The Fast Way to Tune Slow Loops


by John Gerry, P.E.
Click here to see the complete presentation in more detail as a web-cast.

Tuning slow loops does not have to take a long time.


Using the strategy outlined in this presentation, you can tune slow loops very
quickly.
To tune a control loop, analysis software must process some loop data. You must
test or bump the loop somehow. For example a setpoint change in automatic or a
controller output change in manual mode. For more information see the
presentation: "Plant Data You Should Use for PID Tuning and Modeling"
available from the articles page on ExperTune.com.
The trick we use for tuning slow loops, is a fast test. A fast test:

Is up to five times faster than a step test


Upsets the process little
Allows less time for outside upsets to interfere (with the test)
You don't need initial PID tuning
You don't need any process model estimates
You don't need to know the process dead time

Above is an example step test performed


on a slow temperature loop. The white line
in the upper portion is the temperature. The
green line in the lower portion is the
controller output. The controller output steps
up at about 20 minutes. After about 1000
minutes the temperature is settled enough
to provide good data for PID tuning and
modeling. This is not a fast test.
To the left is the fast test performed on the
same loop. The temperature reached a
temporarily settled area at about 140
minutes. This fast test data will result in the
same PID tuning as using the step test data and it went 5 times faster.

Fast Test Steps


a. Check to be sure the controller output is between about 30% and 70%. If it
is outside 30% and 70%, change the controller output to between this area
if possible because valves are often non-linear at limits.
b. Let the loop settle out and direct the analysis software to start archiving or
recording data.

c. Put the controller in manual and be


ready with a stopwatch or timer.
d. Change the controller output quickly
by 10% to 20% (This controller
output change can be relatively large
since we will be moving it back fairly
soon.) As soon as you make the
change, start timing.
e. After a short amount of time or when you see the process variable move
from the change you made, move the output in the opposite direction by
twice as much as the change in the previous step. Also immediately
record the time that has passed since the first change - call this time, T,
and start timing again.
f. As soon as time T has passed, return the output to its original value.
g. Wait until the PV seems to settle from the changes made before using the
data for tuning. The temperature here is not settled. You need to wait
longer as shown in the next slide.
To the left is the temperature loop test data after more time has gone by. You
need to wait until the PV seems to settle or turn the corner from the pulses made
- about at time 260 minutes in this case. The red region shows the time window
of data to use for tuning. This window of data results in excellent PID tuning.
When you do a fast test you probably will not change the controller output at
exactly a symmetrical interval - the first half will either be longer or shorter than
the second half - and this is recommended. In the previous example, the second
time period is slightly longer than the first. The shape of the response of the PV
will depend on your process dynamics and the time durations of your pulse.
In this fast test on the same temperature loop, the first portion of the controller
output pulse is shorter. For tuning, you can stop taking data at about 180
minutes. The data shown in the red shaded area gives excellent results.

Again we have the same temperature loop. This time the first half of the
controller output pulse is longer than the second half. You only need to collect
data in this case until about 130 minutes. This test, the previous one and a step
test all give almost identical tuning parameters from ExperTune's PID tuning
software.
If your temperature loop responds differently up than down, it is best to take data
in both directions and use the more conservative tuning. ExperTune's Advanced
PID tuner includes a Loop Summary Table that lists the results of several tests,
automatically picking the more conservative tuning for you.
Use the fast test combined with the analysis power of ExperTune software to
quickly get PID tuning on slow loops. From this data ExperTune's Tuner/analyzer
also gives you a high fidelity model of the loop, simulation, and robustness
analysis. See the response in simulation and know how robust the loop is before
you download tuning.