Sei sulla pagina 1di 6

LOG

SHEET

Name: MUTHUKUMAR SWATHY Group: Date: GP18

Results and Discussion

Tabulation and Calculations

1. Tabulate your results under the following headings in Table 1:


2. Calculate the rates of heat removal from the evaporator Q L and
heat delivered to the condenser Q H at different water flow rates
and then determine their coefficients of performance of air
refrigerator (COPR) and heat pump (COPH) at different cooling
water msflow rates.


3. Using the data obtained in Table 1 and the calculated values from
step (2), plot

the graphs below and discuss.

(i) Heat delivered Q H (kW) to the condenser and compressor load
W
C (kW) against condenser water mass flow rate (kg/s).

(ii) Heat delivered Q H (kW) to the condenser and COPH versus
condenser water mass flow rate (kg/s).



4. Based on the data obtained for the maximum and minimum
cooling water flow
rates, plot the vapour compression cycle on P-H diagram (Fig. 5)
and compare with those based on ideal cycles. Discuss the results
obtained.





1.

Condenser water
mass flow rate, mw
Compressor
electrical power
input, WC
Absolute pressure of
condenser, PH
Absolute pressure of
evaporator, PL
HFC134a
temperature at
compressor inlet, T1
HFC134a
temperature at
compressor outlet,
T2
HFC134a
temperature of
condensed liquid,
T3
HFC134a
temperature at
expansion valve
outlet, T4
Compressor cooling
water inlet
temperature, T5
Compressor cooling
water outlet
temperature, T6
Condenser water
outlet temperature,
T7
Refrigerant mass
flow rate, m
Heat delivered to
condenser, QH
Heat removal from

unit
Kg/s x
10^-3

1
20

2
30

3
40

4
50

590

540

520

500

1451

1201

1101

1001

346

321

321

301

22.3

22.5

22.4

21.8

102.6

99.0

96.4

88.1

54.6

47.7

44.1

40.4

10.4

8.5

7.0

5.0

30.3

30.9

31.3

30.5

30.8

31.2

31.4

30.6

50.8

43.7

40.1

37.2

7.5

6.9

6.5

6.3

1672

1567.5

1454.64

1379.4

937.5

862.5

812.5

787.5

evaporator, QL
Compressor waste
41.8
37.62
16.72
20.9
heat, Qcmp
Total heat delivered,
1713.8
1605.1
1471.3
1399.9
QT
Performance of air
1.588
1.597
1.562
1.575
refrigerator COPR
Performance of heat
2.833
2.90
2.79
2.75
pump COPH
Performance of heat
2.90
2.97
2.82
2.79
pump COPH-T -


2. The values of QH , QL , COPR , COPH at different cooling water
flow rates are calculated and entered in the table above.

3. (i) QH , Wc Versus condenser water mass flow rate

heat delivered QH ,Compressor


load Wc

1800

1672
1567.5

1600

1454.5

1379.4

1400
1200
1000

Series1
Series2

800

590

600

540

520

500

Linear (Series1)
Linear (Series2)

400
200
0
0

10

20

30

40

50

60

condenser water mass Plow rate



Y axis : series 1 QH , Series 2 WC
X axis : mw



(ii) QH, COPH versus condenser water mass flow rate


1800

1672
1567.5

heat delivered QH, COPH

1600

1454.5

1379.4

1400
1200
1000

Series1

800

Series2
Linear (Series1)

600

Linear (Series2)

400
200

2.833

2.9

2.79

2.75

20

30

40

50

0
0

10

60

condenser water mass Plow rate





Y axis : series 1 QH , Series 2 COPH
X axis : mw













4. Vapor compression cycle on P-H diagram :



A difference between the real cycle and the ideal is that
temperature at which evaporation takes place is lower than the
temperature of the cold region so heat transfer can take place.
Similarly the temperature of the heat rejection must be higher
than the hot region temperature to bring about heat transfer in
the condenser.