December 1989
Page 1 of 5
Chevron
PURPOSE ............................................................................................................................3
2.0
SCOPE .................................................................................................................................3
3.0
4.0
DESCRIPTION OF ITEMS.................................................................................................3
4.1
4.2
4.3
4.4
4.5
Page 2 of 5
December 1989
Chevron
PURPOSE
This guide provides instruction on how to complete the Extended Surface Air Cooled Heat
Exchanger Data Sheet EXH-DS-1826. It does not provide rules for the design of air coolers.
Section 600, Model Specification EXH-MS-1826 and API STANDARD 661 have more detailed
information and illustrations of air coolers. Unless otherwise specified, the sections referred to in
this guide refer to sections in the Heat Exchanger and Cooling Tower Manual.
2.0
SCOPE
Data Sheet EXH-DS-1826 summarizes important parameters of performance, construction and
materials. This guide explains terms on the Data Sheet. The section headings in Section 4.0 of this
guide correspond to the section headings on the Data Sheet. This guide does not define every term
on the Data Sheet, only those which need some interpretation.
3.0
4.0
DESCRIPTION OF ITEMS
4.1 Performance Data
4.1.1
Duty is the rate of energy transfer between the process fluid and the ambient air.
4.1.2
4.1.3
Overall Transfer Coefficient (Service and Clean) - The value for clean includes
resistances for film coefficients of the process fluid and air, the tube wall, the fin
bond, and the effect of fin efficiency (variable fin temperature). The value for
service includes the expected fouling resistance and/or an allowance to provide
operating flexibility.
4.1.4
December 1989
Page 3 of 5
Chevron
Enter tube side fouling allowance where experience indicates the need and the value.
Where tube side fouling is not expected (the usual situation), indicate the desired
degree of excess surface area in a note (i.e., "provide 125% of calculated clean
surface area.").
4.1.6
Design dry bulb air temperature is the highest ambient air temperature at which the
design duty can be achieved. Section 610 gives the normal basis for picking this
temperature.
Page 4 of 5
4.2.1
Number of bays - A bay is one or more tube bundles serviced by one or two fans
with a common plenum chamber. See API STANDARD 661 for illustrations.
4.2.2
Effective surface all bays (finned and bare tube) - Finned surface is the actual
external surface area including the fins. Bare tube surface is the outside surface area
of the tubes without fins.
4.2.3
Louvers, air recirculation and steam coils are used for winterization. See API
Recommended Practice 632 for guidance.
4.2.4
Mounting refers to where the air cooler will be installed. Specify pipe-rack and it's
width and elevation for air coolers to be mounted over pipe ways. The vendor
usually decides overall length and width for grade mounted units.
4.2.5
4.2.6
Minimum design pressure is the highest pressure the unit will see in service and is
specified by the engineer. The as-built design pressure is determined by the vendor
and should be equal to or greater than the specified minimum.
4.2.7
Nozzle size, facing and rating should match the piping classification and is specified
by the engineer.
4.2.8
Standard air cooler tubes are 1" OD. Tube wall thickness, or Birmingham Wire Gage
(BWG), is usually minimum wall (min) for carbon steel and average wall (ave) for
alloys. The difference between average and minimum wall is approximately one
BWG point. Specified tube thickness is based on design pressure and corrosion
considerations.
4.2.9
Tube layout should be specified as triangular in all cases. In-line layouts result in
channelling and poor heat transfer.
December 1989
Chevron
The blanks in Note 2 should be filled in to tell the vendor how to balance fan power
cost against the cost of heat transfer surface, and how we intend to evaluate the
vendor's bid.
4.4.2
Additional notes should be added to the Data Sheet to describe any design features
not addressed by the pre-printed items on the Data Sheet.
December 1989
Page 5 of 5