Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Model:
Frequency:
Fuel type:
kVA rating:
Emissions level:
DQGAG
50 Hz
Diesel
1700 standby
1540 prime
1250 continuous
EPA NSPS Stationary Emergency Tier 2
2g TA Luft
EDS-1143
EPA-1208
MSP-1127
MCP-230
PTS-310
A042V080
A042V082
A043A395
A042V084
Standby
Prime
Fuel consumption
kVA (kW)
kVA (kW)
kVA (kW)
Ratings
Load
US gph
L/hr
1700 (1360)
1/4
1/2
26
53
102
202
1540 (1232)
1/4
1/2
25.4
48
96
183
1250 (1000)
Full
74
281
Engine
Engine manufacturer
Engine model
Configuration
Aspiration
Gross engine power output, kWm (bhp)
BMEP at set rated load, kPa (psi)
Bore, mm (in)
Stroke, mm (in)
Rated speed, rpm
Piston speed, m/s (ft/min)
Compression ratio
Lube oil capacity, L (qt)
Overspeed limit, rpm
Regenerative power, kW
3/4
75
284
Full
98
372
Continuous
3/4
68
258
Full
89
338
Standby
Prime
Continuous
rating
rating
rating
Cummins Inc.
QSK50-G4 NR2
Cast iron, V 16 cylinder
Turbocharged and low temperature aftercooled
1477 (1980)
1328 (1780)
1100 (1474)
2344 (340)
2110 (306)
1759 (255)
159 (6.25)
159 (6.25)
1500
7.9 (1562)
15:1
204 (215)
1725
116
Fuel flow
Maximum fuel flow, L/hr (US gph)
Maximum fuel inlet restriction, kPa (in Hg)
Maximum fuel inlet temperature, C (F)
836 (221)
30 (9.0)
70 (160)
cumminspower.com
2012 Cummins Power Generation Inc. | D-3523a (11/12)
Air
Combustion air, m3/min (scfm)
Maximum air cleaner restriction, kPa (in H2O)
Alternator cooling air, m3/min (cfm)
Standby
rating
122 (4315)
6.2 (25)
161 (5700)
Prime
rating
118 (4150)
Continuous
rating
103 (3625)
310 (10935)
518 (965)
6.78 (27)
288 (10165)
485 (905)
250 (8825)
477 (890)
54 (50865)
43 (40385)
54 (50865)
43 (40385)
Exhaust
Exhaust flow at set rated load, m3/min (cfm)
Exhaust temperature, C (F)
Maximum back pressure, kPa (in H2O)
40 (104)
40 (53)
401 (106)
1783 (62983)
59 (55530)
0.12 (0.5)
50 (122)
45.5 (61)
496 (131)
2094 (73937)
59 (55530)
0.12 (0.5)
cumminspower.com
2012 Cummins Power Generation Inc. | D-3523a (11/12)
Standby
rating
Prime
rating
Continuous
rating
1666 (440)
1893 (500)
1575 (416)
371 (98)
538 (142)
36 (34495)
22 (21035)
10.7 (10141)
48 (7)
35 (5)
18.3 (60)
18.3 (60)
104 (220)
49 (120)
71 (160)
458 (121)
34 (32275)
20 (18590)
9.9 (9383)
25 (24252)
13 (12444)
6.6 (6292)
7.5 (7108)
100 (212)
100 (212)
66 (150)
66 (150)
Weights2
Unit dry weight kgs (lbs)
Unit wet weight kgs (lbs)
11851 (26127)
12484 (27522)
Notes:
1
For non-standard remote installations contact your local Cummins Power Generation representative.
2
Weights represent a set with standard features. See outline drawing for weights of other configurations.
Derating factors
Standby
Prime
Continuous
Standard Cooling System: Full rated power available up to 650 m (2132 ft) at 40 C. Above these
conditions, derates by 19% per 1000 m (3281 ft) and 19% per 10 C.
Enhanced Cooling System: Derates by 6.5% at sea level at 50 C. Above these conditions, derate by
19% per 1000 m (3281 ft).
Standard Cooling System: Full rated power available up to 650 m (2132 ft) at 40 C. Above these
conditions, derates by 19% per 1000 m (3281 ft) and 19% per 10 C.
Enhanced Cooling System: Derates by 6.5% at sea level at 50 C. Above these conditions, derates by
19% per 1000 m (3281 ft).
Standard Cooling System: Full rated power available up to 510 m (1628 ft) at 40 C. Above these
conditions, derates by 24.5% per 1000 m (3281 ft) and 22.5% per 10 C.
Enhanced Cooling System: Derates by 9.5% at sea level at 50 C. Above these conditions, derates by
23% per 1000 m (3281 ft).
Ratings definitions
Emergency standby power
(ESP):
cumminspower.com
2012 Cummins Power Generation Inc. | D-3523a (11/12)
Alternator data
Voltage
380-440
400-415
400-415
380 &440
380 & 440
380-440
380-440
3300
3300
3300
6300-6600
11000
Connection1
Wye, 3-phase
Wye, 3-phase
Wye, 3-phase
Wye, 3-phase
Wye, 3-phase
Wye, 3-phase
Wye, 3-phase
Wye, 3-phase
Wye, 3-phase
Wye, 3-phase
Wye, 3-phase
Wye, 3-phase
Temp rise
degrees C
105
125/80
150/125/80
80
163/125/80
105/80/80
80/80/80
105
80
105/105/80
80/80/80
80/80/80
Duty2
C
P/C
S/P/C
C
S/P/C
S/P/C
S/P/C
C
C
S/P/C
S/P/C
S/P/C
Single
phase
factor3
Max
surge
kVA4
3375
3688
3960
3688
3960
4563
5000
4287
4922
5398
5250
5196
Winding
No.
312
312
312
312
312
312
312
51
51
51
61
83
Alternator
data sheet
ADS-330
ADS-331
ADS-332
ADS-331
ADS-332
ADS-333
ADS-334
ADS-322
ADS-323
ADS-324
ADS-521
ADS-521
Feature
Code
BA01-2
BA13-2
BA22-2
BA04-2
BA24-2
BA09-2
BA27-2
BA29-2
BA28-2
BA30-2
BA47-2
BA46-2
Notes:
1
Limited single phase capability is available from some three phase rated configurations. To obtain single phase rating, multipy the three
phase kW rating by the Single Phase Factor3. All single phase ratings are at unity power factor.
2
Standby (S), Prime (P) and Continuous ratings (C).
3
Factor for the Single Phase Output from Three Phase Alternator formula listed below.
4
Maximum rated starting kVA that results in a minimum of 90% of rated sustained voltage during starting.
kW x 1000
Voltage x 1.73 x 0.8
kW x SinglePhaseFactor x 1000
Voltage
Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any buildings electrical system
except through an approved device or after building main switch is open.
North America
1400 73rd Avenue N.E.
Minneapolis, MN 55432
USA
Phone 763 574 5000
Fax 763 574 5298
cumminspower.com