Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
REPUBLIC OF
SENEGAL
LOC PROJECT
PHASE-II
KSLPEIRR-1501-EE-TS-01
R0
Contents
Volume III (Technical specification for Electrical Items)
KSLPEIRR-1501-EE-TS-01
R0
This specification.
Materials in cables conforming to any other standard, which ensures equal or better
quality, may be accepted. In such case, copies of the English version of the
standard adopted shall be submitted along with the bid.
1. IEC: 502
for rated
Voltages of 1kV to 36kV
2.
IEC:540 &540A
cords
3.
4.
5.
IEC:332
IEC: 754
ASTM-D-2843
or
Parameter
Description
No.
HV Power Cables 33000V Grade
1
33000 grade 900 C rating heavy duty XLPE power cable suitable for use in
non effectively earthed system conforming to following requirement and in
line with IS 7098, IS-8130, IS-5831 and IS-3975.
1.1
Conductor
Stranded and compacted aluminum conductor of grade
H2 and class 2 for all sizes, generally conforming to
IS:8130
1.2
Conductor
Extruded semi conducting compound.
Screen
1.3
Insulation
1.4
Insulation
Screen
1.5
1.6
Core
Identification
Inner Sheath
1.7
Armour
KSLPEIRR-1501-EE-TS-01
R0
2.2
2.3
2.4
2.5
1100 V grade, 850 C/ 900 C rating, heavy duty, HR PVC/XLPE power cable
conforming to following requirement and in line with IS 1554, IS 5831, IS
8130 and IS 3975.
Conductor
Stranded and compacted plain aluminium of grade H2
and class 2/stranded, high conductivity annealed plain
copper as per Annexure, generally conforming to IS:
8130.
Insulation
Extruded HR PVC compound conforming to type C of IS:
5831 or XLPE.
Inner Sheath
Extruded PVC compound conforming to type ST2 of IS:
5831 for multicore cable. Single core cables shall have
no inner sheath.
Armour
Galvanized single round steel wire armour for twin and
multicore cables.
Non magnetic hard drawn aluminium single round wire
conforming to H4 grade for single core cables.
Overall Sheath
Extruded FRLS PVC compound conforming to type ST2
of IS:5831.
KSLPEIRR-1501-EE-TS-01
R0
Cables
1-2Core or 3Core
1-5Core
1-7Core
1-12Core
1-16Core
Separate cables for each type of following services / functions as applicable shall be
used for each feeder. One multicore cable using different services shall not be
acceptable.
(a) Power.
(b) Control, interlock and indication.
(c) Metering and measuring.
(d) Alarm and annunciation.
This is a proprietary document of Kirloskar Brothers Limited, Pune INDIA
KSLPEIRR-1501-EE-TS-01
R0
KSLPEIRR-1501-EE-TS-01
R0
All cables external to buildings shall be laid in PVC Conduit or on trays or racks
within reinforced concrete trenches. Direct burial of cables in the ground shall not
be permitted unless specifically approved when they shall be of the armoured type
or mechanically protected in an approved manner. All cable racking/trays shall be
bonded to the earthing system.
Drum length and tolerance
The cables shall be supplied in wooden/metal drums, each containing minimum 500
meters length for power cables and 1000 meters for control cables. Allowable
tolerance on individual drum length is 5%.
Non-standard length
Owner may accept non standard lengths up to 5% of the total ordered quantity.
However, the
Contractor will be required to obtain Owner's approval before packing the cables on
drums. Non standard lengths shall not be less than 100 meters in any case.
Joints and terminations
Materials of construction for a joint/termination shall perfectly match with the
dielectric chemical and physical characteristics of the associated cables. The
material and design concepts shall incorporate a high degree of operating
compatibility between the cable and joints. The protective outer covering (jacket)
used on the joints/terminations shall have the same qualities as that of the cable
outer sheath in terms of ambient/operating temperature withstand capability and
resistance to hazardous environments and corrosive elements. Special provision of
protection shall have to be made considering coastal location of site.
The other mandatory accessories viz., ferrules, cable ties, clamps, cable markers,
sand, bricks, etc shall be supplied.
Cable identification
Cable identification shall be provided by embossing the following on the outer
sheath:
(a) Manufacturer's name or trade mark
(b) Voltage grade
(c) Year of manufacture
(d) Type of insulation, e.g. HR85 for HR PVC etc.
(e) Type of outer sheath e.g. "FRLS" etc.
(f) ISI marks
This is a proprietary document of Kirloskar Brothers Limited, Pune INDIA
KSLPEIRR-1501-EE-TS-01
R0
KSLPEIRR-1501-EE-TS-01
R0
(c) Flame Retardance test on single cable and on bunched cables (for both C1 &
C2)
After the test, there should be no visible damages on the test specimen within
300mm from
its upper end. After burning has ceased, the cables should be wiped clean and the
charred or affected portion should not have reached a height exceeding 2.5 meter
above the bottom edge of the burner, measured at the front and rear of the cable
assembly.
(d) Halogen acid gas evolution test (for category C2).
The level of HCL evolved shall not exceed 20 per cent by weight
(e) Smoke density test (for category C2)
The cables shall meet the requirements of light transmission of minimum 40% after
the test.
(f) Test for rodent & termite repulsion property
The test shall be carried out to note the presence of rodent and termite repelling
chemical in
PVC compound. Normal procedure is that a few chippings of the PVC compound are
slowly
ignited in a porcelain dish or crucible in a muffle furnace at about 600C. The
resulting
ignited ash is boiled with a little ammonium acetate solution (10%). A drop of
aqueous
sodium sulphide solution is placed on a thick filter paper and it is allowed to soak.
The spot
is touched with a drop of above extract. A black spot indicates the presence of antitermite
& rodent compound.
Test witness
Tests shall be performed in presence of Owners representative if so desired by the
Owner. The Contractor shall give at least thirty (30) days' advance notice of the
date when the tests are to be carried out.
Test certificates
(a) Certified reports of all the tests carried out at the works shall be furnished for
approval of the Owner.
This is a proprietary document of Kirloskar Brothers Limited, Pune INDIA
KSLPEIRR-1501-EE-TS-01
R0
(b) Test reports shall be completed with all details and shall also contain IS specified
limit
Values, wherever applicable, to facilitate review.
(c) The cables shall be dispatched from works only after receipt of Owner's written
approval of the test reports.
lightning.
IS: 2629
IS: 2633
IS: 3043
IEEE: 80
IEEE: 142
KSLPEIRR-1501-EE-TS-01
R0
(a) Galvanized steel flats shall be used for all connections above earth. Sizing shall
be
decided during detailed engineering stage.
(b) Inside building, ground conductors will be run for each floor supported on
building steel
and/or cable trays. These ground conductors in turn will be connected to the station
ground
grid through riser (at least two) coming up along building columns/cable shafts.
(c) Two separate and distinct ground connections will be provided for each electrical
equipment in compliance with I.E. Rules.
(d) All connections above ground will be welded type except connection to
equipment/structures which shall be bolted type with appropriate washers.
(iv) Equipment ground lead
Equipment ground connections shall be sized to carry the available ground fault
current.
Considerations shall also be given to mechanical ruggedness of the connections
and to limit the number of sizes.
Entire erection of grounding work shall be carried out in such a way as to be
capable of withstanding the intended services of carrying full short circuit level
currents to ground mat without any damage/deformation.
KSLPEIRR-1501-EE-TS-01
R0
Equipment
1.
2.
33kV/11kV
switchgear/equipmen
t 415V switchgear
33KV/11KV
Transformer
HT Motor
3.
4.
5.
6.
7.
8.
9.
10.
11.
LT motors 3.7kW to
15kW
LT motor up to 3.7
kW
Power transformer
Neutral
Control panel &
control desk
Push button station /
JunctionBox
Columns, structures,
cable
trays and busduct
enclosures
Crane, rails, rail
tracks & other noncurrent carrying
metal parts
Earth
conductor
buried in earth
40 mm dia.MS
rod
---
---
50x6mm GS flat
---
50x6mm GS flat
---
---
---
50 x 6mm CU flat
---
25 x 3 mm GS flat
---
---
50x6mm GS flat
50x6mm GS flat
25x6mm GS flat
KSLPEIRR-1501-EE-TS-01
R0
above ground level properly clamped or supported along the outer edge of the
concrete foundation. Connection to the ground mat shall be done by arc welding
and the other end is to be kept free at least 300 mm above grade level/concrete
floor level unless otherwise shown.
(VII) Column Grounding
All columns are required to be grounded by 40 mm dia M.S. rod from ground mat.
Laying, supporting along with foundation, connecting at ground mat are within the
scope of this specification. At least 300 mm length of the above rods shall be left
free above the grade level/concrete floor level for connection with columns.
(VIII) Galvanising
The galvanising shall be uniform, clean, smooth, continuous and free from acid
spots. Should the galvanising of the samples be found defective, the entire batch of
steel has to be regalvanised, at Bidder's cost. The amount of zinc deposit shall not
be less than 610 grams per square metre of surface area and in addition, the
thickness of the zinc deposit at any spot whatsoever shall not be less than 75
microns. The Owner reserves the right to measure the thickness of zinc deposit by
Elkometer or any other instrument and reject any component which shows
thickness of zinc at any location less than 75 microns.
The maximum fault current for 33kV system is to be considered as 25 kA for 1 sec.
KSLPEIRR-1501-EE-TS-01
R0
(a) Air termination network with down conductors and earthing electrodes will be
provided on
the basis of IS Code of Practice.
(b) Horizontal air termination shall be so laid out that no part of the roof will be
more than 9
meters from the nearest conductor.
(c) Shielding angle for one vertical air termination shall be 45o. For more than one
rod, shielding angle between the rods shall be taken as 60 o.
(d) Down conductors will run along the outer surfaces of the building and shall have
a test joint
about 1500 mm above ground.
(e) An earth electrode will be provided at the connection point of the down
conductor with the
station ground.
(f) Galvanized steel rods and flats will be generally used for air termination and
connections.
Lightning protection system shall be in strict accordance with standards as
mentioned in
Clause Lightning conductor shall be of 25x6mm GS strip when used above ground
level and
shall be connected through test link with earth electrode/earthing system.
Lightning system shall comprise of air terminations, down conductors, test links,
earth electrode etc. as per approved drawings.
(iii) Down Conductors
Down conductors shall be as short and straight as practicable and shall follow a
direct path to earth electrode.
Each down conductor shall be provided with a test link at 1000 mm above ground
level for testing. No connections other than the one direct to an earth electrode
shall be made below a test point. All joints in the down conductors shall be welded
type.
Down conductors shall be cleatted on outer side of building wall, at 750 mm
interval or welded to outside building columns at 1000 mm interval.
KSLPEIRR-1501-EE-TS-01
R0
Physical
&
dimensional
check
on
all
equipments
as
per
approved
drawings/standards.
HV/IR as applicable.
c) Check/measurement of thickness of paint/zinc coating/nickel-chrome plating as
per specification & applicable standard.
(V) Commissioning
The Contractor shall carry out the following commissioning tests and checks after
installation at site. In addition the Contractor shall carry out all other checks and
tests as recommended by the Manufacturers.
Earthing and Lightning protection system
1) Earth continuity checks.
2) Earth resistance of the complete system as well as sub-system.