1.0
2.0
3.0
4.0
PAGE
CONTENTS
1
INTRODUCTION
2
WARRANTY
2
REFRIGERATED DRYER
NOMENCLATURE
2
5.0
RECEIVING AND INSPECTION 3
5.1
INSPECTION
5.2
UNPACKING AND HANDLING
6.0
SAFETY AND OPERATION
PRECAUTIONS
3
7.0
PRINCIPLES OF OPERATION 5
7.1
INTRODUCTION
7.2
AIR SYSTEM
7.3
MOISTURE REMOVAL SYSTEM
7.4
REFRIGERATION SYSTEM
7.5
THERMAL MASS CIRCULATING
SYSTEM
7.6
CONTROLS
7.6.1 BASIC USER INTERFACE
7.6.2 EXCHANGER TEMPERATURE
SET POINT AND ALARMS
7.6.3 ADJUSTING SET POINTS
7.6.4 ALARMS AND
THEIR FUNCTIONS
7.6.5 ALERT MESSAGES
7.6.6 START MODES
7.6.6.1 Manual Mode
7.6.6.2 Remote Mode (Optional)
7.6.6.3 Auto Restart
CONTENTS
PAGE
8.0
INSTALLATION AND
INITIAL START-UP
8.1
LOCATION AND MOUNTING
8.2
PIPING AND VALVES
8.3
FILTRATION
8.4
ELECTRICAL CONNECTION
8.5
INITIAL START-UP
8.5.1 START- UP SEQUENCE
9.0
SCHEDULED MAINTENANCE
9.1
INTRODUCTION
9.2
REFRIGERANT CONDENSER
9.3
CONDENSATE DISCHARGE
SYSTEM
9.4
PANEL FILTER ELEMENT
9.5
PRE-FILTERS AND
POST-FILTERS
9.5.1 THREADED FILTERS
10.0 TROUBLESHOOTING
10.1 INTRODUCTION
10.2 PROBLEM / ACTION GUIDE
11.0 WIRING DIAGRAMS
12.0 GENERAL ARRANGEMENT
13.0 REPLACEMENT PARTS
14.0 ENGINEERING
SPECIFICATIONS
10
13
15
17
18
19
2.0 INTRODUCTION
Ingersoll Rand Nirvana Cycling refrigerated air dryer removes
moisture, oil vapor, and other contaminants from compressed air. These
contaminants are detrimental to pneumatically operated appliances,
controls, instruments, machinery and tools.
This removal is
accomplished by cooling the air with a refrigeration unit to a temperature
at which moisture in the air is condensed and separated from the air
stream. The temperature the air is cooled to, normally between 34 and
38F (1 and 3C), is known as dew point. This dryer can be easily
installed into various pneumatic systems in which dry air is required or
desired. Please refer to Principles of Operation for complete operating
details.
3.0 WARRANTY
The Company warrants that the equipment manufactured by it and
delivered hereunder will be free of defects in material and workmanship
for a period of twelve months from the date of placing the Equipment in
operation or eighteen months from the date of shipment from the factory,
whichever shall first occur. The Purchaser shall be obligated to promptly
report any failure to conform to this warranty, in writing to the Company
in said period, whereupon the Company shall, at its option, correct such
nonconformity, by suitable repair to such equipment or, furnish a
replacement part F.O.B. point of shipment, provided the Purchaser has
stored, installed, maintained and operated such Equipment in
accordance with good industry practices and has complied with specific
recommendations of the Company. Accessories or equipment furnished
by the Company, but manufactured by others, shall carry whatever
warranty the manufacturers have conveyed to the Company and which
can be passed on to the Purchaser. The Company shall not be liable for
any repairs, replacements, or adjustments to the Equipment or any costs
of labor performed by the Purchaser or others without Company's prior
written approval.
The effects of corrosion, erosion and normal wear and tear are
specifically excluded. Performance warranties are limited to those
specifically stated within the Company's proposal. Unless responsibility
for meeting such performance warranties are limited to specified tests,
the Company's obligation shall be to correct in the manner and for the
period of time provided above.
PREFIX
NVC
NOMINAL*
FLOW
(SCFM)
200-400
CONDENSER
TYPE
A = AIR
W = WATER
POWER
2 = 230-1-60
4 = 460-3-60
5 = 230-3-60
6 = 575-3-60
7 = 380-3-50
8 = 220-3-50
RATING
0 = NEMA 1
H = NEMA 4
* Nominal Flows indicated are for 100F inlet temperature, 100F ambient temperature and 100 psig compressed air pressure.
a WARNING
Under no circumstances should any person attempt to lift heavy
objects without proper lifting equipment (i.e., crane, hoist, slings or fork
truck). Lifting any unit without proper lifting equipment, may cause
serious injury.
OSHA
Heading Descriptions
a WARNING
Warning is used to indicate a hazardous situation which has some
probability of death or severe injury. Warning should not be considered
for property damage accidents unless personal injury risk is present.
a CAUTION
Caution is used to indicate a hazardous situation which may result in
minor or moderate injury.
a NOTICE
Notice is used to indicate a statement of company policy as the
message relates directly or indirectly to the safety of personnel or
protection of property. Notice should not be associated directly with a
hazard or hazardous situation and must not be used in place of
Danger, Warning, or Caution.
a NOTICE
The user of any air dryer manufactured by Ingersoll Rand, is hereby
warned that failure to follow the above Safety and Operation
Precautions may result in personal injury or equipment damage.
However, Ingersoll Rand does not state as fact, nor does it mean to
imply, that the preceding list of Safety and Operating Precautions is all
inclusive, and further, that the observance of this list will prevent all
personal injury or equipment damage.
2
FACTORY
WIRING
100-125VAC / 1 PH
GRN
WHT
BLK
L1
3
4
5
6
200-575VAC / 3 PH
1
2
INCOMING
LINE VOLTAGE
100-125VAC
1PH/50-60HZ
(BY OTHERS)
(REFER TO UNIT
NAMEPLATE FOR
POWER
REQUIREMENTS)
FACTORY
WIRING
GRN
3
4
BLK
L1
RED
L2
5
6
2
INCOMING
LINE VOLTAGE
200-240VAC
1PH/50-60HZ
(BY OTHERS)
(REFER TO UNIT
NAMEPLATE FOR
POWER
REQUIREMENTS)
FACTORY
WIRING
GRN
RED
L1
WHT
L2
BLK
L3
3
4
5
6
HIGH VOLTAGE
INCOMING
LINE VOLTAGE
200-575VAC
3PH/50-60HZ
(BY OTHERS)
(REFER TO UNIT
NAMEPLATE FOR
POWER
REQUIREMENTS)
The air system consists of the dryer components which are in contact
with the compressed air. Referring to Figure 1 and following the bold
AIR FLOW, hot saturated air from the compressor enters the
precooler/reheater where the air temperature is reduced prior to
entering the chiller by the cool air exiting the air/moisture separator. This
precooling allows for the use of a smaller refrigeration system. The air
then goes into the chiller section where it is further cooled to the desired
dew point by a thermal mass fluid. The temperature of the thermal mass
fluid is maintained by the refrigeration circuit and controls. The air
continues to the separator where moisture is removed, thereby, allowing
the cool, dry air to return back to the precooler/reheater to be heated by
the incoming moist hot air. The air exiting the reheater portion of the
dryer should be approximately 15- 20F lower than the inlet air
temperature based on standard conditions at full rated flow.
FLOW DIAGRAM
FIGURE 1
7.3 MOISTURE REMOVAL SYSTEM
Ingersoll Rand condensate drains discharge condensed moisture and
lubricants (condensate) from compressed air equipment. The
condensate drain operates as a zero-air-loss drain, returning air that is
displaced in the drain bowl back into the compressed air system.
Consistent discharging of condensate from compressed air equipment
is essential for proper equipment operation and performance.
The condensate drain uses a unique sensing method to determine the
level of condensate in the drain bowl. A transducer located in the drain
bowl continuously sends out a signal 50 times per second. Once the
transducer determines that the level of condensate has reached a
predetermined level within the drain bowl, a signal is sent to the no-loss
drain valve to open. This operation permits removal of condensate of up
to 80 gallons per hour.
The drain also features a test button that permits manual operation of
the no-loss drain valve. Depressing the test button illuminates the LED
and energizes the solenoid valve. The LED illuminates to indicate
"POWER ON" and goes off when the no-loss drain valve is operated by
the transducer or manual test button.
PROCESS AND
INSTRUMENTATION
DIAGRAM
NVC200-400
AIR AND
WATERCOOLED
the liquid level and passes a signal to the electronic control as soon as
the container is filled. The pilot valve is then activated and the
diaphragm opens the outlet line for discharging the condensate. When
the drain unit has been emptied, the outlet line is closed again quickly
and tightly without wasting compressed air."
7.4 REFRIGERATION SYSTEM
The Refrigeration System consists of all the components which handle
R-404A. This is a hermetically sealed closed-loop system. Referring to
Figure 1 and following the phantom REFRIG(R-404A) FLOW, refrigerant
is shown leaving the evaporator section where, in the process of
removing heat, it is changed from a low pressure liquid into a low
pressure gas. This gas enters the suction side of the compressor where
it is compressed into a high pressure gas. The high pressure gas is
cooled in the condenser section until it becomes a high pressure liquid.
It then goes through a permanent filter dryer that ensures the
refrigeration system is free of contaminants. A small diameter capillary
tube (expansion valve on water-cooled dryers) meters the refrigerant for
introduction into the evaporator. The refrigerant pressure is reduced
upon entering the evaporator where as it evaporates, removes heat from
the thermal mass fluid.
The condensate flows through the feed line into the drain unit and
accumulates in the container. A capacitive sensor continuously registers
Nirvana Cycling Refrigerated Dryer Models 200-400
http://air.irco.com
7.6.1
7.6 CONTROLS
The Ingersoll Rand NVC200-400 Series dryers incorporate automatic
controls for proper operation. The thermal mass fluid temperature is
maintained by a microprocessor control that monitors the temperature
and cycles the refrigeration system in response to varying air flow and
temperature. Upon an increase in the temperature of the thermal mass
fluid, the refrigeration compressor is cycled on. When the fluid is cooled
to two deg.F below its control set point, the refrigerant compressor is
cycled off. The thermal mass fluid functions as a thermal storage mass
in the NVC Series dryer.
A low pressure cut out (LPCO) switch is provided for all NVC series
dryers. This switch is factory set to open at 20 psig. If the refrigerant
suction pressure draws below 20 psig, the LPCO opens to shut off the
refrigerant compressor. Once the switch has opened, it will prevent the
compressor from running until the suction pressure rises above 60 psig
and the LPCO has been manually reset.
All water cooled units come with a high pressure cut out (HPCO) switch.
This switch is set to open at 320 psig and close at 270 psig. To
compensate for water temperature variation, it may be necessary to
adjust the water regulating valve to maintain a 250 psig discharge
pressure. Adjustment can be done by rotating the adjusting screw
counterclockwise for an increase in discharge pressure. For conditions
where low water temperature and/or high water pressure are expected
it is advisable to install a water pressure regulator ahead of the
condenser.
BUTTONS
ON / OFF
Toggles the dryer operation between "On Line" and Off Line status;
Energizes glycol pump. Note that the refrigeration system will operate based
on temperature.
EXCH SET
When depressed, will display the current exchanger set point in the LCD
window. While the exchanger set point is displayed, the up and down arrows
may be used to increase or decrease the exchanger set point temperature.
ALARM RESET
Pressing once clears the local alarm indication and de-energizes the remote
alarm contact. Should the alarm condition persist, the alarm will return after
the alarm inhibit time has expired.
% SAVINGS
Depressing once changes LCD display to indicate ratio of refrigeration system
running time vs. total dryer ON time.
F / C
Toggles the LED temperature indicators between Fahrenheit and Celsius units
of measure.
+/Allows user to modify set point values. Set point values cycle through a fixed
range.
LIGHTS
LCD Display
Displays exchanger temperature during normal operation. Also used to
display exchanger temperature set point, alarm condition and timing functions.
ADJUSTMENT
SCREW
SYSTEM ENERGIZED
Indicates when power is applied to unit.
DRYER ON
Illuminated when the On/Off switch has been pressed to place the unit in
operation. The refrigerant system may start at any time when the light is on.
REFRIGERATION COMPRESSOR ON
Indicates that the refrigeration system is operating.
FIGURE 2
WATER REGULATING VALVE
DEGREES F / DEGREES C
Indicates the temperature units of measure.
HIGH TEMP ALARM
Indicates that the exchanger temperature has risen to 10F or 5C above the
exchanger temperature set point.
LOW TEMP ALARM
When activated, indicates that the exchanger temperature has dropped below
29F or -2C. This condition stops the compressor. The compressor will not
restart until the temperature has risen two degrees above exchanger set point.
7.6.3
36
EXCH.
SET
ALERT MESSAGES
37
Pressing the UP or DOWN arrows modifies the EXCHANGER
SETPOINT in one degree increment.
PF
38
Pressing the UP or DOWN arrows modifies the EXCHANGER
SETPOINT in one degree increment.
38
a CAUTION
Do not set the Exchanger Temperature greater than 50 deg.F. Running
dryer at an Exchanger Temperature higher than 50 deg.F may damage
refrigeration system.
7.6.4
Alarm
HIGH TEMPERATURE
ALARM
LOW TEMPERATURE
ALARM
Display
HI TEMP ALARM
EXCH SETPOINT + 10 F
cd
7.6.6
The Controller accepts the last setpoint. After 5 seconds, the readout
will return to displaying the current Exchanger Temperature.
28 F
START MODES
The NCV200-400 dryers are capable of starting in one of the
following start modes:
7.6.6.1
Manual Mode
Auto Restart
Should the dryer lose power while in the "On" mode, the dryer
will revert to the "On" mode once power is restored. Similarly,
should power be removed from the dryer while the dryer is in
the "Off" mode, the dryer will remain in the "Off" mode once
power is restored until the On/Off switch is depressed or the
remote switch is closed.
a NOTICE
Failure to comply to the above instructions may result in equipment
malfunction and will void warranty.
a NOTICE
FILTRATION
AIR
DRYER
B
AIR IN
C
AIR OUT
PRE-FILTER
PREFILTER
DRAIN
VALVE
CHECK
VALVE
DRAIN
VALVE
CHECK
VALVE
CHECK
VALVE
OIL
SEPARATOR
CHECK
VALVE
UNIT AS DELIVERED
OPTIONAL ACCESSORY ITEMS
NOTE:
FIGURE 3
TYPICAL PIPING ARRANGEMENT
8.4
8.5
ELECTRICAL CONNECTION
INITIAL START-UP
a NOTICE
For water cooled models, the water valve must be manually opened to
ensure that the condenser is full of water prior to start-up.
8.5.1
START- UP SEQUENCE
Apply power to dryer. LCD Panel will illuminate. The AntiShort Cycle delay will commence counting down.
a NOTICE
a CAUTION
Never wire directly or connect any additional wires to the compressor
junction box. This will cause severe system malfunction.
a WARNING
1
Before drain maintenance work, always close the drain isolation ball
valves and ensure that the device is pressureless and de-energized.
Maintenance recommendations
2
1
or
by undoing screws (8) at intermediate adapter (9)
which is then detached from the service unit by
downward movement.
6
7
8
10
9
9
10
Open drain isolation ball valve. Press drain test button to verify proper
drain operation.
2
4
2
6
Check if service unit (3) matches control unit (1) (type designation and
colour of latching hook)
Fit latching hook (6) of control unit (1) into sensor tube
plate (5).
Press control unit (1) against service unit (3) and snap
into place
Open drain isolation ball valve. Press drain test button to verify proper
drain operation.
a WARNING
Depressurize the system before disassembling filters. Failure to do so
may result in injury or death.
AC 19-1380
10,000
`
hrs
1,000
THREADED FILTERS:
20
(68)
30
(86)
40
(104)
50 C
(122) F
9.5.1
11
2
1
3a
3b
1
1
1
6
4
7
3
2
1
2
16mm
(5/8)
12
10.0 TROUBLESHOOTING
10.1 INTRODUCTION
Ingersoll Rand Nirvana Cycling dryers are designed for reliable, trouble-free operation. In the event of any dryer malfunction, the guide below
has been developed to facilitate problem identification and corrective actions.
a WARNING
a WARNING
Prior to working on the unit, make sure that all circuit breakers or
disconnected switches are tagged Out of Service.
PROBLEM
Moisture down stream
SYMPTOM(S)
Dryer is properly cooling air
stream (Check Chiller. Temp
on controller)
POSSIBLE CAUSE
CORRECTIVE ACTION
Excessive flow
Refrigerant leak
Defective Pump
13
10.0 TROUBLESHOOTING
PROBLEM
Apparent controller display
malfunction
SYMPTOM(S)
Display Blank
POSSIBLE CAUSE
CORRECTIVE ACTION
Blown Fuse
Check Fuses
Board Failure
Unrealistic temperature
displayed
Erratic or inaccurate
temperature readings
Defective probe
Replace probe
Unrealistic pressure
displayed
Replace transducer
High pressure drop across
dryer
Problem persists
Open valves
CONNECTIONS
DRAIN SV (SV)
BY OTHERS
208-230 VAC/1PH/60HZ
200-220 VAC/1PH/50HZ
5A/120VAC MAX
WHT
RED
TB-1
L3
L1
L2
BLK
J1
CUSTOMER
CONNECTIONS
24VAC
BLK
BLK
GRN
GRN
BLK
J4
SENSORS
J5
TEMPERATURE
PROBE
TO EXCHANGER
THERMOWELL
SHIELDED PAIR
GRND SCREW
1. CUSTOMER POWER HOOK UP AT THE TERMINAL STRIP IN THE ELECTRICAL CONNECTION BOX IN THE
NOTES:
CUSTOMER SUPPLIED
REMOTE START/STOP
SWITCH
COMPR HOT
COMPR
POWER
N
H
MICROPROCESSOR BOARD
DRAIN/PUMP HOT
DRAIN TIMER
RED
RED
PUMP/DRAIN
ALARM HOT
ALARM
RED
RED
YELLOW
YELLOW
CR1
TS-3
WHT
3
TS-2
YEL
1
YEL
ELEC. PLUG
RED
WHT
RED
RED
WHT
WHT
L1
PUMP (PM)
RED
H3
H2
RED
RED
GND
GRN
HIGH PRESS
CUT OUT SW.
SEE NOTE 2.
GRN
XFMR1
TRANSFORMER
HPCO
H1
CONNECTIONS
WHT
GRN
WHT
WHT
WHT
WHT
WHT
RED
200VAC THRU
240VAC
CONNECTION
380VAC THRU
480VAC
CONNECTION
GROUND
LUG
SIDE
(TYPICAL)
GRN
BLK
BLK
GRN
GRN
GRN
115V
200V
THRU
480V
SIDE
GROMMETED
HOLES IN
ELECTRICAL
COMPARTMENT
H4
RED
RED
FAN
BLK
* SEE NOTE 3
BLK
BLK
BLK
RED
WHT
RED
RED
C
R
COMP
BLK
GND
RED
BLK
WHT
RED
LPCO
LOW PRESS
CUT OUT SW.
(C1)
ENCLOSURE
550037
230/1/60, 220/1/50
RUN
WIRING DIAGRAM
NVC200 AIR AND
WATERCOOLED
WIRING DIAGRAM
NVC200220/1/50
AIR AND WATERCOOLED
230/1/60,
BLK
FU2
START
COMPRESSOR
RELAY AND
CAPACITOR
FU1
PRIMARY
FUSES
CONTACTOR
BLK
BLK
XFMR SECONDARY
FUSE - FU3-250V
RED
RED
D
N
U
RO
G
OL
COMPRESSOR
CONNECTIONS
230V/1PH/60HZ
GRN
L1
BLK
15
CONNECTIONS
DRAIN SV (SV)
BY OTHERS
230-575 VAC/3PH/60HZ
200-440 VAC/3PH/50HZ
5A/120VAC MAX
WHT
TS-1
BLK
BLK
L3
BLK
GRN
GRN
L2
BLK
J1
BLK
J4
J5
GRND SCREW
SENSORS
L1
TERM STRIP
CUSTOMER
CONNECTIONS
RED
24VAC
CUSTOMER.
AUTOTRANSFORMER. NOTE: MAIN INCOMING POWER DISCONNECT AND FUSING WILL BE PROVIDED BY
4. FOR CONNECTION TO 575V/3PH SYSTEMS, SWAP BOXES ABOVE RIGHT TO INCLUDE 575V TO 460V
1. CUSTOMER POWER HOOK UP AT THE TERMINAL STRIP IN THE ELECTRICAL CONNECTION BOX IN THE
NOTES:
CUSTOMER SUPPLIED
REMOTE START/STOP
SWITCH
COMPR HOT
COMPR
POWER
N
H
MICROPROCESSOR BOARD
DRAIN/PUMP HOT
DRAIN TIMER
PUMP/DRAIN
RED
RED
ALARM HOT
ALARM
RED
RED
YELLOW
YELLOW
L3
L2
L1
460V/3PH CONNECTION
CR1
575V
L3
L2
L1
X1
X3
XFMR 2
XFMR 1
X3
X1
X2
X4
H1
H1
H4
H4
X4
X2
H2
H3
H3
H2
TEMPERATURE
PROBE
TO EXCHANGER
THERMOWELL
SHIELDED PAIR
L3A
L2A
L1A
* SEE NOTE 4
460V
* SEE NOTE 4
TS-3
WHT
3
TS-2
YEL
1
YEL
ELEC. PLUG
RED
WHT
RED
RED
WHT
16
WHT
L1
RED
H3
H2
RED
RED
GND
GRN
HIGH PRESS
CUT OUT SW.
SEE NOTE 2.
GRN
XFMR1
TRANSFORMER
HPCO
H1
CONNECTIONS
PUMP (PM)
GRN
WHT
WHT
WHT
WHT
WHT
RED
200VAC THRU
240VAC
CONNECTION
380VAC THRU
480VAC
CONNECTION
GROUND
LUG
SIDE
RED
GRN
BLK
BLK
RED
WHT
RED
FAN
BLK
* SEE NOTE 3
BLK
BLK
BLK
L2
BLK
200-240V/3PH/50-60HZ
380-480V/3PH/50-60 HZ
GROUND
GRN
L1
L3
LOW PRESS
CUT OUT SW.
LPCO
FU1
PRIMARY
FUSES
BLK
FU2
CONNECTIONS
COMPRESSOR
(CM)
(C1)
CONTACTOR
BLK
BLK
XFMR SECONDARY
FUSE - FU3-250V
RED
RED
550031
WIRING DIAGRAM
NVC200-400 AIR AND WATERCOOLED
WIRING DIAGRAM
NVC200-400 AIR AND WATERCOOLED
208-575V/3PH/60HZ,
200-440V/3PH/50HZ
208-575V/3PH/60HZ, 200-440V/3PH/50HZ
(TYPICAL)
GRN
GRN
GRN
115V
200V
THRU
480V
SIDE
GROMMETED
HOLES IN
ELECTRICAL
COMPARTMENT
H4
RED
RED
CUSTOMER ELECTRICAL
CONNECTIONS ACCESS
REAR VIEW
OUTFLOW VALVE
ADJUSTMENT
ACCESS
2.50
51.19
57.75
25.00
30.38
32.56
23.38
28.12
FRONT VIEW
2.38
TOP VIEW
55.25
550030
CONTROL PANEL
GENERAL ARRANGEMENT
NVC200-400
AIR AND WATERCOOLED
CONDENSATE DRAIN
MICROPROCESSOR CONTROL
(SEE TECHNICAL MANUAL FOR
OPERATION DETAILS)
17
DESCRIPTION
SPARES
UNIT
38052197
BOARD, CONTROL
38052718
CONTACTOR, COMPRESSOR
22719421
DRAIN, CONDENSATE
38448239
38052916
38052437
38054268
38052361
38052676
38052908
38052171
38053252
38052148
VALVE, DRAIN
38052320
Spare. Quantities under this heading reflect the number of each item which we recommend be kept on hand for maintenance or repair.
The appropriate quantity for your application will depend on how critical interruptions in service are to your operation.
Class
Quantity
Minimum
Suggested for
Domestic service where interruptions in service are acceptable.
Average
Maximum Export service or for domestic service where interruptions in service are unacceptable.
NEMA 1
NEMA 4
NEMA 1
NEMA 4
MODEL
CONDENSERS
230V
230V
460V
460V
200
38053104
38053229
3854789
38446498
38446498
300
38052700
38053229
3854789
38446498
38446498
400
38052700
38053229
3854789
38446498
38446498
CONDENSERS
VALVES
200
38054581
38054623
300
38450029
38054631
400
38450029
38054631
COMPRESSORS
NVC
18
MODEL
230/1/60
230/3/60
230/3/50
380/3/50
460/3/60
575/3/60
200
38446746
38054649
38054672
38450003
38450003
38450003
300
38054656
38054680
38052288
38052270
38052270
400
38054664
38054698
38054706
38052288
38052288
R-404A
VOLTS/PH/HZ
LBS.
KG.
LB-OZ
KG.
NVC200
230/1/60
540
245
2-4
1.02
20
NVC200
460/3/60
540
245
2-4
1.02
NVC200
230/3/60
540
245
2-4
NVC200
575/3/60
540
245
2-4
NVC250
460/3/60
570
259
3-8
NVC250
230/3/60
570
259
3-8
NVC250
575/3/60
570
259
NVC300
460/3/60
630
NVC300
230/3/60
630
NVC300
575/3/60
NVC400
NVC400
NVC400
COMPRESSOR RATINGS
FAN RATINGS
HP
RLA
LRA
QTY
HP
RLA
13.7
9.7
40
1/6
LRA
3
3.9
2.4
13
1/6
0.5
1.2
1.02
12
7.7
4.8
25
1/6
1.02
3.0
2.4
13
1/6
0.5
1.2
1.588
5.3
11/2
3.6
16
1/6
0.5
1.2
1.588
15
9.6
11/2
6.4
38
1/6
3-8
1.588
4.3
11/2
3.6
16
1/6
0.5
1.2
286
4-0
1.814
10
6.2
4.3
16
1/6
0.5
1.2
286
4-0
1.814
18
11.5
7.9
38
1/6
630
286
4-0
1.814
4.9
4.3
16
1/6
0.5
1.2
460/3/60
670
304
4-0
1.814
12
7.6
2 1/2
5.4
23
1/6
0.5
1.2
230/3/60
670
304
4-0
1.814
25
15.9
2 1/2
11.4
57
1/6
575/3/60
670
304
4-0
1.814
10
6.0
2 1/2
5.4
23
1/6
0.5
1.2
a NOTICE
Specification information above accurate at time of publication. Refer to equipment serial label
for actual refrigerant charges and specifications for units.
19
C.C.N.
FECHA
MOD.
: 80442775
: ABRIL DE 2007
:B
NDICE
NDICE
PGINA
1.0
2.0
3.0
4.0
NDICE
1
INTRODUCCIN
2
GARANTA
2
NOMENCLATURA DE LA
SECADORA REFRIGERANTE 2
5.0
RECEPCIN E INSPECCIN
3
5.1
INSPECCIN
5.2
DESEMBALAJE Y MANIPULACIN
6.0
PRECAUCIONES DE
SEGURIDAD Y OPERACIN
3
7.0
PRINCIPIOS DE
FUNCIONAMIENTO
5
7.1
INTRODUCCIN
7.2
SISTEMA DE AIRE
7.3
SISTEMA DE ELIMINACIN
DE LA HUMEDAD
7.4
SISTEMA DE REFRIGERACIN
7.5
SISTEMA DE CIRCULACIN
DE MASA TRMICA
7.6
CONTROLES
7.6.1 INTERFAZ DE USUARIO BSICA
7.6.2 PUNTO DE REFERENCIA Y
ALARMAS DE TEMPERATURA
DEL INTERCAMBIADOR
7.6.3 AJUSTE DE LOS PUNTOS
DE REFERENCIA
7.6.4 ALARMAS Y SUS FUNCIONES
7.6.5 MENSAJES DE ALERTA
7.6.6 MODOS DE INICIO
7.6.6.1 Modo manual
7.6.6.2 Modo remoto (opcional)
7.6.6.3 Reinicio automtico
NDICE
PGINA
8.0
INSTALACIN Y PUESTA
EN MARCHA INICIAL
8.1
UBICACIN E INSTALACIN
8.2
TUBERAS Y VLVULAS
8.3
FILTRACIN
8.4
CONEXIN ELCTRICA
8.5
PUESTA EN MARCHA INICIAL
8.5.1 SECUENCIA DE PUESTA
EN MARCHA
9.0
MANTENIMIENTO
PROGRAMADO
9.1
INTRODUCCIN
9.2
CONDENSADOR
DEL REFRIGERANTE
9.3
SISTEMA DE DESCARGA
DE CONDENSADO
9.4
ELEMENTO DE FILTRO
DEL PANEL
9.5
PREFILTROS Y POSTFILTROS
9.5.1 FILTROS ROSCADOS
10.0 LOCALIZACIN DE FALLAS
10.1 INTRODUCCIN
10.2 GUA DE PROBLEMAS/
MEDIDAS
11.0 DIAGRAMAS DE CABLEADO
12.0 DISPOSICIN GENERAL
13.0 PIEZAS DE REPUESTO
14.0 ESPECIFICACIONES
DE INGENIERA
10
13
15
17
18
19
2.0 INTRODUCCIN
La secadora de aire refrigerante Nirvana Cycling de Ingersoll Rand
elimina la humedad, el vapor de aceite y otros contaminantes del aire
comprimido. Estos contaminantes provocan efectos adversos en los
aparatos, controles, instrumentos, mquinas y herramientas operados
neumticamente. Esta eliminacin se logra mediante el enfriamiento del
aire con una unidad de refrigeracin a una temperatura a la que la
3.0 GARANTA
Ingersoll-Rand Company Limited garantiza que los equipos que fabrica
y distribuye conforme a este documento estarn libres de defectos tanto
de materiales como de mano de obra, durante un perodo de doce
meses desde la fecha en que los Equipos se ponen en funcionamiento
o de dieciocho meses desde la fecha de envo desde la fbrica, lo que
suceda primero. El Comprador estar obligado a informar
oportunamente y por escrito a la Compaa de cualquier tipo de
incumplimiento de las condiciones de esta garanta dentro de dicho
perodo, y la Compaa corregir, a su discrecin, dicho incumplimiento
reparando el equipo en forma apropiada, o proporcionar una pieza de
repuesto F.O.B. en el punto de embarque, siempre y cuando el
Comprador haya almacenado, instalado, mantenido y operado dichos
Equipos en conformidad con las buenas prcticas industriales y haya
cumplido con las recomendaciones especficas de la Compaa. Los
accesorios o equipos que proporcione la Compaa pero que fabriquen
terceros, mantendrn cualquier garanta que los fabricantes hayan
traspasado a la Compaa y que se pueda transferir al Comprador. La
Compaa no ser responsable de reparaciones, reemplazos o ajustes
a los Equipos ni de ningn tipo de costo por mano de obra en que
incurra el Comprador u otras personas que no cuenten con la previa
autorizacin por escrito de la Compaa.
Se excluyen especficamente de esta garanta los efectos de la
corrosin, erosin y del desgaste normal. Las garantas de
cumplimiento se encuentran limitadas a las que se indican
especficamente dentro de la propuesta de la Compaa. A menos que
la responsabilidad de cumplir tales garantas de rendimiento se
PREFIJO
NVC
FLUJO
NOMINAL *
(SCFM)
200-400
TIPO DE
CONDENSADOR
A = AIRE
W = AGUA
ENERGA
2 = 230-1-60
4 = 460-3-60
5 = 230-3-60
6 = 575-3-60
7 = 380-3-50
8 = 220-3-50
CLASIFICACIN
0 = NEMA 1
H = NEMA 4
* Los flujos nominales que se indican son para una temperatura de entrada de 100 F, una temperatura ambiente de 100 F y una presin de
aire comprimido de 100 psig.
a ADVERTENCIA
Ninguna persona debe tratar de levantar objetos pesados sin los
equipos adecuados para este fin (es decir, gras, montacargas,
eslingas u horquillas elevadoras) bajo ninguna circunstancia. El
levantamiento de cualquier unidad sin los equipos adecuados puede
causar lesiones graves.
OSHA
Descripciones del encabezado
a ADVERTENCIA
"Advertencia" se usa para indicar una situacin peligrosa con alguna
probabilidad de muerte o lesin grave. Advertencia no debe
considerarse para accidentes que provoquen daos a la propiedad, a
menos que exista riesgo de lesin personal.
a PRECAUCION
"Precaucin" se usa para indicar una situacin peligrosa que puede
provocar lesiones menores o moderadas.
a AVISO
"Aviso" se usa para indicar una declaracin de la poltica de la
compaa, si el mensaje tiene relacin directa o indirecta con la
seguridad del personal, o la proteccin de la propiedad. Aviso no se
debe asociar directamente con un peligro o una situacin peligrosa y
no se debe usar en lugar de "Peligro", "Advertencia" o "Precaucin".
a AVISO
Por medio de este documento se le advierte al usuario de cualquier
secadora de aire fabricada por Ingersoll Rand que el incumplimiento
de las Precauciones de seguridad y operacin anteriores puede
provocar lesiones personales o daos a los equipos. Sin embargo,
Ingersoll Rand no declara como hecho ni pretende implicar que la lista
anterior de Precauciones de seguridad y operacin sea exhaustiva, ni
tampoco que su cumplimiento evitar todas las lesiones personales y
los daos a los equipos.
ADVERTENCIA
ADVERTENCIA
CAJA DE CONEXIONES ELCTRICAS
CONTIENE ALTO VOLTAJE
Corte la energa y bloquee TODAS las fuentes antes de abrirla
para realizar mantenimiento.
El cableado de contacto de la alarma remota posee control
de encendido de una fuente separada.
200-240 V CA/1 PH
2
CABLEADO
DE FBRICA
VERDE
BLANCO N
NEGRO L1
3
4
5
6
VOLTAJE
DE LNEA
DE ENTRADA
100 a 125 V CA
1 PH/50 a 60 HZ CABLEADO
(DE TERCEROS) DE FBRICA
(CONSULTE
LA PLACA DE
IDENTIFICACIN
PARA CONOCER
LOS REQUISITOS
DE POTENCIA)
2
VERDE
3
4
NEGRO L1
ROJO
L2
5
6
VOLTAJE
DE LNEA
DE ENTRADA
200 a 240 V CA
1 PH/50 a 60 HZ CABLEADO
(DE TERCEROS) DE FBRICA
(CONSULTE
LA PLACA DE
IDENTIFICACIN
PARA CONOCER
LOS REQUISITOS
DE POTENCIA)
200-575 V CA/3 PH
1
2
VERDE
ROJO
L1
BLANCO L2
NEGRO
L3
3
4
5
6
VOLTAJE
DE LNEA
DE ENTRADA
200 a 575 V CA
3 PH/50 a 60 HZ
(DE TERCEROS)
(CONSULTE
LA PLACA DE
IDENTIFICACIN
PARA CONOCER
LOS REQUISITOS
DE POTENCIA)
ADVERTENCIA
ADVERTENCIA
ADVERTENCIA
EL VENTILADOR SE PUEDE
ENCENDER AUTOMTICAMENTE
EN CUALQUIER MOMENTO
ADVERTENCIA
Esta unidad est cargada
con refrigerante bajo alta presin.
ADVERTENCIA
ALTO VOLTAJE
DIAGRAMA DE FLUJO
FIGURA 1
7.3 SISTEMA DE ELIMINACIN DE LA HUMEDAD
Los drenajes de condensado Ingersoll Rand descargan humedad
condensada y lubricantes (condensado) de compresores de aire. El
drenaje de condensado funciona como un drenaje de cero prdida de
aire, lo que devuelve el aire que se desplaza en el recipiente de drenaje
al sistema de aire comprimido. La descarga adecuada del condensado
de los compresores de aire es esencial para el funcionamiento y
rendimiento correcto del equipo.
El drenaje de condensado usa un mtodo de deteccin exclusivo para
determinar el nivel de condensado en el recipiente de drenaje. Un
transductor que se ubica en el recipiente de drenaje enva
constantemente una seal 50 veces por segundo. Luego de que el
transductor determine que el nivel de condensado ha alcanzado un
nivel predeterminado dentro del recipiente de drenaje, se enva una
seal a la vlvula de drenaje sin prdidas para que se abra. Este
proceso permite la eliminacin de condensado en hasta 80 galones por
hora.
El drenaje tambin cuenta con un botn de prueba que permite la
operacin manual de la vlvula de drenaje sin prdidas. Al presionar el
botn de prueba se enciende el LED y se activa la vlvula solenoide. El
LED se enciende para indicar "ENCENDIDO" y se apaga cuando la
vlvula de drenaje sin prdidas se acciona mediante el transductor o el
botn de prueba manual.
DIAGRAMA DE
PROCESOS E
INSTRUMENTACIN
NVC200-400
ENFRIADO POR
AIRE Y AGUA
7.6.1
BOTONES
ON / OFF (Encendido/Apagado)
Alterna el funcionamiento de la secadora entre los estados "en lnea" y "fuera
de lnea"; activa la bomba de glicol. Observe que el sistema de refrigeracin
funcionar basndose en la temperatura.
EXCH SET (Punto de referencia del intercambiador)
Cuando se presiona, mostrar el punto de referencia actual del
intercambiador en la ventana LCD. Mientras se muestre el punto de
referencia del intercambiador, las flechas hacia arriba y hacia abajo se
pueden usar para aumentar o disminuir la temperatura del punto de referencia
del intercambiador.
ALARM RESET (Reinicio de la alarma)
Si se presiona una vez, elimina la indicacin de alarma local y desactiva el
contacto de la alarma remota. Si la condicin de alarma persiste, la alarma
volver a aparecer luego de que expire el tiempo de inhibicin de la alarma.
% SAVINGS (% de ahorro)
Si se presiona una vez, cambia la visualizacin del LCD para indicar la
relacin del tiempo de funcionamiento del sistema de refrigeracin con el
tiempo de encendido total de la secadora.
F / C
Alterna los indicadores de temperatura del LED entre unidades de medida
Fahrenheit y Celsius.
+/Permiten que el usuario modifique los valores de punto de referencia. Los
valores de punto de referencia varan dentro de un rango fijo.
LUCES
Pantalla LCD
Muestra la temperatura del intercambiador durante el funcionamiento normal.
Tambin se usa para mostrar el punto de referencia de temperatura del
intercambiador, la condicin de alarma y las funciones de sincronizacin.
SYSTEM ENERGIZED (Sistema activado)
Indica que se alimenta energa a la unidad.
DRYER ON (Secadora encendida)
Se enciende cuando se ha presionado el interruptor de encendido/apagado
para poner la unidad en funcionamiento. El sistema refrigerante se puede
iniciar en cualquier momento cuando la luz est encendida.
TORNILLO
DE AJUSTE
FIGURA 2
VLVULA DE REGULACIN
DE AGUA
7.6.3
36
EXCH.
SET
37
Si se presionan las flechas HACIA ARRIBA o HACIA ABAJO se
modifica el PUNTO DE REFERENCIA DEL INTERCAMBIADOR en
incrementos de un grado.
38
Si se presionan las flechas HACIA ARRIBA o HACIA ABAJO se
modifica el PUNTO DE REFERENCIA DEL INTERCAMBIADOR en
incrementos de un grado.
a PRECAUCION
No ajuste la temperatura del intercambiador a ms de 50 grados F. Si
se hace funcionar la secadora con una temperatura del intercambiador
mayor que 50 grados F puede daar el sistema de refrigeracin.
ALARMAS Y SUS FUNCIONES
El controlador indica las alarmas crticas que deben alertar al
usuario de una condicin fuera de tolerancia. Luego de que
se detecte cada condicin de alarma, se encender el
indicador LED correspondiente y se cerrar el contacto de la
alarma remota.
ALARMA DE ALTA
TEMPERATURA
ALARMA DE BAJA
TEMPERATURA
Pantalla
HI TEMP ALARM
cd
MODOS DE INICIO
Las secadoras NCV200-400 tienen la capacidad de arrancar
en uno de los siguientes modos de inicio:
Alarma
PF
7.6.6
38
7.6.4
MENSAJES DE ALERTA
28 F
7.6.6.1
Modo manual
Reinicio automtico
a AVISO
El incumplimiento de las instrucciones anteriores puede ocasionar el
mal funcionamiento del equipo y anular la garanta.
a AVISO
FILTRACIN
SECADORA
AIR
DE AIRE
DRYER
B
ENTRADA
AIR IN DE AIRE
C
SALIDA
DE AIRE
AIR
OUT
PREFILTRO
PREFILTER
VLVULA
VLVULA
DRAIN
DE
VALVE
DRENAJE
DRAIN
DE
VALVE
DRENAJE
VLVULA
CHECKDE
RETENCIN
VALVE
VLVULA
CHECKDE
RETENCIN
VALVE
VLVULA
CHECK DE
RETENCIN
VALVE
SEPARADOR
OIL
DE ACEITE
SEPARATOR
VLVULA
CHECKDE
RETENCIN
VALVE
UNIT
AS
DELIVERED
UNIDAD
TAL
COMO SE ENTREG
ELEMENTOS ACCESSORY
ACCESORIOS OPCIONALES
OPTIONAL
ITEMS
NOTA:
EL TUBO DE DRENAJE NO SE DEBE ELEVAR NI CONECTAR A UNA TUBERA
NOTE:
DRAIN TUBE MUST NOT RISE OR BE CONNECTED TO
EXCESIVAMENTE LARGA, YA QUE PUEDE CREAR CONTRAPRESIN SE REQUIERE UNA
EXCESSIVELY
PIPE
WHICH
CONEXIN
PARA ABRIR ELLONG
DESAGE
DEL
PISO MAY CREATE BACK PRESSURE
FIGURA 3
DISPOSICIN TPICA DE LAS TUBERAS
8.4
8.5
CONEXIN ELCTRICA
a PRECAUCION
a AVISO
Para los modelos enfriados por agua, la vlvula de agua se debe abrir
manualmente para asegurarse de que el condensador est lleno de
agua antes de la puesta en marcha.
8.5.1
a AVISO
a ADVERTENCIA
1
2
1
7
10
o
quitando los tornillos (8) en el adaptador intermedio (9)
la que luego se separa de la unidad de servicio mediante
movimiento descendente.
6
7
9
Abra la vlvula de bola de aislamiento del drenaje. Presione el botn
de prueba del drenaje para verificar el funcionamiento correcto del
drenaje.
10
2
4
2
6
a ADVERTENCIA
Despresurice el sistema antes de desmontar los filtros. De lo
contrario, se pueden provocar lesiones o la muerte.
10,000
`
hrs
1,000
FILTROS ROSCADOS
20
(68)
30
(86)
40
(104)
50 C
(122) F
9.5.1
AC 19-1380
11
2
1
3a
3b
1
1
1
6
4
7
3
2
1
2
16mm
(5/8)
12
a ADVERTENCIA
a ADVERTENCIA
PROBLEMA
SNTOMAS
CAUSA POSIBLE
MEDIDA CORRECTIVA
Filtracin de refrigerante.
No funciona el compresor y
funciona el ventilador.
13
SNTOMAS
Pantalla en blanco.
Se muestra una
temperatura poco realista.
CAUSA POSIBLE
Fusible fundido.
Sonda defectuosa.
Reemplace la sonda.
La presin de salida es
sustancialmente ms baja
que la presin de entrada.
La temperatura de
funcionamiento del sistema
es mayor que 32 F.
La presin de salida es
sustancialmente ms baja
que la presin de entrada.
La temperatura de
funcionamiento del sistema
es menor que 32 F.
El rel/contactor del
compresor est atascado.
Reemplace el rel/contactor.
Reemplace el rel.
La sonda no se encuentra
completamente en el pozo
trmico.
Persiste el problema.
MEDIDA CORRECTIVA
Reemplace el transductor.
No se activa el drenaje de
condensado.
El dimetro interno de la
Reemplcela con una tubera de mayor
tubera de entrada/salida es
dimetro.
demasiado pequeo, lo que
provoca que se bloquee el aire
o que haya contrapresin.
El uso excesivo de
curvaturas/codos en las
tuberas de entrada/salida
produce bloqueo del
aire/contrapresin.
La tubera de salida es
Vuelva a configurar la tubera de
demasiado larga/demasiado alta, condensado.
lo que produce contrapresin.
Ms de una fuente de
condensado est conectada, lo
que proporciona una ruta
alternativa para el condensado.
El LED de drenaje de
condensado est apagado.
CONNECTIONS
DRAIN SV (SV)
BY OTHERS
208-230 VAC/1PH/60HZ
200-220 VAC/1PH/50HZ
5A/120VAC MAX
WHT
RED
TB-1
L3
L1
L2
BLK
J1
CUSTOMER
CONNECTIONS
24VAC
BLK
BLK
GRN
GRN
BLK
J4
SENSORS
J5
TEMPERATURE
PROBE
TO EXCHANGER
THERMOWELL
SHIELDED PAIR
GRND SCREW
1. CUSTOMER POWER HOOK UP AT THE TERMINAL STRIP IN THE ELECTRICAL CONNECTION BOX IN THE
NOTES:
CUSTOMER SUPPLIED
REMOTE START/STOP
SWITCH
COMPR HOT
COMPR
POWER
N
H
MICROPROCESSOR BOARD
DRAIN/PUMP HOT
DRAIN TIMER
RED
RED
PUMP/DRAIN
ALARM HOT
ALARM
RED
RED
YELLOW
YELLOW
CR1
TS-3
WHT
3
TS-2
YEL
1
YEL
ELEC. PLUG
RED
WHT
RED
RED
WHT
WHT
L1
PUMP (PM)
RED
H3
H2
RED
RED
GND
GRN
HIGH PRESS
CUT OUT SW.
SEE NOTE 2.
GRN
XFMR1
TRANSFORMER
HPCO
H1
CONNECTIONS
WHT
GRN
WHT
WHT
WHT
WHT
WHT
RED
200VAC THRU
240VAC
CONNECTION
380VAC THRU
480VAC
CONNECTION
GROUND
LUG
SIDE
(TYPICAL)
GRN
BLK
BLK
GRN
GRN
GRN
115V
200V
THRU
480V
SIDE
GROMMETED
HOLES IN
ELECTRICAL
COMPARTMENT
H4
RED
RED
FAN
BLK
BLK
C
R
COMP
BLK
GND
WHT
RED
LPCO
LOW PRESS
CUT OUT SW.
(C1)
ENCLOSURE
RUN
BLK
FU2
START
COMPRESSOR
RELAY AND
CAPACITOR
FU1
PRIMARY
FUSES
CONTACTOR
BLK
BLK
XFMR SECONDARY
FUSE - FU3-250V
RED
RED
D
N
U
RO
G
L1
OL
COMPRESSOR
CONNECTIONS
230V/1PH/60HZ
GRN
RED
550037
DIAGRAMA DE CABLEADO
NVC200 ENFRIADA POR
AIRE Y AGUA
WIRING DIAGRAM
NVC200
AIR AND WATERCOOLED
230/1/60,
220/1/50
230/1/60, 220/1/50
* SEE NOTE 3
BLK
BLK
BLK
RED
WHT
RED
RED
BLK
15
CONNECTIONS
DRAIN SV (SV)
BY OTHERS
230-575 VAC/3PH/60HZ
200-440 VAC/3PH/50HZ
5A/120VAC MAX
WHT
TS-1
BLK
BLK
L3
BLK
GRN
GRN
L2
BLK
J1
BLK
J4
J5
GRND SCREW
SENSORS
L1
TERM STRIP
CUSTOMER
CONNECTIONS
RED
24VAC
CUSTOMER.
AUTOTRANSFORMER. NOTE: MAIN INCOMING POWER DISCONNECT AND FUSING WILL BE PROVIDED BY
4. FOR CONNECTION TO 575V/3PH SYSTEMS, SWAP BOXES ABOVE RIGHT TO INCLUDE 575V TO 460V
1. CUSTOMER POWER HOOK UP AT THE TERMINAL STRIP IN THE ELECTRICAL CONNECTION BOX IN THE
NOTES:
CUSTOMER SUPPLIED
REMOTE START/STOP
SWITCH
COMPR HOT
COMPR
POWER
N
H
MICROPROCESSOR BOARD
DRAIN/PUMP HOT
DRAIN TIMER
PUMP/DRAIN
RED
RED
ALARM HOT
ALARM
RED
RED
YELLOW
YELLOW
L3
L2
L1
460V/3PH CONNECTION
CR1
575V
L3
L2
L1
X1
X3
XFMR 2
XFMR 1
X3
X1
X2
X4
H1
H1
H4
H4
X4
X2
H2
H3
H3
H2
TEMPERATURE
PROBE
TO EXCHANGER
THERMOWELL
SHIELDED PAIR
L3A
L2A
L1A
* SEE NOTE 4
460V
* SEE NOTE 4
TS-3
WHT
3
TS-2
YEL
1
YEL
ELEC. PLUG
RED
WHT
RED
RED
WHT
16
WHT
L1
RED
H3
H2
RED
RED
GND
GRN
HIGH PRESS
CUT OUT SW.
SEE NOTE 2.
GRN
XFMR1
GROUND
LUG
SIDE
(TYPICAL)
GRN
GRN
GRN
115V
200V
THRU
480V
SIDE
GROMMETED
HOLES IN
ELECTRICAL
COMPARTMENT
H4
RED
GRN
BLK
BLK
RED
WHT
RED
FAN
BLK
* SEE NOTE 3
BLK
BLK
BLK
L2
BLK
200-240V/3PH/50-60HZ
380-480V/3PH/50-60 HZ
GROUND
GRN
L1
L3
LOW PRESS
CUT OUT SW.
LPCO
FU1
PRIMARY
FUSES
BLK
FU2
CONNECTIONS
COMPRESSOR
(CM)
(C1)
CONTACTOR
BLK
BLK
XFMR SECONDARY
FUSE - FU3-250V
RED
RED
550031
DIAGRAMA DE CABLEADO
NVC200-400 ENFRIADA POR AIRE
Y AGUA
WIRING DIAGRAM
NVC200-400 AIR AND WATERCOOLED
208-575V/3PH/60HZ,
200-440V/3PH/50HZ
208-575V/3PH/60HZ, 200-440V/3PH/50HZ
TRANSFORMER
HPCO
H1
CONNECTIONS
PUMP (PM)
GRN
WHT
WHT
WHT
WHT
WHT
RED
200VAC THRU
240VAC
CONNECTION
380VAC THRU
480VAC
CONNECTION
RED
RED
CUSTOMER ELECTRICAL
CONNECTIONS ACCESS
REAR VIEW
OUTFLOW VALVE
ADJUSTMENT
ACCESS
2.50
51.19
57.75
25.00
30.38
32.56
23.38
28.12
FRONT VIEW
2.38
TOP VIEW
55.25
550030
CONTROL PANEL
DISPOSICIN GENERAL
NVC200-400
ENFRIADA POR AIRE Y AGUA
CONDENSATE DRAIN
MICROPROCESSOR CONTROL
(SEE TECHNICAL MANUAL FOR
OPERATION DETAILS)
17
DESCRIPCIN
REPUESTOS
UNIDAD
38052197
TABLERO DE CONTROL
38052718
22719421
38448239
38052916
38052437
38054268
38052361
38052676
38052908
38052171
38053252
38052148
VLVULA DE DRENAJE
38052320
Repuesto. Las cantidades bajo este encabezado reflejan el nmero de cada artculo que recomendamos mantenga a
mano para mantenimiento o reparacin. La cantidad apropiada para su aplicacin depender de cun graves sean las
interrupciones de servicio para su operacin.
Clase
Mnima
Mxima
NEMA 1
NEMA 4
NEMA 1
NEMA 4
NVC
CONDENSADORES
230V
230V
460V
460V
200
38053104
38053229
3854789
38446498
38446498
300
38052700
38053229
3854789
38446498
38446498
400
38052700
38053229
3854789
38446498
38446498
CONDENSADORES
VLVULAS
200
38054581
38054623
300
38450029
38054631
400
38450029
38054631
COMPRESORES
MODELO
18
NVC
230/1/60
230/3/60
230/3/50
380/3/50
460/3/60
575/3/60
200
38446746
38054649
38054672
38450003
38450003
38450003
300
38054656
38054680
38052288
38052270
38052270
400
38054664
38054698
38054706
38052288
38052288
R-404A
CAPACIDAD DEL
COMPRESOR
N DE
MODELO
VOLTIOS/
PH/HZ
LB
KG
LB-OZ
KG
TAMAO
MX. DEL
FUSIBLE
AMPACIDAD
MN. DEL
CIRCUITO
HP
RLA
LRA
QTY
HP
NVC200
230/1/60
540
245
2-4
1.02
20
13.7
9.7
40
1/6
NVC200
460/3/60
540
245
2-4
1.02
3.9
2.4
13
1/6
0.5
1.2
NVC200
230/3/60
540
245
2-4
1.02
12
7.7
4.8
25
1/6
NVC200
575/3/60
540
245
2-4
1.02
3.0
2.4
13
1/6
0.5
1.2
NVC250
460/3/60
570
259
3-8
1.588
5.3
11/2
3.6
16
1/6
0.5
1.2
NVC250
230/3/60
570
259
3-8
1.588
15
9.6
11/2
6.4
38
1/6
NVC250
575/3/60
570
259
3-8
1.588
4.3
11/2
3.6
16
1/6
0.5
1.2
NVC300
460/3/60
630
286
4-0
1.814
10
6.2
4.3
16
1/6
0.5
1.2
NVC300
230/3/60
630
286
4-0
1.814
18
11.5
7.9
38
1/6
NVC300
575/3/60
630
286
4-0
1.814
4.9
4.3
16
1/6
0.5
1.2
NVC400
460/3/60
670
304
4-0
1.814
12
7.6
2 1/2
5.4
23
1/6
0.5
1.2
NVC400
230/3/60
670
304
4-0
1.814
25
15.9
2 1/2
11.4
57
1/6
NVC400
575/3/60
670
304
4-0
1.814
10
6.0
2 1/2
5.4
23
1/6
0.5
1.2
RLA
LRA
a AVISO
La informacin sobre especificaciones anterior es precisa al momento de la publicacin.
Consulte la etiqueta de la serie del equipo para obtener las cargas y especificaciones reales
de refrigerante para las unidades.
19
PAGE
1
2
2
2
3
3
5
PAGE
8.0
INSTALLATION ET
DMARRAGE INITIAL
8
8.1
POSITIONNEMENT
ET MONTAGE
8.2
TUYAUTERIE ET ROBINETS
8.3
FILTRATION
8.4
BRANCHEMENT LECTRIQUE
8.5
DMARRAGE INITIAL
8.5.1 SQUENCE DE DMARRAGE
9.0
MAINTENANCE DE ROUTINE 10
9.1
INTRODUCTION
9.2
CONDENSEUR
DE FRIGORIGNE
9.3
SYSTME DE PURGE
DE CONDENSATS
9.4
PANNEAU DE FILTRATION
9.5
PR-FILTRES ET
POST-FILTRES
9.5.1 FILTRES FILETS
10.0 DPANNAGE
13
10.1 INTRODUCTION
10.2
11.0
12.0
13.0
14.0
GUIDE DE PROBLME/
RSOLUTION
SCHMAS DE CBLAGE
DISPOSITION GNRALE
PICES DE RECHANGE
SPCIFICATIONS
TECHNIQUES
15
17
18
19
2.0 INTRODUCTION
Le scheur d'air frigorifique cyclique Nirvana d'Ingersoll Rand extrait
l'humidit, les vapeurs d'huile et autres contaminants de l'air comprim.
Ces contaminants peuvent compromettre le fonctionnement des
appareils, commandes, instruments, mcanismes et outils de type
pneumatique. Un dispositif frigorifique qui refroidit l'air une
temprature o l'humidit de l'air est condense puis spare du flux
3.0 GARANTIE
La socit Ingersoll Rand garantit que l'quipement fabriqu et livr par
les prsentes ne comporte aucun dfaut de matriel ou de malfaon et
ce pendant une priode de douze (12) mois partir de la date de mise
en service de l'quipement ou de dix-huit (18) mois partir de la date
de l'expdition de l'usine, selon la premire ventualit. Pour se
conformer cette garantie, l'acheteur sera tenu de signaler rapidement
et par crit la socit toute dfaillance survenue au cours de ladite
priode, aprs quoi la socit pourra soit corriger cette non-conformit
par une rparation adapte au matriel, soit fournir une pice de
rechange FAB, pourvu que l'acheteur ait stock, install, exploit et
entretenu l'quipement conformment aux pratiques acceptes de
l'industrie et qu'il ait suivi les recommandations particulires de la
socit. Les accessoires et les quipements fournis par la socit mais
fabriqus par un tiers seront protgs par la garantie obtenue du tiers
par Ingersoll Rand, garantie qui sera ensuite cde l'acheteur. La
socit ne sera en aucun cas tenue responsable des rparations,
remplacements ou rglages effectus l'quipement ou du cot de
main-d'uvre engag par l'acheteur ou par des tiers sans l'autorisation
crite pralable de la socit.
Les effets de la corrosion, de l'rosion et de l'usure normale sont
spcifiquement exclus. Les garanties de performance sont limites
celles spcifiquement cites dans la proposition de la socit. Sauf si sa
responsabilit dans le respect de ces garanties de performance se limite
aux tests spcifis, les obligations de la socit se limiteront alors
assurer un correctif de la manire et dans les dlais prciss ci-dessus.
PRFIXE
NVC
DBIT
NOMINAL *
(PCNM)
200-400
TYPE DE
CONDENSEUR
A = AIR
W = EAU
PUISSANCE
2 = 230-1-60
4 = 460-3-60
5 = 230-3-60
6 = 575-3-60
7 = 380-3-50
8 = 220-3-50
SPCIFICATIONS
0 = NEMA 1
H = NEMA 4
* Les dbits nominaux indiqus correspondent une temprature d'admission de 100F, une temprature ambiante de 100F et une pression
d'air comprim de 100 psig.
a MISE EN GARDE
Il ne faut en aucun cas essayer de soulever des objets lourds sans
utiliser un quipement de levage appropri (c'est--dire, grue, palan,
lingues ou chariot lvateur fourches). Le soulvement de tout
appareil sans l'utilisation d'un quipement de levage appropri peut
provoquer des blessures corporelles graves.
a MISE EN GARDE
Mise en garde est utilis pour indiquer une situation dangereuse
qui peut conduire la mort ou de srieuses blessures corporelles. La
mise en garde ne doit pas tre prise en compte pour les accidents
entranant des dommages matriels moins qu'un risque de blessure
corporelle ne soit prsent.
a ATTENTION
Attention est utilis pour indiquer une situation dangereuse qui peut
conduire des blessures corporelles mineures ou modres.
a AVIS
Avis est utilis pour indiquer un nonc de la politique de la socit
car le message se rapporte directement ou indirectement la scurit
du personnel ou la protection de la proprit. Un avis ne doit pas tre
associ directement un risque ou une situation dangereuse et ne doit
pas tre utilis la place de danger , mise en garde ou
attention .
a AVIS
L'utilisateur de tout scheur d'air fabriqu par Ingersoll Rand, est, de
ce fait, averti que le non respect des consignes de scurit et des
prcautions en fonctionnement nonces ci-dessus, peut conduire
des blessures corporelles ou des dommages matriels. Cependant,
Ingersoll Rand n'nonce pas comme fait ou n'implique pas que la liste
prcdente des consignes de scurit et des prcautions en
fonctionnement est exhaustive et que le respect de cette liste vitera
toutes les blessures corporelles ou les dommages matriels.
MISE EN
GARDE
MISE EN GARDE
BOTIER DE CONNEXION LECTRIQUE
CONTENANT DES TENSIONS LEVES
Coupez lalimentation et verrouillez TOUTES les sources avant
douvrir lappareil pour procder la rvision.
Le cblage des contacts dalarme distance tire son
alimentation de contrle dune seconde source.
200-240VAC / 1 PH
2
CBLAGE
DE LUSINE
VERT
BLANC N
NOIR
L1
3
4
5
6
TENSION
SECTEUR
DENTRE
100-125VAC
CBLAGE
1PH/50-60HZ
(PAR DES TIERS) DE LUSINE
(SE REPORTER
LA PLAQUE
SIGNALTIQUE DU
DISPOSITIF POUR
LES PUISSANCES
NCESSAIRES)
2
VERT
NOIR
L1
3
4
ROUGE L2
5
6
TENSION
SECTEUR
DENTRE
200-240VAC
CBLAGE
1PH/50-60HZ
(PAR DES TIERS) DE LUSINE
(SE REPORTER
LA PLAQUE
SIGNALTIQUE DU
DISPOSITIF POUR
LES PUISSANCES
NCESSAIRES)
200-575VAC / 3 PH
1
2
VERT
ROUGE L1
BLANC
L2
NOIR
L3
3
4
5
6
TENSION
SECTEUR
DENTRE
200-575VAC
3PH/50-60HZ
(PAR DES TIERS)
(SE REPORTER
LA PLAQUE
SIGNALTIQUE DU
DISPOSITIF POUR
LES PUISSANCES
NCESSAIRES)
MISE EN
GARDE
MISE EN
GARDE
Le retrait des fusibles ne permet pas
de dbrancher lalimentation du
scheur. Toujours dbrancher
lalimentation de TOUTES les sources
avant de procder la rvision.
LIRE LE MANUEL TECHNIQUE
MISE EN GARDE
LE VENTILATEUR PEUT
DMARRER AUTOMATIQUEMENT
TOUT MOMENT
MISE EN GARDE
Cet appareil est aliment
par un frigorigne haute pression.
MISE EN GARDE
HAUTE TENSION
DIAGRAMME DE CIRCULATION
FIGURE 1
7.3 SYSTME DE SPARATION D'HUMIDIT
Les purgeurs de condensats Ingersoll Rand dchargent l'eau et les
lubrifiants de condensation (condensats) des appareils air comprim.
Le purgeur de condensats fonctionne comme un drain sans perte d'air,
retournant l'air arriv dans la cuve de vidange vers le systme d'air
comprim. L'extraction constante de condensats des appareils air
comprim est essentielle pour assurer un fonctionnement et des
performances adquats.
Le purgeur de condensats utilise une mthode de dtection unique pour
dterminer le niveau de condensats dans la cuve de vidange. Un
transducteur situ l'intrieur de la cuve de vidange met
continuellement un signal 50 fois par seconde. Lorsque le transducteur
a dtermin que le niveau de condensats a atteint un niveau
prdtermin l'intrieur de la cuve de vidange, un signal est envoy
la soupape de vidange sans perte pour qu'elle s'ouvre. Ceci permet
l'extraction des condensats un maximum de 80 gallons par heure.
Le purgeur dispose galement d'un bouton-test permettant de faire
fonctionner manuellement la soupape de vidange sans perte.
L'enfoncement du bouton-test fait allumer le voyant DEL et actionne
l'lectrovalve. Le voyant DEL s'allume pour indiquer la MISE SOUS
TENSION et s'teint lorsque la soupape de vidange sans perte est
actionne par le transducteur ou le bouton-test manuel.
SCHMA DE
PROCD ET
D'INSTRUMENTATION
NVC200-400
REFROIDISSEMENT
PAR AIR ET EAU
7.6.1
BOUTONS
ON / OFF (MARCHE / ARRT)
Fait basculer le scheur du mode de fonctionnement En ligne vers le
mode Hors ligne ; met la pompe glycol sous tension. Veuillez noter que
la mise en route du systme frigorifique dpend de la temprature.
EXCH SET (POINT DE CONSIGNE D'CHANGEUR)
Lorsque ce bouton est enfonc, le point de consigne de l'changeur en cours
est affich dans la fentre CL. Avec le point de consigne de l'changeur
affich, les flches haut et bas peuvent tre utilises pour augmenter ou
rduire la temprature de point de consigne de l'changeur.
ALARM RESET (RINITIALISATION D'ALARME)
Appuyez une fois sur ce bouton pour effacer l'indication d'alarme locale et
mettre hors tension le contact d'alarme distance. Si le problme ayant
dclench l'alarme persiste, celle-ci se redclenchera une fois le dlai
d'inhibition d'alarme coul.
% SAVINGS (% D'CONOMIE)
Appuyez une fois sur ce bouton pour modifier l'affichage CL et indiquer le
rapport entre le temps d'exploitation du systme frigorifique et le temps
d'exploitation total du scheur.
F / C
Fait basculer les indicateurs de temprature de voyant DEL des units de
mesure Fahrenheit vers les Celsius et inversement.
+/Permettent l'utilisateur de modifier les valeurs des points de consigne. Les
valeurs de point de consigne suivent un gamme de valeurs pralablement fixes.
VOYANTS
Affichage CL
Permet d'afficher la temprature de l'changeur lors d'un fonctionnement
normal. galement utilis pour afficher le point de consigne de temprature,
les tats d'alarme et les fonctions de synchronisation de l'changeur.
SYSTEM ENERGIZED (SYSTME SOUS TENSION)
Indique la mise sous tension du dispositif.
DRYER ON (SCHEUR EN MARCHE)
S'allume lorsque l'interrupteur On/Off est enfonc pour mettre le dispositif en
marche. Le systme frigorifique peut dmarrer tout moment lorsque ce
voyant est allum.
VIS DE RGLAGE
FIGURE 2
ROBINET AUTOMATIQUE
DE DBIT D'EAU
7.6.3
36
EXCH.
SET
37
MESSAGES D'ALERTE
Appuyez sur les touches flches HAUT ou BAS pour modifier le point
de consigne EXCHANGER SETPOINT en incrment de un degr.
38
PF
cd
38
a ATTENTION
vitez de rgler la temprature de l'changeur plus de 50 deg. F.
L'exploitation du scheur une temprature d'changeur de plus de
50 deg. F pourrait endommager le systme frigorifique.
7.6.4
Alarme
ALARME DE
TEMPRATURE LEVE
ALARME DE
TEMPRATURE FAIBLE
Affichage
HI TEMP ALARM
EXCH SETPOINT + 10 F
MODES DE DMARRAGE
28 F
7.6.6.1
Mode Manuel
Redmarrage automatique
a AVIS
Tout non respect des instructions ci-dessus pourra entraner un
mauvais fonctionnement du matriel et annulera la garantie.
a AVIS
Il est recommand de toujours utiliser deux cls lors de la ralisation
de connexions filetes au niveau du scheur. Tout manque d'utiliser
une deuxime cl pourra endommager la tubulure interne et les
composantes l'intrieur de l'enceinte.
FILTRATION
SCHEUR
AIR
D'AIR
DRYER
B
ENTRE
AIR IN D'AIR
C
SORTIE
D'AIR
AIR
OUT
PR-FILTRE
PREFILTER
SOUPAPE
SOUPAPE
DRAIN
DE
VALVE
VIDANGE
DRAIN
DE
VALVE
VIDANGE
SOUPAPE
CHECK
CLAPET
VALVE
SOUPAPE
CHECK
CLAPET
VALVE
SOUPAPE
CHECK
CLAPET
VALVE
SPARATEUR
OIL
D'HUILE
SEPARATOR
SOUPAPE
CHECK
CLAPET
VALVE
UNIT
AS DELIVERED
DISPOSITIF
PRT POUR L'EXPDITION
ACCESSOIRES
EN OPTION
OPTIONAL
ACCESSORY
ITEMS
REMARQUE
TUBE DE VIDANGE NE DOIT PAS TRE EN HAUTEUR OU TRE RACCORD
NOTE: : LEDRAIN
TUBE MUST NOT RISE OR BE CONNECTED TO
UN TUYAU TROP LONG POUR VITER D'ENTRANER UNE CONTRE-PRESSION.
LONG
PIPE WHICH
CREATE
BACK PRESSURE
UNEXCESSIVELY
RACCORDEMENT
UN SIPHON
DE SOLMAY
OUVERT
EST NCESSAIRE
FIGURE 3
CONFIGURATION TYPE DE LA TUYAUTERIE
8.4
8.5
BRANCHEMENT LECTRIQUE
a AVIS
Pour les modles refroidissement par eau, le robinet de dbit d'eau
doit tre ouvert manuellement pour assurer que le condenseur est
rempli d'eau avant de procder au dmarrage.
8.5.1
SQUENCE DE DMARRAGE
Mettez le scheur sous tension. Le panneau CL s'allume.
Le dlai de cycle de protection commencera son dcompte.
a AVIS
a ATTENTION
Ne jamais raccorder directement ou connecter des fils additionnels au
botier de jonction du compresseur. Ceci entranerait un mauvais
fonctionnement grave du systme.
a MISE EN GARDE
1
Recommandations de maintenance
Remplacez le dispositif de service (5) annuellement.
2
1
6
7
8
10
ou
en dvissant les vis (8) au niveau de l'adaptateur intermdiaire
(9) qui est ensuite dtach du dispositif de service par un
mouvement vers le bas.
6
7
9
9
10
2
4
2
6
a MISE EN GARDE
Dpressurisez le systme avant de dsassembler les filtres. Tout
manquement au respect de cette rgle pourrait entraner des
blessures voire la mort.
10,000
hrs
1,000
FILTRES FILETS
20
(68)
30
(86)
40
(104)
50 C
(122) F
9.5.1
AC 19-1380
11
2
1
3a
3b
1
1
1
6
4
7
3
2
1
2
16mm
(5/8)
12
10.0 DPANNAGE
10.1 INTRODUCTION
Les scheurs cycliques Nirvana d'Ingersoll Rand sont conus pour un fonctionnement fiable et sans problme. En cas de mauvais fonctionnement
du scheur, le guide ci-dessous a t cr dans le but de faciliter l'identification des problmes et leur correction.
a MISE EN GARDE
a MISE EN GARDE
PROBLME
Humidit en aval
SYMPTME(S)
Le scheur refroidit
correctement le flux d'air
(Vrifiez la temp. du
refroidisseur sur le
contrleur)
CAUSE POSSIBLE
CORRECTION
chec du purgeur de
Remplacez le dispositif de service.
condensats caus par un
dispositif de service dfectueux
Dbit excessif
Humidit en aval
Les tempratures
d'admission et de
refoulement sont les mmes
Aucune alimentation au
niveau du scheur
Fuite de rfrigrant
Le compresseur ne
fonctionne pas mais le
ventilateur fonctionne
Le compresseur et le
ventilateur ne fonctionnent
pas
Le compresseur et le
ventilateur ne fonctionnent
pas. Le contrleur indique
que le compresseur est en
marche (ON).
Le compresseur et le
ventilateur fonctionnent, la
temp. d'changeur est
leve, la pompe ne
fonctionne pas
Pompe dfectueuse
13
10.0 DPANNAGE
PROBLME
Mauvais fonctionnement de
l'affichage du contrleur
SYMPTME(S)
Affichage vide
CAUSE POSSIBLE
CORRECTION
Fusible saut
chec de carte
Temprature improbable
affiche
Lectures de temprature
erratiques ou inexactes
Remplacez la sonde.
Inspectez le cble de transducteur et le
raccordement terminal.
Remplacez le transducteur.
Pression de refoulement
considrablement plus faible
que la pression d'admission.
La temprature d'exploitation
du systme est au-dessus de
32F
Pression de refoulement
considrablement plus faible
que la pression d'admission.
La temprature d'exploitation
du systme est au-dessous
de 32F
Le relais/contacteur du
compresseur est coinc
Remplacez le relais/contacteur.
Relais de contrle de
Remplacez le relais.
microprocesseur dfectueux
La sonde n'est pas insre Inspectez la sonde et comparez les lectures
fond dans le puits thermique avec une source indpendante (p. ex. un
analyseur de temprature/pyromtre/bain de
glace) au niveau du puits de temprature et
de l'air ambiant.
Le problme persiste
Le purgeur de condensats ne
se dclenche pas
Le diamtre interne de la
tuyauterie d'admission/de
refoulement est trop petit et
entrane une poche d'air ou
une contre pression
Utilisation excessive de
Rduisez le nombre de coudes.
coudes dans la tuyauterie
d'admission/de refoulement
entranant une poche d'air ou
une contre pression.
Tuyauterie de refoulement trop
longue / trop leve entranant
une contre pression
La cuve de vidange de
condensats ne semble pas se
remplir de condensats, le purgeur
ne semble pas fonctionner
cause d'une poche d'air
14
CONNECTIONS
DRAIN SV (SV)
BY OTHERS
208-230 VAC/1PH/60HZ
200-220 VAC/1PH/50HZ
5A/120VAC MAX
WHT
RED
TB-1
L3
L1
L2
BLK
J1
CUSTOMER
CONNECTIONS
24VAC
BLK
BLK
GRN
GRN
BLK
J4
SENSORS
J5
TEMPERATURE
PROBE
TO EXCHANGER
THERMOWELL
SHIELDED PAIR
GRND SCREW
1. CUSTOMER POWER HOOK UP AT THE TERMINAL STRIP IN THE ELECTRICAL CONNECTION BOX IN THE
NOTES:
CUSTOMER SUPPLIED
REMOTE START/STOP
SWITCH
COMPR HOT
COMPR
POWER
N
H
MICROPROCESSOR BOARD
DRAIN/PUMP HOT
DRAIN TIMER
RED
RED
PUMP/DRAIN
ALARM HOT
ALARM
RED
RED
YELLOW
YELLOW
CR1
TS-3
WHT
3
TS-2
YEL
1
YEL
ELEC. PLUG
RED
WHT
RED
RED
WHT
WHT
L1
PUMP (PM)
RED
H3
H2
RED
RED
GND
GRN
HIGH PRESS
CUT OUT SW.
SEE NOTE 2.
GRN
XFMR1
TRANSFORMER
HPCO
H1
CONNECTIONS
WHT
GRN
WHT
WHT
WHT
WHT
WHT
RED
200VAC THRU
240VAC
CONNECTION
380VAC THRU
480VAC
CONNECTION
GROUND
LUG
SIDE
(TYPICAL)
GRN
BLK
BLK
GRN
GRN
GRN
115V
200V
THRU
480V
SIDE
GROMMETED
HOLES IN
ELECTRICAL
COMPARTMENT
H4
RED
RED
FAN
BLK
BLK
C
R
COMP
BLK
GND
WHT
RED
LPCO
LOW PRESS
CUT OUT SW.
(C1)
ENCLOSURE
RUN
550037
230/1/60, 220/1/50
BLK
FU2
START
COMPRESSOR
RELAY AND
CAPACITOR
FU1
PRIMARY
FUSES
CONTACTOR
BLK
BLK
XFMR SECONDARY
FUSE - FU3-250V
RED
RED
D
N
U
RO
G
L1
OL
COMPRESSOR
CONNECTIONS
230V/1PH/60HZ
GRN
RED
SCHMA DE CBLAGE
NVC200
REFROIDISSEMENT PAR
AIR ET EAU
WIRING DIAGRAM
NVC200220/1/50
AIR AND WATERCOOLED
230/1/60,
* SEE NOTE 3
BLK
BLK
BLK
RED
WHT
RED
RED
BLK
15
CONNECTIONS
DRAIN SV (SV)
BY OTHERS
230-575 VAC/3PH/60HZ
200-440 VAC/3PH/50HZ
5A/120VAC MAX
WHT
TS-1
BLK
BLK
L3
BLK
GRN
GRN
L2
BLK
J1
BLK
J4
J5
GRND SCREW
SENSORS
L1
TERM STRIP
CUSTOMER
CONNECTIONS
RED
24VAC
CUSTOMER.
AUTOTRANSFORMER. NOTE: MAIN INCOMING POWER DISCONNECT AND FUSING WILL BE PROVIDED BY
4. FOR CONNECTION TO 575V/3PH SYSTEMS, SWAP BOXES ABOVE RIGHT TO INCLUDE 575V TO 460V
1. CUSTOMER POWER HOOK UP AT THE TERMINAL STRIP IN THE ELECTRICAL CONNECTION BOX IN THE
NOTES:
CUSTOMER SUPPLIED
REMOTE START/STOP
SWITCH
COMPR HOT
COMPR
POWER
N
H
MICROPROCESSOR BOARD
DRAIN/PUMP HOT
DRAIN TIMER
PUMP/DRAIN
RED
RED
ALARM HOT
ALARM
RED
RED
YELLOW
YELLOW
L3
L2
L1
460V/3PH CONNECTION
CR1
575V
L3
L2
L1
X1
X3
XFMR 2
XFMR 1
X3
X1
X2
X4
H1
H1
H4
H4
X4
X2
H2
H3
H3
H2
TEMPERATURE
PROBE
TO EXCHANGER
THERMOWELL
SHIELDED PAIR
L3A
L2A
L1A
* SEE NOTE 4
460V
* SEE NOTE 4
TS-3
WHT
3
TS-2
YEL
1
YEL
ELEC. PLUG
RED
WHT
RED
RED
WHT
16
WHT
L1
RED
H3
H2
RED
RED
GND
GRN
HIGH PRESS
CUT OUT SW.
SEE NOTE 2.
GRN
XFMR1
TRANSFORMER
HPCO
H1
CONNECTIONS
PUMP (PM)
GRN
WHT
WHT
WHT
WHT
WHT
RED
200VAC THRU
240VAC
CONNECTION
380VAC THRU
480VAC
CONNECTION
GROUND
LUG
SIDE
RED
GRN
BLK
BLK
RED
WHT
RED
FAN
BLK
* SEE NOTE 3
BLK
BLK
BLK
L2
BLK
200-240V/3PH/50-60HZ
380-480V/3PH/50-60 HZ
GROUND
GRN
L1
L3
LOW PRESS
CUT OUT SW.
LPCO
FU1
PRIMARY
FUSES
BLK
FU2
CONNECTIONS
COMPRESSOR
(CM)
(C1)
CONTACTOR
BLK
BLK
XFMR SECONDARY
FUSE - FU3-250V
RED
RED
550031
SCHMA DE CBLAGE
NVC200-400 REFROIDISSEMENT
PAR AIR ET EAU WIRING DIAGRAM
NVC200-400 AIR AND WATERCOOLED
208-575V/3PH/60HZ,
200-440V/3PH/50HZ
208-575V/3PH/60HZ, 200-440V/3PH/50HZ
(TYPICAL)
GRN
GRN
GRN
115V
200V
THRU
480V
SIDE
GROMMETED
HOLES IN
ELECTRICAL
COMPARTMENT
H4
RED
RED
CUSTOMER ELECTRICAL
CONNECTIONS ACCESS
REAR VIEW
OUTFLOW VALVE
ADJUSTMENT
ACCESS
2.50
51.19
57.75
25.00
30.38
32.56
23.38
28.12
FRONT VIEW
2.38
TOP VIEW
55.25
550030
CONTROL PANEL
DISPOSITION GNRALE
NVC200-400
REFROIDISSEMENT PAR AIR ET EAU
CONDENSATE DRAIN
MICROPROCESSOR CONTROL
(SEE TECHNICAL MANUAL FOR
OPERATION DETAILS)
17
PICES DE RECHANGE
UNIT
38052197
CARTE, DE CONTRLE
38052718
CONTACTEUR, DE COMPRESSEUR
22719421
PURGEUR, DE CONDENSAT
38448239
38052916
38052437
PANNEAU DE FILTRATION
38054268
38052361
38052676
38052908
38052171
38053252
38052148
SOUPAPE, DE VIDANGE
38052320
Pices de rechange. Les quantits sous cet en-tte refltent le nombre de pices de rechange qu'il faut garder sous la main pour la
rparation ou l'entretien. La quantit convenant le mieux votre application dpend de l'importance des consquences d'une interruption
de fonctionnement sur vos activits.
Classe
Quantit
Minimum
Suggre pour
Service domestique lorsque des interruptions de fonctionnement sont acceptables.
Moyen
Maximum Fonctionnement pour l'exportation ou domestique lorsque des interruptions de fonctionnement sont inacceptables.
NEMA 1
NEMA 4
NEMA 1
NEMA 4
NVC
CONDENSEURS
230V
230V
460V
460V
200
38053104
38053229
3854789
38446498
38446498
300
38052700
38053229
3854789
38446498
38446498
400
38052700
38053229
3854789
38446498
38446498
CONDENSEURS
SOUPAPES
200
38054581
38054623
300
38450029
38054631
400
38450029
38054631
COMPRESSEURS
MODLE
18
NVC
230/1/60
230/3/60
230/3/50
380/3/50
460/3/60
575/3/60
200
38446746
38054649
38054672
38450003
38450003
38450003
300
38054656
38054680
38052288
38052270
38052270
400
38054664
38054698
38054706
38052288
38052288
POIDS
R-404A
N DE
MODLE
VOLTS/PH/HZ
LB
KG
LB-OZ
KG
NVC200
230/1/60
540
245
2-4
1,02
NVC200
460/3/60
540
245
2-4
1,02
3,9
2,4
13
1/6
0,5
NVC200
230/3/60
540
245
2-4
1,02
12
7,7
4,8
25
1/6
NVC200
575/3/60
540
245
2-4
1,02
3,0
2,4
13
1/6
0,5
1,2
NVC250
460/3/60
570
259
3-8
1,588
5,3
11/2
3,6
16
1/6
0,5
1,2
NVC250
230/3/60
570
259
3-8
1,588
15
9,6
11/2
6,4
38
1/6
NVC250
575/3/60
570
259
3-8
1,588
4,3
11/2
3,6
16
1/6
0,5
1,2
NVC300
460/3/60
630
286
4-0
1,814
10
6,2
4,3
16
1/6
0,5
1,2
NVC300
230/3/60
630
286
4-0
1,814
18
11,5
7,9
38
1/6
NVC300
575/3/60
630
286
4-0
1,814
4,9
4,3
16
1/6
0,5
1,2
NVC400
460/3/60
670
304
4-0
1,814
12
7,6
2 1/2
5,4
23
1/6
0,5
1,2
NVC400
230/3/60
670
304
4-0
1,814
25
15,9
2 1/2
11,4
57
1/6
NVC400
575/3/60
670
304
4-0
1,814
10
6,0
2 1/2
5,4
23
1/6
0,5
1,2
1,2
a AVIS
Les informations de spcification donnes ci-dessus taient correctes au moment de la
publication de ce manuel. Reportez-vous l'tiquette de srie de l'quipement pour les
charges frigorifiques actuelles et les spcifications actuelles des dispositifs.
19
SECADOR REFRIGERADO
INTERMITENTE NIRVANA
MODELOS 200-400
MANUAL DO OPERADOR
C.C.N.
DATA
REV.
: 80442775
: ABRIL DE 2007
:B
NDICE
NDICE
PGINA
1.0
2.0
3.0
4.0
NDICE
INTRODUO
GARANTIA
NOMENCLATURA PARA
O SECADOR REFRIGERADO
5.0
RECEBIMENTO E INSPEO
5.1
INSPEO
5.2
DESEMBALAGEM E MANUSEIO
6.0
PRECAUES DE
SEGURANA E OPERAO
7.0
PRINCPIOS DE OPERAO
7.1
INTRODUO
7.2
SISTEMA DE AR
7.3
SISTEMA DE REMOO
DE UMIDADE
7.4
SISTEMA DE REFRIGERAO
7.5
SISTEMA DE CIRCULAO
DE MASSA TRMICA
7.6
CONTROLES
7.6.1 INTERFACE BSICA
DO USURIO
7.6.2 PONTO DE CONTROLE DA
TEMPERATURA E ALARMES
DO TROCADOR DE CALOR
7.6.3 AJUSTE DOS PONTOS
DE CONTROLE
7.6.4 ALARMES E SUAS FUNES
7.6.5 MENSAGENS DE ALERTA
7.6.6 MODOS DE PARTIDA
7.6.6.1 Modo manual
7.6.6.2 Modo remoto (opcional)
7.6.6.3 Reincio automtico
1
2
2
2
3
3
5
NDICE
PGINA
8.0
INSTALAO E
FUNCIONAMENTO INICIAL
8.1
LOCALIZAO E MONTAGEM
8.2
TUBULAO E VLVULAS
8.3
FILTRAGEM
8.4
CONEXES ELTRICAS
8.5
FUNCIONAMENTO INICIAL
8.5.1 SEQNCIA DE PARTIDA
9.0
MANUTENES
PROGRAMADAS
9.1
INTRODUO
9.2
CONDENSADOR
DE REFRIGERANTE
9.3
SISTEMA DE DESCARGA
DE CONDENSADO
9.4
ELEMENTO DE FILTRO
DO PAINEL
9.5
PR-FILTROS E PS-FILTROS
9.5.1 FILTROS COM ROSCA
10.0 IDENTIFICAO E SOLUO
DE PROBLEMAS
10.1 INTRODUO
10.2 GUIA DE PROBLEMAS / AES
11.0 DIAGRAMAS DE FIAO
12.0 DISPOSIO GERAL
13.0 PEAS DE REPOSIO
14.0 ESPECIFICAES
DE ENGENHARIA
10
13
15
17
18
19
2.0 INTRODUO
O de ar refrigerado intermitente Nirvana da Ingersoll Rand remove
umidade, vapor de leo e outros contaminantes de ar comprimido.
Esses contaminantes so prejudiciais a aparelhos, controles,
instrumentos, mquinas e ferramentas operadas pneumaticamente. Tal
remoo feita atravs do resfriamento do ar com uma unidade de
refrigerao at uma temperatura na qual a umidade presente no ar
3.0 GARANTIA
A empresa garante que o seguinte equipamento fabricado e entregue
sob as condies aqui estabelecidas est livre de defeitos decorrentes
de materiais e fabricao por um perodo de doze meses a partir da
data de entrada do equipamento em operao ou dezoito meses a partir
da data de remessa da fbrica, o que ocorrer antes. O comprador est
obrigado a prontamente informar empresa, por escrito, qualquer falha
coberta por esta garantia dentro do perodo supracitado. Mediante o
recebimento de tal informao, a companhia poder optar, a seu
exclusivo critrio, por corrigir este problema atravs de reparos
adequados ao equipamento ou fornecer peas de reposio, F.O.B. no
ponto de embarque, desde que o comprador tenha armazenado,
instalado, mantido e operado o equipamento de acordo com as prticas
industriais apropriadas e tenha seguido as recomendaes especficas
da empresa. Acessrios ou equipamentos fornecidos pela empresa,
mas fabricados por terceiros, sero cobertos por qualquer garantia que
os respectivos fabricantes tenham cedido empresa e que possa ser
passada ao comprador. A empresa no se responsabiliza por quaisquer
reparos, substituies ou ajustes feitos ao equipamento, bem como por
quaisquer custos de mo-de-obra incorridos pelo comprador ou
terceiros, realizados e/ou incorridos sem aprovao prvia por escrito
da empresa.
Os efeitos decorrentes da corroso, eroso e uso e desgaste normal
so explicitamente excludos. As garantias de desempenho esto
limitadas quelas declaradas especificamente dentro da proposta da
empresa. A no ser que a responsabilidade por atender a tais garantias
PREFIXO
NVC
VAZO
NOMINAL*
(SCFM)
200-400
TIPO DE
CONDENSADOR
A = AR
W = GUA
POTNCIA
2 = 230-1-60
4 = 460-3-60
5 = 230-3-60
6 = 575-3-60
7 = 380-3-50
8 = 220-3-50
CLASSIFICAO
0 = NEMA 1
H = NEMA 4
* As vazes nominais indicadas so para uma temperatura de entrada de 100F, temperatura ambiente de 100F e presso do ar
comprimido de 100 PSIG.
a ALERTA
Sob nenhuma circunstncia qualquer pessoa deve tentar erguer
objetos pesados sem o equipamento de suspenso apropriado (por
exemplo, guindaste, grua, ganchos e cabos ou empilhadeira).
Levantar qualquer unidade sem o equipamento de suspenso
adequado pode causar ferimentos srios.
OSHA
Descries dos cabealhos
a ALERTA
"Alerta" usado para indicar uma situao de risco que tenha alguma
probabilidade de causar morte ou ferimentos graves. Um alerta no
deve ser considerado para acidentes causadores de danos a bens e
equipamentos, a no ser que esteja presente o risco de ferimentos
pessoais.
a CUIDADO
"Cuidado" usado para indicar uma situao de risco que possa
causar ferimentos leves ou moderados.
a AVISO
"Aviso" usado para indicar uma declarao da poltica da empresa,
uma mensagem relacionada direta ou indiretamente segurana do
pessoal ou proteo de propriedade. Um aviso no deve ser
associado diretamente a um risco ou situao de risco, no devendo
ser usado no lugar de "Perigo", "Alerta" ou "Cuidado".
a AVISO
O usurio de qualquer secador de ar fabricado pela Ingersoll Rand ,
atravs deste, alertado que no seguir as precaues de segurana e
operao acima pode resultar em ferimentos pessoais ou danos ao
equipamento. No entanto, a Ingersoll Rand no afirma explicitamente,
nem tem inteno de deixar implcito, que a lista anterior de
precaues de segurana e operao seja exaustiva e, assim, que a
observncia da referida lista possa prevenir todos os tipos de
ferimento ou danos ao equipamento.
ALERTA
ALERTA
CAIXA DE CONEXES ELTRICAS
CONTM ALTA TENSO
Desligue a alimentao de energia e trave TODAS as fontes
antes de abrir para dar manuteno.
A fiao dos contatos de alarmes remotos possui alimentao
de energia de controle de uma fonte separada.
100-125 V CA/MONO
200-240 V CA/MONO
2
FIAO DE
FBRICA
VRD
BRN
PRT
L1
3
4
5
6
TENSO DA LINHA
DE ENTRADA
100-125 V CA
MONO/50-60 HZ
FIAO DE
(DE TERCEIROS)
FBRICA
(CONSULTE A
PLACA DE
IDENTIFICAO
DA UNIDADE PARA
REQUISITOS DE
ALIMENTAO
DE ENERGIA)
2
VRD
PRT
L1
VRM
L2
3
4
5
6
200-575 V CA/TRI
TENSO DA LINHA
DE ENTRADA
200-240 V CA
MONO/50-60 HZ
FIAO DE
(DE TERCEIROS)
FBRICA
(CONSULTE A
PLACA DE
IDENTIFICAO
DA UNIDADE PARA
REQUISITOS DE
ALIMENTAO
DE ENERGIA)
1
2
VRD
VRM
L1
BRN
L2
PRT
L3
3
4
5
6
ALERTA
ALERTA
Remover os fusveis no desconecta
a alimentao de energia do secador.
Sempre desconecte a alimentao
de energia de TODAS as fontes
antes de dar manuteno.
LEIA O MANUAL TCNICO
ALERTA
O VENTILADOR PODE COMEAR
A FUNCIONAR AUTOMATICAMENTE,
A QUALQUER MOMENTO
ALERTA
Esta unidade carregada
com refrigerante sob alta presso.
ALERTA
ALTA TENSO
TENSO DA LINHA
DE ENTRADA
200-575V CA
TRI/50-60 HZ
(DE TERCEIROS)
(CONSULTE A
PLACA DE
IDENTIFICAO
DA UNIDADE PARA
REQUISITOS DE
ALIMENTAO
DE ENERGIA)
DIAGRAMA DE FLUXO
FIGURA 1
7.3 SISTEMA DE REMOO DE UMIDADE
O dreno de condensado da Ingersoll Rand descarrega umidade e
lubrificantes condensados (o condensado) do equipamento de ar
comprimido. O dreno de condensado opera como um dreno de perda
de ar zero, devolvendo o ar deslocado na bacia de drenagem de volta
ao sistema de ar comprimido. A descarga regular do condensado do
equipamento de ar comprimido essencial para o desempenho e
operao apropriados do equipamento.
O dreno de condensado usa um mtodo de deteco nico para
determinar o nvel de condensado na bacia de drenagem. Um
transdutor localizado na bacia de drenagem envia continuamente um
sinal, 50 vezes por segundo. Quando transdutor determinar que o nvel
de condensado atingiu um nvel predeterminado dentro da bacia de
drenagem, enviado um sinal para abrir a vlvula de drenagem sem
perda. Esta operao permite a remoo de at 80 gales de
condensado por hora.
O dreno tambm conta com um boto de teste, que permite a operao
manual da vlvula de drenagem sem perda. Pressionar o boto ilumina
o LED e energiza a vlvula solenide. O LED acende para indicar
"LIGADO" e apaga quando a vlvula de drenagem sem perda
operada pelo transdutor ou pelo boto de teste manual.
DIAGRAMA DE
INSTRUMENTAO E
PROCESSO PARA O
NVC200-400
REFRIGERADO A AR
E A GUA
7.6.1
BOTES
ON / OFF (LIGA/DESLIGA)
Alterna a operao do secador entre os status "on-line" e "off-line". Energiza
a bomba de glicol. Observe que o sistema de refrigerao ir operar com
base na temperatura.
EXCH SET (AJUSTE DO TROCADOR DE CALOR)
Quando pressionado, exibe o ponto de controle atual do trocador de calor na
tela de LCD. Enquanto o ponto de controle do secador exibido, as setas
para cima e para baixo podem ser usadas para aumentar e diminuir,
respectivamente, a temperatura de ponto de controle do trocador de calor.
ALARM RESET (REINICIALIZAO DE ALARME)
Pressionar uma vez libera a indicao de alarme local e desenergiza o
contato de alarme remoto. Caso a condio de alarme persista, o alarme
retornar aps o tempo de inibio do alarme ter decorrido.
% SAVINGS (% ECONOMIA)
Pressionar uma vez muda o mostrador LCD para que ele indique a proporo
entre o tempo total de funcionamento do sistema de refrigerao em relao
ao tempo total em que o secador esteve ligado.
F / C
Alterna os indicadores LED de temperatura entre as unidades de medida
Fahrenheit e Celsius.
+/Permite que o usurio modifique valores de pontos de controle. Os valores dos
pontos de controle so ciclados ao longo de um intervalo fixo.
LUZES
Mostrador LCD
Exibe a temperatura do trocador de calor durante operao normal. Tambm
usado para mostrar o ponto de controle da temperatura do trocador de
calor, condies de alarme e funes de tempo.
SYSTEM ENERGIZED (SISTEMA ENERGIZADO)
Indica quando a unidade est recebendo alimentao de energia.
DRYER ON (SECADOR LIGADO)
Iluminado quando o boto On/Off foi pressionado, para colocar a unidade em
operao. Quando a luz est acesa, o sistema de refrigerante pode comear
a funcionar a qualquer momento.
PARAFUSO
DE AJUSTE
FIGURA 2
VLVULA REGULADORA
DE GUA
7.6.3
36
EXCH.
SET
37
MENSAGENS DE ALERTA
38
PF
cd
7.6.6
38
MODOS DE PARTIDA
Os secadores NCV200-400 so capazes de iniciar o seu
funcionamento atravs de um dos seguintes modos de
partida:
a CUIDADO
No ajuste a temperatura do trocador de calor acima de 50 graus
Fahrenheit. Operar o secador com a temperatura do trocador de calor
acima de 50 graus Fahrenheit pode danificar o sistema de
refrigerao.
7.6.4
7.6.6.1
Modo manual
7.6.6.2
Alarme
ALARME DE
TEMPERATURA ALTA
ALARME DE
TEMPERATURA BAIXA
Visor
HI TEMP ALARM
EXCH SETPOINT + 10 F
28 F
Reincio automtico
a AVISO
No obedecer s instrues acima pode resultar em falha no
funcionamento do equipamento e anular a garantia.
a AVISO
FILTRAGEM
SECADOR
AIR
DE AR
DRYER
B
ENTRADA
AIR IN DE AR
C
SADA
DE AR
AIR
OUT
PR-FILTRO
PREFILTER
VLVULA
VLVULA
DRAIN
DE
VALVE
DRENAGEM
DRAIN
DE
VALVE
DRENAGEM
VLVULA
CHECK
DE
VALVE
RETENO
VLVULA
CHECK
DE
VALVE
RETENO
VLVULA
CHECK
DE
VALVE
RETENO
SEPARADOR
OIL
DE LEO
SEPARATOR
VLVULA
CHECK
DE
VALVE
RETENO
UNIT
AS DELIVERED
A UNIDADE,
CONFORME ENTREGUE
ACESSRIOSACCESSORY
OPCIONAIS
OPTIONAL
ITEMS
NOTA:
A TUBULAO DE DRENAGEM NO DEVE SER ELEVADA OU ESTAR CONECTADA
NOTE:
DRAIN TUBE MUST NOT RISE OR BE CONNECTED TO
A UM TUBO EXCESSIVAMENTE LONGO, O QUE PODE CRIAR CONTRAPRESSO.
EXCESSIVELY
LONG
PIPE
WHICH
MAYABERTO.
CREATE BACK PRESSURE
NECESSRIA
UMA CONEXO
A UM
DRENO
DE CHO
FIGURA 3
ARRANJO TPICO DA TUBULAO
8.4
8.5
CONEXES ELTRICAS
a CUIDADO
FUNCIONAMENTO INICIAL
a AVISO
Em modelos refrigerados a gua, a vlvula de gua precisa ser aberta
manualmente para assegurar que o condensador esteja cheio de gua
antes da partida.
8.5.1
SEQNCIA DE PARTIDA
Aplique energia ao secador. O painel de LCD ser
iluminado. O retardo de proteo contra ciclos curtos
comear a contagem regressiva.
a AVISO
a ALERTA
1
Recomendaes de manuteno
Substitua a unidade de servio (5) anualmente.
2
1
6
7
8
10
ou
soltando os parafusos (8) do adaptador intermedirio (9), que
liberado da unidade de servio atravs de um movimento para
baixo.
6
7
9
9
10
2
4
2
6
a ALERTA
Despressurize o sistema antes de desmontar filtros. No fazer isso
pode resultar em ferimentos ou morte.
AC 19-1380
10,000
`
hrs
1,000
FILTROS DE ROSCA:
20
(68)
30
(86)
40
(104)
50 C
(122) F
9.5.1
11
2
1
3a
3b
1
1
1
6
4
7
3
2
1
2
16mm
(5/8)
12
a ALERTA
a ALERTA
PROBLEMA
Umidade a jusante
SINTOMA(S)
O secador est resfriando
apropriadamente o fluxo de
ar (verifique a temperatura de
resfriamento no controlador).
As temperaturas da entrada
e da sada so iguais.
Umidade a jusante
As temperaturas da entrada
e da sada so iguais.
POSSVEL CAUSA
AO CORRETIVA
Falha de drenagem de
condensado, causada por
unidade de servio com
defeito.
Vazo excessiva.
A vlvula de desvio do
secador no est fechada.
No h alimentao de
energia no secador.
Vazamento de refrigerante.
O compressor no est
funcionando, mas o
ventilador est.
O compressor e o ventilador
esto funcionando, a
temperatura do trocador de
calor alta, a bomba no
est funcionando.
13
SINTOMA(S)
Mostrador em branco.
POSSVEL CAUSA
AO CORRETIVA
Fusvel queimado.
Verifique os fusveis.
Falha da placa
Temperaratura fora da
realidade sendo exibida.
Leituras de temperatura
errticas ou imprecisas.
A sonda no est
completamente inserida no
poo trmico.
Substitua a sonda.
A presso na sada
substancialmente menor do
que a presso na entrada. A
temperatura de operao do
sistema superior a 32 F.
As vlvulas da entrada e da
sada no esto
completamente abertas.
Abra as vlvulas.
Os filtros da entrada e da
sada esto bloqueados.
A presso na sada
substancialmente menor do
que a presso na entrada. A
temperatura de operao do
sistema inferior a 32 F.
O contator/rel do
compressor est preso.
Substitua o contator/rel.
Problemas no rel do
Substitua o rel.
controlador microprocessador.
A sonda no est
completamente inserida no
poo trmico.
O problema persiste.
O dreno de condensado no
dispara
O LED de dreno de
condensado est apagado
CONNECTIONS
DRAIN SV (SV)
BY OTHERS
208-230 VAC/1PH/60HZ
200-220 VAC/1PH/50HZ
5A/120VAC MAX
WHT
RED
TB-1
L3
L1
L2
BLK
J1
CUSTOMER
CONNECTIONS
24VAC
BLK
BLK
GRN
GRN
BLK
J4
SENSORS
J5
TEMPERATURE
PROBE
TO EXCHANGER
THERMOWELL
SHIELDED PAIR
GRND SCREW
1. CUSTOMER POWER HOOK UP AT THE TERMINAL STRIP IN THE ELECTRICAL CONNECTION BOX IN THE
NOTES:
CUSTOMER SUPPLIED
REMOTE START/STOP
SWITCH
COMPR HOT
COMPR
POWER
N
H
MICROPROCESSOR BOARD
DRAIN/PUMP HOT
DRAIN TIMER
RED
RED
PUMP/DRAIN
ALARM HOT
ALARM
RED
RED
YELLOW
YELLOW
CR1
TS-3
WHT
3
TS-2
YEL
1
YEL
ELEC. PLUG
RED
WHT
RED
RED
WHT
WHT
L1
PUMP (PM)
RED
H3
H2
RED
RED
GND
GRN
HIGH PRESS
CUT OUT SW.
SEE NOTE 2.
GRN
XFMR1
TRANSFORMER
HPCO
H1
CONNECTIONS
WHT
GRN
WHT
WHT
WHT
WHT
WHT
RED
200VAC THRU
240VAC
CONNECTION
380VAC THRU
480VAC
CONNECTION
GROUND
LUG
SIDE
(TYPICAL)
GRN
BLK
BLK
GRN
GRN
GRN
115V
200V
THRU
480V
SIDE
GROMMETED
HOLES IN
ELECTRICAL
COMPARTMENT
H4
RED
RED
FAN
BLK
BLK
C
R
COMP
BLK
GND
WHT
RED
LPCO
LOW PRESS
CUT OUT SW.
(C1)
ENCLOSURE
RUN
550037
230/1/60, 220/1/50
BLK
FU2
START
COMPRESSOR
RELAY AND
CAPACITOR
FU1
PRIMARY
FUSES
CONTACTOR
BLK
BLK
XFMR SECONDARY
FUSE - FU3-250V
RED
RED
D
N
U
RO
G
L1
OL
COMPRESSOR
CONNECTIONS
230V/1PH/60HZ
GRN
RED
DIAGRAMA DE FIAO
NVC200
REFRIGERADO
A AR E GUA
WIRING DIAGRAM
NVC200220/1/50
AIR AND WATERCOOLED
230/1/60,
* SEE NOTE 3
BLK
BLK
BLK
RED
WHT
RED
RED
BLK
15
CONNECTIONS
DRAIN SV (SV)
BY OTHERS
230-575 VAC/3PH/60HZ
200-440 VAC/3PH/50HZ
5A/120VAC MAX
WHT
TS-1
BLK
BLK
L3
BLK
GRN
GRN
L2
BLK
J1
BLK
J4
J5
GRND SCREW
SENSORS
L1
TERM STRIP
CUSTOMER
CONNECTIONS
RED
24VAC
CUSTOMER.
AUTOTRANSFORMER. NOTE: MAIN INCOMING POWER DISCONNECT AND FUSING WILL BE PROVIDED BY
4. FOR CONNECTION TO 575V/3PH SYSTEMS, SWAP BOXES ABOVE RIGHT TO INCLUDE 575V TO 460V
1. CUSTOMER POWER HOOK UP AT THE TERMINAL STRIP IN THE ELECTRICAL CONNECTION BOX IN THE
NOTES:
CUSTOMER SUPPLIED
REMOTE START/STOP
SWITCH
COMPR HOT
COMPR
POWER
N
H
MICROPROCESSOR BOARD
DRAIN/PUMP HOT
DRAIN TIMER
PUMP/DRAIN
RED
RED
ALARM HOT
ALARM
RED
RED
YELLOW
YELLOW
L3
L2
L1
460V/3PH CONNECTION
CR1
575V
L3
L2
L1
X1
X3
XFMR 2
XFMR 1
X3
X1
X2
X4
H1
H1
H4
H4
X4
X2
H2
H3
H3
H2
TEMPERATURE
PROBE
TO EXCHANGER
THERMOWELL
SHIELDED PAIR
L3A
L2A
L1A
* SEE NOTE 4
460V
* SEE NOTE 4
TS-3
WHT
3
TS-2
YEL
1
YEL
ELEC. PLUG
RED
WHT
RED
RED
WHT
16
WHT
L1
RED
H3
H2
RED
RED
GND
GRN
HIGH PRESS
CUT OUT SW.
SEE NOTE 2.
GRN
XFMR1
GROUND
LUG
SIDE
(TYPICAL)
GRN
GRN
GRN
115V
200V
THRU
480V
SIDE
GROMMETED
HOLES IN
ELECTRICAL
COMPARTMENT
H4
RED
GRN
BLK
BLK
RED
WHT
RED
FAN
BLK
* SEE NOTE 3
BLK
BLK
BLK
L2
BLK
200-240V/3PH/50-60HZ
380-480V/3PH/50-60 HZ
GROUND
GRN
L1
L3
LOW PRESS
CUT OUT SW.
LPCO
FU1
PRIMARY
FUSES
BLK
FU2
CONNECTIONS
COMPRESSOR
(CM)
(C1)
CONTACTOR
BLK
BLK
XFMR SECONDARY
FUSE - FU3-250V
RED
RED
550031
DIAGRAMA DE FIAO
NVC200-400 REFRIGERADO AWIRING
AR DIAGRAM
E GUA
NVC200-400 AIR AND WATERCOOLED
208-575V/3PH/60HZ,
200-440V/3PH/50HZ
208-575V/3PH/60HZ, 200-440V/3PH/50HZ
TRANSFORMER
HPCO
H1
CONNECTIONS
PUMP (PM)
GRN
WHT
WHT
WHT
WHT
WHT
RED
200VAC THRU
240VAC
CONNECTION
380VAC THRU
480VAC
CONNECTION
RED
RED
CUSTOMER ELECTRICAL
CONNECTIONS ACCESS
REAR VIEW
OUTFLOW VALVE
ADJUSTMENT
ACCESS
2.50
51.19
57.75
25.00
30.38
32.56
23.38
28.12
FRONT VIEW
2.38
TOP VIEW
55.25
550030
CONTROL PANEL
DISPOSIO GERAL
NVC200-400
REFRIGERADO A AR E GUA
CONDENSATE DRAIN
MICROPROCESSOR CONTROL
(SEE TECHNICAL MANUAL FOR
OPERATION DETAILS)
17
DESCRIO
SOBRESSALENTES
UNID.
38052197
PLACA, CONTROLE
38052718
CONTATOR, COMPRESSOR
22719421
DRENO, CONDENSADO
38448239
38052916
38052437
38054268
38052361
38052676
38052908
38052171
38053252
38052148
VLVULA, DRENAGEM
38052320
Sobressalentes. Os valores sob esse ttulo refletem a quantidade de cada componente que recomendamos ter mo para
manuteno ou reparos. A quantidade apropriada para a sua aplicao depender do quo crticas as interrupes do
funcionamento so para a sua operao.
Tipo
Quantidade
Sugerida para:
Mnima
Mdia
Mxima
NEMA 1
NEMA 4
NEMA 1
NEMA 4
NVC
CONDENSADORES
230V
230V
460V
460V
200
38053104
38053229
3854789
38446498
38446498
300
38052700
38053229
3854789
38446498
38446498
400
38052700
38053229
3854789
38446498
38446498
CONDENSADORES
VLVULAS
200
38054581
38054623
300
38450029
38054631
400
38450029
38054631
COMPRESSORES
MODELO
18
NVC
230/1/60
230/3/60
230/3/50
380/3/50
460/3/60
575/3/60
200
38446746
38054649
38054672
38450003
38450003
38450003
300
38054656
38054680
38052288
38052270
38052270
400
38054664
38054698
38054706
38052288
38052288
R-404A
TAM. MX.
FUSVEL
AMPACIDADE
MN.
CIRCUITO
N. DO
MODELO
VOLTS/
FASES/HZ
LBS.
KG
LBONA
KG
NVC200
230/1/60
540
245
2-4
1,02
20
NVC200
460/3/60
540
245
2-4
1,02
NVC200
230/3/60
540
245
2-4
1,02
NVC200
575/3/60
540
245
2-4
1,02
NVC250
460/3/60
570
259
3-8
NVC250
230/3/60
570
259
3-8
NVC250
575/3/60
570
259
NVC300
460/3/60
630
NVC300
230/3/60
630
NVC300
575/3/60
NVC400
NVC400
NVC400
VALORES NOMINAIS DO
COMPRESSOR
HP
RLA*
LRA**
QTY
HP
RLA*
LRA**
13,7
9,7
40
1/6
3,9
2,4
13
1/6
0,5
1,2
12
7,7
4,8
25
1/6
3,0
2,4
13
1/6
0,5
1,2
1,588
5,3
11/2
3,6
16
1/6
0,5
1,2
1,588
15
9,6
11/2
6,4
38
1/6
3-8
1,588
4,3
11/2
3,6
16
1/6
0,5
1,2
286
4-0
1,814
10
6,2
4,3
16
1/6
0,5
1,2
286
4-0
1,814
18
11,5
7,9
38
1/6
630
286
4-0
1,814
4,9
4,3
16
1/6
0,5
1,2
460/3/60
670
304
4-0
1,814
12
7,6
2 1/2
5,4
23
1/6
0,5
1,2
230/3/60
670
304
4-0
1,814
25
15,9
2 1/2
11,4
57
1/6
575/3/60
670
304
4-0
1,814
10
6,0
2 1/2
5,4
23
1/6
0,5
1,2
a AVISO
As informaes sobre especificaes acima eram exatas no momento da publicao.
Consulte a etiqueta de srie do equipamento para as especificaes e cargas de refrigerante
especficas para aquela unidade.
19