Table of Contents

Fire Alarm Systems.


Product Catalogue.

B-HB-028DE

Produktkatalog Brandmeldesysteme 2012/2013 V 1.1

Table of Contents

Table of Contents
Table of Contents ..............................................................................................................................2
1

General hints .............................................................................................................................4

Modular control panels Integral IP MX .......................................................................................5

2.1
2.2
2.3
2.4
2.5
2.6
3

Fire alarm control panel Integral IP MXF......................................................................................................... 8


Controller unit for multizone extinguishing systems Integral IP MXE........................................................ 9
Integral IP MX in Floor Standing Cabinets.....................................................................................................10
Integral IP MX Modules.....................................................................................................................................12
Accessories & replacement parts.......................................................................................................................21
Software for Integral IP control panels............................................................................................................24

Compact control panels Integral IP CX ......................................................................................25

3.1
3.2
3.3
3.4

Fire alarm control panel Integral IP CXF........................................................................................................25


Integral IP CXF Modules ...................................................................................................................................27
Controller unit for single zone extinguishing systems Integral IP CXE.....................................................31
Accessories & replacement parts.......................................................................................................................32

Compact control panel Integral IP BX........................................................................................35

External indicating & operating panels .....................................................................................36

5.1 MMI-BUS Devices ..............................................................................................................................................36


5.2 EPI-BUS Devices ................................................................................................................................................42
6

Management system SecoLOG IP .............................................................................................45

Integral X-LINE .........................................................................................................................47

7.1
7.2
7.3
7.4
7.5
8

Special detectors ......................................................................................................................74

8.1
8.2
8.3
8.4
8.5
8.6
8.7
9

Automatic fire detectors & detector bases ......................................................................................................47


Manual call points ................................................................................................................................................51
Modules .................................................................................................................................................................55
Alarm devices .......................................................................................................................................................65
Testing devices & Accessories...........................................................................................................................69
Linear smoke detectors .......................................................................................................................................74
Aspirating smoke detectors................................................................................................................................79
Linear heat detectors ...........................................................................................................................................90
Flame detectors ....................................................................................................................................................98
Radio-linked detectors ........................................................................................................................................99
Fire gas detectors ...............................................................................................................................................102
Hazardous areas .................................................................................................................................................103

Accessories ............................................................................................................................112

9.1 Fire brigade key safes & plan case...................................................................................................................112


9.2 Sounders & Flashing Lights .............................................................................................................................114
9.3 Holding magnets & anchoring plates .............................................................................................................122
9.4 External power supply units ............................................................................................................................124
9.5 Overvoltage protection .....................................................................................................................................131
9.6 Modems & Converters......................................................................................................................................133
9.7 Transmission devices ........................................................................................................................................136
9.8 Hold-open systems ............................................................................................................................................138
9.9 Cables...................................................................................................................................................................142
9.10 Labelling Panels & Stickers ..............................................................................................................................144
9.11 Printed items & brochures ...............................................................................................................................146

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Table of Contents

10 System overviews..................................................................................................................147

10.1 Fire alarm control panel Integral IP MXF.....................................................................................................147


10.2 Multiple zone extinguishing system Integral IP MXE.................................................................................148
10.3 Fire alarm control panel Integral IP CXF......................................................................................................149
10.4 Single zone extinguishing system Integral IP CXE......................................................................................150
10.5 Fire alarm control panel Integral IP BX ........................................................................................................151
10.6 MMI & EPI BUS...............................................................................................................................................152
10.7 Integral X-LINE ................................................................................................................................................153
10.8 Integral LAN ......................................................................................................................................................154

Responsible for the content of this document:


Michaela Schwantner Product Management Fire Alarm Systems
Tel: +43-1-81157-304 m.schwantner@schrack-seconet.com

B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

General hints

1 General hints
This product catalogue describes the most important components of the Integral IP fire alarm system, thereby
representing a mere fraction of our very extensive range of products. All information which is not contained in
this catalogue is available upon request at any time from one of our offices.
All Schrack fire alarm systems are developed in Austria and constitute the technological state-of-the-art and the
latest scientific findings, whilst observing the currently enforced standards (European standards, fire brigade
specifications, and certification from European Testing and Certification Centres etc.). Schrack Seconet frequently
cooperates with technical universities and international companies, as well as with testing and accreditation
centres, fire prevention centres and fire brigade associations, so that our products can be constantly improved and
adapted to meet new demands. Our employees are active in all important national and international bodies (such
as CEN, DIN, ON, VB etc.). Schrack Seconets high quality is documented in a quality management system,
which has been certified in accordance with ISO 9001 for all the companys divisions.
The planning of fire alarm systems as well as the installation, commissioning and maintenance of products and the
systems which they form required specialist expert knowledge, and therefore may only be undertaken by specially
trained experts. The product-specific training of staff members must be carried out by Schrack Seconet or by
people who have been specifically authorised to carry out this duty by Schrack Seconet. In addition to this, the
currently applicable country-specific regulations and guidelines for the planning, construction of and use of the
products must be observed and complied with without fail. Damage and consequential damage which have been
caused due to interference or modifications made to our products or by improper handling of them are excluded
from liability. The same is also true for inappropriate storage of items or other detrimental external factors.
We would explicitly like to point out that the fire alarm system must be periodically serviced in accordance with
the respective relevant standards (e.g. NORM F 3070, DIN 14675 etc.), in order to also ensure that the system's
range of functions and protective scope is also maintained in the long term.
The descriptions and technical information contained below corresponds to the current status stands at the time
of printing. We reserve the right to make alterations, particularly where they are the result of technical
improvements. The products illustrated in this document may differ in terms of their appearance as a result of the
constant continued development from those products which are delivered.
The design of this catalogue is subject to copyright. Printing or transferring of texts, illustrations and photos in all
media (e.g. Print, CD ROM, the Internet etc.) from this catalogue, both as excerpts as well as in their entirety, is
only permitted with our explicit written permission. We assume no liability for misprints and blatant errors. When
ordering or making an enquiry, please quote article numbers.

Information about the structure of the catalogue


Name, Description &

No.: 20-1000002-01

Illustration of the main article


with article number

B5-OM8 Module for monitored outputs Technical Specifications


For controlling and monitoring 8 primary lines (flashing lights, sirens etc.) in
accordance with EN 54-13, each with a maximum current of 1.3 A.
Power supply:
internally via the system BUS
Current draw:
28 mA (battery current without peripherals)
Ambient temperature:
-5 to +50C
Output voltage:
22 V min. / 24 V typ. / 28 V max.
Output current:
1.3 A max., short circuit resistant
Short circuit current:
1.45 A min. / 1.75 A typ./ 2.76 A max.
Legend

Type

Art. No.

B5-OM8 Module for monitored outputs


Connector plugs for B3/B5-OM8 outputs
(spare part)

B5-OM8
ST-OM8

20-1000002-01
FG74095

Product variants, accessories & replacement parts with type name and article number

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Modular control panels Integral IP MX

2 Modular control panels Integral IP MX


The Integral IP MX system is a modular, decentrally constructed system, comprising of individual components,
and is programmed and configured according to the individual requirements. The system can be deployed as a fire
alarm control panel, as a multizone extinguishing system or as a combined fire alarm control panel and
extinguishing system. A detailed description of the system is contained in the "Integral IP MX System
Description" document, a system overview can be found in chapter 10.

Complete redundancy
One of the main features of the system is its complete, intelligent redundancy. This means that not only is the
microprocessor structure duplicated, but all system structures, components and electronic elements in the control
panel are present in duplicate. The occurrence of a fault in the active system causes the system to be automatically
switched over to the second system running in parallel and for a system fault to be indicated. All functions, such
as detection, triggering of alarms, plain text indication and controlling of fire alarm devices etc. remain unaffected
by this occurrence.
The data circuits to the external operating panels and the connections between the subcontrol units are also
present in duplicate, in order to also guarantee in all instances that the system remains fully functional even in the
event of wire breaks or faults.

Subcontrol unit
The fire alarm control panel comprises of 1 to 16 subcontrol units, which are spread around the building as
required. The system is operated in a clear manner from a single location, with the system operating, despite its
decentralized construction, exactly like a traditional centralized fire alarm control panel. The interconnection of
several subcontrol units to a single fire alarm control panel is known as an Integral LAN.

Integral LAN and Mesh Network


In the Integral LAN mesh network, multiple connections are established between the individual control panels, in
order to ensure, even in the event of connection faults that might occur, that every device still continues to have a
connection to the network. The completely freely selectable topology of the cabling allows the mesh network to
be adapted optimally to suit the physical configuration of the building. There are network modules with different
interfaces (RS485, optic fibre, DSL) available for the Integral LAN, thereby making external modems and
converters a thing of the past.
The Integral IP control panels can be directly connected to the IT infrastructure of a building, with access via
Intranet or Internet being possible without requiring any additional effort. Various parallel indicator tableaux or
superordinated centralized indication devices may, as long as they are not dedicated to alarming the emergency
services, use the existing communications paths of the PC networks.

SecoNET Network
Every Integral LAN is suitable for connection building management systems and field buses. If more than 16
subcontrol units are required, then Integral LANs are connected to the SecoNET Fire Alarm Network. In the
SecoNET, all connected fire alarm control panels (Integral, Integral IP MX, Integral IP CX, Integral LAN, etc.)
are configured separately from one another, and furthermore, in every SecoNET device, there is an interface set
aside for SecoNET. A standardised interface protocol is used for connecting control systems produced by
different manufacturers with one another, which allows the connection to occur with the device functioning fully.

Length of wires
The distance between two Integral IP MX or Integral IP CX control panels may be up to 1200 metres. Neither
repeaters nor other additional devices such as modems are required, and only the types of cable used and the
environmental factors must be observed. In special cases - where the distance has to be greater than 1,200 metres
- then additional external transmission equipment can be used.
B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

Modular control panels Integral IP MX

External Operating Panels & Devices Bus


External operating panels and devices and connected to the control panel via the MMI BUS. Up to 8 devices can
be connected to this serial data bus - without using any additional devices e.g. repeaters etc. - located up to 1200
metres away from the control panel. Data communication uses redundant digital communication circuits, with the
devices being able to be used in any possible combination regardless of the devices locations. For safety reasons
the data circuit as well as the power supply circuit are both fully redundant. Moreover all internal and external
Integral MAP operating panels and the Integral PIP indicator panel have an EPI-BUS interface. Up to 3 nonredundant indication and operating devices can be connected to this data bus and can be located up to 1 metre
away. Max. 15 devices can be connected per MMI BUS, of which there may be a maximum of 8 MMI bus devices.

Overvoltage protection
The Integral IP system is fitted with a comprehensive integrated overvoltage protection concept, which protects
all peripheral inputs, including the power supply in accordance with EN50130-4 (EMC) and EN50082-2
(interference in industrial use). The EMC protection concept involves the deployment of measures such as a zonal
concept, tranzorb diodes, filters and broadband decoupling of the power supply to protect the electronic devices.
As a result, no additional measures, e.g. an overvoltage arrester etc. are required for operation within building
where heavy- and medium-duty protection is installed (protection against lightning strikes, supply side overvoltage
arrester).

Approvals

VdS Device and System Approval: G298029, S298029, G204087


EC Conformity Certificate No. 0786-CPD-20240 (VdS)
Austrian Testing Centre for Fire Prevention Technology: No: FT 14/159/10, FT 14/622/10
VB Cert sterreich: Nos. 002/BM-PSys/014, 002/BM-PSys/015, 002/BM-PSys/016
German Institute for Bulding Technologies: Z-6.5-1871
Test for Electromagnetic Compatibility: TV Austria No. M/EMV-96/381
Country-specific approvals in Austria, Germany, Denmark, Italy, Croatia, The Netherlands, Poland,
Romania, Russia, Sweden, Switzerland, Slovakia, Czech Republic, Turkey, Hungary, Ukraine and many
more.

Important Features

Microprocessor-controlled and monitored system topology


Fully redundant system composition to ensure that the system remains fully operational, even in the event
of a fault or in the event that one half of the processor unit fails
Constant automatic test routines for all system components and programs
Six line display for displaying the system status in plain text (alarms, faults etc.)
Acoustic and optical alarm notification for alarms and faults
Alarm buffering
Possibility to manually test the control panel and its functions
Plain text indication of individual detector and indicator zones
Up to 8 external operating panels per control panel, maximum distance 1200 m
Operating panel language can be selected, with the ability to switch between up to 4 languages during
normal operation
External device bus for up to 15 indication and operation devices
Serial log printers with UPS power supply, event memory and message filter
Suitable for connection to the public alarm system of the fire brigade
11 free connection slots for modules (detector zones, inputs and outputs, relays etc.)
Saving of system configuration by using flexible flash memory technology
Emergency power supply for a supply interruption period of 72 hours
Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Modular control panels Integral IP MX

Options

Control panel networking using a TCP/IP-based local mesh network:


up to 16 control panels can be networked to form a logical unit without requiring a
superordinated management system
Mesh network with up to 4 connections per subcontrol unit: in the event of a device failing or a
connection fault occurring, it is possible for data communications to continue by diverting
(routing) the data.
Data transmission at 625/2500 Kbit
Flexible topology: stub connection to loop is possible
Ethernet protocol: Using the customer's IT infrastructure
Access to the control unit over the Intranet and Internet
Standardised IT components are used
Can be connected to hierarchically superior computer systems or fire alarm control systems via serial data
interfaces with a full range of functions (message and command modes)
Connection for fire brigade control panels pursuant to NORM F3031, DIN 14661, SN 054002 and
DIN 14662
Daytime/Night time operation mode switching can be individually programmed for each detector zone
and every week day
Intervention mode
Detectors can be freely assigned and linked to controller criteria - software controlled
Software-controlled two zone dependency or two detector dependency for alarm notification and
controlling of devices
Recognition and evaluation of the status of detectors (contamination)
Disablement of individual detectors
Can be networked with all Schrack fire alarm control panels

B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

Modular control panels Integral IP MX Fire alarm control panel Integral IP MXF

2.1

Fire alarm control panel Integral IP MXF


Basic Configuration
In their basic configuration, all Integral IP MX control panels contain:
back panel with cutaways for cable inlets and battery shelf
Module rack with bus circuit boards for fitting of 8 freely selectable
line modules or input/output modules as well as 3 connection slots for
fitting relay modules
B5-MCU Main processor unit with interface for built-in operating
panel and service PC
Power supply
2 emergency power supply batteries
Power clips and battery cable

Integral IP MX in basic configuration

No.: FG052100

No.: FG052101

No.: FG052102

No.: FG052107

Integral IP MXF cabinet variants


Integral IP MX cabinet in basic configuration, consisting of:
Sheet steel cabinet
B5-MCU main processor unit
B5-PSU power supply unit
Module rack with BUS circuit boards
Power clips and battery cable
Space for fitting batteries (max. size 2 x 12 V/45 Ah)
Input voltage / frequency:
230 VAC +15%/-20% 47-63 Hz
Input power:
max. 280 W
Output voltage:
26,3 VDC (+50C) to 28,3 VDC (0C)
Output current:
7,5 A
Quiescent current:
74 mA (without operating panel and
without printer)
Batteries that can be used:
2 pcs. 12 V / 38...40 Ah in series
Emergency power supply:
72 h normal operation + 0.5 h alarm
Protection category:
IP 30 (acc. to DIN 40050)
Ambient temperature:
-5 to +50C
Rel. air humidity:
5 to 95%, without condensation
Air pressure:
80 kPa, up to 2000 m above sea level
Case:
sheet steel, red RAL 3000
Dimensions:
600 x 445 x 225 mm (HxWxD)
Weight basic configuration:
15 kg (without batteries)
Weight per battery:
15 kg
VdS-Approval:
G298029
CPD-Approval:
0786-CPD-20240
Description

Type

Art. No.

Integral IP MXF basic configuration


cabinet with full door
Integral IP MXF basic configuration, cabinet
with cutaway for built-in operating panel
Integral IP MXF Basic configuration, cabinet
with cutaway and log printer
Integral IP MXF basic configuration, cabinet
with cutaway, log printer and LED indicator
panel f. 32 detector zones
B5 MAP internal operating panel german
B5 MAP internal operating panel english
B5 MAP internal operating panel (other
languages)

B5-SCU

FG052100

B5-SCU-C

FG052101

B5-SCU-CP

FG052102

B5-SCU-CP-EAT32

FG052107

B5-CII-DE
B5-CII-EN

FG91600-9
FG91601-9

B5-CII-XX

upon request

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Modular control panels Integral IP MX Controller unit for multizone extinguishing systems Integral IP MXE

2.2

Controller unit for multizone extinguishing systems Integral IP MXE

Due to the special redundancy concept and the particular degree of safety that it provides for the widest range of
usages, the Integral IP MX system can able be used as an Integral IP MXE extinguishing system control panel
(electronic control and delay unit) or as a combined Integral IP MXF/MXE fire alarm and extinguishing system
panel. For this purpose, various types of cabinet are available, which contain an additional LED parallel indicator
panel. As a result of this enhancement in accordance with standards and directives EN 12094-1 and VdS 2496, the
Integral IP MXE is now suitable and approved for use for controlling and monitoring the following types of fire
extinguishing systems:
CO2 high and low pressure extinguishing systems where life is or is not endangered.
Inert gas and argon extinguishing systems where life is or is not endangered.
Water spray and mist water deluge systems
Sprinkler systems and pre-action sprinkler systems
Chemical extinguishing systems

No.: FG052103

No.: FG052105

B-HB-028EN

Integral IP MXE cabinet B5-SCU-CP4L


Integral IP MX cabinet in basic configuration, consisting of:
Sheet steel cabinet
B5-MCU main processor unit
B5-PSU power supply unit
Module rack with BUS circuit boards
Power clips and battery cable
Space for fitting batteries (max. size 2 x 12 V/45 Ah)
Doors with cutaway for built-in operating panel and log printer
LED indicator panel for 4 extinguishing zones
Input voltage / frequency:
230 VAC +15%/-20% 47-63 Hz
Input power:
max. 280 W
Output voltage:
26,3 VDC (+50C) to 28,3 VDC (0C)
Output current:
7,5 A
Quiescent current:
74 mA (without operating panel, without
log printer)
Batteries that can be used:
2 pcs. 12 V / 38...40 Ah in series
Emergency power supply:
72 h normal operation + 0.5 h alarm
Protection category:
IP 30 / IP 55 (acc. to DIN 40050)
Ambient temperature:
-5 to +50C
Rel. air humidity:
5 to 95%, without condensation
Air pressure:
80 kPa, up to 2000 m above sea level
Standard case:
sheet steel, red RAL 3000
Dimensions:
600 x 445 x 225 mm (HxWxD)
Weight of basic configuration: 15 kg (without batteries)
IP 55 Case:
1.5 mm sheet steel, red tipping frame
Front door:
Aluminium profile, 3 mm acrylic glass
Dimensions:
600 x 600 x 370 mm (HxWxD)
Weight:
ca. 35 kg (without batteries)
Weight per battery:
15 kg
VdS-Approval:
G204087
CPD-Approval:
0786-CPD-20240
Description

Type

Art. No.

Integral IP MXE in standard case


Integral IP MXE in IP 55 case
B5 MAP internal operating panel german
B5 MAP internal operating panel english
B5 MAP internal operating panel (other
languages)
Indicator panel for 4 extinguishing zones
(spare part)

B5-SCU-CP4L
B5-SCU-CP4L-IP55
B5-CII-DE
B5-CII-EN

FG052103
FG052105
FG91600-9
FG91601-9

B5-CII-XX
B3-MMI-IPES BFE

upon request
FG81620A9F

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

Modular control panels Integral IP MX Integral IP MX in Floor Standing Cabinets

2.3

Integral IP MX in Floor Standing Cabinets

For housing up to five Integral IP MX subcontrol units in a space-saving single case there are special control panel
components available that can be fitted into 19 inch floor standing cabinets.
This option is available for various different uses, such as for modernising of existing older systems, for
extinguishing controllers with several indicator panels or where space confinements do not permit any other
option.

20-1060030-01

20-1060030-02

10

Integral IP MX floor standing cabinet


Floor standing cabinet (40 height units) with a full-length glass door and a
tipping frame opening either from the right or the left.
Each floor standing cabinet contains all the cable channels and drilling holes
to be expanded to include up to five subcontrol units. The module rack is
fitted on to the back wall of the cabinet, and can as was always previously the
case be modularly fitted with the relevant modules depending on the
structure required. The tipping frame contains operating panels and blanking
plates on the front side and on the back side contains compartments for
storing the batteries. All floor standing cabinets are shipped completely
prewired, equipped and installed in accordance with the customers wishes.
The module racks are pre-wired as Integral LAN or subcontrol unit loops.
Maximum fitting:
5 module racks
8 front panels each 5 HUs high
1 printer
4 extinguishing zone indicators each for 8
extinguishing zones or
4 indicator panels each for 64 detectors
Protection category:
IP 54
Ambient temperature:
-5 to +50 C
Electrical Protection:
Klasse B
Dimensions:
2000 x 800 x 600 mm (HxWxD)
Base height:
200 mm
Case:
light grey, RAL 7035
Weight:
130 kg
VdS-Approval:
G298029, G204087
CPD-Approval:
0786-CPD-20240

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Modular control panels Integral IP MX Integral IP MX in Floor Standing Cabinets

Description

Type

Art. No.

Integral IP MX floor standing cabinet


Doors hinged on the right

B5-STS-RT1-R

20-1060030-01

Integral IP MX floor standing cabinet


Doors hinged on the left

B5-STS-RT1-L

20-1060030-02

MAP operating panel with 19" front panel german


MAP operating panel with 19" front panel english

B5-STS-CIP-DE-2
B5-STS-CIP-EN-2

20-1060009-01
20-1060009-02

High-End operating panel with 19" front panel


(languages other than German available upon
request)

B5-STS-HCIP-2

20-1060010-01

19" front panel with cutaway for installation of


Integral MAP operating panels in other languages

B5-STS-BF-2

20-1060000-01

MAP operating panel (different language versions)


for fitting in a 19" floor standing cabinet

B5-MMI-CII-xx

upon request

19" front panel with log printer for


connecting to Integral MAP operating panels

B5-STS-PR-2

20-1060001-01

19" front panel with log printer for


connecting to Integral High-End operating panels

B5-STS-PR-HE-2

20-1060002-01

19 Frontplatte mit LED-Anzeigefeld EAT64


for 64 detector zones

B5-STS-EAT64-2

20-1060011-01

19 front panel with LED indicator panel IPEL


for 8 extinguishing zones

B5-STS-IPEL-2

20-1060012-01

19 blanking plate (5 height units)

B5-STS-BFP-2

20-1060003-01

19 blanking plate (1 height unit)

B5-STS-BFP2-2

20-1060008-01

B5-module rack Integral IP MX


incl. B5-PSU. B5-BUS, B5-MCU, battery shelf

B5-STS-BGT

20-1060006-01

Battery shelf for additional batteries

B5-STS-AF

20-1060007-01

B5-STS-MMI-SUB

20-1060040-01

B5-STS-MMI

20-1060041-01

B5-STS-SCU

20-1060042-01

B5-STS-CAT5

20-1060043-01

B5-STS-SECONET
B5-STS-KL

20-1060044-01
20-1060045-01

MMI-BUS cable with connector for connecting the


BAF/PSU with the 1st MMI BUS device
MMI-BUS cable with connector for connection
between MMI-BUS devices
Networking cable with connector for B3-LPI or B3USI4 for SCU connection in floor standing cabinet
Cat5 cable with connector for B5-NETx for
SCU connection in floor standing cabinet
Networking cable for SecoNET connections
Terminal block for supply voltage
B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

11

Modular control panels Integral IP MX Integral IP MX Modules

2.4

Integral IP MX Modules

All modules and components of the Integral IP MX system are constructed redundantly for system availability
reasons, which also guarantees in the event of a fault that indication information, signal processing and the
controlling of all connected fire alarm devices is ensured.
The module rack is attached to the back panel of every entry level Integral IP MX as contains, as standard, the
B5-MCU main processor unit and the B5-PSU power supply unit. Eleven further push-in connection slots can be
fitted with additional flat modules as required. This modular structure also allows various line technologies (loop
and stub lines) to be connected to a single control unit.

Empty module rack with


BUS circuit boards

Module rack fitted with modules

Important information about the fitting modules in the module rack


The power supply and data communication between the individual modules is carried out using the bus circuit
boards, which are located on the back of the module rack using plug and socket connections.
Connection slot 1

exclusively for B5-MCU main processor module

Connection slot 2

if any of the networking modules B5-LAN, B5-NET2-485 or B5-NET4-485 are being


used, then they must be connected to connection slot 2, otherwise if this is not the
case then the connection slot can be used for any module (with the exception of B3RELx modules)
freely available for connection of all modules described hereafter (except B3-RELx)
must be fitted with a module of the type B5-BAF, B5-MRI16 or B3-LPI if relay
modules are intended to be fitted on connection slots 11 to 13, since only these
modules are suitable for controlling the relay bus
exclusively for B5-PSU power supply unit

Connection slots 3 to 8
Connection slot 9

Connection slot 10

Connection slots 11 to 13 only for B3-REL10/16/16E relay modules, which can only be fitted in these
connection slots

12

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Modular control panels Integral IP MX Integral IP MX Modules

No.: EG072912

No.: EG072908

B-HB-028EN

B5-DXI2 Module for X-LINE


For connecting two loop circuits (loops) to the relevant detectors and
Integral X-LINE technology modules. Alternatively one loop circuit and two
stub lines or four stub lines can be connected. Shipped including connector.
Power supply:
internally over B5 system bus
Current consumption:
ca. 35 mA typ.
Ambient temperature:
-5 to +50C
Elements:
2 loops, 250 devices each
Logical elements:
max. 750 per B5-DXI2
Short circuit isolator:
integrated into detectors and controller
modules
Individual detect. identification: integrated as standard
Cable:
1 x 2 x 0,8 mm shielded (standard)
Loop length:
max. 3500 m
Max. line resistance:
255
Description

Type

Art. No.

B5-DXI2 Module for X-LINE


16-pole connector plug (spare part)

B5-DXI2
ST-B3 16

EG072912
YY970138

B5-BAF Control Module


For connecting fire brigade control panels, transmission equipment (main
detectors), alarm systems (sirens) and for controlling the relay bus. The
module also controls an interface for the MMI-BUS (bus for external
devices) to which external operating panels and the Austrian fire brigade
operating panel among other devices are connected. Shipped including
connector.
Power supply:
internally over B5 system bus
Current consumption:
35 mA typ. with turned on
output driver without peripheral current
Ambient temperature:
-5 to +50C
Relay bus interface:
for B3-REL10 or B3-REL16(E)
Interface FBP (DIN14661):
12 pin connectable screw clip plug
Transmission type:
parallel, bidirectional
Range:
max. 5 m
OM1 interface:
Transmission equipment or
monitored output, 26 V/1,5 A
OM2 interface:
monitored output, 26 V/1,5 A
MMI-BUS interface:
galv. separated RS 485, max. 1200 m
Description

Type

Art. No.

B5-BAF Control Module


IDC connector MMI-BUS (spare part)
Solder lug connector MMI-BUS (spare part)
Connector plug for Fire brigade panel (spare
part)
Connector plug for monitored inputs/outputs
(spare part)

B5-BAF
ST-BAF-MMI-S
ST-BAF-MMI-L
ST-BAF-FBD

EG072908
FG74085
FG74086
YK130459

ST-BAF-OM

FG74088

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

13

Modular control panels Integral IP MX Integral IP MX Modules

No.: 20-1000002-01

No.: EG072855

14

B5-OM8 Module for monitored outputs


For controlling and monitoring 8 primary lines (flashing lights, sirens etc.) in
accordance with EN 54-13, each with a maximum current of 1.3 A.Shipped
including connector.
Power supply:
internally over B5 system bus
Current consumption:
28 mA (battery current without peripherals)
Ambient temperature:
-5 to +50C
Output voltage:
22 V min / 24 V typ. / 28 V max.
Output current:
1,3 A max., short circuit resistant
Short circuit current:
1,45 A min. / 1,75 A typ. / 2,76 A max.
Load range:
Controlling current
Line resistance
Range 1 (160-1k
1 mA
max. 50
Range 2 (57-375
3 mA
max. 20
Range 3 (20-75
15 mA
max. 5
Description

Type

Art. No.

B5-OM8 Module for monitored outputs


Stecker f. Ausgnge B3/B5-OM8 (Ersatz)

B5-OM8
ST-OM8

20-1000002-01
FG74095

B3-IM8 Module for monitored inputs


For connecting up to eight stub lines, which can either be configured as
detector zones (Hekatron 130 detector series or Hochiki Ex-i detectors) or
as monitored inputs (e.g. VdS extinguishing interface, primary inputs, valve
monitoring etc.). The operating mode of the individual stub lines can be set
independently of one another using programming and jumper cap settings
on the module. Shipped including connector.
Power supply:
internally over B5 system bus
Current consumption:
9 mA (battery current without peripherals)
Ambient temperature:
-5 to +50C
Connection:
8 detector zones or
8 monitored inputs
Description

Type

Art. No.

B3-IM8 Module for monitored inputs


Connector plug for B3-IM8 (spare part)
Jumper 953R f. B3-IM8 (8 pcs.)
Jumper 110R f. B3-IM8 (8 pcs.)

B3-IM8
ST-MTI8
JUMP-IM8-953R
JUMP-IM8-110R

EG072855
FG74087
FG74113
FG74114

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Modular control panels Integral IP MX Integral IP MX Modules

No.: EG072815

No.: EG072903

B-HB-028EN

B3-USI4 Universal Interface Module


For connecting Integral subcontrol units to management systems, for
controlling external printers, pagers, ComBOX, telephony servers etc. and
for interconnection of several Integral subcontrol units (in loop form, serially
using 2 redundant cables). A total of 4 redundant, serial, asynchronous
interfaces can be used as redundant RS 485 connections in half-duplex mode
(for loops) or as non-redundant RS 422 connections in full-duplex mode (for
lines). Furthermore, two of the four interfaces can also be operated as RS
232 in full-duplex operation (line) each with 2 control circuits. The selection
of each interfaces operating mode is done by programming and hardware
configuration, with it also being possible to select between a connection
being made to a subcontrol unit loop and/or a redundant/non-redundant
connection to control systems etc. A maximum of five B3-USI4 units can be
fitted per subcontrol unit. Shipped including connector.
Power supply:
internally over B5 system bus
Current consumption:
20 mA
Ambient temperature:
-5 to +50C
Range:
RS 485 = 1200 m
RS 232 = 15 m
Transmission type:
serial, asynchronous
Baud rate:
57,6 kBaud
Interfaces:
2x2 redundant half-duplex RS 485, also
full-duplex operation, galvanically isolated
2 redundant RS232 interfaces,
galvanically isolated
Description

Type

Art. No.

B3-USI4 Universal interface module


9 pole solder lug terminal connector for B3-USI4
(spare part)
15 pole solder lug connector for B3-USI4
(spare part)

B3-USI4
ST-LPI/USI4/HFI

EG072815
FG74097

ST-USI4

FG74098

B5-LAN Network module


For non-redundant networking of Integral IP MX control panels and for
non-redundant connection of PC applications. Two 8 pole RJ-45 sockets can
be found on the front side of the module. The module can only be fitted in
connection slot 2 in the module rack.
Power supply:
internally over B5 system bus
Current consumption:
0 mA
Ambient temperature:
-5 to +50C
Transmission type:
TCP/IP
Physical characteristics:
2 x RJ-45 sockets - 8 pole
Direction:
bidirectional, full-duplex
LAN-interface:
Ethernet 100 Base TX
Speed:
max. 100 Mbit/s
Distance:
max. 100 m
Description

Type

Art. No.

B5-LAN Network module


RJ45-connector Cat5e
Crimping tool RJ45

B5-LAN
RJ45-IP
CRIMP-IP

EG072903
MM010008
MM010001

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

15

Modular control panels Integral IP MX Integral IP MX Modules

No.: EG072910

No.: EG072915

16

B5-NET2-485 Network Module


For redundant networking of Integral IP MX control panels or for
redundant connection of PC applications. The module consists of two
network connectors (RS 485 interface) and two 100 Base TX interfaces. On
the front side there are 6 RJ 45 sockets for connecting from the subcontrol
unit network and to the Ethernet. The module can only be fitted in
connection slot 2 in the module rack.
Power supply:
internally over B5 system bus
Current consumption:
120 mA
Ambient temperature:
-5 to +50C
Transmission type:
TCP/IP
Physical characteristics:
6 x RJ-45 sockets - 8 pole
Direction:
bidirectional, full-duplex
LAN-interfaces:
2 x Ethernet 100 Base TX
Speed:
max. 100 Mbit/s
Distance:
max. 100 m
RS485-interfaces:
2 x RS485 with redundant cabling,
of which 1 galvanically isolated
Speed:
max. 1,25 Mbit/s
Distance:
max. 1200 m
Cable:
UTP Cat5
Description

Type

Art. No.

B5-NET2-485 Network Module


RJ45-connector Cat5e
Crimping tool RJ45
9-Sub-D RJ45 coupling
15Sub-D RJ45 coupling

B5-NET2-485
RJ45-IP
CRIMP-IP
KUP 9RJ45
KUP 15RJ45

EG072910
MM010008
MM010001
20-1400000-01
20-1400001-01

B5-NET4-485 Network Module


For redundant networking of Integral IP MX control panels or for
redundant connection of PC applications. The module consists of four
network connectors (RS 485 interface) and two 100 Base TX interfaces. On
the front side there are 10 RJ45 sockets for connecting from the subcontrol
unit network and to the Ethernet. The module can only be fitted in
connection slot 2 in the module rack.
Power supply:
internally over B5 system bus
Current consumption:
127 mA
Ambient temperature:
-5 to +50C
Transmission type:
TCP/IP
Physical characteristics:
10 x RJ-45 sockets - 8 pole
Direction:
bidirectional, full-duplex
LAN-interfaces:
2 x Ethernet 100 Base TX
Speed:
max. 100 Mbit/s
Distance:
max. 100 m
RS485-interfaces:
4 x RS485 with redundant cabling,
of which 2 galvanically isolated
Speed:
max. 1,25 Mbit/s
Distance:
max. 1200 m
Cable:
UTP Cat5
Description

Type

Art. No.

B5-NET4-485 Network Module


RJ45-connector Cat5e
Crimping tool RJ45
9Sub-D RJ45 coupling
15Sub-D RJ45 coupling

B5-NET4-485
RJ45-IP
CRIMP-IP
KUP 9RJ45
KUP 15RJ45

EG072915
MM010008
MM010001
20-1400000-01
20-1400001-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Modular control panels Integral IP MX Integral IP MX Modules

No.: 20-1000000-01

No.: 20-1000001-01

B5-NET2-FXM/FXS Network Modules


For redundant networking of Integral IP MX control panels or for
redundant connection of PC applications. The modules contain two RS 485
network connections, two optical network connections (Multimode version
FXM with a range of 2 km or Singlemode FXS with a range of up to 10 km)
and two 100 Base TX interfaces. The modules can only be fitted in
connection slot 2 in the module rack.
Power supply:
internally over B5 system bus
Current consumption:
FXM: 205 mA
FXS: 179,5 mA
Ambient temperature:
-5 to +50C
Physical characteristics:
RJ-45 socket - 8 pole
LAN-interfaces:
Transmission type:
Direction:
Speed:
Distance:

2 x Ethernet 100 Base TX


TCP/IP
bidirectional, full duplex operation
max. 100 Mbit/s
max. 100 m

FX-interfaces (optic fibre):


Transmission type:
Direction:
Speed:
Distance:

2 x Ethernet 100 Base FX


TCP/IP
bidirectional, full duplex operation
max. 100 Mbit/s
FXM: max. 2.000m
FXS: max. 10.000m
FXM: 62,5/125 m or 50/125 m
FXS: 9/125 m
FXM: MTRJ
FXS: LC 2x5

Optic fibre type:


Connector type:
RS485-interfaces:
Transmission type:
Direction:
Speed:
Distance:
Cable:

B-HB-028EN

2 x RS485 with redundant cabling,


of which 1 galvanically isolated
Difference signal
bidirectional, half duplex operation
max. 1,25 Mbit/s
max. 1200 m
UTP Cat5

Description

Type

Art. No.

B5-NET2-FXS Network Module


B5-NET2-FXM Network Module
RJ45-connector Cat5e
Crimping tool RJ45
9-Sub-D RJ45 coupling
15Sub-D RJ45 coupling

B5-NET2-FXS
B5-NET2-FXM
RJ45-IP
CRIMP-IP
KUP 9RJ45
KUP 15RJ45

20-1000000-01
20-1000001-01
MM010008
MM010001
20-1400000-01
20-1400001-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

17

Modular control panels Integral IP MX Integral IP MX Modules

No.: EG072804

B3-REL10 Relay module


The module contains 10 bistable, freely programmable 230 V/3 A relay
contacts. Whether a contact is a make contact or a break contact is
ascertained by configuration using software. By programming a fail-safe
position the status of every individual relay can be defined in the event of a
supply voltage failure or the fire alarm control panel being switched off. A
module of type B5-BAF, B3-LPI or B5-MRI16 must be fitted to connection
slot 9 of the Integral module rack for controlling the relay. Module B3REL10 can only be fitted to connection slots 11 to 13 of the module rack.
Power supply:
internally over B5 system/relay bus
Ambient temperature:
-5 to +50C
Relay construction:
bistable
Contact resistance:
30 m
Maximum switching surge:
230 VAC / 125 VDC
Maximum switching current:
3A both poles routed to terminals
Caution:

No.: EG072807

Description

Type

Art. No.

B3-REL10 Relay module


2 pcs. connector plug (standard)
2 pcs. connector plug, can be connected front on

B3-REL10
ST-SET REL10 W
ST-SET REL10

EG072804
FG74103
FG74104

B3-REL16 Relay module


The module contains 16 bistable, freely programmable 24 V/3 A relay
contacts and is used for controlling sirens, holding magnets, relays etc.
Whether the contact is a make or break contact is determined by softwarebased programming. By programming a fail-safe position the status of every
individual relay can be defined in the event of a supply voltage failure or the
fire alarm control panel being switched off. A module of type B5-BAF, B3LPI or B5-MRI16 must be fitted to connection slot 9 of the Integral module
rack for controlling the relays. Module B3-REL16 can only be fitted to
connection slots 11 to 13 of the module rack.
Power supply:
internally over B5 system/relay bus
Ambient temperature:
-5 to +50C
Relay construction:
bistable
Contact resistance:
30 m
Maximum switching surge:
30 VAC/ 30 VDC
Maximum switching current:
3A both poles routed to terminals
Caution:

18

The connection plugs for the relay outputs are not shipped
with the module and must be ordered separately!

The connection plugs for the relay outputs are not shipped
with the module and must be ordered separately!

Description

Type

Art. No.

B3-REL16 Relay module


2 pcs. connector plug (standard)
2 pcs. connector plug, can be connected front on

B3-REL16
ST-SET REL16 W
ST-SET REL16

EG072807
FG74105
FG74106

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Modular control panels Integral IP MX Integral IP MX Modules

No.: EG072822

B3-REL16E Relay module


Identical to module B3-REL16 in terms of technical specifications and
function, but, however, also contains additional fused relay contacts (the
fuses are not monitored) and resistors (3.3k monitoring resistance and
680 working resistance) for use as a VdS extinguishing interface. Using
jumpers it is possible to choose between normal relay contacts and VdS
interfaces.
Contact protection:
3.15 A miniature fuse with slow
triggering characteristic
Caution:

No.: EG072956

Description

Type

Art. No.

B3-REL16E Relay module


2 pcs. connector plug (standard)
2 pcs. connector plug, can be connected front on

B3-REL16E
ST-SET REL16 W
ST-SET REL16

EG072822
FG74105
FG74106

B5-MRI16 Relay module


The module contains 16 bistable, freely programmable 24 V/3 A relay
contacts. Whether a contact is a make contact or a break contact is
ascertained by configuration using software. By programming a fail-safe
position the status of every individual relay can be defined in the event of a
supply voltage failure or the fire alarm control panel being switched off. The
B5-MRI16 can be fitted in any of connection slots 2-9 of the Integral
module rack and also contains an interface for controlling the relay bus. By
fitting the module to connection slot 9, relay modules of type B3-REL10,
B3-REL16 and B3-REL16E can also be controlled.
Power supply:
internally over B5 system bus
Current consumption:
6 mA typ. (battery current)
Ambient temperature:
-5 to +50C
Relay construction:
bistable
Contact resistance:
30 m
Maximum switching surge:
30 VAC / 30 VDC
Maximum switching current:
3A both poles routed to terminals
Caution:

B-HB-028EN

The connection plugs for the relay outputs are not shipped
with the module and must be ordered separately!

The connection plugs for the relay outputs are not shipped
with the module and must be ordered separately!

Description

Type

Art. No.

B5-MRI16 Relay module


2 pcs. connector plug (standard)
2 pcs. connector plug, can be connected front on

B5-MRI16
ST-SET REL16 W
ST-SET REL16

EG072956
FG74105
FG74106

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

19

Modular control panels Integral IP MX Integral IP MX Modules

Modernisation modules

No.: EG072809

No.: EG072853

No.: EG072811

20

B3-MTI8 Module for Monologue Technology


For connection of up to eight stub lines, which can either be configured as
detector zones using Monologue Technology or as monitored inputs. For
reasons relating to approvals, this module may only be used for renovation
purposes. Shipped including connector.
Power supply:
internally over B5 system bus
Current consumption:
9 mA
Ambient temperature:
-5 to +50C
Detector zones:
8 (max. 62 detectors per zone)
Individual detector identification: integrated as standard
Cable diameter:
0,6 or 0,8 mm
Range:
max. 1000 m
B3-DTI2 Module for dialogue technology
For connection of 2 loop circuits (loops) or 4 stub lines to the relevant BMZ
Maxima dialogue technology detectors and modules. The module only
functions in conjunction with B3-MCU32E2 or B5-MCU main processor
units, and may only be deployed for renovation purposes according to
approvals. Shipped including connector.
Power supply:
internally over B5 system bus
Current consumption:
52 mA
Ambient temperature:
-5 to +50C
Devices/Elements:
2 loop circuits, each with max. 128 devices
Short circuit isolator:
integrated into detectors and controller
modules
Individual detector identification: integrated as standard
Cable diameter:
1 x 2 x 0,8 mm shielded (standard)
Loop length:
max. 1100 m
B3-DCI6 Module for DC Technology
For connecting up to 6 inputs, which can be set either as detector zones
using DC technology, as monitored inputs or as extinguisher inputs. Shipped
including connector.
Power supply:
internally over B5 system bus
Current consumption:
30 mA max. current limited
Connection:
6 detector zones (max. 30 detectors/zone)
Terminal resistor:
11,8 k
Alarm resistor:
560
Line resistor:
max. 71,5 per core
Ambient temperature:
-5 to +50C
Individual detector identification: possible
Range:
max. 2000 m
Cable diameter:
2-core: 0,6 or 0,8 mm
3-core: 0,8 mm
Description

Type

Art. No.

B3-MTI8 Module for Monologue Technology


Connector plug for B3-MTI8 (spare part)
B3-DTI2 Module for dialogue technology
Connector plug for B3-DTI2 (spare part)
B3-DCI6 Module for DC Technology
Connector plug for B3-DCI6 (spare part)

B3-MTI8
ST-MTI8
B3-DTI2
ST-B3 16
B3-DCI6
ST-DCI6

EG072809
FG74087
EG072853
YY970138
EG072811
FG74099

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Modular control panels Integral IP MX Accessories & replacement parts

2.5

Accessories & replacement parts

No.: 20-1400110-01

No.: 20-1400112-01

No.: 20-1400114-01

Integral MX empty cabinet B5-CAB


Empty cabinet in Integral IP MX design with full door for use as a cabinet
for batteries, as a storage unit etc.
Dimensions:
600 x 445 x 225 mm (HxWxD)
Case colour:
red RAL 3000
Weight:
ca. 10 kg
Description

Type

Art. No.

Integral MX empty cabinet

B5-CAB

20-1400110-01

Integral MX battery cabinet B5-CBE


Empty cabinet in Integral IP MX design with full door, with built-in battery
shelf for extending battery capacity.
Dimensions:
600 x 445 x 225 mm (HxWxD)
Case colour:
red RAL 3000
Weight:
ca. 12 kg
Description

Type

Art. No.

Integral MX battery cabinet

B5-CBE

20-1400112-01

Integral MX top hat rail cabinet B5-CTR


Cabinet in Integral IP MX design with full door, built-in top-hat rail and
cable conduits for use as a distributor case, for installation of modules etc.
Dimensions:
600 x 445 x 225 mm (HxWxD)
Case colour:
red RAL 3000
Weight:
ca. 11 kg
Description

Type

Art. No.

Integral MX top hat rail cabinet

B5-CTR

20-1400114-01

Description

Type

Art. No.

Battery 12 V / 40 Ah for emergency power supply


Battery 12 V / 38 Ah for emergency power supply
Battery 12 V / 44 Ah for emergency power supply
USB cable 3 m for Service PC
USB cable 4,5 m for Service PC
B5 battery holder set
B5 distance piece set
Battery current measuring cable
Front blanking panel for module rack
Log Printer Interface (electronic circuit board)
B5 log printer printer unit
Paper roll for log printer
Colour printer ribbon cassette for log printer
Printer cover
B5 battery cable set
B5 battery cable set long
Bayonet fuses for cable set
Lock for Integral MX/CX cabinets
Key for Integral MX/CX cabinets

AKKU 40
AKKU 38
AKKU 44
KAB USB 3
KAB USB 45
B5-BATH-SET
B5-DISTH-SET
KAB PSU
B5 BFP
B5-PIF
B5-PDR-DW
PD PPR
PD FRB
B5-PDR-CO
B5 BATKAB1
B5 BATKAB2
ZUB SICH8
SCU LOCK
SCU LOCK
KEY
B5-UGK
B5-RAIL 35
B5-CAT7-RJ45

HG691017-C
HG691017-D
HG691017-E
FG022051
FG022052
FG74108
FG74110
FG81720
FG06240
EG072906
FG030550
PPF-519057
HG694076
20-1400202-01
FG29910
FG29911
IS625040
FG29516
750000027

B3/B5 Upgrade Kit


Top-hat rail 35 mm wide
Connection unit Cat7 / RJ45

B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

20-1000100-01
20-1400003-01
20-1400004-01

21

Modular control panels Integral IP MX Accessories & replacement parts

No.: 20-1000100-01

No.: EG072939

No.: EG072918

22

B3/B5 Upgrade Kit


For upgrading existing Integral (B3) control panels to Integral IP MX (B5)
control panels. The upgrade kit consists of a module rack with built-in B5MCU main processor unit, B5-PSU power supply unit, bus circuit board and
relay circuit board.
Description

Type

Art. No.

B3/B5 Upgrade Kit

B5-UGK

20-1000100-01

B5-MCU main processor unit


The B5-MCU communicates with all other modules and with the operating
panel, manages configuration data and the system clock, and undertakes all
processes that are necessary for the logical behaviour of the system. The
module contains USB interfaces for loading software and configuration data
and for connecting memory sticks or dongles. In addition there are also a
connection slot for an SD card for saving customer texts and configuration
parameters. The B5-MCU is supplied with all Integral IP MX control panels,
but the SD card must be ordered separately.
Power supply:
via the system bus from B5-PSU
Quiescent current:
38 mA typ. (battery current)
Operating voltage:
Battery voltage VL+22 V .. 30 V
Logic voltage VCC+5,0 V 5%
Logic voltage VCC+3,3V 5%
Service interface:
USB 1.1 Device, connector Type B
USB 1.1 Host, connector Type A
Ambient temperature:
-5 to +50C
Rel. air humidity:
5 to 95 %, without condensation
Description

Type

Art. No.

B5-MCU main processor unit (spare part)


SD-CARD

B5-MCU
SD-CARD

EG072939
FG020325

B5-PSU power supply unit


The B5-PSU 7A power supply unit supplies the internally required voltages
in every Integral IP MX control unit of 3.3 V, 5 V and 27 V. In parallel
standby operating mode it feeds two 38...40 Ah batteries connected in series
for use as the emergency power supply, and furthermore, also has 5
separately fused 27 V outputs for external devices via connectable screw-type
terminals. The battery monitoring circuitry present on the module is
controlled and evaluated by the B5-MCU main processor unit. The B5-PSU
power supply unit is shipped as standard with all Integral IP MX control
panels.
Input voltage / frequency:
230 VAC +15%/-20% 47-63 Hz
Outputs for external devices:
5 x 27 V, 2,5 A FF
Current uptake:
max. 280 VA
Description

Type

Art. No.

B5-PSU power supply unit (spare part)


Replacement fuse
Connection plug for external devices

B5-PSU
ZUB SICH 2.5FF
ST-PSU EV

EG072918
IS625228
FG74090

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Modular control panels Integral IP MX Accessories & replacement parts

Connectors for Integral IP MX modules


The necessary connector plugs are supplied with the modules, with the items
listed below intended for ordering as replacements.
Exception: Connector plugs must always be ordered separately for relay
modules B3-REL10, B3-REL16, B3-REL16E and B5-MRI16!
Description

Connector for B5-DXI2


16 pole connector for detector zones/inputs
Connector for B3-DCI6
18 pole connector for detector zones
Connector for B3-DTI2
16 pole connector for detector zones
Connector for B3-MTI8
16 pole connector for detector zones
Connector for B3-OM8
16 pole connector for monitored outputs
Connectors for B3-REL10
2 connectors f. relays can be connected sideways
2 connectors f. relays can be connected front on
Connectors for B3-REL16(E)
2 connectors f. relays can be connected sideways
2 connectors f. relays can be connected front on
Connectors for B3-USI4
9 pole connector for interfaces
15 pole connector for interfaces
Connectors for B5-BAF
6 pole connector for monitored outputs
13 pole connector f. FBP acc. to DIN 14661
9 pole solder lug connector for MMI-BUS
9 pole IDC connector for MMI-BUS
Connectors for B5-MRI16
2 connectors f. relays can be connected sideways
2 connectors f. relays can be connected front on
Connectors for B5-PSU
10 pole connector for external devices
Connectors for B5-LAN & B5-NETx485
RJ45 connector Cat5e
RJ45 crimping tool
9-Sub-D RJ45 coupling
15Sub-D RJ45 coupling

B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

Type

Art. No.

ST-B3 16

YY970138

ST-DCI6

FG74099

ST-B3 16

YY970138

ST-MTI8

FG74087

ST-OM8

FG74095

ST-SET REL10W
ST-SET REL10

FG74103
FG74104

ST-SET REL16W
ST-SET REL16

FG74105
FG74106

ST-LPI/USI4/HFI
ST-USI4

FG74097
FG74098

ST-BAF-OM
ST-FBF
ST-BAF-MMI-L
ST-BAF-MMI-S

FG74088
YK130459
FG74086
FG74085

ST-SET REL16W
ST-SET REL16

FG74105
FG74106

ST-PSU EV

FG74090

RJ45-IP
CRIMP-IP
KUP 9RJ45
KUP 15RJ45

MM010008
MM010001
20-1400000-01
20-1400001-01

23

Modular control panels Integral IP MX Software for Integral IP control panels

2.6

Software for Integral IP control panels


Integral IP Software V 7.x
For configuration and programming the entire Integral IP system family.
The software only functions using a dongle and can be downloaded free of
charge from our website.
Operating system:
Windows 2000/ XP/VISTA
Windows 7 32-Bit
Hardware requirements:
CPU Pentium 1 GHz, minimum 1 GB
RAM (2 GB recommended)
300 MB free hard drive space
VGA graphics card 1280x1024 pixels
2 free USB ports
Internet connection for unlocking the
dongle
Description

Type

Art. No.

Dongle for Integral Software

DONGLE USB

upon request

Integral VirtualMAP
For remote access to the Integral IP fire alarm system over TCP/IP from a
PC with Windows operating system.
The control panel's operating panel is displayed on screen, with message and
command mode operation possible. A multi-layer security concept ensures
that non-authorised system access is blocked. Technical data and system
requirements are available upon request.
Description

Type

Art. No.

Dongle for Integral VirtualMAP

DONGLE IVM

20-1300200-01

Protocol converter BACnet - Integral ISP IP


Software for connecting Schrack Seconet fire detection and fire alarm
systems to a superordinated management system using BACnet protocol.
Details, hardware and software requirements available upon request.
Protocol converter OPC - Integral ISP IP
Software for connecting Schrack Seconet fire detection and fire alarm
systems to a superordinated management system using OPC protocol.
Details, hardware and software requirements available upon request.
Protocol converter Modbus - Integral ISP IP
Software for connecting Schrack Seconet fire detection and fire alarm
systems to a superordinated management system using Modbus protocol.
Details, hardware and software requirements available upon request.

24

Description

Type

Art. No.

Protocol converter BACnet - Integral ISP IP


Protocol converter OPC - Integral ISP IP
Protocol converter Modbus - Integral ISP IP

ISP IP BACNET
ISP IP OPC
ISP IP MODBUS

upon request
upon request
upon request

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Compact control panels Integral IP CX Fire alarm control panel Integral IP CXF

3 Compact control panels Integral IP CX


3.1

Fire alarm control panel Integral IP CXF

The compact fire alarm control panel Integral IP CXF is suitable to connect a maximum of 500 elements on two
loop circuits in its basic version. Additionally it contains an interface, to which either a LAN networking module,
two further loop circuits, an universal interface module or an input/output module can be fitted.

Important Features

Microprocessor-controlled and monitored system topology


Software redundancy pursuant to TRVB S 123, annex 6/1, Point 2.2. (from SW V 6.1)
Constant automatic test routines for all system components and programs
Six line display for displaying the system status in plain text (alarms, faults etc.)
Acoustic and optical alarm notification for alarms and faults
Alarm buffering
Possibility to manually test the control panel and its functions
Plain text indication of individual detector and indicator zones
Up to 8 external operating panels per control panel, maximum distance 1200 m
Operating panel language (labelling and display indication) can be selected, can be constantly toggled
between up to 4 languages.
External device bus for up to 15 indication and operation devices.
Serial data log printer with UPS power supply, with an event memory and message filter.
Suitable for connection to the fire brigades public alarm notification system
System configuration saved using flexible flash memory technology
Emergency power supply for a supply interruption period of 72 hours

Options

Control panel networking using a TCP/IP-based local mesh network:


up to 16 control panels can be networked to form a logical unit without requiring a superordinated
management system
Mesh network with up to 3 connections per subcontrol unit: in the event of a device failing or a
connection fault occurring, it is possible for data communications to continue by diverting (routing)
the data.
Data transmission at 625/2500 Kbit
Flexible topology: stub connection to loop is possible
Ethernet protocol: Using the customer's IT infrastructure
Access to the control unit over the Intranet and Internet
Standardised IT components are used
Serial data interfaces for connection to fire alarm management systems, external log printers etc.
Connection for fire brigade control panels pursuant to NORM F3031, DIN 14661, SN 054002 and
DIN 14662
Daytime/Night time operation mode switching can be individually programmed for each detector zone
and every week day
Intervention mode
Detectors can be freely assigned and linked to controller criteria by software
Software-controlled two zone dependency or two detector dependency for alarm notification and
controlling of devices.
Recognition and evaluation of the status of detectors (contamination)
Disablement of individual detectors
Can be networked with all Schrack fire alarm control panels

B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

25

Compact control panels Integral IP CX Fire alarm control panel Integral IP CXF

Approvals

VdS Device and System Approval: G200081, S200081, G206045, G206055, S206055
CPD-Approval No. 0786-CPD-20239 (VdS)
Austrian Testing Centre for Fire Prevention Technology: No. FT 14/159/10, FT 14/622/10
VB Cert Austria: 002/BM-PSys/014, 002/BM-PSys/015, 002/BM-PSys/016
Country-specific approvals in Austria, Germany, Denmark, Italy, Croatia, Netherlands, Poland, Romania,
Russia, Sweden, Switzerland, Slovakia, Czech Republic, Turkey, Hungary, Ukraine and many more.

No.: FG052600

No.: FG052601

No.: FG052602

26

Integral IP CXF cabinet variants


All variants of Integral IP CXF units contain the following basic structure:
Sheet steel cabinet
B6-BCU-X2 main processor unit
B6-PSU power supply unit
Power clips and battery cable
Connections for two loops
2 monitored outputs for transmission equipment and alarm systems
Connector plug for two monitored inputs
five relay outputs (24 V/3 A)
Connection for fire brigade control panel in accordance with DIN 14661
Connection for external operating panels and fire brigade indicator panel
(FAT) in accordance with DIN 14662
Interface for either B6-LAN, B4-USI or B4-DAI2 or B6-EIO
Maximum battery size 2 x 12 V/18 Ah
Input voltage / frequency:
230 VAC, +15% -20% / 47-63 Hz
Input power:
160 W
Output voltage:
26,3 VDC (50C) to 28,3 VDC (0C)
Output current:
4A
Batteries that can be used:
2 pcs. 12 V / 15...18 Ah in series
Emergency power supply:
72 h normal operation + 0.5 h alarm
Ambient temperature:
-5 to +50C
Case:
sheet steel, red RAL 3000
Rel. air humidity:
5 to 95%, without condensation
Air pressure:
80 kPa, up to 2000 m above sea level
Protection category:
IP 30 (acc. to DIN 40050)
Dimensions:
400 x 445 x 140 mm (HxWxD)
Weight:
19 kg incl. batteries
VdS-Approval:
G200081
CPD-Approval:
0786-CPD-20239
Description

Type

Art. No.

Integral IP CXF basic configuration


cabinet with full door
Integral IP CXF basic configuration
with cutaway for built-in operating panel
Integral IP CXF basic configuration
with cutaway and log printer
B6 MAP internal operating panel german
B6 MAP internal operating panel english
B6 MAP internal operating panel (other
languages)

B6-X2

FG052600

B6-X2-C

FG052601

B6-X2-CP

FG052602

B6-CII-DE
B6-CII-EN

FG91300-9
FG91301-9

B6-CII-XX

upon request

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Compact control panels Integral IP CX Integral IP CXF Modules

3.2

Integral IP CXF Modules

No.: 20-1100002-01

No.: 20-1100003-01

B-HB-028EN

B6-LXI extension module


For extending Integral IP CXF control panels by 2 additional X-LINE loop
circuits. Alternatively, up to four stub lines can be controlled. In addition
the module also has a standard Ethernet connection for network connection
or PC applications. The module can be connected onto the B6-BCU-X2
main processor unit, with the connector plug for peripherals being supplied.
Power supply:
internally over B6-BCU-X2
Current consumption:
ca. 31 mA typ.
Ambient temperature:
-5 to +50C
Elements:
2 X-LINE loops, max. 250 elements each
Short circuit isolator:
integrated into detectors and controller
modules
Individual detector identification: integrated as standard
Loop length:
max. 3.500 m
Dimensions:
143 x 94 x 18 mm
Description

Type

Art. No.

B6-LXI Extension Module


Connector plug for loops

B6-LXI
ST-LOOP/DAI

20-1100002-01
YK130295

B6-EIO input/output module


For connection of up to 10 stub lines each with a maximum of 30 detectors
from the 130 A detector series, primary inputs or VdS sprinkler interfaces
and eight monitored outputs each with an output current of max. 1.3 A.
Furthermore it is suitable for connection from intrinsically safe detectors for
use in hazardous areas of the MSD/UTD 523 and MCP 525 detector series
(or SSD/UTD 521) over a safety barrier. The module is connected onto the
B6-BCU-X2 main processor unit. Shipped including connectors.
Power supply:
internally over B6-BCU-X2
Battery current:
13,5 mA with activated output driver
without peripheral current
Ambient temperature:
-5 to +50C
Number of inputs:
max. 10
Number of outputs:
max. 8
Line length:
max. 1000 m
Dimensions:
143 x 94 x 18 mm
Description

Type

Art. No.

B6-EIO input/output module


B6-EIO Replacement connector set

B6-EIO
ST-SET-EIO

20-1100003-01
FG74109

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

27

Compact control panels Integral IP CX Integral IP CXF Modules

No.: EG072940

No.: EG072934

28

B6-LAN network module


For non-redundant networking of Integral IP CXF control panels for nonredundant connection of PC applications. The module is connected to the
B6-BCU-X2 main processor unit.
Power supply:
internally over B6-BCU-X2
Current consumption:
0 mA
Ambient temperature:
-5 to +50C
Transmission type:
TCP/IP
Physical characteristics:
1 x RJ45 connector plug
Direction:
bidirectional, full-duplex
LAN-interface:
Ethernet 100 Base TX
Speed:
max. 100 Mbit/s
Distance:
max. 100 m
Description

Type

Art. No.

B6-LAN Network module


RJ45 connector Cat5e
RJ45 crimping tool
9-Sub-D RJ45 coupling
15Sub-D RJ45 coupling

B6-LAN
RJ45-IP
CRIMP-IP
KUP 9RJ45
KUP 15RJ45

EG072940
MM010008
MM010001
20-1400000-01
20-1400001-01

B6-NET2-485 network module


For redundant networking of Integral IP CXF control panels or for
redundant connection of PC applications. The module consists of 2 network
connectors (RS 485 interface) and one 100 Base TX interfaces. The module
is connected to the B6-BCU-X2 main processor unit.
Power supply:
internally over B6-BCU-X2
Current consumption:
53 mA
Ambient temperature:
-5 to +50C
Transmission type:
TCP/IP
Physical characteristics:
RJ-45 connector plug
Direction:
bidirectional, full-duplex
LAN-interface:
Ethernet 100 Base TX
Speed:
max. 100 Mbit/s
Distance:
max. 100 m
RS485-interfaces:
2 x RS485 with line redundancy,
of which 1 galvanically isolated
Speed:
max. 2,5 Mbit/s
Distance:
max. 1200 m
Cable:
UTP Cat5
Description

Type

Art. No.

B6-NET2-485 network module


RJ45 connector Cat5e
RJ45 crimping tool
9-Sub-D RJ45 coupling
15-Sub-D RJ45 coupling

B6-NET2-485
RJ45-IP
CRIMP-IP
KUP 9RJ45
KUP 15RJ45

EG072934
MM010008
MM010001
20-1400000-01
20-1400001-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Compact control panels Integral IP CX Integral IP CXF Modules

No.: 20-1100000-01

No.: 20-1100001-01

B6-NET2-FXM/FXS network modules


For redundant networking of Integral IP CX control panels or for redundant
connection of PC applications. The modules contains a RS 485 network
connection, two optical network connections (Multimode version FXM with
a range of 2 km or Singlemode FXS with a range of up to 10 km) and a
100 Base TX interface. The module is connected onto the B6-BCU-X2 main
processor unit.
Power supply:
internally over B6-BCU-X2
Current consumption:
FXM 122 mA
FXS 99 mA
Ambient temperature:
-5 to +50C
Physical characteristics:
RJ-45 socket - 8 pole
LAN-interface:
Transmission type:
Direction:
Speed:
Distance:

Ethernet 100 Base TX


TCP/IP
bidirectional, full duplex operation
max. 100 Mbit/s
max. 100m

FX-interfaces (optic fibre):


Transmission type:
Direction:
Speed:
Distance:

Ethernet 100 Base FX


TCP/IP
bidirectional, full duplex operation
max. 100 Mbit/s
FXM: max. 2.000m
FXS: max. 10.000m
FXM: 62,5/125 m oder 50/125 m
FXS: 9/125 m
FXM: MTRJ
FXS: LC 2x5
RS 485 galvanic isolation
Difference signal
bidirectional, half duplex operation
max. 1,25 Mbit/s
max. 1200 m

Optic fibre type:


Connector type:
RS485-interface:
Transmission type:
Direction:
Speed:
Distance:

B-HB-028EN

Description

Type

Art. No.

B6-NET2-FXS network module


B6-NET2-FXM network module
RJ45 connector Cat5e
RJ45 crimping tool
9-Sub-D RJ45 coupling
15-Sub-D RJ45 coupling

B6-NET2-FXS
B6-NET2-FXM
RJ45-IP
CRIMP-IP
KUP 9RJ45
KUP 15RJ45

20-1100000-01
20-1100001-01
MM010008
MM010001
20-1400000-01
20-1400001-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

29

Compact control panels Integral IP CX Integral IP CXF Modules

No.: EG072834

30

B4-USI universal interface module


For connecting Integral IP CXF control units to Integral networks, to
management systems, for controlling external printers, pagers, ComBOX,
telephone servers etc. The module contains two serial asynchronous
interfaces and is connected on to the B6-BCU-X2 main processor unit. All
required connector plugs are supplied.
Power supply:
internally over B6-BCU-X2
Current consumption:
21 mA
Ambient temperature:
-5 to +50C
Range:
RS 485 to 1200 m
RS 232 to 15 m
Interfaces:
1 galvanically isolated redundant RS 485
1 galvanically isolated RS 232/RS 485
Dimensions:
143 x 102 x 12 mm
Description

Type

Art. No.

B4-USI universal interface module


9 pole solder lug connector (spare part)
15 pole solder lug connector (spare part)

B4-USI
ST-LPI/USI4/HFI
ST-USI4

EG072834
FG74097
FG74098

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Compact control panels Integral IP CX Controller unit for single zone extinguishing systems Integral IP CXE

3.3

Controller unit for single zone extinguishing systems Integral IP CXE

The Integral IP CX system can also be deployed as an Integral IP CXE extinguishing system control panel
(electronic control and delay unit) or as a combined Integral IP CXF/CXE fire detector/extinguishing system
control panel. There are separate versions of the case available for this purpose, which contain an additional LED
parallel indicator tableau for a single extinguishing zone and also additional freely programmable inputs and
outputs. In this version, the Integral IP CXE conforms to the terms of the standards and directives EN 12094-1
and VdS 2496, and is also suitable and approved for controlling a single extinguishing zone and for monitoring the
following fire extinguishing systems:
CO2 high and low pressure extinguishing systems where life is or is not endangered.
Inert gas and argon extinguishing systems where life is or is not endangered.
Water spray and mist water deluge systems
Sprinkler systems and pre-action sprinkler systems
Chemical extinguishing systems

No.: 20-1112000-03

No.: 20-1112000-02

B-HB-028EN

Single zones extinguishing panel Integral IP CXE


variants of Integral IP CXE units contain the following basic configuration:
Sheet steel cabinet with cutaway for operating panel
built-in log printer (as an option)
B6-EIO input/output module
LED indicator panel for indications from an extinguishing zone
B6-BCU-X2 main processor unit
B6-PSU power supply unit
Power clips and battery cable
Connection for two loop circuits (max. 500 elements)
2 monitored outputs for transmission equipment and alarm systems
Connector plug for two monitored inputs
five relay outputs (24 V/3 A)
Connection for fire brigade control panel in accordance with DIN 14661
Connection for external operating panels and fire brigade panel FAT
Maximum battery size 2 x 12 V/18 Ah
Input voltage / frequency:
230 VAC, +15% -20% / 47-63 Hz
Input power:
160 W
Output voltage:
26,3 VDC (50C) to 28,3 VDC (0C)
Output current:
4A
Batteries that can be used:
2 pcs. 12 V / 15...18 Ah in series
Emergency power supply:
72 h normal operation + 0.5 h alarm
Ambient temperature:
-5 to +50C
Case:
sheet steel, red RAL 3000
Rel. air humidity:
5 to 95%, without condensation
Air pressure:
80 kPa, up to 2000 m above sea level
Protection category:
IP 30 (acc. to DIN 40050)
Dimensions:
400 x 445 x 140 mm (HxWxD)
Weight:
19 kg incl. batteries
VdS-Approval:
G206045
CPD-Approval:
0786-CPD-20239
Description

Type

Art. No.

Integral IP CXE cabinet with cutaway for built-in


operating panel, log printer and LED indicator
panel for a single extinguishing zone
Integral IP CXE cabinet with cutaway for built-in
operating panel and LED indicator panel for a
single extinguishing zone
B6 MAP internal operating panel german
B6 MAP internal operating panel english
B6 MAP internal operating panel (other languages)

B6-X2-CP1L

20-1112000-03

B6-X2-C1L

20-1112000-02

B6-CII-DE
B6-CII-EN
B6-CII-XX

FG91300-9
FG91301-9
upon request

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

31

Compact control panels Integral IP CX Accessories & replacement parts

3.4

Accessories & replacement parts


B4/B6 Upgrade Kit 2-Loop

No.: 20-1100100-01

No.: 20-1400111-01

No.: 20-1400113-01

No.: 20-1400115-01

32

For upgrading existing Integral C (B4) control panels to Integral IP CX (B6)


two loop control panels. The following components are contained in the
upgrade kit:
B6-BCU-X2 main processor unit
B6-PSU power supply unit
BCU cover
Distance bolts
Type plate
Description

Type

Art. No.

B4/B6 Upgrade Kit 2-Loop

B6-UGK-X2

20-1100100-01

Integral CX empty cabinet B6-CAB


Empty cabinet in Integral IP CX design with full door for use as a cabinet
for batteries, as a storage unit etc.
Dimensions:
400 x 445 x 140 mm (HxWxD)
Case colour:
red RAL 3000
Weight:
ca. 6 kg
Description

Type

Art. No.

Integral CX empty cabinet

B6-CAB

20-1400111-01

Integral CX battery cabinet B6-CBE


Empty cabinet in Integral IP CX design with full door, with built-in battery
holder for extending battery capacity.
Dimensions:
400 x 445 x 140 mm (HxWxD)
Case colour:
red RAL 3000
Weight:
ca. 8 kg
Description

Type

Art. No.

Integral CX battery cabinet

B6-CBE

20-1400113-01

Integral CX top hat rail cabinet B6-CTR


Cabinet in Integral IP CX design with full door, built-in top-hat rail and
cable conduits for use as a distributor case, for installation of modules etc.
Dimensions:
400 x 445 x 140 mm (HxWxD)
Case colour:
red RAL 3000
Weight:
ca. 7 kg
Description

Type

Art. No.

Integral CX top hat rail cabinet

B6- CTR

20-1400115-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Compact control panels Integral IP CX Accessories & replacement parts

No.: EG072938

No.: EG072950

B-HB-028EN

B6-BCU X2 main processor unit


The B6-BCU-X2 is a component of every Integral IP CXF and CXE and
contains all the interfaces required for the connection of peripheral devices,
relay contacts, the MMI Bus, monitored outputs and the service PC, as well
as a connection slot in which an additional module (B4-DAI2, B4-USI or
B6-EIO) can be fitted. Power is supplied by the B6-PSU power supply unit,
with the built-in operating panel being connected by a 34 pole ribbon cable
connector. All required connector plugs are supplied, the SD card must be
ordered separately.
Power supply:
via power supply unit B6-PSU
Operating voltage:
Battery voltage VL+22 V .. 30 V
Logic voltage VCC+5.0 V 5%
Logic voltage VCC+3.3V 5%
Power consumption:
Battery current (idle) typically 48 mA
Ambient temperature:
-5 to +50C
Rel. air humidity:
5 to 95 %, without condensation
Description

Type

Art. No.

B6-BCU X2 main processor unit


SD-Card

B6-BCU-X2
SD-CARD

EG072938
FG020325

B6-PSU power supply unit


The internal 4A power supply in every Integral IP CX control unit supplies
the required output voltages of 3.3V, 5V and 27V. It is always fitted in the
case of every Integral IP CX on the right hand side next to the main
processor unit and is always connected to it using a 64 pin multipoint
connector. On the bottom side of the power supply unit there is a 2 pole clip
for connection to the rechargeable batteries and a 10 pin pluggable screw
connector, to which external devices can be connected using five separately
fused outputs. The B6-PSU power supply contains a battery monitoring
facility, which is controlled and evaluated by the main processor unit. The
connectors for connection to the mains power supply and external devices
are supplied.
Mains supply voltage/frequency: 230 VAC +15%/-20% 47-63 Hz
Power consumption:
max. 200 VA, max. 160W
Mains fuse:
10A current surge-resistant
Mains fuses in power supply:
4.0A T
Outputs for internal devices:
3.3V/3A, 5V/1A, 27V/4A
Outputs for external devices:
5 x 27V / 2.5A FF
Charging output for batteries: 27V / 3.2A
Replacement fuses F1 to F5:
2.5A superfast, glass tube 5x20 mm
Description

Type

Art. No.

B6-PSU power supply unit


connection plug for external devices (spare part)
Replacement fuses F1 to F5
Battery current measuring cable

B6-PSU
ST-PSU EV
ZUB SICH 2.5FF
KAB PSU

EG072950
FG74090
IS625228
FG81720

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

33

Compact control panels Integral IP CX Accessories & replacement parts

Accessories & Spare Parts for Integral IP CX control panels


Description

Type

Art. No.

Battery 12 V / 17 Ah
3m USB cable for service PC
4.5 m USB cable for service PC
B6 battery holder set
B6 distance piece set
Battery current measuring cable
Log printer interface (electronic circuit board)
B5 log printer printer unit
Paper roll for log printer
Colour printer ribbon cassette for log printer
Printer cover
B6 battery cable set
Bayonet fuses for cable set
Lock for Integral IP MX/CX cabinets
Key for Integral IP MX/CX cabinets

AKKU 17
KAB USB 3
KAB USB 45
B6-BATH-SET
B6-DISTH-SET
KAB PSU
B5-PIF
B5-PDR-DW
PD PPR
PD FRB
B5-PDR-CO
B6 BATKAB
ZUB SICH8
SCU LOCK
SCU LOCK KEY

HG691013
FG022051
FG022052
FG74112
FG74111
FG81720
EG072906
FG030550
PPF-519057
HG694076
20-1400202-01
EI29940
IS625040
FG29516
750000027

Connectors for Integral IP CX modules


The connector plugs are supplied with the modules, or shipped with the
control panels, with the items listed below intended for ordering as
replacements.
Description

Connector for B4-DAI


16 pole detector zones
Connectors for B6-EIO
2x10 & 1x16-pole, inputs/outputs
Connectors for B4-USI
9 pole interfaces
15 pole interfaces
Connectors for B6-BCU-X2
16 pole for detector zones
5 pole for monitored outputs
13 pole for fire brigade panel acc. to DIN 14661
10 pole for relay outputs
9 pole solder lug terminal connector MMI-BUS
Connectors for B6-PSU
10 pole for external devices
3 pole power connector plug B6
Connectors for B6-LAN & B6-NET2 485
RJ45 connector Cat5e
Ratschen RJ45 crimping tool
9-Sub-D RJ45 coupling
15-Sub-D RJ45 coupling

34

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

Type

Art. No.

ST-LOOP/DAI

YK130295

ST-SET EIO

FG74109

ST-LPI/USI4/HFI
ST-USI4

FG74097
FG74098

ST-LOOP/DAI
ST-B6-OM
ST-FBF
ST-B6-REL
ST-BAF-MMI-L

YK130295
FG74116
YK130459
FG74115
FG74086

ST-PSU EV
ST-PSU NS

FG74090
YK130302

RJ45-IP
CRIMP-IP
KUP 9RJ45
KUP 15RJ45

MM010008
MM010001
20-1400000-01
20-1400001-01

B-HB-028EN

Compact control panel Integral IP BX Accessories & replacement parts

4 Compact control panel Integral IP BX

No.: 20-1111000-01

B-HB-028EN

Fire alarm control panel Integral IP BX


The single loop compact control unit comprises of a plastic case and an
Integral MAP operating panel built into the door. The built-in main
processor unit with integrated power supply unit contains all the interfaces
for connecting peripherals with the lower area of the case containing space
for fitting two 7.2 Ah batteries. Fire brigade control panels and remote
external indicator panels are connected over the EPI-bus, and a 100 MbitTX LAN interface can be used for remote access to the control panel. The
labelling of the operating panel (language) is done by means of a stick-on
panel. The control panel is also suitable for connection to a 110V supply
voltage (e.g. for markets in South America). The Integral IP BX consists of
the following:
Plastic case
B7-CPU-X1 main processor unit with integrated 50 W power supply unit
Integral MAP operating panel (language-neutral),
labelling can be stuck on
Connection for a single X-LINE loop (max. 250 elements on a length of
max. 3,500m)
2x primary outputs for transmission and alarm notification equipment
2x primary inputs
1x LAN (100 Mbit-TX)
1x EPI Bus (for controlling fire brigade control panels)
1x USB device service interface
Maximum battery size 2 x 12 V/7.2 Ah
Input voltage / frequency:
230/110 VAC, 15% / 47-63 Hz
Input power:
160 W
Output voltage:
26,3 VDC (50C) to 28,3 VDC (0C)
Output current:
4A
Batteries that can be used:
2 pcs. 12 V / 7,2 Ah in series
Cable inlets:
surface mounted from above or
countersunk mounting
Event memory:
10,000 events memory on board
Terminals:
screw-type terminals directly on the circuit
board (no plug and socket connections)
Protection category:
IP 30
Ambient temperature:
-5 to +50C
Dimensions:
300 x 360 x 85 mm (HxWxD)
Case colour:
red RAL 3000
Case material:
ABS/PC
Weight:
2,2 kg without batteries, 7.5 kg with
batteries
VdS-Approval:
applied for
CPD-Approval:
applied for
Description

Type

Art. No.

B7 Integral IP BX
Labelling panel german
Labelling panel german, incl. inscription
Alarmzhler and Anzeigetest
Labelling panel english
Labelling panel (other languages)
B7-CPU-X1 main processor unit (spare part)
Battery 12 V / 7,2 Ah
Metal key (spare part)

B7-X1-C
MAPTXT DE01

20-1111000-01
20-1111101-01

MAPTXT DE02

20-1111101-02

MAPTXT EN01
MAPTXT xx01
B7-CPU-X1
AKKU 7
DKM SCHL

20-1111102-01
upon request
20-1101000-01
HG691021
FG020015

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

35

External indicating & operating panels MMI-BUS Devices

5 External indicating & operating panels


5.1

MMI-BUS Devices

All external operating panels and devices in the Integral system whose device descriptor contains the letters
MMI are connected via the "MMI BUS" and can therefore be connected to all Integral IP MX and Integral IP
CX control panels.
Caution: Both versions of the high-end operating panel - B5-MMI-HCIP and B5-MMI-HCPP - can
only by connected to Integral CX control panels from version 7.1 onwards of the Integral
software!
The interface for connection the MMI-BUS can be found on module B5-BAF for the Integral IP MX control
panels and on the main processor unit B6-BCU-X2 or B6-BCU-X1x for the Integral IP CX control panels.
The external Integral operating panels B3-MMI-CIP and B3-MMI-CPP, as well as both high end operating fields
B5-MMI-HCIP and B5-MMI-HCPP are available in a wide range of languages.

No.: FG052200

No.: FG052300

36

External operating panel Integral MAP


External operating panel with or without a log printer for connection to the
MMI-BUS, available in many language versions (key labels and indicator
display). The order numbers listed below are for the German and English
language version, other languages being available on request.
Display with 6 lines, 40 characters per line
Conforms to all options of EN 54-2:2006
can be deployed as a main operating panel in a SecoNET
up to four languages can be toggled between in normal operating mode
Connection for EPI-Bus (various other indication and operating devices)
2 freely programmable and labelled keys
2 three colour LEDs can be freely programmed and labelled
5 status lists (alarms, faults, disablements, etc.)
Status indicator in the first line of the display
Zone operation (e.g. disable zone 1-10)
Group operation (e.g. simultaneously disable all detector zones)
individual user management with password and user level
every change of user is logged in the event log memory
Operating voltage:
10 to 30 V
Quiescent current:
20 mA
Data transmission:
MMI-BUS
Elektrisch:
galvanically isolated RS 485
Protocol:
serial, DIN 19244-3
Distance to subcontrol unit:
max. 1200 m
Protection category:
IP 30
Ambient temperature:
-5 to +50C
Dimensions without printer:
230 x 445 x 35 mm (HxWxD)
Dimensions with printer:
360 x 445 x 55 mm (HxWxD)
Case colour:
red RAL 3000
Description

Type

Art. No.

External Operating Panel MAP - german


External Operating Panel MAP - english
External Operating Panel MAP - other languages
Ext. Operating Panel MAP with printer - german
Ext. Operating Panel MAP with printer - english
Ext. Operating Panel MAP with printer - other
languages
Ext. Operating Panel MAP without case - german
Ext. Operating Panel MAP without case - english
Ext. Operating Panel MAP without case - other
languages

B5-MMI-CIP-DE
B5-MMI-CIP-EN
B5-MMI-CIP-XX
B5-MMI-CPP-DE
B5-MMI-CPP-EN
B5-MMI-CPP-XX

FG052200
FG052201
upon request
FG052300
FG052301
upon request

B5-MMI-CII-DE
B5-MMI-CII-EN
B5-MMI-CII-XX

FG91600A9
FG91601A9
upon request

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

External indicating & operating panels MMI-BUS Devices

No.: 20-1210000-01

No.: FG052500

No.: FG052501

B-HB-028EN

External indicating panel Integral PIP


For parallel indication of operating states of the fire alarm control panel. The
device can be programmed in such a way, that only the information that is
relevant for the surrounding area is displayed on it, e.g. for use as a floor
terminal. The labelling of the keys, as well as indications on the display is
available in more than 20 languages.
Display with 6 lines, 40 characters per line
2 freely programmable and labelled keys
2 three colour LEDs can be freely programmed and labelled
3 status lists (alarms, faults, disablements)
acoustic alarm and fault signals
acoustic feedback when pressing the keys
EPI-BUS interface
Robust ABS plastic case with IP 42 protection class
Operating voltage:
10 to 30 VDC
Quiescent current:
49 mA
Data transmission:
MMI-BUS
Electrical:
galvanically isolated RS 485
Protocol:
serial, DIN 19244-3
Distance to subcontrol unit:
max. 1200 m
Protection category:
IP 42
Ambient temperature:
-5 to +50C
Case:
ABS plastic
Case colour:
red RAL 3000
Dimensions:
170 x 227 x 40 mm (HxWxD)
Weight:
ca. 500 g
Description

Type

Art. No.

Indicating panel Integral PIP - german


Indicating panel Integral PIP - english
Indicating panel Integral PIP - other languages

B5-MMI-PIP-DE
B5-MMI-PIP-EN
B5-MMI-PIP-xx

20-1210000-01
20-1210000-02
upon request

High-End operating panels B5-MMI-HCIP and B5-MMI-HCPP


External operating panel with VGA colour display and multi-function
keys for centralised operation and indication of a fire alarm control panel or
an entire SecoNET fire alarm network, in accordance with EN 54-2 and EN
54-4 as well as NORM F 3000. Available in many language versions (key
labelling and indicator display) on request. The high-end operating panel can
only by connected to Integral CX control panels from version 7.1 onwards
of the Integral software.
Operating voltage:
10 to 30 V
Quiescent current:
97 mA
Data transmission:
MMI-BUS
Electrical:
galvanically isolated RS 485
Protocol:
serial, DIN 19244-3
Distance to subcontrol unit:
max. 1200 m
Protection category:
IP 30
Ambient temperature:
-5 to +50C
Dimensions without printer:
230 x 445 x 35 mm (HxWxD)
Dimensions with printer:
360 x 445 x 55 mm (HxWxD)
Case colour:
red RAL 3000
Description

Type

Art. No.

High-End operating panels without printer - german


High-End operating panels with printer - german
High-End operating panels with/without printer other languages

B5-MMI-HCIP
B5-MMI-HCPP
B5-MMI-HCxx

FG052500
FG052501
upon request

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

37

External indicating & operating panels MMI-BUS Devices

No.: FG050250

No.: FG050251

38

External LED indicator panel for 8 extinguishing zones


External LED indicator panel for eight extinguishing zones (twelve LEDs
per extinguishing zone and group indicator with nine LEDs), including case,
keyswitch and controller module. The labelling uses push-in strips (not
supplied) with the device also available without a case for fitting in switching
cabinets.
Operating voltage:
10 to 30 V
Quiescent current:
2 mA per lit LED
Data transmission:
MMI-BUS
Electrical:
galvanically isolated RS 485
Protocol:
serial, DIN 19244-3
Distance to subcontrol unit:
max. 1200 m
Protection category:
IP 30
Ambient temperature:
-5 to +50C
Dimensions:
228 x 445 x 48 mm (HxWxD)
Case colour:
red RAL 3000
Description

Type

Art. No.

External LED indicator panel for 8 exting. zones


External LED indicator panel for 8 exting. zones
without case

B3-MMI-IPEL
B3-MMI-IPEL BFE

FG050250
FG81620

External LED indicator panel for 64 detector zones


LED indicator panel for indication of alarm, fault and disablement states for
64 detector zones. The labelling uses push-in strips (not supplied) with the
device also available without a case for fitting in switching cabinets.
Operating voltage:
10 to 30 V
Quiescent current:
2 mA per lit LED
Data transmission:
MMI-BUS
Electrical:
galvanically isolated RS 485
Protocol:
serial, DIN 19244-3
Distance to subcontrol unit:
max. 1200 m
Protection category:
IP 30
Ambient temperature:
-5 to +50C
Dimensions:
228 x 445 x 48 mm (HxWxD)
Case colour:
red RAL 3000
Description

Type

Art. No.

External LED indicator panel for 64 detector


zones
External LED indicator panel for 64 detector
zones without case

B3-MMI-EAT64

FG050251

B3-MMI-EAT64 BFE

FG81623

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

External indicating & operating panels MMI-BUS Devices

No.: FG050400

No.: FG050403

B-HB-028EN

Fire Brigade panel Austria B3-MMI-FPA


Fire Brigade panel conforming to NORM F 3031, including LCD display,
case and controller module with keys and LEDs. For visually displaying the
more important operating states of fire alarm control panels for simple and
uniform operation of a fire alarm system by the fire brigade.
Operating voltage:
10 to 30 V
Quiescent current:
14 mA
Data transmission:
MMI-BUS
Electrical:
galvanically isolated RS 485
Protocol:
serial, DIN 19244-3
Distance to subcontrol unit:
max. 1200 m
Protection category:
IP 30
Ambient temperature:
-5 to +50C
Dimensions:
300 x 200 x 55 mm (HxWxD)
Case colour:
red RAL 3000
Description

Type

Art. No.

Fire Brigade panel Austria


Metal key

B3-MMI-FPA
DKM SCHL

FG050400
FG020015

Fire Brigade indication panel B3-MMI-FAT


Indicator panel conforming to the requirements of DIN 14662, including an
LCD display, case and controller module with keys and LEDs. Visually
displays the more important operating states of fire alarm control panels to
ensure simple and uniform operation of a fire alarm system by fire brigade
members. A fire brigade control panel in accordance with DIN 14661 can
also be connected to the fire brigade display panel.
Operating voltage:
22 to 30 V
Quiescent current:
21 mA
Data transmission:
MMI-BUS
Electrical:
galvanically isolated RS 485
Protocol:
serial, DIN 19244-3
Distance to subcontrol unit:
max. 1200 m
Protection category:
IP 30
Ambient temperature:
-5 to +50C
Dimensions:
185 x 255 x 65 mm (HxWxD)
Dimensions without case:
180 x 240 x 40 mm (HxWxD)
Case colour:
grey RAL 7032
VdS-Approval:
G206116
Description

Type

Art. No.

Fire Brigade indication panel


Fire Brigade indication panel without case

B3-MMI-FAT
B3-MMI-FAT-BFE

FG050403
FG050405

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

39

External indicating & operating panels MMI-BUS Devices

No.: FG050402

No.: 20-1210011-01

40

Fire Brigade panel Sweden B3-MMI-FPS


Fire brigade control panel with Swedish labelling conforming to the
requirements of Swedish Standard SS 3654 with an LCD display, metal case,
keys and LEDs for optical indication of the most important operating
statuses of the fire alarm control panel and for simple and uniform operation
of the fire alarm system by the fire brigade.
Operating voltage:
15 to 30 V
Quiescent current:
14 mA
Data transmission:
MMI-BUS
Electrical:
galvanically isolated RS 485
Protocol:
serial, DIN 19244-3
Distance to subcontrol unit:
max. 1200 m
Protection category:
IP 30
Ambient temperature:
-5 to +50C
Dimensions:
180 x 280 x 55 mm (HxWxD)
Case colour:
red RAL 3000
Description

Type

Art. No.

Fire Brigade panel Sweden

B5-MMI-FPS

FG050402

Intervention panel Sweden B5-MMI-IPS


Extra operating panel in plastic case with Swedish labelling for triggering a
(programmed) intervention and for displaying the most important operating
statuses of the fire alarm control panel.
Operating voltage:
10 to 30 VDC
Quiescent current:
49 mA
Data transmission:
MMI-BUS
Electrical:
galvanically isolated RS 485
Protocol:
serial, DIN 19244-3
Distance to subcontrol unit:
max. 1200 m
Protection category:
IP 42
Ambient temperature:
-5 to +50C
Case:
ABS plastic
Case colour:
red RAL 3000
Dimensions:
170 x 227 x 40 mm (HxWxD)
Weight:
ca. 500 g
Description

Type

Art. No.

Intervention panel Schweden

B5-MMI-IPS

20-1210011-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

External indicating & operating panels MMI-BUS Devices

No.: EG072827

No.: FG69041

No.: FG81725

B-HB-028EN

Universal input/output module B3-MMI-UIO


For controlling the floor plan and parallel display panels or as a remotely
located input/output module for querying potential-free contacts (sprinkler
systems), or also for controlling non-monitored horns, lamps, relays etc. The
module is either built directly in to the relevant panel or in branch cases. The
system connection is via the MMI-BUS.
Operating voltage:
10 to 30 V
Current consumption:
14 mA
Data transmission:
MMI-BUS
Electrical:
galvanically isolated RS 485
Protocol:
serial, DIN 19244-3
Distance to subcontrol unit:
max. 1200 m
Connection:
Floor plan panels, parallel indicator panels,
flashing lights, sirens, horns, sprinkler
systems, etc.
Connection information:
64 LED outputs 2 mA
max. 256 LED outputs per control panel
8 open collector outputs up to max.100 mA
output voltage max. +30 V
8 inputs with 8 outputs can be
interconnected as an 8 x 8 matrix
input voltage +5 V
input current max. 3.3 mA
Ambient temperature:
-5 to +50C
Dimensions:
160 x 105 x 20 mm
VdS-Approval:
G200116
CPD-Approval:
0786-CPD-20422
Plastic case and steel mounting board for B3-MMI-UIO
For fitting the module B3-MMI-UIO. The UIO STP steel mounting board
consists of a zinc-plated sheet steel with 5 insertion pins and is used to
secure the B3-MMI-UIO module into the plastic case.
Protection category:
IP 66 flame resistant
Ambient temperature:
up to +70C
Case material:
impact-resistant plastic (polystyrol)
Case colour:
grey RAL 7035
Case dimensions:
182 x 180 x 90 mm (HxWxD)
Steel mounting board:
150 x 173 x 1,5 mm (HxWxD)
Description

Type

Art. No.

Universal input/output module


Plastic case for B3-MMI-UIO
Steel mounting plate for B3-MMI-UIO
34 pole ribbon cable (1 m) for B3-MMI-UIO
40 pole ribbon cable (1 m) for B3-MMI-UIO
Diode terminal block f. UIO
34 pole UIO connection module
40 pole UIO connection module

B3-MMI-UIO
UIO GEH
UIO STP
UIO KAB 34
UIO KAB40
DK 20
UM 45-FLK 34
UM 45-FLK 40

EG072827
FG69041
FG05203
FG81725
FG81726
FG020980
FG020981
FG020982

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

41

External indicating & operating panels EPI-BUS Devices

5.2

EPI-BUS Devices

All external operating panels and devices in the Integral IP system, in which the type descriptor contains the
letters "EPI", can be directly connected over the EPI-BUS to all internal and external Integral Map operating
panels, and to the Integral IP BX control panel.

No.: 20-1240117-01

No.: 20-1240115-01

42

Fire Brigade panel Austria B5-EPI-FPA


Indicator panel conforming to the requirements of DIN 14662 with an LCD
display, case, keys and LEDs for optical indication of the most important
operating statuses of the fire alarm control panel and for simple and uniform
operation of the fire alarm system by the fire brigade. The B5-EPI-FAT
must always be fitted directly adjacent to the control panel or next to an
external Integral MAP or PIP operating panel. Shipped incl. a Cat 5e 1m
patch cable.
Operating voltage:
3,3 V 5%
Quiescent current:
5 mA
Data transmission:
EPI-BUS
Range:
max. 1 m
Protection category:
IP 30
Ambient temperature:
-5 to +50C
Dimensions:
300 x 200 x 55 mm (HxWxD)
Case colour:
red RAL 3000
Approval:
in accordance with NORM F 3031
Description

Type

Art. No.

Fire Brigade panel Austria B5-EPI-FPA

B5-EPI-FPA

20-1240117-01

Fire Brigade indication panel B5-EPI-FAT


Indicator panel conforming to the requirements of DIN 14662 with an LCD
display, case, keys and LEDs for optical indication of the most important
operating statuses of the fire alarm control panel and for simple and uniform
operation of the fire alarm system by the fire brigade. The B5-EPI-FAT
must always be fitted directly adjacent to the control panel or next to an
external Integral MAP or PIP operating panel. Shipped incl. a Cat 5e 1m
patch cable.
Operating voltage:
3,3 V 5%
Quiescent current:
12 mA
Data transmission:
EPI-BUS
Range:
max. 1 m
Protection category:
IP 30
Ambient temperature:
-5 to +50C
Dimensions:
185 x 255 x 65 mm (HxWxD)
Dimensions without case:
158 x 133 x 20 mm (HxWxD)
Case colour:
grey RAL 7032
VdS-Approval:
G211102
Description

Type

Art. No.

Fire Brigade indication panel B5-EPI-FAT


Fire Brigade indication panel B5-EPI-FAT
without case

B5-EPI-FAT
B5-EPI-FAT-E

20-1240115-01
20-1240119-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

External indicating & operating panels EPI-BUS Devices

No.: 20-1240118-01

No.: 20-1240116-01

B-HB-028EN

Fire Brigade panel Sweden B5-EPI-FPS


Fire brigade control panel conforming to the requirements of Swedish
Standard SS 3654 with an LCD display, case, keys and LEDs for optical
indication of the most important operating statuses of the fire alarm control
panel and for simple and uniform operation of the fire alarm system by the
fire brigade. The B5-EPI-FPS must always be fitted directly adjacent to the
control panel or next to an external Integral MAP or PIP operating panel.
Shipped incl. a Cat 5e 1m patch cable.
Operating voltage:
3,3 V 5%
Quiescent current:
11 mA
Data transmission:
EPI-BUS
Range:
max. 1 m
Protection category:
IP 42
Ambient temperature:
-5 to +50C
Case:
ABS plastic
Case colour:
red RAL 3000
Dimensions:
170 x 227 x 40 mm (HxWxD)
Weight:
ca. 500 g
Description

Type

Art. No.

Fire Brigade panel Sweden B5-EPI-FPS

B5-EPI-FPS

20-1240118-01

Fire Brigade panel Germany B5-EPI-FPD


Conforming to the requirements of DIN 14661 including a case and
controller module with keys and LEDs for optical indication of the most
important operating statuses of the fire alarm control panel and for simple
and uniform operation of the fire alarm system by the fire brigade. The B5EPI-FPD must always be fitted directly adjacent to the control panel or next
to an external Integral MAP or PIP operating panel. Shipped incl. a Cat 5e
1m patch cable.
Operating voltage:
3,3 V 5%
Quiescent current:
6 mA
Data transmission:
EPI-BUS
Range:
max. 1 m
Ambient temperature:
-5 to +50C
Protection category:
IP 30
Case colour:
grey RAL 7032
Dimensions:
185 x 255 x 65 mm (HxWxD)
Dimensions ohne Gehuse:
137 x 95 x 20 mm (HxWxD)
VdS-Approval:
applied for
Description

Type

Art. No.

Fire Brigade panel Germany


Fire Brigade panel Germany without case

B5-EPI-FPD
B5-EPI-FPD-E

20-1240116-01
20-1240120-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

43

External indicating & operating panels EPI-BUS Devices

No.: 20-1240121-01

44

Fire Brigade panel Czech Republic B5-EPI-FPCZ


Fire brigade control panel with Czech labelling conforming to the
requirements of DIN 14661 including a metal case, keys and LEDs for
optical indication of the most important operating statuses of the fire alarm
control panel and for simple and uniform operation of the fire alarm system
by the fire brigade. Shipped incl. a Cat 5e 1m patch cable.
Operating voltage:
3,3 V 5%
Quiescent current:
6 mA
Data transmission:
EPI-BUS
Range:
max. 1 m
Protection category:
IP 30
Ambient temperature:
-5 to +50C
Dimensions:
185 x 255 x 65 mm (HxWxD)
Dimensions without case:
137 x 95 x 20 mm (HxWxD)
Case colour:
grey RAL 7032
Description

Type

Art. No.

Fire Brigade panel Czech Republic

B5-EPI-FPCZ

20-1240121-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Management system SecoLOG IP

6 Management system SecoLOG IP


Graphical control system for use with
multiple workstations in accordance with
NORM F 3003 for simple, clear and
centralised indication and operation of fire
alarm systems using the latest IP technology.
All messages and system states of the fire
alarm control panels that are connected to
the system are collated and displayed clearly
at one or more PC workstations.

Features

Simple standardised operation of fire alarm systems and fire alarm devices using messages and commands
Maximum reliability
For use with one or several work stations, modular extension
Compatible with all Schrack fire alarm systems
2 monitor user interface gives a clear overview, with automatic changeover in the event of a fault and with
a dynamic zoom function
Hierarchical password system with individually assigned access privileges and passwords
The user interface language can be changed whilst the system is still online
Alarm print out, messages and reaction texts can be individually configured
Automatic backup of data providing an online backup
All connected fire alarm systems and wiring is monitored
Continuous logging with note and reports functions
Events can be displayed and the system operated either using symbols or text fields in the building floor
plan
Fastest print out times for graphical representations of the alarm and reaction texts
Floor plans for reaction diagrams can be imported from all current graphics and CAD programs
Data can be received from detectors to allow automatic positioning and assignment of levels
(autoconfiguration)
Configurable processes and control processes can be triggered manually or automatically
Tested and approved in accordance with Austrian Standard NORM F 3003 (fire detection control
systems).

System requirements

PC with at least a dual core processor and 1 GB RAM


2 mirrored hard drives, each with at least 2 GB
Microsoft Windows XP/7 operating system
Hard disk controller for RAID 1 operation (mirroring)
10/100 Mbit network adapter
Dual output graphics card with 128 MB RAM (minimum resolution 2560 x 1024)
1 serial COM interface and 2 USB interfaces
Mouse and keyboard
Sound card and speakers
2 colour monitors
Professional colour printer with USB or network connection with USB or network connection, at least 12
pages A4/min.
Emergency power supply for backup in the event of a brief power failure
Modem for simple maintenance and data administration

B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

45

Management system SecoLOG IP

Software packages
Description

No.: FG022000

Type

Art. No.

SECOLOG-IP GP 1000

FG022007

SECOLOG-IP EP 1000

FG022008

SECOLOG-IP GP 2500

FG022000

SECOLOG-IP EP 2500

FG022001

SECOLOG-IP NWG

FG022010

SECOLOG-IP DEMO

FG022004

Description

Type

Art. No.

SecoLOG Control System Computer


PC including operating system, suitable for
SecoLOG operation in 2 monitor operating
mode

SECOLOG ELR

FG022040

SecoLOG 19" flat panel monitor


Active TFT monitor (min. 1280 x 1024)

SECOLOG BS19

FG022042

SecoLOG 24" flat panel monitor


Active TFT monitor (min. 1920 x 1200)
SecoLOG Modem 56k V.92 USB
for SecoLOG remote diagnosis

SECOLOG BS24

FG022053

SECOLOG MOD 56K

FG022055

SecoLOG ISDN Adapter ISDN


for SecoLOG remote diagnosis

SECOLOG ISDN

FG022045

SecoLOG emergency power supply


For SecoLOG workstation in the event of a
brief power failure (at least 5 minutes).

SECOLOG EPS

FG022046

SecoLOG PC Cable RS 232/USI connection


(15 m) SecoLOG - Integral IP

SECOLOG PC KAB

FG022047

SecoLOG Printer
Professional colour printer (min. 12 pages A4
alarm print out within 60 secs.)

SECOLOG EDR

FG022048

SecoLOG USB printer cable(3 m)


For connecting the printer - SecoLOG

KAB USB 3

FG022051

SecoLOG USB printer cable(4.5 m)


For connecting the printer - SecoLOG

KAB USB 45

FG022052

Wall mounting bracket for TFT/LCD-TV

VM-L01

FG022060

SecoLOG 1000 basic package


for connection up to 1,000 elements incl. a
dongle and basic configuration of the control
system computer
Expansion pack for SecoLOG 1000
for connecting up to 2,500 elements.
(with this expansion pack the SecoLOG 1000
basic package is upgraded to a SecoLOG 2500
basic package)
SecoLOG 2500 basic package
for connection up to 2,500 elements incl. a
dongle and basic configuration of the control
system computer
Expansion pack for SecoLOG 2500
for extending the SecoLOG 2500 basic
package by 1,000 elements
SecoLOG Network license
for systems for multiple workstations (1x per
system)
SecoLOG Demo Version

Components & Accessories

46

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Integral X-LINE Automatic fire detectors & detector bases

7 Integral X-LINE
7.1

Automatic fire detectors & detector bases

No.: 30-5000003-01

Multiple sensor detector MTD 533X


Combined scattered light smoke detector and temperature detector for early
detection of smouldering or open fires with or without smoke formation..
The detector can be programmed and used, depending on the type of system
and depending on the area in which it is to be deployed, as a smoke detector,
as a temperature detector or as a combined detector. For use in areas where
there are difficult prevailing conditions, the MTD 533X CP version is
available with greater protection against increased air humidity. It is shipped
including a protective dust cap.
Fire alarm triggered by smoke, heat or heat and warmth
Smoke sensor with CUBUS levelling for automatic adaptation to
environmental conditions without time-consuming setting of parameters
Sensitivity towards smoke and heat class can be set acc. to EN 54
temperature-based smoke evaluation
Pre-alarm evaluation at 30% and 75% of the alarm threshold
2 level contamination detection
Integrated short circuit isolator
Adjustment of alarm thresholds to compensate for environmental
influences
Alarm filter for reducing the number of deceptive alarms
Alarm output for external indication of alarms
Operating time and contamination level values can be read out
Operating voltage:
12 to 30 VDC (without modulation
deviation)
Quiescent current:
120 A typ.
Alarmausgang
programmable: 0,1 mA/1 mA/5 mA
Alarm-LED active:
2,5 mA max.
Alarm current:
min. 0,5 mA, max. 10 mA
Output voltage:
X-LINE: 5 V, Loop: 6,8 V
Functional principle:
Tyndall-Effekt/NTC Sensor
Detector base:
series USB 501-x
Signal transmission:
serial, 2 wire technology
Short circuit isolator:
integrated
Smoke sensitivity:
acc. to EN 54-7
Heat sensitivity:
acc. to EN 54-5 (A1, A2, B (Index S+R))
Protection category:
IP 44 (with base USB 501-1/-6)
Ambient temperature:
-20 to +60C
Rel. air humidity:
10 to 95 % rel/F
Air speed:
max. 20 m/s
Dimensions with base:
118 x 67,5 mm (DxH)
Case:
ABS/PC, white similar to RAL 9003
Weight:
125 g
VdS-Approval:
G210115
CPD-Approval:
0786-CPD-20993

B-HB-028EN

Description

Type

Art. No.

MTD 533X Multiple Sensor Detector


MTD 533X CP Multiple Sensor Detector
MTD 533X colour black, RAL 9005)
MTD 533X MC (other RAL colours)
Sticker grey ring (20 pcs.) when used as heat detector
Dust protection cap for MTD 533X (spare part)

MTD 533X
MTD 533X CP
MTD 533X SW
MTD 533X MC
S GR
DDC 533

30-5000003-01
30-5000003-51
FG030500
upon request
FG28422
FG030398

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

47

Integral X-LINE Automatic fire detectors & detector bases

No.: FG030126

No.: FG030700

No.: FG030132

48

Detector bases USB 501-1 and USB 501-6


For connecting automatic fire detectors to the Integral X-LINE, set up for
surface mounting with a built-in 6 pole terminal block An additional 4 pin
terminal block can be fitted in the designated snap-fit holder to form
additional isolation points. The detector is attached by means of a bayonet
fitting. When using the USB 501-1, the installation can be checked easily
even when detectors are not used, using an integrated automatic circuit
closing mechanism built into the terminal block, while the USB501-6 does
not possess such a circuit closing mechanism, with the loop circuit only
being closed when the detector is inserted.
Area for deployment:
dry and wet rooms
Installation type:
Surface mounting
Connection:
screw-type terminals, max. 2 x 1.5 mm
Protection category:
IP 44
Ambient temperature:
-20 to +70C
Rel. air humidity:
briefly without condensation 95%
permanent without condensation 70%
Dimensions:
118 x 28 mm (DxH)
Case colour:
white (other RAL colours upon request)
Case material:
ABS / PC, FR90
Weight:
65 g
VdS-Approval:
G204106
CPD-Approval:
0786-CPD-20246
Description

Type

Art. No.

Detector base white


Detector base black, RAL 9005
Detector base (other colours)
Detector base white without base contact
Detector base black, RAL 9005 without base contact
Detector base (other colours) without base contact
Isolation point terminal block for USB 501-x
Socket connector black (10 pcs.)

USB 501-1
USB 501-1 SW
USB 501-1 MC
USB 501-6
USB 501-6 SW
USB 501-6 MC
KL USB501
STE 01-BK PU10

FG030126
FG030164
upon request
FG030700
FG030701
upon request
FG030132
30-4100002-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Integral X-LINE Automatic fire detectors & detector bases

No.: FG030135

No.: FG030136

B-HB-028EN

Countersunk base for cavity ceilings USB 501-2


For connecting automatic fire detectors to the Integral X-LINE, suitable for
installation in standard cavity ceilings, consisting of standard base USB 5011, fitting ring with fastening clips, collar and bezel ring. Apertures and predetermined breaking points are present in the fitting ring for feeding in the
cable, while the bezel ring is fitted together with the detector.
Area for deployment:
dry rooms, cavity ceiling installation
Connection:
screw-type terminals, max. 2 x 1.5 mm
Protection category:
IP 44
Ambient temperature:
-20 to +70C
Rel. air humidity:
briefly without condensation 95%
permanent without condensation 70%
Dimensions:
158 x 52,5 mm (DxH)
Colour bezel ring:
white (other RAL colours upon request)
Case material:
ABS / PC, FR90
Weight:
100 g
VdS-Approval:
G204106
CPD-Approval:
0786-CPD-20246
Detector base for use in wet rooms USB 501-3
For connecting automatic detectors to the Integral X-LINE, consisting of a
fitting case with 4 cable inlets, USB 501-1 standard base, and a sealing ring
made of closed cell rubber. Taking into consideration the environmental
conditions that are permissible for the detector to be used, the USB 501-3
can be used in wet rooms, or anywhere where the installation process
requires the use of thick cabling. The cable is fed in through the installation
case, with the detector base only being attached to the case after cable has
been fed in, using the screws supplied. A 6 pole terminal block is used for
connecting the fire alarm cabling, and an additional 4 pole terminal block can
be clipped into the dedicated snap-fit holder, if required, to form additional
isolation points. The sealing ring is inserted between the detector and the
USB 501-3 base.
Area of deployment:
wet rooms
Installation type:
Surface mounting
Connection:
screw-type terminals, max. 2 x 1.5 mm
Protection category:
IP 54
Ambient temperature:
-20 to +70C
Rel. air humidity:
briefly without condensation 95%
permanent without condensation 70%
Dimensions:
123 x 53 mm (DxH)
Case colour:
white
Case material:
ABS / PC, FR90
Weight:
200 g
VdS-Approval:
G204106
CPD-Approval:
0786-CPD-20246
Description

Type

Art. No.

Detector base for cavity ceilings


Detector base for use in wet rooms
Isolation point terminal block for USB 501-x
Socket connector black (10 pcs.)
Bezel ring for USB 501-2 (many RAL colours)

USB 501-2
USB 501-3
KL USB501
STE 01-BK PU10
USB BR MC

FG030135
FG030136
FG030132
30-4100002-01
upon request

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

49

Integral X-LINE Automatic fire detectors & detector bases

No.: FG030191

No.: FG030189

50

Ventilation duct detector LKM 531


For use in places where there is a high airspeed and strong smoke dispersal
e.g. air conditioning or ventilation ducts. Consisting of a plastic case with
built-in detector base and SSD 31K smoke detector. The case has a clear
cover, so that the smoke detectors alarm LED can be seen externally. The
SSD 531K detector, detector base, as well as all stopped and sealers are
supplied with the unit as standard.
Operating voltage:
15 to 30 V DC
Current consumption:
see SSD 531K
Areas for use:
ventilation ducts
oblong ventilation duct:
lengths of sides from 15 cm to 1 m
circular ventilation ducts:
diameter 20 cm to 1 m
Dimensions without pipe:
95,3 x 247 x 135 mm (H x W x D)
Ventilation pipe length:
140 to 345 mm
Apertures for fittings:
for inlet/outlet pipe:
2 x 28-30 mm / 150 mm distance
for fastening the case:
2 x max. 6 mm / 206 mm distance
Cable entry points:
4 x 6-10 mm
Colour:
blue / transparent
Material:
PC / anodised aluminium pipe
Suitable for detector type:
SSD 531K
Air speed:
1 to 20 m/s
Protection category:
IP 54
Weight:
without pipe: ca. 392 g
with pipe: ca. 485 g
VdS-Approval:
G206086
Optical smoke detector SSD 531K for LKM 531
Only for use in LKM 531 ventilation duct detector. The SSD 531K is
shipped as standard with the LKM 531, the order number is listed only for
ordering replacement parts.
Operating voltage:
15 to 30 VDC
Quiescent current:
250 A max.
Alarm current:
6 mA typ. (with LED)
Detector base:
USB 501-1 in LKM 531
Functional principle:
Scattered light (Tyndall effect)
Signal transmission:
serial, 2 wire technology
Short circuit isolator:
integrated
Protection category:
IP 54 in LKM 531
Ambient temperature:
-20 to +60C
Sensitivity:
0,14 dB/m (EN 54-7)
Dimensions:
118 x 67,5 mm (DxH)
Case colour:
electro white with blue ring
Case material:
ABS / PC, FR90
Weight:
105 g
VdS-Approval:
G206086
Description

Type

Art. No.

Ventilation duct detector LKM 531


Optical smoke detector SSD 531K
Socket connector black (10 pcs.)

LKM 531
SSD 531K
STE 01-BK PU10

FG030191
FG030189
30-4100002-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Integral X-LINE Manual call points

7.2

Manual call points

No.: 30-5700007-01

No.: 30-5700007-03

No.: 30-5700007-05

B-HB-028EN

Manual call points MCP 535X-1 and MCP 535X-3


For manual actuation of a fire alarm in conformance with EN 54-11 (type
B). The alarm is triggered by smashing the glass panel and pressing the
button. The push button remains locked, and the actuated state is indicated
by means of the built-in LED. The protection class of the detector can be
increased to IP 54 by fitting a rubber seal. Both the insert (with a hand
symbol) and the outer labelling of the blue version and the key for opening
the door must be ordered separately.
Operating voltage:
7 to 31 VDC
Quiescent current:
max. 120 A typ. 90 A
Alarm current:
max. 2,5 mA, max. 20mA backup-alarm
Functional principle:
manual call point type B acc. to EN 54-11
Connection:
Integral X-LINE
Terminals:
Screw clips, maximum 1.5 mm
Signal transmission:
serial, 2 wire technology
Short circuit isolator:
integrated
Protection category:
IP 52 (optional IP 54)
Ambient temperature:
-20 to +50C
Dimensions:
134 x 134 x 36 mm (HxWxD)
Case:
red plastic (RAL 3001)
blue plastic (RAL 5005)
Weight:
450 g
G210095 (EN 54-11, EN 54-17)
VdS-Approval:
CPD-Approval:
0786-CPD-20988
Manual triggering device MCP 535X-5
For manually triggering an extinguishing operation using gas extinguishing
agents conformant to EN 12094-3. The gas extinguishing system is triggered
by smashing the glass panel and pressing the button. The push button
remains locked, and the actuated state is indicated by means of the built-in
LED. The protection class of the detector can be increased to IP 54 using a
rubber seal. Both the insert (with a hand symbol) and the outer labelling and
the key for opening the door must be ordered separately.
Operating voltage:
7 to 31 VDC
Quiescent current:
max. 120 A typ. 90 A
Alarm current:
max. 2,5 mA, max. 20mA backup-alarm
Functional principle:
Manual triggering device (EN 12094-3)
Connection:
Integral X-LINE
Signal transmission:
serial, 2 wire technology
Terminals:
Screw clips, maximum 1.5 mm
Short circuit isolator:
integrated
Protection category:
IP 52 (optional IP 54)
Ambient temperature:
-20 to +50C
Dimensions:
134 x 134 x 36 mm (HxWxD)
Case colours:
yellow plastic (RAL 1003)
Weight:
450 g
VdS-Approval:
G210096
CPD-Approval:
0786-CPD-20989

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

51

Integral X-LINE Manual call points

No.: 30-5700007-07

No.: FG030235

52

Stop-Button MCP 535X-7


To manually interrupt the triggering of an extinguishing process using gasbased extinguishing agents during the pre-warning period. Triggering then
occurs indirectly, i.e. after the glass panel has been smashed, the control
element must be pushed in order to interrupt the triggering of the
extinguishing operation. The control element does not lock. Both the insert
(with a hand symbol) and the outer labelling and the key for opening the
door must be ordered separately.
Operating voltage:
7 to 31 VDC
Quiescent current:
max. 120 A typ. 90 A
Alarm current:
max. 2,5 mA, max. 20mA backup-alarm
Functional principle:
Stop button acc. to EN 12094-3
Connection:
Integral X-LINE
Signal transmission:
serial, 2 wire technology
Terminals:
Screw clips, maximum 1.5 mm
Short circuit isolator:
integrated
Protection category:
IP 54
Ambient temperature:
-20 to +50C
Dimensions:
134 x 134 x 36 mm (HxWxD)
Case colours:
blue plastic (RAL 5005)
Weight:
450 g
VdS-Approval:
G210097
CPD-Approval:
0786-CPD-20990
Weather protection case for MCP 535X
For additional protection for series MCP 535X manual call points against the
ingress of water on the top and back side when used in difficult atmospheric
conditions (outdoor areas). The weather resistant case has four drill holes on
it to allow it to be screwed in with manual call points.
Material:
1 mm sheet steel
Dimensions:
160 x 184 x 100 mm (HxWxD)
Colour:
red RAL 3000 (painted)

Description

Type

Art. No.

Manual call point MCP 535X-1


Manual call point MCP 535X-3
Manual call point MCP 535X-5
Stop Button MCP 535 X-7
Hand symbol sticker for MCP535X
Labelling strip for MCP 535X
Replacement PCB f. MCP 535X-1 to MCP535-7
Replacement glass panel for MCP 535X
Key for MCP 535X
Rubber seal for MCP 535X
Weather protection case for MCP 535X (red)
Weather protection case for MCP 535X (blue)

MCP535X-1
MCP535X-3
MCP535X-5
MCP535X-7
MCP535 AK
MCP535 BGD
MCP535X LP
MCP535 GLAS
DKM SCHL
MCP535 DG
MCP WSG
MCP WSG BL

30-5700007-01
30-5700007-03
30-5700007-05
30-5700007-07
FG030230
FG030232
30-5700007-90
FG030231
FG020015
30-4100001-01
FG030235
FG030236

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Integral X-LINE Manual call points

No.: FG030930

No.: FG030931

No.: FG030932

No.: FG030921

Manual call points MCP 545X


For manual actuation of a fire alarm in conformance with EN 54-11 (type
A). The alarm is triggered by pushing in the glass panel. The triggered status
is indicated by the built-in LED and continues to exist until a new glass
panel is inserted. The three different versions differ in terms of their case
construction and IP protection class. Electronics, connections and their
functions are identical for all types of detector. Shipped including glass panel
for triggering and test key for checking that device is functioning.
MCP 545X-1:
suitable for use indoors and for surface mounting,
any cable inlets required must be drilled.
MCP 545X-2:
suitable for use indoors and is fitted straight into a
standard size 1 (round or square) countersunk mounting
case.
MCP 545X-3:
suitable for use outdoors and for surface mounting
(protection class IP 67). Cables are fed in using an M 20
M 20 connection joint from below or above. 2 pcs. M 20
connection joints and 2 pcs. blanking stoppers, as well as
the fitting screws are supplied as standard.
Operating voltage:
7 to 31 VDC
Quiescent current:
max. 120 A at 30 VDC
Alarm current:
2,5 mA
Connection:
Integral X-LINE
Terminals:
Screw clips, max. 2,5 mm
Signal transmission:
serial, 2 wire technology
Protection category:
MCP 545X-1/2: IP 24
MCP 545X-3: IP 67
Ambient temperature:
-20 to +50C
Dimensions:
MCP 545X-1:
93 x 89 x 59,5 mm (HxWxD)
MCP 545X-2:
93 x 89 x 27,5 mm (HxWxD)
MCP 545X-3:
93 x 97,5 x 71 mm (HxWxD)
Case colour:
red (RAL 3001), yellow (RAL 1006),
blue (RAL 5002)
Case material:
Fibreglass reinforced plastic
Weight MCP 545X-1/2/3:
160 g/110 g/240 g
VdS-Approval:
G210092
CPD-Approval:
0786-CPD-20998
Description

Manual call point red, IP24 with surface


mounting base
Manual call point red, IP24 without base
Manual call point red, IP67 (waterproof)
Manual call point yellow, IP24 with surface
mounting base
Manual call point yellow, IP24 without base
Manual call point yellow, IP67 (waterproof)
Manual call point blue, IP24 with surface
mounting base
Manual call point blue, IP24 without base
Manual call point blue, IP67 (waterproof)
Back panel for surface mounting
Transparent cover
Cover seal
Plastic triggering element
Replacement glass for MCP 545X
Replacement test key

B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

Type

Art. No.

MCP545X-1R
MCP545X-2R
MCP545X-3R

FG030930
FG030931
FG030932

MCP545X-1Y
MCP545X-2Y
MCP545X-3Y

FG030933
FG030934
FG030935

MCP545X-1B
MCP545X-2B
MCP545X-3B
MUS041W
PS200
P 037
PS210
DKM K GLAS
SC070

FG030936
FG030937
FG030938
FG030332
FG030921
FG030331
FG030920
FG030328
FG030329

53

Integral X-LINE Manual call points

No.: FG020286

54

Manual call point C31 with protection category IP66


Non-automatic detector for use outdoors or in damps rooms (Type B
according to EN 54-11). The manual call point contains a 560 ohm
integrated resistor, however, both terminating resistors the 19k1 for
connection to the BX-AIM loop circuit module or the 11k8 for connection
to the B3-DCI are not supplied as standard. Built into a robust plastic case
protected from dust and water, suitable for surface mounting and
countersunk mounting. The detector is available with or without an LED
alarm indicator.
Operating voltage:
to max. 30 VDC
Operating current:
55 mA
Terminals:
Screw clips, 0,08 to 2,5 mm
Cable entry points:
2 x M20 x 1,5; diameter: 6 - 12 mm
Protection category:
IP 66
Ambient temperature:
-35 to +60C
Dimensions:
135 x 135 x 61 mm (HxWxD)
Colour:
red RAL 3000
Material:
PC
Weight:
475 g
VdS-Approval:
G206113
CPD-Approval:
0786-CPD-20309
Description

Type

Art. No.

Manual call point C31


Manual call point C31 with LED
Replacement glass panel
Key

C31
C31 LED
C31 GV
DKM SV

FG020285
FG020286
FG020282
FG020289

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Integral X-LINE Modules

7.3

Modules

No.: 20-2100001-01

Input/output module BX-OI3


Contains a relay output with a programmable fail-safe position, two inputs
for monitored querying of potential-free contacts and an optocoupler input
which can be used, if required, for monitoring external voltages. In addition,
the voltage on the loop circuit is internally monitored for undervoltage. The
BX-OI3 is particularly well-suited for connecting special detectors (flame
and line detectors, smoke aspirating systems etc.) using the Integral X-LINE.
Both the addressing of the module and the setting of parameters for
connected special detectors (e.g. how they behave when there is an alarm or
a fault) is carried out via the fire alarm control panel using PC software.
An IP 66 protection class plastic case is used for fitting the module, which
can be fitted with various different cable inlets as required. Shipped including
4 180 Ohm resistors for the monitored inputs. The case must be ordered
separately.
Operating voltage:
12 to 30 VDC
Power consumption:
typ. 550 A
Signal transmission:
serial, 2 wire technology
Relay output:
bistable change-over contact 230 V/2 A,
(max. 60 W)
Monitored inputs:
for potential-free contacts
Optocoupler input:
Querying of potentially-bound signals, or
external voltages from
0 to 30 VDC
Terminals:
Screw clips, maximum 1.5 mm
Short circuit isolator:
integrated
Protection category:
IP 66 with case
Ambient temperature:
-20 to +60C
Rel. air humidity:
5 to 95% without condensation
Dimensions:
67 x 67 x 20 mm
with case: 94 x 94 x 57 mm
Case:
Polystyrol, halogen-free
Colour:
grey RAL 7035
VdS-Approval:
G210133
CPD-Approval:
0786-CPD-21011

B-HB-028EN

Description

Type

Art. No.

BX-OI3 input/output module


IP66 case for loop module
Extension connection joint M 16
Stepped nipple M 20
Lock nut M16

BX-OI3
GEH MOD IP66
MM ANB M16
MM SN M20
MM GM M16

20-2100001-01
FG020234
MM000185
MM000181
MM000186

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

55

Integral X-LINE Modules

No.: 20-2100014-01

Input/output module BX-O2I4


The module contains two potential-free bistable relay outputs for switching
of loads of up to 2A and up to 230V. In the event that loop voltage is lost, a
fail-safe position can be individually programmed for each output. In
additional the module contains 4 primary inputs for querying potential-free
contacts. Every input can be configured with/without cable monitoring, and
moreover the element type "input" or "detector zone" can be assigned for
each input. An IP 66 protection class plastic case is used for fitting the
module, which can be fitted with various different cable inlets as required.
Shipped with 8 pcs 180 Ohm resistors for the monitored inputs, the case
must be ordered separately.
Operating voltage:
Quiescent current:
Signal transmission:
Function:
Relay output:
Monitored inputs:
Terminals:
Short circuit isolator:
Protection category:
Ambient temperature:
Rel. air humidity:
Dimensions:
Case material:
Case colour:
VdS-Approval:
CPD-Approval:

56

12 to 30 VDC
typ. 630 A
serial, 2 wire technology
2 relay outputs
4 primary inputs
bistable change-over contact
230 V/2 A, (max. 60 W)
for potential-free contacts
Screw clips, maximum 1.5 mm
integrated
IP 66 with case
-20 to +60C
5 to 95% without condensation
100 x 67 x 20 mm
with case: 130 x 94 x 57mm
Polystyrol, halogen-free
grey RAL 7035
G211050
0786-CPD-21066

Description

Type

Art. No.

BX-O2I4 input/output module


Case for loop module
Extension connection joint M 16
Stepped nipple M 20
Lock nut M16

BX-O2I4
GEH MOD2 IP66
MM ANB M16
MM SN M20
MM GM M16

20-2100014-01
FG020235
MM000185
MM000181
MM000186

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Integral X-LINE Modules

No.: 20-2100002-01

Input/output module BX-IOM


For controlling monitored devices, which are supplied with power by an
external power supply (e.g. sirens etc.). The module contains a short circuit
resistant monitored output (suitable for continuous operation of fur a
configurable pulse emission with emission time limitation) and a galvanically
isolated input which can be used either as a voltage input or for external
voltage monitoring. In addition, the voltage on the loop circuit is internally
monitored for undervoltage. Both the addressing of the module and the
setting of its parameters, which are set separately for every input, are carried
out using PC software via the fire alarm control panel.
An IP 66 protection class plastic case is used for fitting the module, which
can be fitted with various different cable inlets as required. The case must be
ordered separately.
Operating voltage:
Power consumption:
Signal transmission:
Function:
Terminals:
Monitored output:
Output current:
Quiescent Current:
Optocoupler input:
Short circuit isolator:
Protection category:
Ambient temperature:
Rel. air humidity:
Dimensions:
Case:
Colour:
VdS-Approval:
CPD-Approval:

B-HB-028EN

12 to 30 VDC
430 A
serial, 2 wire technology
1 short circuit resistant monitored output,
1 optocoupler input
Screw clips, maximum 1.5 mm
Loads of 20 to 1k , 3 load ranges
max. 1.3 A short circuit resistant
1 to 15 mA can be set using software
IM1+: 20-30V
VEXT: 20-30V
integrated
IP 66 with case
-20 to +60C
5 to 95% without condensation
67 x 67 x 20 mm
with case: 94 x 94 x 57 mm
Polystyrol, halogen-free
grey RAL 7035
G210132
0786-CPD-21010

Description

Type

Art. No.

BX-IOM input/output module


IP66 case for loop module
Extension connection joint M 16
Stepped nipple M 20
Lock nut M16

BX-IOM
GEH MOD IP66
MM ANB M16
MM SN M20
MM GM M16

20-2100002-01
FG020234
MM000185
MM000181
MM000186

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

57

Integral X-LINE Modules

No.: 20-2100005-01

Input module BX-AIM


Can be configured as a monitored input for querying potential-free contacts
or as a collectively addressable detector zone (DC technology). The
monitored input can, if required, be used as a standard extinguishing
interface in accordance with VdS directives, and furthermore a balancing
function of the fault thresholds for the quiescent current level is also
possible (pursuant to EN 54-13 or VdS 2489). By interconnecting a zener
barrier and by using intrinsically safe detectors it is also possible to monitor
hazardous areas. An IP 66 protection class plastic case is used for fitting the
module, which can be fitted with various different cable inlets as required. It
is shipped incl. the terminal resistor (19k1), but the case must be ordered
separately.
Operating voltage:
Power consumption:
Signal transmission:
Function:
Terminals:
Short circuit isolator:
Protection category:
Ambient temperature:
Rel. air humidity:
Dimensions:
Case:
VdS-Approval:
CPD-Approval:

58

12 to 30 VDC
without DC branch: typ 460 A
with DC branch: typ. 1800 A
serial, 2 wire technology
DC branch module, monitored input
Screw clips, maximum 1.5 mm
integrated
IP 66 with case
-20 to +60C
5 to 95%, without condensation
67 x 67 x 20 mm
with case: 94 x 94 x 57 mm
Polystyrol, halogen-free, grey RAL7035
G208138
0786-CPD-20601

Description

Type

Art. No.

BX-AIM input module


IP66 case for loop module
Extension connection joint M 16
Stepped nipple M 20
Lock nut M16

BX-AIM
GEH MOD IP66
MM ANB M16
MM SN M20
MM GM M16

20-2100005-01
FG020234
MM000185
MM000181
MM000186

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Integral X-LINE Modules

No.: 20-2100003-01

Input module BX-IM4


For indication and monitoring of various types of acknowledgements, e.g.
door contacts, fire zones, extinguishing systems, sprinkler messages, etc. The
module contains 4 inputs for monitored and non-monitoring querying of
potential-free contacts, which are suitable for processing switching states of
longer than 330ms. Both the addressing of the module and the setting of its
parameters, which are set separately for every input, are carried out using PC
software via the fire alarm control panel. An IP 66 protection class plastic
case is used for fitting the module, which can be fitted with various different
cable inlets as required. Shipped with 8 pcs 180 Ohm resistors, the case must
be ordered separately.
Operating voltage:
Power consumption:
Signal transmission:
Function:
Terminals:
Short circuit isolator:
Protection category:
Ambient temperature:
Rel. air humidity:
Dimensions:
Case:
Colour:
VdS-Approval:
CPD-Approval:

B-HB-028EN

12 to 30 VDC
typ. 450 A
serial, 2 wire technology
4 inputs for monitored or non-monitored
querying of potential-free contacts
Screw clips, maximum 1.5 mm
integrated
IP 66 with case
-20 to +60C
5 to 95%, without condensation
67 x 67 x 20 mm
with case: 94 x 94 x 57 mm
Polystyrol, halogen-free
grey RAL 7035
G210131
0786-CPD-21009

Description

Type

Art. No.

BX-IM4 input module


IP66 case for loop module
Extension connection joint M 16
Stepped nipple M 20
Lock nut M16

BX-IM4
GEH MOD IP66
MM ANB M16
MM SN M20
MM GM M16

20-2100003-01
FG020234
MM000185
MM000181
MM000186

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

59

Integral X-LINE Modules

No.: 20-2100016-01

Input module BX-I2


The module contains a primary input for querying a potential-free contact.
This input can be inverted as well as being configured with/without cable
monitoring, and moreover the element type input or detector zone can be
assigned. In addition, the module possesses an optocoupler input for
monitoring a potentially-bound signal or an external power supply. This can
be inversely configured. An IP 66 protection class plastic case is used for
fitting the module, which can be fitted with various different cable inlets as
required. Shipped with 4 pcs 180 Ohm resistors, the case must be ordered
separately.
Operating voltage:
Power consumption:
Signal transmission:
Function:
Terminals:
Short circuit isolator:
Protection category:
Ambient temperature:
Rel. air humidity:
Dimensions:
Case:
VdS-Approval:
CPD-Approval:

60

12 to 30 VDC
460 A typ.
serial, 2 wire technology
1 primary input
1 optocoupler input
Screw clips, maximum 1.5 mm
integrated
IP 66 with case
-20 to +60C
5 to 95%, without condensation
67 x 67 x 20 mm
with case: 94 x 94 x 57 mm
Polystrol, halogen-free, grey RAL7035
G212023
0786-CPD-21143

Description

Type

Art. No.

BX-I2 input module


IP66 case for loop module
Extension connection joint M 16
Stepped nipple M 20
Lock nut M16

BX-I2
GEH MOD IP66
MM ANB M16
MM SN M20
MM GM M16

20-2100016-01
FG020234
MM000185
MM000181
MM000186

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Integral X-LINE Modules

No.: 20-2100015-01

Output module BX-O1


The module contains a potential-free bistable relay output for switching of
loads of up to 2A and up to 230V (max. 60W). In the event that voltage is
lost in the loop, a fail-safe position can be programmed for the output. An
IP 66 protection class plastic case is used for fitting the module, which can
be fitted with various different cable inlets as required. The case must be
ordered separately.
Operating voltage:
Power consumption:
Signal transmission:
Function:
Terminals:
Short circuit isolator:
Protection category:
Ambient temperature:
Rel. air humidity:
Dimensions:
Case:
VdS-Approval:
CPD-Approval:

B-HB-028EN

12 to 30 VDC
480 A typ.
serial, 2 wire technology
potential-free, bistable relay output
Screw clips, maximum 1.5 mm
integrated
IP 66 with case
-20 to +60C
5 to 95%, without condensation
67 x 67 x 20 mm
with case: 94 x 94 x 57 mm
Polystrol, halogen-free, grey RAL7035
G212024
0786-CPD-21144

Description

Type

Art. No.

BX-O1 output module


IP66 case for loop module
Extension connection joint M 16
Stepped nipple M 20
Lock nut M16

BX-O1
GEH MOD IP66
MM ANB M16
MM SN M20
MM GM M16

20-2100015-01
FG020234
MM000185
MM000181
MM000186

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

61

Integral X-LINE Modules

No.: 20-2100004-01

Relay module BX-REL4


Contains 4 relays each with a potential-free double-throw contact with a
switching capacity of up to 2 A and up to 230 V. The BX-REL 4 is also
suitable for emitting switching impulses. The relay outputs can be switched
to a fail-safe position in the event of voltage loss on the loop circuit, and the
voltage on the loop circuit is also internally monitored for under voltage.
Both the addressing of the module and the setting of its parameters, which
are set separately for every input, are carried out using PC software via the
fire alarm control panel. An IP 66 protection class plastic case is used for
fitting the module, which can be fitted with various different cable inlets as
required. The case must be ordered separately.
Operating voltage:
Power consumption:
Signal transmission:
Function:
Terminals:
Relay output connection:
Leitungslnge:
Short circuit isolator:
Protection category:
Ambient temperature:
Rel. air humidity:
Relay output:
Switching power:
Switching frequency:
Pulse emission:
Dimensions:
Case:
Colour:
VdS-Approval:
CPD-Approval:

62

12 to 30 VDC
typ. 510 A
serial, 2 wire technology
4 potential-free relay outputs
Screw clips, max. 1.5 mm
Screw clips, max. 2.5 mm
max. 100 m
integrated
IP 66 with case
-20 to +60C
5 to 95% without condensation
bistable change-over contact
230V/2 A
60 W (230 V, 0.25 A)
max. 3,125 Hz
200ms- 25 s in 100 ms intervals
100 x 67 x 20 mm
with case: 130 x 94 x 57 mm
Polystyrol, halogen-free
grey RAL 7035
G210134
0786-CPD-21012

Description

Type

Art. No.

BX-REL4 Relay module


Case for loop module

BX-REL4
GEH MOD2 IP66

20-2100004-01
FG020235

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Integral X-LINE Modules

No.: 20-2100007-01

B-HB-028EN

End-position switch BX-ESL


End position switch for deployment in sprinkler monitoring and for
blocking systems. The module contains an optical light barrier which
measures the movement of an activation plunger. The cables are fed into the
unit using PG connection joints, with connection to the loop module being
via 3 screw-type terminals. Both the addressing of the module and the setting
of its parameters are carried out using PC software via the fire alarm control
panel. The BX-ESL is fitted in a plastic case with IP 65 protection class and
is shipped with 2 connection joints.
Operating voltage:
12 to 30 VDC
Power consumption:
without lit LED: 400 A
with lit LED: 1300 A
Signal transmission:
serial, 2 wire technology
Function:
1 optical light barrier
Response Time:
500 ms
Terminals:
Screw clips, maximum 1.5 mm
Short circuit isolator:
integrated
Protection category:
IP 65 with case
Ambient temperature:
-20 to +60C
Rel. air humidity:
5 to 95%, without condensation
Dimensions:
58 x 58 x 34 mm with case
Case:
PA-Taromide (thermoplastic)
Colour:
case red (RAL 3016)
cover black (RAL 9005)
VdS-Approval:
G210130
CPD-Approval:
0786-CPD-21014
Description

Type

Art. No.

BX-ESL End-position switch

BX-ESL

20-2100007-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

63

Integral X-LINE Modules

No.: 20-2100006-01

No.: FG030171

No.: FG030173

Radiogateway BX-RGW
Communications interface between the fire alarm control panel and the
DOW 1171 and SMF 6120 radio controlled smoke detectors. Up to 30 radio
controlled smoke detectors can be connected to a gateway. If the radio
connection between the detector and the gateway is briefly interrupted, then
a diversion via the neighbouring detector will be automatically established to
the next gateway. Both the addressing of the module and the setting of its
parameters are carried out via the fire alarm control panel. The built-in
battery is used for commissioning and for ensuring the power supply during
revision.
Operating voltage:
Power consumption:
Wireless module interface:
Buffer battery:
Frequency range:
Transmission power:
No. of connectible detectors:
Range in buildings:
Aerial:
Protection category:
Ambient temperature:
Rel. air humidity:
Dimensions:
Case:
Colour:
VdS-Approval:
CPD-Approval:

64

12 to 30 VDC
typ. 950 A
20 pin 2 rowed multipoint connector
9V Lithium/Manganese (lifespan > 5 years)
868 to 870 MHz
max. 5 mW
max. 30
up to 40 metre where there is intervisibility
integrated, separate transmitter and receiver
aerials
IP 54 with case
-10 to +55C
5 to 95% without condensation
93 x 70 x 24 mm
with case: 120 x 80 x 57 mm
Polystyrol, halogen-free
grey RAL 7035
applied for
applied for

Description

Type

Art. No.

Radiogateway
Radio module
Battery for radio module
Extension connection joint M 16
Stepped nipple M 20
Lock nut M16

BX-RGW
SPU 6002
BATT FM
MM ANB M16
MM SN M20
MM GM M16

20-2100006-01
FG030171
FG030173
MM000185
MM000181
MM000186

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Integral X-LINE Alarm devices

7.4

Alarm devices

No.: 20-2100009-01

No.: FG020093

No.: 20-2100030-01

B-HB-028EN

Flashing Light BX-FOL


Addressable flashing light for optical signalling of a fire alarm in indoor
areas, suitable for direct connection to the Integral X-LINE. The BX-FOL is
available in red or white, with the flash rate being set using software of DIP
switches.
Operating voltage:
12 to 30 VDC
Alarm current:
max. 3.7 mA @ 24 VDC
Quiescent current:
500 A
Signal transmission:
serial, 2 wire technology
Flashing frequency:
0,5 Hz (slow) or 1 Hz (fast)
Short circuit isolator:
integrated
Protection category:
IP 21c
Ambient temperature:
-10 to +50C
Dimensions:
93 x 54 mm (DxH)
Case colour:
white or red
Case material:
ABS
Weight:
110 g
VdS-Approval:
G210085
CPD-Approval:
0786-CPD-20987
Description

Type

Art. No.

BX-FOL loop flashing light red, red lens


BX-FOL loop flashing light white, red lens
BX-FOL loop flashing light red, orange lens
BX-FOL loop flashing light white, orange lens

BX-FOL-RR
BX-FOL-WR
BX-FOL-RO
BX-FOL-WO

20-2100009-01
20-2100009-02
20-2100009-03
20-2100009-04

Universal parallel indicator BX-UPI


For optical individual or group indication of fire detectors in the event of a
fire in addition to the integrated LED in the detector or the detector base.
The BX-UPI can be used in different line technologies, with controlling and
power supply coming directly over the alarm output of the alarm output of
the fire detector or using a loop module that is suitable for this. The white
plastic case with a red illuminated surface and the electronic circuit board
must be ordered separately.
Operating voltage:
4,5 to 30 VDC
Power consumption:
0,9 mA typ.
Flashing frequency:
1,2 Hz to 3,0 Hz
Connection:
Screw clips, max. 1,5 mm
Protection category:
IP 42
Ambient temperature:
-20 to +60C
Rel. air humidity:
5 to 95 % without condensation
Dimensions:
85 x 85 x 30 mm (HxWxD)
Weight:
ca. 50 g
Description

Type

Art. No.

Parallel indicator case


BX-UPI parallel indicator (PCB)

PIG
BX-UPI

FG020093
20-2100030-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

65

Integral X-LINE Alarm devices

No.: 20-2100008-01

No.: 20-2100010-01

66

Loop sounder BX-SOL


Addressable signal emitter for acoustic signalling of a fire alarm in indoor
areas, suitable for direct connection to the Integral X-LINE. The siren is
shipped in red or white, and 4 different tones and the volume can be set
using DIP switches.
Operating voltage:
12 to 30 VDC
Power consumption:
low: 2,3 mA , high: 4,7 mA @ 24 VDC
Volume:
89 dB (99 dB) 3 dB(A)/m @ 24 VDC
Possible tones:
DIN 1200 ~ 500 Hz (acc. to DIN 33404)
Slow Whoop 500 ~ 1200 Hz (EN 2575)
Continous tone 990 Hz (pulse can be set)
Sweden-tone (150 ms on/ 150 ms off)
Short circuit isolator:
integrated
Protection category:
IP 21c
Ambient temperature:
-10 to +55C
Dimensions:
max. 108 x 91 mm (D x H)
Case colour:
white or red
Case material:
ABS
Weight:
230 g
VdS-Approval:
G210086
CPD-Approval:
0786-CPD-20986
Description

Type

Art. No.

BX-SOL-R Loop siren red


BX-SOL-W Loop siren white

BX-SOL-R
BX-SOL-W

20-2100008-01
20-2100008-02

Base sounder BX-API


For fitting in USB 501-x Integral loop technology detector base for local
acoustic warnings of a fire. The BX-API snaps directly into the detector base
and connects directly to its connector clips. If a detector is activated, then
module BX-API is triggered as well as the alarm message being sent, with the
base-mounted siren emitting an acoustic alarm signal. The volume setting
(LOW or HIGH) is set by means of a DIP switch.
Operating voltage:
15 to 30 VDC
Power consumption:
low: max. 2mA, high: max. 4mA
Connection:
detector base USB 501-x
Tone types:
can be selected by dip switches:
DIN 1200 ~ 500 Hz (acc. to DIN 33404)
slow whoop 500 ~ 1200 Hz (EN 2575)
continuous tone 990 Hz (pulse can be set)
Sweden tone (150 ms on/ 150 ms off)
Volume:
Low 70dB @24VDC @1m @90
High 75dB @24VDC @1m @90
Ambient temperature:
+5C to +40C
VdS-Approval:
applied for
CPD-Approval:
applied for
Description

Type

Art. No.

Base sounder BX-API


Sticker for USB 501 base
with fitted BX-API (36 pcs.)

BX-API

20-2100010-01

S SOSIR

FG27821

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Integral X-LINE Alarm devices

No.: 20-2100011-02

B-HB-028EN

Base sounder BX-SBL501


For signalling a fire alarm in interior rooms (EN 54-3/type A), fitted as a
unit with a USB 501 detector base and directly connected to the X-LINE.
The siren is shipped in white, and four different tones and the volume can
be set using software or by Dip switches. The cable inlet is from above, with
variant BX-SBL501-WDB with a higher base being available for a cable inlet
from the side.
Operating voltage:
12 to 30 VDC
Quiescent current:
max. 0.5 mA
Power consumption:
low: 1.5 mA, high: 4.0 mA @ 24 VDC
Volume:
80 dB (90 dB) 3 dB(A)/m @ 24 VDC
Types of tone:
DIN 1200 ~ 500 Hz (acc. to DIN 33404)
slow whoop 500 ~ 1200 Hz (EN 2575)
continuous tone 990 Hz (pulse can be set)
Sweden tone (150 ms on/ 150 ms off)
Connection:
Screw clips, maximum 2.5 mm
Short circuit isolator:
integrated
Protection category:
IP 31 D
Ambient temperature:
-10 to +55C
Dimensions:
114 x 32 mm (DxH)
114 x 36 mm (DxH) with high base
Case material:
PC-ABS
Case colour:
white RAL 9003
Weight:
ca. 170 g
VdS-Approval:
applied for
CPD-Approval:
applied for
Description

Type

Art. No.

Base sounder BX-SBL501 white


Base sounder BX-SBL501 white (high base)

BX-SBL501-W
BX-SBL501-WDB

20-2100011-02
20-2100011-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

67

Integral X-LINE Alarm devices

No.: 20-2100012-04

No.: 20-2100012-03

68

Platform sounder BX-SBL502


For signalling a fire alarm in indoor areas (EN 54-3/ type A), suitable for
direct connection to the Integral X-LINE. The siren is shipped in red or
white, and four different tones and the volume can be set using software or
by Dip switches. The cable inlet is from above, with variants BX-SBL502WDB and BX-SBL502-RDB with a higher base being available for a cable
inlet from the side.
Operating voltage:
12 to 30 VDC
Quiescent current:
max. 0,5 mA
Power consumption:
low: 1,5 mA, high: 4,0 mA @ 24 VDC
Volume:
80 dB (90 dB) 3 dB(A)/m @ 24 VDC
Types of tones:
DIN 1200 ~ 500 Hz (acc. to DIN 33404)
slow whoop 500 ~ 1200 Hz (EN 2575)
continuous tone 990 Hz (pulse can be set)
Sweden tone (150 ms on/ 150 ms off)
Connection:
Screw clips, maximum 2.5 mm
Short circuit isolator:
integrated
Protection category:
IP 31 D
Ambient temperature:
-10 to +55C
Dimensions:
114 x 32 mm (DxH)
114 x 36 mm (DxH) with high base
Case material:
PC-ABS
Case colour:
white RAL 9003
Weight:
ca. 165 g
VdS-Approval:
G211029
CPD-Approval:
0786-CPD-21065
Description

Type

Art. No.

Platform sounder BX-SBL502 white


Platform sounder BX-SBL502 white high
Platform sounder BX-SBL502 red
Platform sounder BX-SBL502 red high

BX-SBL502-W
BX-SBL502-WDB
BX-SBL502-R
BX-SBL502-RDB

20-2100012-04
20-2100012-02
20-2100012-03
20-2100012-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Integral X-LINE Testing devices & Accessories

7.5

Testing devices & Accessories

No.: FG030200

No.: FG030209

Universal telescopic bar UTP


Locking telescopic bar, suitable for all Schrack detector removers and testing
equipment. Available with a length of three or four metres, with the range of
the telescopic bar can be increased by 1.5 m to 6 m or 7 m respectively using
the 1.3 m extension.
Transport length UTP 3:
1,7 m installation heights of up to 4,5 m
Transport length UTP 4:
2,2 m installation heights of up to 5,5 m
Weight:
UTP 3: 1 kg, UTP 4: 1,2 kg
Description

Type

Art. No.

Universal telescopic bar 3m


Universal telescopic bar 4m
1.3m extension for UTP 3 & 4

UTP3
UTP4
UTP V

FG030200
FG030201
FG030208

Telescopic bar UTP 30kV


Telescopic bar with voltage sustaining capability of up to 30kV, for
installation heights of up to 4.5m. Suitable for use with all Schrack detector
removers and testing devices.
Transport length UTP3 30KV: 1,7 m for installation heights of up to 4,5 m
Transport length UTP10 30KV: 1,7 m for installation heights of up to 11 m
Weight:
UTP3 30KV: 2,2 kg, UTP10 30KV: 3,9 kg
Description

Type

Art. No.

Universal telescopic 3m 30kV


Universal telescopic 11m 30kV

UTP3 30KV
UTP10 30KV

FG030209
FG030210

Test gas for smoke detector


Suitable for function test from automatic smoke detectors. The test aerosol
does not contain halogenated hydrocarbons (CFCs or similar). The FDT 533
holder with trigger mechanism is used to hold the test gas bottle.
No.: FG030202 with FG030117

No.: FG030240

No.: FG030241

B-HB-028EN

Description

Type

Art. No.

Test gas 918/5 for smoke detectors


Holder unit for testing gas

PRUEFGAS
FDT 533

FG030117
FG030202

Detector remover tool UDR 533


For fitting MTD 533 multiple sensor detectors to or removing them from
USB 501 detector bases.
Detector removers UDR 533S and UDR 533K can be fitted on to UTP
series telescopic bars, with the UDR 533K detector remover also being
suitable for remote fitting and removal of the detector thanks to its cardan
joint.
The UDR 533A adapter can be placed in the UDR 531K detector remover
(for 531 detector series).
Dimensions
Weight
UDR 533A
62 x 71 x 98 mm
150 g
UDR 533S
100 x 100 x 232 mm
200 g
UDR 533K
160 x 170 x 232 mm
530 g
Description

Type

Art. No.

Detector remover tool UDR 533A


Detector remover tool UDR 533S
Detector remover tool UDR 533K
Replacement rubber for UDR 533

UDR 533A
UDR 533S
UDR 533K
UDR 533 G

FG030240
FG030241
FG030242
FG030243

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

69

Integral X-LINE Testing devices & Accessories

No.: FG030280

No.: FG030282

No.: FG030284

70

Detector testing device TESTIFIRE 1001


Combination testing device for smoke and temperature testing of automatic
fire detectors. Thanks to the combination of different functions in a single
device, it is possible to test not only optical smoke detectors, but also
temperature detectors (maximum temperature or temperature change) and
multiple sensor detectors simply and efficiently. The device is battery
operated and is completely user friendly and environmentally friendly. The
testing agent required for the smoke and temperature test is contained in a
cartridge that can be easily replaced. Two cylindrical batteries and a charger
are supplied as standard, and the device can be fitted on to UTP series
telescopic bar using the Adapter UTP SOL.
Electrical Power Source:
Rechargeable battery pack 7.2V / 2.2 Ah
NiMH battery
Battery charging time:
75-90 min. (if fully uncharged)
Operating temperature:
+5C to +45C
Protection category:
IP 20
Weight:
0,75 kg
Dimensions:
224 x 153 mm (H x D)
Description

Type

Art. No.

TESTIFIRE 1001 detector testing device


Adapter for telescopic bar
Smoke cartridge for Testifire (spare part)
Replacement battery pack for Testifire
Quick charger for Testifire (spare part)

TESTIFIRE 1001
UTP SOL
TS3
SOLO 720
SOLO 725

FG030280
FG030281
FG030282
FG030283
FG030284

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Integral X-LINE Testing devices & Accessories

No.: FG052606

No.: 50-1000004-01

No.: 20-1400320-01

B-HB-028EN

Loop Assistant Interface B6-LAI


With the Loop Assistance Interface, a service PC and the necessary software
are all present, it is possible to check and program (assignment of logical
addresses) Integral X-LINE on-site even if there is no fire alarm control
panel. The programming is saved on the service PC and then transferred to
the fire alarm control panel thereafter. The device consists of a case,
modules, main processor unit, power supply unit, operating panel and
batteries (to permit operation for up to 4 hours) and is supplied in a red
impact-resistant plastic case including a power connection cable.
Connection:
max. two loop circuits each with
max. 250 elements
Programming connection:
Service PC over USB
Range:
max. 10 m
Batteries:
24 V / 1,2 Ah
Protection category:
IP 20
Ambient temperature:
-5 to +50C
Dimensions:
440 x 310 x 100 mm (HxWxD)
Weight:
8 kg
Description

Type

Art. No.

B6-LAI LoopAssistant Interface


USB cable 3 m
USB cable 4.5 m

B6-LAI
KAB USB 3
KAB USB 45

FG052606
FG022051
FG022052

Loop circuit testing device STB 01X


Portable device used to simply check an installed Integral loop circuit or
X-LINE without a fire alarm control panel being attached. Data for up to
1,000 loop circuits can be saved on the built-in SD memory card and then
supplied in XML data format using a converter. Supplied including an SD
memory card, a USB cable for firmware updates and a power supply unit,
but the carrying case must be ordered separately.
Mains supply voltage:
230 VAC
Operating voltage:
20 to 30 VDC
Operating voltage loop:
12 VDC or 24 VDC
Quiescent current:
110 mA (without external devices)
Terminals:
1,5 mm can be connected
Protection category:
IP 20
Ambient temperature:
+5C to +40C
Case:
Polyamid, black-grey similiar to RAL 7021
Dimensions:
220 x 116 x 60 mm (HxWxD)
Weight:
480g (without power supply)
Description

Type

Art. No.

Testing device for X-LINE (German labelling)


Testing device for X-LINE (English labelling)
Case for STB01X

STB 01X-D
STB 01X-E
STB01X CASE

50-1000004-01
50-1000004-02
20-1400320-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

71

Integral X-LINE Testing devices & Accessories

Protective Cage
White painted metal protective cage for preventing detectors from sustaining
physical damage. Suitable for all automatic detectors.
Dimensions:
160 x 110 mm (DxH)
No.: FG020026

No.: FG020189

No.: MM000250

72

Description

Type

Art. No.

Protective cage f. detectors

SKORB

FG020026

Rubber cap for detector base


Rubber cap made of transparent silicone to protect the USB-501 detector
base against moisture. The rubber cap is placed over the USB 501 detector
base prior to fitting, in particular in areas where there are difficult
environmental conditions where condensation water and moisture can
quickly form, in order to prevent moisture from getting into the base.
Description

Type

Art. No.

Transparent rubber cap

G KAPPE 501

FG020189

Fitting set for rubber cap


Consisting of a fitting clip, 2 fixed distance pieces and two M4 x 16 cheese
head screws for fitting detector bases in damp rooms. Supplied without a
detector base and without a rubber cap.
Description

Type

Art. No.

Fitting set for rubber cap

MON SET GK

MM000250

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Integral X-LINE Testing devices & Accessories

No.: FG020480

No.: FG020205 & FG020206

No.: FG020520

B-HB-028EN

Detector heater for USB 501


The detector heater allows the MTD 533 CP multiple sensor detectors with
the USB 501 detector base in critical atmospheric conditions, e.g. where
there is a risk of icing up or dew formation, in cold stores, walk-in freezers,
collectors, attics, cheese cellars, power stations, loading bays etc. By fitting
the detector heater the temperature of the detector is increased by about 5C
in comparison with the ambient temperature. An external power supply unit
must be used to supply the detector heater with power, as the unit cannot be
supplied directly from the loop. The detector heater is controlled using the
base terminal block for the USB501, with the unit being fastened in the
detector base using cable ties.
Operating voltage:
20 to 30 VDC
Residual ripple:
max. 2V
Operating current:
35 to 55 mA
Wattage:
1.2 W
Resistance:
580
Wire diameter / terminal:
2 x 0.5 to 2.5 mm
Ambient temperature:
-30C to +40C
Description

Type

Art. No.

Detector heater
Isolating point terminal block for USB501
Adhesive cable tie holder

DBZ1190A-AC
KL USB501
MM KBH KL

FG020480
FG030132
MM000047

Baffle plate for riser cable shafts


Hot-dip galvanized 1.2 mm thick sheet steel for improving detection
properties of smoke detectors in riser cable shafts, including drill holes for
fitting and cable inlet for installation.
Dimensions FG020205:
130 x 130 mm
Dimensions FG020206:
300 x 300 mm
Description

Type

Art. No.

Baffle plate 130 x 130 mm


Baffle plate 300 x 300 mm

STBLECH
STBLECH G

FG020205
FG020206

Detector fitting console MMK 200/350


The console can be tilted from 0 to 90 and height can be adjusted between
200 and 350 mm. The detector is attached using 2 M4 screws. Both USB 501
and Hochiki bases can be fitted on to the console. Supplied without
detector.
Adjustable height:
200 to 350 mm with 4 mm Allen key
Angle of tilt:
0 to 90 with 3 mm Allen key
Material:
Sheet steel, powder coated
Colour:
light grey (RAL 7035)
Dimensions:
175 x 105 x 200 to 350 (HxWxD)
Description

Type

Art. No.

Detector fitting console

MMK 200/350

FG020520

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

73

Special detectors Linear smoke detectors

8 Special detectors
8.1

Linear smoke detectors

No.: FG020073

No.: FG020125

No.: FG020126

74

Linear smoke detector SPC-E


The linear smoke detector SPC-E comprises of a transmitter and receiver
unit, which are fitted opposite one another between 5 and 100 m away from
each other. In the event of a fire, the rising smoke reduces the intensity of
the infrared ray between the transmitter and receiver and an alarm is sent to
the fire alarm control panel. The SPC-E is particularly reliable where the
ambient temperature or air humidity is constantly changing and is simple to
install and configure.
Operating voltage:
15 to 33 VDC
Quiescent current:
250 A max.
Alarm current:
50 mA max.
Monitoring length:
5 to 100 m
Signal processing:
8-Bit micro processor
Sensitivity:
levels can be set: 25%, 50%, 60%
Indicators:
LEDs for operation, fault and alarm
Compensation:
Contamination of the optical sensor
compensated to 1% every half hour
Protection category:
IP 42
Ambient temperature:
-10 to + 50C
Max. Air Humidity:
95 % non-condensing
Colour:
white
Dimensions:
86 x 100 x 145 (transmitter and receiver)
Weight:
Receiver: 685 g
Transmitter: 600 g
VdS-Approval:
G207152
CPD-Approval:
0832-CPD-0547
Description

Type

Art. No.

Linear smoke detector SPC-E


Wall mounting joint:
Ceiling mounting joint:

SPC-E
BEAM WH SPBC
BEAM DH SPBC

FG020073
FG020125
FG020126

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Linear smoke detectors

Linear smoke detector ILIA

No.: 20-3000100-01

No.: 20-3000101-01

No.: 20-3000120-01

For detecting fires in areas where spot detectors cannot be used (e.g. in production halls, churches, warehouses, railway stations etc.) The system is available in 2 versions:
Transmitter and receiver ILIA S/E
Combined transmitter and receiver unit with reflector ILIA S/R
Devices are connected to the fire alarm control panel using a control unit,
where all settings, as well as testing and maintenance work can be carried out.
In the basic version it is possible to connect 2 systems, while the interconnection of a total of 8 systems is possible using an extension circuit board. All
ILIA systems are equipped with an integrated seamlessly adjustable shade,
which can be used in difficult optical conditions (e.g. where there is direct
parallel solar radiation, strong reflections or secondary light). For use in difficult atmospheric conditions (e.g. with particularly high concentration of dust),
both systems are also available as ILIA DUST versions. These devices are
particularly non-sensitive towards faults occurring due to dust and steam, and
to a certain extent contamination is compensated for.
Operating voltage:
1 detector
Quiescent Current:
Alarm Current:
8 detectors
Quiescent Current:
Alarm Current:
Monitoring length:
Transmitter/receiver system:
Transmitter/reflector system:
Monitoring area:
Monitoring width:
Misalignment tolerance:
Ambient temperature:
Cable:
Maximum cable length:
Dimensions:
Detector (transmitter/receiver):
Control unit:
Protection category:
Weight:
Colour:
VdS-Approval:
CPD-Approval:

B-HB-028EN

12 to 24 VDC
48 mA to 98 mA
50 mA to 100 mA
261 mA to 502 mA
270 mA to 512 mA
10 to 200 m
10 to 150 m
max. 1600 m per detector
max. 15 m
up to 1 for transmitter (Tx) and
receiver (Rx)
-20C to +65
0.5 mm with 4 cores
1200 m
162 x 145 x 193 mm
145 x 177 x 68 mm
IP 65
Detector:
ca. 780g
Control unit: ca. 375g
blackish blue RAL 5004
G209195
0786-CPD-20925

Description

Type

Art. No.

Linear smoke detector ILIA S/R


Linear smoke detector ILIA S/E
Controller for ILIA
Extension module for controller
Linear smoke detector ILIA DUST S/R
Linear smoke detector ILIA DUST S/E
Controller for ILIA DUST

ILIA S/R
ILIA S/E
CSRLS-2
RL6
ILIA DUST S/R
ILIA DUST S/E
CSRLS-2-C-DUST

20-3000100-01
20-3000101-01
20-3000120-01
20-3000121-01
20-3000110-01
20-3000111-01
20-3000122-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

75

Special detectors Linear smoke detectors

No.: FG020373

No.: FG020390

No.: FG020254

76

Linear smoke detector ARDEA for hazardous areas


Its construction and principle functions are the same as those of standard
linear smoke detectors, but the detector also reacts particularly well to fires
in their earliest stages containing hydrocarbon-based propellants, plastic and
rubber mixtures and is suitable and approved for monitoring areas where
there is a risk of explosion.
Operating voltage:
12 to 24 VDC 20%
Quiescent current @ 24V:
37 mA (low), 58 mA (high)
Alarm current @24V:
62 mA (low), 84 mA (high)
Monitoring length:
5 to 100 m
Protection category:
IP 66 (with cable clamps)
Ambient temperature:
-10 to +65C
Case:
Aluminium
Dimensions with bracket:
365 x 241 x 215 mm
Dimensions without bracket:
220 x 190 x 170 mm
Weight:
Transmitter and Receiver 4.6 kg each
ATEX approval:
INERIS 02 ATEX 0090X
Description

Type

Art. No.

Linear smoke detector ARDEA S EX

ARDEA S EX

FG020373

Linear Smoke Detector ECO ES50


Consisting of a combined transmitter/receiver unit and reflector, which are
fitted at a distance of between 2 and 50 metres opposite one another. The
infrared beam that is emitted by the transmitter is bounced back by the
reflector and evaluated. The unit is fitted as standard directly on the wall,
using a jointed mounting bracket on diagonally sloping or walls that are not
flat. A reflector and an SSM jointed mounting bracket are supplied.
Operating voltage:
12 to 24 VDC 20%
Quiescent current @ 24V::
up to 25 m distance: 19 mA
up to 50 m distance: 39 mA
Alarm current @ 24V:
up to 25 m distance: 32 mA
up to 50 m distance: 52 mA
Contact rating:
Alarm relay: 1 A @ 30 V
Fault relay: 170mA at 30V
Maximum cable length:
1000 m with 0.8 mm cables, 2000 m with
1.0 mm cables.
Monitoring length:
2 to 50 m (2 switch positions)
Monitoring width:
15 m in accordance with EN54-14
Protection category:
IP 44
Ambient temperature:
-20 to +60C
Rel. air humidity:
95%
Dimensions without fixing joint: 103 x 110 x 63 mm
Dimensions with fixing joint:
103 x 110 x 119 mm
Case material top:
Polycarbonate / ABS
Case colour:
white RAL 1013
Weight (without fixing joint):
360 g
VdS-Approval:
G205128
CPD-Approval:
0786-CPD-20214
Description

Type

Art. No.

Linear smoke detector ECO ES50


Jointed mounting bracket (2 pcs.)
Test filter
Reflector for ECO (spare part)

ECO ES50
SSM
STF4
MBK40

FG020390
FG020254
FG020398
FG020259

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Linear smoke detectors

No.: FG020393

Linear smoke detector ECO ES80


Consisting of a combined transmitter and receiver unit and a prism reflector.
Both devices are usually fitting of facing walls without further accessories at
a distance of between 10 to 80 m, although, if required (e.g. diagonal fitting,
curved walls etc.) additional special stable ball and socket joints can be used
to ensure precise fitting. The infrared beam that is emitted by the transmitter
is bounced back by the reflector and evaluated by the receiver. This is done
by measuring the absorption of the infrared beam and of the smoke or fire
modulation.
Operating voltage:
Quiescent current @ 24V:
Alarm current @ 24V:
Contact rating:

12 to 24 VDC 20%
19 mA to 39 mA (10 to 80 m)
32 mA to 52 mA (10 to 80 m)
Alarm relay: 1 A @ 30 V
Fault relay: 170mA at 30V
Maximum cable length:
1000 m with 0.5 mm cables, 2000 m with
1.0 mm cables.
Monitoring length:
10 to 80 m
Monitoring width:
15 m in accordance with EN54-14
Protection category:
IP 44
Ambient temperature:
-20 to +60C
Rel. air humidity:
95%
Dimensions without fixing joint: 103 x 110 x 63 mm (transmitter+reflector)
Dimensions with fixing joint:
103 x 110 x 119 mm (transmitter+reflector)
Case material top:
Polycarbonate / ABS
Case colour:
white RAL 1013
Weight (without fixing joint):
360 g
VdS-Approval:
G205128
CPD-Approval:
0786-CPD-20214

No.: FG020392

B-HB-028EN

Description

Type

Art. No.

Linear smoke detector ECO ES80


Jointed mounting bracket (2 pcs.)

ECO ES80
SSM

FG020393
FG020254

Linear smoke detector ECO ES25-I


The unit is largely the same as the ECO ES50, but is intended for being built
into a wall (countersunk installation). This version is shipped with the jointed
mounting bracket for fitting the reflector as standard.
Case:
blue, similar to RAL 5017
Front panel:
black
Dimensions without fixing joint: 136 x 140 x 73 mm
Weight:
ca. 350 g
VdS-Approval:
G205128
CPD-Approval:
0786-CPD-20214
Description

Type

Art. No.

Linear smoke detector ECOES25-I

ECO ES25-I

FG020392

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

77

Special detectors Linear smoke detectors

No.: 11-3000006-01

No.: 11-3000001-01

No.: 11-3000003-01

No.: 11-3000004-01

No.: 11-3000005-01

No.: 11-3000002-01

78

Linear smoke detector BSD 535


The BSD 535 linear smoke detection system consists of a
transmitter/receiver unit and a reflector which is fitted on the opposite wall.
The infrared beam that is emitted by the transmitter is bounced back by the
reflector and evaluated for obscuration.
The distance between the detector and the reflector can be between 3 m and
100 m. The programming and commissioning is carried out directly from the
detector or using the BRC 535 operating device, with the optical alignment
using knurled screws and a temporarily visible light beam.
Operating voltage:
12 to 30 V DC
Quiescent current:
15 mA typ. (at 24 V DC)
Monitoring length:
3 to 100 m
Outputs:
Relay for alarm and faults
Contact rating relay:
30 V DC / 1 A
Case:
ABS white, RAL 9016
Protection category:
IP 31
Ambient temperature:
-10 to 55 C
Dimensions:
BSD 535:
160 x 170 x 150 mm
BAB 535:
176 x 130 x 65 mm
1 reflector:
100 x 102 x 20 mm
4 reflectors:
204 x 200 x 20 mm
Weight:
ca. 1 kg
VdS-Approval:
G210082
CPD-Approval:
0333-CPD-075019
Description

Type

Art. No.

Linear smoke detector BSD 535


incl. 1 x BRE 535 reflector
Jointed mounting bracket for BSD 535
Remote control unit for BSD 535
Extension reflector for BSD 535
Extension reflectors for BSD 535 (3 pcs.)
Protective shade BRP 535
for affixing to reflector BRE 535
Reset Unit for BSD 535

BSD 535

11-3000006-01

BAB 535
BRC 535
BRE 535-1
BRE 535-3
BRP 535

11-3000001-01
11-3000002-01
11-3000003-01
11-3000003-03
11-3000004-01

BRU 535

11-3000005-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Aspirating smoke detectors

8.2

Aspirating smoke detectors

No.: FG030800

No.: FG030801

No.: FG030802

No.: FG030803

B-HB-028EN

Aspirating smoke detector AirSCREEN ASD 535


Active linear smoke aspirating system, consisting of one or two independent
aspirating lines, each with a smoke sensing element with one built-in smoke
sensor for monitoring rooms and establishments. A high performance fan
transports the air from the room to be monitored through the aspirating line
into the evaluation unit, where an increase in the smoke concentration is
detected immediately. The aspirating line is constantly monitored for a pipe
break and contamination. For every aspirating line three pre-alarms and one
main alarm can be programmed, which are transmitted to the fire alarm
control panel either over potential-free contacts or the loop circuit. The
indicator and operating panel displays the smoke concentration of the
aspirated air, as well as all alarm, fault and status messages. The ASD 535
also contains four connection slots, in which relay and interface modules can
be fitted. The smoke sensors (not supplied as shipped) are available with
different classes of sensitivity and can also be adapted to the environmental
conditions.
Using an ABS aspirating pipe and the corresponding accessories the devices
can also be used in areas where there are low temperatures (deep freeze
areas).
The "PipeFlow" software can be used to calculate asymmetrical aspirating
lines, with the PC commissioning software "ASD Config" being used for the
commissioning of larger systems.
Operating voltage:
10,5 to 30 VDC
Quiescent current:
290 mA @ 24 VDC
Alarm current:
385 mA @ 24 VDC
Relay outputs:
3 freely programmable,
potential-free contacts
Additional modules (max. 4)
SLM 35, MCM 35, 2x RIM 35
Sensitivity range:
see SSD 535
Aspirating pipes:
ABS and hard PVC
Cable entry points:
4 x M20, 1 x M25
Pipe lengths:
max. 2 x 240m pursuant to EN 54-20
Pipe diameter:
25 mm external diameter
Fan:
radial, 5 different rotation speed levels
Aspirating pressure:
> 400 Pa (level 5)
Aspirating noise:
43 dB(A) (standard setting)
Protection category:
IP 54
Ambient temperature:
-30 to +60C
Case material:
ABS, UL 94-V0
Case colour:
grey RAL 280 7005 & RAL 300 2005
Dimensions:
397 x 263 x 146 mm (HxWxD)
Weight:
3,8 kg
VdS-Approval:
G208154
CPD-Approval:
0786-CPD-20600
Description

Type

Art. No.

AirSCREEN ASD 535-1 (1 aspirating pipe)


AirSCREEN ASD 535-2 (2 aspirating pipes)
AirSCREEN ASD 535-3
1 aspirating pipe with smoke level indicator
AirSCREEN ASD 535-4
2 aspirating pipes with smoke level indicator

ASD 535-1
ASD 535-2
ASD 535-3

FG030800
FG030801
FG030802

ASD 535-4

FG030803

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

79

Special detectors Aspirating smoke detectors

Spare parts for ASD 535

80

Description

Type

Art. No.

PCB for ASD 535-1 and ASD 535-3

AMB 35-1

FG030830

PCB for ASD 535-2 and ASD 535-4

AMB 35-2

FG030831

Airflow sensor including connection cable

AFS 35

FG030833

Ventilator unit for ASD 535

AFU 35

FG030834

Standard Indicator Panel for ASD 535

BCB 35

FG030835

Enhanced Indicator Panel for ASD 535

ACB 35

FG030836

Module holder UMS 35

UMS 35

FG030826

Protective grating against insects for ASD535

IPS 35

11-2300012-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Aspirating smoke detectors

No.: FG030810

No.: FG030811

No.: FG030812

No.: FG030821

No.: FG020325

B-HB-028EN

Smoke detector SSD 535 for ASD 535


Highly sensitive HD sensor using the scattered light principle for use in the
various ASD 535 models. The sensor is designed to optimally fulfil the
requirements of a smoke detection in conjunction with a aspirating smoke
detector. The threshold sensitivity of the smoke sensor can be set anywhere
in the given range.
High power LED with lowest air resistance and highest resistance
against contamination.
Compares sample parameters for fires
Intelligent alarm buffering
Alarm threshold tracking with two level contamination indicator
Dynamic particle suppression for detection and fading out of dust
particles
Auto learning function for critical atmospheric conditions
Operating voltage:
5 V DC
Protection category:
IP 44
Alarm sensitivity range:
SSD 535-1:
0.5 to 10 %/m
SSD 535-2:
0.1 to 10 %/m
SSD 535-3:
0.02 to 10 %/m
Pre-signal sensitivity:
0.002 to 10 %/m
Ambient temperature:
-30 C to +60 C
Dimensions:
145 x 120 x 95 mm (HxWxD)
Case colour:
grey
Description

Type

Art. No.

Smoke detector SSD 535-1 for ASD 535


Smoke detector SSD 535-2 for ASD 535
Smoke detector SSD 535-3 for ASD 535

SSD 535-1
SSD 535-2
SSD 535-3

FG030810
FG030811
FG030812

Memory card module MCM 35


Additional module for fitting in the ASD 535 for recording operating data.
The module enables recordings for a long period of time for smoke
concentrations and air flows (sensor 1 and 2) as well as saving event data
every second. A maximum of 251 log files each with 28,800 entries or 251
event files each with 64,000 events can be saved, and a maximum of two
MCM 35 units can be fitted per ASD 535. One SD memory card and a
fitting kit are supplied.
Operating voltage:
5 V DC
Current consumption:
max. 25 mA
Dimensions:
58 x 99 x 17 mm (HxWxD)
Description

Type

Art. No.

Memory card module MCM 35 for ASD 535


SD-card (spare part)

MCM 35
SD-CARD

FG030821
FG020325

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

81

Special detectors Aspirating smoke detectors

No.: FG030820

No.: 11-2200003-01

No.: FG030822

No.: 11-2200000-01

82

Loop module SLM 35


Additional module for connecting the ASD 535 to the Integral loop circuit.
Operation, configuration and querying of data from the ASD 535 can be
carried out directly from the fire alarm control panel. Shipped including
fitting kit.
Operating voltage:
5 V DC
Current consumption:
max. 20 mA
Dimensions:
58 x 95 x 17 mm (HxWxD)
Description

Type

Art. No.

Loop module SLM 535

SLM 35

FG030820

Interface module XLM 35


Additional module for connecting the ASD 535 to the Integral X-LINE
(from version 7.3 of the Integral Software). Operation, configuration and
querying of data from the ASD 535 can be carried out directly from the fire
alarm control panel. Shipped including fitting kit.
Operating voltage:
5 V DC
Current consumption:
max. 20 mA
Dimensions:
58 x 95 x 17 mm (HxWxD)
Description

Type

Art. No.

Interface module XLM 535

XLM 35

11-2200003-01

Relay module RIM 35


Additional module for fitting in the ASD 535 with five relays (potential-free
change-over contacts). The modules guarantees that the three pre-signal
levels as well as the contamination/blockage statuses are available. The relays
can be freely programmed in accordance with any control criteria, while a
maximum of two RIM 35 units can be used per ASD 535. Shipped including
fitting kit.
Operating voltage:
5 V DC
Current consumption:
max. 15 mA
Load for relay contact:
max. 50 V DC/1 A/30 W
Dimensions:
58 x 97 x 17 mm (HxWxD)
Description

Type

Art. No.

Relay module RIM 35

RIM 35

FG030822

Serial interface module SIM 35


For networking several ASD535s using the RS 485 bus. Consequently, using
the "ASD Config" configuration software from a single PC, all the ASD 535
units in the network can be visualised and operated. The SIM 35 ensures
galvanic isolation between the RS 485 interface and the ASD 535. To
visualise all ASD units simultaneously in "ASD Config" the software must be
unlocked using a dongle.
Operating voltage:
5 V DC
Current consumption:
max. 20 mA
Dimensions:
58 x 95 x 17 mm (HxWxD)
Description

Type

Art. No.

Serial interface module SIM 35

SIM 35

11-2200000-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Aspirating smoke detectors

No.: 11-2200001-01

Serial master module SMM 535


Master module for networking several ASD535s using the RS 485 bus. The
SMM 535is connected to a PC using a USB cable and therefore forms the
access point for ASD networking. The "ASD Config" configuration software
is used as the operating interface on the PC. The SMM 535 ensures galvanic
isolation between the RS 485 bus and the USB interface. To visualise all
ASD units simultaneously in "ASD Config" the software must be unlocked
using a dongle.
Operating voltage:
5 V DC
Current consumption:
max. 100 mA
Dimensions:
89 x 82 x 55 mm (HxWxD)
Description

Type

Art. No.

Serial master module SMM 535

SMM 535

11-2200001-01

Software for AirSCREEN ASD 535


The ASD PIPEFLOW calculation software is used for programming an
aspiring line pursuant to EN 54-20.
The ASD CONFIG configuration software is used for commissioning and
configuring the ASD 535.
Prerequisites:
WIN XP/Vista, 1 GB RAM, 50 MB HD

B-HB-028EN

Description

Type

Art. No.

Calculation software ASD PIPEFLOW


Configuration software ASD CONFIG
USB connection cable ASD 535/PC (4,5m)

ASD PIPEFLOW
ASD CONFIG
KAB USB 45

FG030850
FG030851
FG022052

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

83

Special detectors Aspirating smoke detectors

No.: FG030386

No.: FG030387

No.: FG030388

84

Dust filter unit DFU 535L


For installation in the aspirating pipe before the smoke aspirating systems
highly sensitive smoke sensor in mildly dusty environments. Including filter
cartridge, two PVC reduction units from 5/4 to 40 mm and two reduction
units from 40 mm to 25 mm.
Filter area:
1.200 cm
Protection category:
IP 65
Ambient temperature:
0 C to +60 C
Dimensions:
165 x 220 x 220 mm (HxWxD)
Case:
ST 37, black
Diameter of pipe connection: 40 or 25 mm
Dust filter unit DFU 535XL
For installation in the aspirating pipe before the smoke aspirating systems
highly sensitive smoke sensor in normal to extremely dusty environments.
Including filter cartridge, two PVC reduction units from 5/4 to 40 mm and
two reduction units from 40 mm to 25 mm.
Filter area:
3.400 cm
Protection category:
IP 65
Ambient temperature:
0 C to +60 C
Dimensions:
230 x 250 x 250 mm (HxWxD)
Case:
ST 37, black
Diameter of pipe connection: 40 or 25 mm
Description

Type

Art. No.

Air filter cartridges DFU 535L (right stop)


Air filter cartridges DFU 535L (left stop)
Replacement cartridge for DFU 535L
Air filter cartridges DFU 535XL (right stop)
Air filter cartridges DFU 535XL (left stop)
Replacement cartridge for DFU 535XL

DFU 535L-R
DFU 535L-L
DFU 535L EP
DFU 535XL-R
DFU 535XL-L
DFU 535XL EP

FG030386
30-6900014-01
FG030387
FG030388
30-6900014-02
FG030389

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Aspirating smoke detectors

No.: FG030150

No.: FG030379

B-HB-028EN

Individual area detection unit REK 511


For fitting in the individual pipe branches of the aspirating line of the smoke
aspirating system for individual area detection. The alarm state of the
triggered smoke detector is displayed using a Plexiglas stem on the surface of
the case (LED). Shipped including !43 A detector base and 2 pcs. M32
connection joints, the smoke detector of type SSD 515-1S, -2S, or -3S must
be ordered separately (see below for sensitivity).
Operating voltage:
18 to 28 VDC
Quiescent current:
18 to 20 mA
Alarm current:
25 to 30 mA
Suitable smoke detectors:
SSD 515-1S: 1,2%/m (standard)
SSD 515-2S: 0,6%/m (sensitive)
SSD 515-3S: 0,3%/m (high sensitivity)
Connection:
Screw clips, maximum 1.5 mm
Cable inlet:
for cables with diameter of up to 6 mm
Protection category:
IP 53
Ambient temperature:
0 to +50C
Dimensions:
122 x 186 x 85 mm (HxWxD)
Case:
ABS, UL 94-V0; light grey RAL 7035
Weight:
ca. 580 g
Description

Type

Art. No.

Detection unit REK 511


Smoke detector SSD 515-1S
Smoke detector SSD 515-2S
Smoke detector SSD 515-3S

REK 511
SSD 515-1S
SSD 515-2S
SSD 515-3S

FG030150
FG030379
FG030380
FG030381

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

85

Special detectors Aspirating smoke detectors

Standard aspirating line material (PVC)


The aspirating line forms part of the VdS device approval for the ASD 535
(EN 54-20), for which reason only the materials listed hereafter may be used.

86

Description

Type

Art. No.

PVC pipe d25, 5m length

RAS R25

FG020805

PVC arch 90 d25

RAS B9025

FG020806

PVC angle 45 d25

RAS W4525

FG020808

PVC T piece d25

RAS T25

FG020809

PVC cross piece d25

RAS K25

FG020810

PVC coupling d25

RAS M25

FG020811

PVC terminal d25

RAS E25

FG020812

Fastening clamp IKS d25

RAS BSIKS25

MM000023

PVC terminal cap with thread d25

RAS VE25

FG020832

PVC connection coupling d25

RAS VE25M

FG020833

PVC connection joint

RAS V25

FG020829

PVC Clip d25/2.0mm


PVC Clip d25/2.5mm
PVC Clip d25/3.0mm
PVC Clip d25/3.5mm
PVC Clip d25/4.0mm
PVC Clip d25/4.5mm
PVC Clip d25/5.0mm
PVC Clip d25/5.5mm
PVC Clip d25/6.0mm
PVC Clip d25/6.5mm
PVC Clip d25/7.0mm
PVC revision clip d25

RAS CLP 2520


RAS CLP 2525
RAS CLP 2530
RAS CLP 2535
RAS CLP 2540
RAS CLP 2545
RAS CLP 2550
RAS CLP 2555
RAS CLP 2560
RAS CLP 2565
RAS CLP 2570
RAS CLP REV

FG020840
FG020841
FG020842
FG020834
FG020835
FG020836
FG020843
FG020844
FG020845
FG020846
FG020847
FG020837

Small funnel d25

RAS KTR

FG020855

Aspirating set for ceiling mounting


M20 / 36 mm white, PVC

SP M20 PVC-SET

FG020883

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Aspirating smoke detectors

B-HB-028EN

Description

Type

Art. No.

Polywell tube 21.2 mm


only for protection of premises!

RAS SCHL PW21

FG020860

M20 straight quick locking adapter


only for protection of premises !

RAS SCHL SV
M20

FG020861

M20 PVC threaded ring


only for protection of premises!

RAS SCHL GR
M20

FG020862

PVC siphoning rose for PVC pipe d=25

RAS ASR

FG020863

Dust trap d25 160x250x90mm

DTB 25 PC

FG020850

Adhesive 0.5 kg
Adhesive 1 kg

RAS KLK
RAS KLG

FG020800
FG020801

Cleaner 1 Litre

RAS RNG

FG020802

Round brush 8mm

RAS RP8

FG020803

PVC three way ballcock, d=25

MV 25 PVC

FG020867

Filter box large d25 incl. filter, 120x122x85mm


Replacement filter for filter box FG020864

FBL 25 PC
RAS FM FKG

FG020864
FG020865

Water trap

WRB 25 PVC

FG020881

Dust and centrifuge trap

DRB 25 PVC

FG020882

Cartridges for air filter DFU 535L


Replacement cartridge for DFU 535L

DFU 535L
DFU 535L EP

FG030386
FG030387

Cartridge-based air filter DFU 535XL,


for very high levels of dust pollution
Replacement cartridge for DFU 535XL

DFU 535XL

FG030388

DFU 535XL EP

FG030389

REK 511 individual area detection unit

REK 511

FG030150

Smoke detector for REK 511 1.2 %/m


Smoke detector for REK 511 0.6 %/m
Smoke detector for REK 511 0.3 %/m

SSD 515-1S
SSD 515-2S
SSD 515-3S

FG030379
FG030380
FG030381

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

87

Special detectors Aspirating smoke detectors

Material for use in refrigerated areas (ABS)


Refrigerated cold stores down to minus 30 C can be monitored in
accordance with EN 54-20 for address classes B and C, in which instance the
use of ABS plastic is recommended due to its better temperature resistance.
Ultimately the type of piping does not influence how the ASD 434 functions,
however, in cold storage facilities, special sampling points with heating
elements must be used, which prevent the sampling points from getting iced
up. For configuring the ASD 535 in cold storage facilities, the "ASD Config"
software must be used so that the controlling of the heating elements can be
configured.

88

Description

Type

Art. No.

ABS pipe d25, 5m length

RAS R25 ABS

FG020789

ABS arch 90 d25

RAS B9025 ABS

FG020790

ABS angle 45 d25

RAS W4525 ABS

FG020791

ABS T piece d25

RAS T25 ABS

FG020792

ABS coupling d25

RAS M25 ABS

FG020794

ABS terminal d25

RAS E25 ABS

FG020795

Fastening clamp IKS d25

RAS BSIKS25

MM000023

ABS connection joint

RAS V25 ABS

FG020793

ABS aspirating fitting set with heating, red


(aspirating point 5.7 mm corresponds to 3 mm)

HEAT 3.0 ABS

FG020870

ABS aspirating fitting set with heating, blue


(aspirating point 6.1 mm corresponds to 3.5 mm)

HEAT 3.5 ABS

FG020872

ABS aspirating fitting set with heating, green


(aspirating point 6.3 mm corresponds to 4.0 mm)

HEAT 4.0 ABS

FG020873

ABS aspirating fitting set with heating, black


(aspirating point 6.7 mm corresponds to 4.5 mm)

HEAT 4.5 ABS

FG020875

ABS aspirating fitting set with heating, brown


(aspirating point 7.1 mm corresponds to 5 mm)

HEAT 5.0 ABS

FG020877

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Aspirating smoke detectors

B-HB-028EN

Description

Type

Art. No.

ABS cable connection set


for splitting cables when branching pipes

CCF 25 ABS

FG020878

Cable connection box for ASD535

WCU 535PC

FG030840

Silicon stranded wire white


Silicon stranded wire black

SLW 0.5 WT
SLW 0.5 BK

FG020879
FG020880

ABS Adhesive 1kg

RAS KLK ABS

FG020796

ABS cleaner 0.5 kg

RAS RNG ABS

FG020797

Round brush 8mm

RAS RP8

FG020803

ABS three way ballcock, d=25

MV 25 ABS

FG020799

Filter box large d25 incl. filter, 120x122x85mm


Replacement filter for filter box FG020864

FBL 25 PC
RAS FM FKG

FG020864
FG020865

REK 511 individual area detection unit

REK 511

FG030150

Smoke detector for REK 511 1.2 %/m


Smoke detector for REK 511 0.6 %/m
Smoke detector for REK 511 0.3 %/m

SSD 515-1S
SSD 515-2S
SSD 515-3S

FG030379
FG030380
FG030381

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

89

Special detectors Linear heat detectors

8.3

Linear heat detectors

Linear heat detectors are predominantly used in the detection of fires in locations where, due to the aggressive and
critical atmospheric conditions (e.g. high air humidity, extreme temperatures, outdoor areas, aggressive gases, dust
pollution etc.), conventional fire detectors cannot be used, or where, due to the exceptionally large monitoring
length or areas, a very large number of temperature detectors would be required. Possible locations for deploying
the unit are for example in road and rail tunnels, cabling channels, car parks, underground garages, refrigeration
and freezer halls, industrial building protection e.g. conveyor belt systems, production lines, loading ramps,
refineries, incinerator plants, saw works, agricultural areas and many more.

No.: 60-1xx0030-30-05

No.: 60-1xx0150-30

Sensor cable HeatSCREEN MHD 535


The linear heat detector functions based on processing data from a large
number of temperature sensors, which are integrated at regular distances in a
sensor cable. The temperature information is forwarded using the sensor
cable to the evaluation unit(s) at the end of the cable. A possible alarm
occurring is ascertained by comparing pre-defined threshold values and are
transmitted to the fire alarm system or management technology over relays
contacts or digital interfaces.
Rapidest detection due to infrared sensitivity and an HS bus
maximum flexibility in the programming of the sensors regarding
different sensitivities, group formation and cross-networking
clear localisation thanks to fixed sensor positions.
Installation across fire zones
Networking possibility for large buildings
Temperature profile emission
maintenance-free
Threshold characteristics:
Standard gap between sensors:
Maximum cable length:
Maximum quantity of sensors:
Relative air humidity:
Tensile force during laying:
Bending radius:
Length of supply cable:
VdS-Approval:
MHD 535 SD
MHD 535 HD

90

Max./Diff. can be freely set


2 m, 4 m, 7 m, 10 m, 20 m
250 m, 1000 m, 1750 m, 2000 m
(dependent on distance between sensors)
125, 250 (dependent on distance between
sensors)
95 % rel/h
500 N (briefly)
max. 100 mm
max. 200 m
G208190

Outer material
PUR / red
ECTFE / grey

Ambient temperature
-40 to +85C (+95 up to 5h)
-55 to +105C

Description

Type

Art. No.

MHD 535 sensor cable SD 2m


MHD 535 sensor cable SD 4m
MHD 535 sensor cable SD 7m
MHD 535 sensor cable SD 10m
MHD 535 sensor cable SD 20m
MHD 535 sensor cable HD 2m
MHD 535 sensor cable HD 4m
MHD 535 sensor cable HD 7m
MHD 535 sensor cable HD 8m
MHD 535 sensor cable HD 10m
MHD 535 sensor cable HD 20m

MHD535-SD2
MHD535-SD4
MHD535-SD7
MHD535-SD10
MHD535-SD20
MHD535-HD2
MHD535-HD4
MHD535-HD7
MHD535-HD8
MHD535-HD10
MHD535-HD20

60-1020030-30
60-1040030-30
60-1070030-30
60-1100030-30
60-1200030-30
60-1020150-30
60-1040150-30
60-1070150-30
60-1080150-30
60-1100150-30
60-1200150-30

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Linear heat detectors

Evaluation units for MHD 535


All important information is drawn together in the evaluation unit. On the
one hand the temperature values of the sensor cable are queried cyclically
here, on the other hand the threshold values are stored in the evaluation unit
for forming pre-alarm signals or alarms. The alarm can be defined either as
an absolute temperature value (maximum temperature evaluation) or as a
temperature increase within a certain period of time (differential temperature
evaluation). Alarms and temperature information is emitted, depending on
the of sensors using relay contacts, digital interfaces or network. The
following specifications apply to all the evaluation units listed below:
Operating voltage:
10 to 36 VDC
Signal transmission:
potential-free relay contacts
digital interfaces or network
Load capacity of relay contacts: max. 1500 VA (250 VAC / 6 A)
min. 12 V / 0.1 A
Protection class:
IP 65
Ambient temperature:
- 25 to +85C
Relative air humidity:
95% briefly without condensation
70% continuous
Case material:
Polycarbonate
Case colour:
light grey RAL 7035

No.: 60-3700120-30

No.: 60-3600120-30

B-HB-028EN

SSP 535 Standalone Signal Processor


Basic evaluation unit with LED indicators as well as an aggregate alarm and a
fault relay. In addition the alarm and temperature information can be also be
distributed over a RS 232, RS 422 or an optional RS 485 Modbus interface.
Quiescent current:
114 to 154 mA at 24 V DC
Max. current consumption:
134 to 174 mA at 24 V DC
Dimensions:
199 x 149 x 73 mm (HxWxD)
Weight:
920 g

SRG 535 Standalone Response Generator


The SRG 535, in addition to the features of the SSP 535, also has 8 zone
relays, to which individual sensor zones can be assigned. Up to six RCU 535
Relay Control Units each with 32 relay outputs and 4 digital outputs can be
connected for additional zone relays. In addition there are six digital inputs,
over which the external alarm or state information can be collected for alarm
generation.
Quiescent current:
124 to 164 mA at 24 V DC
Max. current consumption:
254 to 356 mA at 24 V DC
Zone relays:
8
Digital inputs:
6
Dimensions:
239 x 159 x 90 mm (HxWxD)
Weight:
1350 g

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

91

Special detectors Linear heat detectors

No.: 60-3400120-30

No.: 60-3500120-30

No.: 60-3300120-00

92

RSP 535 Remote Signal Processor


The RSP 535 is the version of the SSP 535 that can be used in networks for
integration in to the FT-NET. In this case the alarm values are also
transmitted over the FT-NET. The alarm and temperature information can
additionally be sent out over the RS 232 interface.
Quiescent current:
114 to 154 mA at 24 V DC
Max. current consumption:
134 to 174 mA at 24 V DC
Dimensions:
199 x 149 x 73 mm (HxWxD)
Weight:
920 g

RXG 535 Remote Extended Generator


The RXG 535 is the version of the SRG 535 that can be used in networks
for integration in to the FT-NET. In this case the alarm values are also
transmitted over the FT-NET. The alarm and temperature information can
additionally be sent out over the RS232 interface. The RXG 535, in addition
to the features of the RSP 535, also has 8 zone relays, to which individual
sensor zones can be assigned. Up to six RCU 535 Relay Control Units each
with 32 relay outputs and 4 digital outputs can be connected for additional
zone relays. In addition there are six digital inputs, over which the external
alarm or state information can be collected for alarm generation.
Quiescent current:
124 to 164 mA at 24 V DC
Max. current consumption:
254 to 356 mA at 24 V DC
Zone relays:
8
Digital inputs:
6
Dimensions:
239 x 159 x 90 mm (HxWxD)
Weight:
1350 g

RRG 535 Remote Response Generator


The RRG 535 is a relay output unit, which can be operated in the FT-NET.
At the RRG 535 alarm information of the HeatSCREEN MHD 535 linear
heat detector which is also connected in the FT-NET can be centrally sent
out to a fire alarm system. The RRG 535 has 8 zone relays, to which
individual sensor zones can be assigned. Up to six RCU 535 Relay Control
Units each with 32 relay outputs and 4 digital outputs can be connected for
additional zone relays. In addition there are six digital inputs, over which the
external alarm or state information can be collected for alarm generation.
Quiescent current:
124 to 164 mA at 24 V DC
Max. current consumption:
254 to 356 mA at 24 V DC
Zone relays:
8
Digital inputs:
6
Dimensions:
239 x 159 x 90 mm (HxWxD)
Weight:
1350 g

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Linear heat detectors

No.: 60-3100120-00

No.: 60-3200120-00

No.: 60-4450000-00
No.: 60-4451000-00

No.: 60-4350000-00

B-HB-028EN

RAP 535 Remote Acces Point & RSS 535 Remote System Server
The RAP 535 and RSS 535 are central interconnection points for system
information (pre-signals, alarm, sensor and zone state, fault messages), which
can be operated in the FT-NET.
Quiescent current:
114 to 154 mA at 24 V DC
Max. current consumption:
134 to 174 mA at 24 V DC
Dimensions:
199 x 149 x 73 mm (HxWxD)
Weight:
920 g

RCU 535 Relay Control Unit


The RCU 535 can be connected to SRG, RXG and RRG units for extending
the relay outputs. Every RCU 535 has 32 relay outputs and 4 digital inputs.
Quiescent current:
110 mA at 24 V DC
Max. current consumption:
540 mA at 24 V DC
Zone relays:
32 relays, potential-free
Load capacity of relay contacts: max. 1500 VA (250 VAC / 6 A)
min. 12 V / 0.1 A
Digital inputs:
4
Dimensions:
239 x 159 x 90 mm (HxWxD)
Weight:
1270 g

MBI Modbus Interface


The SSP 535 and SRG 535 evaluations units can be optionally be extended
by a Modbus card for data output over the RS 485 Modbus RTU.

FOO Fibre Optic Option


The RSP 535, RXG 535, RRG 535, RAP 535 and RSS 535 evaluation units
can optionally be extended by one or two FOO cards for data transmission
over optic fibre for connection to the FT-NET. This is compulsory for
distances over 1,200 m and recommended in the event of increased EMC
disturbance.
Fibre optic connection:
Multimode fibre 125/62.5 m
ST-plug connector
Description

Type

Art. No.

Evaluation unit RSP 535


Evaluation unit RXG 535
Evaluation unit SRG 535
Evaluation unit SSP 535
Glass fibre interface FOO 535
Full duplex Modbus interface
Half duplex Modbus interface
Relay output unit RCU 535
Relay output unit RRG 535
System transmission unit RAP 535
System transmission unit RSS 535

RSP 535
RXG 535
SRG 535
SSP 535
FOO 535
MBI 535 FULL-DUPLEX
MBI 535 HALF-DUPLEX
RCU 535
RRG 535
RAP 535
RSS 535

60-3400120-30
60-3500120-30
60-3600120-30
60-3700120-30
60-4350000-00
60-4450000-00
60-4451000-00
60-3200120-00
60-3300120-00
60-3100120-00
60-3150120-00

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

93

Special detectors Linear heat detectors

Modules for HeatSCREEN MHD 535


In addition to the evaluation units and the sensor cable there are also
various different modules available for the MHD 535, which guarantee that
they function and increase resistance against external influences. The follow
data apply for all modules listed below:
Operating voltage:
10-20 V DC (over sensor cable)
Protection category:
IP 65
Ambient temperature:
-40 to +85 C
Rel. Air humidity:
f. short periods without condensation 95 %
continuously 70 %
Dimensions:
110 x 75 x 56 mm (HxWxD)
Case material
fibreglass reinforced polyester
Weight
ca. 400 g

No.: 60-2200110-30

No.: 60-2100110-30

No.: 60-2400110-30

No.: 60-2300110-30

No.: 60-2800110-30

No.: 60-2500110-00

94

CFM 535 Connection Filter Module


Connection module for proper connection of two sensor cables, which can
be used both in the installation of longer cable lengths as well as for repair
purposes.
Current consumption
0 mA
CTM 535 Cable Terminator Module
For defined termination of the sensor cable in a stub line.
Current consumption
8.5 mA
SSM 535 Sensor Separator Module
For splitting the sensor cable into several sections; in the event of faults
occurring in one section, the rest of the system remains functional.
Current consumption
8.5 mA
PFM 535 Protection and Filter Module
Is installed as the start of the sensor cable for protecting the sensor cable
from overvoltages (e.g. lightning strike)..
Current consumption
11 mA
CPM 535 Connection Protection Module
For protecting the sensor cable from overvoltages (e.g. lightning strike) for
sensor cables supplied with power from both ends.
Current consumption
0 mA
ECB 535 Earth Connection Box
For protection the evaluation units from overvoltage (e.g. lightning strike).
Current consumption
0 mA
Description

Type

Art. No.

Connection Filter Module CFM 535


Cable Terminator Module CTM 535
Sensor Separator Module SSM 535
Protection and Filter Module PFM 535
Connection Protection Module CPM 535
Earth Connection Box ECB 535

CFM 535
CTM 535
SSM 535
PFM 535
CPM 535
ECB 535

60-2200110-30
60-2100110-30
60-2400110-30
60-2300110-30
60-2800110-30
60-2500110-00

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Linear heat detectors

Accessories for HeatSCREEN MHD 535


For operating, installation and maintenance of the HeatSCREEN MHD 535
linear heat detector the following accessories are available.
Compact Flash Card
Any standard compact flash card can be used in the evaluation units, which
save temperature values, alarms and status information for a longer period of
time. This can make sense in the event that the HeatSCREEN MHD 535 is
not continuously connected to a management system or an evaluation unit.
CMC 535 Fitting Clip
The CMC 535 fitting clip is used for fixing the sensor cable precisely to
ceilings, walls or other surfaces. The sensor cable can then by fitted either
horizontally or upright. The distance between the individual fitting clips
should be max. 1m. Elements of up to 6 mm diameter can be used for fixing
it, e.g. the CMS 511 screwnail anchor.
STE 515 Sensor Testing Device
The threshold characteristics can also be easily checked in high areas (e.g.
tunnels) using the optional STE 515 sensor testing device. To do so a sensor
that is easily recognised thanks to its markings is warmed up, in order to test
the complete chain of reactions all the way to the fire alarm system.

B-HB-028EN

Description

Type

Art. No.

Stainless steel fitting clip


Stainless steel fire safety anchor
MHD 535 demonstration case
Fitting clips (100 pcs.)
Supply cable CCA 535
Programming cable for MHD 535
Anchor with screw CMS 511
Cable grip
Sachet of silica gel
Strain relief set for CTM/CFM
Crimping tool
Cable stripping knife
SD double connection cable SSM
HD double connection cable SSM
Flat connector plug for sensor cable
(spare part)
Transportation lock for MHD 535
Compact flash memory card

CMC 535 T
CMS 535 T DUB
MHD 535 DEMO
CMC 535
CCA 535
KAB RS 232
CMS 511
VAC025
VAC026
VAC050
VAC090
VAC092
MHD535SD-SSM 535
MHD535HD-SSM 535

50-0500003-01
50-0500005-01
60-3250060-19
60-4700970-09
60-6000010-00
60-6000015-00
60-6000022-00
60-6000025-00
60-6000026-00
60-6000050-00
60-6000090-00
60-6000092-00
60-6000141-00
60-6000142-00

VAC902
VAC903
VAC905

60-6000902-00
60-6000903-00
60-6000905-00

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

95

Special detectors Linear heat detectors

No.: FG020355

No.: FG020356

No.: FG020357

No.: FG020368

No.: FG020358

96

Linear Heat Detector LWM1


Temperature sensor cable using the resistance principle for early recognition
of a fire or overheating in narrow proportions by volume or harsh
atmospheric conditions. The system consists of the LWM-1 evaluation unit
and the corresponding sensor cable.
up to 300 m monitoring length (min. 10 m)
Maximum monitoring width: 6 m
Detection based on the absolute temperature or temperature increase
Four LED indicators
Two testing keys and a reset key
Operating voltage:
10 to 30 VDC
Current consumption:
25 mA max.
Input surge current:
< 100mA
Cable length:
10 to 300 m
Protection category case:
IP 65
Ambient temperature:
- 20 to +50C
with special cable: -60C to 175C
Case:
ABS grey, similar to RAL 7035
Dimensions:
120 x 200 x 80 mm (HxWxD)
VdS-Approval:
G205066
Description

Type

Art. No.

Evaluation unit LWM-1


with alarm and fault relay (2 A, 30 VDC )
Blue sensor cable
Basic cable dust and water resistant
Black sensor cable
with nylon coating, acid and alkali resistant
Black sensor cable with steel braiding acid and
alkali resistant
Terminating connection set for sensor cable end
Interconnection set for connecting two
sensor cable sections
Plastic sliding clamp

LWM-1

FG020355

K82017

FG020356

K82021

FG020357

K98166

FG020368

K82024
K82023

FG020358
FG020359

ADW KBRD

FG020925

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Linear heat detectors

No.: FG020900

B-HB-028EN

Linear Heat Detector ADW 511A


Linear temperature detector with temperature change and maximum
temperature processing. The detector works on the principle of a gas
expanding in volume when it get hotter, and the associated increase in
pressure in a pneumatically sealed system.
The ADW 511 consists of a measuring unit and a copper sensor tube
(stainless steel or Teflon tubes are available for use where there are
particularly difficult environmental conditions). Pressure is artificially created
in the sensor tube, with a fully electronic pressure sensor constantly
measuring the absolute pressure in the tube, with a microprocessor carrying
out the evaluation of the results. The sensitivity of the ADW 511 can be set
via a using PC-based software, with disturbance factors such as weatherrelated fluctuations in temperature being filtered out.
Damage to the sensor tube is also recognised, by means of a precisely
defined surplus pressure being created in the sensor tube by means of a test
motor and a pressure pump at regular intervals. Its robust construction
makes the ADW 511 particularly suitable for use in detecting fires in
hazardous areas (in tunnel systems, hazardous areas, industrial applications
etc.).
Operating voltage:
10,5 to 30 VDC
Quiescent current:
90 mA at 24 VDC
Alarm current:
99 mA at 24 VDC
Max. Current consumption:
108 mA at 24 VDC
Connection:
Schraubklemmen, max. 1,5 mm
Protection category Gehuse: IP 65
Ambient temperature:
Auswerteeinheit: - 20 to +50C
Fhlerrohr:
- 40 to +160C
Colour Gehuse:
grey RAL 7000
Dimensions Gehuse:
160 x 160 x 90 mm
Lnge Fhlerrohr:
20 to 80 m
(fr Tunnelanwendungen bis 130 m)
Durchmesser Fhlerrohr:
innen: 4 mm / auen: 5 mm
Weight:
1,7 kg
VdS-Approval:
G200111
Description

Type

Art. No.

Transafe ADW 511 standard processing unit


Copper sensor tube diameter=5/4mm
Stainless steel sensor tube diameter=5/4mm
Teflon sensor tube diameter=5/3mm
ADW 511 test motor
ADW-511 (ADP-51) base plate
Brass cable gland
Brass - terminating stopper
Brass adapter
Plastic sliding clip
Plastic tubing
Stainless steel cable gland
Stainless steel terminating stopper
Stainless steel support sleeve 4 mm
Stainless steel support sleeve 3 mm

ADW 511
ADW CUFR
ADW ESFR
ADW TFFR
ADW PM
ADW ADP51
ADW MV
ADW MEZ
ADW MSH
ADW KBRD
ADW KSCHL
ADW ESV
ADW ESEZ
ADW ESSH1
ADW ESSH2

FG020900
FG020910
FG020911
FG020912
FG020920
FG020921
FG020922
FG020923
FG020924
FG020925
FG020926
FG020927
FG020928
FG020929
FG020930

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

97

Special detectors Flame detectors

8.4

Flame detectors

No.: FG020360

No.: FG020363

No.: FG020361

No.: FG020363

98

Infrared flame detector DF 1191


For detection of liquid and gas fires without smoke formation as well as
open fires with smoke formation, which occur during the combustion of
carbon-based materials such as wood, plastics, gases, oil products etc. The
detector is suitable for simple interior applications, an contains an infrared
sensor, which measures the hot carbon dioxide in the flames at a specific
wavelength.
Operating voltage:
16 to 28 VDC
Quiescent current:
500 A
Field of detection:
90
Detection distance:
27 m with 0 angle of sight (standard)
46 m with 0 angle of sight (increased)
Protection category:
IP 44
Ambient temperature:
-25 to +70C
Rel. air humidity:
95% (no strong build-up of dew)
Case material:
Pressure case aluminium
Colour:
white (similar to RAL 9010)
Dimensions including base:
135 x 135 x 77 mm (HxWxD)
Weight including base:
750 g
VdS-Approval:
G299085
Triple infrared flame detector DF 1192
Three sensor infrared flame detector with fuzzy logic and wavelet analysis,
suitable for the detection of smokeless liquid and gas fires, as well as open
fires with smoke formation, which arise from the burning of materials
containing carbon. The detector is suitable for use both indoors and
outdoors.
Operating voltage:
16 to 28 VDC
Quiescent current:
500 A
Field of detection:
90
Detection distance:
27 m with 0 angle of sight (standard)
46 m with 0 angle of sight (increased)
Protection category:
IP 67
Ambient temperature:
-35 to +70C
Rel. air humidity:
100% (no strong build-up of dew)
Case material:
Pressure case aluminium
Colour:
white (similar to RAL 9010)
Dimensions (including base):
135 x 135 x 77 mm (H x W x D)
Weight (including base):
750 g
VdS-Approval:
G299085
Description

Type

Art. No.

Infrared flame detector DF 1191


Triple infrared flame detector DF 1192
Base for flame detector DFB 1190
Installation bracket for DFx detectors
Fitting joint MWV1
Rain protection hood DFZ1190
Test lamp for flame detector

DF 1191
DF 1192
DFB 1190
MV1
MWV1
DFZ1190
STABEX HF

FG020360
FG020361
FG020363
FG020364
FG020365
FG020366
FG020367

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Radio-linked detectors

8.5

Radio-linked detectors

No.: FG030172

No.: FG030173

B-HB-028EN

Radio-linked smoke detector DOW 1171


Radio-linked wireless optical smoke detector for extending fire alarm
systems in areas, where architectural aspects or particular operating processes
do not allow wires to be laid (e.g. in historical buildings, hotels, museums
etc.). The system comprises of one or more optical DOW 1171 radio
controlled smoke detectors and a receiver unit (radio gateway with wireless
module), which is connected directly to the Integral loop technology. The
transmission of data between wireless smoke detectors and the receiver unit
is bidirectional using the SRD waveband (868-870 MHz), thereby ensuring
the highest possible degree of transmission security and operational security.
The detector is supplied with power by two batteries, the receiver via the
loop circuit. Up to 30 radio controlled smoke detectors can communicate
with a single wireless module. Supplied including a detector base and 2 pcs.
9V batteries.
Operating voltage:
2 pcs. 9V lithium batteries
Median current uptake:
68 A
Battery operating life:
> 5 years in normal use
Frequency range:
868 to 870 MHz (SRD band)
Channel spacing:
25 kHz
Transmission power:
max. 5 mW
Range in buildings:
up to 40 m where there is intervisibility
Aerials:
double integrated aerials
Protection category:
IP 44
Ambient temperature:
-10 to +55C
Rel. air humidity:
max. 95% at 34C
Dimensions:
119 x 73 mm (D x H)
Case material:
PC / ABS plastic
Colour:
white, similar to RAL 9010
Weight:
335 g
Radio approval:
CE 0123
VdS-Approval:
G200112
CPD-Approval:
0786-CPD-20089
Battery for radio-linked smoke detector and radio gateway
The 9V lithium ultralife battery is used both for supplying power to
the radio gateway (1 battery required for commissioning and for ensuring
that the configuration settings are maintained during maintenance), as well as
also acting as a replacement in the radio controlled detector (2 pcs). Caution:
Due to their construction, the batteries are very vulnerable to impacts!
System:
Lithium / Manganese Dioxide
Name:
NEDA 1604 LC
Rated voltage:
9V
Wattage:
1,2 Ah @ 900 up to 5.4 V @ 23C
Maximum discharge:
120 mA
Ambient temperature:
-20 to +60C
Case:
Aluminium / Mylar
Safety:
less than 2g lithium;
no transport restrictions
Description

Type

Art. No.

Radio-linked smoke detector


Battery for DOW 1171 and radio gateway

DOW 1171
BATT FM

FG030172
FG030173

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

99

Special detectors Radio-linked detectors

No.: FG030176

100

Radio-linked manual callpoint


For manually triggering a fire alarm in areas, where architectural aspects or
particular operating processes mean that cables can only be laid with
difficulty, or not at all. The alarm is triggered by smashing the glass panel and
pressing the button. The detector communicates bidirectionally with the BXRGW radio gateway over the 868-870 MHz Short Range Device frequency
band. Power is supplied by 2 batteries (not supplied).
Power supply:
2 pcs. 3.6V lithium batteries
Median current uptake:
60 A
Battery life:
at least 5 years in normal use
Frequency range:
868 - 870 MHz (SRD)
Frequency selection:
16 groups with 5 channels
Channel spacing:
25 kHz
Transmission power:
max. 5 mW
Range in buildings:
up to 40 m where there is intervisibility
Aerials:
double integrated aerials
Protection category:
IP 43
Ambient temperature:
-10 to +55C
Rel. air humidity:
95%, without condensation
Dimensions:
125 x 125 x 57 mm (HxWxD)
Case material:
ABS
Colour:
red RAL 3000
Weight:
350 g
Radio approval:
CE 0123
VdS-Approval:
G299032, G203060
CPD-Approval:
0786-CPD-20736
Description

Type

Art. No.

Radio-linked manual callpoint SMF 121


Base for SMF 121
Lithium battery 3.6 V
Key for manual callpoint
Replacement glass panel for SMF 6120

SMF 121
SMF 6120
SMF 6120 BATT
DKM SV
SMF 6120 GLAS

FG030176
FG030177
FG030178
FG020289
FG030187

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Radio-linked detectors

No.: 20-2100006-01

No.: FG030171

No.: FG030173

Radiogateway BX-RGW
Communications interface between the fire alarm control panel and the
DOW 1171 and SMF 6120 radio controlled smoke detectors. Up to 30 radio
controlled smoke detectors can be connected to a gateway. If the radio
connection between the detector and the gateway is briefly interrupted, then
a diversion via the neighbouring detector will be automatically established to
the next gateway. Both the addressing of the module and the setting of its
parameters are carried out via the fire alarm control panel. The built-in
battery is used for commissioning and for ensuring the power supply during
revision.
Operating voltage:
Power consumption:
Wireless module interface:
Buffer battery:
Frequency range:
Transmission power:
No. of connectible detectors:
Range in buildings:
Aerial:
Protection category:
Ambient temperature:
Rel. air humidity:
Dimensions:
Case:
Colour:
VdS-Approval:
CPD-Approval:

12 to 30 VDC
typ. 950 A
20 pin 2 rowed multipoint connector
9V Lithium/Manganese (lifespan > 5 years)
868 to 870 MHz
max. 5 mW
max. 30
up to 40 metre where there is intervisibility
integrated, separate transmitter and receiver
aerials
IP 54 with case
-10 to +55C
5 to 95% without condensation
93 x 70 x 24 mm
with case: 120 x 80 x 57 mm
Polystyrol, halogen-free
grey RAL 7035
applied for
applied for

Description

Type

Art. No.

Radiogateway
Radio module
Battery for radio module
Extension connection joint M 16
Stepped nipple M 20
Lock nut M16

BX-RGW
SPU 6002
BATT FM
MM ANB M16
MM SN M20
MM GM M16

20-2100006-01
FG030171
FG030173
MM000185
MM000181
MM000186

Radio testing device


The FTG wireless testing device is used to check radio transmission
conditions in situ (using a field strength check between two points) and
supports the necessary number of detectors and gateways in the planning
stage.
No.: FG030174

Radiospy
For configuration, commissioning and checking installed wireless detectors.
This tool only works in combination with a PC or laptop and is user for
measuring the strength of the fields (to assist in configuration), for observing
and monitoring wireless communications, for changing the configuration of
a wireless cell (e.g. changing detectors without reconfiguration).

B-HB-028EN

Description

Type

Art. No.

Radio testing device DZW1171


Radiospy

FTG
FRSP

FG030174
FG030175

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

101

Special detectors Fire gas detectors

8.6

Fire gas detectors

No.: FG030950

102

Fire gas detector GSME


Gas sensor with multiple criteria technology for use in environments where
there is a heightened chance of risk, for selective detection of gases with
characteristics of a fire, which are released in the initial phase of a fire (even
where there is no open fire or visible smoke formation). The robust
construction and the pressure cast aluminium case offers a high level of
immunity against moisture and dust, with sources of interference e.g. vehicle
exhaust fumes being filtered out by the multiple criteria evaluation. The
standard connection cable (5m) with bayonet locking mechanism is not
supplied as standard and must be ordered separately with all types of
detector.
Hose-proofing and detector heating elements must be ordered when the
detector is ordered, since they are fitted in factory as optional extras. It is not
possible to fit them afterwards, as the detector cannot be guaranteed to work
properly.
Areas of use:
Industry, coal processing, wood processing
and wood-based industries, grain silos etc.
(see technical documentation for details)
Operating voltage:
40 VDC (min. 20V , max. 40V)
Current uptake @ 27V:
GSME-L3/HC: 74 mA
GSME-F: 93 mA
GSME-FR: 130 mA
Power consumption:
GSME-L3/HC: 2.0VA
GSME-F: 2.5VA
GSME-FR: 3.5VA
Electrical connection:
Plug and socket connection with bayonet
locking mechanism
Installation type:
Surface mounting
Protection category:
IP 64
Ambient temperature:
-10 to +50C (short-time -20 to +60C)
Rel. air humidity:
20 to 99% (non-condensing)
Case dimensions:
60 x 100 x 100 mm (HxWxD)
Material:
coated aluminium pressure die case
(corrosion resistant))
Case colour:
grey
Weight:
0,6 kg
Description

Type

Art. No.

GSME-L3 with alarm resistor 180R


GSME-HC with alarm resistor 180R
GSME-F with alarm resistor 180R
GSME-FR with alarm resistor 180R
Standard connection cable 5m
Hose-proofing protection for GSME-x
Detector heating 24V for GSME-x
Mounting plate for GSME-x and connection box
Connection box for GSME-x

GSME-L3
GSME-HC
GSME-F
GSME-FR
GSME Kabel
GSME SWS
GSME MHZ
GSME MPL
GSME ASB

FG030950
FG030951
FG030952
FG030953
FG030954
FG030955
FG030956
FG030957
FG030958

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Hazardous areas

8.7

Hazardous areas

No.: FG020070

No.: FG020072

B-HB-028EN

Optical smoke detector for hazardous areas SLR-E-IS


For use in areas where there is a risk of explosion - zones 1 and 2 The
detector contains two LEDs lined up opposite one another for alarm
indication and is connected via the YBN-R/4IS detector base and with a
safety barrier being interconnected to either the BX-AIM module or to the
Integral DC technology.
Operating voltage:
15 to 30 VDC
Quiescent current:
50 A
Alarm current:
40 mA max.
Protection category:
IP 42
Ambient temperature:
-10 to +50C
Max. Air Humidity:
95% non-condensing at +40C
Diameter:
100 mm
Unit height with base:
46 mm
Colour:
Ivory white
Material:
ABS
Weight:
115 g (160 g with base)
Marking:
EX II 1G EEx ia IIC T5
ATEX-Approval:
BAS 01 ATEX 1281
CPD-Approval:
0832-CPD-0113
Description

Type

Art. No.

Optical smoke detector for hazardous areas


Detector base for detectors for hazardous areas

SLR-E-IS
YBN-R/4IS

FG020070
FG020071

Temperature detector for hazardous areas DCD-1E-IS


Conventional class 1 maximum/change in temperature detector with an
extra fixed alarm threshold of 60C for use in zone 1 and 2 hazardous areas.
The detector contains two LEDs lined up opposite one another for alarm
indication and is connected via the YBN-R/4IS detector base and with a
safety barrier being interconnected to either the BX-AIM loop circuit
module or to the Integral DC technology.
Operating voltage:
15 to 30 VDC
Quiescent current:
50 A
Alarm current:
50 mA max.
Protection category:
IP 63
Ambient temperature:
-10 to +55C
Max. Air Humidity:
95% non-condensing (at +40C)
Diameter:
100 mm
Unit height with base:
46 mm
Colour:
Ivory white
Material:
Polycarbonate
Weight:
95 g (140 g with base)
Marking:
EX II 1 G EEx ia IIC T5
ATEX-Approval:
BAS 01 ATEX 1021
CPD-Approval:
0832-CPD-0121
Description

Type

Art. No.

Temperature detector for hazardous areas


Detector base for detectors for hazardous areas

DCD-1E-IS
YBN-R/4IS

FG020072
FG020071

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

103

Special detectors Hazardous areas

No.: 30-5000005-01

No.: FG020069

104

Multiple sensor detector for hazardous areas MMD 130 Ex-i


For use in areas where there is a risk of explosion - zones 1 and 2 The
detector can, depending on configuration, be used as a smoke or
temperature detector for the classes A1, A1S, A2, A2S as well as B and BS,
with the operating mode being set via a DIP switch. The detector can be
connected to the USB 501-7 Ex-i detector base, with a safety barrier being
interconnected, to the BX-AIM module or to modules B3-DCI6, B3-IM8
and B6-EIO.
Operating voltage:
10 to 28 VDC
Quiescent current:
150 A max.
Alarm current:
27 mA max.
Signal transmission:
2 core stub line, current increase
Protection category:
IP 44 (with base USB 501-7 Ex-i)
Ambient temperature:
-20 to +60 C
Max. Air Humidity:
95% non-condensing up to +34C
Dimensions:
118.8 x 58.1 mm (D x H)
Dimensions with base:
175 x 94.6 mm (D x H)
Colour:
white (similar to RAL 9003)
Material:
ABS / PC
Weight:
123 g (165 g incl. base)
Ignition protection class:
EX II 2G Ex ib IIC T4
ATEX-Approval:
EPS 11 ATEX 1346 X
VdS-Approval:
G211094
CPD-Approval:
0786-CPD-21104
Description

Type

Art. No.

Multiple sensor detector for hazardous areas


Detector base for MMD 130 Ex-i
Detector base for MMD 130 Ex-i

MMD 130 EX-I


USB 501-7 EX-I
USB 501-8 EX-I

30-5000005-01
FG020069
FG020065

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Hazardous areas

No.: FG020460

B-HB-028EN

Manual callpoints for hazardous areas dC31


For manually triggering a fire alarm in hazardous areas of group II, category
2GD (Zone 1, 2, 21 and 22), conformant to type B pursuant to EN 54-11.
There are three different models available for connection to different wiring
technologies, each of which can be connected as a detector in series as well
as being used as the terminal detector. Supplied with cable glands and
blanking stoppers.
Operating voltage:
max. 30 VDC
Current consumption:
serial detector: 0 mA
terminal detector: ca. 2 mA with B3-DCI6,
ca. 1,5 mA with BX-AIM
Stray power:
max. 1.3 W
Connection:
0.08 to 2.5 mm
Cable entry points:
2 x M20 x 1,5 6 to 12 mm
Protection category:
IP 66
Ambient temperature:
-20 to +60C
Dimensions:
135 x 135 x 61 mm (HxWxD)
Colour:
red RAL 3000
Material:
PC
Weight:
ca. 500 g
Ignition protection class:
EX II2G Ex emb IIC T6
EX II2D Ex tD A21 IP6x T80C
ATEX-Approval:
BVS 09 ATEX E 016 X
VdS-Approval:
G206113, G207079, G207099
CPD-Approval:
0786-CPD-20309, 0786-CPD-20310,
0786-CPD-20311
Description

Type

Art. No.

Manual callpoint dC31 red 560R/11k8


for connecting to B3-DCI
Manual callpoint dC31 red 560R/19k1
for connecting to BX-AIM
Manual callpoint dC31 red 1k5/3k
for connection to B3-IM8, B3-MTI8 & B6-EIO
Manual callpoint dC31 yellow 1k5/3k
for connection to B3-IM8, B3-MTI8 & B6-EIO
Manual callpoint dC31 blue 1k5/3k
for connection to B3-IM8, B3-MTI8 & B6-EIO
Metal key for manual call point
Replacement glass for manual call point

DC31

FG020460

DC31

FG020461

DC31

FG020462

DC31

FG020465

DC31

FG020466

DKM SV
DKM GV

FG020463
FG020464

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

105

Special detectors Hazardous areas

No.: FG030909

No.: FG030910

No.: FG030911

No.: FG030921

106

Manual callpoints for hazardous areas MCP/WCP 1A


The MCP/WCP 1A intrinsically safe manual call points for hazardous areas
conform to standard EN 54-11 (Type A), as well as ATEX 100a and are
connected to the BX-AIM input module with a zener barrier being placed in
between. The four different versions differ from one another solely in terms
of their case form and IP protection class, with the electronic circuitry,
connection and how they function being identical for all types.
The MCP 1A surface mounting version is suitable for indoor applications,
with the case being fastened to the wall using two screws. Cable inlets
required for surface mounting must be drilled into the case as required.
The countersunk mounting version MCP 545A-2 is suitable for use indoors,
and the detector is fitted straight into a standard size 1 (round or square)
countersunk mounting case.
The WCP 1A is also suitable for use outdoors and is surface mounted. The
detector has IP 67 protection class (waterproof); with the cables being fed in
from above or below using an M20 cable gland. 2 pcs. M 20 connection
joints and 2 pcs. blanking stoppers, as well as the fitting screws are supplied
as standard.
Operating voltage:
15 to 30 VDC
Quiescent current:
ca. 900 A
Alarm current:
5 mA
Connection:
via BX-AIM and Zener barrier
Screw connections:
max. 2,5 mm
Protection category:
MCP 1A: IP 24
WCP 1A: IP 67
Ambient temperature:
-30 to +70C
Dimensions (HxWxD):
MCP 1A (aP): 93 x 89 x 60 mm
MCP 1A (uP): 93 x 89 x 28 mm
WCP 1A:
93 x 97,5 x 71 mm
Case colour:
red RAL 3001
Case material:
Fibreglass reinforced plastic
Weight:
MCP 1A (surface mount.): 160g
MCP 1A (countersunk): 110g
WCP 1A: 240g
ATEX-Approval:
SIRA 04 ATEX 2350X
Description

Type

Art. No.

Manual callpoint MCP 1A red, IP24 (indoor),


with surface mounting base
Manual callpoint MCP 1A red, IP24 (indoor),
without base
Manual callpoint WCP 1A red, IP67 (waterproof)
Plastic triggering element
Transparent cover
Cover seal
Glass panel for MCP 545A / MCP 1A
Back panel for surface mounting
10 pcs. replacement test key

MCP 1A

FG030909

MCP 1A

FG030910

WCP 1A
PS210
PS200
P 037
DKM K GLAS
MUS041W
SC070

FG030911
FG030920
FG030921
FG030331
FG030328
FG030332
FG030329

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Hazardous areas

No.: FG020362

No.: FG020363

No.: FG020367

No.: FG020364

No.: FG020365

No.: FG020366

B-HB-028EN

Infrared flame detector for hazardous areas DF 1101Ex


For use in areas where there is a risk of explosion - zones 1 and 2. The
detector is suitable for the detection of smokeless liquid and gas fires, as well
as open fires with smoke formation, which arise from the burning of
materials containing carbon and is suitable for indoor and outdoor use.
Operating voltage:
16 to 28 VDC
Quiescent current:
500 A
Field of detection:
90
Detection distance:
27 m with 0 angle of sight (standard)
46 m with 0 angle of sight (increased)
Protection category:
IP 67
Ambient temperature:
-25 to +70C
Rel. air humidity:
100% (no strong build-up of dew)
Case:
Pressure cast aluminium / white
Dimensions (including base):
135 x 135 x 77 mm (H x W x D)
Weight (including base):
750 g
Hazardous Area Marking:
EEx ib IIC T4
ATEX-Approval:
PTB 02 ATEX 2161
VdS-Approval:
G299085
CPD-Approval:
0786-CPD-20497
Fitting bracket for DFx flame detectors
Fitting bracket for fixing flame detectors DF 1191, DF 1192 and DF 1101Ex
at an angle of 45.
Weight:
285 g
Dimensions:
120 x 136 x 120 mm (HxWxD)
Angle of tilt:
45 fixed
Fitting joint for DFx flame detectors
For special arrangements (e.g. facility monitoring without a 45 angle) fitting
using the MWV1 fitting joint is recommended. This part allows the detector
to be fitted simply and directly in the room to be monitored.
Dimensions:
118 x 120 x 78 mm (HxWxD)
Rain protection cover for DFx flame detectors
To protect the case when being used outside.
Dimensions:
165 x 150 x 130 mm (HxWxD)
Description

Type

Art. No.

Infrared flame Detector DF 1101Ex


Base for flame detector DFB 1190
Test lamp for DFx flame detectors
Installation bracket for DFx detectors
Fitting joint MWV1 for DFx detectors
Rain protection cover for DFx detectors

DF 1101EX
DFB 1190
Stabex HF
MV1
MWV1
DFZ1190

FG020362
FG020363
FG020367
FG020364
FG020365
FG020366

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

107

Special detectors Hazardous areas

No.: FG020320

No.: FG020322

108

UV flame detector X2200


Particularly suitable for use in areas with high temperatures, munitions
stores, hydrogen, silane, turbines etc. and offers the highest degree of
reliability, even in the event that multiple disturbing sources are present
simultaneously (electric arcing, sunlight, etc.). The detector has a 90 angle of
sight, has an automatic self-test function, a three colour LED for indicating
the detector status and current configuration, as well as integrated sensor
heating for installation outdoors. The X2200 can be used in hazardous areas
of types zone 1 and 2, the fitting bracket for wall and ceiling fitting is
supplied.
Operating voltage:
18 to 30 VDC
Power consumption:
13,1 W max. with heating unit
Signal transmission:
potential-free relay contacts
Connection:
Screw clips, maximum 1.5 mm
Protection category:
IP 66
Ambient temperature:
-40 to +75C
Rel. air humidity:
0 to 95%
Dimensions:
246 x 119 x 122 mm
Weight:
Aluminium: 2,7 kg, stainless steel: 4,5 kg
Hazardous Area Marking:
0539 II 2 GD EEx d IIC T5-T6 T86C
ATEX-Approval:
DEMKO 02 ATEX 132195
VdS-Approval:
G203083
Description

Type

Art. No.

UV flame detector X2200 aluminium


UV flame detector X2200 stainless steel
Weather protection ring

X2200
X2200
DET WS

FG020320
upon request
FG020324

Triple IR flame detector X3301


Detects burning light and heavy mineral oils, and is notable for its high
resistance against deceptive alarms. Possible uses include e.g. on oil drilling
platforms, in refineries, volume compressors, turbine systems, production
lines etc. The detector is fitted out with three identical IR sensors, with the
alarm only being triggered with all three sensors detect flames. The detector
has a 90 angle of sight, has an automatic self-test function, a three colour
LED for indicating the detector status and current configuration, as well as
integrated sensor heating for installation outdoors. The X3301 can be used
in hazardous areas of types zone 1 and 2, the fitting bracket for wall and
ceiling fitting is supplied.
Operating voltage:
18 to 30 VDC
Power consumption:
14,5 W max. with heating unit
Signal transmission:
potential-free relay contacts
Connection:
Screw clips, maximum 1.5 mm
Protection category:
IP 66
Ambient temperature:
-40 to +75C
Rel. air humidity:
0 to 95%
Dimensions:
246 x 119 x 122 mm
Weight:
Aluminium: 2,7 kg, stainless steel: 4,5 kg
Hazardous area marking:
0539 II 2 GD EEx d IIC T5-T6 T86C
ATEX-Approval:
DEMKO 01 ATEX 130204
VdS-Approval:
G202136
Description

Type

Art. No.

Triple IR flame detector X3301 Aluminium


Triple IR flame detector X3301 stainless steel

X3301
X3301

FG020322
upon request

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Hazardous areas

No.: FG020321

No.: FG020323

B-HB-028EN

IR flame detector X9800


The single frequency infrared detector is suitable for detector of fires in areas
where flames can be caused by the presence of high-pressure combustible
hydrocarbons, and where there are high concentrations of oil or pollutants in
the air (e.g. in pipelines, drilling platforms, petrochemical installations,
turbines etc.). The detector is able to provide reliable detection even when
there are sources of interference (e.g. hot sources of radiation with
movement, ovens etc.) and has a 90 visible range, an automatic self-test
function, 3 colour LED for signalling the detector status and the current
configuration, as well as an integrated sensor heating unit for installation in
outdoor areas. The detector can be used in zone 1 and 2 hazardous areas.
The bracket for mounting it on walls or ceiling is supplied.
Operating voltage:
18 to 30 VDC
Power consumption:
12 W max. with heating unit
Signal transmission:
potential-free relay contacts
Connection:
Screw clips, maximum 1.5 mm
Protection category:
IP 66
Ambient temperature:
-40 to +75C
Rel. air humidity:
0 to 95%
Dimensions:
246 x 119 x 122 mm
Weight:
Aluminium: 2,7 kg, stainless steel: 4,5 kg
Hazardous area marking:
0539 II 2 GD EEx d IIC T5-T6 T86C
ATEX-Approval:
DEMKO 02 ATEX 132195
VdS-Approval:
G203084
Description

Type

Art. No.

IR flame detector X9800 Aluminium


IR flame detector X9800 stainless steel

X9800
X9800

FG020321
upon request

Combined UV/IR flame detector X 5200


Particularly suitable for uses where hydrocarbon fires may arise, or where
there are sources of UV radiation present (e.g. in aircraft hangars, tank
systems etc.). The detector enjoys a 90 angle of sight, has an automatic selftest function, a 3 colour LED for indicating the detector status and current
configuration, as well as integrated sensor heating for installation outdoors
and can be deployed in hazardous area zones 1 and 2. The bracket for
mounting it on walls or ceiling is supplied.
Operating voltage:
18 to 30 VDC
Power consumption:
14,5 W max. with heating unit
Signal transmission:
potential-free relay contacts
Connection:
Screw clips, maximum 1.5 mm
Protection category:
IP 66
Ambient temperature:
-40 to +75C
Rel. air humidity:
0 to 95%
Dimensions:
246 x 119 x 122 mm
Weight:
Aluminium: 2,7 kg, stainless steel: 4,5 kg
Hazardous area marking:
0539 II 2 GD EEx d IIC T5-T6 T86C
ATEX-Approval:
DEMKO 02 ATEX 132195
VdS-Approval:
G203085
Description

Type

Art. No.

UV/IR flame detector X 5200 Aluminium


UV/IR flame detector X 5200 stainless steel

X5200
X5200

FG020323
upon request

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

109

Special detectors Hazardous areas

No.: FG020121

No.: FG020430

110

Safety barrier Z787


The safety barriers for intrinsically safe detector zones prevent too high an
energy level from entering a hazardous area, which could cause ignition
sparks if discharged there. The barrier is connected in series into the wiring
of the detector zone, and is tested and approved in accordance with the
requirements of ATEX 100a for use in hazardous areas.
Rated operational voltage:
max. 28 V
End-to-end resistance:
285 , max. 340
Operating current:
35 mA
Total cabling length:
max. 700 m
Max. short circuit current:
93 mA
Max. external capacity:
0,07 F / 0,5 F (IIC/IIB)
Max. external inductance:
4 mH / 15 mH (IIC/IIB)
Ambient temperature:
-20 to +60C
Hazardous area marking:
EX II 3 G EEx n A II T4
ATEX-Approval:
TV 99 ATEX 1484 X
BAS 01 ATEX 7005
Safety barrier Z787F
Identical in function and construction to the Z787 safety barrier, but
contains an integrated series fuse carrier in the safe part. The barrier is
intended for use in exposed surroundings, where overvoltages, lightning
strikes, voltage changes etc. could lead to the ex barrier being destroyed. The
selective series fuses prevent the internal fuses from being destroyed and can
be replaced.
Rated operational voltage:
max. 28 V
End-to-end resistance:
327 , max. 363
Operating current:
35 mA
Total cabling length:
max. 350 m
Max. short circuit current:
93 mA
Max. external capacity:
0,07 F / 0,5 F (IIC/IIB)
Max. external inductance:
4 mH / 15 mH (IIC/IIB)
Hazardous area marking:
EX II 3 G EEx n A II T4
ATEX-Approval:
TV 99 ATEX 1484 X
BAS 01 ATEX 7096
Description

Type

Art. No.

Safety barrier Z787


Safety barrier Z787.F
G-fuse 50 mA F 5x20 f. Z787.F (spare part)
Safety barrier 9002
IP55/65 case for safety barrier

Z787
Z787F
Z787F SI
9002
GEH EXB

FG020121
FG020430
FG020431
FG020038
FG020432

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Special detectors Hazardous areas

No.: FG020432 & FG020433

B-HB-028EN

IP55/65 case for safety barrier


Case with a built-in 35mm fitting bracket for fitting up to 3 Z787 or Z787F
safety barriers. When fitting only one safety barrier, the protective conductor
terminal needed can also be fitted in the case. Shipped including three M 32
stoppers. The case contains ten M32/40 cable inlets, and the fastening
bracket and two screws must be ordered separately.
Installation type:
Surface mounting
Number of inlets:
10
Nominal diameter:
25 mm
Measured isolating voltage Ui:
690 V
Can be sealed with leads:
yes
Ambient temperature:
-40 to +70 C
Protection category:
IP 65 / IP 55 with M40 stoppers
Halogen-free:
no
Colour:
light grey (RAL 7035)
Material:
plastic
Dimensions:
200 x 160 x 98 mm (LxWxH)
Description

Type

Art. No.

IP55/65 case for safety barrier


Mounting bracket for FG020432
Tallow-drop screw max. 4 x 8

GEH EXB
GEH EXBW
MS LKS 4-8

FG020432
FG020433
MS00004008

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

111

Accessories Fire brigade key safes & plan case

9 Accessories
9.1

Fire brigade key safes & plan case

No.: FG020507

No.: FG020515

No.: FG020509

112

Fire brigade key safe conforming to NORM F 3032


For installing in the outside wall of a building for storing the building key in
a thief-proof case. In the event of a fire, the fire brigade can open the door
with their key and take out the keys to the building.
Power consumption:
Releasing building key:
typically 210 mA
Door opener:
typically 130 mA
Buzzer:
typically 30 mA
Equipotential bonding:
4 mm
Connection clips:
max. 1.5 mm
Alarm current resistance:
2.2 k 5%
Profile half cylinder:
max. length: 40mm, lock measure: 30mm;
stop lug can be rotated 45
Protection category:
IP 44
Ambient temperature:
-25 to +60C
Dimensions Safe:
350 x 280 x 115 mm (HxWxD)
Flush mounted frame:
300 x 270 x 140 mm (HxWxD)
Surface mounted case:
352 x 282 x 130 mm (HxWxD)
Material:
Stainless steel
Weight:
12,5 kg / 17 kg with build-in frame
Approval:
in accordance with NORM F 3032
Controller Device
For connecting the fire brigade key safe to the fire alarm control panel.
Operating voltage:
24 VDC
Quiescent current:
30 mA
Protection category:
IP 30
Ambient temperature:
-10 to +50C
Colour:
red, RAL 3000
Dimensions:
300 x 200 x 50 mm (HxWxD)
Weight:
2 kg
Description

Type

Art. No.

Fire brigade key safe


Flush mounted frame for key safe
Surface mounted case for key safe
Controller device for key safe
Fire brigade cylinder MHZ52NI Austria
Locking pin for key safe (spare part)
Sticker with Schrack logo (40 x 10 mm)
Fire brigade sticker (spare part)

FSS
FSS UP
FSS AP
FSS AD
FSS ZYL A
FSS AS
FSS LOGO
FSS AK

FG020507
FG020508
FG020515
FG020509
FG020510
FG020512
FG020521
FG020519

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Accessories Fire brigade key safes & plan case

No.: FG020513

No.: FG020511

B-HB-028EN

Fire brigade key box FASB


In addition to the Fire brigade key safe, without electronic unlocking,
particularly suitable for storage of gate and engine room keys for Fire brigade
access, lift companies, electricians or emergency services. The panel
mounting cylinder is not supplied and must be ordered separately.
Dimensions:
150 x 150 x 57 mm (HxWxD)
Colour:
grey RAL 7032
Description

Type

Art. No.

Fire brigade key box FASB


Fire brigade mounting cylinder MHZ52NI

FSS FASB
FSS ZYL B

FG020513
FG020514

Fire brigade plan case


Metal cabinet for secure storage of plans for action forces (e.g.: alarm
organisation, fire safety plans, detector zone directories, operating
instructions for the fire alarm control panel etc.) in immediate reach from
the fire alarm control panel conformant to TRVB S 115. The Fire
brigadeplan case is fitted with the Fire brigade lock, which is also used on
Fire brigade control panels and manual call points. The box is supplied with
one key and three mounting screws.
Dimensions:
400 x 350 x 110 mm (HxWxD)
Colour:
red RAL 3000
Weight:
ca. 4,5 kg
Description

Type

Art. No.

Fire brigade plan case


Key (spare part)
Sticker Feuerwehrplne (spare part)

FWPK AP
DKM SCHL
S FWP

FG020511
FG020015
FG27800

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

113

Accessories Sounders & Flashing Lights

9.2

Sounders & Flashing Lights

No.: FG020147

No.: FG020342

No.: FG020344

114

Flashing light V4
Surface mounted flashing light to indicate a fire alarm visually.
Operating voltage:
24 VDC
Alarm current:
150 mA
Flashing frequency:
1 Hz
Protection category:
IP 65
Ambient temperature:
-25 to +40C
Rel. air humidity:
95% at 40C
Colour:
red or orange
Dimensions:
88 x 88 x 81 mm
Weight:
240 g
VdS-Approval:
G28714
Description

Type

Art. No.

Flashing light V4 red


Flashing light V4 orange

BL V4 RT
BL V4 OR

FG020147
FG020144

Combined sounder / flashing light VTB-32E


Siren with built-in orange flashing light, suitable for indoor and outdoor
usage. Sound type and volume can be set using DIP switches. The device is
available in red or white and in protection classes IP 43 and IP 65.
Operating voltage:
18 to 35 VDC
Alarm current:
41 mA max. (dependent on sound)
Signalpegel:
78 to 98 dB @ 1 m @ 90 (dep. on sound)
Signal frequency:
440 to 2900 Hz
Types of tone:
32 (can be set)
Protection category:
IP 43 / IP 65
Ambient temperature:
-20 to +70C
Case colour:
white or red
Dome colour:
orange
Dimensions:
IP 43: 93,6 x 89,6 mm (D x H)
IP 65: 93,6 x 106,9 mm (D x H)
Weight:
IP 43: 233 g
IP 65: 258 g
CPD-Approval:
0359-CPD-0060
Description

Type

Art. No.

Combined sounder/flashing light, red case, IP43


Combined sounder/flashing light, red case, IP65
Combined sounder/flashing light, white case, IP43
Combined sounder/flashing light, white case, IP65

VTB-32E-SB-RB/AL
VTB-32E-DB-RB/AL
VTB-32E-SB-WB/AL
VTB-32E-DB-WB/AL

FG020342
FG020343
FG020344
FG020345

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Accessories Sounders & Flashing Lights

No.: 20-2100009-01

No.: FG020161

B-HB-028EN

Loop flashing light BX-FOL


Addressable flashing light for optical signalling of a fire alarm in indoor
areas, suitable for direct connection to the Integral X-LINE. The BX-FOL is
available in red or white, with the flash rate being set using software of DIP
switches.
Operating voltage:
12 to 30 VDC
Alarm current:
max. 3,7 mA @ 24 VDC
Quiescent current:
500 A
Signal transmission:
serial, 2 wire technology
Flashing frequency:
0,5 Hz (slow) or 1 Hz (fast)
Short circuit isolator:
integrated
Protection category:
IP 21c
Ambient temperature:
-10 to +50C
Dimensions:
93 x 54 mm (DxH)
Case colour:
white or red
Case material:
ABS
Weight:
110 g
VdS-Approval:
G210085
CPD-Approval:
0786-CPD-20987
Description

Type

Art. No.

BX-FOL Loop flashing light red, red lens


BX-FOL Loop flashing light white, red lens
BX-FOL Loop flashing light red, orange lens
BX-FOL Loop flashing light white, orange lens

BX-FOL-RR
BX-FOL-WR
BX-FOL-RO
BX-FOL-WO

20-2100009-01
20-2100009-02
20-2100009-03
20-2100009-04

Revolving Mirror Light


Optical signalling device for indoor and outdoor installation. Shipped incl.
halogen lamp.
Operating voltage:
230 VAC
Alarm current:
170 mA
Mounting:
on floor, or a bracket or on a pipe
Rotating speed:
180 U/min.
Protection category:
IP 65
Ambient temperature:
-30 to +60C
Case:
ABS/PC, schlagfest, schwarz
Kalotte:
black, impact resistant ABS/polycarbonate
Dimensions:
130,9 x 216 mm (DxH)
Weight:
680 g
Description

Type

Art. No.

Revolving Mirror Light orange 230V


Wall mounting bracket

BL D OR
BL D ORW

FG020161
FG020162

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

115

Accessories Sounders & Flashing Lights

No.: FG020145

No.: FG020660

No.: FG020661

116

Siren Y04
To acoustically indicate a fire alarm, for indoor and outdoor use. 32 different
alarm signals can be chosen from using a 5 way DIP switch. The device is
available in red or white and in protection classes IP 54 and IP 65.
Operating voltage:
10 to 35 VDC
Alarm current:
35 mA at 24 V
Volume:
102 dB @ 1 m
Signal frequency:
800 to 1000 Hz
Connection:
Screw clips, maximum 1.5 mm
Protection category:
IP 54 or IP 65
Ambient temperature:
-25 to +55C
Rel. air humidity:
95% at 40C
Case:
red/white ABS
Dimensions:
88 x 88 x 80,8 mm
Weight:
215 g
VdS-Approval:
G28702
CPD-Approval:
0086-CPD-96705
Description

Type

Art. No.

Siren Y04 red


Siren Y04 red IP 65
Siren Y04 white
Siren Y04 white IP 65

SIR Y04 R
SIR Y04 R65
SIR Y04 W
SIR Y04 W65

FG020145
FG020163
FG020218
upon request

Siren for countersunk mounting


For acoustic indication of a fire alarm, suitable for installation in a standard
installation case. The siren has 32 different types of tones, which are set
using a 5 switch DIP switch block, with the volume setting being set using a
rotary switch.
Operating voltage:
9 to 28 VDC
Current consumption:
6 to 35 mA
Signal volume:
68 to 106 dB(A) typ. @ 1 m
Sounds:
32 (incl. DIN-tone)
Protection category:
IP54 (with fitting case)
Ambient temperature:
-25 to +70C
Material:
ABS
Colours:
white, red
Dimensions:
86 x 86 x 42 mm (HxWxD)
Weight:
ca. 100 g
VdS-Approval:
G206025
CPD-Approval:
0832-CPD-0138
Description

Type

Art. No.

Siren for countersunk mounting white


Siren for countersunk mounting red

ACW
ACR

FG020660
FG020661

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Accessories Sounders & Flashing Lights

No.: 20-2100008-01

No.: FG020386

No.: FG020387

No.: FG020388

B-HB-028EN

Loop Siren BX-SOL


Addressable signal emitter for acoustic signalling of a fire alarm in indoor
areas, suitable for direct connection to the Integral X-LINE. The siren is
shipped in red or white, and 4 different tones and the volume can be set
using DIP switches.
Operating voltage:
12 to 30 VDC
Power consumption:
low: 2,3 mA, high: 4,7 mA @ 24 VDC
Volume:
89 dB (99 dB) 3 dB(A)/m @ 24 VDC
Possible tones:
DIN 1200 ~ 500 Hz (acc. to DIN 33404)
Slow Whoop 500 ~ 1200 Hz (EN 2575)
Dauerton 990 Hz (pulse can be set)
Sweden-tone (150 ms on/ 150 ms off)
Short circuit isolator:
integrated
Protection category:
IP 21c
Ambient temperature:
-10 to +55C
Dimensions:
max. 108 x 91 mm (D x H)
Case colour:
white or red
Case material:
ABS
Weight:
230 g
VdS-Approval:
G210086
CPD-Approval:
0786-CPD-20986
Description

Type

Art. No.

BX-SOL-R Loop siren red


BX-SOL-W Loop siren white

BX-SOL-R
BX-SOL-W

20-2100008-01
20-2100008-02

Siren CS 200
Signal emitter for acoustic signalling of a fire alarm in interior areas pursuant
to EN 54-3. The device can be shipped in red or in white, has 32 different
tone types, which can be set using a 5 switch DIP switch block. For every
tone that is set, a second tone can be used as an addition alarm, with the
volume being set using a rotary switch.
Operating voltage:
18 to 28 VDC
Alarm current:
16 mA at 24 VDC (tone 3)
Volume:
100 dB(A) @ 1 m (tone 3)
Connection:
Screw clips, maximum 2.5 mm
Possible tones (32):
DIN:
1200 to 500 Hz
Sweep:
800 to 970 Hz
Alternating tone: 800 and 970 Hz
Protection category:
IP 21c
Ambient temperature:
-10 to +55C
Case:
ABS, red, white, black
Dimensions:
96 x 62 mm
Weight:
240 g
VdS-Approval:
G209123
CPD-Approval:
0832-CPD-1654
Description

Type

Art. No.

Siren CS200 white


Siren CS200 red
Siren CS200 black

CS200-SV
CS200-SV
CS200-SV

FG020386
FG020387
FG020388

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

117

Accessories Sounders & Flashing Lights

No.: 20-2100010-01

No.: 20-2100011-02

118

Base sounder BX-API


For fitting in USB 501-x Integral loop technology detector base for local
acoustic warnings of a fire. The BX-API snaps directly into the detector base
and connects directly to its connector clips. If a detector is activated, then
module BX-API is triggered as well as the alarm message being sent, with the
base-mounted siren emitting an acoustic alarm signal. The volume setting
(LOW or HIGH) is set by means of a DIP switch.
Operating voltage:
15 to 30 VDC
Power consumption:
low: max. 2mA, high: max. 4mA
Connection:
detector base USB 501-x
Tone types:
can be selected by dip switches:
DIN 1200 ~ 500 Hz (acc. to DIN 33404)
slow whoop 500 ~ 1200 Hz (EN 2575)
continuous tone 990 Hz (pulse can be set)
Sweden tone (150 ms on/ 150 ms off)
Volume:
Low 70dB @24VDC @1m @90
High 75dB @24VDC @1m @90
Ambient temperature:
+5C to +40C
VdS-Approval:
applied for
CPD-Approval:
applied for
Description

Type

Art. No.

Base sounder BX-API


Sticker for USB 501 base
with fitted BX-API (36 pcs.)

BX-API

20-2100010-01

S SOSIR

FG27821

Base sounder BX-SBL501


For signalling a fire alarm in interior rooms (EN 54-3/type A), fitted as a
unit with a USB 501 detector base and directly connected to the X-LINE.
The siren is shipped in white, and four different tones and the volume can
be set using software or by Dip switches. The cable inlet is from above, with
variant BX-SBL501-WDB with a higher base being available for a cable inlet
from the side.
Operating voltage:
12 to 30 VDC
Quiescent current:
max. 0.5 mA
Power consumption:
low: 1.5 mA, high: 4.0 mA @ 24 VDC
Volume:
80 dB (90 dB) 3 dB(A)/m @ 24 VDC
Types of tone:
DIN 1200 ~ 500 Hz (acc. to DIN 33404)
slow whoop 500 ~ 1200 Hz (EN 2575)
continuous tone 990 Hz (pulse can be set)
Sweden tone (150 ms on/ 150 ms off)
Connection:
Screw clips, maximum 2.5 mm
Short circuit isolator:
integrated
Protection category:
IP 31 D
Ambient temperature:
-10 to +55C
Dimensions:
114 x 32 mm (DxH)
114 x 36 mm (DxH) with high base
Case material:
PC-ABS
Case colour:
white RAL 9003
Weight:
ca. 170 g
VdS-Approval:
applied for
CPD-Approval:
applied for
Description

Type

Art. No.

Base sounder BX-SBL501 white


Base sounder BX-SBL501 white (high base)

BX-SBL501-W
BX-SBL501-WDB

20-2100011-02
20-2100011-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Accessories Sounders & Flashing Lights

No.: 20-2100012-04

No.: 20-2100012-03

No.: FG020177

B-HB-028EN

Platform sounder BX-SBL502


For signalling a fire alarm in indoor areas (EN 54-3/ type A), suitable for
direct connection to the Integral X-LINE. The siren is shipped in red or
white, and four different tones and the volume can be set using software or
by Dip switches. The cable inlet is from above, with variants BX-SBL502WDB and BX-SBL502-RDB with a higher base being available for a cable
inlet from the side.
Operating voltage:
12 to 30 VDC
Quiescent current:
max. 0,5 mA
Power consumption:
low: 1,5 mA, high: 4,0 mA @ 24 VDC
Volume:
80 dB (90 dB) 3 dB(A)/m @ 24 VDC
Types of tones:
DIN 1200 ~ 500 Hz (acc. to DIN 33404)
slow whoop 500 ~ 1200 Hz (EN 2575)
continuous tone 990 Hz (pulse can be set)
Sweden tone (150 ms on/ 150 ms off)
Connection:
Screw clips, maximum 2.5 mm
Short circuit isolator:
integrated
Protection category:
IP 31 D
Ambient temperature:
-10 to +55C
Dimensions:
114 x 32 mm (DxH)
114 x 36 mm (DxH) with high base
Case material:
PC-ABS
Case colour:
white RAL 9003
Weight:
ca. 165 g
VdS-Approval:
G211029
CPD-Approval:
0786-CPD-21065
Description

Type

Art. No.

Platform sounder BX-SBL502 white


Platform sounder BX-SBL502 white high
Platform sounder BX-SBL502 red
Platform sounder BX-SBL502 red high

BX-SBL502-W
BX-SBL502-WDB
BX-SBL502-R
BX-SBL502-RDB

20-2100012-04
20-2100012-02
20-2100012-03
20-2100012-01

Signal horn
Loud small horn with sound funnel, suitable for indoor and outdoor
installation. Available in a 24V or 230V version, with values which are
different for the 230V version being listed in brackets.
Operating voltage:
24 VDC (230 VAC)
Alarm current:
70 mA (15mA)
Volume:
98 dB @ 1 m
Connection:
Screw connection, cable of up to 9mm
Montage:
sound emission aperture facing downwards
Protection category:
IP 43
Ambient temperature:
-20 to +70C
Colour:
grey
Dimensions:
170 x 70 x 78 mm
Weight:
160 g
Case:
ABS, impact resistant
Description

Type

Art. No.

Signal horn 24 V
Signal horn 220V/30mA

SIR HUP1
SIR HUP2

FG020177
FG020178

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

119

Accessories Sounders & Flashing Lights

No.: FG020270

No.: FG020381

120

Alarm bell
Robust motorised alarm bell with a sonorous tone and high sound output
suitable for use indoors.
Operating voltage:
24 VDC
Alarm current:
15 mA
Signal volume:
94 dB @ 1 m
Ambient temperature:
-10 to +50C
Air humidity:
45 to 85%
Case:
Aluminium
Colour:
red
Dimensions:
150 x 53 mm (DxH)
Weight:
410 g
Description

Type

Art. No.

Alarm bell 24V

MBF-6WE

FG020270

Flashing light for hazardous areas CWB


For optical danger detection in areas with a risk of explosion of categories,
2G, 2D, 3G and 3D. The case is made of aluminium, thus making it suitable
for use in all chemical, petrochemical and offshore facilities. The high
protection class, and the units stable mechanical construction also allow
them to be used in the harshest operational conditions.
Operating voltage range:
22 to 26,5 V
Rated current draw:
230 mA
Rated power:
5,6 W
Flash frequency:
ca. 1 Hz
Flash energy:
5 Joule
Connection:
Schraubklemmen
Terminal range:
max. 2 x 4 mm eindrhtig,
max. 2 x 2,5 mm feindrhtig
Cable inlet:
1x gland seal connection joint M20 x1.5
terminal range 613 mm
1x connection gland, M20 x 1.5
Protection category:
IP 66 (EN 60529)
Ambient temperature:
-20 to +50C
Rel. air humidity:
90%, without condensation
Dimensions:
70 x 260 mm (DxH)
Case material:
Aluminium alloy
Dome material:
Polycarbonate (temperature resistant)
Colour:
Black base, yellow case
Dome colour:
red or yellow
Weight:
ca. 1.3 kg.
Marking:
II 2G EEx de IIC T, II 2G EEx de IIC T,
II 2D T 85 C IP66
ATEX-Approval:
LCIE 02 ATEX 6113
Conformity certification:
CE 0344 in accordance with 94/9EG
Description

Type

Art. No.

CWB flashing light for hazardous areas red


CWB flashing light for hazardous areas yellow
Wall mounting bracket

CWB EX RT
CWB EX GE
CWB EX WW

FG020380
FG020381
FG020382

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Accessories Sounders & Flashing Lights

No.: FG020276

No.: FG020273

B-HB-028EN

Flashing light V6 for hazardous areas


Robust explosion-proof flashing lights, suitable and approved for use in
areas where there is a risk of explosion.
Operating voltage:
24 VDC
Peak current draw:
2.5 A / for a duration of ~100s when
charging
Current consumption:
860 mA typ.
Flashing frequency:
1 Hz
Protection category:
IP 66
Ambient temperature:
-35 to +60C
Dimensions:
ca. 280 x 150 mm
Colour:
case: red, dome: orange
Weight:
4,6 kg
Ignition protection class:
d (explosion proof)
ATEX-Approval:
BAS 02 ATEX 0212X
Description

Type

Art. No.

Flashing light V6 for hazardous areas, orange

BL V6 EX

FG020276

Siren YO4 for hazardous areas


Robust intrinsically safe multisignal sirens, suitable and approved for use in
areas where there is a risk of explosion.
Operating voltage:
24 VDC (via Zener barrier)
Alarm current:
23 mA
Connection:
Screw clips, maximum 1.5 mm
Signal volume:
99 dB @ 1 m
Signal frequency:
800 to 1000 Hz
Protection category:
IP 55
Ambient temperature:
-25 to +40C
Dimensions:
178 x 88 x 80,8 mm
Case colour:
red
Weight:
430 g
ATEX-Approval:
BAS 02 ATEX 0212 X
Description

Type

Art. No.

Siren YO4 for hazardous areas

Y04 EX

FG020273

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

121

Accessories Holding magnets & anchoring plates

9.3

Holding magnets & anchoring plates

No.: FG020099

No.: FG020100

No.: FG020226

No.: 20-4001003-01

No.: 20-4001001-01

122

Flexible anchoring plate


Flexible anchoring plate for holding magnet on a plastic mounting plate
Mounting is using four countersunk screws.
Diameter of anchoring plate:
55 or 65 mm
Dimensions:
HM ANK01: 55 x 55 x 18 mm (HxWxD)
HM ANK04: 75 x 75 x 23 mm (HxWxD)
Swivelling anchoring plate
Swivelling anchoring plate for holding magnet on a plastic mounting plate
Mounting is using four countersunk screws.
Diameter of armature plate:
55 mm (other diameters upon request)
Swivel range:
ca. 2 x 60
Dimensions:
55 x 55 x 50 mm (HxWxD)
Telescopic Armature
Moveable armature plate with telescopic damper. Mounting is using four
countersunk screws.
Diameter of armature plate:
55 mm
Spring deflection:
20 mm
Dimensions:
55 x 55 x 79 mm (HxWxD)
Description

Type

Art. No.

Flexible anchoring plate on 55 mm mounting plate


Flexible anchoring plate on 65 mm mounting plate
Swivelling anchoring plate 55 mm
Telescopic armature

HM ANK01
HM ANK04
HM ANK02
HM ANK03

FG020099
FG020227
FG020100
FG020226

Door holding magnet on mounting plate


Electronic holding magnet on a plastic mounting place with concealed
connection clips. Shipped incl. a swivelling anchoring plate
Operating voltage:
24 VDC
Wattage:
1.6 W
Magnetic contact area:
48 mm diameter
Maximum holding strength:
400 N
Protection category:
IP 42
Dimensions:
55 x 55 x 35 mm (HxWxD)
Holding magnet
Electronic holding magnet with breaker switch for bridging larger distances
between the door and the wall. Shipped incl. a swivelling anchoring plate
Operating voltage:
24 VDC
Wattage:
1.6 W
Magnetic contact area:
48 mm diameter
Maximum holding strength:
400 N
Protection category:
IP 42
Dimensions:
70 x 70 x 65 mm (HxWxD)

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Accessories Holding magnets & anchoring plates

No.: 20-4001000-01

No.: 20-4001004-01

No.: FG020224

No.: 20-4001002-01

B-HB-028EN

Holding magnet for surface mounting


Electromagnetic holding magnet with circuit breaker button in a plastic case
for surface mounting. Supplied incl. a swivelling anchoring plate and
blanking stoppers.
Operating voltage:
24 VDC
Wattage:
1.6 W
Magnetic holding area:
48 mm diameter
Maximum holding strength:
400 N
Protection category:
IP 42
Dimensions:
120 x 85 x 38 mm (HxWxD)
Holding magnet for countersunk mounting
Electronic holding magnet for countersunk fitting without a breaker button.
Shipped incl. a swivelling anchoring plate
Operating voltage:
24 VDC
Wattage:
1.6 W
Magnetic contact area:
48 mm diameter
Maximum holding strength:
400 N
Protection category:
IP 42
Dimensions:
85 x 85 x 15 mm (HxWxD)
Holding magnet for floor mounting
Electromagnetic holding magnets for floor mounting in an aluminium case
and with a circuit breaker button. The electronic connection is done before
floor mounting, by connecting the unit to a two pole terminal.
Operating voltage:
24 VDC
Wattage:
1.5 W
Magnetic contact area:
50 mm diameter (63 mm upon request)
Maximum holding strength:
490 N
Protection category:
IP 65
Dimensions:
109 x 120 x 86 mm (HxWxD)
Holding magnet for floor or wall mounting
Electronic holding magnet with breaker button for floor or wall mounting
with swivelling magnetic head. There are three basic lengths for different
distances between the walls. Shipped incl. a swivelling anchoring plate
Operating voltage:
24 VDC
Wattage:
1.6 W
Magnetic contact area:
48 mm diameter
Maximum holding strength:
400 N
Protection category:
IP 42
Dimensions:
85 x 90 mm (W x H)
Lengths: 175 /325 /475 mm
Description

Type

Art. No.

Door holding magnet on mounting plate


Holding magnet
Surface mounted holding magnet with a break key
Countersunk holding magnet
Holding magnet for floor/wall (150/175 mm)
Holding magnet for floor/wall (300/325 mm)
Holding magnet for floor/wall (450/475 mm)
Fitting base for 20-4001002-xx

GTR0480002
GTR0480007
GTR0480008
GTR0480004
GTR0480011
GTR0480014
GTR0480015
SZB000.257500

20-4001003-01
20-4001001-01
20-4001000-01
20-4001004-01
20-4001002-01
20-4001002-02
20-4001002-03
20-4001005-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

123

Accessories External power supply units

9.4

External power supply units

No.: 20-4000106-01

No.: 20-4000105-01

12A power supply unit BE-PSU12


Used to supply peripheral devices with battery backed DC power in
accordance with standards, for devices which cannot be supplied with power
by the fire alarm control panels power supply (e.g. smoke aspirating systems
or special detectors with high quiescent current consumption).
The BE-PSU12 power supply unit has an output voltage of 24 V and an
output current of 12 A and is available in 2 different physical versions. The
CF version is for installation in an IP 54 wall-mounted cabinet, with version
OF suitable for installation in an IP 30 compact case. The mains supply
voltage and the battery circuit are constantly monitored, with the loading
current of the batteries being temperature-monitored. In the event of an
overload, the maximum output current is limited accordingly, and in the
event of the voltage falling below the cut-off voltage, low battery protection
ensures that automatic load shedding occurs. Both power supply units are
fitted with potential-free contacts, to allow the battery status to be queried
and forwarded onto a superordinated system.
Rated input voltage:
230 VAC (+10%-15%)
Current uptake:
max. 380 VA
Rated output voltage:
24 VDC
Output nominal current:
12 A
Charge plateau voltage:
27.4 VDC 0.4% (25C)
Low battery protection/load shedding: 20.4 VDC 0.4%
Battery type:
Lead rechargeable, no maintenance
required
Power supply fuse:
2 A, slow
Fuse DC battery circuit:
15 A, FK2
Device fuse:
10 x 1 A fairly slow
Protection category:
IP 20
Ambient temperature:
-5 to +40C
Dimensions CF version:
155 x 95 x 183 mm (HxWxD)
Dimensions OF version:
185 x 176 x 122 mm (HxWxD)
Weight:
ca 1,6 kg without battery
VdS-Approval:
G209171, G209173
CPD-Approval:
0786-CPD-20875, 0786-CPD-20877
Description

24V/12A power supply unit


for IP 54 wall-mounted cabinet
24V/12A power supply unit
for IP 30 compact case

124

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

Type

Art. No.

BE-PSU12-CF

20-4000106-01

BE-PSU12-OF

20-4000105-01

B-HB-028EN

Accessories External power supply units

No.: 20-4000100-01

No.: 20-4000101-01

B-HB-028EN

Compact case BE-PSE12-C


With fitted BE-PSU12-OF power supply unit, 10 monitored and an optional
10 additional output fuses. The cabinet has space for the fitting of two
batteries (max. 65 Ah). An input/output module (for connection to the
BMZ) can also be fitted directly on the power supply unit or on the top-hat
rail. The 4 LEDs on the front side are used for status indication.
Case colour:
light grey, RAL 7035
Case Dimensions:
608 x 464 x 213 mm (HxWxD)
Protection category:
IP 30
Ambient temperature:
-5 to +40C
Weight:
ca 12,5 kg without batteries
VdS-Approval:
G209171
CPD-Approval:
0786-CPD-20875
Description

Type

Art. No.

24V/12A power supply unit in IP30 cabinet


Basic fuse circuit board (spare part)
Extension fuse circuit board (optional)
BX-OI3 input/output module
IP66 case for BX-OI3 (94 x 94 x 57mm)
Fastening bracket for IP66 case
Cylinder screw M5x10 for fastening bracket

BE-PSE12-C
BE-FIB10
BE-FIE10
BX-OI3
GEH MOD IP66
BKL M5
MS ZS 05

20-4000100-01
20-4000107-01
20-4000108-01
20-2100001-01
FG020234
FG020238
MS00845010

Wall-mounted cabinet BE-PSE12-P45


With a built-in BE-PSU12-CF power supply unit, 10 monitored and an
optional 10 additional output fuses, as well as all connectors and cables for
controlling peripheral devices and the batteries. The cabinet has space for
the fitting of two batteries (max. 45 Ah). In additional to the power supply
unit, an input/output module (for connection to the BMZ) can also be
fitted. 12 pcs. connection joints and 8 pcs. M25/M16 reducing pieces are
supplied as standard.
Case colour:
light grey, RAL 7035
Case dimensions:
500 x 500 x 300 mm (HxWxD)
Protection category:
IP 54
Ambient temperature:
-5 to +40C
Weight:
ca 27,5 kg without batteries
VdS-Approval:
G209173
CPD-Approval:
0786-CPD-20877
Description

Type

Art. No.

24V/12A power supply unit in IP54 cabinet


Temperature sensor for BE-PSE (replacement)
Basic fuse circuit board (replacement)
Extension fuse circuit board (optional)
BX-OI3 input/output module
IP66 case for BX-OI3 (94 x 94 x 57mm)
Fastening bracket for IP66 case
Cylinder screw M5x10 for fastening bracket

BE-PSE12-P45
BE-TSENS
BE-FIB10-P
BE-FIE10-P
BX-OI3
GEH MOD IP66
BKL M5
MS ZS 05

20-4000101-01
20-4000119-01
20-4000115-01
20-4000116-01
20-2100001-01
FG020234
FG020238
MS00845010

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

125

Accessories External power supply units

No.: 20-4000102-01

Wall-mounted cabinet BE-PSE12-P170


With a built-in power supply unit BE-PSU12-CF, 10 monitored as well as 10
additional optional output fuses, shipped incl. all terminals and cables for
connecting the peripherals and the batteries. The cabinet has space for the
fitting of four batteries (max. 85 Ah). An input/output module (for
connection to the BMZ) can also be fitted via the power supply unit. 12 pcs.
connection joints and 8 pcs. M25/M16 reducing pieces are supplied as
standard.
Case colour:
light grey, RAL 7035
Case dimensions:
1000 x 800 x 300 mm (HxWxD)
Protection category:
IP 54
Ambient temperature:
-5 to +40C
Weight:
ca 64,5 kg without batteries
VdS-Approval:
G209173
CPD-Approval:
0786-CPD-20877
Description

Type

Art. No.

24V/12A power supply unit in IP54 cabinet


Basic fuse circuit board (replacement)
Extension fuse circuit board (optional)
Temperature sensor for BE-PSE (replacement)
BX-OI3 input/output module
IP66 case for BX-OI3 (94 x 94 x 57mm)
Fastening bracket for IP66 case
Cylinder screw M5x10 for fastening bracket

BE-PSE12-P170
BE-FIB10-P
BE-FIE10-P
BE-TSENS
BX-OI3
GEH MOD IP66
BKL M5
MS ZS 05

20-4000102-01
20-4000115-01
20-4000116-01
20-4000119-01
20-2100001-01
FG020234
FG020238
MS00845010

Empty IP30 case for batteries


For extension the battery capacity and with space for fitting two batteries
with a maximum 65 Ah capacity.
Protection category:
IP 30
Dimensions:
608 x 464 x 213 mm (HxWxD)
Case colour:
light grey, RAL 7035
Weight:
11 kg without batteries
No.: 20-4000104-01

126

Description

Type

Art. No.

Empty IP30 case for batteries

BE-CBE12-C

20-4000104-01

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Accessories External power supply units

No.: 20-4000103-01

B-HB-028EN

Wall-mounted cabinet BE-PSE24-P170


With a built-in power supply unit BE-PSU12-CF, 10 monitored as well as 10
additional optional output fuses, shipped incl. all terminals and cables for
connecting the peripherals and the batteries. The cabinet has space for the
fitting of up to four batteries (max. 85 Ah). An input/output module can be
fitted above the power supply units (for connection to the fire alarm control
panel). 12 pcs. connection joints and 8 pcs. M25/M16 reducing pieces are
supplied as standard.
Case colour:
light grey, RAL 7035
Case dimensions:
1000 x 800 x 300 mm (HxWxD)
Protection category:
IP 54
Ambient temperature:
-5 to +40C
Weight:
ca 64,5 kg without batteries
VdS-Approval:
G209173
CPD-Approval:
0786-CPD-20877
Description

Type

Art. No.

2x 24V/12A power supply unit in IP54 cabinet


Basic fuse circuit board (replacement)
Extension fuse circuit board (optional)
Temperature sensor for BE-PSE (replacement)
BX-OI3 input/output module
IP66 case for BX-OI3 (94 x 94 x 57mm)
Fastening bracket for IP66 case
Cylinder screw M5x10 for fastening bracket

BE-PSE24-P170
BE-FIB10-P
BE-FIE10-P
BE-TSENS
BX-OI3
GEH MOD IP66
BKL M5
MS ZS 05

20-4000103-01
20-4000115-01
20-4000116-01
20-4000119-01
20-2100001-01
FG020234
FG020238
MS00845010

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

127

Accessories External power supply units

No.: 20-4000112-01

No.: 20-4000111-01

3A power supply unit BE-PSU03


It is used to supply peripheral devices with battery backed DC power
conforming with standards, for devices which cannot be supplied with
power by the fire alarm control panels power supply (e.g. smoke aspirating
systems special detectors with a high quiescent current consumption). The
BE-PSU03 power supply unit has an output voltage of 24 V and an output
current of 3 A and is available in 2 different shapes. The CF version is
suitable for fitting in an IP 54 wall-mounted cabinet, while the OF version is
suitable for fitting in a IP 30 compact case. The mains supply voltage and the
battery circuit are constantly monitored, with the loading current of the
batteries being temperature-monitored. In the event of an overload, the
maximum output current is limited accordingly, and in the event of the
voltage falling below the cut-off voltage, low battery protection ensures that
automatic load shedding occurs. Both power supply units are fitted with
potential-free contacts, to allow the battery status to be queried and
forwarded onto a superordinated system.
Rated input voltage:
230 VAC (+10%-15%)
Current uptake:
max. 90 VA
Rated output voltage:
24 VDC
Output nominal current:
3A
Charge plateau voltage:
27.4 VDC 0.4% (25C)
Low battery protection/load shedding: 20.4 VDC 0.4%
Battery type:
Lead rechargeable, no maintenance
required
Power supply fuse:
2 A, slow
Fuse DC battery circuit:
5 A, FK2/ FKS
Device fuse:
5 x 1 A slow
Protection category:
IP 20
Ambient temperature:
-5 to +40C
Dimensions CF version:
155 x 75 x 128 mm (HxWxD)
Dimensions OF version:
185 x 126 x 120 mm (HxWxD)
Weight:
1 kg
VdS-Approval:
G209170, G209172
CPD-Approval:
0786-CPD-20874, 0786-CPD-20876
Description

24V/12A power supply unit


for IP 54 wall-mounted cabinet
24V/3A power supply unit
for IP 30 compact case

128

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

Type

Art. No.

BE-PSU03-CF

20-4000112-01

BE-PSU03-OF

20-4000111-01

B-HB-028EN

Accessories External power supply units

No.: 20-4000109-01

No.: 20-4000110-01

B-HB-028EN

Compact case BE-PSE03-C


With fitted BE-PSU03-OF power supply unit, five monitored and an
optional five additional output fuses. The cabinet has space for fitting two
batteries (max. 26 Ah). An input/output module can be fitted on the top-hat
rail (for connection to the fire alarm control panel). The four LEDs on the
front side of the unit are used for displaying the operating state.
Case colour:
light grey, RAL 7035
Case dimensions:
361,6 x 464 x 145 mm (HxWxD)
Protection category:
IP 30
Ambient temperature:
-5 to +40C
Weight:
ca. 7,5 kg without batteries
VdS-Approval:
G209170
CPD-Approval:
0786-CPD-20874
Description

Type

Art. No.

24V/3A power supply unit in IP30 cabinet


Basic fuse circuit board (replacement)
Extension fuse circuit board (optional)
BX-OI3 input/output module
IP66 case for BX-OI3 (94 x 94 x 57mm)
Fastening bracket for IP66 case
Cylinder screw M5x10 for fastening bracket

BE-PSE03-C
BE-FIB05
BE-FIE05
BX-OI3
GEH MOD IP66
BKL M5
MS ZS 05

20-4000109-01
20-4000113-01
20-4000114-01
20-2100001-01
FG020234
FG020238
MS00845010

Wall-mounted cabinet BE-PSE03-P


With built-in BE-PSU03-CF power supply unit, five monitored and optional
five extra output fuses, as well as all clips required for connecting the
peripherals and the batteries. The cabinet includes space for fitting two
batteries (max. 45 Ah). An input/output module can be fitted next to the
power supply unit (for connection to the fire alarm control panel). 8 pcs.
connection joints and 4 pcs. M25/M16 reducing pieces are supplied as
standard.
Case colour:
light grey, RAL 7035
Case dimensions:
500 x 500 x 300 mm (HxWxD)
Protection category:
IP 54
Ambient temperature:
-5 to +40C
Weight:
ca 25,5 kg without batteries
VdS-Approval:
G209172
CPD-Approval:
0786-CPD-20876
Description

Type

Art. No.

24V/3A power supply unit in IP54 cabinet


Basic fuse circuit board (replacement)
Extension fuse circuit board (optional)
Temperature sensor for BE-PSE (replacement)
BX-OI3 input/output module
IP66 case for BX-OI3 (94 x 94 x 57mm)
Fastening bracket for IP66 case
Cylinder screw M5x10 for fastening bracket

BE-PSE03-P
BE-FIB05-P
BE-FIE05-P
BE-TSENS
BX-OI3
GEH MOD IP66
BKL M5
MS ZS 05

20-4000110-01
20-4000117-01
20-4000118-01
20-4000119-01
20-2100001-01
FG020234
FG020238
MS00845010

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

129

Accessories External power supply units

No.: 20-4000121-01

Compact case BE-PSE01


The BE-PSE01 power supply unit serves in the first instance for battery
backed DC power supply for peripheral devices, which cannot be supplied
by the fire alarm control panel's power supply unit for power consumption
reasons (e.g. sirens or holding magnets) and is optionally also available with a
built-in BX-IOM input/output module. The mains supply voltage and the
battery circuit are constantly monitored, with the loading current of the
batteries being temperature-monitored. In the event of an overload, the
maximum output current is limited accordingly, and in the event of the
voltage falling below the cut-off voltage, low battery protection ensures that
automatic load shedding occurs. The BE-PSE01 power supply unit is fitted
with potential-free contacts, to allow the battery status to be queried and
forwarded onto a superordinated system.
Rated input voltage:
230 VAC (+10% - 15%)
Power supply frequency:
47 to 63 Hz
Rated output voltage:
24 VDC
Nominal output current:
max. 1.6 A
Charge plateau voltage:
27.4 VDC 0.4%
Low battery protection/load shedding: 20.4 VDC 0.4%
Battery type:
Lead rechargeable, no maintenance
required
Power supply fuse:
4 A slow 250 V
Fuse for batteries:
2.5 A slow 250 V
Protection category:
IP 30
Ambient temperature:
-5 to +40C
Case dimensions:
204 x 200 x 80 mm
Case colour:
light grey, RAL 7035
Weight:
3,2 kg (incl. batteries)
VdS-Approval:
G211063
CPD-Approval:
0786-CPD-21076
Description

Type

Art. No.

Power supply unit 24V/1A in IP30 cabinet


incl. 2 batteries
Power supply unit 24V/1A in IP30 cabinet
incl. BX-IOM and 2 batteries
Top-hat rail fitting bracket for BE-PSE01

BE-PSE01

20-4000121-01

BE-PSE01-IOM

20-4000121-02

BE-THRH

20-4000122-01

Batteries for power supply unit cabinets

130

Description

Type

Art. No.

Battery 12 V / 1,2 Ah
Battery 12 V / 2,3 Ah
Battery 12 V / 17 Ah
Battery 12 V / 24 Ah
Battery 12 V / 44 Ah
Battery 12 V / 65 Ah
Battery 12 V / 85 Ah

AKKU 1,2
AKKU 2,3
AKKU 17
AKKU 24
AKKU 44
AKKU 65
AKKU 85

HG691014
HG691020
HG691013
HG691023
HG691017
HG691018
HG691019

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Accessories Overvoltage protection

9.5

Overvoltage protection

The components listed below are used for supplementing the Integral's overvoltage protection concept, if parts of
the peripheral devices (controllers or detectors) cannot be fitted within protection zone 1 (in accordance with VdS
directive 2833). The use of these components is dependent upon there being a competent overvoltage and
earthing concept in place for the entire building.

No.: 20-4000500-01

No.: 20-4000501-01

B-HB-028EN

Base unit for protection module


4 pole, universal feed-through terminal block for connecting an arrester
module without signal interruption. The safe earthing of the arrester module
is guaranteed by the top-hat rail rack by means of a snap-in fastening.
Fitting:
on a 35 mm top-hat rail acc. to EN 60715
Connection for Input/Output: screw / screw
Connection:
0.08 to max. 4 mm
Tightening torque:
0.4 Nm (connection terminals)
Earthing:
over 35 mm top-hat rail acc. to EN 60715
Protection category:
IP 20
Ambient temperature:
-40 to +80C
Dimensions:
90 x 50 x 12 mm (HxWxD)
Case:
Polyamid PA 6.6, yellow
ATEX-Approval:
DEKRA 11ATEX0089 X: II 3 G Ex nA
IIC T4 Gc
IECEx DEK 11.0032X: Ex nA II T4 Gc
Approvals:
CSA, VdS, UL, GOST
Protection module 24V
Combination arrester module for plugging into the base unit BXT BAS, for
protecting the 4 individual cores with a common reference potential as well
as asymmetric interfaces. Can be deployed using the lightning protection
zone concept on interfaces 0A to 2.
Usage: Integral loop technology (B3/B4-DAI), conventional stub lines
(DCI/MTI) and (monitored) controllers with a nominal current of up to
0.75 A.
Arrester class:
type 1/P1
Rated voltage:
24 V
Maximum continuous voltage: 33 V DC / 23.3 V AC
Nominal current:
0.75 A (at 45C)
Lightning surge current (10/350): 2.5 kA per core
Rated discharge current (8/20): 10 kA per core
Serial impedance per core.
1.8 Ohm
Capacity Ad-Ad:
0.5 nF
Capacity Ad-PG:
1.0 nF
Protection category:
IP 20 (connected)
Ambient temperature:
-40 to +80C
Dimensions:
45 x 51 x 12 mm (HxWxD)
Earth:
over base component BXT BAS
Case:
Polyamide PA 6.6, yellow
Prfnormen:
IEC 61643-21, UL 497B
ATEX-Approval:
DEKRA 11ATEX0089 X: II 3 G Ex nA
IIC T4 Gc
IECEx DEK 11.0032X: Ex nA II T4 Gc
Approvals:
CSA, VdS, UL, GOST

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

131

Accessories Overvoltage protection

No.: 20-4000502-01

132

Protection module 36V


Combination arrester module for plugging into the base unit BXT BAS, for
protecting the 4 individual cores with a common reference potential as well
as asymmetric interfaces. Can be deployed using the lightning protection
zone concept on interfaces 0A to 2.
Usage: Integral X-LINE (B5/B6-DXI)
Arrester class:
Type 1/P1
Rated voltage:
36 V
Maximum continuous voltage: 45 V DC / 31 V AC
Nominal current:
1.8 A (at 45C)
Lightning surge current (10/350):
2.5 kA per core.
Rated discharge current (8/20): 10 kA per core.
Serial impedance per core.
0.43 Ohm
Capacity Ad-Ad:
0.8 nF
Capacity Ad-PG:
1.6 nF
Protection category:
IP 20 (connected)
Ambient temperature:
-40 to +80C
Dimensions:
45 x 51 x 12 mm (HxWxD)
Earth:
over base component BXT BAS
Case:
Polyamide PA 6.6, yellow
Testing standards:
IEC 61643-21
ATEX-Approval:
ATEX: DEKRA 11ATEX0089 X: II 3 G
Ex nA IIC T4 Gc
IECEx DEK 11.0032X: Ex nA II T4 Gc
Approvals:
VdS, GOST
Description

Type

Art. No.

Base unit for protection module


24V protection module
36V protection module
Protection modules for other applications

BXT BAS
BXT ML4 BE 24
BXT ML4 BE 36

20-4000500-01
20-4000501-01
20-4000502-01
upon request

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Accessories Modems & Converters

9.6

Modems & Converters

No.: FG021060

No.: FG021061

No.: FG021062

No.: FG021063

Single mode optic fibre modems are used to connect Integral subcontrol
units and are deployed in SecoNET fire alarm networks, if the connection
between the individual control units is greater than 1,200 m or a single mode
fibre optic connection (9/125m) is necessary. The fibre optic modems
function in this process as a interface converter, from the Integral RS 422 /
RS 485 interfaces to fibre optic cables. The modem to be used should be
selected based on the type of fibres being used.
Operating voltage:
12 - 30 VDC
Power uptake:
max. 2.4 W (<100mA at 24V)
Required battery capacity:
7.2 Ah for 72h supply interruption period
2.5 Ah for 24h supply interruption period
Installation:
on a 35 mm DIN top-hat rail
Transmission type:
Half duplex
Interface 1:
RS 485 on DB 9 and 6 pin screw
connection clip
Interface 2 (1 fibres):
1 SC optic fibre connection;
Single mode 9/125m
Interface 2 (2 fibres):
2 ST optic fibre connections
Single mode 9/125m
Range:
typically 15 km (depending on the
insulation of the fibres and the number of
connections)
Transmission speeds:
up to 1.5 Mbit/s
Status - LEDs:
Power supply (green)
Data received (yellow)
Optical connection faulty (red)
Ambient temperature:
-10C to +55C (operation)
-40C to +85C (storage)
Dimensions:
115 x 61 x 113 mm (HxWxD)
Case:
Stainless steel, powder-coated
Weight:
500 g
Description

Type

Art. No.

DL-485/13-SM-ST-L

FG021060

2 fibres per modem section

Optic fibre modem RS485 single mode


1 channel, 2x fibre optic cables 9/125m,
ST connector

1 fibre per modem section (only as pairs for channel A+B)

Optic fibre modem RS485 single mode


channel A, 1x fibre optic cable 9/125m,
SC connector
Optic fibre modem RS485 single mode
channel B, 1x fibre optic cable 9/125m,
SC connector
Adapter SC to ST single mode

B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

DL-485/13-SM-SC-A-L

FG021061

DL-485/13-SM-SC-B-L

FG021062

SC/ST AD SM

FG021063

133

Accessories Modems & Converters

No.: FG021064

No.: FG021065

No.: FG021066

No.: FG021067

Optic fibre modem RS485 / multi mode


Multimode optic fibre modems are used for connecting Integral subcontrol
units and in the SecoNET fire alarm network, if the connection between the
individual control panels is longer than 1,200 m or a Multimode optic fibre
connection (50(62)m) is required. The fibre optic modems function in this
process as a interface converter, from the Integral RS 422 / RS 485
interfaces to fibre optic cables. The modem to be used should be selected
based on the type of fibres being used.
Operating voltage:
12 to 30 VDC
Power uptake:
max. 2.4 W (<100mA at 24V)
Required battery capacity:
7.2 Ah for 72h supply interruption period
2.5 Ah for 24h supply interruption period
Installation:
on a 35 mm DIN top-hat rail
Transmission type:
Half duplex
Interface 1:
RS 485 on DB 9 and 6 pin screw
connection clip
Interface 2 (1 fibres):
1 SC optic fibre connection;
Multimode 50/125m
Interface 2 (2 fibres):
2 ST optic fibre connections
Multimode 50/125m
Range:
typically 3 km (depending on the insulation
of the fibres and the number of
connections)
Transmission speeds:
up to 1.5 Mbit/s
Status - LEDs:
Power supply (green)
Data received (yellow)
Optical connection faulty (red)
Ambient temperature:
-10C to +55C (operation)
-40C to +85C (storage)
Dimensions:
115 x 61 x 113 mm (HxWxD)
Case:
Stainless steel, powder-coated
Weight:
500 g
Description

Type

Art. No.

DL-485/13-MM-ST

FG021064

2 fibres per modem section

Optic fibre modem RS485 multi mode


1 channel, 2x fibre optic cables 50/125m
ST connector

1 fibre per modem section (only as pairs for channel A+B)

Optic fibre modem RS485 multi mode


channel A, 1 fibre, connector ST
Optic fibre modem RS485 multi mode
channel B, 1 fibre, connector ST
Adapter SC to ST multi mode

134

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

DL-485/13-SM-SC-A

FG021065

DL-485/13-SM-SC-B

FG021066

SC/ST AD MM

FG021067

B-HB-028EN

Accessories Modems & Converters

No.: FG021052

No.: FG020212

B-HB-028EN

RS 422 / RS 485 Telephone Modem


Synchronous/asynchronous industrial modem, suitable both for telephony
use (dedicated line), as for 2 and 4 wire operation for interconnecting
Integral subcontrol units or SecoNET network if the distance between the
subcontrol units is greater than 1,200 m and a optical fibre connection is not
possible.
Operating voltage:
12 to 48 VDC
Power uptake:
ca. 2 W (ca. 80 mA at 27 V )
Required battery capacity:
6.5 Ah (for 72 hour supply interruption
period)
Installation:
on a 35 mm DIN top-hat rail
Transmission types:
asynchronous, full duplex, half duplex or
simplex
Interface 1:
EIA RS 422 / RS 485 / ITU-T V.11
5 pole screw-type terminal
Interface 2:
2 or 4 core wire
4 pole screw-type terminal or
dedicated telephone line over RJ-11
Range:
max. 24 km
Transmission speed:
max. 33.6 kbps on wire
max. 115 kbps on Interface
LEDs:
Operation, TD, RD, RTS, DCD
Ambient temperature:
+5 to +50C
Rel. air humidity:
0 to 95%, non-condensing
Dimensions:
100 x 55 x 128 mm (HxWxD)
Weight:
300 g
Description

Type

Art. No.

Telephone modem RS 422 / 485

TD-36LV485

FG021052

Interface Converter
Galvanically isolated interface converter RS 232 to RS 422 /RS 485 for
connection of Integral to Maxima control panels, to superordinated
management systems etc. If the interface converter in not built into the fire
alarm control panel, then a connector plug power supply unit is also
required.
Operating voltage:
10 to 30 VDC
Bit rate:
115,2 kBit/sec.
Range RS 485/422:
1200 m
Range RS 232:
15 m
Interfaces:
RS 422 / RS 485 using screw-type
terminals
RS 232 using DB9-F
Ambient temperature:
0 to +70C
Recommended cable type:
2 x 2 x 0,5 twisted, unshielded
e.g. MMI-BUS cable (L228022516)
Description

Type

Art. No.

Interface Converter

ADAM 4520

FG020212

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

135

Accessories Transmission devices

9.7

Transmission devices

No.: FG021010 & FG021006

No.: FG021011

No.: FG021012

136

ComBOX SMS transmission device


As a communications medium for automatically forwarding information and
events from the fire alarm system (e.g. alarm and fault messages, servicing
requests etc.) via SMS. External data communications are carried out over
the mobile phone network, with a built-in GSM modem being used to
transmit the SMS. The data to be transmitted are filtered in the fire alarm
control panel, transmitted to the ComBOX and then sent on from there to
up to 100 freely- programmable telephone numbers.
integrated dual band GPRS data modem (GSM900 / GSM1800)
RS 422 / 485 interface for configuration and communications
two RS 232 interfaces for communications
16 inputs, which can either be digitally or analogue controlled
Remote configuration of important operating parameters by SMS/GPRS
Power supplied by the fire alarm control panels batteries also in the
event of a power failure
up to a maximum of 100 participants (telephone nos.) can be freely
configured.
Participants can be grouped
Data transmission over GSM aerials
Sheet steel case with top-hat rail in Integral Design
Operating voltage:
12 to 30 VDC
Current uptake:
ca. 100 mA without switching outputs and
without modem
Data transmission:
GSM modem
Ambient temperature:
+5 to +55C
ComBOX dimensions:
55 x 75 x 150mm (HxWxD)
Case dimensions:
300 x 345 x 100mm (HxWxD)
Case colour:
red RAL 3000
Protection category:
IP 20
Weight:
ca. 230 g
Interfaces:
1 x RS 422 / RS 485
2 x RS 232
16 inputs, 8 outputs
Description

Type

Art. No.

ComBOX
ComBOX case, red, lockable
Key for Integral IP MX/CX cabinets (spare part)
ComBOX GSM aerial with magnetic foot with
FME connector 5DB
GSM aerial with wall mounting bracket and FME
connector
RS232 to RS485/RS422 interface converter
Service PC cable
Glass tube fuse 2.5A T 5x20

COMBOX
COMBOX GEH
SCU LOCK KEY
ComBOX MFANT

FG021010
FG021006
750000027
FG021011

ComBOX ANT WH

FG021012

ADAM 4520
KAB SPC
ZUB SICH 2,5T

FG020212
FG81719
IS625028

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Accessories Transmission devices

No.: FG020060

Manual callpoint MCP 525-7


For manually triggering a fire alarm, suitable for connection to the Integral
DC technology. The detector can be used as an external manual call point
(main detector) for TUS/Infranet controlling. The alarm is triggered by
smashing the glass panel and pressing the button and then forwarded to the
fire alarm control panel or directly to the emergency services. The built-in
LED indicates the detectors triggered state. After pressing the alarm button,
this button requires unlocking so that the system can be electronically reset
at the fire alarm control panel.
Operating voltage:
Current consumption:
Functional principle:
Installation type:
Protection category:
Ambient temperature:
Dimensions:
Case:
Colour:
Weight:
VdS-Approval:
CPD-Approval:

16,2 to 30 VDC
prescribed by line technology used
manual callpoint type B acc. to EN 54-11
Surface mounting
IP 52
-10 to +55C
134 x 134 x 36 mm
Plastic (ASA)
red RAL 3001
450 g
G207007
0786-CPD-20294

Description

Type

Art. No.

MCP 525-7 manual call point red


Hand symbol sticker
Replacement glass panel
Key

MCP525-7
MCP535 AK
MCP535 GLAS
DKM SCHL

FG020060
FG030230
FG030231
FG020015

Transmission 2020E device with case


For transmitting hazard messages and/or technical alarms over an analogue
telephone connection, in the form of spoken texts to as many telephone
users as required, and/or in the form of digital signals to one or several
alarm receiver systems. When connected to Schrack Seconet fire alarm
control panels, a DC/DC stabiliser module must be used for converting the
24 V power into the 12V operating voltage required by the transmission
device.
Operating voltage:
10,2 to 15 V DC
Quiescent current:
ca. 30 mA at 12 V, ca. 20 mA at 24 V
Operational current:
ca. 150 mA at 12 V, ca. 105 mA at 24 V
Dimensions:
205 x 250 x 55 mm (HxWxD)
Environmental protection class: Class II in accordance with VdS 2110
VdS-Approval:
G105806

B-HB-028EN

Description

Type

Art. No.

Comline 2002E/S3
DC / DC Stabiliser Module

2002E
DCDC STM

100073171
100046033

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

137

Accessories Hold-open systems

9.8

Hold-open systems

No.: FG030600

ORS 142 Optical Smoke Switch


For detecting smouldering and open fires with smoke formation, as well as
for controlling hold-open systems on doors and gates. An additional
temperature sensor is triggered when the ambient temperature reaches 70C,
with the alarm threshold detection ensuring that the level of contamination is
permanently monitored and the alarm threshold is therefore adapted
automatically. The operating state of the unit is indicated visually by means
of an LED.
Operating voltage:
18 to 28 VDC
Current consumpt. at 28 VDC: Quiescent current: 21mA; Alarm: 10 mA,
Fault: 25mA
Smoke detection:
conforming to EN 54-7
Temperature:
70 C
Relay contact:
Opener
Switching voltage:
30 VDC
Switching current:
1A
Switching power:
30 W
Protection category:
IP 42
Ambient temperature:
-20 to +60C
Dimensions incl. base:
80 x 65 mm (DxH)
Colour:
white, similar to RAL 9010
Weight:
120 g
DIBt-approvals:
Z-6.5-1571, Z-6.5-1725
Description

Type

Art. No.

Optical Smoke Switch ORS 142


Base 143A

ORS 142
143A

FG030600
FG030602

TDS 247 Rate-of-rise switch

No.: FG030601

138

Temperature differential switch with maximum level for detecting open fires
with or without smoke formation, when operating conditions mean that
sources of interference like dust, smoke or steam are to be expected. Both
the rate of temperature increase and the exceeding of a set threshold value
are detected. The operating state of the unit is indicated visually by means of
an LED.
Operating voltage:
18 to 28 V DC
Current consumpt. at 28 VDC: Quiescent current: 21mA, Alarm current:
10mA, fault current: 25mA
Fire recognition:
Temperature class A1 in accordance with
EN 54-5
Maximum range:
+54 to +65C
Relay contact:
Opener
Switching voltage:
30 VDC
Switching current:
1A
Switching power:
30 W
Protection category:
IP 42
Ambient temperature:
-20 to +80C
Dimensions incl. base:
80 x 65 mm (DxH)
Colour:
white, similar to 9010
DIBt-approvals:
Z-6.5-1571, Z-6.5-1725
Description

Type

Art. No.

Rate-of-rise switch TDS 247


Base 143A

TDS 247
143A

FG030601
FG030602

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Accessories Hold-open systems

No.: FG030602

No.: FG030640

Base 143A
The 143A detector base with a bayonet fitting is suitable for attaching the
ORS 142 optical smoke switch and the TDS 247 rate-of-rise switch for
surface mounting in dry rooms. The electrical connection with the detector
is by means of the base having contact springs enclosing the detectors
connecting pins on two sides. The base has six terminals, with terminal 6 not
having a connection to the detector, being intended merely as a supporting
structure.
Cable inlet:
max. 9 mm
Protection category:
IP 42
Dimensions:
80 x 33 mm (DxH)
Colour:
white, similar to RAL 9010
Description

Type

Art. No.

Base 143A

143A

FG030602

Manual triggering device HAT 02


Manual triggering device for installation in dry rooms, to manually actuate
hold-open devices in accordance with DIBt regulations.
Contact type:
Opener
Switching voltage:
30 VDC
Switching current:
1A
Protection category:
IP 20
Colour:
Case white, rocker switch red
Installation:
Surface / countersunk mounting
Inscription:
Tr schlieen
Description

Type

Art. No.

Manual triggering device HAT 02

HAT 02

FG030640

No.: FG020133

Break button
To manually shut a fire prevention door, in order to checking whether the
hold-open system is working properly even without a simulated fire.
Surface mounted dimensions: 80 x 80 x 35 mm (H x W x D)
Countersunk dimensions:
80 x 80 mm (front panel)
fits in countersunk mounting case 55 mm

No.: FG020148

Description

Type

Art. No.

Countersunk mounting break button


Surface mounting break button

UT UP
UT AP

FG020133
FG020148

B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

139

Accessories Hold-open systems

No.: FG030630

No.: FG030631

140

Power supply unit NG 519


Power supply and triggering device for supplying smoke switches with
power. The device contains a longitudinal controller and a thermal
protection unit (special disablement technology to prevent the relay contacts
from sticking in the event of a short circuit). Also there is a connection slot
for fitting the extra SAB 04 circuit board.
Rated input voltage:
230 VAC
Power consumption:
21 VA
Rated output voltage:
24 VDC
Output current:
350 mA
Output power:
8.4 W
Relay contact:
potential-free changeover contact
Switching voltage:
30 VDC
Switching current:
1A
Switching power:
30 W
Protection category:
IP 30
Overvoltage category:
II
Ambient temperature:
+5 to +40C
Cable entry points:
Diameter 12 mm (2 on top, 3 below)
Case material:
Polycarbonate
Colour:
white, similar to RAL 9010
Installation:
Wall mounting, surface mounting
DIBt-approvals:
Z-6.5-1725
Description

Type

Art. No.

Power supply unit NG 519

NG 519

FG030630

Connection case FAD 01


The connection case for hold-open systems is used for connecting all
components in a hold-open system. The connection for the smoke switch
and the hold-open devices is electronically fuses at 900 mA, with this output
also having the relevant relay contact available. This connection card
contains special disablement technology to prevent the relay contacts from
sticking in the event of a short circuit.
Rated input voltage:
24 VDC
Rated output voltage:
24 VDC
Output current:
900 mA
Output power:
21 W
Relay contact:
1 potential-free, changeover contact
Switching voltage:
250 VAC/ 30 VDC
Switching current:
5 A @ 24 VDC, 3 A @ 30 VDC
Protection category:
IP 30
Ambient temperature:
+5 to +40C
Cable entry points:
Diameter 12 mm (2 on top, 3 below)
Case:
Polycarbonate
Colour:
white, similar to RAL 9010
Installation:
On a wall, horizontally or vertically
DIBt-approvals:
Z-6.5-1571, Z-6.5-1725, Z-6.5-1871
Description

Type

Art. No.

Connection case FAD 01

FAD 01

FG030631

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Accessories Hold-open systems

No.: FG030632

No.: upon request

B-HB-028EN

Set signal indicator unit SAB 04


Connection card for saving alarm information if the connected smoke switch
is triggered, with a red alarm LED and reset button. We recommend the
SAB 04 when using optical and acoustic signalling devices, so that the
signalling process is guaranteed to continue for the entire closing process
until the reset occurs. To be fitted in NG 519, NAG 03 and NAG 04 power
supply units and for fitting in FAD 01 connection cases..
Description

Type

Art. No.

Set signal indicator unit SAB 04 Set

SAB 04 SET

FG030632

Power supply unit SVG 522


For hold-open systems with emergency power supplies for supplying power
when there is an interruption in the power supply. Two emergency power
supply batteries must be ordered separately.
For fitting the door controller tableau (2 pcs. FAK 01)
Short circuit resistance
primary clocked
maintenance-free emergency power supply
Acoustic and visual announcement of power, battery and fuse failures,
total discharge, processor faults and earth faults
Indicator denotes readiness for operation
Low battery protection and temperature protection.
Rated input voltage:
230 VAC
Rated frequency
50 Hz
Power consumption:
48 VA
Rated output voltage:
24 V DC
Output voltage range:
21.6 to 27.6 V DC
Output current:
max. 1.3 A
Output power:
43 W
Battery charging monitor:
yes
Low voltage indication:
<21 V DC
Low battery protection:
<20 V DC
Fault indication:
power failure, battery fault,
total discharge, earth fault
Ambient temperature:
+5 C to +40 C
Protection category:
IP 54
Case:
Sheet steel
Cable inlets on top:
20
Colour:
RAL 9010
Installation:
Wall mounted
Weight without batteries:
ca. 10 kg
DIBt-approvals:
Z-6.5-1725, Z-6.5-1871
Description

Type

Art. No.

Power supply unit SVG 522


Emergency power supply battery (2 pcs. required)

SVG 522

upon request
upon request

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

141

Accessories Cables

9.9

142

Cables
Description

Type

Art. No.

Integral LAN data cable


Cat 5e UTP (AWG24), halogen-free, red

UTP 100 FRH

20-4100000-01

MMI-BUS cable red LF-2YY 2x2x0.5

KAB MMI RT

L228022516

MMI-BUS cable red LF-2YY 2x2x0.5,


unshielded, halogen-free

KAB MMI RTHF

L228022520

MMI-BUS cable red LF-2YACVY 1x2x0.5


shielded

KAB MMI RT S

L228022518

Earth cable 2x2x0.5 red

LI-2YCYV

L228022519

Red shielded fire alarm cable 1x2x0.8


for Loop Technology

KAB 1*2*0,8 S

L198200804

Fire alarm cable blue shielded 1x2x0.8


for loop technology

KAB 1*2*0,8 S BL

L198200802

Red shielded fire alarm cable 1x2x0.8


for Loop Technology, halogen-free

KAB 1*2*0,8 S HF

L198200803

Fire alarm cable blue shielded 1x2x0.8


for loop technology (-20 to +105C)

JB-Y(ST)Y
1X2X0,8BL

L198200805

Cable for high temperature detectors 2x0.75


orange (-50C to +180C)

SIHF-O 2X0,75

L198275800

Fire alarm cable red 3x0.6 LF-XYY

KAB 3*0,6 RT

L198300607

Fire alarm cable red 4x0.6 LF-XYY

KAB 4*0,6 RT

L198400607

Fire alarm cable red F-YAY 5x2x0.6

F-YAY 5 X 2 X 0,6

L225005267

Fire alarm cable red F-YAY 10x2x0.6

KAB 10*2*0,6 RT

L225010267

Fire alarm cable red F-YAY 20x2x0.6

KAB 20*2*0,6 RT

L225020267

Fire alarm cable red 2x0.6 LF-XYY

KAB 2*0,6

L198200607

Cable YMM 2x2.5 grey

KAB 2*2,5

MM000110

Cable YYSCH3x0.6 grey, 100m

KAB 3*0,6 GR

MM000111

Cable YYSCH 5x0.6 grey, 100m

KAB 5*0,6 GR

MM000112

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Accessories Cables

B-HB-028EN

Description

Type

Art. No.

Cable YMM-O 3x1,5 without print red

KAB 3*1,5

MM000113

Cable YMM-O 3x2,5 without print red

KAB 3*2,5

MM000114

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

143

Accessories Labelling Panels & Stickers

9.10 Labelling Panels & Stickers

144

Description

Dimensions

Art. No.

Sticker Brandmelderzentrale

161 x 33 mm
173 x 51 mm
297 x 110 mm

FG27812
FG27803
FG28405

Sticker Brandmeldesystem Teilzentrale/Blackbox

173 x 51 mm

FG27801

Sticker Externes Anzeigefeld"

161 x 33 mm

FG27810

Sticker Externe Energieversorgungseinrichtung fr


Brandmeldeanlage

242 x 51 mm

FG27811

Sticker Feuerwehrplne

297 x 105 mm

FG27800

Sticker Feuerwehrbedienfeld

297 x 110 mm

FG27813

Sticker with arrow

292 x 103 mm

FG27802

Sticker Brandmelder red/white for detector


labelling in false ceilings

90 x 20 mm

FG27842

Sticker Brandmelder red/white for detector


labelling in false ceilings

87 x 27 mm

FG28406

Schrack Logo sticker, resin coated

40 x 10 mm

FG020521

Grey ring stickers for MTD 533X (20 pcs.)

d=2 cm

FG28422

Labelling panel for USB 501 detector base

for labels up to
45 x 75 mm

FG030138

Detector inscription sign for high-ceilinged areas


printed
unprinted

120 x 175 mm
120 x 175 mm

FG28399
FG28398

Detector labelling card

80 x 55 mm

FG28400

Stickers Alarmzhler for Integral MAP operating


panels (28 pcs.)

35 x 15 mm

FG28423

Stickers Anzeigetestfor Integral MAP operating


panels (28 pcs.)

35 x 15 mm

FG28424

Stickers Erkundung & Auslsungen


for Integral PIP operating panels (2 pcs.)

40 x 30 mm

FG28425

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Accessories Labelling Panels & Stickers

B-HB-028EN

Description

Dimensions

Art. No.

Warning sticker
Achtung Brandfallsteuerungen (6 pcs.)
blank labels (6 pcs.)

174 x 15 mm
174 x 15 mm

FG28408
FG28409

Sticker for USB 501 base


with fitted BX-API base-mounted siren (36 pcs.)

14 x 20 mm

FG27821

Security seal (20 pcs.)

50 x 20 mm

FG28410

Sticker for MCP 535X

90 x 19 mm

FG27820

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

145

Accessories Printed items & brochures

9.11 Printed items & brochures

146

Brochures

No. German

No. English

Fire alarm systems (overview)


Integral IP MX
Integral IP CX
Integral IP BX
Integral IP MX system overview
Integral IP CX system overview
Integral VirtualMAP
High End Operating Panel
Integral IP network
SecoNET Network
Integral X-LINE
Integral X-LINE overview
MTD 533X Multiple Sensor Detector
SecoLOG Management System
AirSCREEN ASD 535
HeatSCREEN MHD 535

B-PR-598DE
B-PR-591DE
B-PR-592DE
B-PR-602DE
B-PR-595DE
B-PR-596DE
B-PR-601DE
B-PR-579D
B-PR-597DE
7PRST578-D
B-PR-594DE
B-PR-600DE
B-PR-599DE
B-PR-571D
B-PR-590DE
B-PR-593DE

B-PR-598EN
B-PR-591EN
B-PR-592EN
B-PR-602EN
B-PR-595EN
B-PR-596EN
B-PR-601EN
B-PR-579E
B-PR-597EN
7PRST578-E
B-PR-594EN
B-PR-600EN
B-PR-599EN
B-PR-571E
B-PR-590EN
B-PR-593EN

Handbooks and printed items

No. German

No. English

Product catalogue Fire alarm systems 2012/2013


Integral MAP operating instructions
Integral MAP short instructions
Integral PIP operating instructions
Integral IP MX system description
Integral IP CX system description
Integral IP MX manual
Integral IP CX manual
Integral IP BX manual
Integral X-LINE manual
Integral MMI & EPI-BUS manual
Integral LAN & network manual
SecoLOG IP operating instructions

B-HB-028DE
B-HB-020DE
B-HB-021DE
B-HB-027DE
B-HB-014DE
B-HB-015DE
B-HB-032DE
B-HB-033DE
B-HB-034DE
B-HB-035DE
B-HB-037DE
B-HB-036DE
B-HB-029DE

B-HB-028EN
B-HB-020EN
B-HB-021EN
B-HB-027EN
B-HB-014EN
B-HB-015EN
B-HB-032EN
B-HB-033EN
B-HB-034EN
B-HB-035EN
B-HB-037EN
B-HB-036EN
B-HB-029EN

Forms

No. German

No. English

Log book for fire alarm systems


Handover log
Commissioning log
Function log
Training log
Hours & Inventory
VB information / snagging log
Maintenance log (NORM F 3070)

B-HB-003DE
A-DS-200D
A-DS-202DE
A-DS-204DE
A-DS-205DE
A-DS-207DE
B-DS-200DE
B-DS-209DE

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

---------

B-HB-028EN

B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

not monitored alarm devices


fire actuation devices

B3-REL10 B3-REL16

(see MMI-BUS overview)

MMI-BUS

Fire brigade panel


acc. to DIN 14661

Fire brigade
key safe

Fire alarm routing


equipment

Fire alarm device

X-LINE

(see X-LINE overview)

triggering
relay bus

B5-MRI16

B5-BAF

B5-DXI2

monitored alarm
devices

B5-OM8

monitored inputs
conventional detector zones

B3-IM8
modernisation
monologue technology

B3-MTI8

EPI-BUS

B3-USI4

B5-LAN
B5-NET2-FXM B5-NET2-485
B5-NET2-FXS B5-NET4-485

RemoteMESSAGE IP

RemoteACCESS IP

SecoLOG IP

Telephone switchboards,
Pager, ESPA

External printers

Voice alarm

ComBOX

SecoLOG

Network LAN

Ethernet

VirtualMAP

System overviews Fire alarm control panel Integral IP MXF

10 System overviews

10.1 Fire alarm control panel Integral IP MXF

147

148

X-LINE

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

not monitored alarm devices


fire actuation devices

B3-REL10 B3-REL16

(see MMI-BUS overview)

MMI-BUS

(see X-LINE overview)

triggering
relay bus

B5-MRI16

B5-BAF

B5-DXI2

valves

monitored
alarm devices

B5-OM8

flood

Stop-button

Manual triggering
device

conventional
detector zones

B3-IM8

EPI-BUS

Ethernet

Network LAN

loss

pressure switch

switch
operation/reserve

blocking device

Monitored inputs

B5-LAN
B5-NET2-FXM B5-NET2-485
B5-NET2-FXS B5-NET4-485

SecoLOG IP

RemoteMESSAGE IP

RemoteACCESS IP

VirtualMAP

System overviews Multiple zone extinguishing system Integral IP MXE

10.2 Multiple zone extinguishing system Integral IP MXE

B-HB-028EN

B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B6-REL5
on main control unit
B6-BCU-X2

not monitored alarm devices


fire actuation devices

(see MMI-BUS overview)

MMI-BUS

Fire brigade panel


acc. to DIN 14661

Fire brigade
key safe

Fire alarm routing


equipment

Fire alarm device

(see X-LINE overview)

X-LINE

Telephone switchboards,
Pager, ESPA

External printers

Voice alarm

ComBOX

SecoLOG

B4-USI

B6-BAF
on main control unit
B6-BCU-X2

B6-DXI
on main control unit B6-BCU-X2

Conventinal
detector zones

B6-EIO

B6-NET2-485

Monitored alarm devices

Monitored inputs

EPI-BUS

B6-LAN

Ethernet

Network LAN

B6-FXS/M

B6-LXI2

X-LINE

SecoLOG IP

RemoteMESSAGE IP

RemoteACCESS IP

VirtualMAP

(see X-LINE overview)

System overviews Fire alarm control panel Integral IP CXF

10.3 Fire alarm control panel Integral IP CXF

149

150

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B6-REL5
on main control unit
B6-BCU-X2

B6-BAF
on main control unit
B6-BCU-X2

B6-DXI
on main control unit B6-BCU-X2

not monitored alarm devices


fire actuation devices

(see MMI-BUS overview)

MMI-BUS

(see X-LINE overview)

X-LINE

flood

Stop-button

Manual
triggering device

Conventional
detector zones

B6-EIO

loss

pressure switch

switch
operation/reserve

blocking device

Monitored inputs

Valves

Monitored alarm devices

EPI-BUS

System overviews Single zone extinguishing system Integral IP CXE

10.4 Single zone extinguishing system Integral IP CXE

B-HB-028EN

(see X-LINE overview)

X-LINE

B7-DXI
on main control unit
B7-CPU-X1

B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

Fire alarm
device
Fire alarm routing
equipment

B7-BAF
on main control unit
B7-CPU-X1

B7-LAN
on main control unit
B7-CPU-X1

EPI-BUS

Ethernet

SecoLOG IP

RemoteMESSAGE IP

RemoteACCESS IP

VirtualMAP

System overviews Fire alarm control panel Integral IP BX

10.5 Fire alarm control panel Integral IP BX

151

152

Integral IP CX

Integral IP MX

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1


B5-EPI-FAT

B5-EPI-FPA

EPI-BUS - max. 1 m
max. 3 subscribers

B5-MMI-CIP
B5-MMI-CPP

B5-EPI-FPS

B5-EPI-FPD

EPI-BUS - max. 1 m
max. 3 subscribers

B5-MMI-HCIP
B5-MMI-HCPP

B3-MMI-FPA

B3-MMI-FAT

B5-MMI-PIP

System limits per control panel MX / CX:


max. 16 operating panels MAP & PIP & VirtualMAP
max. 8 Firebrigade panels FPA, FPS, FPD, FAT
max. 3 protocol printer (internal & external)

System limits MMI-BUS


total max. 15 subscribers (EPI & MMI devices)
on a MMI-BUS

B3-MMI-IPEL
B3-MMI-EAT64

MMI-BUS - max. 1.200 m

System overviews MMI & EPI BUS

10.6 MMI & EPI BUS

B-HB-028EN

B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

BX-RGW

X-LINE module
4 relay outputs

BX-REL4

max. 3.500 m length


max. 250 subscribers

Base sounder

BX-API

X-LINE module
2 relay output
4 monitored inputs

BX-O2I4

Base sounder

BX-SBL 501

Integral X-LINE

Manual callpoint

MCP 545X

X-LINE module
1 Optokoppler input X-LINE module
1 monitored input for radio detectors

BX-I2

Manual callpoint

MCP 535X

X-LINE module
4 monitored inputs

BX-IM4

Ventilation duct
detector

LKM 531*

X-LINE module
1 relay output

BX-O1

Multisensor
detector

X-LINE module
End-position switch

BX-ESL

Integral IP BX

Integral IP CX

Integral IP MX

MTD 533X

BX-UPI
Parallelindikator

X-LINE module
1 monitored output
1 monitored input

BX-IOM

Platform sounder

BX-SBL 502

X-LINE module
for special detectors
BX-OI3

XLM35

Loop flashing light

BX-FOL

* X-LINE variant is coming soon

X-LINE module
2 monitored inputs
1 Optokoppler input
X-LINE module
1 relay output
1 primary line f.
detector zones

BX-AIM

Loop siren

BX-SOL

System overviews Integral X-LINE

10.7 Integral X-LINE

153

154

TZ x

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

TZ 4

TZ 2

FXM

Subcontrol unit
TX Ethernet connection
FXS/M Fibre optic connection
Highspeed RS 485 redundant

TZ 9

TZ 3

TZ 1

TZ 16

TZ 15

TZ 10

FXS
TZ 11

TZ 14

TZ 7

TZ 5

TX

TZ 13

TZ 12

TZ 8

TX

TZ 6

System overviews Integral LAN

10.8 Integral LAN

B-HB-028EN

System overviews Integral LAN

B-HB-028EN

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

155

156

Product Catalogue Fire Alarm Systems 2012/2013 V 1.1

B-HB-028EN

Schrack Productions B-HB-028EN - V 1.1

Subject to technical alterations!

System overviews Integral LAN