Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Circuit Protection
Fuses
The fuse is a reliable overcurrent protective device. A fusible link
or links encapsulated in a tube and connected to contact terminals
comprise the fundamental elements of the basic fuse. Electrical
resistance of the link is so low that it simply acts as a conductor.
However, when destructive currents occur, the link very quickly
melts and opens the circuit to protect conductors and other circuit
components and loads. Modern fuses have stable characteristics.
Fuses do not require periodic maintenance or testing. Fuses have
three unique performance characteristics:
1. Modern fuses have an extremely high interrupting
ratingcan open very high fault currents without rupturing.
2. Properly applied, fuses prevent blackouts. Only the fuse
nearest a fault opens without upstream fuses (feeders or
mains) being affectedfuses thus provide selective coordination. (These terms are precisely defined in subsequent
pages.)
3. Fuses provide optimum component protection by keeping
fault currents to a low value. . .They are said to be currentlimiting.
Overcurrents
An overcurrent is either an overload current or a short-circuit current. The overload current is an excessive current relative to normal operating current, but one which is confined to the normal
conductive paths provided by the conductors and other components and loads of the distribution system. As the name implies, a
short-circuit current is one which flows outside the normal conducting paths.
Overloads
Overloads are most often between one and six times the normal
current level. Usually, they are caused by harmless temporary
surge currents that occur when motors start up or transformers are
energized. Such overload currents, or transients, are normal
occurrences. Since they are of brief duration, any temperature rise
is trivial and has no harmful effect on the circuit components. (It is
important that protective devices do not react to them.)
Continuous overloads can result from defective motors (such
as worn motor bearings), overloaded equipment, or too many
loads on one circuit. Such sustained overloads are destructive and
must be cut off by protective devices before they damage the distribution system or system loads. However, since they are of relatively low magnitude compared to short-circuit currents, removal of
the overload current within a few seconds to many minutes will
generally prevent equipment damage. A sustained overload current results in overheating of conductors and other components
and will cause deterioration of insulation, which may eventually
result in severe damage and short-circuits if not interrupted.
Short-Circuits
Whereas overload currents occur at rather modest levels, the
short-circuit or fault current can be many hundred times larger
than the normal operating current. A high level fault may be 50,000
amperes (or larger). If not cut off within a matter of a few thousandths of a second, damage and destruction can become rampantthere can be severe insulation damage, melting of conductors, vaporization of metal, ionization of gases, arcing, and fires.
1
Fuseology
Circuit breaker
480Y/277 slash voltage rating
480 volts
Line-to-line
480Y/277 Volt
three phase,
four wire,
solidly
grounded,
wye system
A
B
C
N
Ground
277 volts
Line-to-ground
Fuses are a universal protective device. They are used in power distribution systems, electronic apparatus, vehicles. . .and as illustrated, our
space program. The Space Shuttle has over 600 fuses installed in it protecting vital equipment and circuits.
Voltage Rating-Fuses
Most low voltage power distribution fuses have 250V or 600V ratings (other ratings are 125, 300, and 480 volts). The voltage rating
of a fuse must be at least equal to or greater than the circuit voltage. It can be higher but never lower. For instance, a 600V fuse
can be used in a 208V circuit. The voltage rating of a fuse is a
function of its capability to open a circuit under an overcurrent
condition. Specifically, the voltage rating determines the ability of
the fuse to suppress the internal arcing that occurs after a fuse link
melts and an arc is produced. If a fuse is used with a voltage rating lower than the circuit voltage, arc suppression will be impaired
and, under some overcurrent conditions, the fuse may not clear
the overcurrent safely. 300V rated fuses can be used to protect
single-phase line-to-neutral loads when supplied from three-phase,
solidly grounded, 480/277V circuits, where the single-phase lineto-neutral voltage is 277V. This is permissible because in this
application, a 300V fuse will not have to interrupt a voltage greater
than its 300V rating. Special consideration is necessary for semiconductor fuse applications, where a fuse of a certain voltage rating is used on a lower voltage circuit.
Slash voltage rated overcurrent protective devices are not intended to open phase-to-phase voltages across only one pole. Where
it is possible for full phase-to-phase voltage to appear across only
one pole, a full or straight rated overcurrent protective device must
be utilized. For example, a 480V circuit breaker may have to open
an overcurrent at 480V with only one pole, such as might occur
when Phase A goes to ground on a 480V, B-phase, corner grounded delta system.
Fuseology
Equipment that utilizes straight voltage rated overcurrent protective
devices provides more value and utilization to the owner or potential future owners than equipment that utilizes slash voltage rated
devices. In todays business environment, machinery and equipment may be moved several times during its useful life. Equipment
utilizing slash voltage rated overcurrent devices is not suitable for
many electrical systems found in industrial environments.
Ampere Rating
Every fuse has a specific ampere rating. In selecting the ampere
rating of a fuse, consideration must be given to the type of load
and code requirements. The ampere rating of a fuse normally
should not exceed the current carrying capacity of the circuit. For
instance, if a conductor is rated to carry 20 amperes, a 20 ampere
fuse is the largest that should be used. However, there are some
specific circumstances in which the ampere rating is permitted to
be greater than the current carrying capacity of the circuit. A typical example is motor circuits; dual-element fuses generally are
permitted to be sized up to 175% and non-time-delay fuses up to
300% of the motor full-load amperes. As a rule, the ampere rating
of a fuse and switch combination should be selected at 125% of
the continuous load current (this usually corresponds to the circuit
capacity, which is also selected at 125% of the load current).
There are exceptions, such as when the fuse-switch combination is
approved for continuous operation at 100% of its rating.
Interrupting Rating
A protective device must be able to withstand the destructive energy of short-circuit currents. If a fault current exceeds a level
beyond the capability of the protective device, the device may
actually rupture, causing additional damage. Thus, it is important
when applying a fuse or circuit breaker to use one which can sustain the largest potential short-circuit currents. The rating which
defines the capacity of a protective device to maintain its integrity
when reacting to fault currents is termed its interrupting rating.
The interrupting rating of most branch-circuit, molded case, circuit
breakers typically used in residential service entrance panels is
10,000 amperes. (Please note that a molded case circuit breakers
interrupting capacity will typically be lower than its interrupting rating.) Larger, more expensive circuit breakers may have interrupting ratings of 14,000 amperes or higher. In contrast, most modern,
current-limiting fuses have an interrupting rating of 200,000 or
300,000 amperes and are commonly used to protect the lower
rated circuit breakers. The National Electrical Code 110.9,
requires equipment intended to break current at fault levels to
have an interrupting rating sufficient for the current that must be
interrupted. The subjects of interrupting rating and interrupting
capacity are treated later in more detail.
Insulated
Caps
Non
Insulated
Caps
Always Test at
the Blade
Fuseology
The table below depicts four different situations involving an
overcurrent device with a normal current rating of 100 amperes
and an interrupting rating of only 10,000 amperes.
Circuit with Overcurrent
Protective Device
Current Rating= 100A and
Interrupting Rating= 10,000A
Circuit
Conditions
Application
And Action
of Protective
Device
Normal
Proper
Overload
Current
Greater Than
Devices
Ampere
Rating
Proper-Safe
Interruption
of Current
100
Amperes AMMETER
LOAD
200
10,000
50,000
As depicted in the diagram that follows, when using overcurrent protective devices with limited interrupting rating, it becomes
necessary to determine the available short-circuit currents at each
location of a protective device. The fault currents in an electrical
system can be easily calculated if sufficient information about the
electrical system is known. (See the Point-to-Point Method for
short-circuit calculations.) With modern fuses, these calculations
normally are not necessary since the 200,000 or 300,000 ampere
interrupting rating is sufficient for most applications.
Also, if using circuit breakers or self-protected starters, it may
be necessary to evaluate the devices individual pole interrupting
capability for the level of fault current that a single pole of a multipole device may have to interrupt. This is covered in-depth in the
Single-Pole Interrupting Capability section.
Short-Circuit Proper-Safe
Current
Interruption
Within Device of Current
Interrupting
Rating
Short-Circuit
Current
Exceeds
Device
Interrupting
Rating
Improper:
Explosion or
Rupture
Could Result
75,000 Amperes
75,000 Amperes
25,000 Amperes
30,000 Amperes
15,000
Amperes
Fuseology
General Fuse Application Data For Compliance With NEC 110.9
New
Installations
System
UpGrading
Guideline
Features
Benefits
Commonly Used
Fuse Types
Usually a short-circuit
current calculation study is
unnecessary.
LOW-PEAK YELLOW
Dual-Element
T-TRON Fast-Acting
LIMITRON Fast-Acting
CUBEFuse
CUBEFuse, T-TRON
Fast-Acting, LOW-PEAK
YELLOW Dual-Element,
LIMITRON Fast-Acting,
LOW-PEAK YELLOW
Time-Delay
Interrupting Rating
It is the maximum short-circuit current that an overcurrent protective device can safely interrupt under standard test conditions.
The phrase under standard test conditions means it is important
to know how the overcurrent protective device is tested in order to
assure it is properly applied. This can be very important when it
comes to the application of circuit breakers, mainly ratings of 100
amperes and less.
Interrupting Capacity
The highest current at rated voltage that the device can interrupt.
This definition is from the IEEE Standard Dictionary of Electrical
and Electronic Terms.
Ip = 48,026A
IRMS = 22,000A
Amps
P.F. = 20%
IRMS = 22,000 Amp
Time
Fuseology
The diagram below illustrates the test circuit as allowed by UL 489.
Standard interrupting rating tests for a 22,000 ampere sym. RMS
S.C.P.F. = 20%
S.C. Avail. = 22,000A
RLINE
20A
XLINE
RCB
XCB
RLOAD
XLOAD
RS
RMS
Symmetrical
Amps
Calibrated Interrupting
Rating Circuit
22,000
48,026
20%
9,900
14,001
88%
XS
SOURCE:
Maximum
Instantaneous Power Factor
Peak
Ip = 14,001A
P.F. = 88%
IRMS = 9,900 Amp
Amps
Test station
source leads
Shorting bar
IRMS = 9,900A
Time
This circuit can now only achieve a peak current of 14,001 amps.
Test station
source leads
Shorting bar
removed, circuit
breaker &
conductors added
Each
4 feet 12 AWG
Ip = 48,026A
IRMS = 22,000A
Ip = 14,001A
P.F. = 20%
IRMS = 22,000A
P.F. = 88%
IRMS = 9,900 Amp
Each
10 inches 12 AWG
Amps
20 A
IRMS = 9,900A
Time
Fuseology
Equally important, the short-circuit power factor is greatly affected
due to the high R values of the small, rated wire. This results in a
lower peak value that the circuit breaker must tolerate during the
first one-half cycle.
Ip
IRMS
Ip
Ip
IRMS
15A
20A
25A
30A
40A
50A
60A
7,200
8,900
10,700
10,700
11,700
11,700
12,500
5,100
6,300
7,500
7,500
8,300
8,300
8,800
8,700
11,400
14,200
14,200
16,000
16,000
17,300
6,100
8,100
10,100
10,100
11,300
11,300
12,200
9,300
12,600
16,500
16,500
19,200
19,200
21,300
6,600
8,900
11,700
11,700
13,600
13,600
15,100
70A
80A
90A
100A
13,000
13,000
13,200
13,200
9,200
9,200
9,300
9,300
18,100
18,100
18,300
18,300
12,800
12,800
12,900
12,900
22,600
22,600
23,000
23,000
16,000
16,000
16,300
16,300
One point to be made is that acceptable bus shot test results per
the product standard do not meet the NEC definition for a circuit
breaker. For example, 7.1.11.6.3.1 of UL 489 states The inability to
relatch, reclose, or otherwise reestablish continuity ... shall be considered acceptable for circuit breakers which are tested under bus
bar conditions. In practical terms, this means the circuit breaker
doesnt have to work after a fault near the circuit breaker occurs.
This is in violation of the 2002 NEC definition for a circuit breaker:
A device designed to open and close a circuit by nonautomatic
means and to open the circuit automatically on a predetermined
overcurrent without damage to itself when properly applied within
its rating. In addition, under bus bar condition tests the circuit
breaker is required to only interrupt one short-circuit current. For
this one short-circuit test shot, the circuit breaker is in its closed
position and the short-circuit current is initiated by the test station
switch closing randomly. The bus bar conditions test procedures
do not evaluate the circuit breaker for closing-on the short-circuit.
Closing-on a short-circuit is an important criteria for safety.
A Fine Print Note was added to 240.85 of the 2002 NEC to alert
users that circuit breakers have single-pole interrupting capabilities that must be considered for proper application. It states:
Single-Pole Interrupting Capabilities For Overcurrent Devices
Current-limiting fuses: the marked interrupting rating is the tested
single-pole interrupting rating. So single-pole interrupting capability is not an issue with fuse applications.
Airframe/power circuit breaker: per ANSI C37.13 and C37.16 the single-pole interrupting rating is 87% of its three-pole interrupting rating.
The single-pole interrupting capability of a circuit breaker, self protected starter and other similar mechanical overcurrent protective
7
Fuseology
page 54 of the IEEE Blue Book, Recommended Practice for
Applying Low-Voltage Circuit Breakers Used in Industrial and
Commercial Power Systems, (Std 1015-1997).
Self protected starters: UL 508, Table 82A.3 specifies the short circuit
test values on one pole as 4320 amps for 0 to 10 hp devices rated 200
to 250 volts and 8660 amperes for 0 to 200 hp devices rated 600 volts
maximum.
Molded case circuit breakers and self protected starters may not be
able to safely interrupt single-pole faults above these respective values
shown in previous paragraphs. Per 110.9, all overcurrent protective
devices that are intended to interrupt fault currents must have singlepole interrupting capabilities for the maximum single-pole fault current
that is available. And typically, engineers, contractors and inspectors
(AHJs) rely on the applicable product standard testing and listing criteria to verify device ratings as being suitable for specific applications.
240V
480/277V
480V
100A Maximum
250V Maximum
4,330
--
--
Actual Example
The diagram below illustrates the UL 489 test procedure for a 100A,
480V, three phase circuit breaker that gets listed for a high interrupting rating. Test A and B are the required standard or base interrupting tests. Test A is a three-pole interrupting test at 10,000 A (Table
1, right column), which is a modest three-phase available short-circuit current, and Test B is a single-pole interrupting test at a modest
single-phase available short-circuit current of 8660A (Table 1).
Then, in addition, to be listed and marked with the higher 65,000A
interrupting rating, the circuit breaker must pass the criteria for Test
C. Test C is a three-pole interrupting test at 65,000A three-phase
available short-circuit current. Test D is not conducted; it is not part
of the UL 489 evaluation procedure. This higher three-phase interrupting rated circuit breaker does not have to undergo any test criteria at a corresponding higher single-pole short-circuit current.
600/347V 600V
--
--
5,000
100A Maximum
251-600V
--
10,000
8,660
10,000
8,660
10,000
101 800
8,660
10,000
8,660
10,000
8,660
14,000
801 1200
12,120
14,000
12,120
14,000
12,120
20,000
1201 2000
14,000
14,000
14,000
14,000
14,000
25,000
2001 2500
20,000
20,000
20,000
20,000
20,000
30,000
2501 3000
25,000
25,000
25,000
25,000
25,000
35,000
3001 4000
30,000
30,000
30,000
30,000
30,000
45,000
4001 5000
40,000
40,000
40,000
40,000
40,000
60,000
5001 6000
50,000
50,000
50,000
50,000
50,000
70,000
Test B
3-Phase Test
10,000A
1-Pole Test
8,660A
From Table 1
From Table 1
Test C
Test D
3-Phase Test
65,000A
1-Pole Test
NONE
Fuseology
Possible Fault Currents During A Ground Fault Condition
The magnitude of a ground fault current is dependent upon the
location of the fault with respect to the transformer secondary.
Referring to Figure 2, the ground fault current flows through one
coil of the wye transformer secondary and through the phase conductor to the point of the fault. The return path is through the enclosure and conduit to the bonding jumper and back to the secondary through the grounded neutral. Unlike three-phase faults,
the impedance of the return path must be used in determining the
magnitude of ground fault current. This ground return impedance
is usually difficult to calculate. If the ground return path is relatively
short (i.e. close to the center tap of the transformer), the ground
fault current will approach the three phase short-circuit current.
Shown below are three still photos from a videotaping of a singlepole fault interruption test on a three-pole circuit breaker rated
480V. This circuit breaker is marked with a three-pole interrupting
rating of 35,000 amperes at 480V. This marked interrupting rating is
per UL 489 test procedures. This circuit breaker is tested for individual single-pole interrupting capabilities in UL 489 at an available
fault current of 8,660 amps (Table 1 prior page). The test that is
shown below is with an available fault current of 25,000 amperes.
BRANCH
PANEL
Steel Conduit
277V
7V
C 27
480V
27
7V
B
B
480V
C
Fuseology
If either Phase A or C is shorted to ground, only one pole of the
branch-circuit overcurrent device will see the 480V fault as shown
in Figure 4. This system requires compliance with single-pole interrupting capabilities for 480V faults on one pole because the
branch-circuit circuit breaker would be required to interrupt
480V with only one pole.
BRANCH
PANEL
Steel Conduit
480V
B
C
Fault to
conduit
480V
BRANCH
PANEL
PANEL
Steel Conduit
A
B
C
48
0V
48
B
C
480V
Fault to
conduit
B
C
SERVICE
PANEL
480V
B
C
10
Fuseology
The magnitude of this fault current can approach 87% of the L-L-L
short-circuit current. Because of the possibility that a second fault
will occur, single-pole interrupting capability must be investigated.
The IEEE Red Book, Std 141-1993, page 367, supports this
requirement, One final consideration for impedance-grounded
systems is the necessity to apply overcurrent devices based upon
their single-pole short-circuit interrupting rating, which can be
equal to or in some cases less than their normal rating.
Resistor
BRANCH
PANEL
Steel Conduit
A
277V
7
C 27
480V
27
7V
B
B
480V
C
Ungrounded Systems
The Ungrounded System of Figure 8 offers the same advantage for
continuity of service that is characteristic of high impedance
grounded systems.
Figure 5 - Impedance Grounded System
Ungrounded System
SERVICE
PANEL
BRANCH
PANEL
Steel
Conduit
480V
B
C
480V
C
BRANCH
PANEL
277V
Steel Conduit
A
27
7V
C 27
7V
480V
C
First fault
to steel
conduit
Ungrounded System
SERVICE
PANEL
480V
B
C
277V
C 27
27
480V
7V
BRANCH
PANEL
Steel Conduit
480V
C
First fault
to steel
conduit
7V
480V
Steel
Conduit
BRANCH
PANEL
First fault
to steel
conduit
The second fault from Phase B to ground (in Figure 10) will create a 480
volt fault across only one pole at the branch circuit overcurrent device.
Again, the values from Table 1 for single pole interrupting capabilities
must be used for molded case circuit breaker systems as the tradeoff
for the increased continuity of service. The IEEE Red Book, Std 1411993, page 366, supports this requirement, One final consideration for
ungrounded systems is the necessity to apply overcurrent devices
based upon their single-pole short circuit interrupting rating, which
can be equal to or in some cases less than their normal rating.
Second Fault
To Enclosure
Fuseology
Ungrounded System
Single pole must
interrupt
fault current
SERVICE
BRANCH
PANEL
PANEL
Steel
Conduit
A
B
First fault
to steel
conduit
480V
C
Second Fault
To Enclosure
Steel Conduit
27
27
7V
480V
First Fault
to Steel
Conduit
Second Fault
to Enclosure
Figure 13- Upon the second fault, the fault is essentially a line-line
fault with the impedance of the conductors and the
ground path. The fuse must interrupt this fault. Since a
fuses interrupting rating is the same as its single-pole
interrupting capability, modern fuses with 200,000A or
300,000A interrupting rating can be applied without further analysis for single pole interrupting capabilities.
BRANCH
PANEL
480V
B
B
480V
7V
A
7V
27
Steel Conduit
A
27
7V
First Fault
to Steel
Conduit
480V
Figure 12 - Upon first fault, the fault current is low due to resistor.
As intended the fuse does not open.
In the 2002 NEC 250.4(B) Ungrounded Systems (4) Path for Fault
Current, it is required that the impedance path through the equipment be low so that the fault current is high when a second fault
occurs on an ungrounded system.
SERVICE
PANEL
B
B
Resistor
7V
27
Steel Conduit
480V
27
7V
BRANCH
PANEL
A
480V
C
SERVICE
PANEL
480V
C
12