Pin 1
The PCE984285 processor is equipped with two Modbus® ports and a
Modbus Plus™ port for both data transfer and programming. Two slide
Pin 9 switches on the front of the processor provide simplified user control of
key functions. The memory protection switch prevents programming
RJ45 jack devices or other input devices from overwriting the user program. The
(8 x 8)
Modbus interface switch sets the Modbus data transfer parameters as
either ASCII, RTU or other.
Every Compact processor has a real-time clock that provides both the
date and time. The PCE984285 provides an input for synchronizing the
50.8mm clock with the Global Positioning System (GPS).
(2.0in) Pin 1
CPU PC The PCE984285 provides six LED indicators. The green ready LED
RJ45 Connector 9-pin D-shell indicates that the processor has passed the power-up diagnostic tests
DTR 1 1 and is functional. The green run LED indicates that the program is
TXD 3 2 RXD started and is solving logic. The red bat low LED indicates that the
RXD 4 3 TXD battery needs replacing (there is a 10-day holdup from the initial
DSR 2 Q
2 DTR indication). The green Modbus 1 and Modbus 2 LEDs indicate activity
GND 5 5 GND on MB1 (Modbus port 1) and MB2 (Modbus port 2) respectively. The
6 DSR
CTS 7 green Modbus+ LED provides network diagnostic information.
7 RTS
RTS 6 8 CTS
Front view:
9 RI
Cable 8 cable of the
Shield connector
Top of Cabinet
Specifications
100 mm
Concept Logic Memory 620 Kbytes
(3.9 in)
Proworx NxT Logic Memory 32 Kwords
Flash RAM 1 MB for storing operating system and application
(Application may be saved to flash RAM)
Data Memory 64 Kwords
Clock Speed 25 MHz
130 mm
(5.07 in) Logic solve time 0.36 ms/K ladder logic instructions
130 mm
(5.07 in)
Schneider Electric USA This document, and the information contained herein, is to be used exclusively by system integrators and
One High Street consulting engineers for the sole purpose of specifying Schneider Electric products or for submitting
North Andover, MA 01845-2699 related documentation in support of engineering project proposals. This information is not intended for use
1-800-468-5342 in system design, implementation or installation. No responsibility is assumed by Schneider Electric for any
For detailed technical documentation visit: consequences arising out of the use of this material.