Sei sulla pagina 1di 52

Analog Addressable Panel

SLC
Wiring Manual
Document 52282
06/26/09
Rev:
P/N 52282:B

B
ECN 07-201

Important Limitations
While a fire alarm system may lower insurance rates,
it is not a substitute for fire insurance!
An automatic fire alarm system- typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control panel with
remote notification capability - can provide early warning of
a developing fire. Such a system, however, does not
assure protection against property damage or loss of life
resulting from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise
following the recommendations of the current edition of the
National Fire Protection Association, Standard 72 (NFPA
72), manufacturers recommendations, State and local
codes, and the recommendations contained in the Guide
for Proper Use of System Smoke Detectors, which are
made available at no charge to all installing dealers. These
documents can be found at http://www.systemsensor.co/
html/applict.html. A study by the Federal Emergency
Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off
in as many as 35% of all fires. While fire alarm systems are
designed to provide early warning against fire, they do not
guarantee warning or protection against fire. A fire alarm
system may not provide timely or adequate warning, or
simply may not function, for a variety of reasons.
Smoke Detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind
walls, on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor
of a building. A second-floor detector, for example, may not
sense a first-floor or basement fire.
Particles of combustion or smoke from a developing
fire may not reach the sensing chambers of smoke
detectors because:

Barriers such as closed or partially closed doors,


walls, or chimneys may inhibit particle or smoke flow.

Smoke particles may become cold, stratify, and not


reach the ceiling or upper walls where detectors are
located.

Smoke particles may be blown away from detectors by


air outlets.

Smoke particles may be drawn into air returns before


reaching the detector.
The amount of smoke present may be insufficient to
alarm smoke detectors. Smoke detectors are designed to
alarm at various levels of smoke density. If such density
levels are not created by a developing fire at the location of
detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have
sensing limitations. Detectors that have photoelectronic
sensing chambers tend to detect smoldering fires better
than flaming fires, which have little visible smoke.
Detectors that have ionizing-type sensing chambers tend
to detect fast-flaming fires better than smoldering fires.
Because fires develop in different ways and are often
unpredictable in their growth, neither type of detector is
necessarily best and a given type of detector may not
provide adequate warning of a fire.
2

Smoke detectors cannot be expected to provide adequate


warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and
violent explosions (caused by escaping gas, improper
storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once per
year by a qualified fire protection specialist. Heat detectors
are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the
system for the connection of alarm transmission wiring,
communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm
system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another floor
of a building. Any warning device may fail to alert people
with a disability or those who have recently consumed
drugs, alcohol or medication. Please note that:

Strobes can, under certain circumstances, cause


seizures in people with conditions such as epilepsy.

Studies have shown that certain people, even when


they hear a fire alarm signal, do not respond or
comprehend the meaning of the signal. It is the
property owners responsibility to conduct fire drills
and other training exercise to make people aware of
fire alarm signals and instruct them on the proper
reaction to alarm signals.

In rare instances, the sounding of a warning device


can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails the system will operate from
standby batteries only for a specified time and only if the
batteries have been properly maintained and replaced
regularly.
Equipment used in the system may not be technically
compatible with the control panel. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission
systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance is
required per the manufacturers recommendations, and UL
and NFPA standards. At a minimum, the requirements of
NFPA 72 shall be followed. Environments with large
amounts of dust, dirt or high air velocity require more
frequent maintenance. A maintenance agreement should
be arranged through the local manufacturers
representative. Maintenance should be scheduled monthly.

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and
associated equipment may be damaged by removing
and/or inserting cards, modules, or interconnecting
cables while the unit is energized. Do not attempt to
install, service, or operate this unit until manuals are read
and understood.
CAUTION - System Re-acceptance Test after
Software Changes: To ensure proper system operation,
this product must be tested in accordance with NFPA 72
after any programming operation or change in sitespecific software. Reacceptance testing is required after
any change, addition or deletion of system components,
or after any modification, repair or adjustment to system
hardware or wiring. All components, circuits, system
operations, or software functions known to be affected
by a change must be 100% tested. In addition, to ensure
that other operations are not inadvertently affected, at
least 10% of initiating devices that are not directly
affected by the change, up to a maximum of 50 devices,
must also be tested and proper system operation
verified.
This system meets NFPA requirements for operation at
0-49 C/32-120 F and at a relative humidity 93% 2%
RH (non-condensing) at 32 C 2 C (90 F 3 F).
However, the useful life of the systems standby batteries
and the electronic components may be adversely
affected by extreme temperature ranges and humidity.
Therefore, it is recommended that this system and its
peripherals be installed in an environment with a normal
room temperature of 15-27 C/60-80 F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate
more than a 10% I.R. drop from the specified device
voltage.
Follow the instructions in the installation, operating,
and programming manuals. These instructions must be
followed to avoid damage to the control panel and
associated equipment FACP operation and reliability
depend upon proper installation.

Survivability
Per the National Fire Alarm Code, NFPA 72, all circuits
necessary for the operation of the operation of the
notification appliances shall be protected until they enter
the evacuation signaling zone that they serve. Any of the
following methods shall be considered acceptable as
meeting these requirements:
1) A 2-hour rated cable or cable system
2) A 2-hour rated enclosure
3) Performance alternatives approved by Authority
Having Jurisdiction (AHJ).
Like all solid state electronic devices, this system
may operate erratically or can be damaged when
subjected to lightning induced transients. Although no
system is completely immune from lightning transients
and interference, proper grounding will reduce
susceptibility. Overhead or outside aerial wiring is not
recommended, due to an increased susceptibility to
nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing
or inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, or printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in
reduced terminal contact pressure and difficulty with
screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed
from the body. Use static suppressive packaging to
protect electronic assemblies removed from the unit.
Precau-D2-8-2008

FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual may
cause interference to radio communications. It has been
tested and found to comply with the limits for Class A
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when devices are
operating in a commercial environment. Operation of this
equipment in a residential area is likely to cause
interference, in which case the user will be required to
correct the interference at his or her own expense.

Canadian Requirements
This digital apparatus does not exceed the Class A limits
for radiation noise emissions from digital apparatus set
out in the Radio Interference Regulations of the
Canadian Department of Communications.
Le present appareil numerique nemet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la Classe A prescrites dan le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.

Gamewell-FCI, Velociti, and E3 Series are registered trademarks of Honeywell International Inc. Echelon is a registered trademark and
LonWorks is a trademark of Echelon Corporation. ARCNET is a registered trademark of Datapoint Corporation. Microsoft and Windows are
registered trademarks of the Microsoft Corporation.
2008 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Software Downloads
In order to supply the latest features and functionality in fire alarms and life safety technology to our customers, we make
frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest
features, we strongly recommend that you download the most current version of software for each product prior to
commissioning any system. Contact Technical Support with any questions about software and the appropriate version for
a specific application.

Documentation Feedback
Your feedback helps us keep out documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
Product name and version number (if applicable)

Printed manual or online Help

Topic Title (for online Help)

Page number (for printed manual)

Brief description of content you think should be improved or corrected

Your suggestion for how to correct/improve documentation

Send email messages to:


FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Table of Contents
Section 1 Introduction ......................................................................................................7
1.1: Scope.................................................................................................................................................... 7
1.2: Overview.............................................................................................................................................. 7
1.3: Polling Protocols.................................................................................................................................. 7
1.4: Input Devices ....................................................................................................................................... 7
1.4.1: Addressable Monitor Modules .................................................................................................. 7
1.4.2: Multi-input Transponder Modules............................................................................................. 8
1.4.3: Manual Pull Stations.................................................................................................................. 8
1.5: Output Devices .................................................................................................................................... 8
1.5.1: Control Modules ........................................................................................................................ 8
1.5.2: Relay Modules........................................................................................................................... 8
1.5.3: Multi-output Transponder Modules........................................................................................... 8
1.6: Detectors .............................................................................................................................................. 9
1.6.1: Isolator Modules ........................................................................................................................ 9
1.6.2: Plug-in Detector Bases .............................................................................................................. 9
1.6.3: Analog Addressable Detectors .................................................................................................. 9
1.7: Reference Documentation ................................................................................................................. 10
1.8: SLC Capacity....................................................................................................................................... 11
1.9: SLC Performance................................................................................................................................. 11

Section 2 Wiring Requirements .......................................................................................12


2.1: Recommended SLC Wiring ................................................................................................................ 12
2.2: Two-Wire SLC - Style 4 (Class B) ...................................................................................................... 12
2.2.1: Measuring Circuit Resistance.................................................................................................... 12
2.2.2: Measuring Total Wire Length ................................................................................................... 12
2.3: Four-Wire SLC Style 6 & 7 (Class A)................................................................................................. 13
2.3.1: Measuring Circuit Resistance.................................................................................................... 13
2.3.2: Measuring Total Wire Length ................................................................................................... 13
2.4: SSM Terminal Blocks.......................................................................................................................... 14
2.4.1: SSM610-2/4............................................................................................................................... 14
2.4.2: SSM-2/2E .................................................................................................................................. 15
2.4.3: IF602SS .................................................................................................................................... 15

Section 3 SLC Circuits with Isolators .............................................................................16


3.1: Overview.............................................................................................................................................. 16
3.2: Fault Isolator Module - M500X........................................................................................................... 16
3.2.1: Wiring an Isolator Module ........................................................................................................ 16
3.3: Isolator Detector Bases ........................................................................................................................ 17
3.3.1: How an Isolator Base Works ..................................................................................................... 17
3.4: NFPA Style 4 SLC Using M500X Modules ........................................................................................ 18
3.5: NFPA Style 6 SLC Using M500X Modules ....................................................................................... 19
3.6: NFPA Style 7 SLC Using an Isolating Device .................................................................................... 20

Section 4 SLC Circuits without Isolators ........................................................................21


4.1: Overview.............................................................................................................................................. 21
4.2: NFPA Style 4 SLC ............................................................................................................................... 21
4.3: NFPA Style 6 SLC ............................................................................................................................... 22

Section 5 Monitor Modules ..............................................................................................23


5.1: Description........................................................................................................................................... 23
5.1.1: AMM-4F Monitor Module ........................................................................................................ 23
5.1.2: AMM-2IF Dual Monitor Module .............................................................................................. 23
5.1.3: AMM-4SF Monitor Module...................................................................................................... 23
5.1.4: AMM-2F Monitor Module ........................................................................................................ 23
5.2: Setting an SLC Address for a Module ................................................................................................. 24

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Table of Contents

5.3: AMM-4F Wiring Diagram: NFPA Style B IDC .................................................................................. 25


5.4: AMM-4F Wiring Diagram: NFPA Style D IDC .................................................................................. 26
5.5: AMM-2IF Wiring Diagrams NFPA Style B IDC ................................................................................ 27
5.6: AMM-4SF Wiring Diagrams: NFPA Style B IDC .............................................................................. 28
5.7: AMM-4SF Wiring Diagrams: NFPA Style D IDC .............................................................................. 29

Section 6 Control Modules ..............................................................................................30


6.1: Description ........................................................................................................................................... 30
6.2: Installation............................................................................................................................................ 30
6.2.1: Setting an SLC address for AOM-2SF Modules ....................................................................... 30
6.2.2: Wiring a Notification Appliance Circuit (NAC) with AOM-2SF
Modules ............................................................................................................................. 30
6.3: Wiring AOM-2SF Modules ................................................................................................................. 31
6.3.1: Wiring a Style Y NAC (Two-Wire) .......................................................................................... 31
6.3.2: Wiring a Style Z NAC (Four-Wire)........................................................................................... 32

Section 7 Relay Module ....................................................................................................33


7.1: Description ........................................................................................................................................... 33
7.2: Installation............................................................................................................................................ 33
7.2.1: Setting an SLC Address for the AOM-2RF Module ................................................................. 33
7.2.2: Wiring the AOM-2RF Module (Form-C Relay) ....................................................................... 33

Section 8 Intelligent Detector Bases ...............................................................................34


8.1: Description ........................................................................................................................................... 34
8.2: Installation............................................................................................................................................ 34
8.2.1: Wiring a Detector Base.............................................................................................................. 34
8.2.2: Wiring an Isolator Base ............................................................................................................. 36
8.3: Wiring a Sounder Base......................................................................................................................... 37
8.4: Wiring a Relay Base............................................................................................................................. 37
8.4.1: Setting the Detector Address ..................................................................................................... 38

Section 9 Addressable Manual Pull Station ...................................................................39


9.1: Description ........................................................................................................................................... 39
9.2: Installation............................................................................................................................................ 39
9.2.1: Setting an SLC address .............................................................................................................. 39
9.2.2: Wiring a Manual Pull Station .................................................................................................... 39

Appendix A Power Considerations .................................................................................40


A.1: Supplying Power to 24 VDC Detectors and NACs ........................................................................... 40
A.2: Supervising 24 VDC Power................................................................................................................ 41
A.2.1: Power Supervision Relay.......................................................................................................... 41

Appendix B Compatibility of Panels and SLC Devices .................................................44


B.1: Velociti Modules ................................................................................................................................. 44

Appendix C.1 Electrical Specifications ..........................................................................46


Index ................................................................................................................................... 49

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Section 1 Introduction
1.1 Scope
This document covers the installation and wiring of various Signaling Line Circuit (SLC) devices, when
used with the following Gamewell-FCI Fire Alarm Control Panels:

IdentiFlex 602 Series


IdentiFlex 610
IdentiFlex 632/654/658

This document also provides basic information that applies to Gamewell-FCI signaling line circuits in
general, such as the branch resistance measurements.
NOTE: See Section 2.4, SSM Terminal Blocks, on page 14 for basic panel-end SLC connections.
Additional information about each control panel can be found in the respective installation manual. See
Table 1.1 on page 10.

1.2 Overview
Communication between the control panel and addressable monitor and control devices takes place via
a Signaling Line Circuit (SLC), which can be wired to meet the requirements of NFPA Style 4, Style 6,
or Style 7*. All panel wiring should be in accordance with Article # 760 of the National Electrical Code.
*Style 7 wiring requires the use of the M500X Fault Isolator Modules.

1.3 Polling Protocols


Velociti is a patented system that greatly enhances the speed of communication between the analog
addressable devices. Communication is in a grouped fashion. If one of the devices within the group has
new information, the panel CPU stops the group poll and concentrates on single points.

1.4 Input Devices


1.4.1 Addressable Monitor Modules
These modules allow the control panel to monitor entire circuits of conventional alarm initiating
devices, such as manual pull stations, smoke sensors, heat sensors, waterflow and supervisory devices.

AMM-4F - Addressable Monitor Module


A Class-B or Class-A fault tolerant initiating device circuit (IDC) for normally open contact fire
alarm and supervisory devices, or either normally open or normally closed security devices.

AMM-2IF - Addressable Dual Monitor Module


Provides two independent Class-B initiating device circuits (IDC) at two separate, consecutive
addresses. Capable of monitoring normally open contact fire alarm and supervisory devices, or
either normally open or normally closed security devices.

AMM-2F- Addressable Monitor Module


Provides a Class-B initiating device circuit for normally open contact fire alarm and security
devices. Can be installed in a single gang junction box directly behind the monitored unit without
rigid mounting.

AMM-4SF - Addressable Monitor Module


Allows addressable panels to interface and monitor two-wire conventional smoke sensors.
Transmits status of one full zone of conventional sensors back to the control panel. Two-wire
sensors being monitored must be UL-compatible with this module.

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Introduction

Output Devices

1.4.2 Multi-input Transponder Modules


The following modules combine multiple inputs into a single device.

MMI-10F - Multi-Mod Ten Input Monitor Module


Supervises ten Class-B addressable Initiating Device Circuits (IDC) which monitor normally
open contact initiating devices. Velociti capable multi-input transponder module; for use on the
SLC. This module is capable of participating in degraded mode where supported by FACP.
Each monitor operates independently from the others and has its own unique address.

MMI-6SF - Multi-Mod Six Zone Interface Module


Allows an intelligent alarm system to monitor six zones of conventional two-wire sensors.
Velociti capable multi-input transponder module; for use on the SLC.

For further information on these modules, see the installation document included with each.

1.4.3 Manual Pull Stations


The MS-7ASF is a single-action pull station that, when activated, provides an address and its
location to the control panel. A status LED is visible through the door handle, and there is an
addressable monitor module mounted inside the pull station to facilitate service and replacement.
Velociti capable. The MS-7AF is a dual-action pull station.

1.5 Output Devices


1.5.1 Control Modules
Through this addressable module, the control panel can selectively activate Notification Appliance
Circuits (NAC).

AOM-2SF - Addressable Output Relay Supervised Control Module


This module is used to switch an external power supply, which can be a separate DC power
supply, to notification appliances. The AOM-2SF has two pairs of output termination points
available for fault-tolerant wiring and a panel-controlled LED indicator.

When using the AOM-2SF Modules as a Notification Appliance Circuit (NAC), the circuit
isolators must be installed in compliance with the Survivability from Attack requirements per
the National Fire Alarm Code, NFPA 72.

1.5.2 Relay Modules


This addressable module provides the control panel with a dry-contact output for activating a
variety of auxiliary devices.

AOM-2RF - Addressable Output Relay Control Module


Allows a compatible control panel to switch discrete contacts by code command. The relay
contains two isolate sets of Form-C contacts, which operate as a DPDT switch and are rated in
accordance with the table in the manual. Circuit connections to the relay contacts are not
supervised by the module.

1.5.3 Multi-output Transponder Modules


The following addressable modules combine multiple outputs in a single device.

MMO-6SF - Multi-Mod Six Signal Output Module Controls six Class-B or three Class-A
NAC circuits. Velociti capable multi-output transponder module; for use on the SLC. Each
module has terminals for connection to an external supply circuit for powering devices on its
NAC. A short circuit protection monitor for each module protects the external power supply
against short circuit conditions on the NAC.
Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Introduction

Detectors

MMO-6RF - Multi-Mod Relay Output Module; Controls six Form-C relays. Velociti
capable multi-output transponder module; for use on the SLC.

1.6 Detectors
1.6.1 Isolator Modules
Isolator Modules permit a short-circuited section of the SLC to be fault isolated from the remainder
of the SLC, allowing critical components to function in the event of a circuit fault. Isolator modules
are required to meet the requirements of an NFPA Style 7 circuit.

M500X Style 7 Isolator Module

1.6.2 Plug-in Detector Bases


Plug-in type bases provide a connection between the SLC and a variety of addressable sensors
which are snapped into place. Use of standard and isolator bases depends upon which NFPA SLC
style is required. Sounder and relay bases are similar to standard bases, but have sound or auxiliary
relay capabilities.

Standard Base - Models (standard small diameter base) and ADB-FLF (standard large
diameter base)

Filtrex Base - Model ADB-FILTREXF

Isolator Base - Model B224BI isolator base

Sounder Base - Models BH(2) (standard sounder base) and BHT(2) (base with temporal
sounder)

Relay Base - Model B224RB relay base

1.6.3 Analog Addressable Detectors

MCS-Acclimate (Acclimate) - multi-detector that combines a photoelectric sensing


chamber and fixed temperature heat detection (135F / 57.2C). Velociti capable.

ASD-IL2F- addressable smoke sensor that incorporates an ionization sensing chamber.


Designed to provide open area protection. Velociti capable.

ASD-PL2F - addressable smoke sensor that uses a photoelectric sensing chamber. Designed to
provide open area protection. Velociti capable. The ASD-PTL2F adds thermal sensors that
will alarm at a fixed temperature of 135 F (57.2C).

ATD-L2F - Intelligent thermistor sensing circuit for fast response. Designed to provide open
area protection with 50 foot spacing capability. A fixed temperature sensor with 135F
(57.2C) fixed temperature alarm. Velociti capable. The ATD-RL2F incorporates a thermal
rate of rise of 15F (8.3C). Velociti capable. The ATD-HL2F is a high temperature sensor
with 190F (87.8C) fixed temperature alarm.

ADPF - Low-flow Photoelectric Duct Sensor, with extended speed range of 1004000 FPM
(30.481219.2 MPM). ADPRF adds a relay.

ASD-FiltrexF - A special smoke sensor that provides early warning smoke detection in hostile
environments where traditional smoke sensors are not practical. Velociti capable.

ABD-2F - Reflected Beam sensor; Long range projected beam smoke sensor provides open
area protection. Consists of a transmitter/receiver unit and a reflector. The ABD-RT2F is the
same as the ABD-2F, but comes with a test feature. The ABD-RT2F requires a separate 24V
power supply.

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Introduction

Reference Documentation

1.7 Reference Documentation


The table below provides a list of documents referenced in this manual, as well as documents for
selected other compatible devices. The document series chart provides the current document
revision. A copy of this document is included in every shipment.
Table 1.1 Reference Documentation
Fire Alarm Control Panel
(FACP) and Main Power
Supply Installation
Description
IdentiFlex 602 Manual
IdentiFlex 602SS Analog/Addressable FACP Manual
IdentiFlex 610 Manual
IdentiFlex 610 FACP Manual
IdentiFlex 632/654/658
600 Series Systems, Flex 624/628, 654 & 658
Manual
Conventional Analog/Addressable FACP Manual
SLC Devices
ASD-PL2F
Analog Addressable Photoelectronic Smoke Sensor
ASD-PTL2F
Analog Addressable Photoelectronic Smoke Sensor, with
Thermal Sensing
MCS-ACCLIMATE
Multi-Criteria Analog, Addressable Sensor
ASD-IL2F
Analog, Addressable Ionization Smoke Sensor
ATD-L2F
Addressable Thermal Sensor
ATD-RL2F
Addressable Thermal Sensor
ASD-FILTREXF
Harsh Environment Analog Addressable Photoelectronic
Smoke Sensor
ATD-HL2F
Addressable Thermal Sensor
M500X
Style 7 Isolator Module
ADB-FLF
Plug-In Detector Base
ADB-FILTREXF
Detector Base for use with ASD-FiltrexF
Plug-In Detector Base
B224BI
Plug-In Isolator Detector Base
BH(2)
Sounder Base
BHT(2)
Temporal Tone Sounder Base
B224RB
Plug-In Relay Detector Base
ADPF
Analog Addressable Low Flow Duct Detector
ADPRF
Analog Addressable Low Flow Duct Detector
AMM-4F
Addressable Monitor Module
AOM-2SF
Addressable Output Relay Supervised Control Module
AMM-2F
Addressable Monitor Module
AOM-2RF
Addressable Output Relay Control Module
AMM-4SF
Addressable Monitor Module
AMM-2IF
Addressable Dual Monitor Module
MMI-10F
Multi-Mod Ten Input Monitor Module
MMO-6RF
Multi-Mod Relay Output Module
MMI-6SF
MMO-6SF
ABD-RT2F
ABD-2F
MS-7ASF
MS-7AF

10

Multi-Mod Six Zone Interface Module


Multi-Mod Six Signal Output Module
Single-Ended Reflected Type Beam Smoke Sensor
Single-Ended Reflected Type Beam Smoke Sensor
Non-Coded Fire Alarm Stations
Non-Coded Fire Alarm Stations

Document Number
52358
GW71810
GW72122

I56-3560-001R-A
I56-3560-001R-A
I56-3560-001R_A
I56-3556-001R_A
I56-3557-001R_A
I56-3557-001R_A
I56-2754-002R_A
I56-3557-001R_A
I56-3557-001R_A
I56-2753-001R_A
I56-2758-001R_A
I56-0357-008_R
I56-0725-012R
I56-0491-007R
I56-1367-004R
I56-2815-000R
I56-2747-001R_A
I56-2746-001R_A
I56-3553-001_A
I56-3550-001_A
I56-3554-001_A
I56-3551-002_A
I56-3552-002_A
I56-2750-002_A
I56-2743-001_A
I56-2739-002_A
I56-2742-001_A
I56-7740-002_A
I56-2741-001R_A
I56-2741-001R_A
I56-3564-001_A
I56-3564-001_A

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Introduction

SLC Capacity

1.8 SLC Capacity


Each Velociti SLC is capable of supporting 99 sensors and 99 I/O module addresses.

1.9 SLC Performance


SLC performance (Style 4, Style 6, or Style 7) depends on the configuration of the circuit and the
components on the circuit.
NOTE: SLC operation meeting Style 7 requirements isolates each addressable device on the
SLC from faults that may occur on the SLC.

Wiring style requirements are determined by national and local codes. Consult with the Authority
Having Jurisdiction before wiring the SLC. See Section 2, Wiring Requirements, on page 12, for
more information.

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

11

Section 2 Wiring Requirements


2.1 Recommended SLC Wiring
1.

Total cable length per circuit: 12,000 feet maximum; including all Class B T-tap runs and Class A
returns.

2.

Use unshielded twisted cable, even when in conduit.

3.

Unshielded twisted cable required on all open wiring runs involving 1,000 ft. or more.

4.

Avoid running circuits parallel with power wiring for any distance.

5.

Avoid running circuits parallel with cables having high switching rates.

6.

Avoid running circuits parallel with fluorescent fixtures.

7.

Avoid running signaling line circuits parallel with notification appliance circuit wiring.

8.

Shield notification appliance circuit wiring even if in conduit, if run together with signaling line
circuits.

9.

Maximum total conductor resistance (out and back) for a circuit is 25 ohms.

10. Maximum total circuit capacitance is 1.0 F line to line and line to ground.

2.2 Two-Wire SLC - Style 4 (Class B)


2.2.1 Measuring Circuit Resistance
T-tapping of the SLC wiring is permitted for two-wire Style 4 configurations. The total DC resistance
from the control panel to each branch end cannot exceed 25 ohms. Measure DC resistance as detailed
and shown below:
1.

With power removed, short the termination point of one branch at a time and measure the DC
resistance from the beginning of the SLC to the end of that particular branch.

2.

Repeat this procedure for all remaining branches in the SLC.

In Figure 2.1, Branches A, B, and C all begin at the SLC terminal, even though Branch B is T-tapped.

SLC-meas5.cdr

Branch A

Branch B

Branch C

SLC Out

Branch
Short Point

SLC Terminal
Block

L2

L1

Figure 2.1 Measuring DC Resistance of a Two-Wire SLC

2.2.2 Measuring Total Wire Length


The total wire length of all combined branches of one SLC cannot exceed 25 ohms. Determine the total
length in each SLC by summing all wire segments. In Figure 2.1, the picture on the right shows an SLC
with 3 branches. Figure 2.2 shows the same SLC divided into segments. The total length of the SLC is
determined by adding the lengths of Segment 1 + Segment 2 + Segment 3 + Segment 4 + Segment 5. No
segment should be summed twice.

12

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Wiring Requirements

Four-Wire SLC Style 6 & 7 (Class A)

Branch C

Branch B

Segment
Five

Segment
One

Segment
Four

Segment
Three

Segment
Two

SLC Terminal Block

SLC-meas2.cdr

Branch A

Figure 2.2 Measuring the Total Wire Length - Two-wire SLC

2.3 Four-Wire SLC Style 6 & 7 (Class A)


2.3.1 Measuring Circuit Resistance
The total DC resistance of the SLC pair cannot exceed 25 ohms. Measure DC resistance as detailed
and shown below.
1.

Disconnect the SLC channel B (Out) and SLC channel A (Return) at the control panel.

2.

Short the SLC at the last device and measure the resistance at SLC Out. Record resistance and
remove the short.

3.

Short the SLC at the first device and measure the resistance at SLC return. Record resistance
and remove the short.

The maximum DC resistance of the SLC is the higher of 2 and 3.


First
Device

SLC Out

STEP 2
Last
Device
SLC Return
Short Point

First
Device

STEP 3
SLC Return

SLC-meas5.cdr

SLC Out

Last
Device

Figure 2.3 Measuring DC Resistance of a Four-Wire SLC

2.3.2 Measuring Total Wire Length


The total wire length in a four-wire SLC cannot exceed the limits set forth in each systems
instruction manual. Figure 2.4 identifies the output and return circuits from the SLC terminal on the
SSM.

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

13

Wiring Requirements

SSM Terminal Blocks

SLC channel A
(return circuit)

SLC channel B
(output circuit)

SLC Terminal
Block
L2

L2R

L1

L1R

Figure 2.4 Measuring the Wire Length Four-Wire SLC

2.4 SSM Terminal Blocks

4L2
4L1
GND
+24

4L2R
4L1R
GNDR
+24R

3L2R
3L1R
GNDR
+24R

3L2
3L1
GND
+24

P7
JP16
JP15
JP14
JP13

JP12
JP11
JP10
JP9

JP8
JP7
JP6
JP5

JP4
JP3
JP2
JP1

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

SLC4

P8

P6

P5

Loop3

Loop2

P4

P3

P2

P1

SLC1

14

2L2
2L1
GND
+24

1L2
1L1
GND
+24

1L2R
1L1R
GNDR
+24R

2L2R
2L1R
GNDR
+24R

2.4.1 SSM610-2/4

Wiring Requirements

SSM Terminal Blocks

2.4.2 SSM-2/2E
1

SSM-2

+24

3L1R

3L2R

+24
GND

GNDR

+24R

3L2

1L2
+24R

3L1

1L1

GNDR

GND

1L1R

4L2
+24R
GNDR
4L1R

16 15 14 13 12 11 10

4L1

+24

16 15 14 13 12 11 10

SSM-2E

GND

1L2R
+24
GND
2L1
212
+24R
GNDR
2L1R
2L2R

4L2R

2.4.3 IF602SS
TB5

1
2
3
4
5
6
7
8

SLC 1

SLC 1
or
SLC 2

Terminal #

Designation

TB-5

+24V

+24V Device power

or

GND

+24V Device power common

TB-6

1L1

Addressable line (-)

1L2

Addressable line (+)

+24VR

GNDR

+24V Device power return

1L1R

Addressable line (-) return

1L2R

Addressable line (+) return

TB6 1
2
3
4
5
6
7
8

SLC 2

Description

+24V Device power return

Notes:
1.

For SLC 1: Jumpers JMP 1 - 4 must be installed for Class B


operation. Remove for Class A operation.

2.

For SLC 2: Jumpers JMP 5 - 8 must be installed for Class B


operation. Remove for Class A operation.

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

15

Section 3 SLC Circuits with Isolators


3.1 Overview
There are two isolator devices used to protect critical elements of the SLC from faults on other SLC
branches or segments:

Fault Isolator Module M500X

Isolator Detector Base B224BI

A Fault Isolator Module on both sides of a device, or the combination of an Isolator Base and Isolator
Module are required to comply with NFPA Style 7 requirements.

CAUTION: If the relay or sounder bases are not used, a maximum of 25 addressable devices can be
connected between the Isolator Modules and/or Bases. When the relay or sounder bases are used,
the maximum number of addressable devices that can be connected between the Isolators is reduced
to seven. Due to the heavy current draw of the ASD-PTL2F Multi-Sensor Detector, the maximum
number of these detectors that can be installed between the isolator modules is reduced to two (2).
Isolator modules will not function properly when these limits are exceeded.

3.2 Fault Isolator Module - M500X


The module continuously monitors the circuit connected to the Terminals 3() and 4(+). Upon powerup, an integral relay is latched on. The module periodically pulses the coil of this relay. A short circuit
on the SLC resets the relay. The module detects the short and disconnects the faulted SLC branch or
segment by opening the positive side of the SLC (Terminal 4). This isolates the faulty branch from the
remainder of the circuit preventing a communication problem with all other addressable devices on the
remaining branches (labeled Continuation of the SLC in the figure below). During a fault condition,
the control panel registers a trouble condition for each addressable device which is isolated on the SLC
segment or branch. Once the fault is removed, the module automatically reapplies power to the SLC
branch or segment.

3.2.1 Wiring an Isolator Module


Figure 3.1 shows a Style 4 example for wiring of an Isolator Module:
Continuation
of the SLC

IN
IN
OUT
SLC-isowire.cdr

OUT

Isolated branch
of the SLC

SLC

Figure 3.1 Wiring the Isolator Module

16

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

SLC Circuits with Isolators

Isolator Detector Bases

3.3 Isolator Detector Bases


Isolator detector bases prevent an entire signaling line circuit from being disabled when a short
circuit occurs. This is accomplished by isolating that part of the circuit containing the short from
the remainder of the circuit. These bases also automatically restore the entire circuit when the cause
of the short circuit is corrected.
B224BI is an intelligent isolator base used with the Velociti detectors.

3.3.1 How an Isolator Base Works


If a short circuit fault occurs at point X, devices A, B, C & detector 2 will cease to function and
display a trouble warning at the control panel. Devices D, E, F & detectors 1, 3, 4, and 5 will
remain normal as they are served by SLC Return.
If a short circuit fault occurs at point Y, all devices will continue to function.
If a short circuit fault occurs at point Z, only detector 4 will cease to function.

Sensor 5

Sensor 2
Y

Sensor 4
SLC Out

Sensor 3

SLC Return
L2 L1

SSM

L2R L21

Isolator Base

Non-Isolating Device

Short-circuit path

SLC-isowork.wmf

Sensor 1

NOTE: For information on wiring an isolator base, refer the installation instructions for this
device.

Figure 3.2 Isolator Base Circuit: Sample Style 6 Wiring

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

17

SLC Circuits with Isolators

NFPA Style 4 SLC Using M500X Modules

3.4 NFPA Style 4 SLC Using M500X Modules


A variation of a Style 4 operation using isolator modules to protect each branch of the SLC. Refer
to Figure 3.1 on page 16 for M500X wiring and to Section 3.1, Overview for limitations.

M500X
Isolated Branch

Two-wire Addressable Detector

M500X
Isolated Branch

Addressable Pull Station


M500X

L1 L2

SLC-style4iso.cdr

Isolated Branch

SSM

Figure 3.3 NFPA Style 4 SLC Using Isolator Modules

18

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

SLC Circuits with Isolators

NFPA Style 6 SLC Using M500X Modules

3.5 NFPA Style 6 SLC Using M500X Modules


A variation of Style 6 operation using the isolator modules to protect a section of the SLC. By
flanking each group of devices with the M500X fault isolator modules, each group is protected
from faults that may occur in the other groups. For example, a fault in Section B will not affect
Sections A & C. The isolator modules on either side of Section B will open the SLC. Section A will
still operate from power on the SLC Outside and Section C will operate from the SLC Return side.

A combination of isolator modules and isolator bases may be used.

T-tapping is NOT allowed within the Style 6 configuration.

M500X modules shall be within 20 feet (6.1 meters) of device and the wire must be enclosed
in metal conduit.

M500X

M500X

Section B
Two-wire
Addressable
Sensor

Section C

Addressable
Pull Station

Section A

M500X

M500X
SLC Out

L1

L2

L2R L1R

SSM

SLC-style6iso.cdr

The first isolator module on SLC Out


and SLC Return must be in conduit.

SLC Return

Figure 3.4 NFPA Style 6 SLC Using M500X Modules

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

19

SLC Circuits with Isolators

NFPA Style 7 SLC Using an Isolating Device

3.6 NFPA Style 7 SLC Using an Isolating Device


Style 7 operation requires using a combination of isolator detector bases and isolator modules or
isolator modules before and after a non-isolator device. Flanking each device with an isolator
provides fault protection to all other devices on the loop.

T-tapping is NOT allowed within the Style 7 wiring configuration.

When a non-isolator base or pull station is used, install M500X modules on both sides of
devices.

When an isolator base is used in conjunction with an isolator module, install M500X module
as shown in Figure 3.5.

There must be a close-nipple connection between a device and the isolator bases or modules
that protect it.

M500X

1
Two-wire Isolator
Sensor Base

Addressable
Pull Station

Addressable
Sensor

M500X

M500X

M500X

M500X

M500X

M500X
SLC Out

The first isolator module on SLC Out


and SLC Return must be connected
within 20 feet (6.1 m) of the FACP
enclosure in conduit.

SLC Return

L1 L2

L2R L1R

SSM

SLC-style7iso.cdr

NOTE: For additional information, refer the installation instructions for this device.

Figure 3.5 NFPA Style 7 SLC


20

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

SLC Circuits without Isolators

Overview

Section 4 SLC Circuits without Isolators


4.1 Overview
This chapter concerns itself with the two styles of circuits that do not require isolation devices:

NFPA 72 Style 4

NFPA 72 Style 6

4.2 NFPA Style 4 SLC


NFPA Style 4 requirements can be met by using the diagram below.

T-tapping of the SLC wiring is allowed for Style 4 configuration.

Two-wire Addressable Sensor

Addressable Module

T-tapped Circuits

SLC-style4.cdr

L2 L1
SSM

Figure 4.1 Basic NFPA Style 4 SLC

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

21

SLC Circuits without Isolators

NFPA Style 6 SLC

4.3 NFPA Style 6 SLC


NFPA Style 6 requirements can be met by using the diagram below.

Two-wire Addressable Sensor

SLC Out

Addressable Module
SLC Return

SLC-style6.cdr

L2 L1 L1R L2R
SSM

NOTE: T-tapping of the SLC wiring is NOT allowed for Style 6 configuration.

Figure 4.2 Basic NFPA Style 6 SLC

22

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Section 5 Monitor Modules


5.1 Description
These addressable modules monitor conventional contact-type alarm initiating devices. You can
configure module circuits as NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuits
(IDC). There is no limit to the number of contact-type devices installed on a monitor module IDC.
NOTE: For more information on the individual module specifications, refer to the Installation
Instructions that are provided with this device.

5.1.1 AMM-4F Monitor Module


An addressable module that monitors either a Style B (Class B) or Style D (Class A) IDC of dry-contact
input devices. This module is capable of participating in degraded mode where supported by FACP.

5.1.2 AMM-2IF Dual Monitor Module


Similar to the AMM-4F, except intended for use in addressable two-wire systems providing two
independent Style B (Class B) IDCs at two separate, consecutive addresses.

5.1.3 AMM-4SF Monitor Module


Similar to the AMM-4F, except it is used to monitor compatible two-wire, 24 volt, conventional (nonaddressable) smoke detectors on a Style B (Class B) or Style D (Class A) IDC.

5.1.4 AMM-2F Monitor Module


Intended to monitor a Style B (Class B) IDC, and offered in a smaller package for mounting directly in
the electrical box of the device being monitored.

ADDRESS

0 1

9 8 7 6

2
3
4
5

TENS

0 1

SLC
9 8 7 6

2
3
4
5

Label Use to record


the device address and
SLC number.

ONES

IDC (+)
Violet

SLC (+)
Red

IDC (-)
Yellow

SLC (-)
Black

AMM-2F.cdr

Rotary Switches

Figure 5.1 AMM-2F Module

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

23

Monitor Modules

Setting an SLC Address for a Module

5.2 Setting an SLC Address for a Module


Control or relay modules, as well as sensors, can be set to one of 99 addresses (01-99) and are
factory preset with an address of 00.
To set an SLC address, use a screwdriver to adjust the rotary switches on the module to the desired
address. The unit shown in Figure 5.2 is set at address 35. When finished, mark the address on
the module face in the place provided.

GWSLC-setadd.cdr

Rotary Switches

Figure 5.2 Setting SLC Address on Module

24

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Monitor Modules

AMM-4F Wiring Diagram: NFPA Style B IDC

5.3 AMM-4F Wiring Diagram: NFPA Style B IDC


Connect the SLC wiring to the module Terminals 1 () and 2 (+). Each module takes one address
on the SLC. Use the rotary switches on the module to set the SLC address.
Figure 5.3 shows typical wiring for a supervised and power-limited NFPA Style B (Class B)
Initiating Device Circuit using the AMM-4F module.

See Appendix A, Power Considerations, on page 40 for information on supervising 24 VDC


power.
From
Supply
24 VDC
Four-wire
Detector
Base

Manual pull
station

24 VDC Power
Filtered, Regulated,
Resettable

47K ELR
(supplied
with module)

To Next IDC
or
Supervision Device
SLC

AMM-4F
Heat
detector

GWSLC-idcB1.cdr

IDC

Figure 5.3 Typical Style B IDC Wiring with AMM-4F

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

25

Monitor Modules

AMM-4F Wiring Diagram: NFPA Style D IDC

5.4 AMM-4F Wiring Diagram: NFPA Style D IDC


Connect the SLC wiring to the module Terminals 1 () and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set the SLC
address.
Figure 5.4 shows typical wiring for a supervised and power-limited NFPA Style D (Class A) IDC
using the AMM-4F module.

See Appendix A, Power Considerations, on page 40 for information on supervising 24 VDC


power.
From
Supply
24 VDC
Four-wire
Detector Base

24 VDC Power
Filtered, Regulated,
Resettable

To Next IDC
or
Supervision Device

Manual pull
station

IDC Return

SLC

AMM-4F
Heat
detector

GWSLC-idcD1.cdr

IDC Out

Figure 5.4 Typical Style D IDC Wiring with AMM-4F

26

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Monitor Modules

AMM-2IF Wiring Diagrams NFPA Style B IDC

5.5 AMM-2IF Wiring Diagrams NFPA Style B IDC


Connect the SLC wiring to the module Terminals 1 () and 2 (+).
Use the rotary switches on the module to set the SLC address. Each dual module takes two
addresses on the SLC. Circuit L corresponds to the address set on rotary switches. Circuit H will
automatically respond at the next higher address. The Circuit L base address is always an even
number with a lowest possible address of 02; the Circuit H base + 1 address is always odd. Use
caution to avoid duplicate addressing of modules on the system.
Each IDC (H & L) is power limited to 230 microamps @ 24 VDC.
Figure 5.5 shows typical wiring for a supervised and power-limited NFPA Style B (Class B)
Initiating Device Circuit using the AMM-2IF module.

Manual Pull
Station

47K ELR

SLC
AMM-2IF

Circuit H

Circuit L
Heat
Detector

GWSLC-idcB3ZO.cdr

47K ELR

Figure 5.5 Typical Style B IDC Wiring with AMM-2IF

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

27

Monitor Modules

AMM-4SF Wiring Diagrams: NFPA Style B IDC

5.6 AMM-4SF Wiring Diagrams: NFPA Style B IDC


Connect the SLC wiring to the module Terminals 1 () and 2 (+). Each module takes one address
on the SLC. Use the rotary switches on the module to set the SLC address.
Figure 5.6 shows typical wiring for a supervised and power-limited NFPA Style B (Class B) IDC
using the AMM-4SF module.

Two-wire
smoke
detectors

3.9K ELR
(supplied with module)
SLC
AMM-4SF

GWSLC-idcB2.cdr

IDC

24 VDC Resettable power

90 mA
External
24 volt supply
required

Figure 5.6 Typical Style B IDC Wiring with AMM-4SF

28

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Monitor Modules

AMM-4SF Wiring Diagrams: NFPA Style D IDC

5.7 AMM-4SF Wiring Diagrams: NFPA Style D IDC


Connect the SLC wiring to the module Terminals 1 () and 2 (+).
Each module takes one address on the SLC. Use the rotary switches on the module to set the SLC
address.
Figure 5.7 shows typical wiring for a supervised and power-limited NFPA Style D (Class A) IDC
using the AMM-4SF module.

3.9K ELR
(supplied with module)

Two-wire
smoke
detectors

SLC
AMM-4SF
IDC Return

IDC Out

GWSLC-idcD2.cdr

90 mA
External
24 volt supply
required

24 VDC Resettable power.

Figure 5.7 Typical Style D IDC Wiring with AMM-4SF

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

29

Control Modules

Description

Section 6 Control Modules


When using a Control Module as a Notification Appliance Circuit (NAC), the isolation described in
Section 3, SLC Circuits with Isolators, on page 16, is required or Riser Conductors must be
installed in accordance with the survivability from attack by fire requirements in National Fire
Alarm Code, NFPA 72.

6.1 Description
The AOM-2SF module is an addressable module that can be used for monitoring and switching 24
VDC Notification Appliance Circuit (NAC) power for NFPA Style Y (Class B) and NFPA Style Z
(Class A) circuits.
Load Description
Resistive
Resistive
Resistive
Resistive

Application
Non-Coded
Coded
Non-Coded
Non-Coded

Inductive (L/R = 5ms)


Inductive (L/R = 2ms)
Inductive (PF = 0.35)

Coded
Coded
Non-Coded

Maximum Voltage
30 VDC
30 VDC
110 VDC
125 VAC (AOM-2SF)
70.7 VAC (MMO-6SF)
30 VDC
30 VDC
125 VAC (AOM-2SF)
70.7 VAC (MMO-6SF)

Current Rating
3.0 A
2.0 A
0.9 A
0.9 A
0.5 A
1.0 A
0.5A

Note: For more information on module specifications, refer to the installation instructions provided with these
devices.

6.2 Installation
6.2.1 Setting an SLC address for AOM-2SF Modules
Each module is factory preset with an address of 00. To set an SLC address, refer to Section 5.2,
Setting an SLC Address for a Module, on page 24.

6.2.2 Wiring a Notification Appliance Circuit (NAC) with AOM-2SF


Modules
Figure 6.1 shows the connections to wire a module for powering a 24 VDC NAC.

Style Z NAC ()
Style Z NAC (+)

SLC ()

Style Y/Z NAC (+)

SLC (+)

Style Y/Z NAC ()

24 VDC Nonresettable Power ()*

AMM-4F.cdr

24 VDC Nonresettable Power (+)*

Note: Module is shown in non-alarm condition.

30

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Control Modules

Wiring AOM-2SF Modules

Figure 6.1 AOM-2SF Wiring Connections

6.3 Wiring AOM-2SF Modules


This section contains instructions and diagrams for wiring a Signaling Line Circuit with the AOM2SF as a Notification Appliance Circuit (NAC).

6.3.1 Wiring a Style Y NAC (Two-Wire)


A supervised and power-limited NFPA Style Y (Class B) NAC using the AOM-2SF module.
Notification appliances are shown connected to the module in a two-wire configuration.
SLC
AOM-2SF

ELR 47K,
1/2-watt

24 VDC Notification
Appliances

24 VDC Nonresettable power

GWSLC-nacY.cdr

NAC Out

Module polarities are shown in Alarm.

Figure 6.2 NFPA Style Y Notification Appliance Circuit

See Appendix A, Power Considerations, on page 40 for information on monitoring 24 VDC


power.

Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive
load (on mechanical bells and horns).

Do not T-Tap or branch a Style Y circuit.

Terminate the circuit across the last device using a UL-listed End-of-Line Resistor 47K,
1/2-watt (SSD P/N A2143-00).

Do not loop wiring under the screw terminals of any notification appliance. To maintain
supervision, break the wire run at each device.

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

31

Control Modules

Wiring AOM-2SF Modules

6.3.2 Wiring a Style Z NAC (Four-Wire)


A supervised and power-limited NFPA Style Z (Class A) NAC using the AOM-2SF module.
Notification appliances are shown connected to the module in a four-wire configuration.
SLC
24 VDC
notification
appliances

AOM-2SF

NAC Return

Module polarities are shown in Alarm.

24 VDC Nonresettable power

SLC-nacZ.cdr

NAC Out

Figure 6.3 NFPA Style Z Notification Appliance Circuit

32

See Appendix A, Power Considerations, on page 40 for information on supervising 24 VDC


power.

Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive
load (on mechanical bells and horns).

Do not T-Tap or branch a Style Z circuit.

Do not loop wiring under the screw terminals of any notification appliance. To maintain
supervision, break the wire run at each device.

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Relay Module

Description

Section 7 Relay Module


7.1 Description
The AOM-2RF module is an addressable module that provides two isolated sets of Form-C relay
contacts.
Ratings for the dry relay contacts on a Form-C module are:

Resistive - 2 amps @ 30 VDC

Inductive - 1 amp @ 30 VDC (0.6pF)

Pilot Duty - 0.5 amp @ 125 VAC (0.35pF)

NOTE: For more information on the module specifications, refer to the Installation Instructions
provided with this device.

7.2 Installation
7.2.1 Setting an SLC Address for the AOM-2RF Module
Each module is factory preset with an address of 00. To set an SLC address, refer to Section 5.2,
Setting an SLC Address for a Module, on page 24.

7.2.2 Wiring the AOM-2RF Module (Form-C Relay)


Figure 7.1 shows the AOM-2RF module wired to the Control Panel.
SLC
AOM-2RF

C
NC
NO
C
NO

SLC-frmC.cdr

NC

Figure 7.1 AOM-2RF Wiring Connections

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

33

Intelligent Detector Bases

Description

Section 8 Intelligent Detector Bases


8.1 Description
The B501and SS-B6 Detector Bases provide the connection between the SLC and a variety of
intelligent detectors. Use the SS-BF Detector Base with all SS-F Filtrex detectors.
NOTE: For more information refer to the Installation Instructions document provided with this device.

8.2 Installation
8.2.1 Wiring a Detector Base
Figure 8.1 shows typical wiring of a B501 detector base connected to an SLC.
SLC

To next device
on SLC

For convenience,
connect to cable
shield
segements.

SLC-B501wire.wmf

RA400Z

NOTE: The SS-B6 base wiring is identical to the B501, except there is no SHIELD terminal.

Figure 8.1 Wiring of a B501 Detector Base

34

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Intelligent Detector Bases

Installation

Figure 8.2 shows typical wiring of a SS-BF detector base (for use with a SS-F Filtrex detector)
connected to an SLC.

SLC
To next device on
SLC

For connection of
cable shield

Power to next
device

To compatible
UL Listed
Power Supply

B710HD.wmf

RA400Z

Figure 8.2 Wiring of a SS-BF Detector Base

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

35

Intelligent Detector Bases

Installation

8.2.2 Wiring an Isolator Base


The B224BI Isolator Base will isolate its detector from short circuits that occur on the SLC
connected at terminals 3 and 2. It will not isolate its installed detector from short circuits that occur
on the SLC connected at terminals 1 and 2. In Style 7 applications the loss of a single detector
during a short circuit is not acceptable, and an isolator module must be installed as shown in
Figure 8.3.
SLC Out

SLC In

SLC-224BIwire.wmf

Conduit

SS-LI
Isolator Module

Figure 8.3 Wiring an Isolator Base

36

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Intelligent Detector Bases

Wiring a Sounder Base

8.3 Wiring a Sounder Base

C0732-00.wmf

Figure 8.4 shows typical wiring of the B501BH sounder base.

Figure 8.4 Wiring of the BH501 Sounder Base

8.4 Wiring a Relay Base


Figure 8.5 shows typical wiring of a B224RB plug-in relay detector base connected to an SLC.

To next
device on
SLC

For connection of
cable shield

3 Relay Common
1 Normally Closed
2 Normally Open

b224rb.wmf

SLC

Figure 8.5 Wiring of a B224RB plug-in relay detector base

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

37

Intelligent Detector Bases

Wiring a Relay Base

8.4.1 Setting the Detector Address


Each intelligent detector head is factory preset with an address of 00. To set an SLC address refer
to Section 5.2, Setting an SLC Address for a Module, on page 24.

38

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Section 9 Addressable Manual Pull Station


9.1 Description
The MS-7ASF/SD is an addressable manual pull station with a key-lock reset feature.
NOTE: For more information, refer to the Installation Instructions document provided with this device.

9.2 Installation
9.2.1 Setting an SLC address
Each unit is factory preset with an address of 00. To set an SLC address, refer to Section 5.2, Setting
an SLC Address for a Module, on page 24 .

9.2.2 Wiring a Manual Pull Station


Typical wiring for the MS-7ASF/SD Manual Pull Station to an SLC.

SLC

To next device
on SLC

SLC-nbg12.cdr

US PAT 444 0991

Figure 9.1 Wiring the MS-7ASF/SD Pull Station to an SLC

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

39

Power Considerations

Supplying Power to 24 VDC Detectors and NACs

Appendix A Power Considerations


A.1 Supplying Power to 24 VDC Detectors and NACs
Resistance and Size
To determine the maximum allowable resistance that can be tolerated in supplying power to 24
VDC four-wire devices and NACs, use the calculations below. These simplified equations assume
that the devices are at the end of a long wire run. With the computed resistance and using the
manufacturers specifications for the desired wire, select the proper gauge wire for the power run.
For Four-Wire Detectors:
(Vms - Vom)

Rmax =

(N)(Is) + (Na)(Ia) + (Ir)

For NACs:
(Vms - Vom)

Rmax =

(Nb)(Ib)

Where:
Rmax

= maximum resistance of the 24 VDC wires

Vms

= minimum supply voltage (see Table A.1 below)

Vom

= minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts

N
Is

= total number of detectors on the 24 VDC supply circuit


= detector current in standby

Na
Ia

= number of detectors on the 24 VDC power circuit which must function at the same time in
alarm
= detector current in alarm

Ir

= end-of-line relay current

Nb

= number of Notification Appliance Devices

Ib

= Notification Appliance current when activated

NOTE: This simplified equation assumes that the devices are at the end of a long wire run.

The minimum supply voltages produced by Gamewell-FCI power supplies are listed below:
FACP

VDC

IF-610

19.36

IF-632/654/658

18.90

Table A.1 Minimum Supply Voltage

40

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Power Considerations

Supervising 24 VDC Power

A.2 Supervising 24 VDC Power


The are options for supervising 24 VDC power are described in Section A.2.1.

A.2.1 Power Supervision Relay


Power used to supply 24 VDC detectors, notification appliances (using the AOM-2SF) and two
wire detectors (using the AMM-4SF) can be supervised with a power supervision relay. This relay,
energized by the 24 VDC power itself, is installed at the end of each respective power run and
wired in-line with the supervised circuit of any intelligent module.
When power is removed from the relay, the normally closed contacts open the supervised circuit,
generating a trouble condition. Therefore, the relay needs to be installed at the end of the
supervised circuit, so as to not disrupt the operating capability of all the devices on that circuit. The
relay can be installed in-line with any leg (+ or ) of the supervised NAC or IDC circuit, either a
two or a four-wire style.
Figure A.2.1.1 illustrates this concept.

ELR 39K
Supervised NAC or IDC

24 VDC Power from Control


Panel or UL-listed compatible
Power Supply

GWSLC-psr.cdr

Power Supervision
Relay
(PAM-1)

Figure A.2.1.1 Supervised 24 VDC Circuit


Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

41

Power Considerations

Supervising 24 VDC Power

Style Y NAC Power Wiring


Program the NAC from the control panel for general alarm. (Refer to the programming manual or
programming section of the FACP documentation for instructions.) Note that if the NAC is a coded
output, the AOM-2SF module will be coded as well.

When using the AOM-2SF Modules as a Notification Appliance Circuit (NAC), the circuit
isolators must be installed in compliance with the Survivability from Attack requirements per
the National Fire Alarm Code, NFPA 72.

A separate 24V power supply is recommended for a group of control modules that comprise a
notification zone.

In this circuit, an external ELR is required at end of the NAC circuit.

Refer to the respective control panel installation manual for NAC terminal block connection
information and ELR value.

Connect the NAC power as follows:


AOM-2SF
SLC

End-of-line
Resistor

NAC Terminal
Block (24 VDC)

GWSLC-nacY1.cdr

AOM-2SF

Figure A.2.1.2 NFPA Style Y NAC Power (Alternate)

42

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Power Considerations

Supervising 24 VDC Power

Style Z NAC Power Wiring


Program the NAC from the control panel for general alarm. (Refer to the programming manual or
programming section of the FACP documentation for instructions.) Note that if the NAC is a coded
output, the AOM-2SF output will be coded as well.

When using the AOM-2SF Modules as a Notification Appliance Circuit (NAC), the circuit
isolators must be installed in compliance with the Survivability from Attack requirements per
the National Fire Alarm Code, NFPA 72.

A separate 24V power supply is recommended for a group of control modules that comprise a
notification zone.

In this circuit, an external ELR is not required at the end of the NAC circuit.

Refer to the respective control panel installation manual for NAC terminal block connection
information.

Connect the NAC power as follows:


AOM-2SF

SLC

NAC on Control Panel


or Module

GWSLC-nacZ1.cdr

AOM-2SF

Figure A.2.1.3 NFPA Style Z NAC Power (Alternate)

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

43

Compatibility of Panels and SLC Devices

Velociti Modules

Appendix B Compatibility of Panels and SLC Devices


B.1 Velociti Modules
Gamewell-FCI SSM modules are compatible with all the Velociti devices.

Control Panel

Velociti Module

IF610-396SS
IF610-792SS

SSM610-2
SSM610-4

IF632
SSM-2
SSM-4

IF654
IF658
IF602SS

IF602 Series
Table B.1

44

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Compatibility of Panels and SLC Devices

Velociti Modules

Notes

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

45

Electrical Specifications

Appendix C.1 Electrical Specifications


Addressable Output
Devices

Standby Current
(Amps)

Alarm Current
(Amps)

AOM-2SF

0.0004

0.0065

AOM-2RF

0.0003

0.0065

MMO-6SF

0.0025

0.0035

MMO-6RF

0.0015

0.0032

Addressable Input
Devices

Standby Current
(Amps)

Alarm Current
(Amps)

AMM-2F

.0004

0.0060

AMM-4F

.0004

0.0060

AMM-2IF

.0008

0.0050

MS-7ASF

.0004

0.0060

MMI-10F

.0035

0.0550

AMM-4SF

0.0003

0.0051

MMI-6SF

0.0020

0.0400

Addressable Smoke
Sensors

Standby Current
(Amps)

Alarm Current
(Amps)

ASD-PL2F

0.0004

0.0065

ASD-IL2F

0.0004

0.0060

ASD-PTLS2F

0.0008

0.0060

MCS-Acclimate

0.0008

0.0060

ATD-L2F/RL2F

0.0003

0.0060

ATD-HL2F

0.0003

0.0060

ASD-FiltrexF

0.0003

0.0051

ABD-2F

0.0020

0.0085

M500X

0.0003

0.0051

ADPF

0.0003

0.087

ADPRF

0.026

0.087

Table C.1 Electrical Specifications

46

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Electrical Specifications

Notes

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

47

Electrical Specifications

Notes

48

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Index
dry-contact 8
duplicate addressing 27

Numerics
24 VDC power 4042
monitoring and switching NAC power

30

A
ABD-2F 9
addressable devices 16
addressable modules 23
ADPF 9
AMM-2F 7
AMM-2IF 7
AMM-4SF 7
analog intelligent devices 7
AOM-2RF 8
AOM-2SF 8
ASD-FiltrexF 9
ASD-IL2F 9
ASD-PL2F 9
ATD-L2F 9
auxiliary devices 8

ELR, see End-of-Line-Resistor


End-of-Line-Resistor 31, 42, 43

F
factory preset 24
fault 17, 19
fault condition 16
Fire Alarm Control Panels 7
Form-C contacts 33
four-wire configuration 32

G
general alarm 42, 43
group poll 7
grouped fashion 7

B
B224BI 9, 16, 17,
B224RB 9, 37
B501 9, 34
B501BH 37
B501BH(2) 9
B501BHT(2) 9
bases 9

36

C
circuit fault 9
coded output 42, 43
communications loop 17
control modules 8

D
DC resistance 12, 13
degraded mode 8, 23
detector bases
list of 9
detectors
24 VDC 41
devices
addressable 16
auxiliary 8
isolator 16
maximum number between isolators 16
supervised 41
dry contact ratings 33
Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

IF-610 40, 44
IF-632/654/658 40, 44
Initiating Device Circuits 2328
integral relay 16
isolator bases 9
how they work 17
wiring 36
isolator detector bases 16, 20
see also isolator bases
isolator devices 16
isolator modules 9, 19, 20
how they work 16
wiring of 16

K
key-lock reset 39

L
Loop Resistance 12
Style 6 & 7 13
loops 13

M
M500X 7
MCS-Acclimate 9
metal conduit 19
MMI-10F 8
MMI-6SF 8
49

Index

NZ

MMO-6RF 9
MMO-6SF 8
module circuits, configuring 23
modules
control 8
isolator 9
monitor 7, 23
relay 8
monitor modules 7, 23
MS-7AF 8
MS-7ASF 8

Signaling Line Circuit 7


see also SLC
SLC
performance 11
setting an SLC address 24
wiring 25, 26, 27, 28, 29
sounder bases 9, 16
SS-B6 34
SS-BF 34
SS-F 35
SSM-2/2E 15
SSM610-2/4 14
standard bases 9
Style 4, Style 6, Style 7, Style B,Style D, Style Y,
Style Z see NFPA Style 21
supervised circuits 41
supervised devices 41

N
NAC power 30, 43
wiring 42
NAC terminal block 42
NFPA Style 4
wiring 21
with M500X 18
NFPA Style 6
wiring 22
with M500X 19
NFPA Style 7 16
with isolator device 20
NFPA Style B
IDC wiring 25, 27, 28
NFPA Style D
IDC wiring 26, 29
NFPA Style Y 30
wiring 31
NFPA Style Z 30
wiring 32
normally closed contacts 41
Notification Appliance Circuit 8
see also NAC
notification appliances 41

T
terminal block, NAC 43
trouble conditions 16
trouble warning 17
T-tapping 12, 19, 20, 21,
two wire detectors 41
two-wire configuration 31

V
Velociti 7, 11, 17
Velociti Modules
IF602 Series 44
SSM-2 44
SSM-4 44
SSM610-2 44
SSM610-4 44

P
Polling Protocols 7
power run 40, 41
power supervision relay 41
power supplies 40
proper gauge wire 40
pull stations 8, 20
addressable manual, wiring

R
ratings, dry contact 33
relay bases 9, 16
Relay Module 8
rotary switches 24, 27,

22

39

wire length
four-wire SLC 13
two-wire SLC 12
wiring
isolater bases 36
isolator modules 16
NACs 42
pull stations 39
SLCs 25, 26, 27, 28,
wiring style requirements 11

29

Z
zone interface modules 28,

29

28, 29

S
short circuit 16,
50

17
Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

Limited Warranty
Honeywell International Inc. warrants products manufactured by it
to be free from defects in materials and workmanship for thirty-six (36)
months from the date of manufacture, under normal use and service.
Products are date stamped at time of manufacture. The sole and
exclusive obligation of Honeywell International Inc. is to repair or
replace, at its option, free of charge for parts and labor, any part that is
defective in materials or workmanship under normal use and service.
All returns for credit are subject to inspection and testing at the factory
before actual determination is made to allow credit. Honeywell
International Inc. does not warrant products not manufactured by it,
but assigns to the purchaser any warranty extended by the
manufacturer of such products. This warranty is void if the product is
altered or repaired by anyone other than Honeywell International
Inc. or as expressly authorized by Honeywell International Inc. in
writing, or is serviced by anyone other than Honeywell International
Inc. or its authorized distributors. This warranty is also void if there is
a failure to maintain the products and systems in which they operate
in a proper and workable manner. In case of defect, secure a Return
Material Authorization form from our Return Authorization
Department.
This writing constitutes the only warranty made by Honeywell
International Inc., with respect to its products.
Honeywell
International Inc., does not represent that its products will prevent
any loss by fire or otherwise, or that its products will in all cases
provide the protection for which they are installed or intended. Buyer
acknowledges that Honeywell International Inc., is not an insurer
and assumes no risk for loss or damages or the cost of any
inconvenience, transportation damage, misuse, abuse, accident or
similar incident.
HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY,
EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR
ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTENDS
BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO
CIRCUMSTANCES SHALL HONEYWELL INTERNATIONAL INC.
BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY,
DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF
THE USE OF, OR INABILITY TO USE HONEYWELL
INTERNATIONAL INC.S PRODUCTS.
FURTHERMORE,
HONEYWELL INTERNATIONAL INC. SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE
COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL
OR INDUSTRIAL USE OF ITS PRODUCTS.
This warranty replaces all previous warranties and is the only
warranty made by Honeywell International Inc. No increase or
alteration, written or verbal, of the obligation of this warranty is
authorized.
Warn-HL_36_5-2007.fm

Analog Addressable Panel SLC Wiring Manual P/N 52282:B 06/26/09

51

Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610 USA
203-484-7161
fax 203-484-7118
www.gamewell-fci.com

Potrebbero piacerti anche