ENGINEERING CONSULTANT
TCE CONSULTING ENGINEERS LIMITED
73/1, ST. MARKS ROAD
BANGALORE 560 001
INDIA
CONTRACTOR:
AL-TOUKHI COMPANY FOR INDUSTRY & TRADING
P.O. BOX 497, RIYADH 11411, KINGDOM OF SAUDI ARABIA
TEL. 00966-1-4633660 : FAX. 00966-1-4631150
P0C
09.12.2004
MP
SR
P0B
12.10.2004
RMRB
HRC
REV NO . DATE
PREPARED BY
CHECKED BY
CLEARED BY
APPROVED BY
TCE FORM 032 R1
CONTENTS
SHEET 1 of 1
OF 4
CONTENTS
CLAUSE No.
DESCRIPTION
PAGE No.
1.0
Introduction
2.0
3.0
Design Basis
4.0
5.0
6.0
7.0
Conclusion
14
ANNEXURES
1.0
15
ISSUE
P0B
1.
SHEET 1 of 15
OF 4
INTRODUCTION:
1.1
1.2
ISSUE
P0C
SHEET 2 of 15
OF 4
2. REFERENCE DRAWINGS/DOCUMENTS
2.1
2.2
2.3
2.4
2.5
2.6
ISSUE
P0C
3.0
SHEET 3 of 15
OF 4
DESIGN BASIS
3.1
The average soil resistivity for the purpose of earthing system design is
taken as 26.588 ohm metre from the soil resistivity test data by taken
the average values measured at various locations.
3.2
3.3
Fault clearing time for sizing the Main earthing conductor is taken as 1
second.
3.4
3.5
3.6
The minimum shock duration for calculation is taken as 0.5 sec (as per
Cl.no 4.0 of SES-P-119.10, page 7 of 43)
3.7
3.8
Current Division factor for the calculation is taken as 0.7 (as per Cl.no4.0 of SES-P-119.10, Page 7 of 43)
3.9
Main Grounding grid conductor not less than 240 Sqmm (as per cl.no
6.18.2-c of PTS 1024, Page 240 of 331)
3.10
ISSUE
P0C
30421008-3CL-00014-
4.0
4.1
Conductor Material
SHEET 4 of 15
OF 4
4.2
a)
b)
c)
Rod Electrodes
d)
Insulated Copper
Conductor.
Size of Conductors
tcxrxrx 10 4
I
TCAPx10 4
K Tm )
x ln 0
tc x r x r
K 0 Ta
A =
or
TCAP
A= Ix
ln 1
Tm Ta
K 0 Ta
ISSUE
P0C
SHEET 5 of 15
OF 4
where:
I=
short
circuit
study
Doc
A=
Tm =
Ta =
r =
234 (ref. IEEE.80 Table 1) or (as per Cl.no 7.2 of SESP-119.10 , Page 14 of 43 Table 10-1.)
tc =
TCAP =
thermal capacity factor = 3.42, (ref. Table 1) or (as per Cl.no 7.2
of SES-P-119.10 Page 14 of 43 table 10-1)
or r=
ISSUE
P0C
SHEET 6 of 15
OF 4
ISSUE
P0C
SHEET 7 of 15
OF 4
Symbol
If
Unit
kA
Value
46
Sf
0.7
IG
kA
32.2
Refer cl.6.4
V
C
m
6504.4
50
0.0185
Ohm
m
26.588
Ohm
m
5000
hs
0.10
Refer cl.6.4
Refer cl.4.2.1
Refer cl. 6.5
From Soil
Resistivity
Report
SES-P-119.10
page 14 of 43
SES-P-119.10
page 5 of 43
Cs
0.691
Refer cl.6.2
ts
Sec.
0.5
Refer cl.6.2
0.75
Km
Ks
Ki
0.634
0.302
2.399
Kii
Kh
1.323
Refer cl.6.5
h0
nR
20
Lr
2.5
LR
50
Refer cl.6.5
Refer cl.
4.2.2/6.5
SES-P-119.10
Page 18 of 43
Refer cl.6.5
Ls
1157
Refer cl.6.6
GPR
Ta
d
Remarks
Refer cl.3.2
SES-P-119.10
page 7 of 43
Refer cl.6.5
Refer cl.6.6
Refer cl.6.5
For grids with
ground rods as
per IEEE-80
ISSUE
P0C
SHEET 8 of 15
OF 4
Lc
1486
Refer cl.6.1
LM
1565.12
Refer cl.6.5/6.3
Lp
A
m
Sq.m
258
3920
Refer cl.6.5
Refer cl.6.1
Refer cl.6.1
Ny
10
Refer cl.6.1
Nx
14
Refer cl.6.1
1014.61
Refer cl.6.2/7.2
831.98
Refer cl.6.5/7.2
3564.78
Refer cl.6.2/7.2
V
Ohm
537.16
0.203
Refer cl.6.6/7.2
Refer cl.6.3
Tolerable
ETOUCH
ETOUCH
Tolerable
ESTEP
ESTEP
Rg
6.0
6.1
The Earthing grid for Power plant area will be arranged in the form of parallel
conductors to form a mat in order to limit the step and touch potential to
permissible limits.
Earth Grid area, A = 49 m x 80 m = 3920 m 2 (GTG Area Ref Dwg no
KA667088, P0C)
N
MAIN PLANT
AREA
49 M
80 M
ISSUE
P0C
SHEET 9 of 15
OF 4
= 10
= 14
a) Tolerable Etouch :
For average 50kg body weight, the tolerable touch voltage as per Eq. 32 of
IEEE-80 or as per Eq.10-4 of SES-P-119.10, page 6 of 43
Etouch
1000 1.5. Cs .
0.116
s
.
ts
0.09. 1
Cs 1
2hs 0.09
Cs = 0.691
Tolerable Etouch = 1014.23 V
b) Tolerable Estep
ISSUE
P0C
SHEET 10 of 15
OF 4
For average 50kg body weight, the tolerable step voltage as per Eq. 29 of
IEEE-80 or as per Eq.10.3 of SES-P-119.10, Page 6 of 43
0.116
ts
1 1
1
Rg 1
LT 20 A 1 h 20 / A
Where,
Rg = Grid Resistance in ohms.
= Average ground receptivity in ohm-m.
A = The area occupied by the ground grid in m2
LT = The total / effective buried length of conductors in m (L M)
h = Depth of grid in meters excluding asphalt covering if any.
Rg = 0.203
6.4 Calculation of maximum Grid potential rise
Maximum grid potential rise, GPR is
GPR IG.Rg
( as
ISSUE
P0C
30421008-3CL-00014-
SHEET 11 of 15
OF 4
Emesh
LM
LM Lc 1.55 1.22
Lr
LR
Lx Ly
2
Where,
Lr is the length of each ground rod = 2.5m
Lx is the Maximum length of grid conductor in x direction = 42m
Ly is the Maximum length of grid conductor in y direction = 80m
LR is the total length of ground rods = 2.5x 20 = 50m
LM (LT)= 1565.12 m The total/effective buried length of conductors
As per Eq.81 of IEEE-80, or as per Eq 10.9 of SES-P-119.10, page 9 of 43
the spacing factor for mesh voltage,
Km
1
2.
8
ln D D 2.h h Kii ln
8 Dd
4d
Kh .( 2n 1)
16.h.d
ISSUE
P0C
30421008-3CL-00014-
Kh 1
SHEET 12 of 15
OF 4
h
h0
nb
2.Lc
Lp
Lp
4. A
SHEET 13 of 15
OF 4
.Ks.Ki.IG
Ls
Ls = 1157 m
The spacing factor for step voltage, KS
1 1
1
1
Ks
1 0.5n 2
2.h D h D
Ks = 0.302
By substituting the above values,
Attainable Estep = 537.16 V
ISSUE
P0C
7.0
CONCLUSION
7.1
a)
b)
c)
d)
7.2
SHEET 14 of 15
OF 4
level
and
1014.23 V
Attainable Etouch
831.98 V
Tolerable Estep
3564.78 V
Attainable Estep
537.16 V
It can be seen that with the selected spacing, the attainable step and
mesh potentials are within permissible step and touch potentials
respectively.
ISSUE
P0C
SHEET 15 of 15
OF 4
ANNEXURE-1
SIZES OF MINIMUM CONDUCTORS AND LEADS
The electrical equipment shall be connected to the secondary earthing
system as described below for equipment safety Grounding as per SES-P119.10, Table 10.3.
EQUIPMENT
Transformers body
Transformer neutral
Generator Switchgear (GCB)
Generator
13.8kV Busducts
MV switchboards
LV switchboards & DBs
125V DCDBs.
UPS & UPSDB
MV motors
LV motors
Battery charger
Main Lighting Distribution Board
Lighting Panel
Power Receptacles
Control and Relay Panels
Street Lighting Poles
Cable Trays
Fuel Tanks
Big metal objects and not-electric
machinery
Main metal structures of buildings
Metal stack
Fence and Gate
NUMBER OF
CONNECTION
2
2
2
CONDUCTOR SIZE
2
2
2
2
2
2
2
2
2
2
1
2
1
1 every 10 m
4
240 Sq.mm cu
240 Sq.mm cu
240 Sq.mm cu
240 Sq.mm cu
240 Sq.mm cu
240 Sq.mm cu
240 Sq.mm cu
240 Sq.mm cu
240 Sq.mm cu
95 Sq.mm.cu
Half the power cable size.
240 Sq.mm cu
240 Sq.mm cu
50 Sq.mm cu
50 Sq.mm cu
95 Sq.mm cu
120 Sq.mm cu
50 Sq.mm cu
185 Sq.mm cu
95 Sq.mm cu
2
-
120 Sq.mm cu
95 Sq.mm cu
50 Sq.mm cu
As per GE
ISSUE
P0C