Sei sulla pagina 1di 81

Power System Protection

Rizwan Khan
University of Engineering and Technology, Lahore
1

Transformer Protection

Rizwan Khan (Lecturer - UET LHE)

Contents of Transformer Protection


Introduction
Overcurrent Protection
Percentage Differential Protection

Causes of False Differential Currents


Supervised Differential Relays
Three Phase Transformer Protection
Rizwan Khan (Lecturer - UET LHE)

Contents of Transformer Protection


Volts per Hertz Protection
Non Electrical Protection
Protection Systems for Transformers

Summary

Rizwan Khan (Lecturer - UET LHE)

Rizwan Khan (Lecturer - UET LHE)

Transformer Faults Statistics

Rizwan Khan (Lecturer - UET LHE)

Introduction
The inherent characteristics of power transformers introduce a
number of unique problems that are not present in the protection

of transmission lines, generators, motors or other power system


apparatus.
In general, a transformer may be protected by fuses, overcurrent
relays, differential relays and pressure relays, and can be
monitored for incipient trouble with the help of winding

temperature measurements, and chemical analysis of the gas


above the insulating oil.
Rizwan Khan (Lecturer - UET LHE)

Factors of Transformer Protection


Transformer Size
Location and Function
Voltage

Connection and Design

Rizwan Khan (Lecturer - UET LHE)

Transformer Size
Transformer Size

Protection

2500kVA

Fuses
Thermal Overload Relays

2500-5000kVA

Fuses
Overcurrent Relays

5000-10000kVA

Fuses
Overcurrent Relays
Ordinary Differential Relays

Above 10MVA

Fuses
Overcurrent Relays
Percentage Differential Relays
Temperature & Pressure Relays

Location and Function


If the transformer is an integral part of the bulk power system,
it will probably require more sophisticated relays in terms of

design and redundancy.


If it is a distribution station step down transformer, a single

differential relay and overcurrent backup will usually sufficient.


If the transformer is near a generation source, the high X/R ratio
of the fault path will require harmonic restraint relays to
accommodate the higher magnetic inrush currents.
Rizwan Khan (Lecturer - UET LHE)

10

Voltage, Connection and Design


Generally, higher voltages demand more sophisticated and costly
protective devices, due to the effect of a delayed fault clearing on

the system performance, and the high cost of transformer repair.


The protection schemes will vary considerably between auto
transformers, and two or three winding transformers. The
winding connection of a three phase transformer, whether delta or
wye, will make a difference in the protection scheme chosen.

Also important are the presence of tertiary windings, type of


grounding used, tap changers or phase-shifting windings.

11

Rizwan Khan (Lecturer - UET LHE)

12

Overcurrent Protection
Fuses
Time Delay Overcurrent Relays
Instantaneous Relays

Rizwan Khan (Lecturer - UET LHE)

13

Fuse
Clearly, the fuse interrupting capability must exceed the maximum
short-circuit current that the fuse will be called upon to interrupt.

The continuous rating of the fuse must exceed the maximum


transformer load.

Typically, the fuse rating should be greater than 150% of the


maximum load.
It is also clear that the transformer magnetizing current should not
cause damage to the fuse.
Rizwan Khan (Lecturer - UET LHE)

14

Fuse
The minimum melt characteristic of the fuse must coordinate with
(i.e. should be well separated from) the protective devices on the

low side of the power transformer. In considering the


coordination, the ambient temperature, prior loading and reclosing
adjustment factors should be taken into account.
The speed ratio of the fuse is dened as the ratio between the
minimum melt current values at two widely separated times: for

example, 0.1 and 100 s. It is desirable to have a fuse with as high a


speed ratio as possible.
Rizwan Khan (Lecturer - UET LHE)

15

Fuse

16

Time Delayed/Instantaneous O/C Relays


Protection against excessive overload, or persisting external fault,
is provided by time-delay overcurrent relays.

The pickup setting is usually 115% of the maximum overload


acceptable.
The time-delay overcurrent relays must coordinate with the lowside protective devices. These may include low-voltage bus relays
for phase-to-phase faults, phase-directional relays on parallel

transformers and the breaker failure relay timers on the lowvoltage breakers.

Rizwan Khan (Lecturer - UET LHE)

17

Rizwan Khan (Lecturer - UET LHE)

18

Differential Protection

Rizwan Khan (Lecturer - UET LHE)

19

Differential Protection
For a normal power transformer

If we use current transformers having turns ratios of 1 : n1 and 1 :


n2 on the primary and the secondary side respectively, under

normal conditions the currents in the secondary windings of the


current transformers are related by

Rizwan Khan (Lecturer - UET LHE)

20

Differential Protection
If we select the CTs appropriately, we may make N1n1 = N2n2, and
then, for a normal transformer, i1s = i2s. However, if an internal

fault develops, this condition is no longer satisfied, and the


difference of ils and i2s becomes much larger; in fact, it is
proportional to the fault current. The differential current provides a
highly sensitive measure of the fault current.

Rizwan Khan (Lecturer - UET LHE)

21

Practical Issues in Differential Protection


Mismatching in CT Ratings
Mismatching in Errors of Transformations
Tap Changer of Transformer

Rizwan Khan (Lecturer - UET LHE)

22

Practical Issues in Differential Protection


First, it may not be possible to obtain the CT ratios on the primary
and the secondary side which will satisfy the condition N1n1 =

N2n2, as we must select CTs with standard ratios.


A somewhat less desirable procedure is to use auxiliary CTs to

achieve the same goal.


In any case, even with these adjustments, there remains some
residual ratio mismatch, which leads to a small differential current
id during normal conditions.
Rizwan Khan (Lecturer - UET LHE)

23

Practical Issues in Differential Protection


Second, the errors of transformation of the two CTs may differ
from each other, thus leading to significant differential current

when there is normal load flow, or an external fault.


Finally, if the power transformer is equipped with a tap changer, it

will introduce a main transformer ratio change when the taps are
changed.

Rizwan Khan (Lecturer - UET LHE)

24

Percentage Differential Protection


In a percentage differential relay, the differential current must exceed a
fixed percentage of the through current in the transformer. The through
current is defined as the average of the primary and the secondary
currents:

The current ir is known as the restraint current a name that comes from

the electromechanical relay design, where this current produced a


restraint torque on the moving disc
25

Percentage Differential Relay Characteristics

Rizwan Khan (Lecturer - UET LHE)

26

Rizwan Khan (Lecturer - UET LHE)

27

Causes of False Differential Currents


Magnetizing Inrush Current during Energization
Harmonic Content of the Inrush Current
Magnetizing Inrush during Fault Removal

Sympathetic Inrush
Transformer Over-excitation
CT Saturation
Rizwan Khan (Lecturer - UET LHE)

28

Magnetizing Inrush Current during Energization


Consider the energization of an unloaded power transformer. As
the switch is closed, the source voltage is applied to the

transformer, and a magnetizing current is drawn from the source.


Let the source voltages and flux linkages are,

Rizwan Khan (Lecturer - UET LHE)

29

Magnetizing Inrush Current during Energization

Rizwan Khan (Lecturer - UET LHE)

30

Magnetizing Inrush Current during Energization


In reality, the magnetizing inductance of the transformer is
nonlinear.

As the flux linkages go above the saturation knee point, a much


larger current is drawn from the source. The magnitude of this
current is determined by the slope of the magnetizing
characteristic in the saturated region, and by the leakage
inductance of the transformer.

It is obvious that magnetizing inrush currents of the order of fault


currents are possible.

Rizwan Khan (Lecturer - UET LHE)

31

Magnetizing Inrush Current during Energization


It should be clear that in most modern transformers very large
inrush currents are possible, depending upon the instant of

energization, and the remnant flux in the transformer core. Since


the inrush current flows only in the primary and not in the
secondary winding of the transformer, it is clear that it produces a
differential current which is 200% of the restraining current, and
would cause a false operation.

Rizwan Khan (Lecturer - UET LHE)

32

Harmonics Content of the Inrush Current


The false operation of a percentage differential relay for a
transformer is prevented by taking advantage of the fact that the

inrush current is rich in harmonic components.

While the fault current is a pure fundamental frequency

component (except for a possible decaying DC component).

Rizwan Khan (Lecturer - UET LHE)

33

Magnetizing Inrush Current during Fault Removal

When a fault external to, but near, the transformer is removed by


the appropriate circuit breaker, the conditions inside the

transformer core are quite similar to those during magnetization of


the transformer.
As the voltage applied to the transformer windings jumps from a
low pre-fault value to the normal (or larger) post-fault value, the
flux linkages in the transformer core are once again forced to
change from a low pre-fault value to a value close to normal.
Rizwan Khan (Lecturer - UET LHE)

34

Magnetizing Inrush Current during Fault Removal

Depending upon the instant at which the fault is removed, the


transition may force a DC offset on the flux linkages, and primary

current

waveforms

similar

to

those

encountered

during

energization would result.


It should be noted that as there is no remnant flux in the core
during this process; the inrush is in general smaller than that
during the transformer energization.

Rizwan Khan (Lecturer - UET LHE)

35

Sympathetic Inrush

Rizwan Khan (Lecturer - UET LHE)

36

Sympathetic Inrush
The phenomenon which causes inrush to flow in a previously
energized transformer, when a parallel bank is energized, is known

as the sympathetic inrush.


The current waveforms of a typical sympathetic inrush

phenomenon are illustrated in next slide.

Rizwan Khan (Lecturer - UET LHE)

37

Sympathetic Inrush

38

Transformer Over-excitation
During load rejection and certain other operating conditions, a
transformer may be subjected to a steady-state overvoltage at its

nominal frequency.
During over-excitation, the transformer flux remains symmetric,

but goes into saturation for equal periods in the positive and the
negative half-periods of the waveform, due to the rich contents of
the harmonics.

Rizwan Khan (Lecturer - UET LHE)

39

CT Saturation
For certain external faults, where the fault currents are large, it is
likely that one of the CTs may saturate, this may directly effect the

operation of both ordinary and percentage differential relay.

Rizwan Khan (Lecturer - UET LHE)

40

Rizwan Khan (Lecturer - UET LHE)

41

How to Avoid False Differential Currents


To desensitize the differential relay when the transformer is
energized.

Introduction of the Concept of Voltage Supervision


Harmonics Characterization as Supervised Differential Relay

Rizwan Khan (Lecturer - UET LHE)

42

Desensitize the Differential Relay


One of the earliest ideas was to desensitize the differential relay when
the transformer is energized. Thus, the less sensitive relay would not see
the inrush current, thus avoiding a false trip.
However, this is a poor practice, as it is precisely during the initial
energization of the transformer, when the transformer is first energized,
or some repair work on the transformer may have been completed, that
the transformer is in need of protection. This is to ensure that the repair

work has been successfully completed, and no maintenance tools


inadvertently left inside or around the transformer.
Rizwan Khan (Lecturer - UET LHE)

43

Voltage Supervision
It may be expected that during the inrush conditions, the
transformer voltage would be close to normal, while during faults,

the voltage would be much less. Thus, an under-voltage relay may


be used to supervise the differential relay.
In general, this type of voltage supervision is not preferred, as the
under-voltage relay tends to be slow, and consequently the entire
protection becomes slower.

Rizwan Khan (Lecturer - UET LHE)

44

Harmonics Characterization
The method currently in use on large transformers is based upon using
the harmonic characterization of the inrush and over-excitation currents.
The differential current is almost purely sinusoidal when the transformer
has an internal fault, whereas it is full of harmonics when the
magnetizing inrush current is present, or when the transformer is
overexcited.
Thus, the differential current is filtered with filters tuned to an

appropriate set of harmonics, and the output of the filters is used to


restrain the differential relay.
45

Supervised Differential Relays

46

Rizwan Khan (Lecturer - UET LHE)

47

Three Phase Transformer Protection


The major difference between three-phase transformer protection and
that of three single-phase transformers is the necessity to deal with the
effect of a wyedelta transformation.
Under normal load conditions, the currents in the primary and secondary
windings are in phase, but the line currents on the wye and delta sides of
the three-phase transformer are out of phase by 30.
The difficulty is resolved by connecting the current transformers in such

a manner that they undo the effect of the wyedelta phase shift produced
by the main transformer.
Rizwan Khan (Lecturer - UET LHE)

48

Three Phase Transformer Protection


The current transformers on the wye side of the power transformer
are connected in delta, and the current transformers on the delta

side of the power transformer are connected in wye.


In addition to the phasing consideration discussed above, it is also

necessary to adjust the turns ratios of the CTs so that the delta
connection on the wye side of the power transformer produces
relay currents that are numerically matched with the relay currents
produced by the wye-connected CTs.
Rizwan Khan (Lecturer - UET LHE)

49

Three Phase Transformer Protection

50

Multi Winding Transformer Protection


Consider the three-winding transformer shown in Figure 8.13. One
winding is assumed to be delta connected, while the other two are

assumed to be wye connected. The CTs must of course be


connected in wye on the delta side and in delta on the wye side of
the power transformer.
This will ensure that the phase shifts created in the currents of the
power transformer are compensated by the CTs, so that the
secondary currents are once again in phase.
Rizwan Khan (Lecturer - UET LHE)

51

Multi-winding Transformer Protection

Rizwan Khan (Lecturer - UET LHE)

52

Multi Winding Transformer Protection


It is interesting to note that under certain conditions a two-winding
differential relay can be used to protect a three-winding

transformer. If the transformer is connected to a source only on


one side, the other two winding CTs could be paralleled to
produce a net secondary current, which can then be used in a twowinding protection scheme.

Rizwan Khan (Lecturer - UET LHE)

53

Regulating Transformers Protection


The regulating transformers may regulate the turns ratio or the
phase shift between the primary and the secondary windings.

The regulating transformers usually consist of two transformers:


one to provide the magnetizing current for the transformers and
the other to provide the variable turns ratio or the variable phase
shift.
In either case, the percentage differential relay is not suitable for

the protection of these transformers. Often, a sudden pressure


relay (SPR) provides the most sensitive protection.

54

Rizwan Khan (Lecturer - UET LHE)

55

Voltage/Hertz Protection
Transformer cores are normally subjected to flux levels
approaching the knee point in their magnetizing characteristic.

If the core flux should exceed the saturation level, the flux patterns
in the core and the surrounding structure would change, and

significant flux levels may be reached in the transformer tank and


other structural members. As these are not laminated, very high
eddy currents are likely to result, producing severe damage to the
transformer.
Rizwan Khan (Lecturer - UET LHE)

56

Voltage/Hertz Protection
As the flux is proportional to the voltage, and inversely
proportional to the operating frequency, the significant relaying

quantity is the ratio of the per unit voltage to the per unit
frequency. This is known as volts/hertz protection.
This protection is specially needed in the case of unit-connected
generator transformers. If the turbinegenerator is shut down with
the voltage regulator in service, the volts/hertz limit of the

transformers (and indeed of generators as well) could be easily


exceeded.
Rizwan Khan (Lecturer - UET LHE)

57

Voltage/Hertz Protection
Similar conditions could also be reached by load rejection with
voltage regulators disconnected, or in manual position, or with

faulty instrumentation in the regulator circuits.


The volts/hertz capability of transformers is specified by

manufacturers.
Many volts/hertz relays have two settings, a lower setting for
alarm and a higher setting which may be used for tripping.

Rizwan Khan (Lecturer - UET LHE)

58

Voltage/Hertz Protection

Rizwan Khan (Lecturer - UET LHE)

59

Rizwan Khan (Lecturer - UET LHE)

60

Pressure Devices
When a fault occurs inside an oil-filled transformer tank, the fault
arc produces gases, which create pressure waves inside the oil. In

the conservator type of tank construction, which is more


common in Europe, the pressure wave created in the oil is detected
by a pressure vane in the pipe which connects the transformer tank
with the conservator.
The movement of the vane is detected by a micro-switch, which

can be used to sound an alarm, or trip the transformer. This type of


a relay is known as a Buchholz relay.
61

Pressure Devices
In the USA, the more common transformer construction is of the
tank type with a gas cushion at the top of the tank. In such a

transformer, the pressure wave is detected by a SPR mounted on


the side of the transformer. The mechanical sensor consists of a
bellows and a pressure equalizer, which together is insensitive to
slow changes of pressure, for example those caused by thermal or
loading changes in the transformer.

However, a pressure wave created by a fault is detected by the


relay, and can be used to trip or alarm.
62

Pressure Devices
Faults on the bushings, and connecting leads, do not create an arc
in the insulating oil or gas, and must be protected by differential

relays.

Rizwan Khan (Lecturer - UET LHE)

63

Temperature Devices
Some devices simply measure the oil temperature, usually the top
oil.

Other devices use a combination of current, by placing a small


search coil around a lead, and oil temperature to measure the total

effect of load and ambient temperature.


The critical temperature is referred to as the hot-spot
temperature, and is the highest temperature that will occur
somewhere in the winding.
Rizwan Khan (Lecturer - UET LHE)

64

Temperature Devices
The temperature devices actuate alarms to a central dispatching
office, to alert the operators, who can either remotely unload the

transformer by opening the circuit breaker, or can dispatch an


operator to the station.
The hot-spot sensors are also commonly used to start and stop
cooling fans and pumps.

Rizwan Khan (Lecturer - UET LHE)

65

Rizwan Khan (Lecturer - UET LHE)

66

Protection Systems for Transformers


Parallel Transformer Banks
Tapped Transformer Banks
Substation Design

Station Service
Generator Station Design
Rizwan Khan (Lecturer - UET LHE)

67

Parallel Transformer Banks


It is not uncommon when two transformers are connected in
parallel with no circuit breakers used to separate them that a single

differential relay is used for the protection of both banks.


However, the problem of sympathetic inrush presents difficulties
to the common differential relay, when one of the transformers is
energized with its switch while the other transformer is in service.
The sympathetic inrush is now likely to trip the two transformers.

The problem can be dealt with satisfactorily by the use of separate


differential relays.

Rizwan Khan (Lecturer - UET LHE)

68

Tapped Transformer Banks


Connecting a transformer directly to the high-voltage transmission
line is a practical and relatively inexpensive way of providing

service to an isolated industrial or residential load.


In the next slides, complete protection schemes are introduced for

the protection of lines and for the protection of tapped transformer,


in different scenarios.

Rizwan Khan (Lecturer - UET LHE)

69

Tapped Transformer Banks

Full complement of circuit breakers for transformer protection

70

Tapped Transformer Banks

Direct connection of transformer and transmission lines - shows a variation in which


the line circuit breakers are not used. In this configuration a line fault will remove the
71
transformer by opening the remote terminals.

Tapped Transformer Banks

Use of motor-operated air break switches at a transformer tap

72

Substation Design
Since a power transformer interconnects two or more voltage
levels, its location requires special consideration in the design of a

substation and the protection of all of the elements within it.


Usually the various voltage levels are contained within separate

areas, each with its own bus configuration and associated


equipment and separated by considerable distances.
Proceeding Figures show 345 kV/138 kV station with different
protection schemes.
Rizwan Khan (Lecturer - UET LHE)

73

Substation Design

Substation transformer with a full complement of circuit breakers

74

Substation Design

MOAB connection of a transformer to a 345 kV bus

75

Station Service
Most power transformers are built with a delta tertiary winding to
provide a path for third harmonics and to help stabilize the neutral.

Although the capacity of the tertiary need not be very large, it is a


good source for the station auxiliary equipment such as circuit

breaker air compressors, oil pumps, battery chargers, etc.


If the load taken off the tertiary is large enough to upset the
transformer differential, it must be connected into the differential
CTs, as shown in Figure on next slide.
Rizwan Khan (Lecturer - UET LHE)

76

Station Service

Protection of generating station service transformer

77

Generator Station Design


The most common configuration used presently for large
generating plants is a unit-connected system. In this system, the

generator, generator step up transformer (GSU), the unit auxiliary


transformer (UAT) and the reserve or start up auxiliary
transformer (RAT) are all connected as a unit and their protection
and controls are interrelated.
Figure on next slide, shows a typical design with the associated
zones of protection.
Rizwan Khan (Lecturer - UET LHE)

78

Generating station transformers and their protection systems

79

References
Stanley H. Horowiz, Arun G. Phadke, Power System
Relaying, 3rd Edition, Chapter No. 8

THANKS FOR YOUR TIME


81

Potrebbero piacerti anche