Dated: 24-03-2015
1. Telecom System Architecture & Network Diagram
I.
The distance between Metro Wind Farm and remote substation-2 is <10 km
therefore Power Line Carrier along with outdoor coupling will not be installed
on 132kV line-2.
MPCL Response:
As per the instruction by NTDC (System Protection, letter is
attached) , we are providing differential relay with distance
protection function which can operate through OPGW and as well as
through DPLC.
Furthermore, DPLC shall be used for communication purpose with
NPCC through Far end substation as required under clause 15 of
Schedule 2 page 2-12 of EPA which states as follows:
DPLC shall be the primary medium of communication between the
Complex and NPCC
Islamabad through new 132 kV NTDC/HESCO grid station ("Grid
Station") as well as adjacent Wind Power Project ("WPP") while
backup communication medium shall be a satellite link between
Complex and NPCC Islamabad for the purpose of data, voice and fax
Communication to be provided by the Seller at the Complex.
Therefore, DPLC with outdoor coupling will be required for both
lines.
II.
III.
For the protection of 132kV line-1 differential relay is shown on the drawing
which does not conform to 15(b), schedule # 2 of EPA.
MPCL Response:
As mentioned above, because of the instruction of NTDC (System Protection),
differential relay with distance function has also been provided for line -1
having length > 10 KM.
IV.
Since the distance between Metro Wind Farm and remote substation-1 is
>10km therefore Distance protection will be used. DPLC shall be used for
inter-tripping of circuit breaker at both ends of 132kV Transmission line.
MPCL Response:
As mentioned above, because of the instruction of NTDC (System Protection),
differential relay with distance function has also been provided for line -1
having length > 10 KM, which can operate through OPGW and as well as
through DPLC.
V.
VI.
II.
III.
IV.
Rest of the SLD from telecom point of view is accurate subject to the
approval by system protection.
MPCL Response:
Overall SLD is already approved by System protection.