OBJECTIVES:
1.
Analyze the volumetric flow measurement using variable area, orifice and
electromagnetic flowmeter.
Flow PATH
:T32
FI31
FT31
LCV31
T31
FT32
T32
The tank T32 should be filled with water up to almost the level of its overflow drain
pipe.
Excess water will overflow into the common drain. Check that the Instrument Air
Supply (IAS) is connected (32psi).
2)
At P31
At T31
Check that the two adjacent manual valves at the control valve LCV31 are fully
open while the by-pass valve fully shut.
Make sure the T32 Drain valve is fully shut.
3)
Turn ON the power supply at the front of the cubicle, to provide power to the
pumps, Recorder and Controller.
4)
Get the RECORDER (LFR31) ready as follows but do not start the pump yet.
The Recorder (LFR31) is ON (open it front swing cover and locate its ON/OFF
push in type switch at the bottom right side below the push button keyboard.
Press in to switch ON )
When the RCD display is lit up at the Recorder, its chart drive is running. The
Recorder chart drive can be switched ON/OFF from the RCD pushbutton at the
front of the Recorder (with its front swing cover opened).
Learn how to access data from the Recorder (LFR31). In particular, note the digital
indication of the various flow rates.
-
the indicator is in engineering units, 0 to 3.0m/Hr for flow rates. Flow rates (in
m/Hr) are displayed at Channels 2 &3. Channel 1 is for Level (0 to 800mm)
5)
6)
Always make sure the pump P32 suction valve and by-pass valve BV32 are always
opened before starting the pump.
7)
Start the pump P32. When the pump is started ad flow is verified (check return
water discharge back into the tank via the appropriate pipelines), shut gradually the
pump manual by-pass valve BV32 until FI31 reads about 2 m/hr.
8)
When the Level at T31 is near its Set point 400mm (see at PV), start pump P31 and
switch the controller LIC31 to Auto (A) mode.
9)
To vary the flow rate, regulate one of the discharge valve at P31 and note the flow
rates at the Recorder display at Channel 2 & 3 and FI31 as per TABLE 1A
Is FI31 = FT31 = FT32 approximately (when the level in tank T31 is controlled)?
Otherwise there is flow leakage or by-pass, OR the instrumentation in inaccurate
and requires calibration check.
10)
EXPERIMENT PROCEDURE
1)
Please refer to the Section Start-up Check List and Preliminary Exercise and
follow the procedures from 1 to 10.
2)
Locate the various flow meters and learn how to read the volumetric flow rates as
follows:
FI31
:Variable area flow meter: Read directly at the flow meter FI31 (m/Hr) near
The next test is to use FE31/FT31 to verify the Orifice/DP flow meter principle that
the flow rate is proportional to the square root of the pressure drop i.e.
Volumetric Flowrate, Fv = kh,
b)
Reduce the flow rate by gradually shutting the pump P31 manual discharge valve
(locate before the strainer) so that the flow rate (read FT32) is reduced. Note the
results in TABLE 1A.
5)
Repeat Procedure 4 at two (2) other flow rates at approximately 1.0 m/Hr (33.3%)
and
Switch the Controller LIC31 to Manual (M) mode with its output MV = 0%.
Make sure the Selector Switch is at position 1:LIC31.
Open fully the pump manual by-pass valve BV32.
Switch off the main power supply switch at the front of the cubicle.
Shut fully the manual valve for instrument air supply (IAS). No need to regulate its
air regulator.
RESULT
I. Note the volumetric flow rate readings in TABLE 1A below at four (4) decreasing and four
(4) increasing flow rates.
Regulate the manual discharge valves at P31 to desired flow rate. Shut one of the pump
manual discharge valve (P31) to reduce flow further.
II. Reading in % and Engineering Units at Recorder LFR31 (Channel 2, 3)
% Reading x Max. Calibrated Range value = Reading in engineering units
% Reading x 3 m/Hr = reading in m/Hr
III. Theoretically, FI31 = FE31/FT31 = FT32, if Level is kept constant
Using FT31 as the reference, note down the various flow rate reading deviations from FI31,
FT32 using the last Column in TABLE 1A.
For FI31
x 100%
FT31
For FT32
x 100%
FT31
IV. Verification of the Orifice / DP flowmeter principle, Fv = kh.
The following are the test readings taken at Procedure 5:
a) Flowrate, Fv at the Recorder Channel 2:____________m/Hr.
b) Pressure drop, h at the orifice/DP flowmeter FT31 : ___________mmH2O.
Note that the pressure drop, h displayed at FT31 is the pressure drop across the
orifice plate
fluctuating due to the turbulence inside the pipeline, take a nominal mean or average
reading for h.
There for:
Fv (m/Hr)
0.03h (mmH2O)