Table of Contents
1.
INTRODUCTION
2.
3.
DC PROTECTIONS
4.
AC PROTECTIONS
10
5.
6.
16
7.
SYSTEM SUPERVISION
18
15
1. INTRODUCTION
This document describes the common features
for a complete HVDC Protection System.
2. GENERAL PROTECTION
PHILOSOPHY
Bipole aspects
The aim with the overall protection philosophy,
especially for bipole related protective functions
shall be to avoid any undue bipole outage during
any circumstances.
a)
b)
c)
d)
e)
3. DC PROTECTIONS
Converter protections
SET 1 CONVERTER PROTECTIONS, SYSTEM A
SHORT CIRCUIT
PROTECTION
COMMUTAION FAILURE
PROTECTION
HIGH ANGLE
SUPERVISION
OVERCURRENT
PROTECTION
**)
VALVE MISFIRE
PROTECTION
CP
CWT
**)
TC
FP
VOLTAGE STRESS
PROTECTION
THYRISTOR
MONITORING
PR FIR IND
IDL *)
IVY *)
UAC
Y
DC current measuring device
AC current transformer
IANC *)
IVD *)
ICN *)
IDNC *)
IF1 *)
UAC *)
IDNE *)
ALP
GAM
CWT
BACKUP
UD SUPERVISION
(Possible Control
function)
BACKUP
SHORT CIRCUIT
PROTECTION **)
BACKUP
OVERCURRENT
PROTECTION **)
*)
Figure 1
the AC currents IVY and IVD in combination
with DC currents IDL and IDNE. During
commutation failures the DC current is higher
than the AC conductor current, which is detected
by the protection.
Back up UD Supervision
DC overcurrent protection
Thyristor monitoring
The thyristor valve monitoring system is a self
supervising system. In every valve control unit
there is a function, detecting if the voltage is
picked up within a specified time by the
corresponding thyristor. At the time the thyristor
picks up the voltage an indication pulse IP is sent
on an optical fiber to the valve control. A failed
thyristor does not pick up voltage and this
condition is detected.
Pole protections
SET 1 POLE PROTECTIONS, SYSTEM A
ELECTRODE LINE
OPEN CIRCUIT
PROTECTION
DC DIFFERENTIAL
PROTECTION
*) Redundant measuring
points for system B
DC LINE/CABLE
GROUND FAULT
PROTECTION
DC FILTER
OVERLOAD
PROTECTION
AC current transformer
DC current measuring device
IDL *)
UDL
IANC *)
IF2 *)
UDN
ICN *)
IF1 *)
ALP
IDNE *)
DC ABNORMAL
PROTECTION
REDUNDANT DC
DIFFERENTIAL
PROTECTION
REDUNDANT DC
FILTER OVERLOAD
PROTECTION
POLEP.PRE
DC HARMONIC
PROTECTION
Figure 2
the converter. To detect ground faults within the
protective zone the direct currents IDL and
IDNE are measured in combination with the AC
conductor currents IVY and IVD neutral bus
currents IANC and ICN in addition with the DC
filter currents IF1 and IF2.
DC harmonic protection
DC harmonic protection detects abnormal
harmonics in the converter current, generated at
control equipment malfunction or during valve
and AC network disturbances. The direct current
is filtered for the fundamental and second
harmonic frequencies.
DC differential protection
The protective zone of the DC differential
protection is from the converter transformer
secondary bushings to the measurements of both
the line and electrode currents, at the DC side of
7
DC switchyard protections
DC BIPOLE SWITCH YARD
SET 1 BIPOLE PROTECTIONS, SYSTEM A, POLE 1
BIPOLE NEUTRAL
DIFFERENTIAL
PROTECTION
TRANSFER BREAKER
PROTECTION, NBS,
NBGS, GRTB, MRTB
METALLIC RETURN
GROUNF FAULT
PROTECTION
DC current measuring
device
ELECTRODE LINE
LONGIT DIFF.
PROTECTION
*) To pole 2 bipole
protection setup
IDEL **)
POLE 1 DC LINE
IDNE 1 *)
POLE 1 NEUT.BUS
MRTB
NBS 1
ELECTR. LINE/CABLE
IDME *)
POLE 2 NEUT.BUS
IDEL *)
NBS 2
GRTB
IDNE 2 *)
X1 *)
NBGS
IDGND *)
POLE 2 DC LINE
STATION GROUND
OVERCURRENT
PROTECTION
TRANSFER BREAKER
PROT. BACKUP, NBS,
NBGS, GRTB, MRTB
METALLIC RETURN
GROUNF FAULT
PROT. BACKUP
ELECTRODE LINE
IMPEDANCE
SUPERVISION
BPP.PRE
Figure 3
SET 2
ELECTRODE CABLE
LONGIT.
DIFFERENTIAL PROT.
ELECTRODE CABLE
UNBALANCE
SUPERVISION
1)
2)
Ex: 1
1)
2)
A1.1 **)
A1.2 **)
A2.1 **)
A2.2 **)
elcp1.pre
Ex: 2
1)
1)
SET 2
X1
ELECTRODE LINE
IMPEDANCE
SUPERVISION
elcp2.pre
10
11
4. AC PROTECTIONS
Converter transformer and AC bus protections
400 kV BUS
RESTRICTED EARTH
FAULT
PROTECTION, Y1, Y2
AND D WINDING
PROTECTIVE RELAYS
FOR THE
TRANSFORMER ( S1 )
*)
UVY
CB
Y2
*)
*)
Y1
*)
*)
UVD
*)
AC CONDUCTOR
GND FAULT AND
XFRM NEUTRAL
O/,PROTECTION.
PROTECTIVE RELAYS
FOR THE
TRANSFORMER ( S2 )
CBUSCL.PRE
Figure 5
12
AC overvoltage protection
The objective is to prevent severe sustained
overvoltage conditions, which could cause
damage to the equipment connected to the AC
bus. The voltage is measured per phase on the
converter AC bus. The protection is sensitive for
fundamental voltage and/or harmonic voltages. In
order to detect an abnormal overvoltage condition
the phase to ground rms and/or peak voltage is
compared to a preset reference.
Overcurrent part:
13
CIRCUIT
BREAKER
SHUNT REACTOR
DIFFERENTIAL
PROTECTION
BREAKER
FAILURE
PROTECTION
CAPACITOR
UNBALANCE
PROTECTION
OVERCURRENT
PROTECTION
PROTECTIVE
RELAYS FOR THE
GROUND FAULT
PROTECTION
BREAKER FAILURE
PROTECTION
*)
***)
*)
SHUNT CAPACITOR
**)
UAC
OVERCURRENT
PROTECTION
REACTOR
*)
GROUND FAULT
PROTECTION
**)
***)
*)
PROTECTIVE
RELAYS FOR THE
REACTOR
SHR.PRE
BACKUP CAP.
UNBALANCE
PROTECTION
REDUNDANT
OVERCURRENT
PROTECTION
REDUNDANT
GROUND FAULT
PROTECTION
SHC.PRE
Figure 6
an unbalance current. The protection orders a
trip when the current exceeds a preset level.
14
AC FILTER (CONTUNE)
UAC
CIRCUIT
BREAKER
*)
AC FILTER (CLASSIC)
ACFCO.PRE
OVER
TEMPERATURE
PROTECTION
CAPACITOR
UNBALANCE
PROTECTION
GROUND
FAULT
PROTECTION
*)
BREAKER
FAILURE
PROTECTION
CAPACITOR
UNBALANCE
PROTECTION
HARMONIC
OVERLOAD
PROTECTION
CAPACITOR
UNBALANCE
PROTECTION
HARMONIC
OVERLOAD
PROTECTION
GROUND
FAULT
PROTECTION
CAPACITOR
UNBALANCE AND
GROUND FAULT
PROTECTION
HARMONIC
OVERLOAD
PROTECTION
**)
***)
BREAKER
FAILURE
PROTECTION
BREAKER FAILURE
PROTECTION
**)
***)
*)
UAC
ACFCOH.PRE
BACKUP CAP.
UNBALANCE
PROTECTION
OVER.
TEMPERATURE
PROTECTION
REDUNDANT
GROUND FAULT
PROTECTION
**)
***)
ACFCL.PRE
*)
BACKUP CAP.
UNBALANCE
PROTECTION
REDUND. HARM.
OVERLOAD
PROTECTION
OVER
TEMPERATURE
PROTECTION
REDUNDANT
GROUND FAULT
PROTECTION
Figure 7
between filters the protection is sensitive only for
the fundamental frequency.
5. APPARATUS PROTECTIVE
RELAYS
Gas detector
The relay detects the gas produced by winding
short circuits and operates if a certain volume
has been collected. The relay also operates when
it detects a shock wave in the oil due to an
internal flashover.
17
6. FAULT CLEARING
ACTIONS
PROTECTION SYSTEM A
SET 1 PROTECTIONS
ANALOG SIGNAL 1
ANALOG SIGNAL 2
>1
CHANGE
OVER REF
CHANGE
OVER DELAY
>1
TRIP REF
TRIP
DELAY
SET 2 PROTECTIONS
R
Q
S
SYS A ACT
PROTECTION SYSTEM B
Figure 8
Control actions
Retarding of the converter
This is normally performed in the rectifier, which
normally operates with firing angles around 15
electrical degrees. Retarding means that the
successive control pulse is delayed in respect to
the previous one. This increases the firing angle
until a full inverter operation is obtained and thus
a limitation of the firing angles has been
achieved. The retarding will reverse the polarity
of the rectifier converter voltage and thereby
extinguish the direct current. To make the
extinguishing of the current more efficient, the
inverter will decrease the firing angle gamma.
Figure 9
Converter actions
SYSTEM A PROTECTIONS
AC BREAKER
ACT. A
TEST
PROTECTION
SET 1
(TRIP A)
CAN 1
(TRIP B)
CAN 2
OPT.
DISTR. A
- V (A)
+ V (A)
TRIP COIL A
ACT. B
PROTECTION
SET 2
OPT.
DISTR. B
(TRIP B)
(TRIP A)
- V (B)
TEST
+ V (B)
TRIP COIL B
SYSTEM B PROTECTIONS
PROTECTION
SET 1
PROTECTION
SET 2
(TRIP A)
CAN 1
(TRIP B)
CAN 2
(TRIP B)
(TRIP A)
OPT.
DISTR. A
OPT.
DISTR. B
ACCB.PRE
Figure 10
Simultaneously with a trip order to the ACbreaker an order to start the breaker failure
protection is executed. If the breaker does not
19
7. SYSTEM SUPERVISION
The HVDC control and protection system is
primarily designed to minimize the need for a
periodic maintenance.
For the protection system this means, that all
parts of the protection system are continuously
supervised and the need for the manual checks is
completely eliminated.
Memory checks