INTRODUCTION
Crompton Greaves Ltd. is one of the leading manufacturers of SF 6 Gas Circuit Breakers in the world. We manufacture Gas
Circuit Breakers ranging from 6.6kV to 420kV .
More than 13,000 Crompton Greaves SF6 Gas Circuit Breakers upto 420kV have been put into service in various
environments in many countries since 1983 where they are operating satisfactorily.
Our manufacturing and quality systems are ISO 9001 certified.
FEATURES
INTERRUPTING UNIT
The interrupting unit filled with pressurized SF6 gas is placed at the top of the pole and contains Stationary Contact,
Nozzle, Moving Contact, Puffer Cylinder and Fixed Piston (Fig.1). During opening operation (Fig.2), the Moving Contact
along with the Puffer Cylinder is pulled down. The Fixed and Moving contacts get separated and arc is formed between
fixed arcing contact and moving arcing contact. Motion of the Puffer Cylinder compresses SF6 gas against the Fixed
Piston thus generating a powerful SF6 gas blast through the Nozzle over the arc. After travelling through some distance,
the dielectric strength of the gap is raised sufficiently to extinguish the arc. The reliability of the system is further
enhanced by the single pressure dual flow puffer interrupter, which reduces the number of moving parts and auxilliary
systems in the circuit breaker. This principle is shown in Fig. 3.
Absorbent
Upper terminal
Contact support
SF6 gas
Nozzle
Moving main contact
Piston
Puffer cylinder
Drive tube
Lower terminal
Contact
Key
Fixed main contact
Arc
Insulators
Nozzle
SF6 gas
Moving arcing contact
Puffer cylinder
Contact
Piston
INTERRUPTER
Cam
Trip spring
Ratchet
Closing spring
Lever
Ratchet wheel
Closing-holding latch
Closing trigger
Trip-holding latch
Closing coil
Interrupter
Trip coil
Trip trigger
PHASE A
VALVE E [406]
PHASE B
PHASE C
VALVE E [406]
VALVE E [406]
VALVE D [405]
O RING P18
[408]
TEMPERATURE
COMPENSATED GAS PRESSURE
GAUGE [402]
GAS PRESSURE
SWITCH [401]
VACUUM PUMP
[712]
ROUTINE TESTING
All routine tests as specified in IEC 56 are conducted on the fully assembled GCBs at our factory. In addition to the
specified tests as per IEC, following tests are also carried out on each breaker.
1) Gas leakage test.
2) Speed and timing test.
3) Gas pressure switch test.
CG testing laboratory is fully equipped with the latest testing equipment viz.
1)
2)
3)
4)
5)
Full
DESCRIPTION
1. TYPE REFERENCE
2. RATED VOLTAGE
3. RATED LIGHTNING IMPULSE
WITHSTAND
4. RATED POWER FREQUENCY
WITHSTAND
5. CREEPAGE DISTANCE (TOTAL)
6. APPLICABLE STANDARDS
7. TYPE OF MECHANISM
8. RATED NORMAL CURRENT
9. RATED OPERATING SEQUENCE
10.RATED FREQUENCY
11.RATED DURATION OF SHORT
CIRCUIT
12.RATED CLOSING / TRIPPING
VOLTAGE
13.CURRENT OF CLOSING /
TRIPPING COIL
14.RATED BREAK TIME
15.RATED CLOSING TIME
16.RATED SHORT CIRCUIT
BREAKING CURRENT
17.RATED SHORT CIRCUIT MAKING
CURRENT
18.RATED LINE CHARGING BREAKING
CURRENT AND OVER VOLTAGE
19.RATED CABLE CHARGING BREAKING
CURRENT AND OVER VOLTAGE
20.RATED SINGLE CAPACITOR BANK
BREAKING CURRENT AND OVER
VOLTAGE.
21.RATED OUT OF PHASE BREAKING
CURRENT
22.FIRST POLE TO CLEAR FACTOR
23.AUXILLIARY CONTACTS
24.SF6 GAS PRESSURE (AT 20C)
- NORMAL
- GAS FEED ALARM
- LOCKOUT
25.DIMENSIONS
A
B
D
H
26.WEIGHT (Approx.)
UNITS
:
:
:
kV
kVp
350
550
650
650
350
550
650
1050
kV
160
230
275
275
160
230
275
460
:
:
:
:
:
:
mm
A
Hz
1815
3075
3625
3625/4595
1815
3075
IEC : 60056, BSS : 5311, JEC : 181
SPRING-SPRING
3150
0-0.3 sec-CO-3 min-CO / CO-15 sec-CO
50
50/60
3625
6125
sec.
110/125/220 V DC
7 A max. at 110 V DC
:
:
mS
mS
kA
31.5
40
31.5
40
kAp
80
100
80
100
A / pu
10/<2.5
A / pu
A / pu
250/<2.5
kA
:
:
: Kg/cm2
: Kg/cm2
: Kg/cm2
:
:
:
:
:
mm
mm
mm
mm
Kg
50/60
50
60
130
50/<2.5
400/<2.5
50/<2.5
400/<2.5
7.9
50/<2.5
400/<2.5
60
150
10/<2.5
50/<2.5
250/<2.5
50/<2.5
400/<2.5
10
400/<2.5
125/<2.5
400/<2.5
7.9
10
1.5
1.3
8 NO + 8 NC
5
4.5
4
8 NO + 8 NC / POLE
6
5.5
5
1100 /1700
3070
1600
4038
1100
1700
3490
2000
4908
1400
1700
4010
2000
5612
1450
7
6.5
6
5
4.5
4
1700
4010
2000
5502
1450
3470
3070
4038
2100
6
5.5
5
3470
3490
4908
2360
7
6.5
6
3470
4010
5428
2460
4600
4602
7146
3000
OPTIONALS
SN
DESCRIPTION
1. CREEPAGE DISTANCE
2. CLOSING / TRIPPING COIL VOLTAGE
3. CLEARANCE OF LIVE PARTS TO
GROUND
4. MAX. ALTITUDE ABOVE SEA LEVEL
5. AUXILLIARY CONTACTS
6. SEISMIC ACCELERATION
UNITS
31
125 / 250
1000
1000
10 NO + 10 NC
0.3 / 0.4
1000
0.3
1700
1000
1000
10 NO + 10 NC / POLE
0.3 / 0.4
1000
Dimensional Details
INTERRUPTER
PORCELAIN
700
280
280 525
700
SUGGESTED TRENCH
FOR CABLE ENTRY
SUPPORT COLUMN
CEMENT
80
300
2220
MECHANISM HOUSING
240
BASE FRAME
FLANGE
(340x300)
376
SUPPORT PORCELAIN
250
795
D
CONCRETE LEVEL
GROUND LEVEL
INTERRUPTER
PORCELAIN
SUPPORT
PORCELAIN
A
FLANGE CEMENT
(340x300)
700
280
240
300
BASE FRAME
MECHANISM
HOUSING
250
80
1085
2220
700
SUPPORT
COLUMN
FOUNDATION DESIGN
DETAILS FOR VIEW "A","B" AND "C"
CONCRETE LEVEL
GROUND LEVEL
1085
PH.A
1085
PH.B
CABLE TRENCH
1085
PH.C
A
PHASE B
PHASE Y
150
490
1000
180
80
2128
540
= =
250
50
150
250
E
800
CONCRETE
LEVEL
520
520
520
100
LEVEL OF UNDRILLED
GLAND PLATE
540
813
x
CONTROL
CABLE
1200
150
520
==
SUPPORTING
PORCELAINS
SECTION E-E
10470
GROUND LEVEL
30
CL
100
DETAILS OF X
100
250
M24 FOUNDATION
BOLTS
16.0
64 44.5
140
40 40 40
140
44.5
14 DRILL
4 HOLES
15.5
44.5 64
140
18 DRILL
4 HOLES
197.0
DETAILS OF UPPER & LOWER
TERMINAL PADS
245 kV (1)
44.5
140
35 40 35
44.5
44.5
19.5
14 DRILL
4 HOLES
12
R180
15.5
100
FOUNDATION BOLTS
72.5 to 145 kV (1 / 3)
225.0
44.5 44.5
400
400
400
400
50
SUPPORT STRUCTURE
72.5 to 145 kV (1 / 3)
DETAILS B
LOWER TERMINAL PADS
DETAILS A
UPPER TERMINAL PADS
245 kV (1)
Power Systems
A Business Unit of Crompton Greaves Ltd.
SF6 Switc
hg
ear Divn.
Switchg
hgear
hg
ear Comple
x
Switchg
hgear
Complex
Switc
A-3, MIDC, Ambad, Nashik - 422 010, India
Tel:
(+91) 253 382271
Fax:
(+91) 253 382219/381247
E-mail: exports@cglmail.com (Exports)
mktg@cglmail.com (General)
URL: www.cgswgear.com
Regd. Office: 6th Floor, CG House, Dr. Annie Besant Road, Prabhadevi, Mumbai - 400 025, India.
CG-S&C/EXP/Cat.No.SF6-105/9/01/5000
Data subject to change