DISEO DE CENTROS DE DATOS

Data Center College

DISEO DE CENTRO DE DATOS - AGENDA

Tendencias Tecnolgicas y de la Industria para Centros de Datos


Tipos de Centro de Datos por Operacin
Estndares

ANSI/TIA
ANSI/BICSI
ISO/IEC
CENELEC

Tecnologas de Red en Salas de Cmputo


Arquitecturas de Cableado

Gestin y Monitoreo de la Infraestructura


Tendencias de Arquitectura en Salas de Cmputo
Conclusiones

Proprietary 2014 Anixter Inc.

TENDENCIAS TECNOLGICAS Y DE LA INDUSTRIA


PARA CENTROS DE DATOS

TRFICO POR DESTINOS


EN CENTROS DE DATOS

Data Centerto-Data Center

7%

Data Centerto-User

17%

Within Data
Center

76%

Data Center-to-Data Center

Data Center-to-User

Within Data Center

Replication,
inter-database links

Web, email, internal


VoD, WebEx, etc.

Storage, production
and development
data, authentication

Source: Cisco

Proprietary 2014 Anixter Inc.

VoD: Video on Demand

ESTNDARES DE CABLEADO

X86 Servers by Ethernet Connection Speed (2012 Pronstico)


Basado en IDC, Dell Oro, Crehan Research e Intel data en el perodo 2H11 1Q12
16
40 GbE
Free

Current Forecastsurely accurate


14
40 GbE
Performance

12

FRINGE
Usuarios que exigen la mayor
parte del ancho de banda

10

PERFORMANCE
Los usuarios demandan
ms rendimiento de I/O
debido a la virtualizacin

FREE
Compradores de servidores
que slo implementan
lo que se ofrece como la
configuracin bsica

100M

1G

10G

40G

2020

2019

2018

2017

2016

2015

2014

2013

2012

2011

2010

2009

2008

2007

2006

2005

2004

2003

2002

2001

0
2000

Millions of server units

40 GbE
Fringe

100G

Proprietary 2014 Anixter Inc.

INFRAESTRUTURA DEL SISTEMA DE CABLEADO


PARA CENTROS DE DATOS

Server-class Adapter & LOM


40 GbE Shipments

Ports in Millions

2017

2016

2015

2014

2013

2012

40 GbE sobre fibra multimodo


Usa 8 fibras:
4 x 10 Gbps Tx y Rx
OM3 = 110 metros
OM4 = 150 metros

CREHAN RESEARCH Inc.

Source: IEEE 802.3 Working Group


LOM=Lan on Motherboard

Proprietary 2014 Anixter Inc.

IMPLEMENTACIONES ETHERNET A100GBPS

Actualmente el estndar de la IEEE especifica 10 x 10Gbps para Tx y Rx


sobre fibra OM3 / OM4 (20 fibras)

Migracin para 100GbE sobre fibra multimodo se ver mejorado sobre


cuatro enlaces (8 fibras) desarrollados en fibra multimodo
4 x 25Gbps para Tx/Rx an en desarrollo por la IEEE 802.3bm
100GBASE-SR4
Hasta 100 metros sobre fibra OM4
El estndar apunta a salir para el Q1 del 2015

Cuatro enlaces para 100GbE significa que NO hay cambios en la


infraestructura de cableado del centro de datos para 40GbE

Proprietary 2014 Anixter Inc.

400GBPS ETHERNET EST EN EL HORIZONTE

La necesidad est siendo


impulsada por la informtica en
todos los mercados:
Ciencia:
CERN Atlas Detector
Generates ~ 1 petabyte/sec
Radio Telescopio SKA (Square
Kilometer Array) 2
petabytes/sec
Secuenciacin del genoma
La ciencias de redes y energa
esperan 100 petabytes/mes de
datos para el 2015
Usos financieros en las redes
Mas:
Usuarios, mviles, video, data,
aplicaciones
Source: IEEE 802.3 Ethernet Working Group
1 petabyte = 1015 bytes

Proprietary 2014 Anixter Inc.

400GBPS ETHERNET EST EN EL HORIZONTE

IEEE estableci un grupo de estudio para 400Gbps Ethernet (Marzo, 2013)


Objectivo: Al menos 100 metros sobre OM4
IEEE estima que un estndar para 400 GbE puede estar listo para el 2017

IEEE 802.3 Pronstico de agregacin de ancho de banda (bandwidth


aggregation)
Capacidad 2015 = 10x requerimientos del 2010 = Terabit
Capacidad 2020 = 100x requerimientos del 2010 = 10 Terabit

Source: IEEE 802.3 Ethernet Working Group

Proprietary 2014 Anixter Inc.

PRINCIPALES PREOCUPACIONES URGENTES PARA


OPERADORES DE CENTROS DE DATOS DE MID-MARKET

Conectividad de centros de datos (82%)


Disponibilidad de carrier, densidad

Dsiponibilidad y Resiliencia del Centro de Datos (80%)


Potencia, espacio, refrigeracin, conectividad

Control sobre las instalaciones (78%)


Acceso a la nube (75%)

De las empresas investigadas:


53% necesitan +2000 sq. ft. de espacio en centros de datos
41% tiene al menos 4 centros de datos
88% estn planeando expandirse dentro de 4 aos

Source: Forrester Research,


US Firms< US$500M Revenue, 2014
Proprietary 2014 Anixter Inc.

10

INFRAESTRUCTURA EN GRADO DE UTILIDAD


PARA CAPACIDADES FUTURAS

Cualidades de los productos para empresa de servicios pblicos

Construidos para capacidad futura no solo hoy


Diseados para especificaciones de rendimiento robusto mas all del estndar
Diseados para alto grado de confiabilidad
Minimiza el downtime (tiempo de inactividad) por fallas o cortes de
mantenimiento

La Infrastructura de los centros de datos deben cumplir un rendimiento con


grado de empresa de servicios con confiabilidad y resistencia al futuro
Debido a la ley de Moore: Nada en Tecnologas de la informacin est a
prueba del futuro!
Las cuatro empresas de
servicios pblicos
Energa
Agua
Gas
Comunicaciones

Proprietary 2014 Anixter Inc.

11

TIPOS DE CENTROS DE DATOS


POR OPERACIN

CENTROS DE DATOS TRADICIONALES


USUARIOS FINALES

Operado por el propietario


Nivel empresarial
Varios tamaos
Varios niveles de Tecnologa
Requerimientos constantes de crecimiento

Los tipos de Centros de Datos estn Evolucionando de Acuerdo a las


Tecnologas y las Necesidades de los Cambios Organizacionales

Proprietary 2014 Anixter Inc.

13

MULTI-TENANT DATA CENTERS (MTDC)

Multi-tenant data centers son instalaciones de


multiples clientes que normalmente son propiedad de
empresas que se especializan en la prestacin de
servicios de infraestructura de internet, incluidos los
servicios del centro de datos a los clientes.
De acuerdo a datacenterknowledge.com,
actualmente hay 986 centros de datos en los Estados
Unidos ofreciendo servicios de Collocation y varios
servicios de hosting.
Cuatro tipos de MTDCs

Wholesale
Colocation/retail
Interconnection
Managed hosting

Proprietary 2014 Anixter Inc.

14

MTDC - WHOLESALE DATA CENTERS

Se ofrecen en PODs o celulas. Los tamaos van desde 10,000 50,000


pies cuadrados (930 4640 m2)
Se vende tanto a empresas como a proveedores de servicios Collocation
Normalmente proporcionan servicios de guardias de seguridad y
mantenimiento de alarmas de incendio, seguridad, generador, climatizacin
y sistemas de UPS.
Proveen tanto servicios a la medida como la opcin de alquiler-venta
(leasing) de las instalaciones del centro de datos
Ejemplos de MTDC tipo wholesale:
Digital realty
DuPont Fabros
Coresite

Proprietary 2014 Anixter Inc.

15

MTDC - COLLOCATION OR
RETAIL DATA CENTERS

El espacio del centro de datos se vende sobre la base


de los distintos racks, gabinetes o jaulas
Normalmente los clientes de proveedores de
Collocation son:

Empresas Fortune 1000


SMBs
Proveedores de aplicaciones de Internet
Proveedores de contenido de Internet y redes sociales
Proveedores de Managed hosting
Operadores de Telecomunicaciones

Sistema completo de instalacin y mantenimiento


incluyen extincin de incendio, seguridad, respaldo de
energa y climatizacin
Tambin se incluyen acceso y monitoreo remoto

Proprietary 2014 Anixter Inc.

16

MTDC - INTERCONNECTION DATA CENTERS

El alto volumen de trfico de Internet est obligando a las redes y a los


usuarios finales a colocar su contenido en, o alrededor de, las instalaciones
de interconexin, que proporcionan acceso a un trnsito de Internet
econmico
Servicios incluidos:
Compra de conectividad de Internet
Conexin de redes de VoIP
Realizacin de e-commerce B2B

Ejemplos
Equinix
Telx
Interxion

Proprietary 2014 Anixter Inc.

17

MTDC - MANAGED HOSTING DATA CENTERS

El hardware del servidor gestionado puede


ser propiedad del proveedor de hosting o
del cliente
Servicios incluidos:
Administracin de los sistemas
Administracin de la base de datos
Gestin de las aplicaciones

Ejemplos

i/o Data Centers


The Planet
Horizon
Peak 10

Proprietary 2014 Anixter Inc.

18

ESTNDARES DE DISEO

ESTNDARES RELEVANTES

ANSI/TIA-942-A (2012) Estndar de Infraestructura de


Telecommunicaciones para Centros de Datos
ANSI/BICSI-002 (2014) Diseo de Centros de Datos e Implementacin
de Buenas Prcticas
ISO/IEC FDIS 24764 (2010) Sistemas de Cableado Genrico para Centros
de Datos
CENELEC EN50600 Centros de Datos Instalaciones e
Infraestructuras
En desarrollo

Proprietary 2014 Anixter Inc.

21

ESTNDAR AMPLIAMENTE RECONOCIDO

Proprietary 2014 Anixter Inc.

22

ANSI/TIA-942-A DATA CENTER


DEFINICIN Y ELEMENTOS DE DISEO

Data Center Un edificio o parte de


un edificio cuya funcin primaria es
albergar un Cuarto de Cmputo y sus
reas de soporte; usualmente contiene
servidores y productos de
almacenamiento para funciones de
misin crtica
Elementos del Data Center
Diseo y planificacin del espacio
Fuente de alimentacin y distribucin
elctrica.
Gestin trmica
Iluminacin
Conectividad
Rutas y Hardware de soporte
Puesta a tierra
Seguridad Fsica
Proprietary 2014 Anixter Inc.

23

ANSI/TIA-942-A (2012) Telecommunications


Infrastructure Standard for Data Centers

El propsito de este estndar es proporcionar los


requisitos y directrices para el diseo y la instalacin del
centro de datos o cuarto de cmputo
Los centros de datos se pueden beneficiar de la
infraestructura que se planea con anticipacin para
soportar el crecimiento y los cambios en los sistemas
informticos que los centros de datos estn diseados
para soportar.
ANSI/TIA-942-A Standard is available from Global Documents (www.global.ihs.com )
Proprietary 2014 Anixter Inc.

24

TIA-942-A DATA CENTER BSICO


TOPOLOGA DE CABLEADO
ACCESS PROVIDERS

ACCESS PROVIDERS

Entrance Room
(Carrier equipment &
demarcation)

Work areas in offices,


operations center,
support rooms

Backbone cabling
Horizontal cabling

TR
(Office & operations
center LAN switches)

Backbone
cabling

Computer
Room

MDA
(Routers, backbone
LAN/SAN switches,
PBX, M13 muxes)
Backbone cabling

HDA
(LAN/SAN/KVM
switches)
Horizontal cabling

ZDA
Horizontal cabling

EDA
(Rack/cabinet)

HDA
(LAN/SAN/KVM
switches)

HDA
(LAN/SAN/KVM
switches)

Horizontal cabling

EDA
(Rack/cabinet)

HDA
(LAN/SAN/KVM
switches)

Horizontal cabling

EDA
(Rack/cabinet)

Horizontal cabling

EDA
(Rack/cabinet)

Source: ANSI/TIA-942-A
Proprietary 2014 Anixter Inc.

MDA: Main Distribution Area


HDA: Horizontal Distribution Area
EDA: Equipment Distribution Area

25

TIA-942-A DATA CENTER REDUCIDO


TOPOLOGA DE CABLEADO
ACCESS PROVIDERS

Horizontal cabling

MDA
(Carrier equipment,
demarcation, routers, backbone
LAN/SAN/KVM switches, PBX)

Computer
Room

Horizontal cabling

Work areas in offices,


operations center,
support rooms

ZDA
Horizontal cabling

EDA
(rack/cabinet)

EDA
(rack/cabinet)

Consolidation of main cross-connect and horizontal cross-connect into a single MDA


TR serving the support areas and the Entrance Room many also be consolidated in the MDA
Source: ANSI/TIA-942-A

Proprietary 2014 Anixter Inc.

26

TIA-942-A DATA CENTER DISTRIBUIDO


TOPOLOGA DE CABLEADO
ACCESS PROVIDERS
Work areas in offices,
operations center,
support rooms

Primary Entrance
Room
(Carrier equipment &
demarcation)

Secondary Entrance
Room
(Carrier equipment &
demarcation)

Backbone cabling

Horizontal cabling

TR
(Office & operations
center LAN switches)

ACCESS PROVIDERS

Backbone
cabling

MDA
(Routers, backbone
LAN/SAN switches,
PBX, M13 muxes)

Backbone cabling
Backbone cabling
Backbone cabling

IDA
(LAN/SAN switches)

Computer Room
IDA
(LAN/SAN Switches)
HDA
(LAN/SAN/KVM
switches)
Horizontal cabling

ZDA
Horizontal cabling

EDA
(Rack/cabinet)

Backbone cabling

Backbone cabling

HDA
(LAN/SAN/KVM
switches)

HDA
(LAN/SAN/KVM
switches)

Horizontal cabling

EDA
(Rack/cabinet)

Horizontal cabling

Backbone cabling

HDA
(LAN/SAN/KVM
switches)

Backbone cabling

HDA
(LAN/SAN/KVM
switches)
Horizontal cabling

ZDA
Horizontal cabling

EDA
(Rack/cabinet)

EDA
(Rack/cabinet)

Horizontal cabling

EDA
(Rack/cabinet)

Source: ANSI/TIA-942-A

Proprietary 2014 Anixter Inc.

IDA: Intermediate Distribution Area

27

TIA-942-A EFICIENCIA ENERGTICA


RECOMENDACIONES

Cableado por encima de los gabinetes puede mejorar la eficiencia de


enfriamiento y es una buena prctica siempre y cuando la altura del techo
lo permita.
Si el cableado es instalado bajo piso tcnico:

Utilice diseos de cableado y de red que minimicen el uso de cableado bajo piso tcnico
Seleccione cables con dimetros ms pequeos para reducir al mnimo el volumen de cable
bajo piso
Disee rutas de cableado de tal manera que minimice el impacto del flujo de aire debajo del
piso tcnico.
Disee rutas de cableado a las filas de tal manera que las rutas de cableado entren por el
pasillo caliente en direccin opuesta a la alimentacin de flujo de aire (es decir, el mximo
volumen de cables entra por el pasillo caliente en el extremo opuesto del CRAC con menor
distribucin de cables cuando se aproxima al CRAC)
Dimensione las rutas y los espacios para acomodar los cables de forma tal que ocasionen la
mnima obstruccin posible

Source: ANSI/TIA-942-A

Proprietary 2014 Anixter Inc.

28

TIA-942-A EFICIENCIA ENERGTICA


RECOMENDACIONES

El cableado dentro de gabinetes, racks, etc., no debe obstaculizar la


correcta refrigeracin de los equipos dentro de los gabinetes.
Se debe mantener el flujo de aire suficiente indicado en las especificaciones de
los equipos por los fabricante.

Deben establecerse procedimientos de manejo de cambios de cableado


que incluyan la eliminacin de cables abandonados de acuerdo con el NEC
(o la normativa jurdica que aplica en cada pas).
El cableado bajo el piso falso no debe colocarse bajo de las baldosas
perforadas o en cualquier lugar que interrumpa el flujo de aire hacia o
desde los CRAC.
Los PDU deben permitir el monitoreo de los niveles de energa
Use esquemas de iluminacin de bajo consumo
Evite las ventanas exteriores y tragaluces en las salas de cmputo

Source: ANSI/TIA-942-A

Proprietary 2014 Anixter Inc.

29

TIA-942-A UBICACION DEL PASILLO FRO Y CALIENTE

ANSI/TIA-942-A distancias
recomendadas:

Front
Cabinets

Frente: recomendado: 4 pies (1.2 metros)


(mnimo 3 pies=1m)
Atrs: recomendado: 3 pies=1m (mnimo
2 pies=60 cm)

This Row of Tiles


Can Be Lifted

.
Align Front or Rear of Cabinets
El cableado de potencia, si va bajo piso
with Edge of Floor Tiles
This Row of Tiles Can Be Lifted
falso, debe estar en el pasillo fro sobre
la losa
This Row of Tiles Can Be Lifted
Front or Rear of Cabinets
El cableado de telecomunicaciones, si Align
with Edge of Floor Tiles
va bajo el piso falso, debe estar ubicado
en bandejas de cables en el pasillo
caliente.

Rear
HOT AISLE
(Rear of Cabinets)

Rear
Cabinets
Front
COLD AISLE
(Front of Cabinets)

Front
Cabinets
Rear

Source: ANSI/TIA-942-A

Proprietary 2014 Anixter Inc.

30

TIA-942-A DATA CENTER


INFRAESTRUCTURA TIERS

El anexo incluye detalles para los cuatro Tiers en las siguientes categoras:
Telecomunicaciones
Elctrica
Architectura
Mecnica

A medida que el Tier es mayor, El DC es ms redundante, pero esto implica


que las construcciones son mas costosas.
La calificacin general Tier del centro de datos se determina por el nmero de
Tier de menor categora
ejem., T2E3A4M3 = Centro de datos Tier 2 total
En el ejemplo anterior, la calificacin general sera un nivel 2 porque las
telecomunicaciones tiene una clasificacin de Nivel 2

Se recomienda comprar el documento de la TIA-942-A para su revisin


completa de la estructura de los Tier
Disponible en: http://www.global.ihs.com

Source: ANSI/TIA-942-A

Proprietary 2014 Anixter Inc.

31

TIA-942-A DATA CENTER


REDUNDANCIA EN RUTAS DE CABLEADO Y ESPACIOS

Least Redundant
|
|
Source: ANSI/TIA-942-A

Most Redundant
Proprietary 2014 Anixter Inc.

32

ESTNDARES DE DISEO

Proprietary 2014 Anixter Inc.

33

ANSI/BICSI-002 (2011) Data Center Design


and Implementation Best Practices

Este estndar proporciona las mejores prcticas y


mtodos de implementacin que complementan la TIA,
CENELEC, ISO y otras publicaciones como estndares y
documentos de centros de datos. Se trata principalmente
de un estndar de diseo, con los requisitos de instalacin
y directrices para los centros de datos

Source: ANSI/BICSI-002-2011

ANSI/BICSI-002 Standard is available from Global Documents (www.global.ihs.com ) or from BICSI (www.bicsi.org)

Proprietary 2014 Anixter Inc.

34

CENELEC (en francs Comit Europen de Normalisation Electrotechnique)

ANSI/BICSI-002 TEMAS CUBIERTOS

Planificacin del espacio

Seleccin del site

Planificacin arquitectnica

Edificios (BAS)

Infraestructura de
telecomunicaciones

Planificacin estructural

Recuperacin de desastres

Sistemas elctricos

Sistemas mecnicos

Comunicaciones y Megafona
(voceo)

Proteccin contra fuego

Diseo de la sala de cmputo

Seguridad fsica

Sistemas de Automatizacin de

Commissioning (puesta en
marcha)

Mantenimiento

Source: ANSI/BICSI-002-2011

Proprietary 2014 Anixter Inc.

35

ANSI/BICSI-002 DATOS DE PLANIFICACIN DEL SITE

Datos Incluidos para estudio de planificacin de la ubicacin

Mapa de riesgo de temblores terrestres


Mapa de riesgo volcnico
Mapa de derrumbes
Mapas de regiones de agua y tipos acuferos
Mapa de actividades de huracanes
Mapa de riesgos de tornados
Mapas de reas con antecedentes de inundaciones.

Source: ANSI/BICSI-002-2011

Proprietary 2014 Anixter Inc.

36

ANSI/BICSI-002 ALCANCES DE LA SEGURIDAD FSICA

Evaluacin de amenazas y riesgos

Requerimientos regulatorios y
legislacin

Videoseguridad

Barreras

Iluminacin

Prevencin del crimen mediante el


diseo ambiental

Controles de acceso

Alarmas

Guardias (vigilantes)

Recuperacin de desastres

Source: ANSI/BICSI-002-2011

Proprietary 2014 Anixter Inc.

37

ANSI/BICSI-002 COMMISSIONING

Commissioning es el proceso de garantizar que los


sistemas sean diseados, instalados, funcionalmente
probados y capaces de ser operados y mantenidos de
acuerdo a la intencin de diseo del propietario y a las
necesidades operacionales.

Hoy en da el commissioning se ha convertido en un


importante proceso de control de calidad que abarca todo
el edificio o centro de datos.
Source: ANSI/BICSI-002-2011

Proprietary 2014 Anixter Inc.

38

ANSI/BICSI-002 SISTEMAS QUE DEBEN INCLUIRSE


EN LOS PROCESOS DEL COMMISSIONING

Elctrico
HVAC
Automatizacin del edificio
Monitoreo del edificio
Supresin y proteccin de fuegos
Seguridad fsica
Infraestructura de TI incluyendo
rutas y espacios

Puesta a tierra

Bombeo de combustible
Monitoreo de inventario
Deteccin de fugas de lquidos
Cumplimiento de los cdigos y
ordenanzas

Source: ANSI/BICSI-002-2011

Proprietary 2014 Anixter Inc.

39

GLOBAL DESIGN STANDARDS

Proprietary 2014 Anixter Inc.

40

ISO/IEC 24764 (2010) Generic cabling


systems for data centres

El estndar internacional especifica cableado genrico


que soporta una amplia gama de servicios de
comunicaciones para su uso con un centro de datos.
Cubre cableado balanceado y cableado de fibra ptica. ...
Se basa y hace referencia a los requisitos del estndar ISO
/ IEC 11801.
... Contiene requisitos adicionales que son? Adecuado a
los centros de datos en donde la distancia mxima es de
2000 m
Source: ISO/IEC 24764 (2010)

ISO/IEC 24764 Standard is available from Global Documents (www.global.ihs.com)


Proprietary 2014 Anixter Inc.

41

ISO/IEC 24764 (2010) Generic cabling


systems for data centres

. Dentro de las instalaciones, la importancia de la


infraestructura de cableado es similar a la de los otros
servicios pblicos (utilities) fundamentales del edificio
tales como calefaccin, iluminacin y electricidad. ... La
mala calidad de servicio debido a la falta de previsin de
diseo, uso de componentes inapropiados, instalacin
incorrecta, mala administracin o el soporte inadecuado
pueden amenazar la efectividad de una organizacin.

Source: ISO/IEC 24764 (2010)

Proprietary 2014 Anixter Inc.

42

ISO/IEC 24764 (2010) ESTRUCTURA GENERAL

ENI

MD

ZD

LDP

EO

EQP

Distributor in
accordance with
ISO/IEC 11801

Network
access
cabling
subsystem

Main distribution
cabling subsystem

Zone distribution
cabling subsystem

Equipment
cabling

Generic cabling system

Source: ISO/IEC 24764 (2010)

ENI = External network interface


MD = Main distributor
ZD = Zone distributor
LDP = Local distribution point
EO = Equipment outlet
Proprietary 2014 Anixter Inc.

43

ISO/IEC 24764 (2010) JERARQUA

ENI

ENI

Distributor in
accordance with
ISO/IEC 11801

Optional cables

Network access
cabling subsystem

MD

ZD

ZD

LDP

LDP

EO

EO

Main distribution
cabling subsystem

EO

EO

LDP

EO

EO

EO

Zone distribution
cabling subsystem

LDP

EO

EO

EO

NOTE: Network access cabling is also used to connect ENI to ZD

Source: ISO/IEC 24764 (2010)


Proprietary 2014 Anixter Inc.

44

ISO/IEC 24764 (2010) JERARQUA CON REDUNDANCIA

ENI

ENI

MD

MD

ZD

ZD

LDP

LDP

It is important to note that in


order to achieve true
redundancy, the redundant
cable paths must have
separate pathway routes.

Distributor in
accordance with
ISO/IEC 11801

EO

EO

EO

EO

EO

EO

EO

EO

EO

EO

EO

EO

NOTE: Additionally, redundancy may be provided by utilizing multiple cables between distributors, with cables following different routes.

Source: ISO/IEC 24764 (2010)


Proprietary 2014 Anixter Inc.

45

TECNOLOGAS DE RED EN LA SALA DE CMPUTO

CENTRO DE DATOS
TENDENCIAS ELECTRNICAS

Consolidacin de servidores y de
almacenamiento mediante la
virtualizacin
Requieren menos servidores fsicos
(menos hardware)
Aumento de los requerimientos de
ancho de banda en la red
Aumenta la densidad de potencia
Requieren enfriamiento de precision
dirigido a pequeas reas

Unified Fabrics
Consolidacin de protocolos LAN
y SAN desiguales sobre un solo
protocolo Ethernet
Simplificar la gestin de red de los
centros de datos

Proprietary 2014 Anixter Inc.

47

VIRTUALIZACIN
UNIDADES DE RED CON ANCHO DE BANDA
OS+App
OS+App

OS+App
OS+App
OS+App
OS+App
OS+App
OS+App
OS+App
Hypervisor

OS+App

OS+App

OS+AppHypervisor

OS+App

OS+App

OS+App

Hypervisor

Hypervisor

Hypervisor

Server
200500 Mbps

Server
200500 Mbps

Server
200500 Mbps

Hypervisor
Server
Server
200500 MbpsServer200500 Mbps
25 Gbps
Proprietary 2014 Anixter Inc.

48

TIA-942 DIRECT CONNECT


ARQUITECTURA CENTRALIZADA

Pro
Electrnica con costos menores que las
arquitecturas distribuidas
Fcil de disear, implementar y
mantener
Minimiza el cuello de botella de la red
Buena utilizacin del puerto del switch
Fcil gestin de dispositivos

Contra
Mayor nmero de cables
(predomina el uso de cobre)
Sobreposicin de cables para
redundancia
Diseo con dificultades en las rutas de
cables
Falta de escalabilidad

Red denotes Network Equipment


Blue denotes Server Equipment

Source: Anixter

Proprietary 2014 Anixter Inc.

49

ARQUITECTURA END-OF-ROW Y MIDDLE-OF-ROW

Pros
Menor cantidad de cables que la
arquitectura centralizada de switching
Hay mas uso de fibra que en la
arquitectura centralizada de switching
Buena escalabilidad
Es ms costo efectiva que la arquitectura
top of rack (ToR)

Contras
Mayor inversin de capital en switches
end of row (EoR) y middle of row (MoR)
Aumento de gastos generales de gestin
debido a la mayor cantidad de switches
Riesgos en la estabilidad de la red
debido al potencial aumento del nmero
de puntos de falla en la electrnica

Red denotes Network Equipment


Blue denotes Server Equipment

Source: Anixter
Proprietary 2014 Anixter Inc.

50

ARQUITECTURA TOP-OF-RACK

Pro

Uso mas eficiente del cable.


Uso eficiente del rea de piso.
Buena escalabilidad.
Fcil administracin de cables.

Contra
Ms switches para administrar.
Mayor cantidad de puertos de agregacin.
Pobre utilizacin de puertos del switch si los
gabinetes estn parcialmente poblados.
Mas puertos de agregacin Spanning Tree
Protocol en los los dispositivos de agregacin.
Mayores costos potenciales en switches
Necesidad del segundo ToR switch
para redundancia.
Creacin de puntos calientes.

Red denotes Network Equipment


Blue denotes Server Equipment
*NOTE: Most cost comparisons between traditional and
ToR network architecture do NOT take into account the
necessity of a second ToR switch to achieve
redundancy

Source: Anixter
Proprietary 2014 Anixter Inc.

51

CONSOLIDACIN DE SERVIDORES I/O USANDO CISCO UCS

All traffic goes


over 10Gig
twinax cabling

Cisco also has


10GBASE-T interfaces

Traditional server
Multiple interfaces
per server

Source: Cisco Systems

Cisco UCS
Consolidated to two
interfaces per server

FC HBA: Fibre Channel Host Bus Adapter: connects a host system (the computer) to other network and storage devices
IPC: Inter-Processor Communication
CNA: Converged Network Adapter
UCS: Unified Computing System

Proprietary 2014 Anixter Inc.

52

CISCO UCS PRO Y CONTRA

Pros
Consolidacin I/O.
Menor congestin de cables.

Contra
Aumento del hardware de red y los costos administrativos.
Pobre utilizacin de puertos/ asignacin.
Arquitectura Cisco Top of Rack no se ajusta al estndar tradicional de cableado
estructurado.
Es proprietario
SFP+ no est estandarizado por la IEEE o la TIA
Carece de flexiblidad
Necesidad de un segundo switch Top of Rack para redundancia
No es una solucin costo efectiva para administracin fuera de banda (out-ofband)

Proprietary 2014 Anixter Inc.

53

CABLEADO ESTRUCTURADO ESTANDARIZADO UTILIZANDO


10GBASE-T SOPORTA VIRTUALIZACIN Y UNIFIED FABRICS

Usa la interface fsica omnipresente RJ45


Cableado en categora 6A es retrocompatible con servidores existentes
habilitados para 10/100/1000BASE-T
Aplicacin independiente

Es mas rentable que SFP+ u otras alternativas pticas


Menor CAPEX total
Menor OPEX debido a menores consumos potenciales de energa que el uso de
switches ToR

Utiliza cableado estructurado estandarizado


Categora 6A para conexin de servidores
Cableado OM3/OM4 para backbone y conexiones SAN

Proprietary 2014 Anixter Inc.

54

CISCO BIDIRECTIONAL (BIDI) QSFP


TECNOLOGA DE FIBRA

Concepto de los transceptores de 40


Gbps existentes

Cisco QSFP-40G-Short Range-BiDi


40 Gbps Transceiver

Cisco QSFP BiDi fibra multimodo duplex


Tx y Rx a 832 nm y 918 nm de longitud de onda
Distancia: OM3 = 100 metros, OM4 = 150 metros
in order to achieve the 150 meter distance on OM4, Cisco requires the link
loss budget to be not greater that 1.0dB.

Es una opcin adicional para migrar a 40G Ethernet


NO es un estndar de la IEEE

Conserva la configuracin fsica de fibra dplex 10G por el momento


La configuracin de la fibra multimodo duplex no es probable que soporte
100G Ethernet en el futuro
Proprietary 2014 Anixter Inc.
Source: Cisco Systems

Quad Small Form-Factor Pluggable (QSFP)

55

ARQUITECTURA DE RED LEAF-SPINE

Un nuevo diseo para centros de datos


Cada leaf esta conectada a cada spine

El cobre es usado como enlace al servidor

Destinados a ser usados en los ToR o EoR


El cobre se usa por que es la opcin mas costo-efectiva
La fibra es usada de switch-to-switch
Ahora la mayora de uplinks requiren mdulos QSFP (BiDi or MPO/MTP)

Spine

Spine
Fiber

Leaf

Leaf

Leaf

Servers

Servers

Servers

Leaf

Leaf

Servers Servers

Leaf

Copper

Servers

Source: TIA High Performance Cabling Task Force


Proprietary 2014 Anixter Inc.

56

MONITOREO Y GESTION DE LA
INFRAESTRUCTURA

NETWORK TAPS ARE A SAN MONITORING


BEST PRACTICE

Traffic Access Points (TAPs)


Han sido ampliamente utilizados en redes IP por mas de 20 aos
Proporcionar acceso directo a todos los niveles de trfico de fibra
Derivan datos sobre rendimientos de SAN/storage, utilizacin y errores de
Tx
Son utilizados por todos los proveedores de sistemas y almacenamiento para
diagnosticar problemas.
Permite al personal de TI:
Asegurar alta disponibilidad de las aplicaciones
Maximizar el desempeo de las aplicaciones
Proactivamente encontrar problemas antes que los usuarios los
experimenten

Permite el uso de pruebas de SAN y analizadores de protocolos

Proprietary 2014 Anixter Inc.

59

MONITOREO DE REDES POR MEDIO DE PUERTOS DE FIBRA

Lo datos de la capa de red primero deben ser extrados en una de las dos
siguientes maneras con el fin de aplicar herramientas de anlisis
Analizadores del puerto del Switch (SPAN=switch port analyzer)
Puertos espejo (activo)
Puerto Tap (pasivo para pticas)

Qu buscamos con el monitoreo?


Amenazas de seguridad
Problemas de desempeo
Optimizacin (I/O cuellos de botella)

Proprietary 2014 Anixter Inc.

60

TAPS PTICOS PARA EXTRACIN DE DATOS

La mejor prctica es hacer planes para la utilizacin de mdulos de fibra TAP en la fase
de diseo de la arquitectura para la infraestructura de cableado en el centro de datos.
Source: Corning and Virtual Instruments
Proprietary 2014 Anixter Inc.

61

COMO LAS TENDENCIAS AFECTAN LA GESTIN DEL DC

Los centros de datos estn evolucionando


Anteriormente monoltico, un tamao nico para todo almacenamiento de TI
Hoy altamente optimizado y edificios transparentemente inteligentes

El mayor desafo es gestionar la infraestructura de TI y su ambiente


Problemas causados si no se gestiona apropiadamente
Implementacin tarda de aplicaciones
Gasto no planificado
Servicio interrumpido
Escasez o falta de recursos de energa, espacio y enfriamiento.

Proprietary 2014 Anixter Inc.

62

DATA CENTER INFRASTRUCTURE


MANAGEMENT (DCIM)

DCIM es una nueva forma de gestin de centros de datos que extiende los
sistemas tradicionales y de gestin de red para incluir componentes fsicos
y de nivel activo.
DCIM aprovecha la integracin de TI y la gestin de instalaciones para
centralizar el monitoreo, la gestin y la planificacin de la capacidad
inteligente de los sistemas crticos de un centro de datos.
Segn IDC, se espera que DCIM pueda crecer a nivel mundial en un tasa
de crecimiento anual compuesta (CAGR) del 22,8% en un mercado
potencial de 690,3 millones dlares para el ao 2016.
Soluciones DCIM son el paso crtico en ayuda a la transformacin de los
edificios transparentemente inteligentes y optimizados
DCIM an no est estandarizado, ni es una plataforma abierta; actualmente
requiere la eleccin de una solucin de un solo proveedor

Proprietary 2014 Anixter Inc.

63

FACTORES QUE IMPULSAN LA ADOPCION DEL DCIM

Aumento de potencia y densidad de calor.


Consolidacin del centro de datos.
Virtualizacin y Cloud computing.
Mayor dependencia organizacional en sistemas crticos de TI.
Seguimiento (rastreo) de activos.
Eficiencia energtica o iniciativas verdes de TI.
Principio orientador: Si algo no se mide o monitorea no se puede controlar.

Proprietary 2014 Anixter Inc.

64

MONITOREO MEJORES PRCTICAS

Monitorear y controlar el desempeo.


Herramientas de monitoreo para capturar el desempeo, la temperatura, la
humedad y energa en el centro de datos.
Medir temperaturas de los servidores en tiempo real.
Crear grficos histricos para tendencias.
Facturacin departamental basado en uso de energa en vez de espacio de
RU

Proprietary 2014 Anixter Inc.

3/11/2015

65

EFICIENCIA MEJORES PRACTICAS

Power Utilization Efficiency (PUE) = relacin de la potencia total que entra


en la instalacin dividido por la energa utilizada por los equipos de TI.

Una indicacin de la eficiencia ms precisa relaciona la potencia utilizada


con la cantidad de trabajo realizado
PUE: Power Usage Effectiveness

Building Load
Demand from grid

Total
Facility
Power

Power
Switchgear
UPS
Battery backup
Etc.

IT
Equipment
Power

IT Load
Servers
Storage
Telco equipment
Etc.

Cooling
Chillers
CRACs
Etc.

Source: The Green Grid

PUE= Total Facility Power


IT Equipment Power
Proprietary 2014 Anixter Inc.

66

EFICIENCIA MEJORES PRACTICAS

Clculo del (PUE) requiere o bien un mtodo de medicin directa o una


aproximacin estimada guiados por clculos deductivos
Necesario para un enfoque de medicin directa:
Medicin de la potencia de entrada a las instalaciones de cmputo
Medicin separada de los subsistemas del edificio:
Iluminacin
HVAC
Circuitos de dispositivos no informticos
Medicin del consumo de energa de dispositivos informticos
Monitoreo del consumo de potencia del circuito derivado al PDU remoto y /
o monitoreo del consumo de energa del PDU a nivel del gabinete

Para un enfoque calculado, se hacen estimaciones deductivas:


El consumo de energa del subsistema del edificio basado en el rea
Consumo de energa del dispositivo informtico
El uso de PDU monitoreable es muy til y aumenta la precisin

Proprietary 2014 Anixter Inc.

67

EFICIENCIA MEJORES PRACTICAS

Elimina la ezcla de aire caliente y fro

Emplea pasillos calientes y pasillos fros


Elimina las brechas en las filas
Use filas mas largas
Use gabinetes con paneles ciegos
Recortes para paso de cables sellados

HOT
AISLE

COLD
AISLE

HOT
AISLE

Proprietary 2014 Anixter Inc.

COLD
AISLE

68

EFICIENCIA MEJORES PRACTICAS

Use las mejores tcnicas para el control de temperatura y distribucin del


flujo de aire
Oriente los CRAC perpendicularmente a los pasillos calientes
Iguale la suma del flujo de aire de los equipos de TI con el flujo de aire de
los CRAC
Uniformiice la presin esttica del aire, utilizando 0,8 - 1,0 m de altura en
piso tcnico , baldosas de ventilacin ajustables y no coloque baldosas
perforadas cerca del CRAC

Proprietary 2014 Anixter Inc.

69

EFICIENCIA
MEJORES PRCTICAS: USO DE ECONOMIZADORES

Chiller

Water side: use of outside


air to cool chilled water

Cooling Tower
CRAC(s)
Routing through Chiller

Bypassing Chiller

Air side: use of outside air


directly into data center

Proprietary 2014 Anixter Inc.

70

EFICIENCIA
GESTIN DE LA ELECTRNICA

Servidores virtuales, consolidacin y almacenamiento:


Virtualizacin de servidores
Por ejemplo: VMware y HyperV (Microsoft), etc.
Consolidacin de equipos utilice servidores blade en lugar de servidores
rackeables (comparten ventiladores y fuentes de alimentacin)

Utilice al aplicacin de administracin del CPU:


Optimice el consumo de energa basado en la utilizacin de la CPU
Reduzca los estados de energa del procesador cuando no es necesario el
mximo desempeo
Reduzca el consumo de energa sin comprometer la capacidad de
procesamiento

Almacenamiento:
Tiered utilice los drivers de alta velocidad nicamente cuando las
aplicaciones requieran de respuesta inmediata.
Consolidacin discos de gran tamao, velocidad lenta, uso ms eficiente
con volumen

Proprietary 2014 Anixter Inc.

71

SALA DE CMPUTO
TENDENCIAS DE ARQUITECTURA

DISEO LOSA VS. PISO TCNICO


CONSIDERACIONES CLAVE

Costo
Motivado por tamao.
Arquitectura de la sala.
Diseo y requerimientos de
energa/enfriamiento.

Flexibilidad.
Carga de piso.
Densidad.
Crecimiento.
No hay decisin correcta o equivocada.
Tanto la arquitectura de losa como la de
piso tcnico son viables, pero requieren
decidirse por una de ellas desde el
principio del proceso de diseo

Photo courtesy: APC

Proprietary 2014 Anixter Inc.

73

ARQUITECTURA DE CENTRO DE DATOS MODULAR

Uso de construcciones prefabricadas


A veces, pero no siempre en contenedores
Puede agregar puntos LEED al edificio

Implementacin rpida:
Reduce el tiempo de construccin (1012
meses)
El diseo permite la construccin simultnea
de subsistemas internos

Puede ser utilizado para modernizar


pequeos centros de datos en edificios
existentes.
Los contenedores puede ser usados como
espacios suplementarios, auxiliares, o para
recuperacin de desastres.
Es posible movilizar las instalaciones

Diagram courtesy: Emerson / Liebert


Proprietary 2014 Anixter Inc.

74

PROYECTO DE CMPUTO ABIERTO

Iniciado en Facebook ~2012


www.opencompute.org: es una fundacin que provee una estructura en la
cual los individuos y las organizaciones pueden compartir su propiedad
intelectual
Objetivo: construir la infraestructura informtica ms eficiente al menor
costo posible
Desafiando los convencionalismos con un diseo desde cero.
Compartir tecnologas conforme evolucionan.

Hardware abierto: servidores, almacenaje, rack, networking


Especificaciones y dibujos mecnicos liberados al pblico
Trabajar con la comunidad para mejorarlos

Diseo del centro de datos


Maximiza el desempeo mecnico as como la eficiencia trmica y energtica

Resultado: el data center es 38% ms eficientes y 24% ms econmico


que los data centers ms modernos.

Source: Opencompute.org
Proprietary 2014 Anixter Inc.

75

SOFTWARE DEFINED NETWORKING (SDN)

Evolucion a partir del trabajo realizado en la Universidad de Berkeley y la Universidad de


Stanford en 2008
Pregunta original: Cmo pueden los investigadores en los campus universitarios probar nuevas
ideas en una red real, a escala?
Es un estndar abierto desacopla la funcin de toma de decisiones de la red del sistema
subyacente que enva el trfico a su destino
La separacin fsica del plano de control de red del plano de envos y donde un plano de
control controla varios dispositivos
La toma de decisiones se realiza mediante un servidor independiente
Principalmente enfocado a la investigacin
www.opennetworking.org
SDN:
is a networking architecture that provides a capability to control or "define" network traffic flows, security policies, or
network topology by dinamically programming network devices.
The programming capability is centralized and hosted on one or a few standard servers knows as SDN controller which is
the brain of SDN network.

SDN is esentially network virtualization

SDN requires a robust physical infraestructure (cabling) and bandwith

Proprietary 2014 Anixter Inc.

76

RESTRUCTURACIN DE LA RED SDN

Feature

Feature

Network OS
Feature

Feature

Operating
System
Feature

Specialized Packet
Forwarding
Hardware
Feature

Feature

Operating
System
Specialized Packet
Forwarding
Hardware

Feature

Operating
System
Feature

Specialized Packet
Forwarding
Hardware

Feature

Operating
System

Feature

Feature

Specialized Packet
Forwarding
Hardware

Operating
System

Source: OpenFlow.org

Specialized Packet
Forwarding
Hardware

Proprietary 2014 Anixter Inc.

77

SOFTWARE DEFINED NETWORKING (SDN)


3. Well-defined open API

Feature

Feature

2. At least one Network OS


probably many.
Open- and closed-source

Network OS
1. Open interface to packet forwarding

Packet
Forwarding

Packet
Forwarding
Source: OpenFlow.org

Packet
Forwarding
Packet
Forwarding

Packet
Forwarding
Proprietary 2014 Anixter Inc.

78

CONCLUCIONES

El entorno del centro de datos sigue evolucionando


Los requerimientos de ancho de banda se incrementarn.
Sern necesarios sistemas de alta-densidad de energa y enfriamiento
Las instalaciones requerirn operaciones costo efectivas y eficientes.

La tecnologa sigue evolucionando en apoyo de nuevas aplicaciones para


centros de datos

Virtualizacin y cloud computing


Mayores tasas de transmisin de datos de las redes
Desempeo de la infraestructura de cableado
Sistemas eficientes de distribucin de energa y enfriamiento.

Proprietary 2014 Anixter Inc.

79

CONCLUSIONES

Anixter Data Center HealthCheckSM


El HealthCheck mira el entorno de un centro de datos y determina si se est
cumpliendo con los objetivos de rendimiento y eficiencia de la organizacin
Diseado para hacer frente a los obstculos y desafos comunes
El aumento del consumo de energa
La construccin de sistemas integrados
El aumento de ancho de banda
Centros de datos convergentes
Entornos virtualizados

Consltenos acerca de nuestro personalizado Data Center HealthCheck!

Proprietary 2014 Anixter Inc.

80

GRACIAS.
81