Contents
Motor Control (AMPGARD)Medium Voltage
Motor Starters
General Description
Application and Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Personnel Safety Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mechanical Non-Loadbreak Isolating Switch . . . . . . . . . . . . . . . . . . .
400 A, 7.2 kV Vacuum ContactorBolt-in, Type SL . . . . . . . . . . . . . .
400 A, 7.2 kV Vacuum ContactorStab-in, Type SL . . . . . . . . . . . . . .
Current Limiting Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Isolated Low Voltage Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bus and Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reduced Voltage StartersMechanical . . . . . . . . . . . . . . . . . . . . . . .
Reduced Voltage StartersSolid-State . . . . . . . . . . . . . . . . . . . . . . . .
Synchronous Motor Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Incoming Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Potential Transformers and Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Type LBS Loadbreak Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main Breaker AMPGARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LBS Loadbreak Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Type SL, 400 A, 7.2 kV Vacuum Contactor . . . . . . . . . . . . . . . . . . . . . .
Type SL, 800 A, 7.2 kV Vacuum Contactor . . . . . . . . . . . . . . . . . . . . . .
Type SL, 300 A, 15 kV Vacuum Contactor . . . . . . . . . . . . . . . . . . . . . .
Main Breaker Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contactor-Fuse Coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protection Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starter Fuse Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Layout Dimensions
Full Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Primary Reactor, Reduced Voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Autotransformer, Reduced Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . .
Synchronous Brush Type Mark V Controller . . . . . . . . . . . . . . . . . . .
Solid-State Reduced Voltage AMPGARD MV4S . . . . . . . . . . . . . . . . .
Incoming Line Switch/PT Layouts . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tie Switch Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Arc-Resistant Starter Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main Breaker AMPGARD Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AMPGARD XP3
General Description
Application and Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Enhanced Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Layout Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjustable Frequency Drives
General Description
Application and Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SC9000 EP Fully Integrated AE-Frame AFD . . . . . . . . . . . . . . . . . . .
Synchronous Transfer Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15 kV Input Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated AMPGARD Main Breaker . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Personnel Safety Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Component Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Output Filters and Reactors . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Data and Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
i
ii
10.1-1
10.1-1
10.1-2
10.1-3
10.1-4
10.1-4
10.1-5
10.1-6
10.1-7
10.1-8
10.1-10
10.1-11
10.1-11
10.1-11
10.1-12
10.1-14
10.1-17
10.1-17
10.1-18
10.1-19
10.1-20
10.1-21
10.1-22
10.1-23
10.1-24
10.1-27
10.1-29
10.1-30
10.1-32
10.1-35
10.1-37
10.1-38
10.1-39
10.1-41
10.1-42
10.1-43
10.1-44
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
10.2-1
10.2-2
10.2-13
10.2-15
10.2-16
10.2-17
10.2-19
10.2-20
10.2-22
10.2-24
17
18
19
20
21
i
ii
1
Specifications
See Eatons Product Specification Guide, available on CD or on the Web.
CSI Format: . . . . . . . . . . . . . . . . . . . . . . . . 1995
2010
AMPGARD Motor Starters . . . . . . . . . . Section 16349
Section 26 18 39
AMPGARD Arc Resistant Starters . . . . Section 16349AR Section
AMPGARD XP3 Starters . . . . . . . . . . . . Section 16349XP3 Section
SC 9000 . . . . . . . . . . . . . . . . . . . . . . . . . Section 16349B
Section 26 18 39.13
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-1
Sheet 10 003
General Description
AMPGARD Motor
Control Assembly
General Description
AMPGARD
Eatons
medium voltage
metal-enclosed control family
provides control and protection
of medium voltage motors and
equipment rated 230013,800V
nominal/15,000V maximum.
Application Description
AMPGARD control has a complete
metal-enclosed offering:
Enclosures
AMPGARD products are available in
NEMA 1 general purpose enclosures
as standard. NEMA 12 (dust tight),
NEMA 3R (outdoor) and arc-resistant
enclosures are available options for
most products. Contact Eaton for
exceptions. Enclosure type affects the
maximum continuous current rating
of the starters in the enclosure.
Arc-Resistant AMPGARD
When specified, AMPGARD is available
in special arc-resistant construction.
AMPGARD AR is available with a 50 kA,
0.5 sec arc resistant rating. The design
has been tested and verified to meet
the requirements of IEEE C37.20.7 for
Type 2B construction. Type 2B construction is defined as arc-resistant at
front, back and sides of the enclosure
with the low voltage compartment door
open. Most types of 400A and 800A
starters, as well as 24-inch (610 mm)
wide incoming cable sections are
available in arc-resistant construction.
A common plenum design to close
couple to Eaton arc-resistant switchgear
is also available. Consult Eaton for
ratings on this design. Main Breaker
AMPGARD, SC 9000 AFD, LBS load
break switches are not available in
arc-resistant construction. Due to the
specific nature of arc-resistant testing,
no modifications may be made to
the enclosure while maintaining the
arc-resistant rating. Consult Eaton
for more details.
Interlocks
Interlocking on AMPGARD starters
includes:
CA08104001E
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
AMPGARD Main Breaker
MV4S
RVSS
2-High FVNR
21
July 2014
Sheet 10 004
General Description
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
Switch Operating
Arm
Control Plug
Isolation Switch
Eatons Type JMT-4/8 and JMT-15 are
each a drawout, lightweight, three-pole,
manually operated isolating switch
mounted in the top of the starter enclosure. They may be easily removed
by loosening two bolts in the rear of
the switch. The JMT-4 is rated 400A
continuous while the JMT-8 is rated
720A continuous. The JMT-15 is rated
300A continuous at 15 kV. All isolation
switches have a mechanical life rating
of 10,000 operations.
14
15
16
17
Features
A positive mechanical interlock
between the isolating switch handle
mechanism and contactor prevents the
isolating switch from being opened
when the contactor is closed or from
being closed if the contactor
is closed.
An operating lever in the isolating
switch handle mechanism is designed
to shear off if the operator uses
too much force in trying to open the
non-loadbreak isolating switch when
the contactor is closed. This feature
ensures that the operator cannot open
the switch with the main contactor
closed, even if excessive force is
used on the operating handle.
To operate the isolating switch, the
operating handle is moved through
a 180 vertical swing from the ON to
the OFF position. In the ON position,
a plunger on the back of the handle
housing extends through a bracket on
the rear of the starter high voltage
door, preventing the door from being
opened with the switch closed. When
the high voltage door is open, a door
interlock prevents the handle from
being inadvertently returned to the
ON position.
When the operating handle is moved
from ON to OFF, copper stabs are
withdrawn from incoming line fingers.
As the stabs withdraw, they are
visible above the top of the fuses
when viewed from the front, and
simultaneously grounded. As the
fingers are withdrawn, a spring-driven
isolating shutter moves across the
back barrier to prevent front access
to the line connections. As the
shutter slides into position, distinctive
markings appear on the back barrier,
making it easier to check the position
of the shutter.
18
19
20
Mechanical Non-Loadbreak
Isolating Switch
Switch Handle
Closed
Switch Handle
Open
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-3
Sheet 10 005
General Description
General Description
Eatons Type SL Vacuum Contactors
were designed and engineered
specifically for use in AMPGARD
starters. 7.2 kV SL 400A Vacuum
Contactors are self-supporting,
compact, drawout, three-pole, DC
magnet closed contactors. To permit
application matching of the starter to
the motor rating, the SL Contactor is
available in 400A standard and high
interrupting ratings.
SL Contactors are available in the
standard bolt-in configuration and
optional stab-in design. Either bolt-in
or stab-in designs can be supplied in a
two-high configuration, with a starter
maximum of 400 full load amperes. The
total NEMA 1 structure rating cannot
exceed 720A for a combination of
two starters. Refer to Table 10.1-4 on
Page 10.1-17 for other ratings.
Design
Maintenance
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
DIP Switch on Contactor Control Board
14
15
16
17
18
19
20
21
CA08104001E
July 2014
Sheet 10 006
General Description
Mechanical Interlock with
Isolation Switch
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
7200V Maximum
Roll-out
Wheels
Self-Aligning
Contactor Line
and Load Fingers
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-5
Sheet 10 007
General Description
Standard Isolation Switch
Viewing Window
i
ii
Bolted
Main Fuses
Customer
Terminal Blocks
for Remote
Control
Connections
1
2
3
Horizontal
Wireway
Fuse Fault
Indicator
Vertical Control
Wireway
5
6
7
8
9
10
Indicating Lights
Start/Stop Pushbutton
(When Specified)
MD-3000 Differential
Relay (When Specified)
Isolation Switch
Operating Handle
(Mechanism Locks
Medium Voltage
Door When Switch
is Closed)
Low Voltage
Access Door
Medium Voltage
Access Door
11
12
13
14
15
16
17
18
19
20
CA08104001E
21
July 2014
Sheet 10 008
General Description
ii
Low Voltage
Conduit Area
1
Phase A
2
Phase B
3
4
Phase C
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Bus Splice
Plates
Vertical
Bus Drops
Main Bus
Vertical Bus
NEMA/ANSI ICS3
UL 347
CSA
The major components, i.e., contactor,
isolating switch, fuses, EMR-3000 and
EMR-4000 are UL recognized.
UL or CSA labeling of a specific starter
requires review to ensure that all
requested modifications and auxiliary
devices meet the appropriate standards.
Refer to factory when specified.
AMPGARD starters meet the requirements of IEC standards 60694, 60298
and 60470.
Seismic Qualification
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-7
Sheet 10 009
General Description
General Description
Reduced Voltage
Autotransformer Starter
i
ii
1
2
3
4
Reactor Starter
%
%
%
%
Motor Motor Line
Torque
Voltage Current Current
80
80% tap
65% tap 1 65
50% tap
50
1
80
65
50
80
65
50
64
42
25
%
%
%
%
Motor Motor Line
Torque
Voltage Current Current
80
80% tap
65% tap 2 65
50% tap
50
Advantages
Advantages
Disadvantages
Sequence of Operation
80
65
50
67
45
28
64
42
25
6
7
8
Disadvantages
10
11
Sequence of Operation
12
13
14
15
16
17
CA08104001E
18
19
20
21
July 2014
Sheet 10 010
General Description
i
ii
1
2
3
4
5
6
7
8
10
11
12
Ratings
Starting Characteristics
The soft start controller provides
a number of selectable starting
characteristics as standard:
Kick Start
Provides an initial boost of current to
overcome motor and system inertia.
Ramp Start
Operator sets the initial starting
voltage and ramp time. Factory
setting for starting voltage is 20%.
Range is 0 to 100%. Factory setting
for starting time is 10 seconds. Range
is 0 to 120 seconds.
Load CablesNormal
Current Limit
Limits the maximum starting current.
Used in long start time applications
and motor protection applications.
Factory setting is 350% of motor FLA.
Range is 200 to 600%.
Motor
Protection
Relay
Main Starter
Cubicle
13
14
15
16
17
18
19
20
Industry Standards
The AMPGARD solid-state starter is
designed and built to meet all applicable
industry standards. The 400A starter is
available as a UL listed assembly.
Soft Starter
LV Control
Compartment
Drawout
SCR Truck
(Located
Behind
MV Door)
NEMA ICS3
UL 347
CSA
Manufactured in an ISO 9001
and ISO 14001 certified facility
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-9
Sheet 10 011
General Description
How It Works
1. At the time of start, the bypass
contactor is open and all current
passes through the SCRs that
ramp the voltage per the preprogrammed starter settings.
2. After start is complete, the run
contactor closes, taking the SCRs
out of the circuit.
3. The SCRs are on for only a short
time therefore no MCC venting or
cooling is required.
i
ii
1
2
3
4
5
Design
Soft start components and bypass
contactor are mounted in a easyto-remove roll-out truck assembly.
Maintenance can be performed with
the truck on a bench away from the
starter cubicle.
6
7
8
9
10
11
12
13
AMPGARD 720A Soft Starter
14
15
16
17
18
19
20
21
CA08104001E
July 2014
Sheet 10 012
General Description
i
ii
1
2
3
4
5
6
7
9
10
11
Basic Brush-type
The Basic Brush-type starter includes
a three-phase exciter to generate DC
rotor current up to 200A plus a control
board that determines the proper
time to apply the DC field while also
providing basic protection, including:
Enhanced Brush-type
Basic Brushless
AMPGARD Synchronous Starter
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-11
Sheet 10 013
General Description
Incoming Line
Depending on the size and number
of incoming cables, an incoming line
enclosure may be necessary. Different
designs are available for incoming
power for top or bottom entry.
When incoming line metering is
specified, an additional 24-inch
(610 mm) wide metering structure
is typically supplied.
Bus for
Top or
Bottom
Entry
Incoming
Power
Potential Transformers,
Control Power Transformer
Disconnect and Fuses
Bus connected (7.2 kV max.) potential
transformers and/or control power
transformers are mounted in a
20-inch (508 mm) high assembly that
includes a disconnect and primary fuses.
The assembly can be mounted in a
24-inch (610 mm) or 36-inch (914 mm)
wide structure.
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
Type LBS Loadbreak Switch Shown
in Upper or Lower Half of 36-Inch
(914 mm) Wide Structure, Height
40 Inches (1016 mm)
13
14
15
16
17
18
19
20
CA08104001E
21
July 2014
Sheet 10 014
General Description
Ratings
ii
1
2
Front/Side Accessible
Connections
ANSI
Interrupting
Rating
Nominal
Voltage Class
Impulse
Withstand
Rating
Short-Circuit
Current at Rated
Maximum kV
Continuous
Current
at 60 Hz
MVA
kV
kV Peak
kA rms
Amperes
250
4.16
60 kV BIL
29 at
4760V
1200
2000
3000
350
4.16
60 kV BIL
41 at
4760V
1200
2000
3000
500
7.2
60 kV BIL
33 at
8250V
1200
2000
3000
7
8
General Description
10
11
12
13
14
15
16
17
Listing/Certification
UL listing and CSA certification is
available, depending on the specific
bill of material.
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-13
Sheet 10 015
General Description
Microprocessor-Based Relays
Enclosures
i
ii
1
Metering
Power Xpert meters are available
for multi-function metering. Refer
to Tab 3.
Communications
4
5
6
7
8
9
10
Side Panel Removed to Show Incoming
Cable Connections
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
July 2014
Sheet 10 016
Technical Data
Technical Data
Typical Wiring Diagram for Full Voltage FVNR Starter
ii
1
Motor
2
3
T3
T2
T1
CG
1CT
X2
X2
X2
X1
X1
X1
CG
GND
DP
MP
H1C H2A
H1A H2A
C1
C11
H1B
H1B H2B
H2B
C2
C12
H1C
H2C
IQ DP4130
25
C3
GND
X2
GF2
X1
GF1
EMR3000 24
G2
GFCT
G1
8
H3
X3
PF1 H2
X2
H2
H1
10
PT
SF2
1Amp
V2
V11
MB
2 4
(BLK) (WHT)
1T1
DC
COIL
2
DC
COIL
1
1T2
Cust.
Rcpt.
M
14
Ground
1 Rcpt.
120 V
ISW
X2
H2
B
Coil
Controller
(X1)
PF1
1 Amp
H1 VA X1
CPT
750
MA
12
IS2
1 Plug
120 V X1
Main
Fuse
Start
8
Amp
SF1
Start
M3
M7
M5
Ma
M2
MX
17
Stop
P1
M7
1A
Ground
Ma
ISW
G
URTD
AC
MP
19
L3
(X1)
MX
(X2)
MA
IS1
15
(X2)
50
(WHT) (BLK)
M 5
L2
ACN 32
Ground
M6
Stop
M5
Mb
M4
Ground
L1
P1
21
M8
12 Set Point
System
11 Trip Mode 1
MP
1T3
13
20
M8
12
18
M9
GND
11
16
Neutral
IQ DP-4130
V13
V2
X1 V1
H1
M9
Mb
V3
12
Ground
DP
P1
4160 Vac
60 Hz
Figure 10.1-1. Induction Motor Across-the-Line Starter, Vacuum Contactor with Optional EMR-3000 Motor Protection and
IQ Metering, Start-Stop Pushbuttons, and Red and Green Indicating Lights
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-15
Sheet 10 017
Technical Data
i
ii
MOTOR
1
T3
T1
T2
2
3
MP
G1 G2
EMR-3000
SCTB
GF12
1CG GF11
5
M9
M9
R9
R9 Mb
M8
R8
R8
M8
R7
R7
Rb
Ground
CG
X2
X1
1CT
X1 X2
X1 X2
X1
GF1
GFCT
Ground
X2
GF2
H2A
C11 H1A
C1
C21
H2B
C12 H1B
C2
C22
H2C
C13 H1C C23
25
24
C3
Ra
R6
R6
R5
R5
Rb
X3 V3
X2
PT
Ground
MB
12
SB
RB
MP
H1 X1
PF1
1 AMP
Main
Fuse
CPT
750 VA
1 PLUG
120V
MA
MX
RX
(BLK)
COIL CONTROLLER
+
(WHT)
(BLK)
+
-
(WHT)
SX
OFF
S5
Sb
M3
X1
10 (DISCRETE
R3
S5
R3
Ra
S4
R2
15
16
M7
M5
17
Ma
M7 M5
Mb
M6 M4
9 4
MP
P1
1A
P1
Figure 10.1-2. Induction Motor Reduced Voltage Autotransformer Starter, Vacuum Contactor with Optional EMR-3000 Motor Protection and
IQ Metering, Start-Stop Pushbuttons, and Red and Green Indicating Lights
CA08104001E
18
19
STOP
L1
14
X1
IN 2)
INC. SEQ.
S6
3 S4 S7
M3
START
M4
M2
2
Ground
4160 Vac
60 Hz
SA
RX
ISW
L2
RA
52
2
MP
1
51
X2
SX MX RX
Ground
X2
50
12
8 AMP
IS1
SF1 1X1 IS2 ISW
H2 X2
13
SA
RA
MP
S 5 1
12
Transition
Cust 120 V
Test Power
ACN
GND
Cust
1 RCPT
RCPT
120 V
(WHT)
(BLK)
+
-
R 5 1
DC
DC
COIL COIL
2
1
11
11
6 2
COIL CONTROLLER
M 5 1
DC
DC
COIL COIL
2
1
(WHT)
(WHT)
(BLK)
DC
DC
COIL COIL
1
2
6 2
(BLK)
80
R
L
6
1T1
(BLK)
50
65
L3
10
12
1SA
VC
VB
VA
MA
M
SF2
1 AMP
COIL CONTROLLER
1T2
50
80
R
L
V11
V1
+
-
80
R
L
V2
(WHT)
65
X1
V2
Ground
65
S
J
K
50
Autotransformer
2SA
1T3
3SA
H2
H1
V13
GND
H3
A B NEU C
DP
IQ DP-4130
G
R4
R4
20
21
July 2014
Sheet 10 018
Technical Data
T2
T1
22
20
72
31
TRPX
AUX 3
MP
30
B7
B6
71
SS2
Softstart Bypass
Position
Cont Normal Bypass
1
X
2
X
3
X
4
X
12
3
X2
SCTB
CG
MAX Run
CG1
CG1
CG
C2
Black
Blue
C1 Red
H1A H2A
C13
C22
H1B H2B
C23
C31
C32
H1C H2C
C33
Continued
from Lower
Left
TB2
EMR-3000
C31
TB3
M5
M3
B3
25
CIB
24
GND
MP
GF21
X2 GF2
G2
GF11 EMR-3000
G1
GFCT
X1
TB1
C12
C21
C21
X1
X1
MP
C11
C11
X2
Off
X1
Green
G GND
1CT
X2
RIL
White
C3
TCB
Ba
21
MAX
All Other Trip Functions Will Operate the Trip Output and Allow the
Softstart Module to Open the Circuit (Controlled Shutdown)
T3
26
23
27
MAX
24
TB8-6
MAX
TB8-5
25
ii
GF1
M3
B3
M5
Ma
Ba
Mb
M2
M4
B2
1T3
1T2
1T1
B
SCR ASSY
400 AMP
Pole ASSY
SCR ASSY
SCR ASSY
X1
H2
X2
H1
X1
11
NEU
V2
B
MP4000
V11
V1
PT
SF2
1 AMP
V13
V13 BLK
V2
V2 GRY
V11
V11 YEL
J2-4
67
J2-1
SS2
MCB
TCB
TCB
CR
Reset
C
GND
TB2-5
TB2-6
RVSS Reset
X2
H1
J2-7
V31
V3
H2
64
TB1-6
TB1-8
Start/Stop
GND
MP G
TB2-1
TB2-2
Emergency Bypass
E
F
10
66
68
CPU
*
TX
65
=
=
=
=
Remote Device
Internal Term. Blk(s)
Term. Blk. for Customer Conn.
TX Type Light
63
See MP
Programming
Notes
12
12
12
MB
BB
2
+
5
MX
MA
BX
BA
SS2
MCB
TB1-9
50
H2
1 Plug
VB
H1
VA
PF1
3 AMP
CPT
2K VA
12
69
70
3
BA
62
ISW
IS1
AMP
SS2
ISW
TCB
4
A1
Main Coil
SS2
TCB
2
TB8-7
GND
A1
TB8-9
MX
*
Start
Start
CR
55
*
Stop
CR
L3
L2
1A
L1
Ring
Transformers
Reset
2
BX
62
Bypass
Coil
EZ Relay
Timing Head .1-30SEC 54
NO/NC
TB3-11
SF1
TCB
TB3-10
Main
Fuse
15
1
19
Stop
21
S N
PHASE C
RVSS
Fault
S N
PHASE B
TRPX
MP
20
Continued
at Right
CIB
1 RCPT
X1
IS2
IS3
ISW
TCB
50
CR
TB4-3
GND
120V
TB1-1
TRPX
X2
18
TRPX
51
CUST
ACN RCPT
CUST 120V
Test Power
17
X2
RVSS
WIL
Fault
X1
15
16
Time Between
Starts Timer
(AUX5 Failsafe)
TB4-1
Mode 2
13
52
(White)
(White)
(White)
1
12
MP
TRIP
TB2-2
DC
Coil
2
TB2-1
14
(White)
DC
Coil
1
(Black)
VA
6
(Black)
+
Coil Controller
VB
DC
Coil
2
(Black)
DC
Coil
1
VC
Mode 1
1
Coil Controller
(Black)
+
-
13
MP
AUX 2
4160 VAC
60 HZ
7
1
S N
PHASE A
GND
1
Figure 10.1-3. Induction Motor Reduced Voltage Solid-State Starter, Vacuum Contactor with EMR-3000 Motor Protection, Local and Remote
Start-Stop Pushbuttons, and Local and Remote Red and Green Indicating Lights
CA08104001E
July 2014
10.1-17
Sheet 10 019
Technical Data
Table 10.1-4. Starter Maximum Continuous Current Ratings
Starter Class
Enclosure Type
NEMA 1
NEMA 12/NEMA 3R
Arc Resistant
330 top
320 top
330 bottom
320 bottom
320 top
230 top
210 top
400 bottom 1
370 bottom
350 bottom
720
650
600
300
300
N/A
ii
360 top
360 bottom
1
2
Limited acceleration time and locked rotor current. Contact Eaton for details.
Continuous
Amperes
Load-Break
Amperes
600
1200
600
1200
40
61
25
38
450
450
600
1200
80
80
50
50
600
750
600
1200
64
64
50
50
1200 2
1200
49
31
1200A rating is for NEMA 1 enclosure with vented covers. NEMA 3R/12 rating is 1000A.
4
5
6
7
8
2200 to 2500V
3000 to 3600V
3800 to 4800V
6000 to 7200V
Interrupting rating
(With 400A high interrupting contactor)
NEMA unfused (E1)
NEMA fused (E2)
8.5 kA
50 kA
8.5 kA
50 kA
8.5 kA
50 kA
8.5 kA
50 kA
Application table
Induction motor
Synchronous motor (0.8 PF)
(1.0 PF)
Transformer
Capacitor three-phase
Arcing time
Pickup voltage
Dropout voltage
Control voltages
AC
DC
Control circuit burden
Closing (AC)/(DC)
Holding (AC)/(DC)
Auxiliary contact rating
Voltage (maximum)
Continuous current
Making capacity (AC)
Making capacity (DC)
Breaking capacity (AC)
Breaking capacity (DC)
Latch (when specified)
Mechanical life
Trip voltages (DC)
Trip voltages (AC)
Minimum trip voltage
Trip burden
24 Vdc
125 Vdc
110/120 Vac
Trip time
Weight
13
14
15
9
10
11
12
600V
10A
7200 VA
125 VA
720 VA
125 VA
250,000 operations
24/125V
110/120V
80% rated coil voltage
400 VA
400 VA
400 VA
30 milliseconds
60 lbs (27 kg) (stab-in/bolt-in)
16
17
18
19
20
21
CA08104001E
July 2014
Sheet 10 020
Technical Data
i
ii
1
2
3
4
5
6
7
8
9
SJ 25V830
SJ 33V830
SJ 50V830
SJ 72V830
22002500V
30003300V
38005000V
60007200V
Interrupting rating
NEMA unfused (E1)
NEMA fused (E2)
NEMA fused (E2)
12.5 kA
200 MVA at 2300V
50 kA
12.5 kA
12.5 kA
12.5 kA
285 MVA at 3300V 408 MVA at 4600V 570 MVA at 6600V
50 kA
50 kA
50 kA
Power rating 1
Induction motor
Synchronous motor (0.8 PF)
(1.0 PF)
Transformer
Capacitor three-phase
3000 hp
3000 hp
3500 hp
2500 kVA
2400 kVAR
4000 hp
4000 hp
5000 hp
3500 kVA
3200 kVAR
12,500A
600/650/720A enclosed
800A open
Arcing time
Pickup voltage
Dropout voltage
Control voltages (AC)/(DC)
8000 hp
8000 hp
10,000 hp
6000 kVA
4800 kVAR
8000A
6400A
4320A
10,800A
86 kA peak
250,000 operations
200,000 operations
At rated current
60 kV (1.2 x 50 microseconds)
18.2 kV (1 minute)
80 milliseconds
50330 milliseconds, field
selectable
10
11
5000 hp
5000 hp
6000 hp
4500 kVA
4000 kVAR
Other power ratings are available based on the specific load data.
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-19
Sheet 10 021
Technical Data
SL12V330
SL15V330
Utilization voltage
10,00011,000V
12,40013,800V
Interrupting rating
EI (unfused)
E2 (fused)
E2 (fused)
5 kA
950 MVA at 11,000V
50 kA
5 kA
1190 MVA at 13,800V
50 kA
1
2
Induction motor
6000 hp
7500 hp
6750 hp
8500 hp
Transformer
3800 kVA at 11 kV
BIL
75 kV
95 kV (with arrestors)
Rating
Maximum voltage
15,000V
5000A
Rated current
300A enclosed
300A open
AC3make 3000
AC3break 2400
Short-time current
30 seconds
1 second
8.75 milliseconds
1800A
4500A
25 kA peak
Mechanical life
250,000 operations
Electrical life
200,000 operations
36 kV (1 minute)
Closing time
80 milliseconds
Opening time
Weight
Arcing time
Pickup voltage
Dropout voltage
Control voltages
(AC)
(DC)
2600 VA
80 VA
600V
10A
7200 VA
200 VA
720 VA
200 VA
3
4
ii
250,000 operations
24/48/96V
110/220V (50/60 Hz)
80% rated coil voltage
1200 VA
400 VA
500 VA
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
July 2014
Sheet 10 022
Technical Data
ii
1
Rated Values
Circuit
Breaker
Type
Voltage
Current
Rated
Transient
Recovery
Voltage
Current Values
Asymmetry Factor
for VCP-W Breakers
Cycles V/K
kA
kV rms rms
kA
rms
kA
Crest
Rated
Reclosing Time
2
5
E2
T2 4
Amps I
kV
mS Cycles Y
kA Crest
Sec
rms
Rated Permissible
Tripping Delay
kV
Crest
kV
rms
Rated Continuous
Current at 60 Hz
1.2 x 50
sec. Impulse
2
kV
MVA V
Class Class kV rms K
K Times Rated
Short-Circuit
Current 3 KI
Closing and
Latching
Capability
(Momentary)
Normal
Frequency
Rated Voltage
Range Factor
Rated
Maximum
Voltage
Nominal
Voltage Class
Nominal Three-Phase
MVA Class
Maximum Sym.
Interrupting
Capability
Rated Withstand
Test Voltage
3-Second Short-Time
Current Carrying
Capability
kA rms S
Assy.
50
VCP-W
250
4.16
250
4.76
1.24 19
60
1200
2000
3000
29
8.9
50
30
3.85
36
36
58
97
132 8 78 8
1.2
50
VCP-W
350
4.16
350
4.76
1.19
19
60
1200
2000
3000
41
8.9
50
30
4.0
49
49
132
78
1.2
10
75
VCP-W
500
7.2
500
8.25
1.25 36
95
1200
2000
3000
33
15.5
60
30
6.6
41
41
111
66
1.2
11
12
13
3
14
15
4
5
For reclosing service, there is No Derating necessary for Eatons type VCP-W family of circuit breakers. R = 100%. Type VCP-W breaker can perform
the O-C-O per ANSI C37.09; O-0.3s-CO-15s-CO per IEC 56; and some VCP-Ws have performed O-0.3s-CO-15s-CO-15s-CO-15s-CO; all with no derating.
Contact Eaton for special reclosing requirements.
V
For three-phase and line-to-line faults, the symmetrical interrupting capability at an operating voltage, Vo =
(Rated Short-Circuit Current)
Vo
But not to exceed KI.
V
(Rated Short-Circuit Current)
Single line-to-ground fault capability at an operating voltage, Vo = 1.15
Vo
But not to exceed KI.
The above apply on predominately inductive or resistive three-phase circuits with normal-frequency line-to-line recovery voltage equal to the
operating voltage.
4000A continuous rating is available for 5/15 kV. Contact Eaton for details.
3-cycle rating available.
Tripping may be delayed beyond the rated permissible tripping delay at lower values of current in accordance with the following formula:
(K Times Rated Short-Circuit current) 2
T (seconds) =Y
Short-Circuit Current Through Breaker
The aggregate tripping delay on all operations within any 30-minute period must not exceed the time obtained from the above formula.
Included for reference only.
Asymmetrical interrupting capability = S times symmetrical interrupting capability, both at specified operating voltage.
8 Non-standard breakers with high momentary rating available for special applications.
Notes: Contact Eaton for capacitor switching, low inductive switching, and cable charging ratings.
6
16
17
18
19
20
Table 10.1-11. VCP-W Breaker Stored Energy Mechanism Control Power Requirements
Rated
Control
Voltage
Time
(Seconds)
Close or Trip
Amperes
48 Vdc
125 Vdc
250 Vdc
9.0
4.0
2.0
6
6
6
16
7
4
120 Vac
240 Vac
4.0
2.0
6
6
6
3
UV Trip mA
(Maximum)
Voltage Range
Close
Trip
Indicating
Light
Amperes
200
80
40
3856
100140
200280
2856
70140
140280
0.35
0.35
0.35
104127
208254
104127
208254
0.35
0.35
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-21
Sheet 10 023
Technical Data
i
ii
1
2
3
4
5
6
7
Time
Contactor
Dropout
24R Fuse
Curve
8
9
Contactor
Interrupting Rating
10
Current
11
12
13
24R Fuse
Curve
Time
Contactor-Fuse Coordination
14
15
Contactor
Dropout
16
Contactor
Interrupting Rating
17
Fault Current Range
where Contactor can
Attempt to Open on a Fault
Greater than its Rating
Current
18
19
20
21
CA08104001E
July 2014
Sheet 10 024
Technical Data
ii
1
2
3
4
5
6
7
8
9
10
Protection Considerations
Coordinated with the motors
characteristics, the protective devices
in the AMPGARD starter provide motor
protection from overload to
full system capacity faults.
Ultimate Trip
Controller Maximum
Interrupting Rating
Time In Seconds
11
Instantaneous
Overcurrent
12
24R Fuse
13
14
Contactor Dropout
15
16
Asymmetrical
Offset Compensation
17
18
19
Contactor Interrupting
Capacity
Figure 10.1-6. Full Range Coordinated Protection Between Current Limiting Type CLS Fuses,
Vacuum Contactor and Motor Protection Relay
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-23
Sheet 10 025
Technical Data
Maximum FLA
Fuse Rating
CT Ratio
22.9
31.1
41.9
46.7
70-2R
70-2R
100-3R
100-3R
25:5
50:5
50:5
75:5
46.8
63.0
74.8
83.0
62.9
74.7
82.9
93.5
130-4R
150-5R
170-6R
170-6R
75:5
100:5
100:5
150:5
93.6
124.0
137.1
166.0
123.9
137.0
165.9
187.0
200-9R
200-9R
230-12R
230-12R
150:5
200:5
200:5
300:5
187.1
247.0
329.0
360.1
246.9
328.9
360.0
400.0 1
390-18R
450-24R
450-24R
450-24R
300:5
400:5
600:5
600:5
250.0
330.0
499.0
650.1
720.0
450-24R
450-24R
650-36R
800-44R
800-44R
300:5
400:5
600:5
800:5
1000:5
ii
1
2
3
4
5
6
7
Specific motor acceleration time and locked rotor current must be reviewed to ensure
24R fuse has sufficient capacity for start cycle.
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
July 2014
Sheet 10 026
Layout Dimensions
Equipment Details
3
4
5
7
8
9
10
Reversing Starter
11
12
Horsepower 1 Volts
Dimensions
Weight
Lbs (kg)
400
400
720
200,000
200,000
200,000
1
1
2
1350 (613)
1350 (613)
1700 (772)
400
400
720
200,000
200,000
200,000
3
3
4
1800 (817)
1800 (817)
2400 (1090)
400
400
720
400,000
400,000
400,000
1
1
2
1350 (613)
1350 (613)
1700 (772)
400
400
720
400,000
400,000
400,000
3
3
4
1800 (817)
1800 (817)
2400 (1090)
6600 6 400
6600 6 400
6600 6 720
570,000
570,000
570,000
1
1
2
1500 (681)
1500 (681)
1800 (817)
6600 6 400
6600 6 400
6600 6 720
570,000
570,000
570,000
3
3
4
1800 (817)
1800 (817)
2400 (1090)
Height 2 Width
Depth
Additional
Starter Spaces
ii
Specifications
Starter
Interrupting
Rating
(kVA)
Layout Dimensions
Contactor
Ampere Rating
(Enclosed)
22002400V Non-Reversing
700/800 3
1500/1750 4
3000
2300
2300
2300
22002400V Reversing
700/800 3
1500/1750 4
3000
2300
2300
2300
40004800V Non-Reversing
1250/1500 3
2500/3000 4
5500
4600
4600
4600
40004800V Reversing
1250/1500 3
2500/3000 4
5500
4600
4600
4600
6600V Non-Reversing
2000/2250 3
4000/4500 4
8000
6600V Reversing
2000/2250 3
4000/4500 4
8000
1
2
3
4
5
6
13
14
15
16
RVS
RVS
M
Arrangement 1
Arrangement 2
Arrangement 3
Arrangement 4
17
Figure 10.1-7. Starter Arrangements
18
19
20
21
CA08104001E
July 2014
10.1-25
Sheet 10 027
Layout Dimensions
1.50 (38)
3.50
(89)
1200 Amp - 4.00" X 1/Ph
4.63 (118)
Main
Bus
Ph Ph Ph
a b c
Low Voltage
Control
1.36
(35)
1.18
(30)
7.39
(188)
5.81
(148)
Low Voltage
Control
80.00
(2032)
62.00
(1575)
22.00
(559)
Load Term
Detail A
Note L
4.63 (118)
2.50
(64)
7.39 21.00
(188) (533)
22.85
(580)
30.00
(762)
36.00
(914)
Front View
2.00 (51)
Main Bus
Note C1
3.00 (76)
6.00 (152)
36.00
(914)
Top View
36.00
(914)
4.50
(114)
9.25 (235)
Note A
2.31
13.75
(58)
(349)
1.00 (25)
6.00 (152)
Note C
Note B
Gnd 1.45
Bus (37)
5.81
(148)
2.00
(51)
61.00
(1549)
ii
5.50 (140)
3.00
(76) 2.00
(51)
Load Term
Detail A
Note L
30.00
(762)
9.32 (237)
Note T
12.00
(305)
1.25
(32)
13.50
(343)
3.00 (76)
27.00
(686)
2.00
(51)
5.50 (140)
6.80 (173)
1
2
3
30.00
(762)
28.00
(711)
21.67
(550)
1.00
(25)
4.50
(114)
4
5
6
Floor Plan
Note D
Side View
Detail A
Load Terms
T1 T2 T3
4.38
4.38
(111)
(111)
Arranged Horizontally
on Rear Wall Load Panel
in Starter
Figure 10.1-8. Arrangement 1 Detail (Full Voltage 400A)See Table 10.1-20 on Page 10.1-34 for Notes
Main
Bus
Ph Ph Ph
a b c
9.32
(237)
12.00
(305)
13.50
(343)
1.25
(32)
Note E
5.50 (140)
Low Voltage
Control
80.00
(2032)
Load Term
Detail A
Note L
7.39
(188)
5.81
(148)
Gnd 1.45
Bus (37)
22.85
(580)
30.00
(762)
36.00
(914)
Front View
1.36
(35)
1.18 (30)
2.00
(51)
4.63 (118)
31.75
(806)
2.50
(64)
2.00
(51)
6.80 (173)
Note G
6.00 (152)
15
4.50 (114)
Note A
Note E
9.25 (235)
2.31
13.75
(59)
(349)
1.00 (25)
6.00 (152)
Note G
3.00 (76)
27.00
(686)
30.00
(762)
28.00
(711)
21.67
(550)
1.00
(25)
16
17
4.50 (114)
Floor Plan
Note D
18
Side View
Detail A
19
800A Starter
Figure 10.1-9. Arrangement 2 Detail (Full Voltage 800A)See Table 10.1-20 on Page 10.1-34 for Notes
CA08104001E
13
14
36.00
(914)
Top View
36.00
(914)
Load Term
T1 T2 T3
4.3
4.3
(109)
(109)
Arranged Horizontally
on Rear Wall Load Panel
in Starter
12
5.50 (140)
Main Bus
29.00
(737)
11
30.00
(762)
2.00
(51)
3.00
(76)
9
10
1.50
(38)
3.50
(89)
20
21
July 2014
Sheet 10 028
Layout Dimensions
11.50 (292.1)
1.25
(31.8)
1.50 (38.1)
ii
PH PH PH Main
A B C Bus
3.50
(88.9)
6.70 (170.2)
Main
Bus
2
Ground
Bus
24.00
(609.6)
1.00
(25.4)
36.00
(914.4)
Shipping Section 1
1500 Lbs
1.50
(38.1)
13.50
(342.9)
Elevation View
9.32
(236.7)
36.00
(914.4)
5.81
(147.5)
60.00
(1524.0)
56.43
(1433.3)
Shipping Section 1
1500 Lbs
0.90
(22.9)
Low Voltage
Control
1.85
(47.0)
7.39
(187.7)
Ground
Bus
1.45
(36.8)
30.00
(762.0)
Load Term
T1 T2 T3
5.50
(139.7)
Note E
30.00
(762.0)
6.70 (170.2)
Main Bus
Note G
3.00
(76.2) 1.36
(34.5)
6.00
(152.4)
1.18
(30.0)
80.00
(2032.0)
36.00
(914.4)
59.00
(1498.6)
Top View
2.00
(50.8)
4.50
(114.3)
22.85
(580.4)
LH Side
Sheet
1.25
(31.8)
2.00 (50.8)
2.00 (50.8)
12.00
(304.8)
Load Term
3.50
Detail A
Note L
(88.9)
15
16
4.50
(114.3)
11
14
Note A
30.00
(762.0)
Structure #1
60.00
(1524.0)
24.00
(609.6)
28.00
(711.3)
1.00
(25.4)
15.00
(381.0)
PH PH PH Main
A B C Bus
13
22.00
(558.8)
Side View
10
12
Note F
19.00
2.00
(482.6)
(50.8)
30.00
(762.0)
UNIT 2D
UNIT 1D
1
8
9
24.00
(609.6)
4.50
(114.3)
22.85
(580.3)
5
6
Top View
62.00
(1574.8)
1.45
(36.8)
Continuation of Bus
from Adjacent Structure
24.00
(609.6)
80.00
(2031.9)
0.90
(22.9)
30.00
(762.0)
27.50
(698.5)
5.50
(139.7)
Note F
12.00
(304.8)
2.50
(63.5)
1.00
(25.4)
13.75
(349.3)
Note E
36.00
(914.4)
9.25
(235.0)
Note A
28.00
2.31
(58.7) 1.00 21.67 (711.3) 30.00
(762.0)
(25.4) (550.5)
Note G
2.92 (74.2)
17
18
Side View
4.38 (111.3)
4.38 (111.3)
2.00
(50.8)
6.00
(152.4)
3.00
(76.2)
Arranged Horizontally
on Rear Wall Load
Panel in Starter
4.50
(114.3)
Detail A
19
27.00
(685.9)
Structure #2
Figure 10.1-10. Arrangement 1 Detail (Full Voltage 15 kV)See Table 10.1-20 on Page 10.1-34 for Notes
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-27
Sheet 10 029
Layout Dimensions
Specifications
400
400
720
200,000
200,000
200,000
1
1
2
80 (2032)
80 (2032)
80 (2032)
72 (1829)
72 (1829)
72 (1829)
30 (762)
30 (762)
30 (762)
2800 (1271)
2800 (1271)
4000 (1816)
400
400
720
200,000
200,000
200,000
3
3
4
80 (2032)
80 (2032)
80 (2032)
72 (1829)
72 (1829)
72 (1829)
30 (762)
30 (762)
30 (762)
3250 (1476)
3250 (1476)
4650 (2111)
400
400
720
400,000
400,000
400,000
1
1
2
80 (2032)
80 (2032)
80 (2032)
72 (1829)
72 (1829)
72 (1829)
30 (762)
30 (762)
30 (762)
2800 (1271)
2800 (1271)
4000 (1816)
400
400
720
400,000
400,000
400,000
3
3
4
80 (2032)
80 (2032)
80 (2032)
72 (1829)
72 (1829)
72 (1829)
30 (762)
30 (762)
30 (762)
3250 (1476)
3250 (1476)
4650 (2111)
6600
6600
6600
400
400
720
570,000
570,000
570,000
1
1
2
80 (2032)
80 (2032)
80 (2032)
72 (1829)
72 (1829)
72 (1829)
30 (762)
30 (762)
30 (762)
3300 (1498)
3300 (1498)
4650 (2111)
6600
6600
6600
400
400
720
570,000
570,000
570,000
3
3
4
80 (2032)
80 (2032)
80 (2032)
72 (1829)
72 (1829)
72 (1829)
30 (762)
30 (762)
30 (762)
3250 (1476)
3250 (1476)
4650 (2111)
700/800 4
1500/1750 5
3000
2300
2300
2300
700/800 4
1500/1750 5
3000
2300
2300
2300
ii
1
2
3
4
40004800V Non-Reversing
1250/1500 4
2500/3000 5
5500
4600
4600
4600
40004800V Reversing
1250/1500 4
2500/3000 5
5500
4600
4600
4600
6600V Non-Reversing
2000/2250 4
4000/4500 5
8000
2000/2250 4
4000/4500 5
8000
2
3
4
5
Run
Contactor
Run
Contactor
5
6
7
8
Reactor
Reactor
M
Arrangement 2
Arrangement 3
Run
Contactor
M
Reversing Reactor
Contactor
12
13
14
Arrangement 4
15
17
18
%
%
%
%
Motor Motor Line
Torque
Voltage Current Current
80
65
50
11
16
80
65
50
Reversing
Reactor
Contactor
9
10
Run
Contactor
Starting Characteristics
Depth
22002400V Reversing
Arrangement 1
80
80% tap
65% tap 1 65
50% tap
50
Width
22002400V Non-Reversing
Starter
Type
Height 3
6600V Reversing
Reversing Starter
Weight
Lbs (kg)
Equipment
Arrangement
Number
Dimensions
Starter
Interrupting
Rating (kVA)
Volts
Contactor
Ampere Rating
(Enclosed)
Horsepower 2
19
64
42
25
20
21
July 2014
Sheet 10 030
Layout Dimensions
i
ii
13.50
(343)
1.50
(38)
3.50
(89)
Main
Ph Ph Ph Bus
a b c
7.39
(188)
80.00
(2032)
61.00
(1549)
4
5
22.00
(559)
5.81
(148)
Front View
30.00
(762)
3.00 (76)
36.00
(914)
22.85
(580)
2.50
(64)
1.00 (25)
6.00 (152) 21.67
Note G (550)
27.00
(686)
Side View
8
RVNR 400A Starter w/Main Bus 1200A
Top View
28.00
(711)
2.00
(51)
30.00
(762)
5.50 (140)
5.50 (140)
6.80 (173)
Note G
36.00
(914)
4.50
(114)
61.00
(1549)
Gnd 1.45
Bus (37)
2.00 (51)
Main Bus
Load Term
4.38 (111)
4.38 (111)
2.92 (74)
9.32
(237)
Note L1
12.00
(305) 2.88 2.00
(73) (51)
1.70
(43)
1.00 (25)
Low Voltage
Control
Load Term
T1 T2 T3
1.25
(32)
36.00
(914)
36.00 (914)
27.00 (686)
4.50 2.00 (51)
(114)
Note E
13.75
(349)
4.63
(118)
1.00 (25)
2.31 (59)
1.00 (25)
Note A
28.00
(711)
1.00
(25)
30.00
(762)
4.50
(114)
Floor Plan
Note D
Figure 10.1-12. Arrangement 1 Detail (Reduced Voltage, 400A)See Table 10.1-20 on Page 10.1-34 for Notes
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-29
Sheet 10 031
Layout Dimensions
Starting Characteristics
Starter
Type
Reversing Starter
One additional magnetic contactor
(duplicate of above), both contactors are
mechanically and electrically interlocked.
80% tap
80
65% tap 1 65
50% tap
50
1
80
65
50
67
45
28
64
42
25
Specifications
Volts
Dimensions
Weight
Lbs (kg)
200,000
200,000
200,000
1
1
2
3100 (1407)
3100 (1407)
4800 (2179)
200,000
200,000
200,000
3
3
4
3650 (1657)
3650 (1657)
5650 (2565)
400,000
400,000
400,000
1
1
2
3100 (1407)
3100 (1407)
4800 (2179)
400,000
400,000
400,000
3
3
4
3650 (1657)
3650 (1657)
5650 (2565)
6600 400
6600 400
6600 720
570,000
570,000
570,000
1
1
2
3100 (1407)
3100 (1407)
4800 (2179)
6600 400
6600 400
6600 720
570,000
570,000
570,000
3
3
4
3650 (1657)
3650 (1657)
5650 (2565)
Height 3 Width
Depth
Number of
Structures
Equipment
Arrangement
Number
ii
%
%
%
%
Motor Motor Line
Torque
Voltage Current Current
Starter
Interrupting
Rating
(kVA)
Contactor
Ampere Rating
(Enclosed)
Reduced Voltage
Autotransformer Starters
Catalog S610 Non-Reversing
Catalog S810 Reversing
4
5
22002400V Non-Reversing
700/800 4
1500/1750 5
3000
2300 400
2300 400
2300 720
22002400V Reversing
700/800 4
1500/1750 5
3000
2300 400
2300 400
2300 720
40004800V Non-Reversing
1250/1500 4
2500/3000 5
5500
4600 400
4600 400
4600 720
40004800V Reversing
1250/1500 4
2500/3000 5
5500
4600 400
4600 400
4600 720
8
9
10
11
6600V Non-Reversing
2000/2250 4
4000/4500 5
8000
12
6600V Reversing
2000/2250 4
4000/4500 5
8000
2
3
4
5
14
15
Short
Run
Auto
Transformer
Arrangement 1
16
Short
Short
Auto
Transformer
Run
M
Arrangement 2
Run
Rev
Auto
Transformer
Arrangement 3
13
Short
M
Rev
Auto
Transformer
17
Run
Arrangement 4
18
19
20
21
July 2014
Sheet 10 032
Layout Dimensions
2
3
4
6
7
8
9
10
11
Reversing Starter
One additional magnetic contactor
(duplicate of above), both contactors
are mechanically and electrically
interlocked.
12
13
14
15
16
17
18
19
Height
Depth
Weight
Lbs (kg)
23
22002400V Non-Reversing
700/800 4
900/1000 4 2300 400
1500/1750 5 1750/2000 5 2300 400
3000
3500
2300 720
200,000 1
200,000 1
200,000 2
200,000 3
200,000 3
200,000 4
400,000 1
400,000 1
400,000 2
400,000 3
400,000 3
400,000 4
570,000 1
570,000 1
570,000 2
570,000 3
570,000 3
570,000 4
22002400V Reversing
900/1000 4 2300 400
700/800 4
1500/1750 5 1750/2000 5 2300 400
3000
3500
2300 720
40004800V Non-Reversing
1250/1500 4 1500/1750 4 4600 400
2500/3000 5 3000/3500 5 4600 400
5500
6000
4600 720
40004800V Reversing
1250/1500 4 1500/1750 4 4600 400
2500/3000 5 3000/3500 5 4600 400
5500
6000
4600 720
6600V Non-Reversing
2000/2250 4 2500/2750 4 7200 400
4000/4500 5 5000/5500 5 7200 400
8000
10,000
7200 720
6600V Reversing
2000/2250 4 2500/2750 4 7200 400
4000/4500 5 5000/5500 5 7200 400
8000
10,000
7200 720
1
2
3
4
5
Field
Panel
Field
Panel
Field
Panel
Field
Panel
Equipment
Arrangement
Number
Starter
Interrupting
Rating (kVA)
ii
Contactor
Ampere Rating
(Enclosed)
Rev
Rev
Arrangement 1
Arrangement 2
Arrangement 3
Arrangement 4
When the field panel requirement exceeds 88A at 125 Vdc or 44A at 250 Vdc, an auxiliary structure
36.00 inches (914.4 mm) wide is required.
Mounting location of exciter transformer when field panel requirement exceeds 88A at 125 Vdc or
44A at 250 Vdc. Otherwise compartment is blank.
20
21
CA08104001E
July 2014
10.1-31
Sheet 10 033
Layout Dimensions
25.0
(635)
Starting &
Discharge res.
1.50
(38)
13.50
(343)
4.63 (118)
Note E
12.25
(311)
3.50
(90)
1000 Amp - 3.00" X 1/Ph
Ph Ph Ph
a b c
Main
Bus
DC Field
Conn's MTD
on rh Side
3.00
(76) 2.00
(51)
80.00
(2032)
Load Term
Detail A
Note L
Low Voltage
Control
36.00
(914)
Front View
30.00
(762)
5.50
(140)
5.50
(140)
6.80
(173)
2.00 (51)
Main Bus
1.18
(30)
5.81
(148)
ii
12.00
(305)
1.36 (35)
22.00
(559)
1.25 (32)
4.13
(105)
Note G
Gnd
Bus
7.39
(188)
1.45
(37)
22.85
(580)
30.00
(762)
Side View
21.00
(533)
2.50
(64)
2
3
3.00 (76)
36.00
(914)
Top View
36.00
(914)
4.50
(114)
Note E
Note A
7.13 (181)
2.31
(59)
13.75 (349)
1.00 (25)
6.00 (152)
Note G
30.00
(762)
28.00
(711)
21.67
(550)
1.00
(25)
6
7
8
2.00
(51)
27.00
(686)
4.50
(114)
Floor Plan
Note D
9
10
Detail A
Load Term
T1 T2 T3
4.38 (111)
4.38 (111)
Arranged Horizontally
On Rear Wall Load Panel
in Starter
11
Synchronous Starter
1000A Main Bus
12
13
Figure 10.1-15. Arrangement 1 Detail (400A, Synchronous)See Table 10.1-20 on Page 10.1-34 for Notes
14
15
16
17
18
19
20
21
CA08104001E
July 2014
Sheet 10 034
Layout Dimensions
Equipment Details
Mounted in the Medium Voltage Sections
ii
1
2
4
5
8
9
11
12
Horsepower 12
SCR/Contactor
Ampere Rating
Starter Interrupting
Rating (AIC)
Dimensions
Height 3
Width 4
Depth
Add. Starter
Spaces
Weight
Lbs (kg)
2300
2300
1500
3000
400
720
50,000
50,000
92.00 (2336.8)
92.00 (2336.8)
36.00 (914.4)
72.00 (1828.8)
30.00 (762.0)
30.00 (762.0)
0
0
2000 (908)
4000 (1816)
3300
3300
1800
3600
400
720
50,000
50,000
92.00 (2336.8)
92.00 (2336.8)
36.00 (914.4)
72.00 (1828.8)
30.00 (762.0)
30.00 (762.0)
0
0
2000 (908)
4000 (1816)
4160
4160
2500
5000
400
720
50,000
50,000
92.00 (2336.8)
92.00 (2336.8)
36.00 (914.4)
72.00 (1828.8)
30.00 (762.0)
30.00 (762.0)
0
0
2000 (908)
4000 (1816)
1
2
13
10
3
4
14
15
16
17
18
19
20
21
CA08104001E
July 2014
10.1-33
Sheet 10 035
Layout Dimensions
PH PH PH Main
A B C Bus
Load Term
Detail A
Note: L
12.00
(305.0)
5.81
(148.0)
POWER
RUN
ALARM
TRIP
62.00
(1575.0)
Low
Voltage
Control
13.50
(343.0)
9.32
Note: E
3.00 2.00
(76.2) (51.0)
3.50
(89.0)
1.36
(345.4)
1.18
(30.0)
80.00
(203.2)
61.00
(155.0)
2.00
(51.0)
36.00
(914.4)
22.85
(580.4)
2.50
(64.0)
2.00 (51.0)
5.50
(140.0)
5.50
(140.0)
6.80
(173.0)
30.00
(762.0)
36.00
(914.4)
1
2
Note: C1
3.00
(76.2)
6.00 (152.4)
36.00
(914.4)
Top View
3
4
4.50
(114.3)
Note: A
Note: E
1.00
(25.4)
6.00 (152.4)
Note: G
2.00
(51.0)
30.00
(762.0)
For seismic installations, mount a
minimum of 6.00 inches (152.4 mm)
from wall.
ii
4.10 (104.1)
10.00
(254.0)
Ground
Bus
1.45
(36.8)
1.25
(32.0)
Main Bus
Low
Voltage
Control
7.39
Ground
(188.0)
Bus
1.45
(36.8)
1.50
(38.1)
28.00
(711.2)
1.00
(25.4)
30.00
(762.0)
6
7
8
3.00 (76.2)
27.00
(686.0)
4.50
(114.3)
9
10
Side View
Floor Plan
Figure 10.1-16. Arrangement Detail (400A Solid-State Reduced Voltage)See Table 10.1-20 on Page 10.1-34 for Notes
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
July 2014
Sheet 10 036
Layout Dimensions
Description
Cable Notes
ii
1
Load connection is designed for maximum of one 350 kcmil or two 4/0.
Load connection is designed for maximum of one 750 kcmil or two 500 kcmil.
Arrangement Notes
0.875 dia. typical 4 holes. Mounting studs to extend a maximum of 2.00 inches (50.8 mm) above grade.
HV conduit space, load cables for two-high starters. Cables for lower starter enter in front half of conduit space, and cables for upper starter enter
in rear half.
B1
HV conduit space, line and load cables for bottom entry stand-alone starters. Line cables should enter in rear half of conduit space,
and load cables should enter in front half of conduit space.
LV conduit space for two-high starters with bottom entry control conduit. Control wiring for upper starter should enter in left half of conduit space,
and lower starter control wiring should enter in right half of conduit space.
C1
LV conduit space for two-high starters with top entry control conduit. Control wiring for upper starter should enter in right half of conduit space,
and lower starter control wiring should enter in left half of conduit space.
90 door swing requires 12.00 inches (304.8 mm) for 12.00-inch (304.8 mm) wide structure, 18.00 inches (457.2 mm) for 18.00-inch (457.2 mm) wide
structure, 24.00 inches (609.6 mm) for 24.00-inch (609.6 mm) wide structure, 36.00 inches (914.4 mm) for 36.00-inch (914.4 mm) wide structure and
40.00 inches (1016.0 mm) for 40.00-inch (1016.0 mm) wide structure.
7
8
9
10
F1
HV conduit space, line only. Line cables to enter in rear half of conduit space only.
Load terminations located on rear wall of starter mounted on a load panel. Terminations are arranged horizontally from left to right. T1, T2, T3
left to right at 4.38-inch (111.3 mm) centers.
L1
Load terminations located on rear wall of reduced voltage enclosure mounted on a load panel. Terminations are arranged horizontally
from left to right. T1, T2, T3 left to right at 4.38-inch (111.3 mm) centers.
HV conduit space, load cables for two-high starters. Cables for lower starter enter in rear half of conduit space, and cables for upper starter enter
in front half.
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-35
Sheet 10 037
Layout Dimensions
i
ii
5.50
(139.7)
PH PH PH MAIN
A B C BUS
2.00 (50.8)
6.70
MAIN BUS (170.2)
Note
C1
3.00
(76.2)
1.36
6.00
(34.5) (152.4)
1.18
(30.0)
12.00
(304.8)
30.00
(762.0)
2.00 (50.8)
3.00
(76.2)
36.00
(914.4)
Top View
3.50
(88.9)
36.0
(914.4)
2.00
(50.8)
4.50
(114.3)
80.00
(2,032.0)
Unit 1B
Unit 2B
7.75
(196.9)
1.45
(36.8)
GND
BUS
Unit 1D
30.00
28.00 (762.0)
(711.2)
Note F
0.90
(22.9)
Unit 2C
34.00
(863.6)
19.00
(482.6)
Line
Term
59.00
(1,498.6)
7
27.00
(685.8)
4.50
(114.3)
Unit 2D
1
36.00
(914.4)
24.00
(609.6)
22.85
(580.4)
30.00
(762.0)
60.00
(1,524)
21.00
(533.4)
1.25
(31.8)
5.50
(139.7)
30.00
5.50 (762.0)
(139.7)
12.00
(304.8)
2.00 (50.8)
6.70
(170.2)
MAIN BUS
12
24.00
(609.6)
13
Top View
80.00
(2,032.0)
2.00
(50.8)
30.00
(762.0)
0.90
(22.9)
GND
BUS
5.81
(147.6)
1.45
(36.8)
22.85
(580.4)
30.00
(762.0)
Side View Structure 2
19.00
(482.6)
10
11
2.00
(50.8)
3.50
(88.9)
1.00
(25.4)
1.00
(25.4)
24.00
(609.6)
24.00
(609.6)
14
4.50
(114.3)
22.00
(558.8)
30.00
(762.0)
15
28.00
(711.2)
1.00
(25.4)
1.00
(25.4)
15.00
(381.0)
16
17
4.50
(114.3)
18
Figure 10.1-17. Incoming LBS, Bottom Entry up to 450A Fuse, Unfused with Metering Section
19
20
21
CA08104001E
July 2014
Sheet 10 038
Layout Dimensions
ii
PH PH PH MAIN
A B C BUS
12.00
(304.8)
1.25
(31.8)
33.00
(838.2)
1.50
(38.1)
5.50
(139.7)
9.32
(236.7)
3.50
(88.9)
2.00
(50.8)
36.00
(914.4)
Top View
80.00
(2,032.0)
36.00
4.50 (914.4)
(114.3)
2.00
(50.8)
4
Unit 2B
GND
BUS
Unit 3B
34.00
(863.6)
19.00
(482.6)
1.45
(36.8)
Note F
1.00
(25.4)
1.00
(25.4)
27.00
(685.8)
22.85
(580.4)
30.00
(762.0)
Unit 3C
6
7
8
36.00
(914.4)
Unit 2D
4.50
(114.3)
36.00
(914.4)
3
24.00
(609.6)
NOTE C1
PH PH PH MAIN
A B C BUS
96.00
(2,438.4)
12.00
(304.8)
36.00
(914.4)
Top View
(30.0)
80.00
(2,032.0)
0.90
(22.9)
11
12
36.00
4.50 (914.4)
(114.3)
2.00
(50.8)
Line
Term
7.75
(196.9)
GND 1.45
BUS (36.8)
34.00
(863.6)
19.00
(482.6)
24.00
(609.6)
1.00
(25.4)
27.00
(685.8)
4.50
(114.3)
PH PH PH MAIN
A B C BUS
14
28.00
(711.2)
30.00
1.00
(762.0)
(25.4)
Note F
22.85
(580.4)
30.00
(762.0)
13
5.50 (139.7)
2.00 (50.8)
1.36
(34.5) 1.18
59.00
(1,498.6)
30.00
(762.0)
2.00 (50.8)
3.00
(76.2)
3.50
(88.9)
9
10
5.50
(139.7)
Unit 3D
2
12.00
(304.8)
1.50
(38.1)
9.32
(236.7)
1.25
(31.8)
5.50
(139.7)
30.00
(762.0)
2.00 (50.8)
2.00 (50.8)
3.50
(88.9)
15
28.00
(711.2) 30.00
(762.0)
30.00
(762.0)
6.70
(170.2)
MAIN BUS
2
3
5.50
(139.7)
2.00 (50.8)
MAIN BUS
24.00
(609.6)
5.50 (139.7)
6.70 (170.2)
Top View
16
80.00
(2,032.0)
2.00
(50.8)
17
5.81
30.00
(762.0) (147.6)
18
0.90
(22.9)
19
GND 1.45
BUS (36.8)
22.85
(580.4)
30.00
(762.0)
19.00
(482.6)
24.00
(609.6)
4.50
(114.3)
22.00
(558.8)
1.00
(25.4)
28.00
(711.2) 30.00
1.00
(762.0)
(25.4)
15.00
(381.0)
4.50
(114.3)
20
Figure 10.1-18. Incoming LBS, Bottom Entry, 600E/750E/1100E/1350E Fused with Metering Section
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-37
Sheet 10 039
Layout Dimensions
i
ii
1
10.25
(260.4)
5.27
(133.9) 1.50
(38.1)
PH PH PH MAIN
A B C BUS
12.00
(304.8)
2
1.25
(31.8)
8.25
(209.6)
3.00
1.36 (76.2)
(34.5)
1.45
(36.8)
5.50
(139.7)
30.00
(762.0)
6.70
(170.2)
MAIN BUS
3.00 (76.2)
6.00 (152.4)
Note C1
1.18
(30.0)
36.00
(914.4)
80.00
(2,032.0)
6
7
0.90
(22.9)
1.45
(36.8)
2.00
(50.8)
GND
BUS
Unit 1D
22.85
(580.4)
30.00
(762.0)
1
Side View
36.00
(914.4)
4.50
(114.3)
9.00
(228.6)
19.50
(495.3)
28.00
(711.2)
36.00
(914.4)
Shipping Section 1 - 1200 lbs.
Top View
59.00
(1,498.6)
Unit 1B
2.00 (50.8)
3.50
(88.9)
GND
BUS
3
5.50
(139.7)
24.50
(622.3)
1.00
(25.4)
1.00
(25.4)
27.00
(685.8)
Floor Plan Note D
30.00
(762.0)
10
11
4.50
(114.3)
12
13
14
15
16
17
18
19
20
21
CA08104001E
July 2014
Sheet 10 040
Layout Dimensions
ii
Notes:
For non-seismic installations, mount a
minimum of 3.00 inches (76.2 mm) from wall.
39.06
(992.1)
3
4
5.90
(149.9)
5.90
(149.9)
5.90
(149.9)
24.20
(614.7)
24.20
(614.7)
Flap Assy.
5.90
(149.9)
21.06
(534.9)
121.78
(3093.2)
Wall
See Notes
97.36
(2472.9)
7
8
1
2
5.50
(139.7)
5.50
(139.7)
10
Low Voltage
Conduit
Side
Covers
12
1.85
(47.0)
13
5.81
(147.6)
Unit 1B
Unit 2B
62.00
(1574.8)
15
Unit 1D
1
Unit 2D
2
36.00
(914.4)
36.00
(914.4)
72.00
(1828.8)
17
Elevation View
18
21
PH
B
PH
C
TYP
1.45
(36.8)
1.85
(47.0)
22.00
(558.8) 5.81
(147.6)
Ground Bus
7.15
(181.6)
3.50
(88.9)
27.48
(698.0)
Load Term
Detail A
Note L
0.85
(21.6)
Rear
Sprt
3.00
9.39 (76.2)
(238.5)
80.00
(2032.0)
27.48
(698.0)
50.09
(1272.3)
51.09
(1297.7)
2.00
(50.8)
36.00
(914.4)
36.00
(914.4)
21.00
(533.4)
2.31
(58.7)
4.50
(114.3)
1.45
(36.8)
5.80
(147.3)
Top View
61.00
(1549.4)
4.63
(117.6)
9.25
(235.0)
13.75
(349.3)
Note X
2.50 1.00
18.66 (63.5) (25.4) 6.00
(152.4)
(474.0)
Note C
3.00
(76.2)
27.00
(685.8)
Note A
50.09
(1272.3)
At
Floor
Level
28.00
(711.2)
21.67
30.00
(550.4)
(762.0)
1.00
(25.4)
4.50
(114.3)
Floor Plan
Note D
Structure #2
49.24
(1250.7)
Note G
1.41
(35.8)
2.00
(50.8)
Structure #1
Main
Bus
Note T
20.77
(527.6)
Main
Bus
Load Term
Detail A
Note L
2.00
(50.8)
127.74
(3244.6)
Side View
19
20
PH
A
8.95
(227.3)
Ground Bus
14
16
5.93
(150.6)
Low Voltage
Control
Side
Covers
Low Voltage
Control
11
13.80
(350.5)
1.21
(30.7)
Cable Chimney
Through Plenum
Plenum Ships
Separately
51.09
(1297.7)
Rear supports
protrude 1.00"
from rear.
Consider this
dimension
before locating
equipment.
Figure 10.1-20. 50 kA Arc-Resistant, 24.00-Inch (609.6 mm) Incoming Cable Section and Two-High 400A Starter Section
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-39
Sheet 10 041
Layout Dimensions
i
31.12
(790.4)
11.00
(279.4)
10.00 MAIN
(254.0) BUS
Low Voltage
Compartment
11.50
(292.1)
Low
Voltage
Wireway
PH
A
PH PH PH
C B A
6.50
(165.1)
GND
90.00
(2286.0)
20.64
(524.3)
36.63
(930.4)
High Voltage
Access
Removable
Barrier
Customer
29.55
Terminal
(750.6)
Block
Low Voltage Wireway
GND
BUS
24.62
(625.3)
Unit 1B
Unit 2C
Unit 2F
1
26.00
(660.4)
4
36.00
(914.4)
1.50
(38.1)
9.32
(236.7)
1.63
(41.4)
Unit 4D
3
2
36.00
(914.4)
6.25
(158.8)
3.00
(76.2)
Note G
4.00
(101.6)
31.12
(790.4)
PH B
102.00
(2590.8)
Shipping Section 1 7900 lbs.
PH A
11.88
(301.8)
HV Conduit
Area
22.00
(558.8)
Vented
Compartment
16.00
(660.4)
30.00
(762.0)
1.18
(30.0)
5.00
(127.0)
Note A
60.00
(1,524)
22.00
(558.8)
1.85
(47.0)
5.81
(147.6)
62.00
(1574.8)
1.85
(47.0)
1.25
(31.8)
2.00
(50.8)
22.00
(558.8)
57.00
(1447.8)
HV Conduit
Area
LV Conduit
Area
Front
2.75
(69.9)
26.00
(660.4)
3.00
(76.2)
1.00
(25.4)
5.00
(127.0)
36.00
(914.4)
Aux. Compt.
Door
(Note D)
10
12.00
(304.8)
11
3.50
(88.9)
7.39
(187.7)
80.00
(2032.0)
61.00
(1549.4)
Load Term
Detail A
Note L
1.45
(36.8)
7.39
(187.7) 21.00
(533.4)
12
13
14
15
22.00
(558.8)
30.00
(762.0)
3.00 (76.2)
0.00
(0.00)
1.45
GND (36.8)
BUS
GND
BUS
11.25
(285.8)
1.25 (31.8)
0.00 (0.00)
Load Term
Detail A
Note L
5.81
(147.6)
36.00
(914.4)
PH PH PH MAIN
A B C BUS
Low
Voltage
Control
36.00
(914.4)
26.00
(660.4)
6.70
(170.2)
Top View
Front
5.50
(139.7)
6.00
(152.4)
3.00
(76.2)
2.00
(50.8)
30.00
(762.0)
5.50
(139.7)
2.00
(50.8)
3.00
(76.2)
1.36
(34.5)
6.00
(152.4)
40.00
(1016.0)
MAIN BUS
11.00
(279.4)
Top View
26.00
(660.4)
1.25
(1.8)
13.50
(342.9)
Note T
60.00
(1524.0)
MAIN BUS
5.00
(127.0)
4.63
(117.6)
2.00
(50.8)
Note C1
3.00
(76.2)
PH C
14.00
(355.6)
24.62
(625.3)
60.00
(1524.0)
6.00
(152.4)
1.50
(38.1)
Unit 1F
GND
BUS
36.00
(914.4)
26.00
(660.4)
52
3.00
(76.2)
26.00
(660.4)
Unit 4B
Customer
Terminal
Block
3.00
(76.2)
60.00
(1524.0)
Unit 1C
90.00
(2286.0)
Main Breaker
Compartment
51.20
(1300.5)
39.63
(1006.6)
Disc SW
(if reqd.)
17.00
(431.8)
14.87
(377.7)
51.20
(1300.5)
6.50
(165.1)
11.50
(292.1)
6.50
(165.1)
Access
Panels
Incoming
Cable
Termination
Disc SW
(if reqd.)
17.00
(431.8)
10.00
(254.0)
Front
Front
Line Termination
Mounted on RH Side
ii
PH PH MAIN
BUS
B C
Upper Compt.
Door
(Note D)
2.00
4.63
(50.8)
(117.6)
Floor Plan
4.50
(114.3)
1.00
(25.4)
16
Note A
17
9.25
(235.0)
Note B
Incoming Cable
Terminal Adapter
Side View
36.00
(914.4)
30.00
(762.0)
2.31
(58.7)
13.75
(349.3)
6.00
(152.4)
1.00
(25.4)
21.67
(550.4)
28.00
(711.2)
18
Note C
2.00
(50.8)
2.50
(63.5)
3.00
(76.2)
27.00
(685.8)
Floor Plan
Note D
4.50
(114.3)
19
20
Figure 10.1-21. AMPGARD Main Breaker and Two-High 400A Starter Section
21
CA08104001E
July 2014
Sheet 10 042
Layout Dimensions
ii
PH PH PH Main
A B
C Bus
12.00
(304.8)
1.25
(31.6)
9.32
(236.7)
5.50
(139.7)
3.50
(88.9)
5.50
(139.7)
2.00
(50.8)
2.00
(50.8)
6.70
(170.2)
MAIN BUS
30.00
(762.0)
24.00
(609.6)
Top View
80.00
(2032.0)
4
5
24.00
(609.6)
4.50
(114.3)
2.00
(50.8)
30.00
(762)
5.81
(147.6)
0.90
(22.9)
30.00
1.00 (762.0)
(25.4)
15.00
(381.0)
30.00
(762.0)
28.00
(711.2)
1.00
(25.4)
22.85
(580.4)
Unit 1B
22.00
(558.8)
19.00
(482.6)
1.45
GND
(36.8)
BUS
4.50
(114.3)
Unit 1C
Continuation of
Bus From Adjacent
Structure
10
Unit 1D
11
12
1
24.00
(609.6)
PH PH PH MAIN
A B
C BUS
Un it 2D
2
24.00
(609.6)
12.00
(304.8)
11.50
(292.1)
1.50
(38.1)
30.00
(762.0)
5.50
(139.7)
5.50
(139.7)
6.70
(170.9)
3.50
(88.9)
48.00
(1219.2)
Shipping Section 1 - 850 lbs.
1.25
(31.8)
Note F
27.50
(698.5)
MAIN BUS
24.00
(609.6)
13
14
Top View
80.00
(2032.0)
0.90
(22.9)
62.00
(1574.8)
2.00
(50.8)
15
16
17
18
24.00
(609.6)
4.50
(114.3)
Note F
GND
BUS
1.45
(36.8)
19.00
(482.6)
22.85
(580.4)
30.00
(762.0)
Side View Structure 2
22.00
(558.8)
1.00
(25.4)
Note A
15.00
(381)
28.00
(711.2)
30.00
(762.0)
1.00
(25.4)
4.50
(114.3)
19
Figure 10.1-22. 24.00-Inch (609.6 mm) Incoming Cable Section with 24.00-Inch (609.6 mm) Metering Section (for Right End of Lineup)
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.1-41
Sheet 10 043
General Description
AMPGARD XP3
i
ii
1
2
3
4
AMPGARD XP3
General Description
For 6.9 kV applications and below,
a premium version of the AMPGARD
offering is available and identified as
AMPGARD XP3. A contactor mounted
Motor Protection and Contactor Controller (MPCC) and a door mounted
Starter Display Module (SDM) replace
the typically supplied motor protection
relay. An encapsulated Sensor Module
with Rogowski Coils and Voltage Dividers
(also contactor mounted) replace the
standard current transformers (CTs)
and potential transformers (PTs).
5
6
7
8
9
I/O Modules
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
July 2014
Sheet 10 044
General Description
i
ii
Protection
1
2
3
4
5
6
10
11
Monitor/meter
12
13
14
Stall/speed Sw (14)
Reduced voltage start sequence (19)
Undervoltage (27)
Reverse power (32)
Jam
Acceleration time
Over torque (32)
Contactor quick trip (34)
Undercurrent (37)
Under power (37)
Bearing RTD (38) (optional)
Contactor condition monitor (39C)
Current balance (46)
Phase reversal (47)
Incomplete sequence (48)
Thermal overload (49)
Stator RTD (49T) (optional)
Instantaneous overcurrent (50)
Time overcurrent (51)
Ground overcurrent (50/51G)
Power factor (55)
Overvoltage (59)
Starts/time (66)
Time between starts (66)
Alarm relay (74)
Fuse fatigue/fuse damage alarm (74F)
Frequency (81)
Lockout (86)
Differential (87) (optional)
Control voltage
Watts
Vars
Power factor
Frequency
Energy
Run time
Number of starts
Number of trips
Mega-watt hours (total accumulated)
Available fault current
Incident energy
Contactor pickup voltage
Contactor dropout voltage
Loss of vacuum detection
Motor thermal life
Motor thermal capacity used
Enhanced Features
Contactor-Fuse Coordination Quickly
Clears Faults
If fault current is less than the contactor
interrupting rating, the contactor will
open without delay (approx. 20 milliseconds). If fault is greater than the
contactor interrupting rating, the
contactor will stay closed until fuse
blows (up to 130 milliseconds). Fault is
removed up to 110 milliseconds faster
than with a conventional starter.
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
CA08104001E
E-STOP
Mb
M5
M7
*
STOP
*
START
M4
M6
Ma
MA
FIBER
SDM
PORT
1 15 AMP
PUSH/PULL
IS4
I/O 1
M5
1-7
1-5
IS5
GND
PSM1
M7
IS5
6
12
M3
Ma
M2
ISW
9
10
(BLK) DC (WHT)
COIL +
2
RIL
X2
GIL
X2
1-7 1-8
1-5 1-6
DIN 3
DIN 2
1-1 1-2
DIN 0
X1
STOP
X1
RUN
1-3 1-4
DIN 1
MB
TO SM
ACN
CUST
RCPT
CUST 120V
TEST POWER
+ DC
COIL
(WHT)
(BLK)
1
MPCC
1-3
120V
GND
X2
1 PLUG
12
ISW IS2 X1
CPT
750 VA
VB
H2
H1
PF1
1 AMP
VA
MAIN
FUSE
1 RCPT
SF1 IS1 ISW IS3
GND
ISW
12
12
12
TO MPCC
GND
SM
2-3
2-4
2-4
2-4
2-5
DOUT 1
1T1
1T2
1T3
2-6
= PLC INPUT
= PLC OUTPUT
2-5
2-7
2-7
2-7
2-8
DOUT 2
ALARM STATUS
INDICATOR
FOR CUSTOMER USE
2-6
DOUT 2
= REMOTE DEVICE
= INTERNAL TERM. BLK(S)
= TERM. BLK. FOR CUSTOMER CONN.
TX = TX TYPE LIGHT
FAULT STATUS
INDICATOR
FOR CUSTOMER USE
2-3
DOUT 1
2-8
4-3
4-4
4-4
4-4
4-5
DOUT 4
RUN STATUS
INDICATOR
FOR CUSTOMER USE
4-3
DOUT 4
T1
T2
T3
4-5
MOTOR
L1
L2
L3
July 2014
Sheet 10 045
Technical Data
Technical Data
i
ii
1
10
11
12
13
14
15
16
17
18
19
20
21
July 2014
Sheet 10 046
Layout Dimensions
Equipment Details
3
4
5
7
8
9
10
700/800 3
1500/1750 4
3000
200,000
200,000
200,000
1
1
2
1350 (613)
1350 (613)
1700 (772)
400
400
720
200,000
200,000
200,000
3
3
4
1800 (817)
1800 (817)
2400 (1090)
400
400
720
400,000
400,000
400,000
1
1
2
1350 (613)
1350 (613)
1700 (772)
400
400
720
400,000
400,000
400,000
3
3
4
1800 (817)
1800 (817)
2400 (1090)
6600 6 400
6600 6 400
6600 6 720
570,000
570,000
570,000
1
1
2
1500 (681)
1500 (681)
1800 (817)
6600 6 400
6600 6 400
6600 6 720
570,000
570,000
570,000
3
3
4
1800 (817)
1800 (817)
2400 (1090)
Depth
2300
2300
2300
2300
2300
2300
40004800V Non-Reversing
1250/1500 3
2500/3000 4
5500
4600
4600
4600
40004800V Reversing
1250/1500 3
2500/3000 4
5500
4600
4600
4600
6600V Non-Reversing
2000/2250 3
4000/4500 4
8000
6600V Reversing
2000/2250 3
4000/4500 4
8000
3
4
5
6
13
15
Weight
Lbs (kg)
400
400
720
Height 2 Width
22002400V Reversing
14
700/800 3
1500/1750 4
3000
Dimensions
22002400V Non-Reversing
Reversing Starter
11
12
Horsepower 1 Volts
Additional
Starter Spaces
ii
Specifications
Starter
Interrupting
Rating
(kVA)
Layout Dimensions
Contactor
Ampere Rating
(Enclosed)
RVS
RVS
16
M
Arrangement 1
Arrangement 2
Arrangement 3
Arrangement 4
17
Figure 10.1-24. Starter Arrangements
18
19
20
21
CA08104001E
July 2014
10.2-1
Sheet 10 047
General Description
SC9000 EP Adjustable
Frequency Drive, SC9000 with
Encapsulated Powerpole
SC9000 EP
General Description
Eatons SC9000 EP medium voltage
adjustable frequency drive (AFD)
family provides precise control and
protection of medium voltage motors
and equipment rated 2400 V, 3300 V
and 4160 V nominal.
Application Description
SC9000 EP AFD has a complete offering:
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
CA08104001E
July 2014
Sheet 10 048
i
ii
Mechanical Non-Loadbreak
Isolating Switch
2
3
Top Entry
HV Conduit
Area
4
5
6
7
8
9
Line and
Load Cable
Termination
Type SL
Vacuum
Contactor
Assembly
Encapsulated
Powerpole
Roll-Out
Inverter
10
24-Pulse
Rectifier
Bridge
11
12
24-Pulse
Isolation
Transformer
13
14
15
16
17
DC Link
Pre-Charge
Circuit
18
19
20
21
Bottom Entry HV
Conduit Area
CA08104001E
July 2014
10.2-3
Sheet 10 049
Layout Dimensions
i
ii
Line Terminals Pullbox
Main Bus
2.00
(50.8)
2.00
(50.8)
27.27
(692.7)
23.33
(592.6)
5.00
(127.0)
5.50
(139.7
7.00
(177.8)
7.00
(177.8)
F
E
7.00
(177.8)
50.00
(1270.0)
36.38
(924.1)
65.00 (1651.0)
Top View
1.60
(40.6)
Recommend
24.00 Inch
24.00
(609.6 mm) Clearance (609.6)
for Blower Removal
3
4
K2
K1
9.00
(228.6)
1.85
(47.0)
Window
1
3
K1
K2
K3
2
4
4.13
(104.9)
5
CTB
0.90
(22.9)
Unit 1D
62.00
(1574.8)
1
65.00 (1651.0)
Shipping Section 1
Approx. Weight 6225 lbs (2826 kg)
User
Interface
18.50
(469.9)
PH PH PH MAIN
A B C BUS
Elevation
View
MP4000
Detail Notes:
A - 0.875 dia. typ. 4 holes. mounting studs to extend
a maximum of 2.00 inches (50.8 mm) above grade.
D - 90 door swing requires:
12.00 inches (304.8 mm) for 12.00 inch (304.8 mm) wide structure,
18.00 inches (457.2 mm) for 18.00 inch (457.2 mm) wide structure,
24.00 inches (609.6 mm) for 24.00 inch (609.6 mm) structure,
30.00 inches (762.0 mm) for 30.00 inch (762.0 mm) wide drive structure,
36.00 inches (914.4 mm) for 36.00 inch (914.4 mm) wide structure,
40.00 inches (1016.0 mm) for 40.00 inch (1016.0 mm) wide structure,
32.50 inches (825.5 mm) for 65.00 inch (1651.0 mm) wide drive structure.
E - HV conduit space, load.
F - HV conduit space, line only.
G - LV conduit space only.
J - Load terminals located on left-hand side of enclosure.
Y - Tolerances: 0.0 inches (0.0 mm) +0.25 inches (6.35 mm) per structure.
Z - Conduits to extend a maximum of 2.00 inches (50.8 mm) into structure.
Line Term
Note J
U V W
12.00
(304.8)
3.50
(88.9)
8
9
6.00 (152.4)
Line Term
Note J
L1
80.00
(2032.0
10
12.81
7.50 (190.5)
62.00
(325.4) L2
(1574.8)
2.50
L3 7.50 (190.5)
(63.5)
3.25
2.50
(82.6) 16.90
(63.5)
(429.3)
Ground Bus
11
12
22.49
(571.2)
49.00
(1244.6)
Right Side View
13
59.00 (1498.6)
2.69
(68.3)
29.50
(749.3)
29.80
(756.9)
43.63
(1108.2)
7.00
(177.8)
2.80
(71.1)
F
E
1.50
(38.1)
32.50
(825.5)
3.00
(76.2)
Front
2.50 4.00
(63.5) (101.6)
60.00
(1524.0)
0.75 (19.1)
59.00 (1498.6)
0.25
(6.4)
0.75 (19.1)
15
2.50 4.00
(63.5) (101.6)
0.75 (19.1)
0.25
(6.4)
32.50
(825.5)
29.30
(744.2)
0.75 (19.1)
1.50 3.00
(38.1) (76.2)
0.75 (19.1)
4.00
(101.6)
14
0.75 (19.1)
1.38
(35.1)
5.00
(127.0)
2.38
(60.5)
38.63
(981.2)
Note A
21.81
(554.0)
12.75
(323.9)
0.50
(12.7)
0.25
(6.4)
0.63
(16.0)
0.50
(12.7)
16
17
18
2.00
(50.8)
0.25
(6.4)
19
Floor Plan
Note D
60.00 Inches (1524.0 mm)
Clear in Front of Drive Unit
for Removal of Drive Inverter
Figure 10.2-1. SC9000 EP AFD Frame A Maximum Dimensions and Incoming Line LayoutsDimensions in Inches (mm)
CA08104001E
20
21
July 2014
Sheet 10 050
i
ii
Top Entry HV
Conduit Area
Mechanical Non-Loadbreak
Isolating Switch
3
4
5
6
7
8
9
10
Line and
Load Cable
Termination
DC Link
Pre-Charge
Circuit
Type SL
Vacuum
Contactor
Assembly
24-Pulse
Isolation
Transformer
(in the rear)
Encapsulated
Powerpole
Roll-Out
Inverter
11
12
24-Pulse
Rectifier
Bridge
13
14
15
16
17
Bottom Entry HV
Conduit Area
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.2-5
Sheet 10 051
Layout Dimensions
i
ii
Main Bus
Main Bus
39.27
(997.5)
5.50
50.00
(139.7)
(1270.0)
7.00
G
(177.8)
1.25
(31.8)
5.00 (127.0)
15.50
(393.7) F
1.25
(31.8)
12.27
(311.7)
2.00
(50.8)
Redundant
Blowers
28.50
(723.9)
2.00
(50.8)
65.00 (1651.0)
1.85
(47.0)
K1
7
WINDOW
K1
K2
K3
Inverter
1
4.13
(104.9)
Converter
Unit 2D
1
65.00 (1651.0)
Shipping Section 1
Approx. Weight
8025 lbs (3643 kg)
50.00
(1270.0)
6.00
(152.4)
12.00 (304.8)
12.00
(304.8)
49.00
(1244.6)
3.50
(88.9)
4.38
(111.3)
4.38
(111.3)
Ground
Bus
2
30.00 (762.0)
Shipping
Section 2
Approx. Weight
900 lbs (409 kg)
PH PH Main
B C Bus
U V W
0.90
(22.9)
64.80
(1645.9)
5.50 31.88
(139.7) (809.8)
36.00 (914.4)
(Optional)
Top View SS #2 (Optional)
Load Term
Note J
CTB
Unit 1D
12.00
(304.8)
30.00
(762.0)
Top View SS #2
MP4000
12.27
(311.7)
2.80 (71.1)
PH
A
K3
2.00
2.00
(50.8) (50.8)
12.27
(311.7)
5.50 50.00
(139.7) (1270.0)
Top View SS #1
K2
Main Bus
2.00 2.00
(50.8) (50.8)
80.00
(2032.0)
66.00
(1676.4)
Redundant
24.00 Blowers
(609.6)
PH PH PH Main
A B C Bus
22.49
(571.2)
12.20
(309.9)
2.86
(72.6)
19.90
(505.5)
9
10
3.50
(88.9)
50.00
(1270.0)
36.80
(934.7)
2.40
(61.0)
4.75
(120.7) 44.20
(1122.7)
Note A
38.30
(972.8)
3.50
(88.9)
43.00
(1092.2)
2.50
(63.5)
1.58 (40.1)
Note A
3.50
(88.9)
Note A
Optional With
Redundant Blowers
43.00
(1092.2)
3.00
(76.2)
4.75
Front
(120.7)
33.50
(850.9)
33.50
(850.9)
25.00
(635.0)
G
2.50
(63.5)
7.00
(177.8)
30.00
(762.0)
2.50
(63.5)
36.00
(914.4)
Front
Floor Plan
Note D
60.00
(1524.0)
12.00
(304.8)
31.00
(787.4)
Front
Floor Plan
Note D
Floor Plan
Note D
2.80
(71.1)
6.00
(152.4)
F
7.00
(177.8)
30.00
(762.0)
60.00
(1524.0)
SS #1
Optional With
Redundant
Blowers
60.00 Inches (1524.0 mm)
Clear in Front of Drive
Unit for Removal of
Drive Inverter
SS #2
SS #2 (Optional)
0.75 (19.1)
0.75 (19.1)
1.50 3.00
(38.1) (76.2)
0.437 x 0.688
0.75 (19.1)
Slot
0.437 x 0.688
Slot
0.75 (19.1)
0.50
(12.7)
0.75 (19.1)
2.50 4.00
(63.5) (101.6)
0.25
(6.4)
Detail Notes:
A - 0.875 dia. typ. 4 holes. Mounting studs to
extend a maximum of 2.00 inches (50.8 mm)
above grade.
D - 90 door swing requires: 12.00 inches (304.8 mm)
for 12.00 inch (304.8 mm) wide structure,
18.00 inches (457.2 mm) for 18.00 inch (457.2 mm)
wide structure, 24.00 inches (609.6 mm) for
24.00 inch (609.6 mm) structure,
30.00 inches (762.0 mm) for 30.00 inch (762.0 mm)
wide drive structure, 36.00 inches (914.4 mm) for
36.00 inch (914.4 mm) wide structure,
40.00 inches (1016.0 mm) for 40.00 inch (1016.0 mm)
wide structure, 32.50 inches (825.5 mm) for
65.00 inch (1651.0 mm) wide drive structure.
E - HV conduit space, load.
F - HV conduit space, line only.
.
G - LV conduit space only.
J - 30.00 inch (762.0 mm) inverter load terminals
located on left side of converter.
36.00 inch (914.4 mm) inverter load terminals
located on right side of inverter.
Y - Tolerances: 0.00 inches (0.0 mm)
+0.25 inches (6.35 mm) per structure.
Z - Conduits to extend a maximum of
2.00 inches (50.8 mm) into structure.
2.50 4.00
(63.5) (101.6)
0.25
(6.4)
0.437 x 0.688
Slot
0.75 (19.1)
0.25
(6.4)
0.562 Dia.
Hole
0.63
(16.0)
Figure 10.2-2. SC9000 EP AFD Frame B Maximum Dimensions and Incoming Line LayoutsDimensions in Inches (mm)
CA08104001E
0.50
(12.7)
CL
11
12
13
14
15
16
17
18
19
2.00
(50.8)
0.25
(6.4)
20
21
July 2014
Sheet 10 052
i
ii
Top Entry HV
Conduit Area
Mechanical Non-Loadbreak
Isolating Switch
DC Link
Pre-Charge Circuit
3
4
5
Line and
Load Cable
Termination
6
7
8
Type SL
Vacuum
Contactor
Assembly
24-Pulse
Isolation
Transformer
9
Encapsulated
Powerpole
Roll-Out
Inverter
10
11
12
13
14
15
Bottom Entry HV
Conduit Area
24-Pulse
Rectifier Bridge
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.2-7
Sheet 10 053
Layout Dimensions
i
ii
1
2.75
(69.9)
Main Bus
Main Bus
2.00
(50.8)
2.00 (50.8)
16.00
(406.4)
5.50
(139.7)
F
7.00
(177.8)
29.25
(743.0) 16.00
(406.4)
50.00
(1270.0)
5.00
(127.0)
2.38
(60.5)
36.00
(914.4)
Top View SS #1
12.00
(304.8)
12.23
(310.6)
3.70
(94.0)
50.00
(1270.0)
5.50
(139.7)
26.70
(678.2)
7.00
(177.8)
31.88
(809.8)
50.00
(1270.0)
7.00
(177.8)
F
E
5.75
(146.1)
12.27
(311.7)
E
6.00
(152.4)
30.00
(762.0)
Optional 36.00 (914.4)
3.70
(94.0)
65.00 (1651.0)
Top View SS #3
Top View SS #2
Recommend
24.00 (609.6) Clearance 24.00
for Blower Removal
(609.6)
Redundant
Blowers
0.75
(19.1)
K3
1.85
(47.0)
WINDOW
Inverter
K1
K2
K3
K4
4
5
CTB
CTB1
1
Shipping
Section 1
36.00 (914.4)
Approx. Weight
1550 lbs (704 kg)
1
Shipping Section 2
65.00 (1651.0)
Approx. Weight
9800 lbs (4449 kg)
2
Shipping
Section 3
30.00 (762.0)
Optional 36.00 (914.4)
Approx. Weight
900 lbs (409 kg)
16.00
(406.4)
29.25
(743.0) 16.00
(406.4)
Note A
7.00
(177.8)
E
5.75
(146.1)
43.00
(1092.2)
29.00
(736.6)
Front
36.00
(914.4)
SS #1
35.00
(889.0)
4.00
(101.6)
8.00 32.50
(203.2) (825.5)
43.00
(1092.2)
2.50 (63.5)
G
3.00
(76.2)
32.50
9.50
(825.5) (241.3)
2.80
(71.1)
6.00
(152.4)
Front
5.00 (127.0)
Front
2.50
(63.5)
Note A
59.00 (1498.6)
3.00
(76.2)
0.437 x 0.688
Slot
0.75
(19.1)
25.00
(635.0)
30.00
(762.0)
Optional
36.00 (914.4)
12.00
(304.8)
11
7.00
(177.8)
2.00
(50.8)
12
13
0.63
(16.0)
Figure 10.2-3. SC9000 EP AFD Frame C Maximum Dimensions and Incoming Line LayoutsDimensions in Inches (mm)
For more information, visit: www.eaton.com/consultants
0.25
(6.4)
60.00
Floor Plan
SS #3
(1524.0)
Note D
Detail Notes:
60.00 Inches
SS #2
A - 0.875 dia. typ. 4 holes. mounting studs to extend
(1524.0 mm)
a maximum of 2.00 inches: (50.8 mm) above grade.
Clear in
D - 90 door swing requires: 12.00 inches (304.8 mm) for 12.00 inch (304.8 mm) wide structure,
for Removal
18.00 inches (457.2 mm) for 18.00 inch (457.2 mm) wide structure,
of Inverter
24.00 inches (609.6 mm) for 24.00 inch (609.6 mm) structure,
30.00 inches (762.0 mm) for 30.00 inch (762.0 mm) wide drive structure,
36.00 inches (914.4 mm) for 36.00 inch (914.4 mm) wide structure, 40.00 inches (1016.0 mm) for 40.00 inch (1016.0 mm) wide structure.
32.50 inches (825.5 mm) for 65.00 inch (1651.0 mm) wide drive structure.
E - HV conduit space, load.
F - HV conduit space, line only.
G - LV conduit space only.
J - Load terminals located on right side of inverter.
Optionload terminals located on left side of converter.
Y - Tolerances: 0.0 inches (0.0 mm) +0.25 inches (6.35 mm) per structure.
Z - Conduits to extend a maximum of 2.00 inches (50.8 mm) into structure.
CA08104001E
2.50
(63.5)
10
0.50
(12.7)
4.00
(101.6)
Note A
0.25
(6.4)
2.50
(63.5)
50.00
(1270.0)
3.50
(88.9)
0.437 x 0.688
Slot
0.75
(19.1)
22.49
(571.2)
3.50 (88.9)
2.75 (69.9)
4.00
(101.6)
2.86
(72.6)
7
8
0.75
(19.1)
80.00
(2032.0)
Ground
Bus
0.25
(6.4)
1.50
(38.1)
0.90
(22.9)
Unit 3D
Converter
3.50
(88.9)
K1
Unit 2D
0.437 x 0.688
Slot
0.75
(19.1)
K4
WINDOW
Main
Disconnect
Unit 1D
3.00
(76.2)
12.00
(304.8)
PH PH PH MAIN
A B C BUS
K2
18.50
(469.9)
14
15
0.25
(6.4)
16
17
18
19
20
21
July 2014
Sheet 10 054
i
ii
Mechanical Non-Loadbreak
Isolating Switch
DC Link
Pre-Charge Circuit
3
Top Load
Conduit Area
4
5
6
Load Cable
Termination
7
8
Type HLE
Current
Limiting
Fuses
9
10
Encapsulated
Powerpole
Roll-Out
Inverter
Type SL
Vacuum
Contactor
Assembly
11
12
13
Bottom Entry HV
Conduit Area
24-Pulse
Rectifier Bridge
24-Pulse
Isolation
Transformer
(in the rear)
Bottom Load
Conduit Area
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.2-9
Sheet 10 055
Layout Dimensions
i
ii
2.00 (50.8)
Main Bus
2.00
(50.8)
2.00
(50.8)
41.42
(1052.1)
12.32
(312.9)
12.32
50.00
(312.9)
(1270.0)
5.50
(139.7)
40.75
1.38 (1035.1)
(35.1)
2.00
(50.8)
50.00
(1270.0)
3.00
(76.2)
5.50
6.00 (152.4) (139.7)
5.00
(127.0)
6.19
(157.2)
36.00
(914.4)
76.00
(1930.4)
SS #1
SS #2
Main Bus
2.00
(50.8)
2.00
(50.8)
12.32
(312.9)
12.00
(304.8)
3.00
(76.2)
50.00
(1270.0)
6.00
(152.4)
36.00
(914.4)
31.88
(809.8)
5.50
(139.7)
SS #3
0.75 (19.1)
Optional Redundant Blowers
0.437 x 0.688
Slot
0.75
(19.1)
24.00
(609.6)
PH
A
K14
K13
1.85
(47.0)
WINDOW
K11
K12
K13
K14
K44
Inverter
CTB
CTB2
K11
CTB1
Isolation Transformer
and Converter
Unit 2D
0.90
(22.9)
UNIT 3D
Main
Disconnect
Unit 1D
1
36.00
(914.4)
Shipping
Section 1
40.00 (1016.0)
Approx. Wt.
2560 lbs (1162 kg)
2
76.00
(1930.4)
3
36.00
(914.4)
Shipping Section 2
76.00 (1930.4)
Approx. Wt.
16,500 lbs (7491 kg)
Shipping
Section 3
36.00 (914.4)
Approx. Wt.
3775 lbs (1714 kg)
PH
B
12.00
(304.8)
PH MAIN
C BUS
K12
5.00
29.00
(127.0)
(736.6)
Note A
12.00
(304.8)
18.00
(457.2) F
23.00
41.33
(584.2)
14.00
7.00 (1049.8)
(355.6)
41.38
(177.8)
(1051.1)
3.00
19.63
(76.2)
(498.6)
4.00
(101.6)
80.00
(2032.0)
0.437 x 0.688
Slot
0.75
(19.1)
5.00
(127.0)
0.437 x 0.688
Slot
0.75
(19.1)
39.00 Front
(990.6)
Note A
44.00
(1117.6)
4.15
(105.4
50.00
(1270.0)
3.00 (76.2)
Front
6.00 1.50
(152.4) (38.1)
8.88
(225.6)
36.00
(914.4)
SS #1
2.75
(69.9)
43.00
(1092.2)
38.00
(965.2)
38.00
(965.2)
Detail Notes:
A - 0.875 dia. typ. 4 holes. mounting studs to extend a maximum of 2.00 inches (50.8 mm) above grade.
D - 90 door swing requires: 12.00 inches (304.8 mm) for 12.00 inch (304.8 mm) wide structure,
18.00 inches (457.2 mm) for 18.00 inch (457.2 mm) wide structure,
24.00 inches (609.6 mm) for 24.00 inch (609.6 mm) structure,
36.00 inches (914.4 mm) for 36.00 inch (914.4 mm) wide structure,
40.00 inches (1016.0 mm) for 40.00 inch (1016.0 mm) wide structure,
32.50 inches (825.5 mm) for 65.00 inch (1651.0 mm) wide drive structure.
E - HV conduit space, load.
F - HV conduit space, line only.
G - LV conduit space only.
J - Load terminals located on right-hand side of enclosure.
Y - Tolerances: 0.00 inches (0.0 mm) +0.25 inches (6.35 mm) per structure.
Z - Conduits to extend a maximum of 2.00 inches (50.8 mm) into structure.
12
30.00
(762.0)
2.80
(71.1)
31.00
(787.4)
2.50
(63.5)
0.50
(12.7)
2.00
(50.8)
12.00
(304.8)
0.25
(6.4)
14
15
16
17
SS #3
18
Figure 10.2-4. SC9000 EP AFD Frame D (Single Inverter) Maximum Dimensions and Incoming Line LayoutsDimensions in Inches (mm)
CA08104001E
13
CL
36.00
(914.4)
1.85
(47.0)
SS #2
11
0.63
(16.0)
Front
0.25
(6.4)
0.562 Dia.
Hole
6.00
(152.4)
43.25
(1098.6)
9
10
4.00
(101.6)
3.50
(88.9)
0.50
(12.7)
0.75
(19.1)
50.00
(1270.0)
25.00
(635.0)
0.25
(6.4)
2.50
(63.5)
Ground
Bus
2.86
(72.6)
49.00
(1244.6)
25.00
(635.0)
6
7
0.75 (19.1)
3.50
(88.9)
3.50
(88.9)
0.25
(6.4)
1.50
(38.1)
38.25
(971.6)
13.00
(330.2)
3.00
(76.2)
19
20
21
July 2014
Sheet 10 056
i
ii
Secondary
Blower
DC Link
Pre-Charge
Circuit
2
3
Top Entry HV
Conduit Area
Mechanical Non-Loadbreak
Isolating Switch
Top Load
Conduit Area
Balancing
Reactor
4
5
6
7
8
9
Load Cable
Termination
Type HLE
Current
Limiting
Fuses
Type SL
Vacuum
Contactor
Assembly
10
11
12
Bottom Entry HV
Conduit Area
24-Pulse
Rectifier
Bridge
24-Pulse
Isolation
Transformer
(mounted
behind rectifier
bridge)
Bottom Entry
Control
Conduit Area
Dual
Encapsulated
Powerpole
Roll-Out Inverters
Bottom Load
Conduit Area
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.2-11
Sheet 10 057
Layout Dimensions
Main Bus
2.00
(50.8)
2.00
(50.8)
41.42
(1052.1)
ii
2.00 (50.8)
2.00 (50.8)
12.32
(312.9)
12.32
(312.9)
6.19
(157.2)
5.50
6.00 (152.4) (139.7)
14.00 50.00
(355.6) (1270.0)
2.11
(53.6)
4
20.50
(520.7)
12.00
(304.8)
K15
K14
K11
K12
K13
K14
K44
1.85
(47.0)
K44
K15
K16
K17
7
CTB
CTB2
K11
CTB1
Main
Disconnect
Isolation Transformer
and Converter
Unit 2D
Unit 1D
1
36.00
(914.4)
Shipping
Section 1
40.00 (1016.0)
Approx. Weight
2560 lbs (1162 kg)
3.50
(88.9)
3
86.00
(2184.4)
U V
5.00
(127.0)
29.00
(736.6)
12.00
(304.8)
14.00
(355.6)
19.63
(498.6)
Front
7.00
(177.8)
80.00
(2032.0)
25.00
(635.0)
36.00
(914.4)
38.00
(965.2)
0.75 (19.1)
4.00
(101.6)
0.437 x 0.688
Slot
0.75
(19.1)
0.25
(6.4)
0.25
(6.4)
2.50
(63.5)
0.50
(12.7)
0.25
(6.4)
0.562 Dia.
Hole
0.63
(16.0)
48.12
(1222.2)
15.50
(393.7)
5.00
(127.0)
3.00
31.00
39.00 (76.2) (787.4)
(990.6)
2.63
(66.8)
2.00
14.00
(50.8)
E
(355.6)
Note A
5.00
(127.0)
3.00
(76.2)
32.50
(825.5)
42.50
6.75
(1079.5) (171.5)
0.50
(12.7)
Detail Notes:
A - 0.875 dia. typ. 4 holes. Mounting studs to extend a maximum
of 2.00 inches (50.8 mm) above grade.
D - 90 door swing requires: 12.00 inches (304.8 mm) for
12.00 inch (304.8 mm) wide structure,
18.00 inches (457.2 mm) for 18.00 inch (457.2 mm) wide structure,
24.00 inches (609.6 mm) for 24.00 inch (609.6 mm) structure,
36.00 inches (914.4 mm) for 36.00 inch (914.4 mm) wide structure,
40.00 inches (1016.0 mm) for 40.00 inch (1016.0 mm) wide structure,
32.50 inches (825.5 mm) for 65.00 inch (1651.0 mm) wide drive structure.
E - HV conduit space, load.
F - HV conduit space, line only.
G - LV conduit space only.
J - Load terminals located on right-hand side of enclosure.
Y - Tolerances: 0.00 inches (0.0 mm) +0.25 inches (6.35 mm) per structure.
Z - Conduits to extend a maximum of 2.00 inches (50.8 mm) into structure.
9
10
11
12
13
14
16
17
18
19
CL
2.00
(50.8)
0.25
(6.4)
Figure 10.2-5. SC9000 EP AFD Frame D (Parallel Inverters) Maximum Dimensions and Incoming Line LayoutsDimensions in Inches (mm)
CA08104001E
SS #3
Front
1.85
(47.0)
Ground 3.26
(82.8)
Bus
22.75
(577.9)
49.00
(1244.6)
50.00
(1270.0)
31.13
(790.7)
38.00
(965.2)
80.00
(2032.0)
15
3.00
(76.2)
1.50
(38.1)
25.00
(635.0)
3.50
(88.9)
68.00
(1727.2)
0.90
(22.9)
0.75 (19.1)
30.36
(771.1)
SS #2
43.25
5.00
Note A
4.15 (1098.6)
(127.0)
44.00
(105.4)
39.00 Front
(1117.6) 50.00
(990.6)
2.75
(1270.0)
(69.9)
3.00 (76.2)
41.33
(1049.8)
4.38
(111.3)
Load Term
Note J
0.437 x 0.688
Slot
0.75
(19.1)
3.50
(88.9)
Ground
Bus 5.00
(127.0)
12.00
(304.8)
PH PH PH MAIN
A B C BUS
38.25
(971.6)
49.00
(1244.6)
50.00
(1270.0)
Shipping Section 3
86.00 (2184.4)
Approx. Weight
6800 lbs (3087 kg)
Shipping Section 2
76.00 (1930.4)
Approx. Weight
16,500 lbs (7491 kg)
41.38
(1051.1)
0.437 x 0.688
Slot
0.75
(19.1)
0.90
(22.9)
Unit 3D
2
76.00
(1930.4)
Note A
18.00
23.00 (457.2) F
(584.2)
3.00
(76.2)
6.00 (152.4)
1.50
(38.1)
8.88
(225.6)
Inverter-2
Inverter-1
PH PH PH MAIN
A B C BUS
WINDOW
2
3
86.00
(2184.4)
3.00
(76.2)
K12 K13
12.32
(312.9)
30.88
5.50 (784.4)
(139.7)
7.00
(177.8)
76.00
(1930.4)
36.00
(914.4)
Optional Redundant Blowers
2.00
(50.8)
50.00
(1270.0)
5.50
(139.7) 40.75
1.38 (1035.1)
(35.1)
50.00
(1270.0)
3.00
(76.2)
5.00
(127.0)
20
21
July 2014
Sheet 10 058
i
ii
2
24.00
(609.6)
3
4
K2
K3
K4
K5
K33
K4
K5
K6
Window
6
MP4000
K1
K2
K3
K33
K1
CTB
CTB2
Unit 2D
CTB1
92.00
(2336.8)
All Units
Isolation Transformer
and Converter
Inverter-1
Inverter-2
80.00
(2032.0)
All Units
Unit 3D
Main Disconnect
Unit 1D
10
11
12
13
14
100.00
(2540.0)
Shipping Section 2
Approx. Weight
(19,500 lbs)
86.00
(2184.4)
Shipping Section 3
Approx. Weight
(6800 lbs)
Motor
FLA
hp
Width
Height
Depth
Height
3300 1
4160
520640
620713
32504000
50006000
222.00 (5638.8)
222.00 (5638.8)
92.00 (2336.8)
92.00 (2336.8)
50.00 (1270.0)
50.00 (1270.0)
12.10 (307.3)
12.10 (307.3)
15
1
36.00
(914.4)
Shipping Section 1
Approx. Weight
(2560 lbs)
Cabinet Size
Redundant Blower
3300 V, 50 Hz.
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
Sheet 10 059
General Description
i
ii
1
2
3
AFD Bus
General Description
AFD Bus
AFD Bus
10
11
12
13
4160 V, 60 Hz, Line
14
15
AFD Bus
AFD Bus
AFD Bus
16
17
18
19
20
AFD Bus
21
July 2014
Sheet 10 060
Layout Dimensions
ii
VFD Bus
Main Bus
1
K2
K4
K3
K1
2
Window
K1
K2
K3
K4
K5
Inverter
A1 Motor Bypass
Door
Unit 6B
Interlock
Output Filter
Unit 5B
AMPGARD
SC 9000
A2 Motor Bypass
Door
Unit 7B
Interlock
A3 Motor Bypass
Door
Unit 8B
Interlock
A4 Motor Bypass
Door
Unit 9B
Interlock
A5 Motor Bypass
Unit 10B Door
Interlock
CTB
Unit 2D
Unit 1D
K5
Unit 3D
4.00
(101.6)
6
7
36.00
(914.4)
36.00
(914.4)
65.00
(1651.0)
36.00
(914.4)
36.00
(914.4)
36.00
(914.4)
36.00
(914.4)
36.00
(914.4)
36.00
(914.4)
65.00
(1651.0)
76.00
(1930.4)
72.00
(1828.8)
72.00
(1828.8)
72.00
(1828.8)
Shipping Section 1
Approx. Weight
(9325 lbs)
Shipping Section 2
Approx. Weight
(4725 lbs)
Shipping Section 3
Approx. Weight
(3600 lbs)
Shipping Section 4
Approx. Weight
(4700 lbs)
Shipping Section 5
Approx. Weight
(4700 lbs)
8
9
Converter
10
Inverter
Optional
Output Filter
BP
BP
M
Unit
6B
24 Pulse
XFMR
Unit
7B
BP
Unit
8B
BP
Unit
9B
BP
Unit
10B
11
12
Unit 2D
Unit 3D
Unit 5D
MS
MS
D
Unit 1D
Unit
6D
Unit
7D
MS
Unit
8D
MS
Unit
9D
MS
Unit
10D
Figure 10.2-14. SC9000 EP Synchronous Transfer System with Five MV Starters (For Reference Only)
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.2-15
Sheet 10 061
Layout Dimensions
i
ii
Redundant Blowers
Recommend 24.00 inch
(609.6 mm) Clearance
for Blower Removal
TypicalAll Units
24.00
(609.6)
1
2
K2
K6
K5
K3
MP4000
K1
K2
K3
K4
Incoming Line
Inverter-1
Unit 2D
CTB
CTB2
Contactor
Unit 1D
K4
K5
K6
Window
K1
1
Inverter-2
Unit 4D
7
1
36.00
(914.4)
36.00
(914.4)
100.00
(2540.0)
86.00
(2184.4)
Shipping Section 2
Approx. Weight (17,925 lbs)
Shipping Section 3
Approx. Weight (6800 lbs)
72.00 (1828.8)
Shipping Section 1
Approx. Weight (4500 lbs)
1.50
(38.1)
2.50
(63.5)
0.75
(19.1)
3.00
(76.2)
0.437 x 0.688
Slot
4.00
(101.6)
0.25
(6.4)
0.75
(19.1)
2.50
(63.5)
0.562 Dia.
Hole
4.00
(101.6)
0.437 x 0.688
Slot
0.75
(19.1)
0.437 x 0.688
Slot
0.25
(6.4)
0.75
(19.1)
0.50
(12.7)
0.25
(6.4)
Detail Notes:
A - 0.875 dia. typ. 4 holes. Mounting studs to extend a maximum
of 2.00 inches (50.8 mm) above grade.
D - 90 door swing requires: 12.00 inches (304.8 mm) for
12.00 inch (304.8 mm) wide structure, 18.00 inches (457.2 mm)
for 18.00 inch (457.2 mm) wide structure, 24.00 inches (609.6 mm)
for 24.00 inch (609.6 mm) structure, 30.00 inches (762.0 mm)
for 30.00 inch (762.0 mm) wide drive structure,
36.00 inches (914.4 mm) for 36.00 inch (914.4 mm) wide structure,
40.00 inches (1016.0 mm) for 40.00 inch (1016.0 mm) wide structure.
32.50 inches (82.6 mm) for 65.00 inch (1651.0 mm) wide drive structure.
E - HV conduit space, load.
F - HV conduit space, line only.
G - LV conduit space only.
J - Load terminals located on right side of inverter.
Optionload terminals located on left side of converter.
Y - Tolerances: 0.0 inches (0.0 mm) +0.25 inches (6.4 mm) per structure.
Z - Conduits to extend a maximum of 2.00 inches (50.8 mm) into structure.
0.50
(12.7)
2.00
(50.8)
8
9
10
11
12
13
14
Description
CL
0.63
(16.0)
K1
K2, K3
K4
K5, K6
0.25
(6.4)
15
16
17
18
19
20
21
July 2014
Sheet 10 062
Layout Dimensions
i
ii
1
2
61.12
(1552.4)
3
Frame B SC9000 EP Medium Voltage Drive
Main Breaker, Output Contactor with Bypass
4
Elevation View
5
1
Fp4000
Cs
Sw
MP3000
Window
Unit 1B
Unit 2B
Window
Unit 1C
Unit 2C
Converter
Inverter
Unit 7D
Ctb
Unit 4D
Unit 5D
Unit 1F
11
12
Unit 2F
1
26.00
(660.4)
36.00 (914.4)
Spacer
Main Breaker
10
Spacer
4.00 (101.6)
Unit 7D
7
4.00 (101.6)
65.00 (1651.0)
30.00 (762.0)
Shipping
Section 1
66.00 (1676.4)
Shipping
Section 2
65.00 (1651.0)
Shipping
Section 3
30.00 (762.0)
Shipping
Section 4
40.00 (1016.0)
Approx. Weight
8025 lbs (3643 kg)
Approx. Weight
8025 lbs (3643 kg)
Approx. Weight
900 lbs (409 kg)
Approx. Weight
1800 lbs (817 kg)
36.00 (914.4)
13
14
Floor Plan
30.00
(762.0)
15
16
60.00
(1524.0)
50.00
(1270.0)
17
18
19
20
201.00 (5105.4)
Overall
Figure 10.2-16. Eaton Medium Voltage Integrated Control Gear with Main Breaker Dimensions(See Page 10.1-6 for Information on Main Bus.
Refer to Eaton for Larger hp Layouts and Detailed Assembly Dimensions.)
Note: For exact conduit locations and descriptions, please see Page 10.1-39.
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
10.2-17
Sheet 10 063
Technical Data
Typical Schematic
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
July 2014
Sheet 10 064
Technical Data
i
ii
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Figure 10.2-18. Typical Schematic for 24-Pulse Transformer, Rectifier and Inverter
CA08104001E
July 2014
Sheet 10 065
General Description
Interlocks
ii
1
2
3
Isolation Switch
Operating Shaft
Mechanical
Interlock with
Contactor
6
7
Isolation Switch
Door Locking
Mechanism
8
9
10
11
12
13
14
15
16
17
18
Distinctive Marking
when Shutter is in
Closed Position
Motion of Shutter
19
20
21
CA08104001E
July 2014
Sheet 10 066
General Description
Modular Roll-in/Roll-out
Stab-in Three-Phase Inverter
ii
1
2
3
4
5
6
7
8
9
10
11
General Description
12
13
14
15
16
17
18
19
20
21
CA08104001E
July 2014
10.2-21
Sheet 10 067
General Description
Mechanical
Interlock with
Isolation Switch
ii
1
2
SC9000 EP
Keypad
3
4
Roll-Out
Wheels
Self-Aligning
Contactor Line
and Load
Fingers
General Description
400 A Vacuum Contactors
A stab-in version of the SL Contactor
is standard. The stab-in contactor is
mounted on wheels and rolls into the
SC9000 EP AFD structure. Contactor
line and load fingers engage cellmounted stabs as the contactor
is inserted into the SC9000 EP AFD
incoming cell. The contactor is held
in position by a bolt and bracket combination. It can be easily withdrawn
from the SC9000 EP AFD incoming cell
by removing the bolt holding the
contactor against the bracket and
disconnecting the isolation switch
interlock. The contactor can be
removed from the SC9000 EP AFD
after disconnecting the medium
voltage cables going to the control
transformer.
9
10
11
12
13
1/4 Turn Door
Latch Top and
Bottom
External Motor
Protection Relay
(optional)
Indicating
Lights and
Pushbuttons
14
15
Fuse Fault
Indicator
16
17
18
19
20
21
CA08104001E
July 2014
Sheet 10 068
General Description
Pre-Charge Circuit
Seismic Qualification
ii
2
3
4
5
SC9000 EP Pre-Charge Circuit
6
7
8
9
10
11
12
13
14
15
16
17
SC9000 EP Options
Communications Options
Johnson Controls N2
Modbus TCP
Modbus
PROFIBUS DP
DeviceNet
BACnet
CANopen
LonWorks
EtherNet/IP
Output Filters
Drive output filters are recommended
for longer cable lengths between the
drive and motor.
Table 10.2-2. Recommended Output
Filter Application
Motor Type
Sine Filter
Non-inverter
duty rated
Over 100 ft
Over 500 ft
Inverter
duty rated
Over 375 ft
Over 1200 ft
Enclosure Options
NEMA 1 Gasketed is standard and
the only enclosure option at this time.
If an outdoor installation is required,
Eaton can supply the AFDs and other
electrical equipment in a modular
building called an Integrated Power
Assembly (see Tab 38).
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
Sheet 10 069
Layout Dimensions
Layout Dimensions
DVDT Filter
Sine Filter
12.27
(311.7)
2.00
(50.8)
2.00
(50.8)
23.80
(604.5)
2.00
(50.8)
31.38
(797.1)
5.50
(139.7)
7.00
(177.8)
26.67
(677.4)
50.00
(1270.0)
23.33
(592.6)
32.47
(824.7)
5.50
(139.7)
2.74
(69.6)
12.00
(304.8)
2.00
(50.8)
Detail Notes:
A - 0.875 dia. typ. 4 holes. Mounting studs to extend
a maximum of 2.00 inches (50.8 mm) above grade.
D - 90 door swing requires: 12.00 inches (304.8 mm) for
12.00 inch (304.8 mm) wide structure, 18.00 inches (457.2 mm)
for 18.00 inch (457.2 mm) wide structure,
24.00 inches (609.6 mm) for 24.00 inch (609.6 mm)
structure, 36.00 inches (914.4 mm) for 36.00 inch (914.4 mm)
wide structure, 40.00 inches (1016.0 mm) for 40.00 inch (1016.0 mm)
wide structure, 32.50 inches (825.5 mm) for 65.00 inch (1651.0 mm)
wide drive structure.
E - HV conduit space, load.
F - HV conduit space, line only.
G - LV conduit space only.
J - Load terminals located on right-hand side of enclosure.
Y - Tolerances: 0.00 inches (0.0 mm) +0.25 inches (6.35 mm)
per structure.
Z - Conduits to extend a maximum of 2.00 inches (50.8 mm)
into structure.
6.00
(152.4)
50.00
(1270.0)
2.63
(66.8)
36.00
(914.4)
40.00
(1016.0)
Top View
SS #2
Top View
SS #1
ii
1
2
3
4
5
PH
A
DVDT Filter
PH MAIN
C BUS
Load Term
Note J
K16
K4
PH
B
Sine Filter
12.00
(304.8)
3.50
(88.9)
7
4.38
(111.3)
6.75
(171.5)
46.88
(1190.8)
80.00
(2032.0)
Output Reactor
Contactor/Output Filter
Unit 1D
0.90
(22.9)
Unit 2D
10
Ground Bus
2
40.00
(1016.0)
Shipping Section 2
2560 lbs (1162 kg)
1
36.00
(914.4)
Shipping Section 1
1875 lbs (851 kg)
21.50
(546.1)
44.00
(1117.6)
0.75 (19.1)
26.63
(676.4)
2.25
(57.2)
43.00
(1092.2)
22.00
(558.8)
31.00
(787.4)
2.50
(63.5)
Front
35.00
(889.0)
2.50
(63.5)
3.00
(76.2)
0.437 x 0.688
0.75
Slot
(19.1)
7.00
(177.8)
36.00
(914.4)
40.00
(1016.0)
SS #1
SS #2
2
3
0.25
(6.4)
0.50
(12.7)
0.75 (19.1)
4.00
(101.6)
2.50
(63.5)
0.437 x 0.688
0.75
Slot
(19.1)
2.50
(63.5)
0.25
(6.4)
0.437 x 0.688
0.75
Slot
(19.1)
1
1.50
(38.1)
14
4.00
(101.6)
14.00
(355.6)
Front
13
0.75 (19.1)
Note A
12
50.00
(1270.0)
Note A
11
22.85
(580.4)
49.00
(1244.6)
2.40
(61.0)
3.00
(76.2)
1.45
(36.8)
0.50
(12.7)
0.562 Dia.
Hole
15
16
17
CL
0.63
(16.0)
0.25
(6.4)
Varies for sine (depends on option), 46.88 (1190.8) standard, dv/dt 57.88 (1470.2).
10.92 (277.4) sine.
9.00 for dv/dt.
2.00
(50.8)
0.25
(6.4)
18
19
20
Figure 10.2-21. SC9000 EP AFD Output Filter Maximum Dimensions and Incoming Line LayoutsDimensions in Inches (mm)
21
CA08104001E
July 2014
Sheet 10 070
Technical Data
Technical Data
Table 10.2-3. Design Specifications
NEMA
IEC
Power rating
3006000 hp
2234474 kW
Motor type
2400 V15,000 V
2400 V15,000 V
10% of nominal
10% of nominal
5 cycles (Std.)
5 cycles (std.)
Input protection
Input frequency
50/60 Hz, 5%
50/60 Hz, 5%
Contactor/fuses
Contactor/fuses
Isolation transformer
Isolation transformer
Output voltage
02400 V
03300 V
04160 V
02400 V
03300 V
04160 V
Inverter design
PWM
PWM
Inverter switch
IGBT
IGBT
Enclosure
NEMA 1
IP20
0 C to +40 C
0 C to +40 C
40 C to +70 C
40 C to +70 C
Relative humidity
95% noncondensing
95% noncondensing
03300 ft
01000 m
Seismic
2006 IBC
2006 IBC
Standards
IEC
Cooling
23 watts/hp
23 watts/hp
>0.96
>0.96
IGBTs
IGBTs
2400 V
12
12
3300 V
12
12
4160 V
12
12
PIV
PIV
2400 V
3300 V
3300 V
3300 V
6500 V
6500 V
4160 V
6500 V
6500 V
Rectifier designs
24-pulse PWM
24-pulse PWM
Rectifier switch
Diode
Diode
Non-rupture, non-arc
Non-rupture, non-arc
Air-cooled
Air-cooled
Sinusoidal current/voltage
Sinusoidal current/voltage
Speed regulation
1120 Hz
1120 Hz
Standard
Standard
Typical efficiency
96.597.5%
96.597.5%
Yes
Yes
ii
1
2
3
6
7
8
9
Description
10
11
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E
July 2014
Sheet 10 071
Technical Data
i
ii
2400/60 Hz VT
3300/50 Hz VT
4160/60 Hz VT
2400/60 Hz VT
3300/50 Hz VT
4160/60 Hz VT
FLA
hp
FLA
hp
FLA
FLA
hp
FLA
hp
FLA
hp
69
80
91
300
350
400
48
56
64
300
350
400
38
44
51
300
350
400
448
504
561
2000
2250
2500
360
400
440
2250
2500
2750
403
434
461
3250
3500
3750
103
114
450
500
72
80
96
450
500
600
57
63
76
450
500
600
480
3000
493
527
558
4000
4250
4500
112
700
89
101
114
700
800
900
2400/60 Hz CT
3300/50 Hz CT
4160/60 Hz CT
124
132
1000 1
1150 1
FLA
hp
FLA
hp
FLA
hp
335
390
448
1500
1750
2000
240
280
320
1500
1750
2000
279
310
341
2250
2500
2750
372
403
3000
3250
hp
2400/60 Hz CT
3300/50 Hz CT
4160/60 Hz CT
FLA
hp
FLA
hp
FLA
69
80
300
350
48
56
64
300
350
400
38
44
51
300
350
400
72
80
450
500
57
63
76
450
500
600
hp
3300/50 Hz VT
4160/60 Hz VT
FLA
FLA
hp
FLA
hp
hp
3300/50 Hz VT
4160/60 Hz VT
FLA
hp
FLA
hp
FLA
hp
520
560
600
3250
3500
3750
589
620
651
4750
5000
5250
640
4000
682
713
744
5500
5750
6000
128
144
160
800
900
1000
124
155
186
1000
1250
1500
2400/60 Hz CT
3300/50 Hz CT
4160/60 Hz CT
FLA
hp
FLA
hp
FLA
hp
201
223
900
1000
200
240
1250
1500
217
248
1750
2000
360
400
2250
2500
434
461
493
3500
3750
4000
3300/50 Hz CT
4160/60 Hz CT
FLA
FLA
hp
hp
hp
91
103
114
400
450
500
96
112
128
600
700
800
89
101
114
700
800
900
134
156
600
700
144
160
900
1000
124
155
1000
1250
2400/60 Hz VT
600
700
800
FLA
134
156
178
2400/60 Hz CT
10
11
12
13
14
15
2400/60 Hz VT
3300/50 Hz VT
4160/60 Hz VT
FLA
hp
FLA
hp
FLA
hp
16
279
335
390
1250
1500
1750
280
320
1750
2000
279
310
341
372
2250
2500
2750 2
3000 2
17
2400/60 Hz CT
3300/50 Hz CT
4160/60 Hz CT
FLA
hp
FLA
hp
FLA
hp
178
201
223
279
800
900
1000
1250
200
1250
186
217
248
1500
1750
2000
18
19
20
21
CA08104001E
July 2014
Sheet 10 072
Technical Data
Table 10.2-9. SC9000 EP Adjustable Frequency Drive Efficiency, Power Factor and
Harmonics Typical Data
Description
ii
1
2
Load (%)
50
75
100
Speed 50%
Input PF (1)
0.96
0.98
0.98
3.13
3.64
3.43
7.59
6.40
6.73
Efficiency (%)
0.943
0.959
0.962
Speed: 75%
Input PF (1)
0.98
0.99
0.99
1.34
2.32
3.15
6.76
4.44
3.85
Efficiency (%)
0.965
0.970
0.971
5
6
Speed: 100%
Input PF (1)
0.98
0.99
0.99
2.16
2.20
2.30
5.95
4.38
3.13
Efficiency (%)
0.971
0.972
0.974
7
8
9
10
11
Horsepower
Watts Loss
as Heat
Horsepower
Watts Loss
as Heat
Horsepower
Watts Loss
as Heat
200
4600
900
20,700
3000
69,000
300
6900
1000
23,000
3500
80,500
350
8050
1250
28,750
3700
85,100
400
9200
1500
34,500
3750
86,250
450
10,350
1750
40,250
4000
92,000
500
11,500
2000
46,000
4500
103,500
600
13,800
2250
51,750
5500
126,500
700
16,100
2500
57,500
6000
138,000
800
18,400
2750
63,250
12
13
14
15
16
17
18
19
20
21
For more information, visit: www.eaton.com/consultants
CA08104001E