Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 2

Project Information
Project Title:
Designed By:
Date:
Comment:
Client Name:
Address:
City:
Phone:
Fax:
Comment:

M:\Refrigercion\oficinas-1.CHV

Ofiicinas
Grupo4
sbado, 02 de mayo de 2015

Company Name:
Representative:
Address:
City:
Phone:
Fax:
Comment:

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 3

General Project Data Input


General Project Information
Project file name:
Project title:
Designed by:
Project date:
Project location:

M:\Refrigercion\oficinas-1.CHV
Ofiicinas
Grupo4
sbado, 02 de mayo de 2015
Lima, Peru

Barometric pressure:
Altitude:
Latitude:
Mean daily temperature range:
Starting & ending time for HVAC load calculations:
Number of unique zones in this project:

29.875
43
12
32.7
8am - 7pm
5

in.Hg.
feet
Degrees
Degrees

Building Default Values


Calculations performed:
Lighting requirements:
Equipment requirements:
People sensible load multiplier:
People latent load multiplier:
Zone sensible safety factor:
Zone latent safety factor:
Zone heating safety factor:
People diversity factor:
Lighting profile number:
Equipment profile number:
People profile number:
Building default ceiling height:
Building default wall height:

Cooling loads only


1.50
1.00
250
200
10
10
10
100
1
1
1
10.8
10.8

Watts per square foot


Watts per square foot
Btuh per person
Btuh per person
%
%
%
%

feet
feet

Internal Operating Load Profiles (C = 100)


1
2
3
4
5
6
7
8
9
10

hr
1
C
C
C
C
C
C
C
C
C
C

hr
2
C
C
C
C
C
C
C
C
C
C

hr
3
C
C
C
C
C
C
C
C
C
C

hr
4
C
C
C
C
C
C
C
C
C
C

hr
5
C
C
C
C
C
C
C
C
C
C

M:\Refrigercion\oficinas-1.CHV

hr
6
C
C
C
C
C
C
C
C
C
C

hr
7
C
C
C
C
C
C
C
C
C
C

hr
8
C
C
C
C
C
C
C
C
C
C

hr
9
C
C
C
C
C
C
C
C
C
C

hr
10
C
C
C
C
C
C
C
C
C
C

hr
11
C
C
C
C
C
C
C
C
C
C

hr
12
C
C
C
C
C
C
C
C
C
C

hr
13
C
C
C
C
C
C
C
C
C
C

hr
14
C
C
C
C
C
C
C
C
C
C

hr
15
90
C
C
C
C
C
C
C
C
C

hr
16
90
C
C
C
C
C
C
C
C
C

hr
17
70
C
C
C
C
C
C
C
C
C

hr
18
60
C
C
C
C
C
C
C
C
C

hr
19
50
C
C
C
C
C
C
C
C
C

hr
20
C
C
C
C
C
C
C
C
C
C

hr
21
C
C
C
C
C
C
C
C
C
C

hr
22
C
C
C
C
C
C
C
C
C
C

hr
23
C
C
C
C
C
C
C
C
C
C

hr
24
C
C
C
C
C
C
C
C
C
C

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 4

General Project Data Input (cont'd)


Building-Level Design Conditions
Design
Month

Outdoor
Dry Bulb

Outdoor
Wet Bulb

Indoor
Rel.Hum

Indoor
Dry Bulb

Grains
Diff

In/Outdoor
Correction

86
87
88
85
82
80
77
75
75
74
78
83
57

76
76
76
75
72
71
68
67
67
66
69
73

55%
55%
55%
55%
55%
55%
55%
55%
55%
55%
55%
55%

72
72
72
72
72
72
72
72
72
72
72
72
72

53.64
54.35
51.51
50.08
39.42
35.84
21.93
21.05
21.21
16.47
26.03
40.67

-9
-8
-8
-11
-13
-15
-18
-20
-20
-22
-18
-13

January
February
March
April
May
June
July
August
September
October
November
December
Winter

Master Roofs
Roof
No.

ASHRAE
Roof#

Roof
U-Fac

Dark
Color

Susp.
Ceil

0.306

No

No

ASHRAE
Group

Wall
U-Fac

Wall
Color

C
C
C
C
C
C
C
C
C
C

0.410
0.306
0.439
0.499
0.410
0.410
0.417
0.410
0.499
0.306

L
L
L
L
L
L
L
L
L
L

Partition
U-Factor

Cool
T-D

Heat
T-D

0.300
0.439
0.499
0.410
0.410
0.499
0.300

7
7
7
7
7
7
7

7
7
7
7
7
7
7

Master Walls
Wall
No.
1
2
3
4
5
6
7
8
9
10

Master Partitions
Partition
No.
1
2
3
4
5
6
7

Master Glass
Glass
No.
1
2
3
4
5

Summer
U-Factor

Winter
U-Factor

Glass
Shd.Coef.

Interior
Shading

Interior
Shd.Coef

0.640
0.640
0.640
0.640
0.640

0.640
0.640
0.640
0.640
0.640

1.000
1.000
1.000
1.000
1.000

1
1
1
1
1

0.640
0.640
0.640
0.640
0.640

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 5

Air Handler Input


Air Handler Number 1 Input Data
Name:
Terminal type:
Method for CV
Supply fan type:
Calculations performed:
Excess supply air:
Occurrences:
People profile number:
Lighting profile number:
Equipment profile number:
Exhaust may not exceed supply air:
Leaving heating coil temp (deg.F):
Leaving cooling coil RH (%):
Cooling coil CFM
Misc. Btuh gain - supply side:
Misc. Btuh gain - return side:
Combined fan & motor efficiency:
Static pressure across fan (in.wg.):
Summer supply duct temp rise (deg.F):
Summer return duct temp rise (deg.F):
Winter supply duct temp drop (deg.F):
Winter return duct temp drop (deg.F):
Chilled water temp difference (deg.F):
Hot water temp difference (deg.F):
Cooling ventilation:
Cooling infiltration:
Heating ventilation:
Heating infiltration:
Pretreated outside air:
Pretreated air Summer DB (deg.F):
Pretreated air Summer WB (deg.F):
Pretreated air Winter DB (deg.F):
Design
Month

Oficina 701
Constant Volume
Sum of Peaks
Blow-thru fan
Cooling loads only
Reserve
1
1
1
1
No
95.0
55
0
0
0
70
0.00
1.000
0.250
2.000
1.000
10.000
10.000
20 CFM/Pr
0 Direct
20 CFM/Pr
0 Direct
none
0
0
0

Outdoor
Dry Bulb

Outdoor
Wet Bulb

Indoor
Rel.Hum

Indoor
Dry Bulb

Grains
Diff

In/Outdoor
Correction

86
87
88
85
82
80
77
75
75
74
78
83
57

76
76
76
75
72
71
68
67
67
66
69
73

55%
55%
55%
55%
55%
55%
55%
55%
55%
55%
55%
55%

72
72
72
72
72
72
72
72
72
72
72
72
72

54.52
55.23
52.39
50.96
40.30
36.72
22.80
21.93
22.09
17.34
26.91
41.55

-9
-8
-7
-10
-13
-15
-18
-20
-20
-21
-17
-12

January
February
March
April
May
June
July
August
September
October
November
December
Winter

Air Handler Number 2 Input Data


Name:
Terminal type:
Method for CV
Supply fan type:
Calculations performed:
Excess supply air:
M:\Refrigercion\oficinas-1.CHV

Oficina 702
Constant Volume
Sum of Peaks
Blow-thru fan
Cooling loads only
Reserve
viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 6

Air Handler Input (cont'd)


Air Handler Number 2 Input Data
Occurrences:
People profile number:
Lighting profile number:
Equipment profile number:
Exhaust may not exceed supply air:
Leaving heating coil temp (deg.F):
Leaving cooling coil RH (%):
Cooling coil CFM
Misc. Btuh gain - supply side:
Misc. Btuh gain - return side:
Combined fan & motor efficiency:
Static pressure across fan (in.wg.):
Summer supply duct temp rise (deg.F):
Summer return duct temp rise (deg.F):
Winter supply duct temp drop (deg.F):
Winter return duct temp drop (deg.F):
Chilled water temp difference (deg.F):
Hot water temp difference (deg.F):
Cooling ventilation:
Cooling infiltration:
Heating ventilation:
Heating infiltration:
Pretreated outside air:
Pretreated air Summer DB (deg.F):
Pretreated air Summer WB (deg.F):
Pretreated air Winter DB (deg.F):
Design
Month

1
1
1
1
No
95.0
55
0
0
0
70
0.00
1.000
0.250
2.000
1.000
10.000
10.000
20 CFM/Pr
0 Direct
20 CFM/Pr
0 Direct
none
0
0
0

Outdoor
Dry Bulb

Outdoor
Wet Bulb

Indoor
Rel.Hum

Indoor
Dry Bulb

Grains
Diff

In/Outdoor
Correction

86
87
88
85
82
80
77
75
75
74
78
83
57

76
76
76
75
72
71
68
67
67
66
69
73

55%
55%
55%
55%
55%
55%
55%
55%
55%
55%
55%
55%

72
72
72
72
72
72
72
72
72
72
72
72
72

54.52
55.23
52.39
50.96
40.30
36.72
22.80
21.93
22.09
17.34
26.91
41.55

-9
-8
-7
-10
-13
-15
-18
-20
-20
-21
-17
-12

January
February
March
April
May
June
July
August
September
October
November
December
Winter

Air Handler Number 3 Input Data


Name:
Terminal type:
Method for CV
Supply fan type:
Calculations performed:
Excess supply air:
Occurrences:
People profile number:
Lighting profile number:
Equipment profile number:
Exhaust may not exceed supply air:
Leaving heating coil temp (deg.F):
M:\Refrigercion\oficinas-1.CHV

Oficina 703
Constant Volume
Sum of Peaks
Blow-thru fan
Cooling loads only
Reserve
1
1
1
1
No
95.0
viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 7

Air Handler Input (cont'd)


Air Handler Number 3 Input Data
Leaving cooling coil RH (%):
Cooling coil CFM
Misc. Btuh gain - supply side:
Misc. Btuh gain - return side:
Combined fan & motor efficiency:
Static pressure across fan (in.wg.):
Summer supply duct temp rise (deg.F):
Summer return duct temp rise (deg.F):
Winter supply duct temp drop (deg.F):
Winter return duct temp drop (deg.F):
Chilled water temp difference (deg.F):
Hot water temp difference (deg.F):
Cooling ventilation:
Cooling infiltration:
Heating ventilation:
Heating infiltration:
Pretreated outside air:
Pretreated air Summer DB (deg.F):
Pretreated air Summer WB (deg.F):
Pretreated air Winter DB (deg.F):
Design
Month

55
0
0
0
70
0.00
1.000
0.250
2.000
1.000
10.000
10.000
20 CFM/Pr
0 Direct
20 CFM/Pr
0 Direct
none
0
0
0

Outdoor
Dry Bulb

Outdoor
Wet Bulb

Indoor
Rel.Hum

Indoor
Dry Bulb

Grains
Diff

In/Outdoor
Correction

86
87
88
85
82
80
77
75
75
74
78
83
57

76
76
76
75
72
71
68
67
67
66
69
73

55%
55%
55%
55%
55%
55%
55%
55%
55%
55%
55%
55%

72
72
72
72
72
72
72
72
72
72
72
72
72

54.52
55.23
52.39
50.96
40.30
36.72
22.80
21.93
22.09
17.34
26.91
41.55

-9
-8
-7
-10
-13
-15
-18
-20
-20
-21
-17
-12

January
February
March
April
May
June
July
August
September
October
November
December
Winter

Air Handler Number 4 Input Data


Name:
Terminal type:
Method for CV
Supply fan type:
Calculations performed:
Excess supply air:
Occurrences:
People profile number:
Lighting profile number:
Equipment profile number:
Exhaust may not exceed supply air:
Leaving heating coil temp (deg.F):
Leaving cooling coil RH (%):
Cooling coil CFM
Misc. Btuh gain - supply side:
Misc. Btuh gain - return side:
Combined fan & motor efficiency:
Static pressure across fan (in.wg.):
M:\Refrigercion\oficinas-1.CHV

Oficina 704
Constant Volume
Sum of Peaks
Blow-thru fan
Cooling loads only
Reserve
1
1
1
1
No
95.0
55
0
0
0
70
0.00
viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 8

Air Handler Input (cont'd)


Air Handler Number 4 Input Data
Summer supply duct temp rise (deg.F):
Summer return duct temp rise (deg.F):
Winter supply duct temp drop (deg.F):
Winter return duct temp drop (deg.F):
Chilled water temp difference (deg.F):
Hot water temp difference (deg.F):
Cooling ventilation:
Cooling infiltration:
Heating ventilation:
Heating infiltration:
Pretreated outside air:
Pretreated air Summer DB (deg.F):
Pretreated air Summer WB (deg.F):
Pretreated air Winter DB (deg.F):
Design
Month

1.000
0.250
2.000
1.000
10.000
10.000
20 CFM/Pr
0 Direct
20 CFM/Pr
0 Direct
none
0
0
0

Outdoor
Dry Bulb

Outdoor
Wet Bulb

Indoor
Rel.Hum

Indoor
Dry Bulb

Grains
Diff

In/Outdoor
Correction

86
87
88
85
82
80
77
75
75
74
78
83
57

76
76
76
75
72
71
68
67
67
66
69
73

55%
55%
55%
55%
55%
55%
55%
55%
55%
55%
55%
55%

72
72
72
72
72
72
72
72
72
72
72
72
72

54.52
55.23
52.39
50.96
40.30
36.72
22.80
21.93
22.09
17.34
26.91
41.55

-9
-8
-7
-10
-13
-15
-18
-20
-20
-21
-17
-12

January
February
March
April
May
June
July
August
September
October
November
December
Winter

Air Handler Number 5 Input Data


Name:
Terminal type:
Method for CV
Supply fan type:
Calculations performed:
Excess supply air:
Occurrences:
People profile number:
Lighting profile number:
Equipment profile number:
Exhaust may not exceed supply air:
Leaving heating coil temp (deg.F):
Leaving cooling coil RH (%):
Cooling coil CFM
Misc. Btuh gain - supply side:
Misc. Btuh gain - return side:
Combined fan & motor efficiency:
Static pressure across fan (in.wg.):
Summer supply duct temp rise (deg.F):
Summer return duct temp rise (deg.F):
Winter supply duct temp drop (deg.F):
Winter return duct temp drop (deg.F):
Chilled water temp difference (deg.F):
Hot water temp difference (deg.F):
M:\Refrigercion\oficinas-1.CHV

Oficina 705
Constant Volume
Sum of Peaks
Blow-thru fan
Cooling loads only
Reserve
1
1
1
1
No
95.0
55
0
0
0
70
0.00
1.000
0.250
2.000
1.000
10.000
10.000
viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 9

Air Handler Input (cont'd)


Air Handler Number 5 Input Data
Cooling ventilation:
Cooling infiltration:
Heating ventilation:
Heating infiltration:
Pretreated outside air:
Pretreated air Summer DB (deg.F):
Pretreated air Summer WB (deg.F):
Pretreated air Winter DB (deg.F):
Design
Month

20 CFM/Pr
0 Direct
20 CFM/Pr
0 Direct
none
0
0
0

Outdoor
Dry Bulb

Outdoor
Wet Bulb

Indoor
Rel.Hum

Indoor
Dry Bulb

Grains
Diff

In/Outdoor
Correction

86
87
88
85
82
80
77
75
75
74
78
83
57

76
76
76
75
72
71
68
67
67
66
69
73

55%
55%
55%
55%
55%
55%
55%
55%
55%
55%
55%
55%

72
72
72
72
72
72
72
72
72
72
72
72
72

54.52
55.23
52.39
50.96
40.30
36.72
22.80
21.93
22.09
17.34
26.91
41.55

-9
-8
-7
-10
-13
-15
-18
-20
-20
-21
-17
-12

January
February
March
April
May
June
July
August
September
October
November
December
Winter

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 10

Zone Input
Zone 1: Oficina 701 (1969.08 sq.ft) (Group 0)
Air Handler number:
Zone length: (feet)
Lighting Watts:
Number of people in zone:
Lighting profile number:
Ceiling height (feet):
Sensible safety factor (%):
Sensible heat per person (Btuh):
Cooling ventilation method:
Cooling infiltration method:
Heating ventilation method:
Heating infiltration method:
Winter exhaust air CFM:
Minimum supply CFM:
Ceil. exposed to plenum (sq.ft):
Cooling loads only are calculated for this zone.
Roof

U-Factor

Dark

Length

Width

Area

Susp.Ceil

0.306

No

183.00

10.76

1,969.1

No

Type

U-Factor

Cool TD

Heat TD

Height

Width

Area

2
2

0.439
0.439

7.200
7.200

7.200
7.200

10.80
10.80

67.35
47.57

727.4
513.8

Type

ASHRAE#

U-Factor

Color

Height

Width

Area

Direction

1
1
1
1

C
C
C
C

0.410
0.410
0.410
0.410

L
L
L
L

10.80
10.80
10.80
10.80

54.19
5.54
8.39
31.40

585.3
59.8
90.6
339.1

SE
SW
E
SW

1
2
3
4
Glass
1
2
3
4

1
10.76
1,969
1
1
5
5
200
0.000
0.000
0.000
0.000
0
0
0

ASHRAE#

5
6
Wall

Zone occurrences:
Zone width (feet):
Equipment Watts:
People profile number:
Equipment profile number:
Heating safety factor (%):
Latent safety factor (%):
Latent heat per person (Btuh):
Cooling ventilation value:
Cooling infiltration value:
Heating ventilation value:
Heating infiltration value:
Summer exhaust air CFM:
Latent Btuh equipment load:
Exposed floor slab perimeter (ft):

Type

1
Part

1
183.00
2,954
20
1
11
5
250
Direct
Direct
Direct
Direct
0
0
1,969

Type

S.U-F.

Shd C.

Height

Width

Occur.

Area

Shade

Tilt

Ref

1
1
1
1

0.640
0.640
0.640
0.640

1.000
1.000
1.000
1.000

4.60
0.10
10.80
10.80

39.80
0.10
8.39
31.40

1
1
1
1

183.1
0.0
90.6
339.1

0
0
0
0

90
90
90
90

1
2
3
4

Zone 2: Oficina 702 (1969.08 sq.ft) (Group 0)


Air Handler number:
Zone length: (feet)
Lighting Watts:
Number of people in zone:
Lighting profile number:
Ceiling height (feet):
Sensible safety factor (%):
Sensible heat per person (Btuh):
Cooling ventilation method:
Cooling infiltration method:
Heating ventilation method:
Heating infiltration method:
Winter exhaust air CFM:
Minimum supply CFM:
Ceil. exposed to plenum (sq.ft):
Cooling loads only are calculated for this zone.
Roof

Type

ASHRAE#

M:\Refrigercion\oficinas-1.CHV

U-Factor

2
183.00
2,954
20
1
11
5
250
Direct
Direct
Direct
Direct
0
0
1,969

Zone occurrences:
Zone width (feet):
Equipment Watts:
People profile number:
Equipment profile number:
Heating safety factor (%):
Latent safety factor (%):
Latent heat per person (Btuh):
Cooling ventilation value:
Cooling infiltration value:
Heating ventilation value:
Heating infiltration value:
Summer exhaust air CFM:
Latent Btuh equipment load:
Exposed floor slab perimeter (ft):

Dark

Length

Width

1
10.76
1,969
1
1
5
5
200
0.000
0.000
0.000
0.000
0
0
0

Area

Susp.Ceil

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 11

Zone Input (cont'd)


Zone 2: Oficina 702 (1969.08 sq.ft) (Group 0)
1
Part

Type

U-Factor

Cool TD

Heat TD

Height

Width

Area

1
1

0.3
0.3

7.200
7.200

7.200
7.200

10.76
10.76

35.16
116.20

378.3
1,250.3

2
3

0.306

No

191.14

10.76

2,056.7

No

Zone 3: Oficina 703 (1969.08 sq.ft) (Group 0)


Air Handler number:
Zone length: (feet)
Lighting Watts:
Number of people in zone:
Lighting profile number:
Ceiling height (feet):
Sensible safety factor (%):
Sensible heat per person (Btuh):
Cooling ventilation method:
Cooling infiltration method:
Heating ventilation method:
Heating infiltration method:
Winter exhaust air CFM:
Minimum supply CFM:
Ceil. exposed to plenum (sq.ft):
Cooling loads only are calculated for this zone.
Roof
1
Part

3
183.00
2,954
20
1
11
5
250
Direct
Direct
Direct
Direct
0
0
1,969

Zone occurrences:
Zone width (feet):
Equipment Watts:
People profile number:
Equipment profile number:
Heating safety factor (%):
Latent safety factor (%):
Latent heat per person (Btuh):
Cooling ventilation value:
Cooling infiltration value:
Heating ventilation value:
Heating infiltration value:
Summer exhaust air CFM:
Latent Btuh equipment load:
Exposed floor slab perimeter (ft):

1
10.76
1,969
1
1
5
5
200
0.000
0.000
0.000
0.000
0
0
0

Type

ASHRAE#

U-Factor

Dark

Length

Width

Area

Susp.Ceil

0.306

No

220.44

10.76

2,371.9

No

Type

U-Factor

Cool TD

Heat TD

Height

Width

Area

0.3

7.200

7.200

10.76

96.69

1,040.4

Zone 4: Oficina 704 (1969.08 sq.ft) (Group 0)


Air Handler number:
Zone length: (feet)
Lighting Watts:
Number of people in zone:
Lighting profile number:
Ceiling height (feet):
Sensible safety factor (%):
Sensible heat per person (Btuh):
Cooling ventilation method:
Cooling infiltration method:
Heating ventilation method:
Heating infiltration method:
Winter exhaust air CFM:
Minimum supply CFM:
Ceil. exposed to plenum (sq.ft):
Cooling loads only are calculated for this zone.
Roof
1
Wall
3

4
183.00
2,954
20
1
35
5
250
Direct
Direct
Direct
Direct
0
0
1,969

Zone occurrences:
Zone width (feet):
Equipment Watts:
People profile number:
Equipment profile number:
Heating safety factor (%):
Latent safety factor (%):
Latent heat per person (Btuh):
Cooling ventilation value:
Cooling infiltration value:
Heating ventilation value:
Heating infiltration value:
Summer exhaust air CFM:
Latent Btuh equipment load:
Exposed floor slab perimeter (ft):

1
10.76
1,969
1
1
5
5
200
0.000
0.000
0.000
0.000
0
0
0

Type

ASHRAE#

U-Factor

Dark

Length

Width

Area

Susp.Ceil

0.306

No

245.30

10.76

2,639.4

No

Type

ASHRAE#

U-Factor

Color

Height

Width

Area

Direction

0.410

10.76

12.11

130.3

NW

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 12

Zone Input (cont'd)


Zone 5: Oficina 705 (695.508 sq.ft) (Group 0)
Air Handler number:
Zone length: (feet)
Lighting Watts:
Number of people in zone:
Lighting profile number:
Ceiling height (feet):
Sensible safety factor (%):
Sensible heat per person (Btuh):
Cooling ventilation method:
Cooling infiltration method:
Heating ventilation method:
Heating infiltration method:
Winter exhaust air CFM:
Minimum supply CFM:
Ceil. exposed to plenum (sq.ft):
Cooling loads only are calculated for this zone.
Roof

1
3.30
696
1
1
5
5
200
0.000
0.000
0.000
0.000
0
0
0

ASHRAE#

U-Factor

Dark

Length

Width

Area

Susp.Ceil

0.306

No

210.76

10.76

2,267.8

No

Type

ASHRAE#

U-Factor

Color

Height

Width

Area

Direction

0.410

10.76

48.04

516.9

SE

2
Glass

Zone occurrences:
Zone width (feet):
Equipment Watts:
People profile number:
Equipment profile number:
Heating safety factor (%):
Latent safety factor (%):
Latent heat per person (Btuh):
Cooling ventilation value:
Cooling infiltration value:
Heating ventilation value:
Heating infiltration value:
Summer exhaust air CFM:
Latent Btuh equipment load:
Exposed floor slab perimeter (ft):

Type

1
Wall

5
210.76
1,043
7
1
35
5
250
Direct
Direct
Direct
Direct
0
0
696

Type

S.U-F.

Shd C.

Height

Width

Occur.

Area

Shade

Tilt

Ref

0.640

1.000

10.76

20.46

220.1

90

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 13

Plenum Input
Plenum Number 1 Input Data
Air Handler Number:
Plenum active:
Percent of light load to zones:
Floor u-factor (Btuh/Sq.ft-F):
Watts of equipment:
Summer plenum-zone temp. difference (deg.F):
Winter plenum-zone temp. difference (deg.F):

1
No
100
0.000
0
0
0

Plenum Number 2 Input Data


Air Handler Number:
Plenum active:
Percent of light load to zones:
Floor u-factor (Btuh/Sq.ft-F):
Watts of equipment:
Summer plenum-zone temp. difference (deg.F):
Winter plenum-zone temp. difference (deg.F):

2
No
100
0.000
0
0
0

Plenum Number 3 Input Data


Air Handler Number:
Plenum active:
Percent of light load to zones:
Floor u-factor (Btuh/Sq.ft-F):
Watts of equipment:
Summer plenum-zone temp. difference (deg.F):
Winter plenum-zone temp. difference (deg.F):

3
No
100
0.000
0
0
0

Plenum Number 4 Input Data


Air Handler Number:
Plenum active:
Percent of light load to zones:
Floor u-factor (Btuh/Sq.ft-F):
Watts of equipment:
Summer plenum-zone temp. difference (deg.F):
Winter plenum-zone temp. difference (deg.F):

4
No
100
0.000
0
0
0

Plenum Number 5 Input Data


Air Handler Number:
Plenum active:
Percent of light load to zones:
Floor u-factor (Btuh/Sq.ft-F):
Watts of equipment:
Summer plenum-zone temp. difference (deg.F):
Winter plenum-zone temp. difference (deg.F):

M:\Refrigercion\oficinas-1.CHV

5
No
100
0.000
0
0
0

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 14

Building Envelope Report


Envelope Report Using Summer U-Factors
Material
Gross
Glass
Types
Area
Area

Net
Area

-UFactor

Area x
U-Factor

Average
U-Factor

Roof
Tot.Roof

11,304.9
11,304.9

0.0
0.0

11,304.9
11,304.9

0.306
N/A

3,459.295
3,459.295

0.306
0.306

Wall
Tot.Wall

1,722.0
1,722.0

833.0
833.0

889.1
889.1

0.410
N/A

364.514
364.514

0.410
0.410

Glass
Tot.Glass

833.0
833.0

N/A
N/A

833.0
833.0

0.640
N/A

533.102
533.102

0.640
0.640

4,356.911

0.334

Totals

Wall
Direction

13,026.9

Wall
Area

Glass
Area

Wall Net
Area

Wall Avg
U-Factor

Glass Avg
U-Factor

Glass Avg
Shd.Coef

N
NE
E
SE
S
SW
W
NW

0.0
0.0
90.6
1,102.2
0.0
399.0
0.0
130.3

0.0
0.0
90.6
403.2
0.0
339.1
0.0
0.0

0.0
0.0
0.0
698.9
0.0
59.8
0.0
130.3

0.000
0.000
0.000
0.410
0.000
0.410
0.000
0.410

0.000
0.000
0.640
0.640
0.000
0.640
0.000
0.000

0.000
0.000
0.640
0.640
0.000
0.640
0.000
0.000

Totals

1,722.0

833.0

889.1

0.410

0.640

0.640

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 15

Building Summary Loads


Building peaks in February at 4pm.

Bldg Load
Descriptions

Area
Quan

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

Roof
Wall
Glass
Floor Slab

11,305
889
833
0

0
0
0
0

0.00
0.00
0.00
0.00

0
0
0
0

38,502
3,496
55,323
0

38,502
3,496
55,323
0

18.07
1.64
25.97
0.00

0.00

97,322

97,322

45.68

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

0
0
16,201
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

41,459
27,640
20,251
10,172
0
0
0
0
0
0
0
0
0
0
0
0
0
0

41,459
27,640
36,452
10,172
0
0
0
0
0
0
0
0
0
0
0
0
0
0

19.46
12.97
17.11
4.77
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

0.00

16,201

196,844

213,045

100.00

Skin Loads
Lighting
Equipment
People
Partition
Cool. Pret.
Heat. Pret.
Cool. Vent.
Heat. Vent.
Cool. Infil.
Heat. Infil.
Draw-Thru Fan
Blow-Thru Fan
Reserve Cap.
Reheat Cap.
Supply Duct
Return Duct
Misc. Supply
Misc. Return

12,858
8,572
86
3,910
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Building Totals

Building
Summary

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

Ventilation
Infiltration
Pretreated Air
Zone Loads
Plenum Loads
Fan & Duct Loads

0
0
0
0
0
0

0.00
0.00
0.00
0.00
0.00
0.00

0
0
0
16,201
0
0

0
0
0
196,844
0
0

0
0
0
213,045
0
0

0.00
0.00
0.00
100.00
0.00
0.00

Building Totals

0.00

16,201

196,844

213,045

100.00

Check Figures
Total Building Supply Air (based on a 0 TD):
Total Building Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

M:\Refrigercion\oficinas-1.CHV

0 CFM
0 CFM
8,572
0.0000
482.8185
0.0021

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft

0 Btuh
17.75 Tons

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 16

Building Summary Loads (G)


Building peaks in February at 4pm.

Bldg Load
Descriptions

Area
Quan

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

Roof
Wall
Glass
Floor Slab

11,305
889
833
0

0
0
0
0

0.00
0.00
0.00
0.00

0
0
0
0

38,502
3,496
55,323
0

38,502
3,496
55,323
0

18.07
1.64
25.97
0.00

0.00

97,322

97,322

45.68

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

0
0
16,201
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

41,459
27,640
20,251
10,172
0
0
0
0
0
0
0
0
0
0
0
0
0
0

41,459
27,640
36,452
10,172
0
0
0
0
0
0
0
0
0
0
0
0
0
0

19.46
12.97
17.11
4.77
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

0.00

16,201

196,844

213,045

100.00

Skin Loads
Lighting
Equipment
People
Partition
Cool. Pret.
Heat. Pret.
Cool. Vent.
Heat. Vent.
Cool. Infil.
Heat. Infil.
Draw-Thru Fan
Blow-Thru Fan
Reserve Cap.
Reheat Cap.
Supply Duct
Return Duct
Misc. Supply
Misc. Return

12,858
8,572
86
3,910
0
0
0
0
0
0
0
0
0
0
0
0
0
0

Building Totals

Building
Summary

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

Ventilation
Infiltration
Pretreated Air
Zone Loads
Plenum Loads
Fan & Duct Loads

0
0
0
0
0
0

0.00
0.00
0.00
0.00
0.00
0.00

0
0
0
16,201
0
0

0
0
0
196,844
0
0

0
0
0
213,045
0
0

0.00
0.00
0.00
100.00
0.00
0.00

Building Totals

0.00

16,201

196,844

213,045

100.00

Check Figures
Total Building Supply Air (based on a 0 TD):
Total Building Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

M:\Refrigercion\oficinas-1.CHV

0 CFM
0 CFM
8,572
0.0000
482.8185
0.0021

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft

0 Btuh
17.75 Tons

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 17

Air Handler #1 - Oficina 701 - Summary Loads


Zn
No

Description
Peak Time

Oficina 701
3pm January

Area
People
Volume

Htg.Loss
Htg.CFM
CFM/Sqft

Sen.Gain
Clg.CFM
CFM/Sqft

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.CFM
Act.CFM

Clg.O.A.
Req.CFM
Act.CFM

1,969
0
83,066
3,722
None
20
0
0
0
0
21,266
0.00
0.00
0
0
Runout duct size: 0in. h x 0in. w, Diffusers: 1, CFM/runout: 0, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft
Zone Peak Totals:
1,969
0
83,066
3,722
Total Zones: 1
20
0
0
0
Unique Zones: 1
21,266
0.00
0.00
0
Main trunk duct size: 0in. h x 0in. w, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft

M:\Refrigercion\oficinas-1.CHV

0
0

None
0
0

0
0

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 18

Air Handler #1 - Oficina 701 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

Oficina 701 Constant Volume - Sum of Peaks


Blow-Thru with program estimated horsepower of 0.00 HP
70% motor and fan efficiency with 0 in. water across the fan
0.96
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:

3pm in January.
86 DB, 76 WB, 118.03 grains

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Btuh
Btuh
Btuh
Btuh
Btuh
Btuh

0 Btuh

Heating Supply Air: 0 / (.998 X 1.08 X 0) =


Winter Vent Outside Air (0.0% of supply) =

0 CFM
0 CFM

Zone space sensible gain:


83,066
Infiltration sensible gain:
0
Draw-thru fan sensible gain:
0
Supply duct sensible gain:
0
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

Btuh
Btuh
Btuh
Btuh
Btuh
83,066 Btuh

Cooling Supply Air: 83,066 / (.998 X 1.1 X 0) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
Return plenum sensible gain:
Outside air sensible gain:
Blow-thru fan sensible gain:
Total sensible gain on return side of coil:
Total sensible gain on air handling system:

0 CFM
0 CFM

0
0
0
0

0 CFM
0 CFM
Btuh
Btuh
Btuh
Btuh

0 CFM
0 Btuh
83,066 Btuh

Zone space latent gain:


3,722 Btuh
Infiltration latent gain:
0 Btuh
Outside air latent gain:
0 Btuh
Total latent gain on air handling system:
Total system sensible and latent gain:

3,722 Btuh
86,787 Btuh

Check Figures
Total Air Handler Supply Air (based on a 0 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

M:\Refrigercion\oficinas-1.CHV

0 CFM
0 CFM
1,969
0.0000
272.2623
0.0037

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft

0 Btuh
7.23 Tons

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 19

Air Handler #2 - Oficina 702 - Summary Loads


Zn
No

Description
Peak Time

Oficina 702
4pm March

Area
People
Volume

Htg.Loss
Htg.CFM
CFM/Sqft

Sen.Gain
Clg.CFM
CFM/Sqft

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.CFM
Act.CFM

Clg.O.A.
Req.CFM
Act.CFM

1,969
0
32,016
3,722
None
20
0
0
0
0
21,266
0.00
0.00
0
0
Runout duct size: 0in. h x 0in. w, Diffusers: 1, CFM/runout: 0, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft
Zone Peak Totals:
1,969
0
32,016
3,722
Total Zones: 1
20
0
0
0
Unique Zones: 1
21,266
0.00
0.00
0
Main trunk duct size: 0in. h x 0in. w, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft

M:\Refrigercion\oficinas-1.CHV

0
0

None
0
0

0
0

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 20

Air Handler #2 - Oficina 702 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

Oficina 702 Constant Volume - Sum of Peaks


Blow-Thru with program estimated horsepower of 0.00 HP
70% motor and fan efficiency with 0 in. water across the fan
0.90
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:

4pm in March.
87 DB, 76 WB, 117.51 grains

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Btuh
Btuh
Btuh
Btuh
Btuh
Btuh

0 Btuh

Heating Supply Air: 0 / (.998 X 1.08 X 0) =


Winter Vent Outside Air (0.0% of supply) =

0 CFM
0 CFM

Zone space sensible gain:


32,016
Infiltration sensible gain:
0
Draw-thru fan sensible gain:
0
Supply duct sensible gain:
0
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

Btuh
Btuh
Btuh
Btuh
Btuh
32,016 Btuh

Cooling Supply Air: 32,016 / (.998 X 1.1 X 0) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
Return plenum sensible gain:
Outside air sensible gain:
Blow-thru fan sensible gain:
Total sensible gain on return side of coil:
Total sensible gain on air handling system:

0 CFM
0 CFM

0
0
0
0

0 CFM
0 CFM
Btuh
Btuh
Btuh
Btuh

0 CFM
0 Btuh
32,016 Btuh

Zone space latent gain:


3,722 Btuh
Infiltration latent gain:
0 Btuh
Outside air latent gain:
0 Btuh
Total latent gain on air handling system:
Total system sensible and latent gain:

3,722 Btuh
35,738 Btuh

Check Figures
Total Air Handler Supply Air (based on a 0 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

M:\Refrigercion\oficinas-1.CHV

0 CFM
0 CFM
1,969
0.0000
661.1739
0.0015

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft

0 Btuh
2.98 Tons

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 21

Air Handler #3 - Oficina 703 - Summary Loads


Zn
No

Description
Peak Time

Oficina 703
4pm March

Area
People
Volume

Htg.Loss
Htg.CFM
CFM/Sqft

Sen.Gain
Clg.CFM
CFM/Sqft

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.CFM
Act.CFM

Clg.O.A.
Req.CFM
Act.CFM

1,969
0
31,877
3,722
None
20
0
0
0
0
21,266
0.00
0.00
0
0
Runout duct size: 0in. h x 0in. w, Diffusers: 1, CFM/runout: 0, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft
Zone Peak Totals:
1,969
0
31,877
3,722
Total Zones: 1
20
0
0
0
Unique Zones: 1
21,266
0.00
0.00
0
Main trunk duct size: 0in. h x 0in. w, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft

M:\Refrigercion\oficinas-1.CHV

0
0

None
0
0

0
0

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 22

Air Handler #3 - Oficina 703 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

Oficina 703 Constant Volume - Sum of Peaks


Blow-Thru with program estimated horsepower of 0.00 HP
70% motor and fan efficiency with 0 in. water across the fan
0.90
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:

4pm in March.
87 DB, 76 WB, 117.51 grains

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Btuh
Btuh
Btuh
Btuh
Btuh
Btuh

0 Btuh

Heating Supply Air: 0 / (.998 X 1.08 X 0) =


Winter Vent Outside Air (0.0% of supply) =

0 CFM
0 CFM

Zone space sensible gain:


31,877
Infiltration sensible gain:
0
Draw-thru fan sensible gain:
0
Supply duct sensible gain:
0
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

Btuh
Btuh
Btuh
Btuh
Btuh
31,877 Btuh

Cooling Supply Air: 31,877 / (.998 X 1.1 X 0) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
Return plenum sensible gain:
Outside air sensible gain:
Blow-thru fan sensible gain:
Total sensible gain on return side of coil:
Total sensible gain on air handling system:

0 CFM
0 CFM

0
0
0
0

0 CFM
0 CFM
Btuh
Btuh
Btuh
Btuh

0 CFM
0 Btuh
31,877 Btuh

Zone space latent gain:


3,722 Btuh
Infiltration latent gain:
0 Btuh
Outside air latent gain:
0 Btuh
Total latent gain on air handling system:
Total system sensible and latent gain:

3,722 Btuh
35,599 Btuh

Check Figures
Total Air Handler Supply Air (based on a 0 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

M:\Refrigercion\oficinas-1.CHV

0 CFM
0 CFM
1,969
0.0000
663.7530
0.0015

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft

0 Btuh
2.97 Tons

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 23

Air Handler #4 - Oficina 704 - Summary Loads


Zn
No

Description
Peak Time

Oficina 704
4pm March

Area
People
Volume

Htg.Loss
Htg.CFM
CFM/Sqft

Sen.Gain
Clg.CFM
CFM/Sqft

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.CFM
Act.CFM

Clg.O.A.
Req.CFM
Act.CFM

1,969
0
30,533
3,722
None
20
0
0
0
0
69,489
0.00
0.00
0
0
Runout duct size: 0in. h x 0in. w, Diffusers: 1, CFM/runout: 0, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft
Zone Peak Totals:
1,969
0
30,533
3,722
Total Zones: 1
20
0
0
0
Unique Zones: 1
69,489
0.00
0.00
0
Main trunk duct size: 0in. h x 0in. w, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft

M:\Refrigercion\oficinas-1.CHV

0
0

None
0
0

0
0

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 24

Air Handler #4 - Oficina 704 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

Oficina 704 Constant Volume - Sum of Peaks


Blow-Thru with program estimated horsepower of 0.00 HP
70% motor and fan efficiency with 0 in. water across the fan
0.89
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:

4pm in March.
87 DB, 76 WB, 117.51 grains

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Btuh
Btuh
Btuh
Btuh
Btuh
Btuh

0 Btuh

Heating Supply Air: 0 / (.998 X 1.08 X 0) =


Winter Vent Outside Air (0.0% of supply) =

0 CFM
0 CFM

Zone space sensible gain:


30,533
Infiltration sensible gain:
0
Draw-thru fan sensible gain:
0
Supply duct sensible gain:
0
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

Btuh
Btuh
Btuh
Btuh
Btuh
30,533 Btuh

Cooling Supply Air: 30,533 / (.998 X 1.1 X 0) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
Return plenum sensible gain:
Outside air sensible gain:
Blow-thru fan sensible gain:
Total sensible gain on return side of coil:
Total sensible gain on air handling system:

0 CFM
0 CFM

0
0
0
0

0 CFM
0 CFM
Btuh
Btuh
Btuh
Btuh

0 CFM
0 Btuh
30,533 Btuh

Zone space latent gain:


3,722 Btuh
Infiltration latent gain:
0 Btuh
Outside air latent gain:
0 Btuh
Total latent gain on air handling system:
Total system sensible and latent gain:

3,722 Btuh
34,255 Btuh

Check Figures
Total Air Handler Supply Air (based on a 0 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

M:\Refrigercion\oficinas-1.CHV

0 CFM
0 CFM
1,969
0.0000
689.7960
0.0014

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft

0 Btuh
2.85 Tons

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 25

Air Handler #5 - Oficina 705 - Summary Loads


Zn
No

Description
Peak Time

Oficina 705
9am January

Area
People
Volume

Htg.Loss
Htg.CFM
CFM/Sqft

Sen.Gain
Clg.CFM
CFM/Sqft

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.CFM
Act.CFM

Clg.O.A.
Req.CFM
Act.CFM

696
0
28,000
1,461
None
7
0
0
0
0
24,544
0.00
0.00
0
0
Runout duct size: 0in. h x 0in. w, Diffusers: 1, CFM/runout: 0, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft
Zone Peak Totals:
696
0
28,000
1,461
Total Zones: 1
7
0
0
0
Unique Zones: 1
24,544
0.00
0.00
0
Main trunk duct size: 0in. h x 0in. w, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft

M:\Refrigercion\oficinas-1.CHV

0
0

None
0
0

0
0

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 26

Air Handler #5 - Oficina 705 - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

Oficina 705 Constant Volume - Sum of Peaks


Blow-Thru with program estimated horsepower of 0.00 HP
70% motor and fan efficiency with 0 in. water across the fan
0.95
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:

9am in January.
63 DB, 62 WB, 81.54 grains

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Btuh
Btuh
Btuh
Btuh
Btuh
Btuh

0 Btuh

Heating Supply Air: 0 / (.998 X 1.08 X 0) =


Winter Vent Outside Air (0.0% of supply) =

0 CFM
0 CFM

Zone space sensible gain:


28,000
Infiltration sensible gain:
0
Draw-thru fan sensible gain:
0
Supply duct sensible gain:
0
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

Btuh
Btuh
Btuh
Btuh
Btuh
28,000 Btuh

Cooling Supply Air: 28,000 / (.998 X 1.1 X 0) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
Return plenum sensible gain:
Outside air sensible gain:
Blow-thru fan sensible gain:
Total sensible gain on return side of coil:
Total sensible gain on air handling system:

0 CFM
0 CFM

0
0
0
0

0 CFM
0 CFM
Btuh
Btuh
Btuh
Btuh

0 CFM
0 Btuh
28,000 Btuh

Zone space latent gain:


1,461 Btuh
Infiltration latent gain:
0 Btuh
Outside air latent gain:
0 Btuh
Total latent gain on air handling system:
Total system sensible and latent gain:

1,461 Btuh
29,460 Btuh

Check Figures
Total Air Handler Supply Air (based on a 0 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

M:\Refrigercion\oficinas-1.CHV

0 CFM
0 CFM
696
0.0000
283.3018
0.0035

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft

0 Btuh
2.46 Tons

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 27

Air Handler #1 - Oficina 701 - Summary Loads (G)


Zn
No

Description
Peak Time

Group 0
3pm January

Area
People
Volume

Htg.Loss
Htg.CFM
CFM/Sqft

Sen.Gain
Clg.CFM
CFM/Sqft

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.CFM
Act.CFM

Clg.O.A.
Req.CFM
Act.CFM

1,969
0
83,066
3,722
n/a
20
0
0
0
0
21,266
0.00
0.00
0
0
Runout duct size: 0in. h x 0in. w, Diffusers: 1, CFM/runout: 0, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft
Group Peak Totals:
Total Groups: 1

1,969
0
83,066
3,722
20
0
0
0
21,266
0.00
0.00
0
Main trunk duct size: 0in. h x 0in. w, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft

M:\Refrigercion\oficinas-1.CHV

0
0

n/a
0
0

0
0

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 28

Air Handler #1 - Oficina 701 - Total Load Summary (G)


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

Oficina 701 Constant Volume - Sum of Peaks


Blow-Thru with program estimated horsepower of 0.00 HP
70% motor and fan efficiency with 0 in. water across the fan
0.96
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:

3pm in January.
86 DB, 76 WB, 118.03 grains

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Btuh
Btuh
Btuh
Btuh
Btuh
Btuh

0 Btuh

Heating Supply Air: 0 / (.998 X 1.08 X 0) =


Winter Vent Outside Air (0.0% of supply) =

0 CFM
0 CFM

Zone space sensible gain:


83,066
Infiltration sensible gain:
0
Draw-thru fan sensible gain:
0
Supply duct sensible gain:
0
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

Btuh
Btuh
Btuh
Btuh
Btuh
83,066 Btuh

Cooling Supply Air: 83,066 / (.998 X 1.1 X 0) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
Return plenum sensible gain:
Outside air sensible gain:
Blow-thru fan sensible gain:
Total sensible gain on return side of coil:
Total sensible gain on air handling system:

0 CFM
0 CFM

0
0
0
0

0 CFM
0 CFM
Btuh
Btuh
Btuh
Btuh

0 CFM
0 Btuh
83,066 Btuh

Zone space latent gain:


3,722 Btuh
Infiltration latent gain:
0 Btuh
Outside air latent gain:
0 Btuh
Total latent gain on air handling system:
Total system sensible and latent gain:

3,722 Btuh
86,787 Btuh

Check Figures
Total Air Handler Supply Air (based on a 0 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

M:\Refrigercion\oficinas-1.CHV

0 CFM
0 CFM
1,969
0.0000
272.2623
0.0037

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft

0 Btuh
7.23 Tons

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 29

Air Handler #2 - Oficina 702 - Summary Loads (G)


Zn
No

Description
Peak Time

Group 0
4pm March

Area
People
Volume

Htg.Loss
Htg.CFM
CFM/Sqft

Sen.Gain
Clg.CFM
CFM/Sqft

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.CFM
Act.CFM

Clg.O.A.
Req.CFM
Act.CFM

1,969
0
32,016
3,722
n/a
20
0
0
0
0
21,266
0.00
0.00
0
0
Runout duct size: 0in. h x 0in. w, Diffusers: 1, CFM/runout: 0, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft
Group Peak Totals:
Total Groups: 1

1,969
0
32,016
3,722
20
0
0
0
21,266
0.00
0.00
0
Main trunk duct size: 0in. h x 0in. w, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft

M:\Refrigercion\oficinas-1.CHV

0
0

n/a
0
0

0
0

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 30

Air Handler #2 - Oficina 702 - Total Load Summary (G)


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

Oficina 702 Constant Volume - Sum of Peaks


Blow-Thru with program estimated horsepower of 0.00 HP
70% motor and fan efficiency with 0 in. water across the fan
0.90
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:

4pm in March.
87 DB, 76 WB, 117.51 grains

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Btuh
Btuh
Btuh
Btuh
Btuh
Btuh

0 Btuh

Heating Supply Air: 0 / (.998 X 1.08 X 0) =


Winter Vent Outside Air (0.0% of supply) =

0 CFM
0 CFM

Zone space sensible gain:


32,016
Infiltration sensible gain:
0
Draw-thru fan sensible gain:
0
Supply duct sensible gain:
0
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

Btuh
Btuh
Btuh
Btuh
Btuh
32,016 Btuh

Cooling Supply Air: 32,016 / (.998 X 1.1 X 0) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
Return plenum sensible gain:
Outside air sensible gain:
Blow-thru fan sensible gain:
Total sensible gain on return side of coil:
Total sensible gain on air handling system:

0 CFM
0 CFM

0
0
0
0

0 CFM
0 CFM
Btuh
Btuh
Btuh
Btuh

0 CFM
0 Btuh
32,016 Btuh

Zone space latent gain:


3,722 Btuh
Infiltration latent gain:
0 Btuh
Outside air latent gain:
0 Btuh
Total latent gain on air handling system:
Total system sensible and latent gain:

3,722 Btuh
35,738 Btuh

Check Figures
Total Air Handler Supply Air (based on a 0 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

M:\Refrigercion\oficinas-1.CHV

0 CFM
0 CFM
1,969
0.0000
661.1739
0.0015

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft

0 Btuh
2.98 Tons

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 31

Air Handler #3 - Oficina 703 - Summary Loads (G)


Zn
No

Description
Peak Time

Group 0
4pm March

Area
People
Volume

Htg.Loss
Htg.CFM
CFM/Sqft

Sen.Gain
Clg.CFM
CFM/Sqft

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.CFM
Act.CFM

Clg.O.A.
Req.CFM
Act.CFM

1,969
0
31,877
3,722
n/a
20
0
0
0
0
21,266
0.00
0.00
0
0
Runout duct size: 0in. h x 0in. w, Diffusers: 1, CFM/runout: 0, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft
Group Peak Totals:
Total Groups: 1

1,969
0
31,877
3,722
20
0
0
0
21,266
0.00
0.00
0
Main trunk duct size: 0in. h x 0in. w, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft

M:\Refrigercion\oficinas-1.CHV

0
0

n/a
0
0

0
0

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 32

Air Handler #3 - Oficina 703 - Total Load Summary (G)


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

Oficina 703 Constant Volume - Sum of Peaks


Blow-Thru with program estimated horsepower of 0.00 HP
70% motor and fan efficiency with 0 in. water across the fan
0.90
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:

4pm in March.
87 DB, 76 WB, 117.51 grains

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Btuh
Btuh
Btuh
Btuh
Btuh
Btuh

0 Btuh

Heating Supply Air: 0 / (.998 X 1.08 X 0) =


Winter Vent Outside Air (0.0% of supply) =

0 CFM
0 CFM

Zone space sensible gain:


31,877
Infiltration sensible gain:
0
Draw-thru fan sensible gain:
0
Supply duct sensible gain:
0
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

Btuh
Btuh
Btuh
Btuh
Btuh
31,877 Btuh

Cooling Supply Air: 31,877 / (.998 X 1.1 X 0) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
Return plenum sensible gain:
Outside air sensible gain:
Blow-thru fan sensible gain:
Total sensible gain on return side of coil:
Total sensible gain on air handling system:

0 CFM
0 CFM

0
0
0
0

0 CFM
0 CFM
Btuh
Btuh
Btuh
Btuh

0 CFM
0 Btuh
31,877 Btuh

Zone space latent gain:


3,722 Btuh
Infiltration latent gain:
0 Btuh
Outside air latent gain:
0 Btuh
Total latent gain on air handling system:
Total system sensible and latent gain:

3,722 Btuh
35,599 Btuh

Check Figures
Total Air Handler Supply Air (based on a 0 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

M:\Refrigercion\oficinas-1.CHV

0 CFM
0 CFM
1,969
0.0000
663.7530
0.0015

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft

0 Btuh
2.97 Tons

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 33

Air Handler #4 - Oficina 704 - Summary Loads (G)


Zn
No

Description
Peak Time

Group 0
4pm March

Area
People
Volume

Htg.Loss
Htg.CFM
CFM/Sqft

Sen.Gain
Clg.CFM
CFM/Sqft

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.CFM
Act.CFM

Clg.O.A.
Req.CFM
Act.CFM

1,969
0
30,533
3,722
n/a
20
0
0
0
0
69,489
0.00
0.00
0
0
Runout duct size: 0in. h x 0in. w, Diffusers: 1, CFM/runout: 0, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft
Group Peak Totals:
Total Groups: 1

1,969
0
30,533
3,722
20
0
0
0
69,489
0.00
0.00
0
Main trunk duct size: 0in. h x 0in. w, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft

M:\Refrigercion\oficinas-1.CHV

0
0

n/a
0
0

0
0

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 34

Air Handler #4 - Oficina 704 - Total Load Summary (G)


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

Oficina 704 Constant Volume - Sum of Peaks


Blow-Thru with program estimated horsepower of 0.00 HP
70% motor and fan efficiency with 0 in. water across the fan
0.89
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:

4pm in March.
87 DB, 76 WB, 117.51 grains

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Btuh
Btuh
Btuh
Btuh
Btuh
Btuh

0 Btuh

Heating Supply Air: 0 / (.998 X 1.08 X 0) =


Winter Vent Outside Air (0.0% of supply) =

0 CFM
0 CFM

Zone space sensible gain:


30,533
Infiltration sensible gain:
0
Draw-thru fan sensible gain:
0
Supply duct sensible gain:
0
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

Btuh
Btuh
Btuh
Btuh
Btuh
30,533 Btuh

Cooling Supply Air: 30,533 / (.998 X 1.1 X 0) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
Return plenum sensible gain:
Outside air sensible gain:
Blow-thru fan sensible gain:
Total sensible gain on return side of coil:
Total sensible gain on air handling system:

0 CFM
0 CFM

0
0
0
0

0 CFM
0 CFM
Btuh
Btuh
Btuh
Btuh

0 CFM
0 Btuh
30,533 Btuh

Zone space latent gain:


3,722 Btuh
Infiltration latent gain:
0 Btuh
Outside air latent gain:
0 Btuh
Total latent gain on air handling system:
Total system sensible and latent gain:

3,722 Btuh
34,255 Btuh

Check Figures
Total Air Handler Supply Air (based on a 0 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

M:\Refrigercion\oficinas-1.CHV

0 CFM
0 CFM
1,969
0.0000
689.7960
0.0014

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft

0 Btuh
2.85 Tons

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 35

Air Handler #5 - Oficina 705 - Summary Loads (G)


Zn
No

Description
Peak Time

Group 0
9am January

Area
People
Volume

Htg.Loss
Htg.CFM
CFM/Sqft

Sen.Gain
Clg.CFM
CFM/Sqft

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.CFM
Act.CFM

Clg.O.A.
Req.CFM
Act.CFM

696
0
28,000
1,461
n/a
7
0
0
0
0
24,544
0.00
0.00
0
0
Runout duct size: 0in. h x 0in. w, Diffusers: 1, CFM/runout: 0, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft
Group Peak Totals:
Total Groups: 1

696
0
28,000
1,461
7
0
0
0
24,544
0.00
0.00
0
Main trunk duct size: 0in. h x 0in. w, Velocity: 0.0 ft/min, Pressure drop: 0.000 in.wg./100ft

M:\Refrigercion\oficinas-1.CHV

0
0

n/a
0
0

0
0

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 36

Air Handler #5 - Oficina 705 - Total Load Summary (G)


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

Oficina 705 Constant Volume - Sum of Peaks


Blow-Thru with program estimated horsepower of 0.00 HP
70% motor and fan efficiency with 0 in. water across the fan
0.95
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:

9am in January.
63 DB, 62 WB, 81.54 grains

Summer: Exhaust controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Btuh
Btuh
Btuh
Btuh
Btuh
Btuh

0 Btuh

Heating Supply Air: 0 / (.998 X 1.08 X 0) =


Winter Vent Outside Air (0.0% of supply) =

0 CFM
0 CFM

Zone space sensible gain:


28,000
Infiltration sensible gain:
0
Draw-thru fan sensible gain:
0
Supply duct sensible gain:
0
Reserve sensible gain:
0
Total sensible gain on supply side of coil:

Btuh
Btuh
Btuh
Btuh
Btuh
28,000 Btuh

Cooling Supply Air: 28,000 / (.998 X 1.1 X 0) =


Summer Vent Outside Air (0.0% of supply) =
Return duct sensible gain:
Return plenum sensible gain:
Outside air sensible gain:
Blow-thru fan sensible gain:
Total sensible gain on return side of coil:
Total sensible gain on air handling system:

0 CFM
0 CFM

0
0
0
0

0 CFM
0 CFM
Btuh
Btuh
Btuh
Btuh

0 CFM
0 Btuh
28,000 Btuh

Zone space latent gain:


1,461 Btuh
Infiltration latent gain:
0 Btuh
Outside air latent gain:
0 Btuh
Total latent gain on air handling system:
Total system sensible and latent gain:

1,461 Btuh
29,460 Btuh

Check Figures
Total Air Handler Supply Air (based on a 0 TD):
Total Air Handler Vent. Air (0.00% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

M:\Refrigercion\oficinas-1.CHV

0 CFM
0 CFM
696
0.0000
283.3018
0.0035

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft

0 Btuh
2.46 Tons

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 37

Zone Detailed Loads (At Group Peak Times)


Load
Unit
-SCCLTD
U.Fac
Sen.
Lat.
Htg.
Description
Quan
CFAC
SHGF
-CLFGain
Gain
Mult.
Zone 1-Oficina 701 - Air Handler 1 (Oficina 701), Group 0 peaks (sensible) in January at 3pm.

Htg.
Loss

Roof-1-8-No.Clg-L
Wall-1-SE-C-L
Wall-2-SW-C-L
Wall-3-E-C-L
Wall-4-SW-C-L
Partition-5-2
Partition-6-2
Gls-SE-1-90-Tran
0%S-0-WS-Solar
Gls-SW-1-90-Tran
0%S-0-WS-Solar
Gls-E-1-90-Tran
0%S-0-WS-Solar
Gls-SW-1-90-Tran
0%S-0-WS-Solar
Lights-Prof=1
Equipment-Prof=1
People-Prof=1

4.468
5.986
5.986
0.000
0.000
3.161
3.161
9.344

8,797
2,407
358
0
0
2,299
1,624
1,711

9.344

9.344

847

9.344

3,169

1,969
402
60
0
0
727.38
513.756
183.1
183.1
0.0
0.0
90.6
90.6
339.1
339.1
2,954
1,969
19.7

0.50
0.65
0.65
0.65
0.65

1.000
0.640
1.000
0.640
1.000
0.640
1.000
0.640
0.900
0.900
0.900

5.0
10.4
3.3
8.1
3.3
7/7
7/7
5
222
5
222
5
196
5
222

0.306
0.410
0.410
0.410
0.410
0.439
0.439
0.640
0.250
0.640
0.830
0.640
0.200
0.640
0.830

Sub-total
Safety factors:
Total w/ safety factors:

3,013
1,719
80
0
0
2,299
1,624
615
6,503
0
1
304
2,273
1,139
39,991
9,070
6,047
4,430

0
3,544

79,110
+5%
--------83,066

3,544
+5%
--------3,722

0
+5%
--------0

Zone 2-Oficina 702 - Air Handler 2 (Oficina 702), Group 0 peaks (sensible) in March at 4pm.
Roof-1-8-No.Clg-L
Partition-2-1
Partition-3-1
Lights-Prof=1
Equipment-Prof=1
People-Prof=1

2,057
378.3216
1250.312
2,954
1,969
19.7

0.50

11.8
7/7
7/7

0.306
0.300
0.300

0.900
0.900
0.900

Sub-total
Safety factors:
Total w/ safety factors:

7,426
817
2,701
9,070
6,047
4,430

4.468
2.160
2.160
0
3,544

30,492
+5%
--------32,016

3,544
+5%
--------3,722

9,188
817
2,701

0
+5%
--------0

Zone 3-Oficina 703 - Air Handler 3 (Oficina 703), Group 0 peaks (sensible) in March at 4pm.
Roof-1-8-No.Clg-L
Partition-2-1
Lights-Prof=1
Equipment-Prof=1
People-Prof=1

2,372
1040.384
2,954
1,969
19.7

0.50

11.8
7/7

0.306
0.300

0.900
0.900
0.900

Sub-total
Safety factors:
Total w/ safety factors:

8,565
2,247
9,070
6,047
4,430

4.468
2.160
0
3,544

30,359
+5%
--------31,877

3,544
+5%
--------3,722

10,597
2,247

0
+5%
--------0

Zone 4-Oficina 704 - Air Handler 4 (Oficina 704), Group 0 peaks (sensible) in March at 4pm.
Roof-1-8-No.Clg-L
M:\Refrigercion\oficinas-1.CHV

2,639

0.50

11.8

0.306

9,530

4.468

11,792

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 38

Zone Detailed Loads (At Group Peak Times) (cont'd)


Load
Description
Wall-3-NW-C-L
Lights-Prof=1
Equipment-Prof=1
People-Prof=1

Unit
Quan

-SCCFAC

CLTD
SHGF

U.Fac
-CLF-

Sen.
Gain

130
2,954
1,969
19.7

0.65
0.900
0.900
0.900

0.0

0.410

1
9,070
6,047
4,430

0
3,544

29,079
+5%
--------30,533

3,544
+5%
--------3,722

Sub-total
Safety factors:
Total w/ safety factors:

Lat.
Gain

Htg.
Mult.

Htg.
Loss

5.986

780

0
+5%
--------0

Zone 5-Oficina 705 - Air Handler 5 (Oficina 705), Group 0 peaks (sensible) in January at 9am.
Roof-1-8-No.Clg-L
Wall-2-SE-C-L
Gls-SE-1-90-Tran
0%S-0-WS-Solar
Lights-Prof=1
Equipment-Prof=1
People-Prof=1
Sub-total
Safety factors:
Total w/ safety factors:

M:\Refrigercion\oficinas-1.CHV

2,268
297
220.1
220.1
1,043
696
7.0

0.50
0.65
1.000
0.640
1.000
1.000
1.000

-8.0
1.3
-7
222

0.306
0.410
0.640
0.810

-5,552
161
-951
25,336
3,560
2,373
1,739

4.468
5.986
9.344

0
1,391

26,666
+5%
--------28,000

1,391
+5%
--------1,461

10,132
1,776
2,057

0
+5%
--------0

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 39

Zone Detailed Loads (At Zone Peak Times)


Load
Unit
-SCCLTD
U.Fac
Sen.
Lat.
Htg.
Htg.
Description
Quan
CFAC
SHGF
-CLFGain
Gain
Mult.
Loss
Zone 1-Oficina 701 peaks (sensible) in January at 3pm, Air Handler 1 (Oficina 701), Group 0, 183.0 x
10.8, Construction Type: 11 (Medium)
MACEDO MAMANI ANDREA, HUAMAN VILCA ELVIS, SULLIVAN FELIPE GASPAR, PAULO MANTILLA HUAMAN
Roof-1-8-No.Clg-L
Wall-1-SE-C-L
Wall-2-SW-C-L
Wall-3-E-C-L
Wall-4-SW-C-L
Partition-5-2
Partition-6-2
Gls-SE-1-90-Tran
0%S-0-WS-Solar
Gls-SW-1-90-Tran
0%S-0-WS-Solar
Gls-E-1-90-Tran
0%S-0-WS-Solar
Gls-SW-1-90-Tran
0%S-0-WS-Solar
Lights-Prof=1
Equipment-Prof=1
People-Prof=1

1,969
402
60
0
0
727.38
513.756
183.1
183.1
0.0
0.0
90.6
90.6
339.1
339.1
2,954
1,969
19.7

0.50
0.65
0.65
0.65
0.65

1.000
0.640
1.000
0.640
1.000
0.640
1.000
0.640
0.900
0.900
0.900

5.0
10.4
3.3
8.1
3.3
7/7
7/7
5
222
5
222
5
196
5
222

0.306
0.410
0.410
0.410
0.410
0.439
0.439
0.640
0.250
0.640
0.830
0.640
0.200
0.640
0.830

Sub-total
Safety factors:
Total w/ safety factors:

3,013
1,719
80
0
0
2,299
1,624
615
6,503
0
1
304
2,273
1,139
39,991
9,070
6,047
4,430

0
3,544

79,110
+5%
--------83,066

3,544
+5%
--------3,722

4.468
5.986
5.986
0.000
0.000
3.161
3.161
9.344

8,797
2,407
358
0
0
2,299
1,624
1,711

9.344

9.344

847

9.344

3,169

0
+5%
--------0

Zone 2-Oficina 702 peaks (sensible) in March at 4pm, Air Handler 2 (Oficina 702), Group 0, 183.0 x 10.8,
Construction Type: 11 (Medium)
MACEDO MAMANI ANDREA, HUAMAN VILCA ELVIS, SULLIVAN FELIPE GASPAR, PAULO MANTILLA HUAMAN
Roof-1-8-No.Clg-L
Partition-2-1
Partition-3-1
Lights-Prof=1
Equipment-Prof=1
People-Prof=1

2,057
378.3216
1250.312
2,954
1,969
19.7

0.50

11.8
7/7
7/7

0.306
0.300
0.300

0.900
0.900
0.900

Sub-total
Safety factors:
Total w/ safety factors:

7,426
817
2,701
9,070
6,047
4,430

4.468
2.160
2.160
0
3,544

30,492
+5%
--------32,016

3,544
+5%
--------3,722

9,188
817
2,701

0
+5%
--------0

Zone 3-Oficina 703 peaks (sensible) in March at 4pm, Air Handler 3 (Oficina 703), Group 0, 183.0 x 10.8,
Construction Type: 11 (Medium)
MACEDO MAMANI ANDREA, HUAMAN VILCA ELVIS, SULLIVAN FELIPE GASPAR, PAULO MANTILLA HUAMAN
Roof-1-8-No.Clg-L
Partition-2-1
Lights-Prof=1
Equipment-Prof=1
People-Prof=1

M:\Refrigercion\oficinas-1.CHV

2,372
1040.384
2,954
1,969
19.7

0.50
0.900
0.900
0.900

11.8
7/7

0.306
0.300

8,565
2,247
9,070
6,047
4,430

4.468
2.160

10,597
2,247

0
3,544

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 40

Zone Detailed Loads (At Zone Peak Times) (cont'd)


Load
Description

Unit
Quan

-SCCFAC

CLTD
SHGF

U.Fac
-CLF-

Sub-total
Safety factors:
Total w/ safety factors:

Sen.
Gain

Lat.
Gain

30,359
+5%
--------31,877

3,544
+5%
--------3,722

Htg.
Mult.

Htg.
Loss
0
+5%
--------0

Zone 4-Oficina 704 peaks (sensible) in March at 4pm, Air Handler 4 (Oficina 704), Group 0, 183.0 x 10.8,
Construction Type: 11 (Medium)
MACEDO MAMANI ANDREA, HUAMAN VILCA ELVIS, SULLIVAN FELIPE GASPAR, PAULO MANTILLA HUAMAN
Roof-1-8-No.Clg-L
Wall-3-NW-C-L
Lights-Prof=1
Equipment-Prof=1
People-Prof=1

2,639
130
2,954
1,969
19.7

0.50
0.65
0.900
0.900
0.900

11.8
0.0

0.306
0.410

Sub-total
Safety factors:
Total w/ safety factors:

9,530
1
9,070
6,047
4,430

4.468
5.986
0
3,544

29,079
+5%
--------30,533

3,544
+5%
--------3,722

11,792
780

0
+5%
--------0

Zone 5-Oficina 705 peaks (sensible) in January at 9am, Air Handler 5 (Oficina 705), Group 0, 210.8 x 3.3,
Construction Type: 11 (Medium)
MACEDO MAMANI ANDREA, HUAMAN VILCA ELVIS, SULLIVAN FELIPE GASPAR, PAULO MANTILLA HUAMAN
Roof-1-8-No.Clg-L
Wall-2-SE-C-L
Gls-SE-1-90-Tran
0%S-0-WS-Solar
Lights-Prof=1
Equipment-Prof=1
People-Prof=1
Sub-total
Safety factors:
Total w/ safety factors:

M:\Refrigercion\oficinas-1.CHV

2,268
297
220.1
220.1
1,043
696
7.0

0.50
0.65
1.000
0.640
1.000
1.000
1.000

-8.0
1.3
-7
222

0.306
0.410
0.640
0.810

-5,552
161
-951
25,336
3,560
2,373
1,739

4.468
5.986
9.344

0
1,391

26,666
+5%
--------28,000

1,391
+5%
--------1,461

10,132
1,776
2,057

0
+5%
--------0

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 41

Air System #1 (Oficina 701) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grains

Sensible

Temp

CFM

0
0
0
83,066
0

71.998
0.000
0.000
1.000
0.000
0.000

0
0
5,626,550,000
44,856,220
0

83,066
0
0
0
0
0

71.600
0.250
0.000
0.000
0.000
0.000

83,066

0.000

64.376

3,722

0.000

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 CFM
Blow-Thru Fan

3,722

64.380

-64.380

Entering Coil Condition

3,722

0.000

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 29.921)


PR x
1.10 x CFM x (DB entering - DB leaving)
PR x
0.68 x CFM x (Grains entering - Grains leaving)
PR x
4.50 x CFM x (Enthalpy entering - Enthalpy leaving)
0.998
0.998

x
x

1.10
0.68

x
x

0
0

x(
x(

0.000
0.000

71.998
64.376

)=
)=

SUM
=
GTH
=
0.998
Total System Load

4.50

x(

0.000

27.333

)=
=

0
0
---------0
0
86,787

Btuh
Btuh
Btuh
Btuh
Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM
Heating GPM
Steam Req.

=
=
=

0 /(
0 /(
0 /

10.00
10.00
970

x
x

500
500

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

M:\Refrigercion\oficinas-1.CHV

=
=
=

0.0 GPM
0.0 GPM
0.0 lb./hr

Entering Heating Coil Conditions


.00
.00
.00
.00 Btu/lbm

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

Dry bulb temperature:

72.00

Leaving Heating Coil Conditions


72.00
61.41
55.00
27.33 Btu/lbm

Dry bulb temperature:

72.00

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 42

Air System #1 (Oficina 701) Psychrometric Analysis (G)


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grains

Sensible

Temp

CFM

0
0
0
83,066
0

71.998
0.000
0.000
1.000
0.000
0.000

0
0
5,626,550,000
44,856,220
0

83,066
0
0
0
0
0

71.600
0.250
0.000
0.000
0.000
0.000

83,066

0.000

64.376

3,722

0.000

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 CFM
Blow-Thru Fan

3,722

64.380

-64.380

Entering Coil Condition

3,722

0.000

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 29.921)


PR x
1.10 x CFM x (DB entering - DB leaving)
PR x
0.68 x CFM x (Grains entering - Grains leaving)
PR x
4.50 x CFM x (Enthalpy entering - Enthalpy leaving)
0.998
0.998

x
x

1.10
0.68

x
x

0
0

x(
x(

0.000
0.000

71.998
64.376

)=
)=

SUM
=
GTH
=
0.998
Total System Load

4.50

x(

0.000

27.333

)=
=

0
0
---------0
0
86,787

Btuh
Btuh
Btuh
Btuh
Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM
Heating GPM
Steam Req.

=
=
=

0 /(
0 /(
0 /

10.00
10.00
970

x
x

500
500

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

M:\Refrigercion\oficinas-1.CHV

=
=
=

0.0 GPM
0.0 GPM
0.0 lb./hr

Entering Heating Coil Conditions


.00
.00
.00
.00 Btu/lbm

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

Dry bulb temperature:

72.00

Leaving Heating Coil Conditions


72.00
61.41
55.00
27.33 Btu/lbm

Dry bulb temperature:

72.00

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 43

Air System #2 (Oficina 702) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grains

Sensible

Temp

CFM

0
0
0
32,016
0

72.002
0.000
0.000
1.000
0.000
0.000

0
0
1,528,148,000
-14,639,400
0

32,016
0
0
0
0
0

71.600
0.250
0.000
0.000
0.000
0.000

32,016

0.000

64.384

3,722

0.000

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 CFM
Blow-Thru Fan

3,722

64.380

-64.380

Entering Coil Condition

3,722

0.000

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 29.921)


PR x
1.10 x CFM x (DB entering - DB leaving)
PR x
0.68 x CFM x (Grains entering - Grains leaving)
PR x
4.50 x CFM x (Enthalpy entering - Enthalpy leaving)
0.998
0.998

x
x

1.10
0.68

x
x

0
0

x(
x(

0.000
0.000

72.002
64.384

)=
)=

SUM
=
GTH
=
0.998
Total System Load

4.50

x(

0.000

27.335

)=
=

0
0
---------0
0
35,738

Btuh
Btuh
Btuh
Btuh
Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM
Heating GPM
Steam Req.

=
=
=

0 /(
0 /(
0 /

10.00
10.00
970

x
x

500
500

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

M:\Refrigercion\oficinas-1.CHV

=
=
=

0.0 GPM
0.0 GPM
0.0 lb./hr

Entering Heating Coil Conditions


.00
.00
.00
.00 Btu/lbm

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

Dry bulb temperature:

72.00

Leaving Heating Coil Conditions


72.00
61.41
55.00
27.34 Btu/lbm

Dry bulb temperature:

72.00

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 44

Air System #2 (Oficina 702) Psychrometric Analysis (G)


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grains

Sensible

Temp

CFM

0
0
0
32,016
0

72.002
0.000
0.000
1.000
0.000
0.000

0
0
1,528,148,000
-14,639,400
0

32,016
0
0
0
0
0

71.600
0.250
0.000
0.000
0.000
0.000

32,016

0.000

64.384

3,722

0.000

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 CFM
Blow-Thru Fan

3,722

64.380

-64.380

Entering Coil Condition

3,722

0.000

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 29.921)


PR x
1.10 x CFM x (DB entering - DB leaving)
PR x
0.68 x CFM x (Grains entering - Grains leaving)
PR x
4.50 x CFM x (Enthalpy entering - Enthalpy leaving)
0.998
0.998

x
x

1.10
0.68

x
x

0
0

x(
x(

0.000
0.000

72.002
64.384

)=
)=

SUM
=
GTH
=
0.998
Total System Load

4.50

x(

0.000

27.335

)=
=

0
0
---------0
0
35,738

Btuh
Btuh
Btuh
Btuh
Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM
Heating GPM
Steam Req.

=
=
=

0 /(
0 /(
0 /

10.00
10.00
970

x
x

500
500

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

M:\Refrigercion\oficinas-1.CHV

=
=
=

0.0 GPM
0.0 GPM
0.0 lb./hr

Entering Heating Coil Conditions


.00
.00
.00
.00 Btu/lbm

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

Dry bulb temperature:

72.00

Leaving Heating Coil Conditions


72.00
61.41
55.00
27.34 Btu/lbm

Dry bulb temperature:

72.00

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 45

Air System #3 (Oficina 703) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grains

Sensible

Temp

CFM

0
0
0
31,877
0

72.002
0.000
0.000
1.000
0.000
0.000

0
0
1,581,821,000
-14,860,590
0

31,877
0
0
0
0
0

71.600
0.250
0.000
0.000
0.000
0.000

31,877

0.000

64.384

3,722

0.000

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 CFM
Blow-Thru Fan

3,722

64.380

-64.380

Entering Coil Condition

3,722

0.000

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 29.921)


PR x
1.10 x CFM x (DB entering - DB leaving)
PR x
0.68 x CFM x (Grains entering - Grains leaving)
PR x
4.50 x CFM x (Enthalpy entering - Enthalpy leaving)
0.998
0.998

x
x

1.10
0.68

x
x

0
0

x(
x(

0.000
0.000

72.002
64.384

)=
)=

SUM
=
GTH
=
0.998
Total System Load

4.50

x(

0.000

27.335

)=
=

0
0
---------0
0
35,599

Btuh
Btuh
Btuh
Btuh
Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM
Heating GPM
Steam Req.

=
=
=

0 /(
0 /(
0 /

10.00
10.00
970

x
x

500
500

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

M:\Refrigercion\oficinas-1.CHV

=
=
=

0.0 GPM
0.0 GPM
0.0 lb./hr

Entering Heating Coil Conditions


.00
.00
.00
.00 Btu/lbm

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

Dry bulb temperature:

72.00

Leaving Heating Coil Conditions


72.00
61.41
55.00
27.34 Btu/lbm

Dry bulb temperature:

72.00

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 46

Air System #3 (Oficina 703) Psychrometric Analysis (G)


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grains

Sensible

Temp

CFM

0
0
0
31,877
0

72.002
0.000
0.000
1.000
0.000
0.000

0
0
1,581,821,000
-14,860,590
0

31,877
0
0
0
0
0

71.600
0.250
0.000
0.000
0.000
0.000

31,877

0.000

64.384

3,722

0.000

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 CFM
Blow-Thru Fan

3,722

64.380

-64.380

Entering Coil Condition

3,722

0.000

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 29.921)


PR x
1.10 x CFM x (DB entering - DB leaving)
PR x
0.68 x CFM x (Grains entering - Grains leaving)
PR x
4.50 x CFM x (Enthalpy entering - Enthalpy leaving)
0.998
0.998

x
x

1.10
0.68

x
x

0
0

x(
x(

0.000
0.000

72.002
64.384

)=
)=

SUM
=
GTH
=
0.998
Total System Load

4.50

x(

0.000

27.335

)=
=

0
0
---------0
0
35,599

Btuh
Btuh
Btuh
Btuh
Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM
Heating GPM
Steam Req.

=
=
=

0 /(
0 /(
0 /

10.00
10.00
970

x
x

500
500

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

M:\Refrigercion\oficinas-1.CHV

=
=
=

0.0 GPM
0.0 GPM
0.0 lb./hr

Entering Heating Coil Conditions


.00
.00
.00
.00 Btu/lbm

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

Dry bulb temperature:

72.00

Leaving Heating Coil Conditions


72.00
61.41
55.00
27.34 Btu/lbm

Dry bulb temperature:

72.00

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 47

Air System #4 (Oficina 704) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grains

Sensible

Temp

CFM

0
0
0
30,533
0

72.002
0.000
0.000
1.000
0.000
0.000

0
0
1,589,073,000
-14,575,650
0

30,533
0
0
0
0
0

71.600
0.250
0.000
0.000
0.000
0.000

30,533

0.000

64.384

3,722

0.000

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 CFM
Blow-Thru Fan

3,722

64.380

-64.380

Entering Coil Condition

3,722

0.000

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 29.921)


PR x
1.10 x CFM x (DB entering - DB leaving)
PR x
0.68 x CFM x (Grains entering - Grains leaving)
PR x
4.50 x CFM x (Enthalpy entering - Enthalpy leaving)
0.998
0.998

x
x

1.10
0.68

x
x

0
0

x(
x(

0.000
0.000

72.002
64.384

)=
)=

SUM
=
GTH
=
0.998
Total System Load

4.50

x(

0.000

27.335

)=
=

0
0
---------0
0
34,255

Btuh
Btuh
Btuh
Btuh
Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM
Heating GPM
Steam Req.

=
=
=

0 /(
0 /(
0 /

10.00
10.00
970

x
x

500
500

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

M:\Refrigercion\oficinas-1.CHV

=
=
=

0.0 GPM
0.0 GPM
0.0 lb./hr

Entering Heating Coil Conditions


.00
.00
.00
.00 Btu/lbm

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

Dry bulb temperature:

72.00

Leaving Heating Coil Conditions


72.00
61.41
55.00
27.34 Btu/lbm

Dry bulb temperature:

72.00

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 48

Air System #4 (Oficina 704) Psychrometric Analysis (G)


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grains

Sensible

Temp

CFM

0
0
0
30,533
0

72.002
0.000
0.000
1.000
0.000
0.000

0
0
1,589,073,000
-14,575,650
0

30,533
0
0
0
0
0

71.600
0.250
0.000
0.000
0.000
0.000

30,533

0.000

64.384

3,722

0.000

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 CFM
Blow-Thru Fan

3,722

64.380

-64.380

Entering Coil Condition

3,722

0.000

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 29.921)


PR x
1.10 x CFM x (DB entering - DB leaving)
PR x
0.68 x CFM x (Grains entering - Grains leaving)
PR x
4.50 x CFM x (Enthalpy entering - Enthalpy leaving)
0.998
0.998

x
x

1.10
0.68

x
x

0
0

x(
x(

0.000
0.000

72.002
64.384

)=
)=

SUM
=
GTH
=
0.998
Total System Load

4.50

x(

0.000

27.335

)=
=

0
0
---------0
0
34,255

Btuh
Btuh
Btuh
Btuh
Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM
Heating GPM
Steam Req.

=
=
=

0 /(
0 /(
0 /

10.00
10.00
970

x
x

500
500

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

M:\Refrigercion\oficinas-1.CHV

=
=
=

0.0 GPM
0.0 GPM
0.0 lb./hr

Entering Heating Coil Conditions


.00
.00
.00
.00 Btu/lbm

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

Dry bulb temperature:

72.00

Leaving Heating Coil Conditions


72.00
61.41
55.00
27.34 Btu/lbm

Dry bulb temperature:

72.00

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 49

Air System #5 (Oficina 705) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grains

Sensible

Temp

CFM

0
0
0
28,000
0

72.004
0.000
0.000
1.000
0.000
0.000

0
0
306,744,400
-6,165,148
0

28,000
0
0
0
0
0

71.600
0.250
0.000
0.000
0.000
0.000

28,000

0.000

64.389

1,461

0.000

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 CFM
Blow-Thru Fan

1,461

64.380

-64.380

Entering Coil Condition

1,461

0.000

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 29.921)


PR x
1.10 x CFM x (DB entering - DB leaving)
PR x
0.68 x CFM x (Grains entering - Grains leaving)
PR x
4.50 x CFM x (Enthalpy entering - Enthalpy leaving)
0.998
0.998

x
x

1.10
0.68

x
x

0
0

x(
x(

0.000
0.000

72.004
64.389

)=
)=

SUM
=
GTH
=
0.998
Total System Load

4.50

x(

0.000

27.336

)=
=

0
0
---------0
0
29,460

Btuh
Btuh
Btuh
Btuh
Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM
Heating GPM
Steam Req.

=
=
=

0 /(
0 /(
0 /

10.00
10.00
970

x
x

500
500

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

M:\Refrigercion\oficinas-1.CHV

=
=
=

0.0 GPM
0.0 GPM
0.0 lb./hr

Entering Heating Coil Conditions


.00
.00
.00
.00 Btu/lbm

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

Dry bulb temperature:

72.00

Leaving Heating Coil Conditions


72.00
61.41
55.00
27.34 Btu/lbm

Dry bulb temperature:

72.00

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 50

Air System #5 (Oficina 705) Psychrometric Analysis (G)


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Zone Loads
Sensible Reserve

Grains

Sensible

Temp

CFM

0
0
0
28,000
0

72.004
0.000
0.000
1.000
0.000
0.000

0
0
306,744,400
-6,165,148
0

28,000
0
0
0
0
0

71.600
0.250
0.000
0.000
0.000
0.000

28,000

0.000

64.389

1,461

0.000

Zone Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 0 CFM
Blow-Thru Fan

1,461

64.380

-64.380

Entering Coil Condition

1,461

0.000

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 29.921)


PR x
1.10 x CFM x (DB entering - DB leaving)
PR x
0.68 x CFM x (Grains entering - Grains leaving)
PR x
4.50 x CFM x (Enthalpy entering - Enthalpy leaving)
0.998
0.998

x
x

1.10
0.68

x
x

0
0

x(
x(

0.000
0.000

72.004
64.389

)=
)=

SUM
=
GTH
=
0.998
Total System Load

4.50

x(

0.000

27.336

)=
=

0
0
---------0
0
29,460

Btuh
Btuh
Btuh
Btuh
Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM
Heating GPM
Steam Req.

=
=
=

0 /(
0 /(
0 /

10.00
10.00
970

x
x

500
500

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

M:\Refrigercion\oficinas-1.CHV

=
=
=

0.0 GPM
0.0 GPM
0.0 lb./hr

Entering Heating Coil Conditions


.00
.00
.00
.00 Btu/lbm

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

Dry bulb temperature:

72.00

Leaving Heating Coil Conditions


72.00
61.41
55.00
27.34 Btu/lbm

Dry bulb temperature:

72.00

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 51

Air System #1 (Oficina 701) Psychrometric Chart


ZC
Zone Condition
OC
LC
Leaving Coil Condition
EC
SD
Supply Duct Temperature Rise
RD
DTF
Draw Through Fan Sensible Gain
BTF
RE
Reserve or Reheat Sensible Gain
PL
SM
Supply Side Miscellaneous Sensible Gain
RM
PRE
Pretreated Air Condition
One or more points or processes failed to be added to the chart:
Zone process could not be added.

Outdoor Condition
Entering Coil Condition
Return Duct Temperature Rise
Blow Through Fan Sensible Gain
Return Air Plenum Sensible Gain
Return Side Miscellaneous Gain

Data out of range.

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 52

Air System #1 (Oficina 701) Psychrometric Chart (G)


ZC
Zone Condition
OC
LC
Leaving Coil Condition
EC
SD
Supply Duct Temperature Rise
RD
DTF
Draw Through Fan Sensible Gain
BTF
RE
Reserve or Reheat Sensible Gain
PL
SM
Supply Side Miscellaneous Sensible Gain
RM
PRE
Pretreated Air Condition
One or more points or processes failed to be added to the chart:
Zone process could not be added.

Outdoor Condition
Entering Coil Condition
Return Duct Temperature Rise
Blow Through Fan Sensible Gain
Return Air Plenum Sensible Gain
Return Side Miscellaneous Gain

Data out of range.

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 53

Air System #2 (Oficina 702) Psychrometric Chart


ZC
Zone Condition
OC
LC
Leaving Coil Condition
EC
SD
Supply Duct Temperature Rise
RD
DTF
Draw Through Fan Sensible Gain
BTF
RE
Reserve or Reheat Sensible Gain
PL
SM
Supply Side Miscellaneous Sensible Gain
RM
PRE
Pretreated Air Condition
One or more points or processes failed to be added to the chart:
Zone process could not be added.

Outdoor Condition
Entering Coil Condition
Return Duct Temperature Rise
Blow Through Fan Sensible Gain
Return Air Plenum Sensible Gain
Return Side Miscellaneous Gain

Data out of range.

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 54

Air System #2 (Oficina 702) Psychrometric Chart (G)


ZC
Zone Condition
OC
LC
Leaving Coil Condition
EC
SD
Supply Duct Temperature Rise
RD
DTF
Draw Through Fan Sensible Gain
BTF
RE
Reserve or Reheat Sensible Gain
PL
SM
Supply Side Miscellaneous Sensible Gain
RM
PRE
Pretreated Air Condition
One or more points or processes failed to be added to the chart:
Zone process could not be added.

Outdoor Condition
Entering Coil Condition
Return Duct Temperature Rise
Blow Through Fan Sensible Gain
Return Air Plenum Sensible Gain
Return Side Miscellaneous Gain

Data out of range.

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 55

Air System #3 (Oficina 703) Psychrometric Chart


ZC
Zone Condition
OC
LC
Leaving Coil Condition
EC
SD
Supply Duct Temperature Rise
RD
DTF
Draw Through Fan Sensible Gain
BTF
RE
Reserve or Reheat Sensible Gain
PL
SM
Supply Side Miscellaneous Sensible Gain
RM
PRE
Pretreated Air Condition
One or more points or processes failed to be added to the chart:
Zone process could not be added.

Outdoor Condition
Entering Coil Condition
Return Duct Temperature Rise
Blow Through Fan Sensible Gain
Return Air Plenum Sensible Gain
Return Side Miscellaneous Gain

Data out of range.

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 56

Air System #3 (Oficina 703) Psychrometric Chart (G)


ZC
Zone Condition
OC
LC
Leaving Coil Condition
EC
SD
Supply Duct Temperature Rise
RD
DTF
Draw Through Fan Sensible Gain
BTF
RE
Reserve or Reheat Sensible Gain
PL
SM
Supply Side Miscellaneous Sensible Gain
RM
PRE
Pretreated Air Condition
One or more points or processes failed to be added to the chart:
Zone process could not be added.

Outdoor Condition
Entering Coil Condition
Return Duct Temperature Rise
Blow Through Fan Sensible Gain
Return Air Plenum Sensible Gain
Return Side Miscellaneous Gain

Data out of range.

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 57

Air System #4 (Oficina 704) Psychrometric Chart


ZC
Zone Condition
OC
LC
Leaving Coil Condition
EC
SD
Supply Duct Temperature Rise
RD
DTF
Draw Through Fan Sensible Gain
BTF
RE
Reserve or Reheat Sensible Gain
PL
SM
Supply Side Miscellaneous Sensible Gain
RM
PRE
Pretreated Air Condition
One or more points or processes failed to be added to the chart:
Zone process could not be added.

Outdoor Condition
Entering Coil Condition
Return Duct Temperature Rise
Blow Through Fan Sensible Gain
Return Air Plenum Sensible Gain
Return Side Miscellaneous Gain

Data out of range.

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 58

Air System #4 (Oficina 704) Psychrometric Chart (G)


ZC
Zone Condition
OC
LC
Leaving Coil Condition
EC
SD
Supply Duct Temperature Rise
RD
DTF
Draw Through Fan Sensible Gain
BTF
RE
Reserve or Reheat Sensible Gain
PL
SM
Supply Side Miscellaneous Sensible Gain
RM
PRE
Pretreated Air Condition
One or more points or processes failed to be added to the chart:
Zone process could not be added.

Outdoor Condition
Entering Coil Condition
Return Duct Temperature Rise
Blow Through Fan Sensible Gain
Return Air Plenum Sensible Gain
Return Side Miscellaneous Gain

Data out of range.

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 59

Air System #5 (Oficina 705) Psychrometric Chart


ZC
Zone Condition
OC
LC
Leaving Coil Condition
EC
SD
Supply Duct Temperature Rise
RD
DTF
Draw Through Fan Sensible Gain
BTF
RE
Reserve or Reheat Sensible Gain
PL
SM
Supply Side Miscellaneous Sensible Gain
RM
PRE
Pretreated Air Condition
One or more points or processes failed to be added to the chart:
Zone process could not be added.

Outdoor Condition
Entering Coil Condition
Return Duct Temperature Rise
Blow Through Fan Sensible Gain
Return Air Plenum Sensible Gain
Return Side Miscellaneous Gain

Data out of range.

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 60

Air System #5 (Oficina 705) Psychrometric Chart (G)


ZC
Zone Condition
OC
LC
Leaving Coil Condition
EC
SD
Supply Duct Temperature Rise
RD
DTF
Draw Through Fan Sensible Gain
BTF
RE
Reserve or Reheat Sensible Gain
PL
SM
Supply Side Miscellaneous Sensible Gain
RM
PRE
Pretreated Air Condition
One or more points or processes failed to be added to the chart:
Zone process could not be added.

Outdoor Condition
Entering Coil Condition
Return Duct Temperature Rise
Blow Through Fan Sensible Gain
Return Air Plenum Sensible Gain
Return Side Miscellaneous Gain

Data out of range.

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 61

Building Pie Charts


Building peaks in February at 4pm.

Partition - 4.77%
Roof - 18.07%
People - 17.11%
Wall - 1.64%

Building
Net
Gain
213,045
Btuh

Equipment - 12.97%
Glass - 25.97%

Lighting - 19.46%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 62

Building Pie Charts (G)


Building peaks in February at 4pm.

Partition - 4.77%
Roof - 18.07%
People - 17.11%
Wall - 1.64%

Building
Net
Gain
213,045
Btuh

Equipment - 12.97%
Glass - 25.97%

Lighting - 19.46%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 63

Air Handler #1 Pie Charts


Air Handler #1 peaks in January at 3pm.

Roof - 3.64%
Wall - 2.18%

Partition - 4.75%
People - 9.65%

Equipment - 7.32%

Air
Handler
#1
Net
Gain
86,787
Btuh

Lighting - 10.97%

Glass - 61.49%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 64

Air Handler #2 Pie Charts


Air Handler #2 peaks in March at 4pm.

Partition - 10.34%
Roof - 21.82%

Air
Handler
#2
Net
Gain
35,738
Btuh

People - 23.43%

Lighting - 26.65%
Equipment - 17.77%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 65

Air Handler #3 Pie Charts


Air Handler #3 peaks in March at 4pm.

Partition - 6.63%
Roof - 25.26%
People - 23.52%

Air
Handler
#3
Net
Gain
35,599
Btuh
Lighting - 26.75%

M:\Refrigercion\oficinas-1.CHV

Equipment - 17.84%

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 66

Air Handler #4 Pie Charts


Air Handler #4 peaks in March at 4pm.

People - 24.44%
Roof - 29.21%

Air
Handler
#4
Net
Gain
34,255
Btuh

Wall - 0.00%
Equipment - 18.54%

Lighting - 27.80%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 67

Air Handler #5 Pie Charts


Air Handler #5 peaks in January at 9am.

Wall - 0.57%

People - 11.16%
Equipment - 8.46%

Air
Handler
#5
Net
Gain
29,460
Btuh

Lighting - 12.69%

Glass - 86.91%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 68

Air Handler #1 Pie Charts (G)


Air Handler #1 peaks in January at 3pm.

Roof - 3.64%
Wall - 2.18%

Partition - 4.75%
People - 9.65%

Equipment - 7.32%

Air
Handler
#1
Net
Gain
86,787
Btuh

Lighting - 10.97%

Glass - 61.49%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 69

Air Handler #2 Pie Charts (G)


Air Handler #2 peaks in March at 4pm.

Partition - 10.34%
Roof - 21.82%

Air
Handler
#2
Net
Gain
35,738
Btuh

People - 23.43%

Lighting - 26.65%
Equipment - 17.77%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 70

Air Handler #3 Pie Charts (G)


Air Handler #3 peaks in March at 4pm.

Partition - 6.63%
Roof - 25.26%
People - 23.52%

Air
Handler
#3
Net
Gain
35,599
Btuh
Lighting - 26.75%

M:\Refrigercion\oficinas-1.CHV

Equipment - 17.84%

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 71

Air Handler #4 Pie Charts (G)


Air Handler #4 peaks in March at 4pm.

People - 24.44%
Roof - 29.21%

Air
Handler
#4
Net
Gain
34,255
Btuh

Wall - 0.00%
Equipment - 18.54%

Lighting - 27.80%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 72

Air Handler #5 Pie Charts (G)


Air Handler #5 peaks in January at 9am.

Wall - 0.57%

People - 11.16%
Equipment - 8.46%

Air
Handler
#5
Net
Gain
29,460
Btuh

Lighting - 12.69%

Glass - 86.91%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 73

Group 0, System 1 Pie Charts


Group 0, System 1 peaks in January at 3pm

Roof - 3.64%
Wall - 2.18%

Partition - 4.75%
People - 9.65%

Equipment - 7.32%

Group 0,
System
1
Net
Gain
86,787
Btuh

Lighting - 10.97%

Glass - 61.49%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 74

Group 0, System 2 Pie Charts


Group 0, System 2 peaks in March at 4pm

Partition - 10.34%
Roof - 21.82%

Group 0,
System
2
Net
Gain
35,738
Btuh

People - 23.43%

Lighting - 26.65%
Equipment - 17.77%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 75

Group 0, System 3 Pie Charts


Group 0, System 3 peaks in March at 4pm

Partition - 6.63%
Roof - 25.26%
People - 23.52%

Group 0,
System
3
Net
Gain
35,599
Btuh
Lighting - 26.75%

M:\Refrigercion\oficinas-1.CHV

Equipment - 17.84%

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 76

Group 0, System 4 Pie Charts


Group 0, System 4 peaks in March at 4pm

People - 24.44%
Roof - 29.21%

Group 0,
System
4
Net
Gain
34,255
Btuh

Wall - 0.00%
Equipment - 18.54%

Lighting - 27.80%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 77

Group 0, System 5 Pie Charts


Group 0, System 5 peaks in January at 9am

Wall - 0.57%

People - 11.16%
Equipment - 8.46%

Group 0,
System
5
Net
Gain
29,460
Btuh

Lighting - 12.69%

Glass - 86.91%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 78

Zone #1 Pie Charts


Zone #1 peaks in January at 3pm

Roof - 3.64%
Wall - 2.18%

Partition - 4.75%
People - 9.65%

Equipment - 7.32%

Zone
#1
Net
Gain
86,787
Btuh

Lighting - 10.97%

Glass - 61.49%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 79

Zone #2 Pie Charts


Zone #2 peaks in March at 4pm

Partition - 10.34%
Roof - 21.82%

Zone
#2
Net
Gain
35,738
Btuh

People - 23.43%

Lighting - 26.65%
Equipment - 17.77%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 80

Zone #3 Pie Charts


Zone #3 peaks in March at 4pm

Partition - 6.63%
Roof - 25.26%
People - 23.52%

Zone
#3
Net
Gain
35,599
Btuh
Lighting - 26.75%

M:\Refrigercion\oficinas-1.CHV

Equipment - 17.84%

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 81

Zone #4 Pie Charts


Zone #4 peaks in March at 4pm

People - 24.44%
Roof - 29.21%

Zone
#4
Net
Gain
34,255
Btuh

Wall - 0.00%
Equipment - 18.54%

Lighting - 27.80%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.

Chvac - Full Commercial HVAC Loads Calculation Program


Elite Software Development
College Station, TX 77845

Elite Software Development, Inc.


Ofiicinas
Page 82

Zone #5 Pie Charts


Zone #5 peaks in January at 9am

Wall - 0.57%

People - 11.16%
Equipment - 8.46%

Zone
#5
Net
Gain
29,460
Btuh

Lighting - 12.69%

Glass - 86.91%

M:\Refrigercion\oficinas-1.CHV

viernes, 22 de mayo de 2015, 11:11 a.m.