Sei sulla pagina 1di 154

GE Oil & Gas

Vector VII

Variable Speed
Drive
104 kVA - 561 kVA

imagination at work

PN: 196399 Revision: 6.6.2

1.
2.

Quick Start Guide.............................................................................................................................................................................................................................................6


I want to............................................................................................................................................................................................................................................................7
2.1. Activate the normal drive screen..............................................................................................................................................................................................................7
2.2. Activate the status indicator screen.......................................................................................................................................................................................................7
2.3. Adjust the frequency setpoint...................................................................................................................................................................................................................7
2.4. Clear the Fault state.......................................................................................................................................................................................................................................7
2.5. Determine the current rating of this drive............................................................................................................................................................................................7
2.6. Change one of the parameters in the Linear List..............................................................................................................................................................................7
2.7. Save Data Log, Current Log, and Events files to USB Flash disk.................................................................................................................................................7
2.8. Set drive parameters to their factory default values.........................................................................................................................................................................7
2.9. Adjust the V/F behavior of the drive........................................................................................................................................................................................................7
2.10. Fine tune the drive output voltage without stopping the drive...................................................................................................................................................7
3.
Installation and Setup...................................................................................................................................................................................................................................8
3.1. Site Installation.................................................................................................................................................................................................................................................8
3.1.1.
Equipment Inspection...............................................................................................................................................................................................................8
3.1.2.
Equipment Installation and Requirements......................................................................................................................................................................8
3.1.3.
Electrical Connections............................................................................................................................................................................................................11
3.2. Hardware Connections..............................................................................................................................................................................................................................13
3.2.1.
Control Terminals.....................................................................................................................................................................................................................14
3.2.2.
External Stop Switches...........................................................................................................................................................................................................17
3.2.3.
Standby Switch Input..............................................................................................................................................................................................................17
3.2.4.
Event Switch................................................................................................................................................................................................................................17
3.2.5.
Remote Run and Reference.................................................................................................................................................................................................17
3.3. Startup Checks...............................................................................................................................................................................................................................................18
3.3.1.
Pre Power-Up..............................................................................................................................................................................................................................18
3.3.2.
Pre Run Checks..........................................................................................................................................................................................................................18
3.3.3.
Drive Start Up.............................................................................................................................................................................................................................19
3.4. Keypad Conventions...................................................................................................................................................................................................................................20
3.4.1.
Soft keys........................................................................................................................................................................................................................................20
3.4.2.
Arrow Keys...................................................................................................................................................................................................................................20
3.4.3.
Start / Stop...................................................................................................................................................................................................................................21
3.4.4.
Status Indicator Screen Old HMI........................................................................................................................................................................................21
3.4.5.
Status Indicator Screen New HMI......................................................................................................................................................................................22
3.5. Configuration..................................................................................................................................................................................................................................................22
3.5.1.
Drive Mode...................................................................................................................................................................................................................................22
3.5.2.
Frequency Behavior.................................................................................................................................................................................................................22
3.5.3.
Alarms and Restarts................................................................................................................................................................................................................23
3.5.4.
Motor Direction..........................................................................................................................................................................................................................23
4.
Screen Descriptions.....................................................................................................................................................................................................................................24
4.1. Run Status........................................................................................................................................................................................................................................................24
4.2. Event Log..........................................................................................................................................................................................................................................................26
4.3. Select Screen (Not logged in)...................................................................................................................................................................................................................27
4.4. Enter Password..............................................................................................................................................................................................................................................28
4.5. Select Screen (Logged in)...........................................................................................................................................................................................................................29
4.6. Fault Status......................................................................................................................................................................................................................................................31
4.7. Amp Chart........................................................................................................................................................................................................................................................32
4.8. Trending............................................................................................................................................................................................................................................................33
4.9. History Screen................................................................................................................................................................................................................................................34
4.10. Setup Screen...................................................................................................................................................................................................................................................35
4.11. SmartGuard..................................................................................................................................................................................................................................................37
4.12. Drive I/O............................................................................................................................................................................................................................................................38
4.13. Last Fault..........................................................................................................................................................................................................................................................39
4.14. All Monitors......................................................................................................................................................................................................................................................40
4.15. Run Info.............................................................................................................................................................................................................................................................44
4.16. Set Date and Time........................................................................................................................................................................................................................................45
4.17. Linear List Menu............................................................................................................................................................................................................................................46
4.17.1. Linear List.....................................................................................................................................................................................................................................47
4.18. Operating Mode............................................................................................................................................................................................................................................48
4.18.1. Selection Parameter Change..............................................................................................................................................................................................49
4.18.2. Operating Mode Frequency Control.............................................................................................................................................................................50
4.18.3. Operating Mode - Analog Follower...................................................................................................................................................................................52
4.18.4. Operating Mode Current Control....................................................................................................................................................................................54
4.18.5. Operating Mode Pressure Control.................................................................................................................................................................................56
4.19. Alarms Setup...................................................................................................................................................................................................................................................58
4.20. Underload Setup...........................................................................................................................................................................................................................................60
4.21. Start Control....................................................................................................................................................................................................................................................62
4.22. Numeric Parameter Change....................................................................................................................................................................................................................64

5.
6.

7.

8.

9.

4.23. Frequency Setup...........................................................................................................................................................................................................................................65


4.24. Analog 1 Setup...............................................................................................................................................................................................................................................67
4.25. Analog 2 Setup...............................................................................................................................................................................................................................................69
4.26. Misc Setup........................................................................................................................................................................................................................................................71
4.27. Comm Setup...................................................................................................................................................................................................................................................73
4.28. Hard Starting..................................................................................................................................................................................................................................................75
4.29. Maintenance Menu......................................................................................................................................................................................................................................76
4.30. Startup Control..............................................................................................................................................................................................................................................78
4.31. Keypad Test.....................................................................................................................................................................................................................................................80
Parameter Locator.......................................................................................................................................................................................................................................81
Remote User Interface...............................................................................................................................................................................................................................83
6.1. What is the Remote User Interface?.....................................................................................................................................................................................................83
6.2. Configuration..................................................................................................................................................................................................................................................83
6.3. Capabilities......................................................................................................................................................................................................................................................84
Volts per Hertz Settings (V/Hz).................................................................................................................................................................................................................85
7.1. V/Hz Factory and Manual Set-up...........................................................................................................................................................................................................85
7.1.1.
Factory Default V/Hz and Definition.................................................................................................................................................................................85
7.1.2.
Selectable 60 Hz V/Hz settings...........................................................................................................................................................................................86
7.1.3.
Selectable 50 Hz V/Hz settings...........................................................................................................................................................................................78
7.1.4.
V/Hz Manual Set-up.................................................................................................................................................................................................................92
SCADA Interface............................................................................................................................................................................................................................................93
8.1. SCADA Interface Port..................................................................................................................................................................................................................................93
8.2. SCADA Addresses.........................................................................................................................................................................................................................................93
8.3. Old HMI Communication Ports 1-5 Pin Out.......................................................................................................................................................................................98
8.4. New HMI Communication Ports Pin Out............................................................................................................................................................................................99
Troubleshooting and Maintenance....................................................................................................................................................................................................100
9.1. Main Circuit Test Procedure...................................................................................................................................................................................................................100
9.1.1.
Test Point Designations.......................................................................................................................................................................................................101
9.1.2.
Main Power Circuit Test and Troubleshooting.............................................................................................................................................................101
9.2. Drive System Troubleshooting.............................................................................................................................................................................................................103
9.2.1.
Drive Frame PC Board Designations.............................................................................................................................................................................104
9.2.2.
System Power Checks and Troubleshooting..............................................................................................................................................................104
9.2.3.
Fan/Heat Exchanger Troubleshooting.........................................................................................................................................................................105
9.2.4.
Drive Status / Fault Codes..................................................................................................................................................................................................105
9.3. General Maintenance...............................................................................................................................................................................................................................108
9.3.1.
Periodic Inspection NO Power Applied......................................................................................................................................................................108
9.3.2.
Periodic Inspection Power Applied (External Only)...............................................................................................................................................108

Appendix............................................................................................................................................................................................................................................................................109
1.
Dimensions and Weights........................................................................................................................................................................................................................109
2.
Default Parameter Values......................................................................................................................................................................................................................113
3.
USB Flash Drive Operation.....................................................................................................................................................................................................................114
3.1. Save History files........................................................................................................................................................................................................................................114
3.2. Save Configuration to USB flash drive..............................................................................................................................................................................................114
3.3. Save Linear List to USB flash drive......................................................................................................................................................................................................115
3.4. Load configuration from a USB flash drive to a Vector VII drive.........................................................................................................................................115
4.
Linear List......................................................................................................................................................................................................................................................117
5.
Tools Recommended for Maintenance and Repair.......................................................................................................................................................................151
6.
CE Conformity for drives purchased with CE Option......................................................................................................................................................................152
6.1. Emergency Stop Function......................................................................................................................................................................................................................152

5500 SE 59th St
Oklahoma City, OK 73135
For more information please visit:
www.geoilandgas.com/esp

GE Oil & Gas

Intended Use

This manual applies to the 104, 150, 253, 344, 428 and 561 models of the GE Oil & Gas Vector VII Variable Speed Drive that
are loaded with Firmware revision 6.6.

General Specifications
Electrical Specifications:
Rated Input Voltage:
480 Volt, 3 phase, 60 Hz (+ / - 10% of rated voltage and frequency).

Consult factory for other input voltages and frequency ratings.
Efficiency: 97% or greater at full load.
Output Voltage:
0 Volts to rated input voltage
Output Frequency:
0 Hertz to 120 Hertz.

Control Specifications:
Control Method:
Accel / Decel:
Drive Overload:
Current Limit:

Sine coded output with optional VSG (Variable Sinewave Generation)


technology.
0 Seconds to 6,000 seconds.
110% of drive rating for 60 seconds (Variable Torque).
Programmable current limit.

Control I/O:
Digital Inputs:
Digital Outputs:
Analog Inputs:


Analog Outputs:
Analog Reference:
Logic Reference:

7 Programmable inputs - 24 VDC, 8 mA Sinking or Sourcing Logic.


2 Programmable dry contacts rated 250 VAC / 30 VDC @ 1A.
1 Fault contact - Form C dry contact rated 250 VAC / 30 VDC @ 1A.
2 Programmable inputs (10 bit).
1 Input 0 to +10 VDC 20 K Ohms
1 Input 0 to +10 VDC 20 K Ohms or 4 to 20 mA 250 Ohms
2 Programmable outputs (10 bit) 0 to +10 VDC 2 mA.
+15 VDC Source 20 mA.
+24 VDC Source 8 mA.

Environmental Specifications:
Ambient Service Temperature:

Ambient Storage Temperature:
Humidity:

Altitude:
Vibration:

0C to 50C (32F to 122F)


to -40C (-40F) with optional arctic package.
-20C to 60C (-4F to 140F)
0 to 100%
Up to 1000 Meters (3300 Feet) without de-rate.
9.81m/s2 (1 G) maximum 10 to 20 Hz, 2.0 m/s2 (0.2 G) 20 Hz to 50 Hz.

Vector, VSG, SmartGuard and SmartLift are all registered trademarks of GE Oil & Gas, Inc.

imagination at work

VII

VECTOR
General Precautions

DANGER: This drive unit requires and produces potentially lethal voltage levels. Failure to comply with the
following may lead to equipment damage, serious personal injury and/or death!!!








Read and understand this manual in its entirety before installing, operating, or servicing this drive. All warnings, cautions, notes and
instructions must be followed. The drive must be installed by qualified personnel only. The drive must be installed following the guidelines in this
manual and following all applicable local codes.
Do not connect or disconnect wiring while power is applied to the drive. Do not remove covers or touch any components while power is on.
To avoid the risk of potentially lethal electrical shock, remove and lock-out all incoming power before servicing this drive unit. The internal
capacitors remain charged even after the power supply is turned off. To prevent electrical shock, wait at least five minutes after removing
power and measure the DC bus voltage between the +3 and terminals to confirm safe level of voltage.
Do not bypass the internal circuit breakers of the drive for any reason.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
Replace any protective covers or shields that may have been removed during servicing before operation of the drive.
Do not connect or operate this unit with visible damage or missing/removed parts.
This unit may start unexpectedly upon application of power. Clear all personnel from the drive and other connected equipment. Secure and/or
remove any mechanical hazards that may be present with the application of power to this drive
This drive contains ESD (ElectroStatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, or
servicing this unit.

Arc Flash Warning:

There is a potential for Arc Flash Hazard with this equipment. It is strongly recommended that an analysis of incident energy levels and determination of
appropriate Personal Protective Equipment be conducted prior to energizing this equipment.

Danger Warning:

A Danger warning symbol is an exclamation mark enclosed in a triangle that precedes the word DANGER. A Danger warning symbol indicates a hazardous
situation which, if not avoided, will result in Death or serious injury. Danger warnings in this manual appear in the following manner.

DANGER Special instructions and descriptions of the associated hazard will be explained in the text following
the Danger warning.

Or for CE marked Applications:

Electrical Warning:

The electrical warning symbol is a lightning bolt mark enclosed in a triangle. The electrical warning symbol is used to indicate locations where hazardous
voltage levels are present and conditions may cause serious injury if proper precautions are not followed.

Or for CE marked Applications:

Caution Warning:

A Caution warning symbol is and exclamation mark enclosed in a triangle that precedes the word CAUTION. A Caution warning symbol indicates a
hazardous situation which, if not avoided, will result in minor or moderate injury.

Or for CE marked Applications:

PN: 196399 Revision: 6.6.2

GE Oil & Gas

1 Quick Start Guide

This section will guide you through drive configuration for a typical GE OIL & GAS installation. It is highly recommended that
the user read the entire manual before proceeding with this procedure!
Step
1

Name
Log on to access drive
configuration
Sections 4.3, 4.4

Set Auto Restart and


Drive Lockout function
Section 4.30

Set drive mode and


related parameters
Sections 3.6.1, 4.18

From the Run Status screen, press the Menu soft key
Use the up and down arrow buttons to select Log In, press the OK soft key.
Enter the password and press the OK soft key.
Default password is 3333.

From the Run Status screen, press the Menu soft key
From the Select Screen, press the Startup soft key
Set Auto Restart to Enable or Disable (Application Dependent)
Set Drive Lockout to Unlock before starting the drive

Determine the operating mode for the drive - Current Control, Pressure Control,
Frequency Control, and Analog Follower.
Edit the Drive Mode parameter in the Operating Mode screen as needed. Modify the
other parameters in the Operating Mode screen as necessary.
Use the up and down arrow buttons in the Select Screen to select the Operating Mode
screen, press the OK button.
Use the up and down arrow buttons to select a parameter, press the Edit key to change
the selected parameter.

Set up alarms

Section 4.19, 4.20

Set up frequency
behavior
Section 4.23

Description

Set up Misc parameters


Section 4.26
Configure analog inputs
Section 4.24, 4.25
Configure User Selected
Parameters
Section 4.10

imagination at work

Set the motor overload and global restart parameters in the Alarms Setup screen.
Set the motor Underload and Underload restart parameters in the Underload Setup
screen.
Select the screen and select / edit parameters as in step 3.
Set the V/F curve, motor direction, maximum and minimum frequencies, acceleration
and deceleration times, jog setpoint, and lockout frequencies in the Frequency Setup
screen.
Select the screen and select / edit parameters as in step 3.

Configure the SmartGuard sensor (if available), transformer ratio, customer password,
and faults as necessary in the Misc Setup screen.
Select the screen and select / edit parameters as in step 3.

If required. Use the Analog 1 Setup and Analog 2 Setup screens.


Select the screen and select / edit parameters as in step 3.

Select parameters to display in the User Selected Parameters section of the Run Status
screen using the Setup screen.
Select the screen and select / edit parameters as in step 3.

VII

VECTOR
2

I want to..

2.1 Activate the normal drive screen


Press any key. Do NOT press the STOP key unless you want the drive to stop. Refer to Section 3.5.4.

2.2 Activate the status indicator screen


The status indicator screen is displayed automatically after 5 minutes of keypad inactivity. It can not be activated
manually.

2.3 Adjust the frequency setpoint


Press the Setp soft key on the Run Status screen to activate setpoint change mode. Use the up and down arrow
keys to adjust the setpoint as desired. Refer to Section 4.1

2.4 Clear the Fault state


Press the STOP key to attempt to clear the fault state. Some faults require a full power cycle to reset.

2.5 Determine the current rating of this drive


Examine the Drive Max Amps parameter displayed on the All Monitors screen. Refer to Section 4.14

2.6 Change one of the parameters in the Linear List


Please discuss this with Engineering. Some of these values are changed automatically when the higher level
parameters are changed via the setup screens. Therefore, changes to the parameters in the Linear List must be
considered carefully to avoid unexpected results. Refer to Section 4.17

2.7 Save Data Log, Current Log, and Events files to USB Flash disk
See description of the Save soft key in the History screen. Refer to Section 4.9 and Appendix 3

2.8 Set drive parameters to their factory default values


Select the Set all parameters to factory defaults. function in Maintenance screen.
Note that this function sets both the high level user interface parameters and low level drive parameters to their
factory defaults. This function may take several seconds. The drive must be powered off and then back on after
this function has completed prior to further drive configuration or use. Refer to Section 4.29

2.9 Adjust the V/F behavior of the drive


The high level parameter V/F Select in the Frequency Menu allows selection from several standard V/F curves (60
Hz Standard Torque, 60 Hz Medium Torque, 60 Hz High Torque, 50 Hz Standard Torque, 50 Hz Medium Torque, 50
Hz High Torque). Using this selection, along with the Maximum Frequency, should accommodate many, if not all,
GE OIL & GAS installations. The V/F behavior can be customized if necessary please contact the WG GE OIL & GAS
controls group at Oklahoma City for advice if such customization is necessary. Refer to sections 4.23 and 7.

2.10 Fine tune the drive output voltage without stopping the drive
Adjust the Voltage Bias parameter in the Frequency Setup screen. Note that the Voltage Bias is applied if the
drive is running a maximum frequency. At lower frequencies, the voltage bias is scaled. Also note that the output
voltage is limited by the DC bus voltage. Refer to section 4.23.

PN: 196399 Revision: 6.6.2

GE Oil & Gas

3 Installation and Setup


3.1 Site Installation
3.1.1 Equipment Inspection
Upon receiving equipment a thorough inspection for external and internal damage should be conducted
before connecting and operating.
Check the external enclosure for broken welds, hinges, bent corners, doors or bent legs.
Check the internal enclosure for loose or broken hardware such as fans, covers or fasteners.
Inspect all wire terminations to ensure connections are tight.
Inspect the enclosure for any signs of water leakage into the drive.
NOTE!!! If the drive is to be used in an GE OIL & GAS application, make sure that the unit is connected
to an output filter (either internal or an external).
NOTE!!! Multi-pulse units require a properly sized and configured phase shift transformer.

3.1.2 Equipment Installation and Requirements


Equipment Placement
The main power service should be located no closer than 100 (30m) from the wellhead.
The drive should be placed at least 50 (15m) from the wellhead, to prevent exposure to hazardous and
explosive gasses, and provide adequate access for well work over equipment.
The drive should be placed on a flat level surface; a concrete pad is recommended but not required, The
VSD should be fastened to the pad through the mounting holes in the enclosure legs. Only use mounting
hardware designed for use with the pad material.
A minimum of 6 of space should be maintained on all four sides of the drive. This will ensure correct
airflow across cooling heat sinks and fan intakes, as well as provide easy access for servicing and cable
entry.
Service Requirements
Main service amperage is based on drive KVA and motor load calculations.
A service disconnect is required between the service transformers and the drive. This should be sized to
accommodate service amperage.
Overhead service drops into disconnects or other equipment must be equipped with a mast mounted
weather head to prevent rain from entering equipment.
Grounding and Bonding
DANGER Correct system grounding and equipment bonding is required to ensure proper operation
of equipment during both normal operation and fault conditions. Grounding and bonding
conductors provide a path to ground for lethal fault currents and voltages. Failure to correctly
ground and bond equipment can lead to equipment damage and personnel injury or death. Refer
to Figure 3.1 and 3.2.

Grounding applies to the main service connection to ground. Service transformer wye-point and
enclosures, including the service disconnect switch, must be connected to a common ground conductor
and grounding electrodes. (Refer to local electrical authority for approved grounding electrodes and
methods in you area) System ground resistance should not exceed 25 Ohms to ground and ideally be
between 1-5 Ohms to ground. Ground resistance checks should only be made by qualified electrical
inspection agencies.
Bonding applies to all other electrical equipment and raceways. A bonding conductor must be
connected from the main grounding electrodes to all enclosures, junction boxes, buildings, electrical
pipes, and the wellhead.

imagination at work

VII

VECTOR

This equipment provides an internal ground connection for the bonding conductor. This connector is
connected to the internal ground bus of the enclosure.

Figure 3.1 Typical Drive Site (Line Power) Installation Grounding and Bonding
Generator requirements
Generator supplied power systems have the same requirements for grounding and bonding as utility
supplied systems. Grounding electrodes must be installed and a common bonding conductor connected
to all equipment and buildings.
Use of generators on drives creates other possible operational problems that can be reduced with
correct generator sizing and design. Generators must be designed to handle the sub-transient
reactance present on VSD applications. When the generator system does not incorporate a wye-point
for connection to the system ground, then an isolation transformer is required between the generator
and input to the VSD. This provides some protection from floating voltages, and provides a wye-point for
connection to the ground system.
Failure to follow the above guidelines will result in poor performance and/or equipment failure.
When a generator unit is used for drive input power, it is highly recommended to use a multi-pulse
VSD (12 Pulse or higher) or the generator should be sized to at least 300% of the VSD rating.

PN: 196399 Revision: 6.6.2

GE Oil & Gas

Figure 3.2 Typical Drive Site (Generator Power) Installation Grounding and Bonding

imagination at work

VII

VECTOR
3.1.3 Electrical Connections

Main Circuit Terminal Configuration


Input power is applied to the drive circuit breaker MCCB1 terminals L1, L2, L3 (and MCCB2 L11, L21, L31
terminals in 12 Pulse units).
Refer to Figures 3.3 and 3.4 for reference
Output power connections are made at the output power block terminals T1, T2, T3.
Applicable wire sizes give in Table 3.2

VECTOR VII 6,12 Pulse Input Lug Sizes / Output Lug Sizes / Ground Lug Sizes
Drive
Model
150

253

344

428

561

Input Lug Size 6 Pulse / Phase

Input Lug size 12 Pulse


/ Phase

Output Lug Size / Phase


PWM

VSG

Ground Lug Size

(1X) #4 - 350 MCM

(1X) #6 - 3/0

(2X) #6 - 350MCM

(2X) #6 - 250MCM

#14 - 2/0

(1X) 25mm2 - 165mm2

(1X) 16mm2 - 95mm2

(2X) 16mm2 - 165mm2

16mm2 - 120mm2

2.5mm2 - 70mm2

(2X) 250MCM - 750MCM

(1X) #4 - 350MCM

(2X) #6 - 350MCM

(2X) #6 - 250MCM

#14 - 2/0

(2X) 120mm2 - 400mm2

(1X) 25 - 165mm2

(2X) 16mm2 - 165mm2

16mm2 - 120mm2

2.5mm2 - 70mm2

(2X) 2/0 - 600MCM

(1X) 2/0 - 600 MCM

(2X) #2 - 600MCM

(2X) 1/0 - 750MCM

#6 - 350MCM

(2X) 70mm2 - 300mm2

(1X) 70mm2 - 300mm2

(2X) 35mm2 - 300mm2

(2X) 55mm2 - 400mm2

16mm2 - 165mm2

(2X) 2/0 - 600MCM

(1X) 3/0 - 600MCM

(2X) #2 - 600MCM

(2X) 1/0 - 750MCM

#6 - 350MCM

(2X) 70mm2 - 300mm2

(1X) 95mm2 - 300mm2


(1X) 250MCM 750MCM
(1X) 150mm2 400mm2

(2X) 35mm2 - 300mm2

(2X) 55mm2 - 400mm2

16mm2 - 165mm2

(2X) #2 - 600MCM

(2X) 1/0 - 750MCM

#6 - 350MCM

(2X) 35mm2 - 300mm2

(2X) 55mm2 - 400mm2

16mm2 - 165mm2

(2X) 500MCM - 750MCM


(2X) 240mm2 - 400mm2

Table 3.1 Applicable Lug Sizes for Main Circuit Terminals

PN: 196399 Revision: 6.6.2

11

GE Oil & Gas

VECTOR VII RECOMMENDED CABLE SIZE

Drive
Model

Cable Temperature Rating and Type

(167F)

(140F)

(167F)

(140F)

(167F)

TYPE

TYPE

TYPE

TYPE

TYPE

TYPE

TW,

RHW,

TW,

RHW,

TW,

RHW,

UF

THHW,

UF

THHW,

UF

THHW,

THW,

THW,

THW,

THWN,

THWN,

THWN,

XHHW,

XHHW

XHHW

USE,

ZW

Input Rating = 180 Amps

150

Input Rating = 180 Amps

253

3/0awg

2awg

3awg

(2X) 1awg

(2X) 2awg

150mm

95mm

35mm

30mm

(2X) 50mm

(2X) 35mm

Input Rating = 304 Amps

(2X) 2/0awg

3/0awg

2/0awg

(2X) 3/0awg

(2X) 2/0awg

(2X) 95mm

(2X) 70mm

95mm

70mm

(2X) 95mm

(2X) 70mm

Input Rating = 414 Amps

428

(2X) 4/0awg

300mcm

4/0awg

(2X) 300mcm

(2X) 4/0awg

(2X) 150mm

(2X) 120mm

150 mm

120mm

(2X) 150mm

(2X) 120mm

Input Rating = 515 Amps

561

Output Rating = 515 Amps

(2X) 400mcm

(2X) 350mcm

400MCM

350MCM

(2X) 400mcm

(2X) 350mcm

(2X) 240mm

(2X) 165mm

240 mm

165 mm

(2X) 240mm

(2X) 165mm

Input Rating = 675 Amps

Input Rating = 675 Amps

Output Rating = 414 Amps

(2X) 300mcm

Input Rating = 515 Amps

Output Rating = 304 Amps

(2X) 3/0mcm

Input Rating = 414 Amps


344

Output Rating = 180 Amps

300mcm

Input Rating = 304 Amps

Cable Temperature Rating and Type

(140F)

Cable Temperature Rating and Type

75 C

T1 T2 T3 Size* (AWG kcmil)

60 C

L1 L2 L3 L11 L21 L31 Size* (AWG kcmil)

75 C

L1 L2 L3 Size* (AWG kcmil)

60 C

Output Conductor / Phase

75 C

Input Conductor 12 Pulse / Phase

60 C

Input Conductor 6 Pulse / Phase

Output Rating = 675 Amps

(2x) 600mcm

(2X) 500mcm

600mcm

500mcm

(2x) 600mcm

(2X) 500mcm

300 mm

(2X) 240mm

300 mm

240mm

300 mm

(2X) 240mm

Table 3.2 Recommended Cable Sizes

* Copper conductors, not more than 3 insulated conductors rated 0-2000 volts in raceway or cable.
Ambient temperature of 30C (86F).

imagination at work

VII

VECTOR

* Table 3.2 Recommended cable sizes are calculated to be sized 125% of Input/Output current rating.

Figure 3.3 6 Pulse Main Circuit Terminal Configuration

Figure 3.4 12 Pulse Main Circuit Terminal Configuration

3.2 Hardware Connections


3.2.1 Control Terminals
Identifying Control Terminals
Digital and Analog I/O are supported through the control terminals. The Control Terminals (located on the
Terminal Card) are mounted on the lower section of the drive chassis. The picture below shows the control
terminals.

PN: 196399 Revision: 6.6.2

13

GE Oil & Gas

Control Terminal Wire Sizes


Terminal
ALL ( Except E(G) )
E(G)

Possible Wire Sizes AWG (1 Amp Max)


Stranded wire: 26 - 16
20 - 14

Figure 3.5
Recommended Wire Size AWG
18
14


Terminal Designations:
Refer to Figure 3.6 and 3.7 for control terminal and HMI terminal diagram.

Digital Inputs
Terminal
S1
S2
S3
S4
S5
S6
S7
SN
SC
SP

Signal
Remote Run
Not Used
External Fault 1
External Fault 2
Standby
Spare
Breaker 2 Fault
Signal Common
Seq Common
Signal Power

Description
Forward Run when CLOSED, stopped when OPEN
Fault When OPEN (Programmable)
Fault When OPEN (Programmable)
Standby when OPEN (Programmable)
Programmable
Fault When OPEN (Programmable)
Must be tied to SP
Digital input supply +24 VDC,

Signal Level
24VDC, 8mA
24VDC, 8mA
24VDC, 8mA
24VDC, 8mA
24VDC, 8mA
24VDC, 8mA
-

Description
+15VDC for analog Inputs or Transmitters
Analog Input or Speed Command
Multi Function Analog Input
Optional Ground Line Connection Point

Signal Level
20 mA Max
0-10VDC
4/20mA, 0-10VDC
-

Analog Inputs



Terminal
+V
A1
A2
AC
E(G)

Signal
+15VDC Output
Analog In 1
Analog In 2
Analog Common
Shield Wire

Digital Outputs
Output Contact Ratings 1Amp Max at 250VAC
Terminal
M1
M2
M3
M4
MA
MB
MC

Signal
Drive Running
NC Contact
Remote/Auto
NO Contact
Drive Fault Output

Description
CLOSED while drive is running.
(Multi Function Digital Input, Programmable)
Closed when in Local.
(Multi Function Digital Input, Programmable)
MA/MC CLOSED during Fault condition
MB/MC OPEN during Fault condition

Signal Level
Dry Contact

Description
Programmable - Output Frequency Default

Signal Level
0-10 VDC, 2mA Max

Programmable - Output Current Default

0-10 VDC, 2mA Max

Dry Contact
Dry Contact

Analog Outputs
Terminal
FM
AC
AM

Signal
Multi-Function
Analog Output
Analog common
Multi-Function
Analog Output

imagination at work

VII

VECTOR

Digital Inputs

Digital Outputs

DIP Switch S1
OFF

S1 Remote Run

ON

1
2

S2 Not Used

MA

S1-1 RS485/422 Terminating resistance


OFF No Termination Resistance
ON Termination Resistance of 110 Ohms
Default - OFF
S1-2 Analog Input A2 Setup
OFF 0-10 Vdc
ON 4-20 mA
Default ON (4-20 mA)

S3 External Fault 1
S4 External Fault 2
S5 Lease Kill

MB
MC
Drive Fault

S6 Spare
[CJ]

S7 Breaker 2 Fault

[CK]

SN Signal Common

M1
M2

SC SEQ Common

Drive Running

SP +24 VDC

M3
M4

Analog Inputs

Remote\Auto

+V +15 VDC

Analog Outputs

A1 Analog Input 1 0-10 Vdc


A2 Analog Input 2 0-10 Vdc or 4-20 mA
AC Analog Common
EG

Frequency Output 0-10 VDC FM


Current Output 0-10 VDC AM
Analog Common AC

EG

EG
+5V GND

To
fan
Relay

[PJ]
[PK]

R+
1
3

CN88

S+
S-

RS+
SIG

COM5

3
8

HMI

COM4

RTU/SSU

1
9

COM3

RESERVED

1
9

COM2

MODBUS SLAVE

1
9

COM1

RESERVED/DEBUG
* 12 Pulse Drives Only

1
9

EXTERNAL USB PORT

Figure 3.6 Control Terminals and OLD BLUE BOX HMI Terminal Diagram

PN: 196399 Revision: 6.6.2

15

GE Oil & Gas


Digital Inputs

Digital Outputs

DIP Switch S1
OFF

S1 Remote Run

ON

1
2

S2 Not Used

MA

S1-1 RS485/422 Terminating resistance


OFF No Termination Resistance
ON Termination Resistance of 110 Ohms
Default - OFF
S1-2 Analog Input A2 Setup
OFF 0-10 Vdc
ON 4-20 mA
Default ON (4-20 mA)

S3 External Fault 1
S4 External Fault 2
S5 Lease Kill

MB
MC
Drive Fault

S6 Spare
[CJ]

S7 Breaker 2 Fault

[CK]

SN Signal Common

M1
M2

SC SEQ Common

Drive Running

SP +24 VDC

M3
M4

Analog Inputs

Remote\Auto

+V +15 VDC

Analog Outputs

A1 Analog Input 1 0-10 Vdc


A2 Analog Input 2 0-10 Vdc or 4-20 mA

Frequency Output 0-10 VDC FM


Current Output 0-10 VDC AM

AC Analog Common
EG

Analog Common AC

EG

EG

J14 Comm 4

To
fan
Relay

[PJ]
[PK]

1
3

CN88

R+
RS+
S-

SS+

1
2
3
4

IG

New HMI
* 12 Pulse Drives Only
Figure 3.7 Control Terminals and New HMI Terminal Diagram

imagination at work

VII

VECTOR
3.2.2 External Stop Switches

The drive supports up to two external stop switches. When a stop switch is activated, an external fault
occurs and the drive stops.
Connecting an External Stop Switch 1:
1. Wire a stop switch between S3 and SN.
2. Enable External Fault 1 on the Misc Setup screen as Normally Open (N.O.) or Normally Closed (N.C.).
Connecting an External Stop Switch 2:
1. Wire a stop switch between S4 and SN.
2. Enable External Fault 2 on the Misc Setup screen as Normally Open (N.O.) or Normally Closed (N.C.).

3.2.3 Standby Switch Input


The drive supports a normally closed external switch that will stop the drive when the switch opens. This can
be used to stop the drive in a tank full or lease kill situation. If the Standby switch opens when the drive is
running, the drive stops and enters the STANDBY state. An event is created but no fault occurs. The drive will
immediately restart when the switch is closed again.
Connecting the Standby Relay:

1. Wire the normally closed terminals of the standby relay between S5 and SN.
2. Enable the Standby Switch parameter on the Misc Setup screen.

3.2.4 Event Switch


The drive supports a switch that logs events when the switch changes states. No fault occurs and the drive
does not stop.
Connecting the drive to an event switch.

1. Wire the switch to be monitored between S6 and SN.

3.2.5 Remote Run and Reference


The drive supports a 2-wire external run interface along with an analog signal for drive speed control.
DANGER When operating in 2-wire mode the drive may start automatically upon power up of the
unit. Ensure that the Remote Run input is OPEN before powering up a drive set up in 2-wire mode
To connect the drive to a remote run control and reference (Refer to figure 3.8):
1. Install a Normally Open relay contact between S1 and SN.
2. Connect the 0V 10V analog reference signal to terminal block position A1.
3. Connect analog ground to terminal block position AC.
The drive will run when S1 is pulled to the SN state (i.e. contactor or switch is closed).

PN: 196399 Revision: 6.6.2

17

GE Oil & Gas

Figure 3.8 Remote Run Operation

3.3 Startup Checks


DANGER The following steps require that the system be energized. Only qualified personnel should
perform the following procedures.

3.3.1 Pre Power-Up









Remove and lock-out incoming power out before connecting the drive.
Ensure that the drive is properly grounded.
Do a complete visual inspection, checking for loose or broken wires.
Make sure all internal and external fans are free to turn.
Perform Main Circuit testing procedure outlined in Section 9.1.
Connect the service power to the main input circuit breaker of the drive (L1, L2, L3 on 6 Pulse drives (and
L11, L21, L31 on 12 Pulse drives)). !!!! Note connecting the input power to the output of the drive can cause
severe damage to the drive.
Ensure that the output of the drive is disconnected (T1, T2, T3). Ensure that main drive circuit breaker(s)
switch is in the Off position and all remote start signals that may be present are defeated.
Turn power on at the service disconnect and measure incoming voltage. Check the voltage phase to
phase and phase to ground and ensure that the voltages are in range before closing drives circuit breaker.
The phase to phase voltage should be 480VAC +/-10% and the phase to ground should be approximately
277VAC +/-10%.

3.3.2 Pre Run Checks


DANGER The following steps require that the system be energized. Only qualified personnel should
perform the following procedures.
Drive Power Up
Energize main input circuit breaker(s) and verify that the HMI powers up with no fault conditions present.
Check the DC Bus level. Measure across +3 and - terminals. Nominal values should be between 650
700 VDC.
In most cases it is wise to reset the drive to its factory default parameter settings before commissioning
the drive. This should always be done when a drive has been used on a previous application. See
Section 4.29 Set All Parameters To Factory Defaults.
Proceed with no-load checks

imagination at work

VII

VECTOR
No-Load Checks
No load checks should be performed to ensure proper operation of the drive before connecting the output of
the drive to its load (Step-up Transformer or Motor). Proceed with the following steps.

Make sure that the drive output connections are disconnected. If they are not, ensure that the
incoming power is locked out. Wait at least five minutes after removing power and measure the DC
bus voltage to confirm safe level of voltage using volt meter set to read DC volts with the black lead
connected to (-) and the red lead connected to (+3). Disconnect the drive output connections.
From the Run Status screen, use the Setp soft key and the down arrow key to adjust the frequency
reference to the minimum frequency.
Navigate to the Underload Setup screen and set the Underload Current to 0.
Set parameter L8-07 in the linear list to 0 (disabled), this will avoid nuisance LF Missing Output Phase
Faults.
Press the Start button.
Navigate to the Run Status screen. Check the output voltage. Use the Setp soft key and the up arrow
key to adjust the frequency reference to the maximum frequency. Check the output voltage. Output
voltage should be equal to the incoming voltage at maximum frequency and approximately half of that
value at minimum frequency (depending on setup of Voltage/Frequency).
Press the Stop button.
Set parameter L8-07 in the linear list back to 1 (enabled).
De-energize the main input circuit breaker and verify the HMI is no longer powered up.
Wait at least five minutes after removing power and measure the DC bus voltage between the +3
and terminals to confirm safe voltage level.
Lock-out incoming power.
Re-connect the motor or Transformer leads to output terminal block T1, T2, T3. Make sure that the drive
output connections are tightly connected before continuing to next step.

3.3.3 Drive Start Up


Once the drive has been set up and checked without the load connected, the drive is ready for startup.
Proceed with the following steps.




Navigate to the Underload Setup screen and set the Underload Current to the desired value.
From the Run Status screen, use the Setp soft key and the up / down arrow keys to set the frequency
reference to the desired operating frequency.
Press the Start button on the HMI.
With the drive running, check the output voltage and output current to ensure that they are within the
limits of the given application.
If any faults are present refer to Section 9 for troubleshooting.

PN: 196399 Revision: 6.6.2

19

GE Oil & Gas

3.4 Keypad Conventions


USB Port

F1

F2

F3

F4

F5

F1

START

STOP

START

STOP

Figure 3.9 Old Blue Box HMI Keypad

F3

F4

START START

197XXX

USB Port

F2

F5

STOP

STOP

197XXX
196783

Figure 3.10 New HMI Keypad

3.4.1 Soft keys


The 5 soft keys are located just below the LCD display and are labeled F1 through F5. The function of a soft
key is defined by the label in the rectangle on the LCD display just above the key. The function of a soft key
varies with the active screen.

3.4.2 Arrow Keys


The arrow keys are screen dependent but the following rules apply
Left and Right Arrows:
If a graph or a chart is displayed, re-draws the chart using older (left arrow) or newer (right arrow) data.
In the Linear List, displays the previous (left arrow) or next (right arrow) set of Linear List parameters.
In the Enter Password and Date / Time screens, selects the field to the left (left arrow) or the right (right
arrow) of the currently selected field.
Up and Down Arrows:
In the Run Status screen with the Setp soft key active, the up and down arrows adjust the set point up
(up arrow) and down (down arrow). The set point applies in the Current Control, Pressure Control, and
Frequency Control modes.
In screens where lists of parameters are displayed, moves the selection to the parameter above (up
arrow) or below (down arrow) the currently selected parameter.
In the Numeric Parameter Entry screen, the Password Entry screen, and the Date / Time Entry screen
adjusts the selected (highlighted) value up (up arrow) or down (down arrow).

imagination at work

VII

VECTOR
3.4.3 Start / Stop

The Start and Stop buttons work from all screens. Start will only start the drive if it is in the Ready state. Stop
has priority over any other key.

3.4.4

Status Indicator Screen Old HMI

The screen will change to display drive state information that can be seen from a distance whenever the
keypad is inactive for 5 minutes. Pressing any key will return the user interface to its normal state. NOTE:
Pressing the Stop key at any time whether the screen is in the normal or status indication mode will
stop the drive!

Drive status indicators are as follows:


Flashing Red
Drive stopped in Fault state.
Red
Drive stopped in Ready state.
Amber
Drive stopped in Restart state. Drive will automatically restart but the time to
restart is greater than 1 minute.
Flashing Amber Drive stopped in Restart or Standby state. Drive will automatically restart. If in
Restart state, the drive will restart in less than 1 minute. If in Standby state, the
drive will restart immediately whenever the standby switch closes.
Green
Drive running.

Flashing Green Drive running in Alarm state.

PN: 196399 Revision: 6.6.2

21

GE Oil & Gas

3.4.5 Status Indicator Screen New HMI


There are three high intensity LEDs located just above the screen. These corrGE Oil & Gasond with the
following indications as the Old HMI screens.

GE Oil & Gas

Drive State
Fault
Ready
Restart (more than 1 minute)
Restart (less than 1 minute)
Standby
Running
Running in Alarm

Stop (Red)
On
On
On
Flash

LED Indicators
Fault (Amber)
On
Off
Flash
Flash

Run (Green)
Off
Off
Off
Off

Off
Off

Off
Flash

On
On

3.5 Configuration
3.5.1 Drive Mode
Note: Refer to Section 3.3.1 for locations of control terminal block connections.
1. From the Run Status screen, select the Menu soft key and then select Log In. Enter the password and select
the OK soft key. (refer to Section 4.3 and 4.4 for log in information)
2. Select the Operating Mode screen and select the OK soft key.
3. Select the Drive Mode parameter and press the Edit soft key.
4. Select the desired Drive Mode.
i. Frequency Control Drive output frequency matches Frequency Setpoint.
ii. Analog Follower Drive speed follows the value of the analog signal (0 10V) connected to
terminal block connection A1. Note that this mode requires additional wiring.
1. Wire the analog input signal (0 10V) to A1 and common to AC
iii. Current Control In this mode the drive frequency is adjusted to maintain a desired output
current. This mode is often used with gassy wells. As the pump encounters gas pockets, the
drive current decreases. The drive speeds up and the gas bubbles are cleared from the system.
iv. Pressure Control In this mode the drive frequency is adjusted to maintain a desired intake or
exhaust pressure. Note: This mode requires additional wiring.
1. Wire the pressure sensor signal (0 10V, 4 20mA) to A2 and common to AC.
5. Press the OK soft key to accept the change.
Note: The user interface displays the Select screen if the drive mode has been changed.
6. Select the Operating Mode screen and press the OK soft key.
7. Select and edit any other parameters associated with the selected drive mode.

3.5.2 Frequency Behavior


1. From the Run Status screen, select the Menu soft key. If the Not Logged In
Selectscreen appears, then select Log In, enter the password, and select the OK soft
key.
2. Select the Frequency Setup screen and select the OK soft key.
3. Select and modify the frequency parameters as desired.

imagination at work

VII

VECTOR
3.5.3 Alarms and Restarts
1. From the Run Status screen, select the Menu soft key. If the Not Logged In Select
screen appears, then select Log In, enter the password, and select the OK soft key.
3. Select the Alarms Setup screen and select the OK soft key.
4. Select and modify the alarms and restart parameters as desired.
5. Select the Menu soft key and then select the Underload Setup screen.
6. Select and modify the Underload parameters as desired.

3.5.4 Motor Direction


From the Run Status screen, select the Menu soft key. If the Not Logged In Select screen appears, then select
Log In, enter the password, and select the OK soft key.
Select the Frequency Setup screen and select the OK soft key.
Select the Motor Direction parameter and modify as desired. Note that motor direction changes CAN be
implemented without stopping the drive. Set the direction as desired. Once the change has been made, press
the Start button. Drive will perform a controlled frequency ramp through 0 Hz to the setpoint frequency in the
specified motor direction.

PN: 196399 Revision: 6.6.2

23

GE Oil & Gas

4 Screen Descriptions
4.1 Run Status

Function:

The Run Status screen is the default screen when the drive is powered up. It displays all data needed to assess
the up-to-date state of the drive.

Field Descriptions:

Screen Name: Run Status. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. Possible values include Not Ready,
Ready, Accelerating, Decelerating, Running, Ready Rem(ote), Start Rem(ote), Run Remote, Stop
Rem(ote), Forced Stop, Fault, Restart (or RST time to restart), DRIVE OFF, Standby, Standby Remote.
Drive Serial Number: Serial number of the drive.
Drive Mode: Frequency Control. Designates the control mode of the drive. The mode can be changed in the
Operating Mode screen.
Date / Time: Date and time (mm/dd/yyyy hh:mm:ss)
Frequency Setpoint: 65.00 Hz. The up-to-date frequency setpoint. This field will not be present in some drive
control modes.
Output Current: 0.0 A. The up-to-date drive output current.
Output Frequency: 0.00 Hz. The up-to-date frequency being emitted by the drive.
Output Voltage: 0.0 V. The up-to-date voltage being emitted by the drive.
Motor Direction Indicator: If the motor is running forward (or set to run forward if drive is currently stopped), the
direction indicator will show a clockwise semi-circle arrow with an F adornment. If the drive is running in
reverse (or set to run in reverse if the drive is currently stopped), the direction indicator will show a counterclockwise semi-circle arrow with an R adornment.
User Selected Parameters: Intake Press, Intake Temp, Motor Temp, Discharge Press, Analog A1. Up to 5 user
selected parameters may be displayed on the run status screen. See the Setup screen for selecting these
parameters.
Graph: Output Frequency. Graph displaying 24 hours of graphical data. Graphed parameters include Output
Current, Output Voltage, Output Frequency, Analog A1, Analog A2, Intake Pressure, Intake Temperature, and
Motor Temperature. Please note that the last 3 parameters require a SmartGuard downhole tool. Note
that red lines in the graph denote data values that are interpolated between actual data values (usually
indicates that the drive was powered off).

imagination at work

VII

VECTOR
Keypad Functions:

F1: Graph. Used to select the parameter to be shown on the graph.


F2: Setp. Used to activate the setpoint change mode. When activated, the Setp button is displayed in black
with white text and the up and down arrows can be used to modify the setpoint. Note that the setpoint
field is also highlighted when setpoint change mode is activated. Setpoint change mode is automatically
cancelled after 45 seconds or can be deactivated by pressing F2 a second time.
F3: Scale. Modifies the scale of the graph. Scale values cycle 1x, 2x, 4x, 8x, 16x.
F4: Events. Activates the Events screen to display the 256 most recent events.
F5: Menu. Activates the menu allowing other screens to be accessed.
Up Arrow: Increases the setpoint in the Current Control, Pressure Control, and Frequency Control modes (when
setpoint change mode is active).
Down Arrow: Decreases the setpoint in the Current Control, Pressure Control, and Frequency Control modes
(when setpoint change mode is active).
Left Arrow: If graph scale is 1x, draws the graph for the previous day. If graph scale is > 1x, allows scrolling
through the scaled graph data.
Right Arrow: If graph scale is 1x, draws the graph for the next day. If graph scale is > 1x, allows scrolling through
the scaled graph data.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

25

GE Oil & Gas

4.2 Event Log

Function:

The Event Log screen displays the last 256 time-stamped events, included drive starts and stops, faults, and
parameter changes.

Field Descriptions:

Screen Name: Event Log. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Time-stamped Events: List of the last 256 events.

Keypad Functions:

F1: Prev. View older events.


F2: Next. View newer events.
F3: Not used.
F4: Not used.
F5: Status. Return to the Run Status Screen.
Up Arrow: Not used.
Down Arrow: Not used.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

imagination at work

VII

VECTOR
4.3 Select Screen (Not logged in)

Function:

The Select Screen allows the user to select and display a different screen. The not logged in version of the
select screen prevents non-privileged users from accessing most setup parameters.

Field Descriptions:

Screen Name: Select Screen. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
List of screens that can be selected.

Keypad Functions:

F1: Unlabeled. Activate the Keypad Test screen.


F2: Not used.
F3: Startup. Activate the Startup Control. Use this screen to enable or disable the drive and to enable or disable
automatic restarts.
F4: Not used.
F5: OK. Proceed to the highlighted screen. Note that the Run Status screen is always highlighted by default
when the Select Screen is drawn.
Up Arrow: Move selection up the list.
Down Arrow: Move selection down the list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

27

GE Oil & Gas

4.4 Enter Password

Function:

The Enter Password screen allows the user to log in. Once logged in, the user has access to all screens and setup
parameters.

Field Descriptions:

Screen Name: Enter Password Screen. This field is the name of the displayed screen.
Password digits to edit.

Keypad Functions:

F1: OK. Accept the entered password. If the password is correct, the Select Screen (Logged in) will be drawn.
F2: CANCEL. Return to the Select Screen.
F3: Not used.
F4: Not used.
F5: Not used.
Up Arrow: Increment the highlighted password digit.
Down Arrow: Decrement the highlighted password digit.
Left Arrow: Select the digit to the left of the currently selected digit.
Right Arrow: Select the digit to the right of the currently selected digit.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.
Note that the default password on the drive is 3333. However, the password can be changed in the Misc. Setup
screen.
If the password is forgotten, please contact your local GE Oil & Gas, Inc service center.

imagination at work

VII

VECTOR
4.5 Select Screen (Logged in)

Function:

The Select Screen allows the user to select and display a different screen. The Logged in version of the
select screen provides access to all screens and setup parameters.

Field Descriptions:

Screen Name: Select Screen. This field is the name of the displayed screen.
Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the
Run Status screen description.
List of screens that can be selected.
Use the following screens to configure the drive:
Operating Mode
Alarms Setup
Underload Setup
Start Control
Frequency Setup
Analog 1 Setup
Analog 2 Setup
Misc Setup
Comm Setup
Hard Starting
Maintenance
The setup screens are listed together in the right column on this screen.

Note: Screens in the left column tend to be informational.

PN: 196399 Revision: 6.6.2

29

GE Oil & Gas


Keypad Functions:
F1: Unlabeled. Activate the Keypad Test screen.
F2: Not used.
F3: Startup. Activate the Startup Control. Use this screen to enable or disable the drive and to enable or disable
automatic restarts.
F4: Not used.
F5: OK. Proceed to the highlighted screen. Note that the Run Status screen is always highlighted by default
when the Select Screen is drawn.
Up Arrow: Move selection up the list. Note that at the top of the list the selection will move to the bottom of the
list.
Down Arrow: Move selection down the list. Note that at the bottom of the list the selection will move to the top
of the list.
Left Arrow: Move selection to the left column.
Right Arrow: Move selection to the right column.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

imagination at work

VII

VECTOR
4.6 Fault Status

Function:

The Fault Status screen allows the user to determine the state of all drive faults. Note that this screen can be
chosen from the Select Screen and is automatically entered when a fault is detected.

Field Descriptions:

Screen Name: Fault Status. This field is the name of the displayed screen.
Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Any active fault or feature that is not in its OK state is displayed.

Keypad Functions:

F1: Not used.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select Screen.
Up Arrow: Not used.
Down Arrow: Not used.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive if running. If in the fault state, pressing STOP will attempt to clear the faults.

PN: 196399 Revision: 6.6.2

31

GE Oil & Gas

4.7 Amp Chart

Function:

The Amp Chart screen displays 1 or 7 days worth of current data in the familiar circular format. Current data is
taken every 10 seconds. The current log is sized to hold 7 days of current data.

Field Descriptions:

Screen Name: Amp Chart. This field is the name of the displayed screen.
Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Outer Ring: 1 A. Displays the current associated with the outer circle of the amp chart.
Resolution: 0.1 A. Displays the current resolution (current difference between adjacent lines) of the amp chart.
Date: 12/01/2008. The day associated with the amp chart. On a 7 day amp chart the date displayed is for the
newest displayed data.
Output Current: 0.2 A. Displays the up-to-date drive output current.

Keypad Functions:

F1: Today. Draws the amp chart associated with todays date.
F2: Not used.
F3: 1/7 Day. Toggles the amp chart between a 1 day and a 7 day scale.
F4: Not used.
F5: Menu. Return to the Select Screen.
Up Arrow: Not used.
Down Arrow: Not used.
Left Arrow: Draw the amp chart associated with the preceding day.
Right Arrow: Draw the amp chart associated with the following day.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive if running.

imagination at work

VII

VECTOR
4.8 Trending

Function:

The Trending screen displays graphs containing 5 days worth of data. Graph data is taken from the Data log and
is sized to hold 35 days worth of data (with data taken every 5 minutes).

Field Descriptions:

Screen Name: Trending. This field is the name of the displayed screen.
Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Graph: Output Frequency (Hz). Graph displaying 5 days of graphical data. Graphed parameters include Output
Current, Output Voltage, Output Frequency, Analog A1, Analog A2, Intake Pressure, Intake Temperature, and
Motor Temperature. Please note that the last 3 parameters require a SmartGuard downhole tool. Note
that red lines in the graph denote data values that are interpolated between actual data values.
Statistics: Min Value, Max Value, Average, RMS. Values calculated from the 5 days of data from the data log.

Keypad Functions:

F1: Graph. Used to select the parameter to be shown on the graph.


F2: Not used.
F3: Scale. Modifies the scale of the graph. Scale values cycle 1x, 2x, 4x, 8x, 16x.
F4: Not used.
F5: Menu. Activates the menu allowing other screens to be accessed.
Up Arrow: Not used.
Down Arrow: Not used.
Left Arrow: If graph scale is 1x, draws the graph for the previous 5 day period. If graph scale is > 1x, allows
scrolling through the scaled graph data.
Right Arrow: If graph scale is 1x, draws the graph for the next 5 day period. If graph scale is > 1x, allows scrolling
through the scaled graph data.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive if running.

PN: 196399 Revision: 6.6.2

33

GE Oil & Gas

4.9 History Screen

Function:

The History screen displays logged performance data.

Field Descriptions:

Screen Name: History Screen. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Time-stamped History Entries: The data log is circular log sized to store the last 35 days of data. Data is
captured every 5 minutes.

Keypad Functions:

F1: Prev. View older logged data.


F2: Next. View newer logged data.
F3: Set. View a different set of data. Currently there are 4 sets of data. The first set is shown. The other sets
include more drive parameters and parameters retrieved from a SmartGuard downhole tool.
F4: Save. Save the Data Log, the Event Log, the Current Data (used for the Amp Chart), and the drive
configuration to a USB Flash drive. This device must be placed in the drives USB port for 10 seconds prior to
activating the function. All files saved will be saved with the drives programmed serial number and the date
the data was retrieved.
F5: Menu. Return to the Select screen.
Up Arrow: Not used.
Down Arrow: Not used.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.
Note: To save history data, refer to Appendix 3.1

imagination at work

VII

VECTOR
4.10

Setup Screen

Function:

The Setup screen allows any user (no login required) to modify the parameters on this screen.

Field Descriptions:

Screen Name: Setup. This field is the name of the displayed screen.
Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Language: Allows the user to change between English and Spanish
Date Format: Allows the user to choose between mm/dd/yyyy (default), dd/mm/yyyy, and dd-Mmm-yyyy (01Jan-2010) as the format the date will be displayed.
Local/Remote: Parameter that determines if control of the drive (Start / Stop and Frequency Reference) is under
control of the drive user interface or a remote 2-wire host.
Control Location: Gives the user the ability to control the drive from Keypad, SCADA or both.
Drive Output: Set to Disabled to inhibit the drives rGE Oil & Gasonse to all start commands.
User Selected 1 5: The parameters selected in these fields are displayed on the Run Status screen.
Parameter Description: Local Control / Remote Control Provides user with information concerning the
selected (highlighted) parameter.
General Help: Use Up and Down arrows General help information on how to use this screen. Note that some
parameters may not be changed when the drive is running. The General Help will state that the drive must
be stopped when such a parameter is selected and the drive is running.
Note: Any parameter that is different from its default value is denoted by an asterisk (*) to the right of its value.

PN: 196399 Revision: 6.6.2

35

GE Oil & Gas


Keypad Functions:

F1: Edit. Edit the selected (highlighted) parameter.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

imagination at work

VII

VECTOR
4.11

SmartGuard

Function:

The SmartGuard screen reports the current state of the SmartGuard interface.

Field Descriptions:

Screen Name: SmartGuard. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.

SmartGuard Data: Displays the state of the SmartGuard data:


Disabled - Interface disabled
SG Fault Relay: Displays the state of the SmartGuard fault relay.
OK - Data is valid, Bad - SmartGuard unit is reporting loss of sync.
When the data state is disabled or bad, all SmartGuard readings are set to 0.
SmartGuard Comms: Displays the communication efficiency of the communications link with the SmartGuard.
100% indicates all messages to the SmartGuard are successful.
SmartGuard Sensor Values Intake Press, Intake Temp, Motor Temp, Discharge Pressure, Vibration, Leakage
Current, Uphole Voltage, and SG Duty Cycle are displayed in their appropriate units
SmartGuard State: Displays the value of the SmartGuard fault detection state machine. Values include Initializing,
OK, Fault, and Restart. Note that this parameter stays in the Init state if the SmartGuard interface is disabled.

Keypad Functions:

F1: Not used.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Not used.
Down Arrow: Not used.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

37

GE Oil & Gas

4.12

Drive I/O

Function:

The Drive I/O screen allows the operator to easily determine the state of all the drive I/O.

Field Descriptions:

Screen Name: Drive I/O. This field is the name of the displayed screen.
Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
S1 S8: Drive digital inputs. Note: S8 is not available. These values will be 0 or 1 if the input is not used or if its
function is disabled. If the function associated with the input is enabled (i.e. external fault 1, standby, and
Breaker 2 detection features are enabled on the Misc Setup screen), more descriptive text will be displayed
(OK, FAULT, RUN, STANDBY).
M1-M2, M3-M4: Drive digital outputs.
Analog 1, Analog 2: Drive analog inputs. The values are scaled as programmed in the Analog 1 Setup and
Analog 2 Setup screens.
General Help: Press Menu soft key General help information on how to use this screen.

Keypad Functions:

F1: Not used.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Not used.
Down Arrow: Not used.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

imagination at work

VII

VECTOR
4.13

Last Fault

Function:

The Last Fault screen allows the operator the ability to easily view the drive condition when the last fault
occurred.

Field Descriptions:

Screen Name: Last Fault. This field is the name of the displayed screen.
Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Parameter Values: Values of key parameters when the drive last faulted. Selecting the fault code parameter will
bring up a window that explains the fault code. Selecting a bitmap parameter (one displayed in hexadecimal
format) will bring up a window that describes the meaning of all set bits.
General Help: Press Menu soft key General help information on how to use this screen.

Keypad Functions:

F1: Not used.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

39

GE Oil & Gas

4.14

All Monitors

Function:

The All Monitors screen displays a variety of parameters that may be useful for troubleshooting problems in the
field.

Field Descriptions:

Screen Name: All Monitors. This field is the name of the displayed screen.
Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Drive Monitor Registers: Most of the parameters displayed are directly from the underlying drive. See table
below for explanation of bitmapped (displayed in hexadecimal) registers.
Drive Comms: Displays the quality of the communications with the drive over the last 30 seconds.
SmartGuard Comms: Displays the quality of the communications with the SmartGuard Surface Unit (always set
to 100% if the SmartGuard is disabled in the Misc Setup screen).
Cabinet Temp: Displays internal drive temp from the power module heat sink with old HMI. With the new HMI, the
temperature is taken from the new HMI.
UI S/W Rev: Displays the revision of the User Interface software.
O/S Build: Displays the date of the Windows CE operating system version installed on the HMI.
General Help: Press Menu soft key General help information on how to use this screen.
Note: You may use the up and down arrow keys to select monitor values. Selecting the fault code parameter will
bring up a window that explains the fault code. Selecting a bitmap parameter (one displayed in hexadecimal
format) will bring up a window that describes the meaning of all set bits.

imagination at work

VII

VECTOR
Bit
0
1
2
3
4
5
6
7F

Drive Status
0 Denotes
Drive Stopped
Forward Operation
Drive Startup in Progress
No Fault
No Data Setting Error
Digital Output 1 is OFF
Digital Output 2 is OFF
Not Used

1 Denotes
Drive Running
Reverse Operation
Drive Startup Completed
Fault
Data Setting Error
Digital Output 1 is ON
Digital Output 2 is ON
Not Used

Fault Details
Bit
0
1
2
3
4
5
6
7
8
9
A
B
C

0 Denotes
No Error
No Error
No Error
No Error
Not Used
No Error
No Error
No Error
No Error
No Error
No Error
No Error
No Error

D
E
F

No Error
No Error
HMI Connected

1 Denotes
Over current or Ground Fault Error
Main Circuit Overvoltage
Drive Overload
Drive Overheat
Not Used
Fuse Blown
PI Feedback Reference Lost
External Error
Hardware Error
Motor Overload or Overtorque
Underload Fault
Main Circuit Undervoltage
Main Circuit Undervoltage, Control Power
Supply Error, Inrush Prevention Circuit Error,
or Power Loss
Missing Output Phase
ModBus Comm Error
HMI Disconnected

Drive Fault Code


Current Fault exhibited by drive.
(There are a few codes that are not included in the Fault Details
bitmapped list above.)
0 No Fault
25 DEV Speed Deviation
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

PUF DC Bus Fuse Open


UV1 DC Bus Undervolt
UV2 Ctl PS Undervolt
UV3 MC Answerback
SC Short Circuit
GF Ground Fault
OC Over current
OV DC Bus Overvolt
OH Heatsink Overtemp
OH1 Heatsink Max Temp
OL1 Motor Overload
OL2 Inverter Overload
OL3 Overtorque 1
OL4 Overtorque 2
RR DynBrk Transistor
RH DynBrk Resistor
EF3 External Fault 1
EF4 External Fault 2
EF5 Fault Not Enabled
EF6 Fault Not Enabled
EF7 Breaker 2 Fault
EF8 Fault Not Enabled
FAN Cooling Fan Error
OS Overspeed Detect

26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48

OVL Enhanced O-load


PF Input Phase Loss
LF Output Phase Loss
OH3 Motor Overheat 1
OPR HMI Disconnect
ERR EEPROM R/W Err
OH4 Motor Overheat 2
CE Serial Com Err
BUS Option Com Err
E-15 SI-F/G Com Err
E-10 SI-F/G CPU Down
CF Out of Control
SVE Zero Servo Fault
EF0 Opt External Fault
FBL Feedback Loss
LL3 Loss of Load
UL4 Undertorq Det 2
OL7 HSB-OL
ULF Underload
A1-HI Terminal A1 High
A1-LO Terminal A1 Low
A2-HI Terminal A2 High
A2-LO Terminal A2 Low

PN: 196399 Revision: 6.6.2

41

GE Oil & Gas


Data Link Status
Bit
0
12
3
4
5F

0 Denotes
Not Writing Data
Not Used
No Range Error
No Integrity Error
Not Used

1 Denotes
Writing Data
Not Used
Upper or Lower Limit Errors
Data Integrity Error
Not Used

Digital Inputs
Bit
0
1
2
3
4
5
6
7-F

0 Denotes
Input 9 OFF
Input 9 OFF
Input 9 OFF
Input 9 OFF
Input 9 OFF
Input 9 OFF
Input 9 OFF
Not Used

1 Denotes
Input 9 ON
Input 10 ON
Input 11 ON
Input 12 ON
Input 13 ON
Input 14 ON
Input 16 ON
Not Used

Drive Status 2
Bit
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F

0 Denotes
Drive Stopped
Drive not at Zero Speed
Drive Freq does not match internal speed
Drive is not at Setpoint (accelerating)
Freq Detect 1 Not Active
Freq Detect 2 Not Active
Drive Startup in Progress
No Low Voltage Detected
Drive Output Baseblock is Not Active
Freq Reference Mode is Communicating
Run Command Mode is Communicating
Overtorque is Not Detected
Frequency Reference OK
Retrying is Not in Progress
No Error
ModBus Comm Timeout is Not Detected

imagination at work

1 Denotes
Drive Running
Drive at Zero Speed
Drive Freq matches internal speed
Drive is at Setpoint
Freq Detect 1 Active
Freq Detect 2 Active
Drive Startup Complete
Low Voltage Detected
Drive Output Baseblock is Active
Freq Ref Mode is Not Communicating
Run Cmd Mode is Not Communicating
Overtorque is Detected
Frequency Reference Lost
Retrying in Progress
Error
ModBus Comm Timeout Detected

VII

VECTOR
Digital Output Status
Bit
0
1
2F

0 Denotes
Digital Output 1 OFF
Digital Output 2 OFF
Not Used

1 Denotes
Digital Output 1 ON
Digital Output 2 ON
Not Used

Communication Error
Bit
0
1
2
3
4
5
6
7F

0 Denotes
No Error
No Error
Not Used
No Error
No Error
No Error
No Error
Not Used

1 Denotes
CRC Error
Invalid Data Length
Not Used
Parity Error
Overrun Error
Framing Error
Timeout
Not Used

Keypad Functions:

F1: Not used.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

43

GE Oil & Gas

4.15

Run Info

Function:

Displays current running information

Field Descriptions:

Screen Name: Run Info. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.

Keypad Functions:

F1: Not used.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu
Up Arrow: Not used
Down Arrow: Not used
Left Arrow: Not used
Right Arrow: Not used
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

imagination at work

VII

VECTOR
4.16

Set Date and Time


Function:

The Set Date and Time screen allows the user to adjust the date and time on the drives real-time clock.

Field Descriptions:

Screen Name: Set Date and Time Screen. This field is the name of the displayed screen.
Date and Time fields to edit.
(mm/dd/yyyy hh:mm 24 hour display)

Note: Selectable date format is adjusted on the Setup Screen.

Keypad Functions:

F1: OK. Accept the new date and time.


F2: CANCEL. Do not change the date and time. Return to the Select Screen.
F3: Not used.
F4: Not used.
F5: Not used.
Up Arrow: Increment the highlighted date / time field.
Down Arrow: Decrement the highlighted date / time field.
Left Arrow: Select the field to the left of the currently selected field.
Right Arrow: Select the field to the right of the currently selected field.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

45

GE Oil & Gas

4.17

Linear List Menu

Function:

The Linear List menu allows the user to quickly jump to the desired section of the linear list - the registers in the
inverter unit. The values of the parameters in the Linear List should only be modified upon recommendation of
GE Oil & Gas, GE OIL & GAS Engineering.

Field Descriptions:

Screen Name: Linear List. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Drive Register Names: A group of 10 drive registers spread throughout the drive register map.
General Help: Use Up and Down arrows General help information on how to use this screen.
Note: See Appendix 4 for full Linear List Parameters, functions, ranges and default settings.

Keypad Functions:

F1: OK. Jump to the page of the Linear List that begins with the selected register.
F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

imagination at work

VII

VECTOR
4.17.1

Linear List

Function:

The Linear List reveals the registers in the inverter. The values of the parameters in the Linear List should only be
modified upon recommendation of GE Oil & Gas, GE OIL & GAS Engineering.

Field Descriptions:

Screen Name: Linear List. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Drive Register Names: A group of 10 drive registers that can be modified. See Appendix 4 for complete linear list
General Help: Use Up and Down arrows General help information on how to use this screen. Note that some
parameters may not be changed when the drive is running. The General Help will state that the drive must
be stopped when such a parameter is selected and the drive is running.
Note: Any parameter that is different from its default value is denoted by an asterisk (*) to the right of its value.

Keypad Functions:

F1: Edit. Edit the selected (highlighted) parameter.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Linear List Menu screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Display the previous set of 10 registers.
Right Arrow: Display the next set of 10 registers.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

47

GE Oil & Gas

4.18

Operating Mode

Function:

The Operating Mode screen allows a logged on user to choose the operating mode of the drive and to set
operating mode specific parameters.
Note: This screen changes based on the drives operating mode. By default the drive operating mode is
Frequency Control. Section 3.6.1 describes all drive operating modes.

Operating Modes:
Frequency Control Section 4.18.2
Analog Follower - Section 4.18.3
Current Control - Section 4.18.4
Pressure Control - Section 4.18.5

imagination at work

VII

VECTOR
4.18.1

Selection Parameter Change

Function:

The Selection Parameter Change screen is drawn when the Edit soft key is activated in the Operating Mode
screen with the Drive Mode parameter selected. In this screen the user selects the drive operating mode option
that is desired.

Field Descriptions:

Screen Name: Selection Parameter Change Screen. This field is the name of the displayed screen.
Parameter Name and present value: Drive Mode: Frequency Control. Shows the name of the parameter being
edited as well as the present selection.
Parameter Description: Defines the operational mode of the drive. Gives a text description of the parameter
being edited.
Options: Current Control, . Displays the options that may be selected.

Keypad Functions:

F1: OK. Accept the highlighted option as the value of the parameter.
F2: CANCEL. Abort the editing procedure and retain the present value of the parameter.
F3: Not used.
F4: Not used.
F5: Not used.
Up Arrow: Select (highlight) the option above the currently selected option (wraps at top back to bottom of list).
Down Arrow: Select (highlight) the option below the currently selected option (wraps at bottom back to top of
list).
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

49

GE Oil & Gas

4.18.2

Operating Mode Frequency Control

Function:

The Operating Mode Frequency Control screen allows the user to set the parameters associated with frequency
control mode.

Field Descriptions:

Screen Name: Operating Mode. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Drive Mode: Parameter that defines the operational mode of the drive. Options include Current Control, Pressure
Control, Frequency Control, and Analog Follower.
Frequency Setpoint: The frequency setpoint when the drive is running. Note that Frequency Setpoint is a
parameter associated with Frequency Control mode; other parameters will be displayed in other control
modes.
Startup Mode: When the Startup Mode is set to ONCE, the drive will ramp up to the Setp1 Frequency for the
Setp1 Time and then return to the original Frequency setpoint. This function will only be activated on the
next startup and then turned OFF. When the Startup Mode is set to ON, this procedure will occur on every
startup.
Setp1 Frequency: The frequency the drive will ramp up to when the Startup mode is activated. It will remain at
this frequency for the duration of the Setp1 Time and then return to the original Frequency Setpoint.
Setp1 Time: The duration the Setp1 Frequency will run when the Startup mode is activated. After this time
expires the Frequency Setpoint is resumed.
Run Ramp Time: Transitions between running frequencies can be programmed to take an extended amount of
time.
1. The extended ramp time does not affect drive start or drive stop, only setpoint changes while the
drive is running.
2. The extended ramp time is only available in Frequency Control mode.
3. The specified ramp time is independent of frequency range change.
4. Ramp time will be aborted if the drive is stopped or faulted.
While running at the Setp1 frequency, the drive state will show Run-Setp1.
Parameter Description: Defines the operational Provides user with information concerning the selected
(highlighted) parameter.

imagination at work

VII

VECTOR
General Help: Use Up and Down arrows General help information on how to use this screen. Note that some
parameters may not be changed when the drive is running. The General Help will state that the drive must
be stopped when such a parameter is selected and the drive is running.
Note: Any parameter that is different from its default value is denoted by an asterisk to the right of its value.

Keypad Functions:

F1: Edit. Edit the selected (highlighted) parameter.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

51

GE Oil & Gas

4.18.3

Operating Mode - Analog Follower

Function:

The Operating Mode Analog Follower screen allows the user to set the parameters associated with signal
follower mode.

Field Descriptions:

Screen Name: Operating Mode. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Drive Mode: Parameter that defines the operational mode of the drive. Options include Current Control, Pressure
Control, Frequency Control, and Analog Follower.
Signal Source: Fixed to Analog Input A1.
Minimum Frequency: The minimum frequency the drive is allowed to run.
Input at Min Freq: The analog input value (in Volts) that signifies the drive should be running at its minimum
allowed frequency.
EU Value Min: The display value (in Engineering Units) associated with the value of Input at Min Freq.
Maximum Frequency: The maximum frequency the drive is allowed to run.
Input at Max Freq: The analog input value (in Volts) that signifies the drive should be running at its maximum
allowed frequency.
EU Value Max: The display value (in Engineering Units) associated with the value of Input at Max Freq.
Analog In A1 Units: Defines the engineering units used when displaying the analog value.
Parameter Description: Defines the operational Provides user with information concerning the selected
(highlighted) parameter.
General Help: Use Up and Down arrows General help information on how to use this screen. Note that some
parameters may not be changed when the drive is running. The General Help will state that the drive must
be stopped when such a parameter is selected and the drive is running.
Note: Any parameter that is different from its default value is denoted by an asterisk (*) to the right of its value.

imagination at work

VII

VECTOR
Keypad Functions:

F1: Edit. Edit the selected (highlighted) parameter.


F2, F3, F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.

STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

53

GE Oil & Gas

4.18.4

Operating Mode Current Control

Function:

The Operating Mode Current Control screen allows the user to set the parameters associated with current
control mode.

Field Descriptions:

Screen Name: Operating Mode. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Drive Mode: Parameter that defines the operational mode of the drive. Options include Current Control, Pressure
Control, Frequency Control, and Analog Follower.
Current Setpoint: Desired current. If the drive current falls below the setpoint, the drive will speed up to try to
restore the current (up to the maximum frequency defined on the Frequency Setup screen). If the current
exceeds the setpoint, the drive will slow to lesson the current (down to the minimum frequency defined on
the Frequency Setup screen).
Current Freq Limit: Upper frequency limit for the drive to run in Current Control mode. Unlike the maximum
frequency (See Frequency Setup screen), this limit can be changed while the drive is running.
PI Proportional: Proportional constant for the proportional integral (PI) control system.
PI Integral: Integral constant for the PI control system.
Parameter Description: Defines the operational Provides user with information concerning the selected
(highlighted) parameter.
General Help: Use Up and Down arrows General help information on how to use this screen. Note that some
parameters may not be changed when the drive is running. The General Help will state that the drive must
be stopped when such a parameter is selected and the drive is running.
Note: Any parameter that is different from its default value is denoted by an asterisk (*) to the right of its value.

imagination at work

VII

VECTOR
Keypad Functions:

F1: Edit. Edit the selected (highlighted) parameter.


F2, F3, F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

55

GE Oil & Gas

4.18.5

Operating Mode Pressure Control

Function:

The Operating Mode Pressure Control screen allows the user to set the parameters associated with pressure
control mode.

Field Descriptions:

Screen Name: Operating Mode. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Drive Mode: Parameter that defines the operational mode of the drive. Options include Current Control, Pressure
Control, Frequency Control, and Analog Follower.
Pressure Source: Selects the location of the pressure sensor at the pump Intake, pump Discharge, or
SmartGuard Intake.
Pressure Setpoint: Desired pressure. If the measured pressure (Discharge is the source) falls below the setpoint,
the drive will speed up to try to restore the pressure (up to the maximum frequency defined on the Frequency
Setup screen). If the pressure exceeds the setpoint, the drive will slow to lesson the pressure (down to the
minimum frequency defined on the Frequency Setup screen). The drive adjusts the frequency in the opposite
direction if the pressure source is Intake.
PI Proportional: Proportional constant for the proportional integral (PI) control system.
PI Integral: Integral constant for the PI control system.
Analog 2 Type: Select between 0 10V or 4 20mA
A2 Input Voltage 1, Engineering Units 1: Values used to define 1 point on the sensor curve. Used in conjunction
with the following parameters to calculate the analog gain and bias. Note that the voltage can also be a
current if set to 4 20mA mode.
A2 Input Voltage 2, Engineering Units 2: Values used to define the second point on the sensor curve. Used in
conjunction with the previous 2 parameters to calculate the analog gain and bias. Note that the voltage can
also be a current if set to 4 20mA mode.
Analog In A2 Units: Defines the engineering units used when displaying the specified analog value.
Parameter Description: Defines the operational Provides user with information concerning the selected
(highlighted) parameter.
General Help: Use Up and Down arrows General help information on how to use this screen. Note that some
parameters may not be changed when the drive is running. The General Help will state that the drive must
be stopped when such a parameter is selected and the drive is running.
Note: Any parameter that is different from its default value is denoted by an asterisk (*) to the right of its value.

imagination at work

VII

VECTOR
Keypad Functions:

F1: Edit. Edit the selected (highlighted) parameter.


F2, F3, F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

57

GE Oil & Gas

4.19 Alarms Setup

Function:

The Alarms Setup screen allows a logged on user to set the overload limits as well as the standard restart
parameters.

Field Descriptions:

Screen Name: Alarms Setup. This field is the name of the displayed screen.
Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Motor Amps: Defines the Motor rated Amps. Drive must be stopped to adjust this parameter.
Motor Overload Amps: Defines the maximum current that should be delivered to the transformer / motor
circuit. The overload trip time is based on an I2T overload calculation. The delay varies with the extent of the
overload current.
Oload Time Const: Time the drive will run at 133% of the Motor Overload Amps setting before shutting down
on a Motor Overload Fault. Set the Oload Time Const to a lower value to shut the drive down faster. Factory
default is 8 minutes.
Oload Start Delay: Defines the amount of time that the overload condition will be ignored when the drive is
started.
Overload Restart: Defines whether the drive will attempt to auto-restart on a motor overload fault. Note: Auto
Restart (see Startup Control screen) must be enabled for any restarts to occur.
Overload @ Min Freq: In conjunction with the Overload Delay parameter, defines an enhanced motor protection
mode. This parameter is in terms of % of Motor Overload Amps. Setting this parameter to 0% (default value)
disables the enhanced overload protection mode. See figure below for details.
Overload Delay: Defines the amount of time that an enhanced protection mode overload condition will be
ignored before declaring a motor overload fault.
Restart Tries: The number of times the drive will automatically try to restart on a non-Underload fault. Set this
value to 0 to disable retries. Note that Auto Restart (see Startup Control screen) must be enabled for any
restarts to occur.
Restart Delay: The time delay after a fault before the drive will attempt a restart.
Restart Clear Time: Defines the time the drive must run without additional faults after a restart before the fault is
considered clear and the restart counter is reset.

imagination at work

VII

VECTOR
Parameter Description: Maximum current allowed to transformer Provides user with information concerning
the selected (highlighted) parameter.
General Help: Use Up and Down arrows General help information on how to use this screen.
Note: Some parameters may not be changed when the drive is running. The General Help will state that the
drive must be stopped when such a parameter is selected and the drive is running.
Note: Any parameter that is different from its default value is denoted by an asterisk (*) to the right of its value.

Keypad Functions:

F1: Edit. Edit the selected (highlighted) parameter.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

Enhanced Motor Protection functionality.

PN: 196399 Revision: 6.6.2

59

GE Oil & Gas

4.20 Underload Setup

Function:

The Underload Setup screen allows a logged on user to set the Underload limits.

Field Descriptions:

Screen Name: Underload Setup. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Underload Current: Defines the minimum running current allowed to the motor system. The drive will fault if the
output current is less than the Underload current for a time that exceeds the Underload Delay.
Uload Start Delay: Defines the amount of time that the Underload condition will be ignored when the drive is
started.
Underload Delay: Defines the amount of time the drive will run with a current less than the Underload current
before faulting.
Uload Restart Tries: Number of times to attempt to restart after an Underload fault. This restart count applies
only to the Underload fault and is independent of the general fault restart tries value below. Set this value to
0 to disable Underload restarts. Note that Auto Restart (see Startup Control screen) must be enabled for any
restarts to occur.
Uload Restart Time: Defines the delay between the drive fault and a restart. Uses the Uload Restart Tries
parameter to determine if a restart should be attempted.
Uload Restart OK: Defines the time the drive must run without an Underload condition after a restart before the
fault is considered cleared and the restart counter is reset.
Underload @ Min Freq: Defines an enhanced motor protection mode. This parameter is in terms of % of
Underload Current. Setting this parameter to 100% (default value) disables the enhanced Underload
protection mode. See figure in section 2.20 for details.
Parameter Description: Minimum allowed drive current without a fault Provides user with information
concerning the selected (highlighted) parameter.
General Help: Use Up and Down arrows General help information on how to use this screen. Note that some
parameters may not be changed when the drive is running. The General Help will state that the drive must
be stopped when such a parameter is selected and the drive is running.
Note: Any parameter that is different from its default value is denoted by an asterisk (*) to the right of its value.

imagination at work

VII

VECTOR
Keypad Functions:

F1: Edit. Edit the selected (highlighted) parameter.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

61

GE Oil & Gas

4.21 Start Control

Function:

The Start Control screen allows a logged on user to set Restart on power loss and Ride thru Restart.

Field Descriptions:

Screen Name: Start Control. This field is the name of the displayed screen.
Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Restart on Power Loss: When Restart on Power Loss is enabled and Auto Restart on the Startup screen is
enabled, the drive will automatically start after a power failure. This will cause the drive to return to its running
state at time of shut down. The restart delay used is the Restart Delay on the Alarms Setup screen. The drive will
run through the programming it has been set up such as ramp times, Hard Start, etc.
Ride Thru Restart: For systems where the HMI is connected to a UPS allowing the HMI to ride through power
losses. Enabling the Ride thru restart and the Auto Restart on the Startup screen as well as restart tries on the
Alarm setup screen is greater than 0, this will restart the drive according to the Restart Delay on the Alarms Setup
screen.
Start Holdoff Time: Setting the Holdoff Time to a non-zero value will restrict manually starting the drive until the
drive has been stopped for the programmed time. Pressing the Start button before the holdoff time has expired
will cause the drive to enter a restart state and then start when the holdoff time has expired. This feature is
designed to allow well conditions to return to a safe state before allowing a restart (i.e. waiting for Back Spin to
finish).

Field Descriptions:

Screen Name: Start Control. This field is the name of the displayed screen.
Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Restart on Pwr Loss: Defines whether the drive will attempt to auto-restart on a power loss fault. Note: Auto
Restart (see Startup Control screen) must be enabled for any restarts to occur.
Ride Thru Restart: Defines whether the drive will attempt to auto-restart on a drive power loss with the HMI still
powered fault.

imagination at work

VII

VECTOR
Note: Auto Restart (see Startup Control screen) must be enabled for any restarts to occur.
Start Holdoff Time: Defines the amount of time the drive will restrict starting after it has stopped.
General Help: Use Up and Down arrows General help information on how to use this screen. Note: Some
parameters may not be changed when the drive is running. The General Help will state that the drive must
be stopped when such a parameter is selected and the drive is running.
Note: Any parameter that is different from its default value is denoted by an asterisk (*) to the right of its value.

Keypad Functions:

F1: Edit. Edit the selected (highlighted) parameter.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

63

GE Oil & Gas

4.22 Numeric Parameter Change

Function:

The Numeric Parameter Change screen is drawn when the Edit soft key is activated on a numeric parameter. The
user adjusts the parameter to the desired value.

Field Descriptions:

Screen Name: Numeric Parameter Change Screen. This field is the name of the displayed screen.
Parameter Name and present value: Maximum Frequency: 65 Hz. Shows the name of the parameter being
edited as well as its present value.
Parameter Description: Maximum frequency that will be emitted by the drive. Gives a text description of the
parameter being edited.
Min, Max, Def: Provides the parameters minimum allowed value, maximum allowed value, and default value.
Highlighted value: The value that is adjusted as the user presses the Up and Down arrow keys.

Keypad Functions:

F1: OK. Accept the highlighted value as the value of the parameter.
F2: CANCEL. Abort the editing procedure and retain the present value of the parameter.
F3: Not used.
F4: Not used.
F5: Not used.
Up Arrow: Increase the highlighted value. Note that the change step size increases as the button is held down.
Note that the value can not be adjusted higher than the Max value displayed.
Down Arrow: Decrease the highlighted value. Note that the change step size increases as the button is held
down. Note that the value can not be adjusted lower than the Min value displayed.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

imagination at work

VII

VECTOR
4.23 Frequency Setup

Function:

The Frequency Setup screen allows a logged on user to define the frequency behavior of the drive.

Field Descriptions:

Screen Name: Frequency Setup. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
V/F Select: Defines the V/F curve utilized by the drive. Options include 60Hz/Std Torque, 60Hz/Med Torque, 60Hz/
Hi Torque, 50Hz/Std Torque, 50Hz/Med Torque, and 50Hz/Hi Torque.
Note: Changing the V/F Select may affect the Maximum Frequency parameter value. Always verify / correct
the Maximum Frequency parameter after changing the V/F Select parameter.
Motor Direction: The direction the motor is running. Note that this parameter can be changed while the drive
is running. After the direction has been changed, press START to activate the change. The motor will
decelerate to 0 and then accelerate to the desired frequency in the motor direction indicated.
Drive Output Volts: Defines the Maximum output volts on the V/Hz curve to allow the user to set the voltage
lower for circumstances such as 50Hz operation manually. Note: The maximum output of the drive will not
exceed the input voltage supplied.
Maximum Frequency: Maximum frequency to be emitted by the drive. Note that the maximum frequency is also
the frequency at which the drive outputs its base voltage, 480V.
Minimum Frequency: Minimum frequency to run the GE OIL & GAS motor. This value should be set high enough
to ensure pump head is sufficient to pump liquids to the surface (providing cooling for the motor).
Acceleration Time: Time required to accelerate from stopped to Maximum Frequency.
Deceleration Time: Time required to decelerate from Maximum Frequency to stopped.
Voltage Bias: Bias voltage added to the output for fine tuning. Note that the bias voltage is the value added
at maximum frequency and is scaled for frequencies lower than maximum frequency. Also note that the
positive bias can be limited by the DC bus voltage.
I-Limit: Defines the maximum allowable Current for the output.
Lockout Frequency 1 3: Frequencies the drive will avoid.
Lockout Deadband: Width of the band that band around the lockout frequencies that the drive will avoid.
Parameter Description: Defines the V/F Curve for Provides user with information concerning the selected
(highlighted) parameter.
General Help: Use Up and Down arrows General help information on how to use this screen. Note that some
parameters may not be changed when the drive is running. The General Help will state that the drive must

PN: 196399 Revision: 6.6.2

65

GE Oil & Gas


be stopped when such a parameter is selected and the drive is running.
Note: Any parameter that is different from its default value is denoted by an asterisk (*) to the right of its value.

Keypad Functions:

F1: Edit. Edit the selected (highlighted) parameter.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

imagination at work

VII

VECTOR
4.24 Analog 1 Setup

Function:

The Analog 1 Setup screen allows a logged on user to configure Analog Input 1.

Field Descriptions:

Screen Name: Analog 1 Setup. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
A1 Input Voltage 1, Engineering Units 1: Values used to define 1 point on the sensor curve. Used in conjunction
with the following parameters to calculate the analog gain and bias.
A1 Input Voltage 2, Engineering Units 2: Values used to define the second point on the sensor curve. Used in
conjunction with the previous 2 parameters to calculate the analog gain and bias.
Analog In A1 Units: Defines the engineering units used when displaying the specified analog value.
Max Value: The maximum allowed value of the Analog Input in engineering units. If Analog 1 Fault is enabled
and if the analog value exceeds the maximum value for the programmed delay time, a fault will be declared.
Min Value: The minimum allowed value of the Analog Input in engineering units. If Analog 1 Fault is enabled and
if the analog value is less than the minimum value for the programmed delay time, a fault will be declared.
Analog 1 Delay: The amount of time to tolerate a range error before declaring a fault.
Analog 1 Fault: Values are Disabled (analog 1 limits are ignored), Fault (analog 1 limits will cause a fault but will
not automatically restart), and Restart (analog 1 limits will cause a fault and automatic restart).
Note: Restart uses the Restart Tries, Restart Delay, and Restart Clear Time parameters from the Alarms Setup
screen.
Parameter Description: Analog 1 sensor Provides user with information concerning the selected (highlighted)
parameter.
General Help: Use Up and Down arrows General help information on how to use this screen. Note that some
parameters may not be changed when the drive is running. The General Help will state that the drive must
be stopped when such a parameter is selected and the drive is running.
Note: Any parameter that is different from its default value is denoted by an asterisk (*) to the right of its value.
Note: The restart count and restart delay time are set in the Alarms menu.

PN: 196399 Revision: 6.6.2

67

GE Oil & Gas


Keypad Functions:

F1: Edit. Edit the selected (highlighted) parameter.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

imagination at work

VII

VECTOR
4.25 Analog 2 Setup

Function:

The Analog 2 Setup screen allows a logged on user to configure Analog Input 2.

Field Descriptions:

Screen Name: Analog 2 Setup. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Analog 2 Type: Select between 0 10V or 4 20mA.
A2 Input Voltage 1, Engineering Units 1: Values used to define 1 point on the sensor curve. Used in conjunction
with the following parameters to calculate the analog gain and bias. Note that the voltage can also be a
current if set to 4 20mA mode.
A2 Input Voltage 2, Engineering Units 2: Values used to define the second point on the sensor curve. Used in
conjunction with the previous 2 parameters to calculate the analog gain and bias. Note that the voltage can
also be a current if set to 4 20mA mode.
Analog In A2 Units: Defines the engineering units used when displaying the specified analog value.
Max Value: The maximum allowed value of the Analog Input in engineering units. If Analog 2 Fault is enabled
and if the analog value exceeds the maximum value for the programmed delay time, a fault will be declared.
Min Value: The minimum allowed value of the Analog Input in engineering units. If Analog 2 Fault is enabled and
if the analog value is less than the minimum value for the programmed delay time, a fault will be declared.
Analog 2 Delay: The amount of time to tolerate a range error before declaring a fault.
Analog 2 Fault: Values are Disabled (analog 2 limits are ignored), Fault (analog 2 limits will cause a fault but will
not automatically restart), and Restart (analog 2 limits will cause a fault and automatic restart).
Note: Restart uses the Restart Tries, Restart Delay, and Restart Clear Time parameters from the Alarms Setup
screen.
Parameter Description: Sets S1-2=OFF Provides user with information concerning the selected (highlighted)
parameter.
General Help: Use Up and Down arrows General help information on how to use this screen. Note that some
parameters may not be changed when the drive is running. The General Help will state that the drive must
be stopped when such a parameter is selected and the drive is running.
Note: Any parameter that is different from its default value is denoted by an asterisk (*) to the right of its value.
Note: The restart count and restart delay time are set in the Alarms menu.

PN: 196399 Revision: 6.6.2

69

GE Oil & Gas

Keypad Functions:

F1: Edit. Edit the selected (highlighted) parameter.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

imagination at work

VII

VECTOR
4.26 Misc Setup

Function:

The Misc Setup screen allows a logged on user to configure some miscellaneous parameters.

Field Descriptions:

Screen Name: Misc Setup. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
SmartGuard: Communication with the SmartGuard downhole tool can be configured as:
Disabled No communications.
Enabled - Read downhole data only.
Fault - Monitor SmartGuard fault relay and generate fault if set.
Restart - Fault on fault relay and allow restarts as programmed in the Alarms menu.
SmartGuard Timeout: the SmartGuard Timeout detects both a loss of Comms between the Viper and SSU and
the loss of sync between the SSU and the downhole tool. The timeout indicates a loss of valid data.

Transformer Ratio: The transformer ratio (for the drive output transformer) can be set to allow calculation of
downhole motor current and voltage. These downhole parameters can be displayed in the User Selected
Parameters.
Drive Type: Set to match the Single or Multi Inverter. Drives 757 - 1515 should be set to Multi.
Password: Defines the password used to log into the system. The default password is 3333.
External Fault 1: 11 Digital Input can be Disabled or set to Normally Closed or Normally Open.
Ext Fault 1 Restart: Enable to allow automatic restarts after External Fault 1. Note that automatic restarts must
be enabled on the Startup Control screen for any automatic restarts to occur.
External Fault 2: 12 Digital Input can be Disabled or set to Normally Closed or Normally Open.
Ext Fault 2 Restart: Enable to allow automatic restarts after External Fault 2. Note that automatic restarts must
be enabled on the Startup Control screen for any automatic restarts to occur.
Standby Switch: Enable or disable Standby Switch detection.
Breaker 2: Enable or disable detection of the MCCB status switch (only used in systems with 2 breakers).
Filter Overheat: Enable to allow automatic drive shutdown when the VSG filter over heats.
Parameter Description: Enable or disable the SmartGuard Provides user with information concerning the
selected (highlighted) parameter.
General Help: Use Up and Down arrows General help information on how to use this screen. Note that some
parameters may not be changed when the drive is running. The General Help will state that the drive must

PN: 196399 Revision: 6.6.2

71

GE Oil & Gas


be stopped when such a parameter is selected and the drive is running.
Note: Any parameter that is different from its default value is denoted by an asterisk (*) to the right of its value.

Keypad Functions:

F1: Edit. Edit the selected (highlighted) parameter.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

imagination at work

VII

VECTOR
4.27 Comm Setup

Function:

The Comm Setup screen allows a logged on user to define the SCADA ModBus Address and assign how the
communication ports are used.

Field Descriptions:

Screen Name: Comm Setup. This field is displays the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
ModBus Address: Defines the ModBus address the drive will rGE Oil & Gasond to when communicating with a
SCADA device.
ModBus Baud Rate: Defines communication baud rate between 2400 and 38400 to communicate with other
units.
Drive Comm Port (485): Defines the serial port that will be used to communicate between HMI and the inverter.
The default is COM3 and must be left there. Note that the drive must be power-cycled for communication
port assignment changes to take effect.
SCADA Comm Port: Defines the serial port that will be used to communicate with an external SCADA system.
The default is COM2. Note that the drive must be power-cycled for communication port assignment changes
to take effect.
SCADA 2 Comm Port: Defines the serial port that will be used to communicate with an external SCADA system.
The default is Disabled. Note: The drive must be power-cycled for communication port assignment changes
to take effect.
SmartGuard Port: Defines the serial port that will be used to communicate with the SmartGuard downhole
sensor. The default is COM4. Note that the drive must be power-cycled for communication port assignment
changes to take effect.
DHCP Enable: Allows Dynamic Host Configuration Protocol for network systems to be enable or disabled.
IP Address 1-4: Defines specific IP address to change from default to allow more than one drive on the same
network.
Parameter Description: ModBus address used by SCADA Provides user with information concerning the
selected (highlighted) parameter.
General Help: Use Up and Down arrows General help information on how to use this screen. Note that some
parameters may not be changed when the drive is running. The General Help will state that the drive must
be stopped when such a parameter is selected and the drive is running.

PN: 196399 Revision: 6.6.2

73

GE Oil & Gas


Note: Any parameter that is different from its default value is denoted by an asterisk (*) to the right of its value.
Note: For old HMI Communication port Pin out refer to section 8.3 and New HMI 8.4.

Keypad Functions:

F1: Edit. Edit the selected (highlighted) parameter.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

imagination at work

VII

VECTOR
4.28 Hard Starting

Function:

The Hard Starting screen allows a logged in user the capability to rock the motor forward and backward a preset
number of times before attempting to ramp to full speed.

Field Descriptions:

Screen Name: Hard Starting. This field is the name of the displayed screen.
Drive State: Ready. This field displays Jog setpoint, Rock start enabled/disabled, rock count, Accel time and
Decel time.
Jog Setpoint: The target frequency for the jog function.
Rock Start: Enables or Disables the rock start function.
Rock Count: Number of times to rock forward and back before attempting to ramp to full speed.
Acceleration Time: Time required to accelerate from stopped to Maximum Frequency.
Deceleration Time: Time required to decelerate from Maximum Frequency to stopped.
General Help: Use Up and Down arrows General help information on how to use this screen. Note that these
functions cannot be activated when the drive is running.

Keypad Functions:

F1: Edit. Edit the selected (highlighted) parameter.


F2: Not used.
F3: Jog While holding this button, the drive ramps up to preset Jog frequency. When button is released, the
drive ramps down to zero.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

75

GE Oil & Gas

4.29 Maintenance Menu

Function:

The Maintenance screen allows a logged in user to perform maintenance functions.


Note that the drive must be stopped to activate these functions.

Field Descriptions:

Screen Name: Maintenance. This field is the name of the displayed screen.
Drive State: Ready. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Check / Update all drive parameters. When executed, this function verifies / updates all low level (drive)
parameters to ensure that the drive configuration matches the high level (user interface) configuration.
Execute this function to set the underlying drive parameters to match the user interface configuration if the
drive control board has been changed or if the configuration has been loaded from a USB flash drive.
Set all parameters to Factory defaults. When executed, this function sets all of the high level (user interface)
parameters and low level (drive) parameters to their default values. Note that the drive must be powered off
and back on after executing this function.
Save configuration to USB Flash drive. When executed, this function saves the high level drive configuration
to a file (CONFIG.TXT) on the USB flash drive. Note please insert the USB Flash drive and wait at least 5
seconds before activating this function.

Refer to appendix 3.2
Load configuration from USB Flash drive. When executed, this function loads the high level configuration from
the configuration file (CONFIG.TXT) on the USB flash drive and then updates the low level (drive) registers
to match the configuration. Note please insert the USB Flash drive and wait at least 5 seconds before
activating this function. Please run the Check / Update all drive parameters after this operation to properly
configure the underlying drive.

Refer to appendix 3.4
Save Linear List to USB Flash drive. When executed, this function saves a file (LLDATA.TXT) with the values of all
the underlying drive (Linear List) parameters on the USB flash drive. Note please insert the USB Flash drive
and wait at least 5 seconds before activating this function. Note this file is for troubleshooting and cannot
be loaded into the drive.

Refer to appendix 3.3
Delete History and Current Logs. When executed, this function deletes all data from the history (see History
screen) and high speed current data (see the Amp Chart screen) logs. Use this function when moving a drive

imagination at work

VII

VECTOR
to a new location.
Upgrade Firmware. Follow the directions to upgrade the firmware in the user interface controller. Note that
upgrading the user interface firmware may require an update to the drive firmware also. Upgrading the
firmware may also require the drive to be reconfigured. Also note that the Config.txt file acquired with the
Save configuration to USB Flash drive may NOT be compatible with the new firmware.
General Help: Use Up and Down arrows General help information on how to use this screen. Note that these
functions cannot be activated when the drive is running.

Keypad Functions:

F1: OK. Activate the selected function.


F2: Not used.
F3: Not used.
F4: Not used.
F5: Menu. Return to the Select screen.
Up Arrow: Select (highlight) the parameter above the currently selected parameter (wraps at top back to bottom
of list).
Down Arrow: Select (highlight) the parameter below the currently selected parameter (wraps at bottom back to
top of list.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

77

GE Oil & Gas

4.30 Startup Control

Function:

The Startup Control screen allows any operator the ability to easily view or control the drive start and autorestart parameters.

Field Descriptions:

Screen Name: Startup Control. This field is the name of the displayed screen.
Drive State: Running. This field displays the up-to-date state of the drive. See list of possible values on the Run
Status screen description.
Drive Serial Number: Serial number of the drive.
Drive Mode: Frequency Control. Designates the control mode of the drive. The mode can be changed in the
Operating Mode screen.
Date / Time: Date and time.
Frequency Setpoint: 60.00 Hz. The up-to-date frequency setpoint. This field will not be present in some drive
control modes.
Output Current: 1.2 A. The up-to-date drive output current.
Output Frequency: 60.00 Hz. The up-to-date frequency being emitted by the drive.
Output Voltage: 479.9 V. The up-to-date phase to phase voltage at the output of the drive.
Drive Lockout graphic: Illustrates the start state of the drive. The illustration shows the drive is enabled. If the
drive is disabled, it will not rGE Oil & Gasond to a start command.
Auto Restart graphic: Illustrates whether the drive auto restart is currently enabled or disabled. The illustration
shows the auto restart is disabled.
General Help: Press Menu soft key General help information on how to use this screen.

imagination at work

VII

VECTOR
Keypad Functions:

F1: Disable. Disable the drive. If running, the drive will be stopped.
F2: Enable. Enable the drive.
F3: Disable. Disable auto restart of drive.
F4: Enable. Enable auto restart of drive.
F5: Menu. Return to the Select screen.
Down Arrow: Not Used.
Left Arrow: Not used.
Right Arrow: Not used.
START: Starts the drive if it is in the Ready state.
STOP: Stops the drive.

PN: 196399 Revision: 6.6.2

79

GE Oil & Gas

4.31 Keypad Test

Function:

The Keypad Test screen provides no functionality for controlling the drive. It is included as an aid for testing the
keypad normally in manufacturing.
The Keypad Test screen is activated by pressing the unlabeled F1 soft key in the Select Screen.

Operation:

There is a box on the screen associated with each keypad key. When a keypad key is pressed, the
associated box on the screen turns red.

Note: Press and hold down the F5 key to exit the Keypad Test screen.
Keypad Failure Detection: Log excessive button presses (>100) as events showing a possible hardware problem.

imagination at work

VII

VECTOR
5 Parameter Locator

The following table describes what parameters are available in each of the different screens.
Screen
Setup (No login required)
Operating Mode
(Current Control)
Operating Mode
(Pressure Control)

Operating Mode
(Frequency Control)
Operating Mode
(Analog Follower)

Alarms Setup

Parameters
Language
Date Format
Local / Remote
Drive Mode
Current Setpoint
Current Freq Limit
Drive Mode
Pressure Source
Pressure Setpoint
PI Proportional
PI Integral
Analog 2 Type

Control Location
User Selected 1 5
PI Proportional
PI Integral
A2 Input Voltage 1
Engineering Units 1
A2 Input Voltage 2
Engineering Units 2
Analog In 2 Units

Drive Mode
Frequency Setpoint
Startup Mode
Drive Mode
Signal Source
Minimum Frequency
Input at Min Freq
EU Value Min

Setp1 Frequency
Setp1 Time
Run Ramp Time
Maximum Frequency
Input at Max Freq
EU Value Max
Analog In A1 Units

Motor Overload Amps


Oload Start Delay
Overload Restart
Overload @ Min Freq

Restart Tries
Restart Delay
Restart Clear Time

Overload Delay
Underload Setup

Start Control

Frequency Setup


Underload Current
Uload Start Delay
Underload Delay
Underload Restart Tries

Underload Restart Time


Underload Restart OK
Underload @ Min Freq


Restart on PWR Loss
Ride Thru Restart
Start Hold Off Time
V/F Select
Motor Direction
Maximum Frequency
Minimum Frequency
Acceleration Time
Deceleration Time

PN: 196399 Revision: 6.6.2

Voltage Bias
Jog Setpoint
I Limit
Lockout Frequency 1
Lockout Frequency 2
Lockout Frequency 3
Lockout Deadband

81

GE Oil & Gas

Analog 1 Setup

A1 Input Voltage 1
Engineering Units 1
A1 Input Voltage 2
Engineering Units 2
Analog In 1 Units

Max Value
Min Value
Analog 1 Delay
Analog 1 Fault Enable

Analog 2 Setup

Analog 2 Type
A2 Input Voltage 1
Engineering Units 1
A2 Input Voltage 2

Analog In A2 Units
Max Value
Min Value
Engineering Units 2

Misc Setup

Comm Setup

Hard Starting
Maintenance

Analog 2 Delay
Analog 2 Fault Enable
SmartGuard Enable
External Fault 2 Enable
Transformer Ratio
Ext Fault 2 Restart
Drive Type
Standby Switch Enable
Password
Breaker 2 Detect Enable
External Fault 1 Enable
Ext Fault 1 Restart
ModBus Address
SmartGuard Port
ModBus Baud Rate DHCP Enable
Drive Comm Port (485)
IP Address 1 - 4
SCADA Comm Port
Jog Set Point
Acceleration Time
Rock Start
Deceleration Time
Rock Count
Check/Update all drive parameters Save linear list to USB Flash
Set all parameters to factory
Delete History and Current Logs
Save Configuration to USB Upgrade Firmware
Load configuration from USB Flash

imagination at work

VII

VECTOR
6 Remote User Interface
6.1 What is the Remote User Interface?
Some Vector VII drives are equipped with a wireless router allowing the use of the remote user interface. The
remote user interface is an interface by which the drive can be controlled and configured using a laptop computer
with a wireless network interface. The remote user interface looks and acts like the actual drive user interface but
appears in Internet Explorer on an appropriately equipped computer.
Note that the remote user interface program resides on the drive itself. The computer needs only Internet Explorer, a
wireless network card, and the Flash Player to make use of the remote user interface.

6.2 Configuration
Equipment Required:
Laptop with wireless network card
Software Microsoft Internet Explorer and Adobe Flash Player 8 or later (www.adobe.com)
Wireless Router (PN 196126 or 197080) Option already configured and installed on your drive.
Microsoft Internet Explorer is a registered trademark of Microsoft Corporation
Adobe Flash Player is a registered trademark of Adobe Incorporated

Procedure:
Configure Wireless Card Utility
Note: The following is an example to access a router already installed and configured on your Vector VII drive or
Vector VII Trainer. Your laptop Wireless utility may be different and not follow this example. You will have to know
how to use the wireless network card on your laptop
If you are installing a router in your drive you should have instructions that came with the Remote User Interface kit
on how to set up the router.

If your Wireless card is enabled you should see the icon in the system tray in the lower right hand corner of your
screen. If it is not enabled you will need to go to Control Panel then Network Connections and enable your Wireless
card. Move your cursor over the wireless icon, which in this case is several vertical bars, and right click on it. Highlight
Connect To and look for VIPERSEC and click on it. If you do not see VIPERSEC listed then open the Wireless utility
and click on Site Monitor. After a few seconds you should see VIPERSEC in the site list. If you do not, then there may
be a problem with the router or your wireless card. Check the router to make sure the lights are on. Once you see
VIPERSEC in the list you can go back to the Wireless Networks screen and add VIPERSEC to this list, make sure and
enter the Network Key (see below) and select it. The Network Key value is 4056701431.

PN: 196399 Revision: 6.6.2

83

GE Oil & Gas

Completing and Connecting


From your desktop enter Internet Explorer. Click on the X to stop the home screen access. Enter
the following into the address bar: http://192.168.2.101/ui.html. You should see a duplicate copy of
the Vector VII HMI display screen. Clicking the buttons on your laptop will do the same thing as
pushing the buttons on the display screen.

6.3 Capabilities
Besides running and configuring the drive, the remote user interface allows the user to download event, history,
configuration, and linear list files. Click the File Menu button on the remote user interface to access these functions.
These files open in their own Internet Explorer windows. Use the File, Save As functionality to save the data as text
files. (Note that the linear list file can not be generated when the drive is running.)

imagination at work

VII

VECTOR
7 Volts per Hertz Settings (V/Hz)
7.1 V/Hz Factory and Manual Set-up.
Refer to section 4.23 Frequency for programming

7.1.1 Factory Default V/Hz and Definition


V/Hz Settings
Factory Defaults
(Logged in, Frequency Setup | V/F Select)
50 Hz Standard

(480 VAC)

Max Volts

E1-05

_
<
Mid Volts B

E1-12

_
<
(0VAC)

Base Volts

E1-13

Voltage (V)

(0VAC)

_
<
(28.8VAC)

(14.4VAC)

Mid Volts A

Min Volts

E1-08

_
<

E1-10

Frequency (Hz)

E1-09
Min Freq
(1.5Hz)

_
<

E1-07
Mid Freq
A
(3Hz)

_
<

E1-06
Base
Freq
(50Hz)

_ E1-11 <
_
<
Mid Freq
B
(0Hz)

E1-04
Max Freq
(50Hz)

Figure 7.1 60Hz Standard Torque

PN: 196399 Revision: 6.6.2

85

GE Oil & Gas


V/HZ Definition
This defines the Voltage and Frequency relationship at the output of the drive.
At maximum frequency (Maximum Speed) E1-04 = 60 Hz, the Maximum Voltage E1-05 = 480 VAC.
o This means that at maximum speed, the drive will try to maintain an output of 480 VAC at
60 HZ.
This is provided there is 480 VAC at the input. Otherwise the maximum voltage cannot be increased
beyond the voltage at the input.
At Minimum Frequency E1-09 = 1.5Hz, the Minimum Voltage E1-10 = 14.4 VAC.
o This means that at minimum speed, the drive will try to maintain an output of 14.4 VAC at
1.5 Hz
Factory Default V/Hz
Figure 7.1 shows the settings for normal operation after Defaults are set in the drive.
o The minimum and maximum frequency limits are changed in the Frequency setup screen.
The Maximum Frequency setting in the frequency setup screen changes the Base
Freq (E1-09) and Max Freq (E1-04) simultaneously to the frequency the user defines.
The Minimum Frequency setting in the frequency setup screen changes Ref
Lower Limit (D2-02). This is the lower cut off of drive operation. The drive
automatically calculates the percentage of Maximum frequency the user sets as
normal operating frequency lower limit. When commanded to stop the drive will
decelerate to the Minimum Frequency and stop instead of decelerating to 0 Hz.

7.1.2 Selectable 60 Hz V/Hz settings


HI MED STD
TRQ TRQ TRQ
E1-05

480

480

480

E1-12

E1-13

E1-08

48

36

28.8

Settings

60 Hz
Hz
60

60

Standard Torque

1.5

60

60

Medium Torque

1.5

60

60

High Torque

E1-04

E1-09

E1-11

ST
ED

M
I
H

1.5

E1-06

26.4 16.8 14.4

E1-07

E1-10

Selectable (Custom) V/Hz

Figure 7.2

imagination at work

VII

VECTOR
60 Hz Selectable Operation

There are 3 selectable settings pre-programmed into the Vector VII drive. In the Medium and High
Torque settings, a predetermined amount of voltage boost is applied at lower frequencies to provide
more torque at Start Up.
o 60 Hz Standard Torque (Default)
o 60 Hz Medium Torque
o 60 Hz High Torque

V/Hz Settings
Factory Defaults
(Logged in, Frequency Setup | V/F Select)
60 Hz Medium Torque

(480 VAC)

Max Volts

E1-05

_
<
E1-12

E1-13

rd

Base Volts

St

(0VAC)

da

_
<

an

Mid Volts B

Voltage (V)

(0VAC)

_
<
(36 VAC)

(16.8 VAC)

Mid Volts A

Min Volts

E1-08

_
<

E1-10

Frequency (Hz)

E1-09
Min Freq
(1.5Hz)

_ E1-07 <
_ E1-06 <
_ E1-11 <
_ E1-04
<
Mid Freq
A
(3Hz)

Base
Freq
(60Hz)

Mid Freq
B
(0Hz)

Max Freq
(60Hz)

Figure 7.3 60Hz Medium Torque Setting

PN: 196399 Revision: 6.6.2

87

GE Oil & Gas

V/Hz Settings
Factory Defaults
(Logged in, Frequency Setup | V/F Select)
60 Hz High Torque

(480 VAC)

Max Volts

E1-05

_
<
E1-12

rd

E1-13

da

Base Volts

St

(0VAC)

an

_
<

Voltage (V)

(0VAC) Mid Volts B

_
<
(48 VAC)

(26.4 VAC)

Mid Volts A

Min Volts

E1-08

_
<

E1-10

Frequency (Hz)

_
E1-09 <
Min Freq
(1.5Hz)

_ E1-06 <
_ E1-11 <
_ E1-04
E1-07 <
Mid Freq
Base
Mid Freq
Max Freq
A
Freq
B
(60Hz)
(0Hz)
(60Hz)
(3Hz)

Figure 7.4 - 60Hz High Torque Setting

imagination at work

VII

VECTOR
7.1.3 Selectable 50 Hz V/Hz settings
Figure 7.5

50 Hz Selectable Operation

There are 3 selectable settings pre-programmed into the Vector VII drive. In the Medium and High
Torque settings, a predetermined amount of voltage boost is applied at lower frequencies to provide
more torque at Start Up.
o 50 Hz Standard Torque
o 50 Hz Medium Torque
o 50 Hz High Torque

HI MED STD
TRQ TRQ TRQ
E1-05

480

480

480

E1-12

E1-13

E1-08

48

36

28.8

Settings

50 Hz
Hz
3

50

50

Standard Torque

1.3

2.5

50

50

Medium Torque

1.3

2.5

50

50

High Torque

E1-06

E1-11

E1-04

ST
ED

M
I

1.5

E1-07

21.6 16.8 14.4

E1-09

E1-10

Selectable (Custom) V/Hz

Figure 7.6 50Hz Standard Torque Settings

PN: 196399 Revision: 6.6.2

89

GE Oil & Gas

V/Hz Settings
Factory Defaults
(Logged in, Frequency Setup | V/F Select)
50 Hz Medium Torque

(480 VAC)

Max Volts

E1-05

_
<
E1-12

E1-13

rd

Base Volts

St

(0VAC)

da

_
<

an

Mid Volts B

Voltage (V)

(0VAC)

_
<
(36 VAC)

(16.8 VAC)

Mid Volts A

Min Volts

E1-08

_
<

E1-10

Frequency (Hz)

E1-09
Min Freq
(1.3Hz)

_ E1-07 <
_ E1-06 <
_ E1-11 <
_ E1-04
<
Mid Freq
A
(2.5Hz)

Base
Freq
(50Hz)

Figure 7.7 - 50Hz Medium Torque Settings

imagination at work

Mid Freq
B
(0Hz)

Max Freq
(50Hz)

VII

VECTOR
V/Hz Settings
Factory Defaults
(Logged in, Frequency Setup | V/F Select)
50 Hz High Torque

(480 VAC)

Max Volts

E1-05

_
<
E1-12

E1-13

rd

Base Volts

St

(0VAC)

da

_
<

an

Mid Volts B

Voltage (V)

(0VAC)

_
<
(48 VAC)

(21.6 VAC)

Mid Volts A

Min Volts

E1-08

_
<

E1-10

Frequency (Hz)

E1-09
Min Freq
(1.3Hz)

_ E1-07 <
_ E1-06 <
_ E1-11 <
_ E1-04
<
Mid Freq
A
(2.5Hz)

Base
Freq
(50Hz)

Mid Freq
B
(0Hz)

Max Freq
(50Hz)

Figure 7.8 - 50Hz High Torque Settings

PN: 196399 Revision: 6.6.2

91

GE Oil & Gas

7.1.4 V/Hz Manual Set-up


In some cases manual setup of the Volts/Hertz curve is required. If this is the case the user must manually
enter the parameters below in the Linear List (refer to section 4.17, 4.17.1 and Appendix 4). Certain
parameters must be programmed to be less that or equal to others in order for the drive to operate correctly.
Important Note!! If the Maximum Frequency is changed in the Frequency Setup screen of the HMI, the
parameters E1-04 and E1-06 will set equal to each other. In many cases this can cause a fault due to E111 being less than E1-06

V/Hz Settings
Manual (Example)
(Logged in, Linear List | E104,05,06,07,08,09,10,11,12,13

(480 VAC)

Max Volts

E1-05

_
<
Mid Volts B

E1-12

_
<
(370 VAC)

Base Volts

E1-13

Voltage (V)

(380 VAC)

_
<
(350 VAC)

(290 VAC)

Mid Volts A

Min Volts

E1-08

_
<

E1-10

Frequency (Hz)

E1-09
Min Freq
(30 Hz)

_
<

E1-07
Mid Freq
A
(37 Hz)

_
<

E1-06
Base
Freq
(45 Hz)

_ E1-11 <
_
<
Mid Freq
B
(60 Hz)

Figure 7.9

Warning: This is an example only!


o Motor Nameplate V/Hz must be maintained to maintain proper motor function.

imagination at work

E1-04
Max Freq
(70 Hz)

VII

VECTOR
8 SCADA Interface
8.1 SCADA Interface Port
COM2 (programmable on the Comm Setup screen) on the drive user interface computer is used for SCADA
communications. It is set up as 2400 38400 baud, No Parity, 8 data bits, and 1 stop bit. The default ModBus slave
address is 2, but this can be changed using the Comm Setup screen from 1 - 247.
The ModBus RTU protocol is employed by the SCADA interface port to allow for remote control and data acquisition.
Added support for redirection file to support additional parameters within the SCADA map as required.

8.2 SCADA Addresses


The following addresses are implemented in the standard SCADA ModBus map. All drive configuration parameters
and linear list parameters are also. Please contact GE Oil & Gas Engineering for information on any parameter not
listed in this section.
ModBus
Address
40001

Name

Description

Control

40002

Mode

40003

Reference

Write Only register to control drive


0 = Stop
1 = Run
Returns 0 when read.
Read / Write register that determines drive mode of operation.
0 = Current Limit Mode
1 = Pressure Control Mode
2 = Frequency Mode
3 = Analog Follower Mode
Read / Write register used to control speed of drive. Meaning of
value changes with drive mode.
Current Mode Current Setpoint (Amps * 10)
Pressure Mode Pressure Setpoint (PSI * 10)
Frequency Mode Frequency Setpoint (Hz * 10)
Analog Follower Mode Not Applicable. Always uses Analog 1.

40004

Poll Count

40005

Motor

40006

Fault

40007

Freq Ref

40008
40009
40010
40011

Output Freq
Output Voltage
Output Current
DC Bus Voltage

Read Only register that counts the number of polls received since the
program was started.
Read Only register that contains the motor state.
0 = Not Running
1 = Running
Read Only register that describes if a fault is active.
0 = No active fault
Bit 0: Internal Drive Fault see Drive Fault Code (40015) and Fault
Details (40016) registers.
Bit 1: Communication lost between user interface and drive.
Bit 2: Fatal User Interface Error see Fatal Error Code (40022).
Bit 3: SmartGuard Fault see SG Fault Source (40035).
Read Only register containing the frequency reference.
(Valid only in Frequency Control Mode.)
Output frequency of drive. Hz * 10
Output voltage of drive. Volts * 10
Output current of drive. Amps * 10
DC Bus Voltage. Volts * 1

PN: 196399 Revision: 6.6.2

93

GE Oil & Gas

ModBus
Address
40012

Name

Description

Analog 1

Analog 1 input value in drive units.


(units and scaling depend on drive configuration)

40013

Analog 2

Analog 2 input value in drive units.


(units and scaling depend on drive configuration)

40014

Drive Status
(internal)

Bitmapped drive status register.


Bit 0: Running

(1 = running, 0 = stopped)
Bit 1: At Zero Speed

(1 = at zero speed)
Bit 2: Reverse Operation (1 = reverse)
Bit 3: Fault Reset Signal
(1 = fault reset active)
Bit 4: Speed Agree

(1 = at speed)
Bit 5: Drive Ready

(1 = ready)
Bit 6: Alarm


(1 = alarm)
Bit 7: Fault


(1 = fault)
Bit 8 Bit 13: Not used
Bit 14: Reference via Comm
(1 = reference via modbus)
Bit 15: Control via Comm (1 = start / stop via ModBus)
Current Fault exhibited by drive.
(There are a few codes that are not included in the Fault Details
bitmapped list above.)
0 No Fault
25 DEV Speed Deviation

40015

Drive Fault Code


(internal)

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

imagination at work

PUF DC Bus Fuse Open


UV1 DC Bus Undervolt
UV2 Ctl PS Undervolt
UV3 MC Answerback
SC Short Circuit
GF Ground Fault
OC Overcurrent
OV DC Bus Overvolt
OH Heatsink Overtemp
OH1 Heatsink Max Temp
OL1 Motor Overload
OL2 Inverter Overload
OL3 Overtorque 1
OL4 Overtorque 2
RR DynBrk Transistor
RH DynBrk Resistor
EF3 External Fault 1
EF4 External Fault 2
EF5 Fault Not Enabled
EF6 Fault Not Enabled
EF7 Breaker 2 Fault
EF8 Fault Not Enabled
FAN Cooling Fan Error
OS Overspeed Detect

26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48

OVL Enhanced O-load


PF Input Phase Loss
LF Output Phase Loss
OH3 Motor Overheat 1
OPR HMI Disconnect
ERR EEPROM R/W Err
OH4 Motor Overheat 2
CE Serial Com Err
BUS Option Com Err
E-15 SI-F/G Com Err
E-10 SI-F/G CPU Down
CF Out of Control
SVE Zero Servo Fault
EF0 Opt External Fault
FBL Feedback Loss
LL3 Loss of Load
UL4 Undertorq Det 2
OL7 HSB-OL
ULF Underload
A1-HI Terminal A1 High
A1-LO Terminal A1 Low
A2-HI Terminal A2 High
A2-LO Terminal A2 Low

VII

VECTOR
ModBus
Address
40016

Name

Description

Fault Details
(internal)

40017

Drive State

40018

Time to Restart

40019

Misc Flags

40020

Digital Inputs

40021
40022
40023
40024

User Interface
State
Fatal Error Code
Software Rev.
SmartGuard State

40025

SG Fault Relay

40026

SG State

40027

Downhole #1
Intake Pressure
Downhole #2
Intake Temp
Downhole #3
Motor Temp

Bitmapped fault list.


Bit 0: Overcurrent (OC) Ground Fault (GF)
Bit 1: Main circuit Overvoltage (OV)
Bit 2: Drive overload (OL2)
Bit 3: Drive overhead (OH1, OH2)
Bit 4: Not used
Bit 5: Fuse blown (PUF)
Bit 6: PI feedback reference lost (FbL)
Bit 7: External error (EF, EF0)
Bit 8: Hardware error (CPF)
Bit 9: Motor overload (OL1) or Overtorque 1 (OL3) detected
Bit 10: PG broken wire detected (PGO), Overspeed (OS), Speed
deviation (DEV), Underload Fault (ULF)
Bit 11: Main circuit Undervoltage (UV) detected
Bit 12: Main circuit Undervoltage (UV1), control power supply error
(UV2), inrush prevention circuit error (UV3), power loss
Bit 13: Missing output phase (LF)
Bit 14: ModBus communications error (CE)
Bit 15: Operator disconnected (OPR)
State of the drive control state machine.
0 = Initializing
8 = Running / Remote
1 = Not Ready
9 = Stop / Remote
2 = Ready / Local
10 = Forced Stop
3 = Accelerating / Local
11 = Fault
4 = Running / Local
12 = Waiting to Restart
5 = Ready / Remote

13 = Off (Drive Disabled)
6 = Start / Remote
14 = Standby(13)
7 = Accelerating / Remote
15 = Standby / Remote
Valid only in Restart State. Time until drive will attempt to restart.
Minutes * 10
Bit 0 0 = Local, 1 = Remote
Bit 1 0 = Auto Restart disabled, 1 = Enabled
Bit 2 0 = Drive output disabled, 1 = Enabled
Bit 0 9
Bit 3 12

Bit 6 16
Bit 1 10

Bit 4 13

(1 = On)
Bit 2 11

Bit 5 14

(0 = Off)
0 = Init, 1 = Waiting for communication with drive, 2 = Normal,
3 = Communication with drive lost, 4 = Fatal Error
0 = No fatal error
Divide by 10
0 = Data OK
1 = Data Bad (SSU not syncd with downhole tool)
2 = SmartGuard interface disabled
0 = Fault Relay OK
1 = Fault Relay Fault
State of the SmartGuard fault detection state.
0 = Initializing
1 = No SmartGuard fault
2 = SmartGuard Fault Relay Detected - Fault
3 = Waiting to Restart
4 = Verifying restart OK
SmartGuard Data
PSI * 10 (default units can be set by CTConfig program)
SmartGuard Data
Degrees F * 10 (default units can be set by CTConfig program)
SmartGuard Data
Degrees F * 10 (default units can be set by CTConfig program)

40028
40029

PN: 196399 Revision: 6.6.2

95

GE Oil & Gas

ModBus
Address
40030
40031
40032
40033
40034
40035

Name

Description

Downhole #4
Discharge Press
Downhole #5
Vibration
Downhole #6
Leakage Current
Downhole #7
Uphole Voltage
Downhole #8
SG Duty Cycle
SG Fault Source

SmartGuard Data
PSI * 10 (default units can be set by CTConfig program)
SmartGuard Data
G * 1000 (default units can be set by CTConfig program)
SmartGuard Data
mA * 100 (default units can be set by CTConfig program)
SmartGuard Data
Volts * 10
SmartGuard Data
%
Bitmap fault source
Bit 0: Intake Pressure High
Bit 1: Intake Pressure Low
Bit 2: Intake Temperature High
Bit 3: Intake Temperature Low
Bit 4: Motor Temperature High
Bit 5: Motor Temperature Low
Bit 6: Discharge Pressure High
Bit 7: Discharge Pressure Low
Bit 8: Vibration High
Bit 9: Vibration Low
Bit 10: Current Leakage High
Bit 11: Current Leakage Low
Bit 12 Bit 15: Not Used

40036
40037
40038
40039
40040
Note

Reserved
Reserved
Reserved
Reserved
Reserved

40041
40042
40043

Reserved
Drive Comms
SG Fault Source 2

40044
40045
40046

Drive Enable
Reserved
Downhole #9
Delta Pressure
Total Starts
Previous Fault
Total Run Time
Current Run
Motor Voltage
Motor Current
A2 Hi Limit
A2 Low Limit
A3 Hi Limit
A3 Low Limit
A1 Hi Limit
A1 Low Limit
Output Power
Power Factor
Group
Membership Mask
Group Shutdown
Mask
Remote / Local
Auto Restart
Enable

40047
40048
40049
40050
40051
40052
40053
40054
42076
42077
40055
40056
40057
40058
40059
40060
40061
40062

imagination at work

Addresses 40041 40xxx are redirects as defined in the file REDIR.


DAT.
Percentage of successful drive polls.
Bit 0: Delta Pressure High
Bit 1: Delta Pressure Low
Bit 2 Bit 15: Not Used.
0 = Drive Locked Out, 1 = Drive Enabled.
SmartGuard delta pressure.
PSI * 10 (default units can be set by CTConfig program)
Drive total starts.
Fault Code for previous fault. See address 40015 for key.
Drive Total Run Time. Hours.
Runtime since last start. Hours.
Downhole motor voltage. V * 10
Downhole motor current. A * 10
Analog Input 2 upper limit.
Analog Input 2 lower limit.
Analog Input 3 upper limit.
Analog Input 3 lower limit.
Analog Input 1 upper limit.
Analog Input 1 lower limit.
Drive output power. KW * 10.
Drive output power factor. % * 10
Used to define groups in conjunction with the Group Shutdown Mask.
Mirrored at address 40441.
Shuts down drive if any bits match with the Group Membership Mask.
Mirrored at address 40444.
0 = Local, 1 = Remote
0 = Auto Restarts disabled
1 = Auto Restarts enabled

VII

VECTOR
ModBus
Address
40063

Name

Description

Last Shutdown
Code

0 48 same as 40015
60 Underload Fault
61 SCADA Stop Command
62 Keypad Stop Command
63 Group Shutdown
69 SmartGuard Data Bad (SG Timeout with data out of sync)
70 SG Intake Pressure High
71 SG Intake Pressure Low
72 SG Intake Temp High
73 SG Intake Temp Low
74 SG Motor Temp High
75 SG Motor Temp Low
76 SG Disch Press High
77 SG Disch Press Low
78 SG Vibration High
79 SG Vibration Low
80 SG Leakage High
81 SG Leakage Low
82 SG Delta Press High
83 SG Delta Press Low

Dumping Events

Events are dumped as strings in rGE Oil & Gasonse to ModBus requests from addresses 40901 41156. The
newest event is at address 40901. To request the newest event, send the command:
(Slave ID) (Code = 3) (Add Hi = 3) (Add Lo = 132) (Len Hi = 0) (Len Lo = 1) (CRC Hi) (CRC Lo)
The rGE Oil & Gasonse is a ModBus rGE Oil & Gasonse with the standard header format (Slave ID) (Code) (Bytes to
follow) followed by the text message associated with the event.

PN: 196399 Revision: 6.6.2

97

GE Oil & Gas


Utility Write Registers
Utility write registers are written one at a time using the ModBus type 6 command.
ModBus
Address
44201

Name

Description

Time High Word

44202

Time Low Word

44203

Digital Output 1

44204

Digital Output 2

Write only register to set the drive time.


High 16 bit word of the 32 bit word that describes the number of
seconds since January 1, 1970 (standard C time).
Write only register to set the drive time.
Low 16 bit word of the 32 bit word that describes the number of
seconds since January 1, 1970 (standard C time).
Write the high word (44201) AND THEN write the low word (44202)
to set the drive time!
Write only register to close or open the digital output 1 relay.
0 = Open
1 = Close
This output NOT available in Multi-inverter drives.
Write only register to close or open the digital output 2 relay.
0 = Open
1 = Close

8.3 Old HMI Communication Ports 1-5 Pin Out


Pin
Signal
1
Data Carrier Detect (DCD)
2
Received Data (RXD)
3
Transmitted Data (TXD)
4
Data Terminal Ready (DTR)
5
Ground
6
Data Set Ready (DSR)
7
Request to Send (RTS)
8
Clear to Send (CTS)
9
Ring Indicator (RI)
Only pins 2, 3, and 5 are used on the SCADA port.

Note: Com1, 2, 3, 4 are RS232. Com5 is the designated RS-485 to the drive.

imagination at work

VII

VECTOR
8.4 New HMI Communication Ports Pin Out
485 GND
A
B
Shield
Ground
+24 VDC

SD Card Interface

Ethernet

1
2
3
4
5
6

SD Card

J8

RS-485 Isolated
Drive Comm

Shield
SS+
Ground

1
2
3
4

J2

J25
Comm 3

1
2 GND (232)
3 RXD (232)
4 TXD (232)
5 RTS (232)
6

J17
Comm 2

J4

USB-B

J3

EXTERNAL
USB-A PORT
6

J14
Comm 4

RJ-11 (232/485)

J5
Comm 1

8
9

1
2

2 - RXD

3 - TXD

DB-9 Male

9 - +5 VDC
5
5 - Ground

Wood Group Manufactured New HMI


J22

1
2

Ground
+24 VDC

+24 VDC Input

J21

1
2
3

Chassis
Neutral
Line

240 VAC Input

All connectors not identified in this drawing are


Phoenix type connection with the number of
terminals depicted.

Figure 8.1

PN: 196399 Revision: 6.6.2

99

GE Oil & Gas

9 Troubleshooting and Maintenance


9.1 Main Circuit Test Procedure
DANGER Before attempting any troubleshooting checks make sure that the incoming
power to the drive has been removed and locked out. To prevent electrical shock, wait at least
five minutes after removing power and measure the DC bus voltage between the +3 and
terminals to confirm safe level of voltage using volt meter set to read DC volts with the black lead
connected to (-) and the red lead connected to (+3).

imagination at work

VII

VECTOR
9.1.1 Test Point Designations

The following describes test points of the drive frame used in the main circuit test procedure.

Figure 9.1 Drive test Point Diagram


Drive Input (Note that the drive input terminals are not the same as the circuit breaker input terminals)
6 Pulse Unit - R/L1, S/L2, T/L3
12 Pulse Unit - R/L1, S/L2, T/L3, R1/L11, S1/L21, T1/L31
DC Bus
+1 DC Bus Pre-Soft Charge Circuit
+3 DC Bus Post-Soft Charge Circuit
Drive Output (Note that the drive output terminals are on the drive located at the drive chassis and not at
the output of the output filter, if equipped)
U/T1, V/T2, W/T3

9.1.2 Main Power Circuit Test and Troubleshooting


DANGER Check DC Bus level before continuing. Ensure that the bus has fully discharged and
incoming power has been removed and locked out. To prevent electrical shock, wait at least five minutes
after removing power and measure the DC bus voltage between the +3 and terminals to confirm safe
level of voltage.
Input Diodes (Converter Section)
The converter section of the drive converts the input AC voltage to a DC voltage level.
Set Meter to Diode Check setting. Failure mode would be a shorted diode.

PN: 196399 Revision: 6.6.2

101

GE Oil & Gas

Red + Lead on Test Point:


R/L1
S/L2
T/L3

Black Lead on Test Point:


(+1)
(+1)
(+1)

Nominal Reading
~ 0.3 0.5V
~ 0.3 0.5V
~ 0.3 0.5V

R/L1
S/L2
T/L3

(-)
(-)
(-)

Charging
Charging
Charging

(-)
(-)
(-)

R/L1
S/L2
T/L3

~ 0.3 0.5V
~ 0.3 0.5V
~ 0.3 0.5V

(+1)
(+1)
(+1)

R/L1
S/L2
T/L3

Charging
Charging
Charging

Soft Charge Circuit


The purpose of the soft charge circuit is to slowly charge the DC Bus capacitors to limit the inrush current when
power is applied to the drive. When the DC bus reaches 380 VDC the soft charge contactor is closed and the soft
charge resistor is bypassed.
A faulty resistor will read infinite Ohms with a meter. The table below gives nominal readings for the soft charge
resistors.
Model - PN
150
253
344
428
561

Soft Charge Resistor Value


2.2 Ohms
2.7 Ohms
2.7 Ohms
3.3 Ohms
3.3 Ohms

DC Bus Fuse
The DC Bus fuse is to protect the main circuit components in the case of an output transistor failure.
i. Set meter to OHMS setting
ii. Place a meter lead on each side of the fuse
iii. Measurement of 0 Ohms the fuse is good, measurement of infinite Ohms the fuse is bad and must be replaced.
!!!NOTE Never replace a DC Bus fuse without checking all of the output transistors!
Output Transistors (Inverter Section)
The inverter section of the drive converts DC voltage from the DC Bus to a PWM AC waveform.
Set Meter to Diode Check setting. Failure mode would be a shorted transistor.
Red + Lead on Test Point:
U/T1
V/T2
W/T3

Black Lead on Test Point:


(+1)
(+1)
(+1)

Nominal Reading
~ 0.3 0.5V
~ 0.3 0.5V
~ 0.3 0.5V

U/T1
V/T2
W/T3

(-)
(-)
(-)

OL (Infinite)
OL (Infinite)
OL (Infinite)

(-)
(-)
(-)

U/T1
V/T2
W/T3

~ 0.3 0.5V
~ 0.3 0.5V
~ 0.3 0.5V

(+1)
(+1)
(+1)

U/T1
V/T2
W/T3

Charging
Charging
Charging

imagination at work

VII

VECTOR
9.2 Drive System Troubleshooting

Figure 9.2 Typical Drive System Diagram

PN: 196399 Revision: 6.6.2

103

GE Oil & Gas

9.2.1 Drive Frame PC Board Designations


Terminal Card (2PCB)
The Terminal Card houses all I/O wiring Control Terminals (See Section 3.3.1)
Control Card (1PCB)
This is the main control board for the drive unit.
Gate Drive Board (3PCB)
This board provides firing signals to the transistors in the inverter section of the drive.
Tap Change Card (4PCB)
Power supply board for the internal drive frame.
DCCT, DCCT Board (5PCB)
These current sensors provide current feedback to the drive controls. These are located at the output of the
drive.

9.2.2 System Power Checks and Troubleshooting


DANGER The following checks require that the drive unit be energized. Ensure that proper Electrically Rated
Personal Protective Equipment is be used before proceeding to work on live electrical equipment. Failure
to use proper Personal Protective Equipment can result in serious personal injury or death. The following
checks should only be performed by qualified electrical personnel.

PPE Minimum: Linemans Gloves (Proper Rating and current calibration stamp)
Safety Shoes

All Cotton clothing (Arc Flash Protection if region requires it)
Electrically rated hard hat and face shield (Arc Flash protection if region requires it)
Refer to Figure 9.1.1 for test points.
Incoming Power Check
Make sure incoming service disconnect placed in the energized state.
6 Pulse: Measure all three phases of incoming power at the top of the circuit breaker MCCB1.
12 Pulse: Measure all three phases of incoming power at the top of the circuit breaker MCCB1, do
the same for MCCB2.
Phases should be balanced at 480VAC +/- 10%
If the phases are low/high (+/- 10% of rated Voltage) or show excessive imbalance (more than 10%),
contact the power service provider. DO NOT energize the drive input circuit breaker(s).
If phases are within nominal values, close the drive input circuit breaker(s).
Control Power Transformer Check
Primary CPT1 (480VAC)
o Measure the primary CPT1 voltage across the H1 (P2) and H4 (P5) terminals. The voltage
reading should be approximately 480 VAC
o If there is no voltage present, de-energize and lock out the drive. Wait until the DC bus has
fully discharged. Check the primary CPT F1 and F2 fuses and replace if necessary.
o If there is voltage present but it is excessively lower/higher (+/- 10% of rated Voltage) that
480VAC, de-energize the drive and repeat Incoming Power Check.
Secondary CPT1 (240VAC/120VAC)
o Measure the secondary CPT1 voltage across the X1(p2) and X4(p5) terminals. The voltage
reading should be approximately 240 VAC. With one meter lead on X1(p2) terminal check

imagination at work

VII

VECTOR
both sides of the secondary CPT fuse F3, both sides should read 240VAC. If 240VAC is not
present on both sides, replace the secondary CPT F3 fuse.
o Measure the secondary CPT1 voltage across the X2(p3) and X4(p5) terminals. The voltage
reading should be approximately 120 VAC. With one meter lead on X2(p3) terminal check
both sides of the duplex receptacle fuse, both sides should read 120VAC. If 120VAC is not
present on both sides, replace the duplex receptacle fuse F4.
5V Power Supply (HMI Power) Check
Measure 5V supply output at terminals -V and +V. Reading should be 5 VDC.
If 5VDC is not present at terminals -V and +V, Check the 240VAC supply voltage between terminals
AC (L) and AC (N). If 240VAC is present replace 5V power supply. If 240VAC is not present repeat
Control Power Transformer Check.
Drive Power Supply Check (Control Terminals)
At the Control Terminals on the Terminal Card check the drive supply voltages
Measure voltage across +V and AC, nominal voltage is +15 VDC.
Measure voltage across Any Digital Input (S1 S7) (positive lead) and SP (negative lead), nominal
voltage is 24 VDC.
If any of the voltages are not present, replace the Terminal Card and/or the Control Card

9.2.3 Fan/Heat Exchanger Troubleshooting


The fan relay FR controls the external cooling fan and the heat exchanger unit (certain sizes). When the drive
receives a run command the fan relay is energized and the fan contactor FR is closed. If the fans do not
operate check the Fan Relay for proper operation. The heat exchanger requires a run signal from the HTX
thermostat to operate.

9.2.4 Drive Status / Fault Codes


The Vector VII drive stores a significant amount of data that can be useful for troubleshooting. It is
recommended to capture this data onto a USB flash drive for reference (this is done from the History screen).
The data and event files can be used to investigate the problem if the troubleshooting procedures in this
document can not solve the problem.
Drive Communications Lost Screen
The drive communications lost screen appears anytime the user interface computer (HMI) cannot
communicate with the drive power unit. This screen covers the entire LCD display and can display one of
two different messages.

Drive Status, Waiting for communications with drive chassis. Please Stand-by.
Drive Status, Lost communications with drive chassis. Trying to reconnect. Please Stand-by.

The first message occurs if communications with the drive have never been established. The second is
displayed if communications have been established and then lost. The drive communications lost screen
disappears when communication with the drive is established (or re-established). Events are logged each
time communications with the drive is lost or re-established (see Events Screen).
Verify that the drive chassis is powered up. Verify the cable connection between COM5 and the drive
chassis is good for and old HMI and between Comm 4 and drive chassis for new HMI. Troubleshoot to faulty
components and replace faulty component if problem persists.
Fatal Error Screen
The fatal error screen is displayed when the drive encounters an error from which it cannot recover. These
are typically file system or timing problems in the HMI. An error code and descriptive message is included on

PN: 196399 Revision: 6.6.2

105

GE Oil & Gas


the screen. This screen covers the entire LCD display.

Drive Status, Fatal Error. Code = <Error Code Here> <Error Description Here> Power must be cycled
off and back on.

Provide the history and event files to the engineering department in OKC for investigation. Power cycle the
drive. If the fatal error recurs, set the drive to factory defaults and try again. If the fatal error recurs, contact
OKC or replace the HMI assembly.
Please Wait Screen
The please wait screen is shown when the HMI will take several seconds to complete an operation.
Examples are when parameters are being written to the drive chassis and when saving history data to a USB
flash drive. This screen does not indicate a problem and should go away in less than a minute. Parameter
write operations usually take 2 3 seconds. Resetting to factory defaults and saving history data to a USB
flash drive can take up to a minute.
Fault Status Screen
The fault status screen is displayed when a fault occurs. One may also access the Fault Status screen using
the HMI menu system. Messages displayed include:
Fault Message

Description

Corrective Action

Analog 1 Hi Limit Fault

The signal on analog 1 (connected to terminal


location 36) is higher than the max limit
programmed in the Analog 1 Setup screen.
The signal on analog 1 (connected to terminal
location 36) is lower than the min limit
programmed in the Analog 1 Setup screen.
The signal on analog 2 (connected to terminal
location 39) is higher than the max limit
programmed in the Analog 2 Setup screen.
The signal on analog 2 (connected to terminal
location 39) is lower than the min limit
programmed in the Analog 2 Setup screen.
The breaker switch in a 2 breaker system has
been thrown. Power is available only from 1 of the
input sources.

This is not a fault. The drive has stopped as it


was programmed.

Analog 1 Lo Limit Fault


Analog 2 Hi Limit Fault
Analog 2 Lo Limit Fault
Breaker 2 Fault

CE ModBus Com Error

CPF Hardware Error

The drive detected a loss of communications from


the HMI. Note that this is common on power up
if the drive is powered off and powered back on
before the drive DC bus has time to discharge.
One or more internal drive controller faults have
occurred.

This is not a fault. The drive has stopped as it


was programmed.
This is not a fault. The drive has stopped as it
was programmed.
This is not a fault. The drive has stopped as it
was programmed.
Test input voltage at both MCCB1 and 2. If one
is missing, locate bad Transformer and replace.
If both input are good, check voltage at bottom
of MCCB1 and 2. Replace faulty MCCB.
Verify HMI screen is on; verify connections to
the HMI and drive.
Try these one at a time
Cycle power off and back on.
Remove drive chassis keypad and reinstall
it.
Reset to factory defaults.
Replace the drive control board.

Fault Message
EF/EF0 External Error

Description
External Fault has occurred. Further data will be
provided below this line.

External Fault #1

External Fault switch 1 (connected to terminal


location 11) is in the fault condition.

Corrective Action
Troubleshoot External Fault #1, External Fault
#2, Breaker 2 Fault based on the additional
data provided.
Verify connection at 11, replace external
component attached to 11

External Fault #2

External Fault switch 2 (connected to terminal


location 12) is in the fault condition.
External Fault switch 3 (connected to terminal
location 16) is in the fault condition.

Verify connection at 12, replace external


component attached to 12
Verify connection at 16, replace external
component attached to 16

External Fault #3

imagination at work

VII

VECTOR
FBL PI FB Lost

PI Control loop feedback is out of the acceptable


range.

LF Missing Output Phase

Output current imbalance among phases has


exceeded the limit. Note that this is common
when running the drive with no load (or a very
small load). This detection can be disabled for
no load testing by setting parameter L8-07 in the
linear list to 0. It is recommended that L8-07 be
returned to 1 prior to field use.
The drive Over current limit has been exceeded.
This designator can also mean Ground Fault.

OC/GF Over current

Verify the analog device used for drive control


is connected to terminal position 39 and is
working properly.
Take voltage reading at output of drive.
Troubleshoot each phase output components
with power removed.

Verify Limits and time delays are set properly.


Troubleshoot to system component beyond
the drive.
Check proper fan operation, check continuity
of Thermistors, check semiconductors for
excessive heat.
Reduce load so drive output current does not
exceed the current set on the HMI.

OH1/OH2 Drive
Overheat

Drive temperature limit has been exceeded.

OL1/OVL Motor
Overload

An excessive motor load exists.

OV DC Bus Overvoltage

DC bus voltage has risen above the maximum


allowed.

Verify incoming (mains) power to be within


specifications.

OL2 Drive Overload

Drive overload has been detected. Drive has been


shut down to protect itself.

Reduce load or extend Accel time.

OPR No Keypad

The internal inverter keypad has been


disconnected.

This error should never occur. Reset drive to


defaults.

PUF Fuse Blown

DC bus fuse has opened.

Check main DC Bus fuse (Must remove from the


system) and all other fuses.

SmartGuard Data
Disabled

The SmartGuard interface has been disabled.

This is not a fault. If you wish to enable the


SmartGuard, see the Misc Setup screen.

SmartGuard Data Fault


SG Code: <code>
<Fault source>

The fault source indicates the SmartGuard


parameter that has exceeded a minimum or
maximum and has stopped the drive (example
Motor Temperature).
The motor load is less than the Underload Current
specified on the Underload setup screen (possibly
due to pumping off the well fluids).

Verify SmartGuard limit settings are set up as


desired. Verify well conditions fall within the
limit settings.

UV DC Bus
Undervoltage

DC bus voltage fell below minimum value.

Check incoming AC line for low voltage or


power interruption.

UV1/UV2/UV3 Other
Undervoltage

Main circuit, control power supply error, soft


charge circuit failure.

Check incoming AC line for low voltage or


power interruption. Check internal power
supply. Check soft charge circuit for proper
operation

ULF Underload

Verify limit is set properly. Verify time delay is


set properly. Troubleshoot to motor.

Events Screen
Events such as drive starts and stops, drive faults, and parameter changes can be viewed using the Events
screen. Events displayed include:
Event
Program Started
Drive Start
Remote Start
Drive Stop
Log In
Log Out
Fault! Code=<> - <Fault Description>
Fault Cleared
Alarm! Code=<> - <Alarm Description>
Alarm Cleared
Fatal Error! Code=<> - <Error Description>

Description
Indicates the drive has been powered up.
Drive started.
Drive started in remote mode.
Drive stopped.
An operator has logged in to the drive.
An operator has logged out or the drive has logged the operator out after
1 hour.
A fault has occurred. Refer to the Fault section above for corrective
actions.
The fault condition has been cleared.
An alarm is active.
The alarm condition has been cleared.
A fatal error has occurred.

PN: 196399 Revision: 6.6.2

107

GE Oil & Gas

Drive Comm! Drive Comms Lost


Drive Comm! Drive Comms
OK
External I/O! SmartGuard Comms Lost
External I/O! SmartGuard Comms OK
External I/O! Data Bad (Sync Loss)
External I/O! Data OK
SG Fault Code:<> <Description>
External Stop Entering Standby State
External Stop Cleared Restarting Drive
Entering Restart State
Excessive Button Presses
Safety Stop Activated
Drive Disabled Drive is NOT rev <required revision>
Overload change during run: <results>
<Parameter Description> Was=<> Now=<>
<Parameter Description> Now=<>
SCADA Time set to <C time value>
SCADA DO1 set to <0, 1>
SCADA DO2 set to <0, 1>
<Parameter Description> : Out of range val = <value>

The HMI lost communications with the drive chassis


Communications with the drive chassis were reestablished.
The HMI lost communications with the SmartGuard SSU.
Communicationswith the SSU has been reestablished.
The SmartGuard SSU has lost synchronization with the downhole tool.
Synchronization between the SSU and the downhole tool has been
reestablished.
The SmartGuard SSU has declared a fault. The code and description
describe the source (i.e. Intake Temperature).
The Standby (Lease Kill) switch has opened. The drive is entering the
Standby state.
The Standby (Lease Kill) switch has closed. The drive is restarting.
The drive has faulted but will restart automatically.
Log excessive button presses (> 100) as events showing a possible
hardware problem.
The HMI detected a drive running state when the drive should have been
stopped. The stop command was re-sent to the drive.
The drive has been disabled because the HMI firmware revision is not
compatible with the drive chassis firmware. This is most likely to occur
when the HMI firmware is updated.
A motor overload change was attempted while the drive was running. The
results of the change are shown.
The specified parameter was changed.
The specified parameter was changed. This message is associated with
setpoint changes from the Run Status screen.
The time has been via SCADA.
Digital output 1 has been set to the specified value via SCADA.
Digital output 2 has been set to the specified value via SCADA.
The operator tried to set the specified parameter to the specified value,
which is out of its acceptable range.

All Monitors Screen


The All Monitors screen can be used to view a significant amount of drive chassis status at one time. Please
see section 4.14 for details on how to interpret the data on the All Monitors screen.

9.3 General Maintenance


9.3.1 Periodic Inspection NO Power Applied
Danger The following inspections require that the drive de-energized and incoming power locked out.
Verify that the DC bus has been completely discharged before continuing. To prevent electrical shock,
wait at least five minutes after removing power and measure the DC bus voltage between the +3 and
terminals to confirm safe level of voltage.
Verify all external terminals, mounting bolts, and connectors are fastened and tightened.
Verify that the cooling fans free to turn and free of dust and dirt.
Verify that the heat sink fins are clear of dirt and debris. Keep them clean.
Verify that there are no signs of water entry into the drive enclosure.
Verify that door seal shows no signs of damage.
Verify that there is no dust/dirt/oil buildup on any of the drive components.
Verify that there are no irregularities (discoloration/odor) with the DC bus capacitors. If there is, replace
immediately.

9.3.2 Periodic Inspection Power Applied (External Only)


Verify proper operation of external cooling fans.
Verify proper operation of heat exchanger.
Check for abnormal noises or vibration. If present, shut down drive immediately.

imagination at work

VII

VECTOR
Appendix
1

Dimensions and Weights


DIMENSIONS & WEIGHTS - VECTOR VII WITHOUT VSG
REFERENCE ONLY

A and B Frames

FRAME

KVA

344
428
561

HEIGHT (INCHES
/ MM)
H
88 / 2236

WIDTH
(INCHES / MM)
W
W1
57 / 1448

48 / 1220

DEPTH
(INCHES / MM)
D
D1
40 / 1016

36 / 915

WEIGHT
(POUNDS / KG)
1281 / 582
1325 / 601
1600 / 726

Note: VSG is recommended for all GE OIL & GAS applications.

PN: 196399 Revision: 6.6.2

109

GE Oil & Gas


DIMENSIONS & WEIGHTS - VECTOR VII WITH AND WITHOUT VSG
REFERENCE ONLY


A Frame

FRAME

KVA

104
150
200
253

B Frames

HEIGHT (INCHES
/ MM)
H
80 / 2032

WIDTH (INCHES / MM)


W
35 / 889

W1
30 / 762

DEPTH
(INCHES / MM)
D
D1
41 / 1042
36 / 915

82 / 2083

48 / 1220

36 / 915

42 / 1067

Note: VSG is required for all GE OIL & GAS applications.

imagination at work

36 / 915

WEIGHT (POUNDS
/ KG)
800 / 363
1320 / 599
1400 / 635
1470 / 667

VII

VECTOR
DIMENSIONS & WEIGHTS - VECTOR VII WITH VSG
REFERENCE ONLY

C Frame
FRAME

KVA

344
428
561

HEIGHT (INCHES
/ MM)
H
103 / 2616

WIDTH (INCHES / MM)


W

W1

57 / 1448

48 / 1220

PN: 196399 Revision: 6.6.2

DEPTH
(INCHES / MM)
D
D1
40 / 1016

36 / 915

WEIGHT (POUNDS
/ KG)
1781 / 808
1825 / 828
2100 / 953

111

GE Oil & Gas

Default Parameter Values

Parameter
Language
Date Format
Local / Remote
Control Location
User Selected 1 5
Drive Mode
Frequency Setpoint
Current Setpoint
Current Frequency Limit
PI Proportional
PI Integral
Pressure Source
Pressure Setpoint
PI Proportional
PI Integral
Analog 2 Type
A2 Input Voltage 1
Engineering Units 1
A2 Input Voltage 2
Engineering Units 2
Analog In 2 Units
Signal Source
Minimum Frequency
Input at Min Freq
EU Value Min
Maximum Frequency
Input at Max Freq
EU Value Max
Analog In A1 Units
Motor Amps
Motor Overload Amps
Oload Time Constant
Oload Start Delay
Overload Restart
Overload @ Min Freq
Overload Delay
Restart Tries
Restart Delay
Restart Clear Time
Underload Current
Uload Start Delay
Underload Delay
Underload Restart Tries
Underload Restart Time
Underload Restart OK
Underload @ Min Freq
Restart on Pwr Loss
Ride Thru Restart
Start Holdoff Time
V/F Select
Motor Direction
Maximum Frequency
Minimum Frequency
Acceleration Time
Deceleration Time
Voltage Bias
Jog Setpoint
Lockout Frequency 1
Lockout Frequency 2
Lockout Frequency 3
Lockout Deadband

Screen
Setup (login not required)
Setup (login not required)
Setup (login not required)
Setup (login not required)
Setup (login not required)
Operating Mode
Operating Mode (Frequency Control)
Operating Mode (Current Control)
Operating Mode (Current Control)
Operating Mode (Current Control)
Operating Mode (Current Control)
Operating Mode (Pressure Control)
Operating Mode (Pressure Control)
Operating Mode (Pressure Control)
Operating Mode (Pressure Control)
Operating Mode (Pressure Control)
Analog 2 Setup
Operating Mode (Pressure Control)
Analog 2 Setup
Operating Mode (Pressure Control)
Analog 2 Setup
Operating Mode (Pressure Control)
Analog 2 Setup
Operating Mode (Pressure Control)
Analog 2 Setup
Operating Mode (Pressure Control)
Analog 2 Setup
Operating Mode (Signal Follower)
Operating Mode (Signal Follower)
Frequency Setup
Operating Mode (Signal Follower)
Operating Mode (Signal Follower)
Operating Mode (Signal Follower)
Frequency Setup
Operating Mode (Signal Follower)
Operating Mode (Signal Follower)
Operating Mode (Signal Follower)
Analog 1 Setup
Alarms Setup
Alarms Setup
Alarms Setup
Alarms Setup
Alarms Setup
Alarms Setup
Alarms Setup
Alarms Setup
Alarms Setup
Alarms Setup
Underload Setup
Underload Setup
Underload Setup
Underload Setup
Underload Setup
Underload Setup
Underload Setup
Start Control
Start Control
Start Control
Frequency Setup
Frequency Setup
Frequency Setup
Operating Mode (Signal Follower)
Frequency Setup
Operating Mode (Signal Follower)
Frequency Setup
Frequency Setup
Frequency Setup
Frequency Setup
Frequency Setup
Frequency Setup
Frequency Setup
Frequency Setup

imagination at work

Default Value
English
mm/dd/yyyy
Local
Keypad + SCADA
None
Frequency Control
60.00 Hz
250 A
60.0 Hz
2.00
5.0 sec
Discharge
0 PSI
2.00
5.0 Sec
0-10V
0.0 V/mA
0
10 V/mA
10
V
Analog Input A1
30.0 Hz
0.0 V
0.0
60.0 Hz
10.0 V
100.0
V
Drive Rated Amps
Drive Rated Amps
8.0 min
0s
Disabled
0%
0.0 s
0
45.0 min
60 min
0.0 A
0s
0.0 sec
0
45.0 min
60 min
100%
Disabled
Disabled
0.0 min
60Hz / Std Torque
Forward
60.0 Hz
30.0 Hz
30.0 Sec
30.0 Sec
0.0 V
60.00 Hz
0.0 Hz
0.0 Hz
0.0 Hz
2.0 Hz

VII

VECTOR
Parameter

A1 Input Voltage 1
Engineering Units 1
A1 Input Voltage 2
Engineering Units 2
Analog In A1 Units

Screen

Max Value
Min Value
Analog 2 Delay
Analog 2 Fault
Enable
SmartGuard Enable
Transformer Ratio
Drive Type
Password
External Fault 1
Ext Fault 1 Restart
External Fault 2
Ext Fault 2 Restart
Standby Switch
Breaker 2 Fault
ModBus Address
Drive Port (485)

Analog 1 Setup
Analog 1 Setup
Analog 1 Setup
Analog 1 Setup
Analog 1 Setup
Operating Mode (Signal Follower)
Analog 1 Setup
Analog 1 Setup
Analog 1 Setup
Analog 1 Setup
Analog 2 Setup
Analog 2 Setup
Operating Mode (Pressure Control)
Analog 2 Setup
Operating Mode (Pressure Control)
Analog 2 Setup
Operating Mode (Pressure Control)
Analog 2 Setup
Operating Mode (Pressure Control)
Analog 2 Setup
Operating Mode (Pressure Control)
Analog 2 Setup
Analog 2 Setup
Analog 2 Setup
Analog 2 Setup
Misc Setup
Misc Setup
Misc Setup
Misc Setup
Misc Setup
Misc Setup
Misc Setup
Misc Setup
Misc Setup
Misc Setup
Comm Setup
Comm Setup

SCADA Comm Port


SCADA 2 Comm
Port
SmartGuard Port

Comm Setup
Comm Setup
Comm Setup

DHCP Enable
IP Address
Jog Setpoint
Rock Start
Acceleration Time
Deceleration Time

Comm Setup
Comm Setup
Hard Starting
Hard Starting
Hard Starting
Hard Starting

Max Value
Min Value
Analog 1 Delay
Analog 1 Fault Enable
Analog 2 Type
A2 Input Voltage 1
Engineering Units 1
A2 Input Voltage 2
Engineering Units 2
Analog In A2 Units

PN: 196399 Revision: 6.6.2

Default Value
0.0 V
0
10.0 V
10
V

0 EU
0 EU
0.0 min
Disabled
0-10 V
0.0 V/mA
0
10.0 V/mA
10
V
0 EU
-30 EU
0.0 min
Disabled
Disabled
1.0 : 1
Single (inverter)
3333
Disabled
Disabled
Disabled
Disabled
Disabled
Disabled
2
Viper COM5
OCP COM4
Disabled
Disabled
Viper COM4
OCP COM3
Disabled
192.168.2.101
60.00 Hz
Disabled
30.0 Sec
30.0 Sec

113

GE Oil & Gas

USB Flash Drive Operation


Necessary Equipment:
1. USB Flash Drive P/N: 810280

Appendix Figure 3.1 Saved files Example

3.1 Save History files


Saving history files is a benefit to the customer and WGGE OIL & GAS to show critical well site information which is
useful for well performance tuning and during troubleshooting operations to maximize flow rates and maintain a
properly working system.
Insert USB flash drive into USB port located on the front of the HMI.
From the (logged in) Menu screen, select History screen.
Press the F4 (Save) soft key.
o The files will save to your USB flash drive as:
CUR_VSD SER_MMDDYYYY.xls (ex. CUR_VSD SER_07092008.xls)
LOG_VSD SER_MMDDYYYY.xls
CONFIG_VSD SER_MMDDYYYY.txt
EVENT_VSD SER_MMDDYYYY.doc.
o This operation will take several seconds, do not remove the USB flash drive or press any
soft keys while the HMI screen shows Drive Busy.
Once you have acquired these files onto your USB Flash portable memory, you can view these files on your laptop or
desktop computer.
The current file will show as an Excel Comma Separated Values spreadsheet and may also be viewed through our
Amp chart program as an actual amp chart. Refer to FSB 08004.
The Log, Config and Event files are viewed as text files and will show you the setup and events (256) as the drive was
functioning when the files were taken.

3.2 Save Configuration to USB flash drive


The following Config file can be used to view the parameters of the drive or to set up another well site identical to the
information that has been saved.



Insert USB flash drive into USB port located on the front of the HMI.
From the (logged in) Menu screen, Select Maintenance screen.
Highlight Save configuration to USB flash drive.
Press the F1 (OK) soft key
o The file will save to your USB flash drive as:
CONFIG.txt
o This operation will take several seconds, do not remove the USB flash drive or press any
soft keys while the HMI screen shows Drive Busy.

Note: Once a drive has been configured for an application, and the Configuration file has been saved to
a USB flash drive, this configuration can be loaded to another Vector VII drive being used for the same
application. The other drive(s) being loaded with this configuration must have the same firmware version

imagination at work

VII

VECTOR
installed.
Note: The drive must be STOPPED to use this function.
To load a previously saved drive configuration into another drive, refer to Appendix 3.4.

3.3 Save Linear List to USB flash drive


Saving the linear list will give the user the ability to view every parameter, the setting of each parameter, each
parameters SCADA Register and an asterisk the will tell you that the parameter has been changed from its factory
default position.



Insert USB flash drive into USB port located on the front of the HMI.
From the (logged in) Menu screen, Select Maintenance screen.
Highlight Save Linear List to USB flash drive.
Press the F1 (OK) soft key
o The file will save to your USB flash drive as:
lldata.txt
o This operation will take several seconds, do not remove the USB flash drive or press any soft keys
while the HMI screen shows Drive Busy.

Note: This feature cannot be loaded to another drive. It is intended for off site troubleshooting using another drive or
drive trainer.
Note: The drive must be STOPPED to use this function.

3.4 Load configuration from a USB flash drive to a Vector VII drive
From the previous 13.2, you can take a previously saved Config file and load it into another Vector 7 drive to create
an identical copy of an existing well programming.



Insert USB flash drive into USB port located on the front of the HMI.
From the (logged in) Menu screen, Select Maintenance screen.
Highlight Load Configuration from USB flash drive.
Press the F1 (OK) soft key
o The file will load from your USB flash drive.
o This operation will take several seconds, do not remove the USB flash drive or press any soft keys
while the HMI screen shows Drive Busy.
Execute the Check / Update all drive parameters function.

Note: The drive must be STOPPED to use this function.


Warning: Do not try to load a previous firmware version configuration file. This will result in Firmware corruption
and all data will be LOST.

PN: 196399 Revision: 6.6.2

115

GE Oil & Gas

Linear List

A1-00

Select
Language

A1-01

Access Level

A1-03

Init
Parameters

Language selection for digital operator display


0 = English
2 = Deutsch
3 = Francais
4 = Italiano
5 = GE Oil & Gasanol
6 = Portuguese
*Not returned to factory setting by initialization
This setting determines which parameters are
accessible.
0 = Operation Only
1 = User Level
2 = Advanced Level
Used to return all parameters to their factory or user
setting.
0 = No Initialize
1110 = User Initialize (The user must set their own
parameter default values and then parameter o2-03
must be set to 1 to save them. If the parameter values
are changed after o2-03 is set to 1, the user default
values can be restored by setting A1-03 to 1110.)

0 to 6

0 to 2

0 to 3330

0 to 9999

0 to 9999

N/A

B1-01
to
O3-02

0 to 3

2220 = 2-Wire Initial


3330 = 3-Wire Initial
A1-04

Enter
Password

A1-05

Select
Password

A2-(0132)

B1-01

User Parameters

Reference
Source

When the value set into A1-04 does NOT match the
value set into A1-05, parameters A1-01 thru A1-03
and A2-01 thru A2-32 cannot be changed. All other
parameters as determined by A1-01 can be changed.
Parameter A1-05 can be accessed by pressing the
MENU key while holding the RESET key.
Selects the parameters to be available in the User
Access Level (A1-01 = 1). These are the only parameters
accessible for the user level. These parameters are not
related to the User Initialize function.
Selects the speed command (frequency reference)
input source.
0 = Operator - Digital preset speed d1-01
1 = Terminals - Analog Input Terminal A1 (or Terminal
A2 see parameter H3-13)
2 = Serial Com - RS-485 terminals R+, R-, S+ and S3 = Option PCB - Option board connected at 2CN

imagination at work

VII

VECTOR
Run Source

Selects the run command input source.


0: Operator - Run and Stop keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 terminals R+, R-, S+ and S3: Option PCB - Option board connected at 2CN

0 to 3

Stopping
Method

Selects the stopping method when the run command is


removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast w/Timer (A new run command is ignored if
input before
the time in C1-02 expires.)

0 to 3

Reverse Oper

Determines the forward rotation of the motor, and if


reverse operation
is disabled.
0: Reverse Enabled
1: Reverse Disabled
2: Exchange Phase - Change direction of forward motor
rotation.
3: ExchgPhs, Rev Dsbl - Change direction of forward
motor
rotation and disable reverse operation.

0 to 3

B1-07

Loc / Rem Run


Sel

0: Cycle Extern RUN - If the run command is closed


when switching from hand(local) mode to auto(remote)
mode, the drive will not run.
1: Accept Extrn RUN - If the run command is closed
when switching from hand(local) mode to auto(remote)
mode, the drive WILL run.

0 or 1

B1-08

Run Cmd at
Prg

0: Disabled - Run command accepted only in the


operation menu.
1: Enabled - Run command accepted in all menus
(except when b1-02 = 0).

0 or 1

B1-11

Drive Delay
Time

After a run command, drive output will start after this


delay time.

0 sec

0 to 600

0 or 1

B1-02

B1-03

B1-04

B1-12

Hand Fref Sel

Selects the speed command input source in hand


mode.*
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2
see
parameter H3-13)

PN: 196399 Revision: 6.6.2

117

GE Oil & Gas

Sets the frequency at which DC injection braking starts


when ramp
to stop (b1-03 = 0) is selected. If b2-01< E1-09, DC
Injection braking
starts at E1-09.

B2-01

DCINJ Start
Freq

B2-02

DCINJ Current

Selects the DC injection braking current as a


percentage of the
Drive rated current.

B2-03

DCINJ Time @
Start

B2-04

B2-09

0.5 Hz

0.0 to 10.0

50%

0 to 100

Sets the time length of DC injection braking at start in


units of 1
second.

0.00 sec

0.00
to
10.00

DCINJ Time @
Stop

When b1-03 = 2 actual DC Injection time is calculated


as follows:
b2-04 * 10 * Output Frequency / E1-04. When b1-03 =
0, this parameter determines the amount of time DC
Injection is applied to
the motor at the end of the decel ramp. This should be
set to a minimum of 0.50 seconds when using HSB. This
will activate DC injection during the final portion of HSB
and help ensure that the motor stops completely.

0.00 sec

0.00
to
10.00

Motor Pre-heat
Current

Motor Pre-heat current in % of drive rated current.


This is used to keep the motor warm to prevent
condensation and is used in conjunction
with a digital input (data = 60).

0%

0 to100

0 to 3

120%

0 to 200

2.0 sec

0.1 to 10.0

B3-01

SPDSRCH at
Start

B3-02

SPDSRCH
Current

B3-03

SPDSRCH Dec
Time

Enables/disables and selects the speed search function


at start.
0: SpdsrchF Disable - Speed search at start is disabled
(estimated speed method is used at other times)
1: SpdsrchF Enable - Speed search is enabled
(estimated speed method)
2: SpdsrchI Disable - Speed search at start is disabled
(current detection method is used at other times)
3: SpdscrhI Enable - Speed search is enabled
(current detection method)
Estimated Speed Method: Actual motor speed and
direction is estimated, then the motor is ramped from
that speed to the commanded speed.
Current Detection Method: Current level is monitored
while output frequency is ramped down.
Used only when b3-01 = 3. Sets the speed search
operation current as a percentage of drive rated
current.
Used only when b3-01 = 3. Sets the deceleration time
during speed search.

imagination at work

VII

VECTOR
B3-05

Search Wait
Time

Delays the speed search operation after a momentary


power loss to allow time for an external output
contactor to re-energize.

B3-14

BIDIR Search
Sel

0: Disabled
1: Enabled

B4-01

Delay-On
Timer

B4-02

Delay-Off
Timer

B5-01

PI Mode

B5-02

P Gain

B5-03

PI I Time

B5-04
B5-06

0.2 sec

0.0 to
20.0sec

0 or 1

0.0 sec

0.0 to
3000.0

0.0 sec

0.0 to
3000.0

0, 1, 3

0.00 to
25.00

Sets the integral time for the PI controller. A setting of


zero disables integral control.

5.0 sec

0.0 to 360.0

PI I Limit

Sets the maximum output possible from the integrator.


Set as a % of fmax.

100%

0.0 to
100.0

PI Limit

Sets the maximum output possible from the entire PI


controller. Set as a % of fmax.

0.00 to
100.0

B5-07

PI Offset

Sets the amount of offset of the output of the PI


controller. Set as a % of fmax. The PI Offset Adjustment
parameter has two different uses. Parameter b5-07
serves different functions depending on whether it is
used on a standard PI loop or a Differential PI loop.
1: Parameter b5-07 causes an offset to be applied to
the output of the PI function in a non-Differential PI
loop. Every time the PI output is updated, the offset
is summed with the PI output. This can be used to
artificially kick-start a slow starting PI loop.
2: If the Drive is configured for Differential PI Regulation
(H3-09=16), then the PI Offset is the targeted
maintained differential between the signal measured
on analog input A1 and the signal measured on analog
input A2.

0.00%

100.0 to
+100.0

B5-08

PI Delay Time

Sets the amount of time for a filter on the output of the


PI controller.

0.00 sec

0.00 to
10.00

B5-09

Output Level
Sel

0 or 1

Used in conjunction with a multi-function digital input


and a multifunction digital output. This sets the amount
of time between when the digital input is closed, and
the digital output is energized.
Used in conjunction with a multi-function digital input
and a multifunction digital output. This sets the amount
of time the output stays energized after the digital
input is opened.
This parameter enables / disables the closed loop (PI)
controller.
0: Disabled
1: Enabled (commanded speed becomes PI setpoint)
3: Fref+PI
Sets the proportional gain of the PI controller.

Determines whether the PI controller will be direct or


reverse acting.
0: Normal Output (direct acting)
1: Reverse Output (reverse acting)

PN: 196399 Revision: 6.6.2

119

GE Oil & Gas

B5-10

PI Output Gain

Sets the output gain of the PI controller.

0.0 to 25.0

B5-11

Output Rev Sel

0: 0 limit (when PI output goes negative Drive stops)


1: Reverse (when PI goes negative Drive reverses) 0 limit
automatic when reverse prohibit is selected using b104

0 or 1

B5-12

FB Los Det Sel

0: Disabled
1: Alarm
2: Fault

0 to 2

B5-13

FB Los Det Lvl

Sets the PI feedback loss detection level as a


percentage of maximum frequency (E1-04).

0%

0 to 100

B5-14

FB Los Det
Time

Sets the PI feedback loss detection delay time in terms


of seconds.

1.0 sec

0.0 to 25.5

B5-15

PI Sleep Level

Sets the sleep function start frequency.

0.0 Hz

0.0 to 200.0

B5-16

PI Sleep Time

Sets the sleep function delay time in terms of seconds.

0.0 sec

0.0 to 25.5

B5-17

PI SFS Time

Applies an accel/decel time to the PI setpoint reference.

0.0 sec

0.0 to 25.5

B5-18

PI Setpoint
Selection

0: Disabled
1: Enabled

0 or 1

B5-19

PI Setpoint

Depends on b5-20.

0.00%

0.00 to
100.00

B5-20

PI Setpoint
Scaling

Set display/setting Unit of b5-19.

0 to 39999

B5-21

PI Sleep Input
Source

Input Source Selection for Sleep function Mode.


0: SFS Input (This is near the PI Output.)
1: PI Setpoint
2: Snooze

0 to 2

B5-22

PI Snooze
Level

0%

0 to 100

B5-23

PI Snooze
Delay Time

Sets the PI snooze function delay time in terms of


seconds.

0 sec

0 to 3600

B5-24

PI Snooze
Deactivation
Level

When the PI feedback drops below this level, normal


PI operation starts again. Set as a percentage of
maximum frequency (E1-04).

0%

0 to 100

B5-25

PI Setpoint
Boost Setting

Temporary increase of PI setpoint to create an


overshoot of the intended PI setpoint.

0%

0 to 100

B5-26

PI Maximum
Boost Time

Sets a time limitation for reaching temporarily boosted


PI setpoint (intended PI setpoint + b5-25).

0 sec

0 to 3600

B5-27

PI Snooze
Feedback Level

PI snooze mode will be activated when PI feedback


is above this level. Set as a percentage of maximum
frequency (E1-04).

60%

0 to 100

Sets the PI snooze function start level as a percentage


of maximum frequency (E1-04).

imagination at work

VII

VECTOR
B5-28

PI Feedback
SQRT

0: Disabled
1: Enabled

0 or 1

B5-29

PI Fb SQRT
Gain

A multiplier applied to the square root of the feedback.

0.00 to 2.00

B5-30

PI Out Moni
SQRT

0: Disabled
1: Enabled

0 or 1

B8-01

Energy Save
Sel

Energy Savings function enable/disable selection


0: Disabled
1: Enabled

0 or 1

B8-04

Energy Save
Coeff

kVA Dep.

0.0 to
655.00

B8-05

KW Filter Time

20 ms

0 to 2000

B8-06

Search V Limit

0%

0 to 100

C1-01

Accel Time 1

Sets the time to accelerate from zero to maximum


frequency.

30.0 sec

C1-02

Decel Time 1

Sets the time to decelerate from maximum frequency


to zero.

30.0 sec

C1-03

Accel Time 2

Sets the time to accelerate from zero to maximum


frequency when selected via a multi-function input.

30.0 sec

C1-04

Decel Time 2

Sets the time to decelerate from maximum frequency


to zero when selected via a multi-function input.

30.0 sec

C1-09

Fast Stop
Time

Sets the time to decelerate from maximum frequency


to zero for the Fast Stop function.

10.0 sec

0.0
to
6000.0

Acc/Decc SW
Freq

Sets the frequency for automatic switching of accel /


decel times.
Fout < C1-11: Accel/Decel Time 2
Fout >= C1-11: Accel/Decel Time 1
Multi-function input Multi-Acc/Dec 1 has priority over
C1-11.

0.0 Hz

0.0 to
200.0

C1-11

Used to fine-tune the energy savings function.

PN: 196399 Revision: 6.6.2

0.0
to
6000.0

121

GE Oil & Gas

C2-01

SCRV Acc @
Start

0.20 sec

0.00 to
2.50

C2-02

SCRV Acc @
End

0.20 sec

0.00 to 2.50

C4-01

Torq Comp
Gain

This parameter helps to produce better starting torque.


It determines the amount of torque or voltage boost
based upon motor current and motor resistance.

0.00 to 2.50

C4-02

Torq Comp
Time

This parameter adjusts a filter on the output of the


torque compensation function. Increase to add torque
stability, decrease to improve torque rGE Oil & Gasonse.

200 ms

0 to 10000

C6-01

Normal Duty
Sel

1: Normal Duty 1
2: Normal Duty 2

1 or 2

C6-02

Carrier Freq
Sel

Carrier frequency sets the number of pulses per second


of the output voltage waveform.
0: Low Noise (Carrier frequency is randomly moduled
for lower audible noise)
1: Fc = 2.0 kHz
2: Fc = 5.0 kHz
3: Fc = 8.0 kHz
4: Fc = 10.0 kHz
5: Fc = 12.5 kHz
6: Fc = 15.0 kHz
F: Program (Determined by the settings of C6-03 thru
C6-05)

kVA Dep.

0 to F

C6-03

Carrier Freq
Max

Maximum carrier frequency allowed when C6-02 = F.

kVA Dep.

kVA
Dependent

C6-04

Carrier Freq
Min

Minimum carrier frequency allowed when C6-02 = F.

kVA Dep.

kVA
Dependent

C6-05

Carrier Freq
Gain

Sets the relationship of output frequency to carrier


frequency when C6-02 = F.

0 to 99

imagination at work

VII

VECTOR
D1-01

Reference 1

Digital preset speed command 1. Used when b1-01 = 0.


Setting units are affected by o1-03.

0.00 Hz

D1-02

Reference 2

Digital preset speed command 2. Selected via multifunction input terminals. Setting units are affected by
o1-03.

0.00 Hz

D1-03

Reference 3

Digital preset speed command 3. Selected via multifunction input terminals. Setting units are affected by
o1-03.

0.00 Hz

D1-04

Reference 4

Digital preset speed command 4. Selected via multifunction input terminals. Setting units are affected by
o1-03.

0.00 Hz

D1-17

Jog Reference

60 Hz

0.00 to
E1-04
Value

Ref Upper
Limit

Determines maximum speed command, set as a


percentage of parameter E1-04. If speed command
is above this value, actual drive speed will be limited
to this value. This parameter applies to all speed
command sources.

100.00%

0.0 to 110.0

Ref Lower
Limit

Determines minimum speed command, set as a


percentage of parameter E1-04. If speed command is
below this value, actual drive speed will be set to this
value. This parameter applies to all speed command
sources.

50.00%

0.0 to 110.0

D2-03

Ref 1 Lower
Limit

Determines the minimum speed command, set as a


percentage of parameter E1-04. If speed command is
below this value, actual drive speed will be set to this
value. This parameter only applies to analog inputs A1
and A2.

0%

0.0 to 110.0

D3-01

Jump Freq 1

D3-02

Jump Freq 2

D3-03

Jump Freq 3

D3-04

Jump
Bandwidth

D4-01

Mop Ref
Memory

D4-02

Trim Control
Lvl

D2-01

D2-02

Speed command used when a jog is selected via multifunction input terminals. Setting units are affected by
o1-03.

0.00 to
E1-04
Value

These parameters allow programming of up to three


prohibited frequency points for eliminating problems
with resonant vibration of the motor / machine. This
feature does not actually eliminate the selected
frequency values, but will accelerate and decelerate
the motor through the prohibited bandwidth.
This parameter determines the width of the deadband
around each selected prohibited frequency point. A
setting of 1.0 will result in
a deadband of +/- 1.0 Hz.
0: Disabled
1: Enabled
Set the percentage of maximum speed to be added or
subtracted via multi-function inputs.

PN: 196399 Revision: 6.6.2

0.0 Hz
0.0 Hz

0.0 to 200.0

0.0 Hz

2.0 Hz

0.0 to 20.0

0 or 1

10%

0 to 100

123

GE Oil & Gas

Input Voltage

Set to the nominal voltage of the incoming line.

480V

310 to 510.0
(480V)

E1-03

V/F Selection

0: 50Hz
1: 60 Hz Saturation
2: 50 Hz Saturation
3: 72 Hz
4: 50 Hz VT1
5: 50 Hz VT2
6: 60 Hz VT1
7: 60 Hz VT2
8: 50 Hz HST1
9: 50 Hz HST2
A: 60 Hz HST1
B: 60 Hz HST2
C: 90 Hz
D: 120 Hz
F: Custom V/F
FF: Custom w/o limit

0FH

0 to FF

E1-04

Max
Frequency

60.0 Hz

0.0 to
120.0

E1-05

Max Voltage

480V

0 to 510.0
(480V)

E1-06

Base
Frequency

60.0 Hz

0.0 to
200.0

E1-07

Mid Out Freq A

3.0 Hz

0.0 to 200.0

E1-08

Mid Out Volts


A

28.8 V

0 to 510.0
(480V

1.5 Hz

0.0 to 200.0

14.4 V

0 to 510.0
(480V)

E1-01

E1-09

Min Frequency

E1-10

Min Out Volts

To set V/f characteristics in a straight line, set the same


values for
E1-07 and E1-09. In this case, the setting for E1-08 will
be disregarded.
Always ensure that the four frequencies are set in the
following
manner:
E1-04 (FMAX) E1-06 (FA) > E1-07 (FB) E1-09 (FMIN)

imagination at work

VII

VECTOR
E1-11

Mid Frequency
B

E1-12

Mid Voltage B

E1-13

Base Voltage

E2-01

Motor Rated
FLA

Set to the motor nameplate full load amps.

kVA Dep.

10% to
200% kVA
Dependent

E2-03

No-Load
Current

Sets the magnetizing current of the motor.

kVA Dep.

kVA
Dependent

E2-05

Term
Resistance

Phase to phase motor resistance, normally set by the


autotuning routine.

kVA Dep.

0.000 to
65.000

F6-01

Bus Fault Sel

Sets the stopping method for option PCB


communications error (BUS fault). Active only when a
communications option PCB is
installed and when b1-01 or b1-02 = 3.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

F6-02

EF0 Detection

0: Always detected
1: Detected only during run

0 or 1

F6-03

EF0 Fault
Action

0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

F6-05

Current Display
Unit Sel

0: A Display (Amps)
1: 100%/8192 (Drive Rated Current)

0 or 1

0.0 Hz
Set only when V/f is finely adjusted at rated output
range.
Adjustment is not normally required.

0.0 VAC
0.0 VAC

PN: 196399 Revision: 6.6.2

0.0 to
200.0
0 to 510.0
(480V)

125

GE Oil & Gas

H1-01

Terminal S3
Sel

H1-02

Terminal S4
Sel

0: 3-wire control
FWD/REV selection for 3-wire sequence
1: Local/Remote Sel
Local/Remote Selection - Closed = Local, Open =
Remote
2: Option/Inv Sel
Selects source of speed command and sequence
Closed = b1-01 & b1-02, Open = Option Card
3: Multi-Step Ref 1
Closed = speed command from d1-02 or Aux Terminal
Open = speed command determined by b1-01
4: Multi-Step Ref 2
Closed = speed command from d1-03 or d1-04
Open speed command determined by b1-01
6: Jog Freq Ref
Closed = speed command from d1-17
Open = speed command determined by b1-01
7: Multi-Acc/Dec 1
Closed = Accel & Decel Ramps determined by C1-03 &
C1-04,
Open = Accel & Decel Ramps determined by C1-01 &
C1-02
8: Ext BaseBlk N.O.
Closed = Output transistors forced off, Open = Normal
operation
9: Ext BaseBlk N.C.
Closed = Normal Operation, Open = Output transistors
forced
off
A: Acc/Dec RampHold
Closed = Acceleration suspended and speed held, Open
=
Normal Operation
C: Term A2 Enable
Closed = Terminal A2 is active, Open = Terminal A2 is
disabled
F: Term Not Used
Terminal has no effect
10: MOP Increase
Closed = Speed Command Increases, Open = Speed
Command
Held.
Must be set in conjunction with MOP Decrease and b102 must
be set to 1.
11: MOP Decrease
Closed = Speed Command Decreases, Open = Speed
Command
Held.
Must be set in conjunction with MOP Increase and b102 must
be set to 1.

imagination at work

0FH

0 to 6E

0FH

0 to 6E

VII

VECTOR

H1-03

Terminal S5
Sel

H1-04

Terminal S6
Sel

12: Forward Jog


Closed = drive runs forward at speed command
entered into
parameter d1-17.
13: Reverse Jog
Closed = drive runs in reverse at speed command
entered into
parameter d1-17.
14: Fault Reset
Closed = Resets the drive after the fault and the run
command have been removed.
15: Fast-Stop N.O.
Closed = Drive decelerates using C1-09, regardless of
run command
status.
17: Fast-Stop N.C.
Closed = Normal operation
Open = Drive decelerates using C1-09, regardless of run
command status.
18: Timer Function
Input for independent timer, controlled by b4-01 and
b4-02.
Used in conjunction with a multi-function digital output.
19: PI Disable
Turns off the PI controller, and PI setpoint becomes
speed command.
1B: Program Lockout
Closed =All parameter settings can be changed.
Open = Only speed command at U1-01 can be
changed.
1C: TrimCtl Increase
Closed = Increase motor speed by value in d4-02.
Open = Return to normal speed command.
Not effective when using d1-01 thru d1-04 as a speed
command.
Must be used in conjunction with Trim Ctrl Decrease.
1D: Trim Ctl Decrease
Closed = Decrease motor speed by value in d4-02
Open = Return to normal speed command.
Not effective when using d1-01 thru d1-04 as speed
command.
Must be used in conjunction with Trim Ctrl Increase.

PN: 196399 Revision: 6.6.2

0FH

0 to 6E

0FH

0 to 6E

127

GE Oil & Gas

H1-05

Terminal S7
Sel

1E: Ref Sample Hold


Analog speed command is sampled then held at time
of input
closure.
20: External fault, Normally Open, Always Detected,
Ramp To
Stop
21: External fault, Normally Closed, Always Detected,
Ramp To
Stop
22: External fault, Normally Open, During Run, Ramp To
Stop
23: External fault, Normally Closed, During Run, Ramp
To Stop
24: External fault, Normally Open, Always Detected,
Coast To
Stop
25: External fault, Normally Closed, Always Detected,
Coast To
Stop
26: External fault, Normally Open, During Run, Coast To
Stop
27: External fault, Normally Closed, During Run, Coast
To Stop
28: External fault, Normally Open, Always Detected,
Fast-Stop
29: External fault, Normally Open, Always Detected,
Fast-Stop
2A: External fault, Normally Open, During Run, FastStop
2B: External fault, Normally Closed, During Run, FastStop
2C: External fault, Normally Open, Always Detected,
Alarm Only
2D: External fault, Normally Closed, Always Detected,
Alarm
Only

imagination at work

0FH

0 to 6E

VII

VECTOR

H1-05
Cont.

Terminal S7
Sel Cont.

2E: External fault, Normally Open, During Run, Alarm Only


2F: External fault, Normally Closed, During Run, Alarm Only
30: PI Integral Reset
Resets the PI Integral component to zero when closed
31: PI Integral Hold
Holds the PI integral value when closed
34: PI SFS Cancel (SFS= SoftStart, also called Accel/Decel,
See Parameter b5-17)
35: PI Input Level Sel
Inverts the PI error signal when closed
36: Option/Inv Sel 2 Selects source of speed command and
sequence
Closed = Option Card, Open = b1-01 & b1-02
60: Motor Preheat
Applies current to create heat to avoid condensation
Closed = Apply amount of current as set in parameter b2-09
(Continued on next page)
61: Speed Search 1When closed as a run command is given,
drive does a speed
search starting at maximum frequency (E1-04). (current
detection)
62: Speed Search 2
When closed as a run command is given, drive does a speed
search starting at speed command. (current detection)
64: Speed Search 3
When opened, the Drive performs a baseblock (motor coasts).
When closed, the Drive performs Speed Search from set
frequency.
67: Com Test Mode - Used to test RS-485/422 interface.
68: High Slip Braking - Closed = Drive stops using High Slip
Braking regardless of run command status.
69: Jog2 - Closed = Drive runs at speed command entered
into
parameter d1-17. Direction determined by fwd/rev input.
3-wire control Only.
6A: Drive Enable - Closed = Drive will accept run command.
Open = Drive will not run. If running, drive will stop per b1-03.
Run Command must be cycled v Sel - Selects source of Speed
Command and Sequence. Closed = Serial Communication
(R+,R-,S+,S-), Open = b1-01 & b1-02
6C: Com/Inv Sel 2 - Selects source of Speed Command and
Sequence. Closed = b1-01 & b1-02, Open = Serial
Communication (R+,R-,S+,S-)
6D: Auto Mode Sel - Hand/Auto Selection - Closed = Auto,
Open = Hand
6E: Hand Mode Sel - Hand/Auto Selection - Closed = Hand,
Open = Auto
70: Bypass/Drv Enbl. Same as 6A except a run command is
accepted
80: Motor Preheat 2 - Closed = Enable motor preheat with the
current level as set by b2-10
81: EmergOverrideFWD - Closed = Forward Emergency
Override Command
82: EmergOverrideREV - Closed = Reverse Emergency
Override Command

PN: 196399 Revision: 6.6.2

0FH
Cont.

0 to 6E Cont.

129

GE Oil & Gas

H2-01

Terminal M1M2 Sel

H2-02

Terminal M3M4 Sel

0: During RUN 1 = Closed when a run command is input or


the drive is outputting voltage.
1: Zero Speed = Closed when drive output frequency is less
than Fmin (E1-09)
2: Fref/Fout Agree 1 = Closed when drive output speed
equals the speed command within the
bandwidth of L4-02.
3: Fref/Set Agree 1 = Closed when the drive output speed
and the speed command are equal to
the value in L4-01 within the bandwidth of L4-02.
4: Freq Detect 1 = Closed when the drive output speed is
less than or equal to the value in L4-01,
with hysteresis determined by L4-02.
5: Freq Detect 2 = Closed when the drive output speed is
greater than or equal to the value in
L4-01, with hysteresis determined by L4-02.
6: Inverter Ready = Closed when the drive is not in a fault
state, and not in program mode.
7: DC Bus Undervolt = Closed when the DC bus voltage
falls below the UV trip level (L2-05)
8: Base Blk 1 = Closed when the drive is not outputting
voltage.
9: Operator Reference = Closed when the speed command
is coming from the digital operator.
A: Remote/Auto Oper = Closed when the run command is
coming from the digital operator.
B: Trq Det 1 N.O. - Closes when the output current exceeds
the value set in parameter
L6-02 for more time than is set in parameter L6-03.
C: Loss of Ref - Closes when the drive has detected a loss
of analog speed command.
Speed command is considered lost when it drops 90% in
0.4 seconds.
Parameter L4-05 determines drive reaction to a loss of
speed command.
D: DB Overheat
E: Fault - Closes when the drive experiences a major fault.
F: Not Used
10: Minor Fault - Closes when drive experiences a minor
fault or alarm.
11: Reset Cmd Active - Closes when the drive receives a
reset command from terminals or serial comms.
12: Timer Output - Output for independent timer, controlled
by b4-01 and b4-02.
Used in conjunction with a multi-function digital input.
17: Trq. Det 1 N.C. - Opens when the output current
exceeds the value set in parameter
L6-02 for more time than is set in parameter L6-03.
1A: Reverse Dir - Closes when the drive is running in the
reverse direction.
1E: Restart Enabled - Closes when the drive is performing
an automatic restart.
Automatic restart is configured by parameter L5-01.
1F: Overload (OL1) - Closes before a motor overload
occurs. (90% of OL1 time)
20: OH Prealarm - Closes when the Drives heatsink
temperature exceeds the setting
of parameter L8-02.
38: Drive Enable - Closes when the drive enable input is
active.
39: Waiting to Run - Closes during the time after a run
command is issued, but the Drive is not running due to
the time set in parameter b1-10.
3A: OH Freq Reduce
3B: Run Src Com/Opt
3D: Cooling Fan Err = Closed during internal cooling fan
failure

imagination at work

0AH

VII

VECTOR
H3-02

Term A1 Gain

Sets the speed command when 10V is input, as a


percentage of the maximum output frequency (E1-04).

100.00%

0.0 to
1000.0

H3-03

Term A1 Bias

Sets the speed command when 0V is input, as a


percentage of the maximum output frequency (E1-04).

0.00%

100.0 to
+100.0

H3-08

Term A2
Signal

Selects the signal level of terminal A2.


0: 0 - 10VDC (switch S1-2 must be in the off position)
2: 4 - 20 mA (switch S1-2 must be in the on position)

0 or 2

Selects what effect the Aux terminal (A2) has on the


drive.
0: Frequency Bias - 0 - 100% bias
2: Aux Reference
B: PI Feedback
D: Frequency Bias 2 - 0 - 100% bias
E: Motor Temperature - See parameters L1-03 & L1-04
16: PI Differential
1F: Not Used

11

0 to 1F

100.00%

0.0 to
1000.0

0.00%

100.0 to
+100.0

0.30 sec

0.00 to
2.00

0 or 1

H3-09

Terminal A2
Sel

H3-10

Terminal A2
Gain

H3-11

Terminal A2
Bias

H3-12

Filter Avg Time

H3-13

TA1/A2 Select

Sets the level of the A2 function corrGE Oil & Gasonding


to a
10V input (in%).
Sets the level of the A2 function corrGE Oil & Gasonding
to a
0V input (in%).
Used to smooth out erratic or noisy analog input
signals.
Determines which terminal will be the main reference
source.
0: Main Fref TA1 - Terminal TA1 is the main speed
command and Terminal TA2 is the Aux speed
command.
1: Main Fref TA2 - Terminal TA2 is the main speed
command and Terminal TA1 is the Aux speed
command. Only effective when H3-09 is set to 2 Aux
Reference.

PN: 196399 Revision: 6.6.2

131

GE Oil & Gas

H4-01

Terminal FM
Sel

H4-02

Terminal FM
Gain

H4-03

Terminal FM
Bias

H4-04

Terminal AM
Sel

H4-05

Terminal AM
Gain

Selects which monitor will be output on terminals FM


and AC.
1: Frequency Ref (100% = max. output frequency)
2: Output Freq (100% = max. output frequency)
3: Output Current (100% = drive rated current)
6: Output Voltage (100% = 230V or 100% = 460V)
7: DC Bus Voltage (100% = 400V or 100% = 800V)
8: Output kWatts (100% = drive rated power)
15: Term A1 Level
16: Term A2 Level
18: Mot SEC Current (100% = Motor rated secondary
current)
20: SFS Output (100% = max. output frequency)
24: PI Feedback
31: Not Used
36: PI Input
37: PI Output (100% = max. output frequency)
38: PI Setpoint
51: Auto Mode Fref (100% = max. output frequency)
52: Hand Mode Fref (100% = max. output frequency)
53: PI Feedback 2
NOTE: 100% = 10V DC output * FM gain setting
(H4-02).
Sets terminal FM output voltage (in percent of 10V)
when selected monitor is at 100% output.
Sets terminal FM output voltage (in percent of 10V)
when selected monitor is at 0% output.
Selects which monitor will be output on terminals AM
and AC.
1: Frequency Ref (100% = max. output frequency)
2: Output Freq (100% = max. output frequency)
3: Output Current (100% = drive rated current)
6: Output Voltage (100% = 230V or 100% = 460V)
7: DC Bus Voltage (100% = 400V or 100% = 800V)
8: Output kWatts (100% = drive rated power)
15: Term A1 Level
16: Term A2 Level
18: Mot SEC Current (100% = Motor rated secondary
current)
20: SFS Output (100% = max. output frequency)
24: PI Feedback
31: Not Used
36: PI Input
37: PI Output (100% = max. output frequency)
38: PI Setpoint
51: Auto Mode Fref (100% = max. output frequency)
52: Hand Mode Fref (100% = max. output frequency)
53: PI Feedback 2
NOTE: 100% = 10V DC output * AM gain setting
(H4-05).
Sets terminal AM output voltage (in percent of 10V)
when selected monitor is at 100% output.

imagination at work

1 to 53

100.00%

0.0 to
1000.0

0.00%

110.0 to
110.0

1 to 53

50.00%

0.0 to
1000.0

VII

VECTOR
H4-06

Terminal AM
Bias

Sets terminal AM output voltage (in percent of 10V)


when selected monitor is at 0% output.

0.00%

110.0 to
110.0

H4-07

AO Level Sel

0: 0 - 10 VDC
2: 4-20 mA*

0 or 2

0: 0 - 10 VDC
2: 4-20 mA*
* An analog output of 4 - 20 mA can not be used with
the standard terminal board. Therefore an optional
terminal board (with shunt connector CN15) is needed.

0 or 2

H4-08

AO Level Sel 2

H5-01

Serial Comm
Adr

Selects drive station node number (address) for


terminals R+, R-, S+, S-.*
An address of 0 disables serial com.

0 to FF

Serial Baud
Rate

Selects the baud rate for terminals R+, R-, S+ and S-.*
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud (APOGEE FLN)
3: 9600 Baud (Metasys N2)
4: 19200 Baud

0 to 4

Serial Com Sel

Selects the communication parity for terminals R+, R-,


S+ and S-.*
0: No Parity
1: Even Parity
2: Odd Parity

0 to 2

Serial Fault Sel

Selects the stopping method when a communication


error is detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

H5-05

Serial Flt DTCT

Enables or disables the communications timeout


detection function.
0: Disabled - A communications loss will NOT cause a
communications fault.
1: Enabled - If communications are lost for more than
the time specified in parameter H5-09,
a communications fault will occur.

0 or 1

H5-06

Transmit Wait
Time

Sets the time from when the drive receives data to


when
the drive sends data.

5 ms

5 to 65

H5-07

RTS Control
Sel

Enables or disables request to send (RTS) control:


0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)

0 or 1

H5-09

Communication
Error Detection
Time

8.0 sec

0 to 10.0
(H5-08=0)
0 to 10.0

H5-02

H5-03

H5-04

Determines how long communications must be lost


before a fault is annunciated. Works in conjunction with
parameters H5-05 and H5-04.

PN: 196399 Revision: 6.6.2

133

GE Oil & Gas

L1-01

Mol Fault
Select

Enables or disables the motor thermal overload


protection.
0: Disabled
1: Std Fan Cooled (Enabled)
2: Std Blower Cooled
3: Vector Motor

L1-02

Mol Time
Const

Determines how much time will elapse prior to a motor


overload fault (OL1), when motor amps exceed the
value set in parameter E2-01 by 10%. Actual (OL1) trip
time will vary depending on severity of overload.

0 to 1

8.0 min

0.1 to 20.0

Mtr OH Alarm
Sel

Operation selection when the motor temperature


analog
input (H3-09=E) exceeds the OH3 alarm level (1.17V)
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

L1-04

Mtr OH Fault
Sel

Stopping method when the motor temperature analog


input (H3-09=E) exceeds the OH4 level (2.34V).
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop

0 to 2

L1-05

Mtr Temp
Filter

Delay Time applied to motor temperature analog input


(H3-09=E) for filtering purposes.

0.20 sec

0.00 to
10.00

L2-01

PWRL
Selection

Enables and disables the momentary power loss


function.
0: Disabled - Drive trips on (UV1) fault when power is
lost.
1: PwrL Ride Thru t - Drive will restart if power returns
within the time set in L2-02.*
2: CPU Power Active - Drive will restart if power
returns prior to internal power supply shut down.*
* In order for a restart to occur, the run command must
be maintained throughout the ride thru period.

0 to 2

L2-02

PWRL Ridethru
Time

Determines the power loss ride-thru time. This value is


dependent on the capacity of the drive. Only effective
when L2-01 = 1.

kVA Dep.

0.0 to
25.5sec

L2-03

PWRL
Baseblock T

Used to allow the residual motor voltage to decay


before the drive output turns back on. After a power
loss, if L2-03 is greater than L2-02, operation resumes
after the time set in L2-03.

kVA Dep.

0.1 to 5.0sec

L2-04

PWRL V/F
Ramp T

The time it takes the output voltage to return to the


preset V/f pattern after speed search (current detection
mode) is complete.

kVA Dep.

0.0 to 5.0sec

L1-03

imagination at work

VII

VECTOR
PUV Det Level

Sets the drives DC Bus undervoltage trip level. If this is


set lower than the factory setting, additional AC input
reactance or DC bus reactance may be necessary.

Volt
Dep.

Voltage
Class
Dependent

L3-01

StallP Accel
Sel

0: Disabled (Motor accelerates at active acceleration,


C1-01 or C1-03. The motor may stall if load is too
heavy or accel time is too short).
1: General Purpose (When output current exceeds L302 level, acceleration stops. It starts to accelerate at
current value recovery).
2: Intelligent (The active acceleration rate, C1-01 or
C1-02, is ignored. Acceleration is completed in the
shortest amount of time w/o exceeding the current
value set in L3-02).

0 to 2

L3-02

StallP Accel Lvl

This function is enabled when L3-01 is 1 or 2.


Drive rated current is 100%. Decrease the set value if
stalling occurs at factory setting.

120%

0 to 200

StallP Decel
Sel

0: Disabled (The drive decelerates at the active


deceleration rate, C1-02 or C1-04. If the load is too
large or the deceleration time is too short, an OV fault
may occur).
1: General Purpose (The drive decelerates at the active
deceleration rate, C1-02 or C1-04, but if the main
circuit DC bus voltage reaches the stall prevention
level the output frequency will clamp. Deceleration
will continue once the DC bus level drops below the
stall prevention level).
2: Intelligent (The active deceleration rate is ignored
and the drive decelerates as fast as possible w/o
hitting OV fault level).

0 to 3

StallP Run Sel

0: Disabled (Drive runs a set frequency). A heavy load


may cause the drive to trip on an OC fault.
1: Decel Time 1 (In order to avoid stalling during heavy
loading, the drive will start to decelerate at Decel
time 1 (C1-02) if the output current exceeds the level
set by L3-06. Once the current level drops below the
L3-06 level the drive will accelerate back to its set
frequency at the active acceleration rate).
2: Decel Time 2 (Same as setting 1 except the drive
decelerates at Decel Time 2 (C1-04).
For 6Hz or less frequency, stall prevention function
during run is disabled regardless of L3-05 set.

0 to 2

StallP Run Lvl

This function is enabled when L3-05 is 1 or 2.


Drive rated current is set as 100%.
Normally, changing the setting is not required.
Decrease the set value if stalling occurs at factory
setting.

120%

30 to 200

L2-05

L3-04

L3-05

L3-06

PN: 196399 Revision: 6.6.2

135

GE Oil & Gas

L4-01

L4-02

Spd Agree
Level

Spd Agree
Width

0.00 Hz

0.0 to 200.0

2.0 Hz

0.0 to 20.0

0 or 1

80.00%

0 to 100.0%

Determines the number of times the drive will perform


an automatic restart.

0 to 10

0 or 1

180.0
sec

0.5 to 600.0

L4-01 and L4-02 are used in conjunction with the


multi-function outputs, (H2-01and H2-02) as a setpoint
and hysteresis for a contact closure.

Ref Loss Sel

Determines how the drive will react when the frequency


reference is lost.
0: Stop (Disabled) - Drive will not run at the frequency
reference
1: Enabled @ % of PrevRef - Drive will run at a
percentage (L4-06) of the frequency reference level at
the time frequency reference was lost.

L4-06

FRef at Loss

If Frequency Reference loss function is enabled


(L4-05=1) and Frequency Reference is lost, then the
drive will run at reduced frequency reference
determined
by L4-06. New Fref =Fref at time of loss x L406.

L5-01

Num of
Restarts

L4-05

L5-02

Restart Sel

Determines if the fault contact activates during an


automatic restart attempt.
0: No Flt Relay - fault contact will not activate during
an automatic restart.
1: Flt Relay Active - fault contact will activate during
an automatic restart.

L5-03

Fault Retry
Continuous
Time

If the restart fails (or is not attempted due to a


continuing fault condition, e.g. an OV fault) the Drive
waits L5-03 seconds before attempting another restart.

imagination at work

VII

VECTOR

L6-01

Torq Det 1 Sel

L6-02

Torq Det 1 Lvl

L6-03

Torq Det 1
Time

L8-01

DB Resistor
Prot

L8-02

OH Pre-Alarm
Lvl

L8-03

OH Pre-Alarm
Sel

L8-06

Ph Loss In Lvl

Determines the drives rGE Oil & Gasonse to an


overtorque /
undertorque condition. Overtorque and Undertorque
are
determined by the settings in parameters L6-02 and
L6-03.
0: Disabled
1: OL@SpdAgree - Alm (Overtorque Detection only
active during Speed Agree and Operation continues
after detection).
2: OL At RUN - Alm (Overtorque Detection is always
active and operation continues after detection)
3: OL@SpdAgree - Flt (Overtorque Detection only
active during Speed Agree and drive output will shut
down on an OL3 fault).
4: OL At RUN - Flt (Overtorque Detection is always
active and drive output will shut down on an OL3
fault.)
5: LL@SpdAgree - Alm (Undertorque Detection is only
active during Speed Agree and operation continues
after detection).
6: LL at RUN - Alm (Undertorque Detection is always
active and operation continues after detection)
7: LL @ SpdAgree - Flt (Undertorque Detection only
active during Speed Agree and drive output will shut
down on an OL3 fault).
8: LL At RUN - Flt (Undertorque Detection is always
active and drive output will shut down on an OL3
fault).
Sets the overtorque/undertorque detection level as a
percentage of Drive rated current.
Sets the length of time an overtorque / undertorque
condition must exist before being recognized by the
drive. OL3 is then displayed.
0: Not Provided
1: Provided
When the cooling fin temperature exceeds the value
set
in this parameter, an overheat pre-alarm (OH) will
occur.
Drive Operation upon OH Pre Alarm Detection.
0: Ramp to Stop (Decel Time C1-02).
1: Coast to Stop
2: Fast-Stop (Decel Time = C1-09).
3: Alarm Only
*0 to 2 is recognized as fault detection, and 3 is
recognized as alarm. (For the fault detection, the fault
contact operates.)
4: OH Alarm & Reduce (Continue operation and reduce
output frequency by L8-19).
Monitors the DC Bus current ripple and activates when
one of the input phases is lost (PF).

PN: 196399 Revision: 6.6.2

0 to 8

15%

0 to 300

10.0 sec

0.0 to 10.0

0 or 1

95C

50 to 130

0 to 4

kVA Dep.

0.0 to 25.0

137

GE Oil & Gas

L8-07

Phase Loss
Output Select

Selects if the output phase loss detection is enabled.


0: Disabled
1: Enabled

0~1

L8-08

Phase Loss
Output Level

Sets the output phase loss detection level in terms of


drive rated current

0 ~ 200%

L8-09

Ground Fault
Sel

Enables and disables drive output ground fault


detection.
0: Disabled
1: Enabled

0 or 1

0 or 1

L8-10

Fan Control
Sel

Controls the Heatsink Cooling Fan Operation.


0: Fan On-Run Mode (Fan will operate only when drive
is running and for L8-11 seconds after RUN is
removed).
1: Fan Always On (Cooling fan operates whenever
drive is powered up).

L8-11

Fan Off Time

When L8-10=0 this parameter sets a delay time for


Cooling Fan de-energization after the run command is
removed.

10 sec

0 to 300

L8-12

Ambient Temp
Set

When the drive is installed in an ambient temperature


exceeding its rating, drive overload (OL2) protection
level is reduced.

45C

45 to 60C

L8-15

OL Chara@LSPD

This parameter assists in protecting the output


transistor
junctions from overheating when output current is high
and output frequency is low.
0: Disabled
1: Enabled (L8-18 is active)

0 or 1

L8-18

Software CLA
Selection

Enables and disables software Current Limit A


(CLA)
0: Disabled
1: Enabled

0 or 1

L8-19

OH Freq
Reference
Reduction Level

20.00%

0.0
to
100.0

0 or 1

N1-01

Hunt Prev
Select

Sets the amount of frequency reference reduction


when
an Overheat Pre-alarm (OH) is detected.
0: Disabled (Hunting prevention function disabled).
1: Enabled (Hunting prevention function enabled).
If the motor vibrates while lightly loaded, hunting
prevention may reduce the vibration. There is a loss of
rGE Oil & Gasonsiveness if hunting prevention is
enabled.

imagination at work

VII

VECTOR
N1-02

Hunt Prev
Gain

Gain setting for the Hunting Prevention Function.


If the motor vibrates while lightly loaded and n1-01=1,
increase the gain by 0.1 until vibration ceases.
If the motor stalls while n1-01=1 decrease the gain by
0.1 until the stalling ceases.

N3-01

HSB Decel
Width

N3-02

N3-03

0.00 to 2.50

Sets how aggressively the drive decreases the output


frequency as it stops the motor. If overvoltage (OV)
faults occur during HSB, this parameter may need to be
increased.

5%

1 to 20

HSB Current
Ref

Sets the maximum current to be drawn during a HSB


stop. Higher n3-02 settings will shorten motor stopping
times but cause increased motor current, and therefore
increased motor heating.

150%

100 to 200

HSB Dwell
Time @ Stop

Sets the amount of time the Drive will dwell at E1-09


(Minimum Frequency). If this time is set too low, the
machine inertia can cause the motor to rotate slightly
after the HSB stop is complete and the Drive output is
shut off.

1.0 sec

0.0 to 10.0

40 sec

30 to 1200

6 to 53

1 to 4

N3-04

HSB OL Time

O1-01

User Monitor
Sel

O1-02

Power-On
Monitor

Sets the time required for a HSB Overload Fault to


occur when the Drive output frequency does not
change
for some reason during a HSB stop. Normally this does
not need to be adjusted.
Selects which monitor will be displayed upon power-up
when o1-02 = 4.
Selects which monitor will be displayed upon
power-up.
1: Frequency Ref
2: Output Freq
3: Output Current
4: User Monitor (set by o1-01)

PN: 196399 Revision: 6.6.2

139

GE Oil & Gas

O1-03

Display
Scaling

0 to 39999

O1-05

LCD Contrast

0 to 5

0 or 1

O1-06

User Monitor
Selection Mode

Selects the U1 monitors displayed on the 4th and 5th


lines of the digital operator display.
0: 3 Mon Sequential (Displays the next 2 sequential U1
monitors).
1: 3 Mon Selectable (Displays U1 monitors set by o107and o1-08).

O1-07

2nd Line User


Monitor

Sets the U1 monitor always displayed on the 4th line


of the digital operator display. Effective only when
o1-06 = 1.

1 to 53

O1-08

3rd Line User


Monitor

Sets the U1 monitor always displayed on the 5th line


of the digital operator display. Effective only when
o1-06 = 1.

1 to 53

imagination at work

VII

VECTOR

Local / Remote
Key

Sets unit display for the frequency reference


parameters
and frequency related monitors when o1-0340.
0: WC:InchOfWater
1: PSI:lb/SqrInch
2: GPM:Gallons/Min
3: F:DegFahrenheit
4: CFM:Cubic ft/Min
5: CMH:Cubic M/Hr
6: LPH:Liters/Hr
7: LPS:Liters/Sec
8: Bar:Bar
9: Pa:Pascals
10: C:DegCelsius
11: Mtr:Meters

0 to 11

Oper Stop Key

Determines if the off key on the digital operator will


stop the drive when drive is operating from external
terminals or serial communications.
0: Disabled
1: Enabled

0 or 1

O2-03

User Defaults

Allows storing of current parameter values as a User


Initialization Selection at parameter A1-03.
0: No Change (No user parameter set active).
1: Set Defaults (Saves current parameter settings as
user
initialization. A1-03 now allows selecting <1110> for
user initialization.
2: Clear All (Clears the currently saved user
initialization. A1-03 no longer allows selecting
<1110>.

0 to 2

O2-04

Inverter Model
#

Sets the kVA of the drive. Enter the number based on


drive Model #. Use the portion of the
CIMR-E7 Model Number.
Reference Appendix B

kVA Dep.

0 to FF

0 or 1

O2-01

O2-02

O2-05

Operator
M.O.P.

Determines if the Data/Enter key must be used to input


a frequency reference from the digital operator.
0: Disabled - Data/Enter key must be pressed to enter a
frequency reference.
1: Enabled - Data/Enter key is not required. The
frequency reference is adjusted by the up and down
arrow keys on the digital operator without having to
press the data/enter key.

PN: 196399 Revision: 6.6.2

141

GE Oil & Gas

O2-06

Oper
Detection

Determines if the drive will stop when the digital


operator is removed.
0: Disabled - The drive will not stop when the digital
operator is removed.
1: Enabled - The drive will fault (OPR) and coast to
stop when the operator is removed.

O2-07

Elapsed Time
Set

Sets the initial value of the elapsed operation timer.

0 hours

0 to 65535

Elapsed Time
Run

Sets how time is accumulated for the elapsed timer


(o2-07).
0: Power-On Time
(Time accumulates whenever drive is powered)
1: Running Time
(Time accumulates only when drive is running)

0 or 1

0 hours

0 to 65535

0 or 1

0 or 1

O2-08

0 or 1

Determines parameter values after a drive initialization


(A1-03) is executed. This should always be set to 1
American Spec.
1: American spec

O2-09

Init Mode Sel

O2-10

Fan Opr Time

Parameter o2-09 should always be set to 1:


American
Spec. (Do not set.) This parameter does not normally
require adjustment. Possible damage to equipment or
injury may occur if this setting is changed from 1:
American Spec. o2-09 is a macro parameter that can
change the default values of terminal I/O and many
other parameters in the drive. Consult the Yaskawa
factory
for details.
This parameter is not available in software version >
1020.
Sets the initial value of the heatsink fan operation time.

O2-12

Fl Trace Init

Clears the fault memory contained in the U2 and U3


monitors.
0: Disabled (no effect)
1: Enabled - resets U2 and U3 monitors, and returns
o2-12 to zero

O2-14

KWH Monitor
Initialization

Used to reset the kilowatt Hour monitor to zero


0: Disabled (no change)
1: Clear all - Resets U1-29 to zero and returns o2-14 to
zero.

imagination at work

VII

VECTOR
Enables or disables the Hand key on the digital
operator.
0: Disabled
1: Enabled

0 or 1

Copy

This parameter controls the copying of parameters to


and from the digital operator.
0: COPY SELECT (no function)
1: INV -> OP READ - All parameters are copied from
the drive to the digital operator.
2: OP -> INV WRITE - All parameters are copied from
the digital operator into the drive.
3: OP<-->INV VERIFY - Parameter settings in the
drive are compared to those in the digital operator.
NOTE: When using the copy function, the drive model
number and software number (U1-14) must match or
an
error will occur.

0 to 3

O3-02

Read

Enables and disables all digital operator copy functions.


0: Disabled - No digital operator copy functions are
allowed
1: Enabled - Copying allowed

0 to 1

P1-01

Underload
Level

Sets the level for underload detection as a percentage


of motor rated current (E2-01). A setting of 0% disables
the underload detection feature.

15%

0 ~ 200%

P1-02

Underload
Restart Count

0 ~ 20

P1-03

Underload
Detect Time

Sets the amount of time the torque (or current) must be


below the P1 01 level before an underload condition is
detected.

12.0 sec

0.0 ~ 600.0 sec

P1-04

Underload
Restart Time

Sets the time the drive waits after an underload


condition is detected before restarting.

45.0 min

0.1 ~ 2000.0
min

P1-05

Underload
Restart Clear

Sets the time the drive needs to run without detecting


an underload condition before the restart counter is
cleared.

60 min

1 ~ 4000
min

P1-06

Underload
Start Delay

Sets the time (in seconds) that the underload protection


features will be ignored when the drive starts from zero
speed.

0 sec

0 ~ 1200 sec

Underload @
D2-02

Sets the underload protection limit to be used when


the drive is running at the Frequency Reference Lower
Limit. This value, along with the Underload Detection
Level (P1-01) is used to form the Underload level for
frequencies between the minimum and maximum
frequencies. The value is a percentage of the
Underload Detection Level (P1-01).

100%

0 ~ 100 %

O2-15

O3-01

P1-07

Hand Function
Key Selection

Sets the maximum number of restarts for Underload


alarm.

PN: 196399 Revision: 6.6.2

143

GE Oil & Gas

P1-08

Overload @
D2-02

Sets the overload protection limit to be used when


the drive is running at the Frequency Reference
Lower Limit. This value, along with the Motor Rated
Current (E2-01) is used to form the Overload level for
frequencies between the minimum and maximum
frequencies. The value is a percentage of motor rated
current (E2-01). When set to 0, this overload protection
method is disabled. When set to a non-zero value, the
drive uses the overload protection method described
below.

P1-09

Overload
Detection Time

Sets the amount of time that the current must be above


overload level (based upon P1-08 and E2-01) before an
overload condition is detected. This value is only used
when the Min Frequency Overload Level is non-zero.

0 sec

0.0 ~ 600.0 sec

P1-10

Overload Start
Delay

Sets the time (in seconds) that the overload protection


features will be ignored when the drive starts from
zero speed. In addition to disabling the P1-08, P109 Overload Detection , the standard Overload OL1
function will be held at its current value during this time
and will be allowed to decrease but not increase.

0 sec

0 ~ 1200 sec

P2-01

Term A1 High
Limit

Sets the upper limit for terminal A1 range detection.


Value is set based on the full scale analog input level,
prior to the gain and bias adjustments. A setting of 0%
will disable this fault.

125%

0 ~ 100%

P2-02

Term A1 Low
Limit

Sets the lower limit for terminal A1 range detection.


Value is set based on the full scale analog input level,
prior to the gain and bias adjustments. A setting of 0%
will disable this fault.

0%

0 ~ 100%

P2-03

Term A1 Limit
Delay

Sets the time for which terminal A1 must be out of


range before a A1 HI or A1 LO fault will occur.

0.0 min

0 ~ 200.0
min

P2-04

Term A2 High
Limit

Sets the upper limit for terminal A2 range detection.


Value is set based on the full scale analog input level,
prior to the gain and bias adjustments. A setting of 0%
will disable this fault.

125%

0 ~ 100%

P2-05

Term A2 Low
Limit

Sets the lower limit for terminal A2 range detection.


Value is set based on the full scale analog input level,
prior to the gain and bias adjustments. A setting of
-30% will disable this fault.

-30%

-30 ~ 100%

P2-06

Term A2 Limit
Delay

Sets the time for which terminal A2 must be out of


range before a A2 HI or A2 LO fault will occur

0.0 min

0 ~ 200.0
min

imagination at work

0%

0 ~ 110 %

VII

VECTOR
P2-07

P2-08

Base Voltage
Bias

Max Voltage
Bias

Controlled using the HMI in the Frequency Setup screen


(Voltage Bias). This bias voltage is calcutated from Max
voltage. i.e. When the Bias is set to 100, and the max
frequency is set to 60 Hz, min frequency is set to 30
Hz at 480 VAC. The drive will output 290 VAC at 45 Hz
(half Speed) instead of 240 VAC. This does not mean
that the max voltage is now 580 VAC on the output.
The Maximum ouput can be Less than or Equal to the
input Voltage.

0V

-50 to 100

45.0 min

0.0 ~ 2000.0
min

60 min

0 ~ 4000 min

770

0000 ~ FFFFH

P3-01

Wait Between
Restarts

Sets the time the drive waits after a fault occurs


before attempting an automatic restart. When set to
0, the drive automatic restart function operates as in
standard software. (Note: if this is changed during a
fault restart, the new restart time wont take effect until
the next fault.)

P3-02

Restart Clear
Time

Sets the time the drive needs to run without detecting


any faults before the restart counter is cleared. (Note:
if this is changed during a fault restart, the new restart
clear time wont take effect until the next fault.)

This parameter allows control over which faults the


drive can perform an automatic fault restart into.
Setting a bit to 1 enables restart for that particular
fault. Setting a bit to 0 disables restart for that fault.

P3-03

Restart Fault
Mask 1

Bit
Fault
0 PUF
1 UV1*2
2
Not used
3
Not used
4
Not used
5
GF
6
OC
7
OV
8
OH
9
OH1
10
OL1
11
OL2
12
OL3
13
Not used
14
Not used
15
Not used

PN: 196399 Revision: 6.6.2

145

GE Oil & Gas

This parameter allows control over which faults the


drive can perform an automatic fault restart into.
Setting a bit to 1 enables restart for that particular
fault. Setting a bit to 0 disables restart for that fault.

P3-04

Restart Fault
Mask 2

Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

Fault
EF3
EF4
EF5
EF6
EF7
Not used
Not used
Not used
Not used
OVL
PF
LF
Not used
Not used
Not used
Not used

0000 ~ FFFFH

0000 ~ FFFFH

This parameter allows control over which faults the


drive can perform an automatic fault restart into.
Setting a bit to 1 enables restart for that particular
fault. Setting a bit to 0 disables restart for that fault.

P3-05

Restart Fault
Mask 3

Bit Fault
0 Not used
1 Not used
2 Not used
3 Not used
4 Not used
5 Not used
6 Not used
7 FBLFAL
8 UL3FAL
9 Not used
10 Not used
11 Not used
12 A1-HI
13 A1-LO
14 A2-HI
15 A2-LO

imagination at work

VII

VECTOR
This parameter will only inhibit restarts when P3-01 >
0.0 min.
P3-06

Fault Restart
Inhibit

T1-02

Mtr Rated
Power

T1-04

0~1

Sets the motor rated power in kW.


NOTE: T1-02 should be left at the Drive default (the
last 3 digits of the Drive model number).

kVA Dep.

0.00 to
650.00

Rated Current

Sets the motor rated current.


(Used only during an auto-tune).

kVA Dep.

kVA
Dependent

U1-01

Frequency Ref

Frequency reference (speed command) monitor when


in auto
mode, frequency reference (speed command) setting
location when
in hand mode. Units changeable via o1-03.

N/A

N/A

U1-02

Output Freq

Output frequency (speed) monitor. Units changeable via


o1-03.

N/A

N/A

Output current monitor

N/A

N/A

Motor speedmonitor

N/A

N/A

Displays Drive output voltage

N/A

N/A

Displays DC Bus Voltage

N/A

N/A

Displays Drive output power

N/A

N/A

Displays torque reference

N/A

N/A

N/A

N/A

U1-03
U1-05
U1-06
U1-07
U1-08
U1-09

U1-10

Output
Current
Motor Speed
Output
Voltage
DC Bus
Voltage
Output
KWatts
Torque
Reference

0: Restarts Enabled - Faults enabled in P3-03 ~ P3-05


and the underload alarm can be restarted.
1: No Restarts No faults are restarted, Underload will
fault and not restart.

Input Term Sts

PN: 196399 Revision: 6.6.2

147

GE Oil & Gas

U1-11

Output Term
Sts

N/A

N/A

U1-12

Int Ctl Stas 1


(Inverter Status)

N/A

N/A

U1-13
U1-14

Elapsed Time
Flash ID

Displays total operating or power-on time of the Drive.


Displays Drives software number.

N/A
N/A

N/A
N/A

U1-15

Term A1 Level

Displays the input voltage on Terminal A1, as a


percentage of 10VDC.

N/A

N/A

U1-16

Term A2 Level

Displays the input current (or voltage) on Terminal A2,


as a percentage of 20mA (or 10 V DC).

N/A

N/A

U1-18

Mot Sec
Current

Displays the amount of current being used by the


motor to produce torque (Iq).

N/A

N/A

U1-20

SFS Output

Displays the frequency reference (speed command)


after the accel and decel ramps.

N/A

N/A

U1-24
U1-28
U1-29
U1-30
U1-34

PI Feedback
CPU ID
KWH Monitor
MWH Monitor
OPE Detected

Displays the feedback signal when PI control is used.


Displays control board hardware revision.
Displays the accumulated kWh.
Displays the accumulated MWh.
Displays the parameter number causing an OPE fault.

N/A
N/A
N/A
N/A
N/A

N/A
N/A
N/A
N/A
N/A

imagination at work

VII

VECTOR
Displays the error in the PI regulator. (U1-36 = PI
Setpoint - PI Feedback)

N/A

N/A

PI Output

Displays the output of the PI as a percentage of


maximum frequency (E1-04).

N/A

N/A

U1-38

PI Setpoint

Displays the setpoint of the PI regulator (U1-38 = PI


reference + PI bias)

N/A

N/A

U1-39

Memobus Error
code

N/A

N/A

U1-40

Fan Opr Time

Displays total operating time of the heatsink cooling


fan.

N/A

N/A

U1-41

Heatsink
Temperature

Displays heatsink temperature in Deg. C

N/A

N/A

U1-51

Frequency Ref
when Auto is
Selected

Displays the frequency reference (speed command)


when in auto mode.

N/A

N/A

U1-52

Frequency Ref
when Hand is
Selected

Displays the frequency reference (speed command)


when in hand mode, or displays Terminal A2 when
differential mode is selected.

N/A

N/A

U1-53

PI Feedback 2
Value

Displays PI feedback 2 value.

N/A

N/A

While the drive is in a fault condition, U1-90 displays


the time remaining until a restart will occur*3. It will
display 0 in situations when the drive will not perform a
restart. U1-90 will also show the time remaining during
an Underload restart.

N/A

N/A

U1-36

PI Input

U1-37

U1-90

Time to
Restart

U2-01
U2-02

Current Fault
Last Fault

Current Fault
Previous Fault

N/A
N/A

N/A
N/A

U2-03

Frequency Ref
at Fault

Frequency Reference at Most Recent Fault

N/A

N/A

U2-04

Output Freq at
Fault

Output Frequency at Most Recent Fault

N/A

N/A

U2-05

Output Current
at Fault

Output Current at Most Recent Fault

N/A

N/A

PN: 196399 Revision: 6.6.2

149

GE Oil & Gas

U2-07

Output Voltage
at Fault

Output Voltage at Most Recent Fault

N/A

N/A

U2-08

DC Bus Voltage
at Fault

DC Bus Voltage at Most Recent Fault

N/A

N/A

U2-09

Output KWatts
at Fault

Output Power at Most Recent Fault

N/A

N/A

U2-11

Input Term STS


at Fault

Input Terminal Status at Most Recent Fault. The format


is the same as for U1-10.

N/A

N/A

U2-12

Output Term
STS at Fault

Output Terminal Status at Most Recent Fault. The


format is the same as for U1-11.

N/A

N/A

U2-13

Inverter Status
at Fault

Drive Operation Status at Most Recent Fault. The


format is the same as for U1-12.

N/A

N/A

U2-14

Elapsed Time
at Fault

Cumulative Operation Time at Most Recent Fault

N/A

N/A

Most Recent Fault

N/A

N/A

2nd Most Recent Fault

N/A

N/A

3rd Most Recent Fault

N/A

N/A

4th Most Recent Fault

N/A

N/A

Cumulative Operation Time at Most Recent Fault

N/A

N/A

Cumulative Operation Time at 2nd Most Recent Fault

N/A

N/A

Cumulative Operation Time at 3rd Most Recent Fault

N/A

N/A

Cumulative Operation Time at 4th Most Recent Fault

N/A

N/A

5th Most Recent Fault

N/A

N/A

6th Most Recent Fault

N/A

N/A

7th Most Recent Fault

N/A

N/A

8th Most Recent Fault

N/A

N/A

9th Most Recent Fault

N/A

N/A

10th Most Recent Fault

N/A

N/A

Cumulative Operation Time at 5th Most Recent Fault

N/A

N/A

Cumulative Operation Time at 6th Most Recent Fault

N/A

N/A

Cumulative Operation Time at 7th Most Recent Fault

N/A

N/A

Cumulative Operation Time at 8th Most Recent Fault

N/A

N/A

Cumulative Operation Time at 9th Most Recent Fault

N/A

N/A

Cumulative Operation Time at 10th Most Recent Fault

N/A

N/A

U3-01
U3-02
U3-03
U3-04
U3-05
U3-06
U3-07
U3-08
U3-09
U3-10
U3-11
U3-12
U3-13
U3-14
U3-15
U3-16
U3-17
U3-18
U3-19
U3-20

Last Fault
Fault Message
2
Fault Message
3
Fault Message
4
Elapsed Time
1
Elapsed Time
2
Elapsed Time
3
Elapsed Time
4
Fault Message
5
Fault Message
6
Fault Message
7
Fault Message
8
Fault Message
9
Fault Message
10
Elapsed Time
5
Elapsed Time
6
Elapsed Time
7
Elapsed Time
8
Elapsed Time
9
Elapsed Time
10

imagination at work

VII

VECTOR
5

Tools Recommended for Maintenance and Repair

Description
10mm Nut Driver
Extension 1/4 drive to 3/8 x 12
10mm Socket 3/8 drive
Extension 1/4 drive to 3/8 x 2
19mm Socket 3/8 drive
24mm Socket 1/2 drive
17mm Socket 3/8 drive
1/2 Hex Socket 1/2 drive
5/16 Allen wrench socket
14mm socket 3/8 drive
1/2 drive ratchet
3/8 drive ratchet
13MM socket
Needle nose pliers 6
Wire Strippers
Side cutters
5/16 Slotted Screwdriver
3/16 Allen Socket 3/8 drive
12 Tape measure
3/8 drive torque wrench
19mm Open/Box wrench
3/16 Slotted Screwdriver
1/8 Slotted Screwdriver
24MM Open/Box wrench
Cable cutters ratcheting
1/2 Drive torque wrench
3/8 drive 6 extension
1/2 drive 5 extension
Cordless Driver
4 Adjustable Wrench
6 Adjustable Wrench
Heat Gun
#3 Phillips 1/4 Drive Bit
#2 Phillips 1/4 Drive Bit
#3 Phillips Screwdriver
Fluke-87V Multi Meter
Precision Screwdriver
#2 Phillips 10 Shank
#2 Phillips Screwdriver
#2 Phillips Screwdriver STUBBY
1/4 Slotted Screwdriver
AMP Pro Crimping Tool 59824-1

Qty
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

PN: 196399 Revision: 6.6.2

151

GE Oil & Gas

6 CE Conformity for drives purchased with CE Option

CE Marked Vector VII Drives are intended for installation in electrical systems or machinery in the European Union This product conforms
to the following product standards of the following directives:
Machine Directive 2006/42/EC
Low Voltage Directive 2006/95/EC
Low Voltage Directive 72/23/EC
EMC Directive 2004/108/EC

6.1 Emergency Stop Function


The Emergency Stop (E-Stop) push button is located on the front of the enclosure door and is bright red for easy
identification.

To use the E-Stop push button to stop the drive,


Press the button in with your finger or hand.

Once the E-Stop push button has been depressed, the Run status Screen will show External Fault 2 stopping the drive.

imagination at work

VII

VECTOR

To reset the E-Stop push button and allow the drive to operate:
Pull the E-Stop button out and away from the drive until it stops

Open the Operator Control Panel window


Press the red Stop button on the operator Control Panel to clear the fault
When ready to start the drive and all conditions are safe, press the green Start button on the Operator
Control Panel.

Warning: When setting factory defaults in this drive, the user must verify the following for safe operation.
From the Run Status screen:
Select Menu
Select Log In
Enter 3333 for Password
Select OK
Select Misc Setup
Select External Fault 2
Select N.C.
Select OK
This procedure must be completed for the Emergency Stop Feature to function.

PN: 196399 Revision: 6.6.2

153

5500 SE 59th St.


Oklahoma City, OK 73135
GE Oil & Gas ESP, Inc.
geoilandgas.com/esp

imagination at work

Potrebbero piacerti anche