Sei sulla pagina 1di 61

Pump FAQ’s by Hydraulic Institute (UK) 1

FAQ’S OF PUMPS

Pump FAQs® September 2001 Article #3

Q. We have many centrifugal pumps, which take their inlet from an overhead tank.
When the centrifugal pump draws down the liquid level in the tank, a vortex
forms in the liquid and air is drawn into the pump. How can this problem be
corrected?
A. At low liquid levels, the formation of a vortex is dependent on the liquid
velocity entering the pipe. Increasing the effective pipe area can reduce this
liquid velocity. Installing a baffle plate above the pipe opening will simulate a
larger intake area thereby reducing the vortex formation. See the figure below:

Pump FAQs® September 2000 Article #1

Q. Our plant is operating a system with several centrifugal pumps in parallel that
exhibits waterhammer problems when one of the pumps is shut down. The
discharge pipe from the pump is 18 inches diameter, forty feet long up to the
common header. The backflow after shutdown causes severe banging of the
check valve. What can be done to relieve this problem?
A. Much has been written on this subject, including a section in the “Pump
Handbook” published by McGraw Hill which include fifteen pages on
waterhammer plus twelve references. Some solutions that have been applied
include:

• Close to the pump isolation valve before shutting down the pump.
• Add a flywheel to the pump in order to slow its rate of coast down.
• Add a surge tank or air chamber which will absorb discharge pressure
energy.
• Use a fast closing check valve which will close before reverse flow begins.

• Use a slow closing check valve which will allow the reverse flow to shut down
more slowly and avoid the shock from the sudden stop of the backflow.

Pump FAQs® September 1999 Article #3

Q. Many manufacturers do not extend the NPSHR curve on their pump rating curve
below about thirty percent of its best efficiency point. Can the NPSHR curve be
extrapolated back to shut off in order to get this information?
A. Extrapolation of the NPSHR curve back to shut off is dangerous, since different
pumps act differently at very low flow rates. Some pumps exhibit a dramatic
increase in NPSHR at very low flows. In addition, the condition known as

1
Pump FAQ’s by Hydraulic Institute (UK) 2

suction recirculation becomes very pronounced at very low flows causing


vortices in the impeller and localized pitting damage to the impeller blades.

The subject of low flow operation is discussed in ANSI/HI 9.6.3-1997


Centrifugal and Vertical Pumps - Allowable Operating Region.

Pump FAQs® September 1999 Article #2

Q. In our process, the primary circulating pump occasionally becomes airbound due
to entrained air in the system and stops pumping. How much air can a
centrifugal pump handle, and what can be done to prevent airbinding?
A. Centrifugal pumps can usually handle up to about five percent by volume of air.
Above that, they will easily become airbound, especially at flow rates below the
best efficiency point. Even when pumping five-percent air, the pressure
developed will be reduced due to the reduced specific gravity of the fluid
mixture. In order to avoid airbinding, try the following:

• Minimize air entrainment by any means possible.


• Add a bypass pipe to maintain a high rate of flow.

• Install a vent in the top of the suction pipe to vent air back to the source.

Pump FAQs® September 1999 Article #1

Q. We are operating a multistage centrifugal pump in our process that is producing


too much head. We intend to reduce the pump head by reducing the impeller
diameters. Can we reduce head by trimming only one or two impellers, and is it
better to cut the impeller shrouds as well as the impeller vanes?
A. It is not necessary to keep all of the impellers at the same diameter. However, it
is better to limit the extent of impeller reduction to five percent or less due to
loss in efficiency as the impeller is cut down. You should evaluate the possible
loss in efficiency by cutting only one or two stages if the reduction is more than
five percent.

Regarding cutting of impeller shrouds, the advantage is that the full shroud
diameter will minimize pump instability when it is operated below fifty percent
of its best efficiency point. However, cutting the shrouds will reduce the
impeller disc friction and improve efficiency.

Pump FAQs® October 2006 Article #2

Q. I keep hearing about suction recirculation but cannot find a good explanation.

2
Pump FAQ’s by Hydraulic Institute (UK) 3

Can you help me?


A. When centrifugal pumps are operated at rates of flow below their best efficiency
point (BEP), the excess flow produced by the impeller is recirculated on the
suction side of the impeller as shown in figure 5-12. These eddy currents cause
local vortices on the impeller vanes, which in turn cause cavitation resulting in
noise, vibration, and damage to the impeller vanes

This action usually begins between 70% and 50% of the BEP flow and many pump
manufacturers do not allow operation below the onset of recirculation. Furthermore,
some impellers, which are designed for low NPSH Available applications, may begin the
recirculation mode close to the BEP. An example of this might be condensate drain
pumps in electric power plants.

Pump FAQs® November 2004 Article #1(1)

Q. The first answer in the September issue of Pumps and Systems says that spring

3
Pump FAQ’s by Hydraulic Institute (UK) 4

mounted baseplates can also work well to avoid pipe strains on pumps. How
can I know if the baseplate stiffness is sufficient to work without grouting?
A. Whether to grout or not depends on the specific application and the design of the
baseplate. Applications that undergo wide temperature variation may do well
with floating baseplates in order to allow for movement of the pump and thereby
minimize pipe strain caused by thermal expansion of the pipe. However, the
baseplate in such cases must be sufficiently rigid and designed to avoid
misalignment between the pump and driver shaft as the baseplate moves.

The purpose of a baseplate is to provide a foundation under a pump and its


driver that maintains shaft alignment between the two. This baseplate must
allow for initial mounting and alignment of equipment, survive handling during
transportation to the installation site, be capable of being installed properly with
minimum difficulty, allow final alignment of the mounted equipment, and allow
removal and reinstallation of equipment. It must be recognized that it is not
necessary that an absolutely rigid baseplate be designed to meet these
requirements. At the same time, the baseplate must not be permanently
deformed after the equipment is mounted at the manufacturing facility.
Compliance with these design criteria, in conjunction with proper installation
procedure, will contribute significantly to meeting the functional requirements.

Baseplates may be designed to be installed free standing, or to be installed using


grout. A free standing baseplate must be rigid enough to maintain coupling
alignment when subjected to loads from piping or motor torque. The rigidity
shall prevent no more than 0.25 mm (.010 inch) parallel coupling misalignment
and .005 mm/mm (.005 inches/inch) angular misalignment when subjected to
maximum motor and piping loads simultaneously.

A grouted baseplate relies on the grout for the majority of its stiffness but it
must be sufficiently rigid to permit handling and allow installation. It is
recommended that this type of baseplate have torsional stiffness of 1.13x10 4
N•M/rad (105 in•lb/rad).

Additional information and calculation of baseplate stiffness can be found in


Appendix A of ANSI/HI 1.3-2000 Centrifugal Pumps for Design and
Application.

Pump FAQs® May 2006 Article #3

Q. How does a change in liquid viscosity effect the performance of a rotary pump?
I have seen a viscosity correction graph for the performance of centrifugal
pumps but nothing for rotary pumps.
A. Because of the variety of rotary pump designs, no general viscosity correction
graph has been developed. Most pump manufacturers produce a range of

4
Pump FAQ’s by Hydraulic Institute (UK) 5

performance curves for each pump at different levels of viscosity.

There are some general guidelines that can be used as follows:


• Net positive inlet pressure required (NPIPR) increases with increasing
viscosity.
• Required pump input power increases with increasing viscosity.
• Maximum allowable pump speed decreases with increasing viscosity.
• Pump internal leakage or slip decreases with increasing viscosity.

• Pump volumetric efficiency increases with viscosity, but pump efficiency


peaks at about one thousand SSU viscosity due to the increasing viscous
drag at increasing viscosity. See figure 3.31 below.

For more information see the HI standard ANSI/HI 3.1-3.5 Rotary Pumps

Pump FAQs® May 2006 Article #2

What is reverse runaway speed? What is the cause? Is it dangerous and can it be
Q.
prevented?
A. Reverse runaway speed occurs when a pump runs in uncontrolled reverse
direction due to the reverse flow of liquid from an elevated or pressurized
source, such as a storage tank. It is most likely to happen with Vertical
Turbine Pumps when pumping from deep wells.

A sudden power failure and/or discharge valve or non-return valve failure


during operation against a static head may result in a flow reversal, and the
pump will operate as a hydraulic turbine in a direction opposite to that of
normal pump operation.

If the pump is driven by a prime mover offering little resistance while running
backwards, the reverse speed may approach a maximum or runaway speed. If

5
Pump FAQ’s by Hydraulic Institute (UK) 6

the runaway speed exceeds the normal pump speed, such speed may impose
high mechanical stresses on the rotating parts of both pump and driver. Figure
2.58B on the right provides a means for estimating reverse runaway speed for
pumps of different specific speed designs.

Vertical pump drivers can be equipped with non-reverse ratchets to prevent


reverse rotation. However, their application is not always desirable and a
review should always be made with the pump manufacturer. Check valves on
the pump discharge and/or suction may also help with the problem.

Figure 2.58B — Reverse runaway speed ratio versus specific speed (US units)

Pump FAQs® May 2006 Article #1

Q. We operate about one thousand centrifugal pumps and find that ball bearing
failure is a major cause of pump shutdown which requires repair, and sometimes
causes unscheduled system shutdown. How can we monitor these pumps to
eliminate or predict these failures?
A. Lubricant analysis is a good way to keep an eye on pump bearings and prevent
unexpected bearing failure. If the lubricant is contaminated, it will accelerate the
normal wear of bearings, and also show if excessive wear is taking place by the

6
Pump FAQ’s by Hydraulic Institute (UK) 7

presence of metallic particles.

Quantitative analysis of metal particles are obtained from a particle counting


analysis which will provide information on the number of particles in a sample
within various size ranges and an analysis of the contaminants. A description of
the methods and codes used can be found in ISO 4402 and SAE ARP 598.

Water is one of the most common contaminates found in large quantities and is
the easiest to detect. Water can come from internal sources such as leaks in
cooling systems and condensation, or external sources such as leaking seals.
Usually the lubricant turns white and emulsifies. A sample from the bottom of
the oil sump is best to indicate the presence of water.

Oil samples for the detection of particles should be taken while the pump is
operating, or immediately after shutdown, to ensure well-mixed lubricant is
obtained. Samples should be withdrawn from within one half inch of the surface
of the oil. Until your experience provides statistics and consistency, it is
suggested that samples be taken monthly.

For further detail on this subject, see ANSI/HI 9.6.5 Centrifugal and Vertical
Pumps for Condition Monitoring.

Pump FAQs® May 2005 Article #3

Q. I know that centrifugal pumps do not operate well on viscous liquids and rotary
pumps are often recommended, but what about reciprocating pumps? Are there
any limits to the viscosity of liquids that can be handled by reciprocating
pumps?
A. Theoretically there is no limit to the viscosity of liquids that can be handled by
reciprocating pumps as long as they can be run slow enough.

The primary limiting factor is the velocity of liquid flow through the suction and
discharge valves. This velocity can be calculated from the following equation:

v = 0.642Q/MA

Where

v = Average liquid velocity in the valve in feet per second;

Q = Rate of flow in gallons per minute;

M = Number of suction valves;

7
Pump FAQ’s by Hydraulic Institute (UK) 8

A = Suction valve flow area in square inches.

Some guidelines in this regard would limit this velocity as follows:

Viscosity Valve velocity

SSU ft/sec

20,000 4.0

9,000 5.0

5,000 6.0

3,000 7.0

2,000 8.0

1,300 9.0

600 10.0

350 11.0

More information on this subject can be found in ANSI/HI 6.1-6.5 -


Reciprocating Power Pumps.

Pump FAQs® May 2005 Article #2

Q. Our plant has a horizontal axially split case pump handling cooling water and
the horizontal suction pipe includes a ninety degree elbow at the suction flange
of the pump. The pump operation is noisy and one side of the impeller shows
cavitation damage and the other side does not. I believe that the elbow on the
suction is the major cause of the problem, but adding straight pipe in between is
not practical. Is there another solution to this problem?
A. Yes, there are several solutions. One is to install one or more vertical flow
dividers in the elbow which will guide the flow through the elbow and keep the
flow to each side of the impeller equal. If the NPSH available is sufficient, the
noise and cavitation damage should cease.

Another solution is to reduce the flow velocity prior to the elbow with an
eccentric increaser and add a reducing elbow at the pump. It may also be
practical to use a combination of a larger elbow followed by a straight pipe
reducer. The process of accelerating the flow rate has a tendency to straighten

8
Pump FAQ’s by Hydraulic Institute (UK) 9

the flow at the same time.

Pump FAQs® May 2005 Article #1

Q. We are operating an end suction centrifugal pump which takes suction from the
bottom of an open tank. As the level in the tank drops, a vortex is formed which
allows air into the pump. This changes the performance of the pump and upsets
the process downstream. I understand that this can be corrected with baffle
plates. Are there any guidelines in this regard?
A. Yes, and baffle plates are effective in correcting this problem. The objective is
to increase the apparent opening to the suction pipe, thereby reducing the
liquid velocity as it leaves the tank. It is the velocity of the liquid flow that
creates the vortex as the liquid level drops.

The simplest solution is the installation of a circular baffle plate with a


diameter of four times the pipe diameter directly over the outlet pipe at a
distance of two diameters above the pipe opening. See the figure on the right.
This results in an apparent opening which is eight times the original opening
and a corresponding reduction in flow velocity as the liquid moves under the
baffle. Of course the velocity increases under the baffle plate, but then it is
protected from the surface air.

If the baffle plate is supported by four to six vertical plates forming a star to a
diameter of two times the pipe diameter, they will further reduce the start of a
vortex.

For more information on this subject see ANSI/HI 9.8 - Pump Intake Design.

9
Pump FAQ’s by Hydraulic Institute (UK) 10

Pump FAQs® May 2004 Article #3

Q. On low NPSH available applications it is often necessary to apply a centrifugal


pump at 50% of its design flow rate to get a pump with low NPSH required
values. What is the downside of doing this?
A. The most significant downside is in excessive power consumption. 50% of BEP
is outside the normal operating range allowed by most pump manufacturers.
This subject is discussed in detail in ANSI HI 9.6.3-1997 Centrifugal and
Vertical Pumps for Allowable Operating Region.

Pump efficiency at 50% of BEP will always be lower than at BEP. If you do the
math, you will find that the cost of excess power will be significant.

The lower NPSHR values at 50% flow do not guaranty cavitation damage free
operation. At low rates of flow the impeller is also suffering from suction side
recirculation in the impeller eye. The vortex caused by recirculation further
increases local cavitation which in turn causes impeller damage, noise and
vibration.

Another problem is the increase in radial forces on the impeller which reduce
bearing and seal life and even cause shaft breakage from bending fatigue.

Pump FAQs® May 2004 Article #2

Q. In applications on handling slurries, we find that for higher heads centrifugal


pumps are limited in what they can do. Can reciprocating pumps be used in
these applications?

If so, are any special design changes necessary?


A. Reciprocating pumps are often used to handle slurries for in-plant process and
pipeline applications. Basic construction may be different from that for clear
liquid applications. The differences may be in types of valves, addition of surge
chambers, fluid injection into the inner portion of the stuffing box or material
for wearing parts. ANSI-HI 6.1-6.5-2000 Reciprocating Power Pumps for
Nomenclature, Definitions, Application and Operation contains considerable
information on this subject.

Hydraulic passages should be sized so that the lowest velocity of the fluid will
be above the critical carrying velocity of 4 to 6 ft/s. The highest velocity should
be below that which causes excessive erosion.

Lubrication and flushing of packing are extremely important. Metered, clear,


external injection, which is timed to the position of the plunger during its stroke,
or continuous flow injection is required.

10
Pump FAQ’s by Hydraulic Institute (UK) 11

Valves for use in slurry service are designed for velocities between 6 and 12 ft/s
to reduce erosion and abrasion of the valve seat and other valve components.
Valve construction usually has replaceable valve inserts that are made of an
elastomer or polymer. Metal to metal ball valves may also be used.

To facilitate starting and stopping a slurry pump, it should be fitted with


adequate connections so the liquid end passages can be flushed of the slurry
with clear liquid.

Rod and plunger packing requires special consideration when dealing with
abrasive materials. In piston pumps, the piston runs in a renewable metal
cylinder or liner. The liners are made of abrasion and corrosion resistant metals.
Piston rods and plungers are coated to resist wear.

Pump FAQs® May 1999 Article #3

Q. Some centrifugal pump manufacturers show a vertical dotted line on their pump
rating curves with the notation “minimum allowable flow.” Is there a
standard procedure for determining this limit? If not, what criteria are used to
determine this value?
A. The factors which determine minimum allowable rate of flow include the
following:

• Temperature rise of the liquid -- This is usually established as 15°F and


results in a very low limit. However, if a pump operates at shut off, it could
overheat badly.
• Radial hydraulic thrust on impellers -- This is most serious with single volute
pumps and, even at flow rates as high as 50% of BEP could cause reduced
bearing life, excessive shaft deflection, seal failures, impeller rubbing and
shaft breakage.
• Flow re-circulation in the pump impeller -- This can also occur below 50% of
BEP causing noise, vibration, cavitation and mechanical damage.
• Total head characteristic curve – Some pump curves droop toward shut off,
and some VTP curves show a dip in the curve. Operation in such regions
should be avoided.

There is no standard which establishes precise limits for minimum flow in


pumps, but ANSI/HI 9.6.3-1997 Centrifugal and Vertical Pumps – Allowable
Operating Region discusses all of the factors involved and provides
recommendations for the “Preferred Operating Region.”

Pump FAQs® May 2004 Article #1

Q. We are replacing a 30,000 gpm vertical pump with a larger one, and are
concerned that the new pump will have enough submergence to prevent vortices
at the pump inlet. What guidelines are available to determine if enough

11
Pump FAQ’s by Hydraulic Institute (UK) 12

submergence is available?
A. This answer provides the recommended minimum submergence of a vertical
pump inlet bell to reduce the probability that strong free-surface air core vortices
will occur. Submerged vortices are not believed to be related to submergence
and are not addressed here.

Approach-flow skewness and the resulting circulation have a controlling


influence on free surface vortices in spite of adequate submergence. The
recommended minimum submergence given here is for a reasonably uniform
approach flow to the pump suction bell. Highly non-uniform approach flows
will require the application of vortex suppression devices.

Experimental analysis and field experience have resulted in the following


empirical relationship:

S = D + 0.574Q/D1.5

Where S is submergence in inches

D is bell diameter in inches

Q is rate of flow in gpm

The required minimum submergence can also be determined from figure


9.8.26B taken from ANSI HI 9.8-1998 Pump Intake Design.

Pump FAQs® May 1999 Article #2

12
Pump FAQ’s by Hydraulic Institute (UK) 13

Q. We operate a sanitary sewage pumping plant, which frequently creates vortices


at the pump inlet pipes. The pumps are mounted in a dry pit adjacent to the
collecting tank. The vortices are reducing the pump flow and causing excessive
vibration in the pumps. Increasing the liquid level over the pumps would be
very expensive. What else can be done to eliminate the vortices?
A. Plates, splitters, vanes, etc. can be added to the collecting tank near the pump
inlet pipe. These will inhibit the formation of vortices. Assuming that the pump
inlet pipe is in the wall between the collecting tank and pump pit, two
suggestions could be tried.

• Add a downward opening flanged elbow to the inlet pipe. This will lower the
point where liquid enters and the flange on the elbow will reduce entrance
velocity. If possible, use a reducing elbow to further increase the size of
opening and flange diameter.
• Attach a horizontal baffle plate to the wall directly above the pump inlet
pipe. The plate should have a length and width equal to 4 times the
diameter of the pump inlet pipe.

These solutions, and others, are discussed in a recently published 62 page


standard, ANSI/HI 9.8-1998 Pump Intake Design addressing this subject. The
standard provides design recommendations for a variety of different intakes for
both solids bearing liquids and clear liquids.

Pump FAQs® May 1999 Article #1

Q. Our plant is operating pumps on cooling tower service which are experiencing
cavitation damage to the cast iron impellers. The pumps are operating close to
the best efficiency point and the NPSH available is slightly higher than the
NPSH required by the pump. Should there be cavitation damage in the pump
impellers under these conditions?
A. There is a common misconception among pump users that if the NPSH available
from the system is greater than the NPSH required by the pump, that the pump
will operate free of cavitation. This is not so. In order for a pump to operate
cavitation free, the NPSHA must be from 2 to 20 times greater than the NPSHR
of the pump. By definition, NPSHR is measured when the pump total head is
reduced by 3% due to cavitation. For satisfactory operation, some NPSH
margin over NPSHR must be provided by the system.

The Hydraulic Institute has recently published a new standard on this subject
namely, ANSI/HI 9.6.1-1998 Centrifugal and Vertical Pumps for NPSH
Margin. According to this standard, for cooling tower service, NPSHA should
be 1.3 to 2.0 times NPSHR, depending on suction energy level, which is also
defined in the standard.

The problem is also aggravated by the use of a cast iron impeller. In cooling
tower service, other materials such as stainless steel, titanium and nickel

13
Pump FAQ’s by Hydraulic Institute (UK) 14

aluminum bronze will withstand cavitation damage much better than cast iron.

Pump FAQs® March 2006 Article #3

Q. We are using a large number of air-operated reciprocating pumps and are


concerned about the amount of power that they are using. How can we check the
efficiency of these pumps?
A. Air operated pumps generally do not show power or efficiency on their rating
curves. See the typical curve on the right.

Note that instead of input power, lines of “constant air consumption” are
shown. Air consumed by the pump is given in terms of the mass flow rate of
the air through the pump at standard atmospheric conditions (68 degrees F and
a pressure of one atmosphere). The standard unit of air consumption is SCFM
(standard cubic feet per minute). Measurement of air consumption by the
pump can be made and compared with the pump performance curve to check
for deterioration. ANSI/HI 10.6 Air- Operated Pump Tests provides more
detail on testing air-operated diaphragm and bellows pumps.

Reciprocating pumps generally have good hydraulic performance, which is


well maintained. The power required by the compressor to produce the motive
air is beyond the Hydraulic Institute scope.

Figure 10.13 - Plotting test results

Pump FAQs® March 2006 Article #1

Q. What is a “can” pump? I have seen this term applied to both centrifugal
and vertical turbine pumps(VTP). Will you please explain it for me?
A. The term “can” pump may be used to describe either VTP, or close
coupled centrifugal pumps. However there is a big difference between them.

14
Pump FAQ’s by Hydraulic Institute (UK) 15

When applied to a close coupled centrifugal pump, the term “can” refers
to a cylinder or can which surrounds the motor rotor to seal it from the liquid
being pumped. See figure 5.2, ref. number 221 on the right. In addition,
another cylinder, ref. 217 is attached to the inner diameter of the stator, and is
called the containment shell.

This design is more properly called a canned motor pump. See ANSI/HI 5.1-
5.6, Sealless Centrifugal Pumps for more detail.

This “can” design is also used with rotary type pumps. When the term
“can” refers to vertical turbine pumps, the pump bowl assembly and
column pipe are inserted in a vertical “can” with sufficient clearance
between the “can” and bowl outside diameter to increase the
submergence of the first stage impeller without friction loss in the downward
flow of the liquid.

Figure 5.2 — Canned motor pump: close coupled end suction, overhung impeller

15
Pump FAQ’s by Hydraulic Institute (UK) 16

16
Pump FAQ’s by Hydraulic Institute (UK) 17

Figure 2.64 — First stage impeller datum closed suction – can pump

See fig. 2.64 above and ANSI/HI 2.1-2.2, Vertical Pumps for Nomenclature and
Definitions for more detail.

Pump FAQs® March 2005 Article #2

Q. I understand that pump vibration is an important parameter in predicting the


imminent failure of a pump. Is this true? How is the vibration level measured,
and what is an acceptable level of vibration for ASME B73 Chemical pumps?
A. Yes, vibration measurements are very useful in predicting pump failure. Such
measurements should be taken on the outside of the pump bearing housing
closest to the coupling. Measurements should be taken in both the horizontal
and vertical direction perpendicular to the pump shaft with an instrument that
measures in units of velocity in inches per second RMS, unfiltered. The graph
from figure 9.6.4.4 shows the normally acceptable vibration level for ASME
B73 pumps.

It must be understood that these are field vibration values for pumps in good

17
Pump FAQ’s by Hydraulic Institute (UK) 18

condition, and exceeding them does not mean imminent failure. Your
experience with pumps that have failed will help you determine an appropriate
vibration level. More detailed information on this subject can be found
in ANSI/HI 9.6.4, Centrifugal and Vertical Pumps for Vibration Measurement
and Allowable Values.

Figure 9.6.4.4

Pump FAQs® March 2005 Article #1

Q. We operate a small plant and would like to improve the reliability of our
centrifugal pumps and minimize unplanned pump shutdowns. Can you suggest
a plan for monitoring pump performance to achieve our goal?
A. To begin with, we suggest a detailed review of each pump’s performance
history to determine which are more likely to fail and why. Based on this
review, take corrective action to upgrade the performance of the most
troublesome pumps.

Monitoring the performance of all of your pumps is the next step. There are
twelve main parameters which can be measured to prevent failure. These
include:

1. Input power
2. Temperature of key components such as bearings, seals, motor windings,
liquid pumped and more
3. Corrosion of pressure containment parts
4. Leakage from seals, gaskets, or pressure parts
5. Pressure of liquid at pump suction and discharge
6. Vibration at pump bearings
7. Lubricant cleanliness or degradation
8. Shaft runout at seal face
9. Rate of flow of pumped liquid
10. Maintenance inspection of critical components
11. Pump operating speed
12. Bearing wear

The frequency of recording these measurements depends on severity of the

18
Pump FAQ’s by Hydraulic Institute (UK) 19

results of failure and the likelihood of failure of the weakest performers. See
table 9.6.5.2 below for the recommended frequency measurement.

Implementation of this program requires considerably more information that is available


from ANSI/HI 9.6.5, Centrifugal and Vertical Pumps for Condition Monitoring.

Pump FAQs® March 2004 Article #2

Q. I understand that the efficiency of variable speed drives is reduced as operating


speed and power is reduced. Does this negate the power saving from the
accompanying reduction in pump speed?
A. The difference in the power consumption with and without the variable speed
drive must be evaluated. The power savings from the reduction in speed of the
pump is typically greater than the loss in efficiency of the driver. Assuming a
change in demand results in a reduction in pump speed of ten percent, the power
required by a 100 horsepower pump is reduced by the cube of the speed so at
ninety percent speed the power required is 0.90 cubed times 100 horsepower or
0.729 times 100 which equals 72.9 horsepower. At 90 percent of full speed the
efficiency of the drive may be reduced by about ten percent of that at full speed
and power. This depends on the design of the drive. If we assume the full load
efficiency of the driver is 92%, then:

electrical power = pump power / driver efficiency

= 100 / 0.92

= 108.7 horsepower

At 90% of full speed:

electrical power = 72.9 / 0.92 X 0.90

= 88.0 horsepower

19
Pump FAQ’s by Hydraulic Institute (UK) 20

Pump FAQs® March 2000 Article #2

Q. We are trying to standardize on a manufacturer of vertical pumps at our plant,


but before doing so we are trying to figure out what is critical in the design of
the pumps. In other words, what makes a vertical pump a GOOD vertical
pump? The vertical pumps we use here are mainly in service all the time. We
use them for pumping liquids from one tank to another part of the plant.

Any suggestions of where to look would be greatly appreciated.


A. I can appreciate your interest in wanting to standardize on a vertical pump
manufacturer and understand the wisdom of finding a GOOD pump which is
suitable for your applications.

Since you have indicated an interest in vertical pumps please refer ANSI/HI 2.1
– 2.5 Vertical Pumps and ANSI/HI Vertical Pump Tests. These standards
should help you to define what constitutes a GOOD pump design for your
service requirements. You may also wish to look at ANSI/AWWA E-101
Vertical Turbine Pumps which was developed by the American Water Works
Association. You may be interested to know that the HI Website
[www.pump.org] will be up and running in mid-April. The website will include
information regarding the HI, a supplier finder with manufacturer names cross-
matched to specific products and hyperlinks to member websites.

Pump FAQs® March 2000 Article #1

Q. I take issue with the second question in FAQs in the February 2000 issue. You
state that valves, elbows or other fittings attached directly to the pump discharge
port will not effect what happens inside the pump impeller and casing. One of
our customers installed a 500-hp double suction axial split case pump with
horizontal discharge and a right angle elbow mounted horizontally on the
discharge of the casing. Another right angle elbow was bolted to the first
elbow. When operated near the best efficiency point, the pump bearing
housings flexed vertically about ¼ inch, and the pump rotor was shuttling back
and forth axially. The pump bearings failed quickly as a consequence. When
the discharge piping was changed to add ten diameters of straight pipe between
the pump and the first elbow, the problem disappeared. Can you explain why?
A. We cannot provide a precise explanation of what took place inside this pump
casing, but apparently the discharge elbows created a hydraulic feedback, which
cause severe vibration in the impeller. The phenomenon is probably similar to
that caused by suction side circulation in the impeller. We thank you for your
input and ask if anyone else can explain what was happening.

Pump FAQs® June 2006 Article #3

Q. When very large pumps, both high rate of flow and high horsepower are

20
Pump FAQ’s by Hydraulic Institute (UK) 21

custom built, a smaller model may be built and tested to prove the proper
performance of the design. What are the rules for building such a model?
A. The model impeller should not be less than twelve inches outside diameter. All
dimensions of the model hydraulic passages, including the relative roughness
of the hydraulic passages in the impeller and casing, should be in accordance
with the model to prototype ratio.

The model test speed n1 and rate of flow Q1 shall be determined by the
following relationship:

n1/n2 = (D2/D1)(H1/H2)0.5

Q1/Q2 = (D1/D2)2(H1/H2)0.5

Where D = diameter and H = head

More detail is available in ANSI/HI 1.6 Centrifugal Pump Tests.


Pump FAQs® June 2006 Article #2

Q. I understand that NPSHR (required) by a pump is measured by the manufacturer


using cold water, and I do not find information on how to correct this for other
liquids. Hydrocarbons, for example, have a wide range of specific gravities and
vapor pressures which must affect the NPSHR performance of a pump. Is this
true?
A. Specific gravity and vapor pressure do not change the NPSHR of a centrifugal
pump. By definition, NPSHR is determined by test and is selected as the value
when the total head of the pump is reduced by three percent due to blockage of
the flow through the impeller by the formation of vapor bubbles.
The most simple NPSHR test is conducted using a closed tank to which the
pump is directly connected and the space above the liquid level in the tank is
kept equal to the vapor pressure of the liquid. When testing with cold water,
this is done by exhausting air or gas from the tank with a vacuum pump.
Under these conditions, the NPSHA (available) is equal to the height of the
liquid above the pump impeller.

When conducting the test, the rate of flow through the pump is kept constant
and the liquid level in the tank is gradually lowered while total head
measurements are recorded. The plot of test points will look like Figure 1.122
on the right.

If a liquid other than water is used, any difference in vapor pressure is


compensated by a change on the surface of the liquid. In a similar manner, if a
different specific weight of liquid is used, the reduced pressure due to the
column height is compensated by the reduced weight of a given volume of

21
Pump FAQ’s by Hydraulic Institute (UK) 22

pumped liquid.

There is another characteristic of liquid that does affect NPSHR. That is


its thermodynamic properties. Some high vapor pressure liquids produce a
lower volume of vapor when they boil and therefore less blockage in the
impeller vanes. See ANSI/HI 1.3 Centrifugal Pumps for Design and
Application for more information.

Figure 1.122 - NPSH Test With Rate of Flow Held Constant

Pump FAQs® June 2005 Article #1

Q. We use several metering pumps in our blending operation and are concerned
about their accuracy. How accurate are these pumps and does accuracy change
with different conditions?
A. Controlled volume metering pumps are reciprocating positive displacement
pumps and are used in applications requiring highly accurate, repeatable and
adjustable rates of flow. Accuracy is a compound definition composed of
steady state accuracy, linearity and repeatability. Specific values for your
pumps can be obtained from the manufacturer.

Steady state accuracy is the variation in the rate of flow over a specific period
of time, under fixed pump and system conditions, expressed as a percent of the
maximum calibrated rate of flow. Steady state accuracy applies over a defined
turndown ratio.

Linearity is an expression of maximum deviation (plus or minus) of a series


of measured rates of flow values versus rate of flow setting points to

22
Pump FAQ’s by Hydraulic Institute (UK) 23

corresponding points on a theoretical best fit straight line drawn through the
points on a graph. Linearity is expressed as percent of maximum calibrated
rate of flow. See the figure on the right.

Repeatability is the rate of flow variation resulting from a specific excursion


from a rate of flow set point, followed by a return to that set point, expressed
as percent of maximum calibrated rate of flow.

More information on this subject can be found in the soon to be published


standard, ANSI/HI 7.1-7.5 Controlled Volume Metering Pumps .

Pump FAQs® June 2004 Article #3

Q. I am aware that pump shafts must be carefully aligned with the driver shaft
before start-up. This requirement is clearly stated in every pump manual.
However, how carefully aligned is seldom answered. Is there a simple
guideline for allowable misalignment measurements?
A. There is no single answer to this question. Misalignment often occurs in any of
the following ways:

• parallel offset

23
Pump FAQ’s by Hydraulic Institute (UK) 24

• angular offset
• combination of both
• axial movement

The extent of the misalignment in these modes depends on the tolerance of the
driver, pump and coupling. By far, the coupling has the greatest ability to
tolerate misalignment.

Elastomeric couplings can tolerate all forms of misalignment by the distortion of


the elastomer. Most single metallic couplings such as gear, plate or grid type can
tolerate only angular misalignment. To accommodate parallel offset, metallic
couplings usually are supplied in pairs separated by a coupling spacer. The most
forgiving is the universal joint when supplied as a pair with a spacer shaft. The
allowable misalignment acceptable by the metallic couplings will depend on the
length of the spacer. The coupling supplier can provide the allowable
misalignment values for each type and size of coupling.

Parallel alignment can also be affected by thermal expansion during operation.


Pumping hot liquids or even heat from the summer sun can affect the alignment.
Pumps on hot applications should be realigned while the pump is at operating
temperature.

Space between the shaft ends must also be provide to permit free axial
movement of the shafts, especially with pumps on hot applications which will
cause axial expansion of the pump shaft.

Pump FAQs® July 2006 Article #2

Q. What is an API pump? I assume it is related to pumps used in the petroleum


industry, but what is special about it?
A. As you guessed, an API pump is one that was built in accordance with standards
published by the American Petroleum Institute. Five different pump types are
described by the following standards:

API 610 Centrifugal Pumps for Petroleum, Petrochemical and Natural Gas
Industries

API 674 Positive Displacement Pumps – Reciprocating

API 675 Positive Displacement Pumps – Controlled Volume

API 676 Positive Displacement Pumps – Rotary

API 685 Sealless Centrifugal Pumps for Petroleum, Heavy Duty Chemical, and

24
Pump FAQ’s by Hydraulic Institute (UK) 25

Gas Industry Services.

There are other API standards covering data sheets, sealing systems and sucker
rods.

In common usage, the term API pump usually refers to an end suction
centrifugal pump which is designed in conformance to API 610 for high
temperature and pressure petroleum products. A primary feature is the support
system which is at the centerline of the pump casing to minimize the effects of
thermal expansion.

Pump FAQs® July 2005 Article #2

Q. During the maintenance of centrifugal pumps, how much wear of the wearing
rings is considered normal, and what is the normal wearing ring clearance for a
new pump?
A. A simple answer is not available. Normal wear of centrifugal pump clearance
depends on many factors such as cleanliness of the liquid, viscosity of the
liquid, the presence and size of abrasive solids, the head developed by the
impeller and the operating speed.

The normal clearance range of a new pump can be obtained from the
manufacturer or his representative, but the figure below can be used as a
guide. Stainless steel impellers typically require greater clearance than bronze
or iron to avoid galling and seizing.

(Insert figure 18 from the Student Workbook for the Energy Reduction Video
- HERE.)

Pump FAQs® June 2004 Article #1

Q. We are considering the use of a magnetic drive pump for handling toxic liquids.
The containment shell between the inner and outer magnet assemblies is very
thin. We have concerns about wear in the shell and leakage of the liquid. Is our
concern valid, and what can be done to protect against leakage?
A. Leakage of toxic liquid from any type of pump is a valid concern. You can take
the following precautions regarding magnetic drive pumps:

• The containment shell material must be selected to resist corrosion and


erosion from the liquid being pumped. Magnetic containment shells shall be
designed for the maximum allowable working pressure within the stress
values for the materials in “Section VIII of the ASME Boiler and Vessel
Code”. There shall be a minimum ratio between bursting pressure and
design pressure of 2 to 1 for the pressure/temperature range in the pump.
• The gasket between the containment shell and the pump cover casing shall

25
Pump FAQ’s by Hydraulic Institute (UK) 26

be confined on the atmospheric side to prevent blowout. The design shall


consider thermal cycling which may occur as a condition of service.
• Sensors should be provided to measure and monitor the position of the inner
and outer magnet assemblies to prevent them from rubbing on the
containment shell.

• A secondary containment shell shall also be provided. This is usually done by


the outer housing which surrounds the outer magnet assembly, and a
suitable sealing device around the input shaft on the pump side of
the inboard bearing (Ref 16). See the figure below:

• Provide a leak detector or pressure sensor at an appropriate location in the outer


containment shell (frame, part 19 or cover, casing, part 239) to detect loss of primary
containment.

For further information see ANSI/HI 5.1-5.6-2000 Sealless Centrifugal Pumps.

26
Pump FAQ’s by Hydraulic Institute (UK) 27

Pump FAQs® July 2006 Article #1

Q. I have been told that the performance characteristics of centrifugal pumps are
changed when pumping viscous liquids such as hydrocarbons. How can this
performance change be calculated?
A. The answer to your question is not that simple. The members of the Hydraulic
Institute and a team of international experts put their collective experience

27
Pump FAQ’s by Hydraulic Institute (UK) 28

together and prepared a thirty-page document on this subject which was


approved as an American National Standard. It is designated as ANSI/HI 9.6.7
Effects of Liquid Viscosity on Rotodynamic (Centrifugal and Vertical) Pump
Performance.

The correction factors used in this standard are based on in-depth hydraulic
design calculations proven by extensive laboratory test data of many pumps on
liquids with a wide range of viscosities.

The correction factors are used to adjust the performance on water as shown
below in Figure 9.6.7.1 a and b.

Figure 9.6.7.1 — Modification of pump characteristics when pumping


viscous liquids

Pump FAQs® July 2006 Article #3

Q. We recently experienced line shaft failure in a multistage vertical turbine pump


with ten-inch diameter bowls. An analysis of the break pointed to torsional
fatigue as the cause but the pump was operating under full load in a steady mode
and vibration monitors did not show excessive vibration. How can the shaft fail
in fatigue under these conditions?
A. The existence of torsional vibration rarely shows itself in the pump column or
driver housing vibration. Thus, pump shafts, coupling or gears can fail without
the usual (radial) vibration monitoring equipment indicating any danger.

Rotor torsional critical speeds can be present any time there are two rotating
masses connected by a shaft that is not infinitely stiff. This implies that any
pump rotor coupled to a driver has a torsional natural frequency of vibration.
Torsional critical speeds are associated with torsional or angular deflection of
the rotor and are not to be confused with lateral critical speeds associated with

28
Pump FAQ’s by Hydraulic Institute (UK) 29

lateral deflection. The resulting stresses and angular deflections can cause
premature equipment failure.

With vertical pumps, the primary hydraulic exciting force is generated by the
impeller vanes passing the bowl vanes. The energy level of this force is
typically low, with resulting negligible vibration amplitudes.

On the other hand, when a pump is driven through a gear, the inaccuracies in the
gear teeth can provide the exciting force and high torsional critical speeds at
tooth meshing frequencies. Similarly, engines can also cause high torsional
vibrations at higher frequencies.

For more information on pump vibration, see ANSI/HI 9.6.4 Centrifugal and
Vertical Pumps for Vibration Measurements and Allowable Values.

Pump FAQs® July 2005 Article #3

Q. When checking the performance of a new centrifugal pump, the plot of the
resulting head versus rate of flow curve appears to be lower than the
manufacturer’s rating curve. How much deviation from the
manufacturer’s rating curve is normal?
A. The Hydraulic Institute Standard contains two performance test acceptance
tolerance levels, "A" or "B" which must be agreed to by both customer and
manufacturer. The acceptance tolerance applies to the specified condition point
only, not to the entire performance curve. It is recommended that the
contractual agreement contain the agreed upon acceptance level. The tolerance
for total head has four different categories that depend on the total head and rate
of flow. There is an alternate tolerance for rate of flow at the rated total head.
All of this is dependent on an agreement with the pump manufacturer to perform
a factory test to determine the true performance and take any necessary
corrective action before the pump is shipped. Field tests are seldom accepted as
reliable due to the difficulty of meeting the proper test procedures in the field
and making corrections.

Assuming acceptance level “A” is applicable and the rated conditions are
3500 gpm at 300 feet, the head variation at the rated flow is +5% to -0%. An
alternate tolerance in rate of flow at rated head is +10% to -0%.

Additional details are available in ANSI/HI 1.6 Centrifugal Pump Tests.

Pump FAQs® July 2004 Article #1

Q. When installing a horizontal pump, is it better to grout the pump baseplate or let
it float free? Different sources provide opposing views on this subject.

29
Pump FAQ’s by Hydraulic Institute (UK) 30

A. Whether to grout or not depends on the specific application and the design of the
baseplate. Applications that undergo wide temperature variation may do well
with floating baseplates in order to allow for movement of the pump and thereby
minimize pipe strain caused by thermal expansion of the pipe. However, the
baseplate in such cases must be sufficiently rigid and designed to avoid
misalignment of the shaft coupling as the baseplate moves.

Functional requirements:

The purpose of a baseplate is to provide a foundation under a pump and its


driver that maintains shaft alignment between the two. This baseplate must
allow for initial mounting and alignment of equipment, survive handling during
transportation to the installation site, be capable of being installed properly with
minimum difficulty, allow final alignment of the mounted equipment, and allow
removal and reinstallation of equipment. It must be recognized that it is not
necessary that an absolutely rigid baseplate be designed to meet these
requirements. At the same time, the baseplate must not be permanently
deformed after the equipment is mounted at the manufacturing facility.
Compliance with these design criteria, in conjunction with proper installation
procedure, will contribute significantly to meeting the functional requirements.

Free standing baseplate:

A free standing baseplate is a design which is intended to be elevated off the


floor or deck and supported by stilts or shims. This type of baseplate must be
designed to provide its own rigidity as there is no grout for support. See Figure
1.94.

Additional information and calculation of baseplate stiffness can be found in ANSI/HI


1.3-2000 Centrifugal Pumps for Design and Application

Pump FAQs® July 2005 Article #1

30
Pump FAQ’s by Hydraulic Institute (UK) 31

Q. We are designing a circular sump for the installation of three sewage pumps.
Because of local restrictions on the size, we are concerned that the pump intake
structure may not provide a good hydraulic design and are considering whether
to build and test of a model of the intake. How do we select the appropriate rate
of flow for the model test?
A. Models involving a free surface are operated using Froude similarity since the
flow process is controlled by gravity and inertial forces. The Froude number,
representing the ratio of inertial to gravitational forces, can be defined for pump
intakes as:

F = u/(gL)0.5

Where:

u = average axial velocity (such as in the suction bell entrance) in ft/sec

g = gravitational acceleration, 32.2 ft/sec2

L = a characteristic length (usually bell diameter or submergence) in ft.

The choice of the parameter that is used for velocity and length is not critical,
but the same parameter must be used for the model and prototype when
determining the Froude number. For similarity of flow patterns, the Froude
number shall be equal in both the model and prototype and solving for the
velocity in the model will answer your question.

In modeling a pump intake to study the potential formation of vortices, it is


important to select a reasonably large geometric scale to minimize viscous and
surface tension scale effects, and to reproduce the flow pattern in the vicinity of
the intake. In addition, the model shall be large enough to allow visual
observations of flow patterns, accurate measurements of swirl and velocity
distribution, and sufficient dimensional control. Realizing that larger models,
though more accurate and reliable, are more expensive, a balancing of these
factors is used in selecting a reasonable model scale. However, the scale
selection based on vortex similitude considerations is a requirement to avoid
scale effects and unreliable test results. Fluid motions involving vortex
formation have been studied by several investigators (Anwar, H.O. et al., 1978;
Hecker, G.E., 1981; Padmanabhan, M. and Hecker, G.E., 1984; Knauss, J.,
1987)

ANSI/HI 9.8 Pump Intake Design includes additional information on this


subject.

Pump FAQs® July 2002 Article #3

31
Pump FAQ’s by Hydraulic Institute (UK) 32

Q. We operate a vertical turbine type well pump that has a clutch at the top of the
motor that often disengages when the pump starts. What causes this to happen
and what can be done to prevent it?
A. Vertical turbine pumps are designed so that the downward thrust due to the
weight of the rotor and hydraulic force from pressure on the back of the
impellers is carried by a high thrust tapered roller bearing on the top of the
motor. This bearing is not capable of carrying any thrust in the upward
direction. However, during pump operation there is also an upward thrust on the
pump rotor caused by the change in momentum of the flow as it changes
direction from axial to radial at the entrance to the impeller blades.

This up thrust is usually less than the heavy down thrust from the weight of the
rotor and hydraulic forces so that no net up thrust occurs. However, at the
moment of start up, there is no resistance to flow and the pump operates
momentarily at a very high rate of flow. In this case there is little down thrust
from the impeller and maximum up thrust from the change in momentum
resulting in a net up thrust which disengages the motor clutch.

To correct this problem the pump rotor needs to be fitted with a thrust collar,
which is capable of resisting the momentary up thrust.

Pump FAQs® July 2002 Article #2

Q. Normal pump operation will eventually corrode and erode the inside of a pump
casing until the thickness of the casing wall is too thin for safe operation. How
can this safe thickness be determined and what are the potential consequences of
operating with less than proper thickness?
A. The minimum casing thickness for a pump is determined by the manufacturer
based on the maximum casing working pressure and temperature and the
material of the casing. This is done using finite element analysis or empirical
calculations based on test. The ASME Pressure Vessel Code is used to
determine the proper factor of safety for the casing material and the
manufacturer publishes the resulting minimum thickness. Pump manufacturers
also add a corrosion allowance to the minimum wall thickness so the casing as
manufactured can safely be eroded by the amount of the allowance.

Operating a pump with less than minimum wall thickness should be avoided.
However, the pump will not immediately fail because of the factor of safety and
possible operation below the maximum working pressure. The consequences of
failure will range from a leak in the casing wall to total fracture.

Pump FAQs® April 2002 Article #2

Q. Our plant uses a 10-inch vertical turbine pump, which is about 30 feet long, to
supply cooling water. The requirements have been changed and we need an

32
Pump FAQ’s by Hydraulic Institute (UK) 33

increase in flow of about 10%.

According to the pump rating curve, the pump should satisfy our needs, but it
does not. We have renewed the impeller wearing ring clearances, but we cannot
reach the rating curve performance. What else can be done? We cannot
increase the impeller diameter due to power limitations.
A. Increasing the pump column pipe diameter will certainly help. Most pump
manufacturer’s performance curves are limited to the bowl assembly
performance, since the length and diameter of the column pipe represent an
unknown variable.

Pump FAQs® April 2002 Article #3

Q. We have difficulty in getting wearing ring data for several older pumps. Is there
a general guideline on recommended wearing ring clearance that we can use?
A. In 1997 the Hydraulic Institute published a listing of recommended clearances
for a range of wearing ring diameters. This was included in an educational
video titled “Energy Reduction in Pumps and Pumping Systems.”

Pump FAQs® April 2004 Article #1

Q. I understand the importance of monitoring pump performance in order to


prevent unexpected pump failures. Performance parameters such as discharge
pressure, rate of flow, input power, and vibration are straight forward. But how
do we know when corrosion or erosion have reduced pump casing wall
thickness to the point at which casing failure may occur?
A. The casing wall thickness must be measured periodically to know when failure
is imminent. But you know this. Measuring the casing wall thickness is the
problem. To this end, several methods can be used:

• Visual inspection is the easiest and may be the most economical method.
However it is cumbersome and messy when dealing with corrosive liquids.
In addition, stress corrosion can occur without any visible signs, resulting in
sudden failure.
• Electrical resistance measurement of the casing wall using a metal probe
shows an increase in resistance as the casing thickness is reduced by
corrosion. However this is not useful in detecting localized forms of corrosion
such as pitting.
• Linear polarization is another method that involves measurement of a current
response to an applied potential through probes that are inserted in the
system. To use this method a conductive liquid is required.
• Ultrasonic thickness measurement can also be used. To use this method the
casing surface must be cleaned to bare metal. Ultra sound is not as accurate
as the other methods.

The frequency of wall thickness measurement depends on the expected

33
Pump FAQ’s by Hydraulic Institute (UK) 34

corrosion rate of the pump on the application. The last three methods lend
themselves to continuous monitoring or frequent checks by use of small,
portable devices. The visual method is more difficult, but the first measurement
should be made no longer than 3 months after start up.

Pump casings are designed with a built in allowance for corrosion. This
allowance can be supplied by the pump manufacturer. Contact the pump
manufacturer or his representative when the allowance has been reduced by 50%
or if a significant change in process conditions causes rapid reduction in wall
thickness. According to ANSI/HI 9.6.5 Centrifugal and Vertical Pumps for
Condition Monitoring, when measurements show that 70% of this corrosion
allowance has been lost, the pump should be “Shutdown”.

Pump FAQs® April 2004 Article #2

Q. Pumps operating in wet pit applications often suffer from the accumulation of
grit or other solid material which accumulates near the pump inlet. This
requires draining of the pit or removal of the pump to remove the solids. Is
there a better way?
A. It is often practical to build the pit with
sloping sides to minimize the horizontal
floor area. See the figure for an example.

The sloped walls should be a minimum of


60 degrees from the horizontal for concrete
or 45 degrees for steel. This design allows
the solids to collect at the pump inlet where
they can be swept away with the flow. The
pump should be periodically operated at its
maximum rate of flow to more effectively
carry away the solids. If two or more pumps
are in the pit, the one farthest from the inlet
to the pit may be run alone to remove the
solids. Verify the NPSHA to ensure there is
sufficient margin to operate at the high rates
of flow. ANSI/HI 9.8 Pump Intake
Design includes considerable detail on this
design.

Pump FAQs® April 2004 Article #3

Q. When pumping liquids with entrained solids, especially slurries, I understand


that hard material for the impeller and casing is recommended to resist erosion.
I also hear that soft rubbery material is also used. How can this be? When are

34
Pump FAQ’s by Hydraulic Institute (UK) 35

rubbery materials best used?


A. As a general guideline, hard metals are often used in applications characterized
by large, sharp edged solids, and elastomers for smaller round-edged solids.
Either high- chrome irons or elastomers are used for their corrosion resistance.
In special applications with low head requirements, solid ceramic-lined pumps
are used for pumpages containing fine material.

Pump speed is also a factor. Impeller tip speed, as distinct from rotational
speed, is often used as a guide for wear in the selection of slurry
pumps. ANSI/HI 1.3 Centrifugal Pumps for Design and
Application recommends the following maximum impeller tip speeds:

• dirty water-130 ft/sec


• medium slurries up to 25% solids and 200 micron solids- 115 ft/sec
• higher slurry concentrations and larger solids-100 ft/sec

• pumps fitted with elastomer impellers- 85 ft/sec.

Pump FAQs® April 2005 Article # 1

Q. We operate a number of end suction centrifugal pumps on a chemical process


application. The seals operate well, but the anti-friction bearings fail in less than
twelve months. Is this normal? If not, what can be done to increase bearing
life?
A. No, pump bearings are usually selected to provide a minimum of two years
continuous operation before failure and the average bearing life is about five
times longer. The next time the bearings fail, check for the following during the
bearing replacement process:

• Shaft coupling alignment: Poor alignment imposes additional loads on the


bearings which will reduce bearing life. For pumps operating in higher
temperature service, hot alignment checks are recommended. Shaft
alignment can be affected by nozzle loads. Be sure that when the pump is
running, the nozzle loads are within acceptable levels. Normally, however,
poor alignment will also lead to premature seal failure.
• Lubricant amount, condition, and cleanliness: Corrosive chemicals,
water, or solids in the oil will attack the bearings and reduce life. Make sure
the bearing cover seals are replaced each time, and if necessary retrofit the
pumps with more elaborate labyrinth bearing seals. Also make sure that the
shaft-mounted rotating flingers are close to the bearing seals to help keep
contaminants away. Follow the manufacturer’s recommended lubrication
intervals. Where grease lubrication is used, use caution and do not
overlubricate the bearing.
• Bearing fit on the shaft: If the shaft diameter under the bearing is too
large it will expand the ID of the inner race of the bearing excessively and
preload the rotating elements of the bearing beyond the recommended
levels. Check the bearing manufacturer’s catalog for the recommended
shaft dimension. Verify that the internal preload of the bearing meets the
recommendation of the pump manufacturer.

35
Pump FAQ’s by Hydraulic Institute (UK) 36

• Bearing assembly procedure: When the replacement bearing is pressed


onto the shaft, make sure that the pressing force is applied evenly to the
inner race only and not to the outer race. Be sure to follow the
manufacturer’s recommendations when preheating the bearing is
required. Care shall be taken to install the bearing square with the pump
shaft, providing uniform contact with all shoulders, rings, and checknuts on
the shaft and in the bearing housing.
• Coupling half assembly: Most couplings are designed with a light
interference fit on the shaft. If the coupling half is assembled to the shaft
with a hammer or press, the restraining force should be applied to the
impeller end of the shaft and not to the pump frame, which will transfer the
load to the bearings.

Finally, when back in operation check that the pump is operating within the
manufacturer’s allowable operating region. Verify that the bearing
temperature and vibration levels are within acceptable limits.

Pump FAQs® April 2005 Article # 2

Q. I have been told that reciprocating pumps must be protected against operation
with a closed discharge valve, but that is not necessary with air operated
diaphragm pumps. Is this true and why?
A. Yes, it is true. Motor driven reciprocating pumps continue to rotate when the
discharge valve is closed. The closed valve prevents the fluid from exiting the
pump, subjecting the motor and other pump components to excess internal stress
due to the high torque that is generated by the motor as load increases and speed
is reduced by that load. Bypass valves, clutches and other mechanisms are
necessary to allow safe operation in this condition. With air operated
pumps, when the discharge valve is closed, the air and fluid pressures equalize
and the diaphragm or bellows stops reciprocating. There is little additional
stress generated because the pressures on both sides of the diaphragm are equal.
The pump end is designed to withstand the force generated by the maximum
rated air pressure so as long as the air pressure is below the rated air pressure,
the pump cannot be damaged. The Hydraulic Institute standard, ANSI/HI 10.1-
10.5 Air Operated Pumps contains much useful information on these pumps.

Pump FAQs® April 2005 Article #3

Q. The December 2004 issue of P&S included a question and answer on air
entrainment in rotary pumps which I found to be useful. Is there similar
information on rotary pumps handling liquid with solids or slurries?
A. Yes, ANSI/HI 3.1-3.5 Rotary Pumps includes several good pages on this
subject.

Rotary pumps may be used for in-plant process and pipeline transfer of slurries
when metered flow or medium-to-high discharge pressures are required. Since
volumetric efficiency and therefore mechanical efficiency are normally

36
Pump FAQ’s by Hydraulic Institute (UK) 37

dependent on the clearances between the pumping elements of a rotary pump,


care must be taken in the selection and application of the pump in slurry service.
Slurries containing hard particles can cause abrasive wear in rotary pumps.
The size and general shape of the solids in a slurry normally govern whether a
particular rotary pump configuration and/or clearances can be used for the
slurry in question. Usually the clearances must be greater than particle size. In
some pumps, the rotor configuration will accept large particles as long as the
size, distribution and shape are controlled. Thus, the size must be related to
porting, rotor cavity size, configuration and interaction and operating
clearance.

The effect on rotary pump performance can vary widely as slurries change
with time, control, character, etc. Low concentrations of fine non-settling
solids in a Newtonian fluid carrier may have no appreciable effect on either
the power requirements or the pump rate of flow. Generally, as the percentage
and size of the solids increase at given conditions of operation, speed and
pressure, the pump input power curve increases (see Figure 3.34).

Although rotary pumps are capable of limited slurry handling, the particular
rotor and housing configuration make the various rotary designs more or less
adaptable to specific types of slurry. Many slurries similar to paper stock
require open porting and clearances and definite minimum velocities of flow.
Clay slurries require low shear rate.
Figure 3.34 - Differential Pressure Vs. Pump Input Power

Pump FAQs® April 2006 Article # 2

Q. What is a balancing disc or drum? I understand that multistage pumps, such as

37
Pump FAQ’s by Hydraulic Institute (UK) 38

on boiler feed service, usually use such a device to balance hydraulic thrust.
Figure 1.21 below shows the last two stages of a multistage pump with a
balancing disc shown on the left. The space between the last impeller and the
balancing drum is under full discharge pressure which creates a force to the right
over the area of the impeller eye, which at the suction end is under suction
pressure. The resulting force can be very large, and difficult to restrain with a
thrust bearing.
A. To counterbalance this force a disc or cylindrical drum, with the same
diameter as the impeller wearing ring, is mounted on the shaft. The hydraulic
pressure acting on this device creates a force in the opposite direction from the
impeller thrust, thereby balancing the force on the impellers. This reduces the
net axial unbalance to practically zero.

Figure 1.21 shows a balancing disc which is slightly larger than the wearing
ring. The pressure here will push the pump rotor to the left, but as the disc
moves, the space between the disc and stationary member opens with a
resulting flow of liquid which is pipe back to the suction.

There is a close clearance bushing between the impeller and disc so as liquid
flows the pressure on the disc drops and the space between the disc and
stationary member closes. This makes the rotor self adjusting so the net thrust
is always zero.

If a cylindrical drum is used in place of the disc, the thrust can be effectively
balanced, but the self adjusting feature will be lost, and an appropriate thrust
bearing will be required.

Figure 1.21 - Multistage Pump with Balancing Disc

38
Pump FAQ’s by Hydraulic Institute (UK) 39

Pump FAQs® April 2006 Article #1

Q. We need to replace several pumps handling paper stock, and need to know what
special problems we should look out for. Can you help with such information?
A. Paper stock varies considerable depending on the wood source that is used and
the consistency of the stock.

Low-consistency stock usually refers to a class of products with 1 to 7 percent


fiber content by weight. These paper stocks are normally handled by end-suction
centrifugal pumps equipped with semi-open impellers and contoured wear
plates.

Medium-consistency stocks are made of 8 to 15 percent paper fiber. The


rheological properties of fiber-water suspensions in this range are dependent on

39
Pump FAQ’s by Hydraulic Institute (UK) 40

the properties of the individual fibers and the viscoelastic network that they
form. Special designs of centrifugal pumps are required to handle this type of
paper stock. For example, some form of “shear generator” is needed at the
inlet to create turbulence and reduce the effective fluid viscosity. Special
impeller design and air-extraction devises are also required to prevent air
binding.

An end-suction centrifugal pumping unit must be specifically designed to handle


medium consistency stock mixtures without clogging the device, or dewatering
the stock. A large suction-eye and unobstructed waterways can be provided by
an overhung, semi-open impeller design. This keeps the suction velocity low to
promote smooth flow, avoid air binding and prevent separation of stock fibers
from water. The contoured front surfaces of the impeller vanes interface with the
replaceable wear plate. This arrangement provides a self-cleaning effect
whereby the impeller resists clogging to improve its reliability.

High consistency paper stocks contain more than 15 percent paper fiber, and are
found in the bleaching operation. Centrifugal pumps cannot handle such high
consistency, and therefore positive-displacement rotary units are used. Proper
suction piping design has to be included to help this high solids mixture to enter
the suction cavities of the rotary pump.

More information on this subject can be found in ANSI/HI 1.3 Centrifugal


Pumps for Design and Application.

Pump FAQs® August 2004 Article #2

Q. Our company operates a high pressure process during which the liquid is
throttled to low pressure after processing. We are considering the use of a
power recovery turbine to recover some of the energy lost by throttling. Can a
typical centrifugal pump be used as a turbine, and if so, what precautions must
be taken?
A. Yes. A typical centrifugal pump can be used as a turbine, however, selection and
installation must be done carefully. While operating in the turbine mode, the
performance characteristics of a pump as turbine (PAT) differ significantly from
operation in the pump mode.

The PAT should be selected by the pump manufacturer to insure that the
selection is both hydraulically and mechanically suited for the application.
Precautions must also be taken to insure that the PAT will operate without
cavitation. The turbine industry uses the terminology TREH (Total Required
Exhaust Head) and TAEH (Total Available Exhaust Head) in place of NPSH.
Some of the other factors which affect the use of pumps as turbines include:

40
Pump FAQ’s by Hydraulic Institute (UK) 41

• Runaway speed
• Liquid flow at runaway speed
• Required solids passage
• Liquid borne abrasives
• Torque reversals during start-up or shut-down

• Overspeed trip and control

Pump FAQs® August 2004 Article #3

Q. One pumping system in our plant makes a load bang when it is shut down. I
have been told that this results from water hammer. What causes water hammer
and what can be done to correct it?
A. Water hammer may have severe effects and damage parts of the pumping
system. It results when liquid flowing through a relatively long length of pipe is
suddenly stopped. The velocity energy of this large mass of liquid is suddenly
converted to pressure energy with a resounding bang. It’s like trying to stop
a long railroad train within in a short distance.

Some suggestions for correction include the following:

• Reduce the liquid flow gradually before stopping the pump


• Add a liquid chamber with an air cushion to absorb the energy
• Reduce the pump speed slowly by using a variable speed drive or by adding
a flywheel

• Install a check valve that closes slowly to minimize shock

Pump FAQs® August 2005 Article #1

Q. When purchasing pumps for water supply systems, is there a simple way to
determine the maximum allowable speed for a specific application? If so, what
factors should be considered?
A. The primary factor to be considered when estimating the maximum pump speed
for water supply systems is minimizing the potential for cavitation damage.
Experience has shown that cavitation risk is minimized when the pump suction
specific speed is equal to or lower than 8500 in US units. Suction specific speed
is a characteristic of a pump, which is determined by the following equation:

S = nQ0.5 / NPSHR0.75, where:

S = suction specific speed

n = speed of pump in rpm

41
Pump FAQ’s by Hydraulic Institute (UK) 42

Q = pump rate of flow in gpm for single suction pumps and half total flow for
double suction pumps

NPSHR = net positive suction head required in feet

If we solve this equation for n, substitute 8500 for S and NPSHA for NPSHR,
we get:

n = ((8500) x (NPSHA)0.75) / Q0.5

Substituting the systems values for NPSHA and Q will give the maximum
recommended speed for this application. Q can also be varied by changing the
number of simultaneously operating pumps in the system

Another consideration is maximizing pump efficiency. Again, experience has


shown that centrifugal pump efficiency is maximum when pump specific speed
is between 2000 and 4000 in US units. Specific speed is determined by the
following equation:

NS = nQ0.5 / H0.75 where:

NS = specific spee

n = speed of pump in rpm

Q = pump discharge rate of flow in gpm for both single suction and double
suction pumps

H = pump total head in feet.

The figure below shows the efficiency correction or reduction as a function of


specific speed. Refer to ANSI/HI 1.3 Centrifugal and Vertical Pumps for Design
and Application for additional details.

42
Pump FAQ’s by Hydraulic Institute (UK) 43

Pump FAQs® September 2006 Article #1

Q. I understand that the radial force on a centrifugal pump impeller increases as the
pump is throttled to lower rates of flow. Why does this occur and how can this
force be calculated?
A. In a properly designed centrifugal pump, the distribution of flow and pressure
around the impeller is uniform at the design rate of flow. Consequently, there is
little if any unbalance of forces around the impeller and very low net radial
force. When the rate of flow is reduced by throttling, some of the liquid from the
impeller is forced back into the casing volute causing an unbalance of flow and
an unbalance in pressure distribution. The flow velocity is higher in the vicinity
of the volute tongue and the pressure is lowest at that point. The result of this is
an unbalance in pressure distribution around the impeller and a net force or
thrust in the radial direction.

This phenomenon was studied experimentally in the early 1950s, and the
following equation was developed:

Where: RT = radial thrust in pounds

K = thrust factor from figure 1.81 below

H = pump head per stage in feet

s = specific gravity of the liquid

43
Pump FAQ’s by Hydraulic Institute (UK) 44

D2 = impeller diameter in inches

b2 = impeller width at discharge including shrouds in inches

The radial thrust must be supported by the pump shaft and bearings. Higher
radial thrust loads may contribute to shorter bearing life and deflection at the
pump seals causing premature seal failure. More detail on this subject can be
found in the American Standard “ANSI/HI 1.3 Centrifugal Pumps for
Design and Application”.

Pump FAQs® September 2005 Article #1

Q. How can we get longer life from the ball bearings in our pump? Our process
uses an end suction centrifugal pump to circulate heat transfer liquid at 750
degrees F. The bearing housing is cooled, and the bearings look clean after they
fail. What else should we look for?
A. Pump bearings are most likely to fail due to contamination and poor lubrication.
However, that does not seem to be the case since the bearings are clean. In
addition, the bearing cooling is a big help.

That leaves the matter of excess bearing load. This is also consistent with the
regularity of the failures.

One common cause of high bearing load is coupling misalignment. If the


coupling halves are aligned when the pump is cold, they will usually move out
of alignment as the pump heats up. Even with the pump supports at the shaft
centerline, some movement from pipe stains is still possible. To avoid this
problem, shut down the pump when it reaches operating temperature and
recheck the coupling alignment. Realign the coupling if necessary.

Another cause of high bearing load is operation below fifty percent of the pumps
best efficiency rate of flow. At low flow rates, all of the flow from the impeller

44
Pump FAQ’s by Hydraulic Institute (UK) 45

cannot exit from the pump casing so it recirculates in the impeller. This causes
an uneven distribution of pressure around the impeller resulting in a high radial
force on the impeller which must be supported by the bearings. To guard against
this, determine the actual rate of flow through the pump and make sure it is close
to the pumps best efficiency flow.

Another problem which is unique to high temperature applications is excessive


expansion on the bearing inner race. Even with bearing cooling, heat is
transmitted to the bearing through the pump shaft. This heat causes the shaft
diameter and the inner raceway of the bearing to expand which in turn squeezes
the rotating balls in the bearing. The result is shorter bearing life which can be
corrected by using bearings with greater internal clearance. Such bearings may
also be referred to as C3 Fit bearings.

Pump FAQs® September 2004 Article #3

Q. The hydraulic coverage charts for standard pump lines published by


manufacturers form a rectangular grid with pump size varying with rate of flow
horizontally and total head vertically. How do pump manufacturers determine
the design rate of flow and total head for each pump in the series?
A. The horizontal spacing between pumps is determined by a reasonable flow
velocity for the discharge opening of the pumps. The popular pipe sizes, 1,
1½, 2, 3, 4. 6 inch etc. also double in area in progression. Hence, pumps
increase in rate of flow in a doubling progression.

Total head between pumps usually increases by a factor of 1.6. This allows an
acceptable cut down range between pumps without an excessive reduction in
efficiency at the lower end of the pumps coverage. These factors of 2 for rate of
flow and 1.6 for head also result in diagonally spaced pumps having the same
design specific speed (NS). For example, a 3 inch discharge pump with a 10
inch impeller has the same NS as a 4 inch with 13 inch impeller and is therefore
geometrically similar. This makes the designer’s job easier.

Finally, experience, competition and standards play a big role as each


manufacture attempts to compete with all others.

Pump FAQs® September 2004 Article #2

Q. Many sources, including the Hydraulic Institute e-learning program Centrifugal


Pumps: Fundamentals, Design and Application, describe the use of Affinity
Laws which are used to predict the performance of a centrifugal pump when the
impeller diameter is reduced or cut down. One of the laws says that Q1/Q2 =
D1/D2, where Q is the rate of flow and D is the impeller diameter.
However, ANSI/HI 1.6-2000 Centrifugal Pump Tests says that at a given speed,

45
Pump FAQ’s by Hydraulic Institute (UK) 46

Q1/Q2 = (D1/D2)2 (H1/H2)0.5 which is equivalent to Q1/Q2 = (D1/D2)3. Which is


correct, or is there some explanation for the difference?
A. Both are correct for their intended use. The Affinity Laws are used to predict the
performance of an existing impeller of known performance when its diameter is
cut or reduced in the order five or ten percent. This is an empirical relationship
and is reasonably accurate for diameter reductions up to five percent, and to
some degree up to ten percent.

The modeling laws as described in the HI Test Standard are used to compare the
performance of two distinct pumps which are of different size but geometrically
similar.

They are also used by pump designers when they design a new pump based on
the geometry of an existing pump of a different size. The modeling laws are
very accurate provided that the surface roughness of the waterways as well as all
other dimensions of the impeller are kept to the same proportions as the original.
In addition to the impeller dimensions the casing dimensions are modeled as
well. This is a true three dimensional comparison, so the rate of flow changes as
the third power of the impeller diameter.

On the other hand, when the diameter of an existing impeller is cut down, no
other dimensions change, and the effect on rate of flow is linear.

Pump FAQs® September 2004 Article #1

Q. I understand that pipe strains are bad for pumps and should be avoided.
However, some installations inherently have this problem due to temperature
changes which result in thermal expansion of the piping. Expansion joints are
designed to relieve such forces, but what else can be done to solve this
problem?
A. Expansion joints have a problem too. Typical expansion joints do not restrain
the axial forces in the piping due to the liquid pressure. For example, the axial
force caused by 150 psi pressure in a six inch pipe is 4,241 pounds. This force is
usually restrained by the pipe, but with an expansion joint, the pipe do not do
this. Such forces must be carried by the pump if the expansion joint is close to
the pump. The maximum allowable force on the discharge flange of an 8X6X13
ANSI B73.1 pump is 3500 pounds according to ANSI/HI 9.6.3-2000
Centrifugal and Vertical Pumps for Allowable Nozzle Loads. At 150 psi, this
allowable limit would be exceeded.

Another approach to this problem is a free floating pump or a spring mounted


baseplate. Close coupled pump designs can facilitate this approach. Vertical-in-
Line pumps are a variation of the close coupled design and are available for
many process applications. VIL pumps can transmit substantial forces through
the casing between the discharge and suction pipe. ANSI/HI 9.6.3 shows and

46
Pump FAQ’s by Hydraulic Institute (UK) 47

allowable force between discharge and suction of a 4 inch discharge pump to be


18,704 pounds.

Spring mounted baseplates can also work well, but the baseplate must have
sufficient stiffness to maintain coupling alignment without relying on a concrete
foundation.

Pump FAQs® September 2002 Article #3

Q. I understand that centrifugal pumps are not well suited to handle viscous
liquids. Is there an easy way to evaluate the viscosity value above which
centrifugal pumps are not recommended?
A. Centrifugal pump performance is significantly impaired when pumping liquids
with viscosities that exceed 1000 SSU. Above 10,000 SSU they are almost
useless. Additional guidance on this subject may be found in the Hydraulic
Institute Standard ANSI/HI 1.3—2000 Centrifugal Pumps for Design and
Application. Page 25 of this standard contains the correction chart that appears
in Figure 2 below.

47
Pump FAQ’s by Hydraulic Institute (UK) 48

Pump FAQs® September 2002 Article #2

Q. We are operating an end suction pump with an elbow connected to the suction

48
Pump FAQ’s by Hydraulic Institute (UK) 49

flange. The suction connection is eroded on one side due to the uneven flow
coming out of the elbow. Is there a simple solution?
A. An improvement can be achieved by using a reducing elbow at the pump.
Reducing two pipe sizes is better than one. If the existing suction line will not
permit this, it should be increased to 2 sizes larger than the connection at the
pump.

A few years ago, one pump manufacturer designed a special elbow that looked
similar to the one shown in Figure 1. Tests showed that this design provided a
more uniform flow output.

Pump FAQs® September 2002 Article #1

Q. One of our utility pumps takes suction from a river that frequently becomes
muddy. The bronze impeller and wearing rings become badly eroded more
quickly than anticipated. What do you recommend to increase useful impeller
life?
A. There are several approaches you may want to consider:

1. Reduce the solids content from the liquid by installing a settling chamber or
cyclone separator upstream of the pump suction.
2. Operate the pump close to its best efficiency point (BEP). This will help to
optimize the angle with which the vane and liquid meet thereby minimize
erosion.
3. Upgrade the impeller material to something more abrasion resistant such as

49
Pump FAQ’s by Hydraulic Institute (UK) 50

series 400 stainless steel.

4. Replace the pump with one that is specifically designed for abrasive service.
You can locate abrasive pump suppliers on www.pumps.org under the
Supplier Finder section.

Pump FAQs® September 2001 Article #2

Q. Is it an acceptable practice to select centrifugal pumps at rates of flow that are


less than 50% of the Best Efficiency Point (BEP) in order to get a pump, which
requires lower values of Net Positive Suction Head Required (NPSHR)? Most
pump curves indicate lower values of NPSHR at lower rates of flow.
A. Continuous operation of centrifugal or vertical pumps below 70% of the BEP
may result in the following problems:

• Recirculation in flow occurs on both sides of the impeller, which causes


cavitation damage to the impeller, excessive noise, and high vibration of the
pump rotor.
• Unbalanced radial forces, which act on the outside diameter of the impeller,
increase as the rate of flow is reduced. This phenomenon is typically more
severe in single volute designs. It results in reduced bearing and
mechanical seal life and may cause premature fatigue failure of the pump
shaft.
• The pump efficiency at 50% of the BEP is considerably lower than at the
BEP. Operating a pump in this manner will require more energy (higher
operating costs), which could be offset by selecting a pump which may have
a greater initial cost and operates at a lower speed and has a lower NPSH
requirement.

This subject is covered in greater detail in ANSI/HI 9.6.3-1997 Centrifugal and


Vertical Pump for Allowable Operating Region.
Pump FAQs® September 2001 Article #1

Q. I know that pumps should not be subjected to excessive forces and moments
from the system piping, but how do excessive forces damage the pump and what
is the weakest link in this regard?
A. Pump damage due to excessive forces and moments from system piping can
cause damage in the following ways:

• Shaft coupling misalignment – Excessive pipe loads can distort the pump
or its baseplate such that the alignment of the driver and pump shaft is
forced beyond that which the coupling can tolerate without transmitting
unacceptably high loads to the shafts. The result is shortened life of the
coupling, bearings and mechanical seals.
• Holddown bolt failure – This can include elongation of the holddown bolts
resulting in shaft movement at the coupling as well as reduced friction
between the pump and baseplate causing the pump to move relative to its
baseplate, thereby affecting the shaft coupling alignment.
• Excessive stress in the pump nozzles – The suction and discharge

50
Pump FAQ’s by Hydraulic Institute (UK) 51

connections of the pump are already under stress due to the internal
pressure in the pump case. Additional stress from the system piping can
result in excessive stress in the casing structure. This is particularly
dangerous with casings produced from a brittle material, such as cast iron.
• Internal pump distortion – End suction pumps, which are built with
supports under the bearing housing, can be distorted by excessive piping
strain which affects the internal alignment between the rotating and
stationary parts. This may result in contact between these parts as well as
misalignment of the mechanical seal faces. Premature seal failure and
wearing ring damage may occur. Bearing life may also be affected.

Which of these problems becomes the weakest link depends on the specific
pump design configuration and the direction or plane in which the forces and
moments act. A recently published document, ANSI/HI 9.6.2–2001
Centrifugal and Vertical Pumps for Allowable Nozzle Loads contains
recommended allowable loads for specific pump types and further explains the
problem.

Pump FAQs® September 2000 Article #3

Q. We are designing a system with nine horizontal centrifugal pumps that will take
suction from a common header. Is there a design standard or good practice that
will provide information on the maximum water velocity in the suction header?
A. The Hydraulic Institute publishes ANSI/HI 9.8 – 1998 Pump Intake Design,
which provides information and design recommendations for suction piping.

“The ideal flow entering the pump inlet should be of a uniform velocity
distribution without rotation and stable over time.”

“The suction piping should be designed such that it is simple with gentle
transitions in changing pipe sizes. Transitions resulting in flow deceleration at
the pump shall not be used.”

“The maximum recommended velocity in the suction piping is 2.4m/sec or


8.0 ft/sec. Velocities may be increased at the pump suction flange by the use of
a gradual reducer.”

Pump FAQs® October 2006 Article #1

Q. Due to a recent thrust bearing failure in one of our deep well pumps, we would
like to determine the down thrust on the bearing from the pump. Is there a
simple way of calculating this?
A. Following is a simplified version of this calculation, which is found in Hydraulic
Institute Standard, ANSI/HI 2.3 Vertical Pump for Design and Application.
This equation is for impellers with no back wearing ring and applies to operation

51
Pump FAQ’s by Hydraulic Institute (UK) 52

at BEP only.

The approximate down thrust at BEP in pounds is calculated as follows:

Where H = Single stage head at BEP in feet


s = Specific gravity of pumped liquid
C = Experimental coefficient from figure 2.45
Adf= Area of impeller front wearing ring minus shaft area in in2
B = Number of bowls
W = Total weight of all impellers and shaft in pounds

Figure 2.45 provides the experimental coefficient “C”, which includes the
impeller flow momentum change. This coefficient was obtained from a number
of tests on vertical pumps with specific speeds from 1700 to 12000. The lines
represent an average of these tests. A pump manufacturer’s specific design

52
Pump FAQ’s by Hydraulic Institute (UK) 53

may have a slightly different “C” value.

Pump FAQs® October 2004 Article #3

Q. We are expanding our building, including the fire protection system. If the
existing fire pump must be replaced, what special requirements must we look for
in their replacement?
A. The purchase and installation of fire pumps must comply with strict regulations
established by the National Fire Protection Association (NFPA) as published in
their “Pamphlet 20, Standard for the Installation of Stationary Pumps for Fire
Protection” and “Pamphlet 25, Standard for Inspection, Testing and
Maintenance of Water Based Fire Protection Systems.”

More specific pump design requirements are also enforced by “Underwriter


Laboratories” (UL) and “Factory Mutual” (FM). These requirements
include the following:

• Pump type: Axially split case, end suction, vertical-in-line or vertical turbine
pump.
• Performance requirements: shut off head, head at 150% of rated flow,
suction lift capability and maximum horsepower requirement.
• Mechanical requirements: shaft strength, bearing life, no mechanical seals,
materials of construction and hydrostatic test pressure.
• Design approval by UL or FM based on their review of the pump design and
witness of factory tests to insure that the pump performance meets their
criteria. Approved pumps may then carry an FM or UL label when shipped.

A list of approved fire pump manufacturers can be found on the Hydraulic


Institute web site www.pumps.org under Supplier Finder.

Pump FAQs® October 2005 Article #1

Q. With the ever increasing cost of oil and resulting increases in the cost of power,
what can be done to decrease the operating cost of existing pump systems?
A. With existing pump systems, the most cost effective change that can be made
is converting to variable speed drives for your pumps. At the same time,
existing control valves must be removed. The result will be a reduction in the
head loss in the system and lower operating speed for the pumps. See the
figure on the right for an example of this effect. If you do the math, you
should see a one or two year payback on the cost of conversion.

• Other opportunities for power savings include:


• Maintain pumps close to new condition to avoid efficiency loss.
• Don’t allow for excess margin in rate of flow or head.
• Review the pump selection and use a more efficient pump design if possible.

53
Pump FAQ’s by Hydraulic Institute (UK) 54

• Use two or more smaller pumps instead of one larger pump so that excess capability
can be turned off.
• Use pumps operating as turbines to recover pressure energy that would otherwise be
wasted.

The Hydraulic Institute publishes an education program on this subject titled, “Energy
Reduction in Pumps and Pumping Systems." Visit the e-Store at www.pumps.org for
details.

Pump FAQs® October 2004 Article #2

Q. I have heard that the rate of flow through centrifugal pumps can be regulated by
submergence control instead of by throttling. How does this work, and does it
cause damage to the pump?
A. Submergence control is sometimes used in applications where NPSH Available
to the pump is limited and the pump would naturally be operating with marginal
NPSH. A good example is condensate pumps in steam power systems.

Condensate pumps take condensed steam from the bottom of the steam
condenser (hotwell). Ideally, when operating at the design conditions, the liquid
level in the condenser hotwell provides sufficient NPSH to the pump so that it
operates on the head curve, producing the design rate of flow. When the load on
the electric generator is reduced, the steam required is reduced and the amount
of condensed steam entering the condenser hotwell is reduced. This reduction in
condensate causes the pump to draw down the level of liquid in the condenser,
thereby reducing the NPSH available to the pump. The reduction of NPSH

54
Pump FAQ’s by Hydraulic Institute (UK) 55

available to the pump causes it to cavitate, resulting in a reduction in the rate of


flow. If the load on the generator does not change, the pump will operate in this
mode until the load is increased back to normal.

The continuous cavitation in the impeller can be damaging to the pump, but this
can be compensated for by selecting a more cavitation resistant impeller
material, and using a more rugged design of the pump shaft and bearings.

Pump FAQs® October 2004 Article #1

Q. I know that a centrifugal pump can overheat badly if run at shut off for some
time, but how can I determine the minimum rate of flow through the pump to
avoid excess temperature build up?
A. A commonly accepted practice limits temperature rise through a pump to 15°F.
For most installations, this is adequate and minimum flow may be calculated
with this equation:

Where:

Q = minimum flow rate, gpm;

Pp = input power at the minimum flow, hp;

2.95 = constant;

Cp = specific heat, BTU/lb-°F;

s = specific gravity.

At the minimum flows calculated using the above equation, the power input is
approximately the same as at shut-off.

Catastrophic failure of the pump and associated equipment may result if the
liquid within the pump casing is allowed to vaporize. To prevent flashing, a flow
must be maintained through the pump which will keep the liquid below its
saturation temperature.

Minimum flow is guaranteed by installing a bypass from the discharge line to


some low-pressure point in the system. The bypass should not lead directly back
to the pump suction.

55
Pump FAQ’s by Hydraulic Institute (UK) 56

An orifice installed in the bypass line breaks down the differential pressure
between the pump discharge and the low-pressure point in the system.

The bypass may be manually or automatically operated but must be open during
periods of light load or when starting or stopping the pump.

This subject is discussed in greater detail in ANSI/HI 1.3 Centrifugal Pumps for
Design and Application.

Pump FAQs® November 2006 Article #3

Q. Mechanical seal failure represents most of the causes for pump repair in our
plant, with unscheduled shutdown and loss of production. What can be done to
relieve this problem?
A. Improved seal life can result from a review of failures with your seal supplier
and making some changes to improve the seal designs and operation. Reducing
unscheduled shutdown can be done by appropriate leakage detection to identify
imminent failures before they occur. Leakage from installed pumps is detected
in a number of ways depending on the hazard posed by the liquid being pumped
and the surrounding environment. Leakage detection is monitored to identify the
failure mode of the seal or pressure boundary. These leaks may be in the form of
liquid or vapor. Following are several means of monitoring leakage.

For less-hazardous liquids, leakage is often detected visually from joints or seal
drains. Larger leaks of volatile light hydrocarbons such as propane may form ice
deposits on the outside surface of the seal gland plate. Continued operation will
cause the ice to melt and be replaced by carbon wear debris from the seal faces.
Visual monitoring is commonly used for single and dual outboard double and
tandem seals.

Sniffers are used to detect minute leakage of volatile organic compounds


(VOCs). Typical locations monitored are joints, connections and seal drains.
Concentrations can be measured to determine the severity of the leak. The
proper sniffer must be used for the compound pumped. All single seal
installations handling VOCs must use this method of monitoring.

Leakage through the inboard seal of a dual tandem seal arrangement may be
detected by a change in pressure in the seal reservoir containing the buffer fluid.
This is accomplished by blocking off the reservoir from the flare (vent) for at
least 10 minutes and noting the increase in pressure. Pressure buildup in
secondary containment areas of sealless pumps may also be used to indicate
leakage past the primary containment.

Leakage through the inboard seal of a dual tandem seal arrangement may be

56
Pump FAQ’s by Hydraulic Institute (UK) 57

detected by monitoring the gas flow from the seal to the flare system. Leakage
through the inboard seal of a dual double seal arrangement may be detected by
measuring the loss of barrier liquid from the circulation system and reservoir.
The consumption of barrier gas through a dual double gas-lubricated seal will
vary with changes to pressure, temperature and speed.

For more detail on this subject, see HI Standard ANSI/HI 9.6.5 Centrifugal
and Vertical Pumps for Condition Monitoring

Pump FAQs® November 2004 Article #2

Q. In our power plants we have several applications where we need to reduce the
NPSH Required by the pumps by as much as fifty percent. Is this possible? If
so, how can this be done?
A. The NPSH required by a pump is a function of the pump operating speed and
rate of flow required. When these criteria are set in a given design, little can
be done to reduce NPSH Required. The only thing that can make a significant
is the addition of an inducer. Inducers are devices designed to benefit the
functioning of the impeller by increasing the liquid pressure before it enters
the impeller. See figure 1.59, which is from ANSI/HI 1.3-2000 Centrifugal
Pumps for Design and Application. Even this device does not change the
basic function or NPSH Required by the impeller, it simple increases the
available inlet pressure.

When properly designed and matched to the impeller, the NPSH Required by
the pump with the inducer can be reduced by as much as 50%. However, most
manufacturers do not make them available.

Regarding further reading on this subject, there is so much available that it is


difficult to identity a starting point. A literature search service or an internet
search should be able to help.

57
Pump FAQ’s by Hydraulic Institute (UK) 58

Pump FAQs® March 2000 Article #3

Q. We have a new water system pump which operates with the excessive noise with
smaller existing pumps. The pump produces 7300 gpm and is driven by a 900-
hp motor. The system provides 23.5 feet of NPSH and only 18 feet is required
by the pump. The noise sounds like the pump is handling sand. What is the
cause of the noise, and can it be eliminated? After nine months of operation,
examination shows no impeller damage.
A. A pump is a hydraulic machine, and all mechanical devices are inherently noisy
to some extent. Recent studies by Hydraulic Institute members show a strong

58
Pump FAQ’s by Hydraulic Institute (UK) 59

correlation between noise and pump power. Higher horsepower pumps are
naturally more noisy. If there was no apparent impeller damage after nine
months of operation, the pump can be expected to operate indefinitely.

Pump FAQs® June 2006 Article #1

Q. We recently rebuilt a vertical turbine pump with new impellers and wearing
rings and tested its performance. The pump is handling water at ambient
temperature (S=1.0). However, the result showed total head performance which
was lower than the published curve as the rate of flow was increased. The pump
is thirty feet long so we put a test gage two pipe diameters downstream of the
discharge elbow. The shut off head nearly matches the published curve. Do you
have any suggestion for increasing the pump head?
A. The performance curve for vertical turbine pumps is usually for the bowl
assembly only and does not include the head losses in the pump column pipe
and discharge head. In order to measure the bowl performance, the discharge
pressure gage must be connected to the pump column pipe two diameters
above the outlet from the bowl assembly. However, the gage can be located
above ground and connected to the lower column pipe with a small diameter
(1/4 inch ) tube. See figure.

Note that the height of the gauge above the first stage impeller must be
measured as well as the inside diameter of the column pipe. The total head
with water can then be calculated as follows:

Hba = 2.31pgba + Zd – Zw + vd 2/2g where:

Hba = bowl assembly head – feet of water

pgba = discharge gage pressure-psi

Zd = height of discharge pressure gage above first stage impeller datum –
feet

Zw = height of water level above first stage impeller datum– feet

vd = liquid velocity in column pipe – feet/second

An alterative to this approach is to calculate the losses in the column pie and
discharge elbow using published data on flow friction losses, such as
the Hydraulic Institute Engineering Data Book or computer software programs
and adding such values to the measured pump head.

59
Pump FAQ’s by Hydraulic Institute (UK) 60

Pump FAQs® June 2005 Article #3

Q. The FAQ in the February 2004 issue of P&S showed the performance curve of a
centrifugal pump when handling entrained air. Do self priming pumps perform
the same way when pumping liquid with entrained air, or can they do better?
A. During the priming cycle, self-priming pumps are handling 100% air which is at
much higher percent than a centrifugal pump could handle, but not at the same
head as when pumping water. When priming, self-priming pumps must be
vented to the atmosphere to allow the air to be expelled . This is usually
accomplished with the discharge pipe empty or with an air release valve on the
pump.

During the pumping cycle, the self priming pump will suffer a similar reduction
in total head as a regular pump but it should be able to handle a greater
percentage of air before pumping stops.

Pump FAQs® April 2002 Article #1

Q. Most industrial pump manufacturers publish centrifugal pump performance curves


that include a curve for NPSHR. I understand that this curve is based on tests, which
determine the NPSH value when the total head is reduced by 3%. Isn’t it better
to publish NPSHR curves with higher values based on 0% reduction in total head or
zero cavitation?

60
Pump FAQ’s by Hydraulic Institute (UK) 61

A. As NPSH available to a centrifugal pump increases, the severity of the cavitation


forces actually increases until NPSHA is about 2 times NPSHR. In order to reach a
level of zero cavitation, values as great as 10 to 20 times the NPSHR are required. In
many applications such high values are impractical to design for. The severity of
cavitation damage to a pump also depends on the properties of the liquid pumped and

61

Potrebbero piacerti anche