RAC-2000P
RAC-2000G
Version:2.1

Two Door Access Control Panel


z
z
z
z
z
z
z
z

Access Control
Alarm Monitoring
CCTV/DVR
Biometric
Video Verification
Facilities Management
Elevator Control
Protects personnel, visitors, buildings, equipments and other assets.

FCC and CE Radiation Norm


FCC
This device has been tested and found to comply with limits for Class B digital device
pursuant to Part 15 of Federal Communications Commission (FCC) rules.
CE
This device has been tested and found to comply with the limits of the European Council
Directive on the approximation of the law of the member states relating to electromagnetic
compatibility (89/336/EEC) according to EN 55022 Class A.
FCC and CE Compliance Statement
These limits are designed to provide reasonable protection against frequency interference
in residential installation. This device generates, uses and can radiate radio frequency
energy, and if not installed or used in accordance with the instructions, may cause harmful
interference to radio communication. However, there is no guarantee that interference will
not occur in television reception, which can be determined by turning the device off and on.
The user is encouraged to try and correct the interference by one or more of the following
measures:
Reorient or relocate the receiving antenna.
Increase the separation between the device and the receiver.
Connect the device into an outlet on a circuit different from that to which the receiver is
connected to.

CAUTION!
The Federal Communications Commission warns the user that changes or modifications to
the unit not expressly approved by the party responsible for compliance could void the
users authority to operate the device.

Table of Contents
Package Contents: ...........................................................................................4
Chapter 1 Product Overview............................................................................5
1.1 Features................................................................................................5
1.2 RAC-2000G/RAC-2000P Comparison Table ........................................6
1.3 Specifications........................................................................................6
1.4 Output ports ..........................................................................................6
1.5 Input ports.............................................................................................6
1.6 Startup ..................................................................................................7
1.7 Door Entry Modes.................................................................................7
Chapter 2 Physical Dimensions ......................................................................8
2.1 Dimensions............................................................................................8
2.2 Board Layout ........................................................................................9
Chapter 3 Safety Precautions ........................................................................10
Chapter 4 System Configuration and Wire Connections ............................11
4.1 System Configuration..........................................................................11
4.2 RAC-2000P/G Wire Connection .........................................................12
Chapter 5 Installation .....................................................................................18
5.1 Metal Housing Installation...................................................................18
5.2 ABA Track2 Reader Connection.........................................................19
5.3 Wiegand Reader Connection ..............................................................20
5.4 HID Reader Connection ......................................................................21
5.5 NO Mode Connection ..........................................................................22
5.6 NC Mode Connection ..........................................................................23
Chapter 6 Configuration.................................................................................24
6.1 Set NODE ID ......................................................................................24
6.2 RS232/RS485 selection......................................................................25
6.3 Reader Configuration..........................................................................26
6.4 Reader Power Configuration...............................................................27
6.5 NO / NC configuration.........................................................................28
6.6 Operation Setup..................................................................................29
6.6.1 Function key 00 Change NODE ID ..........................................30
6.6.2 Function key 01 Emergency Outlet Control .............................30
6.6.3 Function key 02 Create Single Temporary Card/ Valid Card ...30
6.6.4 Function key 03 Delete Single Temporary Card ......................31
6.6.5 Function key 05 Delete All Card Numbers ...............................31
6.6.6 Function key 10 Change MASTER CODE...............................31
6.6.7 Function key 99 System Initialization .......................................32
6.7 Important Tips.....................................................................................33
Chapter 7 Testing ...........................................................................................34
Chapter 8 Troubleshooting ............................................................................35
Chapter 9 Appendices ....................................................................................36
9.1 Appendix 1 (Wiring Material Requirements) ........................................36
9.2 Appendix 2 (DIP Switch Setting) .........................................................37
Chapter 10 .......................................................................................................38

Package Contents:
When you unpack your new RAC-2000P/RAC-2000G, Two Door Access Control Panel, please make sure
that all of the following items are included and are not damaged.

RAC-2000P or
RAC-2000G
Control Panel x 1

Quick Start
Guide x 1

Software CD
with manual x 1

If any of the following items are missing or damaged, please contact your dealer immediately.

Chapter 1 Product Overview


Thank you for purchasing this high quality Two Door Access Control Panel.
RAC-2000P and RAC-2000G is a truly dependable, flexible access control solution with real time on site or
remote operation, event recording, programmable duress, multiple access modes, anti pass back functions
for entrance security. RAC-2000P can support max. up to 15,000 card holders(10,000 for RAC-2000G), and
can connect 4 external ABA-T2 readers or 2 Wiegand readers (2 external ABA-T2 or 2 Wiegand readers for
RAC-2000G). Operated with Management Software, RAC-2000P and RAC-2000G is your ideal solution
for residential zone, hospital, warehouse, airport, offices, factories, university, campus, and parking lot
barrier etc. access control.
To better serve you, We also offers additional accessories for RAC-2000P/RAC-2000G such as:
z
z
z
z

RS-232 to RS-485 Converter : Model : EPC-402


TCP/IP Converter : Model: e-P132
Slave Readers: PXR-50 / PXR-52 / PXR-54 / PXR-62
Power Supply: Model: PSU-320
Metal Housing/Battery

To create a custom system, large or small, we also have controllers up to 4 doors, 8 doors, 16 doors, and 30
doors available, contact your sales representatives for more information.

1.1 Features
z 2 Door controller, fully expandable up to 255 sets, 510 doors per loop.
z Remote real time operation to enhance door control security
z Add/Delete cards using Master Card.
z Dynamic control of memory up to 10,000 events for RAC-2000G, 15,000 events for
RAC-2000P.
z Preset events recording function.
z Standalone/Network communication via RS232/RS485, dial-up modem and TCP/IP
(External Converter Required).
z Definable 128 sets of time schedule, 8 sets of door control schedule, and 200 sets of
holiday schedule for RAC-2000P.
z Alarm program and outputs
z Duress alarm
z 3 entry modes: card, card or pin codes, card and pin codes.
z Support card number with English alphabets, max. 13 characters.
z Programmable 1~255 seconds door open duration.
z Memory buffer full warning- when memory capacity reaches 90%, it will send an alarm
to remind the system administrator for data collection. System halts card data
storage as memory capacity reaches 100%.
z Limitation of unsuccessful swipe card attempts with real time alarm.
z 50 sets of programmable temporary card for RAC-2000P.
z Blacklist to prevent unknown usage of lost card for RAC-2000P.
z Door alarm and real time monitoring alarm.
z Built in RTC (Real Time Clock) maintaining accurate time regardless of power outage.
z On board lithium battery for data storage max. 1 year in case of power outage.
z CRC (Cyclic Redundancy Checker) to ensure data accuracy.
z Adjustable Baud Rate, max. up to 38400 bps for RAC-2000P

1.2 RAC-2000G/RAC-2000P Comparison Table


Description
Maximum number of cardholders
Maximum number of events stored.
Reader Ports

RAC-2000G
10,000 (max)
10,000 (max)
T2 x 2
Wiegand-26 x 2
User card verification
YES
128 sets of time schedule, 8 sets of door N/A
control schedule and 200 sets of holiday
schedule
Temporary Card
N/A
Blacklist
N/A
Adjustable baud rate max. up to 38,400 19,200 bps
bps

RAC-2000P
15,000 (max)
10,000 (max)
T2 x 4
Wiegand-26 x 2
YES
YES
50 sets
YES
38,400 bps

1.3 Specifications
Processor
Memory
Input/Output Ports
Cardholders/Events
Comm. Interface
Baud Rate
Reader Ports
Indicator
Operating Voltage
Power Consumption
Dimensions
Weight
Operating Temp.
Relative Humidity

8 bit
Program memory: 64K/
Data memory: 128K for RAC-2000G;
256K for RAC-2000P
Input: 8 (isolation)/Output: 4 Form C relay (NO,NC)
Max. 10,000 for RAC-2000G/15,000 for RAC-2000P
RS-232/RS-485
19,200 bps-N-8-1 for RAC-2000G/9,600. 19,200. 38,400
bps-N-8-1 for RAC-2000P
2*T2/2*Wiegand 26 bit for RAC-2000G/4*T2/2*Wiegand 26
bit for RAC-2000P
LED indicator for power, communication status and output
ports.
DC 12V 500mA (Excluding readers)
300mA(Excluding readers)
210mm(L) x 150mm(W) x 28.2mm(H)
390g
-10~55/14~131
20% ~ 95% (Non Condensing)

1.4 Output ports


RAC-2000P/G is built in with 4 RELAY to control electric lock or alarm. The maximum controllable voltage/
electric current is 28VDC/10A. RELAY output provides Normally Opened (NO) / Normally Closed(NC)
output selection(JP14JP17 jumper setting required).

1.5 Input ports


RAC-2000P/G has 2 sets of built-in Exit Button input ports.
RAC-2000P/G has 2 sets of built-in Door Sensor ports to detect door status. Such function is to be enabled
or disabled by means of proper software settings.
RAC-2000P/G has Case Sensor (RAC-2000P has 4 sets and RAC-2000G has 2 sets) for real time alarm
monitoring of reader. This function requires readers with case sensor (All our reader series have case
sensors) & proper software settings.
Please refer to Chapter 4 for installation guides.

1.6 Startup
When RAC-2000P/G is powered on, there will be a beep sound to indicate successful system startup. If the
beep sound continues endlessly, there may be problems with the panel. Please contact the dealer for
assistance.
During normal operation of RAC-2000P/G, red PWR LED will blink to indicate Ready Status. Under Ready
Status, you can enter card number and press  or swipe the card on the reader.

1.7 Door Entry Modes


RAC-2000P can save up to 15,000 valid card numbers (RAC-2000G can save up to 10,000). It supports
card number with English alphabets, max. up to 13 characters. When a valid card is swiped on the reader,
the green LED will blink with one beep, and simultaneously the control panel activates electric lock relay
(default 4 seconds) and opens the door.
When the exit button connected to RAC-2000P or RAC-2000G is pressed, the control panel will activate
electric lock relay (default 4 seconds) to open the door.

Chapter 2 Physical Dimensions


2.1 Dimensions

2.2 Board Layout

RS-485 / RS-232 Mode Selection

Communication LED

Reset button

Power LED

NODE ID configuration switch

Relay NC/NO selection


Relay Status LED

Reader power +12V/+5V selection

Hardware initialization selection

Wiegand/ T2 selection

Chapter 3 Safety Precautions


To ensure the maximum reliability of the RAC-2000P/RAC-2000G Two Door Access
Control Panel, please follow the guidelines listed below:
z
z
z
z
z
z
z
z
z

z
z
z
z
z
z

Always read the safety precautions carefully. Keep this user manual for future
reference.
Do not expose this control panel to extreme temperature or humid environment.
Do not alter this control panel for it will VOID your warranty.
Do not place this control panel in an area with an excessive amount of dirt.
Use only the power supply that comes with your control panel. Power supply of other
electronic devices may look similar, but they may affect your control panels
performance or damage it.
Electrical equipment may be hazardous if misused. Do not attempt to alter any
interior components. Doing so may be extremely dangerous and may result in fire or
electric shock.
Installation of this product must be done by authorized, qualified technicians.
Never pour away liquid into the opening that could damage or cause electrical shock.
If any of the following situations arises, get the product checked by a service
personnel:
- The power cord or plug is damaged.
-Liquid has penetrated into the equipment.
-The equipment has been exposed to moisture.
-The equipment does not work well or you cannot get it work accordingly to the User
Manual.
-The equipment has been dropped and damaged.
-The equipment has obvious signs of breakage.
Use only the metal housing specified / supplied by the manufacturer to ensure
compliance with EN55024 safety requirement.
Use only attachments/accessory cord specified by the manufacturer.
Unplug this product from wall outlet and refer service to qualified service personnel if
the product does not operate normally after following the user manual.
Use only the power cord designated by our dealer to ensure safety and EMC. When
used with other power supply voltage, the power cable will be damaged. Use the
standard power plug and cord set of specified country. Consult your product dealer.
Do not overload wall outlets, extension cords, or convenient receptacles on other
equipments as this may result in a risk of fire or electric shock.
When replacement parts are required, be sure that the service technician has used
replacement parts specified by the manufacturer or with same characteristics as
original part. Unauthorized substitutions may result in fire, electric shock, or other
hazards.
CAUTION: Danger of explosion if battery is incorrectly replaced. Replace only
with the same or equivalent type recommended by the manufacturer.

For better environmental protection, waste batteries should be collected separately


for recycling or special disposal.

10

Chapter 4 System Configuration and Wire


Connections
4.1 System Configuration

11

4.2 RAC-2000P/G Wire Connection

A21

A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
A13
A14
A15
A16
A17
A18
A19
A20
A21

PWR
GND
DATA1/W1
CLK1/W0
OK1
ERR1
BZ1
DATA2/W1
CLK2/W0
PWR
GND
DATA3/W1
CLK3/W0
OK2
ERR2
BZ2
DATA4/W1
CLK4/W0
485+
485GND

A1

Reader power output (12V or 5V)


Ground Connection
Reader 1 Data 0 (data) input
Reader 1 Data 1 (clock) input
Reader LED output for valid card
Reader LED output for invalid card
Reader Buzzer Output
Reader 2 Data 0 (data) input
Reader 2 Data 1 (clock) input
Reader power output (12V or 5V)
Ground Connection
Reader 3 Data 0 (data) input
Reader 3 Data 1 (clock) input
Reader LED output for valid card
Reader LED output for invalid card
Reader Buzzer Output
Reader 4 Data 0 (data) input
Reader 4 Data 1 (clock) input
RS-485 + or RS-232 TXD to PC
RS-485 or RS-232 RXD to PC
Ground Connection

12

RAC-2000P Wire Connection

DOOR1
Reader

DOOR2
Reader

RS-485 to PC

PWR
GND
DATA1/W1
CLK1/W0
OK1
ERR1
BZ1
DATA2/W1
CLK2/W0
PWR
GND
DATA3/W1
CLK3/W0
OK2
ERR2
BZ2
DATA4/W1
CLK4/W0
485+
485GND

Reader power output (Note 1)


External reader input (T2 or Wiegand)
Ready Status LED output (Note 2)
ERROR LED output (Note 2)
BUZZER output (Note 2)
Internal reader input (T2 or Wiegand)
Reader power output (Note 1)
External reader input (T2 or Wiegand)
Ready status LED output (Note 2)
ERROR LED output (Note 2)
BUZZER output (Note 2)
Internal reader input (T2 or Wiegand)
RS-485+ or RS-232 TXD
RS-485- or RS-232 RXD
Ground Connection

Note 1:The readers power supply is provided by the control panels power supply. A reader consumes
averagely 250mA power (please refer to the readers specification.)
a. Do not install excessive readers to prevent overload.
b. Do not use the same power supply when you are to connect electric lock or security alarms to the
control panel.
c. Use a separate power supply when the distance of the reader and the control panel exceeds 15
meters.
d. When the reader uses a separate power supply, make sure the ground is connected with the control
panel.
Note 2: Commonly used for both internal and external readers.

13

RAC-2000G Wire Connection

DOOR1
Reader

DOOR2
Reader

RS-485 to
PC

(Note

PWR
GND
DATA1/W1
CLK1/W0
OK1

Reader power output

ERR1
BZ1
DATA2/W1
CLK2/W0
PWR
GND
DATA3/W1
CLK3/W0
OK2

ERROR LED output (Note 2)


BUZZER output (Note 2)

ERR2
BZ2
DATA4/W1
CLK4/W0
485+
485-

ERROR LED output (Note 2)


BUZZER output (Note 2)

GND

1)

External reader input (T2


or Wiegand)
Ready Status LED output
(Note 2)

No Connection Needed
Reader power output

(Note

1)

External reader input (T2


or Wiegand)
Ready Status LED output
(Note 2)

No Connection Needed
RS-485+ or RS-232 TXD
RS-485-or RS-232 RXD
Ground Connection

Note 1:The readers power supply is provided by the control panels power supply. A reader consumes
averagely 250mA power (please refer to the readers specification.)
a. Do not install excessive readers to prevent overload.
b. Do not use the same power supply when you are to connect electric lock or security alarms to the
control panel.
c. Use a separate power supply when the distance of the reader and the control panel exceeds 15m.
d. When the reader uses a separate power supply, make sure the ground is connected with the control
panel.
Note 2: Commonly used for both internal and external readers.

14

15

RAC-2000P Wire Connection


Connect to ground

B1

FG

B2

GND

DC12V ground input

B3

+12V

+DC12V input (Note1)

B4

DOOR1+

B5

DOOR1-

Door 1 ALARM
RELAY

B6

ALARM1+

B7

ALARM1-

Door 2 DOOR
RELAY output

B8

DOOR2+

B9

DOOR2-

B10

ALARM2+

B11

ALARM2-

B12

PUSH1

B13

GND

B14

PUSH2

B15

SENSOR1

B16

GND

B17

SENSOR2

B18

CASE1

B19

GND

B20

CASE2

Internal card reader CASE SENSOR input

B21

CASE3

External card reader CASE SENSOR input

B22

GND

B23

CASE4

Power input

Door 1 DOOR
RELAY output

Door 2 ALARM
RELAY output

PUSH BUTTON
input

DOOR SENSOR
input

Door 1 card reader


CASE SENSOR
input

Door 2 card reader


CASE SENSOR
input

Door 1 DOOR RELAY output


(dry contact)
Door 1 ALARM RELAY output
(dry contact)
Door 2 DOOR RELAY output
(dry contact)

Door 2 ALARM RELAY output


(dry contact)
Door 1 PUSH BUTTON (Exit Button)
Ground Connection
Door 2 PUSH (Exit) BUTTON input
Door 1 DOOR SENSOR input
Ground Connection
Door 2 DOOR SENSOR input
External card reader CASE SENSOR input
Ground Connection

Ground Connection
Internal card reader CASE SENSOR input

Note 1:The readers power supply is provided by the control panels power supply. A reader consumes
averagely 250mA power (please refer to the readers specification.)
a. Do not install excessive readers to prevent overload.
b. Do not use the same power supply when you are to connect electric lock or security alarms to the
control panel.
c. Use a separate power supply when the distance of the reader and the control panel exceeds
15m.
d. When the reader uses a separate power supply, make sure the ground is connected with the control
panel.

16

RAC-2000G Wire Connection

Power input

Door 1 DOOR RELAY input

Door 1 ALARM RELAY

FG

B2

GND

DC12V ground input

B3

+12V

+DC12V input (Note1)

B4

DOOR1+

B5

DOOR1-

B6

ALARM1+

B7

ALARM1-

B8

DOOR2+

B9

DOOR2-

B10

ALARM2+

B11

ALARM2-

B12

PUSH1

B13

GND

B14

PUSH2

Door 2 PUSH (Exit) BUTTON


input

B15

SENSOR1

Door 1 DOOR SENSOR input

B16

GND

B17

SENSOR2

Door 2 DOOR SENSOR input

B18

CASE1

Reader CASE SENSOR input

B19

GND

B20

CASE2

Not connected

B21

CASE3

Reader CASE SENSOR input

B22

GND

B23

CASE4

Door 2 DOOR RELAY output

Door 2 ALARM RELAY


output

PUSH BUTTON input

DOOR SENSOR input

Door 1 reader CASE


SENSOR input

Door 2 reader CASE


SENSOR input

Connect to ground

B1

Door 1 DOOR RELAY output


(dry contact)
Door 1 ALARM RELAY output
(dry contact)

Door 2 DOOR RELAY output


(dry contact)

Door 2 ALARM RELAY output


(dry contact)

Door 1 PUSH (Exit) BUTTON


Ground Connection

Ground Connection

Ground Connection

Ground Connection
Not connected

Note 1:The readers power supply is provided by the control panels power supply. A reader consumes
averagely 250mA power (please refer to the readers specification.)
a. Do not install excessive readers to prevent overload.
b. Do not use the same power supply when you are to connect electric lock or security alarms to the
control panel.
c. Use a separate power supply when the distance of the reader and the control panel exceeds 15m.
d. When the reader uses a separate power supply, make sure the ground is connected with the control
panel.

17

Chapter 5 Installation
5.1 Metal Housing Installation

1. Align the notch of the control panel backer (No. 1) to the metal rail, press with a click to allow the
backer to move to and fro on the metal rail.
2. To dismount the control panel from the metal rail, press the orange button (No. 2) on top of the backer.
3. To remove the control panel from the metal rail, please gently push and pull the panel.
4. Mount the switch onto the metal housing by fastening the screws.
5. Mount the power supply onto the metal housing by fastening the screws.
18

5.2 ABA Track2 Reader Connection


(With RS-232 / RS485 converter)
Other devices

Note: The illustration above is for PXR-52ET/PXR-62ET readers wiring connection. For other readers
wiring connection with RAC-2000P/G, please refer to respective readers users manual.
Note: Please refer to Chapter 9.1 Appendix 1 for the requirements of all wiring materials.

19

5.3 Wiegand Reader Connection


(RS232 connection)
Other devices

Note: The illustration above is for PXR-52ET/PXR-62ET readers wiring connection.


For other readers wiring connection with RAC-2000P/G, please refer to respective readers users manual.
Note: Please refer to Chapter 9.1Appendix 1 for the requirements of all wiring materials.

20

5.4 HID Reader Connection

Note: The illustration above is for HID readers wiring connection.


For other readers wiring connection with RAC-2000P/G, please refer to respective readers users manual.
Note: Please refer to Chapter 9.1Appendix 1 for the requirements of all wiring materials.

21

5.5 NO Mode Connection

Other devices
Note: Please refer to Chapter 9.1Appendix 1 for the requirements of all wiring materials.
z
We suggest to use NO mode for connection of:
1. Electric Bolt Lock
2. Alarm Outputs

22

5.6 NC Mode Connection

Other devices
Note: Please refer to Appendix 1 of Chapter 9.1 for the requirements of all wiring materials.
z

We suggest to use NC mode for connection of:


1. Electric Strikes
2. Electromagnetic Lock

23

Chapter 6 Configuration
6.1

Set NODE ID

NODE ID should be set within the range 0255. NODE ID set as 0 stands for allowing reader to set
NODE ID. Please refer to Function key 00 described in Chapter 5.4.
The following is the quick configuration list of NODE ID:031, for NODE ID after 31, please refer to
Appendix 2 of Chapter 8.2
NODE ID: 0~31 Quick Configuration List (Condition ON=, OFF=)
ID No.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

SW Configuration
1~8
00000000
10000000
01000000
11000000
00100000
10100000
01100000
11100000
00010000
10010000
01010000
11010000
00110000
10110000
01110000
11110000

ID No.

SW Configuration
1~8
00001000
10001000
01001000
11001000
00101000
10101000
01101000
11101000
00011000
10011000
01011000
11011000
00111000
10111000
01111000
11111000

16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31

Note: For NODE ID : 0 ~ 255 configuration, please refer to Appendix 2 of Chapter 8.2

24

6.2 RS232/RS485 selection

For communication of only one control panel with 15 meters, We recommend to adopt
RS232 mode.
For communication of more than one control panel or communication distance is over 15
meters, We recommend to adopt RS485 mode

25

6.3

Reader Configuration

Set jumper JP13 to T2 for connection of ABA Track 2 readers.


Set jumper JP13 to Wiegand for connection of Wiegand readers..

26

6.4

Reader Power Configuration

Set jumper JP11 to +12V for connection of +12V readers.


Set jumper JP11 to +5V for connection of +5V readers.
Note 1:The readers power supply is provided by the control panels power supply. A reader consumes
averagely 250mA power (please refer to the readers specification.)
a. Do not install excessive readers to prevent overload.
b. Do not use the same power supply when you are to connect electric lock or security alarms to the
control panel.
c. Use a separate power supply when the distance of the reader and the control panel exceeds 15
meters.
d. When the reader uses a separate power supply, make sure the ground is connected with the control
panel.

27

6.5 NO / NC configuration

Set jumper to NO for connection of:


1.Electric Bolt Lock
2.Alarm output
Set jumper to NC for connection of:
1.Electric strikes
2.Electromagnetic Lock

28

6.6

Operation Setup
Function Key
00
01
02
03
05
10
99

Description
Change ID (DIP Switch node ID is set to 0)
Emergency Outlet Control
Create temporary card number/ Create valid card
number
Delete temporary card number/ Delete valid card
number
Delete all cards
Change Master Code
System initialization

Use reader with keypads for function key input. It is recommended to connect the OK LED of
RAC-2000P/G to the green/ blue LED of reader, and connect ERR LED of RAC-2000P/G to the red/ orange
LED of reader.
Please enter Master Code for configuration mode (default: 30191000).
The OK LED on reader blinks, waiting for function key inputs.
After function key inputs, OK LED will be lit continuously (except for key 01 and 05).
Function key 05 will delete all card numbers. Please be careful when using this function.
Function key 10 is for changing Master Code, the system will use the new Master Code.
In this case, PXR-52ETK is connected-OK1 of RAC-2000P/G to green LED of reader and ERR1 or
RAC-2000P/G to orange LED of reader. For connection of other readers, please refer to their respective
manuals.
* RAC-2000P/G will resume to ready status when idling for 30 seconds during operation.

29

6.6.1 Function key 00 Change NODE ID


No.

Description

Note

Ready mode, the red LED of reader is lit.

Enter Default Master Code : 30191000(Enter 

The green LED of reader blinks.

Enter 00 (Enter 

Green LED of reader is lit continuously.

Enter NODE ID, the range is 1~255 (Enter  )

Green LED of reader goes off. Red LED blinks and beeps four times.

RAC-2000P/G automatically restarts and red LED of reader is lit.

*Set DIP Switch NODE ID as 0, or this function will not activate.

6.6.2 Function key 01 Emergency Outlet Control


No.

Description

Note

Ready mode, the red LED of reader is lit.

Enter Default Master Code : 30191000(Enter 

The green LED of reader blinks.

Enter 01 (Enter ( 

RAC-2000P/G automatically restarts and red LED of reader is lit.

), reader beeps twice and the door opens.

6.6.3 Function key 02 Create Single Temporary Card/ Valid Card


No.

Description

Note

Ready mode, the red LED of reader is lit.

Enter Default Master Code : 30191000(Enter 

The green LED of reader blinks.

Enter 02 (Enter 

Green LED of reader is lit continuously.

6
7

Method 1: Detect the card to create card number.


Method 2: Enter the card number to add the new card.
Reader beeps once and green LED blinks.

Enter  to return to ready mode or go to item 4 to add another


card.
Function key (02) can add only one card each time. To add another record, repeat the same procedure.
For card number and pin code entry mode, application software setting is required.
8

30

6.6.4 Function key 03 Delete Single Temporary Card


No.

Description

Note

Ready mode, the red LED of reader is lit.

Enter Default Master Code : 30191000(Enter 

The green LED of reader blinks.

Enter 03 (Enter 

Green LED of reader is lit continuously.

6
7

Method 1: Detect the card to delete card number.


Method 2: Enter the card number to delete the card.
Reader beeps once and green LED blinks.

Enter  to return to ready mode or go to item 4 to delete another


card.
Function key (03) can delete only one card each time. To delete another record, repeat the same
procedure.
8

6.6.5 Function key 05 Delete All Card Numbers


No.

Description

Note

Ready mode, the red LED of reader is lit.

Enter Default Master Code : 30191000(Enter 

The green LED of reader blinks.

Enter 05 (Enter 

Green LED of reader goes off. Red LED blinks and beeps four times.

RAC-2000P/G automatically restarts and red LED of reader is lit.

). Delete all card numbers.

6.6.6 Function key 10 Change MASTER CODE


No.

Description

Note

Ready mode, the red LED of reader is lit.

Enter Default Master Code : 30191000(Enter 

The green LED of reader blinks.

Enter 10 (Enter 

Green LED of reader lights continuously.

Method 1, detect card to configure new master code.


Method 2, enter the card number of the master code.
Green LED of reader goes off. Red LED blinks and beeps four times.

RAC-2000P/G automatically restarts and red LED of reader is lit.

31

6.6.7 Function key 99 System Initialization


No.

Description

Note

Ready mode, the red LED of reader is lit.

Enter Default Master Code : 30191000(Enter 

The green LED of reader blinks.

Enter 99 (Enter 

Orange LED of reader lights.

Enter [0] for ignore, [1] for repair, [2] for refresh.
After entering [0] or [1], the red LED blinks four times and beeps four
times. RAC-2000P/G automatically restarts and red LED of reader is
6
lit.
After entering [2]. The red and green LED blinks alternatively for 5
seconds and beeps once. RAC-2000P/G automatically restarts and
red LED of reader is lit.
When the hardware installation is complete, make sure to execute system initialization to resume system
back to default values.

32

6.7 Important Tips


RAC-2000P/G is often installed separately from the reader with the wire connection attached to the reader
near the door. It is recommended to use wiring material listed in Appendix to ensure system efficiency and
stability.

Avoid installing RAC-2000P/G near the following locations:


*High voltage earth wire (ex: steel frame of a building).
*High voltage, noise, surge generator, such as motor or compressor.
Note: Please refer to Appendix 1 of Chapter 9.1 for connection wire requirement.

33

Chapter 7 Testing
The following test is conducted on reader with keypads. The OK1 of RAC-2000P/G is connected to green
LED of the reader and ERR1 is connected to the orange LED of the reader.
Configure system according to the following procedure after RAC-2000P/G is installed.
Please refer to the installation and wiring diagrams. The power LED blinks after power connection,
RAC-2000P/G is in ready mode. (Contact the dealer if the power LED does not blink).
X
Enter Master Code (default value is 30191000). Then press
Y The green LED of the reader blinks. Press9
9
, the orange LED of the reader is lit continuously.
Press 2and then. The red and green LEDs blink alternatively for 5 seconds and the reader beeps
once. RAC-2000P/G automatically restarts and the red LED is lit.
Z
Enter Master Code, and the green LED blinks.
[
Enter01(Emergency Outlet Control). The reader will beep twice and door relay 1, 2 activates.
The door will open and RAC-2000P/G resumes to ready status.
\
After 4 seconds (default door open duration), door relay 1, 2 will resume to standby mode.
]
Enter Master Code and the green LED of reader blinks.
^
Enter02, create a valid legal card as instructed in Chapter 5.4.3.
_ Swipe a valid card. The green LED of the reader will blink and beep once. Door relay will activate for four
seconds and resume to standby mode.
` Swipe an invalid card and the green LED of the reader will blink once. The red LED will blink and beep
four times simultaneously. Door relay will not activate.
Note: Please refer to the user manual for other function settings.
The above steps can be ignored if there is no keypad on reader. Follow the steps
below for hardware initialization.
Move JP12 JUMPER to the back of HW INITIAL. Restart the RAC-2000P/G and
there will be continuous beep sound. Set JP12 JUMPER back to NORMAL and
wait for 5 seconds. The RAC-2000P/G will beep and complete hardware
initialization.

34

Chapter 8 Troubleshooting
Q: The PWR LED of the control panel does not blink.
A: Please check if 12V power supply is connected to the power source. Verify if the power polarity is correct,
and the power input is sufficient or not.
Q: The reader beeps once after swiping card, there is no other sound and the door is not open.
A: Make sure the connection and interface of the reader are correct.
Q: The reader beeps after swiping card, there is other sound but the door is not open.
A: Make sure the RAC-2000P/G authority is correctly downloaded and electric lock connection is correct.
Q: The reader beeps after swiping card, there is no other sound and the door is open.
A: Make sure the BZ (Buzzer) wire of the reader is connected correctly.
Q: Cannot enter configuration mode after swiping MASTER CODE.
A: 1. Make sure the connection of the reader is correct.
2. If Master Code is forgotten, reset it from the software application.
Q: Cannot open the door after pressing exit button.
A: 1. Make sure the exit button is correctly installed.
2. Make sure the electric door lock is correctly installed.

35

Chapter 9 Appendices
9.1 Appendix 1 (Wiring Material Requirements)
Cable Type
RAC-2000P/G power cable
Door Relay and its power cable
Alarm Relay connection cable
Door Sensor connection cable
Exit Button connection cable
External reader connection cable
RS-232 cable
RS-485 cable

Cable Specification
18-22 AWG
18-22 AWG
18-22 AWG
18-22 AWG
18-22 AWG
Power: 2-conductor shielded cable 20AWG
Signal: 4-conductor (at least) shielded twisted
pair wire 2022AWG
4-conductor shielded twisted pair wire 20~22
AWG
4-conductor shielded twisted pair wire 20~22
AWG

Maximum Connection
Length
N/A
50M
50M
50M
50M
30M
25M
800 M

Upgrade the cable specification according to transmission distance.


Upgrade the cable specification as per environmental interference factors.
It is recommended to use larger cable cores for future use.
It is highly recommended to use shielded twisted pair wire for readers and communication cable to
increase transmission distance and interference resistance ability.

36

9.2 Appendix 2 (DIP Switch Setting)


(Condition: ON=, OFF=)
ID
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51

SW 1~8
00000000
10000000
01000000
11000000
00100000
10100000
01100000
11100000
00010000
10010000
01010000
11010000
00110000
10110000
01110000
11110000
00001000
10001000
01001000
11001000
00101000
10101000
01101000
11101000
00011000
10011000
01011000
11011000
00111000
10111000
01111000
11111000
00000100
10000100
01000100
11000100
00100100
10100100
01100100
11100100
00010100
10010100
01010100
11010100
00110100
10110100
01110100
11110100
00001100
10001100
01001100
11001100

ID
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103

SW 1~8
00101100
10101100
01101100
11101100
00011100
10011100
01011100
11011100
00111100
10111100
01111100
11111100
00000010
10000010
01000010
11000010
00100010
10100010
01100010
11100010
00010010
10010010
01010010
11010010
00110010
10110010
01110010
11110010
00001010
10001010
01001010
11001010
00101010
10101010
01101010
11101010
00011010
10011010
01011010
11011010
00111010
10111010
01111010
11111010
00000110
10000110
01000110
11000110
00100110
10100110
01100110
11100110

ID
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155

SW1~8
00010110
10010110
01010110
11010110
00110110
10110110
01110110
11110110
00001110
10001110
01001110
11001110
00101110
10101110
01101110
11101110
00011110
10011110
01011110
11011110
00111110
10111110
01111110
11111110
00000001
10000001
01000001
11000001
00100001
10100001
01100001
11100001
00010001
10010001
01010001
11010001
00110001
10110001
01110001
11110001
00001001
10001001
01001001
11001001
00101001
10101001
01101001
11101001
00011001
10011001
01011001
11011001

37

ID
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207

SW1~8
00111001
10111001
01111001
11111001
00000101
10000101
01000101
11000101
00100101
10100101
01100101
11100101
00010101
10010101
01010101
11010101
00110101
10110101
01110101
11110101
00001101
10001101
01001101
11001101
00101101
10101101
01101101
11101101
00011101
10011101
01011101
11011101
00111101
10111101
01111101
11111101
00000011
10000011
01000011
11000011
00100011
10100011
01100011
11100011
00010011
10010011
01010011
11010011
00110011
10110011
01110011
11110011

ID
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255

SW1~8
00001011
10001011
01001011
11001011
00101011
10101011
01101011
11101011
00011011
10011011
01011011
11011011
00111011
10111011
01111011
11111011
00000111
10000111
01000111
11000111
00100111
10100111
01100111
11100111
00010111
10010111
01010111
11010111
00110111
10110111
01110111
11110111
00001111
10001111
01001111
11001111
00101111
10101111
01101111
11101111
00011111
10011111
01011111
11011111
00111111
10111111
01111111
11111111

ONE YEAR LIMITED WARRANTY


HUNDURE warrant this product against defect in material or workmanship for
1 year from the date of purchase. If such a defect is discovered within this warranty period,
contact your direct vendor for repair or replacement of your unit.
When returning the product, you must ship the product in its original packaging or
packaging that gives an equal degree of protection. This warranty becomes invalid if the
factory-supplied serial number has been removed or altered on the product.
This warranty does not cover cosmetic damage or damage due to acts of God, accident,
misuse, abuse, negligence or modification of any part of the product. This warranty does
not cover damage due to improper operation or maintenance, connection to improper
equipment, or attempted repair by anyone other than HUNDURE.
In no event shall HUNDUREs liability exceed the price paid for the product from direct,
indirect, special, incidental, or consequential, damages resulting from the use of the
product, its accompanying software, or its documentation. HUNDURE make no warranty
or representation expressed, implied, or statutory, with respect to its products, contents of
use of this documentation and all accompanying software, and specially disclaim its quality,
performance, merchantability or fitness for any particular purpose. HUNDURE reserve the
right to revise or update its product, software or documentation without obligation to notify
any individual or entity.