Instruction Bulletin

PowerLogicTM Meter Configuration Utility Installation Notes


(Version 2.0)
Use this instruction sheet when you install the PowerLogic Meter
Configuration Utility, version 2.0.

Whats in the PowerLogic Meter


Configuration Utility?

The PowerLogic Meter Configuration Utility (PMCU) is a device setup utility


application. You will use PMCU to configure the onboard setup of
PowerLogic devices over a communications network. With PMCU you can:

add RS485 Serial or Modbus TCP communication connections

perform phasor diagram analysis using the Fundamental Phasors


Diagnostic table

perform a system communication test to verify communication


connection between the computer and the devices in the system

view device, system, and communications diagnostics information using


the Activity Log file

create a backup of the PMCU database, which contains communication


and device configuration information

add devices for onboard configuration


set up and configure onboard device settings like CT/PT ratio, system
type, demand calculations, I/O setup, onboard data logging, onboard
waveform capture, and onboard alarming

PMCU includes an optional feature called Viewing Features. See details


about Viewing Features activation on page 4 of these installation
instructions. With the Viewing Features, you can:

view real-time data in quick tables


view waveforms
view on-board data files
view PowerLogic meter configuration reports
check device status
perform device registry read and write commands

By default, PMCU is a standalone application. It uses its own database to


store device configuration information and communication information.

What PowerLogic Devices Can You Set


Up, Configure, and View in PMCU?

The standard devices installed with PMCU are the PM500, PM700, PM800,
PM9C, CM3000, and CM4000 family of meters. There is an option to install
other device types as well. The optional device types, PM600 and CM2000,
are found in the POWERLOGIC\PMCU\OptionalInstalls folder. That folder
also contains a file called Installing Optional Device Types.txt. See that file
for instructions on installing these device types.

PowerLogic Meter Configuration Utility Installation Notes

Before Installing

63220-060-237C1
08/2008

Ensure that the prerequisites have been met (see table below). If all of the
prerequisites are not met, the install program will notify you and will exit the
installation.
NOTE: PMCU will not install on a computer that has any version of System
Manager Software (SMS) or GFX software. If SMS or GFX is installed on
the computer, the PMCU install detects it and stops the install. PMCU will
install on a computer that has ION Enterprise 5.6, Service Pack 1 or higher.

PMCU Hardware/Software Requirements


Feature

Minimum Requirements

Processor Speed

733 MHz

RAM
Disk Space

256 MB
600 MB free space to install PMCU
An additional 200 MB is recommended for file storage.

PC Monitor Resolution
Operating System
and Service Pack (SP)

800x600
Windows Vista Business
Windows Vista Enterprise
Windows Vista Ultimate
Windows XP Professional, SP1
(SP2 also supported)
Windows 2000 Professional, SP3 (SP4 also supported)
Windows 2000 Server/2000 Advanced Server, SP3
(SP4 also supported)
Windows Server 2003, SP1

Internet Access
(recommended)

About Microsoft Access

Some internet access is recommended for downloading files


and Viewing Features activation. If no internet access is
available, contact your local Schneider Electric representative
for assistance.

Microsoft Access is an application that is included in some versions of


Microsoft Office. Access is used to create, modify, and view databases. In
PMCU, a version of Access 2000 is used to view PowerLogic Meter
Configuration Reports.
If Microsoft Access 97 (or any version prior to Access 2000) is installed on
the computer, the PMCU install detects it and stops the install.
We recommend you upgrade to Access 2000 before you install PMCU. If this is
not possible, you can install the Access 2000 Runtime version on the same
computer as Access 97. Access Runtime is a version of the Access application
that allows database viewing, but does not allow database creation or database
modification. When Access 2000 Runtime is installed, you can install and use
PMCU. Access 2000 Runtime is a free application, and it is included with the
PMCU package (on the PMCU CD, select Access > setup.exe).
If, when you begin the PMCU install, you see a message about Microsoft
Access 97, follow the instructions in the message to go to the
PowerLogic.com downloads area:
www.powerlogic.com/downloadlist.cfm
You must follow special steps to install two versions of Microsoft Access on
one computer. Following these steps ensures that the Microsoft Access
database files can be opened, used, and saved properly. A .pdf file called
"Dual Access Install" is available from the PowerLogic.com downloads area.
Read this .pdf file for assistance on the subject. If you have any questions or
need additional assistance, contact your local Schneider Electric
representative.

2008 Schneider Electric All Rights Reserved

63220-060-237C1
08/2008

PowerLogic Meter Configuration Utility Installation Notes

Install PMCU Using a Dedicated


Windows Administrator Account

The person who installs the PMCU must be logged on to the computer as a
Windows Administrator on the local computer. Create this Administrator
account, if it does not already exist, before you begin the PMCU install.

Installation Instructions

Follow these steps to install PMCU:


1. Read and follow all of the instructions in these Installation Notes.
2. Download the installation file from the PowerLogic website. The file you
will download is called PMCUInstall.exe.
3. When you download it, place PMCUInstall.exe anywhere on the PMCU
computer. Remember where you put it; you will need to access it during
the installation.
4. Close all Windows applications on the PMCU computer.
5. Log on to the local computer with a Windows Administrator account.
6. Navigate to the PMCUInstall.exe file that you downloaded. Double-click
PMCUInstall.exe. At the PowerLogic Meter Configuration Utility
Extraction screen, choose the location where you want to install PMCU:
Browse to the preferred location.
Accept the default (C:\POWERLOGIC\PMCU\Install).
Click Install. Navigate to the location you chose, open the folder named
PMCUv1, and double-click setup.exe.
7. When the Welcome screen displays, click Next.
8. The System Manager Software License Agreement screen displays.
9. If you want to print a copy of the license text, click Print. The text prints at
the computers default printer.
Before you continue, read the license agreement to be sure you accept
its terms. To continue the installation, click Yes. To terminate the
installation, click No.
The Microsoft SQL Desktop license agreement screen displays.
10. If you want to print a copy of the license text, click Print; the text prints at
the default printer. To continue with the install, click Yes.
The Select a Drive screen displays.
11. Select the drive on which both PMCU and SQL will be installed. It is
recommended that you accept the default C drive. Click Next.
The Ready to Install the Program screen displays.
12. Click Install.
Several progress messages display, which can take several minutes.
13. When the Machine Reboot Required message displays, click OK. At the
Windows log-in screen, log in with a Windows Administrator password.

2008 Schneider Electric All Rights Reserved

PowerLogic Meter Configuration Utility Installation Notes

63220-060-237C1
08/2008

SQL Service Pack 3 Installation

The SQL Desktop Engine (MSDE 2000) installation includes the


components for SQL Service Pack 3. If you have already installed SQL,
please be sure that you have installed SQL Service Pack 3. If you still need
to install it, see the Microsoft website for the download.

Launching and Using PMCU

To launch PMCU, click Start > Programs > POWERLOGIC > Meter
Configuration Utility. You will be asked to log on to the application. Enter the
user ID and password that was provided to you.
NOTE: To set up and configure devices, you must have logged on to PMCU
with the master/master login/password.
After the main PMCU window displays, you can begin to use the PMCU
features. For help using PMCU, click Help > PMCU Help.

Activating the Viewing Features

If you do not have internet access, you will need to contact your local
Schneider Electric representative for help in completing activation.
The Viewing Features option requires separate activation. To activate this
feature, click Start > Programs > POWERLOGIC > Activate Viewing &
Feedback.
A Registration and Feedback form screen displays.
Enter the following information:
First Name/Last Name: Type the name of the person who will receive the
confirmation e-mail and activation information.
Company/Country: Type your company name; select your country from the
pull-down list.
Activate Viewing Features: Check this box only when you are activating
your software. If you are sending feedback only, leave this box unchecked.
E-mail Address: Type your e-mail address. This is the address that will
receive instructions for activating the Viewing Features.
Feedback: This is an optional field. Type any comment or suggestion
concerning PMCU and/or the Viewing Features. The information you enter
will enable us to improve the PMCU product. You may visit this website as
often as needed to submit comments or suggestions.
Click Submit to send the activation request and/or feedback. You will be
contacted by return e-mail or by your local Schneider Electric representative
with information about your activation request.

Backing Up the Database

Before you uninstall PMCU, you should first back up the system database.
System backup files are written to the Backup folder in the main PMCU
folder (default: C:\POWERLOGIC\PMCU\Backup). Each backup file
(SMS_System_Data.bak) overwrites the previous file; thus, if you want to
keep the older file, rename or move it before running the backup procedure.
Follow these steps to back up the PMCU system database:
1. With PMCU running, click Tools > System Backup.
2. In response to the prompt asking if you want to continue, click Yes.
The file SMS_System_Data.bak appears in the PMCU > Backup folder.
The message The backup succeeded displays.

2008 Schneider Electric All Rights Reserved

63220-060-237C1
08/2008

Restoring the Database

PowerLogic Meter Configuration Utility Installation Notes

To restore a backed up system database, follow these steps:


1. Close the PMCU application.
2. In the Bin folder, locate and double-click the file RestoreDB.exe (default
location: C:\POWERLOGIC\PMCU\Bin).
3. In response to the prompt asking if you want to continue, click Yes.
The file RestoreDB.log appears in the Bin folder. A message displays
telling you that the restore process succeeded.

Reinstalling and Uninstalling PMCU

NOTE: Never reinstall or uninstall MSDE. Doing so could destroy the data in
your database.
If you install SMS PE on a computer that has PMCU installed, you must
remove both the PMCU and MSDE applications before you install SMS PE.
To reinstall the PMCU and its components, do the following:
1. Shut down the PMCU application.
2. Go to Add or Remove Programs in the Control Panel.
3. Click the Change or Remove Programs button if it is not already
selected.
From the list of currently installed programs, highlight PMCU. Click
Change.
4. When the Setup Type screen displays, check the Reinstall PowerLogic
Meter Configuration Utility radio button. Click Next.
Several messages display while the PMCU files are being reinstalled.
5. When a message displays telling you that the reinstall was successful,
click OK.
At the Machine Reboot Required screen, click OK. At the Windows login
screen, you must log in with a Windows Administrator password.
To uninstall PMCU and its components, do the following:
1. Shut down the PMCU application.
2. Go to Add or Remove Programs in the Control Panel.
3. Click the Change or Remove Programs button if it is not already
selected.
4. From the list of currently installed programs, highlight PMCU. Click
Remove.
5. When the Setup Type screen displays, check the Uninstall PowerLogic
Meter Configuration Utility radio button. Click Next.
NOTE: A message displays, telling you all PMCU files will be removed
from the computer. If you need to back up the PMCU database, click No.
Back up the database, following instructions in the PMCU help file.
When you are ready to uninstall PMCU, repeat steps 1 through 4. Click
Yes at the warning message.
Several messages display while the PMCU files are being uninstalled.
6. At the message that says the PMCU uninstall was successful, click OK.
7. At the Machine Reboot Required screen, click OK. At the Windows login
screen, you must log in with a Windows Administrator password.

2008 Schneider Electric All Rights Reserved

PowerLogic Meter Configuration Utility Installation Notes


Instruction Bulletin

Square D / Schneider Electric


295 Tech Park Dr, Suite 100
Lavergne, TN 37086 USA
1-888-SquareD (1-888-778-2733)
www.SquareD.com

63220-060-237C1
08/2008