1. The HFSR Soft Starter shall work on the principles of Harmonics free Series Reactor [HFSR]
Technology. It should follow the [IS standard 5553[part 3] year 1990 / IEC 60289/076 year
1988] for the design of the current limiting reactors which is the prime and key component of
the soft starter.
2. The Soft starter shall be designed for Supply Voltage Variation of 10% & Frequency variation
5 %.
3. The HT Soft Starter shall be rated corresponding to the Motor Power & shall be capable of
Operating satisfactorily with the Motor under the various loading & starting condition of the
Motor over the entire Operating Range. The Soft Starter rating offered shall not be less than
the rated KW of the Motor.
4. The HFSR Soft Starter shall reduce the starting current of the Motor at least to 60% of the direct
online (DOL) starting current of the Motor & should have a provision to further reduction of
starting current up to 50 % if motor / load torque permits so. The Soft starter shall control the
starting torque in such a manner so as to effect smooth starting of the Motor Drive is achieved.
Further line current reduction should be [if required] achieved by the use of dynamic
compensator. For further system current reduction a standalone dynamic compensator can be
used to reduce the current up to 1.5 X FLC.
5. The HFSR Soft starter shall be provided with suitably rated digital ammeter to indicate the
Motor current during starting.
6. The Soft Starter shall be so rated as to allow at least three starts equally spaced per hour or one
hot start.
7. The Reactor Windings of HFSR Soft Starters shall be with insulation Class H; maximum
temperature of winding shall be limited to that of Class B. The HFSR reactor modules must be
all weather and vermin proof epoxy casted. Three reactors for three phases must be
independent in construction for easy maintenance and cooling, any reactor should be easily
removable from the panel without disturbing the remaining two. The reactors should be clearly
visible for inspection as well as ventilation and should not be encapsulated or enclosed in any
structure. Suitable TAPs should be provided for onsite current adjustment.
8. The Reactors of HFSR Soft Starter shall be of air core design for smooth linear acceleration and
high efficiency, Natural Air Cooled [meeting all the specification of standard IS 5553[part3] IEC
60289/076] & shall not lead to generation of Harmonics and humming noise during starting
process. No iron or magnetic core should be used for the series reactor as to avoid the eddy
currents, noise/vibrations and heat generation as well as to avoid core saturation and power
losses.
9. The HFSR Soft starters shall have the built in facility to bypass the Reactor near to Full Speed of
the Motor by suitable vacuum device/power device so that the voltage to the Motor is equal to
the supply voltage. The bypass event must be a close loop operation controlled by current and
Temperature monitoring Relay [CTMR].
10. Current and Temperature Monitoring Relay [CTMR]: should be a microcontroller based
intelligent device to control the bypass event for HFSR soft starter. The CTMR must be in-house
tested for EMI/EMC interference. The CTMR must protect the HFSR soft starter from:
Interlock failure
Over current protection
Bypass device failure
Control voltage failure
Total number of starts
Over temperature fault
CTMR must have a proper visual annunciation for the faults.
11. The HT Soft Starter shall have suitable hour meter and operation counter for counting
motor running hours & counting no. of startstop operations of the motor.
12. The HT Soft Starter shall have Anti Condensation Heater with switch & Thermostat. The Heater
shall have interlocking in such a way that it is switched OFF when Motor is in run mode.
13. The HT Soft Starter shall have suitable rated control switchgear like Contactors, Timers, Push
Buttons & Indication Lamps.[ all components should follow the IS standard as per the table 2]
14. The HT Soft Starter shall be indoor, metal clad with separate metal enclosed compartments
for
I. Control, Metering & Push Buttons with indicating Lamps
II. Power Switchgear
III. HFSR Compartment
IV.Power Cable Terminations.
15.
Each cubicle of HT Soft Starter shall be fitted with a label in the front & rear of the
cubicle, indicating the panel designation, rating & duty. Each relay, instrument, switch, fuse &
other devices should be provided with separate labels.
16. The Soft Starter shall be housed in a sheet steel enclosure of thickness not less than 2 mm &
internal frame 3 mm. The enclosure shall be painted with powder coating corrosion resistive
paint as per IS-5 such as Epoxy or Polyurethane. The degree of Protection shall be IP 51. The
enclosure should be only CNC fabricated.
17. The HT Soft Starter should be suitable for up to 50 degree Ambient Temperature and Altitude
up to 1000 m.
18. All the equipments used in the soft starter panel must meet appropriate IS/IEC standards and it
should follow the standard practices and specifications [ refer table 2.0 ]
Page
The manufacturer should be designing and manufacturing the air core based HFSR type [IS 5553/IEC
60289] soft starters for at least 3 years. The manufacturer should have at least five performance
certificates for air core based soft starters for at least 500 kW and above rated motors with minimum
25 units supplied over 3 years of span.
Description
Type of Soft starter
Unit
HFSR
Particular
Air core based Series Reactor as Per IS 5553 Part 3
IEC 60269/076
KV
%
3-3.3
+/- 10
6-6.6
+/-10
10-12
+/- 10
0.380-0.690
+/-10
Hz
%
50/60
+/- 5
50/60
+/- 5
50/60
+/- 5
50/60
+/- 5
2
2a
3
3a
4
5
Supply Voltage
Allowable Voltage
Variation
Supply frequency
Supply Frequency
Variation
Motor Ratting
Application
HP/KW
Maximum System
Voltage
KV
3.6
7.2
12
1.1
KV
RMS
7.6
14.2
28
2.5
KV
Peak
37
60
75
9a
9b
Dynamic
10
Reference Ambient
Temperature
Altitude Above MSL
Method of connection
50
50
50
50
10a
11
Built and panel particulars
KA
KA
RMS
KA
Peak
C
Meters 1000
1000
Line/neutral Line/neutral
12
Housing
13
Paint
IS
14
15
16
Degree of protection
Colour finish shade
Bus bar ratting and size
IP
17
18
Cable entry
1000
1000
Line/neutral Line
Page
Comments :
19
Bypass Device
20
Control Voltage
21
22
22a
22b
Vacuum
device
110/220 V
AC/DC
240 VAC
Vacuum
device
110/220 V
AC/DC
240 VAC
Vacuum
device
110/220 V
AC/DC
240 VAC
Power
contactor
Internally
generated
240 VAC
Page
Table 2.0: Relevant IS / IEC standards for all major and minor components used during design and
manufacturing of the HFSR soft starter:
Sl
No.
Specifications
IS No.
a) Series Reactor
5553 (Part 3)
12661 (Part-1)
IEC No
13947-2
60947-2
13118
62271-100
13703
60269
13947-4-1/2
60947-4-1/2
2026
60726
5561
----
8 Current Transformers
2705
60044
9 Voltage Transformers
3156
60186
10 HT Contactor
9046
60470
11 Indicator Lamps
1901
----
12 Time Switch
1766
13947-1
60947-1
3043
----
15 HT Contactor
9046
60470
11353
----
325
----
5578
----
2544
----
13925
871
13 Degree of protection
Note:
All the components specified other than the list as table 2.0 must bear an appropriate standard.
The columns in grey in table 1 indicate the value must be decided by the end user as per the
site/application/system requirement.
Magnetic core based solution must not be used to ensure safety of the system as a whole.
Page
60289/60076