Generation
APPLICATIONS
Medium to large generator applications
FEATURES
Protection
Two stage field ground resistance based element - 64F
Diagnostics
Injected voltage and frequency supervision
Digital Energy
1
Generation
Slip Rings
Injection Unit
Resistor Box
Field ground units are used to protect the field windings in the generator.
This assists with preventing serious damage to the generator. The field
ground units come with two options:
Single box solution for field voltages up to 600 VDC
An additional resistor box for field voltages between 600-800 VDC
www.GEDigitalEnergy.com
Rotor
Stator
Trip
25
24
27P
32
40
50/27 21P
50P 50N
51P 51N
46
68
78
49
EX
64F
GPM-F
Metering
1.000
87S
1.000
59X
10.072
64TN
7.574
10.072
7.574
64S
Dimensional Data
Generation
Close
52
Function
21P
24
25
27P
27TN
27X
32
40
46
49
50G
50N
50P
50SP
50/27
51G
51P
59N
59P
59X
59_2
64F
64S
64TN
67_2
67N
67P
68
78
81O
81R
81U
87G
87S
11.770
11.770
Top
1.000
2.306
2.306
12.270
7.000
10.072
12.270
Side
7.574
10.142
10.142
6.500
5.875
5.000
11.770
9.090
9.090
High Voltage Resister Box Module (Field Voltages 600 VDC - 800 VDC)
3.500
Top
2.306
7.000
Side
12.270
7.000
6.500
5.875
5.000
2.500
10.142
2.750
8.600
3.500
9.090
www.GEDigitalEnergy.com
7.000
Protection Specifications
Field Ground
Generation
Field voltage
measurement range:
Field voltage
measurement accuracy
- low
Field voltage
measurement accuracy
- high
Field ground RMS
current accuracy:
Fault location accuracy:
Field ground resistance
elements typical
operating time:
Field ground element
dropout level accuracy:
Time delay accuracy:
Field Current
Field current
measurement (dcmA)
accuracy:
Field over and under
current elements
operating time:
Field current element
dropout level accuracy:
Time delay accuracy:
Tests
1 k20 M
Dielectric voltage
withstand
Impulse voltage
withstand
Insulation resistance
Damped oscillatory
Electrostatic discharge
RF immunity
Fast transient
disturbance
Surge immunity
Conducted RF
immunity
Voltage interruption
and ripple DC
Radiated and
conducted emissions
Sinusoidal vibration
Shock and bump
Seismic
Power magnetic
immunity
Pulse magnetic
immunity
Damped magnetic
immunity
Voltage dip and
interruption
Voltage ripple
Ingress protection
Environment (Cold)
Environment (Hot)
Humidity
SWC oscillatory
SWC transients
RF immunity
ESD
Safety
Safety
Approvals
EN60255-5
CE compliance
EN60255-5
EN60255-5
IEC 61000-4-18 /
IEC 60255-22-1
EN61000-4-2 / IEC 60255-22-2
EN61000-4-3 / IEC 60255-22-3
EN61000-4-4 / IEC 60255-22-4
EN61000-4-5 / IEC 60255-22-5
EN61000-4-6 / IEC 60255-22-6
IEC 60255-11
North America
ISO
Environmentals
Temperature:
Humidity:
Altitude:
Pollution Degree:
Overvoltage Category:
Ingress Protection:
CISPR11/CISPR22/IEC
60255-25
IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-3
IEC 61000-4-8
EN60255-5
EN60255-27
EN60255-26
EN50263
UL508
UL1053
C22.2 No. 14
ISO9001
Storage: -40C to +85C
Operating: -40C to +70C
Up to 95% (non condensing)
@ 55C (as per IEC60068-2-30
Variant 1, 6 days)
2000m (maximum)
II
II
IP10
IEC 61000-4-9
IEC 61000-4-10
IEC 61000-4-11
IEC 61000-4-17
IEC 60529
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEEE/ANSI C37.90.1
IEEE/ANSI C37.90.1
IEEE/ANSI C37.90.2
IEEE/ANSIC37.90.3
UL508
ULC22.2-14
Ordering
GPM-F
Generator Field
Voltage
*
L
H
Description
Field Low Voltage (up to 600VDC field voltage)
Field High Voltage (up to 800VDC field voltage)
Multilin Accessories
UR Applications I learning CD
TRCD-URA1-C-S-1
ML2400-F-HI-HI-A2-A2-A6-G1
Viewpoint Engineer
VPE-1
Viewpoint Maintenance
VPM-1
VP-1-61850
www.GEDigitalEnergy.com
110331-v1