weight due to buoyancy

-807.91KN

Net self weight

1131.09KN

0.150

0.000

Vertical component of earth pressure

102.11KN

1.200

0.000

Upward wind force

-90.94KN

0.000

0.000

Horizontal load acting/transferred on the abutment (H) composes of the following components
S.No

Type of load

Intensity in KN Direction x or y

Location(Ht.from the
section considered).
(m)

Wind load

58.68KN

x-Direction

5.86

Tractive,Braking&Frictional resistance of bearings

0.00KN

y-Direction

0.00

Water current force

0.11KN

x-Direction

2.70

Horizontal load due to earth pressure

381.27KN

y-Direction

2.80

Water pressure force

881.12KN

y-Direction

1.55

Check for stresses:About x-axis:Breadth of bottom footing b =


Depth of bottom footing d =
Area of the footing = A =
Section modulus of bottom footing
about x-axis --Zx =

8.15m
3.60m
29.34 m2
(1/6)bd2 =

17.60 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

Type of load

Intensity in KN Eccentricity/Lever
(P)
arm

Stress at heel
P/A(1+6e/d)

1
2
3
4
4
5

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings
Vertical component of Earth pressure
Upward wind force
Horizontal loads:- (Stress = M/Z)
Horizontal load due to earth pressure
Water pressure force

S.No

1
2
3
4
4
5

Type of load

0.00
0.15
1.20
0.00

19.99
48.19
10.44
-3.1

381.27KN
881.12KN

2.80
1.55

-60.56
77.6
92.54

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings
Vertical component of Earth pressure
Upward wind force
Horizontal loads:- (Stress = M/Z)
Horizontal load due to earth pressure
Water pressure force

Stress at heel =

586.59KN
1131.09KN
102.11KN
-90.94KN

P/A(1+6e/b)+M/Z =

Stress at toe
P/A(1+6e/d)

586.59KN
1131.09KN
102.11KN
-90.94KN

0.00
-0.15
-1.20
0.00

19.99
28.91
-3.48
-3.1

381.27KN
881.12KN

2.80
1.55

60.56
-77.6
25.3

92.54 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at toe =

P/A(1+6e/b)+M/Z =

25.3 KN/Sqm<4000KN/sqm

Hence safe.

About y-axis:Breadth of bottom footing b =


Depth of bottom footing d =
Area of the footing = A =
Section modulus of bottom footing
about y-axis --Zy =

3.60m
8.15m
29.34 m2
(1/6)bd2 =

39.85 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings

Intensity in KN Eccentricity/Lever
(P)
arm

586.59KN
1131.09KN

0.00
0.00

Stress at U/S Edge


P/A(1+6e/d)

19.99
38.55

3
4
4
5

Vertical component of Earth pressure


Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

S.No

1
2
3
4
4
5

Type of load

0.00
0.00

3.48
-3.1

58.68KN
0.11KN

5.86
2.70

-8.63
0.0
50.28

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings
Vertical component of Earth pressure
Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

Stress at up stream side


edge =

102.11KN
-90.94KN

P/A(1+6e/d)+M/Z =

Stress at D/S edge


P/A(1+6e/d)

586.59KN
1131.09KN
102.11KN
-90.94KN

0.00
0.00
0.00
0.00

19.99
38.55
3.48
-3.1

58.68KN
0.11KN

5.86
2.70

8.63
0.0
67.56

50.28 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at down stream side
edge =

P/A(1+6e/d)+M/Z =

67.56 KN/Sqm<4000KN/sqm

Hence safe.

ii)On top of 3rd footing


The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the abutment (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about x- Eccentricty about yaxis(m)


axis(m)

Reaction due to dead load from super structure

586.59KN

0.00

0.00

Self wieght of abutment&footings

1586.92KN

Reduction in self weight due to buoyancy

-661.22KN

Net self weight

925.70KN

0.330

0.000

Vertical component of earth pressure

102.11KN

1.200

0.000

Upward wind force

-90.94KN

0.000

0.000

Horizontal load acting/transferred on the abutment (H) composes of the following components

S.No

Type of load

Intensity in KN Direction x or y

Location(Ht.from the
section considered).
(m)

Wind load

58.68KN

x-Direction

5.36

Tractive,Braking&Frictional resistance of bearings

0.00KN

y-Direction

0.00

Water current force

0.11KN

x-Direction

2.20

Horizontal load due to earth pressure

381.27KN

y-Direction

2.30

Water pressure force

881.12KN

y-Direction

1.05

Check for stresses:About x-axis:Breadth of 2nd footing b =


Depth of 2nd footing d =
Area of the footing = A =

8.15m
3.30m
26.895 m2

Section modulus of bottom footing


about x-axis --Zx =

(1/6)bd2 =

14.79 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
4
5

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings
Vertical component of Earth pressure
Upward wind force
Horizontal loads:- (Stress = M/Z)
Horizontal load due to earth pressure
Water pressure force

S.No

1
2
3
4
4
5

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings
Vertical component of Earth pressure
Upward wind force
Horizontal loads:- (Stress = M/Z)
Horizontal load due to earth pressure
Water pressure force

Stress at heel =

P/A(1+6e/d)+M/Z =

Intensity in KN Eccentricity/Lever
(P)
arm

Stress at heel
P/A(1+6e/d)

586.59KN
925.70KN
102.11KN
-90.94KN

0.00
0.33
1.20
0.00

21.81
55.07
12.08
-3.38

381.27KN
881.12KN

2.30
1.05

-59.18
62.5
88.94

Intensity in KN Eccentricity
(P)

Stress at toe
P/A(1+6e/d)

586.59KN
925.70KN
102.11KN
-90.94KN

0.00
-0.33
-1.20
0.00

21.81
13.77
-4.49
-3.38

381.27KN
881.12KN

2.30
1.05

59.18
-62.5
24.35

88.94 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at toe =

P/A(1+6e/d)+M/Z =

24.35 KN/Sqm<4000KN/sqm

Hence safe.

About y-axis:Breadth of 1st footing b =


Depth of 1st footing d =
Area of the footing = A =

3.30m
8.15m
26.895 m2

Section modulus of bottom footing


about y-axis --Zy =

(1/6)bd2 =

36.53 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
4
5

S.No

1
2
3
4
4
5

Type of load

Intensity in KN Eccentricity/Lever
(P)
arm

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings
Vertical component of Earth pressure
Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

Type of load

Stress at up stream side


edge =

586.59KN
925.70KN
102.11KN
-90.94KN

0.00
0.00
0.00
0.00

21.81
34.42
3.8
-3.38

58.68KN
0.11KN

5.36
2.20

-8.61
0.0
48.03

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings
Vertical component of Earth pressure
Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

P/A(1+6e/d)+M/Z =

Hence safe.

Stress at U/S Edge


P/A(1+6e/d)

Stress at D/S edge


P/A(1+6e/d)

586.59KN
925.70KN
102.11KN
-90.94KN

0.00
0.00
0.00
0.00

21.81
34.42
3.8
-3.38

58.68KN
0.11KN

5.36
2.20

8.61
0.0
65.27

48.03 KN/Sqm>-2000KN/sqm.

Stress at down stream side


edge =

P/A(1+6e/d)+M/Z =

65.27 KN/Sqm<4000KN/sqm

Hence safe.

iii)On top of 2nd footing


The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the abutment (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about x- Eccentricty about yaxis(m)


axis(m)

Reaction due to dead load from super structure

586.59KN

0.00

0.00

Self wieght of abutment&cut waters

1264.18KN

Reduction in self weight due to buoyancy

-526.74KN

Net self weight

737.44KN

0.270

0.000

Vertical component of earth pressure

102.11KN

1.200

0.000

Upward wind force

-90.94KN

0.000

0.000

Horizontal load acting/transferred on the abutment (H) composes of the following components
S.No

Type of load

Intensity in KN Direction x or y

Location(Ht.from the
section considered).
(m)

Wind load

58.68KN

x-Direction

4.86

Tractive,Braking&Frictional resistance of bearings

0.00KN

y-Direction

0.00

Water current force

0.11KN

x-Direction

1.70

Horizontal load due to earth pressure

381.27KN

y-Direction

1.80

Water pressure force

881.12KN

y-Direction

0.55

Check for stresses:About x-axis:Breadth of 1st footing b =


Depth of 1st footing d =
Area of the footing = A =
Section modulus of bottom footing
about x-axis --Zx =

8.15m
3.00m
24.45 m2
(1/6)bd2 =

12.23 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2
i.e, 4000KN/sqm

For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
4
5

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings
Vertical component of Earth pressure
Upward wind force
Horizontal loads:- (Stress = M/Z)
Horizontal load due to earth pressure
Water pressure force

S.No

1
2
3
4
4
5

Intensity in KN Eccentricity/Lever
(P)
arm

Type of load

Stress at heel =

586.59KN
737.44KN
102.11KN
-90.94KN

0.00
0.27
1.20
0.00

23.99
46.45
14.2
-3.72

381.27KN
881.12KN

1.80
0.55

-56.01
39.6
64.55

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings
Vertical component of Earth pressure
Upward wind force
Horizontal loads:- (Stress = M/Z)
Horizontal load due to earth pressure
Water pressure force

P/A(1+6e/d)+M/Z =

Stress at heel
P/A(1+6e/d)

Stress at toe
P/A(1+6e/d)

586.59KN
737.44KN
102.11KN
-90.94KN

0.00
-0.27
-1.20
0.00

23.99
13.87
-5.85
-3.72

381.27KN
881.12KN

1.80
0.55

56.01
-39.6
44.66

64.55 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at toe =

P/A(1+6e/d)+M/Z =

44.66 KN/Sqm<4000KN/sqm

Hence safe.

About y-axis:Breadth of 1st footing b =


Depth of 1st footing d =
Area of the footing = A =
Section modulus of bottom footing
about y-axis --Zy =

3.00m
8.15m
24.45 m2
(1/6)bd2 =

33.21 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm

S.No

1
2
3
4
4
5

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings
Vertical component of Earth pressure
Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

S.No

1
2
3
4
4
5

Intensity in KN Eccentricity/Lever
(P)
arm

Type of load

Stress at up stream side


edge =

586.59KN
737.44KN
102.11KN
-90.94KN

0.00
0.00
0.00
0.00

23.99
30.16
4.18
-3.72

58.68KN
0.11KN

4.86
1.70

-8.59
0.0
46.01

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings
Vertical component of Earth pressure
Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

P/A(1+6e/d)+M/Z =

Stress at U/S Edge


P/A(1+6e/d)

Stress at D/S edge


P/A(1+6e/d)

586.59KN
737.44KN
102.11KN
-90.94KN

0.00
0.00
0.00
0.00

23.99
30.16
4.18
-3.72

58.68KN
0.11KN

4.86
1.70

8.59
0.0
63.21

46.01 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at down stream side
edge =

P/A(1+6e/d)+M/Z =

63.21 KN/Sqm<4000KN/sqm

Hence safe.
iii)On top of 1st footing
The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the abutment (P) composes of the following components
S.No

2
3
4

Type of load

Reaction due to dead load from super structure


Self wieght of abutment&cut waters
Reduction in self weight due to buoyancy
Net self weight
Vertical component of earth pressure
Upward wind force

Intensity in KN Eccentricty about x- Eccentricty about yaxis(m)


axis(m)
586.59KN
1264.18KN
-526.74KN
737.44KN
102.11KN
-90.94KN

0.00

0.00

0.270
1.200
0.000

0.000
0.000
0.000

Horizontal load acting/transferred on the abutment (H) composes of the following components

S.No

1
2
3
4
5

Type of load

Intensity in KN Direction x or y

Wind load
Tractive,Braking&Frictional resistance of bearings
Water current force
Horizontal load due to earth pressure
Water pressure force

58.68KN
0.00KN
0.11KN
381.27KN
881.12KN

Location(Ht.from the
section considered).
(m)

x-Direction
y-Direction
x-Direction
y-Direction
y-Direction

4.36
0.00
1.20
1.30
0.05

Check for stresses:About x-axis:Breadth of abutment b =


Depth of abutment d =
Area of the footing = A =

8.15m
2.40m
19.56 m2

Section modulus of bottom footing


about x-axis --Zx =

(1/6)bd2 =

7.82 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
4
5

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings
Vertical component of Earth pressure
Upward wind force
Horizontal loads:- (Stress = M/Z)
Horizontal load due to earth pressure
Water pressure force

S.No

1
2
3
4
4
5

Intensity in KN Eccentricity/Lever
(P)
arm

Type of load

Stress at heel =

586.59KN
737.44KN
102.11KN
-90.94KN

0.00
0.27
1.20
0.00

29.99
63.15
20.88
-4.65

381.27KN
881.12KN

1.30
0.05

-63.15
5.6
51.85

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings
Vertical component of Earth pressure
Upward wind force
Horizontal loads:- (Stress = M/Z)
Horizontal load due to earth pressure
Water pressure force

P/A(1+6e/d)+M/Z =

Hence safe.

Stress at heel
P/A(1+6e/d)

Stress at toe
P/A(1+6e/d)

586.59KN
737.44KN
102.11KN
-90.94KN

0.00
-0.27
-1.20
0.00

29.99
12.25
-10.44
-4.65

381.27KN
881.12KN

1.30
0.05

63.15
-5.6
84.67

51.85 KN/Sqm>-2000KN/sqm.

Stress at toe =

P/A(1+6e/d)+M/Z =

84.67 KN/Sqm<4000KN/sqm

Hence safe.

About y-axis:Breadth of abutment b =


Depth of abutment d =
Area of the footing = A =

2.40m
8.15m
19.56 m2

Section modulus of bottom footing


about y-axis --Zy =

(1/6)bd2 =

26.57 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
4
5

S.No

1
2
3
4
4
5

Type of load

Intensity in KN Eccentricity/Lever
(P)
arm

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings
Vertical component of Earth pressure
Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

Type of load

Stress at up stream side


edge =

586.59KN
737.44KN
102.11KN
-90.94KN

0.00
0.00
0.00
0.00

29.99
37.7
5.22
-4.65

58.68KN
0.11KN

4.36
1.20

-9.63
0.0
58.63

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of abutment&footings
Vertical component of Earth pressure
Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

P/A(1+6e/d)+M/Z =

Stress at U/S Edge


P/A(1+6e/d)

Stress at D/S edge


P/A(1+6e/d)

586.59KN
737.44KN
102.11KN
-90.94KN

0.00
0.00
0.00
0.00

29.99
37.7
5.22
-4.65

58.68KN
0.11KN

4.36
1.20

9.63
0.0
77.89

58.63 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at down stream side
edge of abutment =

P/A(1+6e/d)+M/Z =

77.89 KN/Sqm<4000KN/sqm

Hence safe.

V)Check for stability of abutments:a)Load Envelope-III:-(The Canal is dry,back fill intact with live load on span)
The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the abutment (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about x- Eccentricty about yaxis(m)


axis(m)

Reaction due to dead load from super structure

586.59KN

0.00

0.00

Self wieght of abutments

970.76KN

0.350

0.000

Reaction due to live load with impact factor

851.08KN

-0.685

0.000

Vertical component of Active Earth pressure

102.11KN

1.200

0.00

Upward wind force

-90.94KN

0.000

0.00

2419.59KN

Horizontal load acting/transferred on the abutment (H) composes of the following components
S.No

Type of load

Intensity in KN Direction x or y

Location(Ht.from the
section considered).
(m)

Wind load

58.68KN

x-Direction

4.36

Tractive,Braking&Frictional resistance of bearings

74.41KN

y-Direction

5.32

Horizontal Active Earth pressure force

381.27KN

y-Direction

1.30

514.37KN
Check for stability against over turning:Taking moments of all the overturning forces about toe of the abutment wrt x-axis,
Moment due to tractive,braking&frictional resistance of bearings =

395.87Kn-m

Moment due to active earth pressure force =

494.12Kn-m

Total overturning moment =

889.99Kn-m

Taking moments of all the restoring forces about toe of the abutment wrt x-axis,,
Moment due to self weight of abutment =

1504.68Kn-m

Moment due to live load reaction on abutment =

438.31Kn-m

Moment due to vertical component of active earth pressure =

245.06Kn-m

Total Restoring moment =

Factor of safety =

2.45850446

2188.04Kn-m

> 2.0
Hence safe
(As per clause 706.3.4 of IRC:78-2000)

Check for stability against sliding:Total vertical load acting on the base of the abutment Vb =

2419.59KN

Total sliding force,ie,horizontal load on the abutment Hb =

514.37KN

Coefficient of friction between concrete surfaces =


Factor of safety against sliding Fs =

0.80

3.76322865 > 1.5


Hence safe
(As per clause 706.3.4 of IRC:78-2000)

b)Load Envelope-II:-(The Canal is running upto HFL with no live load on span)
The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the abutment (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about x- Eccentricty about yaxis(m)


axis(m)

Reaction due to dead load from super structure

586.59KN

0.00

0.00

Self wieght of abutments

970.76KN

Reduction in self weight due to buoyancy

-404.50KN

Net self wieght

566.26KN

0.350

0.000

Vertical component of Active Earth pressure

102.11

1.200

0.00

Upward wind force

0.00

0.00

-90.94KN

Horizontal load acting/transferred on the abutment (H) composes of the following components
S.No

Type of load

Intensity in KN Direction x or y

Location(Ht.from the
section considered).
(m)

Wind load

58.68KN

x-Direction

4.36

Tractive,Braking&Frictional resistance of bearings

0.00KN

y-Direction

0.00

Active Earth pressure force

y-Direction

1.30

381.27KN

Force due to water pressure

881.12KN

y-Direction

0.05

Check for stability against over turning:Taking moments of all the overturning forces about toe of the abutment wrt x-axis,
Moment due to tractive,braking&frictional resistance of bearings =
Moment due to active earth pressure force =

0.00Kn-m
494.12Kn-m

Total overturning moment =

494.12Kn-m

Taking moments of all the restoring forces about toe of the abutment wrt x-axis,
Moment due to self weight of abutment =

877.70Kn-m

Moment due to water pressure force on the abutment =

44.06Kn-m

Moment due to vertical component of active earth pressure =

245.06Kn-m

Total Restoring moment =

Factor of safety =

2.36140264

1166.82Kn-m

> 2.0
Hence safe
(As per clause 706.3.4 of IRC:78-2000)

Check for stability against sliding:Total vertical load acting on the base of the abutment Vb =

1458.54KN

Total sliding force,ie,horizontal load on the abutment Hb =

381.27KN

Coefficient of friction between concrete surfaces =


Factor of safety against sliding Fs =

3.06035913 > 1.5


Hence safe
(As per clause 706.3.4 of IRC:78-2000)

0.80

Design of pier for skew bridge


I)Design Parameters:Clear Right Span

6.00m

Deck slab length

7.387m

Width of the carriage way

7.50m

Length of pier

8.15m

Thickness of deck slab as per MOST Dg.BD 12-74

0.540m

Thickness of wearing coat

0.075m

Height of hand rail(Vertical)

0.845m

Sectional area of hand rail (vertical)

0.220sqm

No.of hand rails per span(Verticals)

10Nos

Length of hand rail(Horizontal)

1.354m

Sectional area of hand rail (Horizontal)

0.020sqm

No.of hand rails per span(Horizontal)

16Nos

Thickness of dirt wall

0.30m

Sectional area of dirt wall

0.240sqm

Sectional area of kerb

0.130sqm

Thickness of raft

0.60m

Height of piers

3.202m

Top width of pier

0.800m

Bottom width of pier

1.20m

Sectional area of pier section

3.202sqm

One side batter of pier

0.200m

Other side batter of pier

0.200m

Width of 1st footing

1.80m

Thickness of 1st footing

0.50m

One side offset of 1st footing wrt pier

0.30m

Other side offset of 1st footing wrt pier

0.30m

Width of 2nd footing

2.40m

Thickness of 2nd footing

0.50m

(As per hydralic calculations)

One side offset of 2nd footing wrt pier

0.60m

Other side offset of 2nd footing wrt pier

0.60m

Width of 3rd footing

3.00m

Thickness of 3rd footing

0.50m

One side offset of 3rd footing wrt pier

0.90m

Other side offset of 3rd footing wrt pier

0.90m

Thickness of VRCC raft footing

0.60m

Offset of top footing along width

0.00m

Offset of 2nd footing along width

0.00m

Offset of 3rd footing along width

0.00m

Type of bearings

Unit weight of RCC (yrc)

25KN/cum

Unit weight of PCC (ypc)

24KN/cum

Unit weight of water (yw)

10KN/Cum

Road crest level (RTL)

9.280m

Low bed level (LBL)

5.62m

High flood Level (HFL)


Bottom of foundation level (BFL)
Safe Bearing Capacity of the soil (SBC)

=
=
=

7.950m
3.30m
15.00t/sqm

Compressive strength of concrete for VRCC raft footing


(fck)

25.00N/sqmm

Yield strength of steel (fy)

415.00N/sqmm

Cover to reinforcement

50.00mm

No bearings proposed

II)General loading pattern:As per IRC:6---2010,the following loadings are to be considered on the bridge or slab
culvert:1.Dead load
2.Live load
3.Impact load
4.Wind load
5.Water current
6.Tractive,braking effort of vehicles&frictional resistance of bearings
7.Buoyancy
8.Seismic force
9.Water pressure force

As per clause 202.3,the increase in permissible stresses is not permissible for the
above loading combination.

III)Loading on the slab culvert for design of piers:1.Dead Load:i)Self wieght of the deck slab =

ii)Self wieght of pier cap over pier =

iii)Self weight of wearing coat =

812.75KN

48.90KN

112.88KN

iv)Self weight of kerb =

48.02KN

v)Self weight of hand rails(verticals) =

46.48KN

vi)Self weight of hand rails(horizontals) =

10.83KN

1079.86KN
There is no need to consider snow load as per the climatic conditions
Self wieght of the piers upto bottom most footing based on the preliminary
section assumed:iv)Self wieght of the pier section =

626.31KN

v)Self wieght of top footing =

176.04KN

vi)Self wieght of 2nd footing =

234.72KN

vii)Self wieght of 3rd footing =

293.40KN

viii)Self wieght of 4th footing =

0.00KN

1330.47KN

ix)Calculation of eccentricity of self weight of pier w.r.t base of pier


S.No

Description Load in KN

Distance of centroid of load from toe of pier

Back
batter(W1)

62.63112

1.067

Centre
portion(W2)

501.04896

0.6

Front
batter(W3)

62.63112

0.133

626.3112
Location of resultant from toe of pier =

0.60m

Eccentricity wrt centre of base of pier =

0.000m

x)Calculation of eccentricity of self weight of pier&1st footing w.r.t bottom of 1st footing
S.No

Description Load in KN

Back batter

Centre portion

Distance of centroid of load from toe of 1st


footing

62.63112

1.367

501.04896

0.9

Front batter

62.63112

0.433

1st footing

176.04

0.9

802.3512

Location of resultant from toe of pier =

0.90m

Eccentricity wrt centre of 1st footing=

0.000m

xi)Calculation of eccentricity of self weight of pier,1st&2nd footings w.r.t bottom of 2nd footing
S.No

Description Load in KN

Back batter

Centre portion

Distance of centroid of load from toe of 2nd


footing

62.63112

1.667

501.04896

1.2

Front batter

62.63112

0.733

1st footing

176.04

1.20

2nd footing

234.72

1.20

1037.0712
Location of resultant from toe of pier =

1.20m

Eccentricity =

0.000m

xii)Calculation of eccentricity of self weight of pier,1st,2nd & 3rd footings w.r.t bottom of 3rd footing
S.No

1
2
3

Description Load in KN

Back batter
Centre portion
Front batter

62.63112
501.04896
62.63112

Distance of centroid of load from toe of 3rd


footing

1.967
1.5
1.033

4
5
6

1st footing
2nd footing
3rd footing

176.04
234.72
293.4
1330.4712

1.50
1.50
1.50

Location of resultant from toe of pier =

1.50m

Eccentricity =

0.000m

2.Live Load:As per clause 204.3 of IRC:6--2010,the bridges of carriage way width 7.5m shall be designed for IRC
loadings of one lane of 70R or two lanes of Class A.
GENERAL IRC Class-AA tracked vehicle loading Pattern

35t
1200

35t
3600

GENERAL IRC Class-AA wheeled vehicle loading Pattern

850

300
300

3.75t

300

6.25t

300

700

6.25t
3.75t
1050
1200

GENERAL IRC Class-A loading Pattern

6.8t

6.8t

3.00

3.00

6.8t

11.4t

3.00

6.8t

4.30

1.20

11.4t

3.20

2.7t

1.80

2.7t

1.10

The IRC Class AA Tracked loading as per the drawing is considered

Y
9071

7387
850

35t

35t

1200

3600

1200

x
Resultant live load:Eccentricity of live load w.r.t y-direction(Along the direction of travel of vehicles)
Taking moments of all the forces w.r.t y-axis
S.No

Wheel
Load/UDL in
KN

Distance from Y-axis

350

1.625m

350

3.675m

700.000
Distance of centroid of forces from y-axis

= 2.650m

Eccentricity of live load w.r.t x-direction(At right angle to the travel of vehicles)
Taking moments of all the forces w.r.t x-axis
S.No

Load in KN

Distance from X-axis

350

4.198m

350

4.198m

700
Distance of centroid of forces from x-axis

= 4.198m

Location of Resultant is as shown in the figure:-

2650
4198

4198

x
Reaction on the abutment =

640.70KN

The IRC Class AA wheeled loading as per the drawing is considered

Y
9071

3.75t

6.25t

6.25t

3.75t

7387

300

1050 1200

3.75t

700

6.25t

6.25t

1200

3.75t

300

x
Resultant live load:-

Eccentricity of live load w.r.t y-direction(Along the direction of travel of vehicles)


Taking moments of all the forces w.r.t y-axis
S.No

Wheel
Load/UDL in
KN

Distance from Y-axis

37.5

1.20m

37.5

1.20m

62.5

1.95m

62.5

1.95m

62.5

2.95m

62.5

2.95m

37.5

3.55m

37.5

3.55m

400.000
Distance of centroid of forces from y-axis

= 2.422m

Eccentricity of live load w.r.t x-direction(At right angle to the travel of vehicles)
Taking moments of all the forces w.r.t x-axis
S.No

Load in KN

Distance from X-axis

37.5

5.310m

62.5

5.310m

62.5

5.310m

37.5

5.310m

37.5

4.110m

62.5

4.110m

62.5

4.110m

37.5

4.110m

400
Distance of centroid of forces from x-axis

= 4.710m

Location of Resultant is as shown in the figure:-

2422
4710

x
Reaction on the abutment =

400.00KN

The details of wheel loads for IRC Class A live load ,each axle wise are as
given below:-

Axle load
(Tonnes)

Ground Contact Area


B(mm)

11.4
6.8
2.7

W(mm)

250
200
150

500
380
200

Placement of two lanes of IRC Class A loading as shown below:-

Y
9071

11.4t
1200

7387

11.4t

1200
4300

6.8t

x
Resultant live load:Eccentricity of live load w.r.t y-direction(Along the direction of travel of vehicles)
Taking moments of all the forces w.r.t y-axis

S.No

Wheel
Load/UDL in
KN

Distance from Y-axis

57

0.835m

57

0.835m

34

0.835m

57

2.625m

57

2.625m

34

2.625m

57

4.325m

57

4.325m

57

6.125m

10

57

6.125m

524.000
Distance of centroid of forces from y-axis

= 3.251m

Eccentricity of live load w.r.t x-direction(At right angle to the travel of vehicles)
Taking moments of all the forces w.r.t x-axis
S.No

Load in KN

Distance from X-axis

57

6.947m

57

6.947m

57

6.947m

57

6.947m

57

5.747m

57

5.747m

57

5.747m

57

5.747m

34

1.447m

10

34

1.447m

524
Distance of centroid of forces from x-axis

= 5.711m
Location of Resultant is as shown in the figure:-

3251

5711

5711

x
Calculation of reactions on abutments:As per PCI bridge design code,apply correction factor for skew angle of bridge,as given below:The reaction at the obtuse corner of skew slab is to be multiplied with correction
factor

1.0+{[Ld/12]0.5 +(Tan/6S)}

Where L =
d=
S=

Effective span
Depth of slab
Width of slab

Hence correction factor =

for 600

1.587654229

Reaction due to loads Ra =

478.36KN

Reaction due to loads = Rb =

45.64KN

The critical reaction from the above loading patterns is

Hence,the critical reaction is Ra =


The corrected reaction at obtuse corner =

640.70KN

640.7KN
1017.21KN

Assuming that the live load reaction acts at the centre of the contact area on the pier,

185
615

215
685
985
1285

815
1415
1715

The eccentricty of the line of action of live load on top of 1st footing =
-----do------ on top of 2nd footing =
-----do------ on top of 3rd footing =
-----do------ on top of raft =

0.215m
0.215m
0.215m
0.215m

The eccentricity in the other direction need not be considered due to high section modulus in transverse
direction.

3.Impact of vehicles:As per Clause 208.3(a) of IRC:6--2010,impact allowance for the spans designed for class AA tracked vehicles,
is increment of live load by a percent of
Hence,the factor is

5+2.5*(25-10)/4 =

14.375%

0.14375

Further as per clause 208.7(a),(b)&(c) of IRC:6--2010,the above impact factor shall be only
50% for calculation of pressure on piers and abutments just below the level of bed block.There
is no need to increase the live load below 3m depth.
As such,the impact allowance for the top 3m of abutments will be

For the remaining portion,impact need not be considered.

4.Wind load:Data:Bredth of the Bridge cross section 'b' =


Depth of the Bridge cross section 'd' =
b/d ratio =
Gust Factor 'G' =
Length of the bridge =
Height of the bridge in elevation =
Basic wind speed =
(From basic wind speed map of India)

8.15m
0.54m
15.0925926
2
6.74m
3.66m
50.00m/s

1)CALCULATION OF WIND FORCES ON SUPER STRUCTURE:A)Transverse Wind force:The drag coefficient for the deck slab bridges with b/d 10 is

=1.10

Hence,drag Coefficient for the bridge 'CD' =

=1.10

Area exposed to the wind A1 = Length of the bridgex(Ht.including ralings-Perforations)


Area of perforations =

3.22sqm

Net exposed area 'A1' =

21.45sqm

Hourly mean wind pressure ' Pz' for height upto 10m =

1064.5N/sqm

(Table 4 of IRC 6:2010)


The transverse wind force FT = PzXA1XGXCD =

50.23KN

B)Longitudinal Wind force:As per the clause 209.3.4. of IRC 6:2010,the longitudinal wind force F L shall be taken as 25% of the
transverse wind force,hence
FL =

12.56KN

C)Upward/Downward Wind force:The upward or downward windforce FV = PzxA3XGXCL


A3 is plan area of the bridge =
CL is lift coefficient =

56.95sqm
0.75

Hence FV =

90.94KN

2)CALCULATION OF WIND FORCES ON LIVE LOAD OVER THE ROAD SURFACE:As per the clause 209.3.2 of IRC 6:2010,the shall not be considered to be carrying
any live load when the wind speed at deck level exceeds 36m/s.
Hence,it is not necessary to consider the effect of wind on live load.

3)CALCULATION OF WIND FORCES ON SUBSTRUCTURE:The ratio of l/b =


The ratio of h/b =
Exposed area =

6.791666667
2.668333333
3.202sqm

The drag coefficient for pier CD from the

0.8

table 5 of IRC 6:2010 =


The tranvese wind force acting on the pier only =

5.45KN

The location of this force from top of raft =

3.63m

Tranverse wind force transmitted to pier from super structure =

50.23KN

The location of this force from top of raft =

6.24m

Taking moments of the above forces about top of raft,the location


of resultant from the top of raft =
5.98m
Hence,the final transverse wind force on pier FT =

55.68KN

The location of the wind force from the top of RCC raft footing =
5.Water current force:Water pressure considered on square ended piers as per clause 210.2 of
IRC:6---2010 is
P = 52KV2 =

3.51 Kg/m2.

(where the value of 'K' is 1.5 for square ended piers)

Hence,the water current force =

0.07KN

Point of action of water current force from the top of RCC raft footing =

6.Tractive,braking effort of vehicles&frictional resistance of bearings:The breaking effect of vehicles shall be 20% of live load acting in longitudinal
direction at 1.2m above road surface as per the clause 211.2 of IRC:6--2010.

As no bearings are assumed in the present case,50% of the above longitudinal


force can be assumed to be transmitted to the supports of simply supported spans resting on
stiff foundation with no bearings as per clause 211.5.1.2 of IRC:6---2010

Hence,the longitudinal force due to braking,tractive or frictional resistance of


bearings transferred to pier is
101.72KN

The location of the tractive force from the top of RCC raft footing =

7.Buoyancy :As per clause 213.4 of IRC:6---2010,for abutments or piers of shallow depth,the
dead weight of the pier shall be reduced by wieght of equal volume of water upto HFL.
For the preliminary section assumed,the volume of pier section is
i)Volume of abutment section =

26.10Cum

ii)Volume of top footing =

7.34Cum

iii)Volume of 2nd footing =

9.78Cum

iv)Volume of 3rd footing =

12.23Cum

v)Volume of 4th footing =

0.00Cum
55.44Cum

Reduction in self wieght =

9.Siesmic force :-

554.36KN

As per clause 219.1.1(a) of IRC:6---2010 in all siesmic zones,the bridges and culverts of spans upto 10m need
not be designed for siesmic forces.As the span of the bridge is only 6.37m,it need not be designed for siesmic forces.

10.Water pressure force:The water pressure distribution on the pier is as given below:-

HFL 7.950m

4.65

BFL 3.30m

46.50kn/sqm

As the pier is subjected to water pressure force from both the sides simultaneously,the
net water pressure will be zero.Hence,
Total horizontal water pressure force =

0.00KN

The above pressure acts at height of H/3 =

0.00m

IV)Check for stresses for piers&footings:-

a)Load Envelope-I:-(The Canal is dry,with live load on span)


i)On top of RCC raft footing
The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles

b)y-Direction-----In the direction of movement of vehicles


Vertical forces acting on the pier (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about xaxis(m)

Reaction due to dead load from super structure

1079.86KN

0.00

Self wieght of pier&footings

1330.47KN

0.000

Reaction due to live load with impact factor---(Wheel


loads)

1163.43KN

Upward wind load

-90.94

-0.215
0.00

3482.83
Horizontal forces acting/transferred on the pier (H) composes of the following components
S.No

Type of load

Intensity in KN Direction x or y

Wind load

55.68KN

x-Direction

Tractive,Braking&Frictional resistance of bearings

101.72KN

y-Direction

Check for stresses:About x-axis:Breadth of 3rd footing b =

8.15m

Depth of 3rd footing d =

3.00m

Area of the footing = A =

24.45 m2

Section modulus
about x-axis --Zx =

(1/6)bd2 =

12.23 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

Type of load

Intensity in KN Eccentricity/Lever
(P)
arm

1
2
3
4
5

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Tractive,Braking&Frictional resistance of bearings

S.No

1
2
3
4
5

Type of load

0.00
0.00
-0.215
0.00

101.72KN

6.82

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Tractive,Braking&Frictional resistance of bearings

Stress at heel =

1079.86KN
1330.47KN
1163.43KN
-90.94KN

P/A(1+6e/d)+M/Z =

1079.86KN
1330.47KN
1163.43KN
-90.94KN

0.00
0.00
0.215
0.00

101.72KN

6.82

65.24 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at toe =

P/A(1+6e/d)+M/Z =

206.74 KN/Sqm<4000KN/sqm

Hence safe.

TOE

U/S

3000

D/S

HEEL

8150

D/S

HEEL

8150
About y-axis:Breadth of 3rd footing b =

3.00m

Depth of 3rd footing d =

8.15m

Area of the footing = A =

24.45 m2

Section modulus about =


y-axis--Zy =

(1/6)bd2 =

33.21 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
5

S.No

1
2
3
4
5

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Wind load

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Wind load

Stress at up stream side


edge =

P/A(1+6e/d)+M/Z =

Intensity in KN Eccentricity/Lever
(P)
arm

1079.86KN
1330.47KN
1163.43KN
-90.94KN

0.00
0.00
0.000
0.00

55.68KN

5.98

Intensity in KN Eccentricity/Lever
(P)
arm

1079.86KN
1330.47KN
1163.43KN
-90.94KN

0.00
0.00
0.000
0.00

55.68KN

5.98

132.42 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at down stream side
edge =

P/A(1+6e/d)+M/Z =

152.48 KN/Sqm<4000KN/sqm

Hence safe.

ii)On top of 3rd footing


The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the pier (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about xaxis(m)

Reaction due to dead load from super structure

1079.86KN

0.00

Self wieght of pier&footings

1037.07KN

0.000

Reaction due to live load with impact factor

1163.43KN

Upward wind load

-90.94

-0.215
0.00

Horizontal load acting/transferred on the pier (H) composes of the following components
S.No

Type of load

Intensity in KN Direction x or y

Wind load

55.68KN

x-Direction

Tractive,Braking&Frictional resistance of bearings

101.72KN

y-Direction

Check for stresses:About x-axis:Breadth of 2nd footing b =


Depth of 2nd footing d =
Area of the footing = A =
Section modulus about
x-axis--Zx =

8.15m
2.40m
19.56 m2
(1/6)bd2 =

7.82 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Tractive,Braking&Frictional resistance of bearings

1
2
3
4
5

S.No

1
2
3
4
5

Intensity in KN Eccentricity/Lever
(P)
arm

Type of load

0.00
0.00
-0.215
0.00

101.72KN

6.32

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Tractive,Braking&Frictional resistance of bearings

Stress at heel =

1079.86KN
1037.07KN
1163.43KN
-90.94KN

P/A(1+6e/d)+M/Z =

1079.86KN
1037.07KN
1163.43KN
-90.94KN

0.00
0.00
0.215
0.00

101.72KN

6.32

48.92 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at toe =

P/A(1+6e/d)+M/Z =

277.2 KN/Sqm<4000KN/sqm

Hence safe.

TOE

2400

D/S

HEEL

U/S

TOE

U/S

2400

D/S

HEEL
8150

About y-axis:Breadth of 1st footing b =


Depth of 1st footing d =
Area of the footing = A =
Section modulus about
y-axis--Zy =

2.40m
8.15m
19.56 m2
(1/6)bd2 =

26.57 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
5

S.No

1
2

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Wind load

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings

Intensity in KN Eccentricity/Lever
(P)
arm

1079.86KN
1037.07KN
1163.43KN
-90.94KN

0.00
0.00
0.000
0.00

55.68KN

5.48

Intensity in KN Eccentricity/Lever
(P)
arm

1079.86KN
1037.07KN

0.00
0.00

3
4
5

Reaction due to live load with impact factor


Upward wind load
Horizontal loads:- (Stress = M/Z)
Wind load

Stress at up stream side


edge =

P/A(1+6e/d)+M/Z =

1163.43KN
-90.94KN

0.000
0.00

55.68KN

5.48

151.58 KN/Sqm>-2000KN/sqm.

Hence safe.

Stress at down stream side


edge =

P/A(1+6e/d)+M/Z =

174.54 KN/Sqm<4000KN/sqm

Hence safe.

i)On top of 2nd footing


The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the abutment (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about xaxis(m)

Reaction due to dead load from super structure

1079.86KN

0.00

Self wieght of pier&footings

802.35KN

0.000

Reaction due to live load with impact factor

1163.43KN

Upward wind load

-90.94

-0.215
0.00

Horizontal load acting/transferred on the abutment (H) composes of the following components
S.No

Type of load

Intensity in KN Direction x or y

Wind load

55.68KN

x-Direction

Tractive,Braking&Frictional resistance of bearings

101.72KN

y-Direction

Check for stresses:About x-axis:Breadth of 1st footing b =


Depth of 1st footing d =
Area of the footing = A =

8.15m
1.80m
14.67 m2

Section modulus
about x-axis--Zx =

(1/6)bd2 =

4.40 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
5

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Tractive,Braking&Frictional resistance of bearings

S.No

1
2
3
4
5

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Tractive,Braking&Frictional resistance of bearings

Stress at heel =

P/A(1+6e/d)+M/Z =

Intensity in KN Eccentricity/Lever
(P)
arm

1079.86KN
802.35KN
1163.43KN
-90.94KN

0.00
0.00
-0.215
0.00

101.72KN

5.82

Intensity in KN Eccentricity
(P)

1079.86KN
802.35KN
1163.43KN
-90.94KN

0.00
0.00
0.215
0.00

101.72KN

5.82

10.05 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at toe =

P/A(1+6e/d)+M/Z =

392.76 KN/Sqm<4000KN/sqm

Hence safe.

U/S

TOE

1800

HEEL

D/S

8150
About y-axis:Breadth of 1st footing b =
Depth of 1st footing d =
Area of the footing = A =
Section modulus
about y-axis--Zy =

1.80m
8.15m
14.67 m2
(1/6)bd2 =

19.93 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2

i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings
Reaction due to live load with impact factor

Intensity in KN Eccentricity/Lever
(P)
arm

1079.86KN
802.35KN
1163.43KN

0.00
0.00
0.000

4
5

Upward wind load


Horizontal loads:- (Stress = M/Z)
Wind load

S.No

Type of load

1
2
3
4
5

0.00

55.68KN

4.98

Intensity in KN Eccentricity/Lever
(P)
arm

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Wind load

Stress at up stream side


edge =

-90.94KN

P/A(1+6e/d)+M/Z =

1079.86KN
802.35KN
1163.43KN
-90.94KN

0.00
0.00
0.000
0.00

55.68KN

4.98

187.49 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at down stream side
edge =

P/A(1+6e/d)+M/Z =

215.33 KN/Sqm<4000KN/sqm

Hence safe.
i)On top of 1st footing
The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the pier (P) composes of the following components
S.No

Type of load

1
2
3

Reaction due to dead load from super structure


Self wieght of pier&footings
Reaction due to live load with impact factor

Upward wind load

Intensity in KN Eccentricty about xaxis(m)


1079.86KN
626.31KN
1163.43KN

0.00
0.000
-0.215

-90.94

0.00

Horizontal load acting/transferred on the pier (H) composes of the following components

S.No

1
2

Type of load

Intensity in KN Direction x or y

Wind load
Tractive,Braking&Frictional resistance of bearings

55.68KN
101.72KN

x-Direction
y-Direction

Check for stresses:About x-axis:Breadth of pier b =


Depth of pier d =
Area of the base = A =

8.15m
1.20m
9.78 m2

Section modulus of base of pier


about x-axis--Zx =

(1/6)bd2 =

1.96 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
5

S.No

1
2
3
4

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Tractive,Braking&Frictional resistance of bearings

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)

Intensity in KN Eccentricity/Lever
(P)
arm

1079.86KN
626.31KN
1163.43KN
-90.94KN

0.00
0.000
-0.215
0.00

101.72KN

5.32

Intensity in KN Eccentricity
(P)

1079.86KN
626.31KN
1163.43KN
-90.94KN

0.00
0.00
0.215
0.00

Tractive,Braking&Frictional resistance of bearings

Stress at heel =

P/A(1+6e/d)+M/Z =

101.72KN

5.32

-120.42 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at toe =

P/A(1+6e/d)+M/Z =

688.66 KN/Sqm<4000KN/sqm

Hence safe.

U/S

TOE

1200

D/S

HEEL
8150

About y-axis:Breadth of abutment b =


Depth of abutment d =
Area of the footing = A =
Section modulus of base of pier
about y-axis--Zy =

1.20m
8.15m
9.78 m2
(1/6)bd2 =

13.28 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2

i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm

S.No

1
2
3
4
5

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Wind load

S.No

1
2
3
4
5

Intensity in KN Eccentricity/Lever
(P)
arm

Type of load

0.00
0.00
0.000
0.00

55.68KN

4.48

Intensity in KN Eccentricity/Lever
(P)
arm

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Self wieght of pier&footings
Reaction due to live load with impact factor
Upward wind load
Horizontal loads:- (Stress = M/Z)
Wind load

Stress at up stream side


edge =

1079.86KN
626.31KN
1163.43KN
-90.94KN

P/A(1+6e/d)+M/Z =

1079.86KN
626.31KN
1163.43KN
-90.94KN

0.00
0.00
0.000
0.00

55.68KN

4.48

265.34 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at down stream side
edge =

P/A(1+6e/d)+M/Z =

302.9 KN/Sqm<4000KN/sqm

Hence safe.
b)Load Envelope-II:-(The Canal is full,no live load on span)
i)On top of RCC raft footing
The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the pier (P) composes of the following components

S.No

Type of load

Intensity in KN Eccentricty about xaxis(m)

Reaction due to dead load from super structure

1079.86KN

0.00

Self wieght of pier&cut waters

1330.47KN

Reduction in self weight due to buoyancy

-554.36KN

Net self weight

776.11KN

0.000

Upward wind force

-90.94KN

0.000

Horizontal load acting/transferred on the pier (H) composes of the following components
S.No

Type of load

Intensity in KN Direction x or y

Wind load

55.68KN

x-Direction

Tractive,Braking&Frictional resistance of bearings

0.00KN

y-Direction

Water current force

0.07KN

x-Direction

Water pressure force

0.00KN

y-Direction

Check for stresses:About x-axis:Breadth of bottom footing b =


Depth of bottom footing d =
Area of the footing = A =
Section modulus of bottom footing
about x-axis --Zx =

8.15m
3.00m
24.45 m2
(1/6)bd2 =

12.23 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure

Intensity in KN Eccentricity/Lever
(P)
arm

1079.86KN

0.00

2
3
4

Net self wieght of pier&footings


Upward wind force
Horizontal loads:- (Stress = M/Z)
Water pressure force

S.No

Type of load

1
2
3
4

0.00
0.00

0.00KN

0.00

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of pier&footings
Upward wind force
Horizontal loads:- (Stress = M/Z)
Water pressure force

Stress at heel =

776.11KN
-90.94KN

P/A(1+6e/b)+M/Z =

1079.86KN
776.11KN
-90.94KN

0.00
0.00
0.00

0.00KN

0.00

72.19 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at toe =

P/A(1+6e/b)+M/Z =

72.19 KN/Sqm<4000KN/sqm

Hence safe.

About y-axis:Breadth of bottom footing b =


Depth of bottom footing d =
Area of the footing = A =
Section modulus of bottom footing
about y-axis --Zy =

3.00m
8.15m
24.45 m2
(1/6)bd2 =

33.21 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

Type of load

Intensity in KN Eccentricity/Lever
(P)
arm

1
2
3
4
5

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of pier&footings
Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

S.No

1
2
3
4
5

Type of load

0.00
0.00
0.00

55.68KN
0.07KN

5.98
2.70

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of pier&footings
Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

Stress at up stream side


edge =

1079.86KN
776.11KN
-90.94KN

P/A(1+6e/d)+M/Z =

1079.86KN
776.11KN
-90.94KN

0.00
0.00
0.00

55.68KN
0.07KN

5.98
2.70

62.15 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at down stream side
edge =

P/A(1+6e/d)+M/Z =

82.23 KN/Sqm<4000KN/sqm

Hence safe.

ii)On top of 3rd footing


The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the pier (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about xaxis(m)

Reaction due to dead load from super structure

1079.86KN

Self wieght of pier&footings

1037.07KN

0.00

Reduction in self weight due to buoyancy

-432.11KN

Net self weight

604.96KN

0.000

Upward wind force

-90.94KN

0.000

Horizontal load acting/transferred on the pier (H) composes of the following components
S.No

Type of load

Intensity in KN Direction x or y

Wind load

55.68KN

x-Direction

Tractive,Braking&Frictional resistance of bearings

0.00KN

y-Direction

Water current force

0.07KN

x-Direction

Water pressure force

0.00KN

y-Direction

Check for stresses:About x-axis:Breadth of 2nd footing b =


Depth of 2nd footing d =
Area of the footing = A =
Section modulus of bottom footing
about x-axis --Zx =

8.15m
2.40m
19.56 m2
(1/6)bd2 =

7.82 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of pier&footings
Upward wind force
Horizontal loads:- (Stress = M/Z)
Water pressure force

Intensity in KN Eccentricity/Lever
(P)
arm

1079.86KN
604.96KN
-90.94KN

0.00
0.00
0.00

0.00KN

-0.50

S.No

1
2
3
4

Type of load

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of pier&footings
Upward wind force
Horizontal loads:- (Stress = M/Z)
Water pressure force

Stress at heel =

P/A(1+6e/d)+M/Z =

1079.86KN
604.96KN
-90.94KN

0.00
0.00
0.00

0.00KN

-0.50

81.49 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at toe =

P/A(1+6e/d)+M/Z =

81.49 KN/Sqm<4000KN/sqm

Hence safe.

About y-axis:Breadth of 1st footing b =


Depth of 1st footing d =
Area of the footing = A =
Section modulus of bottom footing
about y-axis --Zy =

2.40m
8.15m
19.56 m2
(1/6)bd2 =

26.57 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
5

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of pier&footings
Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

Intensity in KN Eccentricity/Lever
(P)
arm

1079.86KN
604.96KN
-90.94KN

0.00
0.00
0.00

55.68KN
0.07KN

5.48
2.20

S.No

1
2
3
4
5

Type of load

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of pier&footings
Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

Stress at up stream side


edge =

1079.86KN
604.96KN
-90.94KN

0.00
0.00
0.00

55.68KN
0.07KN

5.48
2.20

P/A(1+6e/d)+M/Z =

70 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at down stream side
edge =

P/A(1+6e/d)+M/Z =

92.98 KN/Sqm<4000KN/sqm

Hence safe.

iii)On top of 2nd footing


The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the pier (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about xaxis(m)

Reaction due to dead load from super structure

1079.86KN

0.00

Self wieght of pier&cut waters

802.35KN

Reduction in self weight due to buoyancy

-334.31KN

Net self weight

468.04KN

0.000

Upward wind force

-90.94KN

0.000

Horizontal load acting/transferred on the pier (H) composes of the following components

S.No

Type of load

Intensity in KN Direction x or y

Wind load

55.68KN

x-Direction

Tractive,Braking&Frictional resistance of bearings

0.00KN

y-Direction

Water current force

0.07KN

x-Direction

Water pressure force

0.00KN

y-Direction

Check for stresses:About x-axis:Breadth of 1st footing b =


Depth of 1st footing d =
Area of the footing = A =
Section modulus of bottom footing
about x-axis --Zx =

8.15m
1.80m
14.67 m2
(1/6)bd2 =

4.40 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4

S.No

1
2
3

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of pier&footings
Upward wind force
Horizontal loads:- (Stress = M/Z)
Water pressure force

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of pier&footings
Upward wind force

Intensity in KN Eccentricity/Lever
(P)
arm

1079.86KN
468.04KN
-90.94KN

0.00
0.00
0.00

0.00KN

-1.00

Intensity in KN Eccentricity
(P)

1079.86KN
468.04KN
-90.94KN

0.00
0.00
0.00

Horizontal loads:- (Stress = M/Z)


Water pressure force

Stress at heel =

0.00KN

P/A(1+6e/d)+M/Z =

-1.00

99.31 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at toe =

P/A(1+6e/d)+M/Z =

99.31 KN/Sqm<4000KN/sqm

Hence safe.

About y-axis:Breadth of 1st footing b =


Depth of 1st footing d =
Area of the footing = A =
Section modulus of bottom footing
about y-axis --Zy =

1.80m
8.15m
14.67 m2
(1/6)bd2 =

19.93 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
5

S.No

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of pier&footings
Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)

Intensity in KN Eccentricity/Lever
(P)
arm

1079.86KN
468.04KN
-90.94KN

0.00
0.00
0.00

55.68KN
0.07KN

4.98
1.70

Intensity in KN Eccentricity
(P)

1
2
3
4
5

Reaction due to dead load from super structure


Net self wieght of pier&footings
Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

Stress at up stream side


edge =

P/A(1+6e/d)+M/Z =

1079.86KN
468.04KN
-90.94KN

0.00
0.00
0.00

55.68KN
0.07KN

4.98
1.70

85.38 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at down stream side
edge =

P/A(1+6e/d)+M/Z =

113.24 KN/Sqm<4000KN/sqm

Hence safe.
iii)On top of 1st footing
The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the pier (P) composes of the following components
S.No

2
3

Type of load

Reaction due to dead load from super structure


Self wieght of pier&cut waters
Reduction in self weight due to buoyancy
Net self weight
Upward wind force

Intensity in KN Eccentricty about xaxis(m)


1079.86KN
802.35KN
-334.31KN
468.04KN
-90.94KN

0.00

0.000
0.000

Horizontal load acting/transferred on the pier (H) composes of the following components
S.No

1
2
3
4

Type of load

Wind load
Tractive,Braking&Frictional resistance of bearings
Water current force
Water pressure force
Check for stresses:-

Intensity in KN Direction x or y

55.68KN
0.00KN
0.07KN
0.00KN

x-Direction
y-Direction
x-Direction
y-Direction

About x-axis:Breadth of abutment b =


Depth of abutment d =
Area of the footing = A =

8.15m
1.20m
9.78 m2

Section modulus of bottom footing


about x-axis --Zx =

(1/6)bd2 =

1.96 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4

Type of load

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of pier&footings
Upward wind force
Horizontal loads:- (Stress = M/Z)
Water pressure force

S.No

1
2
3
4

Intensity in KN Eccentricity/Lever
(P)
arm

Type of load

0.00
0.00
0.00

0.00KN

-1.50

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of pier&footings
Upward wind force
Horizontal loads:- (Stress = M/Z)
Water pressure force

Stress at heel =

1079.86KN
468.04KN
-90.94KN

P/A(1+6e/d)+M/Z =

1079.86KN
468.04KN
-90.94KN

0.00
0.00
0.00

0.00KN

-1.50

148.98 KN/Sqm>-2000KN/sqm.

Hence safe.
Stress at toe =

P/A(1+6e/d)+M/Z =

Hence safe.

148.98 KN/Sqm<4000KN/sqm

About y-axis:Breadth of pier b =


Depth of pier d =
Area of the footing = A =

1.20m
8.15m
9.78 m2

Section modulus of bottom footing


about y-axis --Zy =

(1/6)bd2 =

13.28 m3

For M15 grade of concrete permissible compressive stress in direct compreession is 4N/mm 2
i.e, 4000KN/sqm
For M15 grade of concrete permissible tensile stress in bending tension is -2N/mm 2
i.e, -2000KN/sqm
S.No

1
2
3
4
5

S.No

1
2
3
4
5

Type of load

Intensity in KN Eccentricity/Lever
(P)
arm

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of pier&footings
Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

Type of load

P/A(1+6e/d)+M/Z =

Hence safe.
Stress at down stream side

0.00
0.00
0.00

55.68KN
0.07KN

4.48
1.20

Intensity in KN Eccentricity
(P)

Vertical loads:-(Stress = P/A(1+6e/d)


Reaction due to dead load from super structure
Net self wieght of pier&footings
Upward wind force
Horizontal loads:- (Stress = M/Z)
Wind load
Water current force

Stress at up stream side


edge =

1079.86KN
468.04KN
-90.94KN

1079.86KN
468.04KN
-90.94KN

0.00
0.00
0.00

55.68KN
0.07KN

4.48
1.20

130.19 KN/Sqm>-2000KN/sqm.

edge of pier =

P/A(1+6e/d)+M/Z =

167.77 KN/Sqm<4000KN/sqm

Hence safe.

V)Check for stability of pier:a)Load Envelope-I:-(The Canal is dry,live load on span)


The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the pier (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about xaxis(m)

Reaction due to dead load from super structure

1079.86KN

0.00

Self wieght of pier

626.31KN

0.000

Reaction due to live load with impact factor

Upward wind force

1163.43KN

-0.215

-90.94KN

0.000

2778.66KN

Horizontal load acting/transferred on the pier (H) composes of the following components
S.No

Type of load

Intensity in KN Direction x or y

Wind load

55.68KN

x-Direction

Tractive,Braking&Frictional resistance of bearings

101.72KN

y-Direction

157.40KN
Check for stability against over turning:Taking moments of all the overturning forces about toe of the pier wrt x-axis,

Moment due to tractive,braking&frictional resistance of bearings =

Total overturning moment =

Taking moments of all the restoring forces about toe of the pier wrt x-axis,,
Moment due to self weight of pier =
Moment due to dead load from super structure =
Moment due to upward wind force =
Moment due to live load reaction on pier =

Total Restoring moment =

Factor of safety =

2.61858085

> 2.0
Hence safe
(As per clause 706.3.4 of IRC:78-2000)

Check for stability against sliding:Total vertical load acting on the base of the pier V b =
Total sliding force,ie,horizontal load on the pier H b =
Coefficient of friction between concrete surfaces =
Factor of safety against sliding Fs =

14.1227255 > 1.5


Hence safe
(As per clause 706.3.4 of IRC:78-2000)

b)Load Envelope-III:-(The Canal is full ,with live load on span)


The following co-ordinates are assumed:a)x-Direction-----At right angle to the movement of vehicles
b)y-Direction-----In the direction of movement of vehicles
Vertical load acting on the pier (P) composes of the following components
S.No

Type of load

Intensity in KN Eccentricty about xaxis(m)

Reaction due to dead load from super structure

1079.86KN

Self wieght of pier

626.31KN

Reduction in self weight due to buoyancy

-261.00KN

0.00

Net self wieght

365.31KN

0.000

Reaction due to live load with impact factor

1017.21KN

-0.215

Upward wind force

-90.94KN

0.00

Horizontal load acting/transferred on the pier (H) composes of the following components
S.No

Type of load

Intensity in KN Direction x or y

Wind load

55.68KN

x-Direction

Tractive,Braking&Frictional resistance of bearings

101.72KN

y-Direction

Force due to water pressure

0.00KN

y-Direction

Check for stability against over turning:Taking moments of all the overturning forces about toe of the pier wrt x-axis,
Moment due to tractive,braking&frictional resistance of bearings =

Total overturning moment =


Taking moments of all the restoring forces about toe of the pier wrt x-axis,
Moment due to self weight of pier =
Moment due to live load reaction =
Moment due to dead load from super structure =

Total Restoring moment =

Factor of safety =

2.32599924

Check for stability against sliding:Total vertical load acting on the base of the pier V b =

Total sliding force,ie,horizontal load on the pier H b =


Coefficient of friction between concrete surfaces =

> 2.0
Hence safe
(As per clause 706.3.4 of IRC:78-2000)

Factor of safety against sliding Fs =

10.1578237 > 1.5


Hence safe
(As per clause 706.3.4 of IRC:78-2000)

ings proposed

Moment

66.83

300.63

8.33

375.79

Moment

85.62

450.94
27.12

158.44
722.12

Moment

104.41

601.26

45.91

211.25

281.66

1244.49

Moment

123.2
751.57
64.7

264.06
352.08
440.1
1995.71

e designed for IRC

850

6.8t

6.8t

0
3.00

Moment

568.75KNm
1286.25KNm
1855.00KNm

Moment
1469.30KNm

1469.30KNm
2938.60KN

7387

Moment

45.00KNm
45.00KNm
121.88KNm
121.88KNm
184.38KNm
184.38KNm
133.13KNm
133.13KNm
968.75KNm

Moment
199.13KNm
331.88KNm
331.88KNm
199.13KNm
154.13KNm
256.88KNm
256.88KNm

154.13KNm
1884.00KN

Moment

47.60KNm
47.60KNm
28.39KNm
149.63KNm
149.63KNm
89.25KNm
246.53KNm
246.53KNm
349.13KNm
349.13KNm
1703.38KNm

Moment
395.98KNm

395.98KNm
395.98KNm

395.98KNm
327.58KNm
327.58KNm
327.58KNm
327.58KNm
49.20KNm
49.20KNm
2992.63KN

given below:-

modulus in transverse

or class AA tracked vehicles,

0.071875

ken as 25% of the

5.98m

2.70m

6.82m

erts of spans upto 10m need

esigned for siesmic forces.

Eccentricty about yaxis(m)


0.00
0.000
0.000
0.00

Location(Ht.from the
section considered).
(m)
5.98
6.82

Stress at heel
P/A(1+6e/d)

44.17
54.42
27.12
-3.72
-56.75
65.24

Stress at toe
P/A(1+6e/d)

m>-2000KN/sqm.

m<4000KN/sqm

44.17
54.42
55.12
-3.72
56.75
206.74

Stress at upstream
edge
P/A(1+6e/d)

44.17
54.42
47.58
-3.72
-10.03
132.42

Stress at D/S edge


P/A(1+6e/d)

m>-2000KN/sqm.

44.17
54.42
47.58
-3.72
10.03
152.48

m<4000KN/sqm

Eccentricty about yaxis(m)


0.00
0.000
0.000
0.00

Location(Ht.from the
section considered).
(m)
5.48
6.32

Stress at heel
P/A(1+6e/d)

55.21
53.02
27.51
-4.65
-82.17
48.92

Stress at toe
P/A(1+6e/b)

m>-2000KN/sqm.

m<4000KN/sqm

55.21
53.02
91.45
-4.65
82.17
277.2

Stress at upstream
edge
P/A(1+6e/d)

55.21
53.02
59.48
-4.65
-11.48
151.58

Stress at D/S edge


P/A(1+6e/d)

55.21
53.02

59.48
-4.65
11.48
174.54

m>-2000KN/sqm.

m<4000KN/sqm

Eccentricty about yaxis(m)


0.00
0.000
0.000
0.00
components
Location(Ht.from the
section considered).
(m)
4.98
5.82

Stress at heel
P/A(1+6e/d)

73.61
54.69
22.47
-6.2
-134.52
10.05

Stress at toe
P/A(1+6e/d)

m>-2000KN/sqm.

73.61
54.69
136.14
-6.2
134.52
392.76

m<4000KN/sqm

Stress at upstream
edge
P/A(1+6e/d)

73.61
54.69
79.31

-6.2
-13.92
187.49

Stress at D/S edge


P/A(1+6e/d)

73.61
54.69
79.31
-6.2
13.92
215.33

m>-2000KN/sqm.

m<4000KN/sqm

Eccentricty about yaxis(m)


0.00
0.000
0.000
0.00

Location(Ht.from the
section considered).
(m)
4.48
5.32

Stress at heel
P/A(1+6e/d)

110.42
64.04
-8.92
-9.3
-276.66
-120.42

Stress at toe
P/A(1+6e/d)

110.42
64.04
246.84
-9.3

276.66
688.66

m>-2000KN/sqm.

m<4000KN/sqm

U/S

Stress at upstream
edge
P/A(1+6e/d)

110.42
64.04
118.96
-9.3
-18.78
265.34

Stress at D/S edge


P/A(1+6e/d)

m>-2000KN/sqm.

m<4000KN/sqm

110.42
64.04
118.96
-9.3
18.78
302.9

Eccentricty about yaxis(m)


0.00

0.000
0.000

Location(Ht.from the
section considered).
(m)
5.98
0.00
2.70
0.00

Stress at heel
P/A(1+6e/d)

44.17

31.74
-3.72
0.0
72.19

Stress at toe
P/A(1+6e/d)

44.17
31.74
-3.72
0.0
72.19

m>-2000KN/sqm.

m<4000KN/sqm

Stress at U/S Edge


P/A(1+6e/d)

44.17
31.74
-3.72
-10.03
0.0
62.15

Stress at D/S edge


P/A(1+6e/d)

44.17
31.74
-3.72
10.03
0.0
82.23

m>-2000KN/sqm.

m<4000KN/sqm

Eccentricty about yaxis(m)


0.00

0.000
0.000

Location(Ht.from the
section considered).
(m)
5.48
0.00
2.20
-0.50

Stress at heel
P/A(1+6e/d)

55.21
30.93
-4.65
0.0
81.49

Stress at toe
P/A(1+6e/d)

55.21
30.93
-4.65
0.0
81.49

m>-2000KN/sqm.

m<4000KN/sqm

Stress at U/S Edge


P/A(1+6e/d)

55.21
30.93
-4.65
-11.48
0.0

70

Stress at D/S edge


P/A(1+6e/d)

55.21
30.93
-4.65
11.48
0.0
92.98

m>-2000KN/sqm.

m<4000KN/sqm

Eccentricty about yaxis(m)


0.00

0.000
0.000

Location(Ht.from the
section considered).
(m)
4.98
0.00
1.70
-1.00

Stress at heel
P/A(1+6e/d)

73.61
31.9
-6.2
0.0
99.31

Stress at toe
P/A(1+6e/d)

73.61
31.9
-6.2

0.0
99.31

m>-2000KN/sqm.

m<4000KN/sqm

Stress at U/S Edge


P/A(1+6e/d)

73.61
31.9
-6.2
-13.92
0.0
85.38

Stress at D/S edge


P/A(1+6e/d)

73.61
31.9
-6.2
13.92
0.0
113.24

m>-2000KN/sqm.

m<4000KN/sqm

Eccentricty about yaxis(m)


0.00

0.000
0.000

Location(Ht.from the
section considered).
(m)
4.48
0.00
1.20
-1.50

Stress at heel
P/A(1+6e/d)

110.42
47.86
-9.3
0.0
148.98

Stress at toe
P/A(1+6e/d)

m>-2000KN/sqm.

m<4000KN/sqm

110.42
47.86
-9.3
0.0
148.98

Stress at U/S Edge


P/A(1+6e/d)

110.42
47.86
-9.3
-18.78
0.0
130.19

Stress at D/S edge


P/A(1+6e/d)

m>-2000KN/sqm.

110.42
47.86
-9.3
18.78
0.0
167.77

m<4000KN/sqm

Eccentricty about yaxis(m)


0.00
0.000
0.000
0.00

Location(Ht.from the
section considered).
(m)
4.48
5.32

541.16Kn-m

541.16Kn-m

375.79Kn-m
647.92Kn-m
-54.56Kn-m
447.92Kn-m

1417.06Kn-m

of IRC:78-2000)

2778.66KN
157.40KN
0.80

of IRC:78-2000)

Eccentricty about yaxis(m)


0.00

0.000
0.000
0.00

Location(Ht.from the
section considered).
(m)
4.48
5.32
-1.50

541.16Kn-m

541.16Kn-m

219.19Kn-m
391.63Kn-m
647.92Kn-m

1258.73Kn-m

of IRC:78-2000)

1291.58KN

101.72KN
0.80

of IRC:78-2000)

DESIGN OF CANTILEVER WING WALL


Data:Height of Retaining wall(h) =
Height of wall above G.L=
Height of wall below G.L=
Density of back fill soil&material in toe portion(y) =
Grade of concrete =
Grade of steel =
Ground water Table level =
Angle of shearing resistance of back fill material&material at toe portion(Q) =
Angle of face of wall supporting earth with horizontal(a)(In degrees)
(in clock wise direction)
Slope of back fill(b) =
Angle of wall friction (q) =
Undrained Cohesion ( c) =
Safe bearing capacity(SBC) =
Surcharge over the back fill(s) =
(Assumed)
Characteristic compressive strength =
Tensile strength of steel =
Unit weight of RCC =
Unit weight of PCC =

Coefficient of active earth pressure by Coulomb's theory


Ka =

Sin(a+Q)
sina

Sin(a+Q) =
Sin(a-q) =
Sina =
Sin(Q+q) =
Sin(Q-b) =
Sin(a+b) =

sin(a-q)

SIN[3.14*(88+30)/180] =
SIN[3.14*(87.55-15)/180] =
SIN[3.14*(87.55)/180] =
SIN[3.14*(30+15)/180] =
SIN[3.14*(30-0)/180] =
SIN[3.14*(87.55+0)/180] =

From the above expression,


Ka =

0.32

Dimensions of the Cantilever wall(Assumed for preliminary design):Thickness of base slab =

sin(Q+q)sin(Q-b)
sin(a+b)

0.887
0.954
0.999
0.707
0.5
0.999

Width of the heel slab =


Thickness of stem at bottom =
Thickness of stem at top =
Length of the toe =

4.20m

C
1.00m

2.00m

Earth pressure at top including surcharge = K ays =

Earth pressure at bottom including surcharge = K ay(s+h) =

Pressure distribution is as shown below:345.6

4.20m

2764.8

345.6

Area of the rectangular portion =


Area of the triangular portion =

1451.52
5806.08
7257.6

Taking moments of the areas about the toe of the wall


S.No
1
2

Description

Area

Lever arm

Moment

Rectangular
Triangular

1451.52
5806.08

2.1
1.4

3048.19
8128.51

7257.60

11176.7

Height from the bottom of the wall =

1.54m

The active Earth pressure acts on the abutment as shown below:-

0.20

17.68

4.200m
1.54m
87.32

0.40m
0.07
Total earth pressure acting on the wall per 1m length P =

7257.60Kg

Horizontal component of the earth pressure P h =

Vertical component of the earth pressure P v =

Eccentricity of vertical component of earth pressure =


Total earth pressure =
It acts at a hieght of
from the base

Stability calculations:Load(Kg)
Weight of the rectangular portion of stem =

2100.00Kg

Weight of the rectangular portion of stem =

1050.00Kg

Wieght of base slab =

3000.00Kg

Wieght of soil on heel including surcharge =

14688.00Kg

Vertical component of earth pressure =

2203.06Kg
23041.06Kg

Note:-Weight of soil on the toe is neglected on the assumption that,it is scoured.


Horizontal earth pressure force =

Lever arm x =

6915.15

M=

1.27m

V
Eccentricuty e = b/2-x =

Maximum stress =

P/A(1+6e/b) =

Minimum stress =

P/A(1-6e/b) =

0.23m

<b/6

Hence there is no uplift

11213.31 < SBC

Hence safe

4147.39

Coefficient of friction between soil and footing u =


Factor of safety against sliding =(uFxW)/Ph =

0.5
1.67 >1.5 Hence,the structure is safe

Moment of overturning force,ie,Horizontal component of earth pressure about toe 'C' =


Moment of restoring forces about toe 'C' =
Factor of safety against overturning =

3.74 >2.0 Hence safe.

Design of heel:Length of heel =

1.60m

Downward load intensity due to self weight of base slab =

3000.00Kg/m

Downward load intensity due to soil including surcharge =

14688.00Kg/m

TOTAL
The upward pressure distribution below the base slab is as given below:F

17688.00Kg/m

4147.39Kg/sqm
11213.31

1.00m

0.40m

1.60m

The upward pressure intensity at point 'F' is

8858.00Kg/sqm

The upward pressure intensity at point 'G' is

7915.88Kg/sqm

Total upward pressure force on heel portion due to soil reaction =

9650.62Kg/m

The distance of centroid of upward soil reaction from 'G' is =

0.72m

The distance of centroid of downward load intensity from 'G' is =

0.80m

Resultant moment =

7233.85Kg-m/m

Factored bending moment Mu =

Effective depth required d =


Over all depth provided =

10850.78Kgm

Mu/0.138fckb =
400.00mm

Effective depth provided(Assuming 50mm cover) d =


Mu/bd2 =

177.35mm

342.00mm

0.928

From table 2 of SP 16,percentage of steel required =


Area of steel required =

0.276
943.92sqmm

Hence provide 12mm dia HYSD bars@ 110mm c/c spacing


Hence Ast provided =

1027.64sqmm

Check for shear:The critical section for beam shear is at distance of 'd' from the face of the support

Hence,the factored design shear force V Fd =

120.56KN

at a distance 'd' from the face of the support

Nominal shear stress Tv =

0.35N/sqmm <2.8 N/sqmm


(As per Table 20 of 1S 456)

Hence,the section is safe from shear point of view

Assumed percentage area of the steel reinforcement =

0.30%

The design shear strength of concrete for the above steel percentage from
Table 19 of IS 456 is
0.39
0.39>0.35
Hence,the depth provided is safe from beam shear point of view
Hence,no shear reinforcement is required.
Provide temperature re inforcement @ 0.15%
Area required =

600.00sqmm

Taking 10mm dia HYSD bars,the spacing comes to 150mm


Hence provide 10mm dia bars @ 150mm c/c

Design of wall or stem:Factored bending moment Mu =

Effective depth required d =


Over all depth provided =

15974.00Kgm

Mu/0.138fckb =
400.00mm

Effective depth provided(Assuming 50mm cover) d =


Mu/bd2 =

215.18mm

342.00mm

1.366

From table 2 of SP 16,percentage of steel required =


Area of steel required =

0.407
1391.94sqmm

Hence provide 16mm dia HYSD bars@ 125mm c/c spacing


Hence Ast provided =

1607.68sqmm

Check for shear:The critical section for beam shear is at distance of 'd' from the face of the support
Hence,the factored design shear force V Fd =
at a distance 'd' from the face of the support

Nominal shear stress Tv =

103.73KN

0.30N/sqmm <2.8 N/sqmm


(As per Table 20 of 1S 456)

Hence,the section is safe from shear point of view

Assumed percentage area of the steel reinforcement =

0.47%

The design shear strength of concrete for the above steel percentage from
Table 19 of IS 456 is
0.466
0.466>0.3
Hence,the depth provided is safe from beam shear point of view
Hence,no shear reinforcement is required.
Provide temperature re inforcement @ 0.15%
Area required =

450.00sqmm

Provide 1/3rd of above reinforcement on earthen side =

150.00sqmm

Provide 8mm dia @ 200mm c/c on earthen side


Provide 2/3rd of above reinforcement on other side =

300.00sqmm

Provide 8mm dia @ 150mm c/c on other side


Provide 10mm bars at 300mm c/c vertically on the outer face to support horizontal rods

Design of Toe:-

Length of toe =

1.00m

Downward load intensity due to self weight =


Downward load intensity due to soil including surcharge =

3000.00Kg/m
0.00Kg/m

TOTAL

3000.00Kg/m

The upward pressure distribution below the base slab is as given below:F

G
4147.39Kg/sqm

11213.31

1.00m

0.40m

1.60m

The upward pressure intensity at point 'F' is

8858.00Kg/sqm

The upward pressure intensity at end of toe is

11213.31Kg/sqm

Total upward pressure force on heel portion due to soil reaction =

10035.66Kg/m

The distance of centroid of upward soil reaction from 'F' is =

0.52m

The distance of centroid of downward load intensity from 'G' is =

0.50m

Resultant moment =

3714.10Kg-m/m

Factored bending moment Mu =


Effective depth required d =
Over all depth provided =

5571.16Kgm
Mu/0.138fckb =
400.00mm

Effective depth provided(Assuming 50mm cover) d =


Mu/bd2 =

127.08mm

342.00mm

0.476

From table 2 of SP 16,percentage of steel required =

0.14

Min.percentage of steel as per IS 456 =

0.15

Area of steel required =

513.00sqmm

Hence provide 12mm dia HYSD bars@ 150mm c/c spacing


Hence Ast provided =

753.60sqmm

Check for shear:The critical section for beam shear is at distance of 'd' from the face of the support
Hence,the factored design shear force V Fd =

105.53KN

at a distance 'd' from the face of the support

Nominal shear stress Tv =

0.31N/sqmm <2.8 N/sqmm


(As per Table 20 of 1S 456)

Hence,the section is safe from shear point of view

Assumed percentage area of the steel reinforcement =

0.22%

The design shear strength of concrete for the above steel percentage from
Table 19 of IS 456 is
0.339
0.339>0.32
Hence,no shear reinforcement is required.
Provide temperature re inforcement @ 0.15%
Area required =

600.00sqmm

Taking 10mm dia HYSD bars,the spacing comes to 150mm


Hence,provide 10mm dia bars @ 150mm c/c

WALL

4.20m
4.20m
0.00m
1800Kg/Cum
M20
Fe415
30
87.32
0
15
0Kg/sqm
11000Kg/sqm
0.60m
25N/sqmm
415N/sqmm
2500Kg/Cum
2400Kg/Cum

0.40m

2.00m
0.40m
0.20m
1.00m

345.6Kg/sqm

2764.8Kg/sqm

6915.15Kg

2203.06Kg

0.13m
7257.6Kg/m
1.54m

Lever arm about C

Moment(Kg-m)

1.10

2310.00

1.27

1330.00

1.500

4500.00

2.00

29376.00

1.07

2357.27
39873.27

1.54m

here is no uplift

nce,the structure is safe


10649.33Kgm
39873.27Kgm

-10649.33
29223.94

o support horizontal rods

167.4666666667

334.9333333333

287.0857142857

DESIGN OF CANTILEVER RETAINING WALL


Data:Height of Retaining wall(h) =
Height of wall above G.L=
Height of wall below G.L=
Density of back fill soil&material in toe portion(y) =
Grade of concrete =
Grade of steel =
Ground water Table level =
Angle of shearing resistance of back fill material&material at toe portion(Q) =
Angle of face of wall supporting earth with horizontal(a)(In degrees)
(in clock wise direction)
Slope of back fill(b) =
Angle of wall friction (q) =
Undrained Cohesion ( c) =
Safe bearing capacity(SBC) =
Surcharge over the back fill(s) =
(Assumed)
Characteristic compressive strength =
Tensile strength of steel =
Unit weight of RCC =
Unit weight of PCC =

Coefficient of active earth pressure by Coulomb's theory


Ka =

Sin(a+Q)
sina

Sin(a+Q) =
Sin(a-q) =
Sina =
Sin(Q+q) =
Sin(Q-b) =
Sin(a+b) =

sin(a-q)

SIN[3.14*(87.44+30)/180] =
SIN[3.14*(87.44-15)/180] =
SIN[3.14*(87.44)/180] =
SIN[3.14*(30+15)/180] =
SIN[3.14*(30-0)/180] =
SIN[3.14*(87.44+0)/180] =

From the above expression,


Ka =

0.32

Dimensions of the Cantilever wall(Assumed for preliminary design):Thickness of base slab =


Width of the heel slab =
Thickness of stem at bottom =
Thickness of stem at top =

sin(Q+q)sin(Q-b)
sin(a+b)

0.888
0.953
0.999
0.707
0.5
0.999

Length of the toe =

4.39m

C
1.20m

2.50m

Earth pressure at top including surcharge = K ays =

Earth pressure at bottom including surcharge = K ay(s+h) =

Pressure distribution is as shown below:345.6

4.39m

2874.2

345.6

Area of the rectangular portion =


Area of the triangular portion =

1517.18
6308.96
7826.14

Taking moments of the areas about the toe of the wall


S.No
1
2

Description

Area

Lever arm

Moment

Rectangular
Triangular

1517.18
6308.96

2.195
1.4633333333

3330.21
9232.11

7826.14
Height from the bottom of the wall =

12562.3
1.61m

The active Earth pressure acts on the abutment as shown below:-

0.20

17.56

4.390m
1.61m
87.44

0.40m
0.07
Total earth pressure acting on the wall per 1m length P =

7826.14Kg

Horizontal component of the earth pressure P h =

Vertical component of the earth pressure P v =

Eccentricity of vertical component of earth pressure =


Total earth pressure =
It acts at a hieght of
from the base

Stability calculations:Load(Kg)
Weight of the rectangular portion of stem =

2195.00Kg

Weight of the rectangular portion of stem =

1097.50Kg

Wieght of base slab =

3700.00Kg

Wieght of soil on heel including surcharge =

19760.40Kg

Vertical component of earth pressure =

2360.02Kg
29112.92Kg

Note:-Weight of soil on the toe is neglected on the assumption that,it is scoured.


Horizontal earth pressure force =

7461.82

Lever arm x =

M=

1.74m

V
Eccentricuty e = b/2-x =

0.11m

Maximum stress =

P/A(1+6e/b) =

Minimum stress =

P/A(1-6e/b) =

<b/6

Hence there is no uplift

9271.9 < 1.5*SBC

6464.81

Coefficient of friction between soil and footing u =

0.5

Factor of safety against sliding =(uFxW)/Ph =

1.95 >1.5 Hence,the structure is safe

Moment of overturning force,ie,Horizontal component of earth pressure about toe 'C' =


Moment of restoring forces about toe 'C' =
Factor of safety against overturning =

5.24 >2.0 Hence safe.

Design of heel:Length of heel =

2.10m

Downward load intensity due to self weight of base slab =

3700.00Kg/m

Downward load intensity due to soil including surcharge =

19760.40Kg/m

TOTAL

23460.40Kg/m

The upward pressure distribution below the base slab is as given below:F

G
6464.81Kg/sqm

9271.9

1.20m

0.40m

2.10m

The upward pressure intensity at point 'F' is

8361.49Kg/sqm

The upward pressure intensity at point 'G' is

8058.02Kg/sqm

Total upward pressure force on heel portion due to soil reaction =

15248.97Kg/m

The distance of centroid of upward soil reaction from 'G' is =

1.01m

The distance of centroid of downward load intensity from 'G' is =

1.05m

Resultant moment =

9207.50Kg-m/m

Factored bending moment Mu =

Effective depth required d =

13811.26Kgm

Mu/0.138fckb =

Over all depth provided =

223.70mm

400.00mm

Effective depth provided(Assuming 50mm cover) d =


Mu/bd2 =

342.00mm

1.181

From table 2 of SP 16,percentage of steel required =

0.57

Area of steel required =

1949.40sqmm

Hence provide 16mm dia HYSD bars@ 100mm c/c spacing


Hence Ast provided =

2009.60sqmm

Check for shear:The critical section for beam shear is at distance of 'd' from the face of the support
Hence,the factored design shear force V Fd =
at a distance 'd' from the face of the support

Nominal shear stress Tv =

123.17KN

0.36N/sqmm <2.8 N/sqmm


(As per Table 20 of 1S 456)

Hence,the section is safe from shear point of view

Assumed percentage area of the steel reinforcement =

0.59%

The design shear strength of concrete for the above steel percentage from

Table 19 of IS 456 is
0.51
0.51>0.36
Hence,the depth provided is safe from beam shear point of view
Hence,no shear reinforcement is required.
Provide temperature re inforcement @ 0.15%
Area required =

600.00sqmm

Taking 12mm dia HYSD bars,the spacing comes to

130.95mm

Hence provide 10mm dia bars @ 125mm c/c

Design of wall or stem:Factored bending moment Mu =

Effective depth required d =


Over all depth provided =

17966.30Kgm

Mu/0.138fckb =
400.00mm

Effective depth provided(Assuming 50mm cover) d =


Mu/bd2 =

255.14mm

342.00mm

1.536

From table 2 of SP 16,percentage of steel required =


Area of steel required =

0.477
1631.34sqmm

Hence provide 16mm dia HYSD bars@ 125mm c/c spacing


Hence Ast provided =

1747.48sqmm

Check for shear:The critical section for beam shear is at distance of 'd' from the face of the support
Hence,the factored design shear force V Fd =

111.93KN

at a distance 'd' from the face of the support

Nominal shear stress Tv =

0.33N/sqmm <2.8 N/sqmm


(As per Table 20 of 1S 456)

Hence,the section is safe from shear point of view

Assumed percentage area of the steel reinforcement =

0.51%

The design shear strength of concrete for the above steel percentage from
Table 19 of IS 456 is
0.483
0.483>0.33
Hence,the depth provided is safe from beam shear point of view
Hence,no shear reinforcement is required.
Provide temperature re inforcement @ 0.15%
Area required =

450.00sqmm

Provide 1/3rd of above reinforcement on earthen side =

150.00sqmm

Provide 8mm dia @ 200mm c/c on earthen side


Provide 2/3rd of above reinforcement on other side =

300.00sqmm

Provide 8mm dia @ 150mm c/c on other side


Provide 10mm bars at 300mm c/c vertically on the outer face to support horizontal rods

Design of Toe:Length of toe =

1.20m

Downward load intensity due to self weight =


Downward load intensity due to soil including surcharge =

3700.00Kg/m
0.00Kg/m

TOTAL

3700.00Kg/m

The upward pressure distribution below the base slab is as given below:F

G
6464.81Kg/sqm

9271.9

1.20m

0.40m

2.10m

The upward pressure intensity at point 'F' is

8361.49Kg/sqm

The upward pressure intensity at end of toe is

9271.90Kg/sqm

Total upward pressure force on heel portion due to soil reaction =

10580.03Kg/m

The distance of centroid of upward soil reaction from 'F' is =

0.61m

The distance of centroid of downward load intensity from 'G' is =

0.60m

Resultant moment =

4237.27Kg-m/m

Factored bending moment Mu =


Effective depth required d =

6355.90Kgm
Mu/0.138fckb =

Over all depth provided =

151.75mm

400.00mm

Effective depth provided(Assuming 50mm cover) d =


Mu/bd2 =

342.00mm

0.543

From table 2 of SP 16,percentage of steel required =

0.158

Min.percentage of steel as per IS 456 =

0.15

Area of steel required =

540.36sqmm

Hence provide 12mm dia HYSD bars@ 150mm c/c spacing


Hence Ast provided =

753.60sqmm

Check for shear:The critical section for beam shear is at distance of 'd' from the face of the support
Hence,the factored design shear force V Fd =

103.20KN

at a distance 'd' from the face of the support

Nominal shear stress Tv =

0.30N/sqmm <2.8 N/sqmm


(As per Table 20 of 1S 456)

Hence,the section is safe from shear point of view

Assumed percentage area of the steel reinforcement =

0.22%

The design shear strength of concrete for the above steel percentage from
Table 19 of IS 456 is

0.336
0.339>0.30
Hence,no shear reinforcement is required.
Provide temperature re inforcement @ 0.15%
Area required =

600.00sqmm

Taking 10mm dia HYSD bars,the spacing comes to


Hence,provide 10mm dia bars @ 125mm c/c

130.95mm

NG WALL

4.39m
4.39m
0.00m
1800Kg/Cum
M20
Fe415
30
87.44
0
15
1600Kg/sqm
6500Kg/sqm
0.60m
20N/sqmm
415N/sqmm
2500Kg/Cum
2400Kg/Cum

0.40m
2.50m
0.40m
0.20m

1.20m

345.6Kg/sqm

2874.2Kg/sqm

7461.82Kg

2360.02Kg

0.13m
7826.1Kg/m
1.61m

Lever arm about C

Moment(Kg-m)

1.30

2853.50

1.47

1609.67

1.850

6845.00

2.45

48412.98

1.27

2997.23
62718.38

1.61m

-11977.53

50740.85

here is no uplift

Hence safe

nce,the structure is safe


11977.53Kgm
62718.38Kgm

o support horizontal rods

167.4666666667

334.9333333333

287.0857142857

DESIGN OF RAFT FOR SKEW BRIDGE


Name of the work:-Construction of High Level Bridge at 1/2Km on the R/F BN Road to Chelisingam
The plan of the raft and position of abutments& piers is as shown below:-

38892
6084

6800
4128

9506

5600

7387

Length of the Raft:-

38.892m

Width of the Raft:-

8.75m

Total load on the Raft:Dead Load:Wt.of Deck slab =

4028.00Kn

Wt.of wearing coat =

559.45Kn

Wt.of dirt wall over abutments =

150.78Kn

Wt.of bed blocks over piers =

195.60Kn

Weight of kerb =

237.95Kn

Weight of hand rails(verticals) =

232.40Kn
54.15Kn

Weight of hand rails(horizontals) =


Wt.of abutments
Footing-I =
Footing-II =
Footing-III =
Footing-IV =
Wt.of abutments =

586.80Kn
645.48Kn
704.16Kn
0.00Kn
1941.52Kn

Wt.of piers
Footing-I =
Footing-II =
Footing-III =
Footing-IV =
Wt.of piers =

704.16Kn
938.88Kn
1173.60Kn
0.00Kn
2505.24Kn
Total

Dead load stress =

43.07Kn/Sqm

Live Load:Taking two lanes of IRC Class-A loading


Wheel width in the direction of movement =0.2+0.2+0.25/2 = 0.625m

14658.17Kn

2.7

2.7
1.1

11.4
3.2

11.4
1.2

6.8
4.3

6.8
3.0

6.8
3.0

6.8
3.0

14.467

0.625

38.892m

Centre of gravity of loading from 1st 2.7t load =


=
Centre of gravity from the end of raft =

8.72m
9.345m

Eccentricity =

10.101m

Stress due to live load = 2xP(1+6e/b)


(Taking two lanes)
A
Max.stress =

25.29Kn/Sqm

Min.stress =

-18.91Kn/Sqm

Total stress due to dead load and live load


Max.Stress =

68.36Kn/Sqm

Min.Stress =

24.16Kn/Sqm

Assuming the depth of raft as 60cm


Stress due to self weight of raft =

15.00Kn/Sqm

Stress due to wieght of base concrete =


Hence,the Max.stress on the soil =

4.80Kn/Sqm
88.16Kn/Sqm

Which is less than 11t/sqm(Soil testing report)


Hence safe.
Net Max.upward pressure acting on Raft =

68.36Kn/Sqm

Net Min.upward pressure acting on Raft =

24.16Kn/Sqm

The design stress =

46.26Kn/Sqm

Hence,the UDL/m width on the raft =

46.26Kn/m

Design of Raft:The raft will be analysed as a continuous beam of 1m width with the loading
as shown below:-

3.65

5.60

6.80

6.80

6.80

UDL of 46.26Kn/m
After analysis the bending moment diagram on TENSION SIDE side is enclosed:
From the above BMD,it can be inferred that,
Max.bending moment at supports =

308.15KNm

Max.bending moment in span =

118.00KNm

Design Negative bending moment Mu =

462.23KNm

Design Positive bending moment Mu =

177.00KNm

Effective depth required d =


Over all depth provided =

Mu/0.138fckb =

366.03mm

600.00mm

Effective depth provided(Assuming 50mm cover) d =

542.00mm

Bottom steel at end supports:Mu/bd2 =

1.573

From table 3 of SP 16,percentage of steel required =


Area of steel required =

0.474
2569.08sqmm

Hence provide 20mm dia HYSD bars(Cranks)@ 200mm c/c spacing as per drawing
along with 16mm dia HYSD bars extra@ 200mm c/c
Hence Ast provided at bottom =
Bottom steel at intermediate supports:-

2574.80sqmm

Mu/bd2 =

0.982

From table 3 of SP 16,percentage of steel required =


Area of steel required =

0.291
1577.22sqmm

Hence provide 20mm dia HYSD bars(Cranks)@ 200mm c/c spacing as per drawing
Hence Ast provided at bottom =

1570.00sqmm

Top steel:Mu/bd2 =

0.603

From table 3 of SP 16,percentage of steel required =


Area of steel required =

0.175
948.50sqmm

Hence provide 20mm dia HYSD bars@ 200mm c/c spacing as per drawing
Hence Ast provided at top =

1570.00sqmm

Provide distribution reinforcement of 0.15% both at top and bottom


Area =

900.00sqmm

Adopting 12mm dia bars,the spacing required is =

174.44mm

Hence provide 10mm dia bars @ 150mm c/c spacing at top& bottom as distribution steel
Hence distribution steel provided =

1046.67sqmm

Effective depth = 300-50-6 =

0.244m

Clear span between abutments = 3.00-2x(0.125+2x(0.15)) =

2.150m

Effective span = 2.15+0.244/2 =

2.27m

For continuous slab,clear span will be the effective span,effective span =


The raft is proposed to be designed for the Max.stress of 5.47t/sqm
Assuming 1m width of raft,the UDL on the raft is

88.160t/Sqm

The raft is treated as simply supported beam with over hangs


Hence,the Max.positive moment = wl2/8 =
Max.Negative moment for over hangs = wl12/2 =

56.89t-m
3.97t-m

Max.negative moment =

3.970t-m

Max.positive moment =

56.890t-m

Hence,the design moment =

56.890t-m

Depth required = 3.53x105


7.7x100

85.955289

Hence provide overall depth of 30cm,the effective depth available is


300-50-6 =

24.4

Area of steel required = 3.53x105


at centre
2000x0.916x24.4

127.27sqcm

Spacing of 12mm dia bars required = 1.13x100/7.9 =

14.303797468

However provide 12mm bars at 125mm c/c at centre

Area of steel required = 0.25x105


for over hangs
2000x0.916x24.4

8.88sqcm

Spacing of 12mm dia bars required = 1.13x100/0.56 =

201.78571429

However provide 12mm bars at 250mm c/c


Provide distribution reinforcement of 0.12% both at top and bottom
Area =

3.60sqcm

Adopting 10mm dia bars,the spacing required is = 0.785x100/3.6 =

21.8055556

Hence provide 10mm dia bars @ 175mm c/c spacing

The details of Reinforcement is as shown below:-

12mm bars@ 125 c/c(Curtail 50% of cranks at the centre of abutment

3.00m

12mm bars@250mm c/c

8750
5600

61.26

5.60

3.65

2.27m

1.1304

1.1304

0.785

12mm bars@250mm c/c

Hydraulic design
Hydraulic Particulars:1.Maximum Flood Level

7.950m

2.Ordinary Flood level


3.Lowest Bed level

5.620

4.Average bed slope


(1 in 15000)

0.000067

5.Rugosity Coefficient(n)
(As per table 5 of IRC:SP 13)

0.033

6.Vertical clearence proposed


(As per clause 15.5 of IRC:SP 13&as per profile)

0.450

6.Bottom of deck proposed


(MFL+Vertical clearence)

8.555

7.Road Crest level


(Bottom of deck level+thickness of deck slab)

9.280

8.Width of carriage way

5.500

Discharge Calculations:1)Area Velocity method:a)At the proposed bridge site:Maximum Flood level
Slope
Rugosity Coefficient
S.No

1
2
3
4
5
6
7
8
9
10
11
12
13

7.950m
0.000067
0.033

Chainage R.L

0
5
10
15
20
25
30
35
40.0
45.0
51.7
55.0
60.0

Depth of
flow
(m)

9.96
9.95
9.930
8.580
7.850
7.560
7.660
7.530
6.790
6.710
9.770
9.800
9.820

0.00
0.00
0.00
0.00
0.10
0.39
0.29
0.42
1.16
1.24
0.00
0.00
0.00

Average
depth of
flow
(m)

Distance
(m)

0.00
0.00
0.00
0.00
0.05
0.25
0.34
0.36
0.79
1.20
0.62
0.00
0.00

0.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
6.70
3.30
5.00

Area
(Sqm)

0.00
0.00
0.00
0.00
0.25
1.23
1.70
1.78
3.95
6.00
4.15
0.00
0.00
19.05

Hydraulic Radius

R=

Total area/Wetted perimeter =

Velocity V =

1/nX(R2/3XS1/2)

Discharge Q =

AXV

0.45
0.15m/sec
2.86Cumecs

b)At 400m downstream of proposed bridge site(As per IRC SP-13):Maximum Flood level
Slope
Rugosity Coefficient
S.No

7.550m
0.00007
0.033

Chainage R.L

1
2
3
4
5
6
7
8
9
10
11
12
13

Depth of
flow
(m)

9.64
9.63
9.610
8.260
7.530
7.240
7.060
6.870
6.470
6.390
9.450
9.480
9.500

0
5
10
15
20
25
30
35
40.0
45.0
53.0
55.0
60.0

Average
depth of
flow
(m)

0.00
0.00
0.00
0.00
0.02
0.31
0.49
0.68
1.08
1.16
0.00
0.00
0.00

Hydraulic Radius

R=

Velocity V =

1/nX(R2/3XS1/2)

Discharge Q =

AXV

Distance
(m)

0.00
0.00
0.00
0.00
0.01
0.17
0.40
0.59
0.88
1.12
0.58
0.00
0.00

Area
(Sqm)

0.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
8.00
2.00
5.00

0.00
0.00
0.00
0.00
0.05
0.82
2.00
2.93
4.40
5.60
4.64
0.00
0.00
20.44

Total area/Wetted perimeter =

0.48
0.15m/sec
3.07Cumecs

c)At 400m Upstream of proposed bridge site(As per IRC SP-13):Maximum Flood level
Slope
Rugosity Coefficient
S.No

1
2

8.350m
0.00007
0.033

Chainage R.L

0
5

Depth of
flow
(m)

10.28
10.27

0.00
0.00

Average
depth of
flow
(m)

Distance
(m)

0.00
0.00

0.00
5.00

Area
(Sqm)

0.00
0.00

3
4
5
6
7
8
9
10
11
12
13

10.250
8.900
8.170
7.880
7.980
7.850
7.680
7.680
10.090
10.120
10.140

10
15
20
25
30
35
40.0
45.0
53.0
54.0
60.0

0.00
0.00
0.18
0.47
0.37
0.50
0.67
0.67
0.00
0.00
0.00

Hydraulic Radius

R=

Velocity V =

1/nX(R2/3XS1/2)

Discharge Q =

AXV

0.00
0.00
0.09
0.33
0.42
0.44
0.59
0.67
0.34
0.00
0.00

5.00
5.00
5.00
5.00
5.00
5.00
5.00
5.00
8.00
1.00
6.00

Total area/Wetted perimeter =

0.00
0.00
0.45
1.63
2.10
2.18
2.93
3.35
2.68
0.00
0.00
15.31

0.36
0.13m/sec
1.99Cumecs

Design Discharge =

72.330Cumecs

Design Velocity =

0.15m/sec

Afflux Calculations(H.F.L Condition):Un obstructed linear water way =

L=

Total water way provided = l =

41.70m
30.00m

Design discharge Q =

72.33Cumecs

Linear water way L =

30.00m

Depth of down stream water Dd =

0.70m

Width of the channel at HFL =

41.70m

Case(a) Assume that afflux is less than 1.4Dd:Using Orifice formula for calculation of discharge
Q = Co X (2g)1/2 X L X Dd X [h+(1+e)u2/2g]1/2
In the present case,
l/L =

0.72

Corresponding to this value the coefficient Co from IRC SP:13--2004 =


Corresponding to this value the coefficient e from IRC SP:13--2004 =
Hence
0.8081038 =

h+

0.0968399592 u2 ------------- (1)

0.865
0.9

At just upstream of the bridge


Q = W X (Dd + h) X u
1.7345324 =
u=

(0.70+h) X u
1.7345323741 ----------------(2)
(0.70+h)

Substituting,the above value in eq (1)


'2
0.8081038 =

h+ 0.096840

Solving by trial and error method,assume h =

1.73453
(0.70+h)

0.30m
0.808104 = 1.193933716

assume h =

Not satisfied

0.057m
0.808104 = 0.8076853719

Hence afflux h =

0.057m

Velocity u =

2.291m/sec

Case(b) Assume that afflux is more than 1.4Dd:Applying Broad crested wier formula,
Q = 1.706 CW LH3/2
As per clause 15.2 of IRC SP:13-2004,the value of CW for narrow bridge opening with or without floor =
Hence H =

1.31m

H = Du + u2/2g Du
Du =

1.31m

Again applying Q = Du x W x u
u=

1.324m/sec

Du = H - u2/2g
Hence, Du =

1.221

Hence afflux h = Du - Dd =

0.521

From the above calculations,it is inferred that afflux is less than 1/4 th Dd
and hence afflux to be adopted is from the Orifice formula,which is equal to

Ventway Calculations(H.F.L Condition):-

0.057m

Assuming the stream to be truly alluvial,the regime width is equal to linear waterway required for the drain.
Hence,as per Lacey's silt theory,the regime width W = 4.8Q 1/2 = 4.8*72.330.5 =

40.82m

But the actual top width is much less than the above regime width.Hence,the stream is no truly alluvial in nature.
It is quasi-alluvial.As per IRC:SP--13,the ventway calculations for quasi-alluvial streams are as given below:-

Assuming afflux =
x =
Width of channel at H.F.L(b+h) =
Effective span =
Effective linear water way =
di =
Depth of flow =

0.20m
41.70m
7.32m
36.60m
2.33m

Head due to velocity of approach =

(Vmax2/2g)X[di/(di+x)]2

0.001m

Combined head due to Velocity of approach and


afflux (0.15+0.06)

hi =

0.201m

Velocity through vents

0.90X(2ghi)1/2 =

Vv =

Linear water way required

LWW = Qd/(VvXdi) =

No.of vents required =

LWW /LC

1.79m/sec
17.37m

2.3729508197
Say---3 Vent

In quasi-alluvial streams,the actual width of the stream should not be reduced,as it results in enhanced scour
depth and expensive training works.
Hence No.of vents required as per the width of the stream at H.F.L=

5.6967213115

No.of vents to be provided

5Nos

No.of piers =

4Nos

Scour Depth Calculations:As per the clause 101.1.2 of IRC:5--1985,the design discharge should be increased by 30% to ensure adequate
margin of safety for foundations and protection works
Hence,the discharge for design of foundations =

1.30XDesign Discharge =

Lacey's Silt factor ' f ' = 1.76Xm1/2(Due to pebbles&boulders in the bed) =


Discharge per metre width of foundations = q =

Normal scour depth D = 1.34(q2/f)1/3 =

Maximum scour depth Dm = 1.5XD =

(For design of abutment foundations,as per clause 110.1.4.2 of IRC:5--1985)

Depth of foundation = Dm + Max.of 1.2m or 1/3 Dm =

Bottom level of foundation =


Depth of foundation below low bed level =
The Minimum Safe Bearing capacity of the soil is considered as 11 KN/m2 at a depth of 2.00m below LBL
Hence open foundation in the form of raft foundation is proposed at a depth of 2.90m below LBL
,ie,at a level of
As the foundations are proposed below the Max.scour level,bed protection is not needed from scour depth
considerations.But,the velocity through vents is more than 2m/s.Hence,it is advisable to provide flexible apron
to protect against excessive scouring action.
Design of LAUNCHING/FLEXIBLE APRONS:Size of stones as per clause 5.3.7.2 of IRC 89-1985
Diametre (d) = (Vmax/4.893)2 =

0.13m
0.30m

Say

Weight of each stone considering the specific gravity of stone as 2.65


Weight of stone =4/3x x(d/2)3 x 2.65 x 1000 =
Say

37.48Kg
40Kg

Weight of each stone shall not be less than 40 Kg.

Dimensions of apron as per clause 5.3.5.2 of IRC 89-1985


( T ) = 0.06 x (Qdf)1/3 =
Thickness of apron at inner edge(near raft) = 1.5 x T =
Say
Thickness of apron at outer edge = 2.25 x T =
Say

0.275
0.413m
0.60m
0.619m
0.90m

Hence provide a thickness of 0.60m at near end and 0.9m at the outer end
Width of Launching Apron on U/S Side:The launching aprons are designed to reach a level of 1.50 times the normal scour depth
1.5 x D =
Bottom level of apron after launching = HFL-1.5 X D =

3.450m
4.50m

Depth below top of the raft =

-0.60m

The apron should launch in a slope of 1V : 2H as per clause 5.3.7.6 of IRC 89


Hence the width of launching apron at U/S =

-1.20m

As per the clause 6.4.2(vi),of IRC SP:82-2008,minimum width =

4.0m

Width of Launching Apron on D/S Side:The launching aprons are designed to reach a level of 2.00 times the normal scour depth
2.0 x D =

4.600m

Bottom level of apron after launching = HFL-2 X D =

3.35m

Depth below top of the raft =

0.55m

The apron should launch in a slope of 1V : 2H as per clause 5.3.7.6 of IRC 89


Hence the width of launching apron at D/S =
As per the clause 6.4.2(vi),of IRC SP:82-2008,minimum width =

1.10m
6.0m

Design of Protection works:Afflux =

0.057m
di =

Depth of flow =

#VALUE!

Head due to velocity of approach =

(Vmax2/2g)X[di/(di+x)]2

#VALUE!

Combined head due to Velocity of approach and


afflux

hi =

#VALUE!

Velocity through vents

0.90X(2ghi)1/2 =

#VALUE!

LWW = Qd/(VvXdi) =

#VALUE!

Vv =

Linear water way required


Area available for flow at H.F.L =

1.99sqm

As per the clause 6.4.2(i),of IRC SP:82-2008,the post construction velocity under the structure should not exceed
2 m/s and the intensity of discharge is limited to 3m3/m except in the case of properly designed raft foundation with adequate
protective works.
Hence Vlim. =

2.00m/sec

Discharge,that can be passed over the causeway safely =

3.98Cumecs
Hence O.K

As per the clause 5.1.3(iv),of IRC SP:82-2008 for the beds consisting of boulders upto 200mm size,the permissible
velocity through vents is 2.5m/s and for beds containing larger sized boulders or rocky strata permissible velocity is 6m/s.
As the bed of the proposed stream is rocky strata,increased velocity of 2.68m/sec is allowed through vents without
rigid floor protection.Hence rigid floor protection is not proposed.
However,suitably designed flexible aprons with cut-off walls are proposed on both upstream and down stream sides to
protect against the probable eddies formed due to uneven spacing of vents along the causeway.
Design of cut-off walls/Toe walls:-

Though,it is sufficient to take the D/S side cut-off upto 1.27 times the normal scour depth as per
caluse 703.2.3.2 of IRC 78-1983 considering that the reach is straight.
1.27XNormal scour depth from HFL =

2.92m

Depth of bottom of Cut-off wall from HFL =

2.92m

Bottom level of cut-off wall =

#VALUE!

Depth of bottom of D/S side Cut-off wall from LBL

#VALUE!

As per the clause 6.4.2(v),of IRC SP:82-2008,the minimum depth of cut-off wall on U/S side is 2.0m below bed
level and 2.5m below bed level on D/S side.
Depth of bottom of D/S side Cut-off wall from LBL

2.50m

Depth of bottom of U/S side Cut-off wall from LBL

2.00m

As rigid floooring is not being proposed,there is no need to provide cut-off walls.But toe walls are proposed to a depth
of 0.90m to protect the flexible apron.
Design of LAUNCHING/FLEXIBLE APRONS:Size of stones as per clause 5.3.7.2 of IRC 89-1985
Diametre (d) = (Vmax/4.893)2 =

0.81m
0.30m

Say

Weight of each stone considering the specific gravity of stone as 2.65


Weight of stone =4/3x x(d/2)3 x 2.65 x 1000 =
Say

37.48Kg
40Kg

Weight of each stone shall not be less than 40 Kg.

Dimensions of apron as per clause 5.3.5.2 of IRC 89-1985


( T ) = 0.06 x (Qdf)1/3 =
Thickness of apron at inner edge(near raft) = 1.5 x T =

0.275
0.413m

Scour Depth Calculations:As per the clause 101.1.2 of IRC:5--1985,the design discharge should be increased by 30% to ensure adequate
margin of safety for foundations and protection works
Hence,the discharge for design of foundations =

1.30XDesign Discharge =
(1.3*16.95)

Lacey's Silt factor ' f ' = 1.76Xm1/2(Due to pebbles&boulders in the bed) =


Discharge per metre width of foundations = q =

(22.54/8.00)
Normal scour depth D = 1.34(q2/f)1/3 =
[1.34*(2.818^2/1.0)0.33]
Maximum scour depth Dm = 1.5XD =
(For design of abutment foundations,as per clause 110.1.4.2 of IRC:5--1985)
(1.5*2.66)
Depth of foundation = Dm + Max.of 1.2m or 1/3 Dm =
(3.99+1.2)
Bottom level of foundation = (9.23-5.19)
Depth of foundation below low bed level = [6.54-4.75)] =
The Minimum Safe Bearing capacity of the soil is considered as 15 KN/m2 at a depth of 1.50m below LBL
Hence open foundation in the form of raft is proposed at a depth of 1.80m below LBL,ie,at a level of
Though, cut-off walls and aprons are not required from scour depth point of view,down stream side apron with
cut-off wall is advisable due to check dam located on upstream side.

Wetted
perimeter
(m)

0.00
0.00
0.00
5.18
5.05
5.01
5.00
5.00
5.05
5.00
7.37
0.00
0.00
42.66

Wetted
perimeter
(m)

0.00
0.00
0.00
5.18
5.05
5.01
5.00
5.00
5.05
5.00
7.37
0.00
0.00
42.66

Wetted
perimeter
(m)

0.00
0.00

0.00
5.18
5.05
5.01
5.00
5.00
5.05
5.00
7.37
0.00
0.00
42.66

0.94

alluvial in nature.

hanced scour

ensure adequate

96.20Cumecs

2.00
3.207

2.30m

3.45m

xible apron

4.65m

3.30m
2.32m

+3.280m

<30.00m

hould not exceed


ion with adequate

>96.20

size,the permissible
locity is 6m/s.

ough vents without

down stream sides to

.0m below bed

e proposed to a depth

ensure adequate

96.20Cumecs

1.80
#DIV/0!

apron with

#DIV/0!

#DIV/0!

#DIV/0!

#DIV/0!
#DIV/0!

#DIV/0!

Potrebbero piacerti anche