SECTION 09511
SUSPENDED CEILINGS
PART 1:
1.01
A.

GENERAL

SECTION INCLUDES
Suspended ceiling systems, including, but not limited to the following:
1. Suspended decorative exposed grid ceiling.
2. Suspension systems with exposed and concealed grids.

1.02

RELATED SECTIONS

A.

Section 03 30 00

Cast in Place Concrete.

B.

Section 09 21 16

Gypsum Board Assemblies.

C.

Section 09 23 00

Gypsum Plaster.

D.

Section 09 30 13

Ceramic Tiling.

E.

Section 09 91 00

Painting.

1.03

REFERENCES

A.

ASTM A 641M

Specification for Zinc Coated (Galvanized) Carbon Steel Wire.

B.

ASTM A 653M

Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or


Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.

C.

ASTM A 666

Standard Specification for Annealed or Cold-Worked Austenitic


Stainless Steel Sheet, Strip, Plate, and Flat Bar.

D.

ASTM B 209M

Standard Specification for Aluminum and Aluminum-Alloy Sheet and


Plate (Metric).

E.

ASTM B 221M

Standard Specification for Aluminum and Aluminum-Alloy Extruded


Bars, Rods, Wire, Profiles, and Tubes (Metric).

F.

ASTM C 423

Standard Test Method for Sound Absorption and Sound Absorption


Coefficients by the Reverberation Room Method.

G.

ASTM C 635

Standard Specification for the Manufacture, Performance, and Testing


of Metal Suspension Systems for Acoustical Tile and Lay-in Panel
Ceilings.

H.

ASTM C 636

Standard Practice for Installation of Metal Ceiling Suspension


Systems for Acoustical Tile and Lay-In Panels.

I.

ASTM E 84

Standard Test Method for Surface Burning Characteristics of Building


Materials.

SUSPENDED CEILINGS

SECTION 09 51 00 - 1

MINISTRY OF HOUSING
Western Sector Projects
Sitework & Infrastructure
OMRANIA and ASSOCIATES

Project Specification

J.

ASTM E 90

Standard Test Method for Laboratory Measurement of Airborne


Sound Transmission Loss of Building Partitions and Elements.

K.

ASTM E 580

Standard Practice for Application of Ceiling Suspension Systems for


Acoustical Tile and Lay-in Panels in Areas Requiring Moderate
Seismic Restraint.

L.

ASTM E 1264

Standard Classification for Acoustical Ceiling Products.

M.

CISCA

Ceilings and Interior Systems Contractors Association-Acoustical


Ceilings: Use and Practice.

N.

UL

Fire Resistance Directory and Building Material Directory.

1.04
A.

1.05

SYSTEM DESCRIPTION
Suspension system to rigidly secure ceiling systems including integral mechanical and
electrical components, with maximum deflection of 1/360.
SUBMITTALS

A.

Comply with Section 01 33 00.

B.

Product Data: Submit manufacturer's product specifications and installation instructions for
each ceiling material required, and for each suspension system, including certified laboratory
test reports and other data as required to show compliance with this Specification. Include
manufacturer's recommendations for cleaning and refinishing acoustical units, including
precautions against materials and methods which may be detrimental to finishes and acoustical
performance.

C.

Samples: Submit two samples full size of ceiling finish unit required, showing full range of
exposed color, texture and finish to be expected in completed work. Sample shall be a set of
600 mm long of each exposed runner and molding.

D.

Shop Drawings: Submit coordinated shop drawings indicating grid layout and dimensions,
junctions with other work or ceiling finishes, locations and connections with mechanical and
electrical items and expansion joints etc., and points of suspension.

1.06

MOCKUP

A.

Comply with Section 01 40 00.

B.

Construct mockup, 6 m long x 6 m wide, including suspension system, finish panels, closures,
fixtures, integral mechanical and electrical components.

C.

Locate where directed by Engineer.

D.

Accepted mockup may be incorporated as part of the work.

1.07

PRE-INSTALLATION MEETINGS

A.

Comply with Section 01 31 00.

B.

Convene minimum one week prior to commencing work of this Section.

1.08

DELIVERY, STORAGE, AND HANDLING

SUSPENDED CEILINGS

SECTION 09 51 00 - 2

MINISTRY OF HOUSING
Western Sector Projects
Sitework & Infrastructure
OMRANIA and ASSOCIATES

Project Specification

A.

Comply with Section 01 61 00.

B.

Deliver ceiling units to project site in original, unopened packages and store them in a fully
enclosed space where they will be protected against damage from moisture, direct sunlight,
surface contamination or other causes.

C.

Handle ceiling units carefully to avoid chipping edges or damaging units in any way. Damaged
tiles will not be accepted.

1.09

QUALIFICATIONS

A.

Grid Manufacturer: Company specializing in manufacturing products specified in this Section


with minimum 5 years experience.

B.

Ceiling Unit Manufacturer: Company specializing in manufacturing the products specified in


this Section with minimum 5 years experience.

1.10
A.

1.11
A.

1.12

REGULATORY REQUIREMENTS
Conform to applicable code for fire rated assembly and combustibility requirements for
materials.
ENVIRONMENTAL REQUIREMENTS
Maintain environmental temperature and humidity within the range required by the
manufacturer during and after installation.
SEQUENCING

A.

Sequence work under the provisions of Section 01 11 00.

B.

Sequence work to ensure acoustical ceilings are not installed until building is enclosed, dust
generating activities have terminated, and overhead work is completed, tested and approved.

1.13

EXTRA MATERIALS

A.

Furnish under provisions of Section 01 77 00.

B.

Provide 5% of installed area or 20 m2, whichever is lesser, of each ceiling tile to Owner.

1.14

COORDINATION

A.

Comply with Section 01 31 13.

B.

Coordinate work of this section with installation of mechanical and electrical components and
with other construction activities affected by work of this Section.

C.

Furnish concrete inserts, clip other supports required to be installed by other trades for support
of acoustical ceilings in advance of time needed for coordination of other work.

D.

Measure each ceiling area and establish layout of ceiling units to balance border widths at
opposite edges of each ceiling. Avoid use of less-than-half width units at borders, and comply
with reflected ceiling plans wherever possible.

SUSPENDED CEILINGS

SECTION 09 51 00 - 3

MINISTRY OF HOUSING
Western Sector Projects
Sitework & Infrastructure
OMRANIA and ASSOCIATES

1.15

Project Specification

WARRANTY

A.

Comply with Section 01 78 36.

B.

Furnish five years manufacturer warranty; include coverage for corrosion resistance and
discoloration of surface finish.

PART 2:
2.01

PRODUCTS

MATERIALS

A.

Colors, Textures, and Patterns: Provide products to match appearance characteristics indicated
or, if not otherwise indicated, as selected by the Engineer from manufacturer's standard colors,
surface textures, and patterns available for ceiling units and exposed metal suspension system
members of quality designated. Materials and systems shall be as shown on the Drawings and
Schedules.

B.

All materials shall be suitable for use in high humidity environmental conditions.

C.

No fibre board or rockwool based board or similar material allowed for ceiling panels.

D.

Exposed Grid Ceiling System:


1. Suspension System: Non-fire rated, exposed, tee-grid, double web, intermediate duty
ASTM C 635, narrow line system, cold rolled electro-galvanized steel system (S24 system)
with 14 mm wide cap. Color: As approved by Engineer.
2. Anti-bacterial Ceiling Panel: 600 mm x 600 mm by minimum 12.5 mm thick with
perforation, factory finished surface panel with fine line (FL) edges. Color: off-white gloss
or as approved by Engineer.

E.

Suspension Wire: ASTM A 641, Class 1 hanger wire, zinc coating, soft temper, for suspended
and furred ceilings, not less than 2.7 mm.

F.

Carrying Channels: 38 mm, 1.6 mm cold-rolled channels painted with rust inhibitive paint.

G.

Furring Channels: Hat-shaped, 22 mm, 0.5 mm, cold-rolled, electro-galvanized steel.

H.

Hold-down Clips: Corrosion resistant clips as recommended by system manufacturer to


achieve ratings indicated. Similar to Armstrong, Retention Clips No. 414.

I.

Space Closures: Recessed, formed metal sections, colored black or as approved by Engineer,
snap fit between exposed linear panels.

J.

Access Panel: Matching hinged panel/with frameless appearance, swinging downward, with
spring latch.

PART 3:

EXECUTION

A.

Examine conditions at the job site where work of this section is to be performed to ensure
proper arrangement and fit of the work.

B.

Starting of work shall imply acceptance of supporting construction and temperature and
humidity conditions as satisfactory.

SUSPENDED CEILINGS

SECTION 09 51 00 - 4

MINISTRY OF HOUSING
Western Sector Projects
Sitework & Infrastructure
OMRANIA and ASSOCIATES

C.

Verify layout of hangers does not interfere with other work.

D.

Verify required utilities are available, in proper location, and ready for use.

E.

Verify field measurements are as indicated on shop drawings.

3.01

Project Specification

INSTALLATION

A.

General: Install materials in accordance with manufacturer's printed instructions, and to


comply with governing regulations, fire-resistance rating requirements as indicated, and
industry standards applicable to work.

B.

Verify all measurements and dimensions at the project site and coordinate work with the work
of other trades, with particular attention given to the work of mechanical and electrical trades.

C.

Anchorages and fastenings shall be secure and adequate for use intended. Ceilings shall be
erected in rigid and secure manner, level, with tight joints and free from waves, buckles and
sags.

D.

Hang carrying members independent of walls, columns, ducts, light fixtures, pipe and conduit.
Where carrying members are spliced, avoid visible displacement of face panels with adjacent
panels.

E.

Make all exposed surfaces of acoustical units level and flush, with all joints straight and true.
Neatly cut and fit units around light fixtures and around other items protruding through
ceilings. Install all exposed members with flush hairline joints.

F.

Factory drill ceiling tile occurring at hidden loudspeakers and fire alarm gongs.

G.

Center tile or board pattern both directions in each major space or room as shown or directed
and, where possible, adjust pattern so that edge pieces will be not less than 6.3 mm unit in
width.

H.

Run grain of units in one direction, as shown or directed, and align joints in both directions
unless otherwise shown.

I.

Use procedures that will minimize damage or soiling of the units during installation. Replace
units which are damaged or cannot be adequately cleaned as directed.

J.

Provide tabs at access tiles to designate locations of required access, for all non-accessible
ceilings.

K.

Openings shall be framed for support of collateral items such as lighting fixtures and access
units and shall be framed for support of or to fit around ventilating devices, as required for the
units specified. These items described in other sections of the specifications.

L.

Install space closures between linear metal panels at interior location.

M.

Install end caps at sight exposed ends of linear panels.

3.02
A.

INSTALLATION OF MECHANICAL SUSPENSION SYSTEM


Install primary suspension members and mechanical suspension system in accordance with
ASTM C 636 and manufacturer's written instructions to support required loads and to prevent

SUSPENDED CEILINGS

SECTION 09 51 00 - 5

MINISTRY OF HOUSING
Western Sector Projects
Sitework & Infrastructure
OMRANIA and ASSOCIATES

Project Specification

deflection in excess of 1/360 of the span between supports. Level accurately in both directions,
leveling to a tolerance of 3 mm in 3 m.
B.

Install suspension systems with hangers supported only from building structural members.
Locate hangers not less than 150 mm from each end and spaced 1.2 m maximum along each
carrying channel or runner. Coordinate spacing of hangers, carrying channels, runners and
molding with the location of electrical fixtures, sprinkler heads, and other items occurring in or
on the ceiling. Splay hangers only where required to miss obstructions and offset horizontal
force by bracing or other approved methods.

C.

Where ceilings are suspended below ductwork, piping or other building elements which are not
suitable for ceiling attachment due to strength limitations, restrictions of authorities having
jurisdiction, or ceiling system manufacturer's limitations, provide additional supplemental
framing, supports and related work as required to span beneath these elements from suitable
support locations. Design supplemental framing and supports to accommodate the spans and
loads to be sustained and to limit maximum deflections to the criteria specified and to finish to
the lines and levels shown.

D.

Coordinate with mechanical and electrical installers in locating and spacing fixtures, diffusers,
and similar items located in ceiling.

E.

Lay out pattern in compliance with reflected ceiling plans. Where not otherwise indicated, lay
out in such manner that margins on opposite sides of rooms are equal or greater than 1/2 tile in
width.

F.

Carrying channel runners shall be place 1.2 m on center, tied to hangers. Install cross channels
as required between main channels, cut in flush and secure to longitudinal channels where
necessary to accommodate design of ceilings.

3.03

ERECTION TOLERANCES

A.

Comply with Section 01 40 00.

B.

Maximum Variation from Flat and Level Surface: 3 mm in 3 m.

C.

Maximum Variation from Plumb of Grid Members Caused by Eccentric Loads: 2 degrees.

D.

Maximum Variation from Dimensioned Position: 6 mm.

3.04

CLEANING

A.

Comply with Section 01 77 00.

B.

Clean exposed surfaces of ceilings, including trim, edge moldings, and suspension members;
comply with manufacturer's instructions for cleaning and touch-up of minor finish damage.
Remove and replace work which cannot be successfully cleaned and repaired to permanently
eliminate evidence of damage.

END OF SECTION