Sei sulla pagina 1di 44

Section 4: Rectifier Operation & Control

Chapter 1 - Rectifier Operating Principles


1.1 Introduction .............................................................................................. 4-1
1.2 SCR principles .......................................................................................... 4-1
1.2.1 Internal semiconductor structure .................................................. 4-2
1.2.2 SCR triggering mechanisms ........................................................ 4-3
1.2.3 SCR Turn-on characteristics ........................................................ 4-6
1.2.4 SCR Turn-off mechanisms .......................................................... 4-7
1.2.5 SCR turn-off characteristics ......................................................... 4-8
1.3 SCR Ratings ............................................................................................. 4-9
1.4 Phase control techniques ........................................................................ 4-11
1.4.1 Basic phase-control principles ................................................... 4-11
1.4.2 3-phase controlled rectifier ........................................................ 4-13
1.5 Rectifier construction ............................................................................. 4-14
1.6 Rectifier control system .......................................................................... 4-17
1.6.1 Control system overview ........................................................... 4-17
1.6.2 Charge mode selection ............................................................... 4-19
1.6.3 Input supply fault detection. ...................................................... 4-19
1.6.4 Input current limit ...................................................................... 4-19
1.6.5 Battery current limit ................................................................... 4-19
1.6.6 Battery temperature compensation ............................................ 4-19
1.6.7 Controlled start/stop ................................................................... 4-20
1.6.8 DC overvoltage and undervoltage fault detection ..................... 4-20
1.6.9 Battery Circuit Breaker .............................................................. 4-20
Chapter 2 - Rectifier Logic Board
2.1 Chapter overview ................................................................................... 4-21
2.2 General description ................................................................................. 4-21
2.2.1 Circuit board functions .............................................................. 4-21
2.2.2 Input/Output connections ........................................................... 4-21
2.2.3 Block diagram description ......................................................... 4-23
2.3 Detailed circuit description .................................................................... 4-26
2.3.1 Introduction ................................................................................ 4-26
2.3.2 Reference voltage generator ...................................................... 4-26
2.3.3 Battery temperature compensation ............................................ 4-27
2.3.4 Volts error amplifier .................................................................. 4-27
Battery current limit ......................................................... 4-29
Input current limit ............................................................ 4-29
Start/Stop control ............................................................. 4-30
2.3.5 Drive pulse generator ................................................................. 4-31
Analogue timing control circuit ....................................... 4-31
Digital signal processing .................................................. 4-33

S-4.FM5 - Issue 2 Dated 21/08/97

SECTION 4 - Rectifier Operation & Control

7200 Series UPS Service Manual

2.3.6 Start/Stop logic .......................................................................... 4-35


Input mains phase rotation error ...................................... 4-35
Input mains undervoltage ................................................. 4-35
ON/OFF control from UPS Logic Board ......................... 4-36
Control power supply failure detection ............................ 4-36
2.3.7 Control power supplies .............................................................. 4-36
2.4 Summary Information ............................................................................ 4-37
Chapter 3 - Rectifier Gate Drive Interface Board (4542040W)
3.1 Introduction ............................................................................................ 4-39
3.2 Rectifier SCR gate drive requirements ................................................... 4-39
3.3 Gate drive circuit .................................................................................... 4-40
Chapter 4 - Rectifier Snubber Board (4540043B)
4.1 Snubber requirements and characteristics .............................................. 4-41
4.2 Snubber board ......................................................................................... 4-42

ii

S-4.FM5 - Issue 2 Dated 21/08/97

Section 4:

Chapter 1 - Rectifier Operating Principles

1.1

Introduction
The 7200 series UPS employs a fully controlled, 3-phase SCR bridge rectifier to
provide a regulated DC busbar suitable for charging the UPS batteries and present
the inverter with a stable input voltage. This chapter describes the principles of
operation of an SCR device and its use in a phase-controlled rectifier circuit.

1.2

SCR principles
The Thyristor, or Silicon Controlled Rectifier (SCR), is a three-terminal device
which was first introduced to the power electronics industry in 1957. It is essentially a solid-state switch which is normally triggered from its non-conducting
state (OFF condition) to its conducting state (ON condition) by a pulse applied between its gate and cathode terminals. In general, in its ON-state the SCR acts as a
unidirectional conducting device and blocks current flow in the reverse direction
(cathode-to-anode). In its OFF-state, it blocks current flow in both directions.
Figure 4-1: SCR principles (summary)
SCR Three Terminal Device

ANODE

An SCR is a three-terminal device which


can be considered to act as an
electronically controlled switch.

CATHODE

GATE

SCR Switch Analogy


SCR ON
current flow anode-cathode
That is, when an SCR is turned ON
(conducting) the forward voltage
drop between its Anode and
Cathode is small and can be
considered to be short-circuit for all
practical purposes.

ANODE

CATHODE

SCR OFF
no current flow
ANODE

CATHODE

s4-c1.fm5 - Issue 2 Dated 21/08/97

Alternatively, in its non-conducting


(OFF) state the SCR presents a
very high Anode/Cathode impedance and can be considered to be
open circuit like an open switch.

4-1

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

1.2.1

7200 Series UPS Service Manual

Internal semiconductor structure


The SCR structure comprises four alternate P and N type semiconductor layers. Figure 4-2 shows how these layers can be split to form a pair of interconnected P-N-P and N-P-N transistors; annotated T1 and T2 in the diagram.
Figure 4-2: SCR Regenerative transistor analogy
Anode
P1
N1

Gate

Gate

P2
N2

Anode

Gate

IA

Anode

P1
N1
P2
N2

N1
P2

T1
T2 (NPN)

T1 (PNP)

Anode

I2

I1

Gate

T2
Ig

Cathode
Cathode

Cathode

Cathode

With reference to the transistor model above, the two transistors are connected in
a regenerative manner i.e. ignoring the gate current (Ig), T2s collector current
(I2) is drawn through T1 emitter-base junction (turning T1 on) and T1s collector
current (I1) flows through T2 base-emitter junction (turning T2 on). This can be
expressed mathematically as I2 = 2 x I1 (where 2 is the current gain of T2)
and I1 = 1 x I2 (where 1 is the current gain of T1).
Regeneration occurs when the sum of the current gain of both transistors (T1 and
T2), also described as the loop gain of the two transistors, is greater than unity;
at which point the transistors try to turn ON each other harder and harder until
both devices rapidly reach full saturation. This equates to the SCR being in its
conduction state, whereby the voltage drop across the device is approximately
1.0V and its anode current is determined only by the external voltage and load impedance.
As with a normal transistor, the current gain T1 and T2 varies proportionally
with emitter current, and in the absence of any gate signal the only current initially
flowing through the transistors is a leakage current comparable to with the reverse
current of a diode. Under these conditions the value of the current gain associated
with each emitter falls to a very low figure, and the device is designed such that
the loop gain is made less than unity, and the transistors remain non-conducting
i.e. this is equivalent to the SCRs non-conducting forward blocking state. Indeed, the fact that the two emitter-base pairs need be designed only for an average
value of of 0.5, to produce the effective unity loop gain necessary to make conduction self-sustaining, makes it possible to use relatively thick base layers, and
hence obtain a much greater voltage blocking capability than in a practicable transistor.
In summary, the SCR can be triggered from its non-conducting to conducting
state by increasing the circulating current through T1 and T2 to the point where
the loop gain rise above unity. This may be accomplished by several means, some
of which are undesirable, as described below.

4-2

s4-c1.fm5 - Issue 2 Dated 21/08/97

7200 Series UPS Service Manual

1.2.2

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

SCR triggering mechanisms


Breakover voltage

Figure 4-3: SCR static characteristic with zero gate current


IA
Forward

Conducting
Holding
Current
Reverse

VAK
Avalanche
Breakdown

Forward

Blocking
Breakover
Voltage

Reverse

Figure 4-3 illustrates the static characteristics for the SCR anode current (IA) and
anode-cathode voltage (VAK) with zero gate current. This shows that in the reverse
direction the SCR characteristic is similar to that of a normal diode, in that very
little current flows as the reverse voltage increases until the reverse avalanche
breakdown point is reached, where-upon the current rapidly increase.
In the forward blocking region, increasing the forward voltage does not tend to
increase the leakage current until the point is reached where avalanche multiplication begins to take place. Past this breakover voltage point, the leakage current
increases quite rapidly until the total current through the device is sufficient to
raise the internal loop gain 1 whereupon the SCR switches to its conduction
state provided the anode current remains in excess of a minimum current known
as the holding current. When the anode current falls below the holding current
the loop gain falls below unity and the device will revert to its forward blocking
(non-conducting) state.
Albeit not necessarily destructive, this means of triggering the SCR is undesirable
(especially in phase-control applications) and usually avoided by employing a
device whose forward breakover voltage and peak inverse voltage ratings are well
outside the available circuit voltage. Additionally, external components may be
used to prevent spurious voltage spikes inadvertently triggering the device by this
means.

s4-c1.fm5 - Issue 2 Dated 21/08/97

4-3

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

7200 Series UPS Service Manual

Gate triggering

Figure 4-4: Effects of gate current on triggering


IA
Forward

Conducting
Ig2 > Ig1 > Ig0

Holding
Current

Ig2

Ig1 Ig0

Reverse

Avalanche
Breakdown

Blocking

VAK
Forward

Reverse

The usual method employed to trigger the SCR from the blocking to the conducting state, is to inject sufficient current into the gate terminal (T2 base) to increase the current in the main circuit by the modest amount required to raise the
loop gain to greater than unity. That is, the injected gate current (Ig) leads to an
increase in I2 which in turn leads to an increase in I1, which further increases I2....
and so on, until both transistors are saturated.
Figure 4-4 shows that for increasing magnitudes of gate current, the region of
characteristics between breakover current and holding current is narrowed and the
effective forward breakover voltage is reduced. For sufficiently high gate currents
the entire forward blocking region is removed and the V-I characteristics are essentially identical to those of a P-N rectifier.
This is a very advantageous mode of operation, since it is possible to use a device
with a forward breakover voltage much higher than any voltage likely to be encountered in the circuit, and use only a moderate amount of trigger power to start
the high-conduction state.
Once the gate has been used to trigger the device into conduction it loses control
and can be removed without affecting the external circuits operation i.e. once
the SCR is conducting, the anode current is determined solely by the external circuits voltage and impedance, and the only method of turning the device off is to
reduce this to below the SCRs holding-current level. To minimise internal losses
and heating effects, it is usual therefore not to apply the gate current for much
longer than is necessary to assure the device turns on; for this reason the gate
signal normally takes the form of a current pulse of sufficient amplitude and duration to ensure this condition is satisfied.

4-4

s4-c1.fm5 - Issue 2 Dated 21/08/97

7200 Series UPS Service Manual

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

Figure 4-5: Gate drive parameters spread

Maximum
gate current
allowed

Gate Voltage (V)

12

Maximum
gate voltage
allowed

SAFE
OPERATING
AREA

Maximum
gate power
dissipation
(V x I)

Minimum
gate voltage
allowed
Minimum
gate current
allowed

0.5

1.0
1.5
Gate Current (A)

2.0

As can be seen from Figure 4-5, the spread of gate voltage versus gate current can
be quite wide for different load variations. The gate circuitry must therefore be
able to accommodate this variation and also allow for different sizes of SCR. Typical design values are for 6V and 1A pulses for 10sec.
dV/dt triggering

As with all semiconductor devices, there are internal capacitive effects between
the various P and N layers, and between the electrodes. In the case of the SCR
these effects can turn-on the device inadvertently if the rate of change of voltage
applied to it are sufficient to raise the current flow to a level which raises the internal loop gain above unity:
i.e.the current flowing through the capacitor = CdV/dt and has the same effect
as injecting a gate current if allowed to increase to the appropriate level.
As with the breakover-voltage triggering mechanism described above, this
method of turning on the device is not generally used as it is uncontrollable and
is normally prevented by connecting additional components (known as snubbers)
across the device to limit the rate of such voltage changes (see paragraph 4.1 on
page 4-41).

s4-c1.fm5 - Issue 2 Dated 21/08/97

4-5

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

1.2.3

7200 Series UPS Service Manual

SCR Turn-on characteristics


Figure 4-6: SCR turn-on characteristics

VAK x IA
Power
Dissipation
t

VAK

90%

Voltage across
SCRs
10%
t

IA
90%

Anode
Current
10%

0
td

t
tr

ton

Gate
Current
0

10%

As described previously, two basic conditions must be satisfied in order to turn


on an SCR. First, the device must be forward-biased i.e. its anode must be positive with respect to its cathode; second, a suitable current pulse must be injected
into its gate terminal. When both these conditions are satisfied, the device will
turn ON and an anode-cathode current will flow through the device depending on
external circuit parameters.
In detail, the turning-on of an SCR in response to a gate trigger signal may be considered to take place in three phases. First, a delay occurs before any kind of significant response is apparent. Secondly, under the direct influence of the gate
current, conduction is established in a small area adjacent to the gate. Finally, the
conducting area spreads with a fairly constant velocity, no longer influenced by
the gate, until the whole area is conducting.
Corresponding to the increase in conducting area, the resistance of the cell falls
from the near-infinite blocking value, rapidly to a relatively high value while
conduction is concentrated in the gate region, and then relatively to a the steady
state value. The instantaneous voltage drop thus follows a waveform such as that
illustrated in Figure 4-6, resulting in an instantaneous power dissipation:
w = VAK x IA .

4-6

s4-c1.fm5 - Issue 2 Dated 21/08/97

7200 Series UPS Service Manual

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

Conventionally, as shown in Figure 4-6, the total switching time is divided into
the delay time (td) and the rise time (tr); these periods are arbitrarily delimited, for
the purpose of measurement, at the instants when the voltage across the SCR falls
to 90% and 10% of the initial blocking voltage. The rise-time (tr) is defined as the
time required for the anode voltage to drop from 90% to 10% of its forward blocking value. The rise of current as voltage across the SCR falls is determined largely
by the external circuit. In a purely resistive circuit the current will rise in the same
manner as the voltage falls; hence the term rise time. It is important that the instantaneous current-voltage product during the turn on interval does not exceed
the device dissipation capability. For this reason, the rate of rise of anode current
(di/dt) must be limited. The delay time (td) is reduced as the gate current is increased; however there are other considerations that affect the chosen gate signal,
as described later (see paragraph 3.2 on page 4-39).
1.2.4

SCR Turn-off mechanisms


To turn an SCR OFF its anode-cathode current must be reduced below the holding current value, which is usually very small. This can be achieved by interrupting the current flow externally, by opening an switch for example, or by some
means reverse biasing the anode-cathode potential i.e. making its anode negative with respect to the cathode.
The processes of turning off an SCR by reversing its anode-cathode voltage is
known as commutation; and can broadly be divided into two forms described
as either natural or forced commutation.
Figure 4-7: SCR Turn-off mechanism
A

Anode

IA

Anode

P1 +
N1

Gate

Gate

P2 +
N2

J1
J2
J3

Cathode
Cathode
Referring to Figure 4-7, when an SCR is conducting, each its three semiconductor
junctions (J1-J3) are forward-biased and the two base regions (N1 & P2) are
heavily saturated with holes and electrons (stored charge).
When the SCR is commutated by the application of a reverse anode-cathode voltage, the holes and electrons in the vicinity of the two end junctions (J1 & J3) will
diffuse to the junctions and result in a reverse current in the external circuit. The
voltage across the SCR will remain at about 0.7V as long as an appreciable reverse current flows. After the holes and electrons in the vicinity of J1 and J3 have
been removed, the reverse current will cease; the junctions J1 and J3 will assume
a blocking state and the voltage across the SCR will then increase to a value determined by the external circuit. However, recovery of the device is not complete,
since a high concentration of holes and electrons still exists in the vicinity of the
centre junction (J2). This concentration decreases by the process of recombination in a manner which is largely independent of the external bias conditions.
After the hole and electron concentration at J2 has decreased to a low value, J2

s4-c1.fm5 - Issue 2 Dated 21/08/97

4-7

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

7200 Series UPS Service Manual

will regain its blocking state and a forward voltage may then be reapplied to the
SCR without turning it back on. The time that elapses after the cessation of forward current flow and before forward voltage may safely be applied is called the
SCR turn-off time (toff), and can typically range from 3sec to 50sec depending on the design and construction of the particular device.
1.2.5

SCR turn-off characteristics


Figure 4-8: SCR turn-off characteristics
Anode-Cathode
Current

trr
0

tfb
toff
Voltage across 0
SCRs

t1

t2

t3

t5
t4

t6

t9

t7

t10

t8

Figure 4-8 illustrates graphically the (some-what idealised) effects on the SCR
voltage and current of the turn-off mechanism described above. The total turn-off
time (toff) is the total time between the anode current falling to zero (t3) and the
device being capable of supporting a forward voltage (t8). This is shown to comprise two components. First the reverse recovery time (trr) (t3 to t6) followed by
the forward blocking time (tfb) (t6 to t8). These intervals are not constant, but are
a affected by several, mainly external, parameters.
For example the turn-off time will increase with:

An increase in junction temperature.


An increase in forward current amplitude (t1 to t2).
An increase in the rate of decay of forward current (t2 to t3).
A decrease in peak reverse current (t4).
A decrease in reverse voltage (t5 to t7).
An increase in the rate of reapplication of forward blocking voltage (t8 to
t9).
An increase in forward blocking voltage (t9 to t10).
An increase in external gate impedance.
A more positive gate bias voltage.
Natural versus forced commutation

As its title suggests, natural commutation takes place automatically when the
voltage across the SCR reverses as part of the external circuit function this is the
case in the phase-controller application, as the device is fed with the input a.c.

4-8

s4-c1.fm5 - Issue 2 Dated 21/08/97

7200 Series UPS Service Manual

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

mains supply and is naturally reverse-biased on every negative half-cycle. As


this happens at 50Hz, the reverse voltage is maintained across the SCR for several
tens of milli-seconds and presents no commutation timing problems.
Forced commutation is used when the SCR is fed from a DC source, such as in
an inverter application. Under such circumstances the reverse voltage must be
generated by a dedicated commutation circuit which must present a reverse voltage pulse of sufficient magnitude and duration to ensure the device has time to
fully turn off under all rated load conditions. (Note: in the 7200 series UPS the
inverter section is transistor based so this does not apply).

1.3

SCR Ratings
Junction temperatures

Power losses in an SCR produces thermal energy (heat) which must be conducted
away from the junction region. Heat dissipation is achieved by mounting the SCR
on a suitable heatsink the heat developed within the device then flows via the
device case and heatsink to the ambient air, and can be dispersed by fan extraction
if necessary.
The maximum operating junction temperatures are typically 125C - 150C.
Heat losses are a function of:
ON-state conduction losses
A product of the voltage drop across the device (about 1.5V) and the
amount of current flowing through it. This can be as high as 500W.
OFF-state losses
These losses are due to leakage current and are therefore very small.
Switching losses
The heat generated during turn-on and turn-off is a function of the voltage
across the device and the current flowing through the device at the time of
switching. These losses can be very large but exist for a very short duration only, as illustrated in the characteristic curves shown previously.
An upper temperature limit must be imposed to restrict mechanical failure and
prevent excessive temperatures to internal joints and leads (which may interfere
within the device package). When such a temperature limit is imposed (e.g.
125C) it will have a direct affect on the device rated current capability.
Current ratings

Several rated current conditions can be stipulated in the device specification; and
thermal breakdown is likely if any one of these values are exceeded.
Average current rating (IAV)
This is the maximum average ON-state current the device may conduct
continuously.
RMS Current rating (IRMS)
This is the maximum RMS ON-state current the device may conduct continuously i.e. this is the steady-state operating current.

s4-c1.fm5 - Issue 2 Dated 21/08/97

4-9

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

7200 Series UPS Service Manual

Peak Current rating (IPK)


This is the repetitive surge current the device may conduct at a specified
short pulse-width.
It rating (It)
This is the maximum forward non-repetitive surge current (i.e. Overload
current) capability, and is usually specified for one half cycle of 50Hz
operation.

Voltage ratings

Maximum Forward Voltage (VFBO)


This is the maximum forward voltage that can be applied across the device
(anode-to-cathode) without the device being forced to turn on.
There is always a small anode-to-cathode leakage current when a voltage
is applied to the device, and if the voltage is increased to the critical VFBO
the SCR will switch rapidly into full conduction. This is not dangerous to
the device itself, but may cause a short circuit within the rectifier if other
SCRs are already conducting when this false triggering occurs.
Maximum reverse voltage (VRBO)
This is the maximum reverse voltage that can be applied across the device
(cathode-to-anode) without the device being forced into reverse breakdown. If VRBO is exceeded it will lead to destructive breakdown, and the
SCR will not recover (thats blown it!).
Maximum rate-of-change (dv/dt)
A very high rate of increase of forward (anode-to-cathode) cathode dv/dt
can turn on the SCR, even though there is no gate signal and VFBO is not
exceeded (see page 4-5).

4-10

s4-c1.fm5 - Issue 2 Dated 21/08/97

7200 Series UPS Service Manual

1.4

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

Phase control techniques


Phase control of the power rectifier is made possible by the fact that it contains
SCRs (Silicon Controlled Rectifiers - also called Thyristors), rather than straightforward power diodes.

1.4.1

Basic phase-control principles


Figure 4-9 shows a single SCR connected in a simple AC circuit and can be used
to illustrate the basic principles of phase control techniques.
Note: although a half wave rectifier circuit is shown, this circuit has no practical
use in the 7200 equipment but is used only to simplify explanation.
Figure 4-9: Simple half-wave rectifier circuit
Vin ( peak )
Vdc ( mean ) = ---------------------------------------2
Vin(peak)
Vdc(mean)

Input
AC

RL

Max Output
SCR gate permanently
turned ON

Mean
DC
Input
AC
RL

0V
Min. Output
SCR gate permanently
turned OFF

The top diagram shows the situation where the SCR receives a permanent gate
drive signal i.e. the gate is permanently positive with respect to the cathode. In
this condition the SCR passes current during the whole of the input AC waveform
positive half-cycles but blocks the negative half-cycles, as the anode-cathode are
reverse biased during the reverse periods i.e. the SCR is said to be naturally
commutated at the end of each positive half-cycle. This results in a half-wave
rectified voltage being developed across the load resistor, and the SCR can be
seen to be acting in the same manner as a normal rectifier diode. Note that in this
example the mean (d.c.) load voltage is approximately 0.45 times the input peak
voltage, and is shown as a dotted line superimposed on the output waveform.
In the lower diagram the SCR gate drive voltage is removed altogether and under
these circumstances the SCR is permanently turned off during both the positive

s4-c1.fm5 - Issue 2 Dated 21/08/97

4-11

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

7200 Series UPS Service Manual

and negative half-cycles of the input voltage waveform. In this case the mean
(d.c.) load voltage will of course be zero.
The two conditions described above illustrate how the maximum and minimum load voltages are obtained. The description on the following page shows
how phase control techniques may be used to vary the mean load voltage to any
point between these two extremes.
Figure 4-10: Simple controlled rectifier; showing 45 and 90 output waveforms
SCR conducts only during the shaded
period of the input positive half-cycle

Vdc(max)
Vdc(mean)

Input
AC
RL
0

90

180

270

360

0V
Output waveform at 45 delay
Vdc(mean) is slightly less than the maximum
available dc voltage Vdc(max)

Gate ON
SCR turned ON by gate pulse

Vdc(max)
Vdc(mean)

Input
AC
0

90

180

Gate ON

270

360

RL

0V
Output waveform at 90 delay
Vmean is even less than that achieved
at 45 delay

The examples on the previous page showed that the mean voltage, Vdc(mean),
produced by the simple half-wave rectifier circuit is at a maximum when the SCR
is turned on throughout the whole of its positive (forward biased) half cycle, and
at a minimum when the SCR gate is totally devoid of a drive signal.
When used in a phase-controlled circuit, the mean voltage, Vdc(mean), is varied
between these two extremes by applying the gate drive signal at a variable point
in its forward biased half-cycle as illustrated in Figure 4-10. In the top diagram
the SCR gate is triggered when the input waveform is 45 into its positive half
cycle. The SCR therefore conducts during the period between 45 and 180 only
i.e. it is not turned on between 0 and 45, and is turned off by natural commutation at 180. As shown in the top waveform diagram, under these circumstances
the mean dc voltage Vdc(mean) is slightly less than maximum Vdc(max).
In the lower diagram the SCR gate trigger is delayed by a further 45, to a total of
90, which leads to a corresponding fall in mean output voltage, as shown.
This is the basic principle of a phase-controlled rectifier i.e. controlling the
mean DC voltage between its maximum and minimum limits by controlling the
variable phase delay between the point at which the SCR becomes forward biased
and the application of its gate drive signal.

4-12

s4-c1.fm5 - Issue 2 Dated 21/08/97

7200 Series UPS Service Manual

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

The terms phase forward and phase back are used in power engineering
fields to describe the action of advancing or retarding the gate drive signal respectively e.g. phasing forward the rectifier implies that the SCR is turned on earlier in its forward conduction cycle and more energy is therefore allowed through
the rectifier, leading to an increased mean DC voltage.
1.4.2

3-phase controlled rectifier


The 7200 series UPS uses a three-phase controlled bridge rectifier, as shown in
Figure 4-11. The circuit is similar to a standard diode bridge rectifier but comprises 6 SCRs in place of the more usual diodes, and each SCR is phase controlled in
the manner described on the previous pages.
Figure 4-11: Basic three-phase bridge rectifier circuit
R+

Shaded area shows R+


SCR forward biased
period
0

Return path period:

S+

T+

90
30

first via S- SCR


then via T- SCR

R+

S+

T+

R (load)

R+

150

S current
T current

Each SCR controls the rectifier conduction during one half cycle period of an
input cycle. Taking the R phase as an example, the top SCR (R+) controls the R
phase positive half cycle, and the lower SCR (R) controls the negative half cycle.
Looking at the R phase positive half cycle (R+) in detail, the three-phase waveform diagram shows that this device is forward-biased only for a 120 period between 30 and 150 of the incoming R phase waveform. This is true of all six
SCRs and means that the bridge output voltage can be controlled over its full
range by controlling the individual SCR conduction angles between 30 and 150.
In practice all six SCRs are controlled such that their conduction phase angles are
identical, therefore the rectifier load current is shared equally between all three
phases.
Note: in the practical 7200 circuit, the load comprises the DC Busbar filter
(smoothing) capacitors, the batteries (when the battery circuit breaker is closed)
and the power inverter section. The rectifier SCRs are thus controlled at the phase
angle necessary to maintain the DC Bus voltage at the required battery charge
voltage while at the same time passing the power demanded by the inverter to
enable it to produce its correct output voltage over a wide load range.

s4-c1.fm5 - Issue 2 Dated 21/08/97

4-13

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

1.5

7200 Series UPS Service Manual

Rectifier construction
The rectifier power components and the static switch power components are assembled on the same heatsink , as illustrated below.
Figure 4-12: Power rectifier construction

Connections to snubber boards


and gate drivers

RECTIFIER 3-Ph
MAINS FEED

STATIC BYPASS
MAINS FEED

Bypass SCRs

Connections to snubber board


and gate driver

Input current CTs


Rectifier SCRs
RECTIFIER OUTPUT
DC Busbar
Gate Driver (trigger)
board

4-14

Snubber board

s4-c1.fm5 - Issue 2 Dated 21/08/97

7200 Series UPS Service Manual

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

Figure 4-13: Rectifier assembly wiring details

Yellow
Red

Yellow
Red

X4
2 1

Yellow
Red

X3
2 1

Yellow
Red

X2
2 1

Yellow
Red

X1
2 1

1 4

2 1
X8

Black

T8

X5
2 1

Black

V6

K2

3
X3

White

Yellow
Red

X6
2 1

G2

Black

G1
K1

X7

G2

4542040W

G1
K1

Black

K2

Black

3
X2

4540043B

V5

White

G2

T7

V4

G1

K1

57
58

59

+
s4-c1.fm5 - Issue 2 Dated 21/08/97

1 4

Black

K2

3
X1

White

From Interface PCB


45900540 (X18)

4-15

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

7200 Series UPS Service Manual

Depending on the module rating, the rectifier SCRs can take the form of Twinpak or individual devices. As their name suggests, Twinpak devices contain
two SCRs in a single moulded package (See Figure 4-14). As shown, the anode
of one device is internally connected to the cathode of the other, and brought out
to a power connection along with the remaining free anode and cathode. This then
forms a convenient package for the phase controlled rectifier application, with the
a.c. input connected to the common power connection and the DC Bus positive
and negative connections made to the appropriate anode and cathode, as shown.
Separate gate connections are provided, with connection G1 being internally connected to the (+) SCR and G2 to the () SCR.
Where single devices are used, their anode, cathode and gate connections are individually identified.
The gate drive signals take the form of a high frequency modulated waveform 2
which is produced by the Rectifier Logic Board and present whenever the particular SCR is due to be turned on. The gate signal is not required once the device is
turned on, in practice it is applied only for a short burst which avoids excessive
wear on the SCR gate material (see paragraph 3.2 on page 4-39).
The Rectifier Logic Board gate drive signals are connected via ribbon cables to
the Driver Interface Board which contains snubber components designed to
ensure clean rectifier SCR switching, and is mounted on the rectifier assembly
itself. This board applies the drive signals to the SCR gate/cathode via twisted pair
cables note that an auxiliary cathode connection is often provided on the SCR
device for connecting to the negative end of the gate drive cables.
Figure 4-14: Twinpak SCR internal details
AC Input
+VE DC BUS

VE DC BUS
+VE SCR Gate (G1)

4-16

VE SCR Gate (G2)

s4-c1.fm5 - Issue 2 Dated 21/08/97

7200 Series UPS Service Manual

1.6

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

Rectifier control system


Figure 4-15: Rectifier control system
Input
Fuses

Rectifier Assembly
Phase
Controlled
Rectifier

Rectifier Logic Board

UPS Logic Board

DC Bus Neg

+
-

Battery
Breaker
Battery

Drive
Interface Bd.

DC Bus Pos
TO INVERTER
SECTION

Battery current sense

Input current sense

Input voltage sense

Input
Choke

Operator Logic Board

DC Busbar
filter capacitors

DC Bus voltage sense

Input mains

Input
Isolator

Alarm Interface Board


(I/O Option)

Remote Alarms
Operator Control
Panel

High Voltage
Interface Board

ON GENERATOR

External Control Options

1.6.1

Control system overview


Figure 4-15 shows the control boards associated with the rectifier control together
with their major control signals.
The Rectifier Logic Board is central to the rectifier control system and is the board
ultimately responsible for generating the rectifier SCR gate drive signals at appropriate phase angles to effect the phase-control techniques described earlier in this
chapter. At its heart is a complex, analogue voltage regulation circuit which uses
the input voltage, input current, DC bus voltage and battery current sense signals
within a series of closed-control loops.
The control system offers the following features, each of which is functionally described in the remainder of this chapter:
charge mode selection i.e. automatic and manually controlled switching
between float and boost charge modes (where applicable).
adjustable input current limit and battery current limit functions.
individually adjustable float, boost, and manual voltage reference levels.
battery temperature compensation which reduces the DC bus voltage progressively if the battery cabinet temperature rises above 25C.
input supply fault detection.
DC overvoltage and undervoltage fault detection.
controlled start/stop features.

s4-c1.fm5 - Issue 2 Dated 21/08/97

4-17

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles
1.6.1.1

7200 Series UPS Service Manual

Analogue control signals


Input mains voltage sense

The 3-phase input mains voltage is attenuated on the High Voltage Interface
Board and three line-line proportional sense signals are passed to the Rectifier
Logic Board where they provide zero-crossing reference signals for the phasecontrol timing circuits and are also monitored by input undervoltage and input
phase sequence fault detection circuits.
Input current sense

The rectifier input current is detected by CTs fitted to the power rectifier assembly. The signals produced by these CTs are rectified on the High Voltage Interface
Board and a single input current sense signal, proportional to the total input current, is connected to the input current limit circuit on the Rectifier Logic Board
via the UPS Logic Board.
Note: the sensitivity of this signal is selected by jumpers on the High Voltage Interface Board.
DC Bus (battery) voltage sense

The DC busbar voltage is a function of the rectifier output when the rectifier is
operative, and a function of the battery voltage when the rectifier is inoperative
and the batteries are discharging. This voltage is attenuated on the High Voltage
Interface Board and a proportional DC voltage sense signal is passed to the Rectifier Logic Board where it provides a feedback input to the rectifier voltage regulation control loop.
Battery current sense

Battery current is sensed by a Hall-effect DCCT connected in the battery positive line. The signal produced by the CT is rectified on the High Voltage Interface
Board and a current-proportional signal is connected to the battery current limit
circuit on the Rectifier Logic Board via the UPS Logic Board. The sense signal is
polarity-sensitive i.e. a positive signal indicates a charging current, and vice
versa.
Note: the sensitivity of this signal is selected by jumpers on the High Voltage Interface Board.
1.6.1.2

Digital control signals

Various digital signals are passed between the UPS Logic Board and all the other
boards connect to it. These can broadly be categorised as:
alarm data generated on the Rectifier Logic Board and UPS Logic Board
which are passed to the Operator Control Panel via the Operator Logic
Board also to the Alarms Interface Board (for remote indication) where
fitted.
rectifier metering data generated on the UPS Logic Board and passed to
the Operator Control Panel e.g. input voltage, battery volts current
metering.
control data entered at the Operator Control Panel which is stored by the
UPS Logic Board e.g. boost charge parameters, DC voltage monitor
threshold parameters; manual selection of Rectifier ON/OFF status and
immediate Boost Charge mode.
external control options e.g. remote stop, emergency shutdown, on-generator input current limit.

4-18

s4-c1.fm5 - Issue 2 Dated 21/08/97

7200 Series UPS Service Manual

1.6.2

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

Charge mode selection


Although the float, boost, and manual charge operating voltage levels are individually adjustable by potentiometers on the Rectifier Logic Board, the selected
mode of operation is determined by digital command signals generated by the
UPS Logic Board and applied to the Rectifier Logic Board control logic (See paragraph 2.3.2).
The automatic boost mode parameters (boost voltage level and duration, and
changeover threshold) are entered via the Operator Control Panel and stored in the
UPS Logic Board micro system. Changeover from float charge to either boost or
manual charge modes can also be initiated manually from the Operator Control
Panel at any time.

1.6.3

Input supply fault detection.


The input voltage sense signal is applied to undervoltage and phase sequence
fault detection circuits on the Rectifier Logic Board which shut down the rectifier
and provide error signals to the UPS Logic Board under fault conditions (See paragraph 2.3.6). On the Rectifier Logic Board, led H9 indicates an input undervoltage error and H8 a phase sequence error.

1.6.4

Input current limit


On the Rectifier Logic Board, if the input current sense signal exceeds the current
limit threshold (adjustable between 100%-130%) it phases-back the rectifier, and
reduces the DC busbar voltage to a level which maintains the input current at its
set limit level (See paragraph 2.3.4.2); it also sends an input overload signal to
the UPS Logic Board which initiates an alarm on the Operator Control Panel.
Note: if required, the input current limit level can be automatically reduced by
25% when the UPS is operating on a stand-by generator. This facility is enabled
from the Operator Control Panel and initiated by auxiliary contacts of the On
Generator contactor which are connected to the UPS Logic Board via the External Alarms Board.
Led H6 illuminates on the Rectifier Logic Board when the input current limit circuit is active.

1.6.5

Battery current limit


A battery current limit circuit on the Rectifier Logic Board operates in a similar
manner to the input current limit circuit described above, and phases-back the
rectifier to reduce the DC busbar voltage if the battery charge current exceeds a
predefined current limit threshold (See paragraph 2.3.4.1). It also sends a battery current limit status signal to the UPS Logic Board where it is used by the
software controlled automatic boost charge changeover function.
Led H5 illuminates on the Rectifier Logic Board when the input current limit circuit is active.

1.6.6

Battery temperature compensation


This is an optional control input to the Rectifier Logic Board which progressively
reduces the DC busbar voltage as the battery cabinet temperature rises above
25C and is included to prevent reduced battery life due to the effects of overheating. The temperature is monitored by a thermistor located in the battery cabinet
which produces a temperature-variable signal on the High Voltage Interface

s4-c1.fm5 - Issue 2 Dated 21/08/97

4-19

SECTION 4 - Rectifier Operation & Control


CHAPTER 1 - Rectifier Operating Principles

7200 Series UPS Service Manual

Board which is then passed to the Rectifier Logic Board via the UPS Logic Board
(See paragraph 1.6.6).
1.6.7

Controlled start/stop
The Rectifier Logic Board contains a start/stop control circuit which effectively
turns ON/OFF the rectifier SCR drive signals. This circuit is affected by several
circuits on the Rectifier Logic Board itself (e.g. input undervoltage or phase rotation error) and also by a start/stop signal produced on the UPS Logic Board in response to various monitored system-wide control signals (See paragraph 2.3.6).

1.6.8

DC overvoltage and undervoltage fault detection


The UPS Logic Board uses DC voltage sense signal to detect various critical DC
busbar voltage levels. DC Over/Under voltage conditions instigate a rectifier
shutdown and trip the battery circuit breaker. Other conditions produce a warning
alarm only; such as the Low Voltage which warn the operator of an impending
DC undervoltage (and therefore battery trip) condition.
Note: the operating threshold of these conditions are programmable via the Operator Control Panel.

1.6.9

Battery Circuit Breaker


The battery circuit breaker is manually closed but can be electrically tripped by
the UPS Logic Board. The circuit breaker cannot be initially closed until the DC
bus voltage rises above the DC Undervoltage trip level. Once closed, it will be
tripped by the UPS Logic Board if:
the DC bus voltage rises to the DC Overvoltage level.
the DC bus voltage falls below the DC Undervoltage level (i.e. with the
mains failed and the batteries discharged to their trip level).
the emergency stop circuit is activated.

4-20

s4-c1.fm5 - Issue 2 Dated 21/08/97

Section 4:

Chapter 2 - Rectifier Logic Board

2.1

Chapter overview
This chapter contains a circuit description of the Rectifier Logic Board used
across the whole 7200 Series UPS model range, and should be read in conjunction
with circuit diagram SE-4520074-A (4 pages). Signal annotations shown on the
circuit diagrams are shown in italics in the following text e.g. [IREC>.

2.2
2.2.1

General description
Circuit board functions
The board is responsible for providing the drive signals for the rectifier SCRs at
the appropriate phase angle necessary to produce the required DC Bus (battery
charging) voltage. In so doing, the board monitors the following UPS parameters
via the High Voltage Interface Board and UPS Logic Board (See Figure 4-15):

Input voltage for SCR synchronisation and mains failure detection.


Input current for SCR current protection.
DC Bus (battery) voltage closed-loop voltage regulation.
Battery current for battery protection.
Battery temperature for battery protection.
System control signals from the UPS Logic Board microcontroller (Run/
Stop; Charge mode selection; On Generator; Current limit selection;
soft-start to reduce dc bus capacitors inrush current on start-up).

As part of its control function, the Rectifier Logic Board detects several abnormal
operating conditions and provides the UPS Logic Board control system with the
following error status signals:

2.2.2

Rectifier overload.
Input supply phase rotation error.
Input supply undervoltage.
Rectifier On/Off.
Control power supply failure.

Input/Output connections
The Rectifier Logic Board has four connectors, described below:
X1 Output SCR gate drive signals to Rectifier Driver Interface Board
4542040-W
X2 System control signals to/from the UPS Logic Board 4550007-H
(See Table 4-1).
X3 Control power supplies input from AC-DC Power Supply Board
4503030-M.
X4 Interface to second rectifier control circuit in a 12-pulse rectifier system (optional facility not used in standard module).

s4-c2.fm5 - Issue 3 Dated 09/11/98

4-21

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

7200 Series UPS Service Manual

Table 4-1: Connector X2 pinout details


PIN

I/O

1-4

I/O

0V ground reference for digital electronics

5-8

+12V power supply to UPSLB

9-12

-12V power supply to UPSLB

13-14

I/O

Common ground reference for analogue sense inputs

15

VREC_AC Input mains voltage sense signal phases U-W (approx. 15Vp-p)

16

VREC_BA Input mains voltage sense signal phases V-U (approx. 15Vp-p)

17

VREC_CB Input mains voltage sense signal phases W-V (approx. 15Vp-p)

18

IB Battery current sense signal

19
20

Function

Not in use
I

21-23

IREC Rectifier input current sense signal (6 pulses/cycle)


Not in use

24

IREC_T Used in parallel systems only (not available)

25

VB DC Bus (battery) voltage feedback 3Vdc @ 432Vbus

26

T_BAT Battery cabinet temperature sensor 2.98Vdc @ 25C

27

IDC_1 Not used in standard model (12 pulse rectifier option only)

28

IDC_2 Not used in standard model (12 pulse rectifier option only)

29

DB Used in parallel systems only (used for input current sharing control)

30

DB_0 Used in parallel systems only (used for input current sharing control)

31

Not in use

32

OVL_REC Signals rectifier overload error status to UPSLB (Overload = 1)

33

BLK_REC Signals rectifier OFF/ON status to UPSLB (OFF = 1 and ON = 0)

34

SEQ Signals input mains phase sequence error status to UPSLB (Error = 1)

35

IN_LOW Signals low input volts error status to UPSLB (Low Volts = 1)

36

ON-REC Rectifier Run/Stop selection from UPSLB micro (RUN = 1 and STOP = 0)

37

STAT Reduced current limit selection (On generator = 1)

38

REC_A Charge mode selection from UPSLB micro

39

REC_B Charge mode selection from UPSLB micro

40

4-22

Not in use

s4-c2.fm5 - Issue 3 Dated 09/11/98

7200 Series UPS Service Manual

2.2.3

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

Block diagram description


The following illustration shows the Rectifier Logic Board at its most basic functional block diagram level each of the blocks shown is described in more detail
in the remainder of this chapter.
Figure 4-16: Rectifier Logic Board basic block diagram
Mains volts sense
(3-phase) sync signal

Batt I sense
Bus Volts F/B

Volts
Error
Amplifier

DC Control
voltage

DC Reference
voltage
Batt temp sense
Charge Mode
Selection
(UPSLB)

Reference
Voltage
Generator

Bi-directional
Control
(UPSLB)

AC-DC Supply

Start/
Stop
Logic

Rectifier
SCR
Drive
Pulses

Start/Stop
control line

Input I sense

Drive
Pulse
Generator

Fault
Detection
Logic

Power
Supply

Phase control principles

The board regulates the DC busbar (battery charging) voltage using standard
phase controlled techniques i.e. by controlling the point at which each rectifier
SCR is turned on during its forward biased period. This is achieved by detecting
the point at which each SCR becomes forward biased and then applying a variable
time delay between this point and the production of its gate drive pulses. Maximum DC busbar voltage is obtained when the delay is very short, whereupon the
SCRs are allowed to conduct for the whole of their forward biased period. Consequently, as the time delay is increased the SCRs conduct for a shorter period
leading to a reduced DC busbar voltage (See paragraph 1.4).
Drive pulse generator

This block has two major responsibilities. First, it contains a timing circuit which,
in conjunction with the DC control voltage signal, controls the timing of the
SCR drive pulses relative to the mains voltage sense signals (i.e. it uses the mains
sense signals to synchronise each SCRs timing to the relevant forward biased
period of the incoming supply); second, it contains a signal conditioning circuit
which processes the resulting drive pulses to provide a modulated drive waveform.
The DC control voltage directly controls the adopted SCR drive signals time
delay and therefore also the DC busbar voltage i.e. increasing the DC control
voltage reduces the time delay and results in a greater DC busbar voltage.

s4-c2.fm5 - Issue 3 Dated 09/11/98

4-23

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

7200 Series UPS Service Manual

Reference voltage generator

The reference voltage generator provides the volts error amplifier with its DC
reference voltage input. This is seen as a voltage demand signal by the voltage
error amplifier in that it represents the DC busbar target voltage.
The reference voltage generator can produce one of four DC reference voltage
levels equating to float charge, boost charge, manual charge, or test; as requested
by the processor on the UPS Logic Board. Note that although the charge mode is
selected by the UPS Logic Board, the respective DC reference voltage for each
mode is individually adjustable by potentiometers on the Rectifier Logic Board
itself.
An analogue signal proportional to the battery temperature is also applied to the
reference voltage generator and can be used to reduce the DC reference voltage by 1.5Vdc/C as the battery temperature rises between 25C and 35C.
The test mode is used for fault-finding only and allows the DC busbar voltage to
be manually adjusted within the range 0V to 650Vdc.
Volts error amplifier

In the block diagram the primary output of the voltage error amplifier is annotated DC control voltage. This is the signal which directly controls the DC
busbar voltage via the time delay circuit in the drive pulse generator see above.
The magnitude of the DC control voltage is determined by a comparator within
the volts error amplifier which compares the DC busbar voltage feedback signal
with the DC reference voltage produced by the reference voltage generator
block. This basically forms a closed-loop control system, in that the error amplifier constantly modifies the DC control voltage in such a way as to make the rectifier phase-forward or phase-back (as required) to maintain equilibrium between
the DC reference and DC bus feedback signal voltages.
The volts error amplifier also monitors the input current and battery current
sense signals and reduces the DC control voltage if either of these signals reaches a preset current limit threshold. Such an event reduces the DC busbar voltage
to maintain the particular current at its limiting value.
Start/Stop Logic

The start/stop command signal produced by this circuit block is controlled by a


signal produced on the UPS Logic Board in response to its system control logic,
and affects both the volts error amplifier and drive pulse generator blocks.
When the signal is in its stop mode it totally inhibits the drive pulse generators
outputs, effectively closing down the rectifier, and also clamps the DC control
voltage to zero by inhibiting the volts error amplifier output thus demanding
zero DC busbar voltage. When the start/stop signal enters its start mode it immediately releases the inhibit on the drive pulse generator block, enabling the
output drive pulses to be produced; however, the clamp on the volts error amplifier is lifted gradually such that the DC reference voltage is allowed to rise to
its operational level at a controlled rate.
The combined effects of these two operations ensure the power rectifier is stopped
and started in a controlled manner providing an input current walk-in on startup to prevent undesirable input current surges damaging the power components.
This soft-start-controlled walk-in takes approximately 5 seconds to charge the dc
capacitor tray.

4-24

s4-c2.fm5 - Issue 3 Dated 09/11/98

7200 Series UPS Service Manual

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

The fault detection block output is also connected to the start/stop control line
and has the same effects as the start/stop control signal applied from the UPS
Logic Board. It also applies an input to the start/stop logic block which passes a
fault status signal back to the UPS Logic Board in response to certain detected
fault events hence the start/stop line between the UPS Logic Board and Rectifier
Logic board is shown as bi-directional in the block diagram.
Fault detection logic

This block detects several abnormal/fault conditions on the Rectifier Logic Board
and, depending on the condition will:
provide on-board led indication.
send a fault signal to UPS Logic Board (via the Start/Stop Logic block).
apply a stop condition to the start/stop control line.
Following is a list of the monitored conditions see paragraph 2.3.4.3 for a full
circuit description.

Table 4-2: Monitored faults


Stop
Line?

Signals to
UPSLB

Indication

Battery current limit

No

CHG

H5

Input current limit

No

OVL

H6

Input mains undervoltage

Yes

IN_LOW
BLK_REC

H9

Input mains phase sequence error

Yes

SEQ
BLK_REC

H8

Control power supply monitor

Yes

BLK_REC

H7

Condition

Control power supplies

The Rectifier Logic Board requires regulated 12Vdc supplies for its operation.
These are obtained from the AC-DC Power Supply Board and will be present
whenever the UPS input mains supply (or static bypass supply in a split-bypass
system) is live. An on-board, three-terminal +5V regulator (N14) is driven from
the +12V supply to provide a regulated +5V supply voltage rail.
In the event of a mains failure the AC-DC Power Supply Board will become inactive and the 12V rails are provided by the DC-DC Power Supply Board via the
UPS Logic Board provided the batteries remain connected to the DC busbar (see
section 3 of this manual for details of the control power supplies).

s4-c2.fm5 - Issue 3 Dated 09/11/98

4-25

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

2.3

7200 Series UPS Service Manual

Detailed circuit description

2.3.1

Introduction
The Rectifier Logic Board circuit diagram (SE-4520074-A) comprises 4 sheets.
With reference to the block diagram description in Figure 4-16, the drawings can
broadly be described as follows:
Sheet 1 contains a signal map showing the interconnection of the signals
passing between the other three sheets.
Sheet 2 contains the:
reference voltage generator circuit
battery temperature compensation circuit
volts error amp circuit
battery current limit circuit
input current limit circuit
soft-start control amplifier
Sheet 3 contains the timing portion of the drive pulse generator circuit
together with the mains undervoltage (-15%) detection circuit
Sheet 4 contains the:
signal conditioning portion of the drive pulse generator circuit
start/stop logic and fault detection circuits
control power supplies and its power failure detection circuit

2.3.2

Reference voltage generator


(refer to diagram sheet 2)
This circuit is responsible for providing the volts error amplifier with a DC reference voltage which acts as a voltage demand signal, informing the volts error
amplifier of the desired DC busbar (battery charging) voltage.
Four reference voltages are available: Test, Boost, Float, and Manual, which are
individually set by R19, R20, R21, R22 respectively. These resistors are connected in independent resistor chains which are fed from a stable +5V supply produced by a voltage regulator circuit comprising N6, R23 and R24. If the regulator
is working correctly its Vref input (junction R23/R24) will be at 2.5V.
A multiplexer i.c. (D1) is used to select one of the four reference voltages under
the control of the microprocessor on the UPS Logic Board (REC_A and REC_B
signals). The four pot wiper voltages at the multiplexers inputs 1X thru 4X are
connected to its X output according to the table below:
Table 4-3: Logic table for Q1 (4052)
Mode

REC_A

REC_B

Output X =

Output Y =

Manual

X1

Y1 (H4 Yellow)

Float

X2

Y2 (H3 Green)

Boost

X3

Y3 (H2 Green)

Test

X4

Y4 (H1 Yellow)

Notice that the multiplexers Y channel provides on-board led indication of the
selected charger mode by switching the return path for leds H1-H4.

4-26

s4-c2.fm5 - Issue 3 Dated 09/11/98

7200 Series UPS Service Manual

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

As shown on sheet 4, the [REC_A/B> signals are obtained directly from the UPS
Logic Board via connector X2-38 and X2-39: however, these can be overridden
by links connected to X9 positions 1 & 2. This is a test facility, and enables the
bench/commissioning engineer to select any one of the four charger modes while
undertaking the board set-up procedures. X9 links 1 and 2 must be open during
normal UPS operation.
The selected reference voltage from Q1 (X) (pin13), which can be monitored at
test-point X8-6, is inverted by N4a and applied to the volts error amplifier (N4b)
via R43 (22k) this is the point annotated DC reference voltage in Figure 4-16,
and is approximately 3.0Vdc when the dc bus is at 432Vdc. As the signal is inverted by N4a, the DC reference voltage is always of a negative polarity i.e.
the demanded DC bus voltage increases as the signal goes more negative. As a
guide, this (linear) signal has a sensitivity of around -7.24mV/V(bus demand).
2.3.3

Battery temperature compensation


Note: this is an optional feature which is normally disabled in a standard module
A temperature sense signal, proportional to the battery cabinet temperature, is
connected via terminal X2-26 and jumper X5 (pins 2-3) to amplifier N2c, where
it is differentially summed with a variable voltage set by R121. The output from
N2c is then summed with the reference voltage generator output (See paragraph
2.3.2) at N4a inverting input (test point X8-5).
The affected of the temperature sense signal is to reduce the DC reference voltage by approximately 1.5Vdc per C as the battery temperature increases above
25C. This is done to prevent the batteries from being overcharged and so prolongs battery life.
That is, the temperature signal has no affect until it overcomes the threshold set
by R121, whereupon it progressively reduces the DC busbar voltage as the temperature increases.
The circuit is calibrated by connecting jumper X5 to position (1-2) and adjusting
R121 to obtain 2.98V at test point X5-1 (equates to 25C).
Note: this must be undertaken before the various charge levels are set.
If the facility is not required, leave jumper X5 in position (1-2). This connects the
reference voltage from R121 to both N2c inputs, where they self cancel.

2.3.4

Volts error amplifier


The earlier block diagram description states that the volts error amplifier produces the DC control voltage which ultimately controls the DC busbar voltage.
In practice the volts error amplifier circuit comprises two amplifiers (circuit diagram sheet 2); N4b (which is the true error amplifier) and N3a (which is a unity
gain buffer amplifier). The output signal, analogous to the DC control voltage
signal in the block diagram, is annotated [MOD>.
N3a has five diode-coupled signals connected to its non-inverting input (pin 3)
obtained from:
a fixed dc biasing circuit
the error amplifier (N4b) output via V5
the input current limit detector (N1d) via V3
the battery current limit detector (N1a) via V4
a soft-start signal from the start/stop logic circuit (N4d) via V6
Each of these inputs can affect N3as [MOD> output, as described in detail below.

s4-c2.fm5 - Issue 3 Dated 09/11/98

4-27

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

7200 Series UPS Service Manual

Fixed bias

A fixed bias voltage of approximately +10.5Vdc is applied to N3a pin 3 by the


circuit comprising V1, R60, R55 and R63.
In the absence of all other inputs to N3a the magnitude of this signal would drive
N3a output [MOD>) to +10.5V which is sufficient to cause the drive pulse generator circuit to turn on the rectifier SCRs with minimum delay producing maximum DC busbar voltage. In practice, the inputs to N3a pin 3 from the voltage
error amplifier and current limit circuits therefore control the rectifier by pulling
down, or clamping, the voltage established by the fixed bias circuit: thereby reducing the SCRs conduction to an angle which produces the desired DC busbar
voltage. Such clamping action is achieved by these circuits via their respective
coupling diodes (V3-V6).
Under normal operating conditions the current limit circuits are inactive and
diodes V3 and V4 are reversed biased and have no affect on N3a. The DC control
voltage ([MOD>) is therefore usually controlled by the output from the voltage
error amplifier (N4b) alone.
Error amplifier (N4b)

N4b compares the DC reference voltage produced by Q1/N4a (See paragraph


2.3.2) with a DC busbar voltage feedback signal (approximately 3.0V at
432Vbus) which is connected to X2-25 and fed to the error amplifier via buffer
N2a and R42 (22k).
Note that the DC reference voltage signal has a positive polarity due to the noninverting action of N2a (monitored at X8-1) while the DC reference voltage produced at N4a pin 1 has a negative polarity. The error amp (N4b) therefore compares the magnitude of these two signals differentially.
Error amplifier regulation circuit action

If the DC busbar falls below its required voltage the DC busbar feedback signal
will be lower in amplitude than the DC reference voltage and the voltage error
amplifier output will ramp in a positive direction, lifting the clamp (by V5) on
N3a non-inverting input. This allows the DC control voltage ([MOD>) to increase so raising the DC Busbar voltage. This action will take place until the
DC busbar feedback signal increases to a level equal to the DC reference voltage at which point the output from N4b output will remain constant and cease
demanding an increase in DC busbar voltage.
If the DC busbar rises above the required voltage the circuit will respond with the
opposite polarity i.e. if the DC busbar feedback signal is higher than the DC
reference voltage then N4b output will decrease and further clamp the input to
N31 with a resulting reduction in the DC control voltage ([MOD>).
Due to the presence of C28 in its feedback path, the volts error amplifier (N4b)
integrates any amplitude difference between its DC busbar feedback (+) and
DC reference voltage (-) input signals, and so affects the rectifiers regulation
speed of response. The circuit response can be selected by jumper X6 which
should be positioned (1-2) in modules rated at 60kVA and below (faster response), and (2-3) in modules rated at 80kVA and above.

4-28

s4-c2.fm5 - Issue 3 Dated 09/11/98

7200 Series UPS Service Manual

2.3.4.1

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

Battery current limit


Battery current sense signal

Battery current is measured by a Hall-effect dc current sensor which produces a


dc voltage proportional to the battery current. This voltage is calibrated on the
High Voltage Interface Board (see paragraph 2.3.22 on page 7-11) and then
passes through the UPS Logic Board to enter the Rectifier Logic Board at X2-18
where it is buffered by N1c. The resulting sense signal appears as a positive voltage at test point X8-2.
Battery current limit circuit operation

From test point X8-2 the battery current sense signal is connected to a level detector circuit (N1a) whose output pin 1 changes from logic high to low if the battery current exceeds the level set by R18. When this occurs it clamps the input to
the volts error summing amplifier (N3a), via V4, reducing the DC control voltage ([MOD>) which in turn reduces the DC busbar voltage thereby reducing the
battery charge current. The reference voltage set by R18 can be monitored at test
point X8-8 and can be in the range 0V to -5V. This range is determined by a 5V
regulator circuit, based on N5, connected between the 0V and -12V power rails.
If the regulator circuit is operating correctly the junction of R12 and R13 will be
held at -2.5V. R18 is normally adjusted to obtain 0.1Vdc per amp of required current limit at X8-8 for the 30kVA, 40kVA and 60kVA models respectively.
This circuit is dynamic in its operation i.e. as the DC busbar voltage reduces so
too does the battery charge current. Ultimately, the circuit operation reduces the
DC busbar voltage to a level which sustains the battery charge current at the level
set by R18.
In practice the battery current limit circuit is only likely to become active when
the UPS input mains supply returns from a prolonged outage: whereupon the
heavily discharged batteries are certain to demand a high initial recharge current.
Under these circumstances the DC busbar voltage is initially restricted but will
gradually increase to its nominal value while maintaining the battery current at its
set limit level as the batteries regain their charge.
Battery current limit indication

Led H5 illuminates when the battery current limit circuit is active. The indication
circuit operates by detecting whether or not V4 is turned on. When V4 is conducting, the input to N3 pin 6 via R56 is approximately -0.6V with respect to the signal
applied via R57 to pin 5. These conditions force N3 pin 7 to switch high which
illuminates H5 and produce a logic high [CHG> signal, which is connected to the
UPS Logic Board, via X2-23, to inform it of the battery current limit status.
2.3.4.2

Input current limit


Input current sense signal

The UPS input current is sensed by current transformers (CTs) fitted to the rectifier assembly input R and T lines. The CTs outputs are rectified and normalised
on the High Voltage Interface Board (see paragraph 2.3.18 on page 7-10) and the
resulting dc voltage, which is proportional to the input current, is connected via
the UPS Logic Board to the Rectifier Logic Board X2-20. From here the sense
signal is buffered by N1b and can be measured as a positive voltage at test point
X8-3.

s4-c2.fm5 - Issue 3 Dated 09/11/98

4-29

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

7200 Series UPS Service Manual

Input current limit circuit operation

From test point X8-3 the input current sense signal is connected to a level detector
circuit (N1d) whose output pin 14 changes from logic high to low if the input current exceeds the level set by R17. When this occurs it clamps the input to the
volts error summing amplifier (N3a), via V3, reducing the DC control voltage
([MOD>) which in turn reduces the DC busbar voltage thereby reducing the input
current. The reference voltage set by R17 can be monitored at test point X8-7 and
can be in the range -0.5V to -5V. This range is determined by a 5V regulator circuit, based on N5, as described above for the battery current limit circuit. In practice R17 is adjusted to obtain 0.8Vdc at test point X8-7 in a 30kVA model; this is
increased to 1.2Vdc for 40kVA and 1.6Vdc for 60kVA models.
This circuit is dynamic in its operation i.e. as the DC busbar voltage reduces so
too does the input current. Ultimately, the circuit operation reduces the DC busbar
voltage to a level which sustains the input current at the level set by R17.
When electronic switch D2 closes it increases the sensitivity of the input current
sense signal to N1d by connecting R35 in parallel with R49. This results in the
current sense signal reaching the set limit threshold at a reduced input current
level and effectively reduces the circuits operation by approximately 25%. This
reduced threshold is controlled by the [STAT> signal generated on the UPS Logic
Board and applied via X3-37 (see paragraph 3.3.12.2 on page 7-46). This is used
to reduce the rectifier input current when the UPS is supplied from a stand-by generator.
Note: this signal is applied via the optional Remote Alarms Board which provides an interface between the external on generator signal and the UPS Logic
Board control logic.
Input current limit indication

Led H6 illuminates when the input current limit circuit is active. The indication
circuit operates by detecting whether or not V3 is turned on. When V3 is conducting, the input to N3c pin 9 via R58 is approximately -0.6V with respect to the
signal applied via R59 to pin 10. These conditions force N3 pin 8 to switch high
which illuminates H6 and produce a logic high [OVL> signal, which is connected
to the UPS Logic Board, via X2-32, to inform it of the input current limit status.
Parallel module operation

When two or more 7200 UPS modules are connected to a common battery a
system of input current sharing is employed to ensure that both modules share the
battery charging burden. Such a system monitors the input current from both
modules and employs a correction signal to either phase-forward or phase-back
the rectifiers as necessary.
In practice the monitored current is obtained from X2-24, which is connected to
the output of the input current sensing buffer amplifier (N1b); and the correction
signal is applied to X2-29, from where it applies an offset signal to the volts error
amplifier (N4b) via buffer N2b. The correction signal can be monitored at test
point X8-4.
2.3.4.3

Start/Stop control

A start/stop control input is applied to the volts error amplifier via diode V6.
This signal, annotated [STOP> (on sheet 1), goes high when the start/stop circuit
requires a rectifier shut-down, and vice-versa. In its stop mode, this signal is inverted to a logic low at N4 pin 8 which is then buffered by N4d and applied as a
clamp to the volts error amplifier. This effectively phases-back the rectifier and

4-30

s4-c2.fm5 - Issue 3 Dated 09/11/98

7200 Series UPS Service Manual

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

demands zero DC busbar voltage.


Note: for a full description of the start/stop control logic see paragraph 2.3.6.
When the start/stop signal goes to its start mode the [STOP> signal goes low and
the output from N4 pin 8 will switch high; however, this is not immediately reflected at the output of N4d pin 14 due to an R-C delay circuit (C19/R39) connected to its input in parallel with the start/stop signal. The effect of the R-C circuit is
to prevent the clamping effect of V6 on the volts error amplifier from being removed too quickly, as this could lead to a large inrush current as the rectifier energises the dc busbar filter capacitors. The presence of the R-C circuit thus leads
to a controlled power walk-in when the rectifier is started. Notice that the delay is
adjustable by means of jumper X7. When X7 is fitted 2-3 the time constant produces a slow walk-in of approximately 5 seconds, but when fitted to position 12 is connects R36 in parallel with R39 which speeds up the walk-in to 1 second.
In practice the link is normally fitted 2-3 (slow).
2.3.5

Drive pulse generator


(refer to diagram sheet 3)
The drive pulse generator monitors sensing signals proportional to the UPS
input mains voltage together with the DC control voltage ([MOD>) and produces
the rectifier SCR gate drive pulses at the conduction angle appropriate to obtaining the desired DC busbar (battery charging) voltage.
This circuit can be divided into two areas:
an analogue circuit based on a series of comparators (sheet 3) controls the
drive signal timing and thereby determines the adopted conduction angle
a digital circuit based on a custom array gate (sheet 4) provides the necessary signal processing.
The ultimate drive signals are despatched to the Gate Drive Interface Board via
transistors V37 to V42 and terminals of connector X1 shown on sheet 4.

2.3.5.1

Analogue timing control circuit

The drive signal timing is controlled by three comparator circuits (one per phase)
which compare sense signals proportional to the three phase input mains supply
with the variable DC control voltage ([MOD>). In reality each comparator contains two similar circuits: one to handle the timing for the positive SCR and the
other for the negative SCR in each phase i.e. one deals with the positive half
cycle and the other with the negative half cycle of the incoming a.c. mains waveform. A full description of the comparators operation is given below.
Note: as all three phases are identical only the R phase is described in detail.
Input supply sensing (for synchronising SCR timing to the Input Supply)

The three phase input mains supply is sensed via an attenuator circuit on the High
Voltage Interface Board (see paragraph 2.3.3 on page 7-7) whose outputs pass
through the UPS Logic Board and are then connected to the Rectifier Logic Board
connector X2 pins 15, 16, 17 (sheet 3). On the High Voltage Interface Board the
mains sense signals are monitored by differential amplifiers on a line-to-line
basis; the input to the R phase control circuit at X2-15 ([VREC_AC>) is in fact derived from the R-T phase and will in fact lag the R phase voltage by 90. A further
lag of 180 is imposed by N12a, therefore the resulting output at N12 pin 1 is a
sine-wave which lags the true mains R phase by 270.

s4-c2.fm5 - Issue 3 Dated 09/11/98

4-31

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

7200 Series UPS Service Manual

Figure 4-17: R-Ph sense voltage phase details


R-Ph Positive
half cycle

Mains R-Ph
[VREC_AC>

Mains delayed
by 270
(N12 pin 1)

270 lag

dead band

Figure 4-17 shows that due to the applied 270 phase shift the maximum and minimum levels of the sense signal at N12 pin 1 coincide with the changeover between positive and negative half cycles of the true incoming R-phase voltage
i.e. the sense signal falls from max to min during the true R-phase positive half
cycle and from min to max during the negative half cycle.
N8a buffers the R-phase sense voltage and passes it to N8b and N8c where it is
compared with the DC control voltage. N8b controls the positive R-phase SCR
(i.e. the SCR connected between the rectifier R phase input and the positive DC
busbar) while N8c controls the R-phase negative SCR.
DC Control voltage

The DC control voltage ([MOD>), which is produced by the voltage error amplifier and fully described in paragraph 2.3.4, was previously described as being a
DC busbar volts demand signal, in that the bus voltage is ultimately proportional
to the [MOD> signal level.
Sheet 3 of the circuit diagram shows that [MOD> is inverted by N11a and connected to the non-inverting input of N8c (pin 10), then re-inverted back to its original
polarity by N11b and connected to N8b non-inverting input (pin 5). These two
sections of N11 are configured as comparators and compare the R-phase sense
voltage with the [MOD> signal, as described below.
Comparators operation

The R-phase drive gate drive generation circuit uses three comparators: N8b controls the timing for the drive to the positive SCR, N8c controls the timing for the
drive to the negative SCR, and N8d provides dead-band timing control to both
devices.
The outputs from the above comparators are annotated [A>, [B>, [C> on the diagram and the their effects on the following digital drive circuit can be summarised
as follows:
The R-phase positive SCR is turned on when [A> and [C> are both high
(logic 1).
The R-phase negative SCR is turned on when [B> and [C> are both low
(logic 0).

4-32

s4-c2.fm5 - Issue 3 Dated 09/11/98

7200 Series UPS Service Manual

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

Considering the action of N8b: If the DC control voltage ([MOD>) applied to


N8b pin 5 is very high, the R-phase sense signal on N8b pin 6 will fall below the
DC control voltage level very early with respect to the R phase positive zerocrossover point. When this happens, the comparators output at N8b pin 7 switches high, which has already been shown in the summary to be the state required to
turn on the R-phase positive SCR. Alternatively, if the DC control voltage
([MOD>) applied to N8b pin 5 is very low, then the R-phase sense signal on N8b
pin 6 will fall below the DC control voltage level very late with respect to the R
phase positive zero-crossover point. This shows that as the DC control voltage
([MOD>) decreases, the R-phase positive SCR will be turned on later in its half
cycle and therefore produce a lower DC busbar voltage.
The negative SCR comparator (N8c) works in exactly the same way except that
the signal polarities are reversed i.e. the [B> output from N8 pin 8 goes low, turning on the R-phase negative SCR, when the R-phased sense voltage applied to
N8c pin 9 rises above the DC control signal at N8c pin 10. As has been previously described, the DC control voltage at N8c pin 10 is an inverted version of
the [MOD> signal. Thus if the volts error amplifier demands a greater DC busbar
voltage the DC control signal will go more negative and will be cut by the Rphase sense signal earlier in its forward-biased (negative) half cycle and thereby
increase the R-phase negative SCR conduction angle
N8d acts as a delayed zero-crossing detector. This open-loop comparator monitors the R-phase voltage sense signal via a C-R circuit which produces a time
delay of approximately 36 (@50Hz) i.e. when the sense voltage traverses its
zero cross-over (ZCO) point in a positive direction N8d pin 14 ([C>) will provide
a negative pulse (holding off the R phase positive SCR) equal to about 36: similarly when the sense signal traverses the ZCO in a negative direction N8d will
produce a positive pulse of 36. These pulses are gated with the main comparator
output signals [A> and [B> and provide a dead-band period while the pulses are
present. The SCR is thus allowed to conduct between 150 and 30.
Note that the DC control signal ([MOD>) is used by all three groups of comparators, therefore the S and T phases adopt the same conduction angle as the R phase.
2.3.5.2

Digital signal processing

The digital signal processing aspect of the drive pulse generator circuit is controlled by D6 and its associated components shown on the diagram sheet 4. This
ASIC applies modulation and start/stop control to the comparators outputs (signals [A> to [I>), and provides further timing checks to ensure that the resulting
drive signals are suitable for driving the rectifier SCRs.
Signal summary

The following signal summary describes the relationship between the [A> [I>
inputs and the drive output signals.
Note 1: the output drive waveforms will be modulated by a 19kHz oscillator connected to D6 pin 7.
Note 2: the outputs all assume that the start/stop line (described in detail later) is
in its start mode i.e. outputs enabled.

s4-c2.fm5 - Issue 3 Dated 09/11/98

4-33

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

7200 Series UPS Service Manual

Table 4-4: Drive logic table


Inputs
A

R-Ph Positive SCR

ON (U6-18 = 1)

S-Ph Positive SCR

ON (U6-20 = 1)

Outputs

ON (U6-19 = 1)

T-Ph Positive SCR

ON (U6-24 = 1)

1
0

R-Ph Negative SCR

S-Ph Negative SCR

ON (U6-21 = 1)

T-Ph Negative SCR

ON (U6-25 = 1)

Modulating oscillator

A modulated high-frequency drive waveform is used to enable easy a.c. coupling


between the Rectifier Logic Board and the SCRs via the Drive Interface Board.
The modulating oscillator comprises a 555 timer, D5, which is set to operate at
approximately 19kHz. A series of mixer gates in the output stage of D6 uses this
signal to modulate the output drive signal and produces a composite signal which
appears as a 19kHz squarewave pulse-train corresponding to the duration of the
required SCR TURN ON period.
D5 is reset by an output from D6 pin 14 which goes low each time D6 initiates an
SCR drive pulse at any of its six drive outputs. This ensures that every driver
output pulsetrain begins with a full-width pulse. Note that the output from D6 pin
14 is also fed back via D4e to pin 13 where it resets a series of latches concerned
with the internal drive signal timing. Thus only 10 pulses are modulated at the beginning of the SCR trigger square-wave.
Start/Stop control

The drive pulse generator circuit is controlled by the same start/stop control line
used to control the volts error amplifier (See paragraph 2.3.4.3) to ensure that
the rectifier stops and starts in a controlled manner. The stop/start logic is contained within U6 and is described in detail below.

4-34

s4-c2.fm5 - Issue 3 Dated 09/11/98

7200 Series UPS Service Manual

2.3.6

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

Start/Stop logic
The start/stop logic circuit is contained within D6 and has several inputs derived
from fault detection circuits on this board and on the UPS Logic Board. It produces summary stop/start line which:
inhibits/enables the production of the rectifier drive pulses within D6
via the [STOP> output on D6 pin 34, reduces to zero the DC control voltage produced by the volts error amplifier when in the stop mode (See
paragraph 2.3.4.3)
produces a start/stop status signal at D6 pin 36 which is connected to the
UPS Logic Board via X2-33 (See paragraph 3.3.11.1). This signal is
annotated [BLK_REC> (Blocked Rectifier) and is logic high when the start/
stop line in the stop mode. This informs the UPS Logic board that the
Rectifier Logic Board has detected a fault which results in the UPS Logic
Board turning OFF the rectifier run command signal.
The start/stop line is affected by the following fault detection and control signals.

2.3.6.1

Input mains phase rotation error

A phase sequence comparator within D6 monitors the R-phase and S-phase zero
crossover signals at D6 pins 4 and 44 (signals [C> and [F>) and produces and error
signal if these are not of the correct phase relationship.
If an error is detected:
the start/stop line is driven to its stop mode
led H8 illuminates to provide on-board indication of phase rotation error
a logic high error signal is produced at U6 pin 33 and passed to the UPS
Logic Board via X2-34 where it is processed by the system control logic
2.3.6.2

Input mains undervoltage

In addition to providing an input to the drive pulse generator comparators, the


input mains 3-phase sense signals (sheet 3) are also connected to a full-wave rectifier comprising V20-V25. The rectifier output is buffered by N11d whose output
is connected to a fixed comparator N11c. An undervoltage condition is sensed if
the sense signal at N11 pin 10 falls below the 4.5V threshold set at N11 pin 9, at
which point N11 pin 8 switches to a logic low. This equates to an undervoltage
error of 15%.
If an error is detected:
the start/stop line is driven to its stop mode
led H9 illuminates to provide on-board indication
a logic high error signal is produced at U6 pin 32 and passed to the UPS
Logic Board via X2-35 where it is processed by the system control logic
Note 1: R82 introduces a slight hysteresis into the detector so that the mains must
go above approximately -12% before the mains OK signal is re-established.
This eliminates nuisance alarms on fast, spurious undervoltage conditions.
Note 2: there is very little capacitance so it will detect an undervoltage condition
on a phase drop.

s4-c2.fm5 - Issue 3 Dated 09/11/98

4-35

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board
2.3.6.3

7200 Series UPS Service Manual

ON/OFF control from UPS Logic Board

One function of the UPS Logic Boards system control logic is to provide the
Rectifier Logic Board with a general ON/OFF control signal (see paragraph 3.3.7
on page 7-29).
This signal, which is annotated [ON_REC>, is connected to the Rectifier Logic
Board X2-36 and goes low when in the OFF state. In this state:
the start/stop line is driven to its stop mode
led H10 illuminates to provide on-board indication
2.3.6.4

Control power supply failure detection

A purpose designed supply voltage supervisor i.c. (N13) monitors the +12V
power rail and flags an error if this falls below approximately 4.55Vdc. If the
+12V supply falls below this level N13 output pin 6 goes high which:
drives the start/stop line to its stop mode
illuminates H10 to provide on-board indication
2.3.7

Control power supplies


The Rectifier Logic Board is powered from the AC-DC Power Supply Board
which applies 12V to X3 pins 3-5, as shown on sheet 4 of the circuit diagram.
Connector X11 is not used.
These inputs provide the general 12V power rails for this board and are also connected to the UPS Logic Board via X2 pins 1 to12, as shown. On the UPS Logic
Board these supplies are diode coupled with a similar set of supplies connected
via the Inverter Logic Board and then distributed to the remaining circuits boards.
A three-terminal +5V regulator (N14) is connected to the +12V rail and provides
the +5V supply required by some of the boards integrated circuits. Note also that
D2 (diagram sheet 2) requires a -5V supply which is obtained by a simple zenerregulator connected to the -12V rail.
Note: the cross-coupled diodes V45 splits the 12V rail into +12H and +12V. The
+12H rail is monitored by the power supply monitor N13 only. H7 illuminates
if the AC-DC Power Supply is OFF i.e. input mains failure. Upon mains return
N13 provides a power-up reset to the soft-start circuit to walk-in the rectifier control electronics. Thus during mains power failure the rectifier control electronics
are still energised via the DC-DC Power Supply but the soft-start is deactivated,
awaiting the mains return.

4-36

s4-c2.fm5 - Issue 3 Dated 09/11/98

7200 Series UPS Service Manual

2.4

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

Summary Information
Table 4-5: Rectifier Logic Board configuration jumpers
Jumper

Link
Position

X5

1-2

Disable battery temperature/voltage compensation


(Standard)

2-3

Enable battery temperature/voltage compensation

1-2

Increased DC regulation speed for units below 60kVA

2-3

Decreased DC regulation speed for units above 80kVA

1-2

Fast walk-in: 1 Second

2-3

Slow walk-in: 5 Seconds

0-1

open

0-2

open

0-1

closed

0-2

open

0-1

open

0-2

closed

0-1

closed

0-2

closed

0-3

closed

Reduced input current limit forced on

open

(Standard)

closed

Rectifier forced on - Ignore UPS Logic

open

UPS Logic control enabled (Standard)

open

Disable driver IC - D6

closed

Enable driver IC - D6 (Standard)

X6

X7

X9

0-4

0-5

X10

Function

Rectifier in Auto mode (Standard)

Rectifier in Float mode

Rectifier in Boost mode

Rectifier in Test mode

1-2

Enable rectifier temperature monitor

2-3

Disable rectifier temperature monitor (Standard)

Table 4-6: Rectifier Logic Board potentiometer adjustment


Potentiometer
R17

Function
Rectifier input current limit adjust (100 - 130%)

R18

Battery current limit adjust (0 - 25%)

R19

Battery test voltage adjust (0 - 550 volts)

R20

Battery boost voltage adjust (200 - 550 volts)

R21

Battery float voltage adjust (200 - 550 volts)

R22

Manual voltage adjust volts (10 - 550 volts)

s4-c2.fm5 - Issue 3 Dated 09/11/98

4-37

SECTION 4 - Rectifier Operation & Control


CHAPTER 2 - Rectifier Logic Board

7200 Series UPS Service Manual

Table 4-7: Rectifier Logic Board LED indications


LED

Colour

Function

H1

Amber

Rectifier in Battery Test mode

H2

Green

Rectifier in Boost mode

H3

Green

Rectifier in Float mode

H4

Amber

Rectifier in Manual mode

H5

Green

Battery in current limit

H6

Red

Rectifier in current limit

Table 4-8: Rectifier Logic Board test points


Test Point X8
X8 - 1

Battery volts reference feedback (3.26 450V dc)

X8 - 2

Battery current feedback

X8 - 3

Rectifier current feedback

X8 - 4

Parallel rectifier compensation N/A

X8 - 5

Battery temperature compensation

X8 - 6

DC voltage reference

X8 - 7

Input current limit adjustment reference

X8 - 8

Battery current limit adjustment reference

Test Point X5
X5 - 1

4-38

Temperature compensation start point

s4-c2.fm5 - Issue 3 Dated 09/11/98

Section 4:

Chapter 3 - Rectifier Gate Drive Interface Board (4542040W)

3.1

Introduction
A single Gate Drive Interface Board is used to interface the gate drive signals to
all six rectifier SCRs.
The boards primary function is to provide the SCR gate drive signals with galvanic isolation between their source (i.e. the low voltage control electronic environment of the Rectifier Logic Board) and the noisy, high voltage environment of
the power rectifier SCR devices to which they are applied. This is achieved
through the means of suitable pulse transformers.

3.2

Rectifier SCR gate drive requirements


As described in chapter 1 of this section, for the successful gate triggering of an
SCR it is essential that the current supplied to the gate:
occurs at a time when the main circuit conditions are favourable to the
SCRss conduction i.e. the SCR must be forward biased.
is of adequate duration i.e. the gate pulse must not be removed until the
anode current has risen above its holding current value, otherwise the
device would turn off.
is of adequate amplitude and sufficiently short rise time to initiate a safe
but rapid turn-on process.
The pulse duration and timing criteria stipulated in the first two of the above conditions are controlled by the Rectifier Logic Board which is responsible for
managing the phase-control timing sequencing and producing the necessary drive
pulses etc. However, the ultimate pulse-shape and rise-time of the signal seen at
the SCR gate is also affected by the signal-coupling circuits on the Gate Drive Interface Board and the conduction path shown in Figure 4-18.
The rise-time as well as the delay time, tends to be reduced by a large gate drive
within the allowable gate dissipation ratings of the SCR. Therefore, in order to
minimize the turn-on switching dissipation, the gate should be driven quite hard,
towards its allowable gate dissipation curve (See Figure 4-5). Thus steep-fronted
gate pulses are desired for proper device operation.

s4-c3.fm5 - Issue 2 Dated 21/08/97

4-39

SECTION 4 - Rectifier Operation & Control


CHAPTER 3 - Rectifier Gate Drive Interface Board

3.3

7200 Series UPS Service Manual

Gate drive circuit


Figure 4-18: R-phase (+) SCR drive circuit details
DC Bus +
+12V

X1
1
2

Rectifier
Logic
Board

1
2
Gate drive
ribbon cables
(maximum 3m)

X1
1

Yellow

100n

1k
22R

3
4

V37

Gate Drive Interface Board

X7

R+

V1

3
4

Red

R-ph
mains
0V

min (30)

max (150)
SCR Conduction
period

40kHz modulated signal

Trigger pulses

R-

DC Bus

SCR gate current (IG)

Figure 4-18 illustrates the complete gate drive signal path for the R-phase positive
SCR (R+) all other SCRs are similarly gated.
As has previously been explained, the Gate Drive interface Board contains a pulse
transformer to provide necessary signal isolation. To minimise the size of this
component the Rectifier Logic Board produces a modulated drive waveform
based on a 40kHz square-wave carrier i.e. when the Rectifier Logic Board wants
to trigger the SCR it sends a 40kHz burst firing signal and the pulse transformer
sees the 40kHz signal as opposed to 50Hz. The chosen 40kHz modulation frequency is sufficiently low so as not to be greatly affected by transmission losses
over the gate drive ribbon cables (to 3m) therefore the signal reaching the pulse
transformer maintains its fast rising edge.
When the Rectifier Logic Board requires to trigger the R+ SCR, the 40KHz
square-wave signal is applied to V37. When V37 turns on it connects the lower
end of the pulse transformer to 0V via a current limiting 22R resistor. A current
is induced in the pulse transformer secondary which makes the SCR gate potential
higher than the cathode and triggers the SCR into conduction. Note that diode
V1 blocks reverse gate current in the event of ringing or voltage reversal of the
pulse transformer secondary and also reduces the SCR holding current.
Figure 4-18 shows that the trigger pulse is not applied for the complete possible
conduction period. In fact the turn-on envelope contains only 9 or 10 of the
40kHz trigger pulses. This prolongs the SCR life by avoiding excessive wear on
the gate which would otherwise occur due to the additional heat generated by the
continued gate current after the SCR has turned on.

4-40

s4-c3.fm5 - Issue 2 Dated 21/08/97

Section 4:

Chapter 4 - Rectifier Snubber Board (4540043B)

4.1

Snubber requirements and characteristics


Like all power semiconductor devices, SCRs are very intolerant of excessive voltages; either steady voltages above their rating, or transient voltages which may
persist only for a few microseconds. Destructive breakdown or damage may
occur. Thus for reliable SCR operation, the use of overvoltage suppression techniques are essential.
A transient can be defined by the rate of voltage rise with respect to time (dv/dt).
Potentially damaging transient voltages, with a dv/dt greater than 200V/sec, can
be externally derived or produced internally by inherent SCR design operation.
One of the effects of high dv/dt transients is that they can cause the SCR to inadvertently turn-on (see page 4-5); and in the case of the rectifier application might
result in placing a short across the DC busbar, leading to a cascading failure of
other SCRs and rectifier components.
External sources

External transients are generated by the external supply and may be super-imposed on the normal AC supply source due to an input circuit breaker switching
operation or occasional lightening strikes.
Transients are also generated when energising and de-energising supply transformers, which may exhibit ringing oscillations on their secondary windings
caused by the sudden application of voltage to secondary leakage reactance and
winding capacitance. Peak voltage of twice the normal value may be observed
when the transformer is energised; whilst de-energising may cause peak values as
high as ten times to be generated as the transformer flux is forced to decay rapidly
to zero.
Also, starting and stopping air conditioning units and motors might momentarily
alter the supply line impedance quite suddenly, and introduce voltage notching
sufficient to cause dv/dt SCR switching within the rectifier.
Internal sources

In general, the interruption of a current flow in a circuit may produce a potentially


dangerous transient voltage due to line inductance etc., unless alternative low resistance discharge paths are provided. If unsuppressed, these transients will
appear within the circuit itself and may affect neighbouring circuits.
Excess di/dt (rate of change of current with respect to time) through the SCR may
cause internal failure due to excessive spot heating of the gate material. To slowdown such di/dt changes, an inductor is connected in series with the rectifier input
augments the overall input supply inductance. Thus when turning-on an SCR, a
forward voltage step is applied which, when combined with the input circuit inductance (L), causes an oscillatory peak voltage to appear across the device.
Similarly, when turning-off the SCR there is an abrupt interruption of the supply
current. During such commutation, the outgoing SCR element does not block
reverse voltage immediately (see paragraph 1.2.5 on page 4-8). The commuta-

s4-c4.fm5 - Issue 2 Dated 21/08/97

4-41

SECTION 4 - Rectifier Operation & Control


CHAPTER 4 - Rectifier Snubber Board (4540043B)

7200 Series UPS Service Manual

tion voltage during the turn-off period causes a reverse current to flow until the
SCR blocks, at which time the reverse current stops suddenly. This rapid change
in current (which can be as high as 106 or 107 amps/second) can result in high reverse voltage spikes which can destroy the SCR device.
These rapid current changes also generate considerable radio frequency interference (RFI); both radiated and conducted.

4.2

Snubber board
A simple R-C snubber circuit is usually employed to provide clamping of such
transient over-voltages. The snubber is connected across the device and if correctly designed will limit both the amplitude and rate-of-rise of the voltage transient.
The R-C circuit is effectively a single-pole high-pass filter, tuned to a high frequency relative to the transient dv/dt. That is, the capacitor blocks the 50Hz
supply voltage but will allow the higher-speed transient voltages through to the
resistor. The R-C time constant at fast dv/dt limits the rate of rise of the over-voltage and therefore also the magnitude. The resistor provides a discharge path for
any transient energy stored within the capacitor, thus the snubber is effective
against both external dv/dt and internal di/dt transient voltage spikes.
Figure 4-19: R-C Snubber filters transients

DC Bus +
Transient only
is allowed through
R-C filter

R+

R-ph
mains
100R
100W
0.1f
1kV

R-

DC Bus

4-42

s4-c4.fm5 - Issue 2 Dated 21/08/97

Potrebbero piacerti anche