INSTALLATION INSTRUCTIONS
1. Remove heater plate assembly (Illustration 1) from back box by
removing 4 flat head screws and set aside.
2. Mount back box and cover assembly in desired position. With hinges
horizontal or vertical, insert the (4) mounting tabs into the back box
slots (see Illustration 2). Mark and drill (4) 1/4 diameter holes 1
1/4 deep. Insert plastic anchors and screw back box to wall with (4)
#10 x 1 1/2 screws.
LOW TEMPERATURE
WARNING TERMOSTAT
CLOSE @ 32F
OPEN @ 50F
3. Route wires for heater and appliance into back box through conduit
or small hole properly sealed.
ILLUSTRATION 2
THUMB LOCK
19051 (4)
#8-32 x 3/8 FLAT
HEAD MS
629721A FRAME
7510Ahtr IS JULY2007
SUB-6297B20
3/4 NPT CONDUIT
HUB KIT (NOT
INCLUDED)
THUMB LOCK
LOW TEMPERATURE
WARNING TERMOSTAT
CLOSE @ 32F
OPEN @ 50F
LED CONTROL
19051 (4)
#8-32 x 3/8 FLAT
HEAD MS
POWER
RESISTOR HEATER
ILLUSTRATION 3
4. Connect heater power and control wires. Note: Terminals are not
polarity sensitive.
12 Volt, 19 WATTS
24 Volt, 77 WATTS
ELECTRONIC DEVICE
MOUNTING HOLES
ILLUSTRATION 4
5. Mount the heater plate assembly to the back box with control
thermostat toward bottom of enclosure (see Illustration 4). Be sure
to route wires for electronic device through the hole in the center of
the heater plate before attaching heater plate. For vertical mounting
(hinges to right or left side) be sure control thermostat is towards the
bottom of the enclosure.
6. Connect the electronic device and mount to the heater plate in
mounting holes indicated using #6 - 32 x 1/2 screws (2) provided.
NOTE: If moisture buildup occurs, drill a weep hole on bottom
side of back box.