G6C

PCB Power Relay

Miniature High Capacity Relays


with SPST-NO 10A and SPST-NO +
SPST-NC 8A
SPST-NO 10A and SPST-NO + SPST-NC 8A for power switching and
output that satisfy the needs for space-saving.
Small High-capacity Relays Compact: 20 15 10 mm (L W H).
Low power consumption: 200 mW.
Ultrasonically cleanable models is available.
Exclusive P6C model for sockets is now available.
RoHS Compliant

Model Number Legend

Application Examples

G6C- @ - @@ @ @ @ -@ -@ -@ -@

Ideal for output applications of control equipments

2 3 4 5 6

1. Relay Function
None: Single-side stable
U : Single-winding latching
K : Double-winding
latching
2. Number of poles
1: 1-pole/SPST-NO (1a)
2: 2-pole/SPST-NO (1a) +
SPST-NC (1b)
3. Contact Form
1: SPST-NO (1a)
4. Contact Type
1: Single
5. Enclosure rating
4: Fully sealed
7: Flux protection
6. Terminal Shape
P: PCB terminals
Socket mounting Terminals

9 10

G
6
C

7. Contact Material
None: Standard (Ag-alloy
(Cd free))
FD : AgSnIn Contacts
(Suitable for DC
inductive load with high
inrush current)
8. Approved Standards
US: UL/CSA
9. Washability
None: Standard model
(not compatible with
ultrasonically cleanable
models)
U : For ultrasonically
cleanable
10. Mounting
None: Mounted directly to
PCB
P6C : Mounted to Socket

G6C

PCB Power Relay

Ordering Information
Standard Models (UL, CSA certified)
Relay
Function
Enclosure
rating

Single-side stable

Contact
form

SPST-NO
(1a)

Model

Rated coil
voltage

G6C-1117P-US

SPST-NO
(1a)

G
6
C

Model

3 VDC

5 VDC

5 VDC

G6CU-1117P-US

G6C-1114P-US

5 VDC
G6CK-1117P-US

6 VDC

12 VDC

12 VDC

24 VDC

24 VDC

3 VDC

3 VDC

3 VDC

5 VDC
G6CU-2117P-US

6 VDC

6 VDC

12 VDC

12 VDC

24 VDC

24 VDC

24 VDC

3 VDC

3 VDC

3 VDC

5 VDC

5 VDC
G6CU-1114P-US

6 VDC

5 VDC
G6CK-1114P-US

6 VDC

12 VDC

12 VDC

12 VDC

24 VDC

24 VDC

24 VDC

3 VDC

3 VDC

3 VDC

6 VDC

5 VDC
G6CU-2114P-US

6 VDC

100 pcs/
tray

5 VDC
G6CK-2114P-US

6 VDC

12 VDC

12 VDC

12 VDC

24 VDC

24 VDC

24 VDC

G6C-1117P
-US
CONTACT:
TV-5
10A 250VAC
24VDC
MADE IN 10A 30VDC
COIL:24VDC
JAPAN

100 pcs/
tray

5 VDC
G6CK-2117P-US

12 VDC

5 VDC

Note. Products with UL/CSA certification marks will be


supplied for orders of standard models (-US
models).

3 VDC

24 VDC

6 VDC

G6C-2114P-US

Model

Minimun
Rated coil packing unit
voltage

12 VDC

6 VDC

Fully sealed
SPST-NO
(1a) +
SPST-NC
(1b)

Rated coil
voltage

5 VDC
G6C-2117P-US

Double-winding latching

3 VDC
6 VDC

Flux protection
SPST-NO
(1a) +
SPST-NC
(1b)

Single-winding latching

G6C-2114P
-US
CONTACT:
TV-5
8A 250VAC
24VDC
MADE IN 8A 30VDC
COIL:24VDC
JAPAN

Ultrasonically Cleanable Models (UL, CSA certified)


Relay
Function
Enclosure
rating

Single-side stable

Contact
form

SPST-NO
(1a)

Model

G6C-1114P-US-U

Rated coil
voltage

Double-winding latching

Rated coil
voltage

Model

5 VDC

5 VDC

5 VDC

6 VDC

G6CU-1114P-US

Note. Products with UL/CSA certification marks will be


supplied for orders of standard models (-US
models).

12 VDC

24 VDC

24 VDC

G6CU-2114P-US

5 VDC
G6CK-2114P-US

12 VDC

12 VDC

24 VDC

G6C-1117P
-US
CONTACT:
TV-5
10A 250VAC
24VDC
MADE IN 10A 30VDC
COIL:24VDC
JAPAN

G6C-2114P
-US
CONTACT:
TV-5
8A 250VAC
24VDC
MADE IN 8A 30VDC
COIL:24VDC
JAPAN

Connecting Sockets (Sold Separately)


Applicable relays

Model

G6C-2114P-US-P6C
G6C-2117P-US-P6C
G6C-1114P-US-P6C
G6C-1117P-US-P6C
G6CU-2114P-US-P6C
G6CU-2117P-US-P6C
G6CU-1114P-US-P6C
G6CU-1117P-US-P6C

P6C-06P

G6CK-2114P-US-P6C
G6CK-2117P-US-P6C
G6CK-1114P-US-P6C
G6CK-1117P-US-P6C

P6C-08P

Removal Tool

P6B-Y1

Hold-down Clips

P6B-C2

Minimun packing unit

20 pcs/tube

Note 1. Use the G6C-@@@@P-US-P6C to mount to a P6C Socket.


2. When using by combining sockets, the rated current will be 5A due to its rated switching current.

G6CK-1114P-US

12 VDC

5 VDC
G6C-2114P-US-U

Model

Minimun
Rated coil packing unit
voltage

3 VDC

12 VDC

Fully sealed
SPST-NO
(1a) +
SPST-NC
(1b)

Single-winding latching

100 pcs/
tray

G6C

PCB Power Relay

Ratings
Coil: 1-Pole, Single-side Stable Type (Including models for ultrasonically cleanable)
Item

Rated
current
(mA)

Rated voltage
3 VDC

Must operate Must release


voltage
voltage
(V)
(V)

Coil
resistance
()

67

Max.
voltage
(V)

Power
consumption
(mW)

% of rated voltage

45

5 VDC

40

125

6 VDC

33.3

180

12 VDC

16.7

720

24 VDC

8.3

2,880

70% max.

10% min.

160%
(at 23C)

Approx. 200

Coil: Single-winding Latching Type (Including models for ultrasonically cleanable)


Item

Rated
current
(mA)

Rated voltage

Coil
resistance
()

3 VDC

67

45

5 VDC

40

125

6 VDC

33.3

180

12 VDC

16.7

720

24 VDC

8.3

2,880

Must set
voltage
(V)

Must reset
voltage
(V)

Max.
voltage
(V)

% of rated voltage

70% max.

70% max.

160%
(at 23C)

Power consumption
Set coil
(mW)

Reset coil
(mW)

200

200

Coil: Double-winding Latching Type (Including models for ultrasonically cleanable)


Item

Rated current (mA)

Coil resistance ()

Set coil

Reset coil

Set coil

Reset coil

3 VDC

93.5

93.5

5 VDC

56.0

56.0

6 VDC

46.7

46.7

129

129

12 VDC

23.3

23.3

514

514

24 VDC

11.7

11.7

2,056

2,056

Must set
voltage
(V)

Rated voltage

Must reset
voltage
(V)

Max.
voltage
(V)

Power consumption

% of rated voltage
32.1

Set coil
(mW)

Reset coil
(mW)

280

280

G
6
C

32.1

89.3

89.3
70% max.

70% max.

130%
(at 23C)

Note 1. The rated current and coil resistance are measured at a coil temperature of 23C with a tolerance of 10%.
2. The operating characteristics are measured at a coil temperature of 23C.
3. The Max. voltage is the maximum voltage that can be applied to the relay coil.

Contact
Contact Form

Rated load
Item

SPST-NO (1a)
Inductive load
(cos = 0.4; L/R = 7 ms)

Resistive load

Inductive load
(cos = 0.4; L/R = 7 ms)

10 A (8 A) at 250 VAC
10 A (10 A) at 30 VDC

5 A (5 A) at 250 VAC
5 A (5 A) at 30 VDC

8 A (8 A) at 250 VAC
8 A (8 A) at 30 VDC

3.5 A (3.5 A) at 250 VAC


3.5 A (3.5 A) at 30 VDC

Contact type

Single

Contact material
Rated carry current

Ag-Alloy (Cd free)


10 A (10 A)

Max. switching voltage


Max. switching current

SPST-NO (1a) + SPST-NC (1b)

Resistive load

8 A (8 A)
380 VAC, 125 VDC

10 A (10 A)

8 A (8 A)

Note. The values shown in parentheses ( ) are for -FD models only.

G6C

PCB Power Relay

Characteristics (Including models for ultrasonically cleanable)


Single-side Stable

Single-winding Latching Double-winding Latching


30 m max.
10 ms max.
10 ms max.
20 ms (at 23C)
20 ms (at 23C)

1,000 m min.
1,000 m min.
1,000 m min. (SPST-NO, SPST-NC)

1,000 m min.

2,000 VAC 50/60Hz for 1min


1,000 VAC 50/60Hz for 1min
2,000 VAC 50/60Hz for 1min (SPST-NO, SPST-NC)
250 VAC 50/60Hz for
1min
10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
1,000 m/s2
100 m/s2
50,000,000 operations min. (at 18,000 operations/hr)
100,000 operation min. (at 1,800 operations/hr under rated load)
10 mA at 5 VDC
-25C to 70C (with no icing or condensation)
5% to 85%
Approx. 5.6 g

Note. The given values are initial values.


*1. Measurement conditions: 5 VDC, 1 A, voltage
drop method.
*2. Testing conditions: measured with a 500 VDC
megohmmeter (at 250 VDC between set/reset
coil).
*3. This value was measured at a switching
frequency of 120 operations/min.

G6C-1114P-FD-US
G6C-1117P-FD-US
Switching current (A)

50
30
AC resistive load
10
7
5
3

DC resistive load
DC inductive load
(L/R = 7 ms)

1
0.7
0.5

AC inductive
load
(cos = 0.4)

50
30
AC resistive load
10
8
5
3
2

DC resistive load

1
0.7
0.5

AC inductive
load
(cos = 0.4)

50
30
AC resistive load
10
8
5
3
2

0.3

0.3

0.2

0.2

0.2

0.1

0.1
3

5 7 10

30 50 100

250 380 1,000

Switching voltage (V)

G6C-2114P-FD-US
G6C-2117P-FD-US
50
30
AC resistive load
10
8
5
3
2

AC inductive
load
(cos = 0.4)

DC resistive load
1
0.7
0.5

DC inductive load
(L/R = 7 ms)

0.3
0.2
0.1
1

5 7 10

30 50 100

250 380 1,000

Switching voltage (V)

DC resistive load
DC inductive load
(L/R = 7 ms)

1
0.7
0.5

DC inductive load
(L/R = 7 ms)

0.3

G6C-2114P-US
G6C-2117P-US
Switching current (A)

Maximum Switching Capacity


G6C-1114P-US
G6C-1117P-US
Switching current (A)

Engineering Data

Switching current (A)

G
6
C

Item
Classification
Contact resistance *1
Operate (set) time
Release (reset) time
Min. set pulse width
Min. reset pulse width
Between coil and
contacts
Between contacts of the
same polarity
Insulation
resistance *2
Between contacts of
different polarity
Between set and reset
coils
Between coil and
contacts
Between contacts of the
same polarity
Dielectric
strength
Between contacts of
different polarity
Between set and reset
coils
Destruction
Vibration
resistance
Malfunction
Destruction
Shock
resistance
Malfunction
Mechanical
Durability
Electrical
Failure rate (P level) (reference value) *3
Ambient operating temperature
Ambient operating humidity
Weight

AC inductive
load
(cos = 0.4)

0.1
1

5 7 10

30 50 100

250 380 1,000

Switching voltage (V)

5 7 10

30 50 100

250 380 1,000

Switching voltage (V)

G6C
Durability
G6C-1114P-US, G6C-2114P-US
G6C-1117P-US, G6C-2117P-US

G6C-1114P-FD-US, G6C-2114P-FD-US
G6C-1117P-FD-US, G6C-2117P-FD-US

Durability ( 104 operations)

Durability (x 104 operations)

PCB Power Relay

500
300

G6C-2114P-US
G6C-2117P-US
250 VAC resistive
30 VDC resistive

100
50

G6C-1114P-US
G6C-1117P-US
250 VAC resistive
30 VDC resistive

30

300

100

G6C-2114P-FD-US
G6C-2117P-FD-US
250 VAC resistive
G6C-1114P-FD-US
30 VDC resistive
G6C-1117P-FD-US
250 VAC resistive
G6C-1114P
-FD-US
G6C-1117P
-FD-US
30 VDC resistive

50
30

10

10
G6C-2114P-US
5 G6C-2117P-US
250 VAC inductive
3 (cos = 0.4)
30 VDC inductive
(L/R = 7 ms)
1

500

G6C-1114P-US
G6C-1117P-US
250 VAC inductive
(cos = 0.4)
30 VDC inductive
(L/R = 7 ms)
5

5 G6C-2114P-FD-US
G6C-2117P-FD-US
3 250 VAC inductive
(cos = 0.4)
30 VDC inductive
(L/R = 7 ms)
1
0 1
2
3
4

10 11

G6C-1114P-FD-US
G6C-1117P-FD-US
250 VAC inductive
(cos = 0.4)
30 VDC inductive
(L/R = 7 ms)
5

Switching current (A)

10 11

Ambient Temperature vs Must


Operate and Must Release voltages
Must Operate and Must Release voltages (%)

Ambient Temperature vs.


Maximum Coil Voltage
Maximum coil voltage (%)

Switching current (A)

200
180

160

140
130
120

100

100

Must operate voltage


Must release voltage
max.
X

Sample:
G6C-114P-US
Number of Relays:
80 5 pcs

min.

G
6
C

60

40

max.
X
min.

20

80
60
10

20 23 30

40

50

60

70

80

0
-40

90

-20

20

Ambient temperature (C)

40

60

80

Ambient temperature (C)

Note. The maximum coil voltage refers to the


maximum value in a varying range of
operating power voltage, not a continuous
voltage.

Shock Malfunction
Y

Magnetic Interference (between Relays)


De-energized
(b contact)

600

600

400

400
X
600

Z
600
200

X
600

400

400

Z
600
200

400

200

200

200
Z'
600

200

400
200

200

200

400

Change rate on the basis of rated value (OV) (%)

Energized
(a contact)

200
500
600
X'

400

200
Z'
600

200

400
600
X'

400
400

Shock direction
600
Y'

Unit: m/s2

600
Y'

Unit: m/s2

X'
Z
Z'

Y'

max.
X
min.

0
l2

Sample

-1
l1

-2
(Mounting pitch)

-3
Initial

l1=2.54a
l2=5.08a

l1=5.08a
l2=7.62a

l1=7.62a
l2=10.16a

(coil)

Sample: G6C-2114P-US DC24V


Number of Relays: 6 pcs
Test conditions: Shock is applied in X, Y, and Z
directions three times each with without energizing the
Relays to check the number of malfunctions.
Requirement: 100 m/s2

G6C

PCB Power Relay

Dimensions
Flux Protection Model
G6C-@117P-US

Terminal
Arrangement/
Internal Connections
(Bottom View)

PCB Mounting Holes


(Bottom View)
Tolerance: 0.1
1-pole
2.54
Four, 1.1-dia. holes

1-pole

2.54

1
20 max.
(19.9)*

15 max.
(14.9)*
(2.4)
10 max.
0.3 (9.9)*
10.16

7.62
(1.1)

3.5

2-pole
0.65
10.16

0.9
7.62

0.9
1.11

0.5
10.16

2.54
Six, 1.1-dia. holes

2-pole

2.54

* Average value

(2.4)

10.16

7.62
(1.1)

Note: Check carefully the coil


polarity of the Relay.

Note: Orientation mark is indicated as follows:

G
6
C Fully Sealed Model
G6C-@114P-US

PCB Mounting Holes


1-pole (Bottom View)
Tolerance: 0.1
2.54

Terminal Arrangement/
Internal Connections
(Bottom View)

Four, 1.1-dia. holes

1-pole

2.54
1

20 max.
(19.9)*

15 max.
(14.9)*

(2.4)

10.16

10 max.
0.3 (9.9)*

7.62
(1.1)

2-pole
3.5
0.65
10.16

0.9
7.62

0.9
1.11

2.54
0.5
10.16

Six, 1.1-dia. holes

2-pole

2.54
1

* Average value

(2.4)

10.16

7.62
(1.1)

Note: Check carefully the coil


polarity of the Relay.

G6C

PCB Power Relay

Flux Protective
Single-winding Latching Model
G6CU-@117P-US

Terminal Arrangement/
Internal Connections
(Bottom View)

PCB Mounting Holes


(Bottom View)
1-pole Tolerance: 0.1
2.54

Four, 1.1-dia. holes

1-pole

2.54
1

SR
20 max.
(19.9)*

15 max.
(14.9)*

(2.4)
10 max.
0.3 (9.9)*

10.16

S: Set coil
R: Reset coil

7.62
(1.1)

3.5
0.65
10.16

0.9
7.62

0.9
1.11

2-pole

0.5
10.16

2.54
Six, 1.1-dia. holes

* Average value

2-pole

2.54
1

SR
(2.4)

10.16

7.62
(1.1)

Fully Sealed Model


Single Latching Models
G6CU-@114P-US

Note: Check carefully the coil


polarity of the Relay.
Terminal Arrangement/
Internal Connections
(Bottom View)

PCB Mounting Holes


(Bottom View)
1-pole Tolerance: 0.1
2.54
Four, 1.1-dia. holes

1-pole

2.54
1

SR
20 max.
(19.9)*

15 max.
(14.9)*

(2.4)
10 max.
0.3 (9.9)*

10.16

S: Set coil
R: Reset coil

7.62
(1.1)

3.5
0.65
10.16

0.9
7.62

* Average value

0.9
1.11

2-pole

0.5
10.16

2.54
Six, 1.1-dia. holes

2-pole

2.54
1

SR
(2.4)

10.16

7.62
(1.1)

Note: Check carefully the coil


polarity of the Relay.

Note: Orientation marks are indicated as follows:

G
6
C

G6C

PCB Power Relay

Flux Protective
Double-winding Latching Model
G6CK-@117P-US

PCB Mounting Holes


(Bottom View)
1-pole Tolerance: 0.1

Terminal Arrangement/
Internal Connections
(Bottom View)

2.54
Six, 1.1-dia. holes

1-pole

2.54
1

S
20 max.
(19.9)*

15 max.
(14.9)*

(2.4)

2.54

10 max.
0.3 (9.9)*

10.16

0.9
7.62

0.9
1.11

R
7

S: Set coil
R: Reset coil

7.62
(1.1)

2-pole

3.5
0.9

0.65

7.62

2.54

0.5
10.16

Eight, 1.1-dia. holes

2-pole

2.54
* Average value

S
(2.4)

7.62

7.62

2.54

Fully Sealed
G Double-winding Latching Model
6 G6CK-@114P-US
C

1-pole
2.54

(1.1)

Note: Check carefully the coil


polarity of the Relay.
Terminal Arrangement/
Internal Connections
(Bottom View)

PCB Mounting Holes


(Bottom View)
Tolerance: 0.1
Six, 1.1-dia. holes

1-pole

2.54
1

S
20 max.
(19.9)*

15 max.
(14.9)*

(2.4)
10 max.
0.3 (9.9)*

7.62

3.5
0.65

0.9
10.16

0.9
7.62

* Average value

0.9
1.11

R
7

(1.1)

2-pole
0.5
10.16

2.54
Eight, 1.1-dia. holes

2-pole

2.54
1

S
(2.4)

7.62
2.54

S: Set coil
R: Reset coil

7.62

2.54

7.62
(1.1)

Note: Check carefully the coil


polarity of the Relay.

G6C

PCB Power Relay

Connecting Sockets Dimensions


Socket for single-winding latching/single-side a table Models
P6C-06P

* Average value

Socket for double-winding latching Models


P6C-08P

G
6
C

* Average value

Note: Orientation marks are indicated as follows:

G6C

PCB Power Relay

Removal Tool

Hold-down Clips

P6B-Y1

P6B-C2

Approved Standards
The rated values approved by each of the safety standards may be different from the performance characteristics individually defined in
this catalog.

UL Recognized
Model

Number of
poles

G
6
C

G6C ( )

CSA Certified
Model

Number of
poles

G6C ( )

(File No. E41643)


Coil ratings

10 A, 250 VAC 80C


10 A, 30 VDC 80C
1/6 HP 250 VAC, 1/4 HP, 125 VAC 80C
1/3 HP 250 VAC, 1/4 HP, 250 VAC 80C
600 W, 120 VAC, (Tungsten) 80C
530 VA, 20~265 VAC Max 2A (Pilot Duty) 80C
43.2 VA, 30 VDC (Pilot Duty) 80C
12 LRA, 2.2 FLA 30 VDC 80C
3 to 60 VDC
8 A, 250 VAC 80C
8 A, 30 VDC 80C
1/6 HP, 125 VAC, 1/4 HP, 125 VAC 80C
1/4 HP, 250 VAC 80C
600 W, 120 VAC (Tungsten) 80C
530 VA, 20~265 VAC Max 2A (Pilot Duty) 80C
43.2 VA, 30 VDC (Pilot Duty) 80C
12 LRA, 2.2 FLA, 30 VDC 80C

Coil ratings

Contact ratings

10 A, 250 VAC 80C


10 A, 30 VDC 80C
1/6 HP 125 VAC, 1/4 HP, 125 VAC 80C
1/3 HP 250 VAC, 1/4 HP, 250 VAC 80C
600 W, 120 VAC, (Tungsten) 80C
530 VA, 20~265 VAC Max 2A (Pilot Duty) 80C
43.2 VA, 30 VDC (Pilot Duty) 80C
3 to 60 VDC
8 A, 250 VAC 80C
8 A, 30 VDC 80C
1/6 HP, 125 VAC, 1/4 HP, 125 VAC 80C
1/4 HP, 250 VAC 80C
600 W, 120 VAC (Tungsten) 80C
530 VA, 20~265 VAC Max 2A (Pilot Duty) 80C
43.2 VA, 30 VDC (Pilot Duty) 80C

6,000

30,000

6,000

30,000

Number of test
operations

6,000

(Certificate No. 40014439)

Number of
poles

Coil ratings

3, 5, 6, 12, 24 VDC

Single-stable:
3, 5, 6, 12, 24 VDC

G6C ( )

Number of test
operations

(File No. LR31928)

EN/IEC, VDE Certified


Model

Contact ratings

Contact ratings
10 A, 250 VAC (cos = 1) 40C
5 A, 250 VAC (cos = 0.4) 40C
7 A, 250 VAC (cos = 1) 40C
3.5 A, 250 VAC (cos = 0.4) 40C

Approved
switching
operations
20,000

EN/IEC, TV Certified (Registration No. R50158249)


Model

Number of
poles
1

G6C ( )
2

10

Coil ratings

Single-stable:
3 to 48 VDC
Latching:
3 to 24 VDC

Contact ratings
10 A, 250 VAC (cos = 1) 40C
5 A, 250 VAC (cos = 0.4) 40C
10 A, 30 VDC (L/R = 0 ms) 40C
8 A, 250 VAC (cos = 1) 40C
3.5 A, 250 VAC (cos = 0.4) 40C
8 A, 30 VDC (L/R = 0 ms) 40C

Approved
switching
operations

20,000

G6C

PCB Power Relay

Precautions
Please refer to PCB Relays Common Precautions for correct use.

Correct Use
Mounting
Do not reverse the polarity of the coil
(+, ).
When mounting more than two relays
side by side, keep the gap between
Relays as shown below to ensure a
good heat dissipation. It may result in
malfunction if heat is not dissipated
smoothly from the Relay.
2.54 mm
3 pitch min.
between
terminals

2.54 mm 2 pitch min. between terminals

Sockets
17 mm max. for sockets
7.5 mm

When mounting the Relay, make sure


to insert the Relay terminals
perpendicularly and correctly into the
socket contact pin.
Hold-down clips (for mounting and
removal) are also available.
The P6C model has a flux-resistant
construction. Do not wash it down with
water.
The max. carry current of sockets is 5A.
Double-winding Latching Circuit
It is recommended to perform wiring of
No.1 and No.2 of the negative (-)
terminal as COM wiring, in order to
improve the operation stability for
Double-winding Latching.

Using SPDT contact of the


SPST-NO+SPST-NC Relay
Do not construct a circuit so that
overcurrent and burning occur if the
NO, NC and SPDT contacts are shortcircuited with the SPST-NO+SPST-NC
Relay. Arcing may generate shortcircuiting between contacts if there is
short-circuiting because of conversion
to the MBB contact caused by
asynchronous operation of the NO and
NC contacts, the interval between the
NO and NC contacts is small, or a
large current is left open.
Other precautions
This Relay is a Power Relay which is
suitable for power load switching. Do
not use the G6C for signal purposes
such as micro load switching under
10 mA.

(+)

COM

Application examples provided in this document are for reference only. In actual applications, confirm equipment functions and safety before using the product.
Consult your OMRON representative before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad
systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems or equipment that may have a serious
influence on lives and property if used improperly. Make sure that the ratings and performance characteristics of the product provide a margin of safety for the system or
equipment, and be sure to provide the system or equipment with double safety mechanisms.

Note: Do not use this document to operate the Unit.

OMRON Corporation
Electronic and Mechanical Components Company

Contact: www.omron.com/ecb

Cat. No. K018-E1-07


0812(0207)(O)

11