Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Rizwan Khan
University of Engineering and Technology, Lahore
1
Transformer Protection
Summary
Introduction
The inherent characteristics of power transformers introduce a
number of unique problems that are not present in the protection
Transformer Size
Transformer Size
Protection
2500kVA
Fuses
Thermal Overload Relays
2500-5000kVA
Fuses
Overcurrent Relays
5000-10000kVA
Fuses
Overcurrent Relays
Ordinary Differential Relays
Above 10MVA
Fuses
Overcurrent Relays
Percentage Differential Relays
Temperature & Pressure Relays
10
11
12
Overcurrent Protection
Fuses
Time Delay Overcurrent Relays
Instantaneous Relays
13
Fuse
Clearly, the fuse interrupting capability must exceed the maximum
short-circuit current that the fuse will be called upon to interrupt.
14
Fuse
The minimum melt characteristic of the fuse must coordinate with
(i.e. should be well separated from) the protective devices on the
15
Fuse
16
transformers and the breaker failure relay timers on the lowvoltage breakers.
17
18
Differential Protection
19
Differential Protection
For a normal power transformer
20
Differential Protection
If we select the CTs appropriately, we may make N1n1 = N2n2, and
then, for a normal transformer, i1s = i2s. However, if an internal
21
22
23
will introduce a main transformer ratio change when the taps are
changed.
24
The current ir is known as the restraint current a name that comes from
26
27
Sympathetic Inrush
Transformer Over-excitation
CT Saturation
Rizwan Khan (Lecturer - UET LHE)
28
29
30
31
32
33
34
current
waveforms
similar
to
those
encountered
during
35
Sympathetic Inrush
36
Sympathetic Inrush
The phenomenon which causes inrush to flow in a previously
energized transformer, when a parallel bank is energized, is known
37
Sympathetic Inrush
38
Transformer Over-excitation
During load rejection and certain other operating conditions, a
transformer may be subjected to a steady-state overvoltage at its
nominal frequency.
During over-excitation, the transformer flux remains symmetric,
but goes into saturation for equal periods in the positive and the
negative half-periods of the waveform, due to the rich contents of
the harmonics.
39
CT Saturation
For certain external faults, where the fault currents are large, it is
likely that one of the CTs may saturate, this may directly effect the
40
41
42
43
Voltage Supervision
It may be expected that during the inrush conditions, the
transformer voltage would be close to normal, while during faults,
44
Harmonics Characterization
The method currently in use on large transformers is based upon using
the harmonic characterization of the inrush and over-excitation currents.
The differential current is almost purely sinusoidal when the transformer
has an internal fault, whereas it is full of harmonics when the
magnetizing inrush current is present, or when the transformer is
overexcited.
Thus, the differential current is filtered with filters tuned to an
46
47
a manner that they undo the effect of the wyedelta phase shift produced
by the main transformer.
Rizwan Khan (Lecturer - UET LHE)
48
necessary to adjust the turns ratios of the CTs so that the delta
connection on the wye side of the power transformer produces
relay currents that are numerically matched with the relay currents
produced by the wye-connected CTs.
Rizwan Khan (Lecturer - UET LHE)
49
50
51
52
53
54
55
Voltage/Hertz Protection
Transformer cores are normally subjected to flux levels
approaching the knee point in their magnetizing characteristic.
If the core flux should exceed the saturation level, the flux patterns
in the core and the surrounding structure would change, and
56
Voltage/Hertz Protection
As the flux is proportional to the voltage, and inversely
proportional to the operating frequency, the significant relaying
quantity is the ratio of the per unit voltage to the per unit
frequency. This is known as volts/hertz protection.
This protection is specially needed in the case of unit-connected
generator transformers. If the turbinegenerator is shut down with
the voltage regulator in service, the volts/hertz limit of the
57
Voltage/Hertz Protection
Similar conditions could also be reached by load rejection with
voltage regulators disconnected, or in manual position, or with
manufacturers.
Many volts/hertz relays have two settings, a lower setting for
alarm and a higher setting which may be used for tripping.
58
Voltage/Hertz Protection
59
60
Pressure Devices
When a fault occurs inside an oil-filled transformer tank, the fault
arc produces gases, which create pressure waves inside the oil. In
Pressure Devices
In the USA, the more common transformer construction is of the
tank type with a gas cushion at the top of the tank. In such a
Pressure Devices
Faults on the bushings, and connecting leads, do not create an arc
in the insulating oil or gas, and must be protected by differential
relays.
63
Temperature Devices
Some devices simply measure the oil temperature, usually the top
oil.
64
Temperature Devices
The temperature devices actuate alarms to a central dispatching
office, to alert the operators, who can either remotely unload the
65
66
Station Service
Generator Station Design
Rizwan Khan (Lecturer - UET LHE)
67
68
69
70
72
Substation Design
Since a power transformer interconnects two or more voltage
levels, its location requires special consideration in the design of a
73
Substation Design
74
Substation Design
75
Station Service
Most power transformers are built with a delta tertiary winding to
provide a path for third harmonics and to help stabilize the neutral.
76
Station Service
77
78
79
References
Stanley H. Horowiz, Arun G. Phadke, Power System
Relaying, 3rd Edition, Chapter No. 8