Sei sulla pagina 1di 12

Fuseology

Circuit Protection

Simultaneously, high level short-circuit currents can develop huge


magnetic-field stresses. The magnetic forces between bus bars
and other conductors can be many hundreds of pounds per linear
foot; even heavy bracing may not be adequate to keep them from
being warped or distorted beyond repair.

Electrical distribution systems are often quite complicated. They


cannot be absolutely fail-safe. Circuits are subject to destructive
overcurrents. Harsh environments, general deterioration, accidental damage or damage from natural causes, excessive expansion
or overloading of the electrical distribution system are factors
which contribute to the occurrence of such overcurrents. Reliable
protective devices prevent or minimize costly damage to transformers, conductors, motors, and the other many components and
loads that make up the complete distribution system. Reliable circuit protection is essential to avoid the severe monetary losses
which can result from power blackouts and prolonged downtime of
facilities. It is the need for reliable protection, safety, and freedom
from fire hazards that has made the fuse a widely used protective
device.

Fuses
The fuse is a reliable overcurrent protective device. A fusible link
or links encapsulated in a tube and connected to contact terminals
comprise the fundamental elements of the basic fuse. Electrical
resistance of the link is so low that it simply acts as a conductor.
However, when destructive currents occur, the link very quickly
melts and opens the circuit to protect conductors and other circuit
components and loads. Modern fuses have stable characteristics.
Fuses do not require periodic maintenance or testing. Fuses have
three unique performance characteristics:
1. Modern fuses have an extremely high interrupting
ratingcan open very high fault currents without rupturing.
2. Properly applied, fuses prevent blackouts. Only the fuse
nearest a fault opens without upstream fuses (feeders or
mains) being affectedfuses thus provide selective coordination. (These terms are precisely defined in subsequent
pages.)
3. Fuses provide optimum component protection by keeping
fault currents to a low value. . .They are said to be currentlimiting.

Fuses are constructed in an almost endless variety of configurations.


These photos depict the internal construction of Bussmann DualElement, SEMI-TRON and LOW-PEAK Class L fuses.

Overcurrents
An overcurrent is either an overload current or a short-circuit current. The overload current is an excessive current relative to normal operating current, but one which is confined to the normal
conductive paths provided by the conductors and other components and loads of the distribution system. As the name implies, a
short-circuit current is one which flows outside the normal conducting paths.
Overloads
Overloads are most often between one and six times the normal
current level. Usually, they are caused by harmless temporary
surge currents that occur when motors start up or transformers are
energized. Such overload currents, or transients, are normal
occurrences. Since they are of brief duration, any temperature rise
is trivial and has no harmful effect on the circuit components. (It is
important that protective devices do not react to them.)
Continuous overloads can result from defective motors (such
as worn motor bearings), overloaded equipment, or too many
loads on one circuit. Such sustained overloads are destructive and
must be cut off by protective devices before they damage the distribution system or system loads. However, since they are of relatively low magnitude compared to short-circuit currents, removal of
the overload current within a few seconds to many minutes will
generally prevent equipment damage. A sustained overload current results in overheating of conductors and other components
and will cause deterioration of insulation, which may eventually
result in severe damage and short-circuits if not interrupted.

The Louisiana Superdome in New Orleans is the worlds largest fully


enclosed stadium. The overall electrical load exceeds 30,000,000 VA.
Distribution circuits are protected with BUSS LOW-PEAK fuses.

Voltage Rating - General


This is an extremely important rating for overcurrent protective
devices (OCPDs). The proper application of an overcurrent protective device according to its voltage rating requires that the voltage rating of the device be equal to or greater than the system
voltage. When an overcurrent protective device is applied beyond
its voltage rating, there may not be any initial indicators. Adverse
consequences typically result when an improperly voltage rated
device attempts to interrupt an overcurrent, at which point it may
self-destruct in an unsafe manner. There are two types of OCPD
voltage ratings: straight voltage rated and slash voltage rated.
The proper application is straightforward for overcurrent protective
devices with a straight voltage rating (i.e. 600V, 480V, 240V, etc.)
which have been evaluated for proper performance with full
phase-to-phase voltage used during the testing, listing and marking. For instance, all fuses are straight voltage rated and there is
no need to be concerned about slash ratings. However, some
mechanical overcurrent protective devices are slash voltage rated
(i.e. 480/277, 240/120, 600/347, etc.). Slash voltage rated devices
are limited in their applications and extra evaluation is required
when they are being considered for use. The next section covers
fuse voltage ratings followed by a section on slash voltage ratings
for other type devices.

Short-Circuits
Whereas overload currents occur at rather modest levels, the
short-circuit or fault current can be many hundred times larger
than the normal operating current. A high level fault may be 50,000
amperes (or larger). If not cut off within a matter of a few thousandths of a second, damage and destruction can become rampantthere can be severe insulation damage, melting of conductors, vaporization of metal, ionization of gases, arcing, and fires.
1

Fuseology
Circuit breaker
480Y/277 slash voltage rating

480 volts
Line-to-line

480Y/277 Volt
three phase,
four wire,
solidly
grounded,
wye system

A
B
C
N
Ground
277 volts
Line-to-ground

Fuses are a universal protective device. They are used in power distribution systems, electronic apparatus, vehicles. . .and as illustrated, our
space program. The Space Shuttle has over 600 fuses installed in it protecting vital equipment and circuits.

Slash voltage rated OCPDs must be utilized only on solidly grounded


systems. This automatically eliminates their usage on impedancegrounded and ungrounded systems. They can be properly utilized
on solidly grounded, wye systems, where the voltage to ground does
not exceed the devices lower voltage rating and the voltage
between any two conductors does not exceed the devices higher
voltage rating. Slash voltage rated devices cannot be used on corner-grounded delta systems whenever the voltage to ground
exceeds the lower of the two ratings. Where slash voltage rated
devices will not meet these requirements, straight voltage rated overcurrent protective devices are required.

Voltage Rating-Fuses
Most low voltage power distribution fuses have 250V or 600V ratings (other ratings are 125, 300, and 480 volts). The voltage rating
of a fuse must be at least equal to or greater than the circuit voltage. It can be higher but never lower. For instance, a 600V fuse
can be used in a 208V circuit. The voltage rating of a fuse is a
function of its capability to open a circuit under an overcurrent
condition. Specifically, the voltage rating determines the ability of
the fuse to suppress the internal arcing that occurs after a fuse link
melts and an arc is produced. If a fuse is used with a voltage rating lower than the circuit voltage, arc suppression will be impaired
and, under some overcurrent conditions, the fuse may not clear
the overcurrent safely. 300V rated fuses can be used to protect
single-phase line-to-neutral loads when supplied from three-phase,
solidly grounded, 480/277V circuits, where the single-phase lineto-neutral voltage is 277V. This is permissible because in this
application, a 300V fuse will not have to interrupt a voltage greater
than its 300V rating. Special consideration is necessary for semiconductor fuse applications, where a fuse of a certain voltage rating is used on a lower voltage circuit.

Overcurrent protective devices that may be slashed rated include,


but are not limited to:
Molded case circuit breakers UL489
Manual motor controllers UL508
Self protected Type E combination starters UL508
Supplementary protectors UL1077 (Looks like a small circuit
breaker and sometimes referred
to as mini-breaker. However,
these devices are not a circuit
breaker, they are not rated for
branch circuit protection and can
not be a substitute where branch
circuit protection is required.)
What about fuses, do they have slash voltage ratings? No, fuses
do not have this limitation. Fuses by their design are full voltage
rated devices; therefore slash voltage rating concerns are not an
issue when using fuses. For instance, Bussmann LOW-PEAK
LPJ (Class J) fuses are rated at 600V. These fuses could be utilized on systems of 600V or less, whether the system is solidly
grounded, ungrounded, impedance grounded, or corner grounded delta.

Slash Voltage Ratings


Some multiple-pole, mechanical overcurrent protective devices,
such as circuit breakers, self-protected starters, and manual motor
controllers, have a slash voltage rating rather than a straight voltage rating. A slash voltage rated overcurrent protective device is
one with two voltage ratings separated by a slash and is marked
such as 480Y/277V or 480/277V. Contrast this to a straight voltage
rated overcurrent protective device that does not have a slash voltage rating limitation, such as 480V. With a slash rated device, the
lower of the two ratings is for overcurrents at line-to-ground voltages, intended to be cleared by one pole of the device. The higher of the two ratings is for overcurrents at line-to-line voltages,
intended to be cleared by two or three poles of the circuit breaker
or other mechanical overcurrent device.

If a device has a slash voltage rating limitation, product standards


require these devices, such as circuit breakers, manual motor controllers, self protected starters, or supplementary protectors to be
marked with the rating such as 480Y/277V. If a machine or equipment electrical panel utilizes a slash voltage rated device inside, it
is recommended that the equipment nameplate or label designate
this slash voltage rating as the equipment voltage rating. UL508A
Industrial Control Panels requires the electrical panel voltage
marking to be slash rated if one or more devices in the panel are
slash voltage rated. Slash voltage devices are limited in application to solidly grounded, wye systems due to the nature of the way
that these devices are tested, listed and labeled. Any piece of
equipment that utilizes a slash voltage rated overcurrent protective
device is therefore, limited to installation only in a solidly grounded,
wye system and should require marking that notes this limitation.

Slash voltage rated overcurrent protective devices are not intended to open phase-to-phase voltages across only one pole. Where
it is possible for full phase-to-phase voltage to appear across only
one pole, a full or straight rated overcurrent protective device must
be utilized. For example, a 480V circuit breaker may have to open
an overcurrent at 480V with only one pole, such as might occur
when Phase A goes to ground on a 480V, B-phase, corner grounded delta system.

Fuseology
Equipment that utilizes straight voltage rated overcurrent protective
devices provides more value and utilization to the owner or potential future owners than equipment that utilizes slash voltage rated
devices. In todays business environment, machinery and equipment may be moved several times during its useful life. Equipment
utilizing slash voltage rated overcurrent devices is not suitable for
many electrical systems found in industrial environments.

In a continuing effort to promote safer work environments,


Bussmann has introduced newly designed versions of knifeblade FUSETRON Fuses (Class RK5) and knife-blade LOW
PEAK Fuses (Class RK1) for some of the ampere ratings. The
improvement is that the end caps are insulated to reduce the possibility of accidental contact with a live part. With these improved
fuses, the informed electrician knows that the end caps are isolated. With older style non-insulated end caps, the electrician doesnt
really know if the fuse is hot or not. A portion of all testing-related
injuries could be avoided by proper testing procedures.
Bussmann hopes to reduce such injuries by informing electricians of proper procedures.

Ampere Rating
Every fuse has a specific ampere rating. In selecting the ampere
rating of a fuse, consideration must be given to the type of load
and code requirements. The ampere rating of a fuse normally
should not exceed the current carrying capacity of the circuit. For
instance, if a conductor is rated to carry 20 amperes, a 20 ampere
fuse is the largest that should be used. However, there are some
specific circumstances in which the ampere rating is permitted to
be greater than the current carrying capacity of the circuit. A typical example is motor circuits; dual-element fuses generally are
permitted to be sized up to 175% and non-time-delay fuses up to
300% of the motor full-load amperes. As a rule, the ampere rating
of a fuse and switch combination should be selected at 125% of
the continuous load current (this usually corresponds to the circuit
capacity, which is also selected at 125% of the load current).
There are exceptions, such as when the fuse-switch combination is
approved for continuous operation at 100% of its rating.

Interrupting Rating
A protective device must be able to withstand the destructive energy of short-circuit currents. If a fault current exceeds a level
beyond the capability of the protective device, the device may
actually rupture, causing additional damage. Thus, it is important
when applying a fuse or circuit breaker to use one which can sustain the largest potential short-circuit currents. The rating which
defines the capacity of a protective device to maintain its integrity
when reacting to fault currents is termed its interrupting rating.
The interrupting rating of most branch-circuit, molded case, circuit
breakers typically used in residential service entrance panels is
10,000 amperes. (Please note that a molded case circuit breakers
interrupting capacity will typically be lower than its interrupting rating.) Larger, more expensive circuit breakers may have interrupting ratings of 14,000 amperes or higher. In contrast, most modern,
current-limiting fuses have an interrupting rating of 200,000 or
300,000 amperes and are commonly used to protect the lower
rated circuit breakers. The National Electrical Code 110.9,
requires equipment intended to break current at fault levels to
have an interrupting rating sufficient for the current that must be
interrupted. The subjects of interrupting rating and interrupting
capacity are treated later in more detail.

Testing Knife-Blade Fuses


A common practice when electricians are testing fuses is to touch
the end caps of the fuse with their probes. Contrary to popular
belief, fuse manufacturers do not generally design their knife-blade
fuses to have electrically energized fuse caps during normal fuse
operation. Electrical inclusion of the caps into the circuit occurs as
a result of the coincidental mechanical contact between the fuse
cap and terminal extending through it. In most brands of knifeblade fuses, this mechanical contact is not guaranteed; therefore,
electrical contact is not guaranteed. Thus, a resistance reading
taken across the fuse caps is not indicative of whether or not the
fuse is open.
A Continuity Test Across Any Knife-Blade Fuse Should
Be Taken Only Along The Fuse Blades
Do Not Test A Knife-Blade Fuse With Meter Probes To
The Fuse Caps

Insulated
Caps

Non
Insulated
Caps

This photograph vividly illustrates


the effects of overcurrents on
electrical components when
protective devices are not sized
to the ampere rating of the
component.

Always Test at
the Blade

Considerable damage to electrical


equipment can result if the interrupting rating of a protective
device is inadequate and is
exceeded by a short-circuit
current.

Fuseology
The table below depicts four different situations involving an
overcurrent device with a normal current rating of 100 amperes
and an interrupting rating of only 10,000 amperes.
Circuit with Overcurrent
Protective Device
Current Rating= 100A and
Interrupting Rating= 10,000A

Circuit
Conditions

Available fault current50,000 amps

Fuse must have short-circuit


interrupting rating of at least
50,000 amperes.

Application
And Action
of Protective
Device

Available fault current50,000 amps


80

Normal

Proper

Overload
Current
Greater Than
Devices
Ampere
Rating

Proper-Safe
Interruption
of Current

Circuit breaker must have


capability of interrupting at least
50,000 amperes.

100
Amperes AMMETER
LOAD

200

10,000

50,000

As depicted in the diagram that follows, when using overcurrent protective devices with limited interrupting rating, it becomes
necessary to determine the available short-circuit currents at each
location of a protective device. The fault currents in an electrical
system can be easily calculated if sufficient information about the
electrical system is known. (See the Point-to-Point Method for
short-circuit calculations.) With modern fuses, these calculations
normally are not necessary since the 200,000 or 300,000 ampere
interrupting rating is sufficient for most applications.
Also, if using circuit breakers or self-protected starters, it may
be necessary to evaluate the devices individual pole interrupting
capability for the level of fault current that a single pole of a multipole device may have to interrupt. This is covered in-depth in the
Single-Pole Interrupting Capability section.

Short-Circuit Proper-Safe
Current
Interruption
Within Device of Current
Interrupting
Rating

Short-Circuit
Current
Exceeds
Device
Interrupting
Rating

Improper:
Explosion or
Rupture
Could Result

In the first three instances above, the circuit current condition


is within the safe operating capabilities of the overcurrent protective device. However, the fourth case involves a misapplication of
the overcurrent device. A short-circuit on the load side of the
device has resulted in a fault current of 50,000 amperes flowing
through the overcurrent device. Because the fault current is well
above the interrupting rating of the device, a violent rupture of the
protective device and resulting damage to equipment or injury to
personnel is possible. The use of high interrupting rated fuses (typically rated at 200,000 or 300,000 amperes) would prevent this
potentially dangerous situation.
The first paragraph of NEC 110.9 requires that the overcurrent protective device be capable of interrupting the available fault
current at its line terminals.

75,000 Amperes

75,000 Amperes

25,000 Amperes

30,000 Amperes

15,000
Amperes

Available short-circuit current (indicated by X) at


each panel location must be determined to assure
short-circuit interrupting rating of overcurrent
protective devices is not exceeded.

Fuseology
General Fuse Application Data For Compliance With NEC 110.9

New
Installations

System
UpGrading

Guideline

Features

Benefits

Commonly Used
Fuse Types

1. Use modern, high interrupting


rated fuses throughout electrical
system.

300,000 ampere interrupting


rating, on LOW-PEAK YELLOW
fuses. 200,000 ampere interrupting rating on other classes of
modern current-limiting fuses.

Assures proper interrupting


rating compliance currently
and future.

All modern current-limiting


fuses (most have 200,000
ampere interrupting
rating). LOW-PEAK YELLOW,
Class R, J & L fuses have a
300,000 ampere interrupting rating.

Usually a short-circuit
current calculation study is
unnecessary.

2. Use current-limiting fuses to


protect low withstand rated
components.

Correct type and size


current-limiting fuse can
protect low withstand rated
equipment against high
short-circuit currents. (See
fuse protection of circuit
breakers).

Compliance with NEC


110.10 and 240.86.

LOW-PEAK YELLOW
Dual-Element
T-TRON Fast-Acting
LIMITRON Fast-Acting
CUBEFuse

3. Where available fault current


has increased or is questionable,
replace old style fuses such as
One-Time and Renewable with
modern high interrupting rated
fuses.

200,000 or 300,000 ampere


interrupting rating.

Assures compliance with


LOW-PEAK YELLOW
interrupting rating requirements Dual-Element
with simple direct retrofit.
FUSETRON Dual-Element
LIMITRON Fast-Acting
Easily achieved since older

4. Where existing equipment may


have questionable withstand
rating due to deterioration, or the
available fault current has
increased, install modern currentlimiting fuses.

Correct type and size


current-limiting fuses can be
put in switch, cut-in system or
sometimes fuses can be cut in
bus structure.

style fuses can physically be


replaced with modern fuses
with no system modification.
Improves the level of
short-circuit protection.
Small size of CUBEFuse
or T-TRON fuse permits easy
cut-in strategy.

CUBEFuse, T-TRON
Fast-Acting, LOW-PEAK
YELLOW Dual-Element,
LIMITRON Fast-Acting,
LOW-PEAK YELLOW
Time-Delay

Interrupting Rating vs. Interrupting Capacity


impedance), their interrupting capacity can be less than their interrupting rating. When the test circuit is calibrated for the circuit
breaker interrupting rating tests, the circuit breaker is not in the circuit. After the test circuit has been verified to the proper level of
short-circuit current, the circuit breaker is placed into the circuit.
However, in addition to the circuit breaker, significant lengths of
conductor are permitted to be added to the circuit after the calibration. This additional conductor impedance can result in a significantly lower short-circuit current. So a circuit breaker marked
with an interrupting rating of 22,000 amperes may in fact have an
interrupting capacity of only 9,900 amperes.

Interrupting Rating
It is the maximum short-circuit current that an overcurrent protective device can safely interrupt under standard test conditions.
The phrase under standard test conditions means it is important
to know how the overcurrent protective device is tested in order to
assure it is properly applied. This can be very important when it
comes to the application of circuit breakers, mainly ratings of 100
amperes and less.
Interrupting Capacity
The highest current at rated voltage that the device can interrupt.
This definition is from the IEEE Standard Dictionary of Electrical
and Electronic Terms.

To better understand this, it is necessary to review the standard


interrupting rating test procedures for circuit breakers: Molded
Case Circuit Breakers - UL 489 and CSA 5 Test Procedures. UL
489 requires a unique test set-up for testing circuit breaker interrupting ratings. The diagram below illustrates a typical calibrated
test circuit waveform for a 20 ampere, 240V, 2-pole molded case
circuit breaker, with a marked interrupting rating of 22,000
amperes, RMS symmetrical.

Standard Test Conditions - Fuses


Branch circuit fuses are tested without any additional conductor in
the test circuit. For instance, if a fuse has an interrupting rating of
300,000 amperes, the test circuit is calibrated to have at least
300,000 amperes at the rated fuse voltage. During the test circuit
calibration, a bus bar is used in place of the fuse to verify the proper short-circuit current. Then the bus bar is removed and the fuse
is inserted; the test is then conducted. If the fuse passes the test,
the fuse is marked with this interrupting rating (300,000 amperes).
In the procedures just outlined for fuses, there are no extra conductors inserted into the test circuit after the short-circuit current is
calibrated. A major point is that the fuse interrupts an available
short-circuit current at least equal to or greater than its marked
interrupting rating. In other words, because of the way fuses are
short-circuit tested (without additional conductor impedance), their
interrupting capacity is equal to or greater than their marked interrupting rating.

Ip = 48,026A

IRMS = 22,000A
Amps

P.F. = 20%
IRMS = 22,000 Amp

Time

Standard Test Conditions - Circuit Breakers


This is not the case with circuit breakers. Because of the way circuit breakers are short circuit tested (with additional conductor
5

Fuseology
The diagram below illustrates the test circuit as allowed by UL 489.
Standard interrupting rating tests for a 22,000 ampere sym. RMS
S.C.P.F. = 20%
S.C. Avail. = 22,000A
RLINE

20A
XLINE

RCB

XCB

RLOAD

XLOAD

RS

RMS
Symmetrical
Amps

Calibrated Interrupting
Rating Circuit

22,000

48,026

20%

9,900

14,001

88%

Actual Circuit With


Wire Impedance Added
After Calibration

XS

SOURCE:

20A, 240V, 2-Pole


Molded Case Circuit
Breaker With 22,000A
Interrupting Rating

4' Rated Wire (12 AWG Cu)

Maximum
Instantaneous Power Factor
Peak

10" Rated Wire (12 AWG Cu)

Note: For calculations, R CB and X CB are assumed negligible.

Conclusion (refer to table above and graphs below)


This 22,000 ampere (with short-circuit power factor of 20%) interrupting rated circuit breaker has an interrupting capacity of 9,900
amperes at a short-circuit power factor of 88%. Unless there is a
guarantee that no fault will ever occur at less than 4' 10" from the
load terminals of the circuit breaker, this circuit breaker must only
be applied where there are 9,900 amperes or less available on its
line side.

interrupting rated circuit breaker will allow for a maximum 4 ft.


rated wire on the line side for each lead, and 10 in. rated wire on
the load side for each lead of the circuit breaker. See the following
diagrams and table, that provide a short-circuit analysis of this test
circuit as seen by the circuit breaker.
Test station source impedance is adjusted to achieve a calibrated
22,000 RMS symmetrical amps at 20% or less power factor. This
circuit can achieve a peak current of 48,026 amps. For the calibration test, a bus bar (shorting bar) is inserted between the test station terminals.
After the circuit calibration is verified, the shorting bar is removed

A graphic analysis of this actual short-circuit follows.

Ip = 14,001A
P.F. = 88%
IRMS = 9,900 Amp
Amps

Test station
source leads
Shorting bar

IRMS = 9,900A

Time

and the circuit breaker is inserted. In addition, lengths of rated


conductor are permitted to be added as shown. This extra rated
conductor has a high impedance and effectively restricts the current to 9,900 RMS symmetrical amps. The power factor increases
to 88% due to small conductor high resistance versus its reactance.
Agency standards allow for a random close during the shortcircuit test, so the peak available current may be as low as
1.414 times the RMS symmetrical current.

This circuit can now only achieve a peak current of 14,001 amps.

Test station
source leads

Shorting bar
removed, circuit
breaker &
conductors added

Thus, the circuit breaker is actually tested to interrupt 9,900


amperes at 88% power factor, not 22,000 amperes at 20% power
factor. The following graph shows the waveforms superimposed
for comparison. Henceforth, this RMS test value will be identified
as the circuit breaker interrupting capacity. (Dont confuse this with
the circuit breaker marked interrupting rating.)

Each
4 feet 12 AWG

Ip = 48,026A

IRMS = 22,000A

20A, 240V, 2-Pole


Circuit Breaker
marked 22,000 A.I.R.

Ip = 14,001A

P.F. = 20%
IRMS = 22,000A
P.F. = 88%
IRMS = 9,900 Amp

Each
10 inches 12 AWG

Amps

20 A

IRMS = 9,900A

Time

Fuseology
Equally important, the short-circuit power factor is greatly affected
due to the high R values of the small, rated wire. This results in a
lower peak value that the circuit breaker must tolerate during the
first one-half cycle.

Bus Bar Conditions- Circuit Breakers


Beginning 10/31/2000, UL 489 requires circuit breakers rated 100A
and less to additionally be tested under bus bar conditions.
However, this does not assure that the circuit breakers interrupting
capacity equals its interrupting rating nor even that the circuit
breaker is reusable. In this test, line and load terminals are connected to 10" of rated conductor. For single pole circuit breakers,
these 10" leads are then connected to 4' of 1 AWG for connection to
the test station. For multi-pole circuit breakers, the 10" line side
leads are connected to the test station through 4' of 1 AWG. The
load side is shorted by 10" leads of rated conductor per pole.
These bus bar condition tests still do not fully address the situation where a fault can occur less than 4'10" from the circuit breaker.

Following is an example of a partial table showing the actual Ip and


IRMS values to which circuit breakers are tested.
240V - 2-Pole CB Interrupting Capacities (amps)
CB
AMP
RATING

10,000 RMS Sym.


Interrupting Rating

14,000 RMS Sym.


Interrupting Rating
IRMS

18,000 RMS Sym.


Interrupting Rating

Ip

IRMS

Ip

Ip

IRMS

15A
20A
25A
30A
40A
50A
60A

7,200
8,900
10,700
10,700
11,700
11,700
12,500

5,100
6,300
7,500
7,500
8,300
8,300
8,800

8,700
11,400
14,200
14,200
16,000
16,000
17,300

6,100
8,100
10,100
10,100
11,300
11,300
12,200

9,300
12,600
16,500
16,500
19,200
19,200
21,300

6,600
8,900
11,700
11,700
13,600
13,600
15,100

70A
80A
90A
100A

13,000
13,000
13,200
13,200

9,200
9,200
9,300
9,300

18,100
18,100
18,300
18,300

12,800
12,800
12,900
12,900

22,600
22,600
23,000
23,000

16,000
16,000
16,300
16,300

One point to be made is that acceptable bus shot test results per
the product standard do not meet the NEC definition for a circuit
breaker. For example, 7.1.11.6.3.1 of UL 489 states The inability to
relatch, reclose, or otherwise reestablish continuity ... shall be considered acceptable for circuit breakers which are tested under bus
bar conditions. In practical terms, this means the circuit breaker
doesnt have to work after a fault near the circuit breaker occurs.
This is in violation of the 2002 NEC definition for a circuit breaker:
A device designed to open and close a circuit by nonautomatic
means and to open the circuit automatically on a predetermined
overcurrent without damage to itself when properly applied within
its rating. In addition, under bus bar condition tests the circuit
breaker is required to only interrupt one short-circuit current. For
this one short-circuit test shot, the circuit breaker is in its closed
position and the short-circuit current is initiated by the test station
switch closing randomly. The bus bar conditions test procedures
do not evaluate the circuit breaker for closing-on the short-circuit.
Closing-on a short-circuit is an important criteria for safety.

These values are known as the circuit breakers interrupting


capacities.

Single-Pole Interrupting Capability


device is its ability to open an overcurrent at a specified voltage utilizing only one pole of the multi-pole device. Multi-pole mechanical
overcurrent protective devices are typically marked with an interrupting rating. This marked interrupting rating applies to all three poles
interrupting a three-phase fault for a three-pole device. The marked
interrupting rating of a three-pole device does not apply to a single
pole that must interrupt a fault current at rated voltage.

An overcurrent protective device must have an interrupting rating


equal to or greater than the fault current available at its line terminals
for both three-phase bolted faults and for one or more phase-toground faults (110.9). Although most electrical systems are designed
with overcurrent devices having adequate three-phase interrupting
ratings, the single-pole interrupting capabilities are easily overlooked. This section will examine single-pole interrupting capability
(also referred to as individual pole interrupting capability).

Single Pole Interrupting Capabilities

This section will show how single-pole interrupting capabilities must


be considered in some applications. It will also show there are simple
solutions that exist to provide adequate interrupting ratings if molded
case circuit breakers, self protected starters and other overcurrent
protective devices are found to have insufficient single-pole interrupting capabilities.

A circuit breakers, self protected starters, or other


mechanical protective devices ability to open an overcurrent
at a specified voltage utilizing only one pole of the device.

A Fine Print Note was added to 240.85 of the 2002 NEC to alert
users that circuit breakers have single-pole interrupting capabilities that must be considered for proper application. It states:
Single-Pole Interrupting Capabilities For Overcurrent Devices
Current-limiting fuses: the marked interrupting rating is the tested
single-pole interrupting rating. So single-pole interrupting capability is not an issue with fuse applications.

240.85 FPN: Proper application of molded case circuit breakers


on 3-phase systems, other than solidly grounded wye, particularly on corner grounded delta systems, considers the circuit
breakers individual pole interrupting capability.

Airframe/power circuit breaker: per ANSI C37.13 and C37.16 the single-pole interrupting rating is 87% of its three-pole interrupting rating.

As will be shown, there are other overcurrent device types and


other grounding system types where individual pole interrupting
capability must be analyzed.

Molded case circuit breakers: Listed three-pole molded case circuit


breakers have minimum single-pole interrupting capabilities according to Table 7.1.7.2 of UL 489. Table 1 on the next page indicates the
single-pole test value for various three-pole molded case circuit breakers taken from Table 7.1.7.2 of UL 489. A similar table is shown on

The single-pole interrupting capability of a circuit breaker, self protected starter and other similar mechanical overcurrent protective
7

Fuseology
page 54 of the IEEE Blue Book, Recommended Practice for
Applying Low-Voltage Circuit Breakers Used in Industrial and
Commercial Power Systems, (Std 1015-1997).

Circuit breakers with interrupting ratings higher than the standard


interrupting values are needed in todays systems, so additional provisions are in UL 489. Higher interrupting rated molded case circuit
breakers are additionally tested and evaluated per 7.1.11 of UL 489 to
a High Short-Circuit Test procedure in order to be marked with a
higher interrupting rating. This test procedure does not include a single-pole test of higher short-circuit current value than the standard
test provisions. The three-pole test current value can be equal to any
value listed in Table 8.1 of UL 489, from 7,500A to 200,000A. This
three-phase test value must be greater than the values in the far right
column of Table 1. If a circuit breaker successfully tested to a higher
three-pole interrupting value per the High Short-Circuit Tests, the
molded case circuit breaker is marked with this higher interrupting rating which corresponds to the three-pole high short-circuit current test
value.

Self protected starters: UL 508, Table 82A.3 specifies the short circuit
test values on one pole as 4320 amps for 0 to 10 hp devices rated 200
to 250 volts and 8660 amperes for 0 to 200 hp devices rated 600 volts
maximum.
Molded case circuit breakers and self protected starters may not be
able to safely interrupt single-pole faults above these respective values
shown in previous paragraphs. Per 110.9, all overcurrent protective
devices that are intended to interrupt fault currents must have singlepole interrupting capabilities for the maximum single-pole fault current
that is available. And typically, engineers, contractors and inspectors
(AHJs) rely on the applicable product standard testing and listing criteria to verify device ratings as being suitable for specific applications.

As mentioned, a single-pole interrupting test at a higher value than


shown in Table 1 is not required in these optional High ShortCircuit Test procedures. Because of this, the marked three-pole
interrupting rating can be much higher than the tested individual
pole interrupting capability. In addition, the single-pole capability
is not required to be marked on the molded case circuit breaker; it
can only be determined by reviewing the UL 489 standard.

TABLE 1 Standard UL 489 Interrupting Tests For 3-Pole Molded Case


Circuit Breakers
Standard
3-Pole
Interrupting
Values

Standard Single-Pole Interrupting


Tests Values
FRAME RATING

240V

480/277V

480V

100A Maximum
250V Maximum

4,330

--

--

Actual Example
The diagram below illustrates the UL 489 test procedure for a 100A,
480V, three phase circuit breaker that gets listed for a high interrupting rating. Test A and B are the required standard or base interrupting tests. Test A is a three-pole interrupting test at 10,000 A (Table
1, right column), which is a modest three-phase available short-circuit current, and Test B is a single-pole interrupting test at a modest
single-phase available short-circuit current of 8660A (Table 1).
Then, in addition, to be listed and marked with the higher 65,000A
interrupting rating, the circuit breaker must pass the criteria for Test
C. Test C is a three-pole interrupting test at 65,000A three-phase
available short-circuit current. Test D is not conducted; it is not part
of the UL 489 evaluation procedure. This higher three-phase interrupting rated circuit breaker does not have to undergo any test criteria at a corresponding higher single-pole short-circuit current.

600/347V 600V
--

--

5,000

100A Maximum
251-600V

--

10,000

8,660

10,000

8,660

10,000

101 800

8,660

10,000

8,660

10,000

8,660

14,000

801 1200

12,120

14,000

12,120

14,000

12,120

20,000

1201 2000

14,000

14,000

14,000

14,000

14,000

25,000

2001 2500

20,000

20,000

20,000

20,000

20,000

30,000

2501 3000

25,000

25,000

25,000

25,000

25,000

35,000

3001 4000

30,000

30,000

30,000

30,000

30,000

45,000

4001 5000

40,000

40,000

40,000

40,000

40,000

60,000

5001 6000

50,000

50,000

50,000

50,000

50,000

70,000

Note: This data is from UL 489 Table 7.1.7.2.


Molded Case Circuit Breaker Testing - UL 489
Devices must be applied within the limitations of their listing. UL 489 is
the standard for molded case circuit breakers. UL 489 has tests which
it refers to as standard interrupting tests for molded case circuit
breakers. A more appropriate term would be base or lowest interrupting level that any circuit breaker of a given rated voltage and
ampere rating must meet. There are circuit breakers on the market
that just test to these standard or base interrupting tests. However,
because these base interrupting ratings are rather modest values,
some circuit breakers are listed with higher interrupting ratings than
the standard or base levels; for these circuit breakers, there are additional procedures for higher level interrupting tests.

Three-Pole Interrupting Rating & Single-Pole Interrupting Capabilities


Test Procedures for Molded Case Circuit Breakers UL 489

100A, 480V, 3-Pole CB


Interrupting Rating = 65,000 A (3-Pole)
Base Interrupting Rating Procedure
Test A

Test B

3-Phase Test
10,000A

1-Pole Test
8,660A

From Table 1

From Table 1

High Interrupting Rating Procedure


These standard or base interrupting tests for three-pole circuit
breakers involve individual single-pole interrupting tests and multipole interrupting tests. Table 7.1.7.2 of UL 489 provides the singlepole (individual) and multi-pole interrupting current values for various
voltage rating and ampere rating circuit breakers. Table 1 shows
the single-pole short-circuit current values (from Table 7.1.7.2 of UL
489) for which all three-pole circuit breakers are tested and evaluated under single-pole interrupting capabilities. The far right column of
Table 1 shows the three-phase short-circuit current values (from
Table 7.1.7.2 of UL 489) for which all three-pole circuit breakers are
tested and evaluated. These standard circuit breakers would be
marked with an Interrupting Rating (if above 5,000 amperes) corresponding to the three-phase short-circuit current value. The standard circuit breaker is not marked with a single-pole interrupting rating which would correspond to the single-pole interrupting test value.

Test C

Test D

3-Phase Test
65,000A

1-Pole Test

NONE

As an example of single-pole interrupting capability in a typical


installation, consider this three-pole, 100 amp, 480V circuit breaker
with a three-pole interrupting rating of 65,000 amperes. Referring to
Table 1, this breaker has an 8,660 ampere single-pole interrupting
capability for 480V faults across one pole. If the available line-toground fault current exceeds 8,660 amps at 480V, such as might
occur on the secondary of a 1000 KVA, 480V, corner-grounded,
delta transformer, the circuit breaker may be misapplied.
8

Fuseology
Possible Fault Currents During A Ground Fault Condition
The magnitude of a ground fault current is dependent upon the
location of the fault with respect to the transformer secondary.
Referring to Figure 2, the ground fault current flows through one
coil of the wye transformer secondary and through the phase conductor to the point of the fault. The return path is through the enclosure and conduit to the bonding jumper and back to the secondary through the grounded neutral. Unlike three-phase faults,
the impedance of the return path must be used in determining the
magnitude of ground fault current. This ground return impedance
is usually difficult to calculate. If the ground return path is relatively
short (i.e. close to the center tap of the transformer), the ground
fault current will approach the three phase short-circuit current.

Shown below are three still photos from a videotaping of a singlepole fault interruption test on a three-pole circuit breaker rated
480V. This circuit breaker is marked with a three-pole interrupting
rating of 35,000 amperes at 480V. This marked interrupting rating is
per UL 489 test procedures. This circuit breaker is tested for individual single-pole interrupting capabilities in UL 489 at an available
fault current of 8,660 amps (Table 1 prior page). The test that is
shown below is with an available fault current of 25,000 amperes.

Theoretically, a bolted line-to-ground fault may be higher than a


three-phase bolted fault since the zero-sequence impedance can
be less than the positive sequence impedance. The ground fault
location will determine the level of short-circuit current. The prudent
design engineer assumes that the ground fault current equals at
least the available three-phase bolted fault current and makes sure
that the overcurrent devices are rated accordingly.
TYPE OF GROUND SYSTEM AFFECT ON SINGLE-POLE INTERRUPTION
The method in which a system is grounded can be a significant
factor in the performance of multi-pole, mechanical overcurrent
protective devices used in three phase systems. To illustrate this,
several different grounding systems with molded case circuit
breakers will be analyzed.
Solidly Grounded WYE Systems
The solidly grounded, wye system shown in Figure 1 is by far the
most common type of electrical system. This system is typically
delta connected on the primary and has an intentional solid connection between the ground and the center of the wye connected
secondary (neutral). The grounded neutral conductor carries single-phase or unbalanced three-phase current. This system lends
itself well to commercial and industrial applications where 480V (LL-L) three-phase motor loads and 277V (L-N) lighting is needed.

Test set up prior to closure of test station switch.

Solidly Grounded WYE System


SERVICE
PANEL

BRANCH
PANEL
Steel Conduit

277V

7V

C 27

480V

27
7V

B
B

480V
C

Photo of 3-pole circuit breaker during test of individual single-pole


interruption of a fault current beyond the value in Table 1.
Magnetic forces of short-circuit current caused test board to move.

Figure 1 - Solidly Grounded WYE System


If a fault occurs between any phase conductor and ground (Figure
2), the available short-circuit current is limited only by the combined impedance of the transformer winding, the phase conductor
and the equipment ground path from the point of the fault back to
the source. Some current (typically 5%) will flow in the parallel
earth ground path. Since the earth impedance is typically much
greater than the equipment ground path, current flow through
earth ground is generally negligible.

Photo (later in sequence) of 3-pole circuit breaker during test of


individual single-pole interruption of a fault current beyond its
single-pole interrupting capability - it violently exploded.
9

Fuseology
If either Phase A or C is shorted to ground, only one pole of the
branch-circuit overcurrent device will see the 480V fault as shown
in Figure 4. This system requires compliance with single-pole interrupting capabilities for 480V faults on one pole because the
branch-circuit circuit breaker would be required to interrupt
480V with only one pole.

Solidly Grounded WYE System


Single pole must
interrupt fault current
SERVICE
PANEL

BRANCH
PANEL
Steel Conduit

Corner Grounded Delta System

480V
B
C

Fault to
conduit

480V

Single pole must


interrupt
SERVICEfault current

BRANCH
PANEL

PANEL

Steel Conduit
A

B
C

Figure 2 - Single-Pole Fault to Ground in Solidly Grounded Wye


System

A disadvantage of corner-grounded delta systems is the inability to


readily supply voltage levels for fluorescent or HID lighting (277V).
Installations with this system require a 480-120V transformer to
supply 120V lighting. Another disadvantage, as given on page 33
of IEEE Std 142-1991, Section 1.5.1(4) (Green Book) is the possibility of exceeding interrupting capabilities of marginally applied
circuit breakers, because for a ground fault, the interrupting duty
on the affected circuit breaker pole exceeds the three-phase fault
duty. A line-to-ground fault with this type grounding system is
essentially a line-to-line fault where the one line is grounded. The
maximum line-to-line bolted short-circuit current is 87% of the three
phase bolted short-circuit current. Review the prior page photo
sequence testing of the 225 amp, three phase circuit breaker with
a 35,000 ampere interrupting rating (three-pole rating). 87% of
35,000 amperes is 30,450 amperes. The single-pole test was run
with an available of only 25,000 amperes.

Corner-Grounded-Delta Systems (Solidly Grounded)


The system of Figure 3 has a delta-connected secondary and is
solidly grounded on the B-phase. If the B-phase should short to
ground, no fault current will flow because it is already solidly
grounded.

Impedance Grounded System


Low or High impedance grounding schemes are found primarily
in industrial installations. These systems are used to limit, to varying degrees, the amount of current that will flow in a phase to
ground fault. Low impedance grounding is used to limit ground
fault current to values acceptable for relaying schemes. This type
of grounding is used mainly in medium voltage systems and is not
widely installed in low voltage applications (600V or below). The
High impedance grounded system offers the advantage that the
first fault to ground will not draw enough current to cause the overcurrent device to open. This system will reduce the stresses, voltage dips, heating effects, etc. normally associated with high shortcircuit current. Referring to Figure 5, high impedance grounded
systems have a resistor between the center tap of the wye transformer and ground. High impedance grounding systems are used
in low voltage systems (600V or less). With high impedance
grounded systems, line-to-neutral loads are not permitted per
National Electrical Code, 250.36(4).

Corner Grounded Delta System


BRANCH
PANEL
Steel Conduit
A
0V

48
0V

48

B
C

480V

Fault to
conduit

Figure 4 - Fault to Ground on a Corner-Grounded Delta System

Although not as common as the solidly grounded wye connection,


the following three systems are typically found in industrial installations where continuous operation is essential. Whenever these systems are encountered, it is absolutely essential that the proper
application of single-pole interrupting capabilities be assured. This
is due to the fact that full phase-to-phase voltage can appear
across just one pole. Phase-to-phase voltage across one pole is
much more difficult for an overcurrent device to clear than the lineto-neutral voltage associated with the solidly grounded wye systems.

B
C

In solidly grounded wye systems, the first low impedance fault to


ground is generally sufficient to open the overcurrent device on the
faulted leg. In Figure 2, this fault current causes the branch circuit
overcurrent device to clear the 277V fault. This system requires
compliance with single-pole interrupting capability for 277V faults
on one pole. If the overcurrent devices have a single-pole interrupting capability adequate for the available short-circuit current,
then the system meets NEC 110.9.

SERVICE
PANEL

480V

B
C

Figure 3 - Corner-Grounded Delta System (Solidly Grounded)

10

Fuseology
The magnitude of this fault current can approach 87% of the L-L-L
short-circuit current. Because of the possibility that a second fault
will occur, single-pole interrupting capability must be investigated.
The IEEE Red Book, Std 141-1993, page 367, supports this
requirement, One final consideration for impedance-grounded
systems is the necessity to apply overcurrent devices based upon
their single-pole short-circuit interrupting rating, which can be
equal to or in some cases less than their normal rating.

High Impedance Grounded System


SERVICE
PANEL

Resistor

BRANCH
PANEL
Steel Conduit
A

277V

7
C 27

480V

27
7V

B
B

480V
C

Ungrounded Systems
The Ungrounded System of Figure 8 offers the same advantage for
continuity of service that is characteristic of high impedance
grounded systems.
Figure 5 - Impedance Grounded System

Ungrounded System

When the first fault occurs from phase to ground as shown in


Figure 6, the current path is through the grounding resistor.
Because of this inserted resistance, the fault current is not high
enough to open protective devices. This allows the plant to continue on line. NEC 250.36(3) requires ground detectors to be
installed on these systems, so that the first fault can be found and
fixed before a second fault occurs on another phase.

SERVICE
PANEL

BRANCH
PANEL

Steel
Conduit

480V
B
C

480V
C

High Impedance Grounded System


SERVICE
PANEL

BRANCH
PANEL

277V

Steel Conduit
A

Figure 8 - Ungrounded System


480V

27
7V
C 27

7V

480V
C

Resistor keeps first


fault current low:
5 Amps or so

Although not physically connected, the phase conductors are


capacitively coupled to ground. The first fault to ground is limited by
the large impedance through which the current has to flow (Figure
9). Since the fault current is reduced to such a low level, the overcurrent devices do not open and the plant continues to run.

First fault
to steel
conduit

Low Value of Fault Current


Because of Ground Resistor in
Short-Circuit Path

Ungrounded System
SERVICE
PANEL

Figure 6 - First Fault in Impedance Grounded System

480V
B
C

277V

C 27

27

480V

7V

Figure 9 - First Fault to Conduit in Ungrounded System

BRANCH
PANEL
Steel Conduit

As with High Impedance Grounded Systems, ground detectors


should be installed (but are not required by the 2002 NEC), to
warn the maintenance crew to find and fix the fault before a second fault from another phase also goes to ground (Figure 10).

480V
C

High Value of Fault


Current Because
Ground Resistor No
Longer in Path

First fault
to steel
conduit

Low Value of Fault Current


Because of Large Capacitively
Coupled Impedance to Ground

7V

480V

High Impedance Grounded System


Single
pole must
SERVICE
interrupt
fault current
PANEL

Steel
Conduit

Even though the system is equipped with a ground alarm, the


exact location of the ground fault may be difficult to determine. The
first fault to ground MUST be removed before a second phase
goes to ground, creating a 480V fault across only one pole of the
affected branch circuit device. Figure 7 shows how the 480V fault
can occur across one pole of the branch circuit device. It is exactly because of this possibility that single-pole interrupting capabilities must be considered for mechanical overcurrent protective
devices.

BRANCH
PANEL

First fault
to steel
conduit

The second fault from Phase B to ground (in Figure 10) will create a 480
volt fault across only one pole at the branch circuit overcurrent device.
Again, the values from Table 1 for single pole interrupting capabilities
must be used for molded case circuit breaker systems as the tradeoff
for the increased continuity of service. The IEEE Red Book, Std 1411993, page 366, supports this requirement, One final consideration for
ungrounded systems is the necessity to apply overcurrent devices
based upon their single-pole short circuit interrupting rating, which
can be equal to or in some cases less than their normal rating.

Second Fault
To Enclosure

Figure 7 - Second Fault in Impedance Grounded System


11

Fuseology
Ungrounded System
Single pole must
interrupt
fault current
SERVICE

High Impedance Grounded System

BRANCH
PANEL

PANEL

Resistor Keeps First


Fault Current Low:
5 Amps or So

Steel
Conduit

A
B

First fault
to steel
conduit

480V
C

High Value of Fault


Current Because
Large Impedance is
No Longer in Path

Second Fault
To Enclosure

High Impedance Grounded System


Single Pole Must Interrupt Fault Current:
Fuses Marked Interrupting Rating Is Its SingleSERVICE
Pole Interrupting
Rating: SimpleBRANCH
Solution
PANEL
PANEL

Steel Conduit

What Are Single-Pole Interrupting Capabilities For Fuses?


By their inherent design a fuses marked interrupting rating is its
single-pole interrupting rating. Per UL/CSA/ANCE 248 Fuse
Standards, fuses are tested and evaluated as single-pole devices.
Therefore, a fuses marked interrupting rating is its single-pole
interrupting rating. So it is simple, fuses can be applied on single
phase or three phase circuits without extra concern for single-pole
interrupting capabilities. There is no need to perform any special
calculations because of the grounding system utilized. Just be
sure the fuses interrupting ratings are equal to or greater than the
available short-circuit currents. Modern current-limiting fuses are
available with tested and marked single-pole interrupting ratings of
200,000 or 300,000 amperes. LOW-PEAK LPJ_SP, KRP-C_SP,
LPS-RK_SP and LPN-RK_SP fuses all have UL Listed 300,000
ampere single-pole interrupting ratings. This is a simple solution to
assure adequate interrupting ratings for present and future systems no matter what the grounding scheme. Review the three
drawings for a fusible, high impedance grounded system.

27

27

7V

480V

First Fault
to Steel
Conduit

Second Fault
to Enclosure

Figure 13- Upon the second fault, the fault is essentially a line-line
fault with the impedance of the conductors and the
ground path. The fuse must interrupt this fault. Since a
fuses interrupting rating is the same as its single-pole
interrupting capability, modern fuses with 200,000A or
300,000A interrupting rating can be applied without further analysis for single pole interrupting capabilities.

BRANCH
PANEL

480V
B
B

480V

7V

High Value of Fault


Current Because
Ground Resistor No
Longer in Path

A
7V

27

Steel Conduit

A
27
7V

High Impedance Grounded System

First Fault
to Steel
Conduit

480V

Figure 12 - Upon first fault, the fault current is low due to resistor.
As intended the fuse does not open.

In the 2002 NEC 250.4(B) Ungrounded Systems (4) Path for Fault
Current, it is required that the impedance path through the equipment be low so that the fault current is high when a second fault
occurs on an ungrounded system.

SERVICE
PANEL

B
B

Figure 10 - Second Fault to Conduit in Ungrounded System

Resistor

7V
27

Steel Conduit

480V

27
7V

BRANCH
PANEL
A

480V
C

SERVICE
PANEL

480V
C

Figure 11 - Fusible high impedance grounded system.

12

Potrebbero piacerti anche