Sei sulla pagina 1di 2

FINAL TEST Document No.

: QF/TR/QAD
Issue No. : 001 Format No: 006
Department : Quality Assurance Issue Date : OCT 09 Page :1 of 1
DATE PCN NO. CUSTOMER :

KVA HV LV HV CURRENT LV CURRENVECTOR TAPPING Conductor


25 11000 433 1.31 33.34 Dyn11 NA Aluminium
1 Measurement of Voltage Ratio & Vector Group 9 225

Sr. No. Tap No. Specified U phase V phase W phase Average Difference %
1 N 44.00 44.00 44.01 44.03 44.01 0.027
2 Measurement of Winding Resistance Ambient Temperature 28 deg C
LV Resi. (mohms) HV Resistance ( ohms)
Tap No.
2u-2n 2v-2n 2w-2n 1U-1V 1V-1W 1W-1U
N 54.47 54.88 56.65 117.51 112.920 113.8
Average LV resi. per phase at principal Tap amb temp 55.333 mohms
Average HV resi. per phase at principal Tap amb temp 172.115 ohms
Average LV resi. per phase at principal Tap 75 deg temp 65.613 mohms
Average HV resi. per phase at principal Tap 75 deg temp 204.089 ohms
3 Measurement of Insulation Resistance at 2500 volts Gohm
HV / LV LV/ E HV / E
9.49 14.3 13.8
4 Measurement of No Load Loss & magnetising current HV OPEN
Tap N Meas. Freq 51.27 Corr. Factor 0.96300 Power 50 Hz 90.737
Phase Voltage Phase Current Phase Watt Rated Loss 90.57
2u-2n 243.61 2u 0.8385 W1 9.12
2v-2n 262.63 2v 0.6002 W2 20.63
2w-2n 254.62 2n 0.7849 W3 64.47
AVG 250.45 AVG 0.741 AVG 94.22
5 Induced Over voltage Test Withstood Two times the rated voltage on LV side at 150 Hz for 40 Sec.
6 Separate Souce on HV=28 KV & LV = 3 KV for one minute withstood successfully
7 Measurement of Load Loss & %age Impedance LV SHORTED TAP N
PHASE VOLTAGE PHASE CURRENT PHASE WATT Temp. 21
1U-1N 236.37 1U 1.3 W1 151.63
1V-1N 252.05 1V 1.3 W2 165.75
1W-1N 245.03 1W 1.3 W3 148.94
AVG 244.5 AVG 1.300 AVG 466.32
CALCULATION : >>
At Rated amp Corr. Load Losses in watts L RC = ((Rated amp )/(Average Test CurrentxCTMF))2xLTC #REF!
LRC 475.11 watts
HV Copper Loss at amb Temp I RH 2
288.16 watts
LV Copper Loss at amb Temp I2RL 179.36 watts
Total Copper Losses TC at amb temp 467.52 watts
Stray Losses at amb LRC - TC 7.59 watts
Total Copper Losses TC at 75 deg temp 570.15 watts
Stray Loss at 75 deg C 6.22 watts
Load Losses at 75 deg C 576.37 watts
At Test Amp Imped. Voltage measured VTC 423.45 volts
At Rated Amp Imped. Voltage meas. VRC= VTC x ((Rated amp)/(Average Test ampxCTMF))
VRC = 427.42 volts
% Resistance at amb Temp 1.90 Sr. No. Particular Guarnteed Measured
% Impedance at amb Temp 3.89 1 No Load Loss 100 91
% Reactance at amb Temp 3.39 2 Load Loss 685 576
% Resistance at 75 deg C 2.31 3 Total Loss 785 667
% Impedance at 75 deg C 4.10 4 % Z at 75oC 4.50% 4.10
TESTED BY: WITNESSED BY: