Vacuum Circuit Breakers Vacuum Interrupter

Pro-MEC

Vacuum Circuit Breakers


Vacuum Interrupter

For your safety, please read user's manual thoroughly before operating.
Contact the nearest authorized service facility for examination, repair, or adjustment.
Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!

Safety Instructions

Any maintenance and inspection shall be performed by the personnel having expertise concerned.
2008.11 LS Industrial Systems Co.,Ltd. All rights reserved.

www.lsis.biz
HEAD OFFICE

Global Network
LS Industrial Systems (Middle East) FZE
Dubai, U.A.E.

LS Tower, 1026-6 Hokyeh 1dong, Dongan-gu, Anyang,


Kyonggi-Do, 431-848, Korea
Tel. (82-2)2034-4870
Fax. (82-2)2034-4713

Address: P.O.Box-114216, API World Tower, 303B, Sheikhe Zayed Road, Dubai, U.A.E.
Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: hwyim@lsis.biz

Dalian LS Industrial Systems Co., Ltd.


Dalian, China
Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China
Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn

LS Industrial Systems (Wuxi) Co., Ltd.


Wuxi, China
Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu,214028, P.R.China
Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn

CHEONG-JU PLANT

LS-VINA Industrial Systems Co., Ltd.


Hanoi, Vietnam
Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam
Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com

Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,


Cheong Ju, 361-720, Korea

LS-VINA Industrial Systems Co., Ltd.


Hochiminh , Vietnam
Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam
Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: sbpark@lsisvina.com

LS Industrial Systems Tokyo Office


Tokyo, Japan
Address: 16FL, Higashi-Kan, Akasaka Twin Tower 17-22, 2-chome, Akasaka, Minato-ku Tokyo 107-8470, Japan
Tel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: jschuna@lsis.biz

LS Industrial Systems Shanghai Office


Shanghai, China
Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China
Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn

LS Industrial Systems Beijing Office


Beijing, China
Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
Beijing 100013, P.R. China
Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn

LS Industrial Systems Guangzhou Office


Guangzhou, China
Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China
Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.biz

LS Industrial Systems Chengdu Office


Chengdu, China
Address: 12Floor, Guodong Building, No52 Jindun Road Chengdu, 610041, P.R. China
Tel: 86-28-8612-9151 Fax: 86-28-8612-9236 e-mail: yangcf@lsis.com.cn

LS Industrial Systems Qingdao Office


Qingdao, China

Specifications in this catalog are subject to change without notice due to


continuous product development and improvement.

2008. 11

Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China
Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn

Vacuum Circuit Breakers/Vacuum Interrupter(E) 2008. 11/(01) 2008. 11 Printed in Korea

STAFF

Electric Equipment

Pro-MEC

VCB/VI

Vacuum Circuit Breaker

Contents

H1

Ratings

H1-4

Constructional and operating characteristics

H1-10

Control circuit diagram

H1-11

7.2kV dimension

H1-12

12kV dimension

H1-23

17.5kV dimension

H1-24

24kV dimension

H1-36

Accessories

H1-44

Types and ordering information

H1-49

Vacuum Interrupter
Features & Ordering information

H1-52

Structure

H1-53

Operating characteristics

H1-54

Ratings and Specifications

H1-55

Dimensions

H1-58

Vacuum Circuit Breaker


LS Pro-MEC VCB is user-friendly to give more convenience
and safety by providing high speed interrupting time (3cycles),
adopting the rapid auto-reclosing method, and having
wide range of accessories.

7.2kV Draw-out (F class)


24kV Draw-out (F class)

Wide range of accessories (optional)


Key Lock
Padlock of earthing switch
Button padlock
Position switch of the earthing switch
Button cover
Locking coil of earthing switch
Position switch (Cell switch)
Shutter padlock
Preparatory trip coil (Secondary trip coil)
MOC (Mechanically operated cell switch)
H1-2

Latch checking switch


TOC (Truck operated cell switch)
Charge indicator
Code plate (Miss insertion prevention)
Position padlock
Capacitor trip device
Earthing switch Note 1)
Rectifier
Note 1) The earthing switch is not available for 17.5kV VCB.

VACUUM CIRCUIT BREAKER

[ Compasion table for VCB (Short circuit test) ]

Compasion table for VCB (Short circuit test)

High reliability of the operating mechanism


- Separate design of the main circuit from the
operating mechanism.
- Adopt the toggle link method.
- Improved the reliability of electric circuit.
- Adopt the rapid auto-reclosing method as a
standard option. (O-0.3sec.-CO-3min.-CO)

High interrupting performance

Great operational safety

Make short of the interrupting time. (3cycles)


Increase the rated short-circuit withstand
characteristics. (1sec. to 3sec.)

Reinforce the insulation in the conduct, by adopting the


molded housing in each phase.
Built in the device making the contacts open first when
draw in and out.
Adopt the tulip-shape connection between the cradle and
the VCB.

H1-3

Vacuum Circuit Breaker


Ratings
-20D
LVB-06

Type
Rated voltage

(kV)

Rated normal current

(A)

-25D
LVB-06

7.2
630

7.2

1250

2000

630

1250

Rated frequency

(Hz)

50/60

Rated short-circuit breaking current

(kA)

20

25

(MVA)

250

310

Rated short-circuit breaking capacity

50/60

Rated short-time withstand current

(kA/3sec)

20

25

Rated short-circuit making current

(kAp)

52

65

Rated breaking time

(Cycle)

Rated opening time

(sec)

0.04

0.04

No-load closing time

(sec)

0.06

0.06

Withstand Power frequency


voltage
Impulse

(kV/min)

20

20

(kV/1.250)

60

60

Rated operating sequence


Mechanical
Type
test

Electrical

O-0.3s-CO-3min-CO

O-0.3s-CO-3min-CO

M2 (10,000 times)

M2 (10,000 times)

E2 (List1)

E2 (List1)

Capacitive current switching Note 1)


Mechanical
Lifetime
Electrical

C2

C2

Without maintenance (Time)

20000

20000

Maintenance

30000

30000

(Time)

Without maintenance (Time)

20000

20000

Maintenance

30000

30000

4a4b, 10a10b

4a4b, 10a10b

(Time)

Auxiliary switch
Fixed
E-type
Installing
method

Draw-out
type

F-type
G-type Note 2)
M-type

2000

Visible, Fixed

Visible, Fixed

Visible, Fixed

Visible, Fixed

Visible, Clip

Visible, Tulip

Visible, Clip

Visible, Tulip

Visible, Clip

Visible, Tulip

Visible, Clip

Visible, Tulip

Visible, Clip

Visible, Tulip

Visible, Clip

Visible, Tulip

Enclosed, Tulip

Enclosed, Tulip

Enclosed, Tulip

Enclosed, Tulip

Enclosed, Tulip

Note 2)

Enclosed, Tulip

E-type

(kg)

94

99

134.5

94

99

134.5

F-type

(kg)

95

100

135.5

95

100

135.5

Weight

G, M-type

(kg)

95 (137)

100 (147)

135.5 (163.5)

95(137)

100(147)

135.5(163.5)

Note 3)

E-type

(kg)

37

39.5

60

37

39.5

60

VCB

Cradle

F-type

(kg)

39

41.5

62.5

39

41.5

62.5

G-type

(kg)

39(103)

41.5(107)

62.5(117)

39(103)

41.5(107)

62.5(117)

Applied standard
Test laboratory

KERI Note 4)

IEC 62271-100

IEC 62271-100

Note 1) Applied cable-charging current switching test


2) In the event of ordering Enclosed Tulip type for G class VCB, please add T in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T)
3) (
)* indicates the weight of Enclosed Tulip installing method VCB.
4) KERI: Korea Electrotechnology Research Institute.

Visible VCB
(Draw-out type)

H1-4

E-type cradle
(Visible, Clip contact)

E-type cradle
(Visible, Tulip contact)

F -type cradle
(Visible, Clip contact)

G-type cradle
(Visible, Tulip contact)

-32D
LVB-06

Type
Rated voltage

(kV)

Rated normal current

-40D
LVB-06

7.2

(A)

1250

2000

7.2
3150

1250

2000

Rated frequency

(Hz)

50/60

50/60

Rated short-circuit breaking current

(kA)

31.5

40
500

Rated short-circuit breaking capacity

(MVA)

390

Rated short-time withstand current

(kA/3sec)

31.5

40

Rated short-circuit making current

(kAp)

82

104

Rated breaking time

(Cycle)

Rated opening time

(sec)

0.04

0.04

No-load closing time

(sec)

0.06

0.06

Withstand Power frequency


voltage
Impulse

(kV/min)

20

20

(kV/1.250)

60

60

Rated operating sequence


Mechanical
Type
test

Electrical

O-0.3s-CO-3min-CO

O-0.3s-CO-3min-CO

M2 (10,000 times)

M2 (10,000 times)

E2 (List1)

E2 (List1)

C2

C2

Without maintenance (Time)

20000

20000

Maintenance

30000

30000

Capacitive current switching Note 1)


Mechanical
Lifetime
Electrical

(Time)

Without maintenance (Time)

20000

20000

Maintenance

30000

30000

(Time)

Auxiliary switch

4a4b, 10a10b

Fixed

Draw-out
type

Visible, Fixed

Visible, Fixed

Visible, Fixed

Visible, Tulip

Visible, Clip

Visible, Tulip

Visible, Tulip

F-type
G-type Note 2)

Visible, Tulip

Visible, Tulip

Visible, Tulip

Visible, Tulip

Visible, Tulip

Visible, Tulip

Visible, Tulip

Visible, Tulip

Enclosed, Tulip

Enclosed, Tulip

M-type

Enclosed, Tulip

E-type
VCB

4a4b, 10a10b

Visible, Fixed
E-type

Installing
method

3150

(kg)

131.5

134.5

Enclosed, Tulip

210

135

138

210

F-type

(kg)

132.5

135.5

211

136

139

211

Weight

G, M-type

(kg)

132.5(159)

135.5(160)

220

136(162.5)

139(163.5)

220

Note 3)

E-type

(kg)

52

60

131

52

60

131

F-type

(kg)

54.5

62.5

135

54.5

62.5

135

G-type

(kg)

62.5(110)

135(117)

155

62.5(110)

135(117)

155

Cradle
Applied standard
Test laboratory

KERI Note 4)

IEC 62271-100

IEC 62271-100

Note 1) Applied cable-charging current switching test


2) In the event of ordering Enclosed Tulip type for G class VCB, please add T in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T)
3) (
)* indicates the weight of Enclosed Tulip installing method VCB.
4) KERI: Korea Electrotechnology Research Institute

Enclosed VCB
(Draw-out type, G-type)

G-type Cradle
(Enclosed, Tulip contact)

Visible, Clip contact

Visible, Tulip contact

Enclosed, Tulip contact

H1-5

Vacuum Circuit Breaker


Ratings
-25D/06, 12, 20-T
LVB-12

Type
Rated voltage

(kV)

Rated normal current

(A)

Rated frequency

-32D/12, 20-T, 30
LVB-12

-40D/12, 20, 30
LVB-12

12

12

12
630

1250

2000

1250

(Hz) 50(E1,C2: KEMA), 60(E2: PT & T)

Rated short-circuit breaking current


Rated short-circuit breaking capacity

2000

25

31.5

40

500

650

831

(kA/3sec)
(kAp)

25

31.5

40

62.5

81.9

104

Rated breaking time

(Cycle)

Rated opening time

(sec)

0.04

(sec)

0.06

No-load closing time

(kV/min)

28

(kV/1.250)

75
O-0.3s-CO-3min-CO

Mechanical

M2 (10,000 times)

Electrical

E2 (List 1)

Capacitive current switching Note 1)


Mechanical

Electrical

C2

Without maintenance (Time)

20,000

Maintenance

(Time)

30,000

Without maintenance (Time)

20,000

Maintenance

(Time)

30,000

Auxiliary switch

4a4b, 10a10b

Fixed

E-TYPE

Installing
Method

Draw-out
type

F-TYPE

G-TYPE

Enclosed, Tulip

M-TYPE

VCB
Weight
Cradle

(kg)

Enclosed, Tulip

F-TYPE

(kg)

G, M-TYPE

(kg)

Visible, Tulip

137

147

163.5

159

160

220

162

163

220

E-TYPE

(kg)

F-TYPE

(kg)

G, M-TYPE

(kg)

103

107

117

110

117

155

110

117

155

IEC 62271-100
KEMA: E1, C2 PT & T: E2 Note 2)

Note 1) Applied cable-charging current switching test


2) PT&T: Power Testing & Technology Institute (LSIS high-power laboratory)

H1-6

Visible, Tulip

Enclosed, Tulip

E-TYPE

Applied standard
Test laboratory

3150

Rated operating sequence

Lifetime

2000

(kA)

Rated short-circuit making current

Type
test

1250

50(E1,C2:KEMA), 60(M2,E2,C2: PT & T)

(MVA)

Rated short-time withstand current

Withstand Power frequency


voltage
Impulse

3150

60(E1,E2,C2: PT & T)

PT & T: E1, E2, C2, M2

-25D/06, 12, 20, 25


LVB-17

Type
Rated voltage

(kV)

Rated normal current

(A)

Rated frequency

630

1250

(Hz)

Rated short-circuit breaking current


Rated short-circuit breaking capacity

-40D/12, 20,30
LVB-17

17.5

17.5
2000

2500

1250

50/60

2000

(kA)

25

40

(MVA)

750

1200

Rated short-time withstand current

(kA/3sec)

25

40

Rated short-circuit making current

(kAp)

65

104

Rated breaking time

(Cycle)

Rated opening time

(sec)

0.04

(sec)

0.06

No-load closing time


Withstand Power frequency
voltage

Impulse

(kV/min)

38

(kV/1.250)

95

Rated operating sequence

O-0.3s-CO-3min-CO

Mechanical
Type
test

M2 (10,000 times)

Electrical

E2 (List1)
C2

Capacitive current switching Note 1)


Mechanical
Lifetime
Electrical

Without maintenance (Time)

20000

Maintenance

(Time)

30000

Without maintenance (Time)

20000

Maintenance

(Time)

30000

Auxiliary switch

4a4b,10a10b

Fixed
Installing
method

Draw-out
type

Visible, Fixed

E-TYPE

Visible, Tulip

F-TYPE

Visible, Tulip

G-TYPE

Visible, Tulip

Visible, Tulip

Fixed type VCB

VCB
Weight
Cradle

(kg)

115

125

135

165

E-TYPE

(kg)

130

140

155

195

F-TYPE

(kg)

130

140

155

195

G-TYPE

(kg)

160

170

190

220

200

205

260

E-TYPE

(kg)

65

67

78

165

F-TYPE

(kg)

75

77

88

172

G-TYPE

(kg)

100

105

115

185

175

175

200

Applied standard
Test laboratory

3150

60

IEC 62271-100
KEMA , PT&T

Note 1) Applied cable-charging current switching test.

H1-7

Vacuum Circuit Breaker


Ratings
Type

-13D LVB-20
-13D/T LVB-20
-16D LVB-20
-16D/T LVB-20
-25D LVB-20
-25D/T
LVB-20

Rated voltage

(kV)

24

24

24

(A)

630

630

630

1250

1250

1250

(Hz)

50/60

50/60

50/60

(kA)

12.5

16

25

(MVA)

520

665

1000

Rated normal current

2000
Rated frequency
Rated short-circuit breaking current
Rated short-circuit breaking capacity
Rated short-time withstand current

(kA/3sec)

12.5

16

25

Rated short-circuit making current

(kAp)

32.5

40

65

Rated breaking time

(Cycle)

Rated opening time

(sec)

0.04

0.04

0.04

(sec)

0.06

0.06

0.06

(kV/min)

50

50

50

(kV/1.250)

125

125

125

No-load closing time


Withstand Power frequency
voltage
Impulse
Rated operating sequence
Type
test

O-0.3s-CO-3min-CO

O-0.3s-CO-3min-CO

M2(10,000 times)

M2(10,000 times)

M2(10,000 times)

E2 (List1)

E2 (List1)

E2 (List1)

C2

C2

C2

Without maintenance (Time)

20000

20000

20000

Maintenance

30000

Mechanical
Electrical
Capacitive current switching Note 1)
Mechanical

Lifetime
Electrical

(Time)

30000

30000

Without maintenance (Time)

20000

20000

20000

Maintenance

30000

30000

30000

4a4b, 10a10b

4a4b, 10a10b

4a4b, 10a10b

(Time)

Auxiliary switch
Fixed
Installing
method

O-0.3s-CO-3min-CO

Visible, Fixed

Visible, Fixed

Visible, Fixed

Visible, Clip

Enclosed, Tulip

Visible, Clip

Enclosed, Tulip

Visible, Clip

Enclosed, Tulip

E-type
Draw-out

F-type

Visible, Clip

Enclosed, Tulip

Visible, Clip

Enclosed, Tulip

Visible, Clip

Enclosed, Tulip

type

G-type Note 2)

Visible, Tulip

Enclosed, Tulip

Visible, Tulip

Enclosed, Tulip

Visible, Tulip

Enclosed, Tulip
Enclosed, Tulip

M-type
VCB
Weight
Cradle

Enclosed, Tulip

Enclosed, Tulip

E-type

(kg)

145

145

145

145

145

145

F-type

(kg)

145

145

145

145

145

145

G, M-type

(kg)

155

187

155

187

155

187/218 (2000A)

E-type

(kg)

80

80

80

80

80

80

F-type

(kg)

82

82

82

82

82

82

G-type

(kg)

110

120

110

120

110

120

Applied standard
Test laboratory

IEC 62271-100

IEC 62271-100

IEC 62271-100

KERI

KEMA

Note 1) Applied cable-charging breaking current


2) In the event of ordering Enclosed Tulip type for G class VCB, please add T in the end of type name. (Ex: LVB-06G-20D/06-1A2B-T)

Fixed type VCB

H1-8

E-type cradle

F-type cradle

G-type cradle
(Withdrawable by lever)

G-type cradle
(Withdrawable by screw)

Motor
When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.
The peak value of the

Rated voltage

inrush current (A)

Rated current (A)

Consumption
power (W)

Charging time
(Sec.)
13

DC 48V

21

350

DC 110V

20

330

12

DC 125V

20

330

12

DC 220V

17

2.6

374

12

Note 1) Range of the normal operating voltage: 85~110%


2) DC 24V is the underdeveloped rating.

Closing Coil (C)

Shunt coil (TC)

The coil operated only when the power is applied continuously


over 45ms. It has built-in electrically anti-pumping circuit.

When the VCB is 'ON' position, even though the control power
of a shunt coil is 'OFF', the VCB maintains the 'ON' position.

Rated voltage

Rated current (A)

Rated voltage

Rated current (A)

DC 48V

DC 48V

DC 110V

DC 110V

DC 125V

DC 125V

DC 220V

2.5

DC 220V

2.5

Note 1) Range of the normal operating voltage: 85~110%


2) DC 24V is the underdeveloped rating.

Note 1) Range of the normal operating voltage: 70~110%


2) DC 24V is the underdeveloped rating.

Auxiliary switch
Position of the Aux.contact switch

Standard 4a4b / Optional 10a10b


General
load (A)

Inductive
load (A)

250V

10

125V

10

250V

10

125V

10

30V

10

Classification
AC
Contact Ratings
DC

Contact
configuration

VCB

a contact

bcontact

ON

ON

OFF

OFF

OFF

ON

4a4b
10a10b

Note) The contact capacity of the following accessories are the same with that of the Aux. switch. Position switch, Closing spring
contact, Charging complete indicating contact, Position switch of the earthing switch, Mechanically operated cell switch,
Truck operated cell switch.

Charge indicator of
the closing spring

Position indicator of the


main contacts

Indicating the condition of the closing spring.

Indicating the 'Close' or the 'Open' of the main contacts.


Open position:OFF

Close position:ON

Charged

Discharged
Close position

Open position

Counter
Mechanically counts the switching of the VCB by 5digits analog type counter (Standard option)

H1-9

Vacuum Circuit Breaker


Constructional and operating characteristics
Charge Indicator
of the closing spring
Close button
Key lock (Optional)
Trip button

Manual charge hole

Position indicator
of the main contacts

Counter
Screw hole for draw-in
and draw-out
Nameplate

Mounting hole

Safety cover

Manual charge
Insert the charge handle into the manual charge hole in the front of a
VCB, and rotate it to clockwise over 40times and the charge
complete with a metal sound.

Motor charge
If you apply the control power to a VCB, the closing spring will be
charged automatically by a motor and then the control power will be
turned off by the built-in limit s/w. Please use the same control
voltage for motor, Closing coil, Trip coil.

Sequence of the switching mechanism

H1-10

Above circuit diagram is based on OFF status of VCB. and closing spring is charged.

5) In fixed type VCB, LS1 (Closing-coil limit switch) is not available.

4) TC1: Secondary trip coil (Preparatory trip coil Terminal No.: 82,83)

3) Position switch: 4a (Terminal No.: 1, 2, 3, 4, 5, 6, 7, 8)

Optional accessories

52b: Auxiliary switch (NC)


LS1: Closing interlock limit switch (only withdrawable type)
LS2: Motor stopping, closing spring charged indication
LS3: Anti-closing, anti-pumping limit switch
LCS1: Opening latch checking switch(preventing closing
unless the trip latch is properly reset)
LS4, LS5: Position s/w (close in test position)
LS6, LS7: Position s/w (close in run position)

2) Trip coil supervision (Trip coil monitoring contact)

Note 1) LCS1: Latch checking switch

: External terminal of VCB


52: Vacuum circuit breaker
M: Spring charging motor
TC: Trip coil
TC1: Secondary Trip coil
C: Closing coil
Y: Anti-pump relay
52a: Auxiliary switch (NO)

A Type

Connecting terminal arrangement


B Type

Control circuit diagram

H1-11

Vacuum Circuit Breaker


7.2kV dimension (VCB)
LVB-06P-20D, 25D, 32D, 40D (Visible, Fixed) - (630/1250/2000A)
(Unit: mm)

Top

<Terminal conductor>

*125.5 applied to all 7.2kV VCB.

Front

Side

Rating

630A

1250A

10

LVB-06P-32D, 40D (Visible, Fixed) - (3150A)


Front

H1-12

Side

Top

LVB-06E, F, G-20D, 25D, 32D, 40D E, F, G class - (630/1250/2000A)


(Unit: mm)

<Terminal conductor>

Top

Front

Side

Rating

630A

1250A

10

LVB-06G-20D/T, 25D/T, 32D/T, 40D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)


Front

Side

H1-13

Vacuum Circuit Breaker


7.2kV dimension (VCB)
LVB-06E-32D, 40D

E class (Visible, Tulip contact) - (3150A)


(Unit: mm)

Front

LVB-06F-32D, 40D
Front

H1-14

Side

Top

F class (Visible, Tulip contact) - (3150A)


Side

Top

LVB-06G-32D, 40D

G class (Visible, Tulip contact) - (3150A)


(Unit: mm)

Front

Side

Top

H1-15

Vacuum Circuit Breaker


7.2kV dimension (Cradle)
LCL-06E-20D, 25D

E class (Visible, Clip contact) - (630/1250A)


(Unit: mm)

Front

Side

Top

H1-16

Rating

630A

1250A

10

55

60

95

90

LCL-06E-20D, 25D, 32D, 40D

E class (Visible, Tulip contact)


(Unit: mm)

Front

Side
Rating

1250A

2000A

10

20

Top
<Terminal conductor>

LCL-06E-32D, 40D
Front

E class (Visible, Tulip contact) - (3150A)


Side

Top

H1-17

Vacuum Circuit Breaker


7.2kV dimension (Cradle)
LCL-06F-20D, 25D

F class (Visible, Clip contact) - (630/1250A)


(Unit: mm)

Front

Side

Rating

1250A

10

55

60

95

90

LCL-06F-20D, 25D
Front

630A

Top

F class (Visible, Tulip contact) - (2000A)


Side

<Terminal conductor>
Top

H1-18

LCL-06F-32D, 40D

F class (Visible, Tulip contact) - (1250/2000A)


(Unit: mm)

Front

Side
Rating

1250A

2000A

10

20

<Terminal conductor>
Top

LCL-06F-32D, 40D
Front

F class (Visible, Tulip contact) - (3150A)


Side

Top

H1-19

Vacuum Circuit Breaker


7.2kV dimension (Cradle)
LCL-06G-20D, 25D, 32D, 40D G class (Visible, Clip contact) - (630/1250/2000A)
(Visible, Tulip contact) - (31.5/40kA 1250/2000A)
Front

Side

Top
Rating

630A

1250A 2000A
10

<Terminal conductor>

H1-20

20

(Unit: mm)

LCL-06G-20D/T, 25D/T, 32D/T, 40D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)


(Unit: mm)

Front

Side

Top

<Terminal conductor>

20/25kA

Rating
630A
A
B

31.5/40kA

1250A 2000A 1250A 2000A

12
29

25
48

12

25
48

H1-21

Vacuum Circuit Breaker


7.2kV dimension (Cradle)
LCL-06G-32D, 40D

G class (Visible, Tulip contact) - (3150A)


(Unit: mm)

Side

Top
<Terminal conductor>

<User busbar reguirement>


*To connect with VCBs bushing terminals
user busbar should have below dimensions
and two holes.

H1-22

12kV dimension (VCB)


LVB-12G-25D/T, 32D/T

G class (Enclosed, Tulip contact) - (630/1250/2000A)


(Unit: mm)

Front

Side

LVB-12G-40D

G class (Enclosed, Tulip contact) - (1250/2000A)

Front

Side
470

Top

325

330
150

496
549

288

33.5

10

69

355

668

726.5

295

150

438

40kA 1250/2000A

G class

H1-23

Vacuum Circuit Breaker


12kV dimension (VCB)
LVB-12G-40D

G class (Enclosed, Tulip contact) - (3150A)


(Unit: mm)

Front

Side
620

336

290

714
747

502

Top
210

676

210

40kA 3150A

H1-24

G class

10

348.5

806.6

360

325

12kV dimension (Cradle)


LCL-12G-25D/T, 32D/T

G class (Enclosed, Tulip contact) - (630/1250/2000A)


(Unit: mm)

Front

Side

Top
<Terminal conductor>

25kA

Rating
630A

31.5kA

1250A 2000A 1250A 2000A

12

29

25

12

25

48

H1-25

Vacuum Circuit Breaker


12kV dimension (Cradle)
LCL-12G-40D

G class (Enclosed, Tulip contact) - (1250/2000A)


(Unit: mm)

Front

Side
1250A:12t

630

1235

295

2000A:25t

731.5
946

40kA 1250/2000A

G class

<Terminal conductor>
Top

150

150

83

26

26

60

150
150

560

600

RUN
4-14 Mount hole

100

H1-26

662

LCL-12G-32D/LCL-12G-40D

G class (Enclosed, Tulip contact) - (3150A)


(Unit: mm)

Front

Side
12

439

1100

360

12

764
1014

40kA 3150A

G class

<Terminal conductor>
Top
230

230
120

145

210

760

800

210

35

70

4-14 Mount hole

100

724

H1-27

Vacuum Circuit Breaker


17.5kV dimension (VCB)
LVB-17P-25D (Visible, Fixed) - (630/1250/2000A)
(Unit: mm)

Side

Front

Top

<Terminal conductor>

LVB-17P-25D (Visible, Fixed) - (2500A)


Front

H1-28

Side

Top

Rating

630A

1250A/2000A

20

LVB-17E, F-25D

E, F class (Visible, Tulip contact) - (630/1250/2000A)


(Unit: mm)

Front

Side

<Terminal conductor>

Top

LVB-17E, F-25D
Front

E, F class (Visible, Tulip contact) - (2500A)


Side

Top

H1-29

Vacuum Circuit Breaker


17.5kV dimension (VCB)
LVB-17G-25D

G class (Visible, Tulip contact) - (630/1250/2000A)


(Unit: mm)

Front

Side

Top

LVB-17G-25D
Front

H1-30

<Terminal conductor>

G class (Visible, Tulip contact) - (2500A)


Side

Top

LVB-17G-40D

G class (Visible, Tulip contact) - (1250/2000A)


(Unit: mm)

Front

LVB-17G-40D
Front

Side

Top

G class (Visible, Tulip contact) - (3150A)


Side

Top

H1-31

Vacuum Circuit Breaker


17.5kV dimension (Cradle)
LCL-17E-25D

E class (Visible, Tulip contact) - (630/1250/2000A)


(Unit: mm)

Front

Side
Rating

630A

Top

<Terminal conductor>

H1-32

1250A 2000A
10

20

LCL-17E-25D

E class (Visible, Tulip contact) - (2500A)


(Unit: mm)

Front

Side

Top

<Terminal conductor>

H1-33

Vacuum Circuit Breaker


17.5kV dimension (Cradle)
LCL-17F-25D

F class (Visible, Tulip contact) - (630/1250/2000A)


(Unit: mm)

Front

Side

Top

<Terminal conductor>

H1-34

Rating

630A

1250A 2000A
10

20

LCL-17F-25D

F class (Visible, Tulip contact) - (2500A)


(Unit: mm)

Front

Side

Top

<Terminal conductor>

H1-35

Vacuum Circuit Breaker


17.5kV dimension (Cradle)
LCL-17G-25D

G class (Visible, Tulip contact) - (630/1250/2000A)


(Unit: mm)

Front

Side

Top

<Terminal conductor>

H1-36

Rating

630A

1250A 2000A
10

20

LCL-17G-25D

G class (Visible, Tulip contact) - (2500A)


(Unit: mm)

Front

Side

Top

<Terminal conductor>

H1-37

Vacuum Circuit Breaker


17.5kV dimension (Cradle)
LCL-17G-40D

G class (Visible, Tulip contact) - (1250/2000A)


(Unit: mm)

Side

Top

H1-38

<Terminal conductor>

LCL-17G-40D

G class (Visible, Tulip contact) - (3150A)


(Unit: mm)

Side

Top
<Terminal conductor>

H1-39

Vacuum Circuit Breaker


24kV dimension (VCB)
LVB-20P-13D, 16D, 25D (Visible, Fixed) - (630/1250/2000A)
(Unit: mm)

Front

Side

<Terminal conductor>

LVB-20E, F-13D/(T), 16D/(T), 25D/(T)


Front

E, F class - (630/1250/2000A)

Side
<Visible, Clip contact>

Note ) In case of 12.5kA & 16kA 630A, the dimension shown in parenthesis should be applied.

H1-40

<Enclosed, Tulip contact>

LVB-20G-13D, 16D, 25D

G class (Visible, Tulip contact) - (630/1250A)


(Unit: mm)

Front

LVB-20G-13D/T, 16D/T, 25D/T


Front

Side

G class (Enclosed, Tulip contact) - (630/1250/2000A)


Side

Note 1) (

): The dimension shown in parenthesis should be applied to LVB-20G-13E/T or LVB-20G-16E/T,


LVB-20G-25E/T for 630A and 1250A in case that distance between phase & phase is 210mm.
2) IP Cover applied both sides in case of 265mm phase distance.

H1-41

Vacuum Circuit Breaker


24kV dimension (Cradle)
LCL-20E-13D, 16D, 25D

E class (Visible, Clip contact) - (630/1250/2000A)


(Unit: mm)

Front

Side
Rating

Top

Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A

H1-42

630, 1250A

768 190.5 10

2000A

778 185.5 20

<Terminal conductor>

LCL-20E-13D/T, 16D/T, 25D/T

E class (Enclosed, Tulip contact) - (630/1250/2000A)


(Unit: mm)

Side
Rating

768 190.5 10

2000A

778 185.5 20
10(630/1250A)

630, 1250A

340
1033

15

265

280

404.5

115

265

20(2000A)

Front

947.5

730
960

6.5

97.5
1120

972

1167

<Terminal conductor>

630A

210.5
90

40
80
40

20

300

245

20

202

40
80
40

20

40

265

40

4-14

4-14

40

820

2-14

145

265

300

25

90 47

660
ST: 260

2000A

40.5

20
40 67

1250A

42
100 45

Top

110

400

400

100

7-14

210

Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A

H1-43

Vacuum Circuit Breaker


24kV dimension (Cradle)
LCL-20F-13D, 16D, 25D

F class (Visible, Clip contact) - (630/1250/2000A)


(Unit: mm)

Front

Side
Rating

630, 1250A

768 190.5 10

2000A

778 185.5 20

<Terminal conductor>
Top

Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A

H1-44

LCL-20F-13D/T, 16D/T, 25D/T F class(Enclosed, Tulip contact) - (630/1250/2000A)


(Unit: mm)

Front

Side
Rating

630, 1250A

768 190.5

10

2000A

778 185.5

20

<Terminal conductor>
Top

Note) Insulation barrirer is not used for rating 12.5kA 630A and 16kA 630A

H1-45

Vacuum Circuit Breaker


24kV dimension (Cradle)
LCL-20G-13D, 16D, 25D

G class (Visible, Tulip contact) - (630/1250A)


(Unit: mm)

Front

Side

Top

<Terminal conductor>

H1-46

LCL-20G-13D/T, 16D/T, 25D/T G class (Enclosed, Tulip contact) - (630/1250/2000A)


(Unit: mm)

Front

Side

Top
<Terminal conductor>

210mm
Note) (

): The dimension shown in parenthesis should be applied to LVB-20G-13E/T or LVB-20G-16E/T,


LVB-20G-25E/T for 630A and 1250A in case that distance between phase & phase is 210mm.

Earthing Switch

H1-47

Vacuum Circuit Breaker


Accessories
Accessories for VCB
Key lock
When it is locked by a key, the closing operation is not available
(electrically and mechanically) without a Key.

Button padlock
Button padlock protects 'ON' or 'OFF' button when accident is occurred
by operation at discretion.
It is available to operate after release button padlock.

Button cover
Button cover protects 'ON' of 'OFF' button when accident is
occurred by operation at discretion. It is available to operate by push
bar.

<Push bar>

Position switch (Cell switch)


Indicating the position (Run or Test) of a VCB, by mechanically
pressing the switch when a VCB change the position.
- RUN: 2a
- TEST: 2a

<G class>

Note) In case that position of VCB


changed to Run or Test position,
a contact will be closed.

H1-48

Accessories
Accessories for VCB
Secondary coil (Preparatory trip coil)
The main coil and the preparatory coil is connected in parallel. So
even though there happens a fault in the trip coil, the VCB can be
tripped by one of the two trip coils.

Latch checking switch


When the Latch is in abnormal position, the Latch checking switch
prevents the closing operation even though there is the 'Closing'
signal.

Charge indicator
Remotely indicates the charging is completed.
(Standard Feature)
- Terminal No.: 9, 10

Position padlock
The hole to prevent the draw-in and out of a VCB from the present
position.('Run' or 'Test')
Standard option in the interlock lever of the E, F class draw-out type
VCB. (Hole size = 8)

H1-49

Vacuum Circuit Breaker


Accessories
Accessories for Cradle
Earthing switch (for G class draw-out type only)
For the safety during the maintenance of a VCB panel, discharge the
charging current in the load side of a VCB with this earthing switch.

Padlock of earthing switch


(for G class draw-out type only)
The hole to prevent the accident through carelessness earthing
switch operation, the locking of the earthing switch is available when
the switch is in 'OFF' position.
(Hole size = 8)

Position switch of the earthing switch


(for G class draw-out type only)
Indicates the 'ON' or 'OFF' status of the earthing switch. (5a5b)

Locking coil of earthing switch


(for G class draw-out type only)

<Earthing Switch Position Switch>

To prevent the accident through carelessness earthing switch


operation, the earthing switch can be changed to 'ON' position after
releasing the lock by magnetizing the coils.

<Earthing Switch Locking Coil>

H1-50

Accessories for Cradle


Shutter padlock
The hole to lock the shutters (load and line side) in close position, to
increase the safety during the maintenance of a VCB draw-out
position.
(Hole size = 8)

Mechanically operated cell switch (MOC)


-for G class draw-out type only
The auxiliary switch (3a4b), which Indicate the 'ON' or 'OFF' condition
of a VCB, but operated only when the VCB is in 'Run' state. (Installed
in the bottom of a cradle)

Note) #11, 21 are Early b contact

Truck operated cell switch (TOC)


-for G class draw-out type only
The auxiliary switch (3a4b), which indicate the 'Run' state of a VCB
and is operated by the movement of a VCB frame. (Installed in the
bottom of a cradle)

Note) #11, 21 are Early b contact

Code plate (Miss insertion prevention)


-for E, F class draw-out type only
To prevent the insert a VCB to a cradle, when the ratings of VCB and
cradle are different.

Padlock
To prevent the insert draw-in/out handle to a screw hole by operating
G class VCB temporarily

H1-51

Vacuum Circuit Breaker


Accessories
Optional accessories
Capacitor trip device (CTD)

Dimension

When the control power is off, the


CTD supply the power for tripping
a VCB.

Ratings

Specification

Type

CB-T1

CB-T2

Rated input voltage

AC100/110V

AC200/220V

Freguency (Hz)

50/60

50/60

Charging volt(V)

140/155

280/310

Charging time

Connection diagram

CDT

Within 10 Sec. after the AC power off

Tripping time

Within 30 Sec. after the AC power off

Allowable Input
voltage range

85% ~ 100%

85% ~ 110%

Capacitor rating(F)

1000

560

Rectifier

Dimension

When the DC power is not available, rectify the AC power and


get the DC power for closing coil.

40A DC

Rating time
10 sec.

25

29.5

70

1 100/110V
1 200/220V

100

VCB-X

AC Input voltage Output current

150

Type

40

80

Connection diagram

Standard tool
E, F class

G class

Handle for draw-in and out

Manual charging handle

Handle for draw-in and out the VCB


(Standard feature in the draw-out type)

Handle for charging the spring manually.


(Standard feature)

H1-52

Types and ordering information


7.2kV & 24kV
LVB

20

LS VCB

13

Installation method
P

Fixed type

E class draw-out type

Rated voltage

F class draw-out type

06

20

7.2kV
24kV

06

Revision No.

1A

2B

Control voltage

D Pro-MEC

00

1A

DC110V

1B

DC220V

G class draw-out type

1C

DC48V

G class draw-out type


+ Bushing

1E

DC125V

Note2)

B, C, D

Pro-MEC
(Minimized type)

Note5)

AC220(M),

1F

DC110(TC)

Accessories
B
C1
C2
C3
D1
D2
D3
E

AC220(M),

1H

DC220(TC)

1T

AC110(M),

DC110(TC)

G
H

Auxiliary switch

Rated current

Breaking current Note1)

400A

00

8kA

04

13

12.5kA

06

630A

16

16kA

12

1250A

2E 10a10b(A type connector)

20

20kA

20

2000A

2G 4a4b(B type connector)

25

25kA

30

3150A

2H 10a10b(B type connector)

32

31.5kA

40

40kA

Note3)

2B 4a4b(A type connector)

J
K
P1
P2
Q
R
S
T

Position Switch (RUN/TEST:2a2a)


Button Padlock (ON)
Button Padlock (OFF)
Button Padlock (ON/OFF)
Button Cover (ON)
Button Cover (OFF)
Button Cover (ON/OFF)
Button padlock (ON)
+ Button cover (OFF)
Button padlock (OFF)
+ Button cover (ON)
Key Lock
Secondary Trip Coil
(Preparatory trip coil)
Fire-endurable wiring cable assy
Opening Latch Checking Switch
Dummy VCB(AMP Jack)
Dummy VCB(Phoenix Jack)
Earthing Truck(Lower terminal earthing)
Earthing Truck(Upper terminal earthing)
Pad Lock (G class)
Enclosed type, Tulip contact Note4)
Option

Note) 1. 12.5kA, 16kA and 25kA are available at 24kV class.


2. Version E is available only at 24kV G class and its distance between phases is 210mm.
3. "00" is used for ordering Earthing Truck and Dummy VCB
4. Accessory only for versions D and E
5. 1F,1H and 1T are only available at 24kV class

N CTD(Capacitor Trip Device)


O Rectifier

Cradle
LCL

20

LS Cradle

Rated voltage
06

7.2kV

20

24kV

Installation method

13

D
Revision No.

Breaking current Note1)

E class draw-out type

8kA

F class draw-out type

13

12.5kA

G G class draw-out type

16

16kA

20

20kA

25

25kA

32

31.5kA

40

40kA

06

Note2)

Accessories

Rated current

A Conventional

04

Pro-MEC
Pro-MEC
(Minimized type)

A, B, C

400A

Note3)

A MOS(3a4b)+ TOC(3a4b)

06

630A

Note3)

B Earthing Switch

12

1250A

Note3)

20

2000A

30

3150A

T
PS

Earthing Switch Position Switch+


Earthing Switch Locking coil
Enclosed type, Tulip contact
Position S/W Block
(24kV E/F class only)

Note) 1. 12.5kA, 16kA and 25kA are available at 24kV class.


2. Version E is available only at 24kV G class and its distance between phases is 210mm.
3. Versions A, B and C are available only at G class VCB.

H1-53

Vacuum Circuit Breaker


Types and ordering information
12kV
LVB
LS VCB

12

25

Installation method
G
M

06

1A

1A

DC110V

G class draw-out type

1B

DC220V

+ Bushing

1C

DC48V

1E

DC125V

B, C1, D1

Control voltage

Revision No.

G class draw-out type

Pro-MEC

Rated voltage
12

2B

12kV

Breaking current

Auxiliary switch

Rated current

25

25kA

06

630A

2B 4a4b(A type connector)

Accessories

32

31.5kA

12

1250A

2E 10a10b(A type connector)

B Position Switch (RUN/TEST:2a2a)

40

40kA

20

2000A

2G 4a4b(B type connector)

C1 Button Padlock (ON)

30

3150A

2H 10a10b(B type connector)

C2 Button Padlock (OFF)


C3 Button Padlock (ON/OFF)
D1 Button Cover (ON)
D2 Button Cover (OFF)
D3 Button Cover (ON/OFF)
E Button padlock (ON)+ Button cover (OFF)
F Button padlock (OFF)+ Button cover (ON)
G Key Lock
H Secondary Trip Coil(Preparatory trip coil)
J Fire-endurable wiring cable assy
K Opening Latch Checking Switch
S Pad Lock (G class)
T Enclosed type, Tulip contact

Cradle
LCL
LS Cradle

12

G
Installation method
G

Rated voltage
12

H1-54

12kV

25
Breaking current

G class

25

25kA

draw-out type

32
40

D
Revision No.
D

Pro-MEC

06
Rated current
06

630A

31.5kA

12

1250A

40kA

20

2000A

30

3000A

A, B, C
Accessories
T Enclosed type, Tulip contact

Vacuum Circuit Breaker


Types and ordering information
17.5kV
LVB
LS VCB

Rated voltage
17

17

25

06

1A

Revision No.

Installation method

2B

B, C1, D1

Control voltage

Pro-MEC

Fixed type

1A

DC110V

E class draw-out type

1B

DC220V

F class draw-out type

1C

DC48V

G class draw-out type

1E

DC125V

17.5kV

Breaking current

Auxiliary switch

Rated current

25

25kA

06

630A

2B 4a4b(A type connector)

Accessories

40

40kA

12

1250A

2E 10a10b(A type connector)

B Position Switch (RUN/TEST:2a2a)

20

2000A

2G 4a4b(B type connector)

C1 Button Padlock (ON)

25

2500A

2H 10a10b(B type connector)

C2 Button Padlock (OFF)

30

3150A

C3 Button Padlock (ON/OFF)


D1 Button Cover (ON)
D2 Button Cover (OFF)
D3 Button Cover (ON/OFF)
E Button padlock (ON) + Button cover (OFF)
F Button padlock (OFF) + Button cover (ON)
G Key Lock
H Secondary Trip Coil(Preparatory trip coil)
K Opening Latch Checking Switch
S Pad Lock (G class)
J Fire-endurable wiring cable assy

Cradle
LCL
LS Cradle

Rated voltage
17

17.5kV

17

25

Installation method

Breaking current

E class draw-out type

25

25kA

F class draw-out type

40

40kA

G class draw-out type

D
Revision No.
D

Pro-MEC

06

A, B, C

Rated current
06

630A

12

1250A

20

2000A

25

2500A

30

3150A

Accessories
A

MOC (3a4b) + TOC (3a4b)

Note) A is for G class only

H1-55

Vacuum Interrupter
Features & Ordering information
Features
Small Size and Light Weight
High performance, reliability, and
long life are assured.
Maintains High Vacuum
High-alumina ceramics provide
superior mechanical strength and
easy degassing.
High speed interruption and short
arcing time.
The LS Vacuum Interrupter can
meet all IEC, ANSI and NEMA
performance standards.

Ordering Information

H1-56

LV

07

08

Basic type

Rated voltage

Rated short
circuit current

Ampere

Revision No.

LS

Vacuum

07
/
10

7.2kV

04

4.5kA

12kV

08

8kA

15kV

12

24

24kV

16

Below
630A

12.5kA

1250A

16kA

2000A

20

20kA

3150A

25

25kA

31

31.5kA

40

40kA

50

50kA

Structure
The internal components of a typical Vacuum Interrupter are shown in Figure1.
LS Vacuum Interrupter consists of a ceramic insulator, two end plates, arc shield,
bellows, a movable and fixed electrode, and contact set.
The ambient gas pressure within the evacuated tube is
approximately 10-6 torr.

Movable Electrode

Movable End Plate

Bellows
Bellows Shield
Ceramic

Arc Shield

Contacts

End Shield
Fixed End Header

Fixed Electrode

Figure 1. Vacuum Interrupter Schematic

H1-57

Vacuum Interrupter
Operating characteristics

Current path

Driving force on
the high current
ARC
ARC

In the closed position, normal current flows through


the interrupter. When a fault occurs and interruption
is required, the contacts are quickly separated.
The arc drawn between the surfaces of contacts is
rapidly moved around the slotted contact surface
by self induced magnetic effects, preventing gross
contact erosion and the formation of hot spot on
the surface.
The arc burns in an ionized metal vapor, which
condenses on the surrounding metal shield. At
current zero the arc extinguishes and vapor
production ceases.
The metal vapor plasma is very rapidly dispersed,
cooled, recombined, and deionized, and the metal
vapor products are quickly condensed so that the
contacts withstand the transient recovery voltage.

Figure 2. Current flow and driving force


on arc for spiral contact

() Weld
() Bridge explosion

() Contact jets
() Shield involvement
High current arc mode

Arc initiation

() Arc instability
() Interruption

Current
zero

Fault
current

Time (ms)

Time ()
Voltage Phenomena
() Arc reignition
() Restrikes
() B. I. L
() AC voltage
withstand
Recovery
voltage

Figure 3. AC arcing and interruption phenomena in vacuum.

H1-58

Ratings and Specifications

Type

LV-07040A

LV-07080A

LV-07130A

LV-07251B

Outer view

Rated voltage

(kV)

3.6

7.2

7.2

7.2

7.2

(kV, rms)

11.5

20

20

20

20

60

60

60

60

50/60

50/60

50/60

50/60

(Amp)

400

630

630

1,250

(Sym.) (kA)

4.5

12.5

20

25

(kA, peak)

20.8

32.5

52

65

(sec)

Interrupter weight

(kg)

0.48

0.83

0.85

1.8

Moving part weight

(kg)

0.19

0.4

0.4

0.6

114

132

132

190

78

92

92

123

62

62

62

79

Electrical ratings

Rated power frequency withstand voltage


Rated impulse withstand voltage

(kV, crest)

Rated frequency

(Hz)

Rated normal current


Rated short circuit current
Rated short circuit making current

Mechanical requirements

Mechanical data

Rated duration of short-circuit

Outline dimension (mm)

Contact stroke

(mm)

Opening speed, average 0 to 75% of full stroke

(m/s)

0.6

0.7~1.0

0.7~1.0

0.7~1.0

Overtravel during opening, Max.

(mm)

Closing speed, average last 33% of full stroke

(m/s)

0.3

0.7~1.0

0.7~1.0

0.7~1.0

Contact bounce duration, Max.

(sec)

0.002

0.002

0.002

0.002

Added force from atmospheric pressure

(kgf)

50

80

Contact force from atmospheric pressure

(kgf)

9.1

9.1

15.9

(mm)

100

Contact erosion limit


Mechanical life

(10 4, Operations)

154

227

H1-59

Vacuum Interrupter
Ratings and Specifications

Type

LV-07251

LV-10252

LV-10312

LV-10403

Outer view

Rated voltage

Electrical ratings

Rated power frequency withstand voltage


Rated impulse withstand voltage
Rated frequency
Rated normal current
Rated short circuit current

Rated duration of short-circuit

Mechanical data

12

15

7.2

12

15

17.5

7.2

12

15 17.5

(kV, rms)

28

36

20

28

36

50

20

28

36

95

60

(kV, crest)

Rated short circuit making current

Mechanical requirements

(kV)

95

60

95

95

(Hz)

50/60

50/60

50/60

50/60

(Amp)

1,250

2,000

2,000

3,150

31.5

40

65/81.9

81.9

104

(Sym.) (kA)

25

20

(kA, peak)

65

52

25/31.5

25

(sec)

Interrupter weight

(kg)

1.9

4.1

4.3

6.4

Moving part weight

(kg)

0.7

0.84

0.9

1.7

209

230

230

169

181

181

213

79

103

108

135

Outline dimension (mm)

12

(mm)

Opening speed, average 0 to 75% of full stroke

(m/s)

1.0~1.3

0.7~1.0

1.0~1.3

1.2~1.6

Overtravel during opening, Max.

(mm)

1.5

Closing speed, average last 33% of full stroke

(m/s)

0.7~1.0

0.7~1.0

0.7~1.0

Contact bounce duration, Max.

(sec)

0.002

0.002

0.002

0.002

227/306

306

367

12

8
0.7~1.0

12
1.0

3
0.7~1.0

(kgf)

Contact force from atmospheric pressure

(kgf)

15.9

16.8

16.8

25

(mm)

Mechanical life

H1-60

(10 4, Operations)

1.2
1.5

Added force from atmospheric pressure

Contact erosion limit

154

10

257(272)

Contact stroke

227

50

LV-24120

LV-24121A

LV-24252A

24

24

24

50

50

50

125

125

125

50/60

50/60

50/60

50/60

50/60

50/60

630

1,250

2,000

3,150

3,150

600

25.8 1)

LV-24403

LV-12503

LV-25000

7.2

24

25.8 1)

4.76

12

25.8

70

20

50

70

19

48

60

150

60

125

150

60

95

125

12.5

12.5

16

25

60

40

31.5

50

0.6

32.5

32.5

41.6

65

130

101

81.9

130

32.5

1)

1.7

2.6

5.0

6.4

7.6

0.91

0.4

0.7

1.7

2.9

0.36

235

235

270

272

272

212

163

174

225

213

213

145

75

95

108

135

135

62

15

15

17

17

10

9.5

1.0~1.3

1.0~1.3

1.0~1.3

1.0~1.3

1.2~1.5

0.9~1.1

1.5

1.5

1.5

0.7~1.0

0.7~1.0

0.7~1.0

1.0~1.3

0.7~1.0

0.76

0.002

0.002

0.002

0.002

0.002

1.002

380

57

80

80

120

227

420

367

306

9.1

15.9

16.8

25

25

9.1

2.54

1) Only with additional external insulation

H1-61

Vacuum Interrupter
Dimensions

LV-07040A

LV-07080/LV-07130A

LV-07251

LV-07251B

LV-10252/LV-10312

LV-10403

Note)

Note) LV-10312 108

H1-62

LV-24120

LV-24252A

LV-24403

LV-24121A

49.5

LV-12503

LV-25000

H1-63

Pro-MEC MCSG

VCB

Vacuum Circuit Breaker for MCSG


Features and Structure

Contents

H2

H2-2

Control circuit diagram

H2-4

Dimensions

H2-5

Vacuum Circuit Breaker for MCSG


Features and Structure
Features
Module type VCB
Convenient especially for fabricating MCSG
- Housing is designed like VCB compartment style
- MCSG panel can be easily constructed if combined with Low voltage compartment, Busbar
compartment and Cable compartment.

Convenient for maintenance and offering high safely


- Earthing switch can be operated from outside of the panel, and which makes earthing of 3 phases at the
same time.
- Without opening the compartment panel door, breaker can be drawn in or out electrically or manually

Main functions
- Breaker : draw- in or out electrically or manually
- Compartment : 3-positions

Standard
- IEC 62271-100

Name plate
Manual closing button
Keylock
Manual trip button
Manual charging hole
Contact position
indicator
Closing spring

charge indicator

Operation counter
Insertion &

Draw-out screw

Geared Mechanism

Electrical
drive unit

Compartment

H2-2

Earthing switch

Bushings

Shutter

Ratings
25
-25
/06
LVB

Type
Rated voltage (kV)
Rated normal current (A)
Rated frequency (Hz)
Rated short-circuit breaking current (kA)
Rated short-circuit breaking capacity (MVA)
Rated short-time withstand current (kA)
Rated short-circuit making current (kA)
Rated breaking time (Cycles)
Withstand Power frequency (kV)
50 )
voltage
Impulse (kV/1.2
TRV rising rate (kV/ )
TRV max. (kV)
Rated operating sequence
Mechanical lifetime
Electrical lifetime
Rated control voltage (V)
Rated trip voltage( V)
Standard auxiliary switch
Rated opening time (s)
No-load closing time (s)
Rated charging motor current (A)
Rated closing coil current (A)
Rated trip coil current (A)
Closing spring charging time (s)
Draw-in/out motor voltage (V)
Draw-in/out motor current (A)
Distance between phases (mm)
breaker
Weight (kg)
compartment
Installing
Applied standard

25
-25
/20
LVB
25.8

630

2000
60
25
1100
25/3s
65
3
50/1min
125
0.47
41
O-0.3s-CO-3min-CO
10,000operations
10,000operations
DC 110V
DC 110V
4a4b, 8a8b
0.04
0.06
7
5
5
12
DC 110V
5
265

205
281

236.5
293
G
IEC 62271-100

Breaker

LVB

25

25

Installation method

LS VCB

06

1A

2B

Control voltage

Version

B,C,D
Accessories

1A DC110V

B Position Switch

1B DC220V

C1 Button Padlock(ON)

1C DC48V

C2 Button Padlock(OFF)

1E DC125V

C3 Button Padlock(ON/OFF)

1F AC220(M), DC110(TC)

D1 Button Cover(ON)

Breaking current

1H AC220(M), DC220(TC)

D2 Button Cover(OFF)

25

1T AC110(M), DC110(TC)

D3 Button Cover(ON/OFF)

Gclass draw-out
Rated current

Rated voltage
25

25.8kV

06

630A

20

2000A

25kA

E Button Padlock(ON)+Button Cover(OFF)


Auxiliary switch

F Button Padlock(OFF)+Button Cover(ON)

2G 4a4b(B type connector)

G Key Lock

2H 8a8b(B type connector)

H Secondary Trip Coil

Cradle(Compartment)

LCL
LS VCB

25

13

06

Rated voltage

Installation method

Breaking current

Version

Rated current

25

25.8kV

Bushing

25

25kA

06

630A

20

2000A

A,B,C
Accessories
B Earthing Switch
E Door

H2-3
3

H2-4

A2

LS2 3
4

A1

10

1
2

30
31

1
5

1 3
2 4

Ya

CLOSING POWER SOURCE

52a

A6

TC

6'

CS
A5

Indication for closing spring "charged" is available.

A4

1
2

52b

Yb

LS1

LS3

CS
A3

TRIP POWER SOURCE

MOTOR POWER SOURCE

LS6

2
2

3
3

4
4

36 37 38 39 B

10 11 12 13 14 15 16
9 10
D

2
2

3
3

4
4

36 37 38 39 B

A A1 A2 A3 A4 A5 A6 22 23 24 25 26 27 28 29 40 41 A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
( 8a 8b )
SECONDARY DISCONNECT WIRING
( TOP VIEW )

B 13 14 15 16 17 42 43 44 45 46 47

10 11 12 13 14 15 16
9 10
D

C 50 51 52 53 54 55 56 57 58 59 70 71

1
D 1

A A1 A2 A3 A4 A5 A6 22 23 24 25 26 27 28 29
A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
( 4a 4b )

B 13 14 15 16 17

C 50 51 52 53

1
D 1

35

52b

9
34

89Y

89X

89X

LS5

22
8

89Y

1
2
21

89X

22
8

2
21

44

43

15

13

14

CCW
()

CW
()

Note. Diagram shows the circuit breaker in positionOFFwith closing springCharged

34

33

44

43

16

89Y
34

33

13

89X

14

89X

89M

14

89Y 13

17

89Y

37 39 51 53 55 57 59 71

37 39 51 53 55 57 59 71

36 38 50 52 54 56 58 70
PS1

1
PS2

Run

Position S/W
Test
1

: External terminal of VCB


52 : Vacuum circuit breaker
M : Spring charging motor
TC : Trip coil
TC1 : Secondary trip coil
C : Closing coil
Y : Anti-pump relay
52a : Auxiliary switch (NO)
52b : Auxiliary switch (NC)
LS1 : Closing interlock limit switch(only withdrawable type)
LS2 : Motor stopping, closing spring charged indication
LS3 : Anti-closing, Anti-pumping limit switch
LS5 : "Off" at Test Position
LS6 : "Off" at Run Position
PS1 : Position S/W("On" at Test Position)
PS2 : Position S/W("On" at Run Position)
89X : Auxiliary Relay for Inserting
89Y : Auxiliary Relay for withdrawing
89M : Motor for withdrawing and Inserting

23 25 27 29 41 43 45 47

23 25 27 29 41 43 45 47

22 24 26 28 40 42 44 46

4b

8b

36 38 50 52 54 56 58 70

Auxiliary switch

22 24 26 28 40 42 44 46

4a

8a

Vacuum Circuit Breaker for MCSG

Control circuit diagram

Dimensions
Cradle(Compartment) - w/o Earthing Switch
Front

<A-A Section View>

Lead wire
(2m)

Rear

293.8

180

263.8
10

894
1000

53

425

RUN

410

553

Earthing

30
86
340

190

86
30

968
1000

963

Top

60

265
175
(Earthing)
6.5

45

652.4

B
TEST

265

95

183.4

(212.4)

(183.4)

15.4

35
53

425

265

2-13

95

1082

265

3-10
1365

1365

26.8

60
425

st:310

372.6

340

70 103 75

45

<B-B Section View>

<Front>

<Rear>

<Front>

410
65

<Rear>

3-11
(Mounting Hole)

<C-View(Cover 2 Cutting)>

3-1122
(Mounting Hole)

513

16.8

128 50

40

700

370

700
175
103

20

600
950

265

205

User Bus

844

20-M8 POP NUT


(DP:18)

50

340

40

483

50

15

(15)

933

963

G type breaker + track(electric draw-in/out)


630A
265

445

265

445

608

340

1013

340

2000A

860
886
912

350
481

50
785

H2-5

Vacuum Circuit Breaker for MCSG


Dimensions
Cradle(Compartment) - w/ Earthing Switch

Side

Rear

16-10
(Mounting Hole Side)

35

35

10-M8 POP NUT


(DP:18)

238.8

st:310
Run

500

Test

45

25t(2000A)
10t(630/1250A)

398.6

125

415

Front

190

Test
340

74

3-10

500

1750

415

(Door)
**Option

265
767.4

36

244

454
265

265

45

(Earthing S/W)
**Option

125
1000

175

415

265

(Earthing)
6.5

M12 TAP
(DP:24)

500

Test

415

User Bus

35

39

963

Top

320.9

<Terminal conductor>

<B-B Section View>

<Front>

<Rear>

<Front>

968

<Rear>
60

2-13
26

17

25

26

83

9-11Mounting Hole
15
700
950

17

20-M8 POP NUT


(DP:18)
50

140 150

26

25

H2-6

340

40

483

50

60
70

50

340

16.8

83

513

600

40

19

26

20 370

65

100

763

100

Power Plants

VCB

Vacuum Circuit Breaker for Power Plants

Contents

H3

Ratings

H3-4

Ratings of Accessories

H3-5

Accessories

H3-6

Control circuit diagram

H3-8

Dimensions

H3-9

Types and ordering information

H3-14

Vacuum Circuit Breaker


Power Plants
A product developed for water and thermal power plants due
to the revision and application of Kepcos standard (ES150)
followed by the IEC standard revision. It has completed the
high capacity (40~50kA) VCB series for power plants by
securing higher breaking capacity, safety and reliability.

VCB Full Option


To prevent fatal error, property and life loss caused from operator during
operation, it is equipped with safety mechanisms such as shutter padlock.

Bushing applied for Window CT adaptation


The bushing provides sufficient strength to collaborate with the internal insulation and is
adaptable with CT offering safety mechanically and electrically when applying large current.

H3-2

Vacuum Circuit Breakers


for Power Plants

It is recognized for reliability by acquiring new


IEC 62271-100 and ES150 (KEPCO standard
specification on AC breakers)

H3-3

Vacuum Circuit Breaker for Power Plants


Ratings
Type

LVB-06G-40H

Rated voltage

LVB-06G-40J

(kV)

Rated normal current

(A)

Rated frequency

LVB-06G-50J

7.2
1200

2000

3000

1250

(Hz)

2000

2500

3150

1250

2000

60

Rated short-circuit breaking current (kA)

40

50

Rated short-circuit breaking capacity (MVA)

500

624

Rated short-time withstand current (kA/3sec)

40

50

Rated short-circuit making current (kAp)

104

130

Rated breaking time

(Cycle)

Rated opening time

(sec)

0.04

No-load closing time

(sec)

0.06

Withstand

Power frequency

voltage

Impulse

(kV/min)

20

50 )
(kV/1.2

60

Rated operating sequence

CO-15s-CO

O-0.3s-CO-3min-CO

Rated charging motor current

(A)

5 (at DC125V)

5 (at DC110V)

Rated closing coil current

(A)

3 (at DC125V)

3 (at DC110V)

Rated shunt coil current

(A)

3 (at DC125V)

3 (at DC110V)

Type

Mechanical

test

Electrical

Lifetime

M2
E2 (Maintenance free)

E2 (List1)

Capacitive current switching

C2

Mechanical Without maintenance

10000 operations

Electrical

3150

Maintenance

20000 operations

Without maintenance

10000 operations

Maintenance

20000 operations

Auxiliary switch

3a3b

Installing

Draw-out G-type

Weight

Breaker G-type

(kg)

200

260

200

260

200

260

Cradle

(kg)

190

230

190

230

190

230

G-type

Visible, Tulip

Applied standard
Type test laboratory
Note) ES150: KEPCO's standard in which IEC62271-100 is applied
KERI: Korea Electrotechnology Research Institute

H3-4

ES150 NOTE)

IEC 62271-100
KERI

Ratings and auxiliary devices


Motor
When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.
The peak value of the

Rated voltage

inrush current (A)

Consumption
power (W)

Rated current (A)

Charging time
(Sec.)

DC 110V

20

330

12

DC 125V

20

330

12

Note) Range of the normal operating voltage: 85~110% of rated voltage

Closing Coil (C)

Shunt coil (TC)

When the rated volt is applied to the coil the breaker is closed.
The electrical anti-pumping circuit is built-in it.

When the rated volt is applied to the coil the breaker is opened.

Rated voltage

Rated current (A)

Rated voltage

Rated current (A)

DC 110V

DC 110V

DC 125V

DC 125V

Note) Range of the normal operating voltage: 75~125% of rated voltage

Note) Range of the normal operating voltage: 60~125% of rated voltage

Auxiliary switch
Standard configuration : 3a3b1b of early-b contact function exists inside
Resistive
load (A)

Inductive
load (A)

110V

10

125V

10

Classification
Contact Ratings

DC

Contact
configuration

Position of the Auxiliary switch


Switch
Breaker

3a3b

Mechanism
a

CLOSE

ON

OPEN

OFF

CLOSE
OPEN

MOC

TOC

OFF

ON

ON

OFF

OFF

ON

OFF

ON

OFF

ON

ON

OFF

ON * OFF * ON

OFF

OFF

ON

OFF * ON * OFF

ON

RUN

Note) The contact ratings of Mechanical Operated Cell Switch(MOC)


are the same with that of the Aux. switch.

TEST

Truck Operated Cell Switch(TOC)


Resistive
load (A)

Classification
Contact Ratings

DC

Inductive
load (A)

110V

10

125V

10

Contact
configuration

Note) * applied in the VCB of which MOC is operable at the TEST position.

3a3b

Charge indicator of
the closing spring

Position indicator of the


main contacts

Indicating the condition of the closing spring.

Indicating the 'Close' or the 'Open' of the main contacts.


Open position:OFF

Close position:ON

Charged

Discharged
Close position

Open position

Counter
Mechanically counts the operation of the VCB by 5digits

H3-5

Vacuum Circuit Breaker for Power Plants


Accessories
Accessories for breakers
Position padlock
It is located at the screw hole to prevent the draw-in and out of a breaker
from the present position(Disconnected, Test or Connected)

Mechanical position indicator


It is located in the lower part of a breaker to check the present position Disconnected, Test or Connected- easily.

Position interlock
The breaker is locked in each position-Disconnected, Test or Connected,
thus it is necessory to release the lock before draw-in or out of a breaker
from the present position.

Auto connection
When the breaker is moved to Test position from Disconnected position
the connector for control powers is automatically connected. In case of
reverse moving of the breaker the connector is automatically
disconnected.

Code plate
When the breaker is inserted to the cradle, if the ratings does not match
with the cradle, it mechanically prevents the breaker from being inserted
into the cradle.

H3-6

Accessories for breakers


Mechanically operated cell switch (MOC)
It is auxiliary switch (6a6b), which indicates the 'ON' or 'OFF' condition of a
VCB, and operated when the VCB is in 'Run' state.

Truck operated cell switch (TOC)


It is auxiliary switch (6a6b), which indicates the 'Run' state of a VCB and is
operated by the movement of a VCB frame.

H3-7

H3-8

7 23 25 27 29 41

22 23 24

A2

52
M
TC
C
Y
52a
52b
LS1
LS2
LS3
LS4

:
:
:
:
:
:
:
:
:
:
:
:

External terminal of VCB


Vacuum circuit breaker
Spring charging motor
Trip coil
Closing coil
Anti-pump relay
Auxiliary switch (NO)
Auxiliary switch (NC)
Closing interlock limit switch
Motor stopping
Anti-closing, Anti-pumping limit switch
Motor Charging interlock limit switch

LS1

A4

CS
A3

1 3
2 4
1
Yb
5
52b 30
31
3

LS3

3
4

LS4

LS2

A1

Note) Diagram shows the circuit breaker in positionOFFwith closing springCharged

6 22 24 26 28 40

12 13 14

31 35 37 39 51 53

25 26 27

<MOC>

30 34 36 38 50 52

15 16 17

22 23 24

12 13 14

25 26 27

15 16 17

4
Ya
6

Cell switch in service position

MOTOR POWER SOURCE

<TOC>

52a

A6

TC

25

56
57

27

27

26

54
55
58
59

24

12

10 11

22 23

54 56 58
2

7 8

21

18 19 20

55

55

54

54

A1 A3 A5 22 24 26

16 17

(12P TAP PLUG)

A1 A3 A5
A2 A4 A6
22 24 26
23 25 27

23

25

24

26

Auxiliary switch

55 57 59

14 15

23

22

22

3a
24

A2 A4 A6 23 25 27

13

TRIP POWER SOURCE

57

59

59

58

58

Early b

57

56

3b
56

SECONDARY DISCONNECT WIRING


(FRONT VIEW OF RECEPTACLE PLUG)

CS
A5

Vacuum Circuit Breaker for Power Plants

Control circuit diagram

CLOSING POWER SOURCE

Dimensions - Breakers
LVB-06G-40H, 40J G class (Visible, Tulip contact)-(1200, 1250, 2000A)
Side

336

368.2

351.3

130

815.2

360

722

54(male conductor)

Front

(unit : mm)

10

60

696

686.2

717

Top
254

254

685.2

532

584

<Conductor>

1200/1250/2000A
745

H3-9

Vacuum Circuit Breaker for Power Plants


Dimensions - Breakers
LVB-06G-40H, 40J G class (Visible, Tulip contact)-(2500, 3000, 3150A)
Side
336

368.2

349.8

130

815.2

360

722

79(male conductor)

Front

10

60

696

686.2

717

Top
<Conductor>

685.2

584

254

532

254

2500/3000/3150A
745

H3-10

(unit : mm)

Heat sink
(only for 3150A)

LVB-06G-50J G class (Visible, Tulip contact)-(1250, 2000A)


Side
54(male conductor)

Front

(unit : mm)

722
115.5

336

140

Moving contact

10

60

368.2

341.3

403.8

815.7

130

360

Fixed contact

696

677.2

717

Top

584

532

676.2

254

254

745

H3-11

Vacuum Circuit Breaker for Power Plants


Dimensions - Breakers
LVB-06G-50J G class (Visible, Tulip contact)-(3150A)
Side

722
115.5

79(male conductor)

Front

(unit : mm)

336
140

358.7

815.7

150.2

267.8

341.8

136.5

130

107

360

Moving contact

541
677.2

717

Top

H3-12

676.2

584

254

532

254

10

445.8
696

Fixed contact

Cradles

(unit : mm)

4-M12
DP20

374

252
50

35

1134
240
500

361

79
148

14
(Earthing)

123

816
776
103.5
175

140

2500/3000/3150A
252

374
35

254

2-M12
DP20

254

50

310

218

150

240

54

148

36

Mounting 6-12

436.5
544
140

Autocon(3a3b)

123

M.O.C(6a6b)

1200/1250/2000A

449.5
151.5

61

644

59
61()

1035

360

338

T.O.C(6a6b)

75.8

310

218

235.5

1038.5

H3-13

Vacuum Circuit Breaker for Power Plants


Types and ordering information
Breaker

LVB
LS VCB

06

40

Installation method
G

G class draw-out

12

1A

2L

P3,Q,R

Control voltage

Standard
H

ESB150

1A

DC110V

IEC

1B

DC220V

C1 Button padlock(ON)

1E

DC125V

C2 Button padlock(OFF)

Option

C3 Button padlock(ON/OFF)
D1 Button Cover(ON)
Rated voltage
06

7.2kV

Breaking current

NOTE2)

Auxiliary switch

Rated current

40

40kA

12

1200/1250A

50

50kA

20

2000A

25

2500A

30

3000/3150A

2L

3a3b(Autocon)

D2 Button Cover(OFF)
D3 Button Cover(ON/OFF)
E

NOTE1)

Button padlock(ON)+
Button cover(OFF)
Button padlock(OFF)+
Button cover(ON)

G Key Lock
P3 Dummy VCB
Note) 1.Rated current 2500A is available only at 7.2kV 40kA, IEC version(J)
2.Control voltage and Auxiliary switch are not applied to Dummy VCB and Earthing Truck

Q Earthing Truck(lower terminal)


R Earthing Truck(upper terminal)

Cradle

LCL

06

LS Cradle

40

Installation method
G

G class draw-out

12

A1, A2

standard
H

ESB150

IEC

Option
MOC(6a6b)+TOC(6a6b)
A1

MOC active only at RUN


position
MOC(6a6b)+TOC(6a6b)

A2
Rated voltage
06

H3-14

7.2kV

Rated current

Breaking current
40

40kV

12

1200/1250A

50

50kV

20

2000A

25

2500A

30

3000/3150A

MOC active only at TEST


and RUN position

Nuclear Power Plants

VCB

Vacuum Circuit Breaker for Nuclear Power Plants

Contents

H4

Ratings

H4-4

Ratings of Accessories

H4-5

Accessories

H4-6

Control circuit diagram

H4-8

Dimensions

H4-9

Types and ordering information

H4-11

Vacuum Circuit Breaker


Nuclear Power Plants
It was developed for KEPCO nuclear power stations. This breaker
satisfies quality, safety measures (secure from earthquake and
other environments), and surge protection class complies with
1E-CLASS provisions. It is featured with high breaking
technologies, safety, and reliability by applying our own vacuum
interrupters (50KA) approved by ANSI standard tests.

H4-2

Vacuum Circuit Breakers


for Nuclear Power Plants

VCB Full Option


To prevent fatal error, property and
life loss caused from operator
during operation, it is equipped
with safety mechanisms such as
shutter padlock.

Bushing applied for


Window CT adaptation
The bushing provides sufficient
strength to collaborate with the
internal insulation and is adaptable
with CT offering safety mechanically
and electrically when applying
large current.

Satisfies earthquake and


other internal environment
specifications
During the lifespan of power stations (40yrs),
it is designed to operate its fundamental
breaking functions even under the most
severe conditions like earthquake, which is
critical from safety perspectives. These
technologies proven through tests that
comply with KEPIC standard and relevant
specifications are to guarantee nuclear
reactor safety.
H4-3

Vacuum Circuit Breaker for Nuclear Power Plants


Ratings
Type
Rated voltage

(kV)

Rated normal current

(A)

LVB-05G-50B

LVB-15G-40B

4.76

15

1200

1200

2000

2000

3000

Rated frequency

(Hz)

60

60

Rated short-circuit breaking current

(kA)

50

40

(MVA)

410

1040

Rated short-time withstand current

(kA/3sec)

50

40

Rated short-circuit making current

(kA)

130

104

Rated short-circuit breaking capacity

Rated breaking time

(Cycle)

Rated opening time

(sec)

0.04

0.04

No-load closing time

(sec)

0.06

0.06

(kV/1min)

19

36

50 )
(kV/1.2

60

95

Withstand

Power frequency

voltage

Impulse

Rated operating sequence

0-0.3s-CO-3min-CO

Rated charging motor current

DC 125V

(A)

Rated closing coil current

DC 125V

(A)

Rated shunt coil current

DC 125V

(A)

Mechanical(w/o maintenance)

10000 operations

10000

Electrical(w/o maintenance)

10000 operations

10000

5a3b

5a3b

G-type

G-type

Lifetime

Auxiliary switch
Installing
1200,2000A

(kg)

300

300

3000A

(kg)

350

ANSI C37

ANSI C37

KERI

KERI

Weight

Applied standard
Type test laboratory

H4-4

Ratings of Accessories
Motor
When the closing spring is charged, the control power of motor is turned off by the built-in limit s/w.
The peak value of
the inrush current (A)

Ratedcurrent(A)

Rated voltage
4.76kV

15kV

4.76kV

15kV

50kA

40kA

50kA

40kA

15

15

DC 125V

Range of the normal


operating voltage

Consumption
power (W)

Charging time
(sec)

90~140

360

Closing Coil (C)

Shunt Coil (TC)

When the rated volt is applied to the coil the breaker is closed.
The electrical anti-pumping circuit is built-in it.

When the rated volt is applied to the coil the breaker is


opened.

The peak value of


the inrush current (A)
Rated voltage
4.76kV

15kV

50kA

40kA

DC 125V

The peak value of


the inrush current (A)

Range of the normal


operating voltage

Range of the normal


operating voltage

Rated voltage

90 ~ 140

4.76kV

15kV

50kA

40kA

DC 125V

70 ~ 140

Auxiliary switch
Standard configuration : Reversible 8C(5a3b)
and 2c(2b) with early-b contact function
Resistive
load(A)

Inductive
load(A)

250V

10

125V

10

Classification

AC
Contact Ratings
DC

Position of the Auxiliary switch

250V

10

125V

10

30V

10

Contact
configuration

Switch
Breaker

Mechanism

MOC

TOC

CLOSE

ON

OFF

ON

OFF

ON

OFF

OPEN

OFF

ON

OFF

ON

OFF

ON

CLOSE

ON

OFF

ON

OFF

ON

OFF

OPEN

OFF

ON

OFF

ON

OFF

ON

RUN
8c

TEST

Note) The contact ratings of Mechanical Operated Cell Switch(MOC)


are the same with that of the Aux. switch.

Charge indicator of
the closing spring

Position indicator of the


main contacts

Indicating the condition of the closing spring.

Indicating the 'Close' or the 'Open' of the main contacts.


Open position:OFF

Close position:ON

Charged

Discharged
Close position

Open position

Counter
Mechanically counts the operation of the VCB by 5digits

H4-5

Vacuum Circuit Breaker for Nuclear Power Plants


Accessories
Accessories for breakers
Position padlock
It is located at the screw hole to prevent the draw-in and out of a breaker
from the present position(Disconnected, Test or Connected)

Mechanical position indicator


It is located in the lower part of a breaker to check the present position Disconnected, Test or Connected- easily.

Auto connection
When the breaker is moved to Test position from Disconnected position the
connector for control powers is automatically connected.
In case of reverse moving of the breaker the connector is automatically
disconnected.

Reversible contact
10 auxiliary switches are provided. 8 of them consist of reversible 8c which
can be changed from a(b) to b(a). Factory composition is 5a3b. And the
other 2 switches are supplied as 2b with early-b contact function

Code plate
When the breaker is inserted to the cradle, if the ratings does not match
with the cradle, it mechanically prevents the breaker from being inserted
into the cradle.

Auto discharge
In case the breaker is drawn-out when the closing spring is charged in the
position-Disconnected, Test or Connected, or the breaker is moved to
Disconnected position from Test position the closing spring shall be
automatically released.

H4-6

Accessories for cradles


Mechanically operated cell switch (MOC)
This 6a6b switch indicates the 'ON' or 'OFF' condition of a VCB and is
operated in the positions of 'Run' and 'Test"..

Truck operated cell switch (TOC)


This 6a6b switch indicates the 'Run' state of a VCB and is operated by the
movement of a VCB frame.

H4-7

H4-8

A2

Yb

LS1

31

A4

52b

5
30

2
1

LS2 3

LS3

A3

A1

CS

4
Ya
6

CLOSING POWER SOURCE

MOTOR POWER SOUREC

Note) Diagram shows the circuit breaker in positionOFFwith closing springCharged

: External terminal of VCB


52 : Vacuum circuit breaker
M : Spring charging motor
TC : Trip coil
C : Closing coil
Y : Anti-pump relay
52a : Auxiliary switch (NO)
52b : Auxiliary switch (NC)
LS1 : Closing interlock limit switch (only withdrawable type)
LS2 : Motor stopping, closing spring charged indication
LS3 : Anti-closing, Anti-pumping limit switch

52a

A6

TC

A5

CS

24

26

5a
28

40

23

18

19

20

22

10

58

24

11

12

56 58

57 59

23

55

57

early b

59

42 55 44 57 46 59

SECONDARY DISCONNECT WIRING

3b
56

43 54 45 56 47 58

54

(FRONT VIEW OF RECEPTACLE PLUG)

21

54

16 17

41

A1 A3 A5 22 24 26 28 40

15

29

55

14

27

A2 A4 A6 23 25 27 29 41

13

25

23 34 25 36 27 38 29 50 41 52

22 35 24 37 26 39 28 51 40 53

22

Auxiliary switch

Vacuum Circuit Breaker for Nuclear Power Plants

Control circuit diagram

TRIP POWER SOURCE

Dimensions
Breaker
722
254

254

722
745

<Front view>

228

369

816

817

228

360

109

360

109

3000A

86.5
109.5

442.5
713

1200/2000A

<Side view>

H4-9

Vacuum Circuit Breaker for Nuclear Power Plants


Dimensions
Cradle
936
254

254

644
850

<Front view>

137

100

343

252

203

360

36

310

213

1070

4-M12 DP18
2-M12 DP24

449

1200/2000A

157

50

2-M12 DP24

3000A
195

630

1020

<Side view>

H4-10

Types and ordering information


Breaker

LVB

05

40

G class draw-out

1A

2K

Control voltage Note)

Version

Installation method

LS VCB

20

Pro-MEC

Nuclear class

1A

DC110V

1E class

1B

DC220V

Non 1E class

1C

DC48V

1E

DC125V

Note) 1A,1B,1C are only available


at 15kV class

Rated voltage
05

4.76kV

15

15kV

40
50

Auxiliary switch

Rated current

Breaking current
40kA

12

1200A

50kA

20

2000A

30

3000A

8c

2K

Cradle

LCL

05

40

Installation method

LS Cradle
G

G class draw-out

Nuclear class

Version
B

Pro-MEC

1E class

Non 1E class

Rated current

Breaking current

Rated voltage

20

05

4.76kV

40

40kA

12

1200A

15

15kV

50

50kA

20

2000A

30

3000A

H4-11

Memo

H4-12

For your safety, please read user's manual thoroughly before operating.
Contact the nearest authorized service facility for examination, repair, or adjustment.
Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!

Safety Instructions

Any maintenance and inspection shall be performed by the personnel having expertise concerned.
2008.11 LS Industrial Systems Co.,Ltd. All rights reserved.

www.lsis.biz
HEAD OFFICE

Global Network
LS Industrial Systems (Middle East) FZE
Dubai, U.A.E.

LS Tower 1026-6, Hogye-dong, Dongan-gu,


Anyang-si, Gyeonggi-do 431-848, Korea
Tel. (82-2)2034-4870
Fax. (82-2)2034-4713

Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates
Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: hwyim@lsis.biz

Dalian LS Industrial Systems Co., Ltd.


Dalian, China
Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China
Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn

LS Industrial Systems (Wuxi) Co., Ltd.


Wuxi, China
Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.China
Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn

CHEONG-JU PLANT

LS-VINA Industrial Systems Co., Ltd.


Hanoi, Vietnam
Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam
Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com

Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,


Cheong Ju, 361-720, Korea

LS-VINA Industrial Systems Co., Ltd.


Hochiminh , Vietnam
Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam
Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: sbpark@lsisvina.com

LS Industrial Systems Tokyo Office


Tokyo, Japan
Address: 16FL, Higashi-Kan, Akasaka Twin Tower 17-22, 2-chome, Akasaka, Minato-ku Tokyo 107-8470, Japan
Tel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: jschuna@lsis.biz

LS Industrial Systems Shanghai Office


Shanghai, China
Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China
Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn

LS Industrial Systems Beijing Office


Beijing, China
Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
Beijing 100013, P.R. China
Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn

LS Industrial Systems Guangzhou Office


Guangzhou, China
Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China
Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.biz

LS Industrial Systems Chengdu Office


Chengdu, China
Address: 12Floor, Guodong Building, No52 Jindun Road Chengdu, 610041, P.R. China
Tel: 86-28-8612-9151 Fax: 86-28-8612-9236 e-mail: yangcf@lsis.com.cn

LS Industrial Systems Qingdao Office


Qingdao, China

Specifications in this catalog are subject to change without notice due to


continuous product development and improvement.

2009. 02

Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China
Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn

Vacuum Circuit Breakers/Vacuum Interrupter(E) 2008. 11/(02) 2009. 02 Printed in Korea