Sei sulla pagina 1di 8

BOM FOR 220/60KV HATATBA OUTDOOR SUBSTATION

Sl. No.
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.10
1.11
1.12
1.13
1.14
1.15
1.16
1.17
2
2.1

DESCRIPTION
METAL STRUCTURAL WORK
Poles for 220kV and 60kV Gantry
Beams for 220kV and 60kV Gantry
Frame for 220kV Line Disconnector + Earthing switch
Frame for 60kV Line Disconnector + Earthing switch
Frame for 220kV Disconnector bars
Frame for 60kV Disconnector bars
Frame for 220kV Neutral Disconnector
Frame for 60kV Neutral Disconnector
Support frame of 220kV Voltage Transformer
Support frame of 60kV Voltage Transformer
Support frame of 220kV Current transformer
Support frame of 60kV Current transformer
Support frame of 220kV and 10kV Surge Arresters
Support frame of 220kV and 60kV Busbar insulators
Support frame of Auxiliary Service Transformer
LT cables support frame, various fittings + Grating
Frame for Auxiliary Service Transformer disconnector Insulator

Rev 00
Unit

Qty

LOT
LOT
LOT
LOT
LOT
LOT
LOT
LOT
LOT
LOT
LOT
LOT
LOT
LOT
LOT
LOT
LOT

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Nos

03

HIGH VOLTAGE EQUIPMENT


120MVA, 220/63/10.5kV Transformers Including Oil and Oil Treatment
Outdoor, Three phase, 50Hz, 220/63/10.5kV, type of cooling
ONAN/ONAF as per specification, vector group YNyn0(d11), with On
load tap changer located on high voltage side with tap range +18% of
HV Variation in steps of 1.5%, RTCC panel, marshalling box, minimum
creepage distance 31mm/kV, HV side terminal connectors suitable for
Almelec Conductor - 3Nos. for each, IV side terminal connectors
suitable for Almelec Conductor - 3Nos. for each, tertiary side terminal
connectors suitable for Almelec Conductor 3Nos. for each, bushing
CTs as per specification, Fittings & accessories specified at clause No.
1.3.7.3 in the specification of Technical requirements of Power
transformers (Part 4 book 4.1), Complete as per technical
specification.

2.2

1600A, 220kV three pole circuit breakers including frame


1600A, 3pole, Short time current rating 31.5kA for 1sec, SF6 type with
Spring operating mechanism, DC motor operated, suitable for control
voltage of 127VDC, control cabinet, piping, interpole cables, cable
glands, terminal blocks, marking ferrules, lugs, pressure gauge, density
monitor, support structure, minimum creepage distance 31mm/kV,
complete as per specification.

Sets

03

2.3

1600A, 220kV single phase three pole circuit breakers including frame

Sets

03

Sets

01

1600A, 1-phase three pole, Short time current rating 31.5kA for 1sec,
SF6 type with Spring operating mechanism, DC motor operated,
suitable for control voltage of 127VDC, control cabinet, piping,
interpole cables, cable glands, terminal blocks, marking ferrules, lugs,
pressure gauge, density monitor, support structure, minimum creepage
distance 31mm/kV, complete as per specification.
2.4

4000A, 220kV coupling circuit breakers including frame


4000A, three pole, Short time current rating 31.5kA for 1sec, SF6 type
with Spring operating mechanism, DC motor operated, suitable for
control voltage of 127VDC, control cabinet, piping, interpole cables,
cable glands, terminal blocks, marking ferrules, lugs, pressure gauge,
density monitor, support structure, minimum creepage distance
31mm/kV, complete as per specification.
Page 1 of 8

Remarks

Sl. No.

DESCRIPTION

Unit

Qty

2.5

1600A, 60kV three pole circuit breaker including frame


1600A, 3pole, Short time current rating 31.5kA for 1sec, SF6 type with
Spring operating mechanism, DC motor operated, suitable for control
voltage of 127VDC, control cabinet, piping, interpole cables, cable
glands, terminal blocks, marking ferrules, lugs, pressure gauge, density
monitor, support structure, minimum creepage distance 31mm/kV,
complete as per specification.

Sets

03

2.6

1250A, 60kV single phase three pole circuit breaker including frame

Sets

09

Sets

01

Sets

12

Sets

02

Sets

06

Sets

18

Sets

02

Sets

03

2.7

2.8

2.9

2.10

2.11

2.12

2.13

1250A, 1-phase 3pole, Short time current rating 31.5kA for 1sec, SF6
type with Spring operating mechanism, DC motor operated, suitable for
control voltage of 127VDC, control cabinet, piping, interpole cables,
cable glands, terminal blocks, marking ferrules, lugs, pressure gauge,
density monitor, support structure, minimum creepage distance
31mm/kV, complete as per specification.
3000A, 60 kV circuit breaker including frame (Coupling)
3000A, three pole, Short time current rating 31.5kA for 1sec, SF6 type
with Spring operating mechanism, DC motor operated, suitable for
control voltage of 127VDC, control cabinet, piping, interpole cables,
cable glands, terminal blocks, marking ferrules, lugs, pressure gauge,
density monitor, support structure, minimum creepage distance
31mm/kV, complete as per specification.
1600A, 220kV Three-pole Disconnectors Bars
1600A, Horizontal Double Break type, main switch shall be gang
operated, DC Motor operated, suitable for operating voltage of
127VDC, Short time current rating 31.5kA for 1sec, Solid core post
insulators, 8KN - 9Nos for each set, minimum creepage distance
31mm/kV and complete as per specification.
4000A, 220kV Three-pole Disconnectors Bars (Coupling)
4000A, Three pole horizontal double break type, main switch shall be
gang operated, DC Motor operated, suitable for operating voltage of
127VDC, Short time current rating 31.5kA for 1sec, Solid core post
insulators, 8KN - 9Nos for each set, minimum creepage distance
31mm/kV and complete as per specification.
1600A, 60kV Three-pole Disconnectors Bars
1600A, Horizontal Double Break type, main switch shall be gang
operated, DC Motor operated, suitable for operating voltage of
127VDC, Short time current rating 31.5kA for 1sec, Solid core post
insulators, 4.5kN - 9Nos for each set, minimum creepage distance
31mm/kV and complete as per specification.
1250A, 60kV Three-pole Disconnectors Bars
1250A, Horizontal Double Break type, main switch shall be gang
operated, DC Motor operated, suitable for operating voltage of
127VDC, Short time current rating 31.5kA for 1sec, Solid core post
insulators, 4.5kN - 9Nos for each set, minimum creepage distance
31mm/kV and complete as per specification.
3000A, 60kV Coupling Three-pole Disconnectors Bars
3000A, Three pole horizontal double break type, main switch shall be
gang operated, DC Motor operated, suitable for operating voltage of
127VDC, Short time current rating 31.5kA for 1sec, Solid core post
insulators, 4.5kN - 9Nos for each set, minimum creepage distance
31mm/kV and complete as per specification.
220kV Three-pole Line Disconnectors + Earthing switch
1600A, Three pole horizontal double break type, main & earth switch
shall be gang operated, DC Motor operated, suitable for operating
voltage of 127VDC, Short time current rating 31.5kA for 1sec, Solid
core post insulators, 8KN - 9Nos for each set, minimum creepage
distance 31mm/kV and complete as per specification.

Page 2 of 8

Remarks

Sl. No.

DESCRIPTION

Unit

Qty

2.14

1250A, 60kV Three-pole Line Disconnectors + Earthing switch


1250A, Horizontal Double Break type, main & earth switch shall be
gang operated, DC Motor operated, suitable for operating voltage of
127VDC, Short time current rating 31.5kA for 1sec, Solid core post
insulators, 4.5kN - 9Nos for each set, minimum creepage distance
31mm/kV and complete as per specification.

Sets

09

2.15

1600A, 60kV Three-pole TR arrival Disconnectors + Earthing switch

Sets

03

Nos

03

Nos

03

Nos

09

Nos

09

Nos

03

Nos

09

Nos

02

2.16

2.17

2.18

1600A, Horizontal Double Break type, main & earth switch shall be
gang operated, DC Motor operated, suitable for operating voltage of
127VDC, Short time current rating 31.5kA for 1sec, Solid core post
insulators, 4.5kN - 9Nos for each set, minimum creepage distance
31mm/kV and complete as per specification.
1250A, 220kV Neutral Disconnectors
1250A, Three pole horizontal double break type, main switch shall be
gang operated, DC Motor operated, suitable for operating voltage of
127VDC, Short time current rating 31.5kA for 1sec, Solid core post
insulators, 8KN - 3Nos for each, minimum creepage distance 31mm/kV
and complete as per specification.
1250A, 60kV Neutral Disconnectors
1250A, Three pole horizontal double break type, main switch shall be
gang operated, DC Motor operated, suitable for operating voltage of
127VDC, Short time current rating 31.5kA for 1sec, Solid core post
insulators, 4.5kN - 3Nos for each, minimum creepage distance
31mm/kV and complete as per specification.
220kV Current transformer, 600-1200/ 1-1-1 A (Line )
Outdoor, 1-phase, oil filled, Short time current rating 31.5kA for 1sec,
Core1 : 600-1200/1A, for metering, 30VA, class: 0.5
Core2 : 600-1200/1A, for Line protection, 30VA, 5P20
Core3 : 600-1200/1A, for Line protection, 30VA, 5P20
Minimum creepage distance 31mm/kV and complete as per
specification.

2.19

220kV Current transformer, 200-400 / 1-1-1 A (Transformer )


Outdoor, 1-phase, oil filled, Short time current rating 31.5kA for 1sec,
Core1 : 200- 400/1A, for metering, 30VA, class: 0.5
Core2 : 200- 400/1A, for Transformer Diff protn, 30VA, 5P20
Core3 : 200- 400/1A, for Transformer back up protn, 30VA, 5P20
Minimum creepage distance 31mm/kV and complete as per
specification.

2.20

220kV Coupling current reducer 2400-1200 / 1-1-1 A


Outdoor, 1-phase, oil filled, Short time current rating 31.5kA for 1sec,
Core1 : 1200-2400/1A, for metering, 30VA, class: 0.5
Core2 : 1200-2400/1A, for protection, 30VA, 5P20
Core3 : 1200-2400/1A, for protection, 30VA, 5P20
Minimum creepage distance 31mm/kV and complete as per
specification.

2.21

2.22

220kV Capacitive voltage transformer


4400pF, Outdoor, single phase, oilfilled, Short time current rating
31.5kA for 1sec,
Core1 : 220/3/0.1/3kV for metering, Class 0.5, 100VA
minimum creepage distance 31mm/kV and complete as per
specification.
220kV Inductive voltage transformer
Outdoor,1-phase,oilfilled, Short time current rating 31.5kA for 1sec,
Core1 : 220/3/0.1/3kV for metering, Class 0.5, 100VA
minimum creepage distance 31mm/kV and complete as per
specification.
Page 3 of 8

Remarks

Sl. No.
2.23

DESCRIPTION
60kV Current transformer, 600-300 / 1-1A

Unit

Qty

Nos

27

Nos

09

Nos

27

Nos

09

Nos

02

Nos

09

Nos

09

Nos

09

LOT
Nos

1
07

Sets

02

LOT

LOT

LOT

Outdoor, 1-phase, oil filled, Short time current rating 31.5kA for 1sec,
Core1 : 600-300/1A, for metering, 30VA, class: 0.5
Core2 : 600-300/1A, for Line protection, 30VA, 5P20
Minimum creepage distance 31mm/kV and complete as per
specification.
2.24

60kV Transformer Incoming current transformer, 1400-700 / 1-1A


Outdoor, 1-phase, oil filled, Short time current rating 31.5kA for 1sec,
Core1 : 1400-700/1A, for metering, 30VA, class: 0.5
Core2 : 1400-700/1A, for Transformer Diff protn, 30VA, 5P20
Minimum creepage distance 31mm/kV and complete as per
specification.

2.25

2.26

2.27

2.28

2.29

2.30

2.31
2.32

2.33

2.34

2.35

2.36

60kV Capacitive voltage reducer


4400pF, Outdoor, single phase, oilfilled, Short time current rating
31.5kA for 1sec,
Core1 : 60/3/0.1/3kV for metering, Class 0.5, 100VA
minimum creepage distance 31mm/kV and complete as per
specification.
Transformer Incoming inductive voltage reducer
Outdoor,1-phase,oilfilled, Short time current rating 31.5kA for 1sec,
Core1 : 60/3/0.1/3kV for metering, Class 0.5, 100VA
minimum creepage distance 31mm/kV and complete as per
specification.
60kV Inductive voltage reducer bar
Outdoor,1-phase,oilfilled, Short time current rating 31.5kA for 1sec,
Core1 : 60/3/0.1/3kV for metering, Class 0.5, 100VA
minimum creepage distance 31mm/kV and complete as per
specification.
220kV Circuit caps/plugs (wave traps)
1600A, 0.2mH, suspension type wave traps, Adjustable for frequency
range of "50 to 400 kHz, Short time current rating 31.5kA for 1sec,
complete as per specification.
60kV Circuit caps/plugs (wave traps)
1250A, 0.2mH, suspension type wave traps, Adjustable for frequency
range of "50 to 400 kHz, Short time current rating 31.5kA for 1sec,
complete as per specification.
220kV surge arresters with discharge counters
Class 3, 10KA nominal discharge current, With insulating base,
discharge counter, milliammeter, Grading / Corona ring, minimum
creepage distance 31mm/kV and complete as per specification
Chord and coupling boxes
10kV surge arresters with discharge counters
Class 1, 10KA nominal discharge current, With insulating base,
discharge counter, milliammeter, minimum creepage distance 31mm/kV
and complete as per specification
Auxiliary Service Transformer Disconnectors
1250A, Three pole horizontal double break type, main switch shall be
gang operated, DC Motor operated, suitable for operating voltage of
127VDC, Short time current rating 31.5kA for 1sec, Solid core post
insulators - 3Nos for each, minimum creepage distance 31mm/kV and
complete as per specification.
220kV Insulator support bars
Solid core post insulators 8kN, minimum creepage distance 31mm/kV
and complete as per specification
60kV Insulator support bars
Solid core post insulators 4.5kN, minimum creepage distance
31mm/kV and complete as per specification
Neutral insulator supports
Page 4 of 8

Remarks

Sl. No.

DESCRIPTION

Unit

Qty

2.37

Lightning conductor Including MAT

LOT

2.38

AGS tube

LOT

LOT

LOT

Nos
Nos

03
03

Nos
Nos
Nos

03
03
02

Nos
LOT

01
1

Nos

03

Nos
Nos

09
07

No

01

LOT

LOT

LOT

LOT

No

01

2.39
2.40
3
3.1

3.2

3.3
3.4
3.5
3.6

3.7

3.8

Set of connectors, 120 mm copper cables, copper tubes, copper bars,


strained, descents, string accessories, Earthing accessories, protection
cable, neutral descents, Isolating plates
Current Transformer Toroids
LT EQUIPEMENT
220/63/10.5kV TRANSFORMER PROTECTION
Protection cabinet
Control cabinet including regulation and parallel operation
OUTGOING FEEDER 220 KV
Protection cabinet
Control and metering cabinet
Towards station differential protection
COUPLING FEEDER 220 KV
Control and protection cabinet (coupling + control bars)
220kV Busbar Protection cabinet ( 08 feeders + 01 Coupling )
60KV Incoming transformer protection
Protection, control and metering cabinet
OUTGOING FEEDER 60 KV
Protection, control and metering cabinet
Towards station differential protection
COUPLING FEEDER 60 KV
Control and protection cabinet (coupling + control bars)
Equipement control system:
Comprehensive system redundancy and split in two cabinets with
different parameters and all constraints including:
02 Industrial PC equiped with keyboard and mouse and integrated
mass storage system
Software including license and upgrades
Printers
21 inch screens 02
- UPS 127 VDC / 220 VAC
Engineering PC
Consumables and accessories
RTU Function with three (03) communication cards (HT) +
specifications, integration and extension to PCG (Clustered Command
Center) standards, communication, testing and commissioning,

3.9

3.10

Local network switches


Metering Equipment
Metering and telemetry system independent of CCN with PC, modem
and accessories, software and licensing and updates including all
contraints
Oscillograph Equipment
168 analog channels + 336 logics with printers, Industrial PC with
keyboard, modem and accessories, software and license including
independent teleperturbographie (remote sensing) and all constraints.

3.11
3.12

GENERAL BRACKET CABINET HT


TG unit, 2nd channel alarm unit, GPS synchronized equipment and all
constraints
Laptop for configuring protective and metering equipment, accessories,
software including licence and updates.

Page 5 of 8

Remarks
MAT is not
known
AGS not
known

Sl. No.

DESCRIPTION

4
4.1

AUXILLIARY SERVICES
500kVA TSA (Auxiliary Service Transformer) minimum
Outdoor, Three phase, 50Hz, 10/0.38kV Auxiliary Service Transformer,
ONAN type of cooling, vector group YnZn11,with insulating oil, with
cable box on secondary side, HV side terminal connectors suitable for
Almelec conductor - 3Nos. for each, and LV side cable box suitable for
7Nos 1C X 630sqmm XLPE armoured Al cable and with cable glands
and lugs, minimum creepage distance 31mm/KV and complete as per
specification.
Emergency unit (100kVA minimum ) + including start-up battery + Fuel
tank
Net electrical output 100kVA, 1500RPM, 380-220V, 3phase, 50Hz, DG
set shall be equipped with following:
(i) Diesel engine complete with all accessories.
(ii) An alternator directly coupled to the engine through coupling,
complete with all accessories.
(iii) Automatic voltage regulator.
(iv) Complete starting arrangement, including two nos. 24V batteries &
chargers.
(v) Base frame, foundation bolts etc.
(vi) Day tank of 990 Litre capacity.
(vii) Engine Cooling and lubrication system.
(viii) Engine air filtering system.
(ix) Exhaust silencer package.
(x) Set of GI pipes, valves, strainers, unloading hose pipes as required
for fuel transfer system from storage area to fuel tank including
electrically driven fuel pump.
(xi) All lubricants, consumable, touch up paints etc. for first filing,
testing & commissioning at site. The fuel oil for first commissioning.
(xii) AMF panel for control, metering and alarm along with transducers.
(xiii) Enclosure for silent type D.G. Set and complete as per
specification

4.2

Unit

Qty

Nos

02

LOT

4.3
4.4

Circuit breaker cabinet Primary overcurrent dry coolers


127Vdc Battery, minimum 350AH
VRLA type with metallic stand/frame, acid resistant paint, insulators,
unearthed system, 58 Cells, 2V/Cell and complete as per specification

LOT
Nos

1
02

4.5

48Vdc Battery, minimum 350AH


VRLA type with metallic stand/frame, acid resistant paint, insulators,
+ve earthed system, 58 Cells, 2V/Cell and complete as per
specification
127 Vdc rectifier with manual/auto changeover
127V , minimum 100A Float Cum Boost charger

Nos

01

Nos

03

4.7

48 Vdc rectifier with manual/auto changeover


48V , minimum 60A Float Cum Boost charger

Nos

02

4.8
4.9
4.10
4.11
4.12
4.13
4.14
4.15

Alternate main auxiliary cabinet (for AC)


Auto / Manual changeover cabinet
Alternate emergency auxiliary cabinet (for AC)
127 Vdc Auxiliary service cabinet, Normal, standby (for DC)
127 Vdc changeover cabinet
Auxiliary service cabinet 48 Vdc
Alternative DC enclosure in BR (in relay building)
Alternative AC enclosure in BR (in relay building)

LOT
LOT
LOT
LOT
LOT
LOT
LOT
LOT

1
1
1
1
1
1
1
1

4.16

Enclosures of all type (current, voltage,48 V HF,guard lodge and booth)

LOT

4.17

Auxiliary Service Transformer cabinet including incoming TSA (Auxiliary


Service Transformer)

LOT

4.6

Page 6 of 8

Remarks

Sl. No.
5
5.1
5.2
5.3
5.3.1

5.3.2

DESCRIPTION
HF, TELEPHONE AND TELEINFORMATION EQUIPMENT
Bi-channel BLU equipment
HF Digital automatic exchange equipment
SDH Equipment - STM16:
Side Post :
SDH Multiplexer - STM16 (Including amplifiers), interfaces, inputs and
outputs :
10 STM-4 interfaces
02 STM-4 interfaces
02 STM-1 interfaces
32 E1 interfaces
16 FE interfaces
PCM equipment: The supplier must provide for each station, PCM
equipment that can be connected to the SDH equipment and can be
recognized by the same management station's SDH equipment
10 E1 interfaces
20 RS 232 interfaces
8 RS 485 interfaces
20 interfaces 2 wire / 4 wire E&M
4 interfaces for remote subscriber connections
4 interfaces for hotline connections
Towards station side :
Extension SDH equipment for existing stations towards including
parameters, integration testing, commissioning and communications

5.4
5.5
5.6

5.7
6
6.1
6.2
6.3
6.4
6.5
7
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.8

Mux equipment at existing stations towards including testing,


commissioning and communications
Remote protection equipment Support MUX
Remote protection equipment Support BLU
Telephone station:
- Normal
- Waterproof
Laptop for configuring telecommunication equipment, accessories,
software including licenses and updates
CABLES
LV Cables (Screen and power)
Telephone cables
Identification and Cabling Connection Accessories (Lugs, Sleeves
etc ....)
Coaxial Cables
Fiber Optic Cables
MISCELLANEOUS EQUIPMENT
Dummie plates
DENY locks
Indoor lighting
Outdoor lighting and peripheral
Air conditioning and heating
Remote monitoring and anti-intrusion equipment
Fire dectection system
Power Transformers 220/63/10.5kV System Monotoring , including (01)
On-line dissolved gas analyzer that gives more moisture 8 gas
separately with cables and connectors.
RECAP

1
2

METAL STRUCTURAL WORK


HIGH VOLTAGE EQUIPMENT
Page 7 of 8

Unit

Qty

Nos
No

22
1

Lot

Lot

Lot

Nos
Nos

18
22

Lot
Nos

1
3

No

LOT
LOT

1
1

LOT

LOT
LOT

1
1

LOT
LOT
LOT
LOT
LOT
LOT
LOT

1
1
1
1
1
1
1

LOT

Remarks

Sl. No.
3
4
5
6
7
8
9

DESCRIPTION

Unit

Qty

LOW VOLTAGE EQUIPMENT


AUXILLIARY SERVICES
TELEPHONE, HF AND TELEINFORMATION EQUIPMENT
CABLES
OTHER EQUIPMENT
SPARE PARTS
TOOLS

NOTE: METAL STRUCTURAL WORK CAN BE DINAR CURRENCY OR FOREIGN CURRENCY

Page 8 of 8

Remarks

Potrebbero piacerti anche