Type range - Short description

GroE

OSP

OGi

OPzS

HOPzS

OGi bloc

USV

Power.bloc
OPzS

Standards

DIN 40738, IEC 896-1

IEC 896-1

DIN 40724, IEC 896-1

DIN 40726, IEC 896-1

IEC 896-1

DIN 40739, IEC 896-1

IEC 896-1

DIN 40737-3, IEC 896-1

Capacity range in Ah

75 - 2.600

150 - 4.000

200 - 3.500

150 - 12.000

110 - 1.200

18 - 254

21 - 336

50 - 300

Nominal voltage range

2V

2V

2V

2V

2V

4 V, 6 V

4 V, 6 V

6 V, 12 V

Container material (UL 94-V0 on request)

Luran 378P, (SAN) clear

Luran 378P, (SAN) clear

Luran 378P, (SAN) clear

Luran 378P, (SAN) clear

PP high translucent

PP high translucent

PP high translucent

PP high translucent

Grid alloy
Positive
Negative

pure lead
Pb + <2% Sb

Pb + <2% Sb
Pb + <2% Sb

Pb + <2% Sb
Pb + <2% Sb

Pb + <2% Sb
Pb + <2% Sb

Pb + <2% Sb
Pb + <2% Sb

Pb + <2% Sb
Pb + <1% Ca

Pb + <2% Sb
Pb + <1% Ca

Pb + <2% Ca
Pb + <2% Ca

Positive plate
Negative plate

Plant
Grid

Grid
Grid

Grid
Grid

Tubular
Grid

Tubular
Grid

Grid
Grid

Grid
Grid

Tubular
Grid

Electrolyte

Sulphuric acid

Sulphuric acid

Sulphuric acid

Sulphuric acid

Sulphuric acid

Sulphuric acid

Sulphuric acid

Sulphuric acid

Internal resistance

Best

Better

Better

Good

Good

Better

Better

Medium

Current behaviour

Best

Good

Good

Good

Good

Good

Good

Good

Expected service life up to (in years)

25

20

20

20

15

15

12

20

Cycles acc. to DIN DOD 80% up to

200 - 300

900

800

1200

1200

600 - 800

800

1200

Special charging technique

No

No

No

No

No

No

No

No

Charging voltage in V/cell


Float charge
Boost charge

2.23
2.40

2.25 (2.23)
2.40

2.23
2.40

2.23
2.40

2.23
2.40

2.23
2.40

2.25
2.40

2.23
2.40

Float charging current/100 Ah nominal capacity (20C,


Ufloat =2.23 - 2.25 V/cell)

20 - 40 mA

20 - 50 mA

20 - 50 mA

20 - 50 mA

20 - 50 mA

20 - 50 mA

20 - 50 mA

20 - 50 mA

Position independent operation possible

No

No

No

No

No

No

No

No

Water-refilling intervals in years at permanent


float-charging/with AquaGen

> 5/no refilling during whole service life

> 5/no refilling during whole service life

> 5/no refilling during whole service life

> 5/no refilling during whole service life

> 5/no refilling during whole service life

> 5/no refilling during whole service life

> 5/no refilling during whole service life

> 5/no refilling during whole service life

Self discharge of nominal capacity at 20C


ambient temperature/per month

3%

3%

3%

3%

3%

3%

3%

3%

Operating temperature range in C

-20 - +40

-20 - +40

-20 - +40

-20 - +40

-20 - +40

-20 - +40

-20 - +40

-20 - +40

Ventilation requirement

with AquaGen similar to VRLA

with AquaGen similar to VRLA

with AquaGen similar to VRLA

with AquaGen similar to VRLA

with AquaGen similar to VRLA

with AquaGen similar to VRLA

with AquaGen similar to VRLA

with AquaGen similar to VRLA

Storage time at 20C before refreshing charge

3 months

3 months

3 months

3 months

3 months

3 months

3 months

3 months

Applications

Our products are subject to constant development. We therefore reserve the right to make changes.
Terminals: M8 (HOPzS M10), screwed with brass inserts. Option: AquaGen.
Key: Emergency Power

Engine Start

Power Plant

Power Supply

Rail

f o r m o r e i n f o r m a t i o n : w w w. H O P P E C K E . c o m

Signal Tower

Solar

Switch Gear

Telecom

Transformer Station

UPS

f o r m o r e i n f o r m a t i o n : w w w. H O P P E C K E . c o m

Type range - Short description

OPzV

USV dry
12V - bloc

OGiV

net.power

Power.bloc
OPzV

FNC

Te l e c o m / I T B a t t e r y S y s t e m s

Standards

DIN 40742, IEC 896-2

IEC 896-2

DIN 40741, IEC 896-2

IEC 896-2

DIN 40744, IEC 896-2

DIN 40736

AGV Battery Systems

Capacity range in Ah

200 - 3.000

30 - 100

18 - 256

100

50 - 300

10 - 520 (1.350 Megaline)

Motive Power Systems

Nominal voltage range

2V

12 V

4 V, 6 V

12 V

6 V, 12 V

1.2 V

Container material (UL 94-V0 on request)

Luran 378P, (SAN) grey

ABS

PP talcum

ABS, UL 94-V0

PP talcum

PP translucent, PP-VO, Grilon, Steel

Grid alloy
Positive
Negative

Pb + <1% Ca
Pb + <1% Ca

Pb + <1% Ca
Pb + <1% Ca

Pb + <1% Ca
Pb + <1% Ca

Pb + <1% Ca
Pb + <1% Ca

Pb + <2% Sb
Pb + <2% Sb

Positive plate
Negative plate

Tubular
Grid

Grid
Grid

Grid
Grid

Grid
Grid

Tubular
Grid

metallized fibre electrode (Ni)


metallized fibre electrode (Ni)

Electrolyte

Fixed in Gel

Fixed in AGM

Fixed in AGM

Fixed in AGM

Sulphuric acid

KOH solution

Internal resistance

Good

Very low

Low

Low

Medium

Best (X/H/M/L performance type)

Current behaviour

Good

Very good

Good

Good

Good

Best (X/H/M/L type)

Expected service life up to (in years)

20

10 - 12

10 - 12

10 - 12

20

25

Cycles acc. to DIN DOD 80% up to

1000

500

800

500

1200

2500

Special charging technique

No

No

No

No

No

No / depending on application

Charging voltage in V/cell


Float charge
Boost charge

2.25
2.35

2.25
2.35

2.25
2.35

2.25
2.35

2.23
2.40

1.40 - 1.50 (type depending)


1.55 - 1.60 (type depending)

Float charging current / 100 Ah nominal capacity at 20C


Ufloat =2.23 - 2.25 V/cell

30 - 120 mA

30 - 120 mA

30 - 120 mA

30 - 120 mA

20 - 50 mA

30 - 200 mA (Type depending)


at 1.45 V/C, 20C

Position independent operation possible

Yes,  1500 Ah

Yes

Yes

Yes

No

No

Water-refilling intervals in years at permanent


float-charging/with AquaGen

No refilling for whole life time

No refilling for whole life time

No refilling for whole life time

No refilling for whole life time

No refilling for whole life time

>3 (type depending),


>10 with AquaGen

Self discharge of nominal capacity at 20C


ambient temperature/per month

2 - 3%

2 - 3%

2 - 3%

2 - 3%

3%

7%

Operating temperature range in C

-20 - +40

-20 - +40

-20 - +40

-20 - +40

-20 - +40

-40 - +50

Ventilation requirement

VRLA regulation; EN 50272-2

VRLA regulation; EN 50272-2

VRLA regulation; EN 50272-2

VRLA regulation; EN 50272-2

VRLA regulation; EN 50272-2

with AquaGen similar to VRLA

Storage time at 20C before refreshing charge

3 months

3 months

3 months

3 months

3 months

see operating instructions

Standby Batteries
product overview

Railway Battery Systems


Power Supply
Standby

Our products are subject to constant development. We therefore reserve the right to make changes.
Terminals: M8 (HOPzS M10), screwed with brass inserts.
Key: Emergency Power

Engine Start

Power Plant

Power Supply

Rail

f o r m o r e i n f o r m a t i o n : w w w. H O P P E C K E . c o m

Signal Tower

Solar

Switch Gear

Telecom

Transformer Station

UPS

HOPPECKE Batterien GmbH & Co. KG Bontkirchener Str. 1, 59929 Brilon, Germany

Standby Batteries product overview EN/04.2002/3 H Printed in Germany