Sei sulla pagina 1di 57

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 1 of 57

TECHNICAL REPORT

Magnetic Testing in the welds of the hatches of the


Gate lock B300, B400, B500, B600 in the Panama Canal
expansion

May 2015

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 2 of 57

Panama, May 2015


Gentlemen:
Cimolai, S. p. A.
Attention. Eng. Simone Cipolotti.
REF:

Magnetic Testing in the welds of the hatches of the Gate lock


B300, B400, B500, B600 in the Panama Canal expansion
Cot C201114-017S

Respected Engineer

Attached Technical Report Magnetic particle inspection, by WDS


Ingeniera, S.A., Testing conducted in welds hatches of the Gate lock
B300, B400, B500, B600 in the Panama Canal expansion.

This report contains observations and conclusions relating to the service.

Best regards

ENG. Daniel Rivero


ASNT-TC-1A Level II PT, VT, MT.
Level I UT, ECT
AWS Member No 675950
WDS INGENIERIA, S.A.
Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 3 of 57

CONTENT.

1. OBJECTIVE
2. INSPECTION DATE, PERSONNEL AND EQUIPMENTS
3. DEFINITIONS
4. PROCEDURE
5. ACCEPTANCE AND REJECT CRITERIA
6. INSPECTION RESULTS
7. CONCLUSSIONS
8. RECOMMENDATIONS
9. ANNEX

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 4 of 57

1. OBJECTIVE.
Evaluate the condition of the welds of the hatches of the new gates lock
in the Panama Canal extension, trough magnetic testing (MT).
The image below represents the planes of the hatches

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 5 of 57

The images below are photographs of the inspection.

Magnetization in two mutually perpendicular directions.

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 6 of 57

The images below are photographs of the inspection.

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 7 of 57

The images below are photographs of hatches in situ.

Top view

Bottom view
WDS INGENIERIA, S.A.
Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 8 of 57

The table here below shows the list of hatches that have been inspected.

Gate Loke B300


Gate lock Components
Hatch No 1
Hatch No 2
Hatch No 3

Type of test
VT, MT
VT, MT
VT, MT

Gate Loke B400


Gate lock Components
Hatch No 1
Hatch No 2
Hatch No 3

Type of test
VT, MT
VT, MT
VT, MT

Gate Loke B500


Gate lock Components
Hatch No 1
Hatch No 2
Hatch No 3

Type of test
VT, MT
VT, MT
VT, MT

Gate Loke B600


Gate lock Components
Hatch No 1
Hatch No 2
Hatch No 3

Type of test
VT, MT
VT, MT
VT, MT

VT: Visual test


MT: Magnetic test

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 9 of 57

2. INSPECTION DATE, PERSONNEL AND EQUIPMENTS.


Gate Lock
Gate Lock
2014.
Gate Lock
Gate Lock

B300. The inspections were made on December 15th 2014.


B400. The inspections were made on December 5th and 6th
B500. The inspections were made on November 22th 2014.
B600. The inspections were made on January 6th 2015.

The personnel involved in the testing was:


- Eng. Daniel Rivero; MT, PT, VT Level II, UT, ECT Level I.
AWS Member No 675950
The equipment used was:
Magnetic Test (MT)
- MAGNAFLUX red magnetic particles.
- MAGNAFLUX Magnetic Yoke, Serial # 1858.

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 10 of 57

3. DEFINITIONS.
Principle: The magnetic particle method is based on establishing a
magnetic field with high flux density in a ferromagnetic material. The flux
lines must spread out when they pass through non-ferromagnetic material
such as air in a discontinuity or an inclusion. Because flux lines cannot
cross, this spreading action may force some of the flux lines out of the
material (flux leakage). Flux leakage is also caused by reduction in
ferromagnetic material (cross-sectional change), a Sharp dimensional
change, or the end of the part. If the flux leakage is strong enough, fine
magnetic particles will be held in place and an accumulation of particles
will be visible under the proper lighting conditions. While there are
variations in the magnetic particle method, they all are dependent on this
principle, that magnetic particles will be retained at the locations of
magnetic flux leakage. The amount of flux leakage at discontinuities
depends primarily on the following factors; flux density in the material,
and size, orientation, and proximity to the surface of a discontinuity. With
longitudinal fields, all of the flux lines must complete their loops though
air and an excessively strong magnetic field may interfere with
examination near the flux entry and exit points due to the high fluxdensity present at these points.
Method: there are three steps essential to the method:

The part must be magnetized.


Magnetic particles of the type designated in the contract/purchase
order/specification should be applied while the part is magnetized
or immediately thereafter.
Any accumulation of magnetic particles must be observed,
interpreted, and evaluated.

Ways to Magnetize: A ferromagnetic material can be magnetized either


by passing an electric current through the material or by placing the
material within a magnetic field originated by an external source. The
entire mass or a portion of the mass can be magnetized as dictated by
WDS INGENIERIA, S.A.
Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 11 of 57

size and equipment capacity or need. As previously noted, in order to be


detectable, the discontinuity must interrupt the normal path of the
magnetic field lines. If a discontinuity is open to the surface, the flux
leakage attracting the particles will be at the maximum value for that
particular discontinuity. When that same discontinuity is below the
surface, flux leakage evident on the surface will be a lesser value.
Field Direction: If a discontinuity is oriented parallel to the magnetic
field lines, it may be essentially undetectable. Therefore, since
discontinuities may occur in any orientation, it may be necessary to
magnetize the part or the area of interest twice or more sequentially in
different directions by the same method or a combination of different
methods to induce magnetic field lines in a suitable direction in which to
perform an adequate examination.
Field Strength: The magnetic field must be of sufficient strength to
indicate those discontinuities which are unacceptable, yet must not be so
strong that an excess of local particle accumulation masks relevant
indications
Types of Magnetic Particles and Their Use: There are various types
of magnetic particles available for use in magnetic particle testing. They
are available as dry powders (fluorescent and nonfluorescent) ready for
use as supplied, powder concentrates (fluorescent and nonfluorescent)
for dispersion in water or suspending in light petroleum distillates,
magnetic slurries/paints, and magnetic polymer dispersions.
Evaluation of Indications: When the material to be examined has been
properly magnetized, the magnetic particles have been properly applied,
and the excess particles properly removed, there will be accumulations of
magnetic particles remaining at the points of flux leakage. These
accumulations show the distortion of the magnetic field and are called
indications. Without disturbing the particles, the indications must be
WDS INGENIERIA, S.A.
Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 12 of 57

examined, classified, compared with the acceptance standards, and a


decision made concerning the disposition of the material that contains the
indication.
Typical Magnetic Particle Indications:
Surface Discontinuities: Surface discontinuities, with few
exceptions, produce sharp, distinct patterns.
Near-surface discontinuities: Near-surface discontinuities
produce less distinct indications than those open to the surface. The
patterns tend to be broad, rather than sharp, and the particles are
less tightly held.
Yokes: Yokes are usually C-shaped electromagnets which induce a
magnetic field between the poles (legs) and are used for local
magnetization. Many portable yokes have articulated legs (poles) that
allow the legs to be adjusted to contact irregular surfaces or two surfaces
that join at an angle.

USE A YOKE AS TOOL FOR INSPECTION


Yoke: Examination of large surface areas for
surface-type discontinuities.
Advantages
Limitations
1. No electrical contact.
2. Highly portable.
3. Can locate
discontinuities in any
direction with proper
orientation.

1. Time consuming.
2. Must be
systematically
repositioned in view of
random discontinuity
orientation.

Yoke, dry powders

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 13 of 57

Dry Particles: Dry magnetic powders are designed to be used as supplied


and are applied by spraying or using directly onto the surface of the part
being examined. They are generally used on an expendable basis because
of the requirement to maintain particle size and control possible
contamination. Reuse is not a normal practice. Dry powders may also be
used under extreme environmental conditions. They are not affected by
cold; therefore examination can be carried out at temperatures that would
thicken or freeze wet baths. They are also heat resistant; some powders
may be usable at temperatures up to 600F (315C). Some colored,
organic coatings applied to dry particles to improve contrast lose their
color at temperatures this high, making the contrast less effective.
Fluorescent dry particles cannot be used at this high a temperature; the
manufacturer should be contacted for the temperature limitations.
USE A DRY PARTICLES FOR INSPECTION
Advantages
Disadvantages
The dry magnetic particle technique is The dry magnetic particle technique:
generally superior to the wet technique for (a) cannot be used in confined areas without
detection of near-surface discontinuities on proper safety breathing apparatus;
parts with a gross indication size:
(b) can be difficult to use in overhead
(a) for large objects when using portable magnetizing positions;
equipment for local magnetization;
(c) does not always leave evidence of complete
(b) superior particle mobility is obtained for coverage of part surface as with the wet
relatively deep-seated flaws using halfwave technique;
rectified current as the magnetizing source;
(d) is likely to have lower production rates
(c) easy for removal.
than the wet technique; and
(e) is difficult to adapt to any type of automatic
system.

Dry Continuous Magnetization Technique: Unlike a wet suspension,


dry particles lose most of their mobility when they contact the surface of
a part. Therefore, it is imperative that the part/area of interest be under
the influence of the applied magnetic field while the particles are still
airborne and free to be attracted to leakage fields. This dictates that the
flow of magnetizing current be initiated prior to the application of dry
magnetic particles and terminated after the application of powder has
WDS INGENIERIA, S.A.
Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 14 of 57

been completed and any excess has been blown off. Magnetizing with HW
current and AC current provide additional particle mobility on the surface
of the part. Examination with dry particles is usually carried out in
conjunction with prod-type or yoke localized magnetizations, and buildup
of indications is observed as the particles are being applied.
4. PROCEDURE.
The procedure is developed based on the standard ASTM E-709-08. What
is summarized in the following steps:
a. Cleaning the inspection area (Chapter 9).
b. Continues magnetization in one direction (using the electromagnetic
yoke).
c. Application of the visible particles (red) dry powder.
d. First evaluation (Chapters 10 and 16).
e. Continues magnetization perpendicular to the first direction of
assessment (using the electromagnetic yoke).
f. Final evaluation (Chapters 10 and 16).
g. Demagnetization (Chapter 18).
h. Cleaning post evaluation (Chapter 19).
i. Demarcation of indications.
j. Filling of the sheet technical report. In accordance with Chapters 17 and
21 of ASTM E-709-08.
5. ACCEPTANCE OR REJECT CRITERIA.
Acceptance or reject criteria was according to Cimolai S.p.A. standards,
regarding all the testing.
6. INSPECTION RESULTS.
The inspection results are observed on sheets of technical reports
attached here.

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 15 of 57

Gate Lock B300

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 16 of 57

Hatch # 1

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 17 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 18 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 19 of 57

Hatch # 2

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 20 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 21 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 22 of 57

Hatch # 3

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 23 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 24 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 25 of 57

Gate Lock B400

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 26 of 57

Hatch # 1

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 27 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 28 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 29 of 57

Hatch # 2

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 30 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 31 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 32 of 57

Hatch # 3

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 33 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 34 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 35 of 57

Gate Lock B500

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 36 of 57

Hatch # 1

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 37 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 38 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 39 of 57

Hatch # 2

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 40 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 41 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 42 of 57

Hatch # 3

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 43 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 44 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 45 of 57

Gate Lock B600

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 46 of 57

Hatch # 1

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 47 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 48 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 49 of 57

Hatch # 2

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 50 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 51 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 52 of 57

Hatch # 3

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 53 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 54 of 57

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 55 of 57

7. GENERAL CONCLUSIONS.

All indications found were considered irrelevant.


All welds were APPROVED.
CIMOLAI staff made the reparations it deemed appropriate.
8. RECOMMENDATIONS.

It is recommended to check the welders qualification records to ensure


continuity in the quality of work.
It is recommended to keep a record of all the testing and their reparations
in order to keep high security standards.
Regarding for the correctives actions of the findings observed by
inspection, these are the responsibility of CIMOLAI.

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 56 of 57

ANNEX.
Referential scheme: Location of hatches on the Gate.

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

TECHNICAL REPORT

Magnetic Testing in the welds of the


hatches of the Gate lock B300, B400,
B500, B600 in the Panama Canal expansion
Rev: 0

May 2015

Page 57 of 57

Detail of
inspection area

WDS INGENIERIA, S.A.


Inspected by:

Report written by:

Report reviewed by:

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Daniel Rivero, ENG.

Calle Ferrer Arias, Edif Dos Mares View, Apto 2D, Dos Mares, Ciudad de Panam
+507 391 0946 / +507 6668 1761
wdsingenieria@gmail.com

Potrebbero piacerti anche