Installation calculation report

Dejan_Pejovski_final
Full

Page 2/61

Project: dejan_pejovski_final

27/05/2015

Page 3/61

Content

Project description................................................................................................................. 4
1.1

Project general settings ................................................................................................................... 4

1.2

Settings for wiring device calculation............................................................................................. 4

1.3

List of loads ....................................................................................................................................... 4

Installation general design .................................................................................................... 5


2.1

List of devices ................................................................................................................................... 5

Calculation notes ................................................................................................................... 7


3.1

Source circuits ...................................................................................... Error! Bookmark not defined.

3.2

Generator circuits ................................................................................. Error! Bookmark not defined.

3.3

LV Source circuits ............................................................................................................................. 7

3.4

UPS circuits ........................................................................................... Error! Bookmark not defined.

3.5

Surge Arrester circuits ......................................................................... Error! Bookmark not defined.

3.6

Capacitor bank circuits ........................................................................ Error! Bookmark not defined.

3.7

Feeder circuits ....................................................................................... Error! Bookmark not defined.

3.8

LV Transformer circuits ........................................................................ Error! Bookmark not defined.

3.9

Couplers circuits ................................................................................... Error! Bookmark not defined.

3.10

Generic load circuits ....................................................................... Error! Bookmark not defined.

3.11

Lighting load circuits ................................................................................................................ 10

3.12

Power socket load circuits ....................................................................................................... 31

3.13

Motor starter combination .............................................................. Error! Bookmark not defined.

3.14

Busbar circuits ........................................................................................................................... 61

3.15

Busbar trunking system circuits .................................................... Error! Bookmark not defined.

3.16

Busbar trunking system circuits .................................................... Error! Bookmark not defined.

3.17

Lighting Busbar trunking system circuits .................................... Error! Bookmark not defined.

Project: dejan_pejovski_final

27/05/2015

Page 4/61

1 Project description
1.1 Project general settings
Installation standard

IEC60364

Calculation standard
Circuit breaker standard
Frequency

TR50480
IEC 60947-2
50 Hz

1.2 Settings for wiring device calculation


Maximal CSA

300 mm

1.3 List of loads


Name
AA 1
AA 2
AA 3
AA 4
AA 5
AA 6
AA 7
AA 8
AA 9
AA 10

Name
EA 11

EA 14

EA 13

EA 12

EA 15

EA 16

EA 17

1.3.1 Power sockets


Sr (kVA) Pr (kW) Ir (A)
1.05
1
2.64
1.05
1
2.64
1.05
1
2.64
1.05
1
2.64
1.05
1
2.64
1.05
1
2.64
1.05
1
2.64
1.05
1
2.64
1.05
1
2.64
1.05
1
2.64

Cos
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95

Nbr
2
2
2
2
2
2
2
2
2
2

1.3.2 Lighting distribution


Type of lamp P Lamp (W)
P ballast (W)
Fluorescent
58
4.5
with electronic
ballast
Fluorescent
58
4.5
with electronic
ballast
Fluorescent
58
4.5
with electronic
ballast
Fluorescent
58
4.5
with electronic
ballast
Fluorescent
58
4.5
with electronic
ballast
Fluorescent
58
4.5
with electronic
ballast
Fluorescent
58
4.5
with electronic
ballast

Project: dejan_pejovski_final

Polarity
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N

Non linear load


No
No
No
No
No
No
No
No
No
No

Nb of lamp/light
4

Nb of light
8

THDi 3 (%)
0
0
0
0
0
0
0
0
0
0

27/05/2015

Page 5/61

2 Installation general design


2.1 List of devices
2.1.1 LV switchboards and busbar
Switchboard name
Range
UC 2
No preference

Busbar name

Switchboard
name
UC 2

WC 1

Name

2.1.2
Nbr

QA 0

QA 1

QA 2

QA 3

QA 4

QA 5

QA 6

QA 7

QA 8

QA 9

QA 10

QA 11

QA 14

QA 13

QA 12

QA 15

QA 16

QA 17

Circuit breaker
Range Rating (A)
Designation
Compact
250
NSX NSX250B
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 6
iC60N
Acti9 iC60 - 6
iC60N
Acti9 iC60 - 6
iC60N
Acti9 iC60 - 6
iC60N
Acti9 iC60 - 6
iC60N
Acti9 iC60 - 6
iC60N
Acti9 iC60 - 6
iC60N

2.1.3 Cable schedule


Name Nbr Incomer Feeder Type
WD 10 2
QA 10 AA 10
Multi-core
Project: dejan_pejovski_final

Rating (A)
0.00

IP
Undefined

Ks

Polarity

SEA

Equipotential bounding

3Ph+N

TN-S

With

Poles

Trip unit/Curve

4P4d

Micrologic 5.2 A

4P4d

4P4d

4P4d

4P4d

4P4d

4P4d

4P4d

4P4d

4P4d

4P4d

4P4d

4P4d

4P4d

4P4d

4P4d

4P4d

4P4d

Insulation L (m)
PVC
60

RCD

L1/L2/L3
1x1.5
Copper

N
1x1.5
Copper

RCD class

PE/PEN
1x1.5
Copper
27/05/2015

Page 6/61

WD 9

QA 9

AA 9

Multi-core

PVC

60

WD 17 1

QA 17

EA 17

Multi-core

PVC

50

WD 16 8

QA 16

EA 16

Multi-core

PVC

50

WD 12 8

QA 12

EA 12

Multi-core

PVC

50

WD 11 8

QA 11

EA 11

Multi-core

PVC

50

WD 2

QA 2

AA 2

Multi-core

PVC

50

WD 1

QA 1

AA 1

Multi-core

PVC

50

WD 15 8

QA 15

EA 15

Multi-core

PVC

45

WD 13 8

QA 13

EA 13

Multi-core

PVC

45

WD 14 8

QA 14

EA 14

Multi-core

PVC

40

WD 4

QA 4

AA 4

Multi-core

PVC

40

WD 3

QA 3

AA 3

Multi-core

PVC

40

WD 6

QA 6

AA 6

Multi-core

PVC

30

WD 5

QA 5

AA 5

Multi-core

PVC

30

WD 8

QA 8

AA 8

Multi-core

PVC

20

WD 7

QA 7

AA 7

Multi-core

PVC

20

WD 0

W0

QA 0

Multi-core

PVC

Project: dejan_pejovski_final

1x1.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x95
Copper

1x1.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x95
Copper

1x1.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x50
Copper

27/05/2015

Page 7/61

3 Calculation notes
3.1 LV Source circuits
3.1.1 Circuit Source 0
LV power supply
W0
Connection description
Type of connection
Private substation
Ur
230 V
Connection capacity - Ir
206 A
Polarity
3Ph+N
System earthing arrangement
TN-S
Equipotential bounding
No
Rb (neutral grounding)
NA
Ra (mass grounding)
NA
Short circuit characteristics
Ik3max
20 kA
Ik1min
8 kA
Ief
10 kA
Ief2min
5 kA
0.3
Cos cc
Cable
WD 0
Parameters
Length
5m
Max length
NA
Installation method
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
206 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Loaded neutral factor
1
Standard table reference
D-52-1
Touching conductor factor
1
Standard table reference
A-52-20
User correction factor
1
Overall factor
1

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Project: dejan_pejovski_final

1x95 mm
Copper
238 A
1x95 mm
Copper
27/05/2015

Page 8/61

Iz under real conditions


Selected PE
Cross section area
Core

238 A
1x50 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 20.00
17.32

9.26

13.37

7.21

8.43 0.00

Synthesis for all operating mode


(kA) 20.00
17.32
9.26

13.37

7.21

8.43 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Circuit breaker
Ib
Distance from origin

QA 0
206 A
NA

Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current

Sized by system
Compact NSX
NSX250B
250 A
40 kA
NA
NA
NA
4P4d
Micrologic 5.2 A
250 A

Discrimination Results
UpStream

207 A
16 s
2070 A
0s
3000 A

Discrimination Limit

Operating mode Normal


NA

Design current
IL1

Discrimination can't be determinated : no


upstream Lv Breaker

IL2

Operating mode Normal


(A)
206.499
206.499

Project: dejan_pejovski_final

IL3

148.235

IN

58.3

27/05/2015

Page 9/61

Synthesis for all operating mode


(A)
206.499
206.499
148.235
Voltage drop
Cumulated from upstream
Operating mode Normal
2.192
U3L (%)
2.222
UL1L2 (%)
2.222
UL2L3 (%)
2.222
UL3L1 (%)
2.192
UL1N (%)
2.192
UL2N (%)
2.192
UL3N (%)

Project: dejan_pejovski_final

58.3
Circuit

0.192
0.222
0.222
0.222
0.192
0.192
0.192

27/05/2015

Page 10/61

3.2 Lighting load circuits


3.2.1 Circuit Load 11
Circuit breaker
QA 11
Ib
5.95 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
6A
20 kA
NA
NA
NA
4P4d
C
6A
6A
NA
48 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 11

50 m
246 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
6A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 11 has been

Project: dejan_pejovski_final

27/05/2015

Page 11/61

increased from 1.5 to 2.5 to comply with


the voltage drop in the circuit.
Sized
with Ir
Correction factors
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.24

0.14

0.14 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.24

0.14

0.14 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Project: dejan_pejovski_final

EA 11
230 V
2.37 kVA
2 kW
5.95 A
0.95
1
8
3Ph+N
Fluorescent with electronic ballast
8
4
58 W
4.5 W
5.95 A
No
0
NA
IL3

IN
27/05/2015

Page 12/61

Operating mode Normal


(A)
5.945
5.945

3.964

Synthesis for all operating mode


(A)
5.945
5.945
3.964
Voltage drop
Cumulated from upstream
Operating mode Normal
4.087
U3L (%)
4.410
UL1L2 (%)
4.045
UL2L3 (%)
4.045
UL3L1 (%)
4.719
UL1N (%)
4.719
UL2N (%)
4.087
UL3N (%)

1.98

1.98
Circuit

1.895
2.188
1.824
1.824
2.527
2.527
1.895

Synthesis for all operating mode


4.087
U3L (%)
4.410
UL1L2 (%)
4.045
UL2L3 (%)
4.045
UL3L1 (%)
4.719
UL1N (%)
4.719
UL2N (%)
4.087
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 13/61

3.2.2 Circuit Load 14


Circuit breaker
QA 14
Ib
5.95 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
6A
20 kA
NA
NA
NA
4P4d
C
6A
6A
NA
48 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 14

40 m
246 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
6A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 14 has been
increased from 1.5 to 2.5 to comply with
the voltage drop in the circuit.
Sized
with Ir
Correction factors
Temperature factor
1

Project: dejan_pejovski_final

27/05/2015

Page 14/61

Standard table reference


Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.30

0.18

0.18 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.30

0.18

0.18 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Operating mode Normal
(A)
5.945
5.945

Project: dejan_pejovski_final

EA 14
230 V
2.37 kVA
2 kW
5.95 A
0.95
1
8
3Ph+N
Fluorescent with electronic ballast
8
4
58 W
4.5 W
5.95 A
No
0
NA
IL3

3.964

IN

1.98

27/05/2015

Page 15/61

Synthesis for all operating mode


(A)
5.945
5.945
3.964
Voltage drop
Cumulated from upstream
Operating mode Normal
3.708
U3L (%)
3.972
UL1L2 (%)
3.681
UL2L3 (%)
3.681
UL3L1 (%)
4.214
UL1N (%)
4.214
UL2N (%)
3.708
UL3N (%)

1.98
Circuit

1.516
1.751
1.459
1.459
2.021
2.021
1.516

Synthesis for all operating mode


3.708
U3L (%)
3.972
UL1L2 (%)
3.681
UL2L3 (%)
3.681
UL3L1 (%)
4.214
UL1N (%)
4.214
UL2N (%)
3.708
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 16/61

3.2.3 Circuit Load 13


Circuit breaker
QA 13
Ib
5.95 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
6A
20 kA
NA
NA
NA
4P4d
C
6A
6A
NA
48 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 13

45 m
246 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
6A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 13 has been
increased from 1.5 to 2.5 to comply with
the voltage drop in the circuit.
Sized
with Ir
Correction factors
Temperature factor
1

Project: dejan_pejovski_final

27/05/2015

Page 17/61

Standard table reference


Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.27

0.16

0.16 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.27

0.16

0.16 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Operating mode Normal
(A)
5.945
5.945

Project: dejan_pejovski_final

EA 13
230 V
2.37 kVA
2 kW
5.95 A
0.95
1
8
3Ph+N
Fluorescent with electronic ballast
8
4
58 W
4.5 W
5.95 A
No
0
NA
IL3

3.964

IN

1.98

27/05/2015

Page 18/61

Synthesis for all operating mode


(A)
5.945
5.945
3.964
Voltage drop
Cumulated from upstream
Operating mode Normal
3.898
U3L (%)
4.191
UL1L2 (%)
3.863
UL2L3 (%)
3.863
UL3L1 (%)
4.466
UL1N (%)
4.466
UL2N (%)
3.898
UL3N (%)

1.98
Circuit

1.706
1.969
1.641
1.641
2.274
2.274
1.706

Synthesis for all operating mode


3.898
U3L (%)
4.191
UL1L2 (%)
3.863
UL2L3 (%)
3.863
UL3L1 (%)
4.466
UL1N (%)
4.466
UL2N (%)
3.898
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 19/61

3.2.4 Circuit Load 12


Circuit breaker
QA 12
Ib
5.95 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
6A
20 kA
NA
NA
NA
4P4d
C
6A
6A
NA
48 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 12

50 m
246 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
6A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 12 has been
increased from 1.5 to 2.5 to comply with
the voltage drop in the circuit.
Sized
with Ir
Correction factors
Temperature factor
1

Project: dejan_pejovski_final

27/05/2015

Page 20/61

Standard table reference


Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.24

0.14

0.14 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.24

0.14

0.14 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Operating mode Normal
(A)
5.945
5.945

Project: dejan_pejovski_final

EA 12
230 V
2.37 kVA
2 kW
5.95 A
0.95
1
8
3Ph+N
Fluorescent with electronic ballast
8
4
58 W
4.5 W
5.95 A
No
0
NA
IL3

3.964

IN

1.98

27/05/2015

Page 21/61

Synthesis for all operating mode


(A)
5.945
5.945
3.964
Voltage drop
Cumulated from upstream
Operating mode Normal
4.087
U3L (%)
4.410
UL1L2 (%)
4.045
UL2L3 (%)
4.045
UL3L1 (%)
4.719
UL1N (%)
4.719
UL2N (%)
4.087
UL3N (%)

1.98
Circuit

1.895
2.188
1.824
1.824
2.527
2.527
1.895

Synthesis for all operating mode


4.087
U3L (%)
4.410
UL1L2 (%)
4.045
UL2L3 (%)
4.045
UL3L1 (%)
4.719
UL1N (%)
4.719
UL2N (%)
4.087
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 22/61

3.2.5 Circuit Load 15


Circuit breaker
QA 15
Ib
5.95 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
6A
20 kA
NA
NA
NA
4P4d
C
6A
6A
NA
48 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 15

45 m
246 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
6A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 15 has been
increased from 1.5 to 2.5 to comply with
the voltage drop in the circuit.
Sized
with Ir
Correction factors
Temperature factor
1

Project: dejan_pejovski_final

27/05/2015

Page 23/61

Standard table reference


Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.27

0.16

0.16 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.27

0.16

0.16 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Operating mode Normal
(A)
5.945
5.945

Project: dejan_pejovski_final

EA 15
230 V
2.37 kVA
2 kW
5.95 A
0.95
1
8
3Ph+N
Fluorescent with electronic ballast
8
4
58 W
4.5 W
5.95 A
No
0
NA
IL3

3.964

IN

1.98

27/05/2015

Page 24/61

Synthesis for all operating mode


(A)
5.945
5.945
3.964
Voltage drop
Cumulated from upstream
Operating mode Normal
3.898
U3L (%)
4.191
UL1L2 (%)
3.863
UL2L3 (%)
3.863
UL3L1 (%)
4.466
UL1N (%)
4.466
UL2N (%)
3.898
UL3N (%)

1.98
Circuit

1.706
1.969
1.641
1.641
2.274
2.274
1.706

Synthesis for all operating mode


3.898
U3L (%)
4.191
UL1L2 (%)
3.863
UL2L3 (%)
3.863
UL3L1 (%)
4.466
UL1N (%)
4.466
UL2N (%)
3.898
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 25/61

3.2.6 Circuit Load 16


Circuit breaker
QA 16
Ib
5.95 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
6A
20 kA
NA
NA
NA
4P4d
C
6A
6A
NA
48 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 16

50 m
246 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
6A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 16 has been
increased from 1.5 to 2.5 to comply with
the voltage drop in the circuit.
Sized
with Ir
Correction factors
Temperature factor
1

Project: dejan_pejovski_final

27/05/2015

Page 26/61

Standard table reference


Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.24

0.14

0.14 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.24

0.14

0.14 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Operating mode Normal
(A)
5.945
5.945

Project: dejan_pejovski_final

EA 16
230 V
2.37 kVA
2 kW
5.95 A
0.95
1
8
3Ph+N
Fluorescent with electronic ballast
8
4
58 W
4.5 W
5.95 A
No
0
NA
IL3

3.964

IN

1.98

27/05/2015

Page 27/61

Synthesis for all operating mode


(A)
5.945
5.945
3.964
Voltage drop
Cumulated from upstream
Operating mode Normal
4.087
U3L (%)
4.410
UL1L2 (%)
4.045
UL2L3 (%)
4.045
UL3L1 (%)
4.719
UL1N (%)
4.719
UL2N (%)
4.087
UL3N (%)

1.98
Circuit

1.895
2.188
1.824
1.824
2.527
2.527
1.895

Synthesis for all operating mode


4.087
U3L (%)
4.410
UL1L2 (%)
4.045
UL2L3 (%)
4.045
UL3L1 (%)
4.719
UL1N (%)
4.719
UL2N (%)
4.087
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 28/61

3.2.7 Circuit Load 17


Circuit breaker
QA 17
Ib
5.95 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
6A
20 kA
NA
NA
NA
4P4d
C
6A
6A
NA
48 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 17

50 m
246 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
6A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 17 has been
increased from 1.5 to 2.5 to comply with
the voltage drop in the circuit.
Sized
with Ir
Correction factors
Temperature factor
1

Project: dejan_pejovski_final

27/05/2015

Page 29/61

Standard table reference


Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.24

0.14

0.14 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.24

0.14

0.14 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Operating mode Normal
(A)
5.945
5.945

Project: dejan_pejovski_final

EA 17
230 V
2.37 kVA
2 kW
5.95 A
0.95
1
1
3Ph+N
Fluorescent with electronic ballast
8
4
58 W
4.5 W
5.95 A
No
0
NA
IL3

3.964

IN

1.98

27/05/2015

Page 30/61

Synthesis for all operating mode


(A)
5.945
5.945
3.964
Voltage drop
Cumulated from upstream
Operating mode Normal
4.087
U3L (%)
4.410
UL1L2 (%)
4.045
UL2L3 (%)
4.045
UL3L1 (%)
4.719
UL1N (%)
4.719
UL2N (%)
4.087
UL3N (%)

1.98
Circuit

1.895
2.188
1.824
1.824
2.527
2.527
1.895

Synthesis for all operating mode


4.087
U3L (%)
4.410
UL1L2 (%)
4.045
UL2L3 (%)
4.045
UL3L1 (%)
4.719
UL1N (%)
4.719
UL2N (%)
4.087
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 31/61

3.3 Power socket load circuits


3.3.1 Circuit Load 1
Circuit breaker
QA 1
Ib
2.64 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 1

50 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors

Project: dejan_pejovski_final

27/05/2015

Page 32/61

Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.15

0.08

0.08 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.15

0.08

0.08 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Operating mode Normal
(A)
2.642
2.642

AA 1
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA
IL3

2.642

Synthesis for all operating mode


(A)
2.642
2.642
2.642
Voltage drop
Cumulated from upstream
Project: dejan_pejovski_final

IN

0
Circuit
27/05/2015

Page 33/61

Operating mode Normal


3.594
U3L (%)
3.841
UL1L2 (%)
3.841
UL2L3 (%)
3.841
UL3L1 (%)
3.594
UL1N (%)
3.594
UL2N (%)
3.594
UL3N (%)

1.402
1.619
1.619
1.619
1.402
1.402
1.402

Synthesis for all operating mode


3.594
U3L (%)
3.841
UL1L2 (%)
3.841
UL2L3 (%)
3.841
UL3L1 (%)
3.594
UL1N (%)
3.594
UL2N (%)
3.594
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 34/61

3.3.2 Circuit Load 2


Circuit breaker
QA 2
Ib
2.64 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 2

50 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16

Project: dejan_pejovski_final

27/05/2015

Page 35/61

Loaded neutral factor


Standard table reference
Touching conductor factor
Standard table reference

1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.15

0.08

0.08 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.15

0.08

0.08 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

AA 2
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA

Operating mode Normal


(A)
2.642
2.642

IL3

2.642

Synthesis for all operating mode


(A)
2.642
2.642
2.642
Voltage drop
Cumulated from upstream
Operating mode Normal
3.594
U3L (%)
3.841
UL1L2 (%)
Project: dejan_pejovski_final

IN

0
Circuit

1.402
1.619
27/05/2015

Page 36/61

UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)

3.841
3.841
3.594
3.594
3.594

1.619
1.619
1.402
1.402
1.402

Synthesis for all operating mode


3.594
U3L (%)
3.841
UL1L2 (%)
3.841
UL2L3 (%)
3.841
UL3L1 (%)
3.594
UL1N (%)
3.594
UL2N (%)
3.594
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 37/61

3.3.3 Circuit Load 3


Circuit breaker
QA 3
Ib
2.64 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 3

40 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16

Project: dejan_pejovski_final

27/05/2015

Page 38/61

Loaded neutral factor


Standard table reference
Touching conductor factor
Standard table reference

1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.18

0.11

0.11 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.18

0.11

0.11 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

AA 3
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA

Operating mode Normal


(A)
2.642
2.642

IL3

2.642

Synthesis for all operating mode


(A)
2.642
2.642
2.642
Voltage drop
Cumulated from upstream
Operating mode Normal
3.314
U3L (%)
3.517
UL1L2 (%)
Project: dejan_pejovski_final

IN

0
Circuit

1.122
1.295
27/05/2015

Page 39/61

UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)

3.517
3.517
3.314
3.314
3.314

1.295
1.295
1.122
1.122
1.122

Synthesis for all operating mode


3.314
U3L (%)
3.517
UL1L2 (%)
3.517
UL2L3 (%)
3.517
UL3L1 (%)
3.314
UL1N (%)
3.314
UL2N (%)
3.314
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 40/61

3.3.4 Circuit Load 4


Circuit breaker
QA 4
Ib
2.64 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 4

40 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16

Project: dejan_pejovski_final

27/05/2015

Page 41/61

Loaded neutral factor


Standard table reference
Touching conductor factor
Standard table reference

1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.18

0.11

0.11 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.18

0.11

0.11 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

AA 4
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA

Operating mode Normal


(A)
2.642
2.642

IL3

2.642

Synthesis for all operating mode


(A)
2.642
2.642
2.642
Voltage drop
Cumulated from upstream
Operating mode Normal
3.314
U3L (%)
3.517
UL1L2 (%)
Project: dejan_pejovski_final

IN

0
Circuit

1.122
1.295
27/05/2015

Page 42/61

UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)

3.517
3.517
3.314
3.314
3.314

1.295
1.295
1.122
1.122
1.122

Synthesis for all operating mode


3.314
U3L (%)
3.517
UL1L2 (%)
3.517
UL2L3 (%)
3.517
UL3L1 (%)
3.314
UL1N (%)
3.314
UL2N (%)
3.314
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 43/61

3.3.5 Circuit Load 5


Circuit breaker
QA 5
Ib
2.64 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 5

30 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16

Project: dejan_pejovski_final

27/05/2015

Page 44/61

Loaded neutral factor


Standard table reference
Touching conductor factor
Standard table reference

1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.24

0.14

0.14 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.24

0.14

0.14 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

AA 5
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA

Operating mode Normal


(A)
2.642
2.642

IL3

2.642

Synthesis for all operating mode


(A)
2.642
2.642
2.642
Voltage drop
Cumulated from upstream
Operating mode Normal
3.033
U3L (%)
3.193
UL1L2 (%)
Project: dejan_pejovski_final

IN

0
Circuit

0.841
0.971
27/05/2015

Page 45/61

UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)

3.193
3.193
3.033
3.033
3.033

0.971
0.971
0.841
0.841
0.841

Synthesis for all operating mode


3.033
U3L (%)
3.193
UL1L2 (%)
3.193
UL2L3 (%)
3.193
UL3L1 (%)
3.033
UL1N (%)
3.033
UL2N (%)
3.033
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 46/61

3.3.6 Circuit Load 6


Circuit breaker
QA 6
Ib
2.64 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 6

30 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16

Project: dejan_pejovski_final

27/05/2015

Page 47/61

Loaded neutral factor


Standard table reference
Touching conductor factor
Standard table reference

1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.24

0.14

0.14 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.24

0.14

0.14 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

AA 6
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA

Operating mode Normal


(A)
2.642
2.642

IL3

2.642

Synthesis for all operating mode


(A)
2.642
2.642
2.642
Voltage drop
Cumulated from upstream
Operating mode Normal
3.033
U3L (%)
3.193
UL1L2 (%)
Project: dejan_pejovski_final

IN

0
Circuit

0.841
0.971
27/05/2015

Page 48/61

UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)

3.193
3.193
3.033
3.033
3.033

0.971
0.971
0.841
0.841
0.841

Synthesis for all operating mode


3.033
U3L (%)
3.193
UL1L2 (%)
3.193
UL2L3 (%)
3.193
UL3L1 (%)
3.033
UL1N (%)
3.033
UL2N (%)
3.033
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 49/61

3.3.7 Circuit Load 7


Circuit breaker
QA 7
Ib
2.64 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 7

20 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16

Project: dejan_pejovski_final

27/05/2015

Page 50/61

Loaded neutral factor


Standard table reference
Touching conductor factor
Standard table reference

1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.36

0.21

0.21 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.36

0.21

0.21 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

AA 7
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA

Operating mode Normal


(A)
2.642
2.642

IL3

2.642

Synthesis for all operating mode


(A)
2.642
2.642
2.642
Voltage drop
Cumulated from upstream
Operating mode Normal
2.753
U3L (%)
2.869
UL1L2 (%)
Project: dejan_pejovski_final

IN

0
Circuit

0.561
0.648
27/05/2015

Page 51/61

UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)

2.869
2.869
2.753
2.753
2.753

0.648
0.648
0.561
0.561
0.561

Synthesis for all operating mode


2.753
U3L (%)
2.869
UL1L2 (%)
2.869
UL2L3 (%)
2.869
UL3L1 (%)
2.753
UL1N (%)
2.753
UL2N (%)
2.753
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 52/61

3.3.8 Circuit Load 8


Circuit breaker
QA 8
Ib
2.64 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 8

20 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16

Project: dejan_pejovski_final

27/05/2015

Page 53/61

Loaded neutral factor


Standard table reference
Touching conductor factor
Standard table reference

1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.36

0.21

0.21 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.36

0.21

0.21 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

AA 8
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA

Operating mode Normal


(A)
2.642
2.642

IL3

2.642

Synthesis for all operating mode


(A)
2.642
2.642
2.642
Voltage drop
Cumulated from upstream
Operating mode Normal
2.753
U3L (%)
2.869
UL1L2 (%)
Project: dejan_pejovski_final

IN

0
Circuit

0.561
0.648
27/05/2015

Page 54/61

UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)

2.869
2.869
2.753
2.753
2.753

0.648
0.648
0.561
0.561
0.561

Synthesis for all operating mode


2.753
U3L (%)
2.869
UL1L2 (%)
2.869
UL2L3 (%)
2.869
UL3L1 (%)
2.753
UL1N (%)
2.753
UL2N (%)
2.753
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 55/61

3.3.9 Circuit Load 9


Circuit breaker
QA 9
Ib
2.64 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 9

60 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16

Project: dejan_pejovski_final

27/05/2015

Page 56/61

Loaded neutral factor


Standard table reference
Touching conductor factor
Standard table reference

1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.12

0.07

0.07 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.12

0.07

0.07 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

AA 9
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA

Operating mode Normal


(A)
2.642
2.642

IL3

2.642

Synthesis for all operating mode


(A)
2.642
2.642
2.642
Voltage drop
Cumulated from upstream
Operating mode Normal
3.875
U3L (%)
4.165
UL1L2 (%)
Project: dejan_pejovski_final

IN

0
Circuit

1.683
1.943
27/05/2015

Page 57/61

UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)

4.165
4.165
3.875
3.875
3.875

1.943
1.943
1.683
1.683
1.683

Synthesis for all operating mode


3.875
U3L (%)
4.165
UL1L2 (%)
4.165
UL2L3 (%)
4.165
UL3L1 (%)
3.875
UL1N (%)
3.875
UL2N (%)
3.875
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 58/61

3.3.10 Circuit Load 10


Circuit breaker
QA 10
Ib
2.64 A
Distance from origin
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Discrimination Results
UpStream

Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA

Discrimination Limit

Operating mode Normal


QA 0
NSX250B
Micrologic 5.2 A
250 A / 4P4d

Full Discrimination

Cable
Parameters
Length
Max length
Installation method

WD 10

60 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16

Project: dejan_pejovski_final

27/05/2015

Page 59/61

Loaded neutral factor


Standard table reference
Touching conductor factor
Standard table reference

1
D-52-1
1
A-52-20
1
1

User correction factor


Overall factor

Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core

1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

0.12

0.07

0.07 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

0.12

0.07

0.07 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.

Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2

AA 10
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA

Operating mode Normal


(A)
2.642
2.642

IL3

2.642

Synthesis for all operating mode


(A)
2.642
2.642
2.642
Voltage drop
Cumulated from upstream
Operating mode Normal
3.875
U3L (%)
4.165
UL1L2 (%)
Project: dejan_pejovski_final

IN

0
Circuit

1.683
1.943
27/05/2015

Page 60/61

UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)

4.165
4.165
3.875
3.875
3.875

1.943
1.943
1.683
1.683
1.683

Synthesis for all operating mode


3.875
U3L (%)
4.165
UL1L2 (%)
4.165
UL2L3 (%)
4.165
UL3L1 (%)
3.875
UL1N (%)
3.875
UL2N (%)
3.875
UL3N (%)

Project: dejan_pejovski_final

27/05/2015

Page 61/61

3.4 Busbar circuits


3.4.1
Busbar
Parameters
Switchboard Name
Switchboard Range
Rating (A)
IP
Feeder
Circuit name

Circuit WC 1
WC 1

Load 1
Load 2
Load 3
Load 4
Load 5
Load 6
Load 7
Load 8
Load 9
Load 10
Load 11
Load 14
Load 13
Load 12
Load 15
Load 16
Load 17

UC 2
No preference
0
Undefined
Protection name

Protection type

QA 1
QA 2
QA 3
QA 4
QA 5
QA 6
QA 7
QA 8
QA 9
QA 10
QA 11
QA 14
QA 13
QA 12
QA 15
QA 16
QA 17

iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N

Short circuit current


Ik3max
Ik2max

Ik1max

Ik2min

Ik1min

Ief

Operating mode Normal


(kA) 18.22
15.78

8.50

13.49

7.27

8.58 0.00

Synthesis for all operating mode


(kA) 18.22
15.78
8.50

13.49

7.27

8.58 0.00

Ief2min

Calculation results in accordance with CENELEC technical report TR50480.


All assumptions and device choices are the user's responsibility.