Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
INFORMATION
Relay output
Voltage output
Current output
SSR
Cycle controller
Power controller
Controlled object
Temperature
Controller
Control signal
Thermocouple
Platinum resistance thermometer
Thermistor
Infrared non-contact sensor
Controller
Temperature Sensor
The Temperature Sensor consists
of an element protected with a
pipe. Locate the element, which
converts temperatures into electric
signals, in places where
temperature control is required.
Controller
The Controller is used to heat up or
cool down furnaces and tubs using a
device, such as a solenoid or fuel valve,
to switch electric currents supplied to
heaters or coolers.
Temperature Control
Temperature
Time
2. Proper response
Temperature
The set point is input into the Temperature Controller in order to operate the
Temperature Controller. The time
required for stable temperature control
varies with the controlled object. Attempting to shorten the response time will
usually result in the overshooting or
hunting of temperature. When reduce the
overshooting or hunting of temperature,
the response time must not be shortened. There are applications that require
prompt, stable control in the waveform
shown in (1) despite overshooting. There
are other applications that require the
suppression of overshooting in the
waveform shown in (3) despite the long
time required to stabilize temperature. In
other words, the type of temperature
control varies with the application and
purpose. The waveform shown in (2) is
usually considered to be the best one for
standard applications.
Time
Temperature
Time
E--2
REFERENCE
INFORMATION
Static
characteristics
Dynamic
characteristics
External
disturbances
J ON/OFF CONTROL
ACTION
J P ACTION
Time
A narrow proportional
band is set.
A wide proportional
band is set.
Set point
A narrow proportional
band is set.
Set
point
Control output
Heater
Proportional
control action
Example:
If a Temperature Controller with a temperature range of 0 to 400C has a 5%
proportional band, the width of the proportional band will be converted into a
temperature range of 20C. In this case,
provided that the set point is 100C, a full
output is kept turned ON until the process value reaches 90C, and the output
is OFF periodically when the process
value exceeds 90C. When the process
value is 100C, there will be no difference in time between the ON period and
the OFF period (i.e., the output is turned
ON and OFF with the same interval).
Control output
Characteristics of
controlled object
Heat capacity
Offset
A wide proportional
band is set.
Time
Temperature
Set
point
Proportional band
E--3
REFERENCE
INFORMATION
J I ACTION
J ADVANCED PID
CONTROL
External
disturbance
P (proportional
control) action
only
Time
Control output
Set point
PD (proportional
and derivative
control) action
Set point
Offset ceases
to exist.
Offset
Time
PI (proportional
and integral
control) action
P (proportional
control) action
only
Set
point
A short derivative time is set.
Time
PID Control
Control output
Time
J PID CONTROL
Set
point
Time
J D ACTION
D action (derivative or rate control action)
is used for obtaining the output in proportion to the time derivative value of the
input. It provides a sudden shift in output
level as a result of a rapid change in actual temperature.
Proportional control action corrects the
result of control and so does integral
control action. Therefore, proportional
control action and integral control action
respond slowly to temperature change,
which is why derivative control action is
required. Derivative control action corrects the result of control by adding the
control output in proportion to the slope
of temperature change. A large quantity
of control output is added for a radical
external disturbance so that the temperature can be quickly in control.
E--4
PID
control
Response to
target value
Response to
external disturbance
REFERENCE
INFORMATION
PID control
Set
point
External
disturbance
An increase in output.
Suppresses the
output to eliminate
overshooting.
PID control
E--5
REFERENCE
INFORMATION
Topical Reference
J SECTION ORGANIZATION
The following Topical Reference discusses how Omron controls perform in
each critical aspect of a temperature or
process control system. The sections are
divided into these categories, then presented in alphabetic order
Control
Alarm
Temperature Sensor
Output
Setting
Control
Temperature or
deviation
J ANTI-RESET WINDUP
(ARW) FUNCTION
Set point
Proportional band
Deviation
Time
Integral output
Overshooting due to
excessive integral output.
Proportional
band
Actual
temperature
T: Control cycle
Control output =
TON
TON + TOFF
x 100 (%)
TON: ON period
TOFF: OFF period
E--6
Example;
If the control cycle is 10 s with an 80%
control output, the ON and OFF periods
will be the following values.
TON: 8 s
TOFF: 2 s
REFERENCE
INFORMATION
J CONTROL OUTPUT
ON/OFF output
Relay output
SSR output
Voltage output
Current output
Voltage output
Control
output
Linear output
E--7
REFERENCE
INFORMATION
Heater
Directly connectable
Number of SSRs
connectable in parallel
Temperature Controller at 12-VDC
Output with 40 mA
5 (8)
E5jJ
(Excluding E5CJ)
3 (4)
E5jK
(Excluding E5CK)
3 (4)
E5AN, E5EN
1 (2)
Values in parentheses
indicate 400 V models.
8
E5ZE
5 to 24 VDC
4
2
Temperature Controller at 12-VDC
Output with 20 mA
E5CS-X
5 (8)
3 (4)
3 (4)
E5CN, E5GN
1 (2)
Values in parentheses
indicate 400 V models.
2
E5CJ
1
E5CK
5
Temperature Controller at 5-VDC
Output with 10 mA
E5C4
12 VDC
5 VDC
Compact, low-cost model
with tab terminals
G3B with 5 A
5 to 24 VDC
6
3
E--8
REFERENCE
INFORMATION
J DERIVATIVE TIME
Deviation
PD action
(with a short derivative time)
PD action
(with a long derivative
time)
Control output
P action
D2 action
(with a short
derivative time)
D1 action
TD: Derivative
time
J FUZZY SELF-TUNING
PID constants must be determined
according to the controlled object for
proper temperature control. The conventional Temperature Controller incorporates an auto-tuning function to calculate
PID constants, in which case, it will be
necessary to give instructions to the
Temperature Controller to trigger the
auto-tuning function. Furthermore, if the
limit cycle method is adopted, temperature disturbance may result. The Temperature Controller in fuzzy self-tuning
operation determines the start of tuning
and ensures smooth tuning without
disturbing temperature control. In other
words, the fuzzy self-tuning function
makes it possible to adjust PID constants
according to the characteristics of the
controlled object.
Auto-tuning Method of a
Conventional Temperature
Controller
Auto-tuning Function: Automatically
calculates the appropriate PID constant
for controlling objects.
Features:
1. Tuning will be performed when the
AT instruction is given.
2. The limit cycle signal is generated
to oscillate the temperature before
tuning.
Target
value
External
disturbance 1
Target
value
PID gain
calculated.
AT starts.
Temperature
oscillated.
PID gain
calculated.
External
disturbance 2
Temperature
in control
Temperature
in control
ST starts.
AT
instruction
Self-tuning Function
Self-tuning (ST) Function: A function to
automatically calculate optimum PID
constants for controlled objects.
Features:
1. Whether to perform tuning or not is
determined by the Temperature
Controller.
2. No signal disturbing the process
value is generated.
Hunting
E--9
INFORMATION
J HYSTERESIS
ON/OFF control action turns the output
ON or OFF on the basis of the set point.
This means the output frequently
changes according to minute temperature changes, which shortens the life of
the output relay or unfavorably affects
some devices connected to the Temperature Controller. Therefore, a temperature
band is created between the ON and
OFF operations. This band is called hysteresis.
Example:
If the Temperature Controller with a
temperature range of 0C to 400C has a
0.2% hysteresis, D will be 0.8C.
Therefore if the set point is 100C, the
output will turn OFF at a process value of
100C and will turn ON at a process
value of 99.2C.
Hysteresis
D: Hysteresis
Control output
REFERENCE
Temperature
J INTEGRAL TIME
Deviation
PI action
(with a long integral time)
Control output
P action
T1: Integral
time
(with a short integral time)
(with a long integral time)
J OFFSET
Offset
Proportional band
Set point
Offset
Set point
J SELF-TUNING FUNCTION
Time
In self-tuning
operation
E--10
REFERENCE
INFORMATION
Manual Tuning
Set point
Oscillation
Hunting cycle
Time
Narrower
Set
point
Auto-Tuning
Set point
Wider
Wider
Set
point
Set
point
Set point
Marginal sensitivity
method
Narrower
Set
point
Narrower
Set
point
Time
Model
PID
Advanced PID
Auto-tuning methods
PID with fuzzy control
Step response
Limit cycle
E5jJ
----
Fuzzy self-tuning
----
Built-in
Built-in
E5jK
----
----
Built-in
Built-in
E5jN
----
----
Built-in
Built-in
E5jS
Self-tuning
----
----
E5ZE
----
----
Not built-in
Built-in
E--11
REFERENCE
INFORMATION
Alarm
J ALARM OPERATION
The Temperature Controller compares
the process value and the preset alarm
value, turns the alarm signal ON, and
displays the type of alarm in the preset
operation mode.
Absolute-value Alarm
Deviation Alarm
The absolute-value alarm turns ON according to the alarm temperature regardless of the set point in the Temperature
Controller.
Setting example
Alarm temperature is set to 110C.
Setting Example
Alarm temperature is set to 110C.
Alarm set
point: 10 C
Alarm value:
110C
Alarm value:
110C
Current value
Current
Transformer
(CT)
Control outpu
Heater current waveform
(CT waveform)
Heater
Switch
E--12
Temperature Drop
Upper limit
alarm set
Set point
Lower-limit
alarm set
Alarm
output
Lower limit
alarm set
Alarm
output
REFERENCE
INFORMATION
Upper- and
lower-limit
(deviation)
K3TL,
K3NH
E5CSX
E5AN,
E5EN,
E5CN,
E5GN
E5AK,
E5EK,
E5CK
E5jK
-T,
E5EKDRT
E5AJ,
E5EJ,
E5CJ
E5ZE
*2
Upper-limit
(deviation)
Lower-limit
(deviation)
Upper-limit with
standby
sequence
(deviation)
Lower-limit with
standby
sequence
(deviation)
Absolute-value
upper-limit
Absolute-value
lower-limit
Absolute-value
upper-limit with
standby
sequence
Absolute-value
lower-limit with
standby
sequence
E5AK
and
E5EK
only
E5AKT and
E5EKT only
Upper- and
lower-limit range
(deviation)
Upper- and
lower-limit with
standby
sequence
(deviation)
Heater burnout
detection alarm
(uses a current
transformer input)
*3
*5
*4
E--13
REFERENCE
INFORMATION
Temperature Sensor
J COLD JUNCTION EFFECT
Thermocouples only give an accurate
reading if the cold end of the device,
which is connected to the terminals on a
controller, is maintained at 0C. Since
this is not practical in industrial applications, controllers are calibrated at a
reference temperature, usually 20C to
25C, and an allowance made for the
cold junction error. A sensor (usually a
semiconductor) built into the controller,
then monitors any changes in this cold
junction, and the controller automatically
compensates for these changes (this is
called cold junction compensation). For
this reason, thermocouple leads should
always be connected directly to the
Sensing
point
350C
Thermo-electromotive force
generated by cold junction
compensating circuit
Cold junction
compensating circuit
J COMPENSATING CONDUCTOR
Compensating
conductor
Connection
terminal
Terminal
Temperature
Controller
Thermo-electromotive
force of thermocouple
Thermo-electromotive force
generated by cold junction
compensating circuit
Metal A
Hot
junction
Metal B
J INPUT COMPENSATION
A preset point is added to or subtracted
from the temperature detected by the
temperature sensor of the Temperature
Controller to display the process value.
The difference between the detected
temperature and displayed temperature
is set as an input compensation value.
Furnace
E--14
Cold
(reference
junction
(0C)
REFERENCE
INFORMATION
Temperature
Controller
Target
value
after
changing
Target
value
before
changing
SP ramp
SP ramp
set value
SP ramp
time unit
Change
point
Time
J THERMISTORS
These are temperature sensitive semiconductors, usually encased in a glass
bead. For industrial applications, this
would be housed in a stainless steel tube
in common with the other forms of sensors described here.
J THERMOCOUPLE
A thermocouple consists of two different
metal wires with the ends connected
together. When this assembly is heated,
a very small voltage, which is
proportional to the temperature, appears
E--15
REFERENCE
INFORMATION
Output
J HEATING AND COOLING CONTROL
Two control outputs (one for heating and
one for cooling) can be provided by a
temperature controller. The relation between these two control outputs is expressed by the V-shaped portion of the
diagram. As shown, the two outputs may
be overlapped, or there may be a dead
band between the two.
Temperature
Controller in
heating and
cooling
control
Heating
Cooling
Controlled
object
Heating
output
Cooling
output
Heating
output
Set point
Cooling
output
Set point
J NORMAL OPERATION
Set point
Low
High
J POSITION-PROPORTIONING CONTROL
This control is also called ON/OFF servo
control. In this control system, the temperature and the degree of opening
(position) of the control valve are fed
back to the temperature controller.
J REVERSE OPERATION
Temperature Controller in
position-proportioning control.
Open
Controlled
object
Close
Low
Set point
Potentiometer
reading valve
opening.
High
J TRANSMISSION OUTPUT
E--16
Temperature
Controller with
transmission
output
Recorder
Temperature sensor
Process value
Lower limit
Upper limit
REFERENCE
INFORMATION
Setting
J MULTIPLE SET POINTS
Two or more set points independent from
each other can be set in the Temperature
Controller in control operation.
J SET LIMIT
The set point range depends on the temperature sensor and the set limit is used to
restrict the set point range. This restriction
affects the transmission output of the Temperature Controller.
Bank 1
Bank 7
Bank 1 is selected.
Temperature
control with
data in memory
bank 1.
E--17
REFERENCE
INFORMATION
DeviceNett Overview
J WHAT IS THE DEVICENET?
DeviceNet is a low-cost communications
link to connect industrial devices to a network and eliminate expensive hardwiring.
Typical devices include limit switches,
photoelectric sensors, valve manifolds,
motor starters, process sensors, bar
code readers, variable frequency drives,
panel displays and operator interfaces.
Up to 64 nodes
Network length
g
Distance
125 Kbps
250 Kbps
500 Kbps
Data packets
0 to 8 bytes
Bus topology
Linear (trunk line/drop line); power and signal on the same network
cable
Bus addressing
System features
Terminator
Node
Tap
Terminator
Node
Drop line
Node
Node
Node
Node
Node
Node
Node
Node
Zero drop
E--18
Node
Short drops
Node
Node
REFERENCE
INFORMATION
CP = 20 (Omron default)
MV = 50%
What would happen in an ideal situation is that the output would trigger ON and OFF throughout the entire 20 seconds, so that at the end
of the 20 seconds, the TOTAL TIME ON would be 10 seconds.
Changing the MV would change the TOTAL TIME ON. For example, with the same CP of 20 and an MV of 75%, the TOTAL TIME ON
would be 15 seconds. As in the previous example, the output would not be on for 15 consecutive seconds.
A 5-second control period allows the MV to have the shortest possible ON time. One percent of 5 seconds is 0.05 seconds or 50 ms.
Therefore, 50 ms is the minimum ON time.
Different types of processes require different CPs. If you are controlling a slow-moving process, a long CP allows time for the process to
react to the controllers output signal. However, for a faster moving process, if the output stays on too long, the process variable (e.g.
temperature) exceeds the set point. The controller would then try to readjust itself by shutting off the output, but because the CP is too
large, the output stays off too long and the PV undershoots the set point. The only way to correct this type of hunting is to shorten the CP
of the controller.
E--19
REFERENCE
INFORMATION
E--20
REFERENCE
INFORMATION
Glossary
Adaptive Tuning
Alpha ()
This represents the temperature
coefficient of the change in electrical
resistance of a material. For each C in
temperature the electrical resistance
changes. It is the defining parameter for
platinum resistance temperature
detectors (RTD sensors). The unit of
measure is ohms/ohms/C.
Analog
Data collected and represented by
continuously variable quantities, such as
voltage measurement or temperature
variation.
Contact Output
Relay control outputs are often available
in these contact forms:
Form A Contact (SPST-NO)
Single-pole, single-throw relays use the
normally open and common contacts to
switch power. The contacts close when
the relay coil is energized and open
when power is removed from the coil.
Form B Contact (SPST-NC)
Single-pole, single-throw relays use the
normally closed and common contacts.
These contacts open when the relay coil
is energized and close when power is
removed from the coil.
Form C Contact (SPDT)
Single-pole, double-throw relays use the
normally open, normally closed and
common contacts. The relay can be
wired as a Form A or Form B contact.
Control Action
Auto-tuning
Control Mode
Analog Output
Burnout Function
An action to release the output when the
thermocouple has burned out, platinum
RTD develops an open or short, or
infrared problems occur.
CE
A marking on products that comply with
European Union requirements pertaining
to safety and electromagnetic
compatibility.
Celsius
A temperature scale in which water
freezes at 0C and boils at 100C at
standard atmospheric pressure. The
formula to convert Fahrenheit
temperatures to Celsius is as follows:
F = (1.8 x C) + 32.
CSA
Canadian Standards Association is an
independent testing laboratory that
establishes commercial and industrial
standards, as well as tests products and
certifies them.
C-UL
This symbol appearing in literature and
marked on products indicates Canadian
recognition of Underwriters Laboratories,
Inc. approval of particular product
classes. The C-UL approval may stand in
place of Canadian Standards Association
certification. All references to C-UL are
based on prior listing or recognition from
the original UL file.
Dead Band
The time period in a control system
between a change in stimuli and any
measurable response in the controlled
variable. In the deadband, specific
conditions can be placed on control
Derivative
The rate of change in a process variable
which forms the D in a PID control
algorithm. This control action anticipates
the rate of change of the process and
compensates to minimize overshoot and
undershoot. Derivative control is an
instantaneous change of the control
output in the same direction as the
proportional error. This is caused by a
change in the process variable (PV) that
decreases over the derivative time.
Deviation
A departure of a controlled variable from
a command such as set point.
Deviation indication
A system of indication in which a
departure of a detected value from the
set point is indicated.
DIN 43760
The standard that defines the
characteristics of a 100-ohm platinum
RTD having a resistance vs. temperature
curve specified by a = 0.00385 ohms per
degree.
Drift
A gradual change over a long period of
time that affects the reading or value.
Changes in ambient temperature,
component aging, contamination,
humidity and line voltage all contribute to
drift.
Droop
Controllers using only proportional
control can settle at a value below the
actual set point once the system
stabilizes. This offset is corrected with
the addition of Integral control in the
control algorithm.
Electromagnetic Compatibility
To conform with CEs EMC requirements,
equipment or a system must operate
without introducing significant
electromagnetic disturbances to the
environment or be affected by
electromagnetic disturbances.
Electromagnetic Interference
There are many possible sources for
electromagnetic interference (EMI) in an
industrial control setting. It can originate
as electrical or magnetic noise caused by
switching AC power on inside the sine
E--21
REFERENCE
INFORMATION
Electromechanical Relay
A power switching device that completes
or interrupts a circuit by physically
moving electrical contacts into contact
with each other. These are used primarily
for ON/OFF control operation.
Event
A programmable ON/OFF output signal.
Events can control peripheral equipment
or processes, or act as an input for
another control loop. Event input boards
are an option for most Omron controllers.
Infrared
Manual Mode
Input Scaling
The ability to scale input readings (% of
full scale) to the engineering units of the
process variable.
Fahrenheit
Input Type
Full Indication
A system of indication in which a
detected value is indicated with a setting
range.
Fuzzy Logic
Heat Sink
Linearity
A measure of the deviation of an
instruments response from a straight
line.
Manipulated Variable
The final output percentage (0 to 100%)
that will be sent to a control element.
This percentage can be related to a
valve position, a 4-20 mA signal, or the
amount of ON time from a pulsed control
output.
Hunting
E--22
NEMA 4X
This enclosure rating specification
certifies that a controllers front panel
resists water washdown and is corrosion
resistant in indoor usage.
Normal Action
A control action which will increase the
control output if the process value is
higher than the set point. This action is
suitable for a cooling system.
Offset
A controlled deviation (the difference in
temperature between the set point and
the actual process temperature)
remaining after a controlled system
reaches its steady state. The offset
(droop) is created by the correlation
between the thermal capacity of the
controlled system and the capacity of
heating equipment.
Overshoot
The number of degrees by which a
process exceeds the set point
temperature.
Process Variable
The parameter that is controlled or
measured, such as temperature, relative
humidity, flow and pressure.
Proportional Band
The range of temperature in which a
manipulated variable is proportionate to
any deviation from the set point.
REFERENCE
INFORMATION
Reverse Action
Proportional Period
A cycle of ON and OFF operations of the
output relay in a time-division
proportional control action.
Range
The difference between the lower and
upper limits of a measurement quantity.
Serial Communications
A method of transmitting information
between devices by sending all bits
serially over a communication channel.
RS-232 is used for point-to-point
connections of a single device, usually
over a short distance.
RS-422/RS-485 communicates with
multiple devices on a single, common
cable over longer distances.
Set Point
The value set on the process or
temperature controller to control the
system.
Undershoot
This is the amount by which the process
variable falls below the set point before it
stabilizes.
Soft Start
A method of applying power gradually
over a period of seconds to controlled
devices such as heaters, pumps and
motors. This lengthens the service life of
the load by limiting in-rush current to
inductive loads.
Thermal Response
The time required for the response curve
of the temperature sensor to rise to a
specified percentage level (usually either
63% or 90%).
Thermistor Sensor
A small bead of semiconducting material
at the tip detects temperature. The
resistance of the bead decreases
significantly with a rise in temperature for
a highly sensitive input device.
Thermocouple Sensor
A device the converts heat to electricity.
Usually made of two wires, each of a
different metal or alloy. The wires are
joined at one end, known as the hot
end. The hot end makes thermal contact
with the process to be controlled. The
cold end terminals are connected to the
sensor input. Voltages are created at
both the hot and cold ends. The
controller measures the cold end
temperature to determine the hot end
temperature.
E--23
REFERENCE
INFORMATION
Enclosure Ratings
J NEMA RATINGS AT A GLANCE FOR NON-HAZARDOUS LOCATIONS
Type of enclosure
Protection against
g
these
environmental
i
t l conditions
diti
3R
3S
4X
6P
11
12
12K
13
Falling dirt
----
----
----
----
----
----
----
----
----
----
----
----
----
----
Windblown dust
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
Corrosive agents
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
Not protected
Not protected.
Dust protected.
Dust tight.
----
----
----
----
E--24
REFERENCE
INFORMATION
10
20
30
40
50
60
70
80
90
0.000
0.397
0.798
1.203
1.611
2.022
2.436
2.850
3.266
3.681
100
4.095
4.508
4.919
5.327
5.733
6.137
6.539
6.939
7.338
7.737
200
8.137
8.537
8.938
9.341
9.745
10.151
10.560
10.969
11.381
11.793
300
12.207
12.623
13.039
13.456
13.874
14.292
14.712
15.132
15.552
15.974
400
16.395
16.818
17.241
17.664
18.088
18.513
18.938
19.363
19.788
20.214
500
20.640
21.066
21.493
21.919
22.346
22.772
23.198
23.624
24.050
24.476
600
24.902
25.327
25.751
26.176
26.599
27.022
27.445
27.867
28.288
28.709
700
29.128
29.547
29.965
30.383
30.799
31.214
31.629
32.042
32.455
32.866
800
33.277
33.686
34.095
34.502
34.909
35.314
35.718
36.121
36.524
36.925
900
37.325
37.724
38.122
38.519
38.915
39.310
39.703
40.096
40.488
40.879
1000
41.269
41.657
42.045
42.432
42.817
43.202
43.585
43.968
44.349
44.729
1100
45.108
45.486
45.863
46.238
46.612
46.985
47.356
47.726
48.095
48.462
1200
48.828
49.192
49.555
49.916
50.276
50.633
50.990
51.344
51.697
52.049
1300
52.398
52.747
53.093
53.439
53.782
54.125
54.466
54.807
Type J Thermocouples
Meet NBS 561, BS 4937 1973, JIS-C 1602-1981
Temperature C
0
10
20
30
40
50
60
70
80
90
0.000
0.507
1.019
1.536
2.058
2.585
3.115
3.649
4.186
4.725
100
5.268
5.812
6.359
6.907
7.457
8.008
8.560
9.113
9.667
10.222
200
10.777
11.332
11.887
12.442
12.998
13.553
14.108
14.663
15.217
15.771
300
16.325
16.879
17.432
17.984
18.537
19.089
19.640
20.192
20.743
21.295
400
21.846
22.397
22.949
23.501
24.054
24.607
25.161
25.716
26.272
26.829
500
27.388
27.949
28.511
29.075
29.642
30.210
30.782
31.356
31.933
32.513
600
33.096
33.683
34.273
34.867
35.464
36.066
36.671
37.280
37.893
38.510
700
39.130
39.754
40.382
41.013
41.647
42.283
42.922
43.563
44.207
44.852
800
45.498
46.144
46.790
47.434
48.096
48.716
49.354
49.989
50.621
51.249
900
51.875
52.496
53.115
53.729
54.341
54.948
55.553
56.155
56.753
57.349
1000
57.942
58.533
59.121
59.708
60.293
60.876
61.459
62.039
62.619
63.199
1100
63.777
64.355
64.933
65.510
66.087
66.664
67.240
67.815
68.390
68.964
1200
69.536
Note:
10
20
30
40
50
60
70
80
90
0.000
0.520
1.050
1.580
2.110
2.650
3.190
3.730
4.270
4.820
100
5.370
5.920
6.470
7.030
7.590
8.150
8.710
9.270
9.830
10.222
200
10.950
11.510
12.070
12.630
13.190
13.750
14.310
14.880
15.440
16.000
300
16.560
17.120
17.680
18.240
18.800
19.360
19.920
20.480
21.040
21.600
400
22.160
22.720
23.290
23.860
24.430
25.000
25.570
26.140
26.710
27.280
500
27.850
28.430
29.020
29.590
30.170
30.750
31.330
31.910
32.490
33.080
600
33.670
34.260
34.850
35.440
36.040
36.640
37.250
37.850
38.470
39.090
700
39.720
40.350
40.980
41.620
42.270
42.920
43.570
44.230
44.890
45.550
800
46.220
46.890
47.570
48.250
48.940
49.630
50.320
51.020
51.720
52.431
E--25
REFERENCE
INFORMATION
Type R Thermocouples
Meet NBS 561, BS 4937 1973, JIS-C 1602-1981
Temperature C
10
20
30
40
50
60
70
80
90
0.000
0.054
0.111
0.171
0.232
0.296
0.363
0.431
0.501
0.573
100
0.647
0.723
0.800
0.879
0.959
1.041
1.124
1.208
1.294
1.380
200
1.468
1.557
1.647
1.738
1.830
1.923
2.017
2.111
2.207
2.302
300
2.400
2.498
2.596
2.695
2.795
2.896
2.997
3.099
3.201
3.304
400
3.407
3.511
3.616
3.721
3.826
3.933
4.039
4.146
4.254
4.362
500
4.471
4.580
4.689
4.799
4.910
5.021
5.132
5.244
5.356
5.469
600
5.582
5.696
5.810
5.925
6.040
6.155
6.272
6.388
6.505
6.623
700
6.741
6.860
6.979
7.098
7.218
7.339
7.460
7.582
7.703
7.826
800
7.947
8.072
8.196
8.320
8.445
8.570
8.696
8.822
8.949
9.076
900
9.203
9.331
9.460
9.589
9.718
9.848
9.978
10.109
10.240
10.371
1000
10.503
10.636
10.768
10.902
11.035
11.170
11.304
11.439
11.574
11.710
1100
11.846
11.983
12.119
12.257
12.394
12.532
12.669
12.808
12.946
13.085
1200
13.224
13.363
13.502
13.642
13.782
13.922
14.062
14.202
14.343
14.483
1300
14.624
14.765
14.906
15.047
15.188
15.329
15.470
15.611
15.752
15.893
1400
16.035
16.176
16.317
16.458
16.599
16.741
16.882
17.022
17.163
17.304
1500
17.445
17.585
17.726
17.866
18.006
18.146
18.286
18.425
18.564
18.703
1600
18.842
18.981
19.119
19.257
19.395
19.533
19.670
19.807
19.941
20.080
1700
20.215
20.350
20.483
20.616
20.748
20.878
21.006
Type S Thermocouples
Meet NBS 561, DIN 43710 1977, BS 4937 1973, JIS-C 1602-1981
Temperature C
Note:
E--26
10
20
30
40
50
60
70
80
90
0.000
0.055
0.113
0.173
0.235
0.299
0.365
0.432
0.502
0.573
100
0.645
0.719
0.795
0.872
0.950
1.029
1.109
1.190
1.273
1.356
200
1.440
1.525
1.611
1.698
1.785
1.873
1.962
2.051
2.141
2.232
300
2.323
2.414
2.506
2.599
2.692
2.786
2.880
2.974
3.069
3.164
400
3.260
3.356
3.452
3.549
3.645
3.743
3.840
3.938
4.036
4.135
500
4.234
4.333
4.432
4.532
4.632
4.732
4.832
4.933
600
5.237
5.339
5.442
5.544
5.648
5.751
5.855
5.960
6.064
6.169
700
6.274
6.380
6.486
6.592
6.699
6.805
6.913
7.020
7.128
7.236
800
7.345
7.454
7.563
7.672
7.782
7.892
8.003
8.114
8.225
8.336
900
8.448
8.560
8.673
8.786
8.899
9.012
9.126
9.240
9.355
9.470
1000
9.585
9.700
9.816
9.932
10.048
10.165
10.282
10.400
10.517
10.635
50.34
5.136
1100
10.754
10.872
10.991
11.110
11.229
11.348
11.467
11.587
11.707
11.827
1200
11.947
12.067
12.188
12.308
12.429
12.550
12.671
12.792
12.913
13.034
1300
13.155
13.276
13.397
13.519
13.640
13.716
13.883
14.004
14.125
14.247
1400
14.368
14.489
14.610
14.731
14.852
14.973
15.094
15.215
15.336
15.456
1500
15.576
15.697
15.817
15.937
16.057
16.176
16.296
16.415
16.534
16.653
1600
16.771
16.890
17.008
17.125
17.243
17.360
17.477
17.594
17.711
17.826
1700
17.942
18.056
18.170
18.282
18.394
18.504
18.612
REFERENCE
INFORMATION
10
20
30
40
50
60
70
17.14
21.46
25.80
30.12
34.42
38.68
42.91
47.11
80
90
51.29
55.44
--100
59.57
63.68
67.77
71.85
75.91
79.96
83.99
88.01
92.02
96.02
100.00
103.97
107.93
111.88
115.81
119.73
123.64
127.54
131.42
135.30
100
139.16
143.01
146.85
150.67
154.49
158.29
162.08
165.86
169.63
173.38
200
177.13
180.86
184.58
188.29
191.99
195.67
199.35
203.01
206.66
210.30
300
213.93
217.54
221.15
224.74
228.32
231.89
235.45
238.99
242.53
246.05
400
249.56
253.06
256.55
260.02
263.49
266.94
270.38
273.80
277.22
280.63
500
284.02
287.40
290.77
294.12
297.47
300.80
304.12
307.43
310.72
600
317.28
320.54
323.78
327.02
330.24
314.01
10
20
30
40
50
60
70
--200
18.53
22.78
27.05
31.28
35.48
39.65
43.80
--100
60.20
64.25
68.28
72.29
76.28
80.25
84.21
100.00
103.90
107.79
111.67
115.54
119.40
100
138.50
142.28
146.06
149.82
153.57
200
175.84
179.51
183.17
186.82
190.46
300
212.03
215.58
219.13
222.66
400
247.06
250.50
253.93
257.34
500
280.93
284.26
287.57
600
313.65
316.86
320.05
700
345.21
80
90
47.93
52.04
56.13
88.17
92.13
96.07
123.24
127.07
130.89
134.70
157.32
161.04
164.76
168.47
172.16
194.08
197.70
201.30
204.88
208.46
226.18
229.69
233.19
236.67
240.15
243.61
260.75
264.14
267.52
270.89
274.25
277.60
290.87
294.16
297.43
300.70
303.95
307.20
310.43
323.24
326.41
329.57
332.72
335.86
338.99
342.10
E--27
REFERENCE
INFORMATION
E--28
Ratio
deviation
--55
3.514
--50
3.415
--40
3.168
--30
Operating
p
g
t
temperature
t
C
0 to 100C
Ratio
Ratio
deviation
Operating
p
g
t
temperature
t
C
50 to 150C
Ratio
Ratio
deviation
--10
3.689
40
3.774
0.022
3.415
0.030
50
3.415
0.037
0.029
10
3.096
0.033
60
3.051
0.036
2.851
0.034
20
2.755
0.034
70
2.700
0.034
--20
2.497
0.036
30
2.419
0.033
80
2.377
0.031
--10
2.148
0.033
40
2.110
0.029
90
2.089
0.027
1.841
0.028
50
1.841
0.025
100
1.841
0.023
10
1.592
0.022
60
1.617
0.020
110
1.630
0.019
20
1.403
0.017
70
1.436
0.016
120
1.454
0.016
30
1.264
0.012
80
1.293
0.013
130
1.309
0.013
40
1.165
0.009
90
1.181
0.010
140
1.191
0.011
50
1.094
0.006
100
1.094
0.008
150
1.094
0.009
110
1.026
160
1.015
Operating
p
g
t
temperature
t
C
Note:
--50 to 50C
Ratio
100 to 250C
Ratio
Ratio
deviation
Operating
p
g
t
temperature
t
C
150 to 300C
Ratio
Ratio
deviation
Operating
p
g
t
temperature
t
C
200 to 350C
Ratio
Ratio
deviation
90
3.627
140
3.672
190
3.665
100
3.415
0.022
150
3.415
0.026
200
3.415
0.025
110
3.186
0.023
160
3.161
0.025
210
3.167
0.025
120
2.953
0.023
170
2.916
0.024
220
2.926
0.024
130
2.722
0.023
180
2.683
0.023
230
2.695
0.023
140
2.499
0.022
190
2.466
0.021
240
2.477
0.021
150
2.290
0.020
200
2.265
0.019
250
2.274
0.020
160
2.096
0.019
210
2.083
0.018
260
2.088
0.018
170
1.921
0.017
220
1.917
0.016
270
1.919
0.016
180
1.764
0.015
230
1.768
0.014
280
1.767
0.014
190
1.626
0.013
240
1.634
0.013
290
1.633
0.013
200
1.504
0.012
250
1.515
0.011
300
1.517
0.011
210
1.398
0.010
260
1.409
0.010
310
1.411
0.010
220
1.305
0.009
270
1.316
0.009
320
1.317
0.009
230
1.225
0.008
280
1.232
0.008
330
1.223
0.008
240
1.155
0.007
290
1.159
0.007
340
1.160
0.007
250
1.094
0.006
300
1.094
0.006
350
1.094
0.006
260
1.041
310
1.036
360
1.036
Ratio deviation means a deviation in the ratio of resistance from specified temperature per each 1C change in the measured
temperature.
REFERENCE
INFORMATION
--50 to 100C
Range
0 to 150C
Range
50 to 200C
Resistance
6 K at 0C (nominal)
Resistance
30 K at 0C (nominal)
Resistance
3 K at 100C (nominal)
Constant B
3390K
Constant B
3450K
Constant B
3894K
Temperature C
Resistance
(K)
Temperature C
Resistance
(K)
Deviation
(K)
Temperature C
Resistance
(K)
Deviation
(K)
Deviation
(K)
--50
75.360
4.280
--20
77.070
30
28.050
--40
42.900
2.280
--10
47.410
40
19.310
--30
25.230
1.260
30.000
1.350
50
13.570
0.470
--20
15.210
0.720
10
19.490
0.800
60
9.717
0.310
--10
9.414
0.422
20
12.970
0.500
70
7.081
0.214
6.000
0.261
30
8.828
0.323
80
5.243
0.151
10
3.934
0.158
40
6.140
0.212
90
3.939
0.108
20
2.637
0.100
50
4.356
0.144
100
3.000
0.080
30
1.812
0.065
60
3.147
0.098
110
2.314
0.058
40
1.266
0.043
70
2.317
0.068
120
1.805
0.043
50
0.904
0.029
80
1.734
0.048
130
1.424
0.033
60
0.685
0.020
90
1.318
0.035
140
1.134
0.025
70
0.487
0.014
100
1.017
0.026
150
0.912
0.019
80
0.366
0.010
110
0.794
0.019
160
0.735
0.015
90
0.279
0.007
120
0.628
0.014
170
0.596
0.012
100
0.216
0.005
130
0.502
0.011
180
0.487
0.010
110
0.168
140
0.405
0.008
190
0.400
0.008
120
0.133
150
0.330
0.006
200
0.331
0.006
160
0.272
170
0.226
Range
100 to 250C
Range
150 to 300C
Range
200 to 350C
Resistance
Resistance
4 K at 200C (nominal)
Resistance
8 K at 200C (nominal)
Constant B
4300K
Constant B
5133K
Constant B
5559K
Temperature C
Resistance
(K)
Temperature C
Resistance
(K)
Temperature C
Resistance
(K)
Deviation
(K)
Deviation
(K)
Deviation
(K)
80
12.660
130
23.060
180
13.390
90
8.626
140
17.440
190
10.290
100
6.281
0.194
150
13.330
0.350
200
38.000
0.190
110
4.649
0.134
160
10.290
0.260
210
6.305
0.146
120
3.495
0.096
170
8.027
0.194
220
5.015
0.111
130
2.664
0.069
180
6.312
0.147
230
4.014
0.086
140
2.056
0.051
190
5.006
0.113
240
3.240
0.067
150
1.510
0.039
200
4.000
0.087
250
2.634
0.054
160
1.273
0.029
210
3.221
0.068
260
2.156
0.042
170
1.017
0.022
220
2.611
0.053
270
1.779
0.033
180
0.824
0.017
230
2.131
0.042
280
1.474
0.027
190
0.669
0.013
240
1.751
0.034
290
1.228
0.022
200
0.550
0.010
250
1.445
0.027
300
1.030
0.018
210
0.455
0.008
260
1.202
0.022
310
0.868
0.014
220
0.381
0.007
270
1.004
0.018
320
0.738
0.012
230
0.319
0.005
280
0.842
0.014
330
0.631
0.010
240
0.270
0.004
290
0.711
0.012
340
0.542
0.008
250
0.230
0.003
300
0.602
0.010
350
0.468
0.007
260
0.197
310
0.513
270
0.169
320
0.428
Note:
Resistance deviation means a deviation of actual resistance at the specified temperature per each 1C change in the measured
temperature.
E--29
REFERENCE
E--30
INFORMATION