Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Year
Daud, Muhamad Zalani, Transient behaviour modelling of underground high voltage cable systems, Masters by Research thesis, School of Electrical, Computer and
Telecommunications Engineering - Faculty of Informatics, University of Wollongong, 2009.
http://ro.uow.edu.au/theses/2032
This paper is posted at Research Online.
from
University of Wollongong
by
July 2009
Abstract
The behaviour of voltage and current transients when a high voltage (HV) cable is first
energised is a problem of practical significance to utilities. Modelling of this behaviour
on a suitable simulation platform is an attractive approach, in many cases, provided that
the results closely match real-world behaviour. This thesis presents modelling and analysis
of transients resulting from energisation of an unloaded cable using PSCADr /EMTDCTM
simulation software. An assessment of the applicability of existing frequency-dependent
(FD) cable models is given. The impact of transients on a simulated cable system is also
presented and discussed.
In cable system modelling, system components must be accurately modelled, primarily
the underground cable. Two common frequency-dependent cable models are based on the
travelling wave method, namely the FD-Mode and FD-Phase models. These models are
investigated by comparing their ability to predict energisation current transients resulting
from the switching of an unloaded 132 kV underground cable. The simulated results are
validated by comparison with the measurement data. It was found that, the FD-Phase
model provides more accurate results compared to the FD-Mode model. This model is
widely applicable and suitable for use in modelling a wide range of frequencies.
The FD-Phase model was used in this study to analyse the distribution of overvoltages
at sending and receiving ends of the cable system. Specifically, statistical analysis has been
carried out correlating the overvoltage magnitudes induced and the closing behaviour of the
circuit breaker (CB). Two statistical switching techniques have been applied, namely the
deterministic and probabilistic approaches. Based on the approaches studied, results from
probabilistic techniques are recommended owing to the fact that it is closer to reality.
iii
Certification
I, Muhamad Zalani Daud, declare that this thesis, submitted in partial fulfilment of the
requirements for the award of Master of Engineering - Research, in the School of Electrical,
Computer and Telecommunications Engineering at the University of Wollongong, is wholly
my own work unless otherwise referenced or acknowledged. The document has not been
submitted for qualification at any other academic institution.
......................................
Muhamad Zalani Daud
July 7, 2009
iv
Acknowledgements
I would like to express sincere appreciation for the intelligent advise, encouragement and
guidance of my supervisors, Dr Philip Ciufo and Associate Prof. Sarath Perera.
Thanks to Integral Energy (IE) and University of Wollongong Power Quality and Reliability
Centre (IEPQRC) for providing the power system network data and the cable energisation
test results used in this research.
Thanks to Mr Sean Elphick and Mr Neil Browne for their valuable advice and help on
the experimental energisation test data.
My gratitude also should go to all my friends in IEPQRC for their support and friendship.
Thanks also to the Ministry of Higher Education (MoHE) and University Malaysia Terengganu (UMT), Malaysia for the financial support.
My special thank to my family in Malaysia who has been my inspiration since the primary school until this stage of my education.
Finally, my deepest feelings and thankfulness I would like to dedicate to my wife for her
love, friendship and endless support and patience during my postgraduate studies.
vi
Table of Contents
Abstract
iii
Certification
iv
Acknowledgements
List of Publications
vi
List of Abbreviations
List of Figures
xi
List of Tables
xiii
1 Introduction
1.1 Statement of the Problem
1.2 Objectives of the Thesis .
1.3 Contributions . . . . . . .
1.4 Outline of the Thesis . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
1
1
4
5
5
2 Literature Review
2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Transients and Travelling Waves . . . . . . . . . . . .
2.3 Cable Modelling . . . . . . . . . . . . . . . . . . . . .
2.3.1 The Wave Equations . . . . . . . . . . . . . . .
2.3.2 Coaxial Cable Electrical Parameters . . . . . .
2.3.3 Impedance and Admittance Matrices . . . . . .
2.4 An Overview of Approaches and Existing Models . . .
2.4.1 Electromagnetic Transients Simulation . . . . .
2.4.2 Lumped Pi Models . . . . . . . . . . . . . . . .
2.4.3 Distributed Parameter Travelling Wave Models
2.5 PSCADr /EMTDCTM Cable Models . . . . . . . . . .
2.5.1 The FD-Mode Model . . . . . . . . . . . . . . .
2.5.2 The FD-Phase Model . . . . . . . . . . . . . .
2.6 Analysis of Switching Transient Overvoltages . . . . .
2.6.1 An Overview of Statistical Switching Studies .
2.6.2 Switching Phenomena and Statistical Methods
2.7 Summary . . . . . . . . . . . . . . . . . . . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
7
7
8
10
10
11
12
13
13
15
15
17
17
20
21
21
22
24
.
.
.
.
.
25
25
26
27
27
29
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
viii
3.4
3.5
3.6
3.7
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
30
31
31
34
35
35
37
37
40
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
42
42
43
43
44
46
48
49
49
50
50
50
53
55
57
60
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
62
62
63
64
64
65
66
66
67
68
69
70
72
74
76
76
78
Appendices
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
ix
A Fundamental Equations in Cable Modelling
A.1 The General Transmission Lines or Wave Equations . . . . . . . . . . . . .
A.2 Coaxial Cable Electrical Parameters . . . . . . . . . . . . . . . . . . . . . .
A.3 Impedance and Admittance Matrices . . . . . . . . . . . . . . . . . . . . . .
79
79
81
83
84
84
89
C Measurement Data
C.1 Current Transients from Experimental Energisation Tests . . . . . . . . . .
C.2 CB Pole Closing Times from Experimental Energisation Tests . . . . . . . .
95
95
99
References
100
List of Abbreviations
HV
high voltage
EHV
UHV
IEC
IEEE
EMTP
DC
direct current
FD
frequency-dependent
CB
circuit breaker
ULM
CC
cable constant
CF
curve fitting
BHTS
BVZS
BTTS
SWTS
CFTS
XLPE
cross-linked polyethylene
PVC
polyvinyl chloride
HDPE
high-density polyethylene
SVL
RMS
FFT
VT
voltage transformer
TV
tertiary voltage
CDF
SE
sending end
RE
receiving end
List of Figures
2.1
2.2
2.3
17
19
23
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
.
.
.
.
.
.
.
.
.
27
30
31
33
35
38
38
39
40
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
4.13
4.14
4.15
44
45
46
48
49
49
52
52
54
54
55
57
58
59
60
5.1
5.2
5.3
5.4
5.5
.
.
.
.
.
65
67
69
71
73
80
81
86
87
C.1
C.2
C.3
C.4
95
96
96
97
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
xii
C.5 Frequency spectrum of current transients from second measurement . . . .
C.6 Frequency spectrum of current transients from fourth measurement . . . . .
C.7 CB pole closing times for each test . . . . . . . . . . . . . . . . . . . . . . .
97
98
99
List of Tables
3.1
3.2
3.3
3.4
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
28
31
34
34
5.1
5.2
5.3
5.4
5.5
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
64
66
68
70
74
B.1
B.2
B.3
B.4
B.5
B.6
model-2
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
85
86
86
87
87
89
xiii
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Chapter 1
Introduction
1.1
In recent times, a steady increase in introduction of underground cables has been seen in new
residential areas across Australia [1]. Their penetration, particularly in urban areas, gives
significant benefits as they can provide additional network capacity without the need for
an expensive overhead transmission easement. They also result in reduced visual impact
as compared to the visual impacts of bulky overhead transmission systems. In certain
situations, the expansion of overhead lines is impossible due to political and environmental
pressures from the public and government. New technology has resulted in underground
cables becoming competitive with overhead lines on technical, environmental and economic
levels.
However, the use of underground cable has a great impact on the quality of power and
has become one of the popular topics of discussion among power engineers and researchers.
Of particular relevance is the high frequency current and voltage transients resulting from
switching operations. The problems depend on several factors, including configuration of the
underground cables, the characteristics of circuit breaker (CB), general network topology,
as well as other external factors. To a certain extent, transients can be worse for the case
of switching at the transition point of overhead to underground transmission. It is crucial
2
to address the impact of this switching on the design requirements, not only for extra high
voltage (EHV) systems but also in the case of medium transmission voltages, such as the
132 kV systems [2]. The systems just described are dominant in urban areas in Australia
such as Sydney and Brisbane [3].
Switching operations cause surges to develop and travel within the cable circuit. The
travelling waves result in high frequency damped oscillations in the cable system. Normally,
voltage and current transients are most severe at the receiving end of the cable with unloaded
conditions. This is due to multiple reflections of surges with different magnitudes occurring
at the end terminals of the circuit. The surges continuously travel throughout the circuit
until they are damped out by resistive elements. Generally, these surges are not only
dangerous to the cable being switched, but also to the nearby power system components
and surrounding circuits.
Underground cable energisation may occur anywhere within a transmission and distribution network, with the time and location of occurrences difficult to predict. Normally
the effects of transients are minimised by means of protective and preventive devices and
other switching techniques. The parameters of these devices may be obtained by evaluation
of switching transient voltage and current magnitudes for a particular network. Switching transients are considered to be one of the more difficult electromagnetic phenomena to
model and predict, and as such has been an ongoing research topic over several decades.
As such, modelling and software simulation of electromagnetic transients to study their
behaviour is one of the key topics of this research.
The Electromagnetic Transients Program (EMTPTM ) is one of the most widely used software tools for electromagnetic transient analysis. Subsequent and based on the EMTPTM
algorithm, the Electromagnetic Transients including DC (EMTDCTM ) program was introduced. To enable easy access and configuration of these programs, they come with computeraided design software, such as the Alternative Transients Program (ATPr ) and the Power
Systems Computer-Aided Design (PSCADr ). Both ATPr /EMTPTM and PSCADr /EMTDCTM
software suites are now major tools in power system studies.
3
There are a number of dedicated models in EMTP-type suites that can be used for cable
and transmission lines. The modelling choices vary from a simple pi model approach to more
complex ones. Some of the models are based on theories developed by early researchers,
which were established over 30 years ago [48]. These models are the frequency-dependent
type that take into account the distributed nature and frequency-dependent characteristics
of the cable (or transmission lines) parameters. In other words, they have been formulated
to model transient analysis. However, these models are not general and in some situations
may not be suitable for certain network configurations. For example, it is not always clear
whether the more sophisticated models should always be used in every transient simulation,
as under some circumstances simpler models may provide comparable results.
The literature shows that verification of the suitability of these models has been predominantly measured for the case of overhead lines, rather than their underground counterparts.
Less rigorous treatment of existing models on cables has raised questions in relation to
their applicability and reliability when applying these models to underground cable analysis. Such concerns can be addressed by further analysis of existing underground cable
models in terms of accuracy and suitability, specifically when they are intended to be used
under a specific network configuration.
Effort in validating cable models by detailed comparison is found for several cases carried
out in ATPr /EMTPTM [9, 10]. However, the approach used in [9] only gives examples of
single phase energisation of cables. Recently, Nichols et al. [10] carried out a practical comparison examining several frequency-dependent models such as KC Lee [11] and Semlyen [4]
approaches for the case of 3-phase energisation. However these models result in inconsistencies in transient magnitudes and introduce numerical instability. Consequently, suggestions
arise from previously studied models which lead to the requirement of studying the more accurate cable model. Such models are currently incorporated in the PSCADr /EMTDCTM ,
for instance, one of them is the Universal Line Model (ULM) [8].
The energisation of an underground cable results in high frequency voltage and current
transients. The behaviour of these transients are determined by many factors. For example,
4
the transient peak magnitudes are influenced by the closing span of CB contacts and the
closing angle (point-on-wave) on power frequency voltage [12]. The voltage transients applies
considerable stress on the insulation of cables as well as the insulation systems of nearby
components. These stresses may result from either transients with high magnitudes or cumulative occurrences of low magnitude overvoltages. It is essential to minimise the impact
of these transients. The assessment of peak values is of importance in the evaluation of insulation co-ordination and examination for determination of protection schemes. Due to the
variability of CB contact closure, a statistical method is the most practical means to carry
out such studies. To ensure precise and reliable results from simulation, a carefully crafted
model of the power system network, with inclusion of an accurate frequency-dependent cable model, is indispensable. The literature shows that these assessments are predominately
carried out for EHV transmission systems using the ATPr /EMTPTM programs [13, 14].
In summary, an examination of transient behaviour and switching overvoltages is an
important task in planning and design of a power system. These studies are important as
they have a direct bearing on the insulation requirements, cost and reliability of the designed
network. PSCADr/EMTDCTM is an attractive platform to carry out these studies.
1.2
The main aim of this research is to carry out studies on the behaviour of the transients
due to the energisation of a high voltage (HV) underground cable system. The two major
objectives of this research are now presented.
Firstly, in order to facilitate selection of a suitable model of an underground cable, the
goal is to investigate the suitability of the cable models currently incorporated in one of
the EMTP-type simulators - the PSCADr/EMTDCTM software suite. As this work is a
continuation of [15], of particular interest is a study on the applicability and validity of
other models, namely the frequency-dependent mode (FD-Mode) and frequency-dependent
phase (FD-Phase) models [16].
5
Secondly, an extensive study of underground cables is carried out with a view to provide
useful information on switching overvoltage distributions based on the statistical method,
as suggested by the IEC standards [17, 18]. The modelling of a power system network
employing the statistical evaluation of overvoltage data is to be carried out. An accurate
cable model investigated earlier is used to represent the underground systems.
1.3
Contributions
Modelling work presented in this thesis is carried out on PSCADr /EMTDCTM platform.
The network representing the power system connected to the cable under investigation
includes the source, overhead transmission lines, distribution transformers and the capacitor
banks. The two major contributions arising from this work are as follows:
1. Analysis and verification of the suitability of the FD-Mode and FD-phase models
by practical comparison, for the purpose of studying the behaviour of energisation
transients on HV cables.
2. An extensive analysis of overvoltage distributions caused by cable energisation using
statistical analysis for the network under study.
1.4
6
and other surrounding components are detailed. Frequency-dependent modelling of transmission lines and underground system are established. Some results from preliminary model
simulations are presented and analysed. Problems arising from the preliminary model are
identified and suggestions for improvement are provided at the end of this chapter.
Chapter 4 focuses on the procedures and methodology undertaken when organising
the experimental tests. Collection of data used in refinement of the preliminary model is
presented. Measurement data of current transients is synthesised to prepare suitable data
for comparison with simulated results. Refinement of the preliminary model and inclusion of
FD-Mode and FD-Phase models for simulation are then presented. Results from simulation
using both models are compared with the measurement data. The analysis of results is
presented in both time and frequency domain. Finally, an overview of overvoltage transients
which stress the underground cable and surrounding network components is presented.
Chapter 5 first provides an overview of switching transient evaluation methods. The
approaches used are also introduced. Then, the refinement of power system model to cater
for two different approaches considered is presented. Particularly, an explanation on the
construction of the multiple run system in PSCADr/EMTDCTM is given. Results from
simulations are presented for the different cases studied.
Chapter 6 provides conclusions based on the work covered in the thesis and provides
recommendations for further work.
Chapter 2
Literature Review
2.1
Introduction
8
porated in EMTP-type platforms are highlighted and compared to emphasise their different
properties and suitability for studying high frequency transients of an underground cable.
Then, modelling approaches of FD-Mode and FD-Phase models are presented. Finally, the
impact of transient overvoltages on the insulation system are reviewed.
2.2
9
used. These layers further worsen the transient due to their coupling effects. Every single
switching operation on a cable may result in the elements of a power system being subjected
to voltages and currents having a wide frequency range which may extend from 50 Hz to
the region of 100 kHz [21]. Over such a frequency range, the parameters of the system and
of the earth path are not constant. Such conditions require the frequency dependent nature
to be accounted for in order to achieve an accurate cable model.
In power system networks, cables are physically long and consist of joints and points of
discontinuity. The complexity of modelling such networks is compounded by the inductive
and capacitive elements that are distributed along its length. As a consequence, the surges
that travel from their origin end up with multiple reflections and refractions at the cable
ends, joints or may be eliminated at surge limiting devices. Furthermore, as the transmission
systems are finite in length, the transmissions and reflections of waves occur iteratively. The
travelling surge is normally referred as an incident wave and its reflection and refraction
can be solved using Kirchhoffs Law [19, 22].
Further complications arise when considering the reflection and refraction at various
junctions. These various terminations may consist of many interconnected lines or cable
circuits having different intrinsic impedances. Bewley [23] devised a convenient diagram
(Bewley Lattice Diagram) which shows the position and direction of motion of every incident, reflected and refracted wave on the system at every instant of time. The multiplicity of
successive reflections at multiple junctions can be monitored. However, it is difficult to apply the Bewley Lattice Diagram for the case of non linear devices. The graphical method of
Bergeron is suitable instead [24]. This method is valid for both linear and nonlinear models
and helps to calculate the delay of an electromagnetic signal on electrical circuits. Well documented information on reflected and refracted waves by means of the lattice diagram method
provided valuable contributions toward the development of a digital computer program for
the simulation of electrical transients. The Bergeron method (Method of Characteristics)
of implementing the travelling wave solution technique into the time domain solution has
been applied by Dommel in the development of EMTPTM [25].
10
2.3
Cable Modelling
(2.1)
d2 I
= 2I
dx2
(2.2)
= + j =
(r + jl)(g + jc) =
zy
(2.3)
where the real, , and imaginary, , parts in (2.3) are known as attenuation and phase
constants respectively. The per unit length parameters of the cable are described as r (resistance), l (inductance), g (conductance) and c (capacitance), whereas is the frequency.
Similarly, z and y are the corresponding series impedance and shunt admittance of the circuit. Another important parameter influencing the wave propagation is the characteristic
impedance, Zc , within the circuit. It is defined as the ratio of circuits series parameters to
its corresponding shunt parameters as given by
Zc =
r + jl
g + jc
(2.4)
The general solutions of (2.1) and (2.2) are described using the DLambert equations as
(2.5)
11
I(x) = I0+ ex + I0 e+x
(2.6)
where the plus and minus signs denote the forward and backward directions of wave propagations respectively.
Depending on the nature of study, modelling of a cable may be described using a constant
or a frequency-dependent parameter approach. Underground cable energisation transient
modelling involves the consideration of frequency variations. Increase in frequency further
increases the non-linear characteristics of cables and the nearby system components which
require frequency-dependency to be accounted for. These greatly increase the burden in
modelling. Marti et al. [27] has postulated several factors that should be treated carefully
in order to achieve better accuracy in modelling such as:
The distributed nature of transmission system parameters.
Asymmetrical arrangement of coupled conductors with ground return.
The strongly frequency-dependent series parameters especially for the ground mode.
12
further minimse the skin effect. In modelling, the resistivity of the stranded core is normally
modified to a new value to account for the air gaps within the core conductors [28].
The proximity effect also greatly affects the non-uniformity of current distribution in
the cable conductor. The conductors in close proximity will produce magnetic flux linkages
which can disturb current distribution amongst each other. Increasing conductor spacing
might reduce such coupled influences. The significance of this effect can be seen particularly
in multi-conductor cable and cables in the same duct. This effect also depends on the size
and length of the conductors. It is another complex and crucial branch in studying electric
cable transient phenomena. Further information on this effect on underground cable can be
found in [30].
In general, the geometrical and material parameters (details of calculation are presented
in Appendix A (Section A.2)) are included as input data in the modelling of a cable system in
PSCADr /EMTDCTM [16,31]. Simplifying assumptions may be considered to overcome the
lengthy and complicated solution of more general ones such as presented in Section 2.3.1. For
instance, in some cases, simple equations which neglect the effect of resistance and conductance are considered valid since the severity from travelling waves is most pronounced in
the early stages before they become attenuated. Another example is when considering a
lossless transmission cable, such as one with nearly perfect conducting materials [26].
13
each conductor (core and sheath with respect to ground). Similarly, the off-diagonal quantities represent their respective mutual impedance (or admittance). The elements in these
matrices are complex and may be given in Cartesian format such as zij = rij + jxij and
yij = gij + jbij . In some circumstances, a correction algorithm may be applied to these
matrices to account for electrical effects such as long line distances. The type of ideal transposition settings may also affect the elements of these matrices [16]. Consequently, the
shunt conductance, g, in some situations can, in general, be ignored as the loss angle of
underground cables is very small. The matrix b is symmetric and has positive values for
main diagonal terms which represent the shunt susceptance while the off-diagonal terms are
zero for underground cables [2].
2.4
14
response). A time domain simulation can then be carried out using convolutions that use
the time domain counterpart of their variables, which are obtained from the inverse Fourier
transform [5, 6]. Some of the models prefer the variables to be transformed into z-domain
by means of the z transformation [7]. The computational effort in modelling is greatly
reduced since the introduction of the recursive convolution technique in the solution of the
time domain convolution integrals [4].
The modelling is difficult when multi-phase conductors are considered. Furthermore, the
nature of frequency dependence is strong for the case of underground cables and the asymmetric structure of transmission lines. In practice, the physical system of conductors (mutually coupled) are firstly decoupled into a mathematically-equivalent decoupled one. The
modal decomposition process [36, 37] increases the burden from the modal transformation
matrices which are also frequency-dependent. Although a constant transformation matrix
can be assumed, it is crucial to consider a frequency-dependent transformation matrix (Tv
or Ti for voltage and current variables respectively) in modelling. L Marti [6] developed a
more accurate model for transmission lines and underground cable which accounted for the
frequency dependence of transformation matrices. However, at the present time and in the
recent past, an increasing effort to overcome difficulties in handling the frequency-dependent
transformation matrix has been evident. Eventually, the direct phase domain models are
much more reliable today [7, 8].
In either EMTPTM or EMTDCTM type programs, the models are divided into two broad
categories; the lumped parameter or the distributed parameter travelling wave models. The
suitable approach may be selected depending on the study requirements. A wide range of
models are available including the lumped pi, Bergeron, Noda, KC Lee, Semlyen, L Marti,
J Marti (FD-Mode) and the ULM (FD-Phase) models [11, 31]. The following section provides an analysis of these models except the FD-Mode and FD-Phase models where detailed
investigations are documented in Section 2.5.
15
16
the characteristic impedance. In other words, it is roughly equivalent to using an infinite
number of pi sections with a lumped resistance in the middle and at line ends to represent
losses. An early attempt by Dommel [25] to provide a frequency-dependent transmission
line model was based on this approach. His model forms the basis of the time domain
algorithm used in the development of transmission line models in EMTPTM . However, the
frequency response of Bergerons method is only good in the neighborhood of the frequency
at which the parameters are evaluated. It is not recommended for high frequency transient
studies [31].
Noda et al. [7], introduced an Auto-Regressive Moving Average (ARMA) model which
employed the method as a substitute for the existing method in approximating time domain convolution. As the modelling is directly performed in the phase domain, it avoided
the use of frequency-dependent transformation matrices. Furthermore, numerical effort is
minimised and stability is greatly increased. However, as the z-transform approach was
used, the resulting model is dependent on the time step settings (t) and is not directly
applicable for an arbitrary time step [42].
KC Lee and Semlyen models are amongst the other dedicated models incorporated in
EMTPTM [4, 11]. The KC Lee approach is suitable for the representation of untransposed
transmission lines. For underground cables, it requires manual calculation of modal transformation matrices [15]. However, as the constant parameter representation is assumed, the
heavily frequency-dependent nature of cable systems means that this method may not be
suitable. The Semlyen model, on the other hand, is theoretically suitable for a wide range
of frequencies. The recursive implementation of convolutions introduced has contributed to
the ongoing research in cable modelling because of the ability in reducing computational
efforts [4]. However, for underground cables, it is very poor in terms of stability of numerical
calculation as proven in recent studies [10].
L Marti [6] has implemented the frequency-dependent calculation of modal transformation matrices to his model which is suitable for cable systems. The formulation improves the
weakness encountered in the J Marti [5] model, especially for the case of strongly frequency-
17
dependent underground cables and untransposed transmission lines. Unfortunately, this
model is not currently available as a dedicated cable model in PSCADr/EMTDCTM . However, for certain cases of transient studies, the J Marti or FD-Mode model can be still used,
provided that a suitable frequency is specified for its transformation matrix [5, 31]. This
model will be further explored in Section 2.5 together with the ULM (FD-Phase model).
2.5
Literature has shown that modelling the distributed nature and frequency-dependent characteristics of underground cables are absolutely necessary in order to achieve better accuracy
of transient modelling. Two distributed parameter travelling wave models in PSCADr will
be treated in this section - the FD-Mode and FD-Phase models. Performance of these
models are to be compared and presented in Chapter 4.
Figure 2.1: Single phase frequency domain equivalent circuit of FD-Mode model [27]
18
and Emhist are the wave transfer sources defined from the change of variables method [43]
used for the simplification of mathematical modelling. For example, they can be represented
as forward travelling wave functions at both sending (Fk ) and receiving (Fm ) ends by
Ekhist = (Vm + ZC Im )e = Fm e
(2.7)
Emhist = (Vk + ZC Ik )e = Fk e
(2.8)
where is the total length of the cable. Whereas, the propagation function, A, as a function
of frequency is described by
A() =
1
= e()
cosh[()] sinh[()]
(2.9)
Figure 2.1 depicts a general line model in terms of the characteristic impedance function,
ZC , and the propagation function, A, with the equivalent transfer sources [27,31]. However,
the time domain model is preferred since it is directly compatible with the time domain
solution algorithm in EMTP-type program. Therefore, the time domain form of (2.7) and
(2.8) are evaluated from convolution integrals as
Ekhist (t) =
Emhist (t) =
fm (t u)a1 (u)du
fk (t u)a1 (u)du
(2.10)
(2.11)
The time domain of the propagation constant, a(t) is obtained from inverse Fourier transform and has the form as illustrated in Figure 2.2. The lower limit of the integral, ,
is the travel time and is calculated using the phase constant, (imaginary term), of the
propagation function. Evaluation of the convolution integrals are greatly accelerated using
the recursive convolution [4]. Unlike the constant parameter model, where the constant
parameter lossless line is considered, the characteristic impedance, ZC , in this approach is
synthesised in the frequency domain with an R C network with constant Rs and Cs.
19
Further details on the evaluation of variables for this model are described in [5], whereas,
detailed explanation on how these variables are implemented in EMTDCTM can be found
in [31].
(2.12)
(2.13)
[T ]Tv = [T ]1
i
(2.14)
The voltage and current variables can be solved individually in the modal domain which is
identical to the treatment of a single phase line. The modal transformation matrices ([Tv ]
and [Ti ]) for matrix diagonalisation used in (2.12) and (2.13) are obtained from eigenvalue
problem and are calculated using cable constant (CC) routines in PSCADr /EMTDCTM .
Consequently, as constant transformation matrices are assumed in this formulation, user
should specify suitable constant frequency for these matrices in PSCADr /EMTDCTM [16].
20
YC V i = 2
n
X
k=1
Hk (t k ) if ar
(2.15)
where V and i are the voltage and current respectively, k is the travelling time and if ar is
the reflected current wave of the receiving end. Hk denotes the modal component of H().
Solution for (2.15) requires H() and YC () to be replaced by a low order rational function
approximation to permit a recursive implementation of convolutions [4]. Fitting of YC is
a straightforward task as it has no time delays and it can be fitted directly in the phase
domain using Vector Fitting (VF) [44] as
si
Him (s)
N
X
cm
s am
m=1
(2.16)
However, fitting of H() is quite difficult as its elements contain modal contributions with
widely different time delays. Firstly, a frequency-dependent transformation matrix is used
to calculate its modes. Then, each mode is fitted using (2.16). Finally, with known values
of poles and time delays from modes, each element of H() is fitted of the form [8]
Ng X
N
X
h(s) =
(
i=1
cm,i
)esi
s
a
m,i
m=1
(2.17)
21
This model is general and theoretically accurate for most overhead lines as well as widely
different modal time delays as found in underground cables. Further detail on the general
aspects of this model are described in [8] and its implementation in PSCADr /EMTDCTM
can be found in [31, 41].
2.6
The preceding sections so far described the modelling related problems of an underground
cable. Selection of a proper model is crucial in transient modelling in achieving better accuracy, particularly at higher frequencies. In addition to this work in studying the behaviour
of transients in electrical systems, this section will further explore the transient overvoltage
distributions due to cable energisation. The most accurate cable model will be selected
(presented in Chapter 4) for this purpose and detailed analysis is presented in Chapter 5.
The information will be useful for future consideration on design of the protective levels in
relation to this class of cable systems.
22
tion which is confirmed by different measurements in field also can be adopted. The latter
method has been used in [46] in studying the influence of the cable length and type of
insulation compound on the risk of insulation failures on MV and HV lines. Some statistical switching studies have also been performed in EMTP-type simulators such as a large
scale statistical switching analysis by Lee and Poon [13] and case studies on the impact
of protective devices carried out in [14]. In the case of a long, cross-bonded cable system,
studies on the overvoltage sensitivity stress on the insulation can be found in [45]. Some
general and specific modelling guidelines in relation to switching overvoltage studies are
also provided [47, 48].
23
terminals. Furthermore, strong coupling effects between phases can cause unexpected high
magnitude and frequency overvoltages. Controlled switching [12], for example, may be used
to make sure closing of contacts at the zero crossings of the power frequency voltage. In
this closing practice, the deviation in pole closing times on 3-phase closing should be small
enough to prevent the pre-strike phenomena. Otherwise, pre-insertion resistors should be
used instead, which cost more [49].
Due to the random behaviour of CB poles during switching, probability analysis is the
most practical way in providing useful data on switching overvoltages. In practice, there
are several analytical methods [50]. However, the statistical study approach is the most
common. Random closing of contacts can be assumed to follow the normal distribution.
Statistics are applied to switching data to derive relevant information suitable for insulation coordination. Cumulative probability distribution of overvoltages is calculated and
compared with the ability of the system to withstand transient overvoltages. An analysis
of several statistical switching evaluation techniques can be found in [51]. Some guidelines
such as the procedures and the reference values are included in the IEC standards [17, 18].
For example, the diagram illustrated in Figure 2.3 may be useful.
Figure 2.3: Range of 2 % slow-front overvoltages at the receiving end due to line energisation
and re-energisation [18]
24
2.7
Summary
This chapter presented an overview of the behaviour of transients due to switching operation on transmission systems. The development of EMTP-type simulation programs was
reviewed with focus given primarily on cable modelling issues. In Section 2.6, the importance
of switching studies was addressed. Of particular interest is in providing relevant data for
the evaluation of insulation coordination and protective schemes for the network.
Over the last 30 years, interest has been primarily focused on the accuracy of transmission line modelling. In other words, underground cable models have not been as exhaustively examined and validated as their overhead line counterparts. Furthermore, it is
unclear whether more sophisticated models or simpler methods should be used for a cable, particularly, when considering modelling and simulation of high frequency behaviour
of transients of underground cable system.
There are two common approaches currently in practice to represent a frequency-dependent
cable model. They are either the formulation in modes (FD-Mode model) or the direct formulation in phase domain (FD-Phase model). Theoretical aspects of these models have been
presented. Literature review also highlighted the advantages of phase domain modelling over
the traditional modal domain approach. However, it is crucial to consider assessment of
both approaches particularly when a suitable model is intended to be used in a specific
network, such as the power system network under study.
The issues stated above are to be investigated by careful simulation, employing the FDMode and FD-Phase models to validate their effectiveness against real-world behaviour.
Then, further studies may be performed on the energisation transient behaviour of a cable
using the most accurate model. The modelling work for such purposes is presented in
Chapter 3.
Chapter 3
Introduction
26
imental measurements. Simulation results obtained from preliminary model for FD-Mode
and FD-Phase approaches are presented and discussed.
3.2
Energising a long cable system is similar to the switching of a capacitive component. This
is due to the complex physical cable construction which has a predominantly capacitive
behaviour. Furthermore, transients developed are influenced by the non-linear characteristics of system components in the vicinity. This means that amplitude, frequency and wave
shape of the current and voltage oscillations are determined by the configuration of the
network as seen from the terminals of switching devices. It is therefore of great importance
to include detailed modelling of these components. For example, as recommended in [53],
specific modelling should be considered on the surrounding network of at least up to one
bus back from the switching location.
The cable to be modelled with a frequency-dependent model is a 132 kV underground
high voltage (HV) cable linking Baulkham Hills transmission substation (BHTS) to Bella
Vista zone substation (BVZS) as illustrated in Figure 3.1 [15]. In this network, power
is supplied by a 132 kV source (upstream) through several kilometres of overhead transmission feeders. Overhead lines are amongst the major components that characterise the
travelling surges from the switching of an underground cable. They are modelled using
the frequency-dependent approach. However, due to lack of detailed modelling data, other
frequency-dependent components such as transformers located near the switching point, are
represented as lumped parameter model. The source and capacitor banks are also developed
based on lumped element models and are included in the circuit. Further details on the
treatment of these components are presented in Section 3.3.
27
Figure 3.1: Single line schematic diagram of power system network under study
3.3
28
models have been used in the simulations, where it was noted that the difference between
the results obtained is marginal as will be demonstrated in Section B.1 of Appendix B.
In this work, source model-2 was used to represent the 132 kV upstream voltage source of
the network in Figure 3.1. The values of positive and zero sequence parameters (resistance,
Rp , and inductance, Lp values at 50 Hz) in the parallel circuit can be obtained from series
sequence components (Rs and Ls ) using the following expressions
Rp =
Rs2 + (Ls )2
Rs
(3.1)
Lp =
Rs2 + (Ls )2
2 Ls
(3.2)
where , is the angular frequency. Table 3.1 provides the input data for the voltage source
model-2, whereas calculation details of sequence impedances are given in Appendix B (Section B.1).
Page
1
2
3
4
29
30
31
3.4
Underground cable
No.
1
2
3
4
5
6
7
8
Radius (m)
0.01525
0.01675
0.03525
0.03725
0.03975
0.04025
0.04275
0.04525
32
The values in Table 3.2 have been used to calculate the capacitance between cylindrical
shells to validate the existing measurements based on example given in [28] (Equation (10)).
It has been found that the new capacitance value was approximately 10 % lower than the
value given by the manufacturer. Apparently in this case, a smaller value of the thickness of
the layer has been provided by the manufacturer. Therefore, from this example, it is important to consider measurement of cable layers from both the data stated from manufacturer
and a cable sample.
However, the data given in Table 3.2 are not the final input data required. For the conductor and insulator properties, as well as the sheath radius, it is also necessary to convert
the existing data to a new set of data to account for inner and outer semiconducting layers
and the air gaps that exist within the stranded core. This is a crucial procedure in the transient simulation of a cable since cable constant (CC) routines in PSCADr /EMTDCTM [31]
only perform calculations based on a simplified configuration of a coaxial cable (detailed
in Appendix A (Section A.2)). It has also been shown that these additional layers have
a significant impact on the wave propagation characteristics in cable system [28]. Figure
3.4 depicts a geometrical representation of a coaxial cable in PSCADr /EMTDCTM . From
Figure 3.4, it is apparent that the cable core is treated as a solid conductor (1st conductor)
rather than stranded wires with air gaps. Similarly, the sheath is represented as a tubular conductor (2nd conductor). To account for such physical conditions the corrected core
resistivity value, 1 , can be calculated using (3.3) [28]
1 =
c r12
A
(3.3)
where c =1.678E-8 m is the original core resistivity value for copper and A is the crosssectional area of the conductor. Similarly for the relative permittivity of XLPE insulator,
1 , it can be calculated with (3.4)
1 =
C ln rr21
20
(3.4)
33
r3 =
Ash
+ r22
(3.5)
where Ash is the total cross-sectional area of cable sheath as stated by manufacturer. The
thickness of outer layers (PVC and HDPE) has been measured to be approximately 5 mm.
Therefore, the new value for the 2nd insulator was approximated as 0.043087 m. Values
for the sheath resistivity, 2 , and the relative electrical permittivity of 2nd insulator, 2 ,
remain unchanged as in [15], while the relative magnetic permeability was assumed to be
identical for all layers (r =1). Table 3.3 depicts the final converted data entered into
PSCADr /EMTDCTM cable model. Impedance (z) and admittance (y) matrices are calculated by CC routines based on the geometrical and physical properties input data entered
by user. The supporting routines were originally developed based on the simplified coaxial
cable geometry model where details can be found in [34, 35].
34
Table 3.3: Cable dimensions and material properties input data
Outer
Resistivity, Relative electrical Relative magnetic
Radius, (m) (m)
permittivity
permeability
Conductor, r1
0.01525
1.946E-8
1
st
1 insulator, r2
0.03725
3.052
1
Sheath, r3
0.038087
1.678E-8
1
2nd insulator, r4
0.043087
3.125
1
Layer
Cable C1
Cable C2
Cable C3
0
1.1985
0.11
1.0075
0.22
1.1985
The ground resistivity was assumed at 100 m based on default value in PSCADr/EMTDCTM .
It was approximated based on Carsons homogeneous earth formula [57]. Users can select
either analytical approximation or numerical integration for the solution to the ground
impedance integral. It is recommended to use the analytical approximation due to time
savings and numerical stability. However, if accuracy is concerned, the latter option can be
selected instead [16].
There are more than two joints along the cable route. Therefore, cross-bonding is a
practice for this cable to further minimise transient stress on the joints introduced by circulating current within the sheaths and cable core. Cross-bonding configuration of sheaths
are divided into two major sections as illustrated in Figure 3.5. Each cross-bonded minor
section is terminated by sheath voltage limiters (SVL), which are grounded with the equivalent earthing impedances (RSV L ). Major sections are directly earthed and represented
35
as resistance to ground (Rmat ) for the corresponding substations ground mat. The selection of adequate rating for SVLs and ground resistance values are explained in [2]. The
hypothetical representation of the cross-bonding of the cable and physical configuration of
phases as depicted in Figure 3.5 is adopted from [2, 15].
3.5
36
In PSCADr /EMTDCTM , the user can freely change some parameters of the curve
fitting algorithm to adapt to the specific requirements. For instance, frequency range can
be defined for the operation of curve fitting. By default, the range is set between 0.5 Hz and
1 MHz. It is important to note that the choice of the lower frequency limit has an influence
on the line or effective conductance of the cable. The number of poles can also be set
based on the simulation requirement. The total number of poles used in the calculation will
depend on the maximum allowed error (in percent) between curves set by the user. Once
the program uses all the poles, a constant approximation will take place for all remaining
higher frequencies.
Another important feature is the least squares weighting factor. It can be set for three
different frequency ranges; 0 to 50 Hz, 50 Hz and 50 Hz to higher. The user can set which
frequency range should be emphasised for more precise calculation. Each factor can be set
as any number (default=1) which implies that the higher the factor, the smaller the error
will be.
The main difference in the implementation of FD-Phase and FD-Mode models is the
specific frequency increment setting required by the FD-Phase model, while for the FDMode model, a constant frequency needs to be specified for the operation of the modal
transformation matrix [16]. This clearly shows the difference between these two models, as
different assumptions are used in the handling of frequency-dependent modal transformation
matrix. In this case, it is possible in the FD-Phase model to set frequency increments of
up to 1000 frequencies (lowest setting is 100 frequencies), which means that cable constants
(CC) will perform the curve fitting for 1000 frequencies equally spaced on a log scale.
For the FD-Mode model, the constant transformation matrix was set to be approximated
in the order of tens of kilohertz. This value was based on previous experience in measurement
that the frequency range extends up to several tens of kilohertz during energisation of cables
in unloaded condition [15]. Care should be taken in setting-up the curve fitting parameters
as instability in the simulation may occur. For example, highly demanding requirements
might slow down the simulation and generate more error warnings. The log file should
37
always be checked as a guide for settings and also to ensure a stable simulation.
2
3
132 kV). The output data for the simulation using preliminary power
3.6
The modelled power system network up to this stage is considered as a preliminary model
since the simulation was performed without the inclusion of details replicating the real
energisation test (as from measurement data). The purpose of simulation is to validate
the stability of the constructed power system model. Observation has been made as to
the behaviour of current and voltage transients during cable energisation. Identification of
potential areas of improvement for the existing model was also sought.
In the simulation, simultaneous closure of the circuit breaker was assumed. Steady
state power was supplied to the downstream with no loads connected at the terminating
connection of the cable as well as at the substation busbars. The cable was then energised by
switching the CB at the sending end at Baulkham Hills transmission substation. Figures 3.6
and 3.7 depict the current transient of each phase predicted by FD-Mode and FD-Phase
models respectively at the instant of switching.
38
Simulated current transients of preliminary FDMode model ( [ T ] = 10kHz)
1
0.5
0
0.5
Current (kA)
1
0
1
0.005
0.01
0.015
0.02
0.025
0.03
0.005
0.01
0.015
0.02
0.025
0.03
0.005
0.01
0.015
Time (s)
0.02
0.025
0.03
0.5
0
0.5
1
0
1.5
1
0.5
0
0.5
1
1.5
0
Figure 3.6: Simulated blue (top), white (middle) and red (bottom) phase current transients
of preliminary model using FD-Mode approach with modal [T ] set at 10 kHz
Simulated current transients of preliminary FDPhase model
1
0.5
0
Current (kA)
0.5
1
0
1
0.005
0.01
0.015
0.02
0.025
0.03
0.005
0.01
0.015
0.02
0.025
0.03
0.005
0.01
0.015
Time (s)
0.02
0.025
0.03
0.5
0
0.5
1
0
1.5
1
0.5
0
0.5
1
1.5
0
Figure 3.7: Simulated blue (top), white (middle) and red (bottom) phase current transients
of preliminary model using FD-Phase approach
39
are observed from both models with only a small deviation (approximately 2 %) of the
transient peak magnitudes for each phase. The transient envelope also decays almost at the
same time in approximately 15 to 20 ms.
Referring to the point-on-wave closing of the CB poles on the respective phases, as in
this case, red phase power frequency voltage was at the highest magnitude compared to
blue and white counterparts. Also, during this instant, blue and white phase instantaneous
magnitudes were negative values. It is evident from these waveforms that the situation is
similar to the behaviour of transients for the case of switching of a capacitor bank [20].
For FD-mode model, it is important to approximate the modal transformation matrix
accurately. For example, as can be seen in Figure 3.8, current transients seem largely different compared to the waveforms in Figures 3.6 and 3.7, where all phases exhibit relatively
higher transient magnitudes. The overvoltage transient at Baulkham Hills transmission
substation is also simulated which is displayed in Figure 3.9. It is clear that the overvoltage
magnitudes, especially of the red phase, rise to nearly 200 kV (1.86 pu).
Simulated current transients of preliminary FDMode model ( [ T ] = 50 Hz)
1
0.5
0
0.5
Current (kA)
1
0
1
0.005
0.01
0.015
0.02
0.025
0.03
0.005
0.01
0.015
0.02
0.025
0.03
0.005
0.01
0.015
Time (s)
0.02
0.025
0.03
0.5
0
0.5
1
0
1.5
1
0.5
0
0.5
1
1.5
0
Figure 3.8: Simulated blue (top), white (middle) and red (bottom) phase current transients
of preliminary model using FD-Mode approach with modal [T ] set at 50 Hz
40
Voltage (kV)
0.005
0.01
0.015
Time (s)
0.02
0.025
0.03
3.7
Summary
In this chapter, the test system for the analysis of FD-Mode and FD-Phase models was
developed. Of primary importance is the frequency-dependent behaviour of system components. Accordingly, careful treatment of the underground cable network has been presented.
Particular care was taken in accounting for the effects of semiconducting layers on the system transients.
Results from the preliminary simulation indicate the general behaviour of transients
developed which are very similar to the case of switching of a capacitor bank. They also
revealed the general characteristics of FD-Phase approach which is much more consistent
over a wide range of frequencies. FD-Mode model, on the other hand, requires careful
selection of its constant frequency for approximation of the modal transformation matrices.
In Chapter 4, the model is to be further refined to match the real-life behaviour for
the case of switching of an underground cable. The key points include incorporation of
pole switching times of CB and also identification of suitable constant frequency modal
41
transformation of FD-Mode model. For both models, curve fitting (CF) parameters are to
be optimised for better accuracy along with a stable run of simulation program.
Chapter 4
Introduction
The preceding chapter highlighted the treatment of system components in the considered
power system network to develop a sufficiently accurate model in PSCADr /EMTDCTM .
Based on the preliminary model simulation results, some suggestions arise. Particularly,
for the underground cable model, employing the FD-Mode approach would require an appropriate constant frequency to cater for precise operation within the expected frequency
range. On the other hand, FD-Phase model is more general which enables calculation over
a wide range of frequencies. In addition, inclusion of these cable models should be organised carefully, particularly in the selection of suitable parameters for the curve fitting (CF)
algorithm to avoid unnecessary warning errors and instability in the simulation.
This chapter explains procedures undertaken during cable energisation tests carried out
in August 2007. The measured current transient data are analysed to select one suitable set
of results to be used as a benchmark for the purpose of detailed comparison with simulation
42
43
outcomes from each cable model. Taking into account several issues discussed in Chapter 3,
the power system model is modified accordingly, such as incorporating the pole switching
times of the circuit breaker (CB). For the FD-Mode model, a suitable frequency for constant
modal transformation matrix is also determined. Analysis of results from both cable model
simulations is then presented and compared with measurement data. The main criteria
includes the ability of the models to predict the following:
Transient amplitudes in time domain.
Transient envelope times in time domain.
Frequency domain response.
4.2
44
45
500
Current (A)
500
0
500
1000
0.05
Current (A)
500
500
0.05
0.1
0.15
0.2
0
500
0
0.05
0.1
Time (s)
0.15
500
Current (A)
500
1000
0.05
0.05
0.1
0.15
500
500
Current (A)
1000
1000
0.05
0.05
0.1
Time (s)
0.15
0.2
0.2
0.05
0.1
Time (s)
0.15
0.2
500
1000
500
0.15
1000
0.05
0.2
0.1
500
0.05
500
1000
1000
0.05
0.2
Current (A)
500
1000
1000
0.05
Current (A)
1000
0.05
1000
Current (A)
Current (A)
0.05
0.1
0.15
0.2
0.05
0.1
Time (s)
0.15
0.2
0
500
1000
0.05
Figure 4.2: Blue (top) and white (bottom) phase current transients from each measurement
for example. The transient envelope for these tests decays at a repeatable rate. This time
is within approximately 10 ms. The system damping depends on the portion of resistive
elements in the circuit. After approximately 30 ms, the 50 Hz charging current is recorded to
be in the average of 21 A (cable length is approximately 5.6 km long). This data correlates
well with the data quoted by manufacturer which is around 3.7 A/km.
46
1000
500
0
500
1000
0.005
0.01
0.015
0.02
0.025
Time (s)
Measured white phase current transient (test 3)
0.03
1000
Current (A)
500
0
500
1000
0.005
0.01
0.015
Time (s)
0.02
0.025
0.03
Figure 4.3: Blue (top) and white (bottom) phase current transients from third measurement
47
It is also apparent that relatively high frequency transients are confined within the first
millisecond after energisation. At the instant of CB closure initiation, the blue and white
phase current amplitudes varied from zero to -587 A and -247 A respectively. This gives a
clear indication that the power frequency (50 Hz) voltage magnitudes of the blue and white
phases are negative values at the instant of switching. Such information is useful when
incorporating CB switching times in the simulation.
Other than the time domain comparison, the frequency response analysis of cable models
are also to be carried out. The intention is to measure the ability of models in predicting
the dominant peaks in the frequency spectrum. The energy spectral density (ESD) plots
of the current transient signals are provided. In theory, an accurate model should be able
to simulate the component frequency behaviour over the specified calculation range. This
analysis is based on evaluation methodology used in [10, 15].
To prepare the frequency domain plots, it is necessary to avoid low frequency signals
from dominating the frequency spectrum. This is achieved by filtering the raw signals using
MATLABr with a third order high pass Butterworth filter with the cut-off frequency set
at 200 Hz. Frequency components below this boundary are then attenuated. It has been
established in [15], that the third order filter is deemed sufficient for this case. The filtered
waveform is then converted into the frequency domain by means of an FFT (Fast Fourier
Transform). The frequency spectrum of the corresponding blue and white phase current
transients are as illustrated in Figure 4.4. From Figure 4.4, it is evident that the frequency
spectrum of blue and white phase signals are dominant in the range of 250 Hz to 10 kHz.
The major peaks of signal energy in this range occur at 1.1 kHz, 1.8 kHz, 2.9 kHz and
5.8 kHz. Measured data (time and frequency domain plots) for the first, second and fourth
tests are included in Appendix C (Section C.1).
The major criteria of measured current transients discussed in this section are to be
compared with results obtained from simulation of both cable models. However, this data
was obtained from measurement in the field where the CB poles no longer behave in an
ideal manner. To include this behaviour in the simulation model, pole closing times were
48
Blue phase frequency spectrum (test 3)
Magnitude
30
20
10
0 2
10
10
10
10
Frequency (Hz)
White phase frequency spectrum (test 3)
Magnitude
10
0 2
10
10
10
10
Frequency (Hz)
Figure 4.4: Frequency spectrum of blue (top) and white (bottom) phase current transients
measured and analysed. The outcome of this analysis is presented in Section 4.2.4.
49
Instantaneous line voltage (Vredwhite) at secondary of VT (test 3)
Voltage (V)
400
1.738E5 (red)
4.574E4 (blue)
200
0
3.894E4 (white)
200
400
0.5
0.5
1.5
Time (s)
2.5
3
3
x 10
Figure 4.5: Determination of CB pole closing times from third energisation test
4.3
2
3
of the source model (set by the user), a stable running simulation may be achieved after
at least one cycle. In this simulation, the snapshot is recorded at the time t=0.0375 s, as
illustrated in Figure 4.6. This value is inferred based on the point-on-wave where the CB
initiates a close as observed in the measurement data. The magnitude and direction of
power frequency voltage of each phase at this instant is similar to the situation as described
in Chapter 3 (Section 3.6), where the blue phase is more negative than the white phase.
In general, it is difficult to anticipate the exact point-on-wave for the closure of the CB.
The technique used in this simulation is based on the available measurement data and
reference [10].
50
4.3.2 Simulation
From measurement data, the current transients were recorded for approximately 30 ms after
the energisation. To capture points between zero to 30 ms, the simulation is re-run from
the snapshot file for about 30 ms. Another crucial aspect to be considered is the simulation
time step. Setting up a smaller time step may increase the degree of accuracy as more
points can be calculated. However, it results in a very slow simulation that sometimes
yields numerical instability and produces subsequent error messages. Based on guidelines
described in Chapter 3 (Section 3.5), the simulation time step of 0.1 s is used and is
considered adequate for this simulation.
4.4
51
The time domain current transient results are as shown in Figure 4.7. In Figure 4.7,
the simulated blue, white and red phase current magnitudes are 751 A, 513 A and 1077 A
respectively. Accuracy in applying switching times ensures the blue phase peak is larger
than white phase peak in the simulation. Comparing these values to the experimental
data, especially of the blue and white phases, gives amplitudes of similar order for the
corresponding phases. The difference from measured values are around 5.1 % and 2.7 %
respectively for blue and white phases. Slight differences in the simulated and actual pointon-wave at which each CB contact closes is one of the major criteria that governed the
behaviour of these transient peaks.
However, the transient envelope times varied significantly. The model approximated
the transient envelope to last 20 ms for blue phase and 15 ms for white and red phases
respectively. This indicates that system damping plays a significant role in dissipating the
energy arising from transients in cable energisation. For the case of measurement data, it
appears that there is still some amount of resistive load near the switching point (sending
end) which help the transients to decay faster. On the other hand, for simulated results,
no resistive components (loads) were added to the simulation model. As a consequence,
the magnitude of oscillation transients was diminishing naturally as a result of system
impedances mostly from the cable, overhead lines and other power system components.
Incorporating system loads is difficult due to their varying characteristics and often detailed
parameters are unavailable.
The consistency of this model is further verified by comparing frequency domain response
as illustrated in Figure 4.8. In this figure, the frequency spectrum seems very poor and
only several dominant peaks can be seen for each phase compared to the measured data
in Figure 4.4. The dominant peaks of blue, white and red phases only occur at 1.5 kHz,
2.2 kHz and 8.7 kHz which is clearly inconsistent with the dominant peaks of the measured
data.
52
Simulated current transients of FDMode model ( [T] = 15 kHz )
1
0.5
0
0.5
1
0
0.005
0.01
0.015
0.02
0.025
0.03
1
0
0.005
0.01
0.015
0.02
0.025
0.03
1.5
1
0.5
0
0.5
1
1.5
0
0.005
0.01
0.015
Time (s)
0.02
0.025
0.03
Current (kA)
1
0.5
0
0.5
Figure 4.7: Simulated blue (top), white (middle) and red (bottom) phase time domain
current transients using FD-Mode model
Frequency spectrum of current transients of FDMode model
0.4
0.2
Magnitude
0 2
10
0.3
10
10
10
0.2
0.1
0 2
10
0.5
10
10
10
0.4
0.3
0.2
0.1
0 2
10
10
10
10
Frequency (Hz)
Figure 4.8: Frequency spectrum of simulated blue (top), white (middle) and red (bottom)
phase current transients using FD-Mode model
53
54
Simulated current transients of FDPhase model
1
0.5
0
0.5
Current (kA)
1
0
1
0.005
0.01
0.015
0.02
0.025
0.03
0.005
0.01
0.015
0.02
0.025
0.03
0.005
0.01
0.015
Time (s)
0.02
0.025
0.03
0.5
0
0.5
1
0
1.5
1
0.5
0
0.5
1
1.5
0
Figure 4.9: Simulated blue (top), white (middle) and red (bottom) phase time domain
current transients using FD-Phase model
Frequency spectrum of current transients of FDPhase model
0.4
0.2
Magnitude
0 2
10
0.3
10
10
10
0.2
0.1
0 2
10
0.5
10
10
10
0.4
0.3
0.2
0.1
0 2
10
10
10
10
Frequency (Hz)
Figure 4.10: Frequency spectrum of simulated blue (top), white (middle) and red (bottom)
phase current transients using FD-Phase model
55
Referring to the frequency response of this model based on the frequency domain plots
displayed in Figure 4.10, it again reveals an inconsistency of this model in predicting dominant peaks for simulated current signals. The resonant peaks are at 1.5 kHz, 2.2 kHz and
8.7 kHz, which are similar to the case approximated by FD-Mode model. Again, there
would appear to be no commonality regarding dominant peaks relative to the measured
data. The discrepancies observed from simulated data of FD-Mode and FD-Phase models
are further discussed in Section 4.4.3.
Figure 4.11: Steady-state 50 Hz charging current predicted by FD-Phase model for the
cable under test (5651 m long)
However, the wave-shape of simulated data differed considerably from those observed
in the measurement data. The frequency response is also very poor with small number of
dominant frequencies as seen in simulated data. These discrepancies can be explained using
56
several considerations.
Firstly, the strong coupling effects between cables at high frequencies exist, for example,
the impact of cable sheath and conductor on the system transients. At high frequencies,
a cable exhibits strong capacitive behaviour due to the distributed capacitances between
sheath and conductor. Furthermore, when it comes to energising a 3-phase cable, the
conductors and sheaths of all cables are mutually coupled. Increasing the frequency, results
in strong electromagnetic coupling which, as a result, affects the evaluation of the impedance
(z) and admittance (y) matrices of the cable.
The second factor may be due to the existing trapped charges in the cable. As described
in Section 4.2.1, before the cable was energised, it had been isolated for approximately 10
minutes to allow capacitive discharge. In this case, the capacitive energy may not be
completely diminished. This would alter the overall behaviour of transients as seen in
measurement data.
There are also influences from the CB, for example, the arc between the CB contacts.
In this case, there is a tendency for arc to occur at any time between the contact start to
close and its final closure. This phenomena is also known as pre-strike which depends on
the closing speed of CB contacts. Further information regarding this factor can be found
in [49]. Another possibility is the mechanical influences. However, it is beyond the scope of
this study and is not of interest in this work.
Finally, another possible factor is the impact of the frequency-dependent nature of distribution transformers. It is difficult to model the frequency-dependent transformer behaviour. Complexities are pronounced at higher frequencies as the non-linear characteristics
significantly increase due to an increase in frequency. Therefore, transient behaviour affected
by transformers in the vicinity can be modelled provided that both non-linear behaviour
and its frequency-dependent effects are taken into account. These approaches unfortunately
have been neglected due to the unavailability of data such as the nameplate information.
Figure 4.12 shows a useful example of a high frequency transformer model. Using this
model, the winding lumped stray capacitance and the phase to ground capacitance values
57
can be obtained using frequency scan features in PSCADr /EMTDCTM [16].
Figure 4.12: High frequency transformer model suitable for 50 Hz - 20 kHz frequency
intervals [56]
The factors discussed greatly influence the measured current transients in Figure 4.3.
In reality, a large number of frequency components exist, particularly within the first 1 ms
following the energisation. When closely analysed the behaviour of current transients seen
in Figure 4.3, the blue phase current tends to respond and rise quickly at the instant of
white phase contact closure. Such phenomena unfortunately failed to be duplicated by the
simulation model. However, based on the comparison from available data, it is apparent
that the FD-Phase approach is more suitable to simulate energisation transient of the cable.
This is purely because of the ability to predict transient magnitudes more accurately.
4.5
The short duration current transient produced, as in the case of cable energisation, might
also produce corresponding voltage transients. Considerable transient stress can be felt
across the main insulation of the cable and also the outer casing due to induced voltages.
Transients introduced along cable sheath are also severe which, in many cases, requires
the use of sheath voltage limiters. Suitable surge arresters are normally installed at either
sending or receiving end of cable and sheath or both. Similarly, they are also found in cross-
58
bonded link boxes to divert the travelling surges in sheaths of a long cross-bonded cable
systems. The selection of rating of surge arrester and sheath bonding or grounding design
on cables are dictated by parameters set by either manufacturer or the relevant electricity
authority.
To enable analysis of overvoltage behaviour, instantaneous voltages are measured at certain points within the power system network under study. The simulation was performed
using FD-Phase cable model. Figure 4.13 depicts the voltages across main insulation measured at sending and receiving ends of the cable near the circuit breakers.
Simulated sending end overvoltage transients
Voltage (kV)
200
100
0
100
200
0
0.005
0.01
0.015
0.02
0.025
Time (s)
Simulated receiving end overvoltage transients
0.005
0.01
0.03
Voltage (kV)
200
100
0
100
200
0
0.015
Time (s)
0.02
0.025
0.03
59
SWTS busbar voltage
Voltage (kV)
200
200
0
0.005
0.01
0.015
0.02
Time (s)
BTTS busbar voltage
0.025
0.03
0.005
0.01
0.025
0.03
0.005
0.01
0.025
0.03
0.005
0.01
0.025
0.03
Voltage (kV)
200
200
0
0.015
0.02
Time (s)
CFTS busbar voltage
Voltage (kV)
200
200
0
0.015
0.02
Time (s)
BHTS busbar voltage
Voltage (kV)
200
200
0
0.015
Time (s)
0.02
Voltages are also induced within the cable sheath. Figure 4.15 shows an example of
instantaneous sheath voltages. In this example, without arresters, the charging current from
main conductor (red phase at approximately 1000 A) causes the induced voltages to rise to
nearly 10 kV. With arresters (rated at 3 kV), some current has been conducted to ground,
thus minimising the voltages to around 6 kV. The magnitude depends on the instant on the
voltage waveform at which the CB contacts close electrically. The higher the instantaneous
voltage, the higher the overvoltage amplitude that will be induced. In practice, evaluation
of insulation co-ordination, and protection schemes is studied by performing a number of
60
energisations over the entire voltage cycle so that the actual peak values can be determined.
Depending on the specific requirement, statistical approaches may be used to evaluate the
required parameters. This method will be further studied in Chapter 5.
Sheath voltages with SVL turned off
Voltage (kV)
10
5
0
5
10
0
0.002
0.004
0.006
0.008
Time (s)
Sheath voltages with SVL turned on
0.01
Voltage (kV)
10
5
0
5
10
0
0.002
0.004
0.006
0.008
0.01
Time (s)
Figure 4.15: Sheath voltages during switching with and without surge arresters
4.6
Summary
61
data, particularly the expected frequency range, FD-Phase model can be an alternative.
Furthermore, the FD-Phase model was found to give better performance when comparing
the time domain results with measured data. This reveals the suitability of FD-Phase model
especially for studying the high frequency transients on underground cables.
However, inconsistencies have been found in both models in predicting the actual wave
shapes as well as the frequency domain response. Possible discrepancies that contributed
to this situation have been raised and discussed. Apparently in this case, accurate power
system modelling in studying high frequency transients phenomena requires detailed knowledge of system parameters. However, often such details are unavailable and in some cases
impractical to obtain such as the system load values during the test. The issues discussed
in Section 4.4.3 are to be further improved in future work.
The impact of energising underground HV cables is of primary interest in electric power
insulation co-ordination and designing protection schemes. Simulation data (based on results from FD-Phase model) has revealed the direct impact of induced transients on the
insulation systems within the network under study. The behaviour of overvoltages (magnitudes) developed are influenced by many factors, but strongly dependent on the point-onwave closing of the circuit breaker. The related issues regarding the evaluation of switching
overvoltages are to be presented in Chapter 5.
Chapter 5
Introduction
The switching problems associated with cable energisation involve studies that account for
large bandwidth of frequency variations where the cable parameters significantly vary within
that range. Therefore, a detailed model for the cable, such as the distributed parameter
travelling wave model with frequency-dependent approach, should be incorporated in the
simulation. Such models are assessed by practical means as presented in Chapter 4. In general, FD-Phase model can be reliably used for instances when the behaviour of overvoltage
magnitudes are intended to be analysed statistically.
It has been established, from the literature, that the behaviour of transients depends
strongly on the network configuration and the characteristics of the switching operation.
The latter is of interest and to be further analysed in this chapter. The study of the sensitivity of the distribution of transient magnitudes as a function of circuit breaker (CB) characteristics is practically carried out according to a probability approach. Statistical methods
are applied to the switching data following the guidelines such as those given by IEEE
PES Switching Transients Task Force [53]. Useful information is then provided accordingly
62
63
following the recommendations given by the insulation co-ordination standards [17, 18].
This chapter first provides an overview of statistical switching studies. The approaches
used in this work are also introduced. Then, network refinement is presented to incorporate
multiple run features to the existing test system. Finally, the results obtained from the
approaches used are analysed, especially the relevant data that may be useful for distribution
system engineers as well as researchers for future planning and design of possible protective
levels related to this class of cable systems.
5.2
Switching of a 3-phase CB involve some degree of uncertainty since all poles do not close
simultaneously. In addition, the poles do not always close in the same sequence but are
randomly distributed for every single switching action. The transient voltage magnitudes
generated are also based on the point-on-the-voltage-wave where the contacts initiate a close.
With the help of digital computers and available mathematical tools, several approaches
can be used in the evaluation of switching surges. Common practices found so far can be
categorised as:
Statistical study approach
Statistical maximisation approach
Optimisation approach
The first approach is the most preferred method based on probability concepts and
is adopted in this work. Detailed explanation of the other two approaches can be found
in [50]. In the statistical study approach, statistics are used to evaluate the switching
surges to obtain relevant data such as those suggested by IEC standards for insulation
coordination [18]. The range of values required include the maximum value, 2 % probability
value, mean amplitude as well as the standard deviation. Scattering characteristics of CB
poles, normally assumed as normal distribution (Gaussian), are applied over the full cycle
64
(20 ms) on the voltage wave. The statistical study has proven to be reliable in many
cases including studies on large scale networks [13, 14]. Martinez et al. [51] provide a
comparison of statistical switching results evaluated using several statistical methods such
as the Systematic switching and Gaussian distribution. The latter is an available feature
in PSCADr/EMTDCTM that can be used readily. However, a similar approach to the
systematic switching technique can be applied manually and is detailed in Section 5.3.1.
5.3
Simulation Approaches
65
66
5.4
The parameters of the system components and underground systems of the existing power
system network model remain unchanged. However, a larger solution time step is used (1 s)
to avoid excessive simulation times. This is reasonable since only voltage magnitudes are
of interest. As given in Table 5.2, less than a 1 % deviation (slightly lower) of overvoltage
magnitudes is obtained compared to the 0.1 s time step setting.
Table 5.2: Red phase magnitudes for different simulation time step
Simulation time step (s)
0.1
0.5
1
Magnitude (pu)
1.6822 1.6788 1.6700
Deviation (%)
0
0.321
0.725
The CB contact timings in Figure 4.6 (Chapter 4) are modified in such a way to make
use of the multiple run component. The multiple run system is programmed to generate
and process the energisation samples. In general, the system allows up to 6 input variables
that can be modified according to a user preference such as the sequential, list, random-flat
or random-normal distribution [16]. It is possible to record up to 6 channels for every run
and a maximum of 10,000 samples can be saved. Auto processing of output data also can
be applied such as the maximum or minimum values.
67
68
Table 5.3: Sending end voltage magnitudes from simultaneous closure of CB
Magnitudes (pu)
Closing time (ms) Phase-A Phase-B Phase-C Maximum (pu)
1
1.069
1.261
1.719
1.719
2
1.120
1.356
1.615
1.615
3
1.153
1.570
1.373
1.570
4
1.151
1.691
1.088
1.691
5
1.263
1.659
1.081
1.659
6
1.509
1.472
1.206
1.509
7
1.691
1.139
1.308
1.691
8
1.708
1.086
1.385
1.708
9
1.559
1.044
1.503
1.559
10
1.257
1.114
1.680
1.680
11
1.069
1.261
1.719
1.719
12
1.120
1.356
1.615
1.615
13
1.153
1.570
1.373
1.570
14
1.151
1.691
1.088
1.691
15
1.263
1.659
1.081
1.659
16
1.509
1.472
1.206
1.509
17
1.691
1.138
1.308
1.691
18
1.708
1.086
1.385
1.708
19
1.559
1.044
1.503
1.559
20
1.257
1.114
1.680
1.680
5.5
A three phase energisation produces switching overvoltages on all three phases of the cable.
Every single switching operation produces three phase-to-ground with the corresponding
phase-to-phase overvoltages. Based on the guidelines given by IEC 60071-2 [18] standard,
there are two methods currently used in practice:
Phase-peak method: The highest peak value of the overvoltage of each phase-to-ground
or between each combination of phases is taken into account.
Case-peak method: Only the highest peak value of peak magnitudes (either phase-toground or phase-to-phase) generated from all three phases is collected.
In this study, only phase-to-ground overvoltages have been measured at both the sending
and receiving ends of the cable being energised. Both recommended methods are feasible
since the voltage is measured at each individual phase. The data are statistically calculated
by means of multiple run systems and then processed in MATLABr to obtain the statistical
plots. The following section provides results based on the approaches considered.
69
20
20
10
10
10
0
20
10
0
10
0
20
10
0
20
20
10
10
20
Frequency of occurrence (%)
20
1.2
1.2
70
difference of sending end overvoltage peaks between the first and the fourth case can still
be considered as a small deficiency.
Based on the overall results of Figure 5.3, the significant overvoltage peaks for each
phase at sending and receiving ends are summarised in Table 5.4. At the sending end,
the highest overvoltage peak is 1.84 pu generated from the third case. Travelling wave
phenomena causes the most severe overvoltage peaks at receiving end when no loads are
connected. This is due to the superposition of voltage waves. For instance, the overvoltage
peak magnitudes, especially in the case of Test 1 and Test 2 energisation schemes, all fall
in the range of 2 pu. Overall, in all of the cases, the sending and receiving ends overvoltage
peak values fall between the range of 1.74 pu to 1.84 pu and 1.84 pu to 2.06 pu respectively.
71
0.8
40
0.8
30
0.6
30
0.6
20
0.4
20
0.4
10
0.2
10
0.2
50
0
0
1.4 1.5 1.6 1.7 1.8 1.9 2 2.1 2.2
Receiving end (2 ms span)
50
1
40
0.8
40
0.8
30
0.6
30
0.6
20
0.4
20
0.4
10
0.2
10
0.2
Occurrence (%)
50
0
0
1.4 1.5 1.6 1.7 1.8 1.9 2 2.1 2.2
Receiving end (3 ms span)
1
50
40
0.8
40
0.8
30
0.6
30
0.6
20
0.4
20
0.4
10
0.2
10
0.2
0
1.4
0
1.4
1.5
1.9
0
2
0
1.4 1.5 1.6 1.7 1.8 1.9 2
Magnitude (pu)
CDF
40
CDF
50
0
1.4
Occurrence (%)
CDF
Occurrence (%)
0
2.1 2.2
Figure 5.4: Sending and receiving ends probability density and the corresponding cumulative distribution curves for 1 ms, 2 ms and 3 ms pole spans studied based on probabilistic
approach (case-peak method)
3 ms spans respectively. It is obvious that higher magnitudes are obtained from smaller
pole span but the occurrences are very low. Inversely, larger pole spans are more prone to
produce a higher frequency of occurrences of relatively lower voltage magnitudes. Overall,
peak magnitudes are decreasing with increasing pole span settings. However, there is only
a very small percentage difference (overvoltages at sending end) in terms of the 1 ms span
and 3 ms span.
It is apparent that the results observed in Figure 5.4 are more realistic compared to the
deterministic approach as different pole span of CB can be considered. The consistency of
results from simulation can be increased by increasing the number of energisations for each
case. However the variation of pole span studied are based on maximum possible span of
CB in EHV and UHV systems [12]. In this case, the nominal pole span of the CB under
72
study (132 kV CB) is not certain due to unavailability of data from manufacturer. Based
on the data displayed in Table 5.1, the maximum span tends to vary between around 0.1 ms
to around 0.8 ms for each case respectively. Therefore, it is also crucial to consider the pole
span within the range quoted by measurement data since it represents the real situation.
Section 5.5.3 provide the results simulated using smaller pole span.
73
0.4
10
Occurrence (%)
10
0
2
1
0.6
0.4
10
0.8
20
10
0.2
0
1.4
30
0
1
0.6
0.4
10
30
0
1
0.8
20
10
0.6
0.4
10
1.5
1.9
0.4
0.2
0.8
20
10
0.2
0
1.4
0.6
0
0
1.4 1.5 1.6 1.7 1.8 1.9 2 2.1 2.2
Receiving end (0.8 ms span)
30
1
0.8
20
0.4
0.2
0.2
0
1.4
0.6
0
0
1.4 1.5 1.6 1.7 1.8 1.9 2 2.1 2.2
Receiving end (0.6 ms span)
30
1
0.8
20
0.4
0
0
1.4 1.5 1.6 1.7 1.8 1.9 2 2.1 2.2
Receiving end (0.4 ms span)
30
1
0.8
20
0.6
0.2
0.2
30
Occurrence (%)
0.8
20
CDF
0.6
CDF
0.8
20
0
1.4
Occurrence(%)
30
CDF
0.6
0.4
CDF
Occurrence (%)
30
0.2
0
1.4 1.5 1.6 1.7 1.8 1.9 2
Magnitude (pu)
0
2.1 2.2
Figure 5.5: Sending and receiving ends probability density and the corresponding cumulative distribution curves for the pole span below 1 ms (case-peak method)
74
Table 5.5: Relevant statistical
Mean (pu)
CB pole span (ms) SE
RE
0.2
1.69 1.90
0.4
1.65 1.85
0.6
1.67 1.86
0.8
1.67 1.85
1
1.65 1.85
2
1.64 1.84
3
1.62 1.82
Of all the results obtained, the 2 % probability values show that the overvoltages due
to cable energisation under current network are at the average level compared to common
cases indicated by IEC standard as displayed in Figure 2.3 (Chapter 2). Therefore, further
studies (to limit the transients) may not be required as the magnitudes, particularly at the
receiving end are not high enough to cause a problem.
5.6
Summary
The energisation of an unloaded cable system causes high overvoltage transients and stresses
the insulation systems. The worst scenario may be experienced for switching of a cable
which is located at the transition point of the overhead to underground system such as the
networks under study. The level of overvoltage experienced is governed by many factors, in
particular, the problems underlying sensitivity of CB contacts as well as the characteristics
of switching operation. In this case, attention has been given to the CB maximum pole
closing span as well as the point-on-wave where the contacts initiate their closure. Due
to statistical characteristics of these variables, it is important to calculate the overvoltage
values by means of statistical methods. Such studies are feasible by manipulating the
multiple run component in PSCADr/EMTDCTM .
Based on two approaches studied, the range of overvoltage magnitudes produced at
sending and receiving ends fall in similar order with slightly higher overvoltage magnitudes
obtained using the probabilistic technique. This revealed the consistency of two methodolo-
75
gies applied. However, probabilistic techniques are more practical as the random nature of
CB contacts can be assumed. It is also flexible because higher number of energisations can
be used to achieve more reliable and optimised overvoltage values. Thus, the data from this
technique are recommended.
According to the data from probabilistic technique, every single energisation at the point
of 1 pu (peak voltage magnitude), will generate approximately 2 pu overvoltage magnitudes
at the receiving end of unloaded cable. Overall, for the cases studied using different pole
spans, all produce transient overvoltage magnitudes at the average level compared to the
values indicated by IEC standard for particular cases of the field results and studies. In
other words, the range of values obtained are within acceptable level and considered to
comply with the standards.
Chapter 6
Conclusions
Switching problems have been a general concern among utilities in ensuring a consistent
quality of supply, reliability as well as continuous prevention from transients and protection
of system components in the networks. Energising a HV cable system introduces significant
voltage and current transients due to its complex construction, comprising sheath and other
semiconducting layers. Strong electromagnetic coupling among these layers and among the
conductors of 3-phase cable system causes cable parameters to vary significantly as frequency
increases. The impact of transients on insulation systems is vital when considering switching
operation at the transition point of overhead to underground transmission. Therefore,
studies on the switching transient behaviour should be carried out using an accurate model
to represent the cable system. Despite a number of frequency-dependent travelling wave
models provided, all of which can be used for modelling of an underground cable, they are
not always suitable for all cases. Such problems are addressed in two stages of studies of
major interest in analysing the behaviour of transients due to cable energisation.
Firstly, an investigation of the suitability of FD-Mode and FD-Phase models for underground cable under study has been presented by comparing their ability to predict accurately the energisation current transient in terms of magnitude, duration and the spectral
76
77
content. A power system network model that replicates the system under study has been
carefully crafted in PSCADr /EMTDCTM electromagnetic transient simulation platform.
Careful treatment of power system components including the underground cable to cater
for frequency-dependent nature of system transients has been given. In cable modelling,
detailed dimensions and calculation of its layered construction and material properties has
been presented. Cable system was then represented by FD-Mode and FD-Phase models.
The curve fitting (CF) parameters were adjusted for better accuracy for both frequencydependent cable models. The simulated results from these models have been compared with
the measurement data. It has been found that there is a very small difference in the performance of two models as both are able to predict the current transient magnitude accurately
with fairly good agreement of the transient envelope times. However, no identical dominant
peaks are observed from both models when comparing their performance in the frequency
domain. Overall, of the results studied, the FD-Phase model showed several advantages
over the FD-Mode model. Specifically, the ability to simulate current transient magnitudes
more accurately. Furthermore, the difficulty in incorporating the FD-Mode model becomes
pronounced because a constant frequency for operation of the modal transformation matrix
required to be identified accurately. Conversely, such a problem does not exist for FD-Phase
counterparts as a frequency-dependent internal transformation matrix is assumed.
Secondly, the impact of transients introduced in a HV underground cable has been
further analysed, particularly the statistical distribution of peak magnitude overvoltages at
the sending and receiving ends of the cable respectively. This has been motivated by the
needs for analysis of the impact of circuit breaker (CB) contact closure which are random
in nature. The magnitudes of overvoltages depend strongly on the point-on-wave where the
CB closed and the influence of 3-phase CB pole span which is the time between the first and
the third pole to close. The existing model has been refined according to deterministic and
probabilistic simulation approaches. These approaches are constructed by manipulating the
multiple-run feature in PSCADr /EMTDCTM . The FD-Phase model has been incorporated
to represent the cable system. Results from both approaches revealed that energisation of
78
an unloaded cable at the point of 1 pu of power frequency voltage results in approximately
2 pu of overvoltages at the receiving end of the cable. At the sending end, the magnitudes
may increase to levels as high as approximately 1.8 pu. However, the data particularly of
the receiving end magnitudes obtained from both deterministic and probabilistic techniques
are still at the average level compared to typical values indicated by IEC standard. These
values are not high enough to cause a problem and further studies to limit the transients
may not be required. The data from probabilistic techniques are recommended as their
approach is closer to a realistic scenario.
The accuracy of results obtained depends on the accuracy of the system model as well
as the accuracy of available input data. In some situations, access to specific data of the
system components is limited. Therefore, the assumptions used are critical in gaining higher
accuracy in modelling and simulation.
6.2
Recommendations
Most of the problems arising from the network modelling were addressed in Chapter 4
(Section 4.4.3). It is apparent that one of the problems with the cable modelling is the
significant electromagnetic coupling effects between phases as well as between conductor
and sheath. To get rid of such effects, comparison of results for the case of single phase
energisation may be performed as an alternative. The problem in relation to the existing
trapped charges prior to energisation tests may be avoided by allowing longer time (more
than 10 minutes) when isolating the cable. Finally, a more improved and accurate model
of system components should be developed particularly for the distribution transformers at
the sending end busbars. References [5456] may be useful as a guideline for such purpose
provided that the required details such as the nameplate data are obtained.
Appendix A
The transmission line equations govern general two conductor uniform transmission lines,
including parallel plates, two-wire lines and coaxial lines. A cable section of x (x 0)
shown in Figure A.1 is described by the parameters representing; r-resistance per unit
length, l-inductance per unit length, g-conductance per unit length and c-capacitance per
unit length. Consequently, rx and lx represent series elements, while gx and cx
represent the corresponding shunt parameters. These parameters are distributed along the
length of the conductor. In general, the line parameters are frequency-dependent where the
series impedance and shunt admittance can be represented as
z = r + jl
(A.1)
y = g + jc
(A.2)
where is the angular frequency. The frequency domain equation for voltage and current
drop along x section at any point of x can be written as (applying Kirchhoffs voltage
79
80
dV
= zI
dx
(A.3)
dI
= yV
dx
(A.4)
where V = V (x, ) and I = I(x, ). Equations (A.3) and (A.4) are referred to as Telegraphers equations. Combining these equations yields a set of coupled wave equations
d2 V
= zyV = 2 V
dx2
(A.5)
d2 I
= yzI = 2 I
dx2
(A.6)
= + j =
(r + jl)(g + jc) =
zy
(A.7)
The real part, , is the attenuation constant in nepers/m and the imaginary part, , is the
phase constant in radian/m. The wave propagation velocity is the fraction of frequency and
the phase constant given by
u=
(A.8)
81
According to Dlamberts solution, (A.5) and (A.6) can be given in the form;
(A.9)
(A.10)
where ex and e+x terms represent wave propagation in the positive and negative x directions respectively. Solving for the unknown voltage (V0 ) and current (I0 ) wave amplitudes
in (A.9) and (A.11) results in the definition of characteristic impedance, ZC , which is the
ratio of the voltage to the current amplitude of the travelling waves for each direction as
V+
V
ZC = 0+ = 0 =
I0
I0
A.2
r + jl
g + jc
(A.11)
The basic geometry, comprising a series of concentric conductor and insulation sections,
are depicted in Figure A.2 where the second conducting element (sheath) is represented as
a third layer of the conductor [26]. For zero frequency, currents are uniformly distributed
Rdc =
c
A
(A.12)
82
where c is the resistivity of conductor and A is the cross-sectional area. However, for
ac, as the frequency increases, the non-uniformity becomes greater where the skin effect
becomes prevalent. With skin effect taken into account, the combined resistance, r (/m)
and inductance, l (H/m) of both conductors per unit length of a coaxial cable in Figure A.2
are described as [26]
r=
Rs 1 1
( + )
2 a b
(A.13)
b
ln
2 a
(A.14)
l=
where Rs = c /s is the intrinsic resistance (surface resistance) that is varying with frequency and inversely proportional to their skin depth (s ). Consequently, the permeability, , of the conductor is based on the free space permeability (0 = 4 107 H/m) and
the relative permeability (r ) of the material (i.e. = 0 r ).
At higher frequencies, there is a possibility of the current flow from inner conductor
through the insulator to the sheath. In the other words, the shunt conductance (g of the
insulation medium in S/m) may be taken into account because of the existence of shunt
resistance across the insulator. Similarly, there exists shunt capacitance (c of the two
conductors in F/m) as the inner and outer conductor work as two parallel plates along the
coaxial cable. Equations (A.15) and (A.16) describe these shunt quantities per unit length
respectively as [26]
g=
2
i ln ab
(A.15)
2
ln ab
(A.16)
c=
83
A.3
z11 z12
z
21 z22
z= .
.
.
.
zN 1 zN 2
y11 y12
y
21 y22
y= .
.
.
.
yN 1 yN 2
. .
. .
. .
. .
. .
. .
. .
. .
. .
. .
z1N
z2N
zN N
(A.17)
y1N
y2N
yN N
(A.18)
The diagonal term represent the self impedance per unit length of the loop formed by
conductors and concentric neutrals with ground return. The off-diagonal elements are the
mutual impedances between the respective conductors.
Appendix B
In this section, calculation of input parameters for 132 kV source, overhead lines, transformers and capacitor banks is given. The original data for these components has been
obtained from the TransGrid Electrical Databook [52] for the corresponding 132 kV systems
commissioned by Integral Energy (IE). Some additional data for cable and transmission lines
are based on the data provided in [15].
To establish the source model, three types of 3-phase voltage source models are available
in PSCADr/EMTDCTM . However, only source model-1 and model-2 are suitable because
source model-3 requires external control of voltage. The main difference between model-1
and model-2 is the connection of sequence impedances (positive and zero sequence) which is
represented in series and parallel form respectively. Table B.1 provides conversion of source
impedance values from the data book [52].
84
85
Table B.1: Calculation of sequence impedances for voltage source model-1 and model-2
Parameter
Values
Remarks
System base values: SLLrmsBase (MVA)
100
VLLrmsBase (kV )
132
ZBase ()
(rad/s)
Positive/Zero sequence impedance: Z+% (% on 100 MVA), Angle, (deg)
Z0% (% on 100 MVA), Angle, (deg)
Physical values: Z+ ()
Z0 ()
Series impedance values (source model-1): R+ ()
L+ (mH)
R0 ()
L0 (mH)
Parallel impedance values (source model-2): R+ ()
L+ (mH)
R0 ()
L0 (mH)
174.24
314.16
2
VLLrmsBase
SLLrmsBase
2f
0.0159, 86.4
0.0183, 84
0.0277
0.0317
Z+%
100 ZBase
Z0%
100 ZBase
0.0017
0.0880
0.0033
0.1004
Z+ cos
Z+ sin
Z0 cos
Z0 sin
0.4513
0.0883
0.3048
0.1015
refer
refer
refer
refer
Eq.
Eq.
Eq.
Eq.
(3.1)
(3.2)
(3.1)
(3.2)
The impact of using either of these two source models on the system transients has been
verified. As can be seen from Figure B.1, only a small difference is noted between the current
transients obtained using the source models. The difference in the peak magnitudes is less
than 1 %. Therefore, either model-1 or model-2 can be used in the simulation. It is also
evident that the source impedance parameters have little impact on the current transients.
This can be attributed to the location of the upstream source which is more than 15 km
away from the origin where the switching takes place.
86
Current (kA)
Blue phase current transients simulated using source model1 and model2
1
model1 (series)
model2 (parallel)
1
0
0.002
0.004
0.006
Time (s)
0.008
0.01
Figure B.1: Energisation current transients of the blue phase of FD-Phase model at sending
end using different source models
Input data for overhead lines are given in Tables B.2 and B.3. Figure B.2 illustrated
the coordinates of all conductors and ground wires.
Table B.2: 132 kV overhead line general data
Feeder name
93A/93Z
9J1/9J2
9J3/9J4
Total length (km)
10.243
10.219
5.470
From
SWTS
SWTS
BTTS
To
BTTS
BTTS
BHTS
Owner
IE
IE
IE
Phase conductor type olive/moose olive/moose
moose
Earth conductor type
opal
opal
opal
wire data
Input data
moose/olive
6
0.013
0.1
2
symmetrical
0.38
5
opal
2
0.00653
2.9
5
930/931
7.370
BHTS
CFTS
IE
moose
opal
87
88
Another component included near the Baulkham Hills busbar is the equivalent capacitor
to represent the capacitor banks installed at 33 kV side of the transformers. Rated at
20 MVAr, value of each capacitor is calculated as
C3 =
Q3
20
2 = 3(314.16)(19.05)2 = 58.47 F
3VLN
(B.1)
89
B.2
The original data from manufacturer were adopted from [15] and given in Table B.6
Description
Details
Manufacturer
Manufacturer address
Cable type
Cu/XLPE/CWS/PVC/HDPE
Conductor material
Copper
Conductor stranding
61/3.9
630
92
ductor (%)
8
Shape of conductor
round
30.5
10
Semiconducting tape
11
XLPE
12
Nom. 18.5
90
Table B.6 continued from previous page
No.
Description
Details
13
14
Curing method
Dry curing
15
See attachment 1
16
17
63/2.0
Approx. 198
PVC
Color
Orange
b) Outer Serving:
Material
HDPE
Color
Black
18
Approx. 90.3
19
Approx. 12.8
20
Steel cap
21
650
(kV peak)
continued on next page
91
Table B.6 continued from previous page
No.
Description
Details
22
190
at 2.00 U0 (pC)
24
25
200000
100000
26
0.16+j0.082
/km)
27
0.03+j0.63
0.06+j0.63
ture
28
29
Design
maximum
operating
0.19
temperature
(R+jX /km)
continued on next page
92
Table B.6 continued from previous page
No.
30
Description
Details
a) Normal ( C)
90
b) Emergency (2 hour)( C)
105
c) Short circuit ( C)
250
Maximum continuous current rating with single point earthing or fully cross bonded:
a) Air (40 C ambient)(A)
1047
798
893
31
839
815
29.1
2.57
gency
b) Four hourcable at 75 % load prior to emer-
2.07
gency
32
90.8
continued on next page
93
Table B.6 continued from previous page
No.
Description
Details
b) Screen (A)
26.0
250
33
max 0.057
34
6.1
(kV/mm)
35
0.5
According to IEC60840
37
1.8
1.8
(m)
39
43218
inette (Newtons)
40
43218
68600
tons)
b) Maximum allowable cable gripping pres-
9.8
sure (kPa)
continued on next page
94
Table B.6 concluded from previous page
No.
Description
Details
42
2.94
installation (kPa)
43
1000
plied (m)
44
Yes
Appendix C
Measurement Data
C.1
Figures C.1 to C.6 depict measured current transients and frequency domain plots recorded
for 30 ms following the cable energisation.
Measured blue phase current transient (test 1)
Current (A)
1000
500
0
500
1000
0.005
0.01
0.015
0.02
0.025
Time (s)
Measured white phase current transient (test 1)
0.005
0.01
0.03
Current (A)
1000
500
0
500
1000
0.015
Time (s)
0.02
0.025
0.03
Figure C.1: Blue and white phase current transients from first measurement
95
96
Measured blue phase current transient (test 2)
Current (A)
1000
500
0
500
1000
0.005
0.01
0.015
0.02
0.025
Time (s)
Measured white phase current transient (test 2)
0.005
0.01
0.03
Current (A)
1000
500
0
500
1000
0.015
Time (s)
0.02
0.025
0.03
Figure C.2: Blue and white phase current transients from second measurement
Measured blue phase current transient (test 4)
Current (A)
1000
500
0
500
1000
0.005
0.01
0.015
0.02
0.025
Time (s)
Measured white phase current transient (test 4)
0.005
0.01
0.03
Current (A)
1000
500
0
500
1000
0.015
Time (s)
0.02
0.025
0.03
Figure C.3: Blue and white phase current transients from fourth measurement
97
Frequency spectrum of measured blue phase current transient (test 1)
Magnitude
30
20
10
0 2
10
10
10
10
Frequency (Hz)
Frequency spectrum of measured white phase current transient (test 1)
Magnitude
60
40
20
0 2
10
10
10
10
Frequency (Hz)
Magnitude
60
40
20
0 2
10
10
10
10
Frequency (Hz)
Frequency spectrum of measured white phase current transient (test 2)
Magnitude
15
10
5
0 2
10
10
10
10
Frequency (Hz)
98
Frequency spectrum of measured blue phase current transient (test 4)
Magnitude
30
20
10
0 2
10
10
10
10
Frequency (Hz)
Frequency spectrum of measured white phase current transient (test 4)
Magnitude
30
20
10
0 2
10
10
10
10
Frequency (Hz)
99
C.2
Figure C.7 is the instantaneous line voltage plots measured at secondary of VT during the
energisation test.
Voltage (V)
Voltage (V)
Voltage (V)
400
200
0
200
400
0.5
400
200
0
200
400
0.5
6.55E5
1.295E4
9.502E6
0.5
1.5
2
2.5
3
3
Time (s)
x 10
Instantaneous line voltage (Vredwhite) at secondary of VT (test 2)
1.675E5
5.968E4
5.288E4
0.5
1.5
2
2.5
3
3
Time (s)
x 10
Instantaneous line voltage (Vredwhite) at secondary of VT (test 4)
1.725E5
8.332E4
7.652E4
0.5
1.5
Time (s)
2.5
3
3
x 10
References
[1] H. Al-Khalidi and Akhtar Kalam. The impact of underground cables on power transmission and distribution networks. In First International Power and Energy Conference
(PECon 2006), Putrajaya, Malaysia, Nov 2006.
[2] D. J. Spoor and J. Zhu. Designing underground cable systems to withstand steady state
and transient voltage. In CIGRE, Australian Panel BI Insulated Cables, Underground
Cables Seminar, Sydney, Australia, 2006.
[3] H. E. Orton. Worldwide underground transmission cable practices. IEEE Transactions
on Power Delivery, 12(2):533541, April 1997.
[4] A. Semlyen and A. Dabuleanu. Fast and accurate switching transient calculations on
transmission lines with ground return using recursive convolutions. IEEE Transactions
on Power Apparatus and Systems, 94(2):561571, Mar 1975.
[5] J. R. Marti. Accuarte modelling of frequency-dependent transmission lines in electromagnetic transient simulations. IEEE Transactions on Power Apparatus and Systems,
PAS-101(1):147157, Jan 1982.
[6] L. Marti. Simulation of transients in underground cables with frequency-dependent
modal transformation matrices. IEEE Transactions on Power Delivery, 3(3):1099
1110, Jul 1988.
[7] T. Noda, N. Nagaoka, and A. Ametani. Phase domain modeling of frequency-dependent
transmission lines by means of an ARMA model. IEEE Transactions on Power Delivery, 11(1):401411, Jan 1996.
[8] A. Morched, B. Gustavsen, and M. Tartibi. A universal model for accurate calculation of electromagnetic transients on overhead lines and underground cables. IEEE
Transactions on Power Delivery, 14(3):10321038, Jul 1999.
100
101
[9] L. Marti. Simulation of electromagnetic transients in underground cables using the
EMTP. In IEE 2nd International Conference and Advances in Power System Control,
Operation and Management, pages 147152, Hong Kong, Dec 1993.
[10] P. Nichols, D. Spoor, R. Gangopadhyay, and T. Summers. A practical comparison of a
132 kV cable energisation with ATP modelling techniques. In Australasian Universities
Power Engineering Conference (AUPEC 2007), pages 15, Perth, Australia, Dec 2007.
[11] H. W. Dommel. Electromagnetic Transients Program Reference Manual: EMTP Theory Book. Bonneville Power Administration, Portland, 1986.
[12] H. M. Ryan. High Voltage Engineering and Testing. IET, 2001.
[13] K. C. Lee and K. P. Poon. Statistical switching overvoltage analysis of the first BC
Hydro phase shifting transformer using the Electromagnetic Transients Program. IEEE
Transactions on Power Systems, 5(4):10541060, Nov 1990.
[14] C. Yu, N. Petcharaks, and C. Panprommin. The statistical calculation of energization
overvoltages, case of EGAT 500 kV lines. In IEEE Power Engineering Society Winter
Meeting, 2000, volume 4, pages 27052709, 2000.
[15] Ramanuj Gangopadhyay. A Study of Transient Behaviour in Underground Transmission Cables. Undergraduate Thesis, University of Sydney, 2007.
R
Users Guide v4.2.
[16] PSCAD
Canada, 2005.
[17] Insulation co-ordination - part 1: Definitions, principles and rules, IEC STD 60071-1
Ed. 8. Technical report, IEC, 2006.
[18] Insulation co-ordination - part 2: Application guide, IEC STD 60071-2 Ed. 3. Technical
report, IEC, 1996.
[19] Allan Greenwood. Electrical Transients in Power Systems. John Wiley & Sons, 1971.
102
[20] IEEE recommended practice for monitoring electric power quality. IEEE Std 11591995, Nov 1995.
[21] Neville Watson and Jos Arrillaga. Power Systems Electromagnetic Transients Simulation. IEE Power and Energy Series 39. The Institute of Electrical Engineers, London,
United Kingdom, 2003.
[22] Pritindra Chowdhuri. Electromagnetic Transients in Power Systems Second Edition.
Research Studies Press Ltd., Baldock, Hertfordshire, England, 2004.
[23] L. V. Bewley. Travelling Waves on Transmission Systems. Dover Publications Inc.,
New York, 1963.
[24] L. Bergeron. Du Coup de Belier en Hydraulique au Coup de Foudre en Electricit,
(Dunod, 1949). (English translation: Water Hammer in Hydraulics and Wave Surges
in Electricity. ASME Committee, Wiley, New York, 1961.
[25] H. W. Dommel. Digital computer solution of electromagnetic transients in single and
multiphase networks. IEEE Transactions on Power Apparatus and Systems, PAS88(4):388399, April 1969.
[26] Fawwaz T. Ulaby. Fundamentals of Applied Electromagnetics. Prentice Hall, Upper
Saddle River, New Jersey, 1997.
[27] J. R. Marti, L. Marti, and H. W. Dommel. Transmission line models for steady-state
and transients analysis. In IEEE Athens Power Tech, volume 2, pages 744750, Athens,
Greece, Sep 1993.
[28] B. Gustavsen. Panel session on data for modeling system transients insulated cables.
In IEEE Power Engineering Society Winter Meeting, 2001, volume 2, pages 718723,
2001.
103
[29] B. Gustavsen, J. A. Martinez, and D. Durbak. Parameter determination for modelling
system transients - Part II: Insulated cables. IEEE Transactions on Power Delivery,
20(3):20452050, July 2005.
[30] B. Gustavsen, J. Sletbak, and T. Henriksen. Calculation of electromagnetic transients
in transmission cables and lines taking frequency dependent effects accurately into
account. IEEE Transactions on Power Delivery, 10(2):10761084, Apr 1995.
[31] EMTDCTM Users Guide v4.2. Manitoba HVDC Research Centre Inc., Manitoba,
Canada, 2005.
[32] F. Pollaczek. On the field produced by an infinitely long wire carrying alternating
current. Elektrische Nachrichtentechnik, 3:339359, 1926.
[33] F. Pollaczek. On the induction effects of a single phase AC line. Elektrische Nachrichtentechnik, 4:1830, 1927.
[34] L. M. Wedepohl. Transient analysis of underground power transmission systems: System model and wave propagation characteristics. Proceedings IEE, 120(2):253260,
1973.
[35] A. Ametani. A general formulation of impedance and admittance of cables. IEEE
Transactions on Power Apparatus and Systems, PAS-99(3):902910, May 1980.
[36] L. M. Wedepohl. Application of matrix methods to the solution of travelling-wave
phenomena in polyphase systems. Proceedings IEE, 110(12):22002212, 1963.
[37] D. E. Hedman. Propagation of overhead transmission lines I - Theory of modal analysis. IEEE Transactions on Power Apparatus and Systems, PAS-84:200205, March
1965.
[38] J. Duncan Glover and Mulukutla Sarma. Power System Analysis and Design. PWS
Publishing Company, 1994.
104
[39] N. Nagaoka and A. Ametani. Transient calculations on crossbonded cables. IEEE
Transactions on Power Apparatus and Systems, PAS-102(4):779787, April 1983.
[40] A. Budner. Introduction of frequency-dependent line parameters into an electromagnetic transients program. IEEE Transactions on Power Apparatus and Systems, PAS89(1):8897, Jan. 1970.
[41] B. Gustavsen, G. Irvin, R. Mangelrod, D. Brandt, and K. Kent. Transmission line
models for the simulation of interaction phenomena between parallel AC and DC overhead lines. In International Conference on Power Systems Transients (IPST), pages
6167, Budapest, Hungary, June 1999.
[42] T. Noda, N. Nagaoka, and A. Ametani. Further improvements to a phase-domain
ARMA line model in terms of convolution, steady-state initialization, and stability.
IEEE Transactions on Power Delivery, 12(3):13271334, Jul 1997.
[43] J. K. Snelson. Propagation of travelling waves on transmission lines - Frequency dependent parameters. IEEE Transactions on Power Apparatus and Systems, PAS-91(1):85
91, Jan. 1972.
[44] B. Gustavsen and A. Semlyen. Rational approximation of frequency domain responses
by vector fitting. IEEE Transactions on Power Delivery, 14(3):10521061, July 1999.
[45] M. S. Thomas, C. S. Indulkar, and P. R. Bijwe. Sensitivity analysis of peak swithching
overvoltages in underground cables. Electric Machines and Power Systems, 16(5):331
342, 1989.
[46] M. Marzinotto, C. Mazzetti, and P. Schiaffino. Statistical approach to the insulation
coordination of medium and high voltage cable lines. In IEEE Russia Power Tech,
2005, pages 18, June 2005.
[47] C. S. Indulkar and D. P. Kothari. Power System Transients: A Statistical Approach.
Prentice-Hall India Pty. Ltd., New Delhi, India, 1996.
105
[48] A. I. Ibrahim and H. W. Dommel. A knowledge base for switching surge transients.
In International Conference on Power Systems Transients (IPST), Montreal, Canada,
June 2005.
[49] D. A. Woodford and L. M. Wedepohl. Transmission line energisation with breaker prestrike. In Communications, Power and Computing Conference (WESCANEX 1997),
Winnipeg, Manitoba Canada, Dec 1997.
[50] C. S. Chang, W. Q. Jiang, and S. Elangovan. Worst-case performance assessment
of switching overvoltage and mitigation for mass rapid transit system using genetic
algorithm. In IEEE Power Engineering Society Winter Meeting, 2000, volume 2, pages
12891298, 2000.
[51] J. A. Martinez, R. Natarajan, and E. Camm. Comparison of statistical switching
results using gaussian, uniform and systematic switching approaches. In IEEE Power
Engineering Society Summer Meeting, 2000, volume 2, pages 884889, 2000.
[52] TransGrid. Electrical data book NSW transmission system June 2002. June 2002.
[53] A. M. Gole, D. W. Durbak, E. H. Camm, M. Marz, R. C. Degeneff, R.P. OLeary,
R. Natarajan, J. A. Martinez-Velasco, K. Chung Leeand A. Morched, R. Shanahan,
E. R. Patico, G. C. Thomann, B. Spherling, A. J. F. Keri, D. A. Woodford, L. Rugeles,
V. Rashkes, and A. Sarshar. Modeling guidelines for switching transients. IEEE PES
Switching Transients Task Force 15.08.09.03 (Draft Copy), available at http://www.
ee.umanitoba.ca/~hvdc/faq_docs/sws97w.pdf.
[54] A. Morched, L. Marti, and J. Ottevangers. A high frequency transformer model for
the EMTP. IEEE Transactions on Power Delivery, 8(3):16151626, July 1993.
[55] Bjorn Gustavsen. Wide band modelling of power transformers. IEEE Transactions on
Power Delivery, 19(1):414422, Jan 2004.
106
[56] Marjan Popov. Switching Three-Phase Distribution Transformers with a Vacum Circuit
Breaker - Analysis of overvoltages and the protection of equipment. PhD thesis, Delft
University of Technology, 2002.
[57] John R. Carson. Wave propagation in overhead wires with ground return. Bell System
Technical Journal, 5:539554, 1926.
[58] John Nordstrom. Tips and tricks: Unstable poles? Manitoba HVDC Research Centre,
Pulse February 2008 Issue, available at https://pscad.com/resource/File/Pulse/
Pulse_Feb2008.pdf.