Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
2.5
Page 1 of 9
Figure 2.5-1
The table below lists the connection methods and connection destinations of the I/O terminals of the
Timer Block (TM).
Table 2.5-1
(TM)
I/O
terminal
OUT
*1:
Connection Methods and Connection Destinations of the I/O Terminals of the Timer Block
Connection type(*1)
Data
Data
Condition
reference setting
testing
Output
terminal
Connection destination(*1)
Status
Terminal Process
manipulation connection
I/O
x
Software
I/O
Function
block
x: Connection available
Blank: Connection not available
Operations such as the timer start or stop can be performed from the sequence control block, calculation
block, and operation and monitoring functions. The block status which indicates an operating status can
also be referenced from other function blocks.
Status manipulation is the only connection method from the OUT terminal of the Timer Block (TM). Thus,
the Timer Block (TM) manipulates the status according to the action signals specified in the OUT
terminals. The logical value of the Timer Block (TM) becomes true when the preset timer function is in
time-up status (block status: CTUP).
The figure below shows an example of connection between the Timer Block (TM) and other sequence
control block.
Figure 2.5-2
Connection Example of Timer Block (TM) and Other Sequence Control Block
Every time the Timer Block (TM) with the tag name TM001 expires, the Software Counter Block (CTS) with
the tag name COUNT01 is increased by one count.
file:///C:/Program%20Files%20(x86)/Yokogawa/IA/iPCS/Products/CENTUMVP/Pro... 25/12/2014
Page 2 of 9
Process Timing
The process timing of Timer block is only based on periodical start period. The periodic start period is
based on high-speed scan period, medium-speed scan period (*1) and basic scan period.
*1:
The medium-speed scan period can only be used for the FFCS series, KFCS2, KFCS, LFCS2, and LFCS.
Set Parameter
Timer Property
The following describes the set parameters of the Timer Block (TM).
Preset time setpoint value (PH)
0 to 100000 (second or minute)
Pre-alarm setpoint value (DL)
PL to PH
The PL is the low-limit value (fixed at 0) of the timer elapsed time (PV).
Use the Function Block Detail Builder to set the unit for the preset time setpoint.
Timer Property
Select from Second timer or Minute timer.
Default is Second timer.
The table below describes the specified format of action signals and action description when giving action
commands to the Timer Block (TM) from sequence control blocks and the calculation block.
Table 2.5-2
Y/N
Action specification True/False
STOP
Action description
Y/True
N/False
Disable
Y/True
file:///C:/Program%20Files%20(x86)/Yokogawa/IA/iPCS/Products/CENTUMVP/Pro... 25/12/2014
Page 3 of 9
START
Element symbol.OP
RSTR
WAIT
*1:
N/False
Y/True
Restart command
N/False
Disable
Y/True
Pause command
N/False
Figure 2.5-3
Figure 2.5-4
The following describes an example of the timer start specified in the action signal column of the
sequence table.
file:///C:/Program%20Files%20(x86)/Yokogawa/IA/iPCS/Products/CENTUMVP/Pro... 25/12/2014
Figure 2.5-5
Page 4 of 9
An example of specifying the timer start in the action signal column of the sequence table
Figure 2.5-6
The following describes an example of specifying the timer stop in the action signal column of the
sequence table.
Figure 2.5-7
An example of specifying the timer stop in the action signal column of the sequence table
Figure 2.5-8
table
An example of specifying the timer pause in the action signal column of the sequence
file:///C:/Program%20Files%20(x86)/Yokogawa/IA/iPCS/Products/CENTUMVP/Pro... 25/12/2014
Figure 2.5-9
Page 5 of 9
The following describes an example of specifying the timer restart in the action signal column of the
sequence table.
Figure 2.5-10
table
An example of specifying the timer restart in the action signal column of the sequence
Preset Timer
The preset timer function notifies that the specified amount of time has elapsed. The content of the
notification includes the time-up status (CTUP) based on the preset time setpoint (PH) and the pre-alarm
status (PALM) which gives prior notices before reaching the preset time.
If one of the following conditions is satisfied for the timers remaining time (DV=PH-PV) when the block
status is counting (RUN), the pre-alarm status (PALM) or time-up status becomes true.
0<DVDL
Pre-alarm status (PALM)
DV=0
Time-up status (CTUP)
However, if the pre-alarm setpoint value (DL) is 0, the pre-alarm status (PALM) will not occur.
The timer block actions and the block statuses are illustrated as follows.
file:///C:/Program%20Files%20(x86)/Yokogawa/IA/iPCS/Products/CENTUMVP/Pro... 25/12/2014
Figure 2.5-11
Page 6 of 9
Figure 2.5-12
TIP
Timer Block Status with Option of Hold PALM in CTUP Status: FFCS Series/KFCS2/LFCS2
Inside the FCS, the block status of TM/CTS/CTP blocks is expressed in 32 bits.
file:///C:/Program%20Files%20(x86)/Yokogawa/IA/iPCS/Products/CENTUMVP/Pro... 25/12/2014
Figure 2.5-13
Page 7 of 9
Internal Bit Image for Block Status of TM/CTS/CTP Blocks: FFCS Series/KFCS2/LFCS2
If the check box of [TM/CTS/CTP blocks hold PALM after CTUP] is checked, the PALM hold bit
synchronizes with the CTUP bit (ON/OFF). The value of the data item [@BSTS] differs between the
checked [TM/CTS/CTP blocks hold PALM after CTUP] and the unchecked [TM/CTS/CTP blocks hold
PALM after CTUP] when the PALM hold bit is ON. If you refer to the block status from a Graphic
modifier conditional formula, a SEBOL program, or a supervisory computer, use the individual bit such
as the CTUP bit or the alphanumeric data BSTS, or uncheck the [TM/CTS/CTP blocks hold PALM after
CTUP] box.
After a snapshot-save in the test function, if you change the checkbox [TM/CTS/CTP blocks hold PALM
after CTUP] and snapshot-load, the setting in the checkbox [TM/CTS/CTP blocks hold PALM after CTUP]
and the bit image indicating the block status become inconsistent.
Operation 1
1. Check the check box of [TM/CTS/CTP blocks hold PALM after CTUP]. After that, start the FCS/FCS
simulator.
2. TM/CTS/CTP blocks go into CTUP status.
3. Snapshot-save.
4. Uncheck the [TM/CTS/CTP blocks hold PALM after CTUP]. After that, restart the FCS/FCS simulator.
5. Snapshot-load the data saved in the step 3.
After the step 5, the setting of the checkbox and the bit image indicating the block status become
inconsistent. Here, if the instrument faceplate for the TM/CTS/CTP is displayed on HIS, the block
status field is blank.
The setting of the checkbox and the bit image become consistent, and the block status is displayed
normally if:
For TM/CTP
The next scan starts, or RUN/STOP is ordered.
For CTS
One of PH/DL/PV is changed, or ACT. ON is executed in a sequence table or a logic chart.
Operation 2
1. Uncheck the check box of [TM/CTS/CTP blocks hold PALM after CTUP]. After that, start the FCS/FCS
simulator.
2. TM/CTS/CTP blocks go into CTUP status.
3. Snapshot-save.
4. Check the [TM/CTS/CTP blocks hold PALM after CTUP]. After that, restart the FCS/FCS simulator.
5. Snapshot-load the data saved in the step 3.
After the step 5, the setting of the checkbox and the bit image indicating the block status become
inconsistent. But [CTUP] is displayed in the block status field for TM/CTS/CTP.
The setting of the checkbox and the bit image become consistent if:
For TM/CTP
The next scan starts, or RUN/STOP is ordered.
For CTS
One of PH/DL/PV is changed, or ACT. ON is executed in a sequence table or a logic chart.
Periodic Action
Periodic Action
When timer block reaches time-up status (CTUP), the timer block can be restarted to count again.
This periodic action can be set using the Function Block Detail Builder.
file:///C:/Program%20Files%20(x86)/Yokogawa/IA/iPCS/Products/CENTUMVP/Pro... 25/12/2014
Page 8 of 9
Figure 2.5-14
Change in Timer Elapsed Time (PV) When Preset Time Setpoint (PH) is 8 Seconds
Data Items TM
The table below shows the data items of the Timer Block (TM):
Table 2.5-3
Data Item
MODE
Block mode
BSTS
ALRM
Range
Default
-----
O/S (AUT)
Block status
-----
STOP
Alarm status
-----
NR
file:///C:/Program%20Files%20(x86)/Yokogawa/IA/iPCS/Products/CENTUMVP/Pro... 25/12/2014
AFLS
-----
AF
Alarm detection
-----
AOFS
Alarm inhibition
-----
PV
Elapsed time
PL to PH
PH
0 to 100000 100000
DV
Remaining time
DL
PL
OPMK
Operation mark
UAID
User application ID
*1:
SEE
ALSO
Page 9 of 9
-PL to PH
PH
PL to PH
PL
Fixed at 0.
0 to 64
-----
For more information about valid block modes of the timer block, refer to:
2.1.2, "Block Mode of Sequence Control Blocks"
Block Status
Symbol
Name
Description
PAUS
Pause
Timer is paused
PALM
CTUP
Time Up
NR
Normal
RUN
Run
STOP
Normal
file:///C:/Program%20Files%20(x86)/Yokogawa/IA/iPCS/Products/CENTUMVP/Pro... 25/12/2014