Sei sulla pagina 1di 4

Technical Data Schedule of Power Cable

Sr. No

Item

Unit

Data

Manufacturer

TBEA Xinjiang Cable Company

Cable type

ZR-YJVP2-62

Rated voltage

kV

Max system voltage

kV

Specification (No. * Cross area)

mm

Standard

Operating temperature of cable

90

Operating temperature of cable at short circuit (5s)

250

Conductor

9.1

Conductor material

Copper

9.2

Cross area of conductor

9.3

Conductor shape

9.4

Conductor structure (No. /single wire diameter)

No/mm

7/0.68

9.5

Conductor diameter

mm

2.04

9.6

Max DC resistance of conductor

/km

4.61

10

Insulation

10.1

Insulation type

XLPE

10.2

Nominal thickness of insulation

10.3

Insulation core identification

Yellow, green, red

11

Inner bedding

11.1

Inner bedding type

FR PVC

0.6/1
1.2
2

3*2.5
IEC60502 and technical specification by
clients

mm2

2.5
Circular Stranded

mm

0.7

Annealed copper tape

11.2

Metallic Screen

11.3

Nominal thickness of copper tape

12

Armor

11.1

Armor type

11.2

Nominal thickness of armor

13

Outer sheath

13.1

Outer sheath type

13.2

Nominal thickness of outer sheath

13.3

Color of outer sheath

14

Cable overall diameter (approx.)

mm

15

Min bending radius of cable when operating

mm

0.1

Aluminum tape
0.5

FR PVC
1.8
Black
18.3
220

16

Weight(approx.)

kg/m

0.450

17

Current rating

17.1

In air (ambient temperature 50)

24.3(with the base of 28 at 40,derating


factor is 0.87)

17.2

In soil (ambient temperature 25, thermal resistance 1.0Km/W)

70

18

Mechanical property of insulation before and after aging

18.1

Tensile strength of insulation before aging

Mpa

12.5

18.2

Min elongation of insulation at break before aging (%)

200

18.3

Aging condition

18.4

Tensile strength of insulation after aging

mm

mm

mm

1353168h air heating aging


Mpa

18.5

Variation of tensile strength of insulation

25

18.6

Elongation of insulation at break after aging

18.7

Variation of elongation of insulation at break

25

18.8

Hot set test of insulation

18.8.1

Hot set test condition

200315min20 N/cm2

18.8.2

Max elongation under load

175

18.8.3

Max permanent elongation after cooling

15

19

Mechanical property of outer sheath before and after aging

19.1

Tensile strength of insulation before aging

Mpa

12.5

19.2

Min elongation of outer sheath before aging (%)

150

19.3

Aging condition

19.4

Tensile strength of outer sheath after aging

Mpa

12.5

19.5

Variation of tensile strength of outer sheath

25

19.6

Elongation of outer sheath at break after aging

150

19.7

Variation of elongation of outer sheath at break

25

Drawing of Power cable

1002168h air heating aging

Drawing
No.

Description of goods

Specifications No.

ZR-YJVP2-62-0.6/1kV
3*2.5

IEC60502 and technical


specification by clients

1
2
3
4
5
6
7
8
9

1. Copper conductor 2. XLPE Insulation 3.Fillings 4.Bindding tape