1. Introduction
Currently in power systems, there are a large number of disconnections
caused by various factors of influence. Determining the factors of cause of these
interruptions and estimation of the level of their influence on the reliability of the
equipment installed in the power system allows developing measures to ensure
continuity of qualitative supply to consumers.
Distributions in time of disconnections, the causes of appearance and their
impact on the reliability of electricity supply to consumers have not been studied
up to the present and are not known.
Reliability of electricity supply to consumers can be provided only on the basis
of knowledge of the factors that have a noticeable impact on indicators of
reliability, which allows justified planning of measures to ensure the level of
confidence.
147
k pn
NC
v 1
NC
k 1
1k
nv
T nv
l 1
r 1
v 1
T1k NC 2 l T 2 l NC 3 r ... NC nv T nv
100 %.
(1)
v, duration
T nv , caused
148
average duration of refusals () the average frequency of rejections (), the average restoration refusals (), the average total time of refusals (T med). The results of
the calculation of reliability indicators are shown in Table 1 .
Table 1. Values of reliability indicators for examined network sectors
The
Seasonal values
examined
Indicator
network
Anual
sector
Spring Summer Autumn Winter
Total
, h
, h
Tmed, h
, h
, h
Tmed, h
, h
, h
Tmed, h
, h
, h
Tmed, h
, h
, h
Tmed, h
, h
, h
Tmed, h
0,92
3,49
0,26
3,81
5,88
5,76
1,02
5,95
8,22
5,36
1,53
7,28
4,40
4,48
0,98
4,01
2,46
2,39
1,03
4,87
3,99
3,64
1,09
5,19
1,12
1,23
1,71
3,54
6,97
4,48
4,66
6,29
8,73
7,01
5,60
8,04
4,64
3,47
2,92
6,95
5,78
4,37
2,90
4,29
7,03
3,67
4,22
3,63
1,09
3,28
1,59
3,58
5,52
5,41
2,36
5,59
7,72
5,04
1,53
6,84
4,13
4,20
0,98
3,77
2,31
2,24
1,03
4,57
3,74
3,42
1,09
4,87
1,23
1,35
1,88
3,88
7,64
4,92
5,11
6,89
9,57
7,69
6,15
8,82
5,09
3,81
3,21
7,62
6,34
4,80
3,18
4,70
7,71
4,02
4,63
3,98
4,36
9,35
0,47
3,70
26,01
20,56
1,26
6,18
34,23
25,10
1,36
7,75
18,26
15,96
1,14
5,58
16,89
13,80
1,22
4,61
22,47
14,75
1,52
4,42
149
Factors
2009
2010
2011
2012
Total
Nr
Description
Weathering
39,7
26,7
37,6
41,0
25,5
34,1
Defects in
equipment
25,0
34,1
23,4
21,0
34,0
27,5
22,0
20,7
18,5
23,2
20,9
Vandalism
4,5
4,7
4,9
4,9
4,1
4,6
Defects in
transport networks
3,1
4,3
4,6
4,7
3,7
4,0
1,7
1,4
2,7
2,9
2,1
2,1
1,2
1,7
1,2
2,3
2,0
1,6
1,5
1,7
2,1
1,7
1,8
1,7
1,5
1,6
1,1
1,5
1,8
1,5
10 Consumer Action
1,1
0,9
0,5
0,5
0,8
0,7
11
Electrical power
quality
0,4
0,5
0,6
0,6
0,5
0,5
12
Operating errors
0,3
0,4
0,4
0,5
0,5
0,42
7
8
9
Animal Action
Action of
mechanisms
Damages caused
by vegetation
150
151
[4] Popescu V., Gin A., Bodarev G., Reliability analysis of power of
distribution system the voltages of which is 6 and 10 kV, Intellectus No.1.
Chisinau, 2012, p 90-96.
[5] Secui D.C., The Sensitivity of the Electrical Substantionns Reliability
Indices at the Variation of the Circuit - Breakers Stucking Probability ,
Annals of the Oradea University, Fascicle of Energy Engineering, Vol.14,
Oradea, 2008.