Project: dejan_pejovski_final
27/05/2015
Page 3/61
Content
Project description................................................................................................................. 4
1.1
1.2
1.3
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
3.10
3.11
3.12
3.13
3.14
3.15
3.16
3.17
Lighting Busbar trunking system circuits .................................... Error! Bookmark not defined.
Project: dejan_pejovski_final
27/05/2015
Page 4/61
1 Project description
1.1 Project general settings
Installation standard
IEC60364
Calculation standard
Circuit breaker standard
Frequency
TR50480
IEC 60947-2
50 Hz
300 mm
Name
EA 11
EA 14
EA 13
EA 12
EA 15
EA 16
EA 17
Cos
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
0.95
Nbr
2
2
2
2
2
2
2
2
2
2
Project: dejan_pejovski_final
Polarity
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
3Ph+N
Nb of lamp/light
4
Nb of light
8
THDi 3 (%)
0
0
0
0
0
0
0
0
0
0
27/05/2015
Page 5/61
Busbar name
Switchboard
name
UC 2
WC 1
Name
2.1.2
Nbr
QA 0
QA 1
QA 2
QA 3
QA 4
QA 5
QA 6
QA 7
QA 8
QA 9
QA 10
QA 11
QA 14
QA 13
QA 12
QA 15
QA 16
QA 17
Circuit breaker
Range Rating (A)
Designation
Compact
250
NSX NSX250B
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 3
iC60N
Acti9 iC60 - 6
iC60N
Acti9 iC60 - 6
iC60N
Acti9 iC60 - 6
iC60N
Acti9 iC60 - 6
iC60N
Acti9 iC60 - 6
iC60N
Acti9 iC60 - 6
iC60N
Acti9 iC60 - 6
iC60N
Rating (A)
0.00
IP
Undefined
Ks
Polarity
SEA
Equipotential bounding
3Ph+N
TN-S
With
Poles
Trip unit/Curve
4P4d
Micrologic 5.2 A
4P4d
4P4d
4P4d
4P4d
4P4d
4P4d
4P4d
4P4d
4P4d
4P4d
4P4d
4P4d
4P4d
4P4d
4P4d
4P4d
4P4d
Insulation L (m)
PVC
60
RCD
L1/L2/L3
1x1.5
Copper
N
1x1.5
Copper
RCD class
PE/PEN
1x1.5
Copper
27/05/2015
Page 6/61
WD 9
QA 9
AA 9
Multi-core
PVC
60
WD 17 1
QA 17
EA 17
Multi-core
PVC
50
WD 16 8
QA 16
EA 16
Multi-core
PVC
50
WD 12 8
QA 12
EA 12
Multi-core
PVC
50
WD 11 8
QA 11
EA 11
Multi-core
PVC
50
WD 2
QA 2
AA 2
Multi-core
PVC
50
WD 1
QA 1
AA 1
Multi-core
PVC
50
WD 15 8
QA 15
EA 15
Multi-core
PVC
45
WD 13 8
QA 13
EA 13
Multi-core
PVC
45
WD 14 8
QA 14
EA 14
Multi-core
PVC
40
WD 4
QA 4
AA 4
Multi-core
PVC
40
WD 3
QA 3
AA 3
Multi-core
PVC
40
WD 6
QA 6
AA 6
Multi-core
PVC
30
WD 5
QA 5
AA 5
Multi-core
PVC
30
WD 8
QA 8
AA 8
Multi-core
PVC
20
WD 7
QA 7
AA 7
Multi-core
PVC
20
WD 0
W0
QA 0
Multi-core
PVC
Project: dejan_pejovski_final
1x1.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x95
Copper
1x1.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x95
Copper
1x1.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper
1x2.5
Copper
1x2.5
Copper
1x2.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x1.5
Copper
1x50
Copper
27/05/2015
Page 7/61
3 Calculation notes
3.1 LV Source circuits
3.1.1 Circuit Source 0
LV power supply
W0
Connection description
Type of connection
Private substation
Ur
230 V
Connection capacity - Ir
206 A
Polarity
3Ph+N
System earthing arrangement
TN-S
Equipotential bounding
No
Rb (neutral grounding)
NA
Ra (mass grounding)
NA
Short circuit characteristics
Ik3max
20 kA
Ik1min
8 kA
Ief
10 kA
Ief2min
5 kA
0.3
Cos cc
Cable
WD 0
Parameters
Length
5m
Max length
NA
Installation method
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
206 A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Loaded neutral factor
1
Standard table reference
D-52-1
Touching conductor factor
1
Standard table reference
A-52-20
User correction factor
1
Overall factor
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Project: dejan_pejovski_final
1x95 mm
Copper
238 A
1x95 mm
Copper
27/05/2015
Page 8/61
238 A
1x50 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
9.26
13.37
7.21
8.43 0.00
13.37
7.21
8.43 0.00
Ief2min
Circuit breaker
Ib
Distance from origin
QA 0
206 A
NA
Sizing Information
Range
Designation
Circuit breaker rating
Breaking capacity
TNS One pole breaking capacity
IT One pole breaking capacity
Reinforced breaking capacity
Pole & protected pole
Trip unit designation
Trip unit rating
Long delay settings
Ir
Tr
Short delay settings
Isd current
Tsd
Instantaneous tripping
Ii current
Sized by system
Compact NSX
NSX250B
250 A
40 kA
NA
NA
NA
4P4d
Micrologic 5.2 A
250 A
Discrimination Results
UpStream
207 A
16 s
2070 A
0s
3000 A
Discrimination Limit
Design current
IL1
IL2
Project: dejan_pejovski_final
IL3
148.235
IN
58.3
27/05/2015
Page 9/61
Project: dejan_pejovski_final
58.3
Circuit
0.192
0.222
0.222
0.222
0.192
0.192
0.192
27/05/2015
Page 10/61
Sized by system
Acti9 iC60
iC60N
6A
20 kA
NA
NA
NA
4P4d
C
6A
6A
NA
48 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 11
50 m
246 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
6A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 11 has been
Project: dejan_pejovski_final
27/05/2015
Page 11/61
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.24
0.14
0.14 0.00
0.24
0.14
0.14 0.00
Ief2min
Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Project: dejan_pejovski_final
EA 11
230 V
2.37 kVA
2 kW
5.95 A
0.95
1
8
3Ph+N
Fluorescent with electronic ballast
8
4
58 W
4.5 W
5.95 A
No
0
NA
IL3
IN
27/05/2015
Page 12/61
3.964
1.98
1.98
Circuit
1.895
2.188
1.824
1.824
2.527
2.527
1.895
Project: dejan_pejovski_final
27/05/2015
Page 13/61
Sized by system
Acti9 iC60
iC60N
6A
20 kA
NA
NA
NA
4P4d
C
6A
6A
NA
48 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 14
40 m
246 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
6A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 14 has been
increased from 1.5 to 2.5 to comply with
the voltage drop in the circuit.
Sized
with Ir
Correction factors
Temperature factor
1
Project: dejan_pejovski_final
27/05/2015
Page 14/61
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.30
0.18
0.18 0.00
0.30
0.18
0.18 0.00
Ief2min
Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Operating mode Normal
(A)
5.945
5.945
Project: dejan_pejovski_final
EA 14
230 V
2.37 kVA
2 kW
5.95 A
0.95
1
8
3Ph+N
Fluorescent with electronic ballast
8
4
58 W
4.5 W
5.95 A
No
0
NA
IL3
3.964
IN
1.98
27/05/2015
Page 15/61
1.98
Circuit
1.516
1.751
1.459
1.459
2.021
2.021
1.516
Project: dejan_pejovski_final
27/05/2015
Page 16/61
Sized by system
Acti9 iC60
iC60N
6A
20 kA
NA
NA
NA
4P4d
C
6A
6A
NA
48 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 13
45 m
246 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
6A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 13 has been
increased from 1.5 to 2.5 to comply with
the voltage drop in the circuit.
Sized
with Ir
Correction factors
Temperature factor
1
Project: dejan_pejovski_final
27/05/2015
Page 17/61
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.27
0.16
0.16 0.00
0.27
0.16
0.16 0.00
Ief2min
Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Operating mode Normal
(A)
5.945
5.945
Project: dejan_pejovski_final
EA 13
230 V
2.37 kVA
2 kW
5.95 A
0.95
1
8
3Ph+N
Fluorescent with electronic ballast
8
4
58 W
4.5 W
5.95 A
No
0
NA
IL3
3.964
IN
1.98
27/05/2015
Page 18/61
1.98
Circuit
1.706
1.969
1.641
1.641
2.274
2.274
1.706
Project: dejan_pejovski_final
27/05/2015
Page 19/61
Sized by system
Acti9 iC60
iC60N
6A
20 kA
NA
NA
NA
4P4d
C
6A
6A
NA
48 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 12
50 m
246 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
6A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 12 has been
increased from 1.5 to 2.5 to comply with
the voltage drop in the circuit.
Sized
with Ir
Correction factors
Temperature factor
1
Project: dejan_pejovski_final
27/05/2015
Page 20/61
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.24
0.14
0.14 0.00
0.24
0.14
0.14 0.00
Ief2min
Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Operating mode Normal
(A)
5.945
5.945
Project: dejan_pejovski_final
EA 12
230 V
2.37 kVA
2 kW
5.95 A
0.95
1
8
3Ph+N
Fluorescent with electronic ballast
8
4
58 W
4.5 W
5.95 A
No
0
NA
IL3
3.964
IN
1.98
27/05/2015
Page 21/61
1.98
Circuit
1.895
2.188
1.824
1.824
2.527
2.527
1.895
Project: dejan_pejovski_final
27/05/2015
Page 22/61
Sized by system
Acti9 iC60
iC60N
6A
20 kA
NA
NA
NA
4P4d
C
6A
6A
NA
48 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 15
45 m
246 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
6A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 15 has been
increased from 1.5 to 2.5 to comply with
the voltage drop in the circuit.
Sized
with Ir
Correction factors
Temperature factor
1
Project: dejan_pejovski_final
27/05/2015
Page 23/61
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.27
0.16
0.16 0.00
0.27
0.16
0.16 0.00
Ief2min
Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Operating mode Normal
(A)
5.945
5.945
Project: dejan_pejovski_final
EA 15
230 V
2.37 kVA
2 kW
5.95 A
0.95
1
8
3Ph+N
Fluorescent with electronic ballast
8
4
58 W
4.5 W
5.95 A
No
0
NA
IL3
3.964
IN
1.98
27/05/2015
Page 24/61
1.98
Circuit
1.706
1.969
1.641
1.641
2.274
2.274
1.706
Project: dejan_pejovski_final
27/05/2015
Page 25/61
Sized by system
Acti9 iC60
iC60N
6A
20 kA
NA
NA
NA
4P4d
C
6A
6A
NA
48 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 16
50 m
246 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
6A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 16 has been
increased from 1.5 to 2.5 to comply with
the voltage drop in the circuit.
Sized
with Ir
Correction factors
Temperature factor
1
Project: dejan_pejovski_final
27/05/2015
Page 26/61
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.24
0.14
0.14 0.00
0.24
0.14
0.14 0.00
Ief2min
Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Operating mode Normal
(A)
5.945
5.945
Project: dejan_pejovski_final
EA 16
230 V
2.37 kVA
2 kW
5.95 A
0.95
1
8
3Ph+N
Fluorescent with electronic ballast
8
4
58 W
4.5 W
5.95 A
No
0
NA
IL3
3.964
IN
1.98
27/05/2015
Page 27/61
1.98
Circuit
1.895
2.188
1.824
1.824
2.527
2.527
1.895
Project: dejan_pejovski_final
27/05/2015
Page 28/61
Sized by system
Acti9 iC60
iC60N
6A
20 kA
NA
NA
NA
4P4d
C
6A
6A
NA
48 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 17
50 m
246 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
6A
Sizing constraint
Voltage drop
Sizing Information
The CSA of cable WD 17 has been
increased from 1.5 to 2.5 to comply with
the voltage drop in the circuit.
Sized
with Ir
Correction factors
Temperature factor
1
Project: dejan_pejovski_final
27/05/2015
Page 29/61
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
25 A
1x2.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.24
0.14
0.14 0.00
0.24
0.14
0.14 0.00
Ief2min
Charge
U
S
P
I
cos
Ku (Normal)
Number of circuit
Polarity
Phase connection
Type of luminaries
Nb of luminaries
Nb of lights/luminaries
Lights power
Ballast power
Ia
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Operating mode Normal
(A)
5.945
5.945
Project: dejan_pejovski_final
EA 17
230 V
2.37 kVA
2 kW
5.95 A
0.95
1
1
3Ph+N
Fluorescent with electronic ballast
8
4
58 W
4.5 W
5.95 A
No
0
NA
IL3
3.964
IN
1.98
27/05/2015
Page 30/61
1.98
Circuit
1.895
2.188
1.824
1.824
2.527
2.527
1.895
Project: dejan_pejovski_final
27/05/2015
Page 31/61
Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 1
50 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Project: dejan_pejovski_final
27/05/2015
Page 32/61
Temperature factor
Standard table reference
Soil thermal resistivity factor
Standard table reference
Loaded neutral factor
Standard table reference
Touching conductor factor
Standard table reference
User correction factor
Overall factor
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
1
A-52-14
1
A-52-16
1
D-52-1
1
A-52-20
1
1
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.15
0.08
0.08 0.00
0.15
0.08
0.08 0.00
Ief2min
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
Operating mode Normal
(A)
2.642
2.642
AA 1
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA
IL3
2.642
IN
0
Circuit
27/05/2015
Page 33/61
1.402
1.619
1.619
1.619
1.402
1.402
1.402
Project: dejan_pejovski_final
27/05/2015
Page 34/61
Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 2
50 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Project: dejan_pejovski_final
27/05/2015
Page 35/61
1
D-52-1
1
A-52-20
1
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.15
0.08
0.08 0.00
0.15
0.08
0.08 0.00
Ief2min
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
AA 2
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA
IL3
2.642
IN
0
Circuit
1.402
1.619
27/05/2015
Page 36/61
UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)
3.841
3.841
3.594
3.594
3.594
1.619
1.619
1.402
1.402
1.402
Project: dejan_pejovski_final
27/05/2015
Page 37/61
Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 3
40 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Project: dejan_pejovski_final
27/05/2015
Page 38/61
1
D-52-1
1
A-52-20
1
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.18
0.11
0.11 0.00
0.18
0.11
0.11 0.00
Ief2min
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
AA 3
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA
IL3
2.642
IN
0
Circuit
1.122
1.295
27/05/2015
Page 39/61
UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)
3.517
3.517
3.314
3.314
3.314
1.295
1.295
1.122
1.122
1.122
Project: dejan_pejovski_final
27/05/2015
Page 40/61
Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 4
40 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Project: dejan_pejovski_final
27/05/2015
Page 41/61
1
D-52-1
1
A-52-20
1
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.18
0.11
0.11 0.00
0.18
0.11
0.11 0.00
Ief2min
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
AA 4
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA
IL3
2.642
IN
0
Circuit
1.122
1.295
27/05/2015
Page 42/61
UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)
3.517
3.517
3.314
3.314
3.314
1.295
1.295
1.122
1.122
1.122
Project: dejan_pejovski_final
27/05/2015
Page 43/61
Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 5
30 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Project: dejan_pejovski_final
27/05/2015
Page 44/61
1
D-52-1
1
A-52-20
1
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.24
0.14
0.14 0.00
0.24
0.14
0.14 0.00
Ief2min
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
AA 5
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA
IL3
2.642
IN
0
Circuit
0.841
0.971
27/05/2015
Page 45/61
UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)
3.193
3.193
3.033
3.033
3.033
0.971
0.971
0.841
0.841
0.841
Project: dejan_pejovski_final
27/05/2015
Page 46/61
Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 6
30 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Project: dejan_pejovski_final
27/05/2015
Page 47/61
1
D-52-1
1
A-52-20
1
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.24
0.14
0.14 0.00
0.24
0.14
0.14 0.00
Ief2min
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
AA 6
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA
IL3
2.642
IN
0
Circuit
0.841
0.971
27/05/2015
Page 48/61
UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)
3.193
3.193
3.033
3.033
3.033
0.971
0.971
0.841
0.841
0.841
Project: dejan_pejovski_final
27/05/2015
Page 49/61
Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 7
20 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Project: dejan_pejovski_final
27/05/2015
Page 50/61
1
D-52-1
1
A-52-20
1
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.36
0.21
0.21 0.00
0.36
0.21
0.21 0.00
Ief2min
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
AA 7
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA
IL3
2.642
IN
0
Circuit
0.561
0.648
27/05/2015
Page 51/61
UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)
2.869
2.869
2.753
2.753
2.753
0.648
0.648
0.561
0.561
0.561
Project: dejan_pejovski_final
27/05/2015
Page 52/61
Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 8
20 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Project: dejan_pejovski_final
27/05/2015
Page 53/61
1
D-52-1
1
A-52-20
1
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.36
0.21
0.21 0.00
0.36
0.21
0.21 0.00
Ief2min
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
AA 8
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA
IL3
2.642
IN
0
Circuit
0.561
0.648
27/05/2015
Page 54/61
UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)
2.869
2.869
2.753
2.753
2.753
0.648
0.648
0.561
0.561
0.561
Project: dejan_pejovski_final
27/05/2015
Page 55/61
Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 9
60 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Project: dejan_pejovski_final
27/05/2015
Page 56/61
1
D-52-1
1
A-52-20
1
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.12
0.07
0.07 0.00
0.12
0.07
0.07 0.00
Ief2min
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
AA 9
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA
IL3
2.642
IN
0
Circuit
1.683
1.943
27/05/2015
Page 57/61
UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)
4.165
4.165
3.875
3.875
3.875
1.943
1.943
1.683
1.683
1.683
Project: dejan_pejovski_final
27/05/2015
Page 58/61
Sized by system
Acti9 iC60
iC60N
3A
50 kA
NA
NA
NA
4P4d
C
3A
3A
NA
24 A
NA
NA
Discrimination Limit
Full Discrimination
Cable
Parameters
Length
Max length
Installation method
WD 10
60 m
148 m
31
E
Multi-core cables on horizontal
perforated tray
Type of cable
Multi-core
Nb of additional touching circuits 0
Insulation
PVC
Ambient temperature
30 C
Level of third harmonic THDI
0%
Ib
3A
Sizing constraint
Iz
Sizing Information
Sized with Ir
Correction factors
Temperature factor
1
Standard table reference
A-52-14
Soil thermal resistivity factor
1
Standard table reference
A-52-16
Project: dejan_pejovski_final
27/05/2015
Page 59/61
1
D-52-1
1
A-52-20
1
1
Selected phase
Cross section area
Core
Iz under real conditions
Selected neutral
Cross section area
Core
Iz under real conditions
Selected PE
Cross section area
Core
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
18.5 A
1x1.5 mm
Copper
Ik1max
Ik2min
Ik1min
Ief
8.50
0.12
0.07
0.07 0.00
0.12
0.07
0.07 0.00
Ief2min
Charge
U
S
P
I
cos
Polarity
Phase connection
Number of circuit
Ku (Normal)
Harmonic generator
THDI3
Sensitivity to over voltage
Design current
IL1
IL2
AA 10
230 V
1.05 kVA
1 kW
2.64 A
0.95
3Ph+N
2
1
No
0
NA
IL3
2.642
IN
0
Circuit
1.683
1.943
27/05/2015
Page 60/61
UL2L3 (%)
UL3L1 (%)
UL1N (%)
UL2N (%)
UL3N (%)
4.165
4.165
3.875
3.875
3.875
1.943
1.943
1.683
1.683
1.683
Project: dejan_pejovski_final
27/05/2015
Page 61/61
Circuit WC 1
WC 1
Load 1
Load 2
Load 3
Load 4
Load 5
Load 6
Load 7
Load 8
Load 9
Load 10
Load 11
Load 14
Load 13
Load 12
Load 15
Load 16
Load 17
UC 2
No preference
0
Undefined
Protection name
Protection type
QA 1
QA 2
QA 3
QA 4
QA 5
QA 6
QA 7
QA 8
QA 9
QA 10
QA 11
QA 14
QA 13
QA 12
QA 15
QA 16
QA 17
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
iC60N
Ik1max
Ik2min
Ik1min
Ief
8.50
13.49
7.27
8.58 0.00
13.49
7.27
8.58 0.00
Ief2min
Project: dejan_pejovski_final
27/05/2015