Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Gas Detectors
www.indsci.com
CTX 300
SENSOR SPE
Gas
Type of sensor
Range
(in ppm)
Operating
temperature
Relative humidity
uncondensed
O2
electrochemical
CO
electrochemical
CO2
H2S
infrared
infrared
infrared
infrared
electrochemical
NO
electrochemical
NO2
electrochemical
SO2
electrochemical
C|2
H2
HCI
electrochemical
electrochemical
electrochemical
HCN
electrochemical
NH3
electrochemical
O3
PH3
ClO2
Toluene
electrochemical
electrochemical
electrochemical
semiconductor
semiconductor
semiconductor
semiconductor
semiconductor
semiconductor
semiconductor
semiconductor
semiconductor
semiconductor
semiconductor
semiconductor
semiconductor
semiconductor
semiconductor
semiconductor
semiconductor
semiconductor
semiconductor
30,0%
100%
100
300
1000
1,00%
10,00%
1%
5%
10%
50%
30,0
100
1000
100
300
1000
10,0
30,0
10,0
30,0
100
10,0
2000
30,0
100
10,0
30,0
100
1000
1,00
1,00
3,00
2000
500
500
2000
5000
500
10000
2000
2000
2000
2000
10000
10000
2000
2000
2000
2000
1000
1000
-20C to + 50C
5C to 40C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-30C to +45C
-30C to +45C
-30C to +45C
-30C to +45C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to + 50C
-20C to +50C
-20C to +50C
-20C to +60C
-20C to +50C
-20C to +60C
-20C to +50C
-20C to +55C'
-20C to +55C'
-20C to +55C'
-20C to +55C'
-20C to +55C'
-20C to +55C'
-20C to +55C'
-20C to +55C'
-20C to +55C'
-20C to +55C'
-20C to +55C'
-20C to +55C'
-20C to +55C'
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
5% to 95% RH
5% to 95% RH
5% to 95% RH
5% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
10% to 95% RH
Trichloroethylene
Xylene
Ethanol
R12
R22
R123
R134a
R142b
R11
R23
R141b
R143a
R404a
R507
R410a
R32
Other gases on request
ECIFICATIONS
Pressure
Accuracy at PA
full scale
Life span
(in month)
T (50)
seconds
IP
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 2%
+/- 2%
+/- 2%
+/- 2%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 1,5%
+/- 2%
+/- 2%
+/- 3%
+/- 3%
+/- 3%
+/- 3%
+/- 2%
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
+/-15% relative to alarm threshold
28
36
36
36
36
36
36
60
60
60
60
36
36
36
36
36
36
24
24
36
36
36
24
24
24
24
24
24
24
24
18
18
24
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
10
< 20
15
15
15
< 20
< 20
70 (T90)
70 (T90)
70 (T90)
70 (T90)
15
15
15
15
15
15
20
20
15
15
15
50
50
50
50
30
30
50
50
40
40
50
20
20
40
20
20
20
30
30
30
30
30
30
30
30
30
30
30
20
20
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
66
CTX 300
SPECIFICATIONS
Enclosure:
Polycarbonate housing
Function:
Detector-transmitter
Display:
Indicator lights:
Clear readability
Link:
Cable inlet:
Better performance
Backlit display
High-Level technology
Pre-calibrated sensor avoiding the need to use
unstable gases on site for calibration purposes
Remote sensor unit allowing measurements in
even the most inaccessible places
High-performance semiconductor type detector
(detection of freon gas, etc.)
15 to 32 V DC
Power consumption:
Gas collector
Operating
temperature:
-20C to + 50C
Advanced design
Sealing:
IP 66
Weight:
520 g
Dimensions:
Certification:
Heavy-duty
Use of polycarbonate and stainless steel
mounting hardware
Resistant to corrosive agents
Durable housing
Calibration cup
REV 0608
EMC:
Compliance with directives
Subject to operation conditions
130
Bypass adapter
136
69