Letter of specification of the parameters of hydro turbine and

generators of Changwa project


Guangxi Yizhou Changmao Power Co.,Ltd,
As per your request, the specification of the comparison conclusion of the parameters
and characteristics between the operated hydro turbine and generator unit and the
designed figures in PDR can be shown as follows,
The main reason of the difference between the actual parameters of the nameplate
and the designed ones in the PDR is the manufacturer was decided through
equipment bid, and the different manufacturers used different type for biding. However,
the parameters of the type for biding were all defined according to the parameters
designed in PDR, and the selected equipments all satisfy the related parameters for
biding.
The Actual operated GZ795-WP-360 type bulb tubular turbines and assorted
SFWG5000-48/3970 generators were selected through the analysis and judge by the
evaluation committee. The output of the Actual operated turbines and fitted
generators are same to the ones designed in the PDR. Although the efficiency is
higher and the rated power is bigger of the Actual operated hydro turbine than the
designed values, and also the type of the generators is different from the designed
values, but the parameters of the generator is same to the designed ones. Further
more, the bigger rated power of the hydro turbine can ensure the output of the
generators after the hydro turbine overcomes the friction and this will cause no
change of the output of the generators. (The detail comparison is shown as below
table)
Comparison table of the main parameters between
the Actual operated and designed units
Hydro Turbine

Mode

Designed in PDR

Actual operated

Remarks

Bulb Tubular

Bulb Tubular Kaplan

GZ- Bulb Tubular Kaplan type

Kaplan Turbine

Turbine

WP- Horizontal Shaft


360-runner diameter(mm)
1250A or 795-type of the runner

Type

GZ1250A-WP-360

GZ795-WP-360

model, the difference between


the two types just because the
runner model is different.

Rated power

5209kw

5263kw

The efficiency of the model


cause little influence to the rated
power

Max Water head

7.8m

7.0m

The max and min water head are

Min Water head

2.5m

2.5m

in the range of Changwa project


designed.

Rated Water Head

5.6m

5.8m

5.8m fit the demands of the


Actual unit, and this value have
no essential change to the one in
PDR

Rated water flow

102m /s

101.34m /s

Rated speed

125r/min

125r/min

Max efficiency

93.86%

94%

Runner Diameter

3.6m

3.6m

Designed in PDR

Actual operated

SF6300-12/2600

SFWG5000-48/3970

Generator
Type

Tubular type turbine fitted


generators

Rated Power

5000kW/5.88MVA

5000kW/5882kVA

Indicate manner of the Rated

Rated Voltage

6.3 kV

6300V

power can be active power kW,

Rated current

539 A

539 A

or apparent output kVA (Inc.

Rated speed

125 r/min

125 r/min

reactive power), apparent output

Rated Frequency

50HZ

50HZ

kVA multiply by Power Factor

Power Factor

0.85

0.85

equal to active power kW


Indicate manner of the Rated
power of the Generator and
transformer

is

always

apparent output kVA


Note: The value with brown color is the indicate value on the nameplate.

Guangxi Hechi Water Conservancy and Power Investigation Design Institute


16/11/2009