Sei sulla pagina 1di 16

CHW-A MODEL

HORIZONTAL UNCASED
FAN COIL UNITS

MAGIC AIRE CHW-A SERIES FAN COILS ARE ETLC


LISTED IN ACCORDANCE WITH UL 1995
AND ARE ASSEMBLED TO ORDER FOR COMPETITIVE DELIVERY.

UNITED ELECTRIC COMPANY, L.P.


501 Galveston St. Wichita Falls, Texas 76301 940-397-2100 Fax 940-397-2166
CHW-A 2.1

www. magicaire.com

Page 1

PI 06/01 6M
CHW-A 2.1

CHW-A MODEL
MAGIC AIRE Horizontal Fan Coil Units are engineered for permanent, ceiling mounted installations in the return airspace.
An insulated return air plenum is available for ducted return applications and is easily field converted for bottom or rear entry.
Units are available in various sizes from 200 to 1200 CFM, with or without factory installed electric heaters.
All Magic Aire fan coil units are designed for easy access and service of heaters, controls and motors. Electrical requirements are
120/208/240/265 VAC, 50/60 Hz single phase.

BOTTOM
FILTER
REMOVAL

UNIT

DISCHARGE
WIDTH
A

HANGER
WIDTH
B

OVERALL
WIDTH
C

PLENUM
RETURN
D

FILTER

COOLING
HEATING
COIL CONN. COIL CONN.

UNIT
WT.

PLENUM
WT.

006-CH*-A

15.10"

22.25"

26.50"

13.80"

10X15X1

5/8" OD

5/8" OD

42

13

012-CH*-A

18.10"

22.25"

26.50"

16.80"

10X18X1

5/8" OD

5/8" OD

45

15

018-CH*-A

27.10"

31.25"

35.50"

25.80"

10X27X1

5/8" OD

5/8" OD

59

20

024-CH*-A

36.10"

40.25"

44.50"

34.80"

10X36X1

5/8" OD

5/8" OD

67

25

030-CH*-A

45.10"

49.25"

53.50"

43.80"

10X45X1

5/8" OD

5/8" OD

81

30

036-CH*-A

54.10"

58.25"

62.50"

52.80"

10X54X1

5/8" OD

5/8" OD

115

35

Page 2

CHW-A 2.1

CH*-A Series
Electrical Data

Model #

Motor
FLA

KW Heat
@ 120
VAC

KW Heat
@ 208
VAC

KW Heat
@ 240
VAC

Miniumum
Circuit
Ampacity
@ 120
VAC

Maximum
Fuse Size
@ 120
VAC

Miniumum
Circuit
Ampacity
@ 208
VAC

Maximum
Fuse Size
@
208VAC

Miniumum
Circuit
Ampacity
@ 240
VAC

Maximum
Fuse Size
@
240VAC

006 CH*A

0.38

0.5

15

N/A

N/A

N/A

N/A

006 CH*A *-1.5E

0.38

1.5

16.1

20

N/A

N/A

N/A

N/A

006 CH*A *-2.0E

0.38

2.00

21.3

25

N/A

N/A

N/A

N/A

006 CH*A *-2.5E

0.38

2.5

26.5

30

N/A

N/A

N/A

N/A

012 CH*A

0.88

1.1

15

N/A

N/A

N/A

N/A

012 CH*A *-1.5E

0.88

1.5

16.7

20

N/A

N/A

N/A

N/A

012 CH*A *-2.0E

0.88

2.00

21.9

25

N/A

N/A

N/A

N/A

012 CH*A *-2.5E

0.88

2.5

27.1

30

N/A

N/A

N/A

N/A

012 CH*A *-3E

0.5

2.25

N/ A

N/A

14.2

20

16.3

20

012 CH*A *-4E

0.5

3.00

N/ A

N/A

18.7

25

21.5

25

012 CH*A *-5E

0.5

3.75

N/ A

N/A

23.2

30

26.7

30

018 CH*A

1.4

1. 8

15

N/A

N/A

N/A

N/A

018 CH*A *-3E

0.6

2.25

N/A

N/A

14.3

20

16.4

20

018 CH*A *-4E

0.6

3.00

N/A

N/A

18.8

25

21.6

25

018 CH*A *-5E

0.6

3.75

N/A

N/A

23.3

30

26.8

30

018 CH*A *-6E

0.6

4.5

N/ A

N/A

27.8

35

32.0

35

018 CH*A *-8E

0.6

6.00

N/ A

N/A

36.9

45

42.4

45

024 CH*A

1.8

2.25

15

N/A

N/A

N/A

N/A

024 CH*A *-3E

0.8

2.25

N/A

N/A

14.5

20

16.6

20

024 CH*A *-4E

0.8

3.00

N/A

N/A

19.1

25

21.8

25

024 CH*A *-5E

0.8

3.75

N/A

N/A

23.6

30

27.0

30

024 CH*A *-6E

0.8

4.50

N/ A

N/A

28.1

35

32.3

35

024 CH*A *-8E

0.8

6.00

N/ A

N/A

37.1

45

42.7

45

024 CH*A *-10E

0.8

7.50

10

N/A

N/A

46.1

60

53.1

60

030 CH*A

1.8

2.25

15

N/A

N/A

N/A

N/A

030 CH*A *-3E

0.9

2.25

N/A

N/A

14.7

20

16.8

20

030 CH*A *-4E

0.9

3.00

N/ A

N/A

19.2

25

22.0

25

030 CH*A *-5E

0.9

3.75

N/ A

N/A

23.7

30

27.2

30

030 CH*A *-6E

0.9

4.50

N/A

N/A

28.2

35

32.4

35

030 CH*A *-8E

0.9

6.00

N/ A

N/A

37.2

45

42.8

45

030 CH*A *-10E

0.9

7.50

10

N/A

N/A

46.3

60

53.2

60

036 CH*A

2.8

3. 5

15

N/A

N/A

N/A

N/A

036 CH*A *-6E

1.2

4.50

N/ A

N/A

28.6

35

32.8

35

036 CH*A *-8E

1.2

6.00

N/ A

N/A

37.6

45

43.2

45

036 CH*A *-10E

1.2

7.50

10

N/A

N/A

46.6

60

53.6

60

Page 3

CHW-A 2.1

CHW-A Blower Performance


with 3 Row Coil
CFM VS EXTERNAL STATIC PRESSURES
(DRY COIL DATA SHOWN)
0.15
0.20
0.25

MODEL
0.10

0.30

006

265

235

210

165

125

012

410

380

350

310

260

018

595

550

500

430

350

024

840

785

730

665

575

030

905

840

750

675

580

036

1190

1100

1000

860

700

CHW-A Blower Performance


with 4 Row Coil
CFM VS EXTERNAL STATIC PRESSURES
(DRY COIL DATA SHOWN)
0.15
0.20
0.25

MODEL
0.10

0.30

006

255

225

190

155

120

012

385

360

325

280

235

018

565

530

460

395

320

024

800

745

680

610

535

030

850

785

705

635

550

036

1130

1060

920

790

640

CHW-A Blower Performance


with 5 Row Coil
MODEL
0.10

CFM VS EXTERNAL STATIC PRESSURES


(DRY COIL DATA SHOWN)
0.15
0.20
0.25

0.30

006

240

210

180

150

110

012

370

335

300

260

220

018

530

480

425

355

300

024

750

700

630

565

500

030

800

735

660

600

510

036

1060

960

850

710

600

BLOWER CORRECTION FACTOR

MED

LOW

006

.90

.80

012

.90

.80

018

.95

.91

024

.95

.91

030

.90

.80

036

.95

.91

To get airflow data at medium and low speeds, multiply blower


performance by correction factor.
Page 4

CHW-A 2.1

CHW-A Blower Performance


006-036-CH*-A High Static Units (50/60 Hz)
Dry Coil Data
3-ROW 4-ROW 5-ROW

006-CH*-A
(50 Hz)
220 V

012-CH*-A
(50 Hz)
220 V

018-CH*-A
(50 Hz)
220 V

024-CH*-A
(50 Hz)
220 V

030-CH*-A
(50 Hz)
220 V

036-CH*-A
(50 Hz)
220 V

3-ROW 4-ROW 5-ROW

ESP

SCFM

SCFM

SCFM

ESP

SCFM

SCFM

0.20

332

307

288

0.20

368

346

328

0.25

310

287

270

0.25

352

331

314

SCFM

0.30

287

266

250

0.30

335

316

300

0.35

263

244

230

0.35

319

300

285

0.40

237

220

209

0.40

301

281

270

0.45

210

195

186

0.45

283

267

254
238

006-CH*-A

0.50

180

168

163

0.50

265

250

0.55

147

139

137

0.55

245

232

222

0.60

110

107

109

0.60

225

213

205

0.20

448

414

377

0.20

519

486

449

0.25

423

390

354

0.25

500

468

432

0.30

396

365

330

0.30

481

449

413

0.35

367

337

303

0.35

460

429

394

0.40

334

306

274

0.40

438

408

374

0.45

297

271

242

0.45

415

386

353

0.50

251

229

204

0.50

391

362

330

0.55

192

174

158

0.55

364

337

306

0.60

130

119

110

0.60

334

309

280

0.20

682

627

584

0.20

747

701

663

0.25

642

589

548

0.25

719

675

638

012-CH*-A

0.30

600

550

511

0.30

691

647

611

0.35

554

507

471

0.35

661

619

584

0.40

505

462

429

0.40

629

589

556

0.45

451

412

383

0.45

596

557

526
494

018-CH*-A

0.50

392

358

332

0.50

562

524

0.55

324

296

274

0.55

525

489

461

0.60

244

222

207

0.60

485

452

425

0.20

871

811

760

0.20

1032

974

914

0.25

823

766

717

0.25

995

940

880

0.30

772

718

671

0.30

957

904

846

0.35

717

667

622

0.35

917

866

810

0.40

657

611

570

0.40

875

827

772

0.45

591

549

513

0.45

832

786

733

0.50

517

480

450

0.50

786

743

692

0.55

430

398

378

0.55

737

698

649

024-CH*-A

0.60

319

295

293

0.60

686

649

603

0.20

1082

1007

948

0.20

1236

1162

1103

0.25

1024

953

898

0.25

1193

1121

1065

0.30

962

896

844

0.30

1148

1080

1026

0.35

897

836

788

0.35

1102

1037

985

0.40

828

771

727

0.40

1054

993

943

0.45

753

702

662

0.45

1005

947

900

030-CH*-A

0.50

671

625

591

0.50

953

899

855

0.55

580

540

511

0.55

900

849

808

0.60

476

441

420

0.60

844

797

759

Double 018 performances

036-CH*-A

Page 5

Double 018 performances

CHW-A 2.1

036-CHWA-3

030-CHWA-3
024-CHWA-3
018-CHWA-3
012-CHWA-3
006-CHWA-3

CHWA-3 Coil Capacities


LWT
LWT

Page 6
LWT

CHW-A 2.1

036-CHWA-4

030-CHWA-4
024-CHWA-4
018-CHWA-4
012-CHWA-4
006-CHWA-4

CHWA-4 Coil Capacities


LWT
LWT

Page 7
LWT

CHW-A 2.1

036-CHWA-2HW

036-CHWA-1HW

030-CHWA-2HW

030-CHWA-1HW

024-CHWA-2HW

024-CHWA-1HW

018-CHWA-2HW

018-CHWA-1HW

012-CHWA-2HW

012-CHWA-1HW

006-CHWA-2HW

006-CHWA-1HW

1 Row Heating
2 Row Heating

Page 8

CHW-A 2.1

036-CHW-3

030-CHW-3

024-CHW-3

018-CHW-3

006-CHW-3

012-CHW-3

3 ROW HEATING

HOT WATER HEATING CORRECTION FACTORS


Entering
Air Temp (F)

Entering Water Temp (F)


100o

110o

120o

130o

140o

150o

160o

170o

180o

50o

.419

.500

.579

.665

.742

.838

.917

1.000

1.090

.376

.460

.544

.629

.708

.791

.873

.963

1.048

.335

.419

.500

.579

.665

.742

.838

.917

1.000

.290

.376

.460

.544

.629

.708

.791

.873

.963

.251

.335

.419

.500

.579

.665

.742

.838

.917

.205

.290

.376

.460

.544

.629

.708

.791

.873

.167

.251

.335

.419

.500

.579

.665

.742

.838

55
60

65
70

75
80

Page 9

CHW-A 2.1

036-CHW-4

030-CHW-4

024-CHW-4

018-CHW-4

006-CHW-4

012-CHW-4

4 ROW HEATING

HOT WATER HEATING CORRECTION FACTORS


Entering
Air Temp (F)

Entering Water Temp (F)


100o

110o

120o

130o

140o

150o

160o

170o

180o

50o

.419

.500

.579

.665

.742

.838

.917

1.000

1.090

.376

.460

.544

.629

.708

.791

.873

.963

1.048

.335

.419

.500

.579

.665

.742

.838

.917

1.000

.290

.376

.460

.544

.629

.708

.791

.873

.963

.251

.335

.419

.500

.579

.665

.742

.838

.917

.205

.290

.376

.460

.544

.629

.708

.791

.873

.167

.251

.335

.419

.500

.579

.665

.742

.838

55

60
65

70
75

80

Page 10

CHW-A 2.1

CH*-A COIL
CONNECTION DIMENSIONS
LEFT HAND SHOWN
(Right Hand is Mirror Image)
A
3.688

3, 4, 5 Row Coil

4.125

C
B

3-1, 4-1, 3-2 Split Coil

3.688

1-3, 1-4,
2-3 Split Coil

D
3.688

1.750

1.750
4.125

R
S
2.250

4.125

R
S

R
S

CHILLED WATER
HOT WATER

S SUPPLY
R RETURN

UNIT

006-036-CHW-3-A

5.438

006-036-CHW-4-A

6.313

006-036-CHW-5-A

7.188

2.250

006-036-CHW-31-A

4.500

6.250

006-036-CHW-41-A

4.500

7.125

006-036-CHW-32-A

5.375

7.125

006-036-CHW-13-A

5.438

6.313

006-036-CHW-14-A

6.313

7.188

006-036-CHW-23-A

5.438

7.188

Page 11

CHW-A 2.1

CH*-A
ACCESS PANELS

27.00

24.75

DIM. A

25.00

DIM. B
DIM. C

UNIT SIZE

DIM "A"

DIM "B"

DIM "C"

RECOMMENDED
CEILING CUT OUT
SIZE ( .125")

FILTER SIZE
(LOUVERED
PANELS ONLY)

LOUVERED
PART NO.

006/012

28.75

31.00

29.00

25.15 x 29.15

1-14 x 20

738458

018/024

45.75

48.00

46.00

25.15 x 46.15

1-14 x 20

738452

030

56.75

59.00

57.00

25.15 x 57.15

2-14 x 20

738454

036

65.75

68.00

66.00

25.15 x 66.15

2-14 x 20

738456

VALVE PACKAGE
ASSEMBLY INSTRUCTIONS
for CHW-A UNITS
If piping is perpendicular to the stubouts of
the coil, as shown, connect the valve package to the
coil with two field supplied 5/8 couplings or 1/2
unions, and two 5/8 street ells.

5/8 Couplings or
1/2 Unions

5/8 Street Ells


NOTE: Left hand coil shown. Procedure is the
same for right hand configuration.
Page 12

CHW-A 2.1

UNCASED HORIZONTAL FAN COILS


CHW-A
3 & 4 ROW CHILLED WATER COOLING
WITH OPTIONAL ELECTRIC OR HOT WATER HEAT
SERIES DESIGNATION

ELECTRIC HEAT ADDERS (KW)*

HOT WATER HEAT ADDERS

Model Size
CHW-A-3
006
012
018
024
030
036

CHW-A-4

1.5-2.5

3-5

6-8

10

NA

NA

NA

NA

NA

NA
NA
NA
NA

NA

1 ROW

NA

2 ROW

As standard equipment all CHW-A series units are equipped with 3 speed Direct Drive 115v single phase motor.
All CHW-A series units are equipped with transformer and one fan relay for 24v control.
1.5 2.5 kW electric heaters are 120v. All other electric heaters are 208-230v.
Coil options are 3, 4, 3/1 split, 4/1 split, 1/3 split, 2/3 split, 1/4 split and 5 row (maximum). Split coils are for four pipe systems.
Use 4/1 split for 5 row coil pricing. Coil hand must be specified at time of order.

Consult Piping & Control Packages brochure for all factory selected thermostat and valve cluster combinations. See Control
Pricing & Coding and Valve Pricing Clusters & Components for pricing of same.

CHW-A OPTIONS (Contact factory for availability)


MODEL NUMBER
OPTIONS
006-CH
High static motor option 208-230/1 (.25 to .50 ESP)
Return air plenums factory installed
Pump Module Kit (field installed for CHW-A-HW)
Louvered or solid ceiling access panel
220v/1 50Hz motor

012-CH

018-CH

024-CH

030-CH

036-CH

Page 13

CHW-A 2.1

VALVE COMPONENTS
FOR CHW-A FAN COIL UNITS SERIES
B

WATER (2-WAY)
R
COIL

A
B

WATER (3-WAY)
R

COIL

1. VALVE SIZE: 5/8 (1/2) OR 7/8 (3/4).


2. CONTROL VOLTAGE (24, 115).
3. 2-WAY OR 3-WAY MOTORIZED VALVES,
TWO-POSITION, SPRING RETURN, NORMALLY
CLOSED CONTROL VALVES WITH MANUAL
OPENING LEVER.
4. THE FIXED GPM FLOW CONTROL VALVE
LISTED AT RIGHT IS SUFFICIENT UP TO 8 GPM.

COMPONENTS

A
SERVICE
VALVES

VOLTS

1/2

BALL VALVES
(BALANCE VAL)

3/4
1/2

GATE VALVES

B
2-WAY
MOTORIZED
CONTROL
VALVES
3-WAY
MOTORIZED

FLOW
CONTROL
(NOT BOTH
AT
SAME TIME)

Page 14

SIZE

3/4
24

1/2

115

1/2

24

3/4

115

3/4

24

1/2

115

1/2

24

3/4

115

3/4
1/2

BALL VALVE W/
MEMORY STOP
-ORCIRCUIT SETTER

3/4

(3 WEEKS)

3/4

1/2

CHW-A 2.1

WIRING DIAGRAM
CHW SERIES

DUAL MOTOR
ON 036 MODEL ONLY
BLACK
BLUE
RED

H
M
L

FAN
MOTOR

H
M
L

FAN
MOTOR

WHITE

BLACK
BLUE

CONNECT TO AN
APPROPRIATE
LINE VOLTAGE
THERMOSTAT
AND FAN SWITCH

RED

L1
N

WHITE

BLACK
WHITE

Page 15

CHW-A 2.1

ENGINEERING SPECIFICATIONS
Cabinets shall be fabricated of LFQ (min) steel. External
parts are to be made with a polyurethane based powder
coated A60 galvanealed, while internal parts are to be built
from G90 galvanized steel. Units shall pass 500 hour salt
spray test as described in ASTM B-117.

Fan wheel bearings shall be self aligning, sealed


cartridge, permanently lubricated ball bearings that
provide dependable fan operation for an average life of
200,000 hours (belt drive only)
Variable pitch motor sheaves.

Coils are to be tested at 500 PSI for operation at 400 PSI


guage. All water coils have air vents.
United Electric Company designs and builds its Magic Aire products to
comply and perform to the following standards:
AIR FLOW

Belt Drive Equipment


Direct Drive Equipment

AMCA 210
ASHRAE 51
ARI 430
ARI 440

Hydronic
Direct Expansion

ARI 410
ARI 210

IN DUCT SOUND RATINGS

Air Moving Equipment

ASHRAE 68
AMCA 330

SAFETY AGENCY LISTINGS

Coils
UL Report #
Equipment

UL 207
SA 3438
CAN/CSA C22.2 #236
ANSI/UL-1995
491893

COIL CAPACITY

General

ETL Report #
MATERIAL SPECIFICATIONS

Sheet Metal
Copper Tubing

Aluminum
MAJOR COMPONENTS

Motors
Wire
Electrical
Filters
Fiberglass

Paint

ASTM
ASTM
ASTM
ASTM
ASTM
ASTM
ASTM

A525
A527
B68
B75
B88
B251
B209

UL/CSA
NEMA
UL/CSA
UL/CSA
UL
ASHRAE 52
UL 181
UL 723 (25/50)
ASTM E-84
ASTM B117

UNITED ELECTRIC COMPANY, L.P.


501 Galveston St. Wichita Falls, Texas 76301 940-397-2100 Fax 940-397-2166
CHW-A 2.1

www. magicaire.com

Page 16

PI 06/01 6M
CHW-A 2.1