TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER

WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

MATERIAL SPECIFICATIONS CELL

TECHNICAL SPECIFICATION

LT AC SINGLE PHASE 5 30 AMPS


STATIC ENERGY METER
WITH
INTERNAL LOW POWER RADIO FREQUENCY

TECHNICAL SPECIFICATION NO.


CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 1 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

INDEX

CLAUSE NO.
DESCRIPTION
PAGE NO.

1.00
SCOPE
3

2.00
MINIMUM TESTING FACILITIES
3

3.00
SERVICE CONDITIONS
4

4.00

APPLICABLE STANDARDS
4

5.00
GENERAL TECHNICAL PARTICULARS
5

6.00
CONSTRUCTION
6

7.00
ENCLOSURE OF METER:
10

8.00
ANTI TAMPER FEATURES
10

9.00
DISPLAY OF MEASURED VALUES
11

10.00
MAXIMUM DEMAND INTEGRATION PERIOD
12

11.00
DEMONSTRATION
12

12.00
BILLING HISTORY & LOAD SURVEY
12

13.00
COMPUTER SOFTWARE
13

14.00
COMMON METER READING INSTRUMENT (CMRI)
15

15.00
METERING PROTOCOL
17

16.00
CONNECTION DIAGRAM & TERMINAL MARKINGS
17

17.00
NAME PLATE AND MARKING
17

18.00
TESTS
17

19.00
PRE DESPATCH INSPECTIONS
20

20.00
INSPECTION AFTER RECEIPT AT STORES
20

21.00
GUARANTEE
21

22.00
PACKING
21

23.00
TENDER SAMPLE
21

24.00
QUALITY CONTROL
22

25.00
MANUFACTURING ACTIVITIES
22

26.00
QUALITY ASSURANCE PLAN
25

27.00
COMPONENT SPECIFICATION
25

28.00
SCHEDULES

25

29.00
SCHEDULE C
26

30.00
ANNEXURE I
27

31.00
ANNEXURE II
29

32.00
ANNEXURE III
32

33.00

ANNEXURE IV
36

34.00
ANNEXURE V
43

35.00
SCHEDULE A
72

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 2 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

SCOPE:

This specification covers the design, engineering, manufacture, assembly stage


testing, inspection and testing before dispatch and supply of ISI marked LT AC 5
30 Amps Static LCD Energy Meters with Communication capability based on
Internal Low Power Radio Frequency (LPRF) with two way communication to read
the meter data suitable for measurement of Energy (kWh) in Single Phase, Two
wire system of LT Consumers at designated stores.

The meter shall conform in all respects to high standards of engineering, design
and workmanship and shall be capable of performing in continuous commercial
operation, in a manner acceptable to purchaser, who will interpret the meaning of
drawings and specification and shall have the power to reject any work or material
which, in his judgment is not in accordance therewith. The offered material shall
be complete with all components necessary for their effective and trouble free
operation. Such components shall be deemed to be within the scope of Bidders
supply irrespective of whether those are specifically brought out in these
specifications and / or the commercial order or not.

2.00 MINIMUM TESTING FACILITIES:

Manufacturer shall posses fully computerized Meter Test Bench System for
carrying out routine and acceptance Tests as per IS: 13779/1999 (amended up to
date). Test Reports for each and every meter shall be generated. The list of testing
equipments shall be enclosed.

The manufacturer shall have the necessary minimum testing facilities for carrying
out the following tests:

Insulation resistance measurement,

No load condition,

Starting current,

Accuracy requirement,

Power consumption,

Repeatability of error,

Transportation test as per clause no. 18.03.1,

Tamper conditions - as per clause no. 8.00,

LPRF communication connectivity Test as per clause no. 6.23.

The manufacturer shall have duly calibrated RSS meter of class 0.1 or better
accuracy.

The manufacturer shall have Glow Wire Testing facility.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 3 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

The bidder shall have fully automatic Test Bench having in-built constant voltage,
current and frequency source with facility to select various loads automatically
and print the errors directly.

Meter Software:

The Bidders shall have to get appraised & obtain CMMI Level III within one year
from the date of letter of award.

3.00 SERVICE CONDITIONS:

The meters to be supplied against this specification shall be suitable for


satisfactory continuous operation under the following tropical conditions:

Environmental Conditions

a)
Maximum ambient temperature
0

55 C
b)
Maximum ambient temperature in shade
0

45 C
c)
Minimum temperature of air in shade
0

35 C
d)

Maximum daily average temperature


0

40 C
e)
Maximum yearly weighted average temperature
0

32 C
f)
Relative Humidity
10 to 95 %
g)
Maximum Annual rainfall
1,450 mm
h)
Maximum wind pressure
150 Kg/m

i)
Maximum altitude above mean sea level
1,000 meters
j)
Isoceraunic level
50 days/year
k)
Seismic level (Horizontal acceleration)
0.3 g
l)
Climate: Moderately hot and humid tropical climate conducive to rust

and fungus growth.

APPLICABLE STANDARDS:

The meters shall conform to IS: 13779 / 1999 (amended up to date) and other
relevant IS specifications including CBIP Tech. report 88 amended up to date, CEA
regulation and MERC guidelines with latest amendments. The specification given in
this document supersedes the relevant clauses of IS: 13779 / 1999 (amended up to
date) wherever applicable.

Bidder must posses the following certifications at the time of submission of the
bid.

ISO 9000.

ISO 14000.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 4 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

5.00 GENERAL TECHNICAL PARTICULARS:

5.01 The meter shall bear ISI mark.

Class of Accuracy:

The class of accuracy of the Energy Meter shall be 1.0. The accuracy shall not drift
with time.

Current & Voltage Rating:

The current rating shall be 5-30 Amps.

Rated basic current (Ib) for L.T. Energy Meters shall be 5 Amps.

The maximum continuous current (Imax) shall be 600% of rated basic current, i.e.
30 Amps. Moreover the 5-30 Amps meters shall work accurately upto 150% of Imax,
i.e. 45 Amps.

d) The Voltage Rating shall be 240 volts. The voltage range shall be (-) 40% to (+)
20% of rated voltage, i.e. 144 Volts to 288 Volts.

5.04 Temperature:

The standard reference temperature for performance shall be 27 C. The mean


temperature co-efficient shall not exceed 0.07%. Temperature rise shall be as per
IS 13779/1999 (amended up to date).

Power Factor:

The meter shall work for Zero to unity PF (All lag or lead).

5.06 Power Consumption:

Voltage Circuit:

The active & apparent power consumption in each voltage circuit including power
supply of meter at reference voltage, reference temperature & frequency shall not
exceed 2.0 Watt & 10 VA as per IS: 13779 / 1999 (amended upto date).

Current Circuit:

The apparent power taken by current circuit at basic current, reference frequency
& reference temperature shall not exceed 4.0 VA as per IS: 13779 / 1999
(amended upto date).

Starting Current:

The meter shall start registering the energy at 0.2 % of basic current (Ib).

Frequency:

The rated frequency shall be 50 Hz with a tolerance of 5%.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 5 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

6.00 CONSTRUCTION:

The meter shall be projection type and dust and moisture proof. The meter base &
cover shall be made out of unbreakable, high grade, fire resistant Polycarbonate
material so as to give it tough and non-breakable qualities. The base and cover
both shall be transparent. The meter body shall be type tested for IP 51 degree of
protection as per IS: 12063 against ingress of dust, moisture & vermin.

Moulded terminal block for current and voltage connections conforming to IS:
13779 / 1999 (amended up to date) to meet the requirement of terminal
connection arrangement shall be provided. The termination arrangement shall be
provided with an extended transparent terminal cover as per clause number 6.5.2
of IS 13779 and shall be sealable independently to prevent unauthorized
tampering. Proper size of grooves shall be provided at bottom of this terminal cover
for incoming and outgoing service wires.

The terminal block, the terminal cover and the meter case shall ensure reasonable
safety against the spread of fire. They shall not be ignited by thermal overload of
live parts in contact with them.

All insulating materials used in the construction of the meter shall be


substantially non-hygroscopic, non ageing and of tested quality.

All parts that are likely to develop corrosion under normal working condition shall
be effectively protected against corrosion by suitable method to achieve durable
results.

Sealing provision shall be made against opening of the terminal cover and front
cover. It is necessary to provide screws with two holes for sealing purpose. The
meter shall be pilfer-proof & tamper-proof. The provision shall be made on the
Meter for at least two seals to be put by utility user.

The transparent base and cover shall be ultra-sonically welded (continuous


welding) so that once the meter is manufactured and tested at factory, it shall not
be possible to open the cover at site except the terminal cover. The Manufacturer
shall put at least one seal on meter body before dispatch. The thickness of
material for meter body shall be 2 mm minimum.

6.08 The meter shall be completely factory sealed except the terminal block cover.

REAL TIME INTERNAL CLOCK (RTC):

The real time quartz clock shall be used in the meter for maintaining time (IST)
and calendar. The RTC shall be non - rechargeable and shall be pre-programmed
for 30 Years Day / date without any necessity for correction.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 6 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

The time accuracy shall be as per provisions of CBIP Tech Report 88. Facility for
adjustment of real time shall be provided through CMRI with proper security.

The clock day / date setting and synchronization shall only be possible through
password / Key code command from CMRI or Meter testing work bench and this
shall need password enabling for meter.

The RTC shall have long life (10 Years) Non rechargeable battery. The RTC battery
& the battery for display in case of power failure shall be separate.

A push button shall be provided for high resolution reading of display with two
decimal digits as brought out elsewhere in this specification. Likewise, a push
button shall be provided for scrolling the parameters in Alternate Display (On
Demand) mode.

OUTPUT DEVICE:

Energy Meter shall have test output, accessible from the front, and be capable of
being monitored with suitable testing equipment while in operation at site. The
operation indicator must be visible from front. The test output device shall be
provided in the form of blinking LED or other similar devices like blinking LCD.
The pulse rate of output device which is Pulse / kWh (meter constant) shall be
indelibly provided on the nameplate.

It shall be possible to check the accuracy of active energy measurement of the


meter on site by means of LED output. Resolution of the test shall be sufficient to
enable the starting current test in less than 10 minutes and accuracy test at the
lowest load shall be completed with desired accuracy within 5 minutes.

PCB used in meter shall be made by Surface Mounting Technology.

There shall be one CT in Neutral circuit and one shunt in phase circuit. The
current whichever is measured as higher either by CT or shunt shall be used for
processing / computing energy. The shunt shall be manganin based and e-beam
welded for the construction purpose. The meter shall have CTs with magnetic
shielding and same shall be tested separately prior to assembly.

The meter shall be capable to withstand phase to phase voltage (440 V) if applied
between phase to neutral for minimum 5 min.

Power supply unit in the meter shall be transformer less to avoid magnetic
influence.

Non specified display parameters in the meter shall be blocked. Display


parameters in the meter shall not be accessible for reprogramming at site through
any kind of communication.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 7 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

Complete metering system & measurement shall not be affected by the external
electromagnetic interference such as electrical discharge of cables and capacitors,
harmonics, electrostatic discharges, external magnetic fields and DC current in AC
supply etc. The Meter shall meet the requirement of CBIP Tech-report 88 (amended
up to date) except 0.2 Tesla AC magnet test.

The accuracy of the meter and the measurement by meter shall not get influenced
by injection of high frequency AC Voltage / chopped signal / DC signal and
harmonics on the terminals of the meter.

The meter accuracy shall not be affected by magnetic field from all sides of the
meter i.e. front, sides, top and bottom of the meter.

The meter shall record and display total energy including Harmonic energy.

Self Diagnostic Features.

The meter shall display unsatisfactory functioning or nonfunctioning of Real Time


Clock battery.

All display segments: "LCD Test" display shall be provided for this purpose.

Wireless/ Cable less design: The meter shall be wireless to avoid improper
soldering & loose connection / contact.

COMMUNICATION CAPABILITY:

Communication capability of the meter shall be based on Internal Low Power


Radio Frequency (LPRF) technology and meter shall have wireless communication

with HHT, i. e. Common Meter Reading Instrument (CMRI), for auto reading and
downloading all types of data from the meter.

Internal Low Power Radio Frequency (LPRF) shall be capable to read meter from
the distance of minimum thirty (30) meter radius with obstructions from the
meter. Longer communication range is preferred. The range shall further be
increased upto 5 hops through mesh networking of installed meters. However, no
pre - installation programming or post installation programming shall be required
for this purpose.

The meter and CMRI shall be based on open ZigBee - 2007 PRO with Smart energy
profile protocol for Interoperability with following settings:

PAN id shall be 123 (This id is only for samples and actual id will be informed to
successful bidder.)

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 8 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY


METER WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

Radio device shall have 64 bits addressing (as per IEEE.802.15.4 standard.)

The radio shall be programmed with 16 byte security key (128 bit
encryption). The value for sample = MSEDCL (This value is only for samples
and actual value will be informed to successful bidder.)

Scan channel setting shall be 0x02.

RF module at meter shall be programmed for router AT firmware.

The baud rate for radio to meter UART shall be 9,600 bps.

Over the air baud rate shall be 256 kbps.

Meter Serial Number shall be programmed inside the radio & shall be
mapped with 64 bit MAC address of the radio.

The simple metering cluster to be implemented as open protocol from Smart


Energy Version 1.0 application layer protocol is as per Annexure V.

The bidder shall submit Zigbee compliance certificate for radio modules used
in the meter and CMRI.

The frequency range of LPRF equipment shall be approved frequency range


from Government of India, Ministry of Communications and Information
Technology (Wireless Planning and Coordination Wing) New Delhi notification
vide G.S.R. 45 (E), dtd. 28th January, 2005, i.e. the frequency band of 2.4
2.4835 GHz. The meter shall use license free frequency band for
communication so that license for use of LPRF equipment to read energy
meter at site is not required. The required license, if any, for use of LPRF

equipment to read energy meter at the site shall not be under the scope of
purchaser. The necessary support shall be provided by the tenderer.

The meters with Internal Low Power Radio Frequency (LPRF) technology
shall have two Way Communication to read the meter data. However, data
could only be downloaded from meter to CMRI, but no command regarding
data alteration in the meter and data retrieval from meter to CMRI shall be
possible in any case. The LPRF module of the meter shall have no physical
access from outside the meter. It shall not be possible to tamper the data
stored in meter and CMRI even after getting the password of the software. It
shall be locked at the time of manufacturing. Adequate tamper proofing shall
be provided to disallow any change of such auto recorded reading by any
means. Meter shall not be accessible for reprogramming at site through any
kind of communication for any alteration in the factory settings. Tamper
proof arrangement shall be made to get such a reading even at the time of
power failure.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 9 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

The meter shall be supplied with battery back up feature for displaying the
parameters during power OFF condition. Battery life shall be minimum ten years.
Separate push button shall be provided for activation of battery during power OFF
condition. Alternatively, push button provided for displaying alternate mode (On
Demand Mode) parameters shall also be acceptable for activation of battery during
power OFF condition. After activating the battery during power OFF condition, the
meter shall display all Default Display (Auto Scrolling Mode) parameters only once,
after which the battery shall switch OFF automatically. The battery shall be locked
after 3 operations during one power OFF cycle.

The accuracy of the meter shall not be affected with the application of abnormal
voltage / frequency generating device such as spark discharge of approximately 35
KV. The meter shall be tested by feeding the output of this device to meter in any of
the following manner for 10 minutes:

On any of the phases or neutral terminals

On any connecting wires of the meter (Voltage discharge with 0-10 mm spark gap)

At any place in load circuit

Anywhere on meter body

The accuracy of meter shall be checked before and after the application of above
device.

The data stored in the meters shall not be lost in the event of power failure. The
meter shall have Non Volatile Memory (NVM), which does not need any battery
backup. The NVM shall have a minimum retention period of 10 years.

7.00 ENCLOSURE OF METER:

As per Annexure III.

8.00 ANTI TAMPER FEATURES:

The meter shall detect and register the energy correctly only in forward direction
under any one or combination of following tamper conditions:

8.01 Reversal of phase & neutral.

8.02 Reversal of line and load terminals.

8.03 Load through local Earth.

8.04 The meter shall work accurately without earth.

Where neutral is disconnected from the load side or from the supply side or both,
the load and supply side, the meter shall record the energy proportionate to the
current drawn through the meter (minimum 30 % Ib)

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 10 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

at reference voltage and unity Power Factor. 5% error in recording is admissible.

All the above tampers shall be verified at basic current at reference voltage.

The potential link shall not be provided on terminal block outside the main meter
cover.

Visual indication as per clause no. 13.00 (c) shall be provided to show tamper
conditions stated above.

The meter shall be immune to the magnetic field (AC / DC / Permanent) up to 0.2
Tesla (except 0.2 Tesla AC). Under influence of any magnetic field (AC / DC /
Permanent) more than 0.2 Tesla, if the accuracy of the meter gets affected, then the
same shall be recorded as magnetic tamper event with date & time stamping and
the meter shall record energy considering maximum value current (Imax) at
reference voltage & unity power factor.

8.07 In the event the meter is forcibly opened, even by 2 to 4 mm variation of the
meter cover, same shall be recorded as tamper event with date & time stamping and
the meter shall continuously display that the cover has been tampered. It is
suggested that the manufacturer shall develop their software such that there shall
be some time delay for activation of this tamper feature and during that period only
the meter cover shall be fitted. After the meter cover is fitted, it shall get activated
immediately with out any delay. The delay in activation of software shall be for one
instance only.

9.00 DISPLAY OF MEASURED VALUES:

The display shall be permanently backlit LCD. The Energy display shall be
minimum 5 digits. The size of digit shall be minimum 9x5 mm. The decimal units
shall not be displayed for Cumulative kWh in auto scroll mode. However it shall be
displayed in push button mode for high resolution display for testing.

The Default Display (Auto scroll mode) shall switch to Alternate Display (On
Demand Display Mode) after pressing the push button continuously for 5 seconds.
The Alternate Display shall switch over to Default Display if the push button is not
operated for 15 seconds.

9.02 Measuring Parameters:

Default Display (Auto Scrolling Mode).

All the following parameters shall be available in Default Display (Auto Scrolling
Mode).

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 11 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

Real time & date.

Active Energy (kWh)

Maximum demand (kWMD) with date & time.

Tamper event of meter cover open with date & time as per clause no. 8.06 The
meter shall display the tamper meter cover open with date & time in auto scroll
mode along with other parameters.

Active cumulative energy (kWh) shall be displayed for 20 seconds & all other
parameters shall be displayed for minimum 6 seconds including LCD check.

Alternate Display (On demand Display Mode) through push button:

The following parameters shall be available in Alternate Display (On demand Display
Mode) and shall be displayed for 6 secs.

Cumulative Active Energy (kWh) for each calendar month for previous six months
with display of month.

Maximum demand (kWMD) in a calendar month for previous six months with date
& time.

Magnetic tamper event with date / time: This shall be displayed as per the
requirement of clause no. 8.06.

The meter shall have a nonvolatile memory, so that the registered parameters shall
not be affected by the loss of power.

10.00 MAXIMUM DEMAND INTEGRATION PERIOD:

Integration period for kWMD shall be of 30 minutes real time based. The maximum
demand shall automatically be reset at 2400 hours of the last day of each calendar
month. No reset push button shall be provided.

11.00 DEMONSTRATION:

The purchaser reserves the right to ask for the demonstration of the equipment
offered at the purchasers place free of cost.

12.00 BILLING HISTORY & LOAD SURVEY:

BILLING HISTORY:

The meter shall have sufficient non-volatile memory for recording history of billing
parameters (Cumulative kWh at the time of reset and kWMD) for last 6 months.

LOAD SURVEY PARAMETERS: kWh, kWMD.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 12 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

The logging interval for load survey shall be 30 minutes. Load survey data shall be
logged for last 45 days on non time based basis, i.e. if there is no power for more
than 24 hours, the day shall not be recorded. Whenever meter is taken out and
brought to laboratory, the load survey data shall be retained for the period of actual
use of meter. This load survey data can be retrieved as and when desired and load
profiles shall be viewed graphically / analytically with the help of meter application
software. The meter application software shall be capable of exporting /
transmitting these data for analysis to other user software in spreadsheet format.

13.00 COMPUTER SOFTWARE:

For efficient and speedy recovery of data downloaded through CMRI on base
computer, licensed copies of base computer software shall be supplied free of cost.
This software will be used at number of places up to Division / Sub Division level.
The computer software shall be "Windows" based & user friendly. The data transfer
from meter to CMRI & from CMRI to laptop computer or PC shall be highly reliable
and fraud proof. (No editing shall be possible on base computer as well as on CMRI
by any means). The software shall have capability to convert all the data into ASCII
format as per MSEDCL requirement as below. As many copies of base computer
software as required up to Division / Sub Division level shall be provided by
supplier.

Billing Data Format:

Reading captured from these meters shall be submitted in one line per meter
reading in following format for billing.

Parameter
length
Position
Remark

Shall be
provided
to

Make Code
3 chars
1-3
successful
bidder
by

MSEDCL.

Meter ID(Serial No)


8 chars
4-11
Left Padded with zeros (0)

Current Reading date


8 chars
12-19
DDMMYYYY format

current KWH reading


8 chars
20-27

Left Padded with zeros (0)

current KW MD with
8 chars
28-35
Left Padded with zeros (0)

date and time

with decimal part if any

Load Survey:

As per clause no. 12.02 above.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 13 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

c) Tamper Data:

SN
Tamper Event name as per Cl.
Occurance
Restoration

9.00
date & time
date & time

1]
Reversal of phase & neutral and

Reversal of line and load terminals

2]
Load through local Earth

3]
Neutral disconnected

4]
Magnetic Tamper

5]
Meter cover Open with date & time
Only occurance

Maximum 10 nos. each of each tamper events shall be registered and displayed by
meter on FIFO basis except tamper feature at sr. no. (5).

Meter manufacturer shall provide API / Exe file with documentation for downloading
the data from the meter along with the sample meter.

Checksum logic shall also be provided for the downloaded data along with the
sample meter.

Checksum checking Exe / API shall also be given for validating downloaded meter
data as well as generated XML file with sample meter.

The total time taken for downloading Billing, Tamper and Load Survey Data for 45
days shall be 8 minutes.

13.06 Downloading time of only Billing data, i.e. kWh shall be less than 5 secs.

The display parameters shall be preprogrammed at factory as per cl. 10.00.

Tamper data shall be stored in memory and retrieved by CMRI with necessary
software.

It shall be possible to upload the CMRI data to any PC having CMRI software. A
consumer based data uploading facility is required so that CMRI shall upload data
only in that PC which has the concerned consumers data. The consumer number +
meter number + make code shall be the key for creating consumers files or
overwriting consumers files in PC.

The BCS software shall create one single file for the uploaded data, e.g. if CMRI
contains the meter readings of 2,000 consumer meters and the said data is
uploaded to BCS, then the BCS shall create a single file containing

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 14 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

separate records for each consumer meter reading. Also there shall be a provision to
give filenames while creating the file. As and when the meter manufacturer releases
new or latest or advanced versions of meter hardware / firmware / software, the
same shall be made available to purchaser immediately on the release date free of
cost. The latest version shall support all existing hardware / meters in the field.

The meter manufacturer shall have to depute Hardware and Software Engineers on
call basis who shall have thorough knowledge of meter hardware / software used for
downloading and converting so as to discuss the problems, if any, or new
development in the hardware / software with General Manager (IT) / Chief Engineer,
(Stores.), MSEDCL, Prakashgad, Bandra (E), Mumbai 400 051 without any
additional charge.

Two separate fields shall be provided for consumer name and address one name
field of one line, and other Address field of two lines.

The meter samples with CMRI shall be tested by our IT Department for the time
required for downloading the data as confirmed by the bidder.

API which will be residing on CMRI will be given to MSEDCL free of cost with all its
documentation and training. Without API, meter samples will not be approved.

As and when the meter manufacturer releases new or latest or advanced versions of
meter hardware / firmware / software, the same shall be made available to
purchaser immediately on the release date free of cost. The latest version shall
support all existing hardware / meters in the field.

14.00 COMMON METER READING INSTRUMENT (CMRI):

14.01 The CMRI shall posses a specific Serial No. which cannot be changed.

The CMRI shall be based on open ZigBee - 2007 PRO with Smart energy profile
protocol for Interoperability with the settings given in clause 7.23 and Annexure V of
the specifications.

The CMRI shall be supplied free of cost in the ratio of one for each 1,000 Nos.
meters supplied including user manual, AA size batteries and a set of direct
communication cords for data downloading to the Laptop or PC for each CMRI.

The CMRI shall be capable to download following data individually after respective
command to CMRI.

Only billing data,

Only billing History,

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 15 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

Only Tamper data,

Only Load Survey data,

All data.

CMRI shall be capable of downloading billing data of at least 2,000 (two thousand)
meters at a time. The CMRI supplied shall be capable for downloading data of
multiple designs and make of meters as well as for meters added in next 5 years for
the common communication protocol attached herewith.

For downloading the data from meter, meter ID shall be manufacturers serial no. of
meter. No separate command for entering meter serial no. in CMRI shall be
necessary.

After successful downloading of meter data to CMRI, an indication on both, CMRI


and meter for confirmation of successful data transfer shall be provided for each set
of data, viz. billing, load survey & tamper data. During this period, the energy
recording shall not be affected. Repeated downloading from the same meter shall be
disabled for a minimum period of 15 minutes for each set of data, viz. billing, load
survey & tamper data. For example, if only the Billing Data is downloaded, then
further downloading of Billing Data shall be disabled for further 15 minutes.

After downloading the data from meters, it shall be possible to create a single file for
all records. The contents of this file shall not be editable.

Further, there shall be facility in CMRI to provide the transfer of meter data to base
computer through RS 232 port as well as USB port.

The interface for communication between CMRI & Base computer shall be supplied
free of cost. Two nos. of chords of minimum length of 1 mtr. shall be provided with
each CMRI for downloading the data from CMRI to base computer.

Necessary software conforming to the enclosed communication protocol, required for


CMRI and Base Computer System with necessary security provisions shall also be
supplied free of cost.

The manufacturer / supplier shall modify the compatibility of CMRI with the meter
and the base computer system due to any change in language or any other reasons
at their own cost within guarantee period.

The CMRI shall have facility for re-entering the meter serial numbers directly from
base computer system so that once these meters are read and the data is uploaded
on base computer system, the serial numbers of existing meters could be deleted
from the CMRI and the meter serial numbers of other meters can be entered in the
CMRI. CMRI shall not download the data of the meters whose serial no. is not in
CMRI.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 16 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

The CMRI shall be with search facility based on either serial number of meter,
consumer number, consumer name and address.

The CMRI shall indicate the status of total consumers / meters, number of
consumers / meters read and balance consumers / meters. The search facility for
the balance meters shall be provided on the CMRI.

METERING PROTOCOL:

As per Annexure IV.

CONNECTION DIAGRAM AND TERMINAL MARKINGS:

The connection diagram of the meter shall be clearly shown on inside portion of the
terminal cover and shall be of permanent nature. Meter terminals shall also be
marked and this marking shall appear in the above diagram. Stickers of any kind
shall not be accepted.

NAME PLATE AND MARKING:

Meter shall have a name plate clearly visible, effectively secured against removal and
indelibly and distinctly marked with all essential particulars as per relevant
standards. The manufacturers meter constant shall be marked on the Name Plate.

In addition to the requirement as per IS, following shall be marked on the Name
Plate.

Purchase Order No.

Month and Year of manufacture Name of purchaser: MSEDCL Guarantee Five Years

ISI mark

Communication Capability: LPRF

The meter Serial No. shall be Bar Coded along with Numeric No. The size of Bar
Code shall not be less than 35X5 mm. Stickers in any case shall not be accepted.

18.00 TESTS:

TYPE TESTS:

Meter shall be fully type tested as per IS 13779/1999 (amended up to date) and
external AC (except 0.2 T AC magnet) / DC magnetic influence tests as per CBIP
Tech-Report 88 with latest amendments. The Type Test Reports shall clearly indicate
the constructional features of the type tested meters. Separate Type Test Reports for
each offered type of meters shall be submitted. All the Type Tests shall have been
carried out from

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 17 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

Laboratories which are accredited by the National Board of Testing and Calibration
Laboratories (NABL) of Govt. of India such as CPRI, Bangalore / Bhopal, ERDA
Vadodara, to prove that the meters meet the requirements of the specification. Type
Test Reports conducted in manufacturers own laboratory and certified by testing
institute shall not be acceptable. The tenderer shall also furnish the particulars
giving specific required details of Meters in schedule `A attached. The offers without
the details in Schedule A stand rejected.

Type test reports shall be submitted along with offer. The type test report of meter
having identical constructional and other features carried out during last three years
shall be valid. The purchaser reserves the right to demand repetition of some or all
the type tests in presence of purchasers representative at purchasers cost.

Meters shall pass all the acceptance and routine tests as laid down in IS: 13779 /
1999 (amended up to date) and also additional acceptance tests as prescribed in this
specification. (3 to 8 meters from a lot more than 1,000 shall be sealed randomly in
the factory and shall be tested for tamper events).

ADDITIONAL ACCEPTANCE TESTS:

The following additional tests shall be carried out in addition to the acceptance tests
specified in IS: 13779 / 1999 (amended up to date).

Transportation Test:

At least 50% of the samples of the meters be tested for error at Imax, Ib and 5% Ib at
unity power factor and 50% Imax and 10% Ib at 0.5 lagging Power Factor besides
checking them for starting current. The meter shall be tested with meter cover duly
tightened and sealed properly. After recording these errors, the meters be put in their
normal packing and transported for at least 50 km in any transport vehicle such as
pick up van, Jeep, etc. on uneven rural roads and then re-tested at all these loads
after the transportation. The variation in errors recorded before and after
transportation shall not exceed 1% at higher loads and 1.5% at low loads.

Other Acceptance Tests:

The meter shall withstand continuously for a period of at least 5 minutes at a voltage
of 440 V between phase and neutral without damage / problems,

Tamper conditions as stated in this specification,

Glow wire testing for polycarbonate material.

Power consumption tests,

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 18 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

Verification of data transfer / downloading via RF port as per technical


specifications,

The meter shall comply all the tests for external AC / DC (except 0.2 Tesla AC
magnet test) magnetic field as per CBIP Tech Report 88 with latest amendments.
Moreover, the magnetic influence test for permanent magnet of 0.5 Tesla for a
minimum period of 15 minutes shall be carried out by putting the magnet on the
meter body. If the accuracy of the meter gets affected during the test, then the same
shall be recorded as magnetic tamper event with date & time stamping and the
meter shall record energy considering maximum value current (Imax) and reference
voltage at unity power factor. After removal of magnet, meter shall be subjected to
accuracy test as per IS 13779 / 1999 (amended up to date). No deviation in error is
allowed in the class index as per IS: 13779 / 1999 (amended up to date) & this
specification.

The meter shall withstand impulse voltage at 10 kV.

The test 18.03.2 (i) to (v) shall be carried out at factory for each inspected lot at the
time of pre-dispatch inspection.

The tests 18.03.2 (vi) & (vii) shall be carried out on one sample from first lot as per
procedure laid down in IS: 13779 / 1999 (amended up to date) and CBIP Tech.
Report 88 in NABL LAB. The test report shall be got approved from Chief Engineer,
MSEDCL, Material Management

Cell, 1

st

Floor, Prakashgad, Bandra (E), Mumbai 400 051 before commencement of

supply.

LIMITS OF ERROR:

Limits of variation in percentage error due to change in voltage shall not exceed the
values given in the following table:

Sr.
Influence
current
Power
Limits of variation in %
No.
quantities
Value
factor
error for class 1 meters

a)
Voltage variation
Ib
1
0.7

15% to +10%
Ib
0.5 lag
1.0

b)
Voltage variation
Ib
1
1.1

40% & + 20%


Ib
0.5 lag
1.5

The meters shall be tested at (-) 15% and at (-) 40% of reference voltage as well as (+)
10% and (+) 20% of reference voltage and shall record

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 19 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

energy within limits of variation indicated above. However the meter shall continue
to register energy up to 50% of the rated voltage.

For other influence quantities like frequency variation the limits of variation in
percentage error shall be as per IS: 13779 / 1999 (amended up to date).

PRE DESPATCH INSPECTIONS:

All Acceptance Tests and Inspection shall be carried out at the place of
manufacturer unless otherwise specially agreed upon by the manufacturer and
purchaser at the time of purchase. The manufacturer shall offer to the inspector
representing the purchaser, all the reasonable facilities, free of charge, for
inspection and testing, to satisfy him that the material is being supplied in
accordance with this specification. The Companys representative / Engineer
attending the above testing shall carry out testing on suitable number of meters as
per sampling procedure laid down in IS: 13779 / 1999 (amended up to date) and
additional acceptance test as per this specification and issue test certificate
approval to the manufacturer and give clearance for dispatch. All the meters offered
for inspection shall be in sealed condition. The seals of sample meters taken for
testing & inspection shall be break open & resealed after inspection.

The first lot of meter may be jointly inspected by the Executive Engineer, Testing
Division and the Executive Engineer, Inspection Wing.

INSPECTION AFTER RECEIPT AT STORES (Random Sample Testing):

For carrying out Random Sample Testing (RST), the sample meters shall be drawn
from any one of the stores against inspected lot and same shall be tested at
respective Testing and Quality Assurance Units at Aurangabad, Bhandup, Kolhapur,
Nagpur, Nashik and Pune. Sample meters shall be drawn as per Annex H of IS:
13779 / 1999 (amended upto

date). Sample meters shall be tested by MSEDCL Testing Engineer in presence of


suppliers representative jointly for (i) Starting Current, (ii) Limits of error, (iii)
Repeatability of error, (iv) No Load Test as per IS: 13779/1999 (amended upto date),
(v) Tamper conditions as per technical specifications and (vi) Data downloading time
as per specifications.

The 5 days advanced intimation shall be given to the supplier and if the supplier
fails to attend the joint inspection on the date informed, the testing shall be carried
out by our Testing Engineer in absence of suppliers representative. If the meters
failed in above Random Sample Testing, the lot shall be rejected.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 20 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

GUARANTEE:

The meter & CMRI shall be guaranteed for the period of five years from the date of
commissioning or five and half year from the date of dispatch whichever is earlier.
The meter / CMRI found defective within above guarantee period shall be replaced
by the supplier free of cost, within one month of receipt of intimation. If defective
meter / CMRI are not replaced within the specified period as above, the Company
shall recover an equivalent amount plus 15% supervision charges from any of the
bills of the supplier.

22.00 PACKING:

The meters shall be suitably packed in order to avoid damage during transit or
handling. Each meter may be suitably packed in the first instance to prevent ingress
of moisture and dust and then placed in a cushioned carton of a suitable material
to prevent damage due to shocks during transit. The lid of the carton may be
suitably sealed. A suitable number of sealed cartons may be packed in a case of
adequate strength with extra cushioning. The cases may then be properly sealed
against accidental opening in transit. The packing cases may be marked to indicate
the fragile nature of the contents.

The following information shall be furnished with the consignment: Name of the
consignee.

Details of consignment. Destination.

Total weight of the consignment.

Sign showing upper / lower side of the crate. Sign showing fragility of the material.

Handling and unpacking instructions.

Bill of Material indicating contents of each package and spare material.

TENDER SAMPLE:

Tenderer are required to submit 10 (Ten) nos. of sample meters and 1 (One) no. of
sample CMRI of offered type and 2 (Two) Nos. of meter enclosures as per technical
specifications along with the API software, BCS, checksum logic & documentation to
EE (SM) in the office of the

Chief Engineer, MSEDCL, Material Management Cell, 1

st

Floor, Prakashgad, Bandra (E),

Mumbai 400 051 on or before the time & date stipulated for submission of offer for
testing the sample meters in third party NABL Lab like ERDA, CPRI, CIPET, ERTL and
testing the offered API by our IT Department as per technical specifications. The offer of
those

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 21 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

eligible bidders shall only be considered if the sample passes the tests at NABL Lab
as well as necessary certification from our IT Department for the offered API. The
results of NABL Lab and the certification from IT Department for offered API shall
not be disputed and shall be binding on the bidder. The required information such
as Manufacturers Name or Trade Name, Sr. No. ISI Certification No. API
specification no., etc. shall be on stickers to be affixed on outer portion of sample
meters being submitted along with the offer. Such information shall not be
embossed or printed on any part of the sample meter.

Out of these, two samples shall be without ultrasonic welding to confirm


constructional features.

24.00 QUALITY CONTROL:

The purchaser has a right to send a team of experienced engineers for assessing the
capability of the firm for manufacturing and testing of meters as per this
specification. The team shall be given all assistance and co-operation for inspection
and testing at the bidders works.

The meters supplied shall give service for a long period with out drifting from the
original calibration & performance must be near to zero percent failure.

MANUFACTURING ACTIVITIES:

The manufacturer shall submit the list of plant and machinery along with the offer.

Meter shall be manufactured using SMT (Surface Mount Technology) components


and by deploying automatic SMT pick and place machine and reflow solder process.
The loops/wired joints must be avoided on PCB. Further, the Bidder shall own or
have assured access (through hire, lease or sub-contract, documentary proof shall
be attached with the offer) of above facilities.

Quality shall be ensured at the following stages:

At PCB manufacturing stage, each Board shall be subjected to computerized bare


board testing.

At insertion stage, all components shall undergo computerized testing for


conforming to design parameters and orientation.

Complete assembled and soldered PCB shall undergo functional testing using
Automatic Test Equipments (ATEs).

Important: - Prior to final testing and calibration, all meters shall be subjected to
O

ageing test (i.e. Meters shall be kept in heating chamber for 72 hours at 55 C
temperature at full load current.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 22 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY


METER WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

After 72 hours, meters shall work satisfactory) to eliminate infant mortality.

The calibration of meters shall be done in-house on a computerized testing


bench having stabilized power supply.

The bidders shall submit the list of all (imported as well as indigenous)
components to be used in meter, separately along with the offer. List of
makes of components is attached herewith as a guide line (Annexure-II).

Bought out items: A detailed list of bought out items which are used in the
manufacturing of the meter shall be furnished indicating the name of firms
from whom these items are procured. The bidder shall also give the details
of quality assurance procedures followed by him in respect of the bought out
items.

List of Plant and Machinery used for production of energy meters.

Sr.

List of Plant and Machinery used for Energy meter Production

No.

Fully
automatic
testing
Bench
Routine
Testing
and

1
with
ICT

for testing link less

meters

Calibration of Meters

Semi
automatic
testing
Bench
Routine
Testing
and

with MSVT

Calibration of Meters

IR Tester

Insulation testing

HV Tester

Insulation testing

Error calculators

Error testing

Long duration Running test set


Reliability Testing

ups

Reference
Meters
cl0.01
Error calculation

accuracy

Ultrasonic welding Machines


Welding of meters

Automatic
Pick
and
Place
Automatic
placing of
SMT

Machines

components

10

Solder Paste Printing Machine

SMT soldering

11

Soldering Furnace IR reflow


SMT soldering

12

PCB Scanner

For testing of PCBs

13

ATE functional tester

For testing of Components

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011


Page 23 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY


METER WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

14
Programmers
and

Program
Chip Programming Tools

Loaders

15
CAD PCB designing setups
PCB designing

16
Furnace IR type for Hybrid Micro
resistance
network
and

Circuits

HMC manufacturing

trimming of
resistances
for

17
Laser Trimming Machines
higher

accuracy

measurement

18
Wave Soldering Machines
Wave soldering of PCBs

19
Humidity Chamber

Accelerated

testing
for
Life

cycle

20
Dry Heat Test Chamber

Accelerated
testing
for
Life

cycle

21
Thermal Shock Chamber
Accelerated
testing
for
Life

cycle

22
PRO -E Mechanical Design
Mechanical CAD stations

Stations

23
Spark
Erosion
Tool
fabricating
Tool
fabrication
and
Die

Machine

manufacturing

24
CNC wire
Cut
Tool
Fabrication
Tool

fabrication
and
Die

machine

manufacturing

25
CNC
Milling
Machine for
Tool
fabrication
and
Die

composite tool fabrication


manufacturing

26
Injection Moulding Machine
Moulding of plastic parts

27
Vibration testing Machine
Vibration testing of Meters

28
Glow Wire Test machine

Testing of Plastic Material

29
Fast
transient
burst
testing
Type testing of Meters

setup

30
Short term over Current testing
Type testing of Meters

setup

31
Magnetic
and
other
tamper
Tamper Testing

testing setups

32
Impulse Voltage Testing Setup
Type testing of Meters

33
Composite

Environmental
Type testing of Meters

testing chambers

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011 Page 24 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

26.00 QUALITY ASSURANCE PLAN:

The tenderer shall invariably furnish QAP as specified in Annexure-I along with his
offer the QAP adopted by him in the process of manufacturing.

Precautions taken for ensuring usage of quality raw material and sub component
shall be stated in QAP.

COMPONENT SPECIFICATION:

As per Annexure - II enclosed.

SCHEDULES:

The tenderer shall fill in the following schedules and submit along with the offer. If
the schedules are not submitted duly filled in with the offer, the offer shall be
rejected.

Schedule A ... Guaranteed Technical particulars (As per GTP parameters uploaded
on e- Tendering site.)

Schedule C ... Tenderer Experience

The discrepancies, if any, between the specification and the catalogs and/or
literatures submitted as part of the offer by the bidders, shall not be considered and
representations in this regard will not be entertained. If it is observed that there are
deviations in the offer in Guaranteed Technical Particulars other than those
specified in the deviation schedules then such deviations shall be treated as
deviations.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 25 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

SCHEDULE C

TENDERER'S EXPERIENCE

Tenderer shall furnish here list of similar orders executed /under execution for
supplying meters boxes by him to whom a reference may be made by purchaser in
case he considers such a reference necessary.

Sr. No. Name of client

Order No. & date

Qty. ordered Qty. supplied

NAME OF FIRM _____________________________________

NAME & SIGNATURE _______________________________

DESIGNATION ______________________________________

DATE _______________________________________________

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 26 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

ANNEXURE I

Quality Assurance Plan

The bidder shall invariably furnish the following information along with his bid,
failing which his bid shall be liable for rejection. Information shall be separately
given for individual type of material offered.

Statement giving list of important raw materials, names of sub - suppliers for the
raw materials, list of standards according to which the raw materials are tested.
List of tests normally carried out on raw materials in presence of Bidder's
representative, copies of test certificates,

Information and copies of test certificates as in (i) above in respect of bought out
accessories,

List of manufacturing facilities available,

Level of automation achieved and list of areas where manual processing exists,

List of areas in manufacturing process, where stage inspections are normally


carried out for quality control and details of such tests and inspections,

List of testing equipments available with the bidder for final testing of equipment
specified and test plan limitation, if any, vis--vis, the type, special acceptance and
routine tests specified in the relevant standards. These limitations shall be very
clearly bought out in schedule of deviation from specified test requirements.

The successful bidder shall within 30 days of placement of order, submit following
information to the purchaser.

List of raw materials as well as bought out accessories and the names of sub suppliers selected from those furnished along with offers.

Type test certificates of the raw materials and bought out accessories if required by
the purchaser.

Quality assurance plan (QAP) with hold points for purchaser's inspection. The
quality assurance plant and purchasers hold points shall be discussed between
the purchaser and bidder before the QAP is finalized.

The contractor shall operate systems which implement the following:

Hold point: A stage in the material procurement or workmanship process beyond


which work shall not proceed without the documental approval of designated
individuals organizations. The purchaser's written approval is required to
authorize work to progress beyond the hold points indicated in quality assurance
plans.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 27 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

Notification point: A stage in the material procurement or workmanship process


for which advance notice of the activity is required to facilitate witness. If the
purchaser does not attend after receiving documented notification in accordance
with the agreed procedures and with the correct period of notice, then the work
may proceed.

The successful bidder shall submit the routine test certificates of bought out
accessories and central excise passes for raw material at the time of routine
testing if required by the purchaser and ensure that Quality Assurance program of
the contractor shall consist of the quality systems and quality plans with the
following details.

The structure of the organization.

The duties and responsibilities assigned to staff ensuring quality of work.

The system for purchasing taking delivery and verification of material.

The system for ensuring quality workmanship.

The system for retention of records.

The arrangement for contractors internal auditing.

A list of administration and work procedures required to achieve and verify


contractor's quality requirements.

These procedures shall be made readily available to the project manager for
inspection on request.

Quality Plans:

An outline of the proposed work and programme sequence.

The structure of the contractor's organization for the contract.

The duties and responsibilities assigned to staff ensuring quality of work.

Hold and notification points.

Submission of engineering documents required by the specification.

The inspection of materials and components on receipt.

Reference to the contractor's work procedures appropriate to each activity.

Inspection during fabrication / construction.

Final inspection and test.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 28 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

ANNEXURE II

COMPONENT SPECIFICATION

Sr.
Component
Requirement

Makes

No.
function

USA:
Analog
Devices,
Cyrus

Logic,
Atmel,
Philips,
Teridian.

Dallas, ST, Texas Instruments,

Motorola,
Maxim,

National

Semiconductors,
Freescale,

Measurement
The
measurement
or
Onsemiconductors

computing chips used in

1
or computing

Germany: Siemens.

the Meter shall be with

chips
the Surface mount type.
South Africa: SAMES.

Japan: NEC, Toshiba, Renasas,

Hitachi.

Austria: AMS

Holland: Philips (N X P )

The memory chips shall

not
be
affected
by

external

parameters

like
sparking,
high

voltage
spikes
or

electrostatic
discharges.

Meter
shall
have
non
USA: Atmel,
Teridian,
National

volatile memory (NVM).


Semiconductors, Philips,
Texas

2
Memory
No other type of memory
Instruments,

ST,
Microchip,

Spanson (Fujitsu), Ramtron

chips
shall
be

used
for
data

recording

and
Japan: Hitachi, Renasas

programming.
(The
life
Germany: Siemens

of the NVM is highest)

There
shall
be
security

isolation

between

metering

circuit,

communication
circuit,

and power circuit.

Display
a) The
display
modules
Singapore:

E-smart,

Bonafied

shall be well protected


Technologies, Display Tech,

modules

from the
external UV

Korea: Advantek, Jebon, Union

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 29 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

radiations.

Display Inc.,

b) The display
visibility
Japan: Hitachi, Sony, L&G.
shall be sufficient
to
Malaysia:
Crystal
Clear
read
the
Meter
Technology.

mounted
at
height
of

0.5 meter as well as at

the height of 2 meters

(refer 3.2 d for viewing

angle).

The construction of the modules shall be such that the displayed quantity shall not
disturbed with the life of display (PIN Type).

It shall be trans-reflective HTN (HTN Hyper Twisted Nematic (120)) or STN (STN
Super Twisted Nematic (160)) type industrial grade with extended temperature
range. HTN Hyper Twisted Nematic (120)

STN Super Twisted Nematic (160)

USA: National Semiconductors,

Atmel,
Philips,
Texas

The active
& passive
Instruments, BC
Component

components
shall be of
Analog devices,
ST,
Maxim,

Electronic
the surface mount type
Kemet
Onsemiconductors,

4
components
& are to be handled &
Freescale,
Intersil,
Raltron,

soldered by the state of


Fairchild, Muruta, Agilent, AVX,

art assembly processes.


Abracon,
Sipex,
Diode
Inc.,

Honeywell,

Power
Integration,

Fox, Roham

Japan: Hitachi, Oki,


AVZ
or

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011


Page 30 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

Ricon,
Toshiba,
Epson,
Kemet,

Alps,
Muruta,
TDK,
Sanyo,

Samsung

India:
Keltron,
Incap,
VEPL,

PEC, RMC,
Gujarat
Polyavx,

Prismatic,
MFR
Electronic

components Pvt. Ltd., Cermet

Korea: Samsung

Japan: Panasonic

Germany:
Vishay,

Epcos,

Diotech, Kemet

Only non rechargeable


USA: Maxell, Renata

battery shall be used for


Japan:
Panasonic,

Sony,

RTC as well as display in


Mitsubishi, Sanyo

5
Battery
absence of Power since
Germany: Varta

the life & Reliability of

these are better than the


France: Saft

rechargeable batteries.
Korea: Tekcell, Vitzrocell

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 31 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

ANNEXURE III

TECHNICAL SPECIFICATION OF SINGLE PHASE POLYCARBONATE


METER BOX

TECHNICAL SPECIFICATION NO. CE/MMC/MSC-IV/003, DATE: 18.07.2011

SCOPE:

This specification covers design, manufacturing, testing and supply of fully


transparent poly-carbonate Meter Box suitable for Single phase Static Energy
meter. The meter box shall be suitable for wall mounting and indoor or outdoor
application.

SERVICE CONDITION:

The meter box to be supplied against this specification shall be suitable for
satisfactory continuous operation under following service conditions.

(i)
Max. ambient temperature
0

50 C
(ii)
Max. relative humidity
100%
(iii)
Max. annual rainfall

1450 mm
(iv)
Max. wind pressure
2

150 Kg./ m
(v)

Max. altitude above mean sea level


1000 meters
(vi)
Seismic level (Horizontal acceleration)
0.3 g
(vii)
Ref. Ambient temperature for temperature rise
0

50 C

Climatic condition: Moderately hot & humid tropical climate


conducive to rust and fungus growth

APPLICABLE STANDARDS:

Unless otherwise modified in this specification the meter box shall be generally
conform to IS: 14772/2000 (amended up to date)

4.00 DESIGN AND CONSTRUCTION:

The meter box shall be so constructed as to have roof tapering down on both sides
for easy flow of rain water and box shall be totally transparent poly-carbonate
material natural white colour and having good workmanship.

4.02

The meter box shall be


made of anti corrosive, dust proof, weather

proof, unbreakable, scratch resistant, water proof, ultra violet stabilized

and flame retardant high grade poly-carbonate material having good

dielectric and mechanical strength.


4.03
The box material
must
be UV stabilized to ensure that the base

and cover does


not get
Yellow over a period of time. The surface

appearance of part must be smooth, non porous and homogeneous, free of ripples,
defects and marks. No fillers or fibers shall be visible at any place.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 32 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

(a) The meter box shall be made from Poly-carbonate as per IS: 14772 / 2000 and
as per requirement of this specification.

(b) The wall thickness of meter box shall be minimum 3 mm on load bearing side
and cover shall be 2 mm.

The internal dimensions of meter box shall be such that there shall be minimum
60 mm clearance at the bottom, 40 mm clearance on three sides, 25 mm clearance
on front and 10 mm clearance from back of the meter.

The meter box shall not change in colour, shape, size, dimension when subjected
to 200 hours on UV ageing test. Also it shall be capable of withstanding
temperature of boiling water for five minutes continuously without distortion or
softening.

4.07 The cover


shall be made overlapping type having collars on all four
sides. The cover of the box shall be provided with semi circular /
circular
gasket of sufficient size to completely fit in the grooves of the

base. The gasket shall be made of neoprene rubber or equivalent good quality
rubber.

The cover shall be made overlapping type having collars on all four sides. The cover
of meter box shall have 4 nos. of non-detachable self-locking push fit type
arrangement. It shall have suitable non-detachable fitting to base such that if
pushed once inside, the cover shall rest on the base of box in such a way that any
access from outside to the meter is not possible. The locking (press fit) knob shall
get completely contained in the locking hub inside the meter box. The locking hub
shall be closed at its base.

Meter box shall confirm IP-51.

The meter base support inside the box shall be raised by about 10 mm in the box
for easy wiring. While fixing the meter, the meter screws shall not protrude
outside.

Suitable circular holes shall be provided at the bottom of the box for inlet and
outlet cables with glands of 6 or 8 mm size made of brass or poly-carbonate
material for the cable securely fixed to the bottom of the box on both sides by
chuck nuts with rubber grommet. All the screws and washers shall be properly
zinc plated.

For fixing the box to wall or wooden board 4 nos. key holes of min. 5 mm diameter
shall be provided at the four corners of meter box. The meter is to be installed in
the box and the box in assembled condition shall have provision to fix it to pole or
a wall. The 4 nos. screws of size 5 mm diameter and 37.5 mm long with suitable
washers shall be provided with each meter box.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 33 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

The tolerance permissible on the various dimensions of the meter box shall be
3%.

The surface appearance of part must be smooth, non porous and homogeneous,
free of ripples, defects and marks. No fillers or fibers shall be visible at any place.

TESTS:

The meter box shall have been successfully type tested as per IS: 14772 / 2000
from NABL Accredited independent testing laboratories such as

CPRI/ERDA. The type test report shall clearly indicate the constructional features
of the type tested meter box. The tenderer shall also furnish certificate from
laboratories where type test carried out. The requisite test facility available in
house for that particular test shall be approved by NABL. The type tests conducted
in manufacturers own laboratory and certified by testing institute shall not be
acceptable. The tenderer shall also furnish the particulars giving specific required
details of meter box in schedule A attached (As per Guaranteed Technical
Particulars uploaded on e - Tendering site). The offers without the details in
schedule A and Type Test reports stands rejected.

6.00 TESTING AND MANUFACTURING FACILITIES

The manufacturer shall have necessary machinery for production of polycarbonate


meter box.

The manufacturer shall have in house testing facilities for carrying out following
tests:

Sr. No.
Test Details

Reference standard

1.
Flammability (V2)
UL 94 or IS: 11731 (Pt.

II)

2.
O

Heat deflection temp. at (min. 150 C)


ISO 75

0.45 SUB MPA Load

3.
Glow wire test
IEC6952-1 or

IS: 11000 (Pt 2/sec.1)

4.
Ball pressure test
IEC: 335

5.
Water absorption
IS: 14772

6.
Mechanical Strength
IS: 14772

7.
Marking Dimensions and construction
IS: 14772

8.
Spirit burner test
IS: 4249

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 34 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

DRAWING /SAMPLE:

The detailed dimensional drawing showing clearly the dimensions and material for
meter box and its constructional features shall be invariably furnished with the
offer. Two samples of meter box as per the specifications shall be submitted along
with offer. The offer would be rejected, if meter box samples are not accompanied.

MARKING / EMBOSSING:

The following information shall be clearly and indelibly embossed (not printed) on
the cover of the meter box except Sr. No. which may be indelibly printed with inkjet
printing on the base and cover of the meter box. The meter box Sr. No. shall be same
as that of the meter Sr. No. fitted inside the meter box.

Purchase order number and date.

Year and month of manufacture.

Purchaser's name: MSEDCL

Guarantee 5.5 Years.

Sign of danger.

Code name of manufacturer

Meter box Sr. No. [Printed on both the base and cover of meter box]

9.00 PACKING:

The meter box shall be suitably packed in corrugated boxes in

order to avoid damage during transit or handling.

10.00 GUARANTEE:

The supplier shall have to give 5.5 years guarantee of meter box from date of supply
to MSEDCL.

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 35 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

ANNEXURE IV

METERING PROTOCOL

(V1.04)

Communication Port Setting: FOR RF

Baud Rate: 9600

Data Bits: 8

Parity: None

Stop Bit: 1

Flow Control: None

Frequency band: 2.4 to 2.4835 GHz

Bandwidth: 200 KHz

Networking: Mesh

1. CMRI Send Request Communication Initialization

Request

2FH+3FH+4FH+53H+47H+49H+5FH+4DH+65H+74H+65H+72H+0FH+0FH+0FH
+0FH+0FH+21H+0DH+0AH

st

Layer Command for Application Layer Connection

This acts as an attention command.

Meter Answer

2FH+2FH+4FH+53H+47H+49H+76H+31H+2EH+30H+31H+0DH+0AH

Fixed response that means meter is ready for communication.

2. CMRI Send Request Communication

Request

06H+54H+31H+0DH+0AH

Authentication Command

nd

Layer command for First Layer Request Authentication

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 36 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

Meter Answer

01h+54h+31h+02h+28H+Token1(8 byte ASCII)+29H +03H+CheckSum

01h+54h+31h+02h+28H Fixed response

29H +03H Fixed response

Checksum Sum of Byte i.e. [01H+54+..+03H]

(The checksum byte from the second byte to the byte of last but one, 1 Byte, LSB)

Token1(Eight byte ASCII) : Byte1+ Byte2+ Byte3+ Byte4+ Byte5+ Byte6 +


Byte7+Byte8

Byte1
First layer Request Connection Result (0, 1)

Authentication of 1st layer

0
Failed

1
Connected
Byte2

Data length = 6

Byte3 Byte8
Fixed Validate data

These 6 bytes of data is randomly generated number by the meter with minimum
value of 0 and maximum value of 254 (each byte).

3. CMRI Send Request: Security Clearance

Request

01H+54H+32H+02H+28H+Token2+29H+03H+CheckSum

rd

Layer command for Clearance

Command Clearance and validation for data transfer

Token 2:

//below is the code to convert Token1 to Token2:

Unsigned char FindASC (int ch)


{

If (ch >= 0 && ch <=9)

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 37 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

Return (0x30 + ch);


Else

If (ch >=10 && ch <=15) Return (0x37 + ch);

Else
Return (0x30);
}

Int FindBCD(unsigned char ch)


{

If (ch.>= 0 && ch,<=9) Return (ch 0x30);

Else

If (ch >= A && ch <=F) Return (ch 0x37);

Else

If (ch >= a && ch <= f) Return (ch- 0x57);

Else

Return (0x00);
}

// Convert Token1 to Token2 For (int i=0; i<8; i+=2)

Unsigned char kk;

kk = FindBCD(Token1[i])+ FindBCD (Token[i+1])*16; kk -= 0x18;

Token2[i] = Find ASC(kk & 0x0F); Token2[i+1] = FindASC (kk >> 4);

Meter Answer

06H (Meter check successes or 15H (meter check failed)

Connection Result:

Connection Failure

Connection Pass

CMRI Send Request Meter Data

Request

01H+54H+33H+02H+Token3+28H+39H+39H+39H+39H+29H+03H+CheckSum

Token 3: Refer Table-1 for Token

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 38 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

Token 3 is data Request ID

Meter Answer

02H+Token4+03H or 04H+CheckSum

If the last byte of packet received equals 03H (excluding checksum), it implies that
the transfer is not yet finished.

CMMR sends 06H for requiring the meter send the next data packet otherwise it
sends 15H (Communication would be ended after 3 retries in case of a
communication failure)

The communication would be ended if last byte received from the meter is 04H (i.e.
there are no more data packets to be received.)

Taken 4: Result Data

Token 4 Formats: 28H+Value1+29H+28H+Value2+29H++28H+ValueN+29H

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 39 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

TABLE 1

Abbreviation

Explanation
Token3
Format
Example

CkWh
Cumulative Active Energy in kWh
0000
XXXXX.X
21345.3

MD

MD of Current month in KW
0001
XX.X
02.4

MDOT
MD occurring time
0002
HH:MM
12:30

MDOD
MD occurring date
0003
DD:MM:YY
13:09:10

Time
Time

0004
HH:MM
12:30

Date
Date

0005
DD:MM:YY
13:09:10

CkWhPM1
Cumulative Active Energy of previous
0006
XXXXX.X
20046.3

month 1
kWh

CkWhPM2
Cumulative Active Energy of previous
0007

XXXXX.X
19834.2

month 2
kWh

CkWhPM3
Cumulative Active Energy of previous
0008
XXXXX.X
18756.1

month 3

kWh

CkWhPM4
Cumulative Active Energy of previous
0009
XXXXX.X
17940.3

month 4
kWh

CkWhPM5
Cumulative Active Energy of previous
000A
XXXXX.X
16620.2

month 5
kWh

CkWhPM6
Cumulative Active Energy of previous
000B
XXXXX.X
15420.3

month 6
kWh

MDPM1
MD of previous month 1 KW
000C
XX.X
02.4

MDPM1OT
MD of previous month 1 occurring date
000D
DD:MM:YY
13:08:10

MDPM1OD
MD of previous month 1 occurring time
000E

HH:MM
13:00

MDPM2
MD of previous month 2 KW
000F
XX.X
02.4

MDPM2OT
MD of previous month 2 occurring date
0010
DD:MM:YY
13:07:10

MDPM2OD
MD of previous month 2 occurring time
0011
HH:MM
13:30

MDPM3
MD of previous month 3 KW
0012
XX.X
02.4

MDPM4OT
MD of previous month 3 occurring date
0013

DD:MM:YY
13:06:10

MDPM3OD
MD of previous month 3 occurring time
0014
HH:MM
12:30

MDPM4
MD of previous month 4 KW
0015
XX.X
02.4

MDPM4OT
MD of previous month 4 occurring date
0016
DD:MM:YY
13:05:10

MDPM4OD
MD of previous month 4 occurring time
0017
HH:MM
11:30

MDPM5
MD of previous month 5 KW
0018

XX.X
02.4

MDPM5OT
MD of previous month 5 occurring date
0019
DD:MM:YY
13:04:10

MDPM5OD
MD of previous month 5 occurring time
001A
HH:MM
12:00

MDPM6
MD of previous month 6 KW
001B
XX.X
02.4

MDPM6OT
MD of previous month 6 occurring date
001C
DD:MM:YY
13:03:10

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011


Page 40 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

MDPM6OD
MD of previous month 6 occurring time
001D
HH:MM
12:30

Meter Serial No
Meter Serial Number
001E
XXXXXXXX
00100845

Make
Make Code
001F

XXXXX

Latest 10 Tamper Events-Reversal of

Refer Note 1

Tamper
phase & neutral and
0020

Reversal of line and load terminals

Tamper
Latest 10 Tamper Events-Load through
0021
Refer Note 1

local Earth.

Tamper
Latest 10 Tamper Events-Neutral
0022
Refer Note 1

disconnected

Tamper
Tamper Event - Meter Cover Open
0023
Refer Note 2

Tamper
Latest 10 Tamper Events-Magnetic
0024
Refer Note 1

Tamper

Load profile upto 45 days selectively

Load profile
Active Energy kWh
XX25
Refer Note 3

(XX shall denote the number of days for

which load survey is required.

Note 1:

28H 01, DD:MM:YY, HH;MM, DD:MM:YY, HH:MM 29H

28H 02, DD:MM:YY, HH;MM, DD:MM:YY, HH:MM 29H

28H 03, DD:MM:YY, HH;MM, DD:MM:YY, HH:MM 29H

28H 04, DD:MM:YY, HH;MM, DD:MM:YY, HH:MM 29H

28H 05, DD:MM:YY, HH;MM, DD:MM:YY, HH:MM 29H

28H 06, DD:MM:YY, HH;MM, DD:MM:YY, HH:MM 29H

28H 07, DD:MM:YY, HH;MM, DD:MM:YY, HH:MM 29H

28H 08, DD:MM:YY, HH;MM, DD:MM:YY, HH:MM 29H

28H 09, DD:MM:YY, HH;MM, DD:MM:YY, HH:MM 29H

28H 10, DD:MM:YY, HH;MM, DD:MM:YY, HH:MM 29H

Example: 28H 01, 08:09:10, 11:30, 09:09:10, 11:30 29H

Note 2:

28H DD:MM:YY, HH:MM 29H

Example: 29H 13:09:10, 12:30 29H

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011 Page 41 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

Note 3:

28H 01, DD:MM:YY,


XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,
XX.X,XX.X,XX.X,XX.X,
XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,
XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,
XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X 29H

28H 02, DD:MM:YY,


XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,
XX.X,XX.X,XX.X,XX.X,
XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,
XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,
XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X 29H

28H 45, DD:MM:YY,


XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,
XX.X,XX.X,XX.X,XX.X,
XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,
XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,
XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X,XX.X 29H

For Example: 28H 01,

13:09:10,02.5,02.4,0.12,01.2,01.5,02.3,03.5,02.7,02.6,02.9,01.7,01.2,01.5,01.9

,02.5,02.7,

02.3,02.1,02.8,01.9,01.1,01.7,01.4,01.7,01.8,03.1,03.6,01.4,01.9,01.8,02.1,02.
5,02.7,02.9,02.3,02.7,01.5,01.8, 01.1,02.1,02.2,02.5,02.9,03.1 29H

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 42 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY


METER WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

ANNEXURE V

Smart Energy Version 1.0 application layer protocol

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011 Page 43 of 80

ZigBee Smart Energy Profile Specification


161

Document 075356r15

D
D
T

1
2
3
4
5
6

2
0
7

2
2
8

2
9

2
2

10

2
2

11

2
2

12

3
3

13

3
3

14

3
3

15

3
3

16

3
3

17

4
4

18

4
4

19

4
4

Page 44 of 80

162
Annex D

Smart Energy Cluster Descriptions

C
advanced forms or data sets from
metering devices will be
supported in the Smart Energy
Tunneling Cluster, which will be
defined in sub-clause D.6.

I
C
C
=

The following figures identify


three configurations as
examples utilizing the Simple
Metering Cluster.

S
=

T
PCT

Copyright 2008 ZigBee Standards


Organization. All rights reserved.

1
4
1
1
1
1
1

2
2

2
2

2
2

2
2

2
2

3
3

3
3

3
3

10

3
3

11

3
4

12

4
4

13

4
4
4

Page 45 of 80

ZigBee Smart Energy Profile Specification


163

Document 075356r15

I
n
H
o
m
e

ESP PCT

End Point ID =

Metering Device

End Point ID =

D
i
s
p
l
a
y

C
= Client

S
= Server

Figure D.10 Standalone ESP Model with Battery


Powered Metering Device

In the example above shown in Figure D.10, the


metering device is running on battery power and its
duty cycle for providing information is unknown. Its
expected the ESP will act like mirrored image or a
mailbox (Client) for the metering device data, allowing
other Smart Energy devices to gain access to the
metering devices data (provided via an image of its
Simple Metering Cluster).

C
o
p
y
r
i
g

ht 2008 ZigBee Standards Organization. All rights


reserved.

1
5

1
6

1
7

1
8

1
9
4

2
0

2
1

2
2

2
3
9

10

11

2
4

2
5

12
2
6
13

14

2
7

28

3
8

29
3
9
30

31

32

33

4
0

4
1

4
2

34
4
3
35

36

37

Page 46 of 80

4
4

4
5

164
Annex D

Smart Energy Cluster Descriptions

C
ESP with Integrated

PCT

S
C

Electric Meter
E

M
S

C
C
=

S
=

I
C

1
2
3
4
5
6
7
8
9

1
1
1

13

2
2

14

2
2

15

2
2

16

3
3

17

3
3

18

3
3

19

3
3

20

3
3

21

4
4

22

4
4

23

4
4

Page 47 of 80

ZigBee Smart Energy Profile Specification


165

Document 075356r15

Other Smart Energy devices can access


EndPoint Y in the ESP to receive the latest
information just as it would to access information
in the ESPs integrated Electric meter (as in
Figure D.11, EndPoint X) and other Metering
devices (as in Figure D.9, EndPoint A).

D.3.2 Server
D.3.2.1 Dependencies
Subscribed reporting of Simple Metering
attributes.

D.3.2.2 Attributes
For convenience, the attributes defined in this
specification are arranged into sets of related
attributes; each set can contain up to 256 attributes.
Attribute identifiers are encoded such that the most
significant Octet specifies the attribute set and the
least significant Octet specifies the attribute within
the set. The currently defined attribute sets are listed
in the following Table D.10.

Table D.10 Simple Metering Attribute Sets

Attribute Set Identifier


Description

0
x
0
7
t
o

0x00
Reading Information Set

0x01
TOU Information Set

0
x
F
F
R
e
s
e
r
v
e
d
a

0x02
Meter Status

0x03

a
.

Formatting

C
C
B

0x04
ESP Historical Consumption

0x05
Load Profile Configuration

0x06
Supply Limit

9
7
4

D.3.2.2.1 Reading Information Set


8

The following set of attributes provides a remote


access to the reading of the Electric, Gas, or
Water metering device. A reading must support
at least one register which is the actual total
summation of the delivered quantity (kWh, m,
ft, ccf, US gl).

Please note: In the following attributes, the term


Delivered refers to the quantity of Energy, Gas, or
Water that was delivered to the customer from the
utility.

Copyright 2008 ZigBee Standards Organization. All rights


reserved.

1
0

1
1

1
2

1
3

1
4

1
5

1
6

1
7
3

1
8

1
9

2
0
7

21

22

23

24

3
5

3
6

3
7

25
3
8
26

27

28

29

3
9

4
0

4
1

30
4
2
31

32

33

34

Page 48 of 80

4
3

4
4

4
5

166
Annex D

Smart Energy Cluster Descriptions

R
A
t
/

Likewise, the term Received


refers to the quantity of Energy,
Gas, or Water that was received
by the utility from the customer.

Table D.11 Reading Information


Attribute Set

0
C
U
0
R
M
o
4
t
O

I
0

Defaul
Man.
Identifier
Name
Type

0
C
U
0
R
-

t
O

onReceived
48 bit
to

I
0

Only

Integer
0xFFFFFFFFFFFF

0
C
U
0
R
O
a
4
t
O

I
0

0x02
CurrentMaxDem
Unsigned
0x000000000000
Read

0
D
U
0
R
O

4
t
O

andDelivered
48 bit

I
0

0
P
S
R
0
O
b
O
0x05
Daily Freeze

Unsigned
0x0000 to 0x183C
Read
0x0000
O

Time

0
R
U

16 bit

R
O

Only

t
e
O

Integer
0
C
U
R
O
a

e
e
Only

me

0
R

0x09

CurrentMaxDem

UTCTim

Read
-

2
3

andReceivedTim

5
6

Only

7
8

2
10

2
2

11

2
3

12

3
3

13

3
3

14

3
3

15

3
3

16

3
4

17

4
4

18

4
4

19

20

21

22

23

24

25

Page 49 of 80

ZigBee Smart Energy Profile Specification


167

Document 075356r15

D
.
3
.

CurrentSummationDelivered is mandatory and


must be provided as part of the minimum data
set to be provided by the metering device.
CurrentSummationDelivered is updated
continuously as new measurements are made.

D.3.2.2.1.2 CurrentSummationReceived
Attribute

CurrentSummationReceived represents the most


recent summed value of Energy, Gas, or Water
generated and delivered from the premise. If
optionally provided, CurrentSummationReceived
is updated continuously as new measurements
are made.

D.3.2.2.1.3 CurrentMaxDemandDelivered
Attribute

CurrentMaxDemandDelivered represents the


maximum demand or rate of delivered value of
Energy, Gas, or Water being utilized at the
premise. If optionally provided,
CurrentMaxDemandDelivered is updated
continuously as new measurements are made.

2.2.1.4 CurrentMaxDemandReceived
Attribute

CurrentMaxDemandReceived represents the


maximum demand or rate of received value of
Energy, Gas, or Water being utilized by the utility.
If optionally provided,
CurrentMaxDemandReceived is updated
continuously as new measurements are made.

D.3.2.2.1.5 DFTSummation Attribute

DFTSummation represents a snapshot of


attribute CurrentSummationDelivered captured at
the time indicated by attribute DailyFreezeTime.
If optionally provided, DFTSummation is updated
once every 24 hours and captured at the time set
in sub-clause D.3.2.2.1.6.

D.3.2.2.1.6 DailyFreezeTime Attribute

DailyFreezeTime represents the time of day


when DFTSummation is captured.
DailyFreezeTime is an unsigned 16 bit value
representing the hour and minutes for DFT. The
byte usages are:

Bits 0 to 7: Range of 0 to 0x3C representing the


number of minutes past the top of the hour.

Bits 8 to 15: Range of 0 to 0x17 representing the


hour of the day (in 24 hour format).

C
o
p
y
r
i
g

ht 2008 ZigBee Standards Organization. All rights


reserved.

1
5

1
6

1
7

1
8

1
9
4

2
0

2
1

2
2

2
3
9

10

11

2
4

2
5

12
2
6
13

14

2
7

28

3
8

29
3
9
30

31

32

33

4
0

4
1

4
2

34
4
3
35

36

37

Page 50 of 80

4
4

4
5

168
Annex D

Smart Energy Cluster Descriptions

D.3.2.2.1.7 PowerFactor
Attribute

PowerFactor contains the


Average Power Factor ratio in
1/100s. Valid values are 0 to 99.

D.3.2.2.1.8
ReadingSnapShotTime
Attribute

The ReadingSnapShotTime
attribute represents the last time
all of the

CurrentSummationDelivered,
CurrentSummationReceived,
CurrentMaxDemandDelivered,
and
CurrentMaxDemandReceived
attributes that are supported by
the device were updated.

Time Attribute

The
CurrentMaxDemandDeliveredTim
e attribute represents the time
when

0
R
O
m
4
0

CurrentMaxDemandDelivered
reading was captured.
I

D.3.2.2.1.10
CurrentMaxDemandReceivedT
ime Attribute

The
CurrentMaxDemandReceivedTim
e attribute represents the time
when

CurrentMaxDemandReceived
reading was captured.

D.3.2.2.2 Summation TOU


Information Set

The following set of attributes


provides a remote access to the
Electric, Gas, or Water metering
devices Time of Use (TOU)
readings.

Table D.12 TOU Information


Attribute Set

0x00
CurrentTier1Sum
Unsigned

0
C
U
0
R
O
m
4
0

0
C
U
0
R
O
m
4
0

Integer

0
C
U
0
R
O
m
4
0

0x03
CurrentTier2Sum
Unsigned
0x000000000000 to
Read Only
O

mationReceived
48 bit

0xFFFFFFFFFFFF

2
3
4
5
6

2
8

2
2

2
2

10

2
3

11

3
3

12

3
3

13

3
3

14

3
3

15

3
4

16
4
4
17
4
4
18
4

19

20

21

22

23

Page 51 of 80

ZigBee Smart Energy Profile Specification


169

Document 075356r15

Table D.12 TOU Information Attribute Set


(Continued)

0x05
CurrentTier3Sum
Unsigned
0x000000000000 to
Read Only
O

mationReceived
48 bit
0xFFFFFFFFFFFF

Integer

0
x
0
6
C
u
r
r
e
n
t
T
i
e
r
4
S
u
m
U
n
s
i
g
n
e
d

0x000000000000 to
Read Only
O

mationDelivered
48 bit
0xFFFFFFFFFFFF

m
a
t
i
o
n
R
e
c
e
i
v
e
d
4
8
b
i
t

Integer

0
x
F
F
F
F
F
F
F
F
F
F
F
F

0x07
CurrentTier4Sum
Unsigned
0x000000000000 to
Read Only
O

I
n
t
e
g
e
r

0
x
0
9

0x08
CurrentTier5Sum
Unsigned
0x000000000000 to
Read Only
O

mationDelivered
48 bit
0xFFFFFFFFFFFF

Integer

C
u
r
r
e
n
t
T
i
e
r
5
S
u
m
U
n
s
i
g
n
e
d

0x000000000000 to
Read Only
O

mationReceived
48 bit
0xFFFFFFFFFFFF

m
a
t
i
o
n
D
e
l
i
v
e
r
e
d
4
8

Integer

b
i
t
0
x
F
F
F
F
F
F
F
F
F
F
F
F

0x0A
CurrentTier6Sum
Unsigned
0x000000000000 to
Read Only
O

I
n
t
e
g
e
r

0
x
0
C

0x0B
CurrentTier6Sum
Unsigned
0x000000000000 to

R
e
s
e
r
v
e
d

Read Only
O

mationReceived
48 bit

t
o

0xFFFFFFFFFFFF

Integer

0
x
F
F

A
t
t
r
i
b
u
t
e
s

D.3.2.2.2.1 CurrentTierNSummationDelivered
Attributes

Attributes

CurrentTier1SummationDelivered

through

CurrentTier5SummationDelivered represent the


most recent summed value of Energy, Gas, or
Water delivered to the premise (i.e delivered to
the customer from the utility) at a specific price
tier as defined by a TOU schedule or a real time
pricing period. If optionally provided, attributes

CurrentTier1SummationDelivered through
CurrentTier5SummationDelivered are updated
continuously as new measurements are made.

D.3.2.2.2.2 CurrentTierNSummationReceived
Attributes

CurrentTier1SummationReceived

through

CurrentTier5SummationReceived represent the most


recent summed value of Energy, Gas, or Water
provided by the premise (i.e received by the utility from
the customer) at a specific price tier as defined by a
TOU schedule or a real time pricing period. If optionally
provided, attributes CurrentTier1SummationReceived

1
0

1
1

1
2

Copyright 2008 ZigBee Standards Organization. All rights


reserved.

1
3

1
4

1
5

1
6

1
7
3

1
8

1
9

2
0
7

2
1

22

3
5

23
3
6
24

25

26

27

3
7

3
8

3
9

28
4
0
29

30

31

32

4
1

4
2

4
3

33
4
4
34
4
5

Page 52 of 80

170
Annex D

Smart Energy Cluster Descriptions

through
CurrentTier5SummationReceive
d are updated continuously as
new measurements are made.

D.3.2.2.3 Meter Status


Attribute

The Meter Status Attribute Set is


defined in Table D.13.

Table D.13 Meter Status Attribute


Set

M
I
N
T
R
A
D
/

0
S
8
0
R
0
M

0
R

D.3.2.2.3.1 Status Attribute

The Status attribute provides


indicators reflecting the current error
conditions found by the metering
device. This attribute is an 8 bit field
where when an individual bit is set,
an error or warning condition exists.
The behavior causing the setting or
resetting each bit is device specific.
In other words, the application within
the metering device will determine
and control when these settings are
either set or cleared. Table D.14 lists
the mapping of the bit is as follows:

Table D.14 Mapping of the Status


Attribute

R
S
L
P
P
T
L
C
D
D
Q
F
D
B
M
O

T
S

Bit 7
Bit 6
Bit 5
Bit 4
Bit 3

L
P
P
T
C

Bit 2
Bit 1
Bit 0

1
2

1
7
3

1
1
4

2
5

2
2

2
2

2
2

2
2

2
3

10

3
3

11

3
3

12

3
3

13

3
3

14

3
4

15

4
4

16

4
4
4

Page 53 of 80

ZigBee Smart Energy Profile Specification


171

Document 075356r15

Low Battery: Set to true when the battery needs


maintenance.

Check Meter: Set to true when a non fatal


problem has been detected on the meter such as
a measurement error, memory error, self check
error.

D.3.2.2.4 Formatting

The following set of attributes provides the ratios and


formatting hints required to transform the received
summations, consumptions or demands/rates into
displayable values. If the Multiplier and Divisor
attribute values are non-zero, they are used in
conjunction with the SummationFormatting,

ConsumptionFormatting, and DemandFormatting


attributes. Equations required to accomplish this
task are defined below:

C
o
n
s
u
m
p
t
i
o
n
F
o
r
m
a
t
t
i
n
g
)

D
e
m
a
n
d

Summation = Summation received * Multiplier /


Divisor (formatted using SummationFormatting)

Consumption = Summation received * Multiplier /


Divisor (formatted using

D
e
m

and received * Multiplier / Divisor (formatted


using DemandFormatting)

If the Multiplier and Divisor attribute values are


zero, just the formatting hints defined in
SummationFormatting, ConsumptionFormatting,
and
DemandFormatting attributes are used.

The following set of attributes provides the ratios and


formatting hints required to transform the received
summations, consumptions or demands/rates into
displayable values. If the Multiplier and Divisor
attribute values are non-zero, they are used in
conjunction with the SummationFormatting,

ConsumptionFormatting, and DemandFormatting


attributes.

Equations required to accomplish this task are


defined below:

text = summation received * Multiplier / Divisor


(formatted using SummationFormatting Attribute)

text = consumption received * Multiplier / Divisor


(formatted using HistoricalConsumptionFormatting
Attribute)

text = demand received * Multiplier / Divisor


(formatted using SummationFormatting Attribute)

The summation received, consumption received


and demand received variables used above can
be replaced by any of the attributes listed in subclauses D.3.2.2.4.4, D.3.2.2.4.5 and D.3.2.2.4.6.

I
f
t
h
e
M
u
l
t
i
p
l
i
e
r
a
n
d
D
i
v
i
s
o
r
a
t
t
r
i
b
u
t
e
v
a
l
u
e
s
a

re zero, just the formatting hints defined in


SummationFormatting,
HistoricalConsumptionFormatting, and

1
2

DemandFormatting attributes are used.


1
3

Copyright 2008 ZigBee Standards Organization. All rights


reserved.

1
4

1
5

1
6
1

1
7

1
8

1
9

2
0
6

2
1

2
2

2
3
10

11

2
4

25

3
7

26
3
8
27

28

29

30

3
9

4
0

4
1

31
4
2
32

33

34

35

36

Page 54 of 80

4
3

4
4

4
5

172
Annex D

Smart Energy Cluster Descriptions

U
k
C
k

Following table shows examples


which demonstrate the relation
between these attributes.

Table D.15

Attribute
Example 1
Example 2

M
1
2
6

D
1
1
1

Example 3
N
5
4
5
D

Value as transmitted and received


52003
617
23629

N
0
2
3
D

Suppress leading zeros

M
I
N
T
R
A
D
O

False
False
True
0
U
8
0
R
0
M
Displayed value
00052
0012.34

E
0
O

14.177

The Consumption Formatting


Attribute Set is defined in Table
D.16.

Table D.16 Formatting Attribute Set

0
M
U
0
R
O
b
t
O

0
S
8
0
R
M
0x02

Divisor

0
O

Unsigned 24
0x000000
Read
O

bit Integer

0
D
8
0
R
O

to
Only

0
O

0xFFFFFF

1
2
3

1
8
1
2

2
2

2
2

2
2

2
2

10

2
3

11

3
3

12

3
3

13

3
3

14

3
3

15

3
4

16

4
4

17

4
4
4

Page 55 of 80

ZigBee Smart Energy Profile Specification


173

Document 075356r15

Table D.16 Formatting Attribute Set (Continued)

Man./
Identifier
Name
Type
Range
Access
Default
Opt.

0
x
0
5
H
i
s
t
o
r
i
c
a
l
C
o
n
s
u
m
p
t
i
8
b
i
t
B
i
t
M
a
p

0x00 to
Read
O

onFormatting

0xFF
Only

0
x
0
7
t
o
R
e
s
e
r
v
e
d

0x06
MeteringDeviceType
8 bit BitMap
0x00 to
Read
M

0xFF
Only

0
x
F
F

0
x
0
1

m
3

D.3.2.2.4.1 UnitofMeasure Attribute

UnitofMeasure provides a label for the Energy, Gas, or


Water being measured by the metering device. The unit
of measure apply to all summations, consumptions/
profile interval and demand/rate supported by this
cluster. Other measurements such as the power factor
are self describing. This Attribute is an 8 bit enumerated
field. The bit descriptions for this Attribute are listed in
Table D.17.

Table D.17 UnitofMeasure Attribute Enumerations

Values

Description

0x00

kW (kilo-Watts) & kWh (kilo-WattHours) in pure Binary format.

(
C
u
b

ic Meter) & m /h (Cubic Meter per Hour) in pure Binary


format.
B
i
n
a
r
y

0x02

ft (Cubic Feet) & ft /h (Cubic Feet per Hour) in pure Binary


format.

f
o
r
m
a
t
.

0x03

ccf ((100 or Centum) Cubic Feet) & ccf/h ((100 or Centum) Cubic
Feet per

Hour) in pure Binary format.

0x04

US gl (US Gallons) & US gl/h (US Gallons per Hour) in pure


Binary format.

0x05

IMP gl (Imperial Gallons) & IMP gl/h (Imperial Gallons per


Hour) in pure

0
x
0
6

BTUs & BTU/h in pure Binary format.

0x07

Liters & l/h (Liters per Hour) in pure Binary format

0x08

kPA(gauge) in pure Binary format.

0x09

kPA(absolute) in pure Binary format.

0x0A to 0x7F

Reserved for future use.

0x80

kW (kilo-Watts) & kWh (kilo-WattHours) in BCD format

0
x
8
1

m (Cubic Meter) & m /h (Cubic Meter per Hour) in BCD


format

1
0

0x82

ft (Cubic Feet) & ft /h (Cubic Feet per Hour) in BCD format

1
1

1
2

1
3

Copyright 2008 ZigBee Standards Organization. All rights


reserved.
1
4

1
5

1
6

1
7

1
8
4

1
9

2
0

21

22

23

24

3
5

3
6

3
7

25
3
8
26

27

28

29

3
9

4
0

4
1

30
4
2
31

32

33

34

Page 56 of 80

4
3

4
4

4
5

174
Annex D

Smart Energy Cluster Descriptions

0
I
f

Table D.17 UnitofMeasure Attribute


Enumerations (Continued)

0
B
0
L

Values

0
k

Description
0
k

0x83

0
R

ccf ((100 or Centum) Cubic Feet) & ccf/h


((100 or Centum) Cubic Feet per

P
Hour) in BCD format

D
M

D
0x84

US gl (US Gallons) & US gl/h (US


Gallons per Hour) in BCD format

D
S
C

1
5
1
1
1
1

1
2

2
2
3

2
4

2
2

2
2

2
2

3
3

3
3

3
3

10

3
3

11

3
3

12

4
4

13

4
4

14

4
4

Page 57 of 80

ZigBee Smart Energy Profile Specification


175

Document 075356r15

Bits 0 to 2: Number of Digits to the right of the


Decimal Point. Bits 3 to 6: Number of Digits to
the left of the Decimal Point. Bit 7: If set,
suppress leading zeros.

This attribute shall be used against the following


attributes:

CurrentSummationDelivered

CurrentSummationReceived

CurrentTier1SummationDelivered

CurrentTier1SummationReceived

CurrentTier2SummationDelivered

CurrentTier2SummationReceived

CurrentTier3SummationDelivered

CurrentTier3SummationReceived

C
u
r
r
e
n
t
T
i
e
r
4
S
u
m
m
a
t
i
o
n
D
e
l
i
v
e
r
e
d

CurrentTier4SummationReceived

CurrentTier5SummationDelivered

CurrentTier5SummationReceived

DFTSummation

D.3.2.2.4.5 DemandFormatting Attribute

I
n
s
t
a
n
t
a
n
e
o
u
s
D
e
m
a
n
d

DemandFormatting provides a method to properly


decipher the number of digits and the decimal
location of the values found in the Demand
related attributes. This attribute is to be decoded
as follows:

Bits 0 to 2: Number of Digits to the right of the


Decimal Point.

Bits 3 to 6: Number of Digits to the left of the


Decimal Point.

Bit 7: If set, suppress leading zeros.

This attribute shall be used against the following


attributes:

CurrentMaxDemandDelivered

CurrentMaxDemandReceived

C
o
p
y
r
i
g

ht 2008 ZigBee Standards Organization. All rights


reserved.

1
5

1
6

1
7

1
8

1
9
4

2
0

2
1

2
2

2
3
9

10

11

2
4

2
5

12
2
6
13

14

2
7

28

3
8

29
3
9
30

31

32

33

4
0

4
1

4
2

34
4
3
35

36

37

Page 58 of 80

4
4

4
5

176
Annex D

Smart Energy Cluster Descriptions

D.3.2.2.4.6
HistoricalConsumptionFormat
ting Attribute

HistoricalConsumptionFormatting
provides a method to properly
decipher the number of digits
and the decimal location of the
values found in the ESP
Historical Consumption Set of
attributes. This attribute is to be
decoded as follows:

Bits 0 to 2: Number of Digits to


the right of the Decimal Point.

Bits 3 to 6: Number of Digits to


the left of the Decimal Point.

Bit 7: If set, suppress leading


zeros.

CurrentDayConsumptionDelivered

0
E

CurrentDayConsumptionReceived

1
G

PreviousDayConsumptionDelivered

2
W

PreviousDayConsumptionReceived

3
T

CurrentPartialProfileIntervalValue

4
P

Intervals

5
H
6
C

D.3.2.2.4.7
MeteringDeviceType Attribute

MeteringDeviceType provides a
label for identifying the type of
metering device present. The
attribute are enumerated values
representing Energy, Gas,
Water, Thermal, Heat, Cooling,
and mirrored metering devices.
The defined values are
represented in Table D.18.

1
2
3
4
5
6

Table D.18 MeteringDeviceType


Attribute Enumerations

7
8

Values

11
2
12

2
2

13

2
2

14

2
2

15

3
3

16

3
3

17

3
3

18

3
3

19

3
3

20

4
4

21

4
4

22

4
4

Page 59 of 80

ZigBee Smart Energy Profile Specification


177

Document 075356r15

1
3
2

Table D.18 MeteringDeviceType Attribute


Enumerations (Continued)

Values

M
i
r
r
o
r
e
d

Description
H
e
a
t
128
Mirrored Gas Metering

129
Mirrored Water Metering

130
Mirrored Thermal Metering

131
Mirrored Pressure Metering

M
e
t
e
r
i
n
g
e

1
3
3

Mirrored Cooling Metering

134 to 255
Reserved for future growth

CCB 986

CCB 986

CCB 986

CCB 986

CCB 986

CCB 986

Note: Heat and cooling meters are used for


measurement and billing of heat (and cooling)
delivered through liquid (water) based central
heating systems. The consumers are typically
billed by the kWh, calculated from the flow and
the temperatures in and out.

19

D.3.2.2.5 ESP Historical Consumption

The ESP Historical Attribute Set is defined in


Table D.19.

1
9
.
C
C
B
9
8
6

C
o
p
y

right 2008 ZigBee Standards Organization. All rights


reserved.

1
5

1
6

1
7

1
8

1
9
4

2
0

2
1

2
2

2
3
9

10

11

2
4

2
5

12
2
6
13

14

2
7

28

3
8

29
3
9
30

31

32

33

4
0

4
1

4
2

34
4
3
35

36

37

Page 60 of 80

4
4

4
5

178
Annex D

Smart Energy Cluster Descriptions

Table D.19 ESP Historical Attribute


Set

0
I
S
0
R
0
O
b
t
O

Man./
Identifier
Name
Type
Range
Access
Default
Opt.

0
C
U
0
R
O
o
2

to
Only
I
0

Integer
0xFFFFFF

0
P
U
0
R
O
i
2
t
O

I
0

0x02
CurrentDayConsumpti
Unsigned
0x000000
Read
O

onReceived
24 bit

0
P
U
0
R
O
i
2
t
O

to
Only

I
0

0
C
U
0
R
O
t
0x05
CurrentPartialProfileIn

t
O

UTCTime
e
Read

tervalStartTimeDeliver

Only

ed

0
C
U
0
R
t
2
t
O

I
0

0
C
U
0
R
-

tervalValueReceived
24 bit
to
Only

C
C
C
C

Integer
0xFFFFFF

D
I
C

1
2
3
4
5
6

0x09 to

Reserved

8
9

1
1
1
1

0xFF

1
1
1

3
3
17
3
3
18
3
3
19
3

20

3
4

21

4
4

22

4
4

23

24

25

26

27

28

29

30

31

32

Page 61 of 80

ZigBee Smart Energy Profile Specification


179

Document 075356r15

the premise where negative values indicate demand


received from the premise. InstantaneousDemand is
updated continuously as new measurements are
made. The frequency of updates to this field is
specific to the metering device, but should be within
the range of once every second to once every 5
seconds.

D.3.2.2.5.2 CurrentDayConsumptionDelivered
Attribute

CurrentDayConsumptionDelivered represents the


summed value of Energy, Gas, or Water generated
and delivered to the premise since midnight local
time. If optionally provided,
CurrentDayConsumptionDelivered is updated
continuously as new measurements are made.

D.3.2.2.5.3 CurrentDayConsumptionReceived
Attribute

CurrentDayConsumptionReceived represents the


summed value of Energy, Gas, or Water generated
and received from the premise since midnight local
time. If optionally provided,
CurrentDayConsumptionReceived is updated
continuously as new measurements are made.

D
.
3
.
2
.
2
.
5
.
4

PreviousDayConsumptionDelivered
Attribute

PreviousDayConsumptionDelivered represents the


summed value of Energy, Gas, or Water generated
and delivered to the premise within the previous 24
hour period starting at midnight local time. If
optionally provided,
CurrentDayConsumptionDelivered is updated
every midnight local time.

r
e
c
e
i
v
e
d
.

D.3.2.2.5.5
PreviousDayConsumptionReceived Attribute

PreviousDayConsumptionReceived represents
the summed value of Energy, Gas, or Water
generated and received from the premise within
the previous 24 hour period starting at midnight
local time. If optionally provided,
CurrentDayConsumptionReceived is updated is
updated every midnight local time.

D.3.2.2.5.6
CurrentPartialProfileIntervalStartTimeDelivere
d Attribute

CurrentPartialProfileIntervalStartTimeDelivered
represents the start time of the current Load Profile
interval being accumulated for commodity
delivered.

D.3.2.2.5.7
CurrentPartialProfileIntervalStartTimeReceive
d Attribute

CurrentPartialProfileIntervalStartTimeReceived
represents the start time of the current Load Profile
interval being accumulated for commodity

C
o
p
y
r
i
g

ht 2008 ZigBee Standards Organization. All rights


reserved.

1
5

1
6

1
7

1
8

1
9
4

2
0

2
1

2
2

2
3
9

10

11

2
4

2
5

12
2
6
13

14

2
7

28

3
8

29
3
9
30

31

32

33

4
0

4
1

4
2

34
4
3
35

36

37

Page 62 of 80

4
4

4
5

180
Annex D

Smart Energy Cluster Descriptions

D.3.2.2.5.8
CurrentPartialProfileIntervalVa
lueDelivered Attribute

CurrentPartialProfileIntervalValu
eDelivered represents the value
of the current Load Profile
interval being accumulated for
commodity delivered.

D.3.2.2.5.9
CurrentPartialProfileIntervalVa
lueReceived Attribute

CurrentPartialProfileIntervalValu
eReceived represents the value
of the current Load Profile
interval being accumulated for
commodity received.

D.3.2.2.6 Load Profile


Configuration

D.20.

0
O

Table D.20 Load Profile


Configuration Attribute Set

e
b
0
O

0
R

Man./

Identifier
Name
Type
Range
Access
Default
Opt.

D
M
D
T

2
C
0x00
MaxNumberOfPeriodsD
Unsigned 8
0x00 to
Read

1
2
3

2
0
4

2
2
5

2
6

2
2

2
2

2
2

3
3

10

3
3

11

3
3

12

3
3

13

3
3

14

4
4

15

4
4

16

4
4

17

18

19

Page 63 of 80

ZigBee Smart Energy Profile Specification


181

Document 075356r15

Table D.21 Supply Limit Attribute Set

0
x
0
0
C
u
r
r
e
n
t
D
e
m
a
n
d

Man /
Identifier
Name
Type
Range
Access
Default
Opt

U
n
s
i
g
n
e
d
2
4

0x000000 to
Read

Delivered
bit Integer
0xFFFFFF
only

0
x
0
2
D
e
m
a
n
d
I
n
t
e
g
r
a
t

0x01
DemandLimit
Unsigned 24
0x000000 to
Read

U
n
s
i
g
n
e
d
8

bit Integer
0xFFFFFF
only

0
x
0
1
t
o
R
e
a
d

ion Period
bit Integer
0xFF
only

0
x
0
4
0x03
NumberOfDem
Unsigned 8
0x01 to
Read
O

and
bit Integer
0xFF
only

Subintervals

0
x
F
F
R
e
s
e
r
v
e
d

D.3.2.2.7.1 CurrentDemandDelivered

CurrentDemandDelivered represents the current


Demand of Energy, Gas, or Water delivered at the
premise. CurrentDemandDelivered may be
continuously updated as new measurements are
acquired, but at a minimum
CurrentDemandDelivered must be updated at the
end of each integration sub-period, which can be
obtained by dividing the DemandIntegrationPeriod by
the

NumberOfDemandSubintervals.

This attribute shall be adjusted using the


Multiplier and Divisor attributes found in the
Formatting Attribute Set and can be formatted
using the DemandFormatting attribute. The final
result represents an engineering value in the unit
defined by the UnitofMeasure attribute.

D.3.2.2.7.2 DemandLimit

DemandLimit reflects the current supply demand


limit set in the meter. This value can be
compared to the CurrentDemandDelivered
attribute to understand if limits are being
approached or exceeded.

Adjustment and formatting of this attribute follow


the same rules as the
CurrentDemandDelivered.

D
.
3
.
2
.
2
.
7
.
3
D
e
m
a
n
d
I
n
t
e
g
r
a
t
i
o
n
P
e
r
i
o
d

D
e
m
a
n
d
I

ntegrationPeriod is the number of minutes over


which the CurrentDemandDelivered attribute is
calculated. Valid range is 0x01 to 0xFF. 0x00 is a
reserved value.

1
2

1
3

Copyright 2008 ZigBee Standards Organization. All rights


reserved.

1
4

1
5

1
6
1

1
7

1
8

1
9
5

2
0

2
1

2
2
9

10

11

2
3

2
4

25

3
7

26
3
8
27

28

29

30

3
9

4
0

4
1

31
4
2
32

33

34

35

36

Page 64 of 80

4
3

4
4

4
5

182
Annex D

Smart Energy Cluster Descriptions

D.3.2.2.7.4
NumberOfDemandSubinterval
s

NumberOfDemandSubintervals
represents the number of
subintervals used within the
DemandIntegrationPeriod. The
subinterval duration (in minutes) is
obtained by dividing the
DemandIntegrationPeriod by the
NumberOfDemandSubintervals. The
CurrentDemandDelivered attribute is
updated at the each of each
subinterval. Valid range is 0x01 to
0xFF. 0x00 is a reserved value.

As a Rolling Demand example,


DemandIntegrationPeriod could
be set at 30 (for 30 minute
period) and
NumberOfDemandSubintervals
could be set for 6. This would
provide 5 minute (30/6 = 5)
subinterval periods.

be set at 30 (for 30 minute


period) and
NumberOfDemandSubintervals
could be set for 1. This would
provide a single 30 minute
subinterval period

0
R
O

21

D.3.2.3 Server
Commands

0
R
O

0
R

D.3.2.3.1 Commands
Generated

The command IDs generated by


the Simple Metering server
cluster are listed in Table D.22.

D
D
T
2

Table D.22 Generated Command


IDs for the Simple Metering Server

Command Identifier

1
2

Mandatory /
Field Value
Description
Optional

3
4
5
6
7
8
9

0x00
Get Profile Response
O

1
1
1
1

14
3
15

3
3

16

3
3

17

3
3

18

3
3

19

4
4

20

4
4

21

4
4

22

23

24

25

26

27

28

29

30

Page 65 of 80

ZigBee Smart Energy Profile Specification


183

Document 075356r15

S
e
r
i
e
s
o
f

Octets
4
1
1
1
Variable

D
a
t
a
T
i
m
e
E
n
u
m
e
r
a
t
i
o
n

UTC
8-bit
8-bit
Unsigned 8-bit

E
n
u
m
e
r
a
t
i
o
n

Integer
Unsigned

l
i
v
e
r
e
d

24 bit

Type

Integers

Field
EndTime
Status
ProfileIntervalPeriod
NumberOfPeriodsDe
Intervals

Name

Figure D.12 Get Profile Response Command Payload

D.3.2.3.1.1.1.1 Payload Details

EndTime: 32 bit value (in UTC) representing the


end time of the most chronologically recent
interval being requested. Example: Data collected
from 2:00 PM to 3:00 PM would be specified as a
3:00 PM interval (end time). It is important to note
that the current interval accumulating is not
included in most recent block but can be retrieved
using the CurrentPartialProfileIntervalValue
attribute.

Status: Table D.23 lists the valid values returned


in the Status field.

Table D.23 Status Field Values

0
x
0
2
I
n
t
e
r
v
a
l
C
h
a
n
n
e
l
n
o
t
s
u
p
p
o
r
t
e
d

Value
Description

0x00
Success

0x01
Undefined Interval Channel requested

0
x
0
3

Invalid End Time

0x04
More periods requested than can be returned

0x05
No intervals available for the requested time

0x06 to 0xFF

Reserved for future use.


7

ProfileIntervalPeriod: Represents the interval or


time frame used to capture metered Energy, Gas,
and Water consumption for profiling purposes.
ProfileIntervalPeriod is an enumerated field
representing the following timeframes listed in
Table D.24:

1
0

1
1

1
2

1
3

Copyright 2008 ZigBee Standards Organization. All rights


reserved.
1
4

15

16

17

18

3
2

3
3

3
4

19
3
5
20

21

22

23

3
6

3
7

3
8

24
3
9
25

26

27

28

4
0

4
1

4
2

29
4
3
30

31

4
4

4
5

Page 66 of 80

184
Annex D

Smart Energy Cluster Descriptions

3
1
4
1

Table D.24 ProfileIntervalPeriod


Timeframes

5
7
6
5

Enumerated Value
Timeframe

7
2
8
R

0
Daily

I
1
60 minutes

D
T
D
T

D
2
30 minutes

1
1
1
1

Copyright 2008 ZigBee Standards


Organization. All rights reserved.

1
1
1
1
2
2
2

2
2

2
2

2
2

2
3

3
3

3
3

3
3

3
3

10

4
4

11

4
4

44

Page 67 of 80

ZigBee Smart Energy Profile Specification


185

Document 075356r15

D.3.2.3.1.2.2 Effect on Receipt

On receipt of this command, the Server shall


send a RequstMirrorReponse command (see
sub-clause D.3.2.4.3).

D.3.2.3.1.3 Remove Mirror Command

This command is used to request the ESP to


remove its mirror of Metering Device data.

D.3.2.3.1.3.1 Payload Details

There are no fields for this command.

D.3.2.3.1.3.2 Effect on Receipt

On receipt of this command, the Server shall


send a MirrorRemoved command (see subclause D.3.2.4.4).

D.3.2.4 Client Commands

D
.
3
.
2
.
4
.
1
C
o
m
m
a
n
d
s
G
e
n
e
r
a
t
e
d

T
h
e
c
o

mmand IDs generated by the Simple Metering


client cluster are listed in Table D.25.

R
e
m
o
v
e

Table D.25 Generated Command IDs for the Simple


Metering Client

M
i
r
r
o
r

Command Identifier

Mandatory /
Field Value
Description
Optional

0
x
0
3

0x00
Get Profile
O

0x01
Request Mirror
O

Response

0x02

0
x
f
f
R
e
s
e
r
v
e
d

D.3.2.4.2 Get Profile Command

The Get Profile command payload shall be formatted


as illustrated in Table D.26.

1
0

1
1

1
2

Copyright 2008 ZigBee Standards Organization. All rights


reserved.

1
3

1
4

1
5

1
6

1
7
3

1
8

1
9

2
0

2
1

3
5
22

23

24

3
6

3
7

25
3
8
26

27

28

29

3
9

4
0

4
1

30
4
2
31

32

33

34

Page 68 of 80

4
3

4
4

4
5

186
Annex D

Smart Energy Cluster Descriptions

D
U
U
U
I

Table D.26

GetProfile Payload
F

I
E
N
C

Octets
1
4
1

D
I
T

B
D

e
0
Consumption Delivered

D
T
C

1
Consumption Received
1
2

2 to 255

Not used

4
5
6
7
8

EndTime: 32 bit value (in UTCTime)


used to select an Intervals block from
all the Intervals blocks available. The
Intervals block returned is the most
recent block with its EndTime equal
or older to the one provided. The
most recent Intervals block is
requested using an End Time set to
0x00000000, subsequent Intervals
block are requested using an End
time set to the EndTime of the
previous block - (number of intervals
of the previous block *
ProfileIntervalPeriod).

1
1
1
1
1
1
1
1
1
1

NumberofPeriods: Represents
the number of intervals being
requested. This value cant
exceed the size stipulated in the
MaxNumberOfPeriodsDelivered
attribute. If more intervals are
requested than can be delivered,
the GetProfileResponse will
return the number of intervals

2
2
2
2
2
2
2

4
3
27
4
4
28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

Page 69 of 80

ZigBee Smart Energy Profile Specification


187

Document 075356r15

T
h
e

store previously gathered data and only request


the most current data. When initially gathering
significant amounts of historical interval data, the
GetProfile command should not be issued any
more frequently than 7.5 seconds to prevent
overwhelming the ZigBee network.

D.3.2.4.2.3 Command Processing Response

If success or failure occurs in recognizing or


processing the payload of the GetProfile
command, the appropriate enumerated ZCL
status (as referenced in the ZCL Cluster Library
specification) will be returned.

D.3.2.4.2.4 Effect on Receipt

On receipt of this command, the device shall


send a GetProfileReponse command (see subclause D.3.2.3.1.1).

D.3.2.4.3 Request Mirror Response Command

R
e
q
u
e
s
t
M
i
r
r
o
r
R
e
s
p
o
n
s
e
C
o
m
m
a
n
d
a

llows the ESP to inform a sleepy Metering Device


it has the ability to store and mirror its data.

D.3.2.4.3.1 Payload Format

The Request Mirror Response command


payload shall be formatted as illustrated in Figure
D.13

Octets
2

Data Type
Unsigned 16-

bit Integer

Field Name
EndPoint ID

F
i
g
u
r
e
D
.
1
3

R
e
q
u
e
s
t
M
i
r
r
o
r
R
e
s
p
o
n
s
e
C
o
m
m
a
n
d
P
a
y
l
o
a
d

D.3.2.4.3.1.1 Payload Details


6

EndPoint ID: 16 Bit Unsigned Integer indicating the


End Point ID to contain the Metering Devices meter
data. Valid End Point ID values are 0x0001 to
0x00F0. If the ESP is unable to mirror the Metering
Device data, EndPoint ID shall be returned as
0xFFFF. All other EndPoint ID values are reserved. If
valid, the Metering device shall use the EndPoint ID
to forward its metered data.

D.3.2.4.4 Mirror Removed Command

The Mirror Removed Command allows the ESP


to inform a sleepy Metering Device mirroring
support has been removed or halted.

1
0

1
1

1
2

Copyright 2008 ZigBee Standards Organization. All rights


reserved.

1
3

1
4

1
5

1
6

1
7
3

1
8

19

3
4

20
3
5
21

22

23

24

3
6

3
7

3
8

25
3
9
26

27

28

29

4
0

4
1

4
2

30
4
3
31

32

33

Page 70 of 80

4
4

4
5

188
Annex D

Smart Energy Cluster Descriptions

D.3.2.4.4.1 Payload Format

The Mirror Removed command


payload shall be formatted as
illustrated in Figure D.14

D
R
Octets

D
A

D
C

D
T
Data Type
Unsigned 16-

bit Integer

1
2
3

1
8
1
2

2
2

2
2

2
2

2
2

10

2
3

11

3
3

12

3
3

13

3
3

14

3
3

15

3
4

16

4
4

17

4
4
4

Page 71 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

SCHEDULE A

GUARANTEED TECHNICAL PARAMETERS

LT AC SINGLE PHASE 5 30 AMPS. STATIC ENERGY METER

ITEM
WITH INTERNAL LPRF (2.4 2.4835 GHz) AS COMMUNICATION

NAME
CAPABILITY with OPEN ZIGBEE 2007 PROTOCOL FOR

INTEROPERABILITY.

SR.
GUARANTTED TECHNICAL PARAMETERS
GTP

NO.

VALUES

1.0

MAKE & TYPE


TEXT

2.0
APPLICABLE STANDARD
TEXT

3.0
ACCURACY CLASS 1.00 (YES/NO)
BOOLEAN

4.0

METER BEARS ISI MARK (YES/NO)


BOOLEAN

5.0
RATED VOLTAGE 240 V (YES/NO)
BOOLEAN

6.0
VOLTAGE RANGE (-) 40% TO (+) 20% OF RATED
BOOLEAN

VOLTAGE (YES/NO)

7.0
FREQUENCY 50 HZ +/- 5% (YES/NO)
BOOLEAN

8.0
RATED BASIC CURRENT 5 AMPS (YES/NO)
BOOLEAN

9.0
MAXIMUM CONTINUOUS CURRENT IMAX 30 AMP
BOOLEAN

(YES/NO)

10.0
STARTING CURRENT 0.2 % OF IB. (YES/NO)
BOOLEAN

11.0
POWER CONSUMPTION IN VOLTAGE CIRCUIT 2 W &
BOOLEAN

10 VA (YES/NO)

12.0
POWER CONSUMPTION IN CURRENT CIRCUIT 4 VA
BOOLEAN

(YES/NO)

13.0
POWER FACTOR ZERO TO UNITY (ALL LAG OR LEAD)
BOOLEAN

(YES/NO)

14.0
STANDARD REFERENCE TEMPERATURE FOR
BOOLEAN

PERFORMANCE IS 27 C (YES/NO)

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011 Page 72 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

15.0
MEAN TEMPERATURE CO-EFFICIENT DOES NOT
BOOLEAN

EXCEED 0.07% (YES/NO)

16.0
TEMPERATURE RISE IS AS PER IS 13779 / 1999
BOOLEAN

(AMENDED UP TO DATE) (YES/NO)

METER BASE & COVER MADE OF UNBREAKABLE,

17.0
TOUGH, HIGH GRADE, FIRE RESISTANT
BOOLEAN

TRANSPARENT
POLYCARBONATE
MATERIAL

(YES/NO)

18.0
METER BODY TYPE TESTED FOR IP 51 DEGREE OF
BOOLEAN

PROTECTION AS PER IS 12063 (YES/NO)

19.0
FURNISH PHYSICAL WATER ABSORPTION VALUE
TEXT

20.0
FURNISH THERMAL HDDT VALUE

TEXT

21.0
FLAMMABILITY V2 (YES/NO)

BOOLEAN

22.0
FURNISH FLAMMABILITY VALUE

TEXT

23.0
GLOW WIRE TEST AT 650 C

TEXT

24.0
TENSILE STRENGTH

TEXT

25.0
FLEXURE STRENGTH

TEXT

26.0
MODULUS OF ELASTICITY

TEXT

27.0
IZOD IMPACT STRENGTH NOTCHED 23 C

TEXT

28.0
FURNISH PHYSICAL WATER ABSORPTION VALUE
TEXT

29.0
MOULDED TERMINAL BLOCK CONFORMS TO IS:
BOOLEAN

13779 / 1999 (AMENDED UP TO DATE) (YES/NO)

EXTENDED TRANSPARENT TERMINAL COVER AS PER

30.0
CLAUSE NUMBER 6.5.2 OF IS: 13779 / 1999
BOOLEAN

(AMENDED UP TO DATE) IS PROVIDED (YES/NO)

31.0
TRANSPARENT TERMINAL COVER IS SEALABLE
BOOLEAN

INDEPENDENTLY (YES/NO)

32.0
PROPER SIZES OF GROOVES ARE PROVIDED AT
BOOLEAN

BOTTOM OF TERMINAL COVER (YES/NO)

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011 Page 73 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

33.0
METER BASE & COVER ARE ULTRA-SONICALLY
BOOLEAN

WELDED (CONTINUOUS WELDING) (YES/NO)

34.0
THICKNESS OF MATERIAL FOR METER 2 MM
BOOLEAN

MINIMUM (YES/NO)

35.0
NON - RECHARGEABLE RTC PRE-PROGRAMMED FOR
BOOLEAN

30 YEARS DAY / DATE (YES/NO)

36.0
TIME ACCURACY OF RTC AS PER CBIP TECH REPORT
BOOLEAN

88 (YES/NO)

37.0
PROVISION TO PUT AT LEAST TWO SEALS BY UTILITY
BOOLEAN

USER (YES/NO)

SEPARATE PUSH BUTTONS PROVIDED FOR HIGH

38.0
RESOLUTION READING AND SCROLLING THE
BOOLEAN

PARAMETERS IN ALTERNATE DISPLAY (ON DEMAND)

MODE (YES/NO)

39.0
OPERATION INDICATOR PROVIDED IN THE FORM OF
BOOLEAN

BLINKING LED / LCD (YES/NO)

40.0
METER CONSTANT INDELIBLY PROVIDED ON THE
BOOLEAN

NAMEPLATE (YES/NO)

METER ACCURACY DOES NOT GET AFFECTED BY

41.0
MAGNETIC FIELD FROM ALL SIDES OF THE METER
BOOLEAN

(YES/NO)

ONE CT IN NEUTRAL CIRCUIT AND ONE MANGANIN

42.0
BASED, E-BEAM WELDED SHUNT IN PHASE CIRCUIT
BOOLEAN

PROVIDED (YES/NO)

METER CAPABLE TO WITHSTAND PHASE TO PHASE

43.0
VOLTAGE (440 V) IF APPLIED BETWEEN PHASE TO
BOOLEAN

NEUTRAL FOR MINIMUM 5 MIN (YES/NO)

44.0
POWER SUPPLY UNIT IS TRANSFORMER LESS
BOOLEAN

(YES/NO)

COMPLETE METERING SYSTEM & MEASUREMENT

45.0
NOT AFFECTED BY EXTERNAL ELECTROMAGNETIC
BOOLEAN

INTERFERENCE AS PER CL. NO. 6.16 OF TECH.

SPECS. (YES/NO)

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011 Page 74 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

METER MEETS THE REQUIREMENT OF CBIP TECH.

46.0
REPORT 88 (AMENDED UP TO DATE) EXCEPT 0.2
BOOLEAN

TESLA AC MAGNET TEST (YES/NO)

ACCURACY DOES NOT GET INFLUENCED BY

47.0
INJECTION OF HIGH FREQUENCY AC VOLTAGE /

BOOLEAN

CHOPPED SIGNAL / DC SIGNAL AND HARMONICS ON

THE TERMINALS OF THE METER (YES/NO)

48.0
METER RECORDS AND DISPLAYS TOTAL ENERGY
BOOLEAN

INCLUDING HARMONIC ENERGY.

METER DISPLAYS
UNSATISFACTORY
FUNCTIONING

49.0
OR NONFUNCTIONING OF REAL TIME CLOCK
BOOLEAN

BATTERY (YES/NO)

50.0
METER PCB IS WIRELESS (YES/NO)

BOOLEAN

51.0
BATTERY BACK UP WITH MINIMUM 10 YEARS LIFE IS
BOOLEAN

PROVIDED (YES/NO)

METER DISPLAYS DEFAULT PARAMETERS ONLY

52.0
ONCE AFTER ACTIVATION OF BATTERY DURING
BOOLEAN

POWER OFF CONDITION (YES/NO)

53.0
BATTERY GETS LOCKED AFTER 3 OPERATIONS
BOOLEAN

DURING ONE POWER OFF CYCLE (YES/NO)

COMMUNICATION CAPABILITY OF THE METER IS AS

54.0
PER LPRF TO READ METER FROM THIRTY (30) METER
BOOLEAN

RADIUS WITH OBSTRUCTIONS (YES/NO)

COMMUNICATION
RANGE FURTHER
INCREASED

55.0
UPTO 5 HOPS THROUGH MESH NETWORKING
BOOLEAN

(YES/NO)

56.0
35 KV SPARK DISCHARGE TEST OF IS CARRIED OUT
BOOLEAN

57.0
METER MANUFACTURED USING SMT (YES/NO)
BOOLEAN

58.0
ALL ANTI-TAMPER FEATURES AS PER CLAUSE 9.00
BOOLEAN

ARE PROVIDED (YES/NO)

59.0
PERMANENT BACKLIT LCD TYPE DISPLAY IS
BOOLEAN

PROVIDED (YES/NO)

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011 Page 75 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

60.0
5 NUMBER OF DIGITS FOR ENERGY DISPAY
BOOLEAN

PROVIDED (YES/NO)

61.0
MINIMUM SIZE OF DIGITS (9X5 MM) (YES/NO)
BOOLEAN

DEFAULT DISPLAY SWITCHES TO ALTERNATE

62.0
DISPLAY AFTER PRESSING THE PUSH BUTTON
BOOLEAN

CONTINUOUSLY FOR 5 SECONDS (YES/NO)

ALTERNATE DISPLAY SWITCHES TO DEFAULT

63.0
DISPLAY IF PUSH BUTTON IS NOT OPERATED FOR 15
BOOLEAN

SECONDS (YES/NO)

64.0
ACTIVE CUMULATIVE ENERGY (KWH) IS DISPLAYED
BOOLEAN

FOR 20 SECONDS (YES/NO)

OTHER PARAMETERS THAN CUMULATIVE ENERGY

65.0
AND ALTERNATE MODE PARAMETERS DISPLAYED
BOOLEAN

FOR MINIMUM 6 SECONDS (YES/NO)

66.0
LCD CHECK IS PROVIDED TO DISPLAY HEALTHINESS
BOOLEAN

OF ALL SEGMENTS (YES/NO)

67.0
KWMD PROVIDED (YES/NO)
BOOLEAN

68.0
INTEGRATION PERIOD OF MD 30 MIN. (YES/NO)
BOOLEAN

69.0
NON-VOLATILE MEMORY PROVIDED (YES/NO)
BOOLEAN

70.0
COMPUTER SOFTWARE PROVIDED IS WINDOWS
BOOLEAN

BASED (YES/NO)

71.0
TOTAL TIME TAKEN FOR DOWNLOADING ALL DATA
BOOLEAN

FOR 45 DAYS IS LESS THAN 90 SECONDS (YES/NO)

72.0
DOWNLOADING TIME OF ONLY BILLING DATA IS
BOOLEAN

LESS THAN 5 SECS (YES/NO)

73.0
CMRI POSSESSES SPECIFIC SERIAL NO. (YES/NO)
BOOLEAN

CMRI CAPABLE OF DOWNLOADING BILLING DATA OF

74.0
AT LEAST 2,000 (TWO THOUSAND) METERS AT A
BOOLEAN

TIME (YES/NO)

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 76 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

CMRI SUPPLIED IS CAPABLE FOR DOWNLOADING

75.0
DATA OF MULTIPLE DESIGNS & MAKE OF METERS
BOOLEAN

(YES/NO)

INDICATION FOR CONFIRMATION OF SUCCESSFUL

76.0
DATA TRANSFER IS PROVIDED IN METER & CMRI
BOOLEAN

(YES/NO)

77.0
RS 232 PORT AS WELL AS USB PORT ARE PROVIDED
BOOLEAN

ON CMRI (YES/NO)

78.0
TWO NOS. OF CHORDS OF MIN. 1 MTR LENGTH ARE
BOOLEAN

PROVIDED WITH EACH CMRI (YES/NO)

CMRI HAS FACILITY FOR RE-ENTERING THE METER

79.0
SERIAL NUMBERS DIRECTLY FROM BASE COMPUTER
BOOLEAN

SYSTEM (YES/NO)

80.0
SEARCH FACILITY PROVIDED ON CMRI (YES/NO)
BOOLEAN

ZIGBEE COMPLIANCE CERTIFICATE FOR RADIO

81.0
MODULES USED IN METER & CMRI IS SUBMITTED
BOOLEAN

(YES/NO)

82.0
ZIGBEE COMPLIANCE CERTIFICATE NUMBER & DATE
TEXT

FOR RADIO MODULES

83.0
METER IS TYPE TESTED (YES/NO)

BOOLEAN

84.0
TYPE TEST REPORT NUMBER & DATE

TEXT

85.0
GUARANTEE 5 YEARS FROM INSTALLATION OR FIVE
BOOLEAN

& HALF YEARS FROM DATE OF DESPATCH (YES/NO)

IN HOUSE TESTING FACILITIES ARE AVAILABLE FOR

86.0
(a) INSULATION
RESISTANCE
MEASUREMENT
BOOLEAN

(YES/NO)

87.0
(b) NO LOAD CONDITION (YES/NO)

BOOLEAN

88.0
(c) STARTING CURRENT TEST (YES/NO)
BOOLEAN

89.0
(d) ACCURACY TEST REQUIREMENT (YES/NO)
BOOLEAN

90.0
(e) POWER CONSUMPTION (YES/NO)

BOOLEAN

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 77 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

91.0
(f) TRANSPORTATION TEST AS PER CLAUSE NO.
BOOLEAN

18.03.1
(YES/NO)

(g) FULLY
COMPUTERISED METER
TEST
BENCH

92.0

SYSTEM FOR CARRYING OUT ROUTINE AND


BOOLEAN

ACCEPTANCE TEST IS AVAILABLE (YES/NO)

(h) THE MANUFACTURER SHALL HAVE DULY

93.0
CALIBRATED STANDARD METER OF 0.1 CLASS
BOOLEAN

ACCURACY (YES/NO)

94.0
(i) VERIFIACTION OF DATA DOWNLOADING AS PER
BOOLEAN

RF PORT (YES/NO)

95.0
(j) GLOW WIRE TESTING (YES/NO)

BOOLEAN

FURNISH PRINCIPLE OF OPERATION OF METER

OUTLINING METHODS AND STAGES OF

96.0
COMPUTATIONS
OF
VARIOUS
PARAMETERS
TEXT

STARTING FROM INPUT VOLTAGE AND CURRENT

SIGNALS INCLUDING SAMPLING RATE IF APPLICABLE

97.0
MANUFACTURING ACTIVITIES ARE AS PER CLAUSE
BOOLEAN

26.00 (YES/NO)

98.0
QAP SUBMITTED AS PER ANNEXURE-I (YES/NO)
BOOLEAN

99.0
AGEING TEST IS CARRIED OUT
FOR
METER
BOOLEAN

(YES/NO)

100.0
GTP FOR METER BOX.

BOOLEAN

101.0
MANUFACTURER'S
/

SUPPLIER'S
NAME
AND
TEXT

ADDRESS WITH WORKS ADDRESS

TRANSPARENT
POLY-CARBONATE
MATERIAL

102.0

NATURAL WHITE COLOUR USED FOR BASE AND


BOOLEAN

COVER OF METER BOX (YES/NO)

103.0
WALL THICKNESS OF METER BOX ON LOAD
BOOLEAN

BEARING SIDE 3 MM (YES/NO)

104.0
THICKNESS OF SHEET OF COVER 2 MM (YES/NO)
BOOLEAN

105.0
LIFE EXPECTED IS 5.5 YEARS (YES/NO)

BOOLEAN

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 78 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER WITH


INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

106.0
APPLICABLE IS: 14772 / 2000 (WITH LATEST
BOOLEAN

AMENDMENT) (YES/NO)

107.0
FURNISH PHYSICAL WATER ABSORPTION VALUE
TEXT

108.0
FURNISH THERMAL HDDT VALUE
TEXT

109.0
FURNISH FLAMMABILITY VALUE
TEXT

110.0
FLAMMABILITY V2 (YES/NO)
BOOLEAN

111.0
GLOW WIRE TEST AT 650 C (YES/NO)
BOOLEAN

112.0
TENSILE STRENGTH
TEXT

113.0
FLEXURE STRENGTH
TEXT

114.0
MODULUS OF ELASTICITY
TEXT

115.0
IZOD IMPACT STRENGTH NOTCHED 23 C
TEXT

116.0
DIMENSIONS OF BOX IN MM (LXBXH)
TEXT

117.0
MINIMUM CLEARANCE OF 40 MM FROM THREE
BOOLEAN

SIDES OF METER (YES/NO)

118.0
MINIMUM CLEARANCE OF 25 MM FROM METER
BOOLEAN

FRONT SIDE (YES/NO)

119.0
MINIMUM CLEARANCE OF 10 MM FROM BACK OF
BOOLEAN

METER (YES/NO)

120.0
MINIMUM CLEARANCE OF 60 MM FROM BOTTOM OF
BOOLEAN

METER (YES/NO)

121.0
WEIGHT OF COMPLETE BOX IN KGS
TEXT

122.0
METER BOX IS TYPE TESTED (YES/ NO)
BOOLEAN

123.0
TYPE TEST REPORT NOS.
TEXT

124.0
INHOUSE TESTING FACILITY AS PER CLAUSE NO. 6.0
BOOLEAN

(YES/NO)

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 79 of 80

TECHNICAL SPECIFICATION OF LT AC SINGLE PHASE 5 30 AMPS STATIC ENERGY METER


WITH INTERNAL LPRF CONNECTIVITY FOR COMMUNICATION.

WHETHER YOU AGREE TO SUPPLY METERS AS PER

ANEXURE-D, I.E. TECHNICAL SPECIFICATIONS OF BOOLEAN THE TENDER.


(YES/NO)

WHETHER TYPE TEST REPORTS ALONGWITH COPY BOOLEAN OF SAME IN


TWO CDS ARE SUBMITTED (YES/NO)

WHETHER 10 NOS. OF TENDER SAMPLE METERS

WITH TWO METER BOXES ARE SUBMITTED. BOOLEAN (YES/NO)

AS PER CLAUSE 4.6 OF ANNEXURE III, I.E.

TECHNICAL SPECIFICATION FOR METER BOX, UV BOOLEAN AGEING TEST IS


CARRIED OUT (YES/NO)

Technical Specification No. CE/MMC/MSC-IV/SP/LPRF/T/03, DATE: 18.07.2011

Page 80 of 80